This document is a detailed electrical one-line diagram for Building 100 at the VA Portland Health Care System, part of a comprehensive electrical infrastructure correction project. The diagram, specifically sheet 7 of 21, provides a technical schematic of the electrical distribution system, focusing on busduct risers and electrical panel configurations. It includes multiple electrical components such as transformers, circuit breakers, panelboards, motor control centers, and various electrical feeds, with specific details like voltage ratings (480V, 208V), amperage, and circuit breaker settings. The diagram shows complex interconnections between different electrical systems, including normal and emergency power distribution, with notations for existing overcurrent protective device settings and requirements for replacement and modification of electrical equipment.
The document includes general notes and key notes that provide critical instructions for the contractor, including requirements to field verify existing conditions, provide shutdown and phasing plans, replace overcurrent protective devices, and update circuit panel directories. The project is part of a larger electrical deficiency correction effort for the VA Portland Health Care System, with a project number of 648-20-119 and an issue date of 01/31/2025. The drawing is prepared by Spees Design Build from Kent, Washington, and is marked as a construction document for a fully sprinklered facility, indicating a comprehensive electrical system upgrade and safety improvement project.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UTIL: USS2
Isc 3P 4437 Amps Isc SLG 3241 Amps
UTIL: USS2 (equip eval) Isc 3P 10553 Amps Isc SLG 8272 Amps
SW: USS2 (3)
SQUARE D (600A)
FU: USS2
GE (EJO-1, 150E)
150A
XF: USS2
2500kVA; 6.09%Z Pri: 12470V Sec: 480V
F: 100_SWBD USS2
(1) #4000 Class B; 1 ft
CB: 100_USS2 Main W/G
SE MASTERPACT MTZ
4000 A
LONG DELAY PICKUP = 0.8X (3200A)
LONG DELAY = 12 SEC
SHORT DELAY PICKUP = 4X (16,000A)
SHORT DELAY = 0.50 SEC
INSTANTANEOUS = 12X (48,000A)
GROUND PICKUP = A (800A)
GROUND DELAY = 0.50 SEC
F: 100_B1-SDN-E-17
(4) #750 THWN; 60 ft
SWBD: 100_B1SDN-E-17
480V, 2000A
36.7K SCA
50K SCAR
CB: 100_MCC-N-B1-D-18
SQUARE D (LH)
400 A
F: 100_MCC-N-B1-D-18
(1) #500 THWN; 170 ft
CB: 100_ATS-LSS2-2 W/G
SE MASTERPACT MTZ
200 A
F: 100_ATS-LS-S2-2 (N)
(1) #3/0 THWN; 80 ft
CB: 100_ATS-CES2-1 W/G
SE MASTERPACT MTZ
800 A
F: 100_ATS-CE-S2-1(N)
(3) #350 THWN; 240 ft
CB: 100_ATS-DES2-3 W/G
SE MASTERPACT MTZ
800 A
F: 100_ATS-DE-S2-3(N)
(3) #350 THWN; 160 ft
SWBD: 100_USS2
480V, 4000A 40.6k SCA 50k SCAR
CB: 100_BAY 2 Normal Riser W/G
SE MASTERPACT MTZ
1200 A
F: 100_BAY 2 Normal G: Riser
(1) #1000 CLASS B; 80 ft
CB: 100_B1H1-F-14
SQUARE D (IK)
200 A
F: 100_B1H1-F-14
(1) #3/0 THWN; 60 ft
CB: 100_104-L1 BLD 107
SQUARE D (FI)
20 A
F: 100_104-L1 BLD 107
(1) #8 THWN; 220 ft
DISC: 107_T-116 PRIM
480V, 1.5K SCA
CB: 107_T-116 PRIM
SQUARE D (FA)
90 A
XF: 107_T-116
30KVA; 2.10%Z
PRI: 480V
SEC: 208V
DISC: 107_T-116 SEC
208V, 2.2K SCA
CB: 107 _T-116 SEC
SQUARE D (FA)
100 A
F: 107_Pnl L1
(1) #1/0 THWN; 10 ft
PNL: 107_L1
208V, 100A
2.1K SCA
10K SCAR
CB: 100_B1L1-E-17
SQUARE D (FI)
50 A
F: 100_B1L1-E-17
(1) #6 THWN; 50 ft
CB: 100_Normal Riser Bay 3
SQUARE D (MH)
800 A
F: 100_Normal Riser Bay 3
(3) #300 THWN; 150 ft
CONTINUE TO BD:
100_S2 N1 B3
(SEE SHEET 100EP607)
CB: 100_1SDN-M-17
SQUARE D (LH)
400 A
F: 100_1SDN-M-17
(2) #4/0 THWN; 180 ft
CB: 100_B1H1-B-13
SQUARE D (KH)
150 A
F: 100_B1H1-B-13
(1) #1/0 THWN; 120 ft
PNL: 100_B1H1-B-13
480V, 225A
12.6K SCA
14K SCAR
CB: 100_STERIS
SQUARE D (EH)
30 A
F: 100_STERIS
(1) #10 THWN; 260 ft
DISC: 100_STERIS
480V, 0.9K SCA
FU: 100_STERIS
BUSSMANN (FRS-R)
30 A
CB: 100_XFMR T-40
SQUARE D (EH)
70 A
F: 100_XFMR T-40
(1) #4 THWN; 25 ft
XF: 100_T-40
45KVA; 6.10%Z
PRI: 480V
SEC: 208V
TAP: 100_XF T-40 SEC
208V, 1.9K SCA
F: 100_PNL B1L1-B-13 SEC 1
(1) #1/0 THWN; 20 ft
CB: 100_B1L1-B-13 SEC 1 Main
SQUARE D (KA)
150 A
PNL: 100_B1L1-B-13 SEC 1
208V, 150A
1.8K SCA
65K SCAR
CB: 100_VS 329
SQUARE D (EH)
20 A
F: 100_PNL B1L1-B-13 SEC 2
(1) #2 THWN; 20 ft
CB: 100_B1L1-B-13 SEC 2 Main SQUARE D (Q1(B)-VH (Obs.)) 100 A
PNL: 100_B1L1-B-13 SEC 2
208V, 100A
1.8K SCA
65K SCAR
XF: 100_T-12
30KVA; 5.60%Z
PRI: 480V
SEC: 208V
TAP: 100_XF T-12 SEC
208V, 1.4K SCA
F: 100_Pnl B1L1-E-17
(1) #2 THWN; 25 ft
CB: 100_B1L1-E-17 Main
SQUARE D (QO)
100 A
PNL: 100_B1L1-E-17
208V, 100A
1.4K SCA
22K SCAR
F: 100_Pnl B1L1-E.1-17
(1) #2 THWN; 10 ft
PNL: 100_B1H1-F-14
480V, 225A
22.4K SCA
200K SCAR
CB: 100_HORI Milling Mach
SQUARE D (FA)
20 A
F: 100_HORI Milling Mach
(1) #12 THWN; 60 ft
DISC: 100_HORI Milling Mach
480V, 2.3K SCA
FU: 100_HORI Milling Mach
BUSSMANN (FRS-R)
20 A
CB: 100_XFMR T-13
SQUARE D (KA)
125 A
F: 100_XFMR T-13
(1) #1 THWN; 25 ft
PANELBOARD
"B1LD1-F-14"
208V, 250A, 3PH, 4W
CB: 100_B1L1-F-14 SEC 1 Main SQUARE D (Q1(B)-VH (Obs.)) 100 A
PNL: 100_B1L1-F-14 SEC 1
208V, 100A
3.7K SCA
22K SCAR
PNL: 100_B1L1-E.1-17
208V, 100A
1.4K SCA
65K SCAR
CB: 100_LATHE B1C-118
SQUARE D (QO)
30 A
F: 100_LATHE B1C-118
(1) #10 THWN; 30 ft
DISC: 100_LATHE B1C-118
208V, 1.1K SCA
FU: 100_LATHE B1C-118
BUSSMANN (FRS-R)
20 A
CB: 100_DISC Work Bench
SQUARE D (QO)
30 A
F: 100_DISC Work Bench
(1) #10 THWN; 10 ft
DISC: 100_Work Bench
208V, 1.3K SCA
FU: 100_Work Bench
BUSSMANN (FRS-R)
30 A
SWBD: 100_1SDN-M-17
480V, 400A
19.8K SCA
50K SCAR
CB: 100_3H1-M-17
SQUARE D (FA)
70 A
THERMAL CURVE = 70A
INSTANTANEOUS = FIXED
F: 100_3H1-M-17
(1) #4 THWN; 180 ft
PANELBOARD "PNL: 100_3H1-M-17"
480V, 100A, 4.0K SCA, 14K SCAR
CB: 100_XFMR T-7
SQUARE D (EH)
50 A
THERMAL; CURVE = 50A
INSTANTANEOUS = FIXED
F: 100_XFMR T-7
(1) #6 THWN; 5 ft
XF: 100_T-7
30kVA; 5.60%Z
PRI: 480V
SEC: 208V
CB: 100_3L1-M-17 Main
SQUARE D (Q1(B)-VH (OBS.))
100 A
PNL: 100_3L1-M-17
208V, 100A
1.3K SCA
65K SCAR
CB: 100_B1L1-F-14 SEC 2 Main
SQUARE D (Q1(B)-VH (OBS.))
100 A
PNL: 100_B1L1-F-14 SEC 2
208V, 100A
3.6K SCA
22K SCAR
CB: 100_B1L1-F-14 SEC 3 Main SQUARE D (Q1 (Obs.)) 100 A
PNL: 100_B1L1-F-14 SEC 3
208V, 100A
3.6K SCA
10K SCAR
CB: 100_XFMR T-2a
SQUARE D (FA)
60 A
F: 100_XFMR T-2a
(1) #8 THWN; 10 ft
XF: 100_T-2a
30KVA; 5.20%Z
PRI: 480V
SEC: 208V
F: 100_Pnl NO NAME
(1) #1/0 THWN; 10 ft
CB: 100_No Name Main
SQUARE D (Q1(B)-VH (OBS.))
100 A
PNL: 100_3L2-M-17
208V, 100A
1.3K SCA
65K SCAR
CB: 100_MCC-N-1-L-17
SQUARE D (KA)
200A
INSTANTANEOUS = 6 OF 7 (1880A)
F: 100_MCC-N-1-L-17
(1) #3/0 THWN; 240 ft
CB: 100_MCC-N-2-L-17
SQUARE D (KA)
200 A
INSTANTANEOUS = 6 OF 7 (1880A)
F: 100_MCC-N-2-L-17
(1) #3/0 THWN; 260 ft
CB: 100_MCC-N-3-L-17
SQUARE D (KA)
200 A
INSTANTANEOUS = 6 OF 7 (1880A)
F: 100_MCC-N-3-L-17
(1) #3/0 THWN; 310 ft
CB: 100_2H1-M-17
SQUARE D (LA)
300 A
F: 100_2H1-M-17
(1) #350 THWN; 140 ft
PNL: 100_2H1-M-17
480V, 400A
12.2K SCA
50K SCAR
CB: 100_XFMR T-5
SQUARE D (KA)
175 A
INSTANTANEOUS = 3 OF 7 (1192A)
F: 100_XFMR T-5
(1) #2/0 THWN; 60 ft
CB: 100_1H1-M-17
SQUARE D (KA)
125 A
F: 100_1H1-M-17
(1) #1 THWN; 120 ft
CB: 100_XFMR T-3
SQUARE D (EH)
50 A
THERMAL; CURVE = 50A
INSTANTANEOUS = FIXED
F: 100_XFMR T-3
(1) #4 THWN; 15 ft
XF: 100_T-3
45KVA; 6.10%Z
PRI: 480V
SEC: 208V
TAP: 100_XF T-3 SEC
208V, 1.9K SCA
F: 100_PNL 1L1-M-17 SEC 1
(1) #1 THWN; 20
CB: 100_1L1-M-17 SEC 1 Main
SQUARE D (KA)
125 A
PNL: 100_1L1-M-17 SEC 1
208V, 125A
1.8K SCA
65K SCAR
CB: 100_1L1-M-17 SEC 2 Main
SQUARE D (Q1(B)-VH (OBS.))
60 A
PNL: 100_1L1-M-17 SEC 2
208V, 60A 1.8k SCA 65k SCAR
XF: 100_T-5
112.5 KVA; 6.20%Z
PRI: 480V
SEC: 208V
CB: 100_2L1-M-17 SEC 1 Main
SQUARE D (KA)
125 A
INSTANTANEOUS = 5 OF 7 (1090A)
PNL: 100_2L1-M-17
208V, 125A
3.4K SCA
22K SCAR
CB: 100_2L1-M-17 SEC 2 Main
SQUARE D (KA)
90 A
PNL: 100_2L1-M-17 SEC 2
208V, 90A
3.4K SCA
22K SCAR
CB: 100_2L2-M-17 SEC 1 Main
SQUARE D (KA)
125 A
INSTANTANEOUS = 5 OF 7 (1090A)
PNL: 100_2L2-M-17 SEC 1
208V, 125A
3.5K SCA
65K SCAR
CB: 100_2L2-M-17 SEC 2 Main
SQUARE D (KA)
100 A
PNL: 100_2L2-M-17 SEC 2
208V, 100A
4.0K SCA
22K SCAR
MCP: 100_EF-42
SQUARE D (FAL)
MCP: 100_RF-31
SQUARE D (FAL)
F: 100_100-RF-31
(1) #12 THWN; 60 ft
VFD: 100_RF-31
MTR: 100_RF-31
2 @ 2.0 HP
MCP: 100_SF-31
SQUARE D (FAL)
F: 100_100-SF-31
(1) #8 THWN; 60 ft
VFD: 100_SF-31
MTR: 100_SF-31
2 @ 2.0 HP
MCP: 100_EF-41
SQUARE D (FAL)
MCC: 100_MCC-N-3-L-17
480V, 600A
6.5K SCA
25K SCAR
MCP: 100_EF-43
SQUARE D (FAL)
MCP: 100_RF-11
SQUARE D (FAL)
F: 100_100-RF-11
(1) #12 THWN; 30 ft
VFD: 100_RF-11
MTR: 100_RF-11
2 @ 5.0 HP
MCP: 100_RF-21
SQUARE D (FAL)
F: 100_RF-21
(1) #10 THWN; 60 ft
VFD: 100_RF-21
MTR: 100_RF-21
2 @ 1.5 HP
MCP: 100_Pump PR-21
SQUARE D (FAL)
F: 100_Pump PR-21
(1) #12 THWN; 60 ft
MTR: 100_Pump PR-21
1 @ 0.5 HP
MCP: 100_SF-11
SQUARE D (FAL)
F: 100_100-SF-11
(1) #6 THWN; 30 ft
VFD: 100_SF-11
MTR: 100_SF-11
2 @ 10.0 HP
MCP: 100_SF-21
SQUARE D (FAL)
F: 100_SF-21
(1) #6 THWN; 60 ft
VFD: 100_SF-21
MTR: 100_SF-21
4 @ 7.5 HP
MCC: 100_MCC-N-2-L-17
480V, 600A
7.3K SCA
25K SCAR
MCP: 100_EF-11
SQUARE D (FAL)
F: 100_100-EF-11
(1) #12 THWN; 30 ft
MTR: 100_EF-11
1 @ 5.0 HP
MCC: 100_MCC-N-1-L-17
480V, 600A
7.7K SCA
25K SCAR
F: 100_Disc FU ERC-11
(1) #10 THWN; 15 ft
DISC: 100_FU ERC-11
480V, 5.4K SCA
FU: 100_ERC-11
BUSSMANN (FRS-R)
30 A
F: 100_Disc CB ERC-11
(1) #10 THWN; 50 ft
DISC: 100_CB ERC-11
480V, 2.6K SCA
CB: 100_ERC-11
SQUARE D (FA)
15 A
F: 100_VFD ERC-11
(1) #12 THWN; 5 ft
VFD: 100_ERC-11
F: 100_ERC-11
(1) #12 THWN; 35 ft
MTR: 100_ERC-11
1 @ 1.5 HP
MCP: 100_SF-B15
SQUARE D (FAL)
MCP: 100_RF-B11
SQUARE D (FAL)
F: 100_100-RF-B11
(1) #10 THWN; 50 ft
VFD: 100_RF-B11
MTR: 100_RF-B11
4 @ 2.0 HP
MCP: 100_SF-B11
SQUARE D (KAL)
F: 100_100-SF-B11
(1) #1/0 THWN; 50 ft
VFD: 100_SF-B11
MTR: 100_SF-B11
6 @ 10.0 HP
MCC: 100_MCC-N-B1-D-18
480V, 600A
16.6K SCA
25K SCAR
MCP: 100_PR-B11
SQUARE D (FAL)
CONTINUE TO ATS:
100_LS-S2-2
(SEE SHEET 100EP610)
CONTINUE TO ATS:
100_CE-S2-1
(SEE SHEET 100EP609)
CONTINUE TO ATS:
100_DE-S2-3
(SEE SHEET 100EP609)
CONTINUE TO BD:
100_S2 N1
(SEE SHEET 100EP605)
THERMAL CURVE = 250A (FIXED)
LONG TIME PICK UP = 0.6 (150A)
LONG TIME DELAY = 10 SEC
INSTANTANEOUS = 8.0(2000A)
INSTANTANEOUS = LO (1500A)
CB: 100_B1-SDN-E-17 W/G SQUARE D
SE MASTERPACT MTZ
1600 A
LONG DEL PICKUP = 1.0X (1600A)
LONG DELAY = 36 SEC
SHORT DELAY PICKUP = 7X (11,200A)
SHORT DELAY = 0.33 SEC
INSTANTANEOUS = 12X (48,000A)
GROUND PICKUP = A (330A)
GROUND DELAY = 0.35 SEC
CB: 100_3L2-M-17
SQUARE D TYPE QO
100 A
INSTANTANEOUS = FIXED
400A 3P
400A 3P
AHF AHF
SPACE SPACE SPACE SPACE
800A 3P
SE MASTERPACT MTZ
ACTIVE HARMONIC
FILTER ''AHF-USS2 1''
300A 480V
ACTIVE HARMONIC
FILTER ''AHF-USS2 2''
300A 480V
5000:5
CB: 100_XF T-1L1-M-17 SEC 2
50A/3P
XF: 100_1L1-M-17 SEC 2
30 KVA
480-208/120V
PANELBOARD "PNL: 100_1H1-M-17",
480V, 225A, 8.5K SCA, 14K SCAR
250AF/250AT
3P
LSIG
XF: 100_T-13
75KVA; 4.90%Z
PRI: 480V
SEC: 208V
CB: 100_XF T-3L2-M-17
50A/3P
THERMAL CURVE = 50A
INSTANTANEOUS = FIXED
XF: 100_3L2-M-17
30 KVA
480-208/120V
100 A/3P
225A/3P
100A 3P
100A 3P
100A 3P
PANELBOARD
"100_2L1-M-18"" 208V, 400A, 3PH, 4W
400AF/400AT
3P
LSIG
125A 3P
90A 3P
125A 3P
100A 3P
70A 3P
SPD
30A 3P
SPD
GENERAL NOTES
BUILDING 100 - ONE LINE DIAGRAM (SUB USS2)
EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS
TO BE REVISED AS SHOWN.
REPLACEMENT OVERCURRENT PROTECTIVE DEVICE.
EXTEND EXISTING CONDUIT AND WIRE TO ENCLOSED
CIRCUIT BREAKER, AS INDICATED.
PROVIDE TAP AS REQUIRED ON LOAD SIDE OR CIRCUIT
BREAKER TO FEED DOWNSTREAM PANELS AS INDICATED.
EXISTING CONDUIT AND WIRE SHALL BE EXTENDED AS
REQUIRED.
PROVIDE PANELBOARD AS SHOWN. EXISTING INCOMING
FEEDER AND BRANCH CIRCUITS SHALL BE EXTENDED AS
REQUIRED.
PROVIDE REPLACEMENT LOW-VOLTAGE SWITCHGEAR
CIRCUIT BREAKER WITH INTEGRAL COMMUNICATION AND
POWER METERING MODULES. REFERENCE
SPECIFICATION 26 23 00 FOR ADDITIONAL INFORMATION.
PROVIDE COMMUNICATIONS CABLE TO PME NETWORK
SWITCH AS INDICATED ON FLOOR PLANS. EQUIPMENT
SHALL BE INSTALLED WITH ALL REQUIRED WIRING,
TERMINATIONS, AND APPURTENANCES TO TRANSMIT
ACTIVE HARMONIC FILTER STATUS / DATA TO FACILITY'S
EXISTING PME NETWORK.
PROVIDE AND INSTALL AHF CTs AT SECONDARY OF UNIT SUBSTATION TRANSFORMER; SIZE CTs AS REQUIRED.
COORDINATE EXACT INSTALLATION LOCATION WITH
EXISTING EQUIPMENT.
221111
2 1
1 1
BLDG 100 - REVISED ONE-LINE
DIAGRAM (PART 6 OF 21)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR
COORDINATION OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVERCURRENT PROTECTIVE
DEVICE (OCPD) SETTING ADJUSTMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER
DISTRIBUTION EQUIPMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE EXISTING ONE-LINE DIAGRAM ON SHEET
100ED605 FOR ALL MODIFICATIONS.
5 5
100EP606
100-C-15
100-P-17 100-P-18
100-C-08
100-C-09
100-P-28
100-P-30100-P-29B
100-P-29A
100-P-27
100-P-26B
100-P-26A
SCALE : NTS
1 BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 6 OF 21)
6 6 6 6
100-P-56100-P-57100-P-58
100-P-61100-P-60100-P-62100-P-59
100ED606
CONTINUE TO SWBD:
100_B1SDN-E-17
(SEE SHEET 100EP606)
F: 100_NORMAL RISER BAY 3
(3) #300 THWN; 150 ft
BD: 100_S2 N1 B3
480V, 800A
26.1K SCA
85K SCAR
FU: 100_T-42
BUSSMANN (FRS-R)
200 A
F: 100_XFMR T-42
(1) #4/0 THWN; 25 ft
XF: 100_T-42
150KVA; 5.10%Z
PRI: 480V
SEC: 208V
F: 100_SWBD 1SDN-D-17
(2) #350 THWN; 10 ft
FU: 100_1H1-D-17
BUSSMANN (FRS-R)
200 A
F: 100_1H1-D-17
(1) #4/0 THWN; 55 ft
F: 100_BD S2 N2 B3
(1) #800 CLASS B; 25 ft
CB: 100_DUST COLLECTOR a
SQUARE D (EH)
20 A
CB: 100_OVEN
SQUARE D (EH)
20 A
CB: 100_DUST COLLECTOR
SQUARE D (EH)
20 A
CB: 100_AIR
COMPRESSOR
SQUARE D (EH)
30 A
PNL: 100_1H1-D-17
480V, 225A
18.9K SCA
14K SCAR
CB: 100_1L1-B-12
SQUARE D (FA)
100 A
F: 100_1L1-B-12
(1) #1 THWN; 100 ft
CB: 100_1L1-D-17 SEC 2
SQUARE D (FA)
100 A
F: 100_1L1-D-17 SEC 2
(1) #1 THWN; 50 ft
CB: 100_1L2-D-17 SEC 1
SQUARE D (Q2)
175 A
F: 100_1L2-D-17 SEC 1
(1) #2/0 THWN; 50 ft
CB: 100_1L2-D-17 SEC 2
SQUARE D (FA)
F: 100_1L2-D-17 SEC 2
(1) #6 THWN; 50 ft
Open CB: 100_1L3-D-17
SQUARE D (Q2)
225 A
F: 100_1L3-D-17
(1) #2/0 THWN; 50 ft
PNL: 100_1L3-D-17
208V, 225A
200K SCAR
CB: 100_1L1-D-17 SEC 1
SQUARE D (Q2)
175 A
F: 100_1L1-D-17 SEC 1
(1) #2/0 THWN; 50 ft
PNL: 100_1L1-D-17
SEC1
208V, 225A
5.5K SCA
65K SCAR
SWBD: 100_1SDN-D-17
208V, 600A
6.9K SCA
50K SCAR
FU: 100_T-43
BUSSMANN (FRS-R)
175 A
F: 100_XFMR T-43
(1) #2/0 THWN; 60 ft
P XF: 100_T-43
113KVA; 6.20%Z
PRI: 480V
SEC: 208V
F: 100_SWBD 2SDN-D-17
(1) #500 THWN; 20 ft
FU: 100_2H1-D-17
BUSSMANN (FRS-R)
200 A
F: 100_2H1-D-17
(1) #3/0 THWN; 60 ft
PNL: 100_2H1-D-17
480V, 225A
17.1K SCA
14K SCAR
CB: 100_XFMR T-137
SQUARE D (EH)
100 A
F: 100_XFMR T-137
(1) #2 THWN; 30 ft
XF: 100_T-137
75KVA; 5.80%Z
PRI: 480V
SEC: 208V
F: 100_PNL 2L3-D-17
(1) #4/0 THWN; 10 ft
PNL: 100_2L3-D-17
208V, 225A
3.2K SCA
200K SCAR
BD: 100_S2 N2 B3
480V, 800A
25.0K SCA
85K SCAR
F: 100_BD S2-N3-B3
(1) #800 CLASS B; 25 ft
FU: 100_3H1-D-17
BUSSMANN (FRS-R)
100 A
F: 100_3H1-D-17
(1) #2 THWN; 50 ft
PNL: 100_3HI-D-17
480V, 100A
13.8K SCA
14K SCAR
CB: 100_XFMR T-45
SQUARE D (EH)
30 A
F: 100_XFMR T-45
(1) #10 THWN; 20 ft
XF: 100_T-45
15KVA; 5.10%Z
PRI: 480V
SEC: 208V
F: 100_PNL 3L1-D-17
(1) #6 THWN; 30 ft
CB: 100_3L1-D-17 Main
SQUARE D (Q1(B)-VH (OBS.))
50 A
PNL: 100_3L1-D-17
208V, 50A
0.7K SCA
65K SCAR
BC: 100_S2-N3-B3
480V, 800A
24.1K SCA
85K SCAR
F: 100_BD S2-N4-B3
(1) #800 CLASS B; 25 ft
FU: 100_T-51
BUSSMANN (FRS-R)
125 A
F: 100_XFMR T-51
(1) #1 THWN; 50 ft
XF: 100_T-51
113KVA; 4.60%Z
PRI: 480V
SEC: 208V
F: 100_PNL 3L2-D-17
(1) #250 THWN; 30 ft
CB: 100_3L2-D-17 Main
SQUARE D (KA)
225 A
CB: 100_Laser Recp.Rm 3c 143
SQUARE D (Q1(B)-VH (OBS.))
50 A
CB: 100_Laser Recp.Rm 3c 134
SQUARE D (Q1(B)-VH (OBS.))
50 A
CB: 100_Laser Recp.Rm 3c 135
SQUARE D (QO)
50 A
PNL: 100_3L2-D-17
208V, 225A
5.3K SCA
65K SCAR
FU: 100_4H1-D-17
BUSSMANN (FRS-R)
70 A
F: 100_4H1-D-17
(1) #2 THWN; 60 ft
PNL: 100_4H1-D-17
480V, 100A
12.3K SCA
14K SCAR
CB: 100_XFMR T-47
SQUARE D (EH)
30 A
F: 100_XFMR T-47
(1) #12 THWN; 60 ft
XF: 100_T-47
15KVA; 5.10%Z
PRI: 480V
SEC: 208V
F: 100_Pnl 4L1-D-17
(1) #6 THWN; 60 ft
CB: 100_4L1-D-17 Main
SQUARE D (Q1(B)-VH (OBS.))
50 A
PNL: 100_4L1-D-17
208V, 50A
0.7K SCA
65K SCAR
FU: 100_T-49
BUSSMANN (FRS-R)
125 A
F: 100_XFMR T-49
(1) #1 THWN; 120 ft
XF: 100_T-49
75KVA; 4.90%Z
PRI: 480V
SEC: 208V
BD: 100_S2-N4-B3
480V, 800A
23.2K SCA
85K SCAR
PNL: 100_5L1-D-17
208V, 225A
3.5K SCA
65K SCAR
F: 100_PNL 5L1-D-17
(1) #250 THWN; 20 ft
CB: 100_5L1-D-17 Main
SQUARE D (KA)
225 A
TAP: 100_XF T-49 SEC
208V, 3.6K SCA
F: 100_PNL 5L2-D-17
(1) #2 THWN; 20 ft
CB: 100_5L2-D-17 Main
SQUARE D (Q2)
125 A
PNL: 100_5L2-D-17
208V, 225A
3.4K SCA
65K SCAR
SWBD: 100_2SDN-D-17
208V, 400A
4.3K SCA
50K SCAR
CB: 100_2L1-D-17 SEC 2
SQUARE D (FA)
100 A
F: 100_2L1-D-17 SEC 2
(1) #1 THWN; 60 ft
CB: 100_2L1-D-17 SEC 2 Main
SQUARE D (KA)
100 A
PNL: 100_2L1-D-17 SEC 2
208V, 100A
3.4K SCA
65K SCAR
CB: 100_2L1-D-17 SEC 1
SQUARE D (Q2)
150 A
F: 100_2L1-D-17 SEC 1
(1) #1/0 THWN; 60 ft
CB: 100_2L1-D-17 SEC 1 MAIN
SQUARE D (KA)
150 A
PNL: 100_2L1-D-17 SEC 1
208V, 150A
3.5K SCA
65K SCAR
CB: 100_2L2-D-17 SEC 2
SQUARE D (Q2)
150 A
F: 100_2L2-D-17 SEC 2
(1) #1/0 THWN; 60 ft
CB: 100_2L2-D-17 SEC 1
SQUARE D (FA)
100 A
F: 100_2L2-D-17 SEC 1
(1) #1 THWN; 60 ft
CB: 100_2L2-D-17 SEC 1 Main
SQUARE D (Q1(B)-VH (OBS.))
100 A
PNL: 100_2L2-D-17 SEC 1
208V, 100A
3.4K SCA
65K SCAR
PNL: 100_2L2-D-17 SEC 2
208V, 225A
3.5K SCA
65K SCAR
CB: 100_WASHER 2C-118b
SQUARE D (QO)
20 A
CB: 100_BANDSAW 2C-154
SQUARE D (QO)
40 A
CB: 100_ORTHO DRILL PRESS
SQUARE D (QO)
20 A
PNL: 100_1L2-D-17 SEC 2
208V, 225A
3.3K SCA
65K SCAR
CB: 100_NETMUX 2C-154
SQUARE D (QO)
20 A
CB: 100_SEWING MACH
SQUARE D (QO)
20 A
CB: 100_BUFFER
SQUARE D (QO)
20 A
PNL: 100_1L2-D-17 SEC 1
208V, 225A
5.5K SCA
65K SCAR
CB: 100_ORTHO SHOE FINISH
SQUARE D (QO)
20 A
PNL: 100_1L1-D-17 SEC 2
208V, 225A
5.1K SCA
65K SCAR
CB: 100_Drill Press_a
SQUARE D (QO-VH)
20 A
PNL: 100_1L1-B-12
208V, 100A
3.9K SCA
10K SCAR
CB: 100_DRILL PRESS
SQUARE D (QO)
20 A
CB: 100_ORTHO BAND SAW
SQUARE D (QO)
20 A
CB: 100_DRILL
SQUARE D (QO)
20 A
CB: 100_SHOE FINISHER
SQUARE D (QO)
20 A
CB: 100_SEWING MACH.
SQUARE D (QO)
20 A
CB: 100_ORTHO LAB GRINDER
SQUARE D (QO)
20 A
CB: 100_SEWING MACHINE
SQUARE D (QO)
20 A
CB: 100_SHOE STITCHER
SQUARE D (QO)
20 A
CB: 100_SPARE IN REHAB
SQUARE D (QO)
20 A
CB: 100_Sewing Machine_a
SQUARE D (QO-VH)
20 A
CB: 100_Shoe Sander
SQUARE D (QO-VH)
20 A
CB: 100_Disc Sander
SQUARE D (QO-VH)
20 A
CB: 100_Delta Grinder
SQUARE D (QO-VH)
20 A
CB: 100_Shoe Sander_a
SQUARE D (QO-VH)
20 A
400A /3P
CB: 100_SWBD 2SDN-D-17 MAIN
THERMAL CURVE = 400A (FIXED)
LONG TIME PICK UP = 1.0 (400A)
LONG TIME DELAY = 8 SEC
INSTANTANEOUS = 8.0 (3200A)
DPM
GENERAL NOTES
KEY NOTES
BUILDING 100 - ONE LINE DIAGRAM (BUSDUCT RISER N1 BAY3)
BLDG 100 - REVISED ONE-LINE
DIAGRAM (PART 7 OF 21)
PROVIDE FIELD MODIFICATIONS AS REQUIRED TO
REPLACE INCOMING LUGS AND ANALOG METERING WITH
MAIN CIRCUIT BREAKER AND INTEGRAL POWER METER
(SE 8244), RESPECTIVELY. MODIFIED EQUIPMENT SHALL
BE RE-CERTIFIED BY UL FIELD ENGINEERS AS REQUIRED.
COORDINATE SHUTDOWN AND RE-CERTIFICATION WITH
VA. EXTEND EXISTING FEEDER "F:100_SWBD 2SDN-D-17"
AS REQUIRED. REFERENCE DETAIL '5' ON SHEET E-502
FOR ADDITIONAL INFORMATION.
PROVIDE PANELBOARD AS SHOWN. EXISTING INCOMING
FEEDER AND BRACH CIRCUITS SHALL BE EXTENDED AS
REQUIRED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR
COORDINATION OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVERCURRENT PROTECTIVE
DEVICE (OCPD) SETTING ADJUSTMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER
DISTRIBUTION EQUIPMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE EXISTING ONE-LINE DIAGRAM ON SHEET
100ED606 FOR ALL MODIFICATIONS.
100EP607
SCALE : NTS
1 BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 7 OF 21)
100ED607
CONTINUE TO SWBD:
100_BISDEC-E-18
(SEE SHEET 100EP609)
F: 100_Critical Riser Bay 3
(1) #600 Class B; 50 ft BD: 100_S2-CE2-B3
480V, 600A 19.7k SCA 85k SCAR
F: 100_Pnl 2CL1-E-17 SEC2
(1) #1 THWN; 30 ft
CB: 100_2CL1-E-17 SEC2 Main
SQUARE D (KA)
125 A
PNL: 100_2CL1-E-17 SEC2
208V, 125A 3.4k SCA 65k SCAR
CB: 100_XFMR T-18
SQUARE D (KA)
125 A
F: 100_XFMR T-18
(1) #1 THWN; 30 ft
XF: 100_T-18
75kVA; 4.90%Z Pri: 480V Sec: 208
TAP: 100_XF T-18 Sec 208V, 3.7k SCA
F: 100_Pnl 2CL1-E-17 SEC 1
(1) #1/0 THWN; 50 ft
CB: 100_2CL1-E-17 SEC 1 Main
SQUARE D (KA)
150 A
PNL: 100_2CL1-E-17 SEC 1
208V, 150A 3.2k SCA 65k SCAR
FU:100_2CH1-E-17
BUSSMANN (FRS-R)
200 A
F: 100_2CH1-E-17
(1)#3/0 THWN; 45 ft
PNL: 100_2CH1-E-17
480V, 225A 15.5k SCA 200k SCAR
CB: 100_UPS 2C
SQUARE D (KA)
F: 100_UPS 2C
(1)#2/0 THWN; 30 ft
FU:100_2CH1-D-17
BUSSMANN (FRS-R)
F:100_2CH1-D-17
(1)#2 THWN; 45 FT
PNL: 100_2CH1-D-17
480V, 100A 12.8k SCA 14k SCAR
F:100_BD S2-CE3-B3
(1)#600 Class B; 25 ft
F: 100_Pnl 3CL2-E-17 (1)#2 THWN; 10 ft
CB: 100_3CL2-E-17 Main
SQUARE D (Q1 (OBS.))
100 A
PNL: 100_3CL2-E-17
208V, 100A 1.9k SCA 65k SCAR
CB: 100_3CL1-E-17
SQUARE D (FA)
70 A
F: 100_3CL1-E-17
(1)#1 THWN; 60 ft
XF: 100_T-20
45kVA; 6.10%Z Pri: 480V Sec: 208V
TAP: 100_XF T-20 Sec 208V, 1.9k SCA
F: 100_Pnl 3CL1-E-17 (1)#1/0 THWN; 60 ft
CB: 100_3CL1-E-17 Main
SQUARE D (KA)
PNL: 100_3CL1-E-17
208V, 125A 1.7k SCA 65k SCAR
FU: 100_3CH1-E-17
BUSSMANN (FRS-R)
200 A
F: 100_3CH1-E-17
(1)#3/0 THWN; 60 ft
PNL: 100_3CH1-E-17
480V, 225A 13.8k SCA 50k SCAR
CB: 100_UPS BYPASS
SQUARE D (FA)
20 A
F: 100_UPS BYPASS
(1)#10 THWN; 60 ft
FU: 100_3CH1-D-17
BUSSMANN (FRS-R)
200 A
F: 100_3CH1-D-17
(1) #3/0 THWN; 40 ft
PNL: 100_3CH1-D-17 SEC 1
480V, 225A 15.2k SCA 14k SCAR
F: 100_Pnl 3CH1-D-17 SEC 2 (1)#3/0 THWN; 5 ft
BD: 100_S2-CE3-B3
480V, 600A 18.7k SCA 85k SCAR
MTS: 100_Surg Lt UPS Bypass 0 A
F: 100_Pnl Surg Lts UPS
(1) #10 THWN; 20 ft
CB: 100_Surg Lts UPS Main
SQUARE D (ED)
25 A
PNL: 100_Surg Lts UPS 480V, 125A 0.3k SCA 100k SCAR
CB: 100_SURGERY
LIGHTING UPS
SQUARE D
30 A
F: 100_Surgery lighting UPS
(1) #10 THWN; 40 f
UPS: 100_Surgery Lighting
F: 100_XF Surg Lts UPS Bypass
(1) #6 THWN; 30 ft
XF: 100_Surg Lts UPS Bypass 15kVA; 5.00%Z Pri: 208V Sec: 480V
F: 100_Surg LT UPS Bypass
(1) #10 THWN; 20 ft
CB: 100_XFMR T-46
SQUARE D (EH)
70 A
F: 100_XFMR T-46
(1)#4 THWN; 20 ft
FU: 100_T-28
BUSSMANN (FRS-R)
125 A
F: 100_XFMR T-28
(1)#1 THWN; 120 ft
XF: 100_T-28
75kVA; 4.90%Z Pri: 480V Sec: 208V
F: 100_SWBD 5SDEC-E-17
(1)#500 THWN; 60 ft
FU: 100_4CH1-D-17
BUSSMANN (FRS-R)
200 A
F: 100_4CH1-D-17
(1) #250 THWN; 40 ft
PNL: 100_4CH1-D-17
480V, 225A 15.1k SCA 50k SCAR
CB: 100_XFMR-T-48
SQUARE D (KA)
175 A
XF:100_T-48
113kVA; 6.20%Z Pri: 480V Sec: 208V
PNL: 100_3CH1-D-17 SEC 2
480V, 225A 14.8k SCA 14k SCAR
F: 100_BD S2-CE4-B3
(1)#600 Class B; 25 ft
CONTINUE TO EP:
100_UPS 2C
(SEE SHEET 100EP610)
BD: 100_S2-CE4-B3
480V, 600A 17.8k SCA 85k SCAR
F: 100_T-50
BUSSMANN (FRS-R)
20 A
F: 100_XFMR T-50
(1)#10 THWN; 120 ft
XF: 100_T-50
9kVA; 4.40%Z Pri: 480V Sec: 208V
F: 100_5CL1-D-17
(1)#10 THHN; 30 ft
CB: 100_5CL1-D-17 MAIN
SQUARE D (QO)
30 A
PNL: 100_5CL1-D-17
208V, 30A 0.5k SCA 65k SCAR
XF: 100_T-46
45kVA; 6.10%Z Pri: 480V Sec: 208V
F: 100_Pnl 3CL1-D-17 SEC 2
(1) #1 THWN; 40 ft
CB: 100_3CL1-D-17 SEC 2 Main SQUARE D (Q1(B)-VH (Obs.)) 70 A
CB: 100_4CL1-D-17 SEC 2 Main
SQUARE D (KA)
150 A
PNL: 100_4CL1-D-17 SEC 2
208V, 150A 3.8k SCA 65k SCAR
CB: 100_4CL1-D-17 SEC 1 Main
SQUARE D (KA)
225 A
PNL: 100_4CL1-D-17 SEC 1
208V, 225A 3.8k SCA 65k SCAR
F: 100_Pnl 4CL1-D-17 SEC. 1A (1)#250 THWN; 30 ft
PNL: 100_4CL1-D-17 SEC. 1A
208V, 225A 3.5k SCA 65k SCAR
PNL: 100_3CL1-D-17 SEC 2
208V, 70A 1.8k SCA 65k SCAR
CB: 100_6CL2-E-17
SQUARE D (FA)
100 A
F: 100_6CL2-E-17
(1)#1 THWN; 80 ft
CB: 100_7CL1-E-17
SQUARE D (FA)
60 A
F: 100_7CL1-E-17
(1)#4 THWN; 100 ft
PNL: 100_6CL2-E-17
208V, 100A 2.5k SCA 65k SCAR
PNL: 100_7CL1-E-17
208V, 100A 1.9k SCA 65k SCAR
CB: 100_8CL1-E-17
SQUARE D (FA)
70 A
F: 100_8CL1-E-17
(1)#4 THWN; 120 ft
PNL: 100_8CL1-E-17
208V, 100A 1.8k SCA 65k SCAR
CB: 100_9CL1-E-17
SQUARE D (FA)
F: 100_9CL1-E-17
(1)#4 THWN; 140 ft
PNL: 100_9CL1-E-17
208V, 100A 1.6k SCA 65k SCAR
CB: 100_5CL1-E-17
SQUARE D (FA)
60 A
F: 100_5CL1-E-17
(1)#4 THWN; 60 ft
PNL: 100_5CL1-E-17
208V, 100A 2.4k SCA 65k SCAR
CB: 100_6CL1-E-17
SQUARE D (FA)
60 A
F: 100_6CL1-E-17
(1)#4 THWN; 80 ft
F: 100_Pnl 3CL1-D-17 SEC 1
(1) #1/0 THWN; 40 ft
CB: 100_3CL1-D-17 SEC 1 Main SQUARE D (Q1(B)-VH (Obs.)) 100 A
PNL: 100_3CL1-D-17 SEC 1
208V, 100A 1.8k SCA 65k SCAR
TAP: 100_XF T-46 Sec 208V, 1.9k SCA
PNL: 100_6CL1-E-17
208V, 100A 2.1k SCA 65k SCAR
UPSBypass
THERMAL CURVE = 250A (FIXED)
LONG TIME PICK UP = 0.5 (125A)
LONG TIME DELAY = 3 SEC
SHORT TIME PICK UP = 4 (1000A)
SHORT TIME DELAY = 0.1 SECI^2T IN
INSTANTANEOUS = 7 (1750A)
THERMAL CURVE = 30A
INSTANTANEOUS = FIXED
THERMAL CURVE = 70A
INSTANTANEOUS = FIXED
INSTANTANEOUS = 5 OF 7
(1488A)
INSTANTANEOUS = LO (1125A)
SWITCHBOARD "SWBD: 100_5SDEC-E-17", 208V, 400A, 3.3k SCA, 50k SCAR
400A
CB: 100_5SDEC-E-17 MAIN
THERMAL CURVE = 400A (FIXED)
INSTANTANEOUS = 2 OF 5 (2564A)
400A/3P
LSI
CB: 100_4CL1-D-17
SQUARE D POWERPACT L.
MICROLOGIC 3.2S
SPARE
SQUARE D (KA)
175 A
DPM
GENERAL NOTES
KEY NOTES
BUILDING 100 - ONE LINE DIAGRAM (BUSDUCT RISER CE BAY3)
EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS
TO BE REVISED AS SHOWN.
REPLACEMENT OVERCURRENT PROTECTIVE DEVICE.
TERMINATE BUSDUCT ENCLOSED CIRCUIT BREAKER TO
EXISTING BUSDUCT AS INDICATED.
PROVIDE ENCLOSED CIRCUIT BREAKER AND LINE SIDE
FEEDER AS SHOWN. ENCLOSED CIRCUIT BREAKER SHALL
BE PROVIDED WITH EXTRA LUGS OR TAPS AS REQUIRED
TO FEED DOWNSTREAM PANELS.
PROVIDE FIELD MODIFICATIONS AS REQUIRED TO
REPLACE INCOMING LUGS AND ANALOG METERING WITH
MAIN CIRCUIT BREAKER AND INTEGRAL POWER METER
(SE 8244), RESPECTIVELY. MODIFIED EQUIPMENT SHALL
BE RE-CERTIFIED BY UL FIELD ENGINEERS AS REQUIRED.
COORDINATE SHUTDOWN AND RE-CERTIFICATION WITH
VA. EXTEND EXISTING FEEDER "F:100_SWBD 5SDEC-E-17"
AS REQUIRED. REFERENCE DETAIL '4' ON SHEET E-502
FOR ADDITIONAL INFORMATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
BLDG 100 - REVISED ONE-LINE
DIAGRAM (PART 8 OF 21)
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR
COORDINATION OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVERCURRENT PROTECTIVE
DEVICE (OCPD) SETTING ADJUSTMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER
DISTRIBUTION EQUIPMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE EXISTING ONE-LINE DIAGRAM ON SHEET
100ED607 FOR ALL MODIFICATIONS.
100EP608
100-P-32A
100-P-32B
100-P-32C
100-P-32D
SCALE : NTS
1 BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 8 OF 21)
100ED608
ATS: 100_DES2-3
800 A
CB: 100_2DEH1-D-17
SQUARE D (IL (OBS.))
600 A
THERMAL CURVE = 600A (FIXED)
LONG TIME PICK UP = 0.6 (360A)
LONG TIME DELAY = 14 SEC
INSTANTANEOUS = 4.0 (2400A)
F: 100_2DEH1-D-17
(1) #500 THWN; 100 ft
PNL: 100_2DEH1-D-17
480V, 400A 18.5k SCA 200k SCAR
CB: 100_RF-23 15HP
SQUARE D (FA)
40 A
THERMAL CURVE = 40A
INSTANTANEOUS = FIXED
F: 100_100-RF-23 15HP
(1) #10 THWN; 120 ft
MTR: 100_100-RF-23 15HP
1 @ 15.0 HP
CB: 100_B1DEH1-F-14
SQUARE D (FI)
100 A
F: 100_B1DEH1-F-14
(1) #1/0 THWN; 80 ft
CB: 100_B1DEH1-B-13
SQUARE D (FI)
100 A
F: 100_B1DEH1-B-13
(1) #1/0 THWN; 120 ft
CB: 100_DE Riser Bay 2
SQUARE D (MA)
600 A
THERMAL CURVE = 600A (FIXED)
LONG TIME PICK UP = 1.0 (600A)
LONG TIME DELAY = 24 SEC
SHORT TIME PICK UP = 10 (6000A)
SHORT TIME DELAY = 0.1 SEC I^2T IN
INSTANTANEOUS = 12 (7200A)
F: 100_DE RISER BAY 2
(3) #3/0 THWN; 80 ft
CB: 100_1DEL1-M-17
SQUARE D (FI)
50 A
F: 100_1DEL1-M-17
(1) #3 THWN; 120 ft
XF: 100_T-4
30kVA; 5.60%Z
PRI: 480V
SEC: 208V
F: 100_PNL 1DEL1-M-17
(1) #2 THWN; 10 ft
CB: 100_1DEL1-M-17 MAIN
SQUARE D (Q1(B)-VH (OBS.))
100 A
PNL: 100_1DEL1-M-17
208V, 100A 1.4k SCA 65k SCAR
F: 100_UPS 2
(1) #2/0 THWN; 100 ft
CB: 100_UPS 2
SQUARE D (kA) 125 A
SWBD: 100_B1SDE-E-18
480V, 800A 29.0k SCA 50k SCAR
CB: 100_UPS 1
SQUARE D (kA) 125 A
F: 100_UPS 1
(1) #2/0 THWN; 100 ft
CB: 100_XFMR T-44
SQUARE D (kA) 175 A
INSTANTANEOUS = HI (1750A)
F: 100_XFMR T-44
(1) #2/0 THWN; 15 ft
XF: 100_T-44
113kVA; 6.20%Z
PRI: 480V
SEC: 208V
TAP: 100_XF T-44 SEC
208V, 4.5k SCA
F: 100_PNL 2DEL2-D-17
(1) #4/0 THWN; 10 ft
PNL: 100_2DEL2-D-17
208V, 225A 4.4k SCA 65k SCAR
F: 100_PNL 2DEL1-D-17 SEC1
(1) #4/0 THWN; 30 ft
CB: 100_2DEL1-D-17 SEC1 Main SQUARE D (kA) 175 A
PNL: 100_2DEL1-D-17 SEC1
208V, 175A 4.2k SCA 65k SCAR
F: 100_PNL 2DEL1-D-17 SEC 2
(1) #4/0 THWN; 30 ft
CB: 100_2DEL1-D-17 SEC 2 Main SQUARE D (kA) 225 A
INSTANTANEOUS = 6 OF 7 (2115A)
PNL: 100_2DEL1-D-17 SEC 2
208V, 225A 4.2k SCA 65k SCAR
CB: 100_4DELI-D-17
SQUARE D (kA) 150 A
F: 100_4DELI-D-17
(1) #1/0 THWN; 240 ft
PNL: 100_4DEL1-D-17
208V, 225A 2.1k SCA 65k SCAR
CB: 100_UNKNOWN 1
SQUARE D (QO)
20 A
CB: 100_VAC PUMP RM 221
SQUARE D (QO)
30 A
CBl: 100_HC-11 1.5HP
SQUARE D (QO)
20 A
CB: 100_1DEL1-D-17
SQUARE D (Q1(B)-VH (OBS.))
60 A
F: 100_1DEL1-D-17
(1) #2 THWN; 80 ft
PNL: 100_1DEL1-D-17
208V, 100A 2.9k SCA 65k SCAR
CB: 100_UNKNOWN 2
SQUARE D (QO)
20 A
PNL: 100_B1DEH1-B-13
480V, 100A 11.3k SCA 14k SCAR
CB: 100_Castle Washer
SQUARE D (EH)
30 A
THERMAL CURVE = 30A
INSTANTANEOUS = FIXED
CB: 100_Washer #1
SQUARE D (EH)
20 A
THERMAL CURVE = 20A
INSTANTANEOUS = FIXED
F: 100_Washer #1
(1) #12 THWN; 80 ft
DISC: 100_Washer #1 480V, 1.6k SCA
FU: 100_Washer #1
BUSSMANN (FRS-R)
15 A
CB: 100_WASHER #2
SQUARE D (EH)
20 A
THERMAL CURVE = 20A
INSTANTANEOUS = FIXED
F: 100_WASHER #2
(1) #12 THWN; 80 ft
DISC: 100_WASHER #2
480V, 1.6k SCA
FU: 100_WASHER #2
BUSSMANN (FRS-R)
15 A
CB: 100_XFMR T-2
SQUARE D (EH)
50 A
THERMAL CURVE = 50A
INSTANTANEOUS = FIXED
F: 100_XFMR T-2
(1) #4 THWN; 80 ft
XF: 100_T-2
30KVA; 5.60%Z
PRI: 480V
SEC: 208V
F: 100_PNL B1DEL1-B-13
(1) #2 THWN; 25 ft
CB: 100_B1DEL1-B-13 Main
SQUARE D (Q1(B)-VH (OBS.))
100 A
PNL: 100_B1DEL1-B-13
208V, 100A 1.3k SCA 65k SCAR
PNL: 100_B1DEH1-F-14
480V, 100A 14.4k SCA 14k SCAR
CB: 100_XFMR T-1
SQUARE D (EH)
50 A
THERMAL CURVE = 50A
INSTANTANEOUS = FIXED
F: 100_XFMR T-1
(1) #6 THWN; 10 ft
XF: 100_T-1
30kVA; 5.80%Z
PRI: 480V
SEC: 208V
F: 100_PNL B1DEL1-F-14
(1) #2 THWN; 15 ft
CB: 100_B1DEL1-F-14 Main
SQUARE D (Q1(B)-VH (OBS.))
100 A
PNL: 100_B1DEL1-F-14
208V, 100A 1.3k SCA 65k SCAR
CB: 100_REFER IN PHARM
SQUARE D (QO)
30 A
CB: 100_BLDG. 101 1DEL-K.6-21
SQUARE D (EH)
30 A
THERMAL CURVE = 30A
INSTANTANEOUS = FIXED
F: 100_BLDG. 101 1DEL-K.6-21
(1) #10 THWN; 190 FT
XF: 101_XFMR T-96
15kVA; 5.00%Z
PRI: 480V
SEC: 208V
F: 101_1DEL-K.6-21
(1) #6 THHN; 60 FT
CB: 101_1DEL-K.6-21 Main
SQUARE D (Q1(B)-VH (OBS.))
50 A
PNL: 101_1DEL-K.6-21
208V, 50A 0.6k SCA 65k SCAR
CB: 101_SSTV CONSOLE
SQUARE D (QO-VH)
20 A
CB: 101_R O POWER
SQUARE D (QO-VH)
20 A
CB: 101_UNKNOWN_A
SQUARE D (QO-VH)
20 A
F: 100_SWBD B1SDE-E-18
(2) #500 THWN; 65 ft
F: 100_ATS-CE-S2-1 (E)
(2) #350 THWN; 240 ft
F: 100_ATS-CE-S2-1(N)
(3) #350 THWN; 240 ft
ATS: 100_CE-S2-1
800 A
F: 100_SWBD BISDEC-E-18
(2) #500 THWN; 50 ft
SWBD: 100_BISDEC-E-18
480V, 800A 21.5k SCA 50k SCAR
CB: 100_Critical Riser Bay 3
SQUARE D (MA)
600 A
F: 100_Critical Riser Bay 3
(1) #600 CLASS B; 50 ft
CB: 100_2CH1-M-17
SQUARE D (LA)
400 A
F: 100_2CH1-M-17
(1) #500 THWN; 160 ft
PNL: 100_2CH1-M-17
480V, 400A 12.8k SCA 50k SCAR
CB: 100_XFMR T-6
SQUARE D (kA) 175 A
INSTANTANEOUS = 2 OF 7 (1052A)
F: 100_XFMR T-6
(2) #2/0 THWN; 60 FT
XF: 100_T-6
113kVA; 6.20%Z
PRI: 480V
SEC: 208V
TAP: 100_XF T-6 SEC
208V, 4.2k SCA
F: 100_PNL 2CL1-M-17 SEC 1
(1) #3/0 THWN; 30 ft
CB: 100_2CL1-M-17 SEC 1 Main SQUARE D (kA) 175 A
INSTANTANEOUS = 4 OF 7 (1316A)
PNL: 100_2CL1-M-17 SEC 1
208V, 175A 3.9k SCA 65k SCAR
F: 100_PNL 2CL1-M-17 SEC 2
(1) #1/0 THWN; 60 ft
CB: 100_2CL1-M-17 SEC 2 Main SQUARE D (kA) 150 A
PNL: 100_2CL1-M-17 SEC 2
208V, 150A 3.5k SCA 65k SCAR
CB: 100_PANEL 1CL1-M-17
SQUARE D (kA) 125 A
INSTANTANEOUS = LO (625A)
F: 100_PANEL 1CL1-M-17
(1) #1 THWN; 80 ft
PNL: 100_1CL1-M-17
208V, 225A 2.6k SCA 65k SCAR
CONTINUE TO BD:
100_S2 DE1
(SEE SHEET 100EP619)
CONTINUE TO TAP:
100_UPS-2-a
(SEE SHEET 100EP610)
CONTINUE TO TAP:
100_UPS-1_b
(SEE SHEET 100EP610)
CONTINUE TO SWBD:
100_2500A SWBD
CONTINUE TO SWBD:
100_USS2
(SEE SHEET 100EP606)
CONTINUE TO BD:
100_S2-CE2-B3
(SEE SHEET 100EP608)
CONTINUE TO SWBD:
"100-DESWBD-G-1"
VIA ''JB-DE''
(SEE SHEET 100EP601)
F: 100_ATS-DE-S2-3 (E)
(3) #350 THWN; 270 FT
F: 100_ATS-DE-S2-3(N)
(3) #350 THWN; 160 ft
CONTINUE TO SWBD:
100_USS2
(SEE SHEET 100EP606)
E N
PM
CM
GENERAL NOTES
KEY NOTES
EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS
TO BE REVISED AS SHOWN.
REPLACEMENT OVERCURRENT PROTECTIVE DEVICE.
PROVIDE INTEGRAL COMMUNICATION MODULE (CM) AND
POWER METER CONNECTIONS (PM) INTERIOR TO ATS.
COMMUNICATION MODULE SHALL BE ASCO #5170, OR
APPROVED EQUAL. POWER METER CONNECTIONS SHALL
BE COMPRISED OF CT'S AND VOLTAGE CONNECTIONS
INTERIOR TO ATS AND SHALL CABLE TO POWER METER
AS INDICATED ON DRAWINGS. POWER METER SHALL BE
SCHNEIDER-ELECTRIC POWERLOGIC #PM8244, OR
APPROVED EQUAL. EQUIPMENT SHALL BE INSTALLED
WITH ALL REQUIRED WIRING, TERMINATIONS, AND
APPURTENANCES AS REQUIRED FOR A COMPLETE AND
FULLY FUNCTIONAL SYSTEM.
BUILDING 100 - ONE LINE DIAGRAM (ATS-CE-S2-1 & ATS-DE-S2-3)
1 2
2 2
2 2 2 2
BLDG 100 - REVISED ONE-LINE
DIAGRAM (PART 9 OF 21)
100-P-08
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR
COORDINATION OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVERCURRENT PROTECTIVE
DEVICE (OCPD) SETTING ADJUSTMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER
DISTRIBUTION EQUIPMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE EXISTING ONE-LINE DIAGRAM ON SHEET
100ED608 FOR ALL MODIFICATIONS.
100EP609
SCALE : NTS
1 BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 9 OF 21)
100ED609
F: 100_ATS-LS-S2-2 (E)
(1) #3/0 THWN; 240 ft
CONTINUE TO SWBD:
100_USS2
(SEE SHEET 100EP606)
F:100_ATS-LS-S2-2 (N)
(1) #3/0 THWN; 80 ft
ATS: 100_LSS2-2
600 A
F: 100_SWBD
B1-SDLS-E-17
(1) #3/0 THWN; 10 ft
CB: 100_107-LSL1
SQUARE D (FA)
50 A
F:100_107-LSL1
(1) #8 THWN; 340 ft
CB: 107_T-115 PRIM.
SQUARE D (FA)
90 A
XF: 107_T-115
30KVA; 2.10%Z
PRI: 480V
SEC: 208V
CB: 107_T-115 SEC.
SQUARE D (FA)
100 A
PNL: 107_107-LSL1
208V, 100A 1.6k SCA 10k SCAR
CB: 107_UNKNOWN
SQUARE D (QO-VH)
20 A
CB: 100_B2LSH1-F-12
SQUARE D (FA)
30 A
F:100_B2LSH1-F-12
(1) #10 THWN; 120 ft
PNL: 100_B2LSH1-F-12
480V, 100A 1.8k SCA 10k SCAR
CB: 100_7LSH1-E-17
SQUARE D (FA)
150 A
THERMAL CURVE = 50A (FIXED)
LONG TIME PICK UP = 0.15 (75A)
LONG TIME DELAY = 8 SEC
SHORT TIME PICK UP= 2(300A)
SHORT TIME DELAY = 0.5 SEC I^2T IN
INSTANTANEOUS = 12 (2400A)
F: 100_7LSH1-E-17
(1) #4 THWN; 280 ft
CB: 100_3LSH1-E-17
SQUARE D (FA)
80 A
F: 100_3LSH1-E-17
(1) #2 THWN; 70 ft
PNL: 100_3LSH1-E-17
480V, 225A 10.0k SCA 14k SCAR
F: 100_3LSL1-F-10.6
(1) #10 THWN; 120 ft
CB: 100_3LSL1-F-10.6
SQUARE D (EH)
30 A
CB: 100_XFMR T-22 PRI
SQUARE D (FA)
100 A
XF: 100_T-22
30KVA; 2.10%Z
PRI: 480V
SEC: 208V
F: 100_PNL 3LSL1-F-10.6
(1) #1/0 THWN; 5 ft
CB: 100_3LSL1-F-10.6 MAIN
SQUARE D (FA)
100 A
PNL: 100_3LSL1-F-10.6
208V, 80A 2.2k SCA 10k SCAR
CB: 100_2LSH1-M-17
SQUARE D (FA)
50 A
F: 100_2LSH1-M-17
(1) #4 THWN; 280 ft
PNL: 100_2LSH1-M-17
480V, 100A 2.7k SCA 65k SCAR
CB: 100_B2LS1-J-12
SQUARE D (FA)
50 A
F: 100_B2LS1-J-12
(1) #4 THWN; 160 ft
XF: 100_T-41
30KVA; 5.00%Z
PRI: 480V
SEC: 208V
F: 100_B1LSL1-J-12
(1) #2 THWN; 20 ft
CB: 100_B1LSL1-J-12 MAIN
SQUARE D (QO-VH)
100 A
PNL: 100_B1LSL1-J-12
208V, 100A 1.4k SCA 65k SCAR
SWBD: 100_B1-SDLS-E-17
480V, 400A 19.4k SCA 50k SCAR
CB: 100_2LSL1-F.1-19
SQUARE D (FA)
30 A
F: 100_2LSL1-F.1-19
(1) #10 THWN; 220 ft
CB: 101_T-95 PRIM.
SQUARE D (FA)
100 A
XF: 101_T-95
30KVA; 2.10%Z
PRI: 480V
SEC: 208V
CB: 101_T-95 Sec.
SQUARE D (FA)
90 A
PNL: 101_2LSL1-F.1-19
208V, 100A 1.7k SCA 10k SCAR
XF: 100_UPS
75KVA; 5.50%Z
PRI: 480V
SEC: 208V
F: 100_UPS-1_c
(1) #2/0 THWN; 3 ft
CB: 100_UPS-1_CB 2
SQUARE D (KA)
125 A
TAP: 100_UPS-1_c 480V, 20.7k SCA
CB: 100_UPS-1_CB 3
SQUARE D (KA)
125 A
F: 100_UPS-1_a
(1) #2/0 THWN; 3 ft
TAP: 100_UPS-1_b 480V, 21.1k SCA
UPS: 100_UPS-1
F: 100_UPS 1
(1) #2/0 THWN; 100 ft
CB: 100_UPS-2_CB 2
SQUARE D (KA)
125 A
F: 100_UPS-2-c
(1) #2/0 THWN; 10 ft
TAP: 100_UPS-1_a 480V, 21.1k SCA
CB: 100_UPS-1_CB 1
SQUARE D (KA)
125 A
F: 100_UPS-1_b
(1) #2/0 THWN; 3 ft
UPS: 100_UPS 2
F: 100_UPS 2
(1) #2/0 THWN; 100 ft
CONTINUE TO SWBD:
100_B1SDE-E-18
(SEE SHEET 100EP609)
CB: 100_UPS-2_CB 3
SQUARE D (KA)
125 A
F: 100_UPS-2-a
(1) #2/0 THWN; 3 ft
TAP: 100_UPS-2-a 480V, 23.0k SCA
F: 100_UPS-2-b
(1) #2/0 THWN; 3 ft
CB: 100_UPS-2_CB 1
SQUARE D (KA)
125 A
OPEN
TAP: 100_UPS-2_b 480V, 22.8k SCA
UTIL: UPS-2
ISC 3P 7187 AMPS
ISC SLG 4735 AMPS
PANELBOARD "PNL: 100_7LSH1-E-17" 480V, 225A, 2.7k SCA, 65k SCAR
CB: 100_XFMR T-37
SQUARE D (EH)
30 A
F: 100_XFMR T-37
(1) #10 THWN; 120 ft
XF: 100_T-37
30KVA; 5.60%Z
PRI: 480V
SEC: 208V
F: 100_PNL PSL1-F-10.6
(1) #1 THWN; 5 ft
CB: 100_PSL1-F-10.6 MAIN
SQUARE D (Q1(B)-VH (OBS.)
60 A
PNL: 100_PSL1-F-10.6
208V, 60A 1.1k SCA 65k SCAR
CB: 100_XFMR T-30
SQUARE D (EH)
50 A
F: 100_XFMR T-30
(1) #6 THWN; 160 ft
CB: 100_XFMR T-30 PRI
SQUARE D (FA)
90 A
XF: 100_T-30
30KVA; 2.10%Z
PRI: 480V
SEC: 208V
F: 100_PNL 7LSL1-F-10.6
(1) #2 THWN; 5 ft
CB: 100_7LSL1-F-10.6 MAIN
SQUARE D (FA)
100 A
PNL: 100_7LSL1-F-10.6
208V, 100A 2.1k SCA 10k SCAR
CB: 100_XFMR T-117
SQUARE D (EH)
15 A
F: 100_XFMR T-117
(1) #12 THWN; 160 ft
XF: 100_T-117
6KVA; 5.00%Z
PRI: 480V
SEC: 208V
F: 100_Pnl 7LSL1-E-17
(1) #10 THWN; 5 ft
CB: 100_7LSL1-E-17 MAIN
SQUARE D (QO)
20 A
PNL: 100_7LSL1-E-17
208V, 20A 0.3k SCA 65k SCAR
CONTINUE TO PNL:
100_2CH1-E-17
(SEE SHEET 100EP608)
F: 100_UPS 2C
(1) #2/0 THWN; 30 ft
EP: 100_UPS 2C
480V, 13.2k SCA
F: 100_UPS 2C CB3
(1) #4 THWN; 5 ft
CB: 100_UPS 2C CB3
SQUARE D (KA)
125 A
F: 100_UPS 2C INPUT
(1) #4 THWN; 30 ft
UPS: 100_2C
F: 100_UPS 2C OUTPUT-1
(1) #4 THWN; 30 ft
CB: 100_UPS 2C CB2
SQUARE D (KA)
125 A
F: 100_UPS 2C OUTPUT-2
(1) #4 THWN; 30 ft
TAP: 100_XF UPS 2C
480V, 5.5k SCA
F: 100_UPS 2C CB1
(1) #4 THWN; 5 ft
OPEN
CB: 100_UPS 2C CB1
SQUARE D (KA)
125 A
F: 100_UPS 2C MAINT BYPASS
(1) #4 THWN; 10 ft
XF: 100_UPS 2C
80KVA; 5.00%Z
PRI: 480V
SEC: 208V
F: 100_PNL 2CL3-E-17 SEC1
(1) #2/0 THWN; 45 FT
CB: 100_2CL3-E-17 SEC1 MAIN
SQUARE D (QD) 225 A
PNL: 100_2CL3-E-17 SEC1
208V, 225A 3.1k SCA 100k SCAR
CB: 100_SEC 2
SQUARE D (QO)
100 A
F: 100_SEC 2
(1) #1/0 THWN; 5 ft
PNL: 100_2CL3-E-17 SEC 2
208V, 100A 3.0k SCA 200k SCAR
TAP: 100_UPS-2_c 480V, 21.3k SCA
CONTINUE TO SWBD:
100_2500A SWBD
CONTINUE TO SWBD:
100_B1SDE-E-18
(SEE SHEET 100EP609)
F: 101_PNL UPS MAIN Panel
(1) #3/0 THWN; 160 ft
PNL: 101_UPS MAIN
PANEL
(SEE SHEET 101EP601)
THERMAL CURVE = 50A
INSTANTANEOUS = FIXED
THERMAL CURVE = 30A
INSTANTANEOUS = FIXED
THERMAL CURVE = 15A
INSTANTANEOUS = FIXED
THERMAL CURVE = 50A
INSTANTANEOUS = FIXED
THERMAL CURVE = 30A
INSTANTANEOUS = FIXED
THERMAL CURVE = 225A
INSTANTANEOUS = HI (2250A)
XF: 100_PSL1-F-9.4
30KVA
480-208/120V
CB: 100_PSL1-F-9.4 MAIN
SQUARE D (Q1(B)-VH (OBS.)
100A
PNL: 100_PSL1-F-9.4
208V, 100A 1.0k SCA 65k SCAR
225 A/3P
CB: 100_XF PSL1-F-9.4
SQUARE D (EH)
50 A
THERMAL CURVE = 50A
INSTANTANEOUS = FIXED
PM
CM
GENERAL NOTES
KEY NOTES
BUILDING 100 - ONE LINE DIAGRAM (UPS-2C, ATS-LS-S2-2, UPS-1_UPS-2)
REPLACEMENT OVERCURRENT PROTECTIVE DEVICE.
PROVIDE PANELBOARD AS SHOWN. EXISTING INCOMING
FEEDER AND BRANCH CIRCUITS SHALL BE EXTENDED AS
REQUIRED.
PROVIDE INTEGRAL COMMUNICATION MODULE (CM) AND
POWER METER CONNECTIONS (PM) INTERIOR TO ATS.
COMMUNICATION MODULE SHALL BE ASCO #5170, OR
APPROVED EQUAL. POWER METER CONNECTIONS SHALL
BE COMPRISED OF CT'S AND VOLTAGE CONNECTIONS
INTERIOR TO ATS AND SHALL CABLE TO POWER METER
AS INDICATED ON DRAWINGS. POWER METER SHALL BE
SCHNEIDER-ELECTRIC POWERLOGIC #PM8244, OR
APPROVED EQUAL. EQUIPMENT SHALL BE INSTALLED
WITH ALL REQUIRED WIRING, TERMINATIONS, AND
APPURTENANCES AS REQUIRED FOR A COMPLETE AND
FULLY FUNCTIONAL SYSTEM.
BLDG 100 - REVISED ONE-LINE
DIAGRAM (PART 10 OF 21)
100-P-34B
100-P-34A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE EXISTING ONE-LINE DIAGRAM ON SHEET
100ED609 FOR ALL MODIFICATIONS.
1 1 1 1
100EP610
SCALE : NTS
1 BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 10 OF 21)
1-F-9.4
100ED610
UTIL: USNW (equip eval) Isc 3P 10806 Amps Isc SLG 8515 Amps
UTIL: USNW
Isc 3P 4481 Amps Isc SLG 3277 Amps
SW: USNW (3)
SQUARE D (600A)
FU: USNW
GE (EJO-1, 150E)
150 A
XF: USNW
2500kVA; 6.03%Z Pri: 12470V Sec: 480V
F: 100_SWBD USNW
(8) #4000 Class B; 3 ft
CB: 100_USNW Main
SE MASTERPACK
4000 A
SWBD: 100_USNW
480V, 4000A 35.1k SCA 50k SCAR
CB: 100_BAY 4 1600 AMP Nor.
SE MASTERPACK MTZ
1600 A
CB: 100_BI-SDN-N-2 BAY 5 Nor.
SE MASTERPACK MTZ
600 A
F: 100_BI-SDN-N-2 BAY 5 Nor
(1) #800 Class B; 250 ft
F: 100_Pump PR-15
(1) #12 THWN; 40 ft
MTR: 100_Pump PR-15 1 @ 1.5 hp
MCP: 100_Pump PR-15
SQUARE D (FAL)
CB: 100_ECC EX FAN a
SQUARE D (FA)
50 A
SWBD: 100_B1-SDN-N-2
480V, 800A 23.1k SCA 50k SCAR
PNL: 100_MCC-N-1-L-3
480V, 600A 10.2k SCA 25k SCAR
CB: 100_SWBD 2SDNM3 x-ray N
SE MASTERPACK MTZ
800 A
F: 100_SWBD 2SDNM3 x-ray N
(1) #800 Class B; 340 ft
SWBD: 100_2SDN-M-3
480V, 800A 20.2k SCA 50k SCAR
CB: 100_MRI RM 2D-124
SQUARE D (IK)
175 A
F: 100_MRI RM 2D-124
(1) #3/0 THWN; 1 ft
CB: 100_ECC EX FAN
SQUARE D (FA)
50 A
F: 100_100-SF-15
(1) #1 THWN; 20 ft
VFD:100_SF-15
MCP: 100_100-SF-15
SQUARE D (FAL)
MTR: 100_SF-15
4 @ 7.5 hp
CB: 100_ATS-CE-NW-2
SE MASTERPACK MTZ
400 A
CB: 100_XRAY RM 2D-150
SQUARE D (IK)
225A
F: 100_XRAY RM 2D-150
(1) #4/0 THWN; 160 ft
CB: 100_MCC-N-1-L-3
SQUARE D (KA)
150 A
THERMAL CURVE = 250A (FIXED)
INSTANTANEOUS = 3(1880A)
F: 100_100-RF-15
(1) #12 THWN; 20 ft
VFD: 100_RF-15
MCP: 100_100-RF-15
SQUARE D (FAL)
MTR: 100_RF-15
2 @ 2.0 hp
F: 100_MCC-N-1-L-3
(1) #1 THWN; 100 ft
CB: 100- X-RAY RM 2D-150
SQUARE D (KA)
80 A
F: 100_Pnl 2L2-M-3
(1) #2 THWN; 30 ft
CB: 100_2L2-M-3 Main
SQUARE D (KA)
125 A
PNL: 100_2L2-M-3
208V, 225A 3.8k SCA 65k SCAR
TAP: 100_T-78 SEC
208V, 4.4k SCA
CB: 100_ATS-LS-NW-3
SE MASTERPACK MTZ
200 A
CB: 100_XRAY RM 2D-151
SQUARE D (IK)
225 A
F: 100_XRAY RM 2D-151
(1) #4/0 THWN; 160 ft
CB: 100_1L3-M3
SQUARE D (KA)
125 A
INSTANTANEOUS = HI (1250A)
CB: 100_1L4-M-3 Main
SQUARE D (QB)
200 A
THERMAL CURVE = 200A (FIXED)
INSTANTANEOUS = HI (2000A)
PNL: 100_1L4-M-3
208V, 225A 4.8k SCA 200k SCAR
F: 100_Pnl 1L4-M-3
(1) #3/0 THWN; 20 ft
CB: 100_COMBI OVEN
SQUARE D (QO)
100 A
F: 100_1L3-M3
(1) #1 THWN; 60 ft
CB: 100_XRAY RM 2D-151 ex 5
SQUARE D (KA)
80 A
F: 100_Pnl 2L1-M-3 SEC 2
(1) #1/0 THWN; 26 ft
CB: 100_2L1-M-3 SEC 2 Main
SQUARE D (KA)
150 A
PNL: 100_2L1-M-3 SEC 2
208V, 150A 4.0k SCA 22k SCAR
XF2-0026
75kVA; 3.50%Z Pri: 480V Sec: 208V
CB: 100_FRYER 29
SQUARE D (QO)
40 A
PNL: 100_1L2-M-3
208V, 100A 6.2k SCA 22k SCAR
F: 100_Pnl 2L1-M-3 SEC 1
(1) #1/0 THWN; 20 ft
CB: 100_2L1-M-3 SEC 1 Main
SQUARE D (KA)
150 A
PNL: 100_2L1-M-3 SEC 1
208V, 150A 4.1k SCA 25k SCAR
XF: 100_T-78
113kVA; 6.20%Z Pri: 480V Sec: 208V
F: 100_XFMR T-78
(1) #3/0 THWN; 20 ft
PNL: 100_2H1-M-3
480V, 225A 13.7k SCA 50k SCAR
CB: 100_XFMR T-78
SQUARE D (KA)
175 A
THERMAL CURVE = 175A (FIXED)
INSTANTANEOUS = HI(1750A)
CB: 100_2H1-M-3
SQUARE D (KA)
150 A
F: 100_2H1-M-3
(1) #2/0 THWN; 80 ft
CB: 100_XRAY RM 2D-147
SQUARE D (IK)
225 A
F: 100_XRAY RM 2D-147
(1) #4/0 THWN; 170 ft
CB: 100_XRAY RM 2D-147 ex 3
SQUARE D (KA)
100 A
CB: 100_ATS-CENW-4
SE MASTERPACK MTZ
800 A
F: 100_Pnl 1L2-M-3
(1) #2/0 THWN; 20 ft
CB: 100_1L2-M-3 Main
SQUARE D (QO)
100 A
CB: 100_DEAD ENDED SPARE
SQUARE D (QO)
50 A
CB: 100_DISPOSAL DISHROOM
SQUARE D (QO)
20 A
PNL: 100_1L1-M-3 SEC 2
208V, 300A 6.3k SCA 10k SCAR
F: 100_Pnl 3L2-M-3
(1) #1/0 THWN; 20 ft
CB: 100_3L2-M-3 Main
SQUARE D (QO)
100 A
PNL: 100_3L2-M-3
208V, 100A 3.0k SCA 65k SCAR
TAP: 100_T-114 SEC
208V, 3.1k SCA
CB: 100_3L1-M-3
SQUARE D (FA)
100 A
F: 100_3L1-M-3
(1) #1 THWN; 120 ft
XF: 100_T-114
75kVA; 5.80%Z Pri: 480V Sec: 208V
CB: 100_XRAY RM 2D-102
SQUARE D (IK)
225 A
F: 100_XRAY RM 2D-102
(1) #4/0 THWN; 170 ft
CB: 100_XRAY RM 2D-102_a
SQUARE D (KA)
90 A
CB: 100_ATS-DENW-1
SE MASTERPACK MTZ
800 A
CONTINUE TO ATS:
100_DE-NW-1
(SEE SHEET 100EP615)
TAP: 100_T-74 Sec 208V, 6.8k SCA
MCP: 100_PIZZA EX FAN
SQUARE D (FAL)
MCC: 100_MCC-N-3-L-3
480V, 600A 6.4k SCA 25k SCAR
CB: 100_DISWASHER
SQUARE D (QO)
70 A
CB: 100_1L1-M-3 Main
SQUARE D (KA)
175 A
CB: 100_3L1-M-3 Main
SQUARE D (QO)
100 A
CB: 100_DISPOSER
SQUARE D (EH)
30 A
CB: 100_1H1-M-3
SQUARE D (FA)
100 A
CB: 100_XRAY RM 2D-104_a
SQUARE D (KA)
70 A
CB: 100_XRAY RM 2D-104
SQUARE D (IK)
225 A
F: 100_XRAY RM 2D-104
(1) #4/0 THWN; 170 ft
F: 100_1H1-M-3
(1) #2 THWN; 35 ft
F: 100_Pnl 3L1-M-3
(1) #1 THWN; 30 ft
F: 100_Pnl 1L1-M-3 SEC 1
(1) #2/0 THWN; 20 ft
PNL: 100_1L1-M-3 SEC 1
208V, 175A 6.2k SCA 22k SCAR
PNL: 100_3L1-M-3
208V, 100A 2.9k SCA 22k SCAR
PNL: 100_1H1-M-3 480V, 100A
15.4k SCA 42k SCAR
CB: 100_XRAY RM 2D-148 ex 4
SQUARE D (KA)
100 A
CB: 100_XRAY RM 2D-148
SQUARE D (IK)
225 A
F: 100_XRAY RM 2D-148
(1) #4/0 THWN; 170 ft
CB: 100_1L1-M-3
SQUARE D (KA)
225 A
LONG TIME PICKUP = 0.75X(225A)
LONG TIME DELAY = 14
SHORT TIME DELAY PICKUP =
4X(1200A)
SHORT TIME DELAY = 0.1 (I2T ON)
INSTANTANEOUS = 8X (2400A)
F: 100_1L1-M-3
(1) #4/0 THWN; 60 ft
XF: 100_T-74
150kVA; 5.10%Z Pri: 480V Sec: 208V
F: 100_Pnl 1L1-M-3 SEC 2
(1) #300 THWN; 20 ft
CB: 100_1L1-M-3 SEC 2 Main
SQUARE D (LA)
300 A
INSTANTANEOUS = LO (1500A)
F: 100_100-SF-35
(1) #4 THWN; 30 ft
VFD: 100_SF-35
MCP: 100_100-SF-35
SQUARE D (FAL)
MTR: 100_SF-35
1 @ 15.0 hp
CB: 100_CANTEEN KIT REC.
SQUARE D (QO)
40 A
DISC: 100_Room 4D-153 480V, 5.4k SCA
CB: 100_XRAY RM 4D-129
SQUARE D (IK)
125 A
F: 100_XRAY RM 4D-129
(1) #3/0 THWN; 400 ft
CB: 100_3H1-M-3
SQUARE D (FA)
100 A
REPLACED 100A
F: 100_3H1-M-3
(1) #1 THWN; 120 ft
F: 100_Pump PR-B12
(1) #12 THWN; 30 ft
MTR: 100_Pump PR-B12 1 @ 1.5 hp
MCP: 100_Pump PR-B12
SQUARE D (FAL)
MCC: 100_MCC-N-B1-L-3
480V, 600A 14.2k SCA 25k SCAR
MCP: 100_100-EF-46
SQUARE D (FAL)
No conductors on load side
PNL: 100_3H1-M-3
480V, 100A 9.1k SCA 14k SCAR
CB: 100- MRI RM 2D-134_a
SQUARE D (KA)
100 A
CB: 100_MRI RM 2D-134
SQUARE D (IK)
225 A
F: 100_MRI RM 2D-134
(1) #4/0 THWN; 160 ft
F: 100_100-SF-B12
(1) #6 THWN; 30 ft
VFD: 100_SF-B12
MCP: 100_100-SF-B12
SQUARE D (FAL)
MTR: 100_SF-B12
6 @ 7.5 hp
CB: 100_COMBI-THERM
SQUARE D (FA)
90 A
F: 100_Pump PR-25
(1) #12 THWN; 50 ft
MCP: 100_Pump PR-25
SQUARE D (FAL)
MTR: 100_Pump PR-25 1 @ 1.5 hp
MCP: 100_100-EF-45
SQUARE D (FAL)
MCC: 100_MCC-N-2-L-3
480V, 600A 10.2k SCA 25k SCAR
F: 100_100-SF-25
(1) #4 THWN; 20 ft
VFD: 100_SF-25
MCP: 100_100-SF-25
SQUARE D (FAL)
MTR: 100_SF-25
6 @ 7.5 hp
F: 100_100-RF-B12
(1) #12 THWN; 30 ft
VFD: 100_RF-B12
MCP: 100_100-RF-B12
SQUARE D (FAL)
MTR: 100_RF-B12
6 @ 1.5 hp
CB: 100_MCC-N-B1-L-3
SQUARE D (LA)
250 A
THERMAL CURVE = 250A (FIXED)
INSTANTANEOUS = 3 (1930A)
F: 100_MCC-N-B1-L-3
(1) #3/0 THWN; 85 ft
MCP:…