Attachment 3-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 1.pdf
PDF 7 MB Posted
- Solicitation number
- 36C26025R0071
About this file
This document is a set of electrical construction drawings for the Portland VA Medical Center's electrical deficiency correction project (Project No. 648-20-119). The comprehensive set of electrical plans covers Buildings 6, 16, 41, 100, 101, 102, 103, 104, 105, and 108 (parking garage), detailing extensive electrical system modifications across multiple building levels.
The project scope involves correcting electrical deficiencies based on a Wiley-Wilson arc-flash hazard risk assessment, with key work including replacing medium voltage switchgear, modifying electrical distribution equipment, installing active harmonic filters, upgrading circuit breakers, replacing emergency generator control panels, and performing ground resistance testing. The work will be phased, with specific requirements for shutdowns, equipment replacement, and coordination with VA medical center operations. The drawings are fully sprinklered and prepared by Spees Design Build, with an anticipated completion date of January 31, 2025.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T51
NO PARKING
27A
Trailer
Trailer
LOT 4
LOT 1
LOT 5
LOT 6
LOT 7
ONLY
ONLY
STOP
ONLY
STOP
STOP
STO
P AHE
AD
ST
OP
STOP
ST
OP
AH
EA
D
ST
OP
STO
P
STOP
AHEAD
ST
OP
BUS
STOP
STOP
LOT 9
SW US VETERANS HOSPITAL ROAD
SW GAIN
ES STREET
SW
U
S V
ETERA
N S H
O
SPITA
L RO
A
D
LOT 14
LOT 8
ST
OP
ST
OP
LOT 4
STOP
POLICE
POLICE
POLICE
POLICE
LOT 1
PORTLAND VA MEDICAL CENTER - PORTLAND, OR
PROJECT NO. 648-20-119
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAOR
1 PORTLAND VAMC VICINITY PLAN
NOT TO SCALE
DESIGN TEAM
GENERAL
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
PHONE: (206) 590-2118
ELECTRICAL
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
PHONE: (206) 590-2118
PROJECT INFORMATION
STATE:
COUNTY:
JURISTICTION:
OWNER:
CODE ANALYSIS
PROJECT DESCRIPTION
APPLICABLE BUILDING
BUILDINGS 6, 16, 100, 101, 102, 103, 104, 105, AND 108 (PARKING GARAGE)
APPLICABLE FLOOR
ALL FLOORS
APPLICABLE CLINIC(S)
N/AICRA CLASS REQUIREMENTS
CONST TYPE:
CLINIC RISK:
CLASS REQS:
APPROXIMATE SQUARE FOOTAGE
NA
TYPE C
HIGHEST
CLASS IV
OREGON
MULTNOMAH
PORTLAND
GOV, VETERANS AFFAIRS
6, 16, 100, 101, 102, 103, 104, 105, AND 108 (PARKING
GARAGE)
THE VA HAS IDENTIFIED VARIOUS ELECTRICAL DEFICIENCIES
THROUGHOUT THE CAMPUS, THESE DEFICIENCIES HAVE BEEN
IDENTIFIED THROUGH PREVIOUS PROJECTS, OTHER GOVERNMENT
AGENCIES, AND LOCAL STATION VA STAFF. THE A/E HAS BEEN
TASKED TO ANALYZE AND PROVIDE DETAILED CONSTRUCTION
PLANS AND SPECIFICATIONS TO RESOLVE AS MANY ELECTRICAL
DEFICIENCIES AS POSSIBLE WITHIN THE GIVEN BUDGET WHILE
MAINTAINING THE VA’S PRIORITIES. THE FOLLOWING SHALL BE
PROVIDED IN THE SUBJECT PROJECT:
1. ALL BUILDINGS WITHIN SCOPE: REPLACE, MODIFY, OR UPGRADE
EXISTING ELECTRICAL POWER DISTRIBUTION EQUIPMENT TO
PROVIDE CORRECTIONS PER WILEY-WILSON ARC-FLASH REPORT.
ONCE ALL POWER ASPECTS OF THE PROJECT HAVE BEEN
COMPLETED, A FACILITY WIDE ARC-FLASH HAZARD RISK
ASSESSMENT WITH REPORT AND LABELING SHALL BE PERFORMED IN
ACCORDANCE WITH SPECIFICATION 26 05 73.
2. BUILDINGS 100, 101, 103: REPLACE ALL MV “OLD SWITCHGEAR” AND
UNIT SUBSTATION CIRCUIT BREAKERS.
3. BUILDING 100: FACILITY WIDE GROUND RESISTANCE TESTING PER
VHA DIRECTIVE 1028-8.J(6)(e).
4. BUILDINGS 100, 101, 103: LS & CRITICAL AUTOMATIC TRANSFER
SWITCHES POWER METER AND COMMUNICATION MODULE
UPGRADES (7ATSs TOTAL).
5. BUILDING 100: PROVIDE POWER DISTRIBUTION EQUIPMENT FOR
DELAYED EQUIPMENT AUTOMATIC TRANSFER SWITCHES;
DISTRIBUTION EQUIPMENT INCLUDES MV INTERRUPTER SWITCHES,
MV DRY-TYPE TRANSFORMER, AND DISTRIBUTION SWITCHBOARD.
6. BUILDING 100: REPLACE MV RING LOOP FEEDER FROM MV OLD
SWITCHGEAR TO UNIT SUBSTATION “USNW”.
7. BUILDING 100: REPLACE EMERGENCY GENERATOR CONTROL PANEL
ELECTRONICS WITHIN GENERATOR MASTER CONTROL PANEL AND
PROVIDE REDUNDANT PLC CPU WITHIN OHSU CONTROL PANEL;
PROVIDE PROGRAMMING AS REQUIRED.
8. BUILDINGS 100, 101, 103: PROVIDE SPARE CIRCUIT BREAKERS FOR
MV AND UNIT SUBSTATION SWITCHGEAR.
9. BUILDING 16: REPLACE MAIN ELECTRICAL DISTRIBUTION EQUIPMENT.
10. BUILDING 105: RENOVATE EXISTING BLDG 105; PROVIDE MODULAR
BUILDING “ELECTRICAL ROOM” TO HOUSE ELECTRICAL DISTRIBUTION
EQUIPMENT AND VFDs FOR BLDG 105 AND COOLING TOWERS.
11. BUILDINGS 100: PROVIDE ACTIVE HARMONIC FILTERS AT UNIT
SUBSTATIONS “USNW”, “USS2”, “USCP”, AND “USCL” TO PROVIDE
HARMONIC MITIGATION AND UNITY POWER FACTOR CORRECT.
PROJECT WORK HOURS
ALL WORK SHALL BE COORDINATED AND
APPROVED WITH VA. ALL WORK SHALL BE
CONDUCTED AFTER-HOURS, UNLESS DIRECTED
OTHERWISE BY VA. IN GENERAL, AFTER HOURS
SPAN FROM 4:00 PM TO 7:00 AM. SPECIALIZED
AREAS/ROOMS HAVE SPECIFIC AFTER-HOURS AS
INDICATED BELOW:
- ED (100-1B), 10:00 PM TO 10:00 AM.
- OR (100-3C), 9:00 PM TO 7:00 AM.
- OCCUPIED WARD, 4:00 PM TO 9:00 PM &
6:00 AM TO 7:00 AM.
- WEEKEND IS CONSIDERED AFTER HOURS.
AREA OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
COVER SHEET
PROJECT
NORTH
G-001
BUILDINGS
CORRECTION.
G E N E R A L N O T E S
ARCHITECTURAL NOTES
1. COORDINATE WORK WITH ALL CONTRACT DOCUMENTS, INCLUDING BUT NOT
LIMITED TO DRAWINGS AND SPECIFICATIONS.
2. COORDINATE ALL WORK WITH IN-HOUSE VA CONSTRUCTION.
3. SPECIFICATIONS SHALL SUPERSEDE DRAWING PLANS IN THE CASE OF ANY
CONFLICTING INFORMATION. VERIFY WITH THE VA COR BEFORE PROCEEDING.
4. CONTRACTOR AND ANY SUB-CONTRACTORS SHALL ENSURE ALL WORK IS DONE
IN CONFORMANCE WITH ALL APPLICABLE CODES, ORDINANCES AND
REGULATIONS. RELEVANT CODES INCLUDE, BUT ARE NOT LIMITED TO THE
FOLLOW:
LATEST EDITION OF THE FOLLOWING CODES
A. INTERNATIONAL BUILDING CODE
B. INTERNATIONAL MECHANICAL CODE
C. INTERNATIONAL PLUMBING CODE
D. NATIONAL ELECTRIC CODE (NEC)
E. FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS
F. NFPA 101
G. NFPA 99
H. ALL VA DESIGN GUIDES, MANUALS AND STANDARDS
5. CONTRACTOR AND ANY SUB-CONTRACTORS SHALL FAMILIARIZE THEMSELVES
WITH EXISTING CONDITIONS, LOCATIONS AND PROJECT REQUIREMENTS PRIOR
TO SUBMITTING A BID.
6. CONTRACTOR AND ANY SUB-CONTRACTORS SHALL FIELD VERIFY DIMENSIONS,
AND FAMILIARIZE THEMSELVES WITH PROJECT REQUIREMENTS PRIOR TO
COMMENCING WORK. CONTRACTOR SHALL REPORT ANY DISCREPANCIES
DIRECTLY TO THE VA COR. NO ALLOWANCES WILL BE MADE ON BEHALF OF THE
CONTRACTOR OR SUB-CONTRACTORS FOR FAILURE TO VISIT THE SITE.
7. THE CONTRACTOR SHALL CHECK AND FIELD VERIFY ALL EXISTING CONDITIONS
AND DIMENSIONS BEFORE BEGINNING WORK. ANY CONFLICTS BETWEEN
EXISTING CONDITIONS AND THE DRAWINGS AND SPECIFICATIONS SHALL BE
BROUGHT IMMEDIATELY TO THE ATTENTION OF THE COR.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL PRODUCT TYPES
AND QUANTITIES DURING SITE WALK THROUGH WITH THE COR, BEFORE
PURCHASING ANY MATERIALS, EQUIPMENT, PRODUCTS OR LABOR.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION AND
COORDINATION WITH ALL INSTALLERS TO ENSURE COMPLIANCE TO THE
DRAWINGS AND SPECIFICATIONS.
10. ALL WORK DONE BY THE CONTRACTOR OR SUB-CONTRACTORS SHALL BE
PERFORMED WITH A HIGH LEVEL OF WORKMANSHIP.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING A CONSTRUCTION
SCHEDULE IN ACCORDANCE WITH IN-HOUSE VA WORK. THE PLAN WILL BE
REVIEWED AND APPROVED BY THE COR PRIOR TO BEGINNING WORK.
12. DIMENSIONS ARE NOT ADJUSTABLE UNLESS NOTED WITH A +/- SYMBOL. ONLY
NORMAL INDUSTRY STANDARD TOLERANCES ARE ACCEPTABLE DEVIATIONS
FROM DIMENSIONS INDICATED. DO NOT SCALE DRAWINGS. ALL DIMENSIONS
NOTED AS CLEAR SHALL MAINTAIN THE FULL SPACE INDICATED WITHOUT
ENCROACHMENTS. ALL VERTICAL HEIGHTS INDICATED ARE FROM THE FINISH
FLOOR ELEVATION UNLESS OTHERWISE NOTED.
13. SEE ABOVE FOR ARCHITECTURAL SYMBOLS, ABBREVIATIONS, AND DRAWING
INDEX.
14. FURNISH ALL PRODUCTS TO COMPLY WITH VA STANDARDS, UON.
15. DAMAGES THAT OCCUR TO VA PROPERTY DURING CONSTRUCTION SHALL BE
FIXED BACK TO THEIR ORIGINAL CONDITION FREE OF CHARGE.
16. WORKING HOURS FOR THE PROJECT SHALL BE OUTSIDE OF NORMAL WORKING
HOURS (7:00AM - 4:00PM, MONDAY THRU FRIDAY).
17. UTILITY TIE-IN COORDINATION FOR SHUT DOWNS SHALL BE AT THE
CONVENIENCE OF THE VA PORTLAND MEDICAL CENTER.
STORAGE AREA NOTES
1. CONTRACTOR SHALL COORDINATE AND VERIFY STORAGE AREA WITH THE
COR.
2. COORDINATE CONTRACTOR STORAGE LOCATION AT THE
PRE-CONSTRUCTION MEETING. THIS INCLUDES, BUT IS NOT LIMITED TO,
AREAS TO BE USED FOR MATERIAL STORAGE, ACCESS FOR MATERIAL
DELIVERIES, PARKING, AND TRANSPORTATION ROUTES TO THE PROJECT
AREA.
3. ENSURE COMPLIANCE WITH ALL NECESSARY CONTRACT DOCUMENTS
REGARDING CONTRACTOR STORAGE AREA.
4. DO NOT STORE MATERIALS, TOOLS, EQUIPMENT OR VEHICLES IN ANY
LOCATION ON MEDICAL CENTER PROPERTY UNLESS GIVEN PRIOR VA
APPROVAL BY THE COR.
5. VERIFY STORAGE PLAN WITH COR BEFORE BRINGING OR DELIVERING
MATERIALS, TOOLS OR EQUIPMENT TO THE MEDICAL CENTER.
6. A LIMITED AMOUNT OF MATERIALS AND TOOLS MAY BE STORED IN THE
CONSTRUCTION AREA WITHIN THE APPLICABLE BUILDING AS LONG AS
SAFETY AND CLEANLINESS ARE NOT COMPROMISED. COR HAS AUTHORITY
TO REQUEST RELOCATION OF ANY AND ALL STORED MATERIALS, TOOLS
AND EQUIPMENT TO A DIFFERENT LOCATION.
AB
ADJ
A/E
AFF
AGG
ALT
ALUM
APPROX
ARCH
ASPH
A/V
BARR
BATH
BRKT
BLDG
BLK
BLKG
BLW
BM
BMTU
BRNG
BOC
BOS
BO
BTM
BRC
CAB
CLG
CTR
CLR
CM
CO
COL
COMP
CONC
CMU
CONN
CONST
CONT
COR
CJ
CS
COORD
CORR
CT
DEMO
DIA
DC
DIM
DN
DR
DBL
DTL
DWG
E
EA
ELEV
ELEC
EOC
EOP
EQ
EQUIP
ES
EX(IST)
EXP
EJ
ETS
EXT
FA
FD
FE(C)
FF
FFB
FFL
FIN
FLASH
FLR
FLOUR
FNDN
FOC
FOF
FOS
FP
FRM
FT
FTG
FUR
FURN
GA
GALV
GC
GMU
GLB
GB/GWB
GFGI
GOVT
GYP
HDWE
HDR
HT
HM
HORZ
HR
ICRA
INCL
INST
ID
INSUL
INT
J-BOX
JT
KV
LAM
LAV
LT
MAT
MAX
MECH
MFR
MIN
MISC
MTL
MOD
N/A
NCS
NC
NOM
N
NTS
NO.
O.C.
OFCI
OFOI
OPNG
OPP
OVHD
P
PR
PNL
PTN(S)
PVMT
P.C.
PRFB
PT
PL
PLYWD
PLAM
PS
PM
PME
QTY
RAD
REF
REINF
REQ
REQ'D
REQ'MT
RESIL
REV
RM
RO
S
SCHED
SECT
SF
SHG
SHT(G)
SIM
SM
SPEC
SQ
SS
STDG
STL
STOR
STRUCT
SUSP
SV
SYS
THK
THRESH
TOC
TOS
TPH
T&G
TRANS
TS
TYP
UON
VA
VAR
VB
VERT
VIF
W
WT
W/
W/O
WD
WDW
WP
WH
WR
WT
AND
ANGLE
AT
CENTERLINE
DEGREES
NUMBER
ANCHOR BOLT
ADJACENT
ARCHITECT/ENGINEER
ABOVE FINISH FLOOR
AGGREGATE
ALTERNATE
ALUMINUM
APPROXIMATELY
ARCHITECT(URAL)
ASPHALT
AUDIO / VIDEO
BARRIER
BATHROOM
BRACKET
BUILDING
BLOCK
BLOCKING
BELOW
BEAM
BONE MARROW TRANSPLANT UNIT
BEARING
BOTTOM OF CURB
BOTTOM OF SLAB
BOTTOM OF
BOTTOM
BRACE, BRACING
CABINET
CEILING
CENTER
CLEAR
COMMUNICATIONS MODULE
CONTRACTING OFFICER
COLUMN
COMPOSITION
CONCRETE
CONCRETE MASONRY UNIT
CONNECTION
CONSTRUCTION
CONTINUOUS
CONTRACTING OFFICER REP.
CONTROL JOINT
CONCRETE SEALER
COORDINATE
CORRIDOR
CURRENT TRANSFORMER
DEMOLISH(ION)
DIAMETER
DIRECT CURRENT
DIMENSION
DOWN
DOOR
DOUBLE
DETAIL
DRAWING(S)
EAST
EACH
ELEVATION
ELECTRIC(AL)
END OF CURB
EDGE OF PAVEMENT
EQUAL
EQUIPMENT
EACH SIDE
EXISTING
EXPANSION
EXPANSION JOINT
EXPOSED TO STRUCTURE
EXTERIOR
FIRE ALARM
FLOOR DRAIN
FIRE EXTINGUISHER (CABINET)
FACTORY FINISH
FINISH FLOOR BREAK
FINISH FLOOR LINE
FINISH(ED)
FLASHING
FLOOR(ING)
FLOURESCENT
FOUNDATION
FACE OF CONCRETE
FACE OF FINISH
FACE OF STUDS
FIRE PROOF
FRAME
FOOT, FEET
FOOTING
FURRING
FURNISHED
GAGE, GAUGE
GALVANIZED
GENERAL CONTRACTOR
GLASS MASONRY UNIT
GLUE LAMINATED BEAM
GYPSUM WALL BOARD
GOVT FURN. GOVT INSTALLED
GOVERNMENT
GYPSUM
HARDWARE
HEADER
HEIGHT
HOLLOW METAL
HORIZONTAL
HOUR
INFECTIOUS CONTROL RISK
ASSESSMENT
INCLUDE(D,ING)
INSTALL
INSIDE DIAMETER OR DIMENSION
INSULATION
INTERIOR
JUNCTION BOX
JOINT
KILOVOLT
LAMINATE(D)
LAVATORY
LIGHT
MATERIAL(S)
MAXIMUM
MECHANIC(AL)
MANUFACTURE(R)
MINIMUM
MISCELLANEOUS
METAL
MODIFIED
NOT APPLICABLE
NURSE CALL STATION
NURSE CALL
NOMINAL
NORTH
NOT TO SCALE
NUMBER
ON CENTER(S)
OWNER FURN. CONTRACTOR INST.
OWNER FURN. OWNER INST.
OPENING
OPPOSITE
OVERHEAD
PAINT
PAIR
PANEL
PARTITION(S)
PAVEMENT
PRECAST CONCRETE
PREFABRICATED
PRESSURE TREATED
PLATE
PLYWOOD
PLASTIC LAMINATE
PLASTIC
POWER METER
POWER METER ENCLOSURE
QUANTITY
RADIUS
REFERENCE
REINFORCE(D,ING)
REQUIRE
REQUIRED
REQUIREMENT
RESILIENT
REVERSE
ROOM
ROUGH OPENING
SOUTH
SCHEDULE
SECTION
SQUARE FEET
SHINGLES
SHEET (SHEATHING)
SIMILAR
SEAM
SPECIFICATION
SQUARE
STAINLESS STEEL
STANDING
STEEL
STORAGE
STRUCTURAL
SUSPENDED
SHEET VINYL
SYSTEM
THICK(NESS)
THRESHOLD
TOP OF CURB
TOP OF SIDEWALK/PAD
TOILET PAPER HOLDER
TONGUE AND GROOVE
TRANSITION
TUBE STEEL
TYPICAL
UNLESS OTHERWISE NOTED
US DEPT. OF VETERANS AFFAIRS
VARIES
VAPOR BARRIER
VERTICAL
VERIFY IN FIELD
WEST
WEIGHT
WITH
WITHOUT
WOOD
WINDOW
WATERPROOF(ING)
WATER HEATER
WATER RESISTANT
WOOD TRIM
TRUE NORTH ARROW
PROJECT NORTH ARROW (NORTH
ARROW SOLID)
S Y M B O L S A B B R E V I A T I O N S
TRUE
NORTH
PROJECT
NORTH
APPLICABLE PUBLICATIONS
· AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
· AMERICAN SOCIETY FOR TESTING MATERIALS (ASTM)
· BUILDING INDUSTRY CONSULTING SERVICE INTERNATIONAL (BICSI)
· FEDERAL COMMUNICATIONS COMMISSION (FCC), ALL REGULATIONS,
PROCEDURES AND STANDARDS FOR TWO-WAY RADIO EQUIPMENT, SYSTEMS
AND OPERATION
· ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA (IESNA)
· INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE)
· INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO), STANDARDS
FOR PROTOCOLS AND INTERFACES THAT INCLUDE OPEN SYSTEM
INTERCONNECTIONS (OSI)
· JOINT COMMISSION ON ACCREDITATION OF HEALTHCARE ORGANIZATIONS
(JCAHO), ENVIRONMENT OF CARE GUIDELINES AND STANDARDS
· FACILITIES GUIDELINES INSTITUTE (FGI): 2010 , OR MOST CURRENT ISSUE,
GUIDELINES FOR THE DESIGN AND CONSTRUCTION OF HEALTH CARE
FACILITIES
· U.S. GREEN BUILDING COUNCIL (USGBC) LEED PROGRAM & SUSTAINABLE
BUILDING DESIGN
· THE GREEN BUILDING INITIATIVE (GBI), GREEN GLOBES ENVIRONMENTAL
ASSESSMENT AND RATING SYSTEM
· THE AMERICAN INSTITUTE OF ARCHITECTS (AIA) AND NATIONAL SOCIETY OF
PROFESSIONAL ENGINEERS(NSPE) RECENT ADDITIONS TO THEIR
PROFESSIONAL CODES OF ETHICS ENCOURAGING ENVIRONMENTALLY
RESPONSIBLE DESIGN
· NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
· INTERNATIONAL BUILDING CODE (IBC 2018)
· INTERNATIONAL EXISTING BUILDING CODE (IEBC 2018)
· OSHA STANDARDS LATEST EDITION
D R A W I N G S E T N A R R A T I V E
THESE CONTRACT DRAWINGS ARE ARRANGED IN CAD STANDARD FORMAT; 100-SERIES DRAWINGS ARE FLOOR PLANS, 400-SERIES ARE ENLARGED PLANS, 500-SHEETS ARE DETAIL SHEETS, 600-SHEETS ARE ONE-LINE DIAGRAMS, AND 700-SHEETS ARE SCHEDULES. A/E RECOMMENDS REVIEWING THE ONE-LINE
DIAGRAMS FIRST, AS THE BULK OF WORK IS INDICATED THERE.
IN GENERAL, THE SHEET TYPES LISTED BELOW INDICATE THE FOLLOWING TYPE OF WORK:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
SYMBOLS, ABBREVIATIONS, AND
GENERAL NOTES SHEET
100-SERIES DRAWINGS IDENTIFY THE ELECTRICAL DISTRIBUTION EQUIPMENT THAT REQUIRE OVER-CURRENT PROTECTIVE DEVICE (OCPD) -
REPLACEMENT AND/OR TIME-CURRENT CURVE (TCC) ADJUSTMENTS.
400-SERIES DRAWINGS INDICATE DETAILED ELECTRICAL PLAN LAYOUTS FOR VARIOUS TASKS.
500-SERIES DRAWINGS INDICATE ELECTRICAL DETAILS, ELEVATIONS, AND WIRING DIAGRAMS.
600-SERIES DRAWINGS INDICATE ALL ELECTRICAL WORK IMPACTING THE FACILITY'S ONE-LINE DIAGRAMS.
700-SERIES DRAWINGS INDICATE ELECTRICAL LOAD/PANEL SCHEDULES, LUMINAIRE SCHEDULES, AND OCPD REPLACEMENT AND/OR
ADJUSTMENT SCHEDULES.
G-002
THESE CONTRACT DRAWINGS ARE ARRANGED IN CAD STANDARD FORMAT; 100-SERIES DRAWINGS ARE FLOOR PLANS, 400-SERIES ARE ENLARGED PLANS, 500-SHEETS ARE DETAIL SHEETS, 600-SHEETS ARE ONE-LINE DIAGRAMS, AND 700-SHEETS ARE SCHEDULES. A/E RECOMMENDS REVIEWING THE ONE-LINE
DIAGRAMS FIRST, AS THE BULK OF WORK IS INDICATED THERE.
IN GENERAL, THE SHEET TYPES LISTED BELOW INDICATE THE FOLLOWING TYPE OF WORK:
100-SERIES DRAWINGS IDENTIFY THE ELECTRICAL DISTRIBUTION EQUIPMENT THAT REQUIRE OVER-CURRENT PROTECTIVE DEVICE (OCPD)
REPLACEMENT AND/OR TIME-CURRENT CURVE (TCC) ADJUSTMENTS.
400-SERIES DRAWINGS INDICATE DETAILED ELECTRICAL PLAN LAYOUTS FOR VARIOUS TASKS.
500-SERIES DRAWINGS INDICATE ELECTRICAL DETAILS, ELEVATIONS, AND WIRING DIAGRAMS.
600-SERIES DRAWINGS INDICATE ALL ELECTRICAL WORK IMPACTING THE FACILITY'S ONE-LINE DIAGRAMS.
700-SERIES DRAWINGS INDICATE ELECTRICAL LOAD/PANEL SCHEDULES, LUMINAIRE SCHEDULES, AND OCPD REPLACEMENT AND/OR
ADJUSTMENT SCHEDULES.
S H E E T I N D E X
G-001 - COVER SHEET
G-002 - SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES SHEET
G-003 - SHEET INDEX AND PHASING NARRATIVE
E-001 - ABBREVIATIONS, GENERAL NOTES, AND GENERAL SYMBOLS
E-002 - ELECTRICAL LEGENDS
006E-101 - BLDG 006 - LEVEL 01 - ELECTRICAL PLAN
016E-101 - BLDG 016 - LEVEL 01 - ELECTRICAL PLAN
100EG101 - BLDG 100 - GROUNDING PLAN
100E-1000 - BLDG 100 - LEVEL B2 - ELECTRICAL PLAN
100E-100 - BLDG 100 - LEVEL B1 - ELECTRICAL PLAN
100E-101 - BLDG 100 - LEVEL 01 - ELECTRICAL PLAN
100E-102 - BLDG 100 - LEVEL 02 - ELECTRICAL PLAN
100E-103 - BLDG 100 - LEVEL 03 - ELECTRICAL PLAN
100E-104 - BLDG 100 - LEVEL 04 - ELECTRICAL PLAN
100E-105 - BLDG 100 - LEVEL 05 - ELECTRICAL PLAN
100E-106 - BLDG 100 - LEVEL 06 - ELECTRICAL PLAN
100E-107 - BLDG 100 - LEVEL 07 - ELECTRICAL PLAN
100E-108 - BLDG 100 - LEVEL 08 - ELECTRICAL PLAN
100E-109 - BLDG 100 - LEVEL 09 - ELECTRICAL PLAN
100E-110 - BLDG 100 - LEVEL 10 - ELECTRICAL PLAN
101E-101 - BLDG 101 - LEVEL 01 - ELECTRICAL PLAN
101E-102 - BLDG 101 - LEVEL 02 - ELECTRICAL PLAN
101E-103 - BLDG 101 - LEVEL 03 - ELECTRICAL PLAN
101E-104 - BLDG 101 - LEVEL 04 - ELECTRICAL PLAN
101E-105 - BLDG 101 - LEVEL 05 - ELECTRICAL PLAN
101E-106 - BLDG 101 - LEVEL 06 - ELECTRICAL PLAN
101E-107 - BLDG 101 - LEVEL 07 - ELECTRICAL PLAN
102E-101 - BLDG 102 - LEVEL P2 - ELECTRICAL PLAN
103E-101 - BLDG 103 - LEVEL 01 - ELECTRICAL PLAN
103E-102 - BLDG 103 - LEVEL P5 - ELECTRICAL PLAN
104E-1000 - BLDG 104 - LEVEL B2 - ELECTRICAL PLAN
104E-100 - BLDG 104 - LEVEL B1 - ELECTRICAL PLAN
104E-101 - BLDG 104 - LEVEL 01 - ELECTRICAL PLAN
105ED101 - BLDG 105 - OVERALL ELECTRICAL DEMOLITION PLAN
105EP101 - BLDG 105 - OVERALL ELECTRICAL PLAN
016E-401 - BLDG 016 - RM 116 - ENLARGED ELECTRICAL PLANS
100E-4000a - BLDG 100 - RM B2C-114 - USS1 ELECTRICAL PLAN 100E-4000b - BLDG 100 - RM B2D-106a - ENLARGED ELECTRICAL PLANS 100E-4000c - BLDG 100 - RMB2D-119 - ENLARGED ELECTRICAL PLANS 100E-4000d - BLDG 100 - RM B2D-122 - USCL ELECTRICAL PLANS 100E-400a - BLDG 100 - RM B1C-119 - ENLARGED ELECTRICAL PLAN 100E-400b - BLDG 100 - RM B1C-127 - USS2 ELECTRICAL PLANS 100E-400c - BLDG 100 - RM B1C-104 - ENLARGED ELECTRICAL PLANS 100E-400d - BLDG 100 - RM B1D-108 - MV ENLARGED ELECTRICAL PLANS 100E-400e - BLDG 100 - RM B1D-109 - ENLARGED ELECTRICAL PLANS 100E-400f - BLDG 100 - RM B1D-112 - USCP ENLARGED ELECTRICAL PLANS 100E-400g - BLDG 100 - RM B1D-111 - ENLARGED ELECTRICAL PLAN 100E-401a - BLDG 100 - RM 1C-154 - ENLARGED ELECTRICAL PLANS 100E-401b - BLDG 100 - RM 1B-133 - ENLARGED ELECTRICAL PLANS 100E-401c - BLDG 100 - RM 1D-156 - ENLARGED ELECTRICAL PLANS 100E-402a - BLDG 100 - RM 2C-121 - ENLARGED ELECTRICAL PLANS 100E-402b - BLDG 100 - RM 2B-127 - ENLARGED ELECTRICAL PLANS 100E-403a - BLDG 100 - RM 3C-115 - ENLARGED ELECTRICAL PLANS 100E-403b - BLDG 100 - RM 3B-116 - ENLARGED ELECTRICAL PLANS 100E-403c - BLDG 100 - RM 3D-170 - ENLARGED ELECTRICAL PLANS 100E-404a - BLDG 100 - RM 4C-118 - ENLARGED ELECTRICAL PLANS 100E-404b - BLDG 100 - RM 4D-153 - ENLARGED ELECTRICAL PLANS
100E-405 - BLDG 100 - RM 5C-142 - ENLARGED ELECTRICAL PLANS
100E-407a - BLDG 100 - RM 7C-132 - ENLARGED ELECTRICAL PLANS 100E-407b - BLDG 100 - RM 7D-148 - ENLARGED ELECTRICAL PLANS
100E-408 - BLDG 100 - RM 8D-149 - ENLARGED ELECTRICAL PLANS
100E-409 - BLDG 100 - RM 9D-149 - ENLARGED ELECTRICAL PLANS
101E-407 - BLDG 101 - RM 703 - ENLARGED ELECTRICAL PLANS
103E-402 - BLDG 103 - RM PF5-107 - ENLARGED ELECTRICAL PLANS
105E-401a - BLDG 105 - ENLARGED ELECTRICAL PLANS 105E-401b - BLDG 105 - ENLARGED ELECTRICAL PLANS 105E-401c - BLDG 105 - ENLARGED ELECTRICAL PLANS
E-501 - ELECTRICAL DETAILS
E-502 - ELECTRICAL DETAILS
E-503 - ELECTRICAL DETAILS
E-504 - ELECTRICAL DETAILS
E-505 - ELECTRICAL DETAILS
E-506 - ELECTRICAL DETAILS
E-507 - ELECTRICAL DETAILS
E-508 - ELECTRICAL DETAILS
E-509 - ELECTRICAL DETAILS
EG-601 - FACILITY GROUNDING ONE-LINE DIAGRAM
006ED601 - BLDG 006 - EXISTING ONE-LINE DIAGRAM
016ED601 - BLDG 016 - EXISTING ONE-LINE DIAGRAM
100ED601 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 1 OF 21)
100ED602 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 2 OF 21)
100ED603 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 3 OF 21)
100ED604 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 4 OF 21)
100ED605 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 5 OF 21)
100ED606 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 6 OF 21)
100ED607 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 7 OF 21)
100ED608 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 8 OF 21)
100ED609 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 9 OF 21)
100ED610 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 10 OF 21)
100ED611 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 11 OF 21)
100ED612 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 12 OF 21)
100ED613 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 13 OF 21)
100ED614 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 14 OF 21)
100ED615 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 15 OF 21)
100ED616 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 16 OF 21)
100ED617 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 17 OF 21)
100ED618 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 18 OF 21)
100ED619 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 19 OF 21)
100ED620 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 20 OF 21)
100ED621 - BLDG 100 - EXISTING ONE-LINE DIAGRAM (PART 21 OF 21)
101ED601 - BLDG 101 - EXISTING ONE-LINE DIAGRAM (PART 1 OF 5)
101ED602 - BLDG 101 - EXISTING ONE-LINE DIAGRAM (PART 2 OF 5)
101ED603 - BLDG 101 - EXISTING ONE-LINE DIAGRAM (PART 3 OF 5)
101ED604 - BLDG 101 - EXISTING ONE-LINE DIAGRAM (PART 4 OF 5)
101ED605 - BLDG 101 - EXISTING ONE-LINE DIAGRAM (PART 5 OF 5)
102ED601 - BLDG 102 - EXISTING ONE-LINE DIAGRAM
103ED601 - BLDG 103 - EXISTING ONE-LINE DIAGRAM (PART 1 OF 4)
103ED602 - BLDG 103 - EXISTING ONE-LINE DIAGRAM (PART 2 OF 4)
103ED603 - BLDG 103 - EXISTING ONE-LINE DIAGRAM (PART 3 OF 4)
103ED604 - BLDG 103 - EXISTING ONE-LINE DIAGRAM (PART 4 OF 4)
104ED601 - BDLG 104 - EXISTING ONE-LINE DIAGRAM (PART 1 OF 2)
104ED602 - BLDG 104 - EXISTING ONE-LINE DIAGRAM (PART 2 OF 2)
105ED601 - BLDG 105 - EXISTING ONE-LINE DIAGRAM
006EP601 - BLDG 006 - REVISED ONE-LINE DIAGRAM
016EP601 - BLDG 016 - REVISED ONE-LINE DIAGRAM
100EP601 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 1 OF 21)
100EP602 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 2 OF 21)
100EP603 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 3 OF 21)
100EP604 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 4 OF 21)
100EP605 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 5 OF 21)
100EP606 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 6 OF 21)
100EP607 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 7 OF 21)
100EP608 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 8 OF 21)
100EP609 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 9 OF 21)
100EP610 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 10 OF 21)
100EP611 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 11 OF 21)
100EP612 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 12 OF 21)
100EP613 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 13 OF 21)
100EP614 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 14 OF 21)
100EP615 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 15 OF 21)
100EP616 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 16 OF 21)
100EP617 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 17 OF 21)
100EP618 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 18 OF 21)
100EP619 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 19 OF 21)
100EP620 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 20 OF 21)
100EP621 - BLDG 100 - REVISED ONE-LINE DIAGRAM (PART 21 OF 21)
101EP601 - BLDG 101 - REVISED ONE-LINE DIAGRAM (PART 1 OF 5)
101EP602 - BLDG 101 - REVISED ONE-LINE DIAGRAM (PART 2 OF 5)
101EP603 - BLDG 101 - REVISED ONE-LINE DIAGRAM (PART 3 OF 5)
101EP604 - BLDG 101 - REVISED ONE-LINE DIAGRAM (PART 4 OF 5)
101EP605 - BLDG 101 - REVISED ONE-LINE DIAGRAM (PART 5 OF 5)
102EP601 - BLDG 102 - REVISED ONE-LINE DIAGRAM
103EP601 - BLDG 103 - REVISED ONE-LINE DIAGRAM (PART 1 OF 4)
103EP602 - BLDG 103 - REVISED ONE-LINE DIAGRAM (PART 2 OF 4)
103EP603 - BLDG 103 - REVISED ONE-LINE DIAGRAM (PART 3 OF 4)
103EP604 - BLDG 103 - REVISED ONE-LINE DIAGRAM (PART 4 OF 4)
104EP601 - BDLG 104 - REVISED ONE-LINE DIAGRAM (PART 1 OF 2)
104EP602 - BLDG 104 - REVISED ONE-LINE DIAGRAM (PART 2 OF 2)
105EP601 - BLDG 105 - REVISED ONE-LINE DIAGRAM
006EP701 - BUILDING 6 ELECTRICAL SCHEDULES
016EP701 - BUILDING 16 ELECTRICAL SCHEDULES
100EP701 - BUILDING 100 ELECTRICAL SCHEDULES
100EP702 - BUILDING 100 ELECTRICAL SCHEDULES
100EP703 - BUILDING 100 ELECTRICAL SCHEDULES
100EP704 - BUILDING 100 ELECTRICAL SCHEDULES
100EP705 - BUILDING 100 ELECTRICAL SCHEDULES
100EP706 - BUILDING 100 ELECTRICAL SCHEDULES
100EP707 - BUILDING 100 ELECTRICAL SCHEDULES
100EP708 - BUILDING 100 ELECTRICAL SCHEDULES
100EP709 - BUILDING 100 ELECTRICAL SCHEDULES
100EP710 - BUILDING 100 ELECTRICAL SCHEDULES
101EP701 - BUILDING 101 ELECTRICAL SCHEDULES
102EP701 - BUILDING 102 ELECTRICAL SCHEDULES
103EP701 - BUILDING 103 ELECTRICAL SCHEDULES
103EP702 - BUILDING 103 ELECTRICAL SCHEDULES
104EP701 - BUILDING 104 ELECTRICAL SCHEDULES
105EP701 - BUILDING 105 ELECTRICAL SCHEDULES
105EP702 - BUILDING 105 ELECTRICAL SCHEDULES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
SHEET INDEX AND PHASING
NARRATIVE
P R O J E C T P H A S I N G N A R R A T I V E
PRIOR TO COMMENCING WORK, CONTRACTOR SHALL SUBMIT A DETAILED CONSTRUCTION PHASING PLAN FOR EACH PHASE EXPLAINED BELOW TO VA FOR REVIEW AND APPROVAL; VA SHALL HAVE 30-DAYS TO REVIEW AND APPROVE EACH PHASING NARRATIVE. PHASING SHALL BE PLANNED TO MINIMIZE DOWNTIME AND IMPACT TO FACILITY OPERATION. PHASING PLAN SHALL INCLUDE ANY ANTICIPATED SHUTDOWNS AND TEMPORARY POWER PROVISIONS. ALL WORK SHALL BE CONDUCTED AFTER-HOURS, UNLESS DIRECTED OTHERWISE BY VA; REFERENCE "PROJECT WORK HOURS" SECTION ON SHEET G-001 FOR EXACT WORKING HOUR REQUIREMENTS.
GENERAL PROJECT CONSTRUCTION SEQUENCING SHALL BE IMPLEMENTED AS FOLLOWS:
1. BUILDING 100: PROVIDE POWER DISTRIBUTION EQUIPMENT FOR DELAYED EQUIPMENT AUTOMATIC TRANSFER SWITCHES; DISTRIBUTION EQUIPMENT INCLUDES MV INTERRUPTER SWITCHES, MV DRY-TYPE
TRANSFORMER, AND DISTRIBUTION SWITCHBOARD.
2. BUILDINGS 100, 101, 103: REPLACE ALL MV “OLD SWITCHGEAR” AND UNIT SUBSTATION CIRCUIT BREAKERS. NOTE - SHUTDOWNS WILL BE REQUIRED FOR EACH MV AND LV SWITCHGEAR LINEUP. UL FIELD RE-CERTIFICATION IS REQUIRED FOR ALL SWITCHGEAR. ALL EXISTING BREAKERS BEING REPLACED SHALL BE PROVIDED TO THE CONTRACTOR AND THE VALUE OF THE CIRCUIT BREAKERS SHALL BE CREDITED BACK
TO VA.
3. BUILDINGS 100: PROVIDE ACTIVE HARMONIC FILTERS AT UNIT SUBSTATIONS “USNW”, “USS2”, “USCP”, AND “USCL” TO PROVIDE HARMONIC MITIGATION AND UNITY POWER FACTOR CORRECT. NOTE - INSTALLATION OF THE FILTER FEEDER CIRCUIT BREAKERS SHALL BE COORDINATED AND CONDUCTED DURING PROJECT PHASE 2 ABOVE.
4. BUILDING 100: REPLACE MV RING LOOP FEEDER FROM MV OLD SWITCHGEAR TO UNIT SUBSTATION “USNW”. NOTE - SHUTDOWN WILL BE REQUIRED; COORDINATE WITH PROJECT PHASE 2 ABOVE.
5. ALL BUILDINGS WITHIN SCOPE: REPLACE, MODIFY, OR UPGRADE EXISTING ELECTRICAL POWER DISTRIBUTION EQUIPMENT TO PROVIDE CORRECTIONS PER WILEY-WILSON ARC-FLASH REPORT. NOTE - VARIOUS SHUTDOWNS WILL BE REQUIRED; COORDINATE WITH VA AS REQUIRED. SOME EQUIPMENT WILL REQUIRED UL FIELD RE-CERTIFICATION.
6. BUILDING 16: REPLACE MAIN ELECTRICAL DISTRIBUTION EQUIPMENT. NOTE - A BUILDING SHUTDOWN WILL BE REQUIRED.
7. BUILDING 105: RENOVATE EXISTING BLDG 105; PROVIDE MODULAR BUILDING “ELECTRICAL ROOM” TO HOUSE ELECTRICAL DISTRIBUTION EQUIPMENT AND VFDs FOR BLDG 105 AND COOLING TOWERS. NOTE - WORK SHALL BE PERFORMED DURING WINTER MONTHS (NOVEMBER - FEBRUARY) TO AVOID THE NEED OF BUILDING COOLING WHILE COOLING TOWERS ARE OFF-LINE.
8. ONCE THE ABOVE PROJECT PHASES ARE COMPLETE, A FACILITY WIDE ARC-FLASH HAZARD RISK ASSESSMENT WITH REPORT AND LABELING SHALL BE PERFORMED IN ACCORDANCE WITH SPECIFICATION 26 05 73.
9. CONSTRUCTION TASKS THAT MAY BE CONDUCTED AT ANY TIME (VA APPROVAL STILL REQUIRED):
A. BUILDING 6, 16, 100, 101, 102, 103, 104, 105 AND 108 (PARKING GARAGE): FACILITY WIDE GROUND RESISTANCE TESTING PER VHA DIRECTIVE 1028-8.J(6)(e).
B. BUILDINGS 100, 101, 103: LS & CRITICAL AUTOMATIC TRANSFER SWITCHES POWER METER AND COMMUNICATION MODULE UPGRADES (7 ATSs TOTAL).
C. BUILDINGS 100, 101, 103: PROVIDE SPARE CIRCUIT BREAKERS FOR MV AND UNIT SUBSTATION SWITCHGEAR.
D. BUILDING 100: REPLACE EMERGENCY GENERATOR CONTROL PANEL ELECTRONICS WITHIN GENERATOR MASTER CONTROL PANEL AND PROVIDE REDUNDANT PLC CPU WITHIN OHSU CONTROL PANEL; PROVIDE
PROGRAMMING AS REQUIRED.
G-003
A B B R E V I A T I O N S G E N E R A L N O T E S
1. THESE "GENERAL NOTES" SHALL APPLY TO ALL DRAWINGS WITHIN THIS DRAWING SET.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE ACCEPTANCE OF THE OWNER.
3. DRAWING AND TEXT SHOWN IN BLACK SHALL INDICATE CONTRACTOR PROVIDED/MODIFIED EQUIPMENT AND WORK REQUIRED. DRAWINGS AND TEXT SHOWN IN
GRAY SHALL BE ASSUMED EXISTING.
4. EXISTING CIRCUITS ASSOCIATED WITH THE PROJECT AREA OF WORK ARE TO BE DE-ENERGIZED DURING CONSTRUCTION.
5. ALL ELECTRICAL WORK SHALL BE COMPLETED WITH ALL PROXIMATE ELECTRICAL CIRCUITS DE-ENERGIZED (i.e. A NEW BREAKER OR CIRCUIT CANNOT BE ADDED TO A PANEL UNLESS THE PANEL IS COMPLETELY DE-ENERGIZED), OR THE CONTRACTOR MUST COMPLY WITH NFPA 70E FOR WORK ON ENERGIZED SERVICE. THE VA WILL DETERMINE IF THE ELECTRICAL SERVICE CAN BE SHUT DOWN OR IT WILL HAVE TO BE WORKED HOT DEPENDING ON THE CRITICALITY OF THE AREA BEING AFFECTED. IF THE WORK MUST BE DONE WITH THE SERVICE LIVE, THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL REQUIRED PROTECTIVE TOOLS, EQUIPMENT, AND CLOTHING, AND MUST FOLLOW THE JOB SPECIFIC WORK PLAN PREPARED BY THE CONTRACTOR AND APPROVED BY THE VA. WORK THAT REQUIRES SHUTTING DOWN ELECTRICAL SERVICE MAY HAVE TO BE ACCOMPLISHED DURING OTHER THAN NORMAL DUTY HOURS.
6. PROVIDE RACEWAYS AND CONDUCTORS/CABLING FROM LUMINAIRES TO THEIR CORRESPONDING CONTROL DEVICES AS INDICATED ON PLANS.
7. LUMINAIRE INSTALLATIONS AND LAYOUTS SHALL BE COORDINATED WITH ALL OBSTACLES, EQUIPMENT AND ARCHITECTURAL FEATURES.
8. WHERE NOT SPECIFICALLY INDICATED ON DRAWINGS, BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG MINIMUM FOR RUNS EQUAL TO OR LESS THAN 65 FEET AND 10 AWG MINIMUM FOR RUNS GREATER THAN 65 FEET. RACEWAYS AND CONDUCTORS SHALL BE SIZED AND QUANTIFIED TO SERVE AND CONTROL APPLICABLE EQUIPMENT WITH VOLTAGE DROP NO GREATER THAN THREE PERCENT. CONDUCTOR SIZE SHALL BE INCREASED TO COMPENSATE FOR DERATING REQUIRED PER NEC 310.15 WHERE MORE THAN THREE CURRENT CARRYING CONDUCTORS WITHIN ONE RACEWAY; CONDUCTOR AMPACITIES SHALL BE TAKEN
FROM THE 75°C COLUMN. INDIVIDUAL CIRCUITS SHALL NOT SHARE NEUTRAL CONDUCTORS.
9. MINIMUM CONDUIT SIZE SHALL BE 1" FOR EXTERIOR AND UNDERGROUND CONDUIT. MINIMUM CONDUIT SIZE SHALL BE 3/4" FOR INTERIOR CONDUIT. ADDITIONAL CONDUCTORS FOR UNSWITCHED HOT CONDUCTOR TO LUMINIARES WITH EMERGENCY BATTERY POWERED BACKUP UNITS OR TRANSFER DEVICES SHALL BE PROVIDED. ALL CONDUIT SHALL BE CONCEALED. THE ABOVE COMMENTS SHALL BE ADHERED TO UNLESS OTHERWISE NOTED ON THE DRAWINGS.
10. EMERGENCY LIGHTING OR EQUIPMENT CIRCUITS SHALL BE ROUTED INDEPENDENT FROM OTHER CIRCUIT TYPES; ENSURE NEC 700.10 REQUIREMENTS ARE MET.
11. PROVIDE ALL CONDUIT AND WIRE FOR ALL CIRCUITS INDICATED AND/OR NOTED ON THE DRAWINGS AND/OR SPECIFICATIONS. ALL AUXILIARY OR REQUIRED APPURTENANCES FOR PROVIDED EQUIPMENT SHALL BE PROVIDED WITH ALL CONNECTIONS AS REQUIRED.
12. ALL EQUIPMENT AND DEVICES INCLUDING, BUT NOT LIMITED TO, ELECTRICAL DISTRIBUTION EQUIPMENT, RECEPTACLES, DATA OUTLETS, AND SPECIAL SYSTEM DEVICES, SHALL HAVE THEIR EXACT LOCATION COORDINATED WITH ARCHITECTURAL DRAWINGS AND ALL TRADES PRIOR TO COMMENCING WORK.
13. COORDINATE WITH LIGHTING MANUFACTURER FOR ALL LIGHTING CONTROL EQUIPMENT AND APPURTENANCES; PROVIDE ANY ADDITIONAL SENSORS TO PROVIDE FULL COVERAGE OF THE SPACE AS REQUIRED. ALL CONDUIT, WIRE, POWER SUPPLIES, AND APPURTENANCES REQUIRED FOR THE LIGHTING CONTROL SYSTEM
SHALL BE PROVIDED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
14. ALL EXTERIOR MOUNTED RECEPTACLES AND LUMINAIRE INSTALLATIONS SHALL COORDINATE EXACT LOCATIONS WITH ARCHITECTURAL SHEETS. ADDITIONALLY, WHERE MASONRY IS USED, SMOOTH BLOCK SHALL BE UTILIZED TO PROVIDE A PROPER MOUNTING SURFACE TO ALL EQUIPMENT; RECEPTACLES SHALL BE
INSTALLED FLUSH.
15. ALL CONDUIT/SLEEVE FLOOR AND WALL PENETRATIONS SHALL BE SEALED WITH FIRE RATED ASSEMBLIES, CAULKING, AND APPURTENANCES. ELECTRICAL BOXES
LOCATED IN FIRE RATED WALLS SHALL BE RATED FOR USE IN FIRE RATED WALLS.
16. ALL EQUIPMENT AND INSTALLATION METHODS SHALL BE LISTED AND LABELED PER NEC, UL LISTED, OR REVIEWED EQUAL.
17. FOR ALL EQUIPMENT, COORDINATE WITH ALL TRADES (ARCHITECTURAL, MECHANICAL, PLUMBING, ETC) FOR ELECTRICAL REQUIREMENTS AND INSTALLATION
LOCATIONS PRIOR TO INSTALLATION.
18. ALL LOW-VOLTAGE SYSTEM CABLING NOT RAN IN CONDUIT TO WALL MOUNTED DEVICE SHALL HAVE A MINIMUM 1"C ROUTED FROM DEVICE THROUGH WALL INTO THE ACCESSIBLE CEILING SPACE; CABLING SHALL NOT BE ROUTED IN WALLS OR IN AN INACCESSIBLE LOCATION WITHOUT CONDUIT.
19. GFCI RECEPTACLES SHALL BE PROVIDED WITHIN 6' OF A SINK/OR WATER SOURCE, WITHIN DAMP ROOMS, OR WHEN MOUNTED OUTDOORS/EXTERIOR TO THE
BUILDING.
20. NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED, OR NOTCHED WITHOUT PRIOR WRITTEN CONSENT FROM THE STRUCTURAL ENGINEER OR ARCHITECT.
21. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.
22. LIGHTING FIXTURES WITH MORE THAN TWO LAMPS SHALL HAVE TWO OUTER LAMPS CONTROLLED WITH ONE SWITCH AND INNER LAMP(S) CONTROLLED BY A
SECOND SWITCH.
23. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC TABLE 250.122. ALL WIRING IS BASED ON CU COPPER PER NEC TABLE 310.15(B)(16), USING 75°C AMPACITIES
FOR FEEDERS.
24. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN
DEVICES.
25. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES, CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND
REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.
26. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.
27. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.
28. ALL AFFECTED AREAS THAT REQUIRE THE REPLACEMENT OF CEILING TILES AT THE END OF EACH SHIFT FOR WORK AREAS OUTSIDE OF A RATED CONSTRUCTION BARRIER. IF THE TILES CANNOT BE REPLACED, THE SPRINKLER SYSTEM MAY BE CONSIDERED OUT OF SERVICE IN THESE AREAS AND 1-HOUR FIRE RATED SEPARATION WILL BE REQUIRED BETWEEN THE CONSTRUCTION AREA AND THE OCCUPIED PORTIONS OF THE BUILDING.
29. WHERE FEEDERS EXTEND FROM FLOOR TO FLOOR, CONTRACTOR SHALL UTILIZE INTERSITIAL SPACE FOR ROUTING NEW FEEDER UNLESS OTHERWISE NOTED.
COORDINATE ALL ROUTING WITH EXISTING CONDITIONS AS REQUIRED.
30. EXISTING CAMPUS WIDE METERING / SCADA SYSTEM IS COMPRISED OF SCHNEIDER-ELECTRIC POWER METERS AND PME SOFTWARE. ALL NEW POWER METERS SHALL BE SCHNEIDER-ELECTRIC POWER METERS TO MATCH CAMPUS INSTALLED BASE AND SHALL INTEGRATE INTO EXISTING PME POWER METERING SYSTEM.
ADDITIONAL DATA TO BE ADDED TO EXISTING PME NETWORK IS AS FOLLOWS: ALL NEW POWER METERS, ATS COMMUNICATION MODULES, AND ACTIVE HARMONIC FILTER DATA. EXISTING FACILITY PME HEADEND/SERVER IS LOCATED IN BUILDING 100, ROOM B2D-112b; ALL DATA SHALL BE TRANSMITTED TO SERVER EITHER DIRECTLY VIA PHYSICAL CONNECTION OR BY USING EXISTING NETWORK INFRASTRUCTURE. ALL EQUIPMENT, COMPONENTS, CONNECTIONS, INTEGRATION, AND PROGRAMMING REQUIRED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM SHALL BE PROVIDED.
1PH
1P 2/C 3/C
3PH
4/C 4W A/C A/E
AAP
AC
ACC
ADDL
ADJ
AF
AFC
AFCI
AFF
AFG
Ah
AHJ
AIC
ALT
AMB
AMP
ARCH
ASC
AT
ATS
AUTO
AV
BAT
BD
BFF
BLDG
BRKR
BYP
C
CAB
CALC
CAP
CAT
CATV
CCR
CCTV
cd
CD
CF
CF/CI
CF/OI
CFE
CHW
CHWP
CKT
C/B
CLF
CLG
COAX
COMM
COMPT
CONC
CONT
CONTR
COORD
CPT
CRI
CT
CTV
CU
CUR
dB
DC
DCP
DEG C
DEG F
DEMO
DIAG
DISC
DMR SW
DPDT
DPST
DRSW
DS
DWG
EL
ELEC
ELEV
EMER/EM
EMI
EMT
CL
CO
DDC
EC
EN
SINGLE-PHASE
SINGLE POLE
TWO-CONDUCTOR
THREE-CONDUCTOR
THREE-PHASE
FOUR-CONDUCTOR
FOUR-WIRE
AIR CONDITIONING UNIT
ARCHITECT/ENGINEER
ALARM ANNUNCIATOR PANEL
ALTERNATING CURRENT OR ARMORED CABLE
ACCESSIBLE
ADDITIONAL
ADJACENT, ADJOINING
AMPERE FRAME OR AMP FUSE
ABOVE FINISHED COUNTER, AUTOMATIC
ARC-FAULT CURRENT INTERRUPTER
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AMPERE HOUR
AUTHORITY HAVING JURISDICTION
AMPERE INTERRUPTING CAPACITY
ALTERNATE
AMBIENT
AMPERE
ARCHITECT
AMPS SHORT CIRCUIT
AMPERE TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AUDIO VISUAL
BATTERY
BOARD
BELOW FINISH FLOOR
BUILDING
BREAKER
BY PASS
CONDUIT
CABINET
CALCULATE
CAPACITY
CATALOG
COMMUNITY ANTENNA TELEVISION
CONTROL CONTACTOR
CLOSED CIRCUIT TELEVISION
CANDELA
CONSTRUCTION DOCUMENTS
CONTRACTOR FURNISHED
CONTRACTOR FURNISHED/
CONTRACTOR FURNISHED/
CONTRACTOR FURNISHED EQUIPMENT
CHILLED WATER
CHILLED WATER PUMP
CIRCUIT
CIRCUIT BREAKER
CURRENT LIMITING FUSE
CEILING
COAX CABLE
COMMUNICATION
COMPARTMENT
CONCRETE
CONTINUE
CONTRACTOR
COORDINATE
CONTROL POWER TRANSFORMER
COLOR RENDERING INDEX
CURRENT TRANSFORMER
CABLE TELEVISION
COPPER
CURRENT
DECIBEL
DIRECT CURRENT
DIMMER CONTROL PANEL
DEGREES CELSIUS
DEGREES FAHRENHEIT
DEMOLITION
DIAGRAM
DISCONNECT
DISTRIBUTION PANEL
DIMMER SWITCH
DOUBLE POLE, DOUBLE THROW
DOUBLE POLE, SINGLE THROW
DOOR SWITCH
DISCONNECT SWITCH
DRAWING
ELEVATION OR EXISTING TO
ELECTRIC OR ELECTRICAL
ELEVATOR
EMERGENCY
ELECTROMAGNETIC INTERFERENCE
ELECTRICAL METALLIC TUBING
CONNECTOR LIGHTING
CONDUIT ONLY
DIRECT DIGITAL CONTROLS
ELECTRICAL CONTRACTOR
EXISTING IN NEW LOCATION
FREQUENCY CONTROL, OR AVAILABLE
FAULT CURRENT
CONTRACTOR INSTALLED
OWNER INSTALLED
BE RELOCATED
ESMT
EWC
EWH
EXIST(E)
FA
FAAP
FACP
FC
FIXT
FLA
FLUOR
FP
FT
FU SW
FVNR
FVR
G
GEN
HID
HOA
HP
HT
HZ
IESNA
IMC
INCAND
IR
IWH
J-BOX
kV kVA kVAh kVAR kW kWh kWhM
LED
LF
LP
LPS
LRA
LT
LTG
LTG PNL
LTNG
LV
MAX
MC
MCA
MCB
MCC
MECH
MH
MIN
MOCP
MLO
MT
MTD
MTG
MTS
MV
MVA
MW
NA
NC
NEC
NEMA
NEUT, N
NFPA
NIC
NL
NO
NTS
OC
OD
OL
P
FCIO
ER
FOIC
GFCI
IG
HTR
LCP
MDP
MS
NAC
NFC
OH
OS
GND
GFP
ENCL
EPO
EPRF
ENCLOSURE
EMERGENCY POWER OFF
EXPLOSION PROOF
EASEMENT
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
EXISTING
FIRE ALARM
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FOOTCANDLE
FIXTURE
FULL LOAD AMPS
FLUORESCENT
FIRE PROTECTION
FEET OR FOOT
FUSED SWITCH
FULL VOLTAGE NON-REVERSING
FULL VOLTAGE REVERSING
ELECTRICAL GROUND
GENERATOR
HIGH INTENSITY DISCHARGE
HAND-OFF-AUTOMATIC
HORSEPOWER
HEIGHT
HERTZ
ILLUMINATION ENGINEERING
INTERMEDIATE METAL CONDUIT
INCANDESCENT
INFRARED
INSTANTANEOUS WATER HEATER
JUNCTION BOX
KILOVOLT
KILOVOLT AMPERE
KILOVOLT AMPERE PER HOUR
KILOVOLT AMPERE REACTIVE
KILOWATT
KILOWATT HOUR
KILOWATT HOUR METER
LIGHT EMITTING DIODE
LINEAR FEET (FOOT)
LIGHT POLE
LOW PRESSURE SODIUM
LOCKED ROTOR AMPS
LIGHT
LIGHTING
LIGHTING PANEL
LIGHTNING
LOW VOLTAGE
MAXIMUM
METAL-CLAD
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MECHANICAL
MANHOLE
MINIMUM
MAXIMUM OVERCURRENT PROTECTION
MAIN LUGS ONLY
MOUNT
MOUNTED
MOUNTING
MANUAL TRANSFER SWITCH
MEDIUM VOLTAGE
MEGAVOLT-AMPERE
MEGAWATT
NOT APPLICABLE
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL
NEUTRAL
NATIONAL FIRE PROTECTION ASSOCIATION
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
ON CENTER
OUTSIDE DIAMETER
OVERLOAD
POLE
NOT FOR CONSTRUCTION
OVERHEAD
OCCUPANCY SENSOR
ANOTIFICATION APPLIANCE CABINET
MOTOR STARTER
MAIN DISTRIBUTION PANEL
LIGHTING CONTROL PANEL
SOCIETY OF NORTH AMERICA
ISOLATED GROUND
HEATER
GROUND
GROUND FAULT PROTECTION
GROUND FAULT
CIRCUIT INTERRUPTER
FURNISHED BY CONTRACTOR,
FURNISHED BY OWNER,
INSTALLED BY CONTRACTOR
INSTALLED BY OWNER
EXISTING TO REMAIN
MANUFACTURERS ASSOCIATION
PB
PEC
PED
PEND
PF
PH
PNL
PT
PVC
PWR
RCP
REC
RECPT
RM
RMS
REQD
SCC
SD
SF
SHT
SPEC
SPST
SURF
SW
SWBD OR SB
SWGR OR SG
TEL
TV
TYP
UFD
UGND
UL
UON
UPS
V
VA
VAR
VFD
VOLT
W
WH
WP/W
XFER
XF/XFMR
UTIL
PIV
PS
R
RMC
SAC
SI
SPD
SM
TR
PULL BOX
PHOTOELECTRIC CELL
PEDESTAL
PENDANT
POWER FACTOR
PHASE
PANEL
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE (PLASTIC)
POWER
REFLECTED CEILING PLAN
RECESSED
RECEPTACLE
ROOM
ROOT MEAN SQUARE
REQUIRED
SHORT CIRCUIT CAPACITY
SMOKE DETECTOR
SQUARE FOOT (FEET)
SHEET
SPECIFICATION
SINGLE POLE, SINGLE THROW
SURFACE
SWITCH
SWITCHBOARD
SWITCHGEAR
TELEPHONE
TELEVISION
TYPICAL
UNDERFLOOR DUCT
UNDERGROUND
UNDERWRITERS LABORATORY
UNLESS OTHERWISE NOTED
UNINTERRUPTIBLE POWER
VOLT
VOLT AMPERE
VOLT AMPERE REACTIVE
VARIABLE FREQUENCY DRIVE
VOLTAGE
WATT/WEATHERPROOF
WATER HEATER
WEATHERPROOF
TRANSFER
TRANSFORMER
(WHILE IN USE)
UTILITY
POST INDICATOR VALVE
POWER SUPPLY
EXISTING TO BE REMOVED
RIGID METAL CONDUIT
SMALL APPLIANCE CIRCUIT
INTERNATIONAL SYSTEM OF UNITS
SURGE PROTECTIVE DEVICE
SMART METER
TAMPER RESISTANT
POWER SUPPLY
DP
SECTION
SCALE
SECTION LETTER
SHEET WHERE SECTION
IS FROM TAKEN
SECTION LETTER
DETAIL NUMBER
SHEET ON WHICH DETAIL APPEARS
DETAIL AREA
CONDUIT AND WIRE TAG
(REFER TO CONDUIT AND WIRE SCHEDULE)
FAULT CURRENT TAG
(3 PH, SYM AMPS)
KEY NOTE
FIGURE OR PHOTO
DETAIL NUMBER
IF PHOTO, ARROW
DENOTES DIRECTION
TAKEN
SHEET WHERE DETAIL IS
TAKEN FROM CONDUIT &
WIRE TAG
DETAIL/PLAN NUMBERSHEET WHERE SECTION
IS FROM TAKEN
ABBREVIATIONS, GENERAL NOTES,
AND GENERAL SYMBOLS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
G E N E R A L S Y M B O L S
E-001
A
XXX
A
XXX
XXX
XXX
XXX
1 DETAIL/PLAN
XXX
C I R C U I T I N G D E S I G N A T I O N S
WHERE A PANEL NAME AND CORRESPONDING CIRCUIT ARE CALLED OUT ADJACENT TO A RECEPTACLE, LUMINAIRE, OR MISC LOAD, THAT LOAD SHALL BE CIRCUITED TO THE CORRESPONDING PANELBOARD CIRCUIT BREAKER. CONDUIT AND WIRE FOR CIRCUIT SHALL BE 3/4" CONDUIT WITH (2) 12 AWG AND (1) 12 AWG GND, UNLESS OTHERWISE NOTED; IF FURTHER THAN 70', PHASE AND GROUND WIRE SHALL BE UPSIZED TO 10 AWG TO ACCOUNT FOR VOLTAGE DROP.
SEE EXAMPLES BELOW:
RECEPTACLE:
PANELBOARD OR POWER SOURCE NAME = "P1"
CIRCUIT NUMBER OF POWER SOURCE = "2"
LUMINAIRE:
PANELBOARD OR POWER SOURCE NAME = "PP3"
CIRCUIT NUMBER OF POWER SOURCE = "4"
TYP LUMINIARE TAG NAME, REFERENCE LUMINAIRE SCHEDULE = "L1"
LIGHTING CONTROL SWITCH LEG = "a"
ALL LUMINAIRES IN SAME ROOM ARE CIRCUITED TO SAME CIRCUIT = PP3-4
MISC LOAD:
PANELBOARD OR POWER SOURCE NAME = "PP"
CIRCUIT NUMBER OF POWER SOURCE = "7"
P1-2 2
PNL-P1
HEAT PUMP
PP-7
L1 a
PP3-4
FACP
PP-7
P1-2
EXISTING CAMPUS WIDE METERING / SCADA SYSTEM IS COMPRISED OF SCHNEIDER-ELECTRIC POWER METERS AND PME SOFTWARE. ALL NEW POWER METERS SHALL BE SCHNEIDER-ELECTRIC POWER METERS TO MATCH CAMPUS INSTALLED BASE AND SHALL INTEGRATE INTO EXISTING PME POWER METERING SYSTEM.
ADDITIONAL DATA TO BE ADDED TO EXISTING PME NETWORK IS AS FOLLOWS: ALL NEW POWER METERS, UNIT SUBSTATION REPLACEMENT CIRCUIT BREAKER DATA, ATS COMMUNICATION MODULES, AND ACTIVE HARMONIC FILTER DATA. EXISTING FACILITY PME HEADEND/SERVER IS LOCATED IN BUILDING 100, ROOM B2D-112b; ALL DATA SHALL BE TRANSMITTED TO SERVER EITHER DIRECTLY VIA PHYSICAL CONNECTION OR BY USING EXISTING NETWORK INFRASTRUCTURE. ALL EQUIPMENT, COMPONENTS, CONNECTIONS, INTEGRATION, AND PROGRAMMING REQUIRED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM SHALL BE
PROVIDED.
31.
32.
CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL FEEDERS WHERE FEEDER RUNS EXCEED 250FT OR HAVE MORE THAN 270 DEGREES OF TOTAL BEND.
PULL BOX PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE PULL BOX LOCATIONS WITH ALL OBSTRUCTIONS, TRADES, AND VA AS REQUIRED.
SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH
ARCHITECTURAL DRAWINGS AS REQUIRED.
ALL INTERIOR AREAS TO HAVE MANUAL 0N/AUTO OFF LIGHTING
CONTROL WITH THE USE OF DUAL TECHNOLOGY OCCUPANCY SENSORS.
EXCEPT WHERE A WALL SWITCH OCCUPANCY SENSOR IS NOTED.
OS
PHOTO ELECTRIC SENSOR
DAYLIGHT SENSOR FOR DAYLIGHT HARVESTING
CONTROL. SENSOR SHALL BE CEILING MOUNTED.
PE
DS
SWITCH, MULTIPOSITION
SWITCH, SINGLE BREAK
FUSE WITH RATING
NORMALLY CLOSED RELAY CONTACT
NORMALLY OPEN RELAY CONTACT
CIRCUIT BREAKER
DRAWOUT AIR CIRCUIT BREAKER
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
DELTA CONNECTION
TRANSFORMER
JUNCTION BOX
PULL BOX
GENERATOR, POWER
BATTERY
CAPACITOR
MEDIUM VOLTAGE CIRCUIT BREAKER
DISCONNECT SWITCH
METER
AMMETER
VOLTMETER
WATTMETER
WATT-HOUR METER
JUNCTION BOX
TRANSFORMER, PLAN
MOTOR
WYE CONNECTION
EARTH GROUND
LADDER CABLE TRAY
PULL BOX
RECEPTACLE, DUPLEX
RECEPTACLE, DUPLEX ON EMERGENCY POWER
RECEPTACLE, DUPLEX WITH GROUND FAULT
CIRCUIT INTERRUPTER
RECEPTACLE, QUADRUPLEX
RECEPTACLE, SINGLE
RECEPTACLE, SINGLE WITH SWITCH
RECEPTACLE, SPECIAL PURPOSE
A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.
B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.
C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.
D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.
E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.
F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.
G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.
H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.
RECEPTACLE, SWITCHED DUPLEX
DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,
GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN FLEXIBLE
CORD (CENTER LINE OF OUTLET: 6'-6" [1981mm] AFF. MINIMUM).
ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm]
CENTERS OR AS DESIGNATED ON DRAWINGS), MTD 3'-6"
[1067mm] AFF OR AS INDICATED.
SWITCH
F = FUSED SWITCH K = KEY OPERATED
L = LOCK LM= LOW VOLTAGE MASTER
M = MANUAL MOTOR STARTING MC= MOMENTARY CONTACT
MP= MOTOR SNAP WITH PILOT LIGHT P = WITH PILOT LIGHT
(THERMAL TYPE)
PB= PUSH BUTTON STATION RC= REMOTE CONTROL
WP= WEATHER PROOF X = EXPLOSION PROOF
SWITCH (# SUBSCRIPT AS INDICATED BELOW):
BLANK = SINGLE POLE 2 = DOUBLE POLE
3 = THREE-WAY 4 = FOUR-WAY
D = DIMMER K = KEY OPERATED
LV= LOW VOLTAGE P = WITH PILOT LIGHT
LM= LOW VOLTAGE MASTER RC= REMOTE CONTROL
PB= PUSH BUTTON STATION WP= WEATHER PROOF
T = TIMER OPERATED Mo= OCCUPANCY SENSOR
RECESSED DOWNLIGHT FIXTURE, LETTER
INDICATES TYPE.
LIGHT FIXTURE, RECESSED, 2'x4';
LETTER INDICATES TYPE.
LIGHT FIXTURE, RECESSED, 1'x4';
LETTER INDICATES TYPE.
LIGHT FIXTURE, RECESSED,1'x8';
LETTER INDICATES TYPE.
LIGHT FIXTURE, SURFACE MOUNTED,2'x4';
LETTER INDICATES TYPE.
LIGHT FIXTURE, SURFACE MOUNTED, 1'x4';
LETTER INDICATES TYPE.
LIGHT FIXTURE, SURFACE MOUNTED,(1'x8');
LETTER INDICATES TYPE.
LIGHT FIXTURE, EMERGENCY;
LETTER INDICATES TYPE.
LIGHTING, ONE HEAD EMERGENCY BATTERY POWER
STREET LIGHT WITH BRACKET
LIGHT POLE, ONE LUMINAIRE
LIGHT POLE, TWO LUMINAIRES
LIGHT POLE, POST TOP MOUNT LUMINAIRE
LIGHTING WALL PACK, EXTERIOR BUILDING
LIGHTING, TWO HEAD EMERGENCY BATTERY POWER
LIGHTING, THREE HEAD EMERGENCY BATTERY POWER
EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL
ARROWS AND FACES AS SHOWN
EXIT SIGN, CEILING MOUNTED WITH DIRECTIONAL
ARROWS AND FACES AS SHOWN
LIGHT FIXTURE, RECESSED,2'x2'; LETTER
INDICATES TYPE.
STRIP LIGHTING, 4' LONG
LIGHT FIXTURE, WALL MOUNTED
OUTLET, COMBINATION TELEPHONE/DATA COMMUNICATION
CABLE TELEVISION LINE = CATV
CLOSED CIRCUIT TELEVISION LINE = CCTV. MINIMUM 1" [25mm] CONDUIT
FIBEROPTICS LINE = FO
FLOOR RECEPTACLE, TELEPHONE
OUTLET TELEPHONE; LETTER INDICATES AS FOLLOWS:
J = JACK TYPE W = WALL TYPE
SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE ON LEGEND
SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE
ON LEGEND. MTD. 7'-6" [2286mm] AFF UNLESS OTHERWISE NOTED.
OUTLET DATA ONLY
TELEPHONE LINE = T
INTERCOM LINE = I. MINIMUM 3/4" [19mm] CONDUIT.
SOUND LINE = S
NURSE CALL LINE = NC. MINIMUM 3/4" [19mm] CONDUIT.
OUTLET; LETTER INDICATES AS FOLLOWS:
A = AUDIO V = VIDEO I = INTERCOM
RADIO CONDUIT RUN, MINIMUM 3/4" [19mm] CONDUIT.
RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" [1372mm] AFF UNLESS OTHERWISE NOTED.
SPEAKER PROGRAM SELECTOR SWITCH & VOLUME CONTROL
MTD. 4'-6" [1372mm] AFF UNLESS OTHERWISE NOTED.
OUTLET, TELEVISION
BLANK = 4 11/16" [119mm] MASTER ANTENNA OUTLET BOX W/BLANK
COVER, MTD. 18" [457mm] AFF UNLESS OTHERWISE NOTED.
C = CAMERA (CCTV SYSTEM), MTD 18" [457mm] AFF
M = MONITOR (CTTV SYSTEM).
NOTE:
FOR WHEELCHAIR PATIENT USE MOUNT TELEPHONE
OUTLET 36" [914mm] AFF TO BOTTOM OF OUTLET BOX.
DESK PHONES - MOUNT OUTLET 1'-6" [457mm] AFF
PAY PHONES - MOUNT OUTLET 4'-0" [1219mm] AFF
HEIGHT OF TELECART OUTLETS SHALL BE AS INDICATED
ON BEDWALLS OR PBPU DETAILS.
SEE VA BARRIER FREE DESIGN GUIDE PG-18-13.
TELEPHONE TERMINAL CABINET
TELEPHONE BACKBOARD (WALL MOUNTED)
3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD. 4'-6" [1372mm] AFF.
REMOTE DICTATING OUTLET MTD 1'-6" [457mm] AFF. UNLESS OTHERWISE NOTED.
INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL
OPERATION OF INSTRUMENT & TYPE REQUIRED).
INTERCOM STAFF STATION.
TELECOMMUNICATIONS MANHOLE
X
X
X
POWER
LIGHTING
DATA/COMMUNICATION
x = LUMINAIRE SWITCH ZONE (ANY LOWER CASE LETTER APPLIES)
ALARM, FIRE, COMMUNICATOR
ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:
FACC = CENTRAL CONSOLE FACP = CONTROL PANEL
MFACP= MASTER CONTROL PANEL FAAP = ANNUNCIATOR PANEL
ALARM, FIRE, MANUAL PULL STATION
ALARM, GONG
ALARM, HORN/LIGHT, ONE ASSEMBLY WITH CHIME
ALARM, HORN/LIGHT, SEPARATE ASSEMBLY
ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE
ALARM, MANUAL CONTROL
ALARM, MINI HORN
ALARM, SPRINKLER SYSTEM WATER FLOW BELL
ALARM, TAMPER SWITCH
DETECTION, GAS
DETECTION, SMOKE CONTROL AND PRESSURE PANEL
DETECTION SWITCH, ABORT
DETECTION SWITCH, VALVE TAMPER
DETECTOR, FLAME FLICKER
DETECTOR, FLOW SWITCH
DETECTOR, HEAT
DETECTOR, HEAT; LETTER INDICATES AS FOLLOWS:
R/T = COMBINATION F = FIXED TEMPERATURE RISE
R/C = RATE COMPENSATION R = RATE OF
DETECTOR; LETTER INDICATES AS FOLLOWS:
BLANK = SMOKE DETECTOR
H = HEAT SMOKE
I = IONIZATION SMOKE
P = PHOTOELECTRIC SMOKE
IH = IONIZATION AND HEAT SMOKE
IP = IONIZATION AND PHOTOELECTRIC SMOKE
PH = PHOTOELECTRIC AND HEAT SMOKE
IPH = IONIZATION, PHOTOELECTRIC, AND HEAT
DETECTOR, SMOKE, FOR DUCT
DETECTOR, SWITCH LEVEL
ALARM, FIRE; LETTERS INDICATE AS FOLLOWS:
BATT = BATTERIES CHR = CHARGER FAR = RECORDER
ALARM, FIRE, VALVE SUPERVISORY SWITCH.
ALARM, FIRE, TERMINAL CABINET.
ALARM, FIRE, POST INDICATOR VALVE.
ALARM, TRANSPONDER OR TRANSMITTER
ALARM, VOICE COMMUNICATION PANEL
FIRE ALARM STATION, MANUAL PULL
FIRE ALARM LINE = FA
ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET
CITY FIRE ALARM MASTER STATION MTD 5'-6" [1676mm] AFF UNLESS NOTED.
FIRE ALARM TRANSMITTER (BASE LOOP)…
This is the start of the file's text. The full file is on GovTribe.