Attachment 6-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 4.pdf

PDF 15 MB Posted

Attached to
Z2DA--CON-NRM 648-20-119 Correct Electrical FCA Deficiencies (Portland)
Solicitation number
36C26025R0071
Issued by

View the file

Other files

File Type Posted
36C26025R0071 0005.docx DOCX document
36C26025R0071 0004.docx DOCX document
F-103-1-TJC-Fire Life Safety - Bldg.103-1.pdf PDF
36C26025R0071 0003.pdf PDF
F-104-2-TJC-Fire Life Safety - Bldg.104-2.pdf PDF
F-104-P2-TJC-Fire Life Safety - Bldg.104-P2.pdf PDF
F-104-R-TJC-Fire Life Safety - Bldg.104-R.pdf PDF
36C26025R0071 0002.docx DOCX document
F-104-1-TJC-Fire Life Safety - Bldg.104-1.pdf PDF
F-104-P3-TJC-Fire Life Safety - Bldg.104-P3.pdf PDF
F-16-2-TJC-Fire Life Safety - Bldg.16-2.pdf PDF
F-6-2-TJC-Fire Life Safety - Bldg.6-2.pdf PDF
F-103-P3-TJC-Fire Life Safety - Bldg.103-P3.pdf PDF
F-103-P5-TJC-Fire Life Safety - Bldg.103-P5.pdf PDF
F-103-R-TJC-Fire Life Safety - Bldg.103-R.pdf PDF
F-6-3-TJC-Fire Life Safety - Bldg.6-3.pdf PDF
F-103-P4-TJC-Fire Life Safety - Bldg.103-P4.pdf PDF
F-16-B-TJC-Fire Life Safety - Bldg.16-B.pdf PDF
F-103-P2-TJC-Fire Life Safety - Bldg.103-P2.pdf PDF
36C26025R0071 0001.pdf PDF
F-16-R-TJC-Fire Life Safety - Bldg.16-R.pdf PDF
F-16-1-TJC-Fire Life Safety - Bldg.16-1.pdf PDF
F-103-2-TJC-Fire Life Safety - Bldg.103-2.pdf PDF
F-6-1-TJC-Fire Life Safety - Bldg.6-1.pdf PDF
Contractor sign in.pdf PDF
F-16-3-TJC-Fire Life Safety - Bldg.16-3.pdf PDF
Portland TJC Set Buildings 100 and 101.pdf PDF
36C26025R0071_2.docx DOCX document
Attachment 3-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 1.pdf PDF
Attachment 7-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 5.pdf PDF
Attachment 15-Past Performance Questionnaire.pdf PDF
Attachment 10-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 8.pdf PDF
Attachment 11-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 9.pdf PDF
Attachment 9-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 7.pdf PDF
Attachment 8-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 6.pdf PDF
Attachment 2-648-20-119-VA OR Portland Electrical FCA SPECS STAMPED.pdf PDF
Attachment 13-Price Schedule by Division.xlsx XLSX spreadsheet
Attachment 12-Wage Determination 7-11-2025.pdf PDF
Attachment 1-Statement of Work 648-20-119.pdf PDF
Attachment 4-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 2.pdf PDF
Attachment 14- VAAR 852.219-75.docx DOCX document
Attachment 5-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 3.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

288 SF

8D-149

ELECTRICAL

288 SF

8D-149

ELECTRICAL

SCALE : 1/2" = 1'-0"

1 BLDG 100 - RM 8D-149 - ENLARGED ELECTRICAL DEMOLITION PLAN

BLDG 100 - RM 8D-149 - ENLARGED

ELECTRICAL PLANS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PNL: 100_8L1-E-3 SEC 1

PNL: 100_8H1-E-3

BUSDUCT

FUSE MCC-N-8-G-3 (ABOVE)

FUSE PNL: 8H1-E-3 (BELOW)

PNL: 100_8DEL1-E-3

PNL: 100_8L1-E-3 SEC 2 TRANSFORMER T-69

PNL: 100_8CL1-E-3

0' 1' 2' 4'

100E-108

PROJECT

NORTH

SCALE : 1/2" = 1'-0"

2 BLDG 100 - RM 8D-149 - ENLARGED ELECTRICAL PLAN

PROJECT

NORTH

0' 1' 2' 4'

100E-108

PNL: 100_8L1-E-3 SEC 1

PNL: 100_8H1-E-3

BUSDUCT

FUSE MCC-N-8-G-3 (ABOVE)

FUSE PNL: 8H1-E-3 (BELOW)

PNL: 100_8DEL1-E-3

PNL: 100_8L1-E-3 SEC 2 TRANSFORMER T-69

PNL: 100_8CL1-E-3

TRANSFORMER

"100_8DEL1-E-3"

CONTINUE FROM PANEL "100_9DEH1-E-3"

SEE SHEET 100E-409

CONTINUE FROM

SHEET 100E-409 TO

SHEET 100E-407b

100-P-44A

100-P-44B

100E-408

PROJECT

NORTH

GENERAL NOTES

KEY NOTES

EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE

ONE-LINE DIAGRAMS ON SHEETS 100ED613 & 100EP613

FOR ADDITIONAL INFORMATION.

EXISTING EQUIPMENT TO BE DEMOLISHED AND REPLACED.

REFERENCE ONE-LINE DIAGRAMS ON SHEETS 100ED621 &

100EP621 FOR ADDITIONAL INFORMATION.

MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS

ON SHEETS 100ED613 & 100EP613 FOR ADDITIONAL

INFORMATION.

REPLACEMENT PANELBOARD. REFERENCE ONE-LINE

DIAGRAMS ON SHEETS 100ED621 & 100EP621 FOR

ADDITIONAL INFORMATION.

KEY PLAN

1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND

ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE

SHOWN FOR CLARITY.

2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.

EXACT LOCATIONS SHALL BE FIELD VERIFIED AND

REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT

IS BEING RELOCATED AND/OR MODIFIED.

4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT

BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,

IMMEDIATELY INFORM AND COORDINATE WITH VA AS

REQUIRED.

5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS

IMPACTED BY THIS PROJECT.

8D-149

100-P-45A

AREA OF WORK

288 SF

9D-149

ELECTRICAL

VITREOUS CHINAC_SINKSCAMERTONK-12867

EYEWASH

EYEWASH

288 SF

9D-149

ELECTRICAL

BUSDUCT

FUSE MCC-N-G-3 (ABOVE)

FUSE PNL: 9H1-E-3 (BELOW)

PNL: 100_9L1-E-3 SEC 21

PNL: 100_9L1-E-3 SEC 11

PNL: 100_9H1-E-31

TRANSFORMER T-70

TRANSFORMER T-71

PNL: 100_9DEH1-E-3

PNL: 100_9CL1-E-3

PNL: 100_9DEL1-E-3

BLDG 100 - RM 9D-149 - ENLARGED

ELECTRICAL PLANS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

PROJECT

NORTH

BUSDUCT

FUSE MCC-N-G-3 (ABOVE)

FUSE PNL: 9H1-E-3 (BELOW)

PNL: 100_9L1-E-3 SEC 24

PNL: 100_9L1-E-3 SEC 14

PNL: 100_9H1-E-34

TRANSFORMER T-70

TRANSFORMER T-71

PNL: 100_9DEH1-E-3

PNL: 100_9CL1-E-3

PNL: 100_9DEL1-E-3

CONTINUE TO TRANSFORMER "100_8DEL1-E-3"

SEE SHEET 100E-408

CONTINUE TO TRANSFORMER "100_7DEL1-E-3"

SEE SHEET 100E-408

100-P-45A

100-P-44A

1 BLDG 100 - RM 9D-149 - ENLARGED ELECTRICAL DEMOLITION PLAN 0'

SCALE : 1/2" = 1'-0"100E-109

0' 4' 6'

PROJECT

NORTH

2' 2 BLDG 100 - RM 9D-149 - ENLARGED ELECTRICAL PLAN 0'

SCALE : 1/2" = 1'-0"100E-109

0' 4' 6'

PROJECT

NORTH

2'

100E-409

GENERAL NOTES

KEY NOTES

EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE

ONE-LINE DIAGRAMS ON SHEETS 100ED613 & 100EP613

FOR ADDITIONAL INFORMATION.

EXISTING EQUIPMENT TO BE DEMOLISHED AND REPLACED.

REFERENCE ONE-LINE DIAGRAMS ON SHEETS 100ED621 &

100EP621 FOR ADDITIONAL INFORMATION.

EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE

ONE-LINE DIAGRAMS ON SHEETS 100ED621 & 100EP621

FOR ADDITIONAL INFORMATION.

MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS

ON SHEETS 100ED613 & 100EP613 FOR ADDITIONAL

INFORMATION.

MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS

ON SHEETS 100ED621 & 100EP621 FOR ADDITIONAL

INFORMATION.

PANEL "9DEH1-E-3" WITH SUBFEED SECTION TO PROVIDE

SPACE FOR THE MCC LSI CIRCUIT BREAKER.

KEY PLAN

1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND

ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE

SHOWN FOR CLARITY.

2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.

EXACT LOCATIONS SHALL BE FIELD VERIFIED AND

REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT

IS BEING RELOCATED AND/OR MODIFIED.

4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT

BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,

IMMEDIATELY INFORM AND COORDINATE WITH VA AS

REQUIRED.

5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS

IMPACTED BY THIS PROJECT.

9D-149

AREA OF WORK

579 SF

ELEC. RM. EMERG. & SWITCHGEAR

PNL: 101_101-LSP 4

5ATS-LS-101-1

101-P-01A 101-C-01A

101-P-01B 101-C-01B

SWBD: "101_101-DE-1P"

PNL: "101_101-EDP

ATS-DE-101-1

STAIR

NO. 14

STAIR

NO. 15

579 SF

ELEC. RM. EMERG. & SWITCHGEAR

PNL: 101_101-LSP 2

2ATS-LS-101-1

ATS-DE-101-1

SCALE : 1/4" = 1'-0"

2 BLDG 101 - RM 703 - ENLARGED ELECTRICAL PLAN

BLDG 101 - RM 703 - ENLARGED

ELECTRICAL PLANS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

101E-107

PROJECT

NORTH

SCALE : 1/4" = 1'-0"

1 BLDG 101 - RM 703 - ENLARGED ELECTRICAL DEMOLITION PLAN

101E-107

PROJECT

NORTH

0'0' 4' 8'2'

PROJECT

NORTH

0'0' 4' 8'2'

SWBD: "101_101-DE-1P"

PNL: "101_101-EDP

101E-407

GENERAL NOTES

KEY NOTES

EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE

DIAGRAMS ON SHEETS 101ED604 & 101EP604 FOR

ADDITIONAL INFORMATION.

EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE

DIAGRAMS ON SHEETS 101ED602 & 101EP602 FOR

ADDITIONAL INFORMATION.

MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS

ON SHEETS 101ED604 & 101EP604 FOR ADDITIONAL

INFORMATION.

MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS

ON SHEETS 101ED602 & 101EP602 FOR ADDITIONAL

INFORMATION.

MODIFIED EQUIPMENT. PROVIDE INTEGRAL

COMMUNICATION MODULE INTERIOR TO ATS, ASCO #5170,

OR APPROVED EQUAL. PROVIDE CT'S AND VOLTAGE

CONNECTIONS INTERIOR TO ATS AND CABLE TO NEW SE

8244 POWER METER ENCLOSURE, OR APPROVED EQUAL.

EQUIPMENT SHALL BE INSTALLED WITH ALL REQUIRED

WIRING, TERMINATIONS, AND APPURTENANCES AS

REQUIRED FOR A COMPLETE AND FULLY FUNCTIONAL

SYSTEM.

PME ENCLOSURE "PME-LS-101-1" WITH SE 8244 POWER

METER, OR APPROVED EQUAL, NETWORK SWITCH, AND

ALL REQUIRED APPURTENANCES OF EACH ATS. EXTEND

POWER CIRCUIT FROM EXISTING METERING SYSTEM

PANEL. REFERENCE SPECIFICATION 251010 FOR

ADDITIONAL INFORMATION.

CONTINUE TO LOCAL METERING SYSTEM PANEL.

REFERENCE SHEET 101E-107 FOR ADDITIONAL

INFORMATION.

AREA OF WORK

KEY PLAN

1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND

ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE

SHOWN FOR CLARITY.

2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.

EXACT LOCATIONS SHALL BE FIELD VERIFIED AND

REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT

IS BEING RELOCATED AND/OR MODIFIED.

4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT

BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,

IMMEDIATELY INFORM AND COORDINATE WITH VA AS

REQUIRED.

5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS

IMPACTED BY THIS PROJECT.

231 SF

P5F-107

ELEC. PANEL

231 SF

P5F-107

ELEC. PANEL

SWBD: 103_NH103DP1

SWBD: 103_EH103DP2

ATS-LS-103

BLDG 103 - RM PF5-107 - ENLARGED

ELECTRICAL PLANS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

P5F-107

0' 1' 2' 4'

103-P-01

PROJECT

NORTH

PROJECT

NORTH

ATS-EQ-103

1 BLDG 103 - RM PF5-107 - ENLARGED ELECTRICAL DEMOLITION PLAN

1/2" = 1'-0"103E-102

SWBD: 103_NH103DP1

SWBD: 103_EH103DP2

ATS-LS-103 ATS-EQ-103

103-P-02

103-C-01

0' 1' 2' 4'

PROJECT

NORTH

2 BLDG 103 - RM PF5-107 - ENLARGED ELECTRICAL PLAN

1/2" = 1'-0"103E-102

LOCAL METERING

BOX

103E-402

GENERAL NOTES

KEY NOTES

EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE

DIAGRAMS ON SHEETS 103ED603 & 103EP603 FOR

ADDITIONAL INFORMATION.

EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE

DIAGRAMS ON SHEETS 103ED601 & 103EP601 FOR

ADDITIONAL INFORMATION.

EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE

DIAGRAMS ON SHEETS 103ED604 & 103EP604 FOR

ADDITIONAL INFORMATION.

MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS

ON SHEETS 103ED603 & 103EP603 FOR ADDITIONAL

INFORMATION.

MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS

ON SHEETS 103EP601 & 103ED601 FOR ADDITIONAL

INFORMATION.

MODIFIED EQUIPMENT. PROVIDE INTEGRAL

COMMUNICATION MODULE INTERIOR TO ATS, ASCO #5170,

OR APPROVED EQUAL. PROVIDE CT'S AND VOLTAGE

CONNECTIONS INTERIOR TO ATS AND CABLE TO NEW SE

8244 POWER METER ENCLOSURE, OR APPROVED EQUAL.

EQUIPMENT SHALL BE INSTALLED WITH ALL REQUIRED

WIRING, TERMINATIONS, AND APPURTENANCES AS

REQUIRED FOR A COMPLETE AND FULLY FUNCTIONAL

SYSTEM.

REPLACE EXISTING RUSSELL ATS CONTROLLER WITH

RUSSELL RPTCS CONTROLLER. PROVIDE ALL HARDWARE,

PROGRAMMING, CONNECTIONS, AND APPURTENANCES AS

REQUIRED.

PME ENCLOSURE "PME-LS-103" WITH SE 8244 POWER

METER, OR APPROVED EQUAL, NETWORK SWITCH, AND

ALL REQUIRED APPURTENANCES OF EACH ATS. EXTEND

POWER CIRCUIT FROM EXISTING METERING SYSTEM

PANEL. REFERENCE SPECIFICATION 251010 FOR

ADDITIONAL INFORMATION.

LOCAL PME METERING BOX; COORDINATE WITH

MANUFACTURER FOR EXACT CABLING AND TERMINATION

REQUIREMENTS.

AREA OF WORK

KEY PLAN

1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND

ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE

SHOWN FOR CLARITY.

2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.

EXACT LOCATIONS SHALL BE FIELD VERIFIED AND

REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT

IS BEING RELOCATED AND/OR MODIFIED.

4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT

BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,

IMMEDIATELY INFORM AND COORDINATE WITH VA AS

REQUIRED.

5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS

IMPACTED BY THIS PROJECT.

103-C-02

FS

a

TYP.

JGD/JRB

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

BLDG 105 - ENLARGED

ELECTRICAL PLANS

a L1E a L1 aL1E a L1E a L1aL1E

PULL BOX

TRANSFORMER "T-118"

(BELOW)

PANEL:105-DEH1

PANEL:105_DEL1

PULL

BOX

UNIT HEATER

ON CEILING

ENVIRONMENTAL

CONTROL PANEL

105_MCC-1

DDC PANEL (CP7 COOLING TOWER)

STARTERS

(ABOVE)

FAN

FAN (DOOR-MOUNTED)

EXISTING SPARE

CONDUIT

PUMP P-11

GUTTER

PUMP P-10

PUMP P-09

PULL BOX

TRANSFORMER "T-118"

(BELOW)

PANEL:105-DEH1

PANEL:105_DEL1

PULL

BOX

UNIT HEATER

ON CEILING

ENVIRONMENTAL

CONTROL PANEL

DDC PANEL (CP7 COOLING TOWER)

STARTERS

(ABOVE)

FAN

EXISTING SPARE

CONDUIT

PUMP P-11PUMP P-10PUMP P-09

1 BLDG 105 - ENLARGED LIGHTING DEMOLITION PLAN

SCALE : 1/2'' = 1'-0"105ED101

2 BLDG 105 - ENLARGED LIGHTING PLAN

SCALE : 1/2'' = 1'-0"105EP101

0' 1' 2' 4'

PROJECT

NORTH

0' 1' 2' 4'

PROJECT

NORTH

105E-401a

BLDG 105

BLDG 41

BLDG 16

BLDG 6

BLDG T-51

BLDG

BLDG 101

BLDG 100

BLDG 102

BLDG 103

BLDG 104

GENERAL NOTES

KEY NOTES

DEMOLISH EXISTING LIGHT FIXTURES AND ASSOCIATED

LIGHT SWITCHES. DEMOLISH ALL ASSOCIATED CONDUITS

AND CABLING BACK TO SOURCE.

UTILIZE EXISTING LIGHTING CIRCUIT TO POWER AND

CONTROL NEW LUMINAIRES AND LIGHT SWITCH. PROVIDE

CONDUIT AND WIRE AS REQUIRED. CONTRACTOR SHALL

PROVIDE LUMINAIRE MOUNTING HARDWARE AS REQUIRED;

COORDINATE MOUNTING WITH EXISTING CONDITIONS.

AREA OF WORK

gmsfgnsfg

PROJECT

NORTH

KEY PLAN

1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND

ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE

SHOWN FOR CLARITY.

2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.

EXACT LOCATIONS SHALL BE FIELD VERIFIED AND

REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT

IS BEING RELOCATED AND/OR MODIFIED.

4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT

BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,

IMMEDIATELY INFORM AND COORDINATE WITH VA AS

REQUIRED.

5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS

IMPACTED BY THIS PROJECT.

FS

J J

JGD/JRB

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

BLDG 105 - ENLARGED

ELECTRICAL PLANS

PULL BOX

TRANSFORMER "T-118"

(ABOVE)

PANEL:105-DEH1

PANEL:105_DEL1

PULL

BOX

UNIT HEATER

ON CEILING

ENVIRONMENTAL

CONTROL PANEL

105_MCC-1

PUMP P-11

DDC PANEL (CP7 COOLING TOWER)

STARTERS

(BELOW)

GUTTER

FAN

FAN (DOOR-MOUNTED)

PUMP P-10

PUMP P-09

E85 FUEL DISPENSARY FEEDEREXISTING SPARE

CONDUIT

FIRE ALARM JUNCTION BOX

FIRE ALARM JUNCTION BOX

105-S-01

105-FA-03

105-P-01

105-P-08B

105-P-07B

105-P-06B

105-FA-02

105-FA-02

105-FA-02

105-P-11

1 BLDG 105 - ENLARGED ELECTRICAL DEMOLITION PLAN

SCALE : 1/2'' = 1'-0"105ED101

2 BLDG 105 - ENLARGED ELECTRICAL PLAN

SCALE : 1/2'' = 1'-0"105EP101

105-FA-01

PULL BOX

TRANSFORMER "T-118"

(ABOVE)

PANEL:105-DEH1

PANEL:105_DEL1

PULL

BOX

UNIT HEATER

ON CEILING

ENVIRONMENTAL

CONTROL PANEL

PUMP P-11

STARTERS

(BELOW)

FAN

PUMP P-10

PUMP P-09

JUNCTION BOX

"JB-DDC"

GUTTER

0' 1' 2' 4'

PROJECT

NORTH

0' 1' 2' 4'

PROJECT

NORTH

FAN (DOOR-MOUNTED)

105E-401b

BLDG 105

BLDG 41

BLDG 16

BLDG 6

BLDG T-51

BLDG

BLDG 101

BLDG 100

BLDG 102

BLDG 103

BLDG 104

GENERAL NOTES

KEY NOTES

EXISTING MOTOR CONTROL CENTER "105_MCC-1" SHALL

BE DEMOLISHED. PRESERVE INCOMING SOURCE FEEDER

FOR REUSE.

EXISTING DDC CONTROL PANEL ENCLOSURE TO BE

REUSED AS A JUNCTION BOX. EXTEND CONDUIT AND WIRE

TO MODULAR BUILDING ELECTRICAL ROOM. REFERENCE

ELECTRICAL ROOM FLOOR PLAN AND ONE-LINE DIAGRAM

FOR ADDITIONAL INFORMATION.

EXISTING CONDUIT AND WIRE TO BE MODIFIED.

REFERENCE SHEET 105E-401c FOR ADDITIONAL

INFORMATION.

EXISTING E85 FUEL DISPENSARY CONDUIT AND WIRE TO

BE DEMOLISHED BACK TO SOURCE.

PROVIDE JUNCTION BOX "JB-MER" AND INSULATED TAPS

TO EXTEND EXISTING CONDUIT AND WIRE TO

PANELBOARD "P-105" AS SHOWN. REFERENCE ONE-LINE

DIAGRAM ON SHEET 105EP601 FOR ADDITIONAL

INFORMATION.

EPO PUMP PANEL. EPO SWITCHES "EPO-P-09", "EPO-P-10",

AND "EPO-P-11" SHALL BE DOOR MOUNTED ON PANEL.

PROVIDE PLEXI GLASS COVER TO ENSURE FALSE

TRIPPING DOES NOT OCCUR. PROVIDE ID PLACARD PER

SPECIFICATIONS. EPO SWITCH SHUNT TRIP PUMP FEEDER

CIRCUIT BREAKERS LOCATED IN PANEL "P-105".

CONDUIT TO BE UTILIZED FOR FIRE ALARM AND FEEDER

TO BUILDING 105 MODULAR BUILDING "ELECTRICAL ROOM".

REFERENCE MODULAR BUILDING ELECTRICAL ROOM

FLOOR PLANS AND ONE-LINE DIAGRAM FOR ADDITIONAL

INFORMATION.

PROVIDE JUNCTION BOX AS NEEDED. EXTEND TO

EXISTING SPARE FIRE ALARM FIELD DEVICE CONDUIT.

REFERENCE SHEET 105EP101 FOR ADDITIONAL

INFORMATION.

AREA OF WORK

gmsfgnsfg

PROJECT

NORTH

KEY PLAN

1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND

ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE

SHOWN FOR CLARITY.

2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.

EXACT LOCATIONS SHALL BE FIELD VERIFIED AND

REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT

IS BEING RELOCATED AND/OR MODIFIED.

4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT

BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,

IMMEDIATELY INFORM AND COORDINATE WITH VA AS

REQUIRED.

5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS

IMPACTED BY THIS PROJECT.

CONTINUE FROM SHEET 105EP101

E-506

"ELECTRICAL ROOM".

$b L1 a 105A-1

W1E b

105A-3 a

L1E a 105A-1

HVAC UNIT

105-ER-HV-01

PANELBOARD

"105A"

TRANSFORMER

"TX-105A"

PANELBOARD

"P-105"

UNISTRUT, TYP

COOLING TOWER #3 VFD

COOLING TOWER #1 VFD

HVAC UNIT

105-ER-HV-01

PANELBOARD

"105A"

TRANSFORMER

"TX-105A"

PANELBOARD

"P-105"

DDC PANEL

COOLING TOWER #2 VFD

FIRE ALARM

JUNCTION BOX

PUMP "P-10" VFD

PUMP "P-9" VFD

PUMP "P-11" VFD

FSTJ

FS

UNISTRUT, TYP

COOLING TOWER #3 VFD

COOLING TOWER #1 VFD

HVAC UNIT

105-ER-HV-01

PANELBOARD

"105A"

TRANSFORMER

"TX-105A"

T

PANELBOARD

"P-105"

DDC PANEL

105A-7

WP

105-C-06105-C-01105-C-02

105-P-09

105-C-03

105-P-05B105-P-10

105-P-03B

105-P-03A

105-P-04B

105-P-04A

COOLING TOWER #2 VFD

J

FIRE ALARM

JUNCTION BOX

105-FA-03

105-FA-02

105-C-05

105-C-04

105-P-06B

105-P-06A

105-P-07A

105-P-07B

PUMP "P-10" VFD

PUMP "P-9" VFD

PUMP "P-11" VFD

105-FA-02

105-P-05A

105-P-02B

105-P-02A

105-P-08A 105-P-08B

105A-5

105A-5

105A-5

105A-2

105-S-01

105A-7

WP

105-P-01

1 BLDG 105 - MODULAR BUILDING "ELECTRICAL ROOM" ENLARGED LIGHTING PLAN

SCALE : 1" = 1'-0"

0" 1' 2'

BLDG 105

BLDG 41

BLDG 16

BLDG 6

BLDG T-51

BLDG

BLDG 101

BLDG 100

BLDG 102

BLDG 103

BLDG 104

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

BLDG 105 - ENLARGED ELECTRICAL

PLANS

105EP101

0.5'

PROJECT

NORTH

2 BLDG 105 - MODULAR BUILDING "ELECTRICAL ROOM" ENLARGED ELECTRICAL PLAN

SCALE : 1" = 1'-0"

0" 1' 2'

105EP101

0.5'

PROJECT

NORTH

105E-401c

GENERAL NOTES

KEY NOTES

CONTINUE TO EMERGENCY POWER OFF ENCLOSURE IN

BUILDING 105. REFERENCE SHEETS 105EP101 AND

105E-401b FOR ADDITIONAL INFORMATION.

CONTINUE TO JUNCTION BOX "JB-MER" IN BUILDING 105.

REFERENCE SHEETS 105EP101 AND 105E-401b FOR

ADDITIONAL INFORMATION.

CONTINUE TO COOLING TOWER DISCONNECTS.

REFERENCE SHEET 105EP101 FOR ADDITIONAL

INFORMATION.

CONTINUE TO FIRE ALARM JUNCTION BOX IN BUILDING 105.

REFERENCE SHEETS 105EP101 AND 105E-401b FOR

ADDITIONAL INFORMATION.

CONTINUE TO JUNCTION BOX "JB-DDC" IN BUILDING 105.

REFERENCE SHEETS 105EP101 AND 105E-401b FOR

ADDITIONAL INFORMATION.

CONTINUE TO PUMPS "P-9", "P-10", AND "P-11" IN BUILDING

105. REFERENCE SHEETS 105EP101 AND 105E-401b FOR

ADDITIONAL INFORMATION.

AREA OF WORK

gmsfgnsfg

PROJECT

NORTH

KEY PLAN

1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND

ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE

SHOWN FOR CLARITY.

2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.

EXACT LOCATIONS SHALL BE FIELD VERIFIED AND

REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT

IS BEING RELOCATED AND/OR MODIFIED.

4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT

BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,

IMMEDIATELY INFORM AND COORDINATE WITH VA AS

REQUIRED.

5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS

IMPACTED BY THIS PROJECT.

7. REFERENCE ONE-LINE DIAGRAM SHEETS 105ED601 AND

105EP601 FOR ADDITIONAL INFORMATION.

E-509

1B E-509

1C E-509

1D E-509

1A E-509

E-507

E-507

E-507

105A-1

105A-3

105A-1

.0

0"

112.00" 33.69" 71.94"

RACK 4 SLOT 1

PLC POWER SUPPLY

BME XBP 1002

G

CB20CB20

REDUNDANT

PLC CPU

GENERAL NOTES

KEY NOTES

2 REVISED OHSU REDUNDANT GENERATOR CONTROL PANEL ELEVATIONS

NTS

1 REVISED MASTER CONTROL PANEL ELEVATIONS

EXISTING HMI TOUCHSCREEN TO BE DEMOLISHED AND

REPLACED WITH REPLACEMENT HMI TOUCHSCREEN (15")

SCHNEIDER-ELECTRIC #HMIDT732 AS SHOWN.

EXISTING PLC CPU TO BE DEMOLISHED AND REPLACED

WITH REPLACEMENT PLC CPU SCHNEIDER-ELECTRIC

#BME-H58-2040 AS SHOWN.

EXISTING RELAY OUTPUT CARD TO BE DEMOLISHED AND

REPLACED WITH REPLACEMENT CARD

SCHNEIDER-ELECTRIC #BMX-DRA-1605 AS SHOWN.

REDUNDANT CPU, SCHNEIDER-ELECTRIC #BME-H58-2040 TO

BE INSTALLED.

RACK POWER SUPPLY, SCHNEIDER-ELECTRIC

#BMX-CPS-4002 TO BE INSTALLED.

6 SLOT RACK BACKPLANE, SCHNEIDER-ELECTRIC

#BME-XBP-0602 TO BE INSTALLED.

2 3

FRONT ELEVATION BACKPANEL ELEVATION

NTS

FRONT ELEVATION OHSU POWER SCHEMATIC OHSU NETWORK DIAGRAM

100E-4000b

100E-400d

5 6 BLANK SLOT, TYP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

ELECTRICAL DETAILS

1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE

CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE

ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

2. MAKE ALL CONNECTIONS TO EQUIPMENT PER

REQUIREMENTS.

3. PRIOR TO EQUIPMENT PROCUREMENT, CONTRACTOR

SHALL PROVIDE DETAILED AND DIMENSIONED SHOP

DRAWINGS INDICATING PROPOSED EQUIPMENT LAYOUT

FOR ALL ELECTRICAL EQUIPMENT INSTALLATIONS DURING

THE SUBMITTAL PROCESS FOR VA AND ENGINEER REVIEW

AND APPROVAL.

4. ALL EQUIPMENT SHALL BE PROVIDED WITH ALL CABLES,

CONNECTIONS, SOFTWARE, PROGRAMMING, AND

APPURTENANCES AS REQUIRED TO PROVIDE A FULLY

FUNCTIONAL SYSTEM.

E-501

6.00" 31.44"

.2

0"

3.50"

35.40"6.00"35.40" 35.40"

.2

0"

3.50"

.0

0"

.0

0"

GENERAL NOTES

KEY NOTES

SCALE : 1" : 1'-0"

1 UNIT SUBSTATIONS USNW AND USS2 ACTIVE HARMONIC FILTER ELEVATION DETAIL UNIT SUBSTATION USCP ACTIVE HARMONIC FILTER ELEVATION DETAIL

SCALE : 1" : 1'-0"

CONDUIT, TYP

300A, 480V ACTIVE HARMONIC FILTER,

SCHNEIDER ELECTRIC MODEL

#NHA5990600, OR APPROVED EQUAL,

TYPICAL

CONDUIT, TYP

300A, 480V ACTIVE HARMONIC FILTER,

SCHNEIDER ELECTRIC MODEL

#NHA5990600, OR APPROVED EQUAL

120A, 480V ACTIVE HARMONIC FILTER,

SCHNEIDER ELECTRIC MODEL

#NHA5990200, OR APPROVED EQUAL

100E-400f100E-400b 100E-400e

EXISTING FLOOR EXISTING FLOOR

22" DEPTH, TYP

22" DEPTH, TYP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

ELECTRICAL DETAILS

1 HOUSEKEEPING PAD, CONCRETE WITH CHAMFERED EDGE,

3-1/2"H, EXTEND PAD 3" BEYOND EQUIPMENT FOOT PRINT.

PROVIDE 5000-PSI CONCRETE WITH #4 REBAR, 12" OC;

REBAR SHALL BE TIED. COORDINATE REBAR INSTALLATION

WITH CONDUIT INSTALLATIONS AS REQUIRED.

EXISTING SWITCHBOARD WITH MAIN INCOMING LUGS AND

ANALOG METERING. PROVIDE FIELD MODIFICATIONS AS

REQUIRED TO REPLACE INCOMING LUGS AND ANALOG

METERING WITH MAIN CIRCUIT BREAKER AND INTEGRAL

POWER METER (SE 8244), RESPECTIVELY. MODIFIED

EQUIPMENT SHALL BE RE-CERTIFIED BY UL FIELD

ENGINEERS AS REQUIRED. COORDINATE SHUTDOWN AND

RE-CERTIFICATION WITH VA.

3", TYP

EQUIPMENT ID PLACARD, TYP

1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE

CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE

ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

2. MAKE ALL CONNECTIONS TO EQUIPMENT PER

REQUIREMENTS.

3. PRIOR TO EQUIPMENT PROCUREMENT, CONTRACTOR

SHALL PROVIDE DETAILED AND DIMENSIONED SHOP

DRAWINGS INDICATING PROPOSED EQUIPMENT LAYOUT

FOR ALL ELECTRICAL EQUIPMENT INSTALLATIONS DURING

THE SUBMITTAL PROCESS FOR VA AND ENGINEER REVIEW

AND APPROVAL.

4. ALL EQUIPMENT SHALL BE PROVIDED WITH ALL CABLES,

CONNECTIONS, SOFTWARE, PROGRAMMING, AND

APPURTENANCES AS REQUIRED TO PROVIDE A FULLY

FUNCTIONAL SYSTEM.

5. NOT ALL RACEWAYS AND CONDUCTORS MAY BE SHOWN

FOR CLARITY. REFERENCE ASSOCIATED FLOOR PLAN OR

CONDUIT AND WIRE SCHEDULE FOR ADDITIONAL

INFORMATION.

EQUIPMENT ID PLACARD, TYP

3", TYP

E-502

TYPICAL INSULATED TAP CONNECTORS DETAIL

NTS

CLEAR INSULATED TAP CONNECTOR, ILSCO ECTS SERIES CLEAR INSULATED TAP CONNECTOR, ILSCO ECTD SERIES

CLEAR INSULATED TAP CONNECTOR, ILSCO ECT SERIES

DETAIL NOTE(S):

1. CLEAR INSULATED-TAP CONNECTORS UTILIZED FOR LOW-VOLTAGE POWER FEEDERS SHALL BE

ILSCO OR APPROVED EQUAL. PROVIDE QUANTITIES AND SIZES AS REQUIRED.

BUILDING 100 SWITCHBOARD "5SDEC-E-17" PHOTO DETAIL

NTS

BUILDING 100 SWITCHBOARD "2SDN-D-17" PHOTO DETAIL

NTS

-100E-405 100E-402a

2 2

GENERAL NOTES

KEY NOTES

1 SUBSTATION USCL SWITCHGEAR ELEVATION

NTS

2 SUBSTATION USNW SWITCHGEAR ELEVATION

NTS

3 SUBSTATION USCP SWITCHGEAR ELEVATION

NTS

4 SUBSTATION USS2 SWITCHGEAR ELEVATION

100E-400b NTS

PROVIDE DRAWOUT CIRCUIT BREAKER FOR ACTIVE

HARMONIC FILTER EQUIPMENT IN EMPTY SWITCHGEAR

BUCKET, 800A/3P, LSIG. EXISTING DRAWOUT SWITCHGEAR

IS SQUARE-D POWER ZONE II. EXISTING DRAWOUT

CIRCUIT BREAKER MODELS ARE OF TYPE SQUARE-D

DS416.

EXISTING CIRCUIT BREAKERS TO BE REPLACED WITH

TYPE SE MASTERPACK MTZ OR APPROVED EQUAL.

REFERENCE ONE-LINE DIAGRAMS ON SHEETS 100ED601 &

100EP601 FOR ADDITIONAL INFORMATION.

EXISTING CIRCUIT BREAKERS TO BE REPLACED WITH

TYPE SE MASTERPACK MTZ OR APPROVED EQUAL.

REFERENCE ONE-LINE DIAGRAMS ON SHEETS 100ED610 &

100EP610 FOR ADDITIONAL INFORMATION.

EXISTING CIRCUIT BREAKERS TO BE REPLACED WITH

TYPE SE MASTERPACK MTZ OR APPROVED EQUAL.

REFERENCE ONE-LINE DIAGRAMS ON SHEETS 100ED605 &

100EP605 FOR ADDITIONAL INFORMATION.

EXISTING CIRCUIT BREAKERS TO BE REPLACED WITH

TYPE SE MASTERPACK MTZ OR APPROVED EQUAL.

REFERENCE ONE-LINE DIAGRAMS ON SHEETS 100ED615 &

100EP615 FOR ADDITIONAL INFORMATION.

SPACE, TYP.

SPACE, TYP.

SPACE, TYP.

SPACE, TYP.

100E-400f

100E-4000d 100E-400e

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

ELECTRICAL DETAILS

1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE

CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE

ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

2. MAKE ALL CONNECTIONS TO EQUIPMENT PER

MANUFACTURER'S REQUIREMENTS.

3. ALL EQUIPMENT SHALL BE PROVIDED WITH ALL CABLES,

CONNECTIONS, SOFTWARE, PROGRAMMING, AND

APPURTENANCES AS REQUIRED TO PROVIDE A FULLY

FUNCTIONAL SYSTEM.

E-503

PROVIDE NETWORK SWITCH WITH CONTROL POWER

TRANSFORMER (CPT) LOCATED INTERIOR TO EXISTING UNIT

SUBSTATION POWER METER CUBICLE; CPT SHALL USE

SUBSTATION AS SOURCE. PROVIDE DATA CABLES FROM

REPLACEMENT UNIT SUBSTATION CIRCUIT BREAKERS TO

NETWORK SWITCH; REFERENCE PLANS FOR ADDITOINAL

DATA CONNECTION REQUIREMENTS. PROVIDE CAT6A

CABLING FROM NETWORK SWITCH TO EXTEND TO LOCAL PME

ENCLOSURE NETWORK SWITCH. PROVIDE PROGRAMMING

AND INTEGRATION FOR ALL DEVICE STATUS / DATA TO

TRANSMIT AND BE VIEWABLE ACROSS EXISTING FACILITY PME

NETWORK.

2 SUBSTATION US103 SWITCHGEAR ELEVATION

NTS

GENERAL NOTES

KEY NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

ELECTRICAL DETAILS

1 SUBSTATION US101 SWITCHGEAR ELEVATION

NTS

1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE

CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE

ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

2. MAKE ALL CONNECTIONS TO EQUIPMENT PER

MANUFACTURER'S REQUIREMENTS.

3. ALL EQUIPMENT SHALL BE PROVIDED WITH ALL CABLES,

CONNECTIONS, SOFTWARE, PROGRAMMING, AND

APPURTENANCES AS REQUIRED TO PROVIDE A FULLY

FUNCTIONAL SYSTEM.

E-504

NTS

NTS

SUBSTATION USS1 SWITCHGEAR ELEVATION4EXISTING BUILDING 100 DELAYED EQUIPMENT FEEDER PHOTO DETAIL

1 EXISTING RACEWAYS AND CONDUCTORS SERVING EMERGENCY

SOURCE LINE SIDE OF DELAYED EQUIPMENT

AUTOMATIC TRANSFER SWITCHES. EXISTING RACEWAYS TO

REMAIN; DEMOLISH EXISTING CONDUCTORS. PROVIDE AND

EXTEND NEW CONDUCTORS THROUGH EXISTING RACEWAYS AND

NEW JUNCTION BOX(ES) TO SERVE EACH ATS FROM

SWITCHBOARD "100-DEWSBD-G-1". EXTEND EXISTING RACEWAYS

AND AND PROVIDE PULLBOX(ES), SIZED PER NEC, AS REQUIRED.

REFERENCE ONE-LINE DIAGRAM ON SHEETS 100ED601 AND

100EP601 FOR ADDITIONAL INFORMATION.

EXISTING CIRCUIT BREAKERS TO BE REPLACED WITH

TYPE SE MASTERPACK MTZ OR APPROVED EQUAL. REFERENCE

ONE-LINE DIAGRAMS ON SHEETS 101ED602 & 101EP602 FOR

ADDITIONAL INFORMATION.

EXISTING CIRCUIT BREAKERS TO BE REPLACED WITH

TYPE SE MASTERPACK MTZ OR APPROVED EQUAL. REFERENCE

ONE-LINE DIAGRAMS ON SHEETS 103ED601 & 103EP601 FOR

ADDITIONAL INFORMATION.

EXISTING CIRCUIT BREAKERS TO BE REPLACED WITH

TYPE SE MASTERPACK MTZ OR APPROVED EQUAL. REFERENCE

ONE-LINE DIAGRAMS ON SHEETS 100ED620 & 100EP620 FOR

ADDITIONAL INFORMATION.

100E-4000c

101E-107 103E-102

100E-4000a

PROVIDE NETWORK SWITCH WITH CONTROL POWER

TRANSFOMER (CPT) LOCATED INTERIOR TO EXISTING UNIT

SUBSTATION POWER METER CUBICLE; CPT SHALL USE

SUBSTATION AS SOURCE. PROVIDE DATA CABLES FROM

REPLACEMENT UNIT SUBSTATION CIRCUIT BREAKERS TO

NETWORK SWITCH; REFERENCE PLANS FOR ADDITOINAL

DATA CONNECTION REQUIREMENTS. PROVIDE CAT6A

CABLING FROM NETWORK SWITCH TO EXTEND TO LOCAL PME

ENCLOSURE NETWORK SWITCH. PROVIDE PROGRAMMING

AND INTEGRATION FOR ALL DEVICE STATUS / DATA TO

TRANSMIT AND BE VIEWABLE ACROSS EXISTING FACILITY PME

NETWORK.

TRANSFORMERTRANSFOMER (CPT) LOCATED INTERIOR TO EXISTING UNITTRANSFORMER

4'-0"

1'-6"

POWER RECEPTACLE

LIGHT

SWITCH

DETAIL NOTE(S):

1. DETAIL SHOWS GENERAL MOUNTING HEIGHTS UNLESS OTHERWISE NOTED.

2.EXACT LOCATION FOR DEVICES ARE SHOWN ON PLANS.

CEILING

FINISHED

FLOOR

FIRE ALARM PULL STATION

7'-6"

FIRE ALARM VOICE

AND STROBE

GENERAL NOTES

KEY NOTES

2 GROUND TEST WELL

NTS

4 TYPICAL EXISTING METERING ENCLOSURE

NTS-

3 EXISTING BUILDING 100 ELECTRICAL RM B2D-106a PHOTO DETAIL

NTS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

ELECTRICAL DETAILS

100E-4000b

1 TAP EXISTING USEM FEEDER AT JUNCTION BOX VIA MV

SPLICE KITS AND PROVIDE CONDUIT AND WIRE AS

REQUIRED TO FEED MV INTERRUPTER SWITCHES

"SW-ITR-L" AND "SW-ITR-R". REFERENCE ONE-LINE

DIAGRAMS ON SHEETS 100ED601 & 100EP601 FOR

ADDITIONAL INFORMATION.

1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE

CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE

ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

2. MAKE ALL CONNECTIONS TO EQUIPMENT PER

MANUFACTURER'S REQUIREMENTS.

3. PRIOR TO EQUIPMENT PROCUREMENT, CONTRACTOR

SHALL PROVIDE DETAILED AND DIMENSIONED SHOP

DRAWINGS INDICATING PROPOSED EQUIPMENT LAYOUT

FOR ALL ELECTRICAL EQUIPMENT INSTALLATIONS DURING

THE SUBMITTAL PROCESS FOR VA AND ENGINEER REVIEW

AND APPROVAL.

4. NOT ALL RACEWAYS AND CONDUCTORS MAY BE SHOWN

FOR CLARITY. REFERENCE ASSOCIATED FLOOR PLAN OR

CONDUIT AND WIRE SCHEDULE FOR ADDITIONAL

INFORMATION.

1 TYPICAL MOUNTING HEIGHT DETAILS

NTS-

E-505

GRADE REMOVABLE COVER - REINFORCED

CONCRETE - CHRISTY CONCRETE

PRODUCTS #F8D OR EQUAL

BURNDY TYPE GK CONNECTOR OR EQUAL

PRECAST CONCRETE CURB VALVE

BOX - 8 1/2" I.D. X 18" D. -CHRISTY

#F14 BOX OR EQUAL

SAND FILL

BARE SOFT-DRAWN COPPER

GROUNDING ELECTRODE

CONDUCTOR. REFERNCE PLANS

FOR WIRE SIZE AND LENGTH.

GROUND ROD, STEEL COPPER

CLAD, 3/4" DIA. X 10'-0" LONG

006E-101 016E-401

100EG101

PROVIDE 6-PORT SWITCH. PROVIDE

CAT6A FROM SWITCH TO EXISTING

POWER METER AND LOCAL

EQUIPMENT SWITCH.

PROVIDE CAT6A JUMPER

CONNECTING EXISTING

DIGITAL POWER METER TO

PROVIDE SWITCH.

EXISTING EQUIPMENT TO BE

RELOCATED AS REQUIRED TO

PROVIDE ROOM FOR 6-PORT

SWITCH.

PROVIDE CAT6A CABLING AND RACEWAY

EXTENDING TO LOCAL UNIT SUBSTATION AND / OR

AUTOMATIC TRANSFER SWITCH. REFERENCE

FLOOR PLANS AS REQUIRED.

EXISTING PME NETWORK

CABLE SHALL BE

RETERMINATED TO SWITCH AS

INDICATED.

MODIFICATION DETAILTERING ENCLOSURE

GENERAL NOTES

KEY NOTES

2 BUILDING 16 ELECTRICAL EQUIPMENT DEMOLITION PHOTO DETAIL

NTSNTS

BUILDING 16 ELECTRICAL EQUIPMENT DEMOLITION PHOTO DETAIL

4 BUILDING 105 ELECTRICAL PHOTO DETAIL

NTS

3 BUILDING 105 E85 FUEL DISPENSORY AND ACCESSORIES DEMOLITION PHOTO DETAIL

EXISTING SWITCHBOARD TO BE DEMOLISHED.

REFERENCE ONE-LINE DIAGRAM ON SHEET 016ED601 FOR

ADDITIONAL INFORMATION.

EXISTING CONDUIT AND CONDUCTORS TO BE

DEMOLISHED. REFERENCE ONE-LINE DIAGRAM ON SHEET

016ED601 FOR ADDITIONAL INFORMATION.

EXISTING TRANSFORMER, DISCONNECT AND PANEL TO BE

DEMOLISHED. REFERENCE ONE-LINE DIAGRAM ON SHEET

016ED601 FOR ADDITIONAL INFORMATION.

EXISTING E85 FUEL DISPENSARY, POS, CHAINLINK FENCE,

AND ACCESS CONTROLS SHALL BE DEMOLISHED. ALL

ASSOCIATED CONDUIT AND WIRE SHALL BE DEMOLISHED

BACK TO SOURCE.

EXISTING EPO, RECEPTACLE, AND TELEPHONE BOX SHALL

BE DEMOLISHED. ALL ASSOCIATED CONDUIT AND WIRE

SHALL BE DEMOLISHED BACK TO SOURCE.

EXISTING VEHICLE VACUUM TO BE RE-FED VIA BUILDING

105 "ELECTRICAL ROOM". REFERENCE ENLARGED PLANS

FOR ADDITIONAL INFORMATION.

EXISTING MOTOR CONTROL CENTER "105_MCC-1" AND

ASSOCIATED RACEWAYS AND CONDUCTORS TO BE

DEMOLISHED. PRESERVE INCOMING SOURCE FEEDER

FOR REUSE REFERENCE ENLARGED PLANS FOR

ADDITIONAL INFORMATION.

EXISTING DDC CONTROL PANEL ENCLOSURE. EXISTING

DDC CONTROLLER TO BE SALVAGED BY VA. EXISTING

CABLING TO BE REUSED; EXISTING ENCLOSURE TO BE

REUSED AS JUNCTION BOX. REFERENCE ENLARGED

PLANS FOR ADDITIONAL INFORMATION.

EXISTING PUMP RACEWAYS TO BE REUSED. REFERENCE

ENLARGED PLANS FOR ADDITIONAL INFORMATION.

DEMOLISH EXISTING LIGHT FIXTURES, AND ASSOCIATED

LIGHT SWITCHES. DEMOLISH ALL ASSOCIATED CONDUITS

AND CABLING BACK TO SOURCE.

TYP

NTS105ED101

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

ELECTRICAL DETAILS

1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE

CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE

ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

2. MAKE ALL CONNECTIONS TO EQUIPMENT PER

MANUFACTURER'S REQUIREMENTS.

3. PRIOR TO EQUIPMENT PROCUREMENT, CONTRACTOR

SHALL PROVIDE DETAILED AND DIMENSIONED SHOP

DRAWINGS INDICATING PROPOSED EQUIPMENT LAYOUT

FOR ALL ELECTRICAL EQUIPMENT INSTALLATIONS DURING

THE SUBMITTAL PROCESS FOR VA AND ENGINEER REVIEW

AND APPROVAL.

4. NOT ALL RACEWAYS AND CONDUCTORS MAY BE SHOWN

FOR CLARITY. REFERENCE ASSOCIATED FLOOR PLAN OR

CONDUIT AND WIRE SCHEDULE FOR ADDITIONAL

INFORMATION.

7TYP

PHOTO DETAIL 'B'PHOTO DETAIL 'A'

105E-401b

016E-401016E-401

E-506

CEILING

8'-0"

6" 6"

PANELBOARD

"P-105"

FIELD

DEVICES,

SEE PLANS

FOR

ADDITIONAL

INFORMATION

PANEL "105A"

TRANSFORMER

"TX-105A"

EQUIPMENT

ID PLACARD,

TYP.

3'-6"1'-8"

1'-8"

10'-6"

CEILING

60"

20" 4"6"12"

DDC PANEL

EQUIPMENT

ID PLACARD,

TYP.

COOLING TOWER #3 VFD

COOLING TOWER #2 VFD

COOLING TOWER #1 VFD

PUMP "P-11" VFD

PUMP "P-10" VFD

PUMP "P-9" VFD

TYPTYP

CEILING

HVAC UNIT WALL PENETRATIONS,

COORDINATE WITH BUILDING

MANUFACTURER AS REQUIRED.

HVAC UNIT, WALL-MOUNTED TO

EXTERIOR WALL

8'-0"

6"

7'-1"

3'-6"

30"

30" 8"

30"

30"

30"

30"

PROVIDE PLACARD TO

INDICATE EQUIPMENT

THAT IS METERED.

PADLOCKABLE WING KNOB

PADLOCKABLE WING KNOB

PROVIDE PLACARD TO

INDICATE EQUIPMENT

THAT IS METERED.

GENERAL NOTES

KEY NOTES

4 TYPICAL POWER METER ENCLOSURE

NTS

3 BLDG 105 - MODULAR BUILDING "ELECTRICAL ROOM" - EAST WALL ELEVATION

NOTES:

1. USE HOT-DIPPED GALVANIZED UNISTRUT AND STAINLESS

STEEL FASTENING HARDWARE FOR MOUNTING ALL

EQUIPMENT TO BUILDING 105 STRUCTURES AS REQUIRED.

NOTES:

1. USE HOT-DIPPED GALVANIZED UNISTRUT AND STAINLESS

STEEL FASTENING HARDWARE FOR MOUNTING ALL

EQUIPMENT TO BUILDING 105 STRUCTURES AS REQUIRED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

ELECTRICAL DETAILS

105E-401c SCALE: 1" = 1'-0"

1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE

CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE

ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

2. MAKE ALL CONNECTIONS TO EQUIPMENT PER

MANUFACTURER'S REQUIREMENTS.

3. PRIOR TO EQUIPMENT PROCUREMENT, CONTRACTOR

SHALL PROVIDE DETAILED AND DIMENSIONED SHOP

DRAWINGS INDICATING PROPOSED EQUIPMENT LAYOUT

FOR ALL ELECTRICAL EQUIPMENT INSTALLATIONS

DURING THE SUBMITTAL PROCESS FOR VA AND

ENGINEER REVIEW AND APPROVAL.

4. ALL EQUIPMENT SHALL BE PROVIDED WITH ALL CABLES,

CONNECTIONS, SOFTWARE, PROGRAMMING, AND

APPURTENANCES AS REQUIRED TO PROVIDE A FULLY

FUNCTIONAL SYSTEM.

5. NOT ALL RACEWAYS AND CONDUCTORS MAY BE SHOWN

FOR CLARITY. REFERENCE ASSOCIATED FLOOR PLAN OR

CONDUIT AND WIRE SCHEDULE FOR ADDITIONAL

INFORMATION.

1 BLDG 105 - MODULAR BUILDING "ELECTRICAL ROOM" - NORTH WALL ELEVATION

-105E-401c SCALE: 1" = 1'-0"

2 BLDG 105 - MODULAR BUILDING "ELECTRICAL ROOM" - SOUTH WALL ELEVATION

-105E-401c SCALE: 1" = 1'-0"

E-507

30"

30"

30"

30" 30"

30"

8"

ALL DIMENSIONS ARE MINIMUM

PS

PS

PS

PS

PM

ERMS

114.00"

91.50"

3.50"

36.00" 42.00" 36.00" 6.00"35.40"

82.20"

3.50"

6.00"

60.00"

EQUIPMENT

ID PLACARD,

TYP.

EQUIPMENT

ID PLACARD

LLI LLI

94.00"

44.25"

3.50"

EQUIPMENT

ID PLACARD

60.00"

100"

90.00"

(QTY=2) COLUMNS (QTY=2) COLUMNS

130"

EQUIPMENT ID PLACARD

GENERAL NOTES

KEY NOTES

4 SWITCHBOARD "100-DESWBD-G-1" AND USCL ACTIVE HARMONIC FILTERS ELEVATION DETAILS

SCALE: 1/2" = 1'

1 EXISTING RAISED TRANSFORMER PAD PHOTO DETAIL

3 MV INTERRUPTER SWITCHES "100-ISW-L" & "100-ISW-R" ELEVATION DETAIL

EXISTING PAD TO BE REUSED FOR TRANSFORMER "TX-DE".

EXISTING GROUND WIRE TO BE REUSED FOR

TRANSFORMER "TX-DE".

HOUSEKEEPING PAD, CONCRETE WITH CHAMFERED EDGE,

3-1/2"H, EXTEND PAD 3" BEYOND EQUIPMENT FOOT PRINT.

PROVIDE 5000-PSI CONCRETE WITH #4 REBAR, 12" OC;

REBAR SHALL BE TIED. COORDINATE REBAR INSTALLATION

WITH CONDUIT INSTALLATIONS AS REQUIRED.

SCALE: 1" = 1'-00"

CONDUIT,TYP.

2 TRANSFORMER "TX-DE" ELEVATION DETAIL

SCALE: 1" = 1'-0"

SCALE: 1" = 1'-0"

EXISTING RAISED

CONCRETE PAD

24" DEPTH

PULL SECTIONPULL SECTION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

ELECTRICAL DETAILS

100E-4000b

100E-4000b 100E-4000d

1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE

CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE

ALL ELECTRICAL WORK WITH ALL OTHER TRADES.

2. MAKE ALL CONNECTIONS TO EQUIPMENT PER

MANUFACTURER'S REQUIREMENTS.

3. PRIOR TO EQUIPMENT PROCUREMENT, CONTRACTOR

SHALL PROVIDE DETAILED AND DIMENSIONED SHOP

DRAWINGS INDICATING PROPOSED EQUIPMENT LAYOUT

FOR ALL ELECTRICAL EQUIPMENT INSTALLATIONS

DURING THE SUBMITTAL PROCESS FOR VA AND

ENGINEER REVIEW AND APPROVAL.

4. ALL EQUIPMENT SHALL BE PROVIDED WITH ALL CABLES,

CONNECTIONS, SOFTWARE, PROGRAMMING, AND

APPURTENANCES AS REQUIRED TO PROVIDE A FULLY

FUNCTIONAL SYSTEM.

5. NOT ALL RACEWAYS AND CONDUCTORS MAY BE SHOWN

FOR CLARITY. REFERENCE ASSOCIATED FLOOR PLAN OR

CONDUIT AND WIRE SCHEDULE FOR ADDITIONAL

INFORMATION.

3TYP. 300A, 480V ACTIVE HARMONIC FILTER,

SCHNEIDER ELECTRIC MODEL

#NHA5990600, OR APPROVED EQUAL,

TYP.

EXISTING FLOOR

100E-4000b

E-508

4 PROVIDE ALL REQUIRED ANCHORING AND SIESMIC

BRACING PER MANUFACTURER'S INSTRUCTIONS. ALL

HARDWARE SHALL BE STAINLESS-STEEL.

HVAC

(HVAC HEIGTH) 6"

(O

VE

R

AL

L H

EI

G

H T

H

IG

H S

ID

E)

/8

(W

AL

L H

EI

G

H T

H

IG

H S

ID

E)

12'-0"

(W

AL

L H

EI

G

H T

LO

W

S

ID

E)

6"

(O

VE

R

AL

L H

EI

G

H T

LO

W

S

ID

E)

/8

(W

AL

L H

EI

G

H T

LO

W

S

ID

E)

6"

(O

VE

R

AL

L H

EI

G

H T

LO

W

S

ID

E)

/8

(O

VE

R

AL

L H

EI

G

H T

H

IG

H S

ID

E)

/8

(W

AL

L H

EI

G

H T

H

IG

H S

ID

E)

12'-0"

8'-7"

8'-0"

(BASE HEIGHT) 6"

12" 1/2"

12" 1/2"

1 1 1

GENERAL NOTES

2 ELECTRICAL ROOM - BUILDING ELEVATIONS

NTS

1 ELECTRICAL ROOM - BUILDING ELEVATIONS

NTS

105E-401c

105E-401c

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

ELECTRICAL DETAILS

E-509

INTERIOR

1 1/2"X 3"X14GA T.S.

COVE BASE

1 1/2"X 3"X14GA T.S.

BUILDING CROSS SECTION

1-1/2"X 3"X14GA T.S.

ALL AROUND FRAME

WELDED TO BASE

1 1/2"X1 1/2"X1/8" ANGLE

MAINTAIN 1" OVERLAP

OF STEEL OVER GLASS

- ALL AROUND

SILICONE CAULK

#8-18 TEK PAN HEAD SCREWS

@ 12" TO 16" SPACING

POLYISOCYANURATE (R-16)

ALUMINUM TREAD PLATE

16GA. STEEL

NOMINAL 36" X 42" HIGH

FIXED WINDOWS

1/2"x4 1/4" WEDGE ANCHOR, 3-1/4" MINIMUM EMBEDMENT

1/8" 1-1/2" @12"

TUBE STEEL TO

C-CHANNEL

3/8" 12

PLATE TO

TUBE STEEL

3/4" T&G ADVANTEK

12-24 x 2" PHILLIPS FLAT HEAD WITH

WINGS SCREWS - 24 PER SHEET

16 GA STEEL SHEET

WELDED TO FRAME

STEEL

CEILING PANS

R-19 INSULATION

L2"x2"x1/8"TH CEILING WALL MOLD

#10 X 1 1/2" PAN HEAD

TEK SCREWS 12" O.C.

3" THICK A/A

ROOF PANEL

1/4" X 5" TEK SCREWS WITH 1/4" X 1 1/2" ZINC

SEALING WASHER (NEOPRENE) 1 PER 12"

CAULK AROUND WASHER ASSEMBLY

TOP PLATE 1-1/2"X 3"X3/16"

TUBE STEEL

16 GA STEEL SHEET

WELDED TO FRAME

#12 x 1-1/4" TEK SCREW

L1-1/2"x1-1/2"x1/8" ROOF PANEL TRIM

3"x3"x1/4" ANGLE

WELD TO C-CHANNEL 1/8"

16GA. STEEL

1-1/2" GRABBER SCREW W/COUNTER

SINK BIT - 24 PER SHEET

EXTERIOR

ELITE E GUTTER

R-16 POLYISOCYANURATE INSULATION

20GA STEEL SHEET

#12x1 1/4" TEK SCREW W/

STEEL/NEOPRENE WASHER

SPACED 12" O.C.

CAULK AROUND

TEK SCREW

1 1/2" X3" X14 GA.TUBE

STEEL ACTS

AS WINDOW SILL AND

HEADER

TYPICAL WELDED

FRAMING SECTION

1 1/2" X 3" X 14 GA. TUBE STEEL

AT EVERY CORNER TO ATTACH

INTERIOR SKINS (TYPICALLY 14 GA.)

1 1/2" X3" TUBE STEEL

ALONG PERIMETER

WALLS TYPICALLY

INSULATED WITH

2 7/8" POLYSTYRENE FOAM

TYP 14GA

INTERIOR

WELD TO BASE

(TYP)

1/16" 1@12

TYP 14GA

EXTERIOR 1/16" 1@12

1 1/2"X3"X14 GA. TUBE STEEL

AT EACH CORNER

3"X3"X14 GA. TUBE STEEL

IN CORNERS

EAST ELEVATIONA SOUTH ELEVATIONB WEST ELEVATIONC NORTH ELEVATIOND

1. PRE-ASSEMBLED WELDED STEEL BUILDING SHALL BE BY

PANEL BUILT INCORPORATED, OR EQUAL. BUILDING SHALL

BE PRE-ENGINEERED AND REVIEWED AND STAMPED BY A

PROFESSIONAL ENGINEER.

2. CONTRACTOR SHALL PROVIDE ALL FASTENING HARDWARE,

ANCHORING, AND SEISMIC BRACING REQUIRED FOR A

COMPLETE AND FUNCTIONAL INSTALLATION. INSTALLATION

SHALL ADHERE TO ALL BUILDING MANUFACTURER

RECOMMENDATIONS AND REQUIREMENTS.

3. FOR ADDITIONAL REQUIREMENTS, REFERENCE

SPECIFICATIONS 13 34 19, 13 05 41, AND 08 71 00.

KEY NOTES

BARD HVAC UNIT "105-ER-HV-01". REFERENCE MECHANICAL

EQUIPMENT SCHEDULE ON SHEET 105EP701 FOR

ADDITIONAL INFORMATION.

BUILDING 101

UNIT SUB

500 MCM

500 MCM, 600 V. THW

H.V. FEEDER, #2 GND.

MH-HV-1

500 MCM (TYP.)

ACCESSIBLE

CONNECTION

GROUND WELL

SEE DRAWING

101-E2 FOR

LOCATION OF

GROUND RODS

L,6 & 6

500 MCM

A&17

DELETE P-343

500 MCM

3/0

3/0

500 MCM

SEE DRAWING 100-E19

FOR LOCATIONS OF

GROUND RODS

500 MCM

SEE DRAWING 100-E10

FOR LOCATIONS OF

GROUND RODS

A&15

500 MCM

500 MCM, 600V, THW

H.V. FEEDER, #2 GND,

SERVICE GROUND BUS

WITHIN ENERGY CENTER

"B2D-127"

WATER

SERVICE MAIN

500 MCMMH-HV-2

MH-HV-3

F&5

SPRINKLER

SERVICE MAIN

500 MCM, 600V. THW

H.V. FEEDER, #1 GND.

UNIT SUB

"USNW" GROUND BUS

F&3

500 MCM

UNIT SUB

"USCP" GROUND BUS

500 MCM

G&3

500 MCM

500 MCM

G&3

500 MCM HV FEEDER, #1 GND.

500 MCM HV FEEDER, #1 GND.

UNIT SUB

"USCL" GROUND BUS

500 MCM H.V. FEEDER, #1 GND.

500 MCM (TYP.)

SEE DRAWING 100-E151 FOR

LOCATIONS OF GROUND RODS

500 MCM (TYP.)

MH-HV-4

MH-HV-5

MH-HV-3

EXISTING BUILDING 102

PADMOUNT TRANSFORMER.

VERIFY LOCATION OF SERVICE

GROUND CONNECTION IN FIELD.

1/8" x 2" x 6" GROUND BAR

GEN #5 GEN #4 GEN #3

500 MCM ACCESSIBLE CONNECTION

IN GROUND WELL

500 MCM

250 MCM NEUTRAL

GROUNDING CONDUCTOR

GROUND BUS B2-GEN-SD-G5

250 MCM GROUND, SEE

FEEDER SCHEDULE ON

DRAWING 100-E159

GEN #2 GEN #1

250 MCM NEUTRAL

GROUNDING

CONDUCTOR

SEE DRAWING 100-E152 FOR

LOCATIONS OF GROUND RODS

UNIT SUB

"USS2" GROUND BUS

500 MCM HV

FEEDER, #2 GND.

UNIT SUB

"USS1" GROUND BUS

UNIT SUB "US103"

GROUND BUS 500 MCM H.V FEEDER, #1 GND

500 MCM H.V FEEDER, #1 GND

OLD SWITCHGEAR

"RM B1D-108"

500 MCM

250 MCM

GENERATOR SWGR

TRANSFORMER

"T-16"

BUILDING 6 SERVICE

EQUIPMENT

TRANSFORMER

"T-6"

BUILDING 16 SERVICE

EQUIPMENT

BUILDING 105 SERVICE

EQUIPMENT

BUILDING 105 "ELECTRICAL ROOM"

SERVICE EQUIPMENT BLDG 108

(PARKING GARAGE)

RM 201

GROUND ROD

WITH TEST WELL

GROUND ROD

WITH TEST WELL

006-G-01 016-G-01

GROUND ROD

WITH TEST WELL

100-G-01

GENERAL NOTES

KEY NOTES

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

2. GROUNDING ONE-LINE DIAGRAM SHOWN IS

DIAGRAMATICAL; NOT ALL GROUNDING CONNECTIONS ARE

SHOWN FOR CLARITY. DIAGRAM IS BASED ON AVAILABLE

FACILITY AS-BUILTS AND ON-SITE INVESTIGATION.

3. FACILITY WIDE GROUND RESISTANCE TESTING PER VHA

DIRECTIVE 1028-8.J(6)(e). REFERENCE GROUNDING

SPECIFICATION 26 05 26 FOR ADDITIONAL INFORMATION.

MAIN BONDING JUMPER

GROUND CONNECTION FROM SERVICE GROUND BUS TO BUILDING STEEL,

(ACCESSIBLE) AT GRID COORDINATES INDICATED, BY EXOTHERMIC PROCESS.

CONNECTION TO 8" WATER SERVICE MAIN AND SPRINKLER SERVICE MAIN PIPES

ON B-2 LEVEL AT APPROXIMATE GRID COORDINATES "N &…