288 SF
8D-149
ELECTRICAL
288 SF
8D-149
ELECTRICAL
SCALE : 1/2" = 1'-0"
1 BLDG 100 - RM 8D-149 - ENLARGED ELECTRICAL DEMOLITION PLAN
BLDG 100 - RM 8D-149 - ENLARGED
ELECTRICAL PLANS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
PNL: 100_8L1-E-3 SEC 1
PNL: 100_8H1-E-3
BUSDUCT
FUSE MCC-N-8-G-3 (ABOVE)
FUSE PNL: 8H1-E-3 (BELOW)
PNL: 100_8DEL1-E-3
PNL: 100_8L1-E-3 SEC 2 TRANSFORMER T-69
PNL: 100_8CL1-E-3
0' 1' 2' 4'
100E-108
PROJECT
NORTH
SCALE : 1/2" = 1'-0"
2 BLDG 100 - RM 8D-149 - ENLARGED ELECTRICAL PLAN
PROJECT
NORTH
0' 1' 2' 4'
100E-108
PNL: 100_8L1-E-3 SEC 1
PNL: 100_8H1-E-3
BUSDUCT
FUSE MCC-N-8-G-3 (ABOVE)
FUSE PNL: 8H1-E-3 (BELOW)
PNL: 100_8DEL1-E-3
PNL: 100_8L1-E-3 SEC 2 TRANSFORMER T-69
PNL: 100_8CL1-E-3
TRANSFORMER
"100_8DEL1-E-3"
CONTINUE FROM PANEL "100_9DEH1-E-3"
SEE SHEET 100E-409
CONTINUE FROM
SHEET 100E-409 TO
SHEET 100E-407b
100-P-44A
100-P-44B
100E-408
PROJECT
NORTH
GENERAL NOTES
KEY NOTES
EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 100ED613 & 100EP613
FOR ADDITIONAL INFORMATION.
EXISTING EQUIPMENT TO BE DEMOLISHED AND REPLACED.
REFERENCE ONE-LINE DIAGRAMS ON SHEETS 100ED621 &
100EP621 FOR ADDITIONAL INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED613 & 100EP613 FOR ADDITIONAL
INFORMATION.
REPLACEMENT PANELBOARD. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED621 & 100EP621 FOR
ADDITIONAL INFORMATION.
KEY PLAN
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT
IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
8D-149
100-P-45A
AREA OF WORK
288 SF
9D-149
ELECTRICAL
VITREOUS CHINAC_SINKSCAMERTONK-12867
EYEWASH
EYEWASH
288 SF
9D-149
ELECTRICAL
BUSDUCT
FUSE MCC-N-G-3 (ABOVE)
FUSE PNL: 9H1-E-3 (BELOW)
PNL: 100_9L1-E-3 SEC 21
PNL: 100_9L1-E-3 SEC 11
PNL: 100_9H1-E-31
TRANSFORMER T-70
TRANSFORMER T-71
PNL: 100_9DEH1-E-3
PNL: 100_9CL1-E-3
PNL: 100_9DEL1-E-3
BLDG 100 - RM 9D-149 - ENLARGED
ELECTRICAL PLANS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
PROJECT
NORTH
BUSDUCT
FUSE MCC-N-G-3 (ABOVE)
FUSE PNL: 9H1-E-3 (BELOW)
PNL: 100_9L1-E-3 SEC 24
PNL: 100_9L1-E-3 SEC 14
PNL: 100_9H1-E-34
TRANSFORMER T-70
TRANSFORMER T-71
PNL: 100_9DEH1-E-3
PNL: 100_9CL1-E-3
PNL: 100_9DEL1-E-3
CONTINUE TO TRANSFORMER "100_8DEL1-E-3"
SEE SHEET 100E-408
CONTINUE TO TRANSFORMER "100_7DEL1-E-3"
SEE SHEET 100E-408
100-P-45A
100-P-44A
1 BLDG 100 - RM 9D-149 - ENLARGED ELECTRICAL DEMOLITION PLAN 0'
SCALE : 1/2" = 1'-0"100E-109
0' 4' 6'
PROJECT
NORTH
2' 2 BLDG 100 - RM 9D-149 - ENLARGED ELECTRICAL PLAN 0'
SCALE : 1/2" = 1'-0"100E-109
0' 4' 6'
PROJECT
NORTH
2'
100E-409
GENERAL NOTES
KEY NOTES
EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 100ED613 & 100EP613
FOR ADDITIONAL INFORMATION.
EXISTING EQUIPMENT TO BE DEMOLISHED AND REPLACED.
REFERENCE ONE-LINE DIAGRAMS ON SHEETS 100ED621 &
100EP621 FOR ADDITIONAL INFORMATION.
EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 100ED621 & 100EP621
FOR ADDITIONAL INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED613 & 100EP613 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED621 & 100EP621 FOR ADDITIONAL
INFORMATION.
PANEL "9DEH1-E-3" WITH SUBFEED SECTION TO PROVIDE
SPACE FOR THE MCC LSI CIRCUIT BREAKER.
KEY PLAN
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT
IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
9D-149
AREA OF WORK
579 SF
ELEC. RM. EMERG. & SWITCHGEAR
PNL: 101_101-LSP 4
5ATS-LS-101-1
101-P-01A 101-C-01A
101-P-01B 101-C-01B
SWBD: "101_101-DE-1P"
PNL: "101_101-EDP
ATS-DE-101-1
STAIR
NO. 14
STAIR
NO. 15
579 SF
ELEC. RM. EMERG. & SWITCHGEAR
PNL: 101_101-LSP 2
2ATS-LS-101-1
ATS-DE-101-1
SCALE : 1/4" = 1'-0"
2 BLDG 101 - RM 703 - ENLARGED ELECTRICAL PLAN
BLDG 101 - RM 703 - ENLARGED
ELECTRICAL PLANS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
101E-107
PROJECT
NORTH
SCALE : 1/4" = 1'-0"
1 BLDG 101 - RM 703 - ENLARGED ELECTRICAL DEMOLITION PLAN
101E-107
PROJECT
NORTH
0'0' 4' 8'2'
PROJECT
NORTH
0'0' 4' 8'2'
SWBD: "101_101-DE-1P"
PNL: "101_101-EDP
101E-407
GENERAL NOTES
KEY NOTES
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 101ED604 & 101EP604 FOR
ADDITIONAL INFORMATION.
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 101ED602 & 101EP602 FOR
ADDITIONAL INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 101ED604 & 101EP604 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 101ED602 & 101EP602 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. PROVIDE INTEGRAL
COMMUNICATION MODULE INTERIOR TO ATS, ASCO #5170,
OR APPROVED EQUAL. PROVIDE CT'S AND VOLTAGE
CONNECTIONS INTERIOR TO ATS AND CABLE TO NEW SE
8244 POWER METER ENCLOSURE, OR APPROVED EQUAL.
EQUIPMENT SHALL BE INSTALLED WITH ALL REQUIRED
WIRING, TERMINATIONS, AND APPURTENANCES AS
REQUIRED FOR A COMPLETE AND FULLY FUNCTIONAL
SYSTEM.
PME ENCLOSURE "PME-LS-101-1" WITH SE 8244 POWER
METER, OR APPROVED EQUAL, NETWORK SWITCH, AND
ALL REQUIRED APPURTENANCES OF EACH ATS. EXTEND
POWER CIRCUIT FROM EXISTING METERING SYSTEM
PANEL. REFERENCE SPECIFICATION 251010 FOR
ADDITIONAL INFORMATION.
CONTINUE TO LOCAL METERING SYSTEM PANEL.
REFERENCE SHEET 101E-107 FOR ADDITIONAL
INFORMATION.
AREA OF WORK
KEY PLAN
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT
IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
231 SF
P5F-107
ELEC. PANEL
231 SF
P5F-107
ELEC. PANEL
SWBD: 103_NH103DP1
SWBD: 103_EH103DP2
ATS-LS-103
BLDG 103 - RM PF5-107 - ENLARGED
ELECTRICAL PLANS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
P5F-107
0' 1' 2' 4'
103-P-01
PROJECT
NORTH
PROJECT
NORTH
ATS-EQ-103
1 BLDG 103 - RM PF5-107 - ENLARGED ELECTRICAL DEMOLITION PLAN
1/2" = 1'-0"103E-102
SWBD: 103_NH103DP1
SWBD: 103_EH103DP2
ATS-LS-103 ATS-EQ-103
103-P-02
103-C-01
0' 1' 2' 4'
PROJECT
NORTH
2 BLDG 103 - RM PF5-107 - ENLARGED ELECTRICAL PLAN
1/2" = 1'-0"103E-102
LOCAL METERING
BOX
103E-402
GENERAL NOTES
KEY NOTES
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 103ED603 & 103EP603 FOR
ADDITIONAL INFORMATION.
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 103ED601 & 103EP601 FOR
ADDITIONAL INFORMATION.
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 103ED604 & 103EP604 FOR
ADDITIONAL INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 103ED603 & 103EP603 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 103EP601 & 103ED601 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. PROVIDE INTEGRAL
COMMUNICATION MODULE INTERIOR TO ATS, ASCO #5170,
OR APPROVED EQUAL. PROVIDE CT'S AND VOLTAGE
CONNECTIONS INTERIOR TO ATS AND CABLE TO NEW SE
8244 POWER METER ENCLOSURE, OR APPROVED EQUAL.
EQUIPMENT SHALL BE INSTALLED WITH ALL REQUIRED
WIRING, TERMINATIONS, AND APPURTENANCES AS
REQUIRED FOR A COMPLETE AND FULLY FUNCTIONAL
SYSTEM.
REPLACE EXISTING RUSSELL ATS CONTROLLER WITH
RUSSELL RPTCS CONTROLLER. PROVIDE ALL HARDWARE,
PROGRAMMING, CONNECTIONS, AND APPURTENANCES AS
REQUIRED.
PME ENCLOSURE "PME-LS-103" WITH SE 8244 POWER
METER, OR APPROVED EQUAL, NETWORK SWITCH, AND
ALL REQUIRED APPURTENANCES OF EACH ATS. EXTEND
POWER CIRCUIT FROM EXISTING METERING SYSTEM
PANEL. REFERENCE SPECIFICATION 251010 FOR
ADDITIONAL INFORMATION.
LOCAL PME METERING BOX; COORDINATE WITH
MANUFACTURER FOR EXACT CABLING AND TERMINATION
REQUIREMENTS.
AREA OF WORK
KEY PLAN
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT
IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
103-C-02
FS
a
TYP.
JGD/JRB
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
BLDG 105 - ENLARGED
ELECTRICAL PLANS
a L1E a L1 aL1E a L1E a L1aL1E
PULL BOX
TRANSFORMER "T-118"
(BELOW)
PANEL:105-DEH1
PANEL:105_DEL1
PULL
BOX
UNIT HEATER
ON CEILING
ENVIRONMENTAL
CONTROL PANEL
105_MCC-1
DDC PANEL (CP7 COOLING TOWER)
STARTERS
(ABOVE)
FAN
FAN (DOOR-MOUNTED)
EXISTING SPARE
CONDUIT
PUMP P-11
GUTTER
PUMP P-10
PUMP P-09
PULL BOX
TRANSFORMER "T-118"
(BELOW)
PANEL:105-DEH1
PANEL:105_DEL1
PULL
BOX
UNIT HEATER
ON CEILING
ENVIRONMENTAL
CONTROL PANEL
DDC PANEL (CP7 COOLING TOWER)
STARTERS
(ABOVE)
FAN
EXISTING SPARE
CONDUIT
PUMP P-11PUMP P-10PUMP P-09
1 BLDG 105 - ENLARGED LIGHTING DEMOLITION PLAN
SCALE : 1/2'' = 1'-0"105ED101
2 BLDG 105 - ENLARGED LIGHTING PLAN
SCALE : 1/2'' = 1'-0"105EP101
0' 1' 2' 4'
PROJECT
NORTH
0' 1' 2' 4'
PROJECT
NORTH
105E-401a
BLDG 105
BLDG 41
BLDG 16
BLDG 6
BLDG T-51
BLDG
BLDG 101
BLDG 100
BLDG 102
BLDG 103
BLDG 104
GENERAL NOTES
KEY NOTES
DEMOLISH EXISTING LIGHT FIXTURES AND ASSOCIATED
LIGHT SWITCHES. DEMOLISH ALL ASSOCIATED CONDUITS
AND CABLING BACK TO SOURCE.
UTILIZE EXISTING LIGHTING CIRCUIT TO POWER AND
CONTROL NEW LUMINAIRES AND LIGHT SWITCH. PROVIDE
CONDUIT AND WIRE AS REQUIRED. CONTRACTOR SHALL
PROVIDE LUMINAIRE MOUNTING HARDWARE AS REQUIRED;
COORDINATE MOUNTING WITH EXISTING CONDITIONS.
AREA OF WORK
gmsfgnsfg
PROJECT
NORTH
KEY PLAN
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT
IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
FS
J J
JGD/JRB
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
BLDG 105 - ENLARGED
ELECTRICAL PLANS
PULL BOX
TRANSFORMER "T-118"
(ABOVE)
PANEL:105-DEH1
PANEL:105_DEL1
PULL
BOX
UNIT HEATER
ON CEILING
ENVIRONMENTAL
CONTROL PANEL
105_MCC-1
PUMP P-11
DDC PANEL (CP7 COOLING TOWER)
STARTERS
(BELOW)
GUTTER
FAN
FAN (DOOR-MOUNTED)
PUMP P-10
PUMP P-09
E85 FUEL DISPENSARY FEEDEREXISTING SPARE
CONDUIT
FIRE ALARM JUNCTION BOX
FIRE ALARM JUNCTION BOX
105-S-01
105-FA-03
105-P-01
105-P-08B
105-P-07B
105-P-06B
105-FA-02
105-FA-02
105-FA-02
105-P-11
1 BLDG 105 - ENLARGED ELECTRICAL DEMOLITION PLAN
SCALE : 1/2'' = 1'-0"105ED101
2 BLDG 105 - ENLARGED ELECTRICAL PLAN
SCALE : 1/2'' = 1'-0"105EP101
105-FA-01
PULL BOX
TRANSFORMER "T-118"
(ABOVE)
PANEL:105-DEH1
PANEL:105_DEL1
PULL
BOX
UNIT HEATER
ON CEILING
ENVIRONMENTAL
CONTROL PANEL
PUMP P-11
STARTERS
(BELOW)
FAN
PUMP P-10
PUMP P-09
JUNCTION BOX
"JB-DDC"
GUTTER
0' 1' 2' 4'
PROJECT
NORTH
0' 1' 2' 4'
PROJECT
NORTH
FAN (DOOR-MOUNTED)
105E-401b
BLDG 105
BLDG 41
BLDG 16
BLDG 6
BLDG T-51
BLDG
BLDG 101
BLDG 100
BLDG 102
BLDG 103
BLDG 104
GENERAL NOTES
KEY NOTES
EXISTING MOTOR CONTROL CENTER "105_MCC-1" SHALL
BE DEMOLISHED. PRESERVE INCOMING SOURCE FEEDER
FOR REUSE.
EXISTING DDC CONTROL PANEL ENCLOSURE TO BE
REUSED AS A JUNCTION BOX. EXTEND CONDUIT AND WIRE
TO MODULAR BUILDING ELECTRICAL ROOM. REFERENCE
ELECTRICAL ROOM FLOOR PLAN AND ONE-LINE DIAGRAM
FOR ADDITIONAL INFORMATION.
EXISTING CONDUIT AND WIRE TO BE MODIFIED.
REFERENCE SHEET 105E-401c FOR ADDITIONAL
INFORMATION.
EXISTING E85 FUEL DISPENSARY CONDUIT AND WIRE TO
BE DEMOLISHED BACK TO SOURCE.
PROVIDE JUNCTION BOX "JB-MER" AND INSULATED TAPS
TO EXTEND EXISTING CONDUIT AND WIRE TO
PANELBOARD "P-105" AS SHOWN. REFERENCE ONE-LINE
DIAGRAM ON SHEET 105EP601 FOR ADDITIONAL
INFORMATION.
EPO PUMP PANEL. EPO SWITCHES "EPO-P-09", "EPO-P-10",
AND "EPO-P-11" SHALL BE DOOR MOUNTED ON PANEL.
PROVIDE PLEXI GLASS COVER TO ENSURE FALSE
TRIPPING DOES NOT OCCUR. PROVIDE ID PLACARD PER
SPECIFICATIONS. EPO SWITCH SHUNT TRIP PUMP FEEDER
CIRCUIT BREAKERS LOCATED IN PANEL "P-105".
CONDUIT TO BE UTILIZED FOR FIRE ALARM AND FEEDER
TO BUILDING 105 MODULAR BUILDING "ELECTRICAL ROOM".
REFERENCE MODULAR BUILDING ELECTRICAL ROOM
FLOOR PLANS AND ONE-LINE DIAGRAM FOR ADDITIONAL
INFORMATION.
PROVIDE JUNCTION BOX AS NEEDED. EXTEND TO
EXISTING SPARE FIRE ALARM FIELD DEVICE CONDUIT.
REFERENCE SHEET 105EP101 FOR ADDITIONAL
INFORMATION.
AREA OF WORK
gmsfgnsfg
PROJECT
NORTH
KEY PLAN
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT
IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
CONTINUE FROM SHEET 105EP101
E-506
"ELECTRICAL ROOM".
$b L1 a 105A-1
W1E b
105A-3 a
L1E a 105A-1
HVAC UNIT
105-ER-HV-01
PANELBOARD
"105A"
TRANSFORMER
"TX-105A"
PANELBOARD
"P-105"
UNISTRUT, TYP
COOLING TOWER #3 VFD
COOLING TOWER #1 VFD
HVAC UNIT
105-ER-HV-01
PANELBOARD
"105A"
TRANSFORMER
"TX-105A"
PANELBOARD
"P-105"
DDC PANEL
COOLING TOWER #2 VFD
FIRE ALARM
JUNCTION BOX
PUMP "P-10" VFD
PUMP "P-9" VFD
PUMP "P-11" VFD
FSTJ
FS
UNISTRUT, TYP
COOLING TOWER #3 VFD
COOLING TOWER #1 VFD
HVAC UNIT
105-ER-HV-01
PANELBOARD
"105A"
TRANSFORMER
"TX-105A"
T
PANELBOARD
"P-105"
DDC PANEL
105A-7
WP
105-C-06105-C-01105-C-02
105-P-09
105-C-03
105-P-05B105-P-10
105-P-03B
105-P-03A
105-P-04B
105-P-04A
COOLING TOWER #2 VFD
J
FIRE ALARM
JUNCTION BOX
105-FA-03
105-FA-02
105-C-05
105-C-04
105-P-06B
105-P-06A
105-P-07A
105-P-07B
PUMP "P-10" VFD
PUMP "P-9" VFD
PUMP "P-11" VFD
105-FA-02
105-P-05A
105-P-02B
105-P-02A
105-P-08A 105-P-08B
105A-5
105A-5
105A-5
105A-2
105-S-01
105A-7
WP
105-P-01
1 BLDG 105 - MODULAR BUILDING "ELECTRICAL ROOM" ENLARGED LIGHTING PLAN
SCALE : 1" = 1'-0"
0" 1' 2'
BLDG 105
BLDG 41
BLDG 16
BLDG 6
BLDG T-51
BLDG
BLDG 101
BLDG 100
BLDG 102
BLDG 103
BLDG 104
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
BLDG 105 - ENLARGED ELECTRICAL
PLANS
105EP101
0.5'
PROJECT
NORTH
2 BLDG 105 - MODULAR BUILDING "ELECTRICAL ROOM" ENLARGED ELECTRICAL PLAN
SCALE : 1" = 1'-0"
0" 1' 2'
105EP101
0.5'
PROJECT
NORTH
105E-401c
GENERAL NOTES
KEY NOTES
CONTINUE TO EMERGENCY POWER OFF ENCLOSURE IN
BUILDING 105. REFERENCE SHEETS 105EP101 AND
105E-401b FOR ADDITIONAL INFORMATION.
CONTINUE TO JUNCTION BOX "JB-MER" IN BUILDING 105.
REFERENCE SHEETS 105EP101 AND 105E-401b FOR
ADDITIONAL INFORMATION.
CONTINUE TO COOLING TOWER DISCONNECTS.
REFERENCE SHEET 105EP101 FOR ADDITIONAL
INFORMATION.
CONTINUE TO FIRE ALARM JUNCTION BOX IN BUILDING 105.
REFERENCE SHEETS 105EP101 AND 105E-401b FOR
ADDITIONAL INFORMATION.
CONTINUE TO JUNCTION BOX "JB-DDC" IN BUILDING 105.
REFERENCE SHEETS 105EP101 AND 105E-401b FOR
ADDITIONAL INFORMATION.
CONTINUE TO PUMPS "P-9", "P-10", AND "P-11" IN BUILDING
105. REFERENCE SHEETS 105EP101 AND 105E-401b FOR
ADDITIONAL INFORMATION.
AREA OF WORK
gmsfgnsfg
PROJECT
NORTH
KEY PLAN
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT
IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
7. REFERENCE ONE-LINE DIAGRAM SHEETS 105ED601 AND
105EP601 FOR ADDITIONAL INFORMATION.
E-509
1B E-509
1C E-509
1D E-509
1A E-509
E-507
E-507
E-507
105A-1
105A-3
105A-1
.0
0"
112.00" 33.69" 71.94"
RACK 4 SLOT 1
PLC POWER SUPPLY
BME XBP 1002
G
CB20CB20
REDUNDANT
PLC CPU
GENERAL NOTES
KEY NOTES
2 REVISED OHSU REDUNDANT GENERATOR CONTROL PANEL ELEVATIONS
NTS
1 REVISED MASTER CONTROL PANEL ELEVATIONS
EXISTING HMI TOUCHSCREEN TO BE DEMOLISHED AND
REPLACED WITH REPLACEMENT HMI TOUCHSCREEN (15")
SCHNEIDER-ELECTRIC #HMIDT732 AS SHOWN.
EXISTING PLC CPU TO BE DEMOLISHED AND REPLACED
WITH REPLACEMENT PLC CPU SCHNEIDER-ELECTRIC
#BME-H58-2040 AS SHOWN.
EXISTING RELAY OUTPUT CARD TO BE DEMOLISHED AND
REPLACED WITH REPLACEMENT CARD
SCHNEIDER-ELECTRIC #BMX-DRA-1605 AS SHOWN.
REDUNDANT CPU, SCHNEIDER-ELECTRIC #BME-H58-2040 TO
BE INSTALLED.
RACK POWER SUPPLY, SCHNEIDER-ELECTRIC
#BMX-CPS-4002 TO BE INSTALLED.
6 SLOT RACK BACKPLANE, SCHNEIDER-ELECTRIC
#BME-XBP-0602 TO BE INSTALLED.
2 3
FRONT ELEVATION BACKPANEL ELEVATION
NTS
FRONT ELEVATION OHSU POWER SCHEMATIC OHSU NETWORK DIAGRAM
100E-4000b
100E-400d
5 6 BLANK SLOT, TYP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
ELECTRICAL DETAILS
1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE
CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE
ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
2. MAKE ALL CONNECTIONS TO EQUIPMENT PER
REQUIREMENTS.
3. PRIOR TO EQUIPMENT PROCUREMENT, CONTRACTOR
SHALL PROVIDE DETAILED AND DIMENSIONED SHOP
DRAWINGS INDICATING PROPOSED EQUIPMENT LAYOUT
FOR ALL ELECTRICAL EQUIPMENT INSTALLATIONS DURING
THE SUBMITTAL PROCESS FOR VA AND ENGINEER REVIEW
AND APPROVAL.
4. ALL EQUIPMENT SHALL BE PROVIDED WITH ALL CABLES,
CONNECTIONS, SOFTWARE, PROGRAMMING, AND
APPURTENANCES AS REQUIRED TO PROVIDE A FULLY
FUNCTIONAL SYSTEM.
E-501
6.00" 31.44"
.2
0"
3.50"
35.40"6.00"35.40" 35.40"
.2
0"
3.50"
.0
0"
.0
0"
GENERAL NOTES
KEY NOTES
SCALE : 1" : 1'-0"
1 UNIT SUBSTATIONS USNW AND USS2 ACTIVE HARMONIC FILTER ELEVATION DETAIL UNIT SUBSTATION USCP ACTIVE HARMONIC FILTER ELEVATION DETAIL
SCALE : 1" : 1'-0"
CONDUIT, TYP
300A, 480V ACTIVE HARMONIC FILTER,
SCHNEIDER ELECTRIC MODEL
#NHA5990600, OR APPROVED EQUAL,
TYPICAL
CONDUIT, TYP
300A, 480V ACTIVE HARMONIC FILTER,
SCHNEIDER ELECTRIC MODEL
#NHA5990600, OR APPROVED EQUAL
120A, 480V ACTIVE HARMONIC FILTER,
SCHNEIDER ELECTRIC MODEL
#NHA5990200, OR APPROVED EQUAL
100E-400f100E-400b 100E-400e
EXISTING FLOOR EXISTING FLOOR
22" DEPTH, TYP
22" DEPTH, TYP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
ELECTRICAL DETAILS
1 HOUSEKEEPING PAD, CONCRETE WITH CHAMFERED EDGE,
3-1/2"H, EXTEND PAD 3" BEYOND EQUIPMENT FOOT PRINT.
PROVIDE 5000-PSI CONCRETE WITH #4 REBAR, 12" OC;
REBAR SHALL BE TIED. COORDINATE REBAR INSTALLATION
WITH CONDUIT INSTALLATIONS AS REQUIRED.
EXISTING SWITCHBOARD WITH MAIN INCOMING LUGS AND
ANALOG METERING. PROVIDE FIELD MODIFICATIONS AS
REQUIRED TO REPLACE INCOMING LUGS AND ANALOG
METERING WITH MAIN CIRCUIT BREAKER AND INTEGRAL
POWER METER (SE 8244), RESPECTIVELY. MODIFIED
EQUIPMENT SHALL BE RE-CERTIFIED BY UL FIELD
ENGINEERS AS REQUIRED. COORDINATE SHUTDOWN AND
RE-CERTIFICATION WITH VA.
3", TYP
EQUIPMENT ID PLACARD, TYP
1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE
CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE
ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
2. MAKE ALL CONNECTIONS TO EQUIPMENT PER
REQUIREMENTS.
3. PRIOR TO EQUIPMENT PROCUREMENT, CONTRACTOR
SHALL PROVIDE DETAILED AND DIMENSIONED SHOP
DRAWINGS INDICATING PROPOSED EQUIPMENT LAYOUT
FOR ALL ELECTRICAL EQUIPMENT INSTALLATIONS DURING
THE SUBMITTAL PROCESS FOR VA AND ENGINEER REVIEW
AND APPROVAL.
4. ALL EQUIPMENT SHALL BE PROVIDED WITH ALL CABLES,
CONNECTIONS, SOFTWARE, PROGRAMMING, AND
APPURTENANCES AS REQUIRED TO PROVIDE A FULLY
FUNCTIONAL SYSTEM.
5. NOT ALL RACEWAYS AND CONDUCTORS MAY BE SHOWN
FOR CLARITY. REFERENCE ASSOCIATED FLOOR PLAN OR
CONDUIT AND WIRE SCHEDULE FOR ADDITIONAL
INFORMATION.
EQUIPMENT ID PLACARD, TYP
3", TYP
E-502
TYPICAL INSULATED TAP CONNECTORS DETAIL
NTS
CLEAR INSULATED TAP CONNECTOR, ILSCO ECTS SERIES CLEAR INSULATED TAP CONNECTOR, ILSCO ECTD SERIES
CLEAR INSULATED TAP CONNECTOR, ILSCO ECT SERIES
DETAIL NOTE(S):
1. CLEAR INSULATED-TAP CONNECTORS UTILIZED FOR LOW-VOLTAGE POWER FEEDERS SHALL BE
ILSCO OR APPROVED EQUAL. PROVIDE QUANTITIES AND SIZES AS REQUIRED.
BUILDING 100 SWITCHBOARD "5SDEC-E-17" PHOTO DETAIL
NTS
BUILDING 100 SWITCHBOARD "2SDN-D-17" PHOTO DETAIL
NTS
-100E-405 100E-402a
2 2
GENERAL NOTES
KEY NOTES
1 SUBSTATION USCL SWITCHGEAR ELEVATION
NTS
2 SUBSTATION USNW SWITCHGEAR ELEVATION
NTS
3 SUBSTATION USCP SWITCHGEAR ELEVATION
NTS
4 SUBSTATION USS2 SWITCHGEAR ELEVATION
100E-400b NTS
PROVIDE DRAWOUT CIRCUIT BREAKER FOR ACTIVE
HARMONIC FILTER EQUIPMENT IN EMPTY SWITCHGEAR
BUCKET, 800A/3P, LSIG. EXISTING DRAWOUT SWITCHGEAR
IS SQUARE-D POWER ZONE II. EXISTING DRAWOUT
CIRCUIT BREAKER MODELS ARE OF TYPE SQUARE-D
DS416.
EXISTING CIRCUIT BREAKERS TO BE REPLACED WITH
TYPE SE MASTERPACK MTZ OR APPROVED EQUAL.
REFERENCE ONE-LINE DIAGRAMS ON SHEETS 100ED601 &
100EP601 FOR ADDITIONAL INFORMATION.
EXISTING CIRCUIT BREAKERS TO BE REPLACED WITH
TYPE SE MASTERPACK MTZ OR APPROVED EQUAL.
REFERENCE ONE-LINE DIAGRAMS ON SHEETS 100ED610 &
100EP610 FOR ADDITIONAL INFORMATION.
EXISTING CIRCUIT BREAKERS TO BE REPLACED WITH
TYPE SE MASTERPACK MTZ OR APPROVED EQUAL.
REFERENCE ONE-LINE DIAGRAMS ON SHEETS 100ED605 &
100EP605 FOR ADDITIONAL INFORMATION.
EXISTING CIRCUIT BREAKERS TO BE REPLACED WITH
TYPE SE MASTERPACK MTZ OR APPROVED EQUAL.
REFERENCE ONE-LINE DIAGRAMS ON SHEETS 100ED615 &
100EP615 FOR ADDITIONAL INFORMATION.
SPACE, TYP.
SPACE, TYP.
SPACE, TYP.
SPACE, TYP.
100E-400f
100E-4000d 100E-400e
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
ELECTRICAL DETAILS
1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE
CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE
ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
2. MAKE ALL CONNECTIONS TO EQUIPMENT PER
MANUFACTURER'S REQUIREMENTS.
3. ALL EQUIPMENT SHALL BE PROVIDED WITH ALL CABLES,
CONNECTIONS, SOFTWARE, PROGRAMMING, AND
APPURTENANCES AS REQUIRED TO PROVIDE A FULLY
FUNCTIONAL SYSTEM.
E-503
PROVIDE NETWORK SWITCH WITH CONTROL POWER
TRANSFORMER (CPT) LOCATED INTERIOR TO EXISTING UNIT
SUBSTATION POWER METER CUBICLE; CPT SHALL USE
SUBSTATION AS SOURCE. PROVIDE DATA CABLES FROM
REPLACEMENT UNIT SUBSTATION CIRCUIT BREAKERS TO
NETWORK SWITCH; REFERENCE PLANS FOR ADDITOINAL
DATA CONNECTION REQUIREMENTS. PROVIDE CAT6A
CABLING FROM NETWORK SWITCH TO EXTEND TO LOCAL PME
ENCLOSURE NETWORK SWITCH. PROVIDE PROGRAMMING
AND INTEGRATION FOR ALL DEVICE STATUS / DATA TO
TRANSMIT AND BE VIEWABLE ACROSS EXISTING FACILITY PME
NETWORK.
2 SUBSTATION US103 SWITCHGEAR ELEVATION
NTS
GENERAL NOTES
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
ELECTRICAL DETAILS
1 SUBSTATION US101 SWITCHGEAR ELEVATION
NTS
1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE
CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE
ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
2. MAKE ALL CONNECTIONS TO EQUIPMENT PER
MANUFACTURER'S REQUIREMENTS.
3. ALL EQUIPMENT SHALL BE PROVIDED WITH ALL CABLES,
CONNECTIONS, SOFTWARE, PROGRAMMING, AND
APPURTENANCES AS REQUIRED TO PROVIDE A FULLY
FUNCTIONAL SYSTEM.
E-504
NTS
NTS
SUBSTATION USS1 SWITCHGEAR ELEVATION4EXISTING BUILDING 100 DELAYED EQUIPMENT FEEDER PHOTO DETAIL
1 EXISTING RACEWAYS AND CONDUCTORS SERVING EMERGENCY
SOURCE LINE SIDE OF DELAYED EQUIPMENT
AUTOMATIC TRANSFER SWITCHES. EXISTING RACEWAYS TO
REMAIN; DEMOLISH EXISTING CONDUCTORS. PROVIDE AND
EXTEND NEW CONDUCTORS THROUGH EXISTING RACEWAYS AND
NEW JUNCTION BOX(ES) TO SERVE EACH ATS FROM
SWITCHBOARD "100-DEWSBD-G-1". EXTEND EXISTING RACEWAYS
AND AND PROVIDE PULLBOX(ES), SIZED PER NEC, AS REQUIRED.
REFERENCE ONE-LINE DIAGRAM ON SHEETS 100ED601 AND
100EP601 FOR ADDITIONAL INFORMATION.
EXISTING CIRCUIT BREAKERS TO BE REPLACED WITH
TYPE SE MASTERPACK MTZ OR APPROVED EQUAL. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 101ED602 & 101EP602 FOR
ADDITIONAL INFORMATION.
EXISTING CIRCUIT BREAKERS TO BE REPLACED WITH
TYPE SE MASTERPACK MTZ OR APPROVED EQUAL. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 103ED601 & 103EP601 FOR
ADDITIONAL INFORMATION.
EXISTING CIRCUIT BREAKERS TO BE REPLACED WITH
TYPE SE MASTERPACK MTZ OR APPROVED EQUAL. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 100ED620 & 100EP620 FOR
ADDITIONAL INFORMATION.
100E-4000c
101E-107 103E-102
100E-4000a
PROVIDE NETWORK SWITCH WITH CONTROL POWER
TRANSFOMER (CPT) LOCATED INTERIOR TO EXISTING UNIT
SUBSTATION POWER METER CUBICLE; CPT SHALL USE
SUBSTATION AS SOURCE. PROVIDE DATA CABLES FROM
REPLACEMENT UNIT SUBSTATION CIRCUIT BREAKERS TO
NETWORK SWITCH; REFERENCE PLANS FOR ADDITOINAL
DATA CONNECTION REQUIREMENTS. PROVIDE CAT6A
CABLING FROM NETWORK SWITCH TO EXTEND TO LOCAL PME
ENCLOSURE NETWORK SWITCH. PROVIDE PROGRAMMING
AND INTEGRATION FOR ALL DEVICE STATUS / DATA TO
TRANSMIT AND BE VIEWABLE ACROSS EXISTING FACILITY PME
NETWORK.
TRANSFORMERTRANSFOMER (CPT) LOCATED INTERIOR TO EXISTING UNITTRANSFORMER
4'-0"
1'-6"
POWER RECEPTACLE
LIGHT
SWITCH
DETAIL NOTE(S):
1. DETAIL SHOWS GENERAL MOUNTING HEIGHTS UNLESS OTHERWISE NOTED.
2.EXACT LOCATION FOR DEVICES ARE SHOWN ON PLANS.
CEILING
FINISHED
FLOOR
FIRE ALARM PULL STATION
7'-6"
FIRE ALARM VOICE
AND STROBE
GENERAL NOTES
KEY NOTES
2 GROUND TEST WELL
NTS
4 TYPICAL EXISTING METERING ENCLOSURE
NTS-
3 EXISTING BUILDING 100 ELECTRICAL RM B2D-106a PHOTO DETAIL
NTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
ELECTRICAL DETAILS
100E-4000b
1 TAP EXISTING USEM FEEDER AT JUNCTION BOX VIA MV
SPLICE KITS AND PROVIDE CONDUIT AND WIRE AS
REQUIRED TO FEED MV INTERRUPTER SWITCHES
"SW-ITR-L" AND "SW-ITR-R". REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED601 & 100EP601 FOR
ADDITIONAL INFORMATION.
1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE
CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE
ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
2. MAKE ALL CONNECTIONS TO EQUIPMENT PER
MANUFACTURER'S REQUIREMENTS.
3. PRIOR TO EQUIPMENT PROCUREMENT, CONTRACTOR
SHALL PROVIDE DETAILED AND DIMENSIONED SHOP
DRAWINGS INDICATING PROPOSED EQUIPMENT LAYOUT
FOR ALL ELECTRICAL EQUIPMENT INSTALLATIONS DURING
THE SUBMITTAL PROCESS FOR VA AND ENGINEER REVIEW
AND APPROVAL.
4. NOT ALL RACEWAYS AND CONDUCTORS MAY BE SHOWN
FOR CLARITY. REFERENCE ASSOCIATED FLOOR PLAN OR
CONDUIT AND WIRE SCHEDULE FOR ADDITIONAL
INFORMATION.
1 TYPICAL MOUNTING HEIGHT DETAILS
NTS-
E-505
GRADE REMOVABLE COVER - REINFORCED
CONCRETE - CHRISTY CONCRETE
PRODUCTS #F8D OR EQUAL
BURNDY TYPE GK CONNECTOR OR EQUAL
PRECAST CONCRETE CURB VALVE
BOX - 8 1/2" I.D. X 18" D. -CHRISTY
#F14 BOX OR EQUAL
SAND FILL
BARE SOFT-DRAWN COPPER
GROUNDING ELECTRODE
CONDUCTOR. REFERNCE PLANS
FOR WIRE SIZE AND LENGTH.
GROUND ROD, STEEL COPPER
CLAD, 3/4" DIA. X 10'-0" LONG
006E-101 016E-401
100EG101
PROVIDE 6-PORT SWITCH. PROVIDE
CAT6A FROM SWITCH TO EXISTING
POWER METER AND LOCAL
EQUIPMENT SWITCH.
PROVIDE CAT6A JUMPER
CONNECTING EXISTING
DIGITAL POWER METER TO
PROVIDE SWITCH.
EXISTING EQUIPMENT TO BE
RELOCATED AS REQUIRED TO
PROVIDE ROOM FOR 6-PORT
SWITCH.
PROVIDE CAT6A CABLING AND RACEWAY
EXTENDING TO LOCAL UNIT SUBSTATION AND / OR
AUTOMATIC TRANSFER SWITCH. REFERENCE
FLOOR PLANS AS REQUIRED.
EXISTING PME NETWORK
CABLE SHALL BE
RETERMINATED TO SWITCH AS
INDICATED.
MODIFICATION DETAILTERING ENCLOSURE
GENERAL NOTES
KEY NOTES
2 BUILDING 16 ELECTRICAL EQUIPMENT DEMOLITION PHOTO DETAIL
NTSNTS
BUILDING 16 ELECTRICAL EQUIPMENT DEMOLITION PHOTO DETAIL
4 BUILDING 105 ELECTRICAL PHOTO DETAIL
NTS
3 BUILDING 105 E85 FUEL DISPENSORY AND ACCESSORIES DEMOLITION PHOTO DETAIL
EXISTING SWITCHBOARD TO BE DEMOLISHED.
REFERENCE ONE-LINE DIAGRAM ON SHEET 016ED601 FOR
ADDITIONAL INFORMATION.
EXISTING CONDUIT AND CONDUCTORS TO BE
DEMOLISHED. REFERENCE ONE-LINE DIAGRAM ON SHEET
016ED601 FOR ADDITIONAL INFORMATION.
EXISTING TRANSFORMER, DISCONNECT AND PANEL TO BE
DEMOLISHED. REFERENCE ONE-LINE DIAGRAM ON SHEET
016ED601 FOR ADDITIONAL INFORMATION.
EXISTING E85 FUEL DISPENSARY, POS, CHAINLINK FENCE,
AND ACCESS CONTROLS SHALL BE DEMOLISHED. ALL
ASSOCIATED CONDUIT AND WIRE SHALL BE DEMOLISHED
BACK TO SOURCE.
EXISTING EPO, RECEPTACLE, AND TELEPHONE BOX SHALL
BE DEMOLISHED. ALL ASSOCIATED CONDUIT AND WIRE
SHALL BE DEMOLISHED BACK TO SOURCE.
EXISTING VEHICLE VACUUM TO BE RE-FED VIA BUILDING
105 "ELECTRICAL ROOM". REFERENCE ENLARGED PLANS
FOR ADDITIONAL INFORMATION.
EXISTING MOTOR CONTROL CENTER "105_MCC-1" AND
ASSOCIATED RACEWAYS AND CONDUCTORS TO BE
DEMOLISHED. PRESERVE INCOMING SOURCE FEEDER
FOR REUSE REFERENCE ENLARGED PLANS FOR
ADDITIONAL INFORMATION.
EXISTING DDC CONTROL PANEL ENCLOSURE. EXISTING
DDC CONTROLLER TO BE SALVAGED BY VA. EXISTING
CABLING TO BE REUSED; EXISTING ENCLOSURE TO BE
REUSED AS JUNCTION BOX. REFERENCE ENLARGED
PLANS FOR ADDITIONAL INFORMATION.
EXISTING PUMP RACEWAYS TO BE REUSED. REFERENCE
ENLARGED PLANS FOR ADDITIONAL INFORMATION.
DEMOLISH EXISTING LIGHT FIXTURES, AND ASSOCIATED
LIGHT SWITCHES. DEMOLISH ALL ASSOCIATED CONDUITS
AND CABLING BACK TO SOURCE.
TYP
NTS105ED101
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
ELECTRICAL DETAILS
1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE
CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE
ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
2. MAKE ALL CONNECTIONS TO EQUIPMENT PER
MANUFACTURER'S REQUIREMENTS.
3. PRIOR TO EQUIPMENT PROCUREMENT, CONTRACTOR
SHALL PROVIDE DETAILED AND DIMENSIONED SHOP
DRAWINGS INDICATING PROPOSED EQUIPMENT LAYOUT
FOR ALL ELECTRICAL EQUIPMENT INSTALLATIONS DURING
THE SUBMITTAL PROCESS FOR VA AND ENGINEER REVIEW
AND APPROVAL.
4. NOT ALL RACEWAYS AND CONDUCTORS MAY BE SHOWN
FOR CLARITY. REFERENCE ASSOCIATED FLOOR PLAN OR
CONDUIT AND WIRE SCHEDULE FOR ADDITIONAL
INFORMATION.
7TYP
PHOTO DETAIL 'B'PHOTO DETAIL 'A'
105E-401b
016E-401016E-401
E-506
CEILING
8'-0"
6" 6"
PANELBOARD
"P-105"
FIELD
DEVICES,
SEE PLANS
FOR
ADDITIONAL
INFORMATION
PANEL "105A"
TRANSFORMER
"TX-105A"
EQUIPMENT
ID PLACARD,
TYP.
3'-6"1'-8"
1'-8"
10'-6"
CEILING
60"
20" 4"6"12"
DDC PANEL
EQUIPMENT
ID PLACARD,
TYP.
COOLING TOWER #3 VFD
COOLING TOWER #2 VFD
COOLING TOWER #1 VFD
PUMP "P-11" VFD
PUMP "P-10" VFD
PUMP "P-9" VFD
TYPTYP
CEILING
HVAC UNIT WALL PENETRATIONS,
COORDINATE WITH BUILDING
MANUFACTURER AS REQUIRED.
HVAC UNIT, WALL-MOUNTED TO
EXTERIOR WALL
8'-0"
6"
7'-1"
3'-6"
30"
30" 8"
30"
30"
30"
30"
PROVIDE PLACARD TO
INDICATE EQUIPMENT
THAT IS METERED.
PADLOCKABLE WING KNOB
PADLOCKABLE WING KNOB
PROVIDE PLACARD TO
INDICATE EQUIPMENT
THAT IS METERED.
GENERAL NOTES
KEY NOTES
4 TYPICAL POWER METER ENCLOSURE
NTS
3 BLDG 105 - MODULAR BUILDING "ELECTRICAL ROOM" - EAST WALL ELEVATION
NOTES:
1. USE HOT-DIPPED GALVANIZED UNISTRUT AND STAINLESS
STEEL FASTENING HARDWARE FOR MOUNTING ALL
EQUIPMENT TO BUILDING 105 STRUCTURES AS REQUIRED.
NOTES:
1. USE HOT-DIPPED GALVANIZED UNISTRUT AND STAINLESS
STEEL FASTENING HARDWARE FOR MOUNTING ALL
EQUIPMENT TO BUILDING 105 STRUCTURES AS REQUIRED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
ELECTRICAL DETAILS
105E-401c SCALE: 1" = 1'-0"
1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE
CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE
ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
2. MAKE ALL CONNECTIONS TO EQUIPMENT PER
MANUFACTURER'S REQUIREMENTS.
3. PRIOR TO EQUIPMENT PROCUREMENT, CONTRACTOR
SHALL PROVIDE DETAILED AND DIMENSIONED SHOP
DRAWINGS INDICATING PROPOSED EQUIPMENT LAYOUT
FOR ALL ELECTRICAL EQUIPMENT INSTALLATIONS
DURING THE SUBMITTAL PROCESS FOR VA AND
ENGINEER REVIEW AND APPROVAL.
4. ALL EQUIPMENT SHALL BE PROVIDED WITH ALL CABLES,
CONNECTIONS, SOFTWARE, PROGRAMMING, AND
APPURTENANCES AS REQUIRED TO PROVIDE A FULLY
FUNCTIONAL SYSTEM.
5. NOT ALL RACEWAYS AND CONDUCTORS MAY BE SHOWN
FOR CLARITY. REFERENCE ASSOCIATED FLOOR PLAN OR
CONDUIT AND WIRE SCHEDULE FOR ADDITIONAL
INFORMATION.
1 BLDG 105 - MODULAR BUILDING "ELECTRICAL ROOM" - NORTH WALL ELEVATION
-105E-401c SCALE: 1" = 1'-0"
2 BLDG 105 - MODULAR BUILDING "ELECTRICAL ROOM" - SOUTH WALL ELEVATION
-105E-401c SCALE: 1" = 1'-0"
E-507
30"
30"
30"
30" 30"
30"
8"
ALL DIMENSIONS ARE MINIMUM
PS
PS
PS
PS
PM
ERMS
114.00"
91.50"
3.50"
36.00" 42.00" 36.00" 6.00"35.40"
82.20"
3.50"
6.00"
60.00"
EQUIPMENT
ID PLACARD,
TYP.
EQUIPMENT
ID PLACARD
LLI LLI
94.00"
44.25"
3.50"
EQUIPMENT
ID PLACARD
60.00"
100"
90.00"
(QTY=2) COLUMNS (QTY=2) COLUMNS
130"
EQUIPMENT ID PLACARD
GENERAL NOTES
KEY NOTES
4 SWITCHBOARD "100-DESWBD-G-1" AND USCL ACTIVE HARMONIC FILTERS ELEVATION DETAILS
SCALE: 1/2" = 1'
1 EXISTING RAISED TRANSFORMER PAD PHOTO DETAIL
3 MV INTERRUPTER SWITCHES "100-ISW-L" & "100-ISW-R" ELEVATION DETAIL
EXISTING PAD TO BE REUSED FOR TRANSFORMER "TX-DE".
EXISTING GROUND WIRE TO BE REUSED FOR
TRANSFORMER "TX-DE".
HOUSEKEEPING PAD, CONCRETE WITH CHAMFERED EDGE,
3-1/2"H, EXTEND PAD 3" BEYOND EQUIPMENT FOOT PRINT.
PROVIDE 5000-PSI CONCRETE WITH #4 REBAR, 12" OC;
REBAR SHALL BE TIED. COORDINATE REBAR INSTALLATION
WITH CONDUIT INSTALLATIONS AS REQUIRED.
SCALE: 1" = 1'-00"
CONDUIT,TYP.
2 TRANSFORMER "TX-DE" ELEVATION DETAIL
SCALE: 1" = 1'-0"
SCALE: 1" = 1'-0"
EXISTING RAISED
CONCRETE PAD
24" DEPTH
PULL SECTIONPULL SECTION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
ELECTRICAL DETAILS
100E-4000b
100E-4000b 100E-4000d
1. ALL WORK SHALL BE CLOSELY COORDINATED WITH THE
CONTRACTOR'S PHASING OF THE PROJECT. COORDINATE
ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
2. MAKE ALL CONNECTIONS TO EQUIPMENT PER
MANUFACTURER'S REQUIREMENTS.
3. PRIOR TO EQUIPMENT PROCUREMENT, CONTRACTOR
SHALL PROVIDE DETAILED AND DIMENSIONED SHOP
DRAWINGS INDICATING PROPOSED EQUIPMENT LAYOUT
FOR ALL ELECTRICAL EQUIPMENT INSTALLATIONS
DURING THE SUBMITTAL PROCESS FOR VA AND
ENGINEER REVIEW AND APPROVAL.
4. ALL EQUIPMENT SHALL BE PROVIDED WITH ALL CABLES,
CONNECTIONS, SOFTWARE, PROGRAMMING, AND
APPURTENANCES AS REQUIRED TO PROVIDE A FULLY
FUNCTIONAL SYSTEM.
5. NOT ALL RACEWAYS AND CONDUCTORS MAY BE SHOWN
FOR CLARITY. REFERENCE ASSOCIATED FLOOR PLAN OR
CONDUIT AND WIRE SCHEDULE FOR ADDITIONAL
INFORMATION.
3TYP. 300A, 480V ACTIVE HARMONIC FILTER,
SCHNEIDER ELECTRIC MODEL
#NHA5990600, OR APPROVED EQUAL,
TYP.
EXISTING FLOOR
100E-4000b
E-508
4 PROVIDE ALL REQUIRED ANCHORING AND SIESMIC
BRACING PER MANUFACTURER'S INSTRUCTIONS. ALL
HARDWARE SHALL BE STAINLESS-STEEL.
HVAC
(HVAC HEIGTH) 6"
(O
VE
R
AL
L H
EI
G
H T
H
IG
H S
ID
E)
/8
(W
AL
L H
EI
G
H T
H
IG
H S
ID
E)
12'-0"
(W
AL
L H
EI
G
H T
LO
W
S
ID
E)
6"
(O
VE
R
AL
L H
EI
G
H T
LO
W
S
ID
E)
/8
(W
AL
L H
EI
G
H T
LO
W
S
ID
E)
6"
(O
VE
R
AL
L H
EI
G
H T
LO
W
S
ID
E)
/8
(O
VE
R
AL
L H
EI
G
H T
H
IG
H S
ID
E)
/8
(W
AL
L H
EI
G
H T
H
IG
H S
ID
E)
12'-0"
8'-7"
8'-0"
(BASE HEIGHT) 6"
12" 1/2"
12" 1/2"
1 1 1
GENERAL NOTES
2 ELECTRICAL ROOM - BUILDING ELEVATIONS
NTS
1 ELECTRICAL ROOM - BUILDING ELEVATIONS
NTS
105E-401c
105E-401c
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
ELECTRICAL DETAILS
E-509
INTERIOR
1 1/2"X 3"X14GA T.S.
COVE BASE
1 1/2"X 3"X14GA T.S.
BUILDING CROSS SECTION
1-1/2"X 3"X14GA T.S.
ALL AROUND FRAME
WELDED TO BASE
1 1/2"X1 1/2"X1/8" ANGLE
MAINTAIN 1" OVERLAP
OF STEEL OVER GLASS
- ALL AROUND
SILICONE CAULK
#8-18 TEK PAN HEAD SCREWS
@ 12" TO 16" SPACING
POLYISOCYANURATE (R-16)
ALUMINUM TREAD PLATE
16GA. STEEL
NOMINAL 36" X 42" HIGH
FIXED WINDOWS
1/2"x4 1/4" WEDGE ANCHOR, 3-1/4" MINIMUM EMBEDMENT
1/8" 1-1/2" @12"
TUBE STEEL TO
C-CHANNEL
3/8" 12
PLATE TO
TUBE STEEL
3/4" T&G ADVANTEK
12-24 x 2" PHILLIPS FLAT HEAD WITH
WINGS SCREWS - 24 PER SHEET
16 GA STEEL SHEET
WELDED TO FRAME
STEEL
CEILING PANS
R-19 INSULATION
L2"x2"x1/8"TH CEILING WALL MOLD
#10 X 1 1/2" PAN HEAD
TEK SCREWS 12" O.C.
3" THICK A/A
ROOF PANEL
1/4" X 5" TEK SCREWS WITH 1/4" X 1 1/2" ZINC
SEALING WASHER (NEOPRENE) 1 PER 12"
CAULK AROUND WASHER ASSEMBLY
TOP PLATE 1-1/2"X 3"X3/16"
TUBE STEEL
16 GA STEEL SHEET
WELDED TO FRAME
#12 x 1-1/4" TEK SCREW
L1-1/2"x1-1/2"x1/8" ROOF PANEL TRIM
3"x3"x1/4" ANGLE
WELD TO C-CHANNEL 1/8"
16GA. STEEL
1-1/2" GRABBER SCREW W/COUNTER
SINK BIT - 24 PER SHEET
EXTERIOR
ELITE E GUTTER
R-16 POLYISOCYANURATE INSULATION
20GA STEEL SHEET
#12x1 1/4" TEK SCREW W/
STEEL/NEOPRENE WASHER
SPACED 12" O.C.
CAULK AROUND
TEK SCREW
1 1/2" X3" X14 GA.TUBE
STEEL ACTS
AS WINDOW SILL AND
HEADER
TYPICAL WELDED
FRAMING SECTION
1 1/2" X 3" X 14 GA. TUBE STEEL
AT EVERY CORNER TO ATTACH
INTERIOR SKINS (TYPICALLY 14 GA.)
1 1/2" X3" TUBE STEEL
ALONG PERIMETER
WALLS TYPICALLY
INSULATED WITH
2 7/8" POLYSTYRENE FOAM
TYP 14GA
INTERIOR
WELD TO BASE
(TYP)
1/16" 1@12
TYP 14GA
EXTERIOR 1/16" 1@12
1 1/2"X3"X14 GA. TUBE STEEL
AT EACH CORNER
3"X3"X14 GA. TUBE STEEL
IN CORNERS
EAST ELEVATIONA SOUTH ELEVATIONB WEST ELEVATIONC NORTH ELEVATIOND
1. PRE-ASSEMBLED WELDED STEEL BUILDING SHALL BE BY
PANEL BUILT INCORPORATED, OR EQUAL. BUILDING SHALL
BE PRE-ENGINEERED AND REVIEWED AND STAMPED BY A
PROFESSIONAL ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL FASTENING HARDWARE,
ANCHORING, AND SEISMIC BRACING REQUIRED FOR A
COMPLETE AND FUNCTIONAL INSTALLATION. INSTALLATION
SHALL ADHERE TO ALL BUILDING MANUFACTURER
RECOMMENDATIONS AND REQUIREMENTS.
3. FOR ADDITIONAL REQUIREMENTS, REFERENCE
SPECIFICATIONS 13 34 19, 13 05 41, AND 08 71 00.
KEY NOTES
BARD HVAC UNIT "105-ER-HV-01". REFERENCE MECHANICAL
EQUIPMENT SCHEDULE ON SHEET 105EP701 FOR
ADDITIONAL INFORMATION.
BUILDING 101
UNIT SUB
500 MCM
500 MCM, 600 V. THW
H.V. FEEDER, #2 GND.
MH-HV-1
500 MCM (TYP.)
ACCESSIBLE
CONNECTION
GROUND WELL
SEE DRAWING
101-E2 FOR
LOCATION OF
GROUND RODS
L,6 & 6
500 MCM
A&17
DELETE P-343
500 MCM
3/0
3/0
500 MCM
SEE DRAWING 100-E19
FOR LOCATIONS OF
GROUND RODS
500 MCM
SEE DRAWING 100-E10
FOR LOCATIONS OF
GROUND RODS
A&15
500 MCM
500 MCM, 600V, THW
H.V. FEEDER, #2 GND,
SERVICE GROUND BUS
WITHIN ENERGY CENTER
"B2D-127"
WATER
SERVICE MAIN
500 MCMMH-HV-2
MH-HV-3
F&5
SPRINKLER
SERVICE MAIN
500 MCM, 600V. THW
H.V. FEEDER, #1 GND.
UNIT SUB
"USNW" GROUND BUS
F&3
500 MCM
UNIT SUB
"USCP" GROUND BUS
500 MCM
G&3
500 MCM
500 MCM
G&3
500 MCM HV FEEDER, #1 GND.
500 MCM HV FEEDER, #1 GND.
UNIT SUB
"USCL" GROUND BUS
500 MCM H.V. FEEDER, #1 GND.
500 MCM (TYP.)
SEE DRAWING 100-E151 FOR
LOCATIONS OF GROUND RODS
500 MCM (TYP.)
MH-HV-4
MH-HV-5
MH-HV-3
EXISTING BUILDING 102
PADMOUNT TRANSFORMER.
VERIFY LOCATION OF SERVICE
GROUND CONNECTION IN FIELD.
1/8" x 2" x 6" GROUND BAR
GEN #5 GEN #4 GEN #3
500 MCM ACCESSIBLE CONNECTION
IN GROUND WELL
500 MCM
250 MCM NEUTRAL
GROUNDING CONDUCTOR
GROUND BUS B2-GEN-SD-G5
250 MCM GROUND, SEE
FEEDER SCHEDULE ON
DRAWING 100-E159
GEN #2 GEN #1
250 MCM NEUTRAL
GROUNDING
CONDUCTOR
SEE DRAWING 100-E152 FOR
LOCATIONS OF GROUND RODS
UNIT SUB
"USS2" GROUND BUS
500 MCM HV
FEEDER, #2 GND.
UNIT SUB
"USS1" GROUND BUS
UNIT SUB "US103"
GROUND BUS 500 MCM H.V FEEDER, #1 GND
500 MCM H.V FEEDER, #1 GND
OLD SWITCHGEAR
"RM B1D-108"
500 MCM
250 MCM
GENERATOR SWGR
TRANSFORMER
"T-16"
BUILDING 6 SERVICE
EQUIPMENT
TRANSFORMER
"T-6"
BUILDING 16 SERVICE
EQUIPMENT
BUILDING 105 SERVICE
EQUIPMENT
BUILDING 105 "ELECTRICAL ROOM"
SERVICE EQUIPMENT BLDG 108
(PARKING GARAGE)
RM 201
GROUND ROD
WITH TEST WELL
GROUND ROD
WITH TEST WELL
006-G-01 016-G-01
GROUND ROD
WITH TEST WELL
100-G-01
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. GROUNDING ONE-LINE DIAGRAM SHOWN IS
DIAGRAMATICAL; NOT ALL GROUNDING CONNECTIONS ARE
SHOWN FOR CLARITY. DIAGRAM IS BASED ON AVAILABLE
FACILITY AS-BUILTS AND ON-SITE INVESTIGATION.
3. FACILITY WIDE GROUND RESISTANCE TESTING PER VHA
DIRECTIVE 1028-8.J(6)(e). REFERENCE GROUNDING
SPECIFICATION 26 05 26 FOR ADDITIONAL INFORMATION.
MAIN BONDING JUMPER
GROUND CONNECTION FROM SERVICE GROUND BUS TO BUILDING STEEL,
(ACCESSIBLE) AT GRID COORDINATES INDICATED, BY EXOTHERMIC PROCESS.
CONNECTION TO 8" WATER SERVICE MAIN AND SPRINKLER SERVICE MAIN PIPES
ON B-2 LEVEL AT APPROXIMATE GRID COORDINATES "N &…