Attachment 8-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 6.pdf

PDF 4 MB Posted

Attached to
Z2DA--CON-NRM 648-20-119 Correct Electrical FCA Deficiencies (Portland)
Solicitation number
36C26025R0071
Issued by

About this file

This document is a detailed electrical one-line diagram for multiple buildings at the VA Portland Health Care System, part of a project to correct electrical facility condition assessment (FCA) deficiencies. The diagrams cover Buildings 101, 102, 103, 104, 105, and 006, providing comprehensive electrical distribution system layouts including switchboards, transformers, panelboards, motor control centers, and associated circuit breakers and connections.

The diagrams indicate a systematic approach to electrical system documentation, with each building's diagram showing detailed electrical infrastructure including voltage levels (primarily 480V and 208V), specific equipment manufacturers (predominantly Square D and Cutler-Hammer), and interconnections between various electrical components. Key notes consistently emphasize contractor responsibilities such as field verification of existing conditions, providing shutdown and power plans, and referencing specific schedules for overcurrent protective device replacements and adjustments. The project number 648-20-119 is consistently referenced, with an issue date of 01/31/2025, and the documents are marked as "Construction Documents" and "Fully Sprinklered".

View the file

Other files

File Type Posted
36C26025R0071 0005.docx DOCX document
36C26025R0071 0004.docx DOCX document
F-103-1-TJC-Fire Life Safety - Bldg.103-1.pdf PDF
36C26025R0071 0003.pdf PDF
F-104-2-TJC-Fire Life Safety - Bldg.104-2.pdf PDF
F-104-P2-TJC-Fire Life Safety - Bldg.104-P2.pdf PDF
F-104-R-TJC-Fire Life Safety - Bldg.104-R.pdf PDF
36C26025R0071 0002.docx DOCX document
F-104-1-TJC-Fire Life Safety - Bldg.104-1.pdf PDF
F-104-P3-TJC-Fire Life Safety - Bldg.104-P3.pdf PDF
F-16-2-TJC-Fire Life Safety - Bldg.16-2.pdf PDF
F-6-2-TJC-Fire Life Safety - Bldg.6-2.pdf PDF
F-103-P3-TJC-Fire Life Safety - Bldg.103-P3.pdf PDF
F-103-P5-TJC-Fire Life Safety - Bldg.103-P5.pdf PDF
F-103-R-TJC-Fire Life Safety - Bldg.103-R.pdf PDF
F-6-3-TJC-Fire Life Safety - Bldg.6-3.pdf PDF
F-103-P4-TJC-Fire Life Safety - Bldg.103-P4.pdf PDF
F-16-B-TJC-Fire Life Safety - Bldg.16-B.pdf PDF
F-103-P2-TJC-Fire Life Safety - Bldg.103-P2.pdf PDF
36C26025R0071 0001.pdf PDF
F-16-R-TJC-Fire Life Safety - Bldg.16-R.pdf PDF
F-16-1-TJC-Fire Life Safety - Bldg.16-1.pdf PDF
F-103-2-TJC-Fire Life Safety - Bldg.103-2.pdf PDF
F-6-1-TJC-Fire Life Safety - Bldg.6-1.pdf PDF
Contractor sign in.pdf PDF
F-16-3-TJC-Fire Life Safety - Bldg.16-3.pdf PDF
Portland TJC Set Buildings 100 and 101.pdf PDF
36C26025R0071_2.docx DOCX document
Attachment 3-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 1.pdf PDF
Attachment 7-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 5.pdf PDF
Attachment 6-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 4.pdf PDF
Attachment 15-Past Performance Questionnaire.pdf PDF
Attachment 10-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 8.pdf PDF
Attachment 11-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 9.pdf PDF
Attachment 9-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 7.pdf PDF
Attachment 2-648-20-119-VA OR Portland Electrical FCA SPECS STAMPED.pdf PDF
Attachment 13-Price Schedule by Division.xlsx XLSX spreadsheet
Attachment 12-Wage Determination 7-11-2025.pdf PDF
Attachment 1-Statement of Work 648-20-119.pdf PDF
Attachment 4-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 2.pdf PDF
Attachment 14- VAAR 852.219-75.docx DOCX document
Attachment 5-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 3.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F: 101_Pnl UPS MAIN Panel

(1) #3/0 THWN; 160 FT

CB: 101_UPS MAIN PANEL Main

SQUARE D (KA)

200 A

PNL: 101_UPS MAIN PANEL

208V, 225A 2.5k SCA 200k SCAR

CB: 101_SUB PANEL 1

SQUARE D (QO)

50 A

F: 101_SUB PANEL 1

(1) #6 THWN; 30 ft

PNL: 101_UPS SUB PANEL 1

208V, 225A 2.1k SCA 200k SCAR

CB: 101_PANEL A

SQUARE D (QO)

100 A

F: 101_PANEL A

(1) #2 THWN; 80 ft

CB: 101_PDU 01

SQUARE D (QO)

100 A

F: 101_PDU 01

(1) #2 THWN; 70 ft

PNL: 101_PDU PANEL A

208V, 225A 2.0k SCA 200k SCAR

CB: 101_AGFA pals 1

SQUARE D (QO)

20 A

CB: 101_BIO MED RACK 2b

SQUARE D (QO)

20 A

CB: 101_PANEL B

SQUARE D (QO)

100 A

F: 101_PANEL B

(1) #2 THWN; 15 ft

PNL: 101_PANEL B

208V, 225A 2.4k SCA 65k SCAR

CB: 101_1C RISER

SQUARE D (QO)

50 A

F: 101_1C RISER

(1) #6 THWN; 150 ft

CB: 100_SP2-UPS Main

SQUARE D (Q2)

225 A

PNL: 100_SP2-UPS

208V, 225A 1.1k SCA 100k SCAR

CB: 101_B101 RISER 1DEL1-K1-24

SQUARE D (QO)

30 A

F: 101_B101 RISER 1DEL1-K1-24

(1) #6 THWN; 120 ft

PNL: 100_1DEL-K.1-24

208V, 100A 1.2k SCA 10k SCAR

CB: 101_PANEL A Main

SQUARE D (QO)

100 A

PNL: 101_PANEL A

208V, 225A 2.0k SCA 65k SCAR

CB: 101_SERVER RACK 7

SQUARE D (QO)

30 A

CB: 101_SERVER RACK 8

SQUARE D (QO)

30 A

CB: 101_BIO MED RACK 3a

SQUARE D (QO)

20 A

CB: 101_BIO MED RACK 1a

SQUARE D (QO)

20 A

CB: 101_GEIST UNIT #3

SQUARE D (QO)

30 A

CB: 101_AGFA pals

SQUARE D (QO)

20 A

CB: 101_BIO MED RACK 2a

SQUARE D (QO)

20 A

CB: 101_BIO MED RACK 1b

SQUARE D (QO)

20 A

CB: 101_BIO MED RACK 3b

SQUARE D (QO)

20 A

CB: 101_PDU PANEL B

SQUARE D (QD)

225 A

F: 101_PDU PANEL B

(1) #225 Class B; 1 ft

PNL: 101_PDU PANEL B

208V, 225A 2.0k SCA 200k SCAR

CB: 101_BIO MEDS RACK 2d

SQUARE D (QO)

20 A

CB: 101_BIO MED RACK 2c

SQUARE D (QO)

20 A

CB: 101_AGFA pals 2

SQUARE D (QO)

20 A

CB: 101_BIO MED RACK 1c

SQUARE D (QO)

20 A

CB: 101_BIO MED RACK 3c

SQUARE D (QO)

20 A

CB: 101_BIO MEDS RACK 1d

SQUARE D (QO)

20 A

CB: 101_BIO MEDS RACK 3d

SQUARE D (QO)

20 A

CB: 101_AGFA pals 3

SQUARE D (QO)

20 A

PNL: 101_PDU 01

208V, 310A 2.0k SCA 200k SCAR

CB: 101_PDU PANEL A

SQUARE D (QO)

225 A

F: 101_PDU PANEL A

(1) #225 Class B; 1 ft

CONTINUE TO XF: 100_UPS

(SEE SHEET 100ED610)

BLDG 101 - EXISTING ONE-LINE

DIAGRAM (PART 1 OF 5)

BUILDING 101 - ONE LINE DIAGRAM (UPS-1-UPS-2)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

GENERAL NOTES

KEY NOTES

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,

TEMPORARY POWER PLANS, AND PHASING PLANS FOR

VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO

COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED

FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.

REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

3. FOR ALL OVERCURRENT PROTECTION DEVICE

REPLACEMENT WORK, REFERENCE ASSOCIATED

BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE

DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR

ADDITIONAL INFORMATION.

4. FOR ALL OVERCURRENT PROTECTION DEVICE

ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING

SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)

SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL

INFORMATION.

5. FOR ALL POWER DISTRIBUTION EQUIPMENT

REPLACEMENT OR ADDITION WORK, REFERENCE

ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION

EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.

6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT

BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,

IMMEDIATELY INFORM AND COORDINATE WITH VA AS

REQUIRED.

7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS

IMPACTED BY THIS PROJECT.

8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET

101EP601 FOR ALL MODIFICATIONS.

101ED601

SCALE : NTS

1 BLDG 101 - EXISTING ONE-LINE DIAGRAM (PART 1 OF 5)

SHEET IS INCLUDED FOR OVERALL ONE-LINE DIAGRAM

COMPLETENESS AND AS-BUILDING PURPOSES.

PNL: 101_PLSL1-N-26

208V, 30A 0.5k SCA 65k SCAR

CB: 101_PLSL1-N-26 Main SQUARE D (Q1(B)-VH (Obs.)) 30 A

F: 101_Pnl PLSL1-N-26

(1) #8 THWN; 10 ft

XF: 101_T-110

9kVA; 4.30%Z Pri: 480V Sec: 208V

F: 101_XFMR T-110

(1) #12 THWN; 10 ft

CB: 101_XFMR T-110

SQUARE D (EH)

15 A

PNL: 101_PLSHI-N-26

480V, 125A 1.9k SCA 14k SCAR

CB: 101_AirCompressor

SQUARE D (EH)

15 A

PNL: 101_2LSL1-K.1-24

208V, 30A 0.5k SCA 22k SCAR

CB: 101_2LSL1-K.1-24 Main SQUARE D (Q1(B)-VH (Obs.)) 30 A

F: 101_Pnl 2LSL1-K.1-24

(1) #10 THWN; 10 ft

XF: 101_T-99

9kVA; 4.40%Z Pri: 480V Sec: 208V

F: 101_XFMR T-99

(1) #10 THWN; 10 ft

CB: 101_XFMR T-99

SQUARE D (EH)

20 A

PNL: 101_2LSH1-K1-24

480V, 125A 1.1k SCA 14k SCAR

F: 101_2LSH1-K.1-24

(1) #6 THWN; 300 ft

CB: 101_2LSH1-K.1-24

SQUARE D (FA)

40 A

F: 101_Pnl 101-LSP

(1) #1 THWN; 80 ft

ATS: 101_LS-101-1

600 A

F: 101_ATS-LS-101-1

(1) #1 THWN; 120 ft

F: 100_ATS-LS-101-1 (E)

(1) #2 THWN; 410 ft

CB: 101_PLSH1-N-26

SQUARE D (FA)

40 A

F: 101_PLSH1-N-26

(1) #6 THWN; 80 ft

PNL: 101_101-LSP

480V, 225A 2.6k SCA 65k SCAR

CB: 101_PLSL1-L.7-21

SQUARE D (FA)

15 A

F: 101_Pnl PLSL1-L.7-2 XFMR

(1) #12 THWN; 10 ft

XF: 101_T-112

9kVA; 4.40%Z Pri: 480V Sec: 208V

F: 101_Pnl PLSL1-L.7-21

(1) #10 THWN; 10 ft

CB: 101_PLSL1-L.7-21 Main SQUARE D (Q1(B)-VH (Obs.)) 30 A

PNL: 101_PLSL1-L.7-21

208V, 30A 0.5k SCA 65k SCAR

MCP: 101_RWP-2

SQUARE D (FAL)

MCP: 101_RWP-1

SQUARE D (FAL)

MCP: 101_101-P-3

SQUARE D (FAL)

MCP: 101_101-P-4

SQUARE D (FAL)

MCP: 101_101-EF-P15

SQUARE D (FAL)

MCP: 101_101-EF-P11

SQUARE D (FAL)

MCP: 101_101-EF-P9

SQUARE D (FAL)

MCP: 101_101-EF-P5

SQUARE D (FAL)

MCP: 101_101-RF-1

SQUARE D (FAL)

F: 101_101-RF-1

(1) #10 THWN; 160 ft

VFD: 101_RF-1

MTR: 100_RF-1

6 @ 1.5 hp

MCP: 101_101-SF-3

SQUARE D (KAL)

F: 101_101-SF-3

(1) #1/0 THWN; 160 ft

VFD: 101_SF-3

MTR: 101_SF-3

8 @ 10.0 hp

MCP: 101_101-SF-4

SQUARE D (KAL)

F: 101_101-SF-4

(1) #3 THWN; 160 ft

VFD: 101_SF-4

MTR: 100_SF-4

6 @ 7.5 hp

MCP: 101_101-SF-1

SQUARE D (KAL)

F: 101_101-SF-1

(1) #3 THWN; 140 ft

VFD: 101_SF-1

MTR: 101_SF-1

6 @ 7.5 hp

MCP: 101_101-EF-P17

SQUARE D (FAL)

F: 101_101-MCC-P_2

(1) #600 Class B; 1 ft

MCC: 101_MCC-P

480V, 600A 23.8k SCA 42k SCAR

CONTINUE TO ATS: 101_DE-101-1

(SEE SHEET 101ED604)

F: 101_ATS-DE-101-1 (N)

(2) #350 THWN; 210 ft

CB: 101_ATS-DE-101-1 W/G

SQUARE D (DS 416)

600 A

CB: 101_ATS-LS-101-1 W/G

SQUARE D (DS 416)

100 A

F: 101_ATS-LS-101-1

(1) #1 THWN; 120 ft

CB: 101_Normal Riser W/G

SQUARE D (DS 416)

1200 A

F: 101_Normal Riser

(1) #1200 Class B; 160 ft

CB: 101_101-MCC-P W/G

SQUARE D (DS 416)

1600 A

F: 101_101-MCC-P

(2) #350 THWN; 80 ft

SWBD: 101_US101

480V, 3000A 29.5k SCA 50k SCAR

CB: 101_US101 Main W/G

SQUARE D (DS 632)

3200 A

F: 101_SWBD US101

(1) #3200 Class B; 1 ft

XF: US101

2000kVA; 6.07%Z Pri: 12470V Sec: 480V

FU: US101

GE (EJO-1, 125E)

125 A

UTIL: US101

Isc 3P 4409 Amps Isc SLG 3218 Amps

MCC: 101_MCC-P_2

480V, 600A 23.7k SCA 42k SCAR

MCP: 101_Blast Fan #2

SQUARE D (FA)

20 A

MCP: 101_101-P17

SQUARE D (FAL)

MCP: 101_101-P-2

SQUARE D (FAL)

MCP: 101_101-P-1

SQUARE D (FAL)

MCP: 101_101-EF-P14

SQUARE D (FAL)

MCP: 101_101-SF-P1

SQUARE D (FAL)

MCP: 101_101-EF-P8

SQUARE D (FAL)

MCP: 101_101-RF-2

SQUARE D (FAL)

F: 101_101-RF-2

(1) #10 THWN; 160 ft

VFD: 101_RF-2

MTR: 101_RF-2

6 @ 1.5 hp

MCP: 101_101-SF-2

SQUARE D (FAL)

F: 101_101-SF-2

(1) #3 THWN; 160 ft

VFD: 101_SF-2

MTR: 101_SF-2

4 @ 10.0 hp

MCP: 101_101-EF-P1

SQUARE D (FAL)

CB: 101_Air Compressor

SQUARE D (FA)

40 A

CONTINUE TO BD: 101_101-N6

(SEE SHEET 101ED603)

CONTINUE TO SWBD:

100_2500A SWBD

GENERAL NOTES

BUILDING 101 - ONE LINE DIAGRAM (ATS-LS-101-1, SUB US101)

EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS

TO BE REVISED.

EXISTING OVERCURRENT PROTECTIVE DEVICE TO BE

REMOVED AND REPLACED.

EXISTING EQUIPMENT TO BE MODIFIED.

BLDG 101 - EXISTING ONE-LINE

DIAGRAM (PART 2 OF 5)

2 2 2 2

222222222222

2 2 2 2 2 2 2 2 2 2 2 2

SPACESPACESPACESPACESPACESPACESPACESPACE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

KEY NOTES

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,

TEMPORARY POWER PLANS, AND PHASING PLANS FOR

VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO

COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED

FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.

REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

3. FOR ALL OVERCURRENT PROTECTION DEVICE

REPLACEMENT WORK, REFERENCE ASSOCIATED

BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE

DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR

ADDITIONAL INFORMATION.

4. FOR ALL OVERCURRENT PROTECTION DEVICE

ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING

SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)

SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL

INFORMATION.

5. FOR ALL POWER DISTRIBUTION EQUIPMENT

REPLACEMENT OR ADDITION WORK, REFERENCE

ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION

EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.

6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT

BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,

IMMEDIATELY INFORM AND COORDINATE WITH VA AS

REQUIRED.

7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS

IMPACTED BY THIS PROJECT.

8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET

101EP602 FOR ALL MODIFICATIONS.

101ED602

SCALE : NTS

1 BLDG 101 - EXISTING ONE-LINE DIAGRAM (PART 2 OF 5)

CONTINUE TO SWBD:

101_US101

(SEE SHEET 101ED602)

F: 101_NORMAL RISER

(1) #1200 CLASS B; 160 ft

BD: 101_101-N6

480V, 1000A 25.1k SCA 85k SCAR

F: 101_BD 101-N5

(1) #1200 CLASS B; 25 ft

FU: 101_T-107

BUSSMANN (FRS-R)

100 A

FU: 101_6H1-K-27

BUSSMANN (FRS-R)

100 A

F: 101_6H1-K-27

(1) #2 THWN; 60 ft

PNL: 101_6H1-K-27

480V, 225A 13.3k SCA 14k SCAR

CB: 101_CAGE WASHER 10HP

SQUARE D (EH)

30 A

F: 101_T-107

(1) #2 THWN; 60 ft

XF: 101_T-107

75kVA; 4.90%Z Pri: 480V Sec: 208V

F: 101_PNL 6SDN-K-27

(1) #4/0 THWN; 10 ft

CB: 101_SPARE IN RM 613

SQUARE D (EH)

20 A

CB: 101_HW-509 2HP

SQUARE D (EH)

20 A

CB: 101_DISPOSER 5HP

SQUARE D (EH)

20 A

F: 101_PH1-K-27

(1) #1 THHN; 60 ft

PNL: 101_PH1-K-27

480V, 125A 9.1k SCA 14k SCAR

CB: 100_XFMR T-109

SQUARE D (EH)

20 A

F: 101_XFMR T-109

(1) #12 THWN; 30 ft

XF: 101_T-109

9kVA; 4.40%Z Pri: 480V Sec: 208V

F: 101_PL1-K-27

(1) #10 THWN; 30 ft

CB: 101_PL1-K-27 MAIN

SQUARE D (Q1(B)-VH (OBS.))

30 A

PNL: 101_PL1-K-27

208V, 30A 0.5k SCA 65k SCAR

FU: 101_T-105

BUSSMANN (FRS-R)

400 A

F: 101_T-105

(1) #500 THWN; 150 ft

XF: 101_T-105

225kVA; 4.60%Z Pri: 480V Sec: 208V

F: 101_SWBD 5SDN-K.1-24

(2) #500 THWN; 10 ft

FU: 101_5H1-K-27

BUSSMANN (FRS-R)

100 A

F: 101_5H1-K-27

(1) #1 THWN; 20 ft

FU: 101_T-103

BUSSMANN (FRS-R)

400 A

F: 101_T-103

(1) #500 THWN; 60 ft

XF: 101_T-103

225kVA; 4.60%Z Pri: 480V Sec: 208V

F: 101_SWBD 4SDN-K.1-24

(2) #500 THWN; 10 ft

BD: 101_101-N5

480V, 1200A 24.5k SCA 85k SCAR

F: 101_BD 101-N4

(1) #1200 CLASS B; 25 ft

BD: 101_101-N4

480V, 1200A 23.9k SCA 85k SCAR

F: 101_BD 101-N2

(1) #1200 CLASS B; 50 ft

FU: 101_T-98

BUSSMANN (FRS-R)

175 A

F: 101_T-98

(1) #2/0 THWN; 120 ft

XF: 101_T-98

113kVA; 6.20%Z Pri: 480V Sec: 208V

F: 101_PNL 2L2-K.1-24

(1) #350 THWN; 10 ft

FU: 101_T-97

BUSSMANN (FRS-R)

175 A

F: 101_T-97

(1) #2/0 THWN; 100 ft

XF: 101_T 97

113kVA; 6.20%Z Pri: 480V Sec: 208V

F: 101_PNL 2L2-K-27

(1) #350 THWN; 20 ft

BD: 101_101-N2

480V, 1200A 22.8k SCA 85k SCAR

FU: 101_2H1-K-27/3H1-K-27

BUSSMANN (FRS-R)

200 A

F: 101_2H1-K-27/3H1-K-27

(1) #3/0 THWN; 20 ft

F: 101_PNL 3H1-K-27

(1) #2/0 THWN; 25 ft

PNL: 101_3H1-K-27

480V, 225A 17.1k SCA 14k SCAR

F: 101_PNL 1H1-K-27

(1) #3/0 THWN; 30 ft

PNL: 101_1H1-K-27

480V, 225A 17.0k SCA 14k SCAR

PNL: 101_2HI-K-27

480V, 225A 20.1k SCA 14k SCAR

PNL: 101_2L2-K-27

208V, 400A 4.2k SCA 65k SCAR

CB: 101_UNKNOWN

SQUARE D (Q2)

225 A

F: 101_UNKNOWN

(1) #3/0 THWN; 35 FT

PNL: 101_1L2-K-27

208V, 225A 3.8k SCA 65k SCAR

CB: 101_1L1-K-27

SQUARE D (Q2)

225 A

F: 101_1L1-K-27

(1) #4/0 THWN; 35 ft

PNL: 101_1L1-K-27

208V, 225A 3.8k SCA 65k SCAR

PNL: 101_2L2-K.1-24

208V, 400A 4.2k SCA 50k SCAR

CB: 101_2L3-K.1-24

SQUARE D (Q2)

225 A

F: 101_2L3-K.1-24

(1) #4/0 THWN; 30 ft

PNL: 101_2L3-K.1-24

208V, 225A 3.9k SCA 65k SCAR

CB: 101_3L1-K-27

SQUARE D (Q2)

225 A

CB: 101_2L1-K-27

SQUARE D (Q2)

225 A

CB: 101_2L2-K-27 SEC 2

SQUARE D (FA)

70 A

F: 101_2L2-K-27 SEC 2

(1) #2 THWN; 35 ft

PNL: 101_2L2-K-27 SEC 2

208V, 100A 3.6k SCA 65k SCAR

F: 101_2L1-K-27

(1) #4/0 THWN; 10 ft

PNL: 101_2L1-K-27

208V, 225A 4.1k SCA 65k SCAR

F: 101_3L1-K-27

(1) #4/0 THWN; 35 ft

PNL: 101_3L1-K-27

208V, 225A 3.8k SCA 65k SCAR

PNL: 101_6SDN-K-27

208V, 225A 3.7k SCA 65k SCAR

CB: 101_6L1-L.7-23

SQUARE D (FA)

100 A

F: 101_6L1-L.7-23

(1) #4 THWN; 80 ft

PNL: 101_6L1-L.7-23

208V, 100A 2.3k SCA 65k SCAR

CB: 101_6L1-K-25

SQUARE D (FA)

60 A

CB: 101_6L1-L.7-27

SQUARE D (FA)

100 A

(1) #4 THWN; 140 ft

PNL: 101_6L1-K-25

208V, 100A 1.7k SCA 65k SCAR

F: 101_6L1-K-27

(1) #2 THWN; 80 ft

PNL: 101_6L1-K-27

208V, 100A 2.7k SCA 65k SCAR

CB: 101_1L1-K.1-24 SEC 2

SQUARE D (FA)

100 A

F: 101_1L1-K.1-24 SEC 2

(1) #1 THWN; 30 ft

PNL: 101_1L1-K.1-24 SEC 2

208V, 100A 3.7k SCA 65k SCAR

CB: 101_3L1-K.1-24

SQUARE D (Q2)

225 A

F: 101_3L1-K.1-24

(1) #4/0 THWN; 30 ft

PNL: 101_3L1-K.1-24 SEC 1

208V, 225A 3.9k SCA 65k SCA

F: 101_Pnl 3L1-K.1-24 SEC 2

(1) #4/0 THWN; 15 ft

PNL: 101_3L1-K.1-24 SEC 2

208V, 225A 3.8k SCA 65k SCAR

CB: 101_1L1-K.1-24

SQUARE D (Q2)

225 A

F: 101_1L1-K.1-24

(1) #4/0 THWN; 30 ft

PNL: 101_1L1-K.1-24 SEC 1

208V, 100A 3.9k SCA 65k SCAR

CB: 101_2L1-K.1-24

SQUARE D (Q2)

225 A

F: 101_2L1-K.1-24

(1) #4/0 THWN; 30 ft

PNL: 101_2L1-K.1-24

208V, 225A 3.9k SCA 65k SCAR

SWBD: 101_5SDN-K.1-24

208V, 800A 9.4k SCA 50k SCAR

CB: 101_5L1-L.6-26

SQUARE D (FA)

100 A

F: 101_5L1-L.6-26

(1) #2 THWN; 80 ft

PNL: 101_5L1-L.6-26

208V, 100A 4.6k SCA 65k SCAR

CB: 101_5L1-K.1-22

SQUARE D (Q2)

125 A

F: 101_5L1-K.1-22

(1) #1 THWN; 60 ft

PNL: 101_5L1-K.1-22

208V, 225A 5.8k SCA 65k SCAR

CB: 101_5L1-K-26

SQUARE D (FA)

100 A

F: 101_5L1-K-26

(1) #2 THWN; 100 ft

PNL: 101_5L1-K-26

208V, 225A 4.0k SCA 65k SCAR

CB: 101_5L1-K-27

SQUARE D (FA)

50 A

F: 101_5L1-K-27

(1) #6 THWN; 160 ft

PNL: 101_5L1-K-27

208V, 225A 1.4k SCA 65k SCAR

CB: 101_5L1-L.7-24

SQUARE D (Q2)

150 A

F: 101_5L1-L.7-24

(1) #1/0 THWN; 180 ft

PNL: 101_5L1-L.7-24

208V, 225A 3.5k SCA 65k SCAR

CB: 101_5L1-L.7-25

SQUARE D (FA)

100 A

F: 101_5L1-L.7-25

(1) #2 THWN; 160 ft

PNL: 101_5L1-L.7-25

208V, 100A 2.9k SCA 65k SCAR

CB: 101_5L1-K.1-24

SQUARE D (FA)

50 A

F: 101_5L1-K.1-24

(1) #6 THWN; 60 ft

PNL: 101_5L1-K.1-24

208V, 100A 3.2k SCA 65k SCAR

CB: 101_5L1-K-22

SQUARE D (Q2)

125 A

F: 101_5L1-K-22

(1) #1 THWN; 110 ft

PNL: 101_5L1-K-22

208V, 225A 4.2k SCA 65k SCAR

CB: 101_5L1-L.6-22

SQUARE D (FA)

70 A

F: 101_5L1-L.6-22

(1) #2 THWN; 80 ft

PNL: 101_5L1-L.6-22

208V, 100A 4.6k SCA 65k SCAR

CB: 101_5L1-K-24

SQUARE D (FA)

100 A

F: 101_5L1-K-24

(1) #2 THWN; 50 ft

PNL: 101_5L1-K-24

208V, 225A 5.9k SCA 65k SCAR

PNL: 101_5H1-K-27

480V, 225A 20.3k SCA 14k SCAR

CB: 101_SPARE

SQUARE D (EH)

20 A

CB: 101_LIEBERT AC CONDENSER 2

SQUARE D (EH)

20 A

CB: 101_FREEZER BY 506E

SQUARE D (EH)

20 A

CB: 101_LIEBERT AC CONDENSER

SQUARE D (EH)

30 A

CB: 101_4TH FLOOR COOLING UNIT

SQUARE D (EH)

20 A

F: 101_Pnl 4H1-K-27

(1) #1 THWN; 25 ft

PNL: 101_4H1-K-27

480V, 125A 16.2k SCA 14k SCAR

CB: 101_XFMR 4L1-K-27

SQUARE D (EH)

30 A

F: 101_XFMR 4L1-K-27

(1) #10 THWN; 120 ft

XF: 101_T-101

23kVA; 5.00%Z Pri: 480V Sec: 208V

F: 101_PNL 4L2-K.1-24

(1) #4 THWN; 30 ft

CB: 101_4L2-K.1-24 MAIN

SQUARE D (Q1(B)-VH (OBS.))

50 A

PNL: 101_4L2-K.1-24

208V, 50A 1.0k SCA 65k SCAR

CB: 101_4L1-L.6-23

SQUARE D (Q2)

150 A

F: 101_4L1-L.6-23

(1) #1/0 THWN; 60 ft

PNL: 101_4L1-L.6-23

208V, 225A 6.5k SCA 65k SCAR

CB: 101_4L1-K-23

SQUARE D (Q2)

150 A

F: 101_4L1-K-23

(1) #1/0 THWN; 140 ft

PNL: 101_4L1-K-23

208V, 225A 4.2k SCA 65k SCAR

CB: 101_4L1-L.7-25

SQUARE D (FA)

100 A

F: 101_4L1-L.7-25

(1) #1 THWN; 120 ft

PNL: 101_4L1-L.7-25

208V, 100A 4.1k SCA 65k SCAR

NO SCALE

CB:101_RECP RM 414

SQUARE D (FA)

50 A

CB: 101_4L1-K.1-27

SQUARE D (Q2)

125 A

F: 101_4L1-K.1-27

(1) #1/0 THWN; 90 ft

PNL: 101_4L1-K.1-27

208V, 225A 5.4k SCA 65k SCAR

CB: 101_4L1-K.1-24

SQUARE D (KH)

225 A

F: 101_4L1-K.1-24

(1) #4/0 THWN; 20 ft

PNL: 101_4L1-K.1-24

208V, 225A 9.1k SCA 65k SCAR

CB: 101_AUTOCLAVE RM 412

SQUARE D (QO)

40 A

CB: 101_4L1-L.7-22

SQUARE D (Q2)

200 A

F: 101_4L1-L.7-22

(1) #1/0 THWN; 80 ft

PNL: 101_4L1-L.7-22

208V, 225A 5.8k SCA 65k SCAR

CB: 101_4L1-K-26

SQUARE D (Q2)

150 A

F: 101_4L1-K-26

(1) #1/0 THWN; 100 ft

PNL: 101_4L1-K-26

208V, 225A 5.1k SCA 65k SCAR

CB: 101_4L1-L.5-27

SQUARE D (FA)

70 A

F: 101_4L1-L.5-27

(1) #4 THWN; 80 ft

PNL: 101_4L1-L.5-27

208V, 100A 3.6k SCA 65k SCAR

CB: 101_RECP RM 414 (2)

SQUARE D (FA)

50 A

CB: 101_4L1-L.7-24

SQUARE D (Q2)

125 A

F: 101_4L1-L.7-24

(1) #1 THWN; 110 ft

PNL: 101_4L1-L.7-24

208V, 225A 4.4k SCA 65k SCAR

CB: 101_4L1-L.6-24

SQUARE D (Q2)

125 A

F: 101_4L1-L.6-24

(1) #1 THWN; 120 ft

PNL: 101_4L1-L.6-24

208V, 225A 4.1k SCA 65k SCAR

SWBD: 101_4SDN-K.1-24

208V, 800A 10.1k SCA 50k SCAR

CB: 101_4L1-K-27

SQUARE D (FA)

30 A

F: 101_4L1-K-27

(1) #10 THWN; 80 ft

PNL: 101_4L1-K-27

208V, 100A 1.2k SCA 65k SCAR

GENERAL NOTES

BUILDING 101 - ONE LINE DIAGRAM (NORMAL RISER)

BLDG 101 - EXISTING ONE-LINE

DIAGRAM (PART 3 OF 5)

2 2 2

2 2

222 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

KEY NOTES

EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS

TO BE REVISED.

EXISTING OVERCURRENT PROTECTIVE DEVICE TO BE

DEMOLISHED AND REPLACED.

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,

TEMPORARY POWER PLANS, AND PHASING PLANS FOR

VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO

COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED

FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.

REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

3. FOR ALL OVERCURRENT PROTECTION DEVICE

REPLACEMENT WORK, REFERENCE ASSOCIATED

BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE

DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR

ADDITIONAL INFORMATION.

4. FOR ALL OVERCURRENT PROTECTION DEVICE

ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING

SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)

SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL

INFORMATION.

5. FOR ALL POWER DISTRIBUTION EQUIPMENT

REPLACEMENT OR ADDITION WORK, REFERENCE

ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION

EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.

6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT

BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,

IMMEDIATELY INFORM AND COORDINATE WITH VA AS

REQUIRED.

7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS

IMPACTED BY THIS PROJECT.

8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET

101EP603 FOR ALL MODIFICATIONS.

101ED603

SCALE : NTS

1 BLDG 101 - EXISTING ONE-LINE DIAGRAM (PART 3 OF 5)

100_SUB-B2-GENSD-G5

F: 100_SWBD 101-EDP (E)

(2) #500 THWN; 410 ft

F: 101_ATS-DE-101-1 (N)

(2) #350 THWN; 210 ft

ATS: 101_DE-101-1

600 A

F: 101_SWBD 101-DE-1P

(2) #350 THWN; 120 ft

CB: 101_XFMR T-102

SQUARE D (KA)

175 A

F: 101_XFMR T-102

(1) #2/0 THWN; 80 ft

XF: 101_T-102

113kVA; 6.20%Z Pri: 480V Sec: 208V

F: 101_SWBD 4SDDE1-K-27

(1) #500 THWN; 20 ft

CB: 101_XFMR T-136

SQUARE D (KA)

70 A

F: 101_XFMR T-136

(1) #4 THWN; 130 ft

XF: 101_T-136

45kVA; 6.20%Z Pri: 480V Sec: 208V

F: 101_Pnl Verizon Pnl.

(1) #2 THWN; 10 ft

CB: 101_Verizon Pnl. Main

SQUARE D (QO)

100 A

PNL: 101_Verizon Pnl.

208V, 100A 1.7k SCA 65k SCAR

CB: 101_TVSS/ Power Fail Relay

SQUARE D (QO)

40 A

CB: 101_5DEH1-K-27

SQUARE D (KA)

125 A

F: 101_5DEH1-K-27

(1) #1 THWN; 240 ft

CB: 101_6CH1-K-27

SQUARE D (FA)

100 A

F: 101_6CH1-K-27

(1) #4 THWN; 200 ft

CB: 101_SWBD 101-PESDP

SQUARE D (LA)

300 A

F: 101_SWBD 101-PESDP

(1) #350 THWN; 80 ft

PNL: 101_6CH1-K-27

480V, 100A 3.3k SCA 14k SCAR

PNL: 101_PDEL1-N-26

208V, 30A 0.7k SCA 65k SCAR

CB: 101_XFMR T-104

SQUARE D (KA)

175 A

F: 101_XFMR T-104

(1) #2/0 THWN; 240 ft

XF: 101_XFMR T-104

150kVA; 5.10%Z Pri: 480V Sec: 208V

F: 101_SWBD 5SDDEL-K-27

(1) #500 THWN; 10 ft

CB: 101_XFMR T-111

SQUARE D (FA)

30 A

F: 101_XFMR T-111

(1) #10 THWN; 80 ft

XF: 101_T-111

15kVA; 5.40%Z Pri: 480V Sec: 208V

F: 101_Pnl PDEL1-N-26

(1) #8 THWN; 20 ft

CB: 101_PDEL1-N-26 Main SQUARE D (Q1(B)-VH (Obs.)) 50 A

CB: 101_IPU X-RAY

SQUARE D (FA)

100 A

CB: 101_Well Water Stoage Tank

SQUARE D (FA)

100 A

CB: 101_XFMR T-108

SQUARE D (FA)

70 A

F: 1F: 101_XFMR T-108

(1) #4 THWN; 200 ft

XF: 101_T-108

45kVA; 6.10%Z Pri: 480V Sec: 208V

F: 101_Pnl 6SDDE1-K.1-24

(1) #4/0 THWN; 20 ft

CB: 101_101-MCC-DE1

SQUARE D (KA)

200 A

F: 101_101-MCC-DE1

(1) #3/0 THWN; 20 ft

DISC: 101_MCC-DE-1

480V, 9.6k SCA

F: 101_MCC-DE1

(1) #3/0 THWN; 10 ft

Start of Single Phase

Open

SWBD: 101_101-DE-1P

480V, 600A 10.1k SCA 50k SCAR

FU: 101_MCC-DE1

BUSSMANN (LPS-RK)

500 A

MCP: 101_101-EF-P7

SQUARE D (FAL)

CB: 101_XFMR T-108

SQUARE D (FA)

70 A

MCP: 101_101-EF-P3

SQUARE D (FAL)

MCP: 101_101-EF-P2

SQUARE D (FAL)

MCP: 101_101-EF-P4

SQUARE D (FAL)

CB: 101_DI Pump 2HP

SQUARE D (EH)

20 A

PNL: 101_5DEH1-K-27

480V, 225A 4.5k SCA 14k SCAR

CB: 101_Loading Dock Door 2HP

SQUARE D (EH)

20 A

CB: 101_Elevator S-11

SQUARE D (KA)

150 A

F: 101_Elevator S-11

(1) #4 THWN; 120 ft

XF: 101_Elevator S-11 45kVA; 4.00%Z Pri: 480V Sec: 480V

VFD: 101_Elevator S-11

MTR: 101_Elevator S-11 1 @ 40.0 hp

CB: 101_Elevator S-12

SQUARE D (FA)

100 A

F: 101_Elevator S-12

(1) #6 THWN; 100 ft

XF: 101_Elevator S-12 34kVA; 5.00%Z Pri: 480V Sec: 480V

VFD: 101_Elevator S-12

MTR: 101_Elevator S-12 1 @ 25.0 hp

CB: 101_Elevator P-7

SQUARE D (KA)

150 A

F: 101_Elevator P-7

(1) #4 THWN; 120 ft

XF: 101_Elevator P-7 34kVA; 5.00%Z Pri: 480V Sec: 480V

VFD: 101_Elevator P-7

MTR: 101_Elevator P-7 1 @ 30.0 hp

CB: 101_Elevator P-8

SQUARE D (KA)

150 A

F: 101_Elevator P-8

(1) #4 THWN; 120 ft

XF: 101_Elevator P-8 34kVA; 5.00%Z Pri: 480V Sec: 480V

VFD: 101_Elevator P-8

MTR: 101_Elevator P-8 1 @ 30.0 hp

SWBD: 101_101-PESDP

480V, 400A 8.6k SCA 50k SCAR

CB: 101_5DEL1-K.1-24

SQUARE D (FA)

100 A

F: 101_5DEL1-K.1-24

(1) #2 THWN; 110 ft

PNL: 101_5DEL1-K.1-24

208V, 100A 2.8k SCA 65k SCAR

CB: 101_5DEL1-K.6-24

SQUARE D (FA)

40 A

F: 101_5DEL1-K.6-24

(1) #8 THWN; 160 ft

CB: 101_5DEL1-L.7-24

SQUARE D (FA)

70 A

F: 101_5DEL1-L.7-24

(1) #4 THWN; 90 ft

PNL: 101_5DEL1-L.7-24

208V, 100A 2.5k SCA 65k SCAR

CB: 101_5DEL1-L.6-22

SQUARE D (FA)

40 A

F: 101_5DEL1-L.6-22

(1) #4 THWN; 100 ft

PNL: 101_5DEL1-L.6-22

208V, 100A 2.3k SCA 65k SCAR

CB: 101_5DEL1-K-22

SQUARE D (FA)

100 A

F: 101_5DEL1-K-22

(1) #1 THWN; 120 ft

PNL: 101_5DEL1-K-22

208V, 100A 2.9k SCA 65k SCAR

CB: 101_5DEL1-K-24

SQUARE D (FA)

70 A

F: 101_5DEL1-K-24

(1) #4 THWN; 160 ft

PNL: 101_5DEL1-K-24

208V, 100A 1.7k SCA 65k SCAR

PNL: 101_5DEL1-K.6-24

208V, 100A 0.8k SCA 65k SCAR

CB: 101_100-UC-15 (3/4 HP)

SQUARE D (QO-VH)

20 A

CB: 101_100-US-12 (3/4 HP)

SQUARE D (QO-VH)

20 A

CB: 101_5DEL1-K-26

SQUARE D (Q2)

150 A

F: 101_5DEL1-K-26

(1) #1/0 THWN; 80 ft

PNL: 101_5DEL1-K-26

208V, 225A 3.6k SCA 65k SCAR

SWBD: 101_5SDDEL-K-27

208V, 400A 4.9k SCA 50k SCAR

CB: 101_5DEL1-K-27

SQUARE D (FA)

50 A

PNL: 101_5DEL1-K-27

208V, 100A 1.8k SCA 65k SCAR

CB: 101_5DEL1-L.7-25

SQUARE D (FA)

70 A

F: 101_5DEL1-L.7-25

(1) #4 THWN; 60 ft

PNL: 101_5DEL1-L.7-25

208V, 100A 3.1k SCA 65k SCAR

CB: 101_5DEL1-L.6-26

SQUARE D (FA)

70 A

F: 101_5DEL1-L.6-26

(1) #4 THWN; 110 ft

PNL: 101_5DEL1-L.6-26

208V, 100A 2.2k SCA 65k SCAR

CB: 101_5DEL1-K.1-22

SQUARE D (FA)

60 A

F: 101_5DEL1-K.1-22

(1) #6 THWN; 120 ft

PNL: 101_5DEL1-K.1-22

208V, 100A 1.5k SCA 65k SCAR

F: 101_5DEL1-K-27

(1) #6 THWN; 100 ft

CB: 101_6DEL1-K.1-24

SQUARE D (FA)

70 A

F: 101_6DEL1-K.1-24

(1) #4 THWN; 100 ft

PNL: 101_6DEL1-K.1-24

208V, 100A 1.2k SCA 65k SCAR

PNL: 101_6SDDE1-K.1-24

208V, 225A 1.7k SCA 65k SCAR

CB: 101_6DEL1-K-25

SQUARE D (FA)

40 A

F: 101_6DEL1-K-25

(1) #6 THWN; 80 ft

PNL: 101_6DEL1-K-25

208V, 100A 1.2k SCA 65k SCAR

CB: 101_6DEL1-K-27

SQUARE D (FA)

70 A

F: 101_6DEL1-K-27

(1) #4 THWN; 90 ft

PNL: 101_6DEL1-K-27

208V, 100A 1.3k SCA 65k SCAR

CB: 101_6DEL1-L.7-23

SQUARE D (FA)

100 A

F: 101_6DEL1-L.7-23

(1) #1 THWN; 80 ft

PNL: 101_6DEL1-L.7-23

208V, 100A 1.4k SCA 65k SCAR

CB: 101_6DEL1-L.7-26

SQUARE D (FA)

70 A

F: 101_6DEL1-L.7-26

(1) #4 THWN; 110 ft

PNL: 101_6DEL1-L.7-26

208V, 100A 1.2k SCA 65k SCAR

CB: 101_6DEL1-K-24

SQUARE D (Q2)

125 A

F: 101_6DEL1-K-24

(1) #1 THWN; 20 ft

PNL: 101_6DEL1-K-24

208V, 225A 1.6k SCA 65k SCAR

CB: 101_4DEL1-K-27

SQUARE D (FA)

100 A

F: 101_4DEL1-K-27

(1) #4 THWN; 80 ft

PNL: 101_4DEL1-K-27

208V, 100A 2.4k SCA 65k SCAR

SWBD: 101_4SDDE1-K-27

208V, 400A 3.8k SCA 50k SCAR

CB: 101_4DEL1-K-23

SQUARE D (FA)

70 A

F: 101_4DEL1-K-23

(1) #4 THWN; 160 ft

PNL: 101_4DEL1-K-23

208V, 100A 1.6k SCA 65k SCAR

CB: 101_4DEL1-L.6-23

SQUARE D (FA)

70 A

F: 101_4DEL1-L.6-23

(1) #4 THWN; 180 ft

PNL: 101_4DEL1-L.6-23

208V, 100A 1.5k SCA 65k SCAR

CB: 101_4DEL1-L.7-22

SQUARE D (FA)

70 A

F: 101_4DEL1-L.7-22

(1) #4 THWN; 200 ft

PNL: 101_4DEL1-L.7-22

208V, 100A 1.4k SCA 65k SCAR

CB: 101_4DEL1-K.1-27

SQUARE D (FA)

30 A

F: 101_4DEL1-K.1-27

(1) #10 THWN; 80 ft

PNL: 101_4DEL1-K.1-27

208V, 100A 1.1k SCA 65k SCAR

CB: 101_4DEL1-L.7-24

SQUARE D (FA)

70 A

F: 101_4DEL1-L.7-24

(1) #4 THWN; 160 ft

PNL: 101_4DEL1-L.7-24

208V, 100A 1.6k SCA 65k SCAR

CB: 101_4DEL1-L.7-25

SQUARE D (FA)

70 A

F: 101_4DEL1-L.7-25

(1) #4 THWN; 180 ft

PNL: 101_4DEL1-L.7-25

208V, 100A 1.5k SCA 65k SCAR

CB: 101_4DEL1-K-26

SQUARE D (FA)

100 A

F: 101_4DEL1-K-26

(1) #2 THWN; 120 ft

PNL: 101_4DEL1-K-26

208V, 100A 2.4k SCA 65k SCAR

CB: 101_4DEL1-K.1-24

SQUARE D (FA)

40 A

F: 101_4DEL1-K.1-24

(1) #8 THWN; 100 ft

PNL: 101_4DEL1-K.1-24

208V, 100A 1.2k SCA 65k SCAR

CB: 101_4DEL1-L.6-24

SQUARE D (FA)

40 A

F: 101_4DEL1-L.6-24

(1) #8 THWN; 150 ft

PNL: 101_4DEL1-L.6-24

208V, 100A 0.9k SCA 65k SCAR

CB: 101_4DEL1-L.5-27

SQUARE D (Q2)

175 A

F: 101_4DEL1-L.5-27

(1) #2/0 THWN; 180 ft

PNL: 101_4DEL1-L.5-27

208V, 225A 2.5k SCA 65k SCAR

CB: 101_2DEL1-K-27

SQUARE D (FA)

100 A

F: 101_2DEL1-K-27

(1) #4 THWN; 210 ft

CB: 101_2DEL1-K-27 Main

SQUARE D (QO)

100 A

PNL: 101_2DEL1-K-27

208V, 100A 1.4k SCA 65k SCAR

NO SCALE

CONTINUE TO SWBD:

101_US101

(SEE SHEET 101ED602)

GENERAL NOTES

BUILDING 101 - ONE LINE DIAGRAM (ATS-DE-101-1)

EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS

TO BE REVISED.

EXISTING OVERCURRENT PROTECTIVE DEVICE TO BE

REMOVED AND REPLACED.

BLDG 101 - EXISTING ONE-LINE

DIAGRAM (PART 4 OF 5)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

KEY NOTES

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,

TEMPORARY POWER PLANS, AND PHASING PLANS FOR

VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO

COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED

FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.

REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

3. FOR ALL OVERCURRENT PROTECTION DEVICE

REPLACEMENT WORK, REFERENCE ASSOCIATED

BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE

DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR

ADDITIONAL INFORMATION.

4. FOR ALL OVERCURRENT PROTECTION DEVICE

ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING

SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)

SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL

INFORMATION.

5. FOR ALL POWER DISTRIBUTION EQUIPMENT

REPLACEMENT OR ADDITION WORK, REFERENCE

ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION

EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.

6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT

BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,

IMMEDIATELY INFORM AND COORDINATE WITH VA AS

REQUIRED.

7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS

IMPACTED BY THIS PROJECT.

8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET

101EP604 FOR ALL MODIFICATIONS.

101ED604

SCALE : NTS

1 BLDG 101 - EXISTING ONE-LINE DIAGRAM (PART 4 OF 5)

PNL: 101_1L1-F.1-19.6

208V, 50A 0.7k SCA 65k SCAR

CB: 101_1L1-F.1-19.6 Main SQUARE D (Q1(B)-VH (Obs.)) 50 A

F: 101_Pnl 1L1-F.1-19.6

(1) #6 THWN; 20 ft

XF: 101_T-93

15kVA; 5.10%Z Pri: 480V Sec: 208V

F: 101_XFMR T-93

(1) #10 THWN; 40 ft

CB: 101_XFMR T-93

SQUARE D (EH)

30 A

CB: 101_RF-5

SQUARE D (EH)

15 A

F: 101_Disc RF-5

(1) #12 THWN; 60 ft

DISC: 101_RF-5

480V, 1.7k SCA

MCP: 101_RF-5

SQUARE D (FAL)

F: 101_RF-5

(1) #12 THWN; 10 ft

MTR: 101_RF-5

1 @ 3.0 hp

CB: 101_101-SF-5 15HP

SQUARE D (EH)

40 A

F: 101_Disc SF-5

(1) #10 THWN; 70 ft

DISC: 101_SF-5

480V, 2.1k SCA

MCP: 101_SF-5

SQUARE D (FAL)

F: 101_SF-5

(1) #12 THWN; 10 ft

MTR: 101_SF-5

1 @ 15.0 hp

PNL: 101_1H1-F.1-19.6

480V, 100A 5.1k SCA 14k SCAR

CB: 101_COM RM OFFICE A/C

SQUARE D (EH)

15 A

F: 101_2H1-F.1-19 Sec 2

(1) #1 THWN; 10 ft

PNL: 101_2H1-F.1-19 Sec 2 480V, 225A 5.0k SCA 14k SCAR

CB: 101_EF-A1

SQUARE D (EH)

15 A

PNL: 101_2L1-F.1-19

208V, 150A 1.7k SCA 22k SCAR

CB: 101_2L1-F.1-19 Main

SQUARE D (KA)

150 A

F: 101_2L1-F.1-19

(1) #1 THWN; 20 ft

XF: 101_T-94

45kVA; 6.10%Z Pri: 480V Sec: 208V

F: 101_XFMR T-94

(1) #4 THWN; 45 ft

CB: 101_XFMR T-94

SQUARE D (EH)

70 A

CB: 101_Audio Rack SQUARE D (Q1(B)-VH (Obs.)) 50 A

CB: 101_Dimmer Rack SQUARE D (Q1(B)-VH (Obs.)) 70 A

F: 101_DImmer Rack

(1) #4 THWN; 30 ft

EP: 101_Dimmer Rack 208V, 1.6k SCA

PNL: 101_2H1-F.1-19 Sec 1 480V, 225A 5.2k SCA 14k SCAR

CONTINUE TO BD:

100_S2 N1

(SEE SHEET 100ED605)

CB: 101_60 AMP RECP.

SQUARE D (FH)

60 A

CB: 101_XFMR T-92

SQUARE D (FA)

30 A

CB: 101_COMP RM

LIBERT SQUARE D (KA)

125 A

F: 101_XFMR T-92

(1) #10 THWN; 10 ft

XF: 101_T-92

15kVA; 5.10%Z Pri: 480V Sec: 208V

F: 101_Pnl 1DEL2-F.1-19.6

(1) #6 THWN; 15 ft

CB: 101_1DEL2-F.1-19.6 Main SQUARE D (Q1(B)-VH (Obs.)) 50 A

PNL: 101_1DEL2-F.1-19.6

208V, 50A 0.8k SCA 65k SCAR

PNL: 101_1DEH1-F.1-19.6

480V, 225A 16.4k SCA 14k SCAR

CONTINUE TO BD:

100_S2 DE1

(SEE SHEET 100ED619)

CONTINUE TO BD:

100_S2 N2

(SEE SHEET 100ED605)

GENERAL NOTES

BUILDING 101 - ONE LINE DIAGRAM (BUSDUCT RISER N1 BAY2, BUSDUCT RISER DE BAY 2)

EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS

TO BE REVISED.

BLDG 101 - EXISTING ONE-LINE

DIAGRAM (PART 5 OF 5)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

KEY NOTES

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,

TEMPORARY POWER PLANS, AND PHASING PLANS FOR

VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO

COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED

FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.

REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

3. FOR ALL OVERCURRENT PROTECTION DEVICE

REPLACEMENT WORK, REFERENCE ASSOCIATED

BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE

DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR

ADDITIONAL INFORMATION.

4. FOR ALL OVERCURRENT PROTECTION DEVICE

ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING

SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)

SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL

INFORMATION.

5. FOR ALL POWER DISTRIBUTION EQUIPMENT

REPLACEMENT OR ADDITION WORK, REFERENCE

ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION

EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.

6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT

BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,

IMMEDIATELY INFORM AND COORDINATE WITH VA AS

REQUIRED.

7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS

IMPACTED BY THIS PROJECT.

8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET

101EP605 FOR ALL MODIFICATIONS.

101ED605

SCALE : NTS

1 BLDG 101 - EXISTING ONE-LINE DIAGRAM (PART 5 OF 5)

EXISTING FEEDER TO BE DEMOLISHED AND REPLACED.2

PNL: 102_NH102-1

480V, 225A 6.0k SCA 14k SCAR

CB: 102_Energy Saver

GE (TED)

80 A

F: 102_Energy Saver

(1) #2 THWN; 180 ft

EP: 102_Energy Saver 480V, 3.4k SCA

CB: 102_Energy Saver-2

CUTLER-HAMMER (FD)

80 A

F: 102_Pnl NH102-2

(1) #2 THWN; 40 ft

CB: 102_SO CORD

SQUARE D (EH)

20 A

CB: 102_Pnl LSH102-1

GE (TED)

30 A

F: 102_Pnl LSH102-1

(1) #10 THWN; 25 ft

CB: 102_LSH102-1 Main

GE (TED)

30 A

PNL: 102_LSH102-1

480V, 100A 3.9k SCA 14k SCAR

CB: 102_XF T-135

GE (TED)

30 A

F: 102_XF T-135

(1) #10 THWN; 5 ft

XF: 102_T-135

15kVA; 5.10%Z

PRI: 480V

SEC: 208V

F: 102_Pnl NL102-1

(1) #6 THWN; 5 ft

CB: 102_NL102-1 Main

GE (THED)

50 A

PNL: 102_NL102-1

208V, 100A 0.8k SCA 22k SCAR

PNL: 102_NH102-2

480V, 100A 3.1k SCA 14k SCAR

CONTINUE TO PNL:

103_DEH103P5

(SEE SHEET 103ED603)

GENERAL NOTES

EXISTING OVERCURRENT PROTECTIVE DEVICE TO BE

REMOVED AND REPLACED.

BLDG 102 - EXISTING ONE-LINE

DIAGRAM

BUILDING 102 - ONE LINE DIAGRAM (ATS-EQ)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

KEY NOTES

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,

TEMPORARY POWER PLANS, AND PHASING PLANS FOR

VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO

COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED

FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.

REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

3. FOR ALL OVERCURRENT PROTECTION DEVICE

REPLACEMENT WORK, REFERENCE ASSOCIATED

BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE

DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR

ADDITIONAL INFORMATION.

4. FOR ALL OVERCURRENT PROTECTION DEVICE

ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING

SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)

SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL

INFORMATION.

5. FOR ALL POWER DISTRIBUTION EQUIPMENT

REPLACEMENT OR ADDITION WORK, REFERENCE

ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION

EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.

6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT

BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,

IMMEDIATELY INFORM AND COORDINATE WITH VA AS

REQUIRED.

7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS

IMPACTED BY THIS PROJECT.

8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET

102EP601 FOR ALL MODIFICATIONS.

102ED601

SCALE : NTS

1 BLDG 102 - EXISTING ONE-LINE DIAGRAM

CB: 103_Pnl NL1032N

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1032N

(1) #1/0 THWN; 20 ft

PNL: 103_NL1032N

208V, 225A 8.0k SCA 200k SCAR

PNL: 103_NL103DP1N

208V, 1000A 9.2k SCA 200k SCAR

CB: 103_Pnl NL1039N

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1039N

(1) #1/0 THWN; 60 ft

PNL: 103_NL1039N

208V, 225A 6.2k SCA 200k SCAR

CB: 103_Pnl NL1035N

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1035N

(1) #1/0 THWN; 140 ft

PNL: 103_NL1035N

208V, 225A 4.1k SCA 200k SCAR

CB: 103_Pnl NL1031N

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1031N

(1) #1/0 THWN; 60 ft

PNL: 103_NL1031N

208V, 225A 6.2k SCA 200k SCAR

CB: 103_Pnl NL1038N

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1038N

(1) #1/0 THWN; 140 ft

PNL: 103_NL1038N

208V, 225A 4.1k SCA 200k SCAR

CB: 103_Pnl NL1034N

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1034N

(1) #1/0 THWN; 135 ft

PNL: 103_NL1034N

208V, 225A 4.2k SCA 200k SCAR

CB: 103_Pnl NL1036N

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1036N

(1) #1/0 THWN; 130 ft

PNL: 103_NL1036N

208V, 225A 4.3k SCA 200k SCAR

CB: 103_Pnl NL10310N

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL10310N

(1) #1/0 THWN; 30 ft

PNL: 103_NL10310N

208V, 225A 7.5k SCA 200k SCAR

CB: 103_Pnl NL1037N

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1037N

(1) #1/0 THWN; 140 ft

PNL: 103_NL1037N

208V, 225A 4.1k SCA 200k SCAR

CB: 103_Pnl NL10311N

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL10311N

(1) #1/0 THWN; 35 ft

PNL: 103_NL10311N

208V, 225A 7.3k SCA 200k SCAR

CB: 103_Pnl NL1033N

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1033N

(1) #1/0 THWN; 25 ft

PNL: 103_NL1033N

208V, 225A 7.8k SCA 200k SCAR

CB: 103_E137 Dishwasher

CUTLER-HAMMER (BAB)

20 A

CB: 103_NL103DP1N Main

CUTLER-HAMMER (ND)

1200 A, 1200 A Plug

CB: 103_XF T-142

CUTLER-HAMMER (LD)

450 A

F: 103_XF T-142

(2) #4/0 THWN; 20 ft

F: 103_Pnl NL103DP1N

(3) #500 THWN; 20 ft

XF: 103_T-142

300kVA; 7.10%Z Pri: 480V Sec: 208V

PNL: 103_NH103DP1N

480V, 600A 22.1k SCA 200k SCAR

CB: 103_Pnl NH1032N

CUTLER-HAMMER (FD)

100 A

F: 103_Pnl NH1032N

(1) #3 THWN; 50 ft

PNL: 103_NH1032N

480V, 100A 12.3k SCA 200k SCAR

CB: 103_Pnl NH1031N

CUTLER-HAMMER (FD)

100 A

F: 103_Pnl NH1031N

(1) #3 THWN; 5 ft

PNL: 103_NH1031N

480V, 100A 20.8k SCA 200k SCAR

CB: 103_Unk Load

CUTLER-HAMMER (GHB)

20 A

CB: 103_E112 Lg An Cage Wash

CUTLER-HAMMER (GHB)

30 A

MTR: 103_103-REF-5

1 @ 20.0 hp

MCP: 103_103-REF-5

CUTLER-HAMMER (HMCP)

F: 103_103-REF-5

(1) #8 THWN; 160 ft

MCC: 103_NH103MC1S

480V, 600A 14.3k SCA 42k SCAR

CB: 103_103-UH-3

CUTLER-HAMMER (HFD)

15 A

CB: 103_103-UH-1

CUTLER-HAMMER (HFD)

15 A

CB: 103_103-ASU-6 Supply

CUTLER-HAMMER (HFD)

40 A

CB: 103_103-ASU-6 Return

CUTLER-HAMMER (HFD)

20 A

CB: 103_103-ASU-2 Supply

CUTLER-HAMMER (HFD)

40 A

CB: 103_103-ASU-2 Return

CUTLER-HAMMER (HFD)

20 A

MCP: 103_103-ASU-1

CUTLER-HAMMER (HMCP)

MTR: 103_103-ASU-6 Supply 1 @ 15.0 hp

MTR: 103_103-ASU-6 Return 1 @ 10.0 hp

MTR: 103_103-ASU-2 Supply 1 @ 15.0 hp

MTR: 103_103-ASU-2 Return 1 @ 7.5 hp

MTR: 103_103-ASU-1

1 @ 60.0 hp

F: 103_103-ASU-6 Supply

(1) #10 THWN; 80 ft

F: 103_103-ASU-6 Return

(1) #12 THWN; 50 ft

F: 103_103-ASU-2 Supply

(1) #10 THWN; 80 ft

F: 103_103-ASU-2 Return

(1) #12 THWN; 50 ft

F: 103_103-ASU-1

(1) #3 THWN; 110 ft

VFD: 103_103-ASU-6 SupplyVFD: 103_103-ASU-6 ReturnVFD: 103_103-ASU-2 SupplyVFD: 103_103-ASU-2 Return

CB: 103_Pnl NL10310S

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL10310S

(1) #1/0 THWN; 40 ft

PNL: 103_NL10310S

208V, 225A 6.2k SCA 200k SCAR

PNL: 103_NL103DP1S

208V, 800A 7.8k SCA 42k SCAR

CB: 103_Pnl NL1036S

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1036S

(1) #1/0 THWN; 210 ft

PNL: 103_NL1036S

208V, 225A 3.0k SCA 200k SCAR

CB: 103_Pnl NL1032S

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1032S

(1) #1/0 THWN; 30 ft

PNL: 103_NL1032S

208V, 225A 6.6k SCA 200k SCAR

CB: 103_Pnl NL1039S

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1039S

(1) #1/0 THWN; 360 ft

PNL: 103_NL1039S

208V, 225A 2.0k SCA 200k SCAR

CB: 103_Pnl NL1035S

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1035S

(1) #1/0 THWN; 100 ft

PNL: 103_NL1035S

208V, 100A 4.5k SCA 200k SCAR

CB: 103_Pnl NL1031S

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1031S

(1) #1/0 THWN; 25 ft

PNL: 103_NL1031S

208V, 225A 6.8k SCA 200k SCAR

CB: 103_Pnl NL1033S

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1033S

(1) #1/0 THWN; 35 ft

PNL: 103_NL1033S

208V, 225A 6.4k SCA 200k SCAR

CB: 103_Pnl NL1037S

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1037S

(1) #1/0 THWN; 160 ft

PNL: 103_NL1037S

208V, 225A 3.5k SCA 200k SCAR

CB: 103_Pnl NL10311S

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL10311S

(1) #1/0 THWN; 45 ft

PNL: 103_NL10311S

208V, 225A 6.0k SCA 200k SCAR

CB: 103_Pnl NL1034S

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1034S

(1) #1/0 THWN; 240 ft

PNL: 103_NL1034S

208V, 100A 2.7k SCA 200k SCAR

CB: 103_Pnl NL1038S

CUTLER-HAMMER (ED)

150 A

F: 103_Pnl NL1038S

(1) #1/0 THWN; 200 ft

PNL: 103_NL1038S

208V, 225A 3.1k SCA 200k SCAR

CB: 103_Unk Load 2

CUTLER-HAMMER (BAB)

20 A

CB: 103_F224-Glass Dishwasher

CUTLER-HAMMER (BAB)

20 A

CB: 103_Unk Load 3

CUTLER-HAMMER (BAB)

20 A

CB: 103_NL103DP1S Main Unknown (Unknown) 800 A

CB: 103_XF T-145

CUTLER-HAMMER (KD)

350 A

F: 103_XF T-145

(1) #500 THWN; 30 ft

F: 103_Pnl NL103DP1S

(2) #500 THWN; 25 ft

XF: 103_T-145

225kVA; 6.40%Z Pri: 480V Sec: 208V

CB: 103_Pnl NH1032S

CUTLER-HAMMER (FD)

100 A

F: 103_Pnl NH1032S

(1) #3 THWN; 120 ft

PNL: 103_NH1032S

480V, 100A 7.2k SCA 200k SCAR

CB: 103_Pnl NH1031S

CUTLER-HAMMER (FD)

100 A

F: 103_Pnl NH1031S

(1) #3 THWN; 25 ft

PNL: 103_NH1031S

480V, 100A 17.8k SCA 200k SCAR

PNL: 103_NH103DP1S

480V, 600A 24.7k SCA 200k SCAR

MTR: 103_103-ASU-5

1 @ 60.0 hp

MCP: 103_103-ASU-5

CUTLER-HAMMER (HMCP)

F: 103_103-ASU-5

(1) #3 THWN; 100 ft

MTR: 103_103-REF-6

1 @ 40.0 hp

MCP: 103_103-REF-6

CUTLER-HAMMER (HMCP)

F: 103_103-REF-6

(1) #6 THWN; 170 ft

CB: 103_103-UH-2

CUTLER-HAMMER (HFD)

15 A

MCC: 103_NH103MC2N

480V, 600A 13.7k SCA 42k SCAR

CB: 103_103-UH-4

CUTLER-HAMMER (HFD)

15 A

CB: 103_NH103MC2N

CUTLER-HAMMER (DSII-508)

800 A, 400 A Plug

F: 103_NH103MC2N

(1) #500 THWN; 240 ft

UNIT SUBSTATION

"US103"

SWBD: 103_NH103MSB

480V, 3200A 33.5k SCA 50k SCAR

CB: 103_NH103DP1S

CUTLER-HAMMER (DSII-508)

800 A, 600 A Plug

F: 103_NH103DP1S

(2) #350 THWN; 105 ft

CB: 103_NH103MC1S

CUTLER-HAMMER (DSII-508)

800 A, 400 A Plug

F: 103_NH103MC1S

(1) #500 THWN; 220 ft

CB: 103_NH103MSB (Fdr F4B)

CUTLER-HAMMER (DSII-508)

800 A, 800 A Plug

F: 103_NH103MSB (Fdr F4B)

(2) #500 THWN; 70 ft

CB: 103_NH104DP1N

CUTLER-HAMMER (DSII-508)

800 A, 600 A Plug

F: 103_NH104DP1N

(2) #350 THWN; 230 ft

CB: 103_NH103DP1N

CUTLER-HAMMER (DSII-508)

800 A, 600 A Plug

F: 103_NH103DP1N

(2) #350 THWN; 150 ft

CB: 103_NH103DP1 W/G

CUTLER-HAMMER (DSII-516)

1600 A, 1200 A Plug

F: 103_NH103DP1

(4) #350 THWN; 70 ft

SWBD: 103_NH103DP1

480V, 1600A 30.3k SCA 50k SCAR

CB: 103_ATS LS (N)

CUTLER-HAMMER (DSII-508)

800 A, 400 A Plug

CB: 103_ATS EQ (N)

CUTLER-HAMMER (DSII-508)

800 A, 800 A Plug

F: 103_ATS EQ (N)

(2) #500 THWN; 10 ft

F: 103_ATS LS (N)

(1) #500 THWN; 10 ft

CB: 103_NH103MSB Main W/G

CUTLER-HAMMER (DSII-632)

3200 A, 3000 A Plug

F: 103_SWBD NH103MSB

(1) #4000 Class B; 2 ft

XF: US103

2000kVA; 5.75%Z Pri: 12470V Sec: 480V

FU: US103

GE (EJO-1, 125E)

125 A

UTIL: US103

Isc 3P 4435 Amps Isc SLG 3240 Amps

UTIL: US103 (equip eval) Isc 3P 10545 Amps Isc SLG 8265 Amp

CONTINUE TO ATS:

103_LS

(SEE SHEET 103ED604)

CONTINUE TO PNL:

104_NH104DP1

(SEE SHEET 104ED602)

CONTINUE TO SWBD:

103_105

(SEE SHEET 103ED602)

CONTINUE TO ATS:

103_EQ

(SEE SHEET 103ED603)

NH103MSB

FEEDER F4C

DSII-508 PROVISION

NH103MSB

FEEDER F4D

DSII-508 PROVISION

GENERAL NOTES

BUILDING 103 - ONE LINE DIAGRAM (SUB US103)

EXISTING OVERCURRENT PROTECTIVE DEVICE

SETTINGS TO BE REVISED.

EXISTING OVERCURRENT PROTECTIVE DEVICE TO BE

REMOVED AND REPLACED.

2 2 2 2 2 2 2

1 1

2 2

BLDG 103 - EXISTING ONE-LINE

DIAGRAM (PART 1 OF 4)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

KEY NOTES

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,

TEMPORARY POWER PLANS, AND PHASING PLANS FOR

VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO

COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED

FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.

REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

3. FOR ALL OVERCURRENT PROTECTION DEVICE

REPLACEMENT WORK, REFERENCE ASSOCIATED

BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE

DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR

ADDITIONAL INFORMATION.

4. FOR ALL OVERCURRENT PROTECTION DEVICE

ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING

SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)

SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL

INFORMATION.

5. FOR ALL POWER DISTRIBUTION EQUIPMENT

REPLACEMENT OR ADDITION WORK, REFERENCE

ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION

EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.

6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT

BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,

IMMEDIATELY INFORM AND COORDINATE WITH VA AS

REQUIRED.

7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS

IMPACTED BY THIS PROJECT.

8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET

103EP601 FOR ALL MODIFICATIONS.

103ED601

SCALE : NTS

1 BLDG 103 - EXISTING ONE-LINE DIAGRAM (PART 1 OF 4)

CB: 103_Pnl NH103P5L

SQUARE D (FH)

60 A

F:103_Pnl NH103P5L

(1) #2 THWN; 45 ft

PNL: 103_NH103P5L

480V, 100A 16.4k SCA 200k SCAR

CB: 103_XF T-152

SQUARE D (FH)

90 A

F: 103_XF T-152

(1) #2 THWN; 20 ft

XF: 103_T-152

75kVA; 4.43%Z Pri: 480V Sec: 208V

F: 103_Pnl NL103P5C (SEC 1)

(1) #4/0 THWN; 15 ft

CB: 103_NL103P5C Main

CUTLER-HAMMER (ED)

225 A

PNL: 103_NL103P5C (Sec 1) 208V, 225A 4.2k SCA 200k SCAR

CB: 103_NCRAR DIMMER RACK

CUTLER-HAMMER (BAB)

40 A

F: 103_Pnl NL103P5C (SEC 2)

(1) #4/0 THWN; 15 ft

PNL: 103_NL103P5C (SEC 2)

208V, 225A 4.0k SCA 200k SCAR

CB: 103_Pnl B1H

SQUARE D (LH)

400 A

F:103_Pnl B1H

(1) #600 THWN; 160 ft

CB: 103_FAN RM

SQUARE D (FH)

100 A

F: 103_FAN RM

(1) #2 THWN; 160 ft

CB: 103_Pnl NH103P5M

SQUARE D (KA)

200 A

F: 103_Pnl NH103P5M

(1) #3/0 THWN; 60 ft

CB: 103_XF T-153

SQUARE D (FH)

90 A

F: 103_XF T-153

(1) #2 THWN; 20 ft

XF: 103_T-153

75kVA; 5.26%Z Pri: 480V Sec: 208V

F: 103_Pnl NL103P5D (SEC 1)

(1) #4/0 THWN; 20 ft

CB: 103_NL103P5D (SEC 1) Main

CUTLER-HAMMER (ED)

225 A

PNL: 103_NL103P5D (SEC 1)

208V, 225A 3.5k SCA 200k SCAR

F: 103_Pnl NL103P5D (SEC 2)

(1) #4/0 THWN; 5 ft

PNL: 103_NL103P5D (SEC 2)

208V, 225A 3.5k SCA 200k SCAR

F: 103_NH103MSB (FDR F4B)

(2) #500 THWN; 70 ft

CONTINUE TO SWBD:

103_NH103MSB

(SEE SHEET 103ED601)

CB: 103_TRAILER

SQUARE D (KA)

200 A

F: 103_TRAILER

(1) #2/0 THWN; 360 ft

XF: 103_TRAILER

150kVA; 5.45%Z Pri: 480V Sec: 208V

F: 103_Disc A

(1) #2/0 THWN; 5 ft

DISC: 103_Disc A 208V, 5.1k SCA

FU: 103_Disc A

BUSSMANN (FRS-R)

200 A

F: 103_Disc A

(1) #2/0 THWN; 1 ft

PNL: 103_PANEL A

208V, START OF SINGLE PHASE

F: 103_Disc B

(1) #2/0 THWN; 5 ft

DISC: 103_Disc B 208V, 5.1k SCA

FU: 103_Disc B

BUSSMANN (FRS-R)

200 A

F: 103_Disc B

(1) #2/0 THWN; 1 ft

PNL: 103_PANEL B

208V, CB: 103_RETURN FAN

CUTLER-HAMMER (GHB)

50 A

F: 103_RETURN FAN

(1) #10 THWN; 100 ft

VFD: 103_RETURN FAN

MTR: 103_RETURN FAN

1 @ 20.0 hp

CB: 103_SUPPLY FAN

CUTLER-HAMMER (GHB)

90 A

F: 103_SUPPLY FAN

(1) #8 THWN; 100 ft

VFD: 103_SUPPLY FAN

MTR: 103_SUPPLY FAN

1 @ 25.0 hp

TAP: 103_XF TRAILER SEC

208V, 5.2k SCA

CB: 103_HEATING PUMP P1

CUTLER-HAMMER (GHB)

20 A

F: 103_VFD HEATING PUMP P1

(1) #12 THWN; 80 ft

VFD: 103_Heating Pump P1

F: 103_HEATING PUMP P1

(1) #12 THWN; 10 ft

DISC: 103_HWP-1

480V, 1.6k SCA

FU: 103_HWP-1

LITTELFUSE (IDSR)

20 A

F: 103_HWP-1

(1) #12 THWN; 5 ft

MTR: 103_HWP-1

1 @ 2.0 hp

CB: 103_HEATING PUMP P2

CUTLER-HAMMER (GHB)

20 A

F: 103_VFD HEATING PUMP P2

(1) #12 THWN; 80 ft

VFD: 103_HEATING PUMP P2

F: 103_Heating Pump P2

(1) #12 THWN; 10 ft

DISC: 103_HWP-2

480V, 1.6k SCA

FU: 103_HWP-2

LITTELFUSE (IDSR)

20 A

F: 103_HWP-2

(1) #12 THWN; 5 ft

MTR: 103_HWP-2

1 @ 2.0 hp

CB: 103_HEATING PUMP P3

CUTLER-HAMMER (GHB)

20 A

F: 103_VFD HEATING PUMP P3

(1) #12 THWN; 80 ft

VFD: 103_HEATING PUMP P3

F: 103_HEATING PUMP P3

(1) #12 THWN; 10 ft

DISC: 103_P3 CIRC PUMP

480V, 1.6k SCA

FU: 103_P3 CIRC PUMP

LITTELFUSE (IDSR)

20 A

F: 103_P3 CIRC PUMP

(1) #12 THWN; 5 ft

MTR: 103_P-3 CIRC PUMP

1 @ 5.0 hp

PNL: 103_NH103P5M

480V, 225A 18.8k SCA 200k SCAR

CB: 103_FAN 1

SIEMENS (BQD)

20 A

F: 103_FAN 1

(1) #10 THWN; 25 ft

VFD: 103_FAN 1

MTR: 103_FAN 1

1 @ 7.5 hp

CB: 103_FAN 2

SIEMENS (BQD)

30 A

F: 103_FAN 2

(1) #10 THWN; 25 ft

VFD: 103_FAN 2

MTR: 103_FAN 2

1 @ 15.0 hp

CB: 103_FAN 3

SIEMENS (BQD)

30 A

F: 103_FAN 3

(1) #10 THWN; 35 ft

VFD: 103_FAN 3

MTR: 103_FAN 3

1 @ 15.0 hp

PNL: 103_FAN RM

480V, 125A 7.0k SCA 100k SCAR

CONTINUE TO PNL:

104_B1H

(SEE SHEET 104ED601)

START OF SINGLE PHASE

SWBD: 103_105, 480V, 800A

27.5k SCA 200k SCAR

GENERAL NOTES

BUILDING 103 - ONE LINE DIAGRAM (SWBD 105)

EXISTING OVERCURRENT PROTECTIVE DEVICE TO BE

REMOVED AND REPLACED.

EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS

TO BE REVISED.

BLDG 103 - EXISTING ONE-LINE

DIAGRAM (PART 2 OF 4)

11111

1111211

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

648-20-119

Date:Revisions:

Approved:

Approved:CHIEF, FACILITY MANAGEMENT SERVICE

MEDICAL CENTER DIRECTOR

CONSULTANT

VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR

CORRECT ELECTRICAL FCA

DEFICIENCIES BLDGS - VAORA/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

(206) 590-2118

RAY SPEES, PRESIDENT

DCW/LRL JGD/JRB01/31/2025

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

KEY NOTES

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE

REPORTED TO COR.

2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,

TEMPORARY POWER PLANS, AND PHASING PLANS FOR

VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO

COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED

FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.

REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION

OF ALL SHUTDOWNS.

3. FOR ALL OVERCURRENT PROTECTION DEVICE

REPLACEMENT WORK, REFERENCE ASSOCIATED

BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE

DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR

ADDITIONAL INFORMATION.

4. FOR ALL OVERCURRENT PROTECTION DEVICE

ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING

SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)

SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL

INFORMATION.

5. FOR ALL POWER DISTRIBUTION EQUIPMENT

REPLACEMENT OR ADDITION WORK, REFERENCE

ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION

EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.

6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT

BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,

IMMEDIATELY INFORM AND COORDINATE WITH VA AS

REQUIRED.

7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS

IMPACTED BY THIS PROJECT.

8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET

103EP602 FOR ALL MODIFICATIONS.

103ED602

SCA…