Attachment 8-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 6.pdf
PDF 4 MB Posted
- Solicitation number
- 36C26025R0071
About this file
This document is a detailed electrical one-line diagram for multiple buildings at the VA Portland Health Care System, part of a project to correct electrical facility condition assessment (FCA) deficiencies. The diagrams cover Buildings 101, 102, 103, 104, 105, and 006, providing comprehensive electrical distribution system layouts including switchboards, transformers, panelboards, motor control centers, and associated circuit breakers and connections.
The diagrams indicate a systematic approach to electrical system documentation, with each building's diagram showing detailed electrical infrastructure including voltage levels (primarily 480V and 208V), specific equipment manufacturers (predominantly Square D and Cutler-Hammer), and interconnections between various electrical components. Key notes consistently emphasize contractor responsibilities such as field verification of existing conditions, providing shutdown and power plans, and referencing specific schedules for overcurrent protective device replacements and adjustments. The project number 648-20-119 is consistently referenced, with an issue date of 01/31/2025, and the documents are marked as "Construction Documents" and "Fully Sprinklered".
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F: 101_Pnl UPS MAIN Panel
(1) #3/0 THWN; 160 FT
CB: 101_UPS MAIN PANEL Main
SQUARE D (KA)
200 A
PNL: 101_UPS MAIN PANEL
208V, 225A 2.5k SCA 200k SCAR
CB: 101_SUB PANEL 1
SQUARE D (QO)
50 A
F: 101_SUB PANEL 1
(1) #6 THWN; 30 ft
PNL: 101_UPS SUB PANEL 1
208V, 225A 2.1k SCA 200k SCAR
CB: 101_PANEL A
SQUARE D (QO)
100 A
F: 101_PANEL A
(1) #2 THWN; 80 ft
CB: 101_PDU 01
SQUARE D (QO)
100 A
F: 101_PDU 01
(1) #2 THWN; 70 ft
PNL: 101_PDU PANEL A
208V, 225A 2.0k SCA 200k SCAR
CB: 101_AGFA pals 1
SQUARE D (QO)
20 A
CB: 101_BIO MED RACK 2b
SQUARE D (QO)
20 A
CB: 101_PANEL B
SQUARE D (QO)
100 A
F: 101_PANEL B
(1) #2 THWN; 15 ft
PNL: 101_PANEL B
208V, 225A 2.4k SCA 65k SCAR
CB: 101_1C RISER
SQUARE D (QO)
50 A
F: 101_1C RISER
(1) #6 THWN; 150 ft
CB: 100_SP2-UPS Main
SQUARE D (Q2)
225 A
PNL: 100_SP2-UPS
208V, 225A 1.1k SCA 100k SCAR
CB: 101_B101 RISER 1DEL1-K1-24
SQUARE D (QO)
30 A
F: 101_B101 RISER 1DEL1-K1-24
(1) #6 THWN; 120 ft
PNL: 100_1DEL-K.1-24
208V, 100A 1.2k SCA 10k SCAR
CB: 101_PANEL A Main
SQUARE D (QO)
100 A
PNL: 101_PANEL A
208V, 225A 2.0k SCA 65k SCAR
CB: 101_SERVER RACK 7
SQUARE D (QO)
30 A
CB: 101_SERVER RACK 8
SQUARE D (QO)
30 A
CB: 101_BIO MED RACK 3a
SQUARE D (QO)
20 A
CB: 101_BIO MED RACK 1a
SQUARE D (QO)
20 A
CB: 101_GEIST UNIT #3
SQUARE D (QO)
30 A
CB: 101_AGFA pals
SQUARE D (QO)
20 A
CB: 101_BIO MED RACK 2a
SQUARE D (QO)
20 A
CB: 101_BIO MED RACK 1b
SQUARE D (QO)
20 A
CB: 101_BIO MED RACK 3b
SQUARE D (QO)
20 A
CB: 101_PDU PANEL B
SQUARE D (QD)
225 A
F: 101_PDU PANEL B
(1) #225 Class B; 1 ft
PNL: 101_PDU PANEL B
208V, 225A 2.0k SCA 200k SCAR
CB: 101_BIO MEDS RACK 2d
SQUARE D (QO)
20 A
CB: 101_BIO MED RACK 2c
SQUARE D (QO)
20 A
CB: 101_AGFA pals 2
SQUARE D (QO)
20 A
CB: 101_BIO MED RACK 1c
SQUARE D (QO)
20 A
CB: 101_BIO MED RACK 3c
SQUARE D (QO)
20 A
CB: 101_BIO MEDS RACK 1d
SQUARE D (QO)
20 A
CB: 101_BIO MEDS RACK 3d
SQUARE D (QO)
20 A
CB: 101_AGFA pals 3
SQUARE D (QO)
20 A
PNL: 101_PDU 01
208V, 310A 2.0k SCA 200k SCAR
CB: 101_PDU PANEL A
SQUARE D (QO)
225 A
F: 101_PDU PANEL A
(1) #225 Class B; 1 ft
CONTINUE TO XF: 100_UPS
(SEE SHEET 100ED610)
BLDG 101 - EXISTING ONE-LINE
DIAGRAM (PART 1 OF 5)
BUILDING 101 - ONE LINE DIAGRAM (UPS-1-UPS-2)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET
101EP601 FOR ALL MODIFICATIONS.
101ED601
SCALE : NTS
1 BLDG 101 - EXISTING ONE-LINE DIAGRAM (PART 1 OF 5)
SHEET IS INCLUDED FOR OVERALL ONE-LINE DIAGRAM
COMPLETENESS AND AS-BUILDING PURPOSES.
PNL: 101_PLSL1-N-26
208V, 30A 0.5k SCA 65k SCAR
CB: 101_PLSL1-N-26 Main SQUARE D (Q1(B)-VH (Obs.)) 30 A
F: 101_Pnl PLSL1-N-26
(1) #8 THWN; 10 ft
XF: 101_T-110
9kVA; 4.30%Z Pri: 480V Sec: 208V
F: 101_XFMR T-110
(1) #12 THWN; 10 ft
CB: 101_XFMR T-110
SQUARE D (EH)
15 A
PNL: 101_PLSHI-N-26
480V, 125A 1.9k SCA 14k SCAR
CB: 101_AirCompressor
SQUARE D (EH)
15 A
PNL: 101_2LSL1-K.1-24
208V, 30A 0.5k SCA 22k SCAR
CB: 101_2LSL1-K.1-24 Main SQUARE D (Q1(B)-VH (Obs.)) 30 A
F: 101_Pnl 2LSL1-K.1-24
(1) #10 THWN; 10 ft
XF: 101_T-99
9kVA; 4.40%Z Pri: 480V Sec: 208V
F: 101_XFMR T-99
(1) #10 THWN; 10 ft
CB: 101_XFMR T-99
SQUARE D (EH)
20 A
PNL: 101_2LSH1-K1-24
480V, 125A 1.1k SCA 14k SCAR
F: 101_2LSH1-K.1-24
(1) #6 THWN; 300 ft
CB: 101_2LSH1-K.1-24
SQUARE D (FA)
40 A
F: 101_Pnl 101-LSP
(1) #1 THWN; 80 ft
ATS: 101_LS-101-1
600 A
F: 101_ATS-LS-101-1
(1) #1 THWN; 120 ft
F: 100_ATS-LS-101-1 (E)
(1) #2 THWN; 410 ft
CB: 101_PLSH1-N-26
SQUARE D (FA)
40 A
F: 101_PLSH1-N-26
(1) #6 THWN; 80 ft
PNL: 101_101-LSP
480V, 225A 2.6k SCA 65k SCAR
CB: 101_PLSL1-L.7-21
SQUARE D (FA)
15 A
F: 101_Pnl PLSL1-L.7-2 XFMR
(1) #12 THWN; 10 ft
XF: 101_T-112
9kVA; 4.40%Z Pri: 480V Sec: 208V
F: 101_Pnl PLSL1-L.7-21
(1) #10 THWN; 10 ft
CB: 101_PLSL1-L.7-21 Main SQUARE D (Q1(B)-VH (Obs.)) 30 A
PNL: 101_PLSL1-L.7-21
208V, 30A 0.5k SCA 65k SCAR
MCP: 101_RWP-2
SQUARE D (FAL)
MCP: 101_RWP-1
SQUARE D (FAL)
MCP: 101_101-P-3
SQUARE D (FAL)
MCP: 101_101-P-4
SQUARE D (FAL)
MCP: 101_101-EF-P15
SQUARE D (FAL)
MCP: 101_101-EF-P11
SQUARE D (FAL)
MCP: 101_101-EF-P9
SQUARE D (FAL)
MCP: 101_101-EF-P5
SQUARE D (FAL)
MCP: 101_101-RF-1
SQUARE D (FAL)
F: 101_101-RF-1
(1) #10 THWN; 160 ft
VFD: 101_RF-1
MTR: 100_RF-1
6 @ 1.5 hp
MCP: 101_101-SF-3
SQUARE D (KAL)
F: 101_101-SF-3
(1) #1/0 THWN; 160 ft
VFD: 101_SF-3
MTR: 101_SF-3
8 @ 10.0 hp
MCP: 101_101-SF-4
SQUARE D (KAL)
F: 101_101-SF-4
(1) #3 THWN; 160 ft
VFD: 101_SF-4
MTR: 100_SF-4
6 @ 7.5 hp
MCP: 101_101-SF-1
SQUARE D (KAL)
F: 101_101-SF-1
(1) #3 THWN; 140 ft
VFD: 101_SF-1
MTR: 101_SF-1
6 @ 7.5 hp
MCP: 101_101-EF-P17
SQUARE D (FAL)
F: 101_101-MCC-P_2
(1) #600 Class B; 1 ft
MCC: 101_MCC-P
480V, 600A 23.8k SCA 42k SCAR
CONTINUE TO ATS: 101_DE-101-1
(SEE SHEET 101ED604)
F: 101_ATS-DE-101-1 (N)
(2) #350 THWN; 210 ft
CB: 101_ATS-DE-101-1 W/G
SQUARE D (DS 416)
600 A
CB: 101_ATS-LS-101-1 W/G
SQUARE D (DS 416)
100 A
F: 101_ATS-LS-101-1
(1) #1 THWN; 120 ft
CB: 101_Normal Riser W/G
SQUARE D (DS 416)
1200 A
F: 101_Normal Riser
(1) #1200 Class B; 160 ft
CB: 101_101-MCC-P W/G
SQUARE D (DS 416)
1600 A
F: 101_101-MCC-P
(2) #350 THWN; 80 ft
SWBD: 101_US101
480V, 3000A 29.5k SCA 50k SCAR
CB: 101_US101 Main W/G
SQUARE D (DS 632)
3200 A
F: 101_SWBD US101
(1) #3200 Class B; 1 ft
XF: US101
2000kVA; 6.07%Z Pri: 12470V Sec: 480V
FU: US101
GE (EJO-1, 125E)
125 A
UTIL: US101
Isc 3P 4409 Amps Isc SLG 3218 Amps
MCC: 101_MCC-P_2
480V, 600A 23.7k SCA 42k SCAR
MCP: 101_Blast Fan #2
SQUARE D (FA)
20 A
MCP: 101_101-P17
SQUARE D (FAL)
MCP: 101_101-P-2
SQUARE D (FAL)
MCP: 101_101-P-1
SQUARE D (FAL)
MCP: 101_101-EF-P14
SQUARE D (FAL)
MCP: 101_101-SF-P1
SQUARE D (FAL)
MCP: 101_101-EF-P8
SQUARE D (FAL)
MCP: 101_101-RF-2
SQUARE D (FAL)
F: 101_101-RF-2
(1) #10 THWN; 160 ft
VFD: 101_RF-2
MTR: 101_RF-2
6 @ 1.5 hp
MCP: 101_101-SF-2
SQUARE D (FAL)
F: 101_101-SF-2
(1) #3 THWN; 160 ft
VFD: 101_SF-2
MTR: 101_SF-2
4 @ 10.0 hp
MCP: 101_101-EF-P1
SQUARE D (FAL)
CB: 101_Air Compressor
SQUARE D (FA)
40 A
CONTINUE TO BD: 101_101-N6
(SEE SHEET 101ED603)
CONTINUE TO SWBD:
100_2500A SWBD
GENERAL NOTES
BUILDING 101 - ONE LINE DIAGRAM (ATS-LS-101-1, SUB US101)
EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS
TO BE REVISED.
EXISTING OVERCURRENT PROTECTIVE DEVICE TO BE
REMOVED AND REPLACED.
EXISTING EQUIPMENT TO BE MODIFIED.
BLDG 101 - EXISTING ONE-LINE
DIAGRAM (PART 2 OF 5)
2 2 2 2
222222222222
2 2 2 2 2 2 2 2 2 2 2 2
SPACESPACESPACESPACESPACESPACESPACESPACE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET
101EP602 FOR ALL MODIFICATIONS.
101ED602
SCALE : NTS
1 BLDG 101 - EXISTING ONE-LINE DIAGRAM (PART 2 OF 5)
CONTINUE TO SWBD:
101_US101
(SEE SHEET 101ED602)
F: 101_NORMAL RISER
(1) #1200 CLASS B; 160 ft
BD: 101_101-N6
480V, 1000A 25.1k SCA 85k SCAR
F: 101_BD 101-N5
(1) #1200 CLASS B; 25 ft
FU: 101_T-107
BUSSMANN (FRS-R)
100 A
FU: 101_6H1-K-27
BUSSMANN (FRS-R)
100 A
F: 101_6H1-K-27
(1) #2 THWN; 60 ft
PNL: 101_6H1-K-27
480V, 225A 13.3k SCA 14k SCAR
CB: 101_CAGE WASHER 10HP
SQUARE D (EH)
30 A
F: 101_T-107
(1) #2 THWN; 60 ft
XF: 101_T-107
75kVA; 4.90%Z Pri: 480V Sec: 208V
F: 101_PNL 6SDN-K-27
(1) #4/0 THWN; 10 ft
CB: 101_SPARE IN RM 613
SQUARE D (EH)
20 A
CB: 101_HW-509 2HP
SQUARE D (EH)
20 A
CB: 101_DISPOSER 5HP
SQUARE D (EH)
20 A
F: 101_PH1-K-27
(1) #1 THHN; 60 ft
PNL: 101_PH1-K-27
480V, 125A 9.1k SCA 14k SCAR
CB: 100_XFMR T-109
SQUARE D (EH)
20 A
F: 101_XFMR T-109
(1) #12 THWN; 30 ft
XF: 101_T-109
9kVA; 4.40%Z Pri: 480V Sec: 208V
F: 101_PL1-K-27
(1) #10 THWN; 30 ft
CB: 101_PL1-K-27 MAIN
SQUARE D (Q1(B)-VH (OBS.))
30 A
PNL: 101_PL1-K-27
208V, 30A 0.5k SCA 65k SCAR
FU: 101_T-105
BUSSMANN (FRS-R)
400 A
F: 101_T-105
(1) #500 THWN; 150 ft
XF: 101_T-105
225kVA; 4.60%Z Pri: 480V Sec: 208V
F: 101_SWBD 5SDN-K.1-24
(2) #500 THWN; 10 ft
FU: 101_5H1-K-27
BUSSMANN (FRS-R)
100 A
F: 101_5H1-K-27
(1) #1 THWN; 20 ft
FU: 101_T-103
BUSSMANN (FRS-R)
400 A
F: 101_T-103
(1) #500 THWN; 60 ft
XF: 101_T-103
225kVA; 4.60%Z Pri: 480V Sec: 208V
F: 101_SWBD 4SDN-K.1-24
(2) #500 THWN; 10 ft
BD: 101_101-N5
480V, 1200A 24.5k SCA 85k SCAR
F: 101_BD 101-N4
(1) #1200 CLASS B; 25 ft
BD: 101_101-N4
480V, 1200A 23.9k SCA 85k SCAR
F: 101_BD 101-N2
(1) #1200 CLASS B; 50 ft
FU: 101_T-98
BUSSMANN (FRS-R)
175 A
F: 101_T-98
(1) #2/0 THWN; 120 ft
XF: 101_T-98
113kVA; 6.20%Z Pri: 480V Sec: 208V
F: 101_PNL 2L2-K.1-24
(1) #350 THWN; 10 ft
FU: 101_T-97
BUSSMANN (FRS-R)
175 A
F: 101_T-97
(1) #2/0 THWN; 100 ft
XF: 101_T 97
113kVA; 6.20%Z Pri: 480V Sec: 208V
F: 101_PNL 2L2-K-27
(1) #350 THWN; 20 ft
BD: 101_101-N2
480V, 1200A 22.8k SCA 85k SCAR
FU: 101_2H1-K-27/3H1-K-27
BUSSMANN (FRS-R)
200 A
F: 101_2H1-K-27/3H1-K-27
(1) #3/0 THWN; 20 ft
F: 101_PNL 3H1-K-27
(1) #2/0 THWN; 25 ft
PNL: 101_3H1-K-27
480V, 225A 17.1k SCA 14k SCAR
F: 101_PNL 1H1-K-27
(1) #3/0 THWN; 30 ft
PNL: 101_1H1-K-27
480V, 225A 17.0k SCA 14k SCAR
PNL: 101_2HI-K-27
480V, 225A 20.1k SCA 14k SCAR
PNL: 101_2L2-K-27
208V, 400A 4.2k SCA 65k SCAR
CB: 101_UNKNOWN
SQUARE D (Q2)
225 A
F: 101_UNKNOWN
(1) #3/0 THWN; 35 FT
PNL: 101_1L2-K-27
208V, 225A 3.8k SCA 65k SCAR
CB: 101_1L1-K-27
SQUARE D (Q2)
225 A
F: 101_1L1-K-27
(1) #4/0 THWN; 35 ft
PNL: 101_1L1-K-27
208V, 225A 3.8k SCA 65k SCAR
PNL: 101_2L2-K.1-24
208V, 400A 4.2k SCA 50k SCAR
CB: 101_2L3-K.1-24
SQUARE D (Q2)
225 A
F: 101_2L3-K.1-24
(1) #4/0 THWN; 30 ft
PNL: 101_2L3-K.1-24
208V, 225A 3.9k SCA 65k SCAR
CB: 101_3L1-K-27
SQUARE D (Q2)
225 A
CB: 101_2L1-K-27
SQUARE D (Q2)
225 A
CB: 101_2L2-K-27 SEC 2
SQUARE D (FA)
70 A
F: 101_2L2-K-27 SEC 2
(1) #2 THWN; 35 ft
PNL: 101_2L2-K-27 SEC 2
208V, 100A 3.6k SCA 65k SCAR
F: 101_2L1-K-27
(1) #4/0 THWN; 10 ft
PNL: 101_2L1-K-27
208V, 225A 4.1k SCA 65k SCAR
F: 101_3L1-K-27
(1) #4/0 THWN; 35 ft
PNL: 101_3L1-K-27
208V, 225A 3.8k SCA 65k SCAR
PNL: 101_6SDN-K-27
208V, 225A 3.7k SCA 65k SCAR
CB: 101_6L1-L.7-23
SQUARE D (FA)
100 A
F: 101_6L1-L.7-23
(1) #4 THWN; 80 ft
PNL: 101_6L1-L.7-23
208V, 100A 2.3k SCA 65k SCAR
CB: 101_6L1-K-25
SQUARE D (FA)
60 A
CB: 101_6L1-L.7-27
SQUARE D (FA)
100 A
(1) #4 THWN; 140 ft
PNL: 101_6L1-K-25
208V, 100A 1.7k SCA 65k SCAR
F: 101_6L1-K-27
(1) #2 THWN; 80 ft
PNL: 101_6L1-K-27
208V, 100A 2.7k SCA 65k SCAR
CB: 101_1L1-K.1-24 SEC 2
SQUARE D (FA)
100 A
F: 101_1L1-K.1-24 SEC 2
(1) #1 THWN; 30 ft
PNL: 101_1L1-K.1-24 SEC 2
208V, 100A 3.7k SCA 65k SCAR
CB: 101_3L1-K.1-24
SQUARE D (Q2)
225 A
F: 101_3L1-K.1-24
(1) #4/0 THWN; 30 ft
PNL: 101_3L1-K.1-24 SEC 1
208V, 225A 3.9k SCA 65k SCA
F: 101_Pnl 3L1-K.1-24 SEC 2
(1) #4/0 THWN; 15 ft
PNL: 101_3L1-K.1-24 SEC 2
208V, 225A 3.8k SCA 65k SCAR
CB: 101_1L1-K.1-24
SQUARE D (Q2)
225 A
F: 101_1L1-K.1-24
(1) #4/0 THWN; 30 ft
PNL: 101_1L1-K.1-24 SEC 1
208V, 100A 3.9k SCA 65k SCAR
CB: 101_2L1-K.1-24
SQUARE D (Q2)
225 A
F: 101_2L1-K.1-24
(1) #4/0 THWN; 30 ft
PNL: 101_2L1-K.1-24
208V, 225A 3.9k SCA 65k SCAR
SWBD: 101_5SDN-K.1-24
208V, 800A 9.4k SCA 50k SCAR
CB: 101_5L1-L.6-26
SQUARE D (FA)
100 A
F: 101_5L1-L.6-26
(1) #2 THWN; 80 ft
PNL: 101_5L1-L.6-26
208V, 100A 4.6k SCA 65k SCAR
CB: 101_5L1-K.1-22
SQUARE D (Q2)
125 A
F: 101_5L1-K.1-22
(1) #1 THWN; 60 ft
PNL: 101_5L1-K.1-22
208V, 225A 5.8k SCA 65k SCAR
CB: 101_5L1-K-26
SQUARE D (FA)
100 A
F: 101_5L1-K-26
(1) #2 THWN; 100 ft
PNL: 101_5L1-K-26
208V, 225A 4.0k SCA 65k SCAR
CB: 101_5L1-K-27
SQUARE D (FA)
50 A
F: 101_5L1-K-27
(1) #6 THWN; 160 ft
PNL: 101_5L1-K-27
208V, 225A 1.4k SCA 65k SCAR
CB: 101_5L1-L.7-24
SQUARE D (Q2)
150 A
F: 101_5L1-L.7-24
(1) #1/0 THWN; 180 ft
PNL: 101_5L1-L.7-24
208V, 225A 3.5k SCA 65k SCAR
CB: 101_5L1-L.7-25
SQUARE D (FA)
100 A
F: 101_5L1-L.7-25
(1) #2 THWN; 160 ft
PNL: 101_5L1-L.7-25
208V, 100A 2.9k SCA 65k SCAR
CB: 101_5L1-K.1-24
SQUARE D (FA)
50 A
F: 101_5L1-K.1-24
(1) #6 THWN; 60 ft
PNL: 101_5L1-K.1-24
208V, 100A 3.2k SCA 65k SCAR
CB: 101_5L1-K-22
SQUARE D (Q2)
125 A
F: 101_5L1-K-22
(1) #1 THWN; 110 ft
PNL: 101_5L1-K-22
208V, 225A 4.2k SCA 65k SCAR
CB: 101_5L1-L.6-22
SQUARE D (FA)
70 A
F: 101_5L1-L.6-22
(1) #2 THWN; 80 ft
PNL: 101_5L1-L.6-22
208V, 100A 4.6k SCA 65k SCAR
CB: 101_5L1-K-24
SQUARE D (FA)
100 A
F: 101_5L1-K-24
(1) #2 THWN; 50 ft
PNL: 101_5L1-K-24
208V, 225A 5.9k SCA 65k SCAR
PNL: 101_5H1-K-27
480V, 225A 20.3k SCA 14k SCAR
CB: 101_SPARE
SQUARE D (EH)
20 A
CB: 101_LIEBERT AC CONDENSER 2
SQUARE D (EH)
20 A
CB: 101_FREEZER BY 506E
SQUARE D (EH)
20 A
CB: 101_LIEBERT AC CONDENSER
SQUARE D (EH)
30 A
CB: 101_4TH FLOOR COOLING UNIT
SQUARE D (EH)
20 A
F: 101_Pnl 4H1-K-27
(1) #1 THWN; 25 ft
PNL: 101_4H1-K-27
480V, 125A 16.2k SCA 14k SCAR
CB: 101_XFMR 4L1-K-27
SQUARE D (EH)
30 A
F: 101_XFMR 4L1-K-27
(1) #10 THWN; 120 ft
XF: 101_T-101
23kVA; 5.00%Z Pri: 480V Sec: 208V
F: 101_PNL 4L2-K.1-24
(1) #4 THWN; 30 ft
CB: 101_4L2-K.1-24 MAIN
SQUARE D (Q1(B)-VH (OBS.))
50 A
PNL: 101_4L2-K.1-24
208V, 50A 1.0k SCA 65k SCAR
CB: 101_4L1-L.6-23
SQUARE D (Q2)
150 A
F: 101_4L1-L.6-23
(1) #1/0 THWN; 60 ft
PNL: 101_4L1-L.6-23
208V, 225A 6.5k SCA 65k SCAR
CB: 101_4L1-K-23
SQUARE D (Q2)
150 A
F: 101_4L1-K-23
(1) #1/0 THWN; 140 ft
PNL: 101_4L1-K-23
208V, 225A 4.2k SCA 65k SCAR
CB: 101_4L1-L.7-25
SQUARE D (FA)
100 A
F: 101_4L1-L.7-25
(1) #1 THWN; 120 ft
PNL: 101_4L1-L.7-25
208V, 100A 4.1k SCA 65k SCAR
NO SCALE
CB:101_RECP RM 414
SQUARE D (FA)
50 A
CB: 101_4L1-K.1-27
SQUARE D (Q2)
125 A
F: 101_4L1-K.1-27
(1) #1/0 THWN; 90 ft
PNL: 101_4L1-K.1-27
208V, 225A 5.4k SCA 65k SCAR
CB: 101_4L1-K.1-24
SQUARE D (KH)
225 A
F: 101_4L1-K.1-24
(1) #4/0 THWN; 20 ft
PNL: 101_4L1-K.1-24
208V, 225A 9.1k SCA 65k SCAR
CB: 101_AUTOCLAVE RM 412
SQUARE D (QO)
40 A
CB: 101_4L1-L.7-22
SQUARE D (Q2)
200 A
F: 101_4L1-L.7-22
(1) #1/0 THWN; 80 ft
PNL: 101_4L1-L.7-22
208V, 225A 5.8k SCA 65k SCAR
CB: 101_4L1-K-26
SQUARE D (Q2)
150 A
F: 101_4L1-K-26
(1) #1/0 THWN; 100 ft
PNL: 101_4L1-K-26
208V, 225A 5.1k SCA 65k SCAR
CB: 101_4L1-L.5-27
SQUARE D (FA)
70 A
F: 101_4L1-L.5-27
(1) #4 THWN; 80 ft
PNL: 101_4L1-L.5-27
208V, 100A 3.6k SCA 65k SCAR
CB: 101_RECP RM 414 (2)
SQUARE D (FA)
50 A
CB: 101_4L1-L.7-24
SQUARE D (Q2)
125 A
F: 101_4L1-L.7-24
(1) #1 THWN; 110 ft
PNL: 101_4L1-L.7-24
208V, 225A 4.4k SCA 65k SCAR
CB: 101_4L1-L.6-24
SQUARE D (Q2)
125 A
F: 101_4L1-L.6-24
(1) #1 THWN; 120 ft
PNL: 101_4L1-L.6-24
208V, 225A 4.1k SCA 65k SCAR
SWBD: 101_4SDN-K.1-24
208V, 800A 10.1k SCA 50k SCAR
CB: 101_4L1-K-27
SQUARE D (FA)
30 A
F: 101_4L1-K-27
(1) #10 THWN; 80 ft
PNL: 101_4L1-K-27
208V, 100A 1.2k SCA 65k SCAR
GENERAL NOTES
BUILDING 101 - ONE LINE DIAGRAM (NORMAL RISER)
BLDG 101 - EXISTING ONE-LINE
DIAGRAM (PART 3 OF 5)
2 2 2
2 2
222 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS
TO BE REVISED.
EXISTING OVERCURRENT PROTECTIVE DEVICE TO BE
DEMOLISHED AND REPLACED.
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET
101EP603 FOR ALL MODIFICATIONS.
101ED603
SCALE : NTS
1 BLDG 101 - EXISTING ONE-LINE DIAGRAM (PART 3 OF 5)
100_SUB-B2-GENSD-G5
F: 100_SWBD 101-EDP (E)
(2) #500 THWN; 410 ft
F: 101_ATS-DE-101-1 (N)
(2) #350 THWN; 210 ft
ATS: 101_DE-101-1
600 A
F: 101_SWBD 101-DE-1P
(2) #350 THWN; 120 ft
CB: 101_XFMR T-102
SQUARE D (KA)
175 A
F: 101_XFMR T-102
(1) #2/0 THWN; 80 ft
XF: 101_T-102
113kVA; 6.20%Z Pri: 480V Sec: 208V
F: 101_SWBD 4SDDE1-K-27
(1) #500 THWN; 20 ft
CB: 101_XFMR T-136
SQUARE D (KA)
70 A
F: 101_XFMR T-136
(1) #4 THWN; 130 ft
XF: 101_T-136
45kVA; 6.20%Z Pri: 480V Sec: 208V
F: 101_Pnl Verizon Pnl.
(1) #2 THWN; 10 ft
CB: 101_Verizon Pnl. Main
SQUARE D (QO)
100 A
PNL: 101_Verizon Pnl.
208V, 100A 1.7k SCA 65k SCAR
CB: 101_TVSS/ Power Fail Relay
SQUARE D (QO)
40 A
CB: 101_5DEH1-K-27
SQUARE D (KA)
125 A
F: 101_5DEH1-K-27
(1) #1 THWN; 240 ft
CB: 101_6CH1-K-27
SQUARE D (FA)
100 A
F: 101_6CH1-K-27
(1) #4 THWN; 200 ft
CB: 101_SWBD 101-PESDP
SQUARE D (LA)
300 A
F: 101_SWBD 101-PESDP
(1) #350 THWN; 80 ft
PNL: 101_6CH1-K-27
480V, 100A 3.3k SCA 14k SCAR
PNL: 101_PDEL1-N-26
208V, 30A 0.7k SCA 65k SCAR
CB: 101_XFMR T-104
SQUARE D (KA)
175 A
F: 101_XFMR T-104
(1) #2/0 THWN; 240 ft
XF: 101_XFMR T-104
150kVA; 5.10%Z Pri: 480V Sec: 208V
F: 101_SWBD 5SDDEL-K-27
(1) #500 THWN; 10 ft
CB: 101_XFMR T-111
SQUARE D (FA)
30 A
F: 101_XFMR T-111
(1) #10 THWN; 80 ft
XF: 101_T-111
15kVA; 5.40%Z Pri: 480V Sec: 208V
F: 101_Pnl PDEL1-N-26
(1) #8 THWN; 20 ft
CB: 101_PDEL1-N-26 Main SQUARE D (Q1(B)-VH (Obs.)) 50 A
CB: 101_IPU X-RAY
SQUARE D (FA)
100 A
CB: 101_Well Water Stoage Tank
SQUARE D (FA)
100 A
CB: 101_XFMR T-108
SQUARE D (FA)
70 A
F: 1F: 101_XFMR T-108
(1) #4 THWN; 200 ft
XF: 101_T-108
45kVA; 6.10%Z Pri: 480V Sec: 208V
F: 101_Pnl 6SDDE1-K.1-24
(1) #4/0 THWN; 20 ft
CB: 101_101-MCC-DE1
SQUARE D (KA)
200 A
F: 101_101-MCC-DE1
(1) #3/0 THWN; 20 ft
DISC: 101_MCC-DE-1
480V, 9.6k SCA
F: 101_MCC-DE1
(1) #3/0 THWN; 10 ft
Start of Single Phase
Open
SWBD: 101_101-DE-1P
480V, 600A 10.1k SCA 50k SCAR
FU: 101_MCC-DE1
BUSSMANN (LPS-RK)
500 A
MCP: 101_101-EF-P7
SQUARE D (FAL)
CB: 101_XFMR T-108
SQUARE D (FA)
70 A
MCP: 101_101-EF-P3
SQUARE D (FAL)
MCP: 101_101-EF-P2
SQUARE D (FAL)
MCP: 101_101-EF-P4
SQUARE D (FAL)
CB: 101_DI Pump 2HP
SQUARE D (EH)
20 A
PNL: 101_5DEH1-K-27
480V, 225A 4.5k SCA 14k SCAR
CB: 101_Loading Dock Door 2HP
SQUARE D (EH)
20 A
CB: 101_Elevator S-11
SQUARE D (KA)
150 A
F: 101_Elevator S-11
(1) #4 THWN; 120 ft
XF: 101_Elevator S-11 45kVA; 4.00%Z Pri: 480V Sec: 480V
VFD: 101_Elevator S-11
MTR: 101_Elevator S-11 1 @ 40.0 hp
CB: 101_Elevator S-12
SQUARE D (FA)
100 A
F: 101_Elevator S-12
(1) #6 THWN; 100 ft
XF: 101_Elevator S-12 34kVA; 5.00%Z Pri: 480V Sec: 480V
VFD: 101_Elevator S-12
MTR: 101_Elevator S-12 1 @ 25.0 hp
CB: 101_Elevator P-7
SQUARE D (KA)
150 A
F: 101_Elevator P-7
(1) #4 THWN; 120 ft
XF: 101_Elevator P-7 34kVA; 5.00%Z Pri: 480V Sec: 480V
VFD: 101_Elevator P-7
MTR: 101_Elevator P-7 1 @ 30.0 hp
CB: 101_Elevator P-8
SQUARE D (KA)
150 A
F: 101_Elevator P-8
(1) #4 THWN; 120 ft
XF: 101_Elevator P-8 34kVA; 5.00%Z Pri: 480V Sec: 480V
VFD: 101_Elevator P-8
MTR: 101_Elevator P-8 1 @ 30.0 hp
SWBD: 101_101-PESDP
480V, 400A 8.6k SCA 50k SCAR
CB: 101_5DEL1-K.1-24
SQUARE D (FA)
100 A
F: 101_5DEL1-K.1-24
(1) #2 THWN; 110 ft
PNL: 101_5DEL1-K.1-24
208V, 100A 2.8k SCA 65k SCAR
CB: 101_5DEL1-K.6-24
SQUARE D (FA)
40 A
F: 101_5DEL1-K.6-24
(1) #8 THWN; 160 ft
CB: 101_5DEL1-L.7-24
SQUARE D (FA)
70 A
F: 101_5DEL1-L.7-24
(1) #4 THWN; 90 ft
PNL: 101_5DEL1-L.7-24
208V, 100A 2.5k SCA 65k SCAR
CB: 101_5DEL1-L.6-22
SQUARE D (FA)
40 A
F: 101_5DEL1-L.6-22
(1) #4 THWN; 100 ft
PNL: 101_5DEL1-L.6-22
208V, 100A 2.3k SCA 65k SCAR
CB: 101_5DEL1-K-22
SQUARE D (FA)
100 A
F: 101_5DEL1-K-22
(1) #1 THWN; 120 ft
PNL: 101_5DEL1-K-22
208V, 100A 2.9k SCA 65k SCAR
CB: 101_5DEL1-K-24
SQUARE D (FA)
70 A
F: 101_5DEL1-K-24
(1) #4 THWN; 160 ft
PNL: 101_5DEL1-K-24
208V, 100A 1.7k SCA 65k SCAR
PNL: 101_5DEL1-K.6-24
208V, 100A 0.8k SCA 65k SCAR
CB: 101_100-UC-15 (3/4 HP)
SQUARE D (QO-VH)
20 A
CB: 101_100-US-12 (3/4 HP)
SQUARE D (QO-VH)
20 A
CB: 101_5DEL1-K-26
SQUARE D (Q2)
150 A
F: 101_5DEL1-K-26
(1) #1/0 THWN; 80 ft
PNL: 101_5DEL1-K-26
208V, 225A 3.6k SCA 65k SCAR
SWBD: 101_5SDDEL-K-27
208V, 400A 4.9k SCA 50k SCAR
CB: 101_5DEL1-K-27
SQUARE D (FA)
50 A
PNL: 101_5DEL1-K-27
208V, 100A 1.8k SCA 65k SCAR
CB: 101_5DEL1-L.7-25
SQUARE D (FA)
70 A
F: 101_5DEL1-L.7-25
(1) #4 THWN; 60 ft
PNL: 101_5DEL1-L.7-25
208V, 100A 3.1k SCA 65k SCAR
CB: 101_5DEL1-L.6-26
SQUARE D (FA)
70 A
F: 101_5DEL1-L.6-26
(1) #4 THWN; 110 ft
PNL: 101_5DEL1-L.6-26
208V, 100A 2.2k SCA 65k SCAR
CB: 101_5DEL1-K.1-22
SQUARE D (FA)
60 A
F: 101_5DEL1-K.1-22
(1) #6 THWN; 120 ft
PNL: 101_5DEL1-K.1-22
208V, 100A 1.5k SCA 65k SCAR
F: 101_5DEL1-K-27
(1) #6 THWN; 100 ft
CB: 101_6DEL1-K.1-24
SQUARE D (FA)
70 A
F: 101_6DEL1-K.1-24
(1) #4 THWN; 100 ft
PNL: 101_6DEL1-K.1-24
208V, 100A 1.2k SCA 65k SCAR
PNL: 101_6SDDE1-K.1-24
208V, 225A 1.7k SCA 65k SCAR
CB: 101_6DEL1-K-25
SQUARE D (FA)
40 A
F: 101_6DEL1-K-25
(1) #6 THWN; 80 ft
PNL: 101_6DEL1-K-25
208V, 100A 1.2k SCA 65k SCAR
CB: 101_6DEL1-K-27
SQUARE D (FA)
70 A
F: 101_6DEL1-K-27
(1) #4 THWN; 90 ft
PNL: 101_6DEL1-K-27
208V, 100A 1.3k SCA 65k SCAR
CB: 101_6DEL1-L.7-23
SQUARE D (FA)
100 A
F: 101_6DEL1-L.7-23
(1) #1 THWN; 80 ft
PNL: 101_6DEL1-L.7-23
208V, 100A 1.4k SCA 65k SCAR
CB: 101_6DEL1-L.7-26
SQUARE D (FA)
70 A
F: 101_6DEL1-L.7-26
(1) #4 THWN; 110 ft
PNL: 101_6DEL1-L.7-26
208V, 100A 1.2k SCA 65k SCAR
CB: 101_6DEL1-K-24
SQUARE D (Q2)
125 A
F: 101_6DEL1-K-24
(1) #1 THWN; 20 ft
PNL: 101_6DEL1-K-24
208V, 225A 1.6k SCA 65k SCAR
CB: 101_4DEL1-K-27
SQUARE D (FA)
100 A
F: 101_4DEL1-K-27
(1) #4 THWN; 80 ft
PNL: 101_4DEL1-K-27
208V, 100A 2.4k SCA 65k SCAR
SWBD: 101_4SDDE1-K-27
208V, 400A 3.8k SCA 50k SCAR
CB: 101_4DEL1-K-23
SQUARE D (FA)
70 A
F: 101_4DEL1-K-23
(1) #4 THWN; 160 ft
PNL: 101_4DEL1-K-23
208V, 100A 1.6k SCA 65k SCAR
CB: 101_4DEL1-L.6-23
SQUARE D (FA)
70 A
F: 101_4DEL1-L.6-23
(1) #4 THWN; 180 ft
PNL: 101_4DEL1-L.6-23
208V, 100A 1.5k SCA 65k SCAR
CB: 101_4DEL1-L.7-22
SQUARE D (FA)
70 A
F: 101_4DEL1-L.7-22
(1) #4 THWN; 200 ft
PNL: 101_4DEL1-L.7-22
208V, 100A 1.4k SCA 65k SCAR
CB: 101_4DEL1-K.1-27
SQUARE D (FA)
30 A
F: 101_4DEL1-K.1-27
(1) #10 THWN; 80 ft
PNL: 101_4DEL1-K.1-27
208V, 100A 1.1k SCA 65k SCAR
CB: 101_4DEL1-L.7-24
SQUARE D (FA)
70 A
F: 101_4DEL1-L.7-24
(1) #4 THWN; 160 ft
PNL: 101_4DEL1-L.7-24
208V, 100A 1.6k SCA 65k SCAR
CB: 101_4DEL1-L.7-25
SQUARE D (FA)
70 A
F: 101_4DEL1-L.7-25
(1) #4 THWN; 180 ft
PNL: 101_4DEL1-L.7-25
208V, 100A 1.5k SCA 65k SCAR
CB: 101_4DEL1-K-26
SQUARE D (FA)
100 A
F: 101_4DEL1-K-26
(1) #2 THWN; 120 ft
PNL: 101_4DEL1-K-26
208V, 100A 2.4k SCA 65k SCAR
CB: 101_4DEL1-K.1-24
SQUARE D (FA)
40 A
F: 101_4DEL1-K.1-24
(1) #8 THWN; 100 ft
PNL: 101_4DEL1-K.1-24
208V, 100A 1.2k SCA 65k SCAR
CB: 101_4DEL1-L.6-24
SQUARE D (FA)
40 A
F: 101_4DEL1-L.6-24
(1) #8 THWN; 150 ft
PNL: 101_4DEL1-L.6-24
208V, 100A 0.9k SCA 65k SCAR
CB: 101_4DEL1-L.5-27
SQUARE D (Q2)
175 A
F: 101_4DEL1-L.5-27
(1) #2/0 THWN; 180 ft
PNL: 101_4DEL1-L.5-27
208V, 225A 2.5k SCA 65k SCAR
CB: 101_2DEL1-K-27
SQUARE D (FA)
100 A
F: 101_2DEL1-K-27
(1) #4 THWN; 210 ft
CB: 101_2DEL1-K-27 Main
SQUARE D (QO)
100 A
PNL: 101_2DEL1-K-27
208V, 100A 1.4k SCA 65k SCAR
NO SCALE
CONTINUE TO SWBD:
101_US101
(SEE SHEET 101ED602)
GENERAL NOTES
BUILDING 101 - ONE LINE DIAGRAM (ATS-DE-101-1)
EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS
TO BE REVISED.
EXISTING OVERCURRENT PROTECTIVE DEVICE TO BE
REMOVED AND REPLACED.
BLDG 101 - EXISTING ONE-LINE
DIAGRAM (PART 4 OF 5)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET
101EP604 FOR ALL MODIFICATIONS.
101ED604
SCALE : NTS
1 BLDG 101 - EXISTING ONE-LINE DIAGRAM (PART 4 OF 5)
PNL: 101_1L1-F.1-19.6
208V, 50A 0.7k SCA 65k SCAR
CB: 101_1L1-F.1-19.6 Main SQUARE D (Q1(B)-VH (Obs.)) 50 A
F: 101_Pnl 1L1-F.1-19.6
(1) #6 THWN; 20 ft
XF: 101_T-93
15kVA; 5.10%Z Pri: 480V Sec: 208V
F: 101_XFMR T-93
(1) #10 THWN; 40 ft
CB: 101_XFMR T-93
SQUARE D (EH)
30 A
CB: 101_RF-5
SQUARE D (EH)
15 A
F: 101_Disc RF-5
(1) #12 THWN; 60 ft
DISC: 101_RF-5
480V, 1.7k SCA
MCP: 101_RF-5
SQUARE D (FAL)
F: 101_RF-5
(1) #12 THWN; 10 ft
MTR: 101_RF-5
1 @ 3.0 hp
CB: 101_101-SF-5 15HP
SQUARE D (EH)
40 A
F: 101_Disc SF-5
(1) #10 THWN; 70 ft
DISC: 101_SF-5
480V, 2.1k SCA
MCP: 101_SF-5
SQUARE D (FAL)
F: 101_SF-5
(1) #12 THWN; 10 ft
MTR: 101_SF-5
1 @ 15.0 hp
PNL: 101_1H1-F.1-19.6
480V, 100A 5.1k SCA 14k SCAR
CB: 101_COM RM OFFICE A/C
SQUARE D (EH)
15 A
F: 101_2H1-F.1-19 Sec 2
(1) #1 THWN; 10 ft
PNL: 101_2H1-F.1-19 Sec 2 480V, 225A 5.0k SCA 14k SCAR
CB: 101_EF-A1
SQUARE D (EH)
15 A
PNL: 101_2L1-F.1-19
208V, 150A 1.7k SCA 22k SCAR
CB: 101_2L1-F.1-19 Main
SQUARE D (KA)
150 A
F: 101_2L1-F.1-19
(1) #1 THWN; 20 ft
XF: 101_T-94
45kVA; 6.10%Z Pri: 480V Sec: 208V
F: 101_XFMR T-94
(1) #4 THWN; 45 ft
CB: 101_XFMR T-94
SQUARE D (EH)
70 A
CB: 101_Audio Rack SQUARE D (Q1(B)-VH (Obs.)) 50 A
CB: 101_Dimmer Rack SQUARE D (Q1(B)-VH (Obs.)) 70 A
F: 101_DImmer Rack
(1) #4 THWN; 30 ft
EP: 101_Dimmer Rack 208V, 1.6k SCA
PNL: 101_2H1-F.1-19 Sec 1 480V, 225A 5.2k SCA 14k SCAR
CONTINUE TO BD:
100_S2 N1
(SEE SHEET 100ED605)
CB: 101_60 AMP RECP.
SQUARE D (FH)
60 A
CB: 101_XFMR T-92
SQUARE D (FA)
30 A
CB: 101_COMP RM
LIBERT SQUARE D (KA)
125 A
F: 101_XFMR T-92
(1) #10 THWN; 10 ft
XF: 101_T-92
15kVA; 5.10%Z Pri: 480V Sec: 208V
F: 101_Pnl 1DEL2-F.1-19.6
(1) #6 THWN; 15 ft
CB: 101_1DEL2-F.1-19.6 Main SQUARE D (Q1(B)-VH (Obs.)) 50 A
PNL: 101_1DEL2-F.1-19.6
208V, 50A 0.8k SCA 65k SCAR
PNL: 101_1DEH1-F.1-19.6
480V, 225A 16.4k SCA 14k SCAR
CONTINUE TO BD:
100_S2 DE1
(SEE SHEET 100ED619)
CONTINUE TO BD:
100_S2 N2
(SEE SHEET 100ED605)
GENERAL NOTES
BUILDING 101 - ONE LINE DIAGRAM (BUSDUCT RISER N1 BAY2, BUSDUCT RISER DE BAY 2)
EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS
TO BE REVISED.
BLDG 101 - EXISTING ONE-LINE
DIAGRAM (PART 5 OF 5)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET
101EP605 FOR ALL MODIFICATIONS.
101ED605
SCALE : NTS
1 BLDG 101 - EXISTING ONE-LINE DIAGRAM (PART 5 OF 5)
EXISTING FEEDER TO BE DEMOLISHED AND REPLACED.2
PNL: 102_NH102-1
480V, 225A 6.0k SCA 14k SCAR
CB: 102_Energy Saver
GE (TED)
80 A
F: 102_Energy Saver
(1) #2 THWN; 180 ft
EP: 102_Energy Saver 480V, 3.4k SCA
CB: 102_Energy Saver-2
CUTLER-HAMMER (FD)
80 A
F: 102_Pnl NH102-2
(1) #2 THWN; 40 ft
CB: 102_SO CORD
SQUARE D (EH)
20 A
CB: 102_Pnl LSH102-1
GE (TED)
30 A
F: 102_Pnl LSH102-1
(1) #10 THWN; 25 ft
CB: 102_LSH102-1 Main
GE (TED)
30 A
PNL: 102_LSH102-1
480V, 100A 3.9k SCA 14k SCAR
CB: 102_XF T-135
GE (TED)
30 A
F: 102_XF T-135
(1) #10 THWN; 5 ft
XF: 102_T-135
15kVA; 5.10%Z
PRI: 480V
SEC: 208V
F: 102_Pnl NL102-1
(1) #6 THWN; 5 ft
CB: 102_NL102-1 Main
GE (THED)
50 A
PNL: 102_NL102-1
208V, 100A 0.8k SCA 22k SCAR
PNL: 102_NH102-2
480V, 100A 3.1k SCA 14k SCAR
CONTINUE TO PNL:
103_DEH103P5
(SEE SHEET 103ED603)
GENERAL NOTES
EXISTING OVERCURRENT PROTECTIVE DEVICE TO BE
REMOVED AND REPLACED.
BLDG 102 - EXISTING ONE-LINE
DIAGRAM
BUILDING 102 - ONE LINE DIAGRAM (ATS-EQ)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET
102EP601 FOR ALL MODIFICATIONS.
102ED601
SCALE : NTS
1 BLDG 102 - EXISTING ONE-LINE DIAGRAM
CB: 103_Pnl NL1032N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1032N
(1) #1/0 THWN; 20 ft
PNL: 103_NL1032N
208V, 225A 8.0k SCA 200k SCAR
PNL: 103_NL103DP1N
208V, 1000A 9.2k SCA 200k SCAR
CB: 103_Pnl NL1039N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1039N
(1) #1/0 THWN; 60 ft
PNL: 103_NL1039N
208V, 225A 6.2k SCA 200k SCAR
CB: 103_Pnl NL1035N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1035N
(1) #1/0 THWN; 140 ft
PNL: 103_NL1035N
208V, 225A 4.1k SCA 200k SCAR
CB: 103_Pnl NL1031N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1031N
(1) #1/0 THWN; 60 ft
PNL: 103_NL1031N
208V, 225A 6.2k SCA 200k SCAR
CB: 103_Pnl NL1038N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1038N
(1) #1/0 THWN; 140 ft
PNL: 103_NL1038N
208V, 225A 4.1k SCA 200k SCAR
CB: 103_Pnl NL1034N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1034N
(1) #1/0 THWN; 135 ft
PNL: 103_NL1034N
208V, 225A 4.2k SCA 200k SCAR
CB: 103_Pnl NL1036N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1036N
(1) #1/0 THWN; 130 ft
PNL: 103_NL1036N
208V, 225A 4.3k SCA 200k SCAR
CB: 103_Pnl NL10310N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL10310N
(1) #1/0 THWN; 30 ft
PNL: 103_NL10310N
208V, 225A 7.5k SCA 200k SCAR
CB: 103_Pnl NL1037N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1037N
(1) #1/0 THWN; 140 ft
PNL: 103_NL1037N
208V, 225A 4.1k SCA 200k SCAR
CB: 103_Pnl NL10311N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL10311N
(1) #1/0 THWN; 35 ft
PNL: 103_NL10311N
208V, 225A 7.3k SCA 200k SCAR
CB: 103_Pnl NL1033N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1033N
(1) #1/0 THWN; 25 ft
PNL: 103_NL1033N
208V, 225A 7.8k SCA 200k SCAR
CB: 103_E137 Dishwasher
CUTLER-HAMMER (BAB)
20 A
CB: 103_NL103DP1N Main
CUTLER-HAMMER (ND)
1200 A, 1200 A Plug
CB: 103_XF T-142
CUTLER-HAMMER (LD)
450 A
F: 103_XF T-142
(2) #4/0 THWN; 20 ft
F: 103_Pnl NL103DP1N
(3) #500 THWN; 20 ft
XF: 103_T-142
300kVA; 7.10%Z Pri: 480V Sec: 208V
PNL: 103_NH103DP1N
480V, 600A 22.1k SCA 200k SCAR
CB: 103_Pnl NH1032N
CUTLER-HAMMER (FD)
100 A
F: 103_Pnl NH1032N
(1) #3 THWN; 50 ft
PNL: 103_NH1032N
480V, 100A 12.3k SCA 200k SCAR
CB: 103_Pnl NH1031N
CUTLER-HAMMER (FD)
100 A
F: 103_Pnl NH1031N
(1) #3 THWN; 5 ft
PNL: 103_NH1031N
480V, 100A 20.8k SCA 200k SCAR
CB: 103_Unk Load
CUTLER-HAMMER (GHB)
20 A
CB: 103_E112 Lg An Cage Wash
CUTLER-HAMMER (GHB)
30 A
MTR: 103_103-REF-5
1 @ 20.0 hp
MCP: 103_103-REF-5
CUTLER-HAMMER (HMCP)
F: 103_103-REF-5
(1) #8 THWN; 160 ft
MCC: 103_NH103MC1S
480V, 600A 14.3k SCA 42k SCAR
CB: 103_103-UH-3
CUTLER-HAMMER (HFD)
15 A
CB: 103_103-UH-1
CUTLER-HAMMER (HFD)
15 A
CB: 103_103-ASU-6 Supply
CUTLER-HAMMER (HFD)
40 A
CB: 103_103-ASU-6 Return
CUTLER-HAMMER (HFD)
20 A
CB: 103_103-ASU-2 Supply
CUTLER-HAMMER (HFD)
40 A
CB: 103_103-ASU-2 Return
CUTLER-HAMMER (HFD)
20 A
MCP: 103_103-ASU-1
CUTLER-HAMMER (HMCP)
MTR: 103_103-ASU-6 Supply 1 @ 15.0 hp
MTR: 103_103-ASU-6 Return 1 @ 10.0 hp
MTR: 103_103-ASU-2 Supply 1 @ 15.0 hp
MTR: 103_103-ASU-2 Return 1 @ 7.5 hp
MTR: 103_103-ASU-1
1 @ 60.0 hp
F: 103_103-ASU-6 Supply
(1) #10 THWN; 80 ft
F: 103_103-ASU-6 Return
(1) #12 THWN; 50 ft
F: 103_103-ASU-2 Supply
(1) #10 THWN; 80 ft
F: 103_103-ASU-2 Return
(1) #12 THWN; 50 ft
F: 103_103-ASU-1
(1) #3 THWN; 110 ft
VFD: 103_103-ASU-6 SupplyVFD: 103_103-ASU-6 ReturnVFD: 103_103-ASU-2 SupplyVFD: 103_103-ASU-2 Return
CB: 103_Pnl NL10310S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL10310S
(1) #1/0 THWN; 40 ft
PNL: 103_NL10310S
208V, 225A 6.2k SCA 200k SCAR
PNL: 103_NL103DP1S
208V, 800A 7.8k SCA 42k SCAR
CB: 103_Pnl NL1036S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1036S
(1) #1/0 THWN; 210 ft
PNL: 103_NL1036S
208V, 225A 3.0k SCA 200k SCAR
CB: 103_Pnl NL1032S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1032S
(1) #1/0 THWN; 30 ft
PNL: 103_NL1032S
208V, 225A 6.6k SCA 200k SCAR
CB: 103_Pnl NL1039S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1039S
(1) #1/0 THWN; 360 ft
PNL: 103_NL1039S
208V, 225A 2.0k SCA 200k SCAR
CB: 103_Pnl NL1035S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1035S
(1) #1/0 THWN; 100 ft
PNL: 103_NL1035S
208V, 100A 4.5k SCA 200k SCAR
CB: 103_Pnl NL1031S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1031S
(1) #1/0 THWN; 25 ft
PNL: 103_NL1031S
208V, 225A 6.8k SCA 200k SCAR
CB: 103_Pnl NL1033S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1033S
(1) #1/0 THWN; 35 ft
PNL: 103_NL1033S
208V, 225A 6.4k SCA 200k SCAR
CB: 103_Pnl NL1037S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1037S
(1) #1/0 THWN; 160 ft
PNL: 103_NL1037S
208V, 225A 3.5k SCA 200k SCAR
CB: 103_Pnl NL10311S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL10311S
(1) #1/0 THWN; 45 ft
PNL: 103_NL10311S
208V, 225A 6.0k SCA 200k SCAR
CB: 103_Pnl NL1034S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1034S
(1) #1/0 THWN; 240 ft
PNL: 103_NL1034S
208V, 100A 2.7k SCA 200k SCAR
CB: 103_Pnl NL1038S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1038S
(1) #1/0 THWN; 200 ft
PNL: 103_NL1038S
208V, 225A 3.1k SCA 200k SCAR
CB: 103_Unk Load 2
CUTLER-HAMMER (BAB)
20 A
CB: 103_F224-Glass Dishwasher
CUTLER-HAMMER (BAB)
20 A
CB: 103_Unk Load 3
CUTLER-HAMMER (BAB)
20 A
CB: 103_NL103DP1S Main Unknown (Unknown) 800 A
CB: 103_XF T-145
CUTLER-HAMMER (KD)
350 A
F: 103_XF T-145
(1) #500 THWN; 30 ft
F: 103_Pnl NL103DP1S
(2) #500 THWN; 25 ft
XF: 103_T-145
225kVA; 6.40%Z Pri: 480V Sec: 208V
CB: 103_Pnl NH1032S
CUTLER-HAMMER (FD)
100 A
F: 103_Pnl NH1032S
(1) #3 THWN; 120 ft
PNL: 103_NH1032S
480V, 100A 7.2k SCA 200k SCAR
CB: 103_Pnl NH1031S
CUTLER-HAMMER (FD)
100 A
F: 103_Pnl NH1031S
(1) #3 THWN; 25 ft
PNL: 103_NH1031S
480V, 100A 17.8k SCA 200k SCAR
PNL: 103_NH103DP1S
480V, 600A 24.7k SCA 200k SCAR
MTR: 103_103-ASU-5
1 @ 60.0 hp
MCP: 103_103-ASU-5
CUTLER-HAMMER (HMCP)
F: 103_103-ASU-5
(1) #3 THWN; 100 ft
MTR: 103_103-REF-6
1 @ 40.0 hp
MCP: 103_103-REF-6
CUTLER-HAMMER (HMCP)
F: 103_103-REF-6
(1) #6 THWN; 170 ft
CB: 103_103-UH-2
CUTLER-HAMMER (HFD)
15 A
MCC: 103_NH103MC2N
480V, 600A 13.7k SCA 42k SCAR
CB: 103_103-UH-4
CUTLER-HAMMER (HFD)
15 A
CB: 103_NH103MC2N
CUTLER-HAMMER (DSII-508)
800 A, 400 A Plug
F: 103_NH103MC2N
(1) #500 THWN; 240 ft
UNIT SUBSTATION
"US103"
SWBD: 103_NH103MSB
480V, 3200A 33.5k SCA 50k SCAR
CB: 103_NH103DP1S
CUTLER-HAMMER (DSII-508)
800 A, 600 A Plug
F: 103_NH103DP1S
(2) #350 THWN; 105 ft
CB: 103_NH103MC1S
CUTLER-HAMMER (DSII-508)
800 A, 400 A Plug
F: 103_NH103MC1S
(1) #500 THWN; 220 ft
CB: 103_NH103MSB (Fdr F4B)
CUTLER-HAMMER (DSII-508)
800 A, 800 A Plug
F: 103_NH103MSB (Fdr F4B)
(2) #500 THWN; 70 ft
CB: 103_NH104DP1N
CUTLER-HAMMER (DSII-508)
800 A, 600 A Plug
F: 103_NH104DP1N
(2) #350 THWN; 230 ft
CB: 103_NH103DP1N
CUTLER-HAMMER (DSII-508)
800 A, 600 A Plug
F: 103_NH103DP1N
(2) #350 THWN; 150 ft
CB: 103_NH103DP1 W/G
CUTLER-HAMMER (DSII-516)
1600 A, 1200 A Plug
F: 103_NH103DP1
(4) #350 THWN; 70 ft
SWBD: 103_NH103DP1
480V, 1600A 30.3k SCA 50k SCAR
CB: 103_ATS LS (N)
CUTLER-HAMMER (DSII-508)
800 A, 400 A Plug
CB: 103_ATS EQ (N)
CUTLER-HAMMER (DSII-508)
800 A, 800 A Plug
F: 103_ATS EQ (N)
(2) #500 THWN; 10 ft
F: 103_ATS LS (N)
(1) #500 THWN; 10 ft
CB: 103_NH103MSB Main W/G
CUTLER-HAMMER (DSII-632)
3200 A, 3000 A Plug
F: 103_SWBD NH103MSB
(1) #4000 Class B; 2 ft
XF: US103
2000kVA; 5.75%Z Pri: 12470V Sec: 480V
FU: US103
GE (EJO-1, 125E)
125 A
UTIL: US103
Isc 3P 4435 Amps Isc SLG 3240 Amps
UTIL: US103 (equip eval) Isc 3P 10545 Amps Isc SLG 8265 Amp
CONTINUE TO ATS:
103_LS
(SEE SHEET 103ED604)
CONTINUE TO PNL:
104_NH104DP1
(SEE SHEET 104ED602)
CONTINUE TO SWBD:
103_105
(SEE SHEET 103ED602)
CONTINUE TO ATS:
103_EQ
(SEE SHEET 103ED603)
NH103MSB
FEEDER F4C
DSII-508 PROVISION
NH103MSB
FEEDER F4D
DSII-508 PROVISION
GENERAL NOTES
BUILDING 103 - ONE LINE DIAGRAM (SUB US103)
EXISTING OVERCURRENT PROTECTIVE DEVICE
SETTINGS TO BE REVISED.
EXISTING OVERCURRENT PROTECTIVE DEVICE TO BE
REMOVED AND REPLACED.
2 2 2 2 2 2 2
1 1
2 2
BLDG 103 - EXISTING ONE-LINE
DIAGRAM (PART 1 OF 4)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET
103EP601 FOR ALL MODIFICATIONS.
103ED601
SCALE : NTS
1 BLDG 103 - EXISTING ONE-LINE DIAGRAM (PART 1 OF 4)
CB: 103_Pnl NH103P5L
SQUARE D (FH)
60 A
F:103_Pnl NH103P5L
(1) #2 THWN; 45 ft
PNL: 103_NH103P5L
480V, 100A 16.4k SCA 200k SCAR
CB: 103_XF T-152
SQUARE D (FH)
90 A
F: 103_XF T-152
(1) #2 THWN; 20 ft
XF: 103_T-152
75kVA; 4.43%Z Pri: 480V Sec: 208V
F: 103_Pnl NL103P5C (SEC 1)
(1) #4/0 THWN; 15 ft
CB: 103_NL103P5C Main
CUTLER-HAMMER (ED)
225 A
PNL: 103_NL103P5C (Sec 1) 208V, 225A 4.2k SCA 200k SCAR
CB: 103_NCRAR DIMMER RACK
CUTLER-HAMMER (BAB)
40 A
F: 103_Pnl NL103P5C (SEC 2)
(1) #4/0 THWN; 15 ft
PNL: 103_NL103P5C (SEC 2)
208V, 225A 4.0k SCA 200k SCAR
CB: 103_Pnl B1H
SQUARE D (LH)
400 A
F:103_Pnl B1H
(1) #600 THWN; 160 ft
CB: 103_FAN RM
SQUARE D (FH)
100 A
F: 103_FAN RM
(1) #2 THWN; 160 ft
CB: 103_Pnl NH103P5M
SQUARE D (KA)
200 A
F: 103_Pnl NH103P5M
(1) #3/0 THWN; 60 ft
CB: 103_XF T-153
SQUARE D (FH)
90 A
F: 103_XF T-153
(1) #2 THWN; 20 ft
XF: 103_T-153
75kVA; 5.26%Z Pri: 480V Sec: 208V
F: 103_Pnl NL103P5D (SEC 1)
(1) #4/0 THWN; 20 ft
CB: 103_NL103P5D (SEC 1) Main
CUTLER-HAMMER (ED)
225 A
PNL: 103_NL103P5D (SEC 1)
208V, 225A 3.5k SCA 200k SCAR
F: 103_Pnl NL103P5D (SEC 2)
(1) #4/0 THWN; 5 ft
PNL: 103_NL103P5D (SEC 2)
208V, 225A 3.5k SCA 200k SCAR
F: 103_NH103MSB (FDR F4B)
(2) #500 THWN; 70 ft
CONTINUE TO SWBD:
103_NH103MSB
(SEE SHEET 103ED601)
CB: 103_TRAILER
SQUARE D (KA)
200 A
F: 103_TRAILER
(1) #2/0 THWN; 360 ft
XF: 103_TRAILER
150kVA; 5.45%Z Pri: 480V Sec: 208V
F: 103_Disc A
(1) #2/0 THWN; 5 ft
DISC: 103_Disc A 208V, 5.1k SCA
FU: 103_Disc A
BUSSMANN (FRS-R)
200 A
F: 103_Disc A
(1) #2/0 THWN; 1 ft
PNL: 103_PANEL A
208V, START OF SINGLE PHASE
F: 103_Disc B
(1) #2/0 THWN; 5 ft
DISC: 103_Disc B 208V, 5.1k SCA
FU: 103_Disc B
BUSSMANN (FRS-R)
200 A
F: 103_Disc B
(1) #2/0 THWN; 1 ft
PNL: 103_PANEL B
208V, CB: 103_RETURN FAN
CUTLER-HAMMER (GHB)
50 A
F: 103_RETURN FAN
(1) #10 THWN; 100 ft
VFD: 103_RETURN FAN
MTR: 103_RETURN FAN
1 @ 20.0 hp
CB: 103_SUPPLY FAN
CUTLER-HAMMER (GHB)
90 A
F: 103_SUPPLY FAN
(1) #8 THWN; 100 ft
VFD: 103_SUPPLY FAN
MTR: 103_SUPPLY FAN
1 @ 25.0 hp
TAP: 103_XF TRAILER SEC
208V, 5.2k SCA
CB: 103_HEATING PUMP P1
CUTLER-HAMMER (GHB)
20 A
F: 103_VFD HEATING PUMP P1
(1) #12 THWN; 80 ft
VFD: 103_Heating Pump P1
F: 103_HEATING PUMP P1
(1) #12 THWN; 10 ft
DISC: 103_HWP-1
480V, 1.6k SCA
FU: 103_HWP-1
LITTELFUSE (IDSR)
20 A
F: 103_HWP-1
(1) #12 THWN; 5 ft
MTR: 103_HWP-1
1 @ 2.0 hp
CB: 103_HEATING PUMP P2
CUTLER-HAMMER (GHB)
20 A
F: 103_VFD HEATING PUMP P2
(1) #12 THWN; 80 ft
VFD: 103_HEATING PUMP P2
F: 103_Heating Pump P2
(1) #12 THWN; 10 ft
DISC: 103_HWP-2
480V, 1.6k SCA
FU: 103_HWP-2
LITTELFUSE (IDSR)
20 A
F: 103_HWP-2
(1) #12 THWN; 5 ft
MTR: 103_HWP-2
1 @ 2.0 hp
CB: 103_HEATING PUMP P3
CUTLER-HAMMER (GHB)
20 A
F: 103_VFD HEATING PUMP P3
(1) #12 THWN; 80 ft
VFD: 103_HEATING PUMP P3
F: 103_HEATING PUMP P3
(1) #12 THWN; 10 ft
DISC: 103_P3 CIRC PUMP
480V, 1.6k SCA
FU: 103_P3 CIRC PUMP
LITTELFUSE (IDSR)
20 A
F: 103_P3 CIRC PUMP
(1) #12 THWN; 5 ft
MTR: 103_P-3 CIRC PUMP
1 @ 5.0 hp
PNL: 103_NH103P5M
480V, 225A 18.8k SCA 200k SCAR
CB: 103_FAN 1
SIEMENS (BQD)
20 A
F: 103_FAN 1
(1) #10 THWN; 25 ft
VFD: 103_FAN 1
MTR: 103_FAN 1
1 @ 7.5 hp
CB: 103_FAN 2
SIEMENS (BQD)
30 A
F: 103_FAN 2
(1) #10 THWN; 25 ft
VFD: 103_FAN 2
MTR: 103_FAN 2
1 @ 15.0 hp
CB: 103_FAN 3
SIEMENS (BQD)
30 A
F: 103_FAN 3
(1) #10 THWN; 35 ft
VFD: 103_FAN 3
MTR: 103_FAN 3
1 @ 15.0 hp
PNL: 103_FAN RM
480V, 125A 7.0k SCA 100k SCAR
CONTINUE TO PNL:
104_B1H
(SEE SHEET 104ED601)
START OF SINGLE PHASE
SWBD: 103_105, 480V, 800A
27.5k SCA 200k SCAR
GENERAL NOTES
BUILDING 103 - ONE LINE DIAGRAM (SWBD 105)
EXISTING OVERCURRENT PROTECTIVE DEVICE TO BE
REMOVED AND REPLACED.
EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS
TO BE REVISED.
BLDG 103 - EXISTING ONE-LINE
DIAGRAM (PART 2 OF 4)
11111
1111211
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE REVISED ONE-LINE DIAGRAM ON SHEET
103EP602 FOR ALL MODIFICATIONS.
103ED602
SCA…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .