Attachment 10-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 8.pdf
PDF 14 MB Posted
- Solicitation number
- 36C26025R0071
About this file
This document is a set of electrical one-line diagrams for the VA Portland Health Care System's electrical infrastructure correction project. The diagrams cover multiple buildings (Buildings 100, 101, 102, 103, 104, 105, and 106) and provide detailed electrical system configurations, including panelboards, transformers, circuit breakers, motors, and power distribution equipment. The drawings are part of a comprehensive electrical facility condition assessment (FCA) project, dated January 31, 2025, prepared by Spees Design Build for the U.S. Department of Veterans Affairs.
The one-line diagrams specify electrical system details such as voltage ratings, amperage, short circuit current ratings, and interconnections between various electrical components across different buildings. Each diagram includes general notes emphasizing contractor responsibilities like field verification of existing conditions, shutdown planning, and providing updated circuit panel directories. The project appears to involve replacing and adjusting overcurrent protective devices, updating power distribution equipment, and ensuring compliance with existing electrical infrastructure requirements at the VA Portland Health Care System facility.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PNL: 101_1L1-F.1-19.6
208V, 50A 0.7k SCA 65k SCAR
CB: 101_1L1-F.1-19.6 Main SQUARE D (Q1(B)-VH (Obs.)) 50 A
F: 101_Pnl 1L1-F.1-19.6
(1) #6 THWN; 20 ft
XF: 101_T-93
15kVA; 5.10%Z Pri: 480V Sec: 208V
F: 101_XFMR T-93
(1) #10 THWN; 40 ft
CB: 101_XFMR T-93
SQUARE D (EH)
30 A
CB: 101_RF-5
SQUARE D (EH)
15 A
F: 101_Disc RF-5
(1) #12 THWN; 60 ft
DISC: 101_RF-5
480V, 1.7k SCA
MCP: 101_RF-5
SQUARE D (FAL)
F: 101_RF-5
(1) #12 THWN; 10 ft
MTR: 101_RF-5
1 @ 3.0 hp
CB: 101_101-SF-5 15HP
SQUARE D (EH)
40 A
F: 101_Disc SF-5
(1) #10 THWN; 70 ft
DISC: 101_SF-5
480V, 2.1k SCA
MCP: 101_SF-5
SQUARE D (FAL)
F: 101_SF-5
(1) #12 THWN; 10 ft
MTR: 101_SF-5
1 @ 15.0 hp
PNL: 101_1H1-F.1-19.6
480V, 100A 5.1k SCA 14k SCAR
CB: 101_COM RM OFFICE A/C
SQUARE D (EH)
15 A
F: 101_2H1-F.1-19 Sec 2
(1) #1 THWN; 10 ft
PNL: 101_2H1-F.1-19 Sec 2 480V, 225A 5.0k SCA 14k SCAR
CB: 101_EF-A1
SQUARE D (EH)
15 A
PNL: 101_2L1-F.1-19
208V, 150A 1.7k SCA 22k SCAR
F: 101_2L1-F.1-19
(1) #1 THWN; 20 ft
XF: 101_T-94
45kVA; 6.10%Z Pri: 480V Sec: 208V
F: 101_XFMR T-94
(1) #4 THWN; 45 ft
CB: 101_XFMR T-94
SQUARE D (EH)
70 A
CB: 101_Audio Rack SQUARE D (Q1(B)-VH (Obs.)) 50 A
CB: 101_Dimmer Rack SQUARE D (Q1(B)-VH (Obs.)) 70 A
F: 101_DImmer Rack
(1) #4 THWN; 30 ft
EP: 101_Dimmer Rack 208V, 1.6k SCA
PNL: 101_2H1-F.1-19 Sec 1 480V, 225A 5.2k SCA 14k SCAR
CONTINUE TO BD:
100_S2 N1
(SEE SHEET 100EP605)
CB: 101_60 AMP RECP.
SQUARE D (FH)
60 A
CB: 101_XFMR T-92
SQUARE D (FA)
30 A
CB: 101_COMP RM
LIBERT SQUARE D (KA)
125 A
F: 101_XFMR T-92
(1) #10 THWN; 10 ft
XF: 101_T-92
15kVA; 5.10%Z Pri: 480V Sec: 208V
F: 101_Pnl 1DEL2-F.1-19.6
(1) #6 THWN; 15 ft
CB: 101_1DEL2-F.1-19.6 Main SQUARE D (Q1(B)-VH (Obs.)) 50 A
PNL: 101_1DEL2-F.1-19.6
208V, 50A 0.8k SCA 65k SCAR
PNL: 101_1DEH1-F.1-19.6
480V, 225A 16.4k SCA 14k SCAR
CONTINUE TO BD:
100_S2 DE1
(SEE SHEET 100EP619)
CONTINUE TO BD:
100_S2 N2
(SEE SHEET 100EP605)
CB: 101_2L1-F.1-19 MAIN
SQUARE D (KA)
150A
THERMAL CURVE = NO CHANGE
INSTANTANEOUS = HI (1500A)
GENERAL NOTES
BUILDING 101 - ONE LINE DIAGRAM (BUSDUCT RISER N1 BAY2, BUSDUCT RISER DE BAY 2)
BLDG 101 - REVISED ONE-LINE
DIAGRAM (PART 5 OF 5)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS
TO BE REVISED AS SHOWN.
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE EXISTING ONE-LINE DIAGRAM ON SHEET
101ED605 FOR ALL MODIFICATIONS.
101EP605
SCALE : NTS
1 BLDG 101 - REVISED ONE-LINE DIAGRAM (PART 5 OF 5)
101-P-02 2
PROVIDE FEEDER TO RE-FEED PANELBOARD AS INDICATED.2
PNL: 102_NH102-1
480V, 225A 6.0k SCA 14k SCAR
CB: 102_Energy Saver
GE (TED) 80 A
THERMAL CURVE = 80A
INSTANTANEOUS = MAX (975A)
F: 102_Energy Saver
(1) #2 THWN; 180 ft
EP: 102_Energy Saver 480V, 3.4k SCA
CB: 102_Energy Saver-2
CUTLER-HAMMER (FD)
80 A
F: 102_Pnl NH102-2
(1) #2 THWN; 40 ft
CB: 102_SO CORD
SQUARE D (EH)
20 A
CB: 102_Pnl LSH102-1
GE (TED) 30 A
THERMAL CURVE = 30A
INSTANTANEOUS = FIXED
F: 102_Pnl LSH102-1
(1) #10 THWN; 25 ft
CB: 102_LSH102-1 Main
GE (TED)
30 A
PNL: 102_LSH102-1
480V, 100A 3.9k SCA 14k SCAR
CB: 102_XF T-135
GE (TED) 30 A
THERMAL CURVE = 30A
INSTANTANEOUS = MAX (920A)
F: 102_XF T-135
(1) #10 THWN; 5 ft
XF: 102_T-135
15kVA; 5.10%Z
PRI: 480V
SEC: 208V
F: 102_Pnl NL102-1
(1) #6 THWN; 5 ft
CB: 102_NL102-1 Main
GE (THED)
50 A
PNL: 102_NL102-1
208V, 100A 0.8k SCA 22k SCAR
PNL: 102_NH102-2
480V, 100A 3.1k SCA 14k SCAR
CONTINUE TO PNL:
103_DEH103P5
(SEE SHEET 103EP603)
GENERAL NOTES
BLDG 102 - REVISED ONE-LINE
DIAGRAM
BUILDING 102 - ONE LINE DIAGRAM (ATS-EQ)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE EXISTING ONE-LINE DIAGRAM ON SHEET
102ED601 FOR ALL MODIFICATIONS.
REPLACEMENT OVERCURRENT PROTECTIVE DEVICE.
102EP601
SCALE : NTS
1 BLDG 102 - REVISED ONE-LINE DIAGRAM
CB: 103_Pnl NL1032N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1032N
(1) #1/0 THWN; 20 ft
PNL: 103_NL1032N
208V, 225A 8.0k SCA 200k SCAR
PNL: 103_NL103DP1N
208V, 1000A 9.2k SCA 200k SCAR
CB: 103_Pnl NL1039N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1039N
(1) #1/0 THWN; 60 ft
PNL: 103_NL1039N
208V, 225A 6.2k SCA 200k SCAR
CB: 103_Pnl NL1035N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1035N
(1) #1/0 THWN; 140 ft
PNL: 103_NL1035N
208V, 225A 4.1k SCA 200k SCAR
CB: 103_Pnl NL1031N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1031N
(1) #1/0 THWN; 60 ft
PNL: 103_NL1031N
208V, 225A 6.2k SCA 200k SCAR
CB: 103_Pnl NL1038N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1038N
(1) #1/0 THWN; 140 ft
PNL: 103_NL1038N
208V, 225A 4.1k SCA 200k SCAR
CB: 103_Pnl NL1034N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1034N
(1) #1/0 THWN; 135 ft
PNL: 103_NL1034N
208V, 225A 4.2k SCA 200k SCAR
CB: 103_Pnl NL1036N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1036N
(1) #1/0 THWN; 130 ft
PNL: 103_NL1036N
208V, 225A 4.3k SCA 200k SCAR
CB: 103_Pnl NL10310N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL10310N
(1) #1/0 THWN; 30 ft
PNL: 103_NL10310N
208V, 225A 7.5k SCA 200k SCAR
CB: 103_Pnl NL1037N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1037N
(1) #1/0 THWN; 140 ft
PNL: 103_NL1037N
208V, 225A 4.1k SCA 200k SCAR
CB: 103_Pnl NL10311N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL10311N
(1) #1/0 THWN; 35 ft
PNL: 103_NL10311N
208V, 225A 7.3k SCA 200k SCAR
CB: 103_Pnl NL1033N
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1033N
(1) #1/0 THWN; 25 ft
PNL: 103_NL1033N
208V, 225A 7.8k SCA 200k SCAR
CB: 103_E137 Dishwasher
CUTLER-HAMMER (BAB)
20 A
CB: 103_NL103DP1N Main
CUTLER-HAMMER (ND)
1200 A, 1200 A Plug
CB: 103_XF T-142
CUTLER-HAMMER (LD)
450 A
F: 103_XF T-142
(2) #4/0 THWN; 20 ft
F: 103_Pnl NL103DP1N
(3) #500 THWN; 20 ft
XF: 103_T-142
300kVA; 7.10%Z Pri: 480V Sec: 208V
PNL: 103_NH103DP1N
480V, 600A 22.1k SCA 200k SCAR
CB: 103_Pnl NH1032N
CUTLER-HAMMER (FD)
100 A
F: 103_Pnl NH1032N
(1) #3 THWN; 50 ft
PNL: 103_NH1032N
480V, 100A 12.3k SCA 200k SCAR
CB: 103_Pnl NH1031N
CUTLER-HAMMER (FD)
100 A
F: 103_Pnl NH1031N
(1) #3 THWN; 5 ft
PNL: 103_NH1031N
480V, 100A 20.8k SCA 200k SCAR
MTR: 103_103-REF-5
1 @ 20.0 hp
MCP: 103_103-REF-5
CUTLER-HAMMER (HMCP)
F: 103_103-REF-5
(1) #8 THWN; 160 ft
MCC: 103_NH103MC1S
480V, 600A 14.3k SCA 42k SCAR
CB: 103_103-UH-3
CUTLER-HAMMER (HFD)
15 A
CB: 103_103-UH-1
CUTLER-HAMMER (HFD)
15 A
CB: 103_103-ASU-6 Supply
CUTLER-HAMMER (HFD)
40 A
CB: 103_103-ASU-6 Return
CUTLER-HAMMER (HFD)
20 A
CB: 103_103-ASU-2 Supply
CUTLER-HAMMER (HFD)
40 A
CB: 103_103-ASU-2 Return
CUTLER-HAMMER (HFD)
20 A
MCP: 103_103-ASU-1
CUTLER-HAMMER (HMCP)
MTR: 103_103-ASU-6 Supply 1 @ 15.0 hp
MTR: 103_103-ASU-6 Return 1 @ 10.0 hp
MTR: 103_103-ASU-2 Supply 1 @ 15.0 hp
MTR: 103_103-ASU-2 Return 1 @ 7.5 hp
MTR: 103_103-ASU-1
1 @ 60.0 hp
F: 103_103-ASU-6 Supply
(1) #10 THWN; 80 ft
F: 103_103-ASU-6 Return
(1) #12 THWN; 50 ft
F: 103_103-ASU-2 Supply
(1) #10 THWN; 80 ft
F: 103_103-ASU-2 Return
(1) #12 THWN; 50 ft
F: 103_103-ASU-1
(1) #3 THWN; 110 ft
VFD: 103_103-ASU-6 SupplyVFD: 103_103-ASU-6 ReturnVFD: 103_103-ASU-2 SupplyVFD: 103_103-ASU-2 Return
CB: 103_Pnl NL10310S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL10310S
(1) #1/0 THWN; 40 ft
PNL: 103_NL10310S
208V, 225A 6.2k SCA 200k SCAR
PNL: 103_NL103DP1S
208V, 800A 7.8k SCA 42k SCAR
CB: 103_Pnl NL1036S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1036S
(1) #1/0 THWN; 210 ft
PNL: 103_NL1036S
208V, 225A 3.0k SCA 200k SCAR
CB: 103_Pnl NL1032S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1032S
(1) #1/0 THWN; 30 ft
PNL: 103_NL1032S
208V, 225A 6.6k SCA 200k SCAR
CB: 103_Pnl NL1039S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1039S
(1) #1/0 THWN; 360 ft
PNL: 103_NL1039S
208V, 225A 2.0k SCA 200k SCAR
CB: 103_Pnl NL1035S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1035S
(1) #1/0 THWN; 100 ft
PNL: 103_NL1035S
208V, 100A 4.5k SCA 200k SCAR
CB: 103_Pnl NL1031S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1031S
(1) #1/0 THWN; 25 ft
PNL: 103_NL1031S
208V, 225A 6.8k SCA 200k SCAR
CB: 103_Pnl NL1033S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1033S
(1) #1/0 THWN; 35 ft
PNL: 103_NL1033S
208V, 225A 6.4k SCA 200k SCAR
CB: 103_Pnl NL1037S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1037S
(1) #1/0 THWN; 160 ft
PNL: 103_NL1037S
208V, 225A 3.5k SCA 200k SCAR
CB: 103_Pnl NL10311S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL10311S
(1) #1/0 THWN; 45 ft
PNL: 103_NL10311S
208V, 225A 6.0k SCA 200k SCAR
CB: 103_Pnl NL1034S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1034S
(1) #1/0 THWN; 240 ft
PNL: 103_NL1034S
208V, 100A 2.7k SCA 200k SCAR
CB: 103_Pnl NL1038S
CUTLER-HAMMER (ED)
150 A
F: 103_Pnl NL1038S
(1) #1/0 THWN; 200 ft
PNL: 103_NL1038S
208V, 225A 3.1k SCA 200k SCAR
CB: 103_Unk Load 2
CUTLER-HAMMER (BAB)
20 A
CB: 103_F224-Glass Dishwasher
CUTLER-HAMMER (BAB)
20 A
CB: 103_Unk Load 3
CUTLER-HAMMER (BAB)
20 A
CB: 103_NL103DP1S Main Unknown (Unknown) 800 A
CB: 103_XF T-145
CUTLER-HAMMER (KD)
350 A
F: 103_XF T-145
(1) #500 THWN; 30 ft
F: 103_Pnl NL103DP1S
(2) #500 THWN; 25 ft
XF: 103_T-145
225kVA; 6.40%Z Pri: 480V Sec: 208V
CB: 103_Pnl NH1032S
CUTLER-HAMMER
100 A
THERMAL CURVE = 100A
F: 103_Pnl NH1032S
(1) #3 THWN; 120 ft
PNL: 103_NH1032S
480V, 100A 7.2k SCA 200k SCAR
CB: 103_Pnl NH1031S
CUTLER-HAMMER
100 A
THERMAL CURVE = 100A
F: 103_Pnl NH1031S
(1) #3 THWN; 25 ft
PNL: 103_NH1031S
480V, 100A 17.8k SCA 200k SCAR
PNL: 103_NH103DP1S
480V, 600A 24.7k SCA 200k SCAR
MTR: 103_103-ASU-5
1 @ 60.0 hp
MCP: 103_103-ASU-5
CUTLER-HAMMER (HMCP)
F: 103_103-ASU-5
(1) #3 THWN; 100 ft
MTR: 103_103-REF-6
1 @ 40.0 hp
MCP: 103_103-REF-6
CUTLER-HAMMER (HMCP)
F: 103_103-REF-6
(1) #6 THWN; 170 ft
CB: 103_103-UH-2
CUTLER-HAMMER (HFD)
15 A
MCC: 103_NH103MC2N
480V, 600A 13.7k SCA 42k SCAR
CB: 103_103-UH-4
CUTLER-HAMMER (HFD)
15 A
CB: 103_NH103MC2N
SE MASTERPACT MTZ
SENSOR RATING = 400A
LONG TIME PICKUP = 1.0 (400A)
LONG TIME DELAY = 12
SHORT TIME PICKUP = 4.0 (1600A)
SHORT TIME DELAY = 0.1 I2T IN
INSTANTANEOUS = 5 (2000A)
F: 103_NH103MC2N
(1) #500 THWN; 240 ft
UNIT SUBSTATION
"US103"
SWBD: 103_NH103MSB
480V, 3200A 33.5k SCA 50k SCAR
CB: 103_NH103DP1S
SE MASTERPACT MTZ
SENSOR RATING = 600A
LONG TIME PICKUP = 1.0 (600A)
LONG TIME DELAY = 24
SHORT TIME PICKUP = 8.0 (4800A)
SHORT TIME DELAY = 0.1 I2T IN
INSTANTANEOUS = 12 (7200A)
F: 103_NH103DP1S
(2) #350 THWN; 105 ft
CB: 103_NH103MC1S
SE MASTERPACT MTZ
SENSOR RATING = 400A
LONG TIME PICKUP = 1.0 (400A)
LONG TIME DELAY = 12
SHORT TIME PICKUP = 4.0 (1600A)
SHORT TIME DELAY = 0.1 I2T IN
INSTANTANEOUS = 5 (2000A)
F: 103_NH103MC1S
(1) #500 THWN; 220 ft
CB: 103_NH103MSB (Fdr F4B)
SE MASTERPACT MTZ
SENSOR RATING = 800A
LONG TIME PICKUP = 1.0 (800A)
LONG TIME DELAY = 24
SHORT TIME PICKUP = 8.0 (6400A)
SHORT TIME DELAY = 0.1 I2T IN
INSTANTANEOUS = 12 (9600A)
F: 103_NH103MSB (Fdr F4B)
(2) #500 THWN; 70 ft
CB: 103_NH104DP1N
SE MASTERPACT MTZ
SENSOR RATING = 600A
LONG TIME PICKUP = 1.0 (600A)
LONG TIME DELAY = 24
SHORT TIME PICKUP = 8.0 (4800A)
SHORT TIME DELAY = 0.1 I2T IN
INSTANTANEOUS = 12 (7200A)
F: 103_NH104DP1N
(2) #350 THWN; 230 ft
CB: 103_NH103DP1N
SE MASTERPACT MTZ
SENSOR RATING = 600A
LONG TIME PICKUP = 1.0 (600A)
LONG TIME DELAY = 24
SHORT TIME PICKUP = 10.0 (6000A)
SHORT TIME DELAY = 0.1 I2T IN
INSTANTANEOUS = 12 (7200A)
F: 103_NH103DP1N
(2) #350 THWN; 150 ft
CB: 103_NH103DP1 W/G
SE MASTERPACT MTZ
SENSOR RATING = 1200A
LONG TIME PICKUP = 1.0 (1200A)
LONG TIME DELAY = 10
SHORT TIME PICKUP = 8.0 (9600A)
SHORT TIME DELAY = 0.3 I2T OUT
GROUND FAULT PICKUP = C (420A)
GROUND FAULT DELAY = 0.1 I2T OUT
F: 103_NH103DP1
(4) #350 THWN; 70 ft
SWBD: 103_NH103DP1
480V, 1600A 30.3k SCA 50k SCAR
CB: 103_ATS LS (N)
CUTLER-HAMMER (DSII-508)
800 A, 400 A Plug
LONG TIME PICKUP = 1.0(400A)
LONG TIME DELAY = 2
SHORT TIME PICKUP = 4.0 (1600A)
SHORT TIME DELAY = 0.1 I2T IN
INSTANTANEOUS = 8(3200A)
CB: 103_ATS EQ (N)
CUTLER-HAMMER (DSII-508)
800 A, 800 A Plug
SENSOR RATING = NO CHANGE
LONG TIME PICKUP = 1.0(800A)
LONG TIME DELAY = 12
SHORT TIME PICKUP = 8.0 (6400A)
SHORT TIME DELAY = 0.2 I2T OUT
INSTANTANEOUS = 12 (9600A)
F: 103_ATS EQ (N)
(2) #500 THWN; 10 ft
F: 103_ATS LS (N)
(1) #500 THWN; 10 ft
CB: 103_NH103MSB Main W/G
SE MASTERPACT MTZ
SENSOR RATING = 3000A
LONG TIME PICKUP = 1.0 (3000A)
LONG TIME DELAY = 4
SHORT TIME PICKUP = 4.0 (12000A)
SHORT TIME DELAY = 0.5 I2T OUT
GROUND FAULT PICKUP = D (1125A)
GROUND FAULT DELAY = 0.3 I2T OUT
F: 103_SWBD NH103MSB
(1) #4000 Class B; 2 ft
XF: US103
2000kVA; 5.75%Z Pri: 12470V Sec: 480V
FU: US103
GE (EJO-1, 125E)
125 A
UTIL: US103
Isc 3P 4435 Amps Isc SLG 3240 Amps
UTIL: US103 (equip eval) Isc 3P 10545 Amps Isc SLG 8265 Amp
CONTINUE TO ATS:
103_LS
(SEE SHEET 103EP604)
CONTINUE TO PNL:
104_NH104DP1
(SEE SHEET 104EP602)
CONTINUE TO SWBD:
103_105
(SEE SHEET 103EP602)
CONTINUE TO ATS:
103_EQ
(SEE SHEET 103EP603)
CB: 103_Unk Load
CUTLER-HAMMER
20 A
CB: 103_E112 Lg An Cage Wash
CUTLER-HAMMER
30 A
NH103MSB
FEEDER F4C
DSII-508 PROVISION
NH103MSB
FEEDER F4D
DSII-508 PROVISION
GENERAL NOTES
EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS
TO BE REVISED AS SHOWN.
REPLACEMENT OVERCURRENT PROTECTIVE DEVICE.
PROVIDE REPLACEMENT LOW-VOLTAGE SWITCHGEAR
CIRCUIT BREAKER WITH INTEGRAL COMMUNICATION AND
POWER METERING MODULES. REFERENCE
SPECIFICATION 26 23 00 FOR ADDITIONAL INFORMATION.
BUILDING 103 - ONE LINE DIAGRAM (SUB US103)
BLDG 103 - REVISED ONE-LINE
DIAGRAM (PART 1 OF 4)
22 2
2 2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE EXISTING ONE-LINE DIAGRAM ON SHEET
103ED601 FOR ALL MODIFICATIONS.
103EP601
SCALE : NTS
1 BLDG 103 - REVISED ONE-LINE DIAGRAM (PART 1 OF 4)
333333
CB: 103_Pnl NH103P5L
SQUARE D
60 A
THERMAL CURVE = 60A
F:103_Pnl NH103P5L
(1) #2 THWN; 45 ft
PNL: 103_NH103P5L
480V, 100A 16.4k SCA 200k SCAR
CB: 103_XF T-152
SQUARE D
90 A
THERMAL CURVE = 90A
F: 103_XF T-152
(1) #2 THWN; 20 ft
XF: 103_T-152
75kVA; 4.43%Z Pri: 480V Sec: 208V
F: 103_Pnl NL103P5C (SEC 1)
(1) #4/0 THWN; 15 ft
CB: 103_NL103P5C Main
CUTLER-HAMMER (ED)
225 A
PNL: 103_NL103P5C (Sec 1) 208V, 225A 4.2k SCA 200k SCAR
CB: 103_NCRAR DIMMER RACK
CUTLER-HAMMER (BAB)
40 A
F: 103_Pnl NL103P5C (SEC 2)
(1) #4/0 THWN; 15 ft
PNL: 103_NL103P5C (SEC 2)
208V, 225A 4.0k SCA 200k SCAR
CB: 103_Pnl B1H
SQUARE D (LH)
400 A
F:103_Pnl B1H
(1) #600 THWN; 160 ft
CB: 103_FAN RM
SQUARE D
100 A
THERMAL CURVE = 100A
F: 103_FAN RM
(1) #2 THWN; 160 ft
CB: 103_Pnl NH103P5M
SQUARE D
200 A
THERMAL CURVE = 200A
INSTANTANEOUS = LO (1125A)
F: 103_Pnl NH103P5M
(1) #3/0 THWN; 60 ft
CB: 103_XF T-153
SQUARE D
90 A
THERMAL CURVE = 90A
F: 103_XF T-153
(1) #2 THWN; 20 ft
XF: 103_T-153
75kVA; 5.26%Z Pri: 480V Sec: 208V
F: 103_Pnl NL103P5D (SEC 1)
(1) #4/0 THWN; 20 ft
CB: 103_NL103P5D (SEC 1) Main
CUTLER-HAMMER (ED)
225 A
PNL: 103_NL103P5D (SEC 1)
208V, 225A 3.5k SCA 200k SCAR
F: 103_Pnl NL103P5D (SEC 2)
(1) #4/0 THWN; 5 ft
PNL: 103_NL103P5D (SEC 2)
208V, 225A 3.5k SCA 200k SCAR
F: 103_NH103MSB (FDR F4B)
(2) #500 THWN; 70 ft
CONTINUE TO SWBD:
103_NH103MSB
(SEE SHEET 103EP601)
SWBD: 103_105
480V, 800A 27.5k SCA 200k SCAR
CB: 103_TRAILER
SQUARE D
200 A
THERMAL CURVE = 200A
F: 103_TRAILER
(1) #2/0 THWN; 360 ft
XF: 103_TRAILER
150kVA; 5.45%Z Pri: 480V Sec: 208V
F: 103_Disc A
(1) #2/0 THWN; 5 ft
DISC: 103_Disc A 208V, 5.1k SCA
FU: 103_Disc A
BUSSMANN (FRS-R)
200 A
F: 103_Disc A
(1) #2/0 THWN; 1 ft
PNL: 103_PANEL A
208V, START OF SINGLE PHASE
F: 103_Disc B
(1) #2/0 THWN; 5 ft
DISC: 103_Disc B 208V, 5.1k SCA
FU: 103_Disc B
BUSSMANN (FRS-R)
200 A
F: 103_Disc B
(1) #2/0 THWN; 1 ft
PNL: 103_PANEL B
208V, CB: 103_RETURN FAN
CUTLER-HAMMER
50 A
THERMAL CURVE = 50A
F: 103_RETURN FAN
(1) #10 THWN; 100 ft
VFD: 103_RETURN FAN
MTR: 103_RETURN FAN
1 @ 20.0 hp
CB: 103_SUPPLY FAN
CUTLER-HAMMER
90 A
THERMAL CURVE = 90A
F: 103_SUPPLY FAN
(1) #8 THWN; 100 ft
VFD: 103_SUPPLY FAN
MTR: 103_SUPPLY FAN
1 @ 25.0 hp
TAP: 103_XF TRAILER SEC
208V, 5.2k SCA
CB: 103_HEATING PUMP P1
CUTLER-HAMMER
20 A
THERMAL CURVE = 20A
F: 103_VFD HEATING PUMP P1
(1) #12 THWN; 80 ft
VFD: 103_Heating Pump P1
F: 103_HEATING PUMP P1
(1) #12 THWN; 10 ft
DISC: 103_HWP-1
480V, 1.6k SCA
FU: 103_HWP-1
LITTELFUSE (IDSR)
20 A
F: 103_HWP-1
(1) #12 THWN; 5 ft
MTR: 103_HWP-1
1 @ 2.0 hp
CB: 103_HEATING PUMP P2
CUTLER-HAMMER
20 A
THERMAL CURVE = 20A
F: 103_VFD HEATING PUMP P2
(1) #12 THWN; 80 ft
VFD: 103_HEATING PUMP P2
F: 103_Heating Pump P2
(1) #12 THWN; 10 ft
DISC: 103_HWP-2
480V, 1.6k SCA
FU: 103_HWP-2
LITTELFUSE (IDSR)
20 A
F: 103_HWP-2
(1) #12 THWN; 5 ft
MTR: 103_HWP-2
1 @ 2.0 hp
CB: 103_HEATING PUMP P3
CUTLER-HAMMER
20 A
THERMAL CURVE = 20A
F: 103_VFD HEATING PUMP P3
(1) #12 THWN; 80 ft
VFD: 103_HEATING PUMP P3
F: 103_HEATING PUMP P3
(1) #12 THWN; 10 ft
DISC: 103_P3 CIRC PUMP
480V, 1.6k SCA
FU: 103_P3 CIRC PUMP
LITTELFUSE (IDSR)
20 A
F: 103_P3 CIRC PUMP
(1) #12 THWN; 5 ft
MTR: 103_P-3 CIRC PUMP
1 @ 5.0 hp
CB: 103_FAN 1
SIEMENS (BQD)
20 A
F: 103_FAN 1
(1) #10 THWN; 25 ft
VFD: 103_FAN 1
MTR: 103_FAN 1
1 @ 7.5 hp
CB: 103_FAN 2
SIEMENS (BQD)
30 A
F: 103_FAN 2
(1) #10 THWN; 25 ft
VFD: 103_FAN 2
MTR: 103_FAN 2
1 @ 15.0 hp
CB: 103_FAN 3
SIEMENS (BQD)
30 A
F: 103_FAN 3
(1) #10 THWN; 35 ft
VFD: 103_FAN 3
MTR: 103_FAN 3
1 @ 15.0 hp
PNL: 103_FAN RM
480V, 125A 7.0k SCA 100k SCAR
CONTINUE TO PNL:
104_B1H
(SEE SHEET 104EP601)
START OF SINGLE PHASE
THERMAL CURVE = NO CHANGE
INSTANTANEOUS = HI (4000A)
PNL: 103_NH103P5M
480V, 225A 18.8k SCA 200k SCAR
BUILDING 103 - ONE LINE DIAGRAM (SWBD 105)
1 REPLACEMENT OVERCURRENT PROTECTIVE DEVICE.
EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS
TO BE REVISED AS SHOWN.
BLDG 103 - REVISED ONE-LINE
DIAGRAM (PART 2 OF 4)
1111211
11111
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
GENERAL NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE EXISTING ONE-LINE DIAGRAM ON SHEET
103EP602 FOR ALL MODIFICATIONS.
103EP602
SCALE : NTS
1 BLDG 103 - REVISED ONE-LINE DIAGRAM (PART 2 OF 4)
103ED602
F: 103_ATS EQ (N)
(2) #500 THWN; 10 ft
ATS_EQ (800A)
F: 103_SWBD EH103DP2
(2) #500 THWN; 25 ft
CONTINUE TO MCC:
104_EH4MC1
(SEE SHEET 104EP602)
CONTINUE TO MCC:
103_EH103MC2N
(SEE SHEET 103EP604)
SWBD: 103_EH103DP2
480V, 1600A
27.7K SCA
50K SCAR
CB: 103_MCC-EH103M2N
CUTLER-HAMMER (DSII-508)
400 A, 200 A Plug
F: 103_MCC-EH103M2N
(1) #3/0 THWN; 240 ft
CB: 103_MCC-EH104MC1
CUTLER-HAMMER (DSII-508)
600 A, 300 A Plug
F: 103_MCC-EH104MC1
(1) #350 THWN; 320 ft
CB: 103_Pnl DEH-103-P5
CUTLER-HAMMER (DSII-508)
800 A, 400 A Plug
F: 103_Pnl DEH-103-P5
(2) #3/0 THWN; 180 ft
CB: 103_MCC-EH103M1S
CUTLER-HAMMER (DSII-508)
400 A, 200 A Plug
F: 103_MCC-EH103M1S
(1) #3/0 THWN; 260 ft
CB: 103_EH103-P-1
CUTLER-HAMMER (DSII-508)
400 A, 200 A Plug
F: 103_EH103-P-1
(1) #3/0 THWN; 80 ft
CB: 103_XF XE41N
CUTLER-HAMMER (DSII-508)
400 A, 200 A Plug
F: 103_XF XE41N
(1) #2/0 THWN; 180 ft
CB: 103_EH103DP1S
CUTLER-HAMMER (DSII-508)
800 A, 400 A Plug
F: 103_EH103DP1S
(1) #500 THWN; 80 ft
PNL: 103_EH103DP1S
480V, 400A
19.6K SCA
200K SCAR
CB: 103_XF EL103DP1N
CUTLER-HAMMER (FD)
175 A
F: 103_XF EL103DP1N
(1) #2/0 THWN; 140 ft
XF: 103_T-143
113kVA; 5.90%Z Pri: 480V Sec: 208V
F: 103_Pnl EL103DP1N
(1) #500 THWN; 20 ft
CB: 103_EL103DP1N MAIN
CUTLER-HAMMER (DK)
400 A
CB: 103_XF EL103DP1S
CUTLER-HAMMER (FD)
175 A
F: 103_XF EL103DP1S
(1) #2/0 THWN; 60 ft
XF: 103_T-144
113kVA; 5.90%Z Pri: 480V Sec: 208V
F: 103_Pnl EL103DP1S
(1) #500 THWN; 15 ft
CB: 103_EL103DP1S MAIN
CUTLER-HAMMER (DK)
400 A
PNL: 103_EL103DP1S
208V, 400A
4.4K SCA
200K SCAR
CB: 103_Pnl EL1031S
CUTLER-HAMMER (ED)
100 A
F: 103_Pnl EL1031S
(1) #3 THWN; 5 ft
PNL: 103_EL1031S
208V, 100A
4.3K SCA
200K SCAR
CB: 103_ELEV S-13
CUTLER-HAMMER (ED)
100 A
F: 103_DISC ELEV S-13
(1) #1 THWN; 180 ft
DISC: 103_ELEV S-13 (S-12)
480V, 7.0K SCA
MCP: 103_EL S-13
CUTLER-HAMMER (HMCP)
F: 103_ELEV S-13
(1) #1 THWN; 20 ft
MTR: 103_S-13
1 @ 50.0 HP
CB: 103_Pnl EL1032S
CUTLER-HAMMER (ED)
100 A
F: 103_Pnl EL1032S
(1) #3 THWN; 15 ft
PNL: 103_EL1032S
208V, 100A 4.1k SCA 200k SCAR
CB: 103_Pnl EH1031N
CUTLER-HAMMER (FD)
100 A
F: 103_Pnl EH1031N
(1) #2 THWN; 160 ft
PNL: 103_EH1031N
480V, 100A
6.4K SCA
14K SCAR
CB: 103_WATER PURIFICATION
CUTLER-HAMMER (GHB)
80 A
CB: 103_Pnl EL1033S
CUTLER-HAMMER (ED)
100 A
F: 103_Pnl EL1033S
(1) #3 THWN; 20 ft
PNL: 103_EL1033S
208V, 100A
4.0K SCA
200K SCAR
CB: 103_F129A COLD RM COMP
CUTLER-HAMMER (BAB)
20 A
CB: 103_Pnl EL1034S
CUTLER-HAMMER (ED)
100 A
F: 103_Pnl EL1034S
(1) #3 THWN; 60 ft
PNL: 103_EL1034S
208V, 225A
3.2K SCA
200K SCAR
PNL: 103_EL1035S
208V, 225A
2.8K SCA
200K SCAR
F: 103_Pnl EL1035S
(1) #3 THWN; 80 ft
CB: 103_Pnl EL1035S
CUTLER-HAMMER (ED)
100 A
CB: 103_Pnl EL1036S
CUTLER-HAMMER (ED)
100 A
F: 103_Pnl EL1036S
(1) #3 THWN; 70 ft
PNL: 103_EL1036S
208V, 225A
3.0K SCA
200K SCAR
CB: 103_Pnl EL1038N
CUTLER-HAMMER (ED)
175 A
F: 103_Pnl EL1038N
(1) #3 THWN; 140 ft
PNL: 103_EL1038N
208V, 225A
2.1K SCA
200K SCAR
CB: 103_LASER DISC
CUTLER-HAMMER (BAB)
70 A
CB: 103_F225 COLD RM COMP
CUTLER-HAMMER (BAB)
20 A
PNL: 103_EL1034N
208V, 100A
2.3K SCA
200K SCAR
F: 103_Pnl EL1034N
(1) #3 THWN; 120 ft
CB: 103_Pnl EL1034N
CUTLER-HAMMER (ED)
100 A
CB: 103_Pnl EL1037N
CUTLER-HAMMER (ED)
100 A
F: 103_Pnl EL1037N
(1) #3 THWN; 130 ft
PNL: 103_EL1037N
208V, 100A
2.2K SCA
200K SCAR
CB: 103_F132 DOCK LEVELER
CUTLER-HAMMER (BAB)
20 A
CB: 103_ROLL-UP DOOR
CUTLER-HAMMER (BAB)
20 A
CB: 103_Pnl EL1033N
CUTLER-HAMMER (ED)
100 A
F: 103_Pnl EL1033N
(1) #3 THWN; 130 ft
PNL: 103_EL1033N
208V, 100A
2.2K SCA
200K SCAR
CB: 103_Pnl EL1031N
CUTLER-HAMMER (ED)
100 A
F: 103_Pnl EL1031N
(1) #3 THWN; 10 ft
PNL: 103_EL1031N
208V, 100A
4.0K SCA
200K SCAR
CB: 103_Pnl EL1035N
CUTLER-HAMMER (ED)
100 A
F: 103_Pnl EL1035N
(1) #3 THWN; 30 ft
PNL: 103_EL1035N
208V, 100A
3.6K SCA
200K SCAR
CB: 103_E145 COLD RM COMP
CUTLER-HAMMER (BAB)
20 A
CB: 103_Pnl EL1032N
CUTLER-HAMMER (ED)
100 A
F: 103_Pnl EL1032N
(1) #3 THWN; 25 ft
PNL: 103_EL1032N
208V, 100A
3.7K SCA
200K SCAR
CB: 103_Pnl EL1036N
CUTLER-HAMMER (ED)
100 A
F: 103_Pnl EL1036N
(1) #2 THWN; 210 ft
PNL: 103_EL1036N
208V, 100A
1.8K SCA
200K SCAR
CB: 103_225 COMP ROOF
CUTLER-HAMMER (BAB)
20 A
CB: 103_E-145 COLD RM COMP
CUTLER-HAMMER (BAB)
20 A
CB: 103_Pnl NH102-1
SQUARE D (KH)
225 A
F: 103_Pnl NH102-1
(1) #3/0 THWN; 310 ft
CB: 103_SEWAGE Pump
SQUARE D
20A
THERMAL CURVE = 20A
F: 103_SEWAGE Pump
(1) #12 THWN; 80 ft
DISC: 103_SEW Pump
480V, 1.7K SCA
FU: 103_SEW PumpS
GOULD SHAWMUT (A6D)
20 A
CB: 103_Pnl NH103-1
SQUARE D
225 A
F: 103_Pnl NH103-1A
(1) #3/0 THWN; 80 ft
CB: 103_BLDG 16 EDP
SQUARE D (KH)
225 A
F: 103_BLDG 16 EDP
(1) #4/0 THWN; 420 ft
CB: 103_ROLLUP DOOR
SQUARE D (EH)
15 A
CB: 103_XF T-151
SQUARE D (EH)
40 A
F: 103_XF T-151
(1) #8 THWN; 10 ft
XF: 103_T-151
15kVA; 5.10%Z Pri: 480V Sec: 208V
F: 103_Pnl NL103-1
(1) #6 THWN; 15 ft
CB: 103_NL103-1 MAIN
SQUARE D (QO-VH)
50 A
PNL: 103_NL103-1
208V, 100A
0.8K SCA
65K SCAR
CB: 103_AIR COMP
SQUARE D (QO)
20 A
CB: 103_EF-1
SQUARE D (EH)
15 A
PNL: 103_NH103-1
480V, 225A
11.3K SCA
14K SCAR
MTR: 103_103-REF-4
1 @ 3.0 HP
F: 103_103-REF-4
(1) #12 THWN; 170 ft
MCP: 103_103-REF-4
CUTLER-HAMMER (HMCP)
MCC: 103_EH103MC1S
480V, 600A
8.5K SCA
42K SCAR
MCP: 103_103-REF-3
CUTLER-HAMMER (HMCP)
F: 103_103-REF-3
(1) #12 THWN; 190 ft
MTR: 103_103-REF-3
1 @ 7.5 HP
MCP: 103_103-REF-2
CUTLER-HAMMER (HMCP)
MCP: 103_103-REF-1
CUTLER-HAMMER (HMCP)
MCP:103_103-HRP-4
CUTLER-HAMMER (HMCP)
F: 103_103-HRP-4
(1) #12 THWN; 120 ft
MTR: 103_103 HRP-4
1 @ 0.5 HP
MTR: 103_103 HRP-3
1 @ 0.5 HP
F: 103_103-HRP-3
(1) #12 THWN; 120 ft
MCP: 103_103-HRP-3
CUTLER-HAMMER (HMCP)
CB: 103_FC UNIT FOR USS
CUTLER-HAMMER (HFD)
15A
CB: 103_SUMP Pump
CUTLER-HAMMER (HFD)
20 A
CB: 103_XF EL103P1
CUTLER-HAMMER (HFD)
50 A
F: 103_XF EL103P1
(1) #6 THWN; 15 ft
XF: 103_EL103P1
30kVA; 5.60%Z Pri: 480V Sec: 208V
F: 103_Pnl EL103P1
(1) #3 THWN; 10 ft
CB: 103_EL103P1 MAIN
CUTLER-HAMMER (BAB)
100 A
PNL: 103_EL103P1
208V, 100A
1.4K SCA
200K SCAR
CB: 103_UH-5
CUTLER-HAMMER (HFD)
15 A
PNL: 103_EL103DP1N
208V, 400A
4.2K SCA
200K SCAR
PNL: 103_DEH103P5
480V, 600A
16.0K SCA
50K SCAR
MCP: 103_103-WEF-1
CUTLER-HAMMER (HMCP)
PNL: 103_EH103P1
480V, 250A
16.9K SCA
200K SCAR
CONTINUE TO DISC:
16_XF T-133.
SEE SHEET 016EP601
CONTINUE TO PNL:
102_NH102-1
(SEE SHEET 102EP601)
CONTINUE TO XF:
104_T-147.
(SEE SHEET 104EP601)
CONTINUE TO SWBD:
103_NH103DP1
(SEE SHEET 103EP601)
SENSOR RATING = NO CHANGE
LONG TIME PICKUP = 1.0 (400A)
LONG TIME DELAY = 15
SHORT TIME PICKUP = 10.0 (4000A)
SHORT TIME DELAY = 0.1 I2T IN
INSTANTANEOUS = 12 (4800A)
SENSOR RATING = NO CHANGE
LONG TIME PICKUP = 0.85 (170A)
LONG TIME DELAY = 24
SHORT TIME PICKUP = 10.0 (1700A)
SHORT TIME DELAY = 0.1 I2T IN
INSTANTANEOUS = 12 (2400A)
SENSOR RATING = NO CHANGE
LONG TIME PICKUP = 1.0 (200A)
LONG TIME DELAY = NO CHANGE
SHORT TIME PICKUP = 5.0 (1000A)
SHORT TIME DELAY = 0.3 I2TIN
INSTANTANEOUS = 8 (1600A)
SENSOR RATING = NO CHANGE
LONG TIME PICKUP = 1.0 (200A)
LONG TIME DELAY = NO CHANGE
SHORT TIME PICKUP = 2.0 (400A)
SHORT TIME DELAY = 0.1 I2T IN
INSTANTANEOUS = 3 (600A)
SENSOR RATING = NO CHANGE
LONG TIME PICKUP = NO CHANGE
LONG TIME DELAY = NO CHANGE
SHORT TIME PICKUP = 8.0 (3200A)
SHORT TIME DELAY = 0.1 I2T IN
INSTANTANEOUS = 12 (4800A)
SENSOR RATING = NO CHANGE
LONG TIME PICKUP = 1.0 (300A)
LONG TIME DELAY = 4
SHORT TIME PICKUP = 6.0 (1800A)
SHORT TIME DELAY = 0.1 I2T IN
INSTANTANEOUS = 8 (2400A)
SENSOR RATING = NO CHANGE
LONG TIME PICKUP = 1.0 (200A)
LONG TIME DELAY = NO CHANGE
SHORT TIME PICKUP = 6.0 (1200A)
SHORT TIME DELAY = 0.5 I2T IN
INSTANTANEOUS = 8 (1600A)
THERMAL CURVE: NO CHANGE
INSTANTANEOUS: LO (1125A)
THERMAL CURVE: 200A
INSTANTANEOUS: 10 (2000A)
THERMAL CURVE: 200A
INSTANTANEOUS: 10 (2000A)
THERMAL CURVE= NO CHANGE
INSTANTANEOUS= 9 (3600A)
THERMAL CURVE= NO CHANGE
INSTANTANEOUS= 9 (3600A)
THERMAL CURVE= 175A
INSTANTANEOUS= FIXED
CONTINUE TO SWBD:
100_SUB-B2-GENSD-G5
F: 100_ATS-EQ-103 (E)
(2) #500 THWN; 480 ft
GENERAL NOTES
BUILDING 103 - ONE LINE DIAGRAM (ATS-EQ)
EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS
TO BE REVISED AS SHOWN.
REPLACEMENT OVERCURRENT PROTECTIVE DEVICE.
BLDG 103 - REVISED ONE-LINE
DIAGRAM (PART 3 OF 4)
1111111
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE EXISTING ONE-LINE DIAGRAM ON SHEET
103ED603 FOR ALL MODIFICATIONS.
103EP603
SCALE : NTS
1 BLDG 103 - REVISED ONE-LINE DIAGRAM (PART 3 OF 4)
CONTINUE TO SWBD:
100_SUB-B2-GENSD-G5
F: 100_ATS-LS-103 (E)
(1) #500 THWN; 460 ft
CONTINUE TO SWBD:
103_NH103DP1
(SEE SHEET 103EP601)
F: 103_ATS LS (N)
(1) #500 THWN; 10 ft
ATS-LS-103
400A
F: 103_Pnl LSH103DP1S
(1) #500 THWN; 240 ft
CB: 103_Pnl LSH1031N
CUTLER-HAMMER (FD)
100 A
F: 103_Pnl LSH1031N
(1) #3 THWN; 80 ft
PNL: 103_LSH1031N 480V, 100A
7.2k SCA 200k SCAR
CB: 103_Pnl LSH1032N
CUTLER-HAMMER (GHB)
60 A
THERMAL CURVE 60A
INSTANTANEOUS = FIXED
F: 103_Pnl LSH1032N
(1) #3 THWN; 80 ft
PNL: 103_LSH1032N
480V, 100A 4.8k SCA 200k SCAR
CB: 103_Pnl LSH103P5
CUTLER-HAMMER (FD)
60 A
F: 103_Pnl LSH103P5
(1) #4 THWN; 60 ft
PNL: 103_LSH103P5 480V, 225A
7.5k SCA 200k SCAR
CB: 103_Pnl LS-A-16
CUTLER-HAMMER (GHB)
30 A
THERMAL CURVE 30A
INSTANTANEOUS = FIXED
F: 103_Pnl LS-A-16
(1) #8 THWN; 160 ft
CB: 16_LSH-A-16 MAIN
SQUARE D (ED)
30 A
PNL: 16_LSH-A-16
480V, 30A 1.7k SCA 65k SCAR
CB: 16_XF T-1334
SQUARE D (ED)
15 A
F: 16_XF T-1334
(1) #12 THWN; 5 ft
XF: 16_T-1334
6kVA; 5.00%Z Pri: 480V Sec: 208V
F: 16_Pnl LSL-A-16
(1) #10 THWN; 5 ft
CB: 16_LSL-A-16 MAIN
SQUARE D (QO)
20 A
PNL: 16_LSL-A-16
208V, 20A 0.3k SCA 65k SCAR
CB: 103_XF T-148
CUTLER-HAMMER (FD)
50 A
F: 103_XF T-148
(1) #6 THWN; 20 ft
XF: 103_T-148
30kVA; 5.60%Z Pri: 480V Sec: 208V
F: 103_Pnl LL1031S
(1) #3 THWN; 15 ft
CB: 103_LL1031S MAIN
CUTLER-HAMMER (BAB)
100 A
PNL: 103_LL1031S
208V, 100A 1.4k SCA 200k SCAR
CB: 103_Pnl LSH1031S
CUTLER-HAMMER (FD)
60 A
F: 103_Pnl LSH1031S
(1) #6 THWN; 70 ft
PNL: 103_LSH1031S
480V, 100A 5.4k SCA 200k SCAR
CB: 103_Pnl LSH1041N
CUTLER-HAMMER (FD)
60 A
F: 103_Pnl LSH1041N
(1) #6 THWN; 80 ft
PNL: 104_LSH1041N
480V, 100A 4.9k SCA 200k SCAR
CB: 103_Pnl LSH1032S
CUTLER-HAMMER (FD)
60 A
F: 103_Pnl LSH1032S
(1) #6 THWN; 110 ft
PNL: 103_LSH1032S
480V, 100A 3.9k SCA 200k SCAR
CB: 103_Elev P-11
CUTLER-HAMMER (FD)
100 A
F: 103_DISC ELEV P-11
(1) #1 THWN; 120 ft
DISC: 103_Elev P-11 480V, 7.2k SCA
PNL: 103_LSH103DP1S
480V, 400A 12.5k SCA 200k SCAR
MCP: 103_Elev P-11
CUTLER-HAMMER
(HMCP)
F: 103_Elev P-11
(1) #1 THWN; 15 ft
MTR: 103_Elev P-11 1 @ 40.0 hp
CONTINUE TO SWBD:
103_EH103DP2
(SEE SHEET 103EP603)
F: 103_MCC-EH103M2N
(1) #3/0 THWN; 240 ft
MCP: 103_103-HRP-1
CUTLER-HAMMER
(HMCP)
F: 103_103-HRP-1
(1) #12 THWN; 80 ft
MTR: 103_103-HRP-1
1 @ 2.0 hp
MCP: 103_103-HRP-2
CUTLER-HAMMER
(HMCP)
F: 103_103-HRP-2
(1) #12 THWN; 80 ft
MTR: 103_103-HRP-2
1 @ 2.0 hp
MCP: 103_103-REF-7
CUTLER-HAMMER
(HMCP)
F: 103_103-REF-7
(1) #12 THWN; 120 ft
MTR: 103_103-REF-7
1 @ 7.5 hp
MCP: 103_103-REF-8
CUTLER-HAMMER
(HMCP)
MCP: 103_103-REF-9
CUTLER-HAMMER
(HMCP)
F: 103_103-REF-9
(1) #12 THWN; 100 ft
MTR: 103_103-REF-9
1 @ 7.5 hp
MCP: 103_103-HP-1
CUTLER-HAMMER
(HMCP)
F: 103_103-HP-1
(1) #8 THWN; 90 ft
VFD: 103_103-HP-1
MTR: 103_103-HP-1
1 @ 20.0 hp
MCP: 103_103-HP-2
CUTLER-HAMMER
(HMCP)
F: 103_103-HP-2
(1) #8 THWN; 90 ft
VFD: 103_103-HP-2
MTR: 103_103-HP-2
1 @ 20.0 hp
CB: 103_103-CHP-1
CUTLER-HAMMER
(HFD)
50 A
F: 103_103-CHP-1
(1) #8 THWN; 120 ft
VFD: 103_103-CHP-1
MTR: 103_103-CHP-1
1 @ 20.0 hp
CB: 103_103-CHP-2
CUTLER-HAMMER
(HFD)
50 A
F: 103_103-CHP-2
(1) #8 THWN; 120 ft
VFD: 103_103-CHP-2
MTR: 103_103-CHP-2
1 @ 20.0 hp
MCP: 103_103-ASU-3
CUTLER-HAMMER
(HMCP)
F: 103_103-ASU-3
(1) #10 THWN; 70 ft
MTR: 103_103-ASU-3
1 @ 20.0 hp
MCP: 103_103-ASU-4
CUTLER-HAMMER
(HMCP
F: 103_103-ASU-4
(1) #12 THWN; 100 ft
MTR: 103_103-ASU-4
1 @ 7.5 hp
MCP: 103_103-WEF-2
CUTLER-HAMMER (HMCP)
MCC: 103_EH103MC2N
480V, 600A 9.2k SCA 42k SCAR
CM
PM
2 3
GENERAL NOTES
BUILDING 103 - ONE LINE DIAGRAM (MCC103MC2N, ATS-LS)
1 1
BLDG 103 - REVISED ONE-LINE
DIAGRAM (PART 4 OF 4)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
REPLACEMENT OVERCURRENT PROTECTIVE DEVICE.
PROVIDE INTEGRAL COMMUNICATION MODULE (CM) AND
POWER METER CONNECTIONS (PM) INTERIOR TO ATS.
COMMUNICATION MODULE SHALL BE ASCO #5170, OR
APPROVED EQUAL. POWER METER CONNECTIONS SHALL
BE COMPRISED OF CT'S AND VOLTAGE CONNECTIONS
INTERIOR TO ATS AND SHALL CABLE TO POWER METER
AS INDICATED ON DRAWINGS. POWER METER SHALL BE
SCHNEIDER-ELECTRIC POWERLOGIC #PM8244, OR
APPROVED EQUAL. EQUIPMENT SHALL BE INSTALLED
WITH ALL REQUIRED WIRING, TERMINATIONS, AND
APPURTENANCES AS REQUIRED FOR A COMPLETE AND
FULLY FUNCTIONAL SYSTEM.
REPLACE EXISTING CONTROLLER WITH RUSSEL ATS
RPTCS CONTROLLER.
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE EXISTING ONE-LINE DIAGRAM ON SHEET
103ED604 FOR ALL MODIFICATIONS.
103EP604
SCALE : NTS
1 BLDG 103 - REVISED ONE-LINE DIAGRAM (PART 4 OF 4)
CB: 104_B1H Main
CUTLER-HAMMER (HKD)
400 A
PNL: 104_B1H
480V, 400A 15.1k SCA 200k SCAR
CB: 104_P3-104-H1 Main
CUTLER-HAMMER (HFD)
100 A
F: 104_P3-104-H1
(1) #1/0 THWN; 100 ft
PNL: 104_P3-104-H1
480V, 225A
9.3K SCA
200K SCAR
90 A
SPARE
XF: 104_T-150
75kVA; 5.50%Z Pri: 480V Sec: 208V
F: 104_Pnl P3-104-L1
(1) #3/0 THWN; 10 ft
CB: 104_P3-104-L1 Main
CUTLER-HAMMER (ED)
200 A
PNL: 104_P3-104-L1
208V, 225A 3.2k SCA 200k SCAR
CB: 104_Pnl B1H1
CUTLER-HAMMER (HFD)
200 A
F: 104_Pnl B1H1
(1) #3/0 THWN; 10 ft
CB:104_XF T-149
CUTLER-HAMMER (HFD)
100 A
F:104_XF T-149
(1) #1 THWN; 10 ft
XF: 104_T-149
75KVA; 4.56%Z
Pri: 480V Sec: 208V
F: 104_Pnl B1L1
(1) #4/0 THWN; 5 ft
CB: 104_B1L1 Main
CUTLER-HAMMER (ED)
225 A
PNL: 104_B1L1
208V, 225A 4.0k SCA 200k SCAR
F: 104_Pnl B1L2
(1) #4/0 THWN; 5 ft
PNL: 104_B1L2
208V, 225A
3.9K SCA
200K SCAR
CB: 104_AIR RETURN & EXH Fan
CUTLER-HAMMER (GHB)
20 A
THERMAL CURVE = 20A
F: 104_VFDAIR RETURN & EXH Fan
(1) #10 THWN; 110 ft
VFD: 104_AIR RETURN & EXH Fan
F: 104_AIR RETURN & EXH Fan
(1) #10 THWN; 5 ft
DISC: 104_AHU RETURN Fan
480V, 1.9K SCA
FU: 104_AHU RETURN
LITTELFUSE (IDSR)
25 A
F: 104_AHU Return
(1) #10 THWN; 40 ft
MTR: 104_AHU Return 1 @ 7.5 hp
CB: 104_AIR SUPPLY UNIT P-3
CUTLER-HAMMER (GHB)
50 A
THERMAL CURVE = 50A
F: 104_VFD AIR SUPPLY UNIT P-3
(1) #8 THWN; 120 ft
VFD: 104_AIR SUPPLY UNIT P-3
F: 104_AIR SUPPLY UNIT P-3
(1) #8 THWN; 5 ft
DISC: 104_AHU SUPPLY Fan
480V, 2.5K SCA
FU: 104_AHU SUPPLY
LITTELFUSE (IDSR)
40 A
F: 104_AHU SUPPLY
(1) #8 THWN; 40 ft
MTR: 104_AHU Supply 1 @ 20.0 hp
CB: 104_AHU-1B
CUTLER-HAMMER (GHB)
60 A
THERMAL CURVE = 60A
F: 104_AHU-1B
(1) #6 THWN; 110 ft
VFD: 104_AHU-1B
MTR: 104_AHU-1B
1 @ 15.0 hp
CB: 104_AHU-1A
CUTLER-HAMMER (GHB)
60 A
THERMAL CURVE = 60A
F: 104_AHU-1A
(1) #6 THWN; 120 ft
VFD: 104_AHU-1A
MTR: 104_AHU-1A
1 @ 20.0 hp
PNL: 104_B1H1
480V, 225A 14.5k SCA 65k SCAR
CONTINUE TO SWBD:
103_105
(SEE SHEET 103EP602)
2 2 2 2
XF: 104_T-147
113kVA; 5.90%Z Pri: 480V Sec: 208V
F: 104_Pnl EL104DP1
(1) #500 THWN; 20 ft
CB: 104_EL104DP1 Main
CUTLER-HAMMER (DK)
400 A
PNL:
104_EL104DP1
208V, 400A 4.2k SCA 200k SCAR
CB: 104_Pnl EL1041N
CUTLER-HAMMER (EHD)
100 A
F: 104_Pnl EL1041N
(1) #3 THWN; 5 ft
PNL:
104_EL1041N
208V, 100A 4.1k SCA 200k SCAR
CB: 104_Pnl EL1042N
CUTLER-HAMMER (EHD)
100 A
F: 104_Pnl EL1042N
(1) #3 THWN; 20 ft
PNL:
104_EL1042N
208V, 100A 3.8k SCA 200k SCAR
CB: 104_Pnl EL1041S
CUTLER-HAMMER (EHD)
100 A
F: 104_Pnl EL1041S
(1) #3 THWN; 100 ft
PNL:
104_EL1041S
208V, 100A 2.5k SCA 200k SCAR
CB: 104_Pnl EL1042S
CUTLER-HAMMER (EHD)
100 A
F: 104_Pnl EL1042S
(1) #3 THWN; 95 ft
PNL: 104_EL1042S
208V, 100A 2.5k SCA 200k SCAR
CB: 104_DEHUM COLD RM
CUTLER-HAMMER (BAB)
20 A
CB: 104_Pnl EL1043S
CUTLER-HAMMER (EHD)
100 A
F: 104_Pnl EL1043S
(1) #3 THWN; 80 ft
PNL: 104_EL1043S
208V, 100A 2.7k SCA 200k SCAR
CONTINUE TO SWBD:
103_EH103DP2
(SEE SHEET 103EP603)
THERMAL CURVE = NO CHANGE
INSTANTANEOUS = 7 (2800A)
BUILDING 104 - ONE LINE DIAGRAM (ATS-EQ)
200A 3P
104-P-01
GENERAL NOTES
EXISTING OVERCURRENT PROTECTIVE DEVICE SETTINGS
TO BE REVISED AS SHOWN.
REPLACEMENT OVERCURRENT PROTECTIVE DEVICE.
BLDG 104 - REVISED ONE-LINE
DIAGRAM (PART 1 OF 2)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
3. FOR ALL OVERCURRENT PROTECTION DEVICE
REPLACEMENT WORK, REFERENCE ASSOCIATED
BUILDING SCHEDULE "OVER-CURRENT PROTECTIVE
DEVICE (OCPD) REPLACEMENT SCHEDULE" FOR
ADDITIONAL INFORMATION.
4. FOR ALL OVERCURRENT PROTECTION DEVICE
ADJUSTMENT WORK, REFERENCE ASSOCIATED BUILDING
SCHEDULE "OVERCURRENT PROTECTIVE DEVICE (OCPD)
SETTING ADJUSTMENT SCHEDULE" FOR ADDITIONAL
INFORMATION.
5. FOR ALL POWER DISTRIBUTION EQUIPMENT
REPLACEMENT OR ADDITION WORK, REFERENCE
ASSOCIATED BUILDING SCHEDULE "POWER DISTRIBUTION
EQUIPMENT SCHEDULE" FOR ADDITIONAL INFORMATION.
6. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS
IMPACTED BY THIS PROJECT.
8. REFERENCE EXISTING ONE-LINE DIAGRAM ON SHEET
104ED601 FOR ALL MODIFICATIONS.
SCALE : NTS
1 BLDG 104 - REVISED ONE-LINE DIAGRAM (PART 1 OF 2)
104EP601
CONTINUE TO SWBD:
103_NH103MSB
(SEE SHEET 103EP601)
F: 103_NH104DP1N
(2) #350 THWN; 230 ft
CB: 104_XF T-146
CUTLER-HAMMER (kD) 350 A
F: 104_XF T-146
(1) #500 THWN; 25 ft
XF: 104_T-146
225kVA; 6.40%Z Pri: 480V Sec: 208V
F: 104_Pnl NL104DP1
(2) #500 THWN; 15 ft
F: 104_Pnl NH1041N
(1) #1 THWN; 5 ft
CB: 104_Pnl NH1041N
CUTLER-HAMMER (FD)
100 A
PNL: 104_NH1041N
480V, 100A 18.1k SCA 200k SCAR
F: 104_MCC NH104MC1
(1) #350 THWN; 250 ft
PNL: 104_NH104DP1
480V, 800A 18.8k SCA 200k SCAR
CB: 104_NL104DP1 MAIN
UNkNOWN (UNkNOWN) 800 A
CB: 104_104-ASU-1 SUPPLY
CUTLER-HAMMER (HFD)
60 A
F: 104_104-ASU-1 SUPPLY
(1) #8 THWN; 100 ft
VFD: 104_104-ASU-1 SUPPLY
MTR: 104_104-ASU-1 SUPPLY
1 @ 30.0 hp
CB: 104_104-ASU-1 RETURN
CUTLER-HAMMER (HFD)
40 A
F: 104_104-ASU-1 RETURN
(1) #10 THWN; 100 ft
VFD: 104_104-ASU-1 RETURN
MTR: 104_104-ASU-1 RETURN
1 @ 15.0 hp
MCP: 104_104-ASU-2 SUPPLY
CUTLER-HAMMER (HMCP)
F: 104_104-ASU-2 SUPPLY
(1) #6 THWN; 70 ft
MTR: 104_104-ASU-2 SUPPLY
1 @ 40.0 hp
CB: 104_104-UH-1
CUTLER-HAMMER (HFD)
15 A
CB: 104_104-UH-2
CUTLER-HAMMER (HFD)
15 A
F: 104_104-UH-2
(1) #12 THWN; 80 ft
CB: 104_104-CHP-1
CUTLER-HAMMER (HFD)
30 A
F: 104_104-CHP-1
(1) #10 THWN; 160 ft
VFD: 104_104-CHP-1
MTR: 104_104-CHP-1
1 @ 10.0 hp
CB: 104_104-CHP-2
CUTLER-HAMMER (HFD)
30 A
F: 104_104-CHP-2
(1) #10 THWN; 160 ft
VFD: 104_104-CHP-2
MTR: 104_104-CHP-2
1 @ 10.0 hp
MCP: 104_104-REF-1
CUTLER-HAMMER (HMCP)
F: 104_104-REF-1
(1) #10 THWN; 140 ft
MTR: 104_104-REF-1
1 @ 7.5 hp
CB: 104_Pnl NL1042S
CUTLER-HAMMER (ED)
150 A
F: 104_Pnl NL1042S
(1) #1/0 THWN; 200 ft
PNL: 104_NL1042S
208V, 225A 3.0k SCA 200k SCAR
CB: 104_Pnl NL1046N
CUTLER-HAMMER (ED)
150 A
F: 104_Pnl NL1046N
(1) #1/0 THWN; 25 ft
PNL: 104_NL1046N
208V, 225A 6.6k SCA 200k SCAR
CB: 104_Pnl NL1044N
CUTLER-HAMMER (ED)
150 A
F: 104_Pnl NL1044N
(1) #1/0 THWN; 15 ft
PNL: 104_NL1044N
208V, 225A 7.0k SCA 200k SCAR
CB: 104_Pnl NL1043S
CUTLER-HAMMER (ED)
150 A
F: 104_Pnl NL1043S
(1) #1/0 THWN; 220 ft
PNL: 104_NL1043S
208V, 225A 2.8k SCA 200k SCAR
CB: 104_Pnl NL1042N
CUTLER-HAMMER (ED)
150 A
F: 104_Pnl NL1042N
(1) #1/0 THWN; 10 ft
PNL: 104_NL1042N
208V, 225A 7.2k SCA 200k SCAR
CB: 104_Pnl NL1041N
CUTLER-HAMMER (ED)
150 A
F: 104_Pnl NL1041N
(1) #1/0 THWN; 15 ft
PNL: 104_NL1041N
208V, 225A 7.0k SCA 200k SCAR
CB: 104_Pnl NL1043N
CUTLER-HAMMER (ED)
150 A
F: 104_Pnl NL1043N
(1) #1/0 THWN; 10 ft
PNL: 104_NL1043N
208V, 225A 7.2k SCA 200k SCAR
CB: 104_Pnl NL1044S
CUTLER-HAMMER (ED)
150 A
F: 104_Pnl NL1044S
(1) #1/0 THWN; 150 ft
PNL: 104_NL1044S
208V, 225A 3.6k SCA 200k SCAR
CB: 104_Pnl NL1045N
CUTLER-HAMMER (ED)
150 A
F: 104_Pnl NL1045N
(1) #1/0 THWN; 20 ft
PNL: 104_NL1045N
208V, 225A 6.8k SCA 200k SCAR
CB: 104_G227 GLASS WASHER
CUTLER-HAMMER (BAB)
20 A
CB: 104_Pnl NL1041S
CUTLER-HAMMER (ED)
150 A
PNL: 104_NL104DP1
208V, 800A 7.6k SCA 200k SCAR
F: 104_Pnl NL1041S
(1) #1/0 THWN; 150 ft
PNL: 104_NL1041S
208V, 225A 3.6k SCA 200k SCAR
CB: 104_MCC NH104MC1
CUTLER-HAMMER (kD) 300 A
MCC: 104_NH4DP1
480V, 600A 9.5k SCA 42k SCAR
BUILDING 104 - ONE LINE DIAGRAM (PNL NH104DP1)
CONTINUE TO SWBD:
103_EH103DP2
(SEE SHEET 103EP603)
F: 103_MCC-EH104MC1
(1) #350 THWN; 320 ft
MCP: 104_104-WEF-1
CUTLER-HAMMER (HMCP)
MCP: 104_104-HRP-1
CUTLER-HAMMER (HMCP)
F: 104_104-HRP-1
(1) #12 THWN; 120 ft
MTR: 104_104-HRP-1
1 @ 5.0 hp
MCP: 104_104-HRP-2
CUTLER-HAMMER (HMCP)
F: 104_104-HRP-2
(1) #12 THWN; 120 ft
MTR: 104_104-HRP-2
1 @ 5.0 hp
MCP: 104_104-HP-1
CUTLER-HAMMER (HMCP)
F: 104_104-HP-1
(1) #12 THWN; 110 ft
MTR: 104_104-HP-1
1 @ 7.5 hp
MCP: 104_104-HP-2
CUTLER-HAMMER (HMCP)
F: 104_104-HP-2
(1) #12 THWN; 110 ft
MTR: 104_104-HP-2
1 @ 7.5 hp
MCP: 104_104-REF-2
CUTLER-HAMMER (HMCP)
F: 104_104-REF-2
(1) #12 THWN; 120 ft
MTR: 104_104-REF-2
1 @ 7.5 hp
MCP: 104_104-REF-3
CUTLER-HAMMER (HMCP)
F: 104_104-REF-3
(1) #12 THWN; 120 ft
MTR: 104_104-REF-3
1 @ 2.0 hp
MCP: 104_104-REF-4
CUTLER-HAMMER (HMCP)
MCP: 104_104-ACCU-1
CUTLER-HAMMER (HMCP)
F: 104_104-ACCU-1
(1) #12 THWN; 150 ft
DISC: 104_104-ACCU-1
480V, 0.9K SCA
FU: 104_104-ACCU-1 FUSE
LITTELFUSE (IDSR)
20 A
F: 104_104-ACCU-1 FUSE
(1) #12 THWN; 20 ft
MTR: 104_104-ACCU-1
1 @ 5.0 hp
MCP: 104_104-FC-1
CUTLER-HAMMER (HMCP)
MCP: 104_104-FC-2
CUTLER-HAMMER (HMCP)
CB: 104_Elev P-9
CUTLER-HAMMER (HFD)
100 A
F: 104_Elev P-9
(1) #3 THWN; 180 ft
DISC: 104_Elev P-9
480V, 4.0K SCA
MCP: 104_Elev P-9 Disc
CUTLER-HAMMER (HMCP)
F: 104_Elev P-9 Disc
(1) #3 THWN; 30 ft
EP: 104_Elev P-9
480V, 3.6K SCA
VFD: 104_Elev P-9
MTR: 104_Elev P-9 1 @ 60.0 hp
CB: 104_Elev P-10
CUTLER-HAMMER (HFD)
100 A
F: 104_Elev P-10
(1) #3 THWN; 180 ft
DISC: 104_Elev P-10
480V, 4.0K SCA
MCP: 104_Elev P-10 Disc
CUTLER-HAMMER (HMCP)
F: 104_Elev P-10 Disc
(1) #3 THWN; 40 ft
EP: 104_Elev P-10
480V, 3.5K SCA
VFD: 104_Elev P-10
MTR: 104_Elev P-10 1 @ 60.0 hp
MCC: 104_EH4MC1
480V, 600A
9.7K SCA
42K SCAR
BUILDING 104 - ONE LINE DIAGRAM (MCC EH4MC1)
GENERAL NOTES
BLDG 104 - REVISED ONE-LINE
DIAGRAM (PART 2 OF 2)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS,
TEMPORARY POWER PLANS, AND PHASING PLANS FOR
VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED
FOR REVIEW 30-DAYS PRIOR TO IMPLEMENTATION.
REFERENCE SPECIFICATION 01 00 00 FOR
COORDINATION OF ALL…