Attachment 5-648-20-119-VA OR Portland Electrical FCA DWGS STAMPED part 3.pdf
PDF 6 MB Posted
- Solicitation number
- 36C26025R0071
About this file
These electrical construction documents are detailed drawings for correcting electrical facility condition assessment (FCA) deficiencies at the VA Portland Health Care System, located in Portland, Oregon. The comprehensive set of technical drawings covers electrical modifications and replacements across multiple rooms and electrical infrastructure components in Building 100, including electrical rooms, substations, panelboards, transformers, and switchboards on various floors.
The drawings, prepared by Spees Design Build for the VA Office of Construction and Facilities Management, specify technical requirements for equipment modifications, including replacing existing electrical panels, upgrading circuit breakers, installing new power meters, modifying bus ducts, and integrating network switches. Each drawing provides detailed demolition and electrical plans, with specific notes referencing one-line diagrams on accompanying sheets, and includes general instructions for contractors such as field verification of existing conditions, coordinating shutdowns, and updating circuit panel directories. The project is fully sprinklered and involves precise electrical infrastructure improvements across multiple electrical rooms and spaces within the medical facility.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
559 SF
B1C-119
ELEC. ROOM
195 SF
B1C-123
ELEC. ROOM
559 SF
B1C-119
ELEC. ROOM
195 SF
B1C-123
ELEC. ROOM
CONTINUE FROM 100E-100
B1C-119 B1C-123
SCALE : 1/4" = 1'-0"
2 BLDG 100 - RM B1C-119 & B1C-123 - ENLARGED ELECTRICAL PLAN
SWBD: 100_B1SDE-E-18
POWER METER ENCLOSURE
SWBD: 100_B1SDN-E-17
ATS-LS-S2-2
B1SDN-E-18
BLDG 100 - RM B1C-119 & B1C-123
- ENLARGED ELECTRICAL PLANS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
ATS-CE-S2-1
100E-100
100-P-52A 100-C-05A
100-P-52B 100-C-05B
100-C-04A 100-P-51A
100-P-51B 100-C-04B
B1SDEC-E-18
XFMR: T-157
B1CL1-E-18
SWBD: 100_B1-SDLS-E-17 8
SWBD: B1-GSDE-E-16
ATS-DE-S2-3
SCALE : 1/4" = 1'-0"
1 BLDG 100 - RM B1C-119 & B1C-123 - ENLARGED ELECTRICAL DEMOLITION PLAN
100E-100
SWBD: 100_B1SDE-E-18
POWER METER ENCLOSURE
B1SDN-E-18
B1SDEC-E-18
XFMR: T-157
B1CL1-E-18 SWBD: B1-GSDE-E-16
ATS-DE-S2-3
PANEL: B1L1-E-17
XFMR: T-12
PANEL: B1L1-E-17
ATS-LS-S2-2
ATS-CE-S2-1
SWBD: 100_B1-SDLS-E-17 2
PROJECT
NORTH
0'0' 4' 8'2'
PROJECT
NORTH
0'0' 4' 8'2'
PANEL: B1L1-E-17
XFMR: T-12
PANEL: B1L1-E-17
JUNCTION BOX
SWBD: 100_B1SDN-E-17
FMS RACK
100E-400a
GENERAL NOTES
KEY NOTES
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED609 & 100EP609 FOR
ADDITIONAL INFORMATION.
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED610 & 100EP610 FOR
ADDITIONAL INFORMATION.
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED606 & 100EP606 FOR
ADDITIONAL INFORMATION.
EQUIPMENT TO BE MODIFIED.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED609 & 100EP609 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. PROVIDE INTEGRAL
COMMUNICATION MODULE INTERIOR TO ATS, ASCO #5170,
OR APPROVED EQUAL. PROVIDE CT'S AND VOLTAGE
CONNECTIONS INTERIOR TO ATS AND CABLE TO NEW SE
8244 POWER METER ENCLOSURE, OR APPROVED EQUAL.
EQUIPMENT SHALL BE INSTALLED WITH ALL REQUIRED
WIRING, TERMINATIONS, AND APPURTENANCES AS
REQUIRED FOR A COMPLETE AND FULLY FUNCTIONAL
SYSTEM. REFERENCE ONE-LINE DIAGRAMS ON SHEETS
100ED610 AND 100EP610 FOR ADDITIONAL INFORMATION.
EXISTING RMS RACK. TERMINATE ATS COMMUNICATION
AND POWER METER MODULE CABLING TO FMS RACK AS
SHOWN. PROVIDE PROGRAMMING AND DATA
INTEGRATION TO ENSURE DATA IS VIEWABLE ACROSS
NETWORK. COORDINATE WITH VA AS REQUIRED.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED610 & 100EP610 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED606 & 100EP606 FOR ADDITIONAL
INFORMATION.
PME ENCLOSURE "PME-LS-S2-2" WITH SE 8244 POWER
METER, OR APPROVED EQUAL, NETWORK SWITCH, AND
ALL REQUIRED APPURTENANCES OF EACH ATS. EXTEND
POWER CIRCUIT FROM EXISTING METERING SYSTEM
PANEL. REFERENCE SPECIFICATION 251010 FOR
ADDITIONAL INFORMATION.
PME ENCLOSURE "PME-CE-S2-1" WITH SE 8244 POWER
METER, OR APPROVED EQUAL, NETWORK SWITCH, AND
ALL REQUIRED APPURTENANCES OF EACH ATS. EXTEND
POWER CIRCUIT FROM EXISTING METERING SYSTEM
PANEL. REFERENCE SPECIFICATION 251010 FOR
ADDITIONAL INFORMATION.
AREA OF WORK
gmsfgnsfg
PROJECT
NORTH
KEY PLAN
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT
IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
FMS RACK7
PME ENCLOUSURE "PME-LS-S2-S" 10
JUNCTION BOX
�3���7�5�����7�5���100-P-52A 100-C-05B
100-C-04B
FMS
NETWORK. COORDINATE WITH VA AS REQUIRED.PME
PME ENCLOSURE "PME-LS-S2-2" WITH SE 8244 POWER
METER, OR APPROVED EQUAL, NETWORK SWITCH, AND
ALL REQUIRED APPURTENANCES OF EACH ATS. METER
ENCLOSURE SHALL RECEIVE POWER FROM EQUIPMENT IT IS
METERING; PROVIDE CPT AS REQUIRED. REFERENCE
SPECIFICATION 251010 FOR ADDITIONAL INFORMATION.
PME ENCLOSURE "PME-CE-S2-1" WITH SE 8244 POWER
METER, OR APPROVED EQUAL, NETWORK SWITCH, AND
ALL REQUIRED APPURTENANCES OF EACH ATS. METER
ENCLOSURE SHALL RECEIVE POWER FROM EQUIPMENT IT IS
METERING; PROVIDE CPT AS REQUIRED. REFERENCE
SPECIFICATION 251010 FOR ADDITIONAL INFORMATION.
100-P-52B100-C-05B100-C-19
765 SF
B1C-127
ELEC. ROOM
SPARE FUSE CABINET
CABINET
UNIT SUBSTATION: USS2
765 SF
B1C-127
ELEC. ROOM
UNIT SUBSTATION USS2 2
ACTIVE HARMONIC
FILTER "AHF-USS2 2" ACTIVE HARMONIC
FILTER "AHF-USS2 1"
100-P-18 100-C-09
100-C-15
100-P-17
100-C-08
SPARE FUSE CABINET
CABINET CONTINUE TO
100E-100
SCALE : 1/4" = 1'-0"
1 BLDG 100 - RM B1C-127 - USS2 ENLARGED ELECTRICAL DEMOLITION PLAN
BLDG 100 - RM B1C-127 - USS2
ENLARGED ELECTRICAL PLANS
JGD/JRB
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
100E-100
PROJECT
NORTH
SCALE : 1/4" = 1'-0"
2 BLDG 100 - RM B1C-127 - USS2 ENLARGED ELECTRICAL PLAN
100E-100
0' 4' 8'2'1'
PROJECT
NORTH
0' 4' 8'2'1'
100E-400b
PROJECT
NORTH
GENERAL NOTES
KEY NOTES
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED606 AND 100EP606 FOR
ADDITIONAL INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED606 AND 100EP606 FOR
ADDITIONAL INFORMATION.
ACTIVE HARMONIC FILTER COMMUNICATION FEED TO
TERMINATE IN SUBSTATION POWER METER LOCATION.
PROVIDE ADDITIONAL SWITCH AS REQUIRED. PROVIDE
CAT6A FROM PROVIDED SWITCH TO TERMINATE IN FMS
RACK IN ROOM B1C-119.
KEY PLAN
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT
IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
9D-149
AREA OF WORK
E-503
E-502 PROVIDE NETWORK SWITCH WITH CONTROL POWER
TRANSFORMER (CPT) LOCATED INTERIOR TO EXISTING UNIT
SUBSTATION POWER METER CUBICLE; CPT SHALL USE
SUBSTATION AS SOURCE. PROVIDE DATA CABLES FROM
REPLACEMENT UNIT SUBSTATION CIRCUIT BREAKERS AND
ACTIVE HARMONIC FILTER (AHF) TO NETWORK SWITCH.
PROVIDE CAT6A CABLING FROM NETWORK SWITCH TO
EXTEND TO LOCAL PME ENCLOSURE NETWORK SWITCH.
PROVIDE PROGRAMMING AND INTEGRATION OF
REPLACEMENT CIRCUIT BREAKER AND AHF STATUS / DATA
TO EXISTING FACILITY PME NETWORK.
100-P-51B100-C-04B100-C-19
B1C-104
CLOSET, ELEC.
B1C-104
CLOSET, ELEC.
PNL: 100_B1H1-F-14
PNL: 100_B1DEH1-F-14
BLDG 100 - RM B1C-104 - ENLARGED
ELECTRICAL PLANS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
TRANSFORMER
"100_T-13"
SCALE : 3/4" = 1'-0"
1 BLDG 100 - RM B1C-104 - ENLARGED ELECTRICAL DEMOLITION PLAN 0' 1' 3'2'
PNL: 100_B1L1-F-14 SEC 2
PNL: 100_B1L1-F-14 SEC 1
PNL: 100_B1L1-F-14 SEC 3
100E-100
PROJECT
NORTH
PNL: 100_B1H1-F-14
PNL: 100_B1DEH1-F-14
TRANSFORMER
"100_T-13"
PNL: 100_B1L1-F-14 SEC 2
PNL: 100_B1L1-F-14 SEC 1
PNL: 100_B1L1-F-14 SEC 3
SCALE : 3/4" = 1'-0"
2 BLDG 100 - RM B1C-104 - ENLARGED ELECTRICAL PLAN 0' 1' 3'2'
100E-100
PROJECT
NORTH
100E-400c
PROJECT
NORTH
GENERAL NOTES
KEY NOTES
EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 100ED609 & 100EP609
FOR ADDITIONAL INFORMATION.
EXISTING SECONDARY TAP TO BE DEMOLISHED.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED609 & 100EP609 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED606 & 100EP606 FOR ADDITIONAL
INFORMATION.
KEY PLAN
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT
IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
B1C-104
AREA OF WORK
TRANSFORMER
(ABOVE)
TRANSFORMER
(ABOVE)
PNL: 100_B1LD1-F-14
100-P-28
100-P-56
100-P-57 100-P-58
5 PROVIDE PANELBOARD AS INDICATED. PANELBOARD SHALL
BE MOUNTED ABOVE TRANSFORMER; PANELBOARD AND
TRANSFORMER FACES SHALL EVENLY ALIGN. PROVIDE
UNISTRUT AND STAINLESS-STEEL FASTENING HARDWARE AS
REQUIRED TO MOUNT PANELBOARD.
966 SF
B1D-108
ELEC. RM. HIGH VOLT. SWITCH
MEDIUM VOLTAGE EQUIPMENT1
BATTERY
RACK
BATTERY
CHARGER
CONTROL PANEL ENCLOSURE
OHSU CONTROL PANEL
WALL-MOUNTED DISCONNECT
2 5
METERING
SYSTEM
UNNAMED PANEL
966 SF
B1D-108
ELEC. RM. HIGH VOLT. SWITCH
MEDIUM VOLTAGE EQUIPMENT6
OHSU CONTROL PANEL
WALL-MOUNTED DICONNECT
UNNAMED PANEL
METERING
SYSTEM
BATTERY
RACK
BATTERY
CHARGER
CONTROL PANEL ENCLOSURE
GENERAL NOTES
KEY NOTES
SCALE : 1/4" = 1'-0"
1 BLDG 100 - RM B1D-108 - MV ENLARGED ELECTRICAL DEMOLITION PLAN
BLDG 100 - RM B1D-108 - MV
ENLARGED ELECTRICAL PLANS
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED601 & 100EP601 FOR
ADDITIONAL INFORMATION.
CONTINUE TO MASTER GENERATOR CONTROL PANEL IN
BUILDLING 100 ROOM B2D-106A. REFERENCE SHEET
100E-4000b FOR ADDITIONAL INFORMATION.
EXISTING FEEDER #1 EXTENDING FROM MV SWITCHGEAR
TO UNITSUBSTATION "USNW" CONDUCTORS TO BE
REPLACED.
CONTINUE TO UNITSUBSTATION "USNW" IN ROOM
B1D-109. REFERENCE SHEET 100E-402e FOR ADDITIONAL
INFORMATION.
EXISTING OHSU PANEL ELECTRONICS TO BE MODIFIED.
REFERENCE DETAIL 2 ON SHEET E-501 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED601 & 100EP601 FOR ADDITIONAL
INFORMATION.
SPARE CIRCUIT BREAKER FOR MV SWITCHGEAR.
REFERENCE ONE-LINE DIAGRAM ON SHEET 100EP601.
COORDINATE FINAL LOCATION WITH VA.
FEEDER #1 EXTENDING FROM MV SWITCHGEAR TO
UNITSUBSTATION "USNW".
CONTINUE TO UNITSUBSTATION "USNW" IN BUILDING 100
ROOM B1D-109. SHEET 100E-400e.
KEY PLAN
AREA OF WORK
B1D-108
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
100E-100
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING
EQUIPMENT IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
PROJECT
NORTH
SCALE : 1/4" = 1'-0"
2 BLDG 100 - RM B1D-108 - MV ENLARGED ELECTRICAL PLAN 0' 1' 2' 4'
100E-100
PROJECT
NORTH
100-P-13
0' 1' 2' 4'
PROJECT
NORTH
100E-400d
E-501
SUBSTATION "USNW" IN BUILDING 100
SUBSTATION "USNW".
SUBSTATION "USNW" IN ROOM
909 SF
B1D-109
ELEC. RM. UNIT SUB.
LOCKERSCABINET
TRANSFORMER (FEEDING BIOMED
PANEL)
BATTERY RACK
ENCLOSED CIRCUIT
BREAKER (BELOW)
JUNCTION BOX (ABOVE)
ATS-CE-NW-4
METERING SYSTEM PANELUPS CABINET WITH
DISTRIBUTION PANEL
SPARE FUSE CABINET
UNIT SUBSTATION:
USNW
909 SF
B1D-109
ELEC. RM. UNIT SUB.
LOCKERSCABINET
TRANSFORMER (FEEDING BIOMED
PANEL) BATTERY RACK
ENCLOSED CIRCUIT
BREAKER (BELOW)
JUNCTION BOX (ABOVE)
METERING SYSTEM PANEL
SPARE FUSE CABINET
UNIT SUBSTATION:
USNW
100-C-03A
100-P-13
ACTIVE HARMONIC
FILTER "AHF-USNW 1" 100-P-21
100-C-11
ACTIVE HARMONIC
FILTER "AHF-USNW 2"
100-P-20
100-C-10
100-C-16
100-P-50A
ATS-CE-NW-4 11
UPS CABINET WITH
DISTRIBUTION PANEL
CONTINUE FROM
100E-100
GENERAL NOTES
KEY NOTES
SCALE : 1/4" = 1'-0"
1 BLDG 100 - RM B1D-109 - USNW ENLARGED ELECTRICAL DEMOLITION PLAN
BLDG 100 - RM B1D-109 - USNW
ELECTRICAL PLAN
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAM ON SHEET 100ED611 & 100EP611 FOR
ADDITIONAL INFORMATION.
CONTINUE TO MV SWITCHGEAR IN BUILDING 100 ROOM
B1D-108. SHEET 100E-400d.
EXISTING FEEDER #1 EXTENDING FROM MV SWITCHGEAR
TO UNIT SUBSTATION "USNW" CONDUCTORS TO BE
REPLACED. REFERENCE ONE-LINE DIAGRAM ON SHEET
100ED601 FOR ADDITIONAL INFORMATION.
CONTINUE TO SUBSTATION "USS1". REFERENCE ONE-LINE
DIAGRAM ON SHEET 100ED601 FOR ADDITIONAL
INFORMATION.
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAM ON SHEET 100ED614 AND 100EP614 FOR
ADDITIONAL INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAM
ON SHEET 100ED611, 100EP611 FOR ADDITIONAL
INFORMATION.
SPARE CIRCUIT BREAKERS. REFERENCE ONE-LINE
DIAGRAM ON SHEET 100EP611. COORDINATE FINAL
LOCATION WITH VA.
ACTIVE HARMONIC FILTER AND AUTOMATIC TRANSFER
SWITCH COMMUNICATION FEED TO TERMINATE IN
SUBSTATION POWER METER LOCATION. PROVIDE
ADDITIONAL SWITCH AS REQUIRED. PROVIDE CAT6A
FROM PROVIDED SWITCH TO TERMINATE IN LOCAL
POWER METER ENCLOSURE.
FEEDER #1 EXTENDING FROM MV SWITCHGEAR TO UNIT
SUBSTATION "USNW". REFERENCE ONE-LINE SHEET
100ED601 FOR ADDITIONAL INFORMATION.
PROVIDE CIRCUIT BREAKER TEST SET. REFERENCE
SPECIFICATION 262300 FOR ADDITIONAL INFORMATION.
MODIFIED EQUIPMENT. PROVIDE INTEGRAL
COMMUNICATION MODULE INTERIOR TO ATS, ASCO
#5170,OR APPROVED EQUAL. PROVIDE CT'S AND
VOLTAGE CONNECTIONS INTERIOR TO ATS AND CABLE
TO PME ENCLOSURE "PME-CE-NW-4". EQUIPMENT
SHALL BE INSTALLED WITH ALL REQUIRED WIRING,
TERMINATIONS, AND APPURTENANCES AS REQUIRED
FOR A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
METERING SYSTEM PANEL. PROVIDE 4-PORT SWITCH FOR
TERMINATION OF COMMUNICATION FEEDS.
KEY PLAN
AREA OF WORK
B1D-109
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
100E-100
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING
EQUIPMENT IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
PROJECT
NORTH
PROJECT
NORTH
SCALE : 1/4" = 1'-0"
2 BLDG 100 - RM B1D-109 - USNW ENLARGED ELECTRICAL PLAN
100E-100
PROJECT
NORTH
0 4' 8'2' 0 4' 8'2'
100E-400e
E-503
E-502
E-505
100-C-01B
DIAGRAMS
SHEETS 100ED611 AND 100EP611 FOR ADDITIONAL
100-C-03A 100-P-50A
100-C-03B 100-P-50B
PME ENCLOSURE12
B1D-109
PROVIDE NETWORK SWITCH WITH CONTROL POWER
TRANSFORMER (CPT) LOCATED INTERIOR TO EXISTING UNIT
SUBSTATION POWER METER CUBICLE; CPT SHALL USE
SUBSTATION AS SOURCE. PROVIDE DATA CABLES FROM
REPLACEMENT UNIT SUBSTATION CIRCUIT BREAKERS AND
ACTIVE HARMONIC FILTER (AHF) TO NETWORK SWITCH.
PROVIDE CAT6A CABLING FROM NETWORK SWITCH TO
EXTEND TO LOCAL PME ENCLOSURE NETWORK SWITCH.
PROVIDE PROGRAMMING AND INTEGRATION OF
REPLACEMENT CIRCUIT BREAKER AND AHF STATUS / DATA
TO EXISTING FACILITY PME NETWORK.
FEEDER #1 EXTENDING FROM MV SWITCHGEAR TO UNIT
SUBSTATION "USNW". REFERENCE ONE-LINE SHEET
100ED601 FOR ADDITIONAL INFORMATION.
PROVIDE CIRCUIT BREAKER TEST SET. REFERENCE
SPECIFICATION 262300 FOR ADDITIONAL INFORMATION.
MODIFIED EQUIPMENT. PROVIDE INTEGRAL
COMMUNICATION MODULE INTERIOR TO ATS, ASCO
#5170,OR APPROVED EQUAL. PROVIDE CT'S AND
VOLTAGE CONNECTIONS INTERIOR TO ATS AND CABLE
TO PME ENCLOSURE "PME-CE-NW-4". EQUIPMENT
SHALL BE INSTALLED WITH ALL REQUIRED WIRING,
TERMINATIONS, AND APPURTENANCES AS REQUIRED
FOR A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
MODIFIED PME ENCLOSURE.12
CONTINUE FROM
100E-100
KEY PLAN
KEY NOTES
PME ENCLOSURE "PME-CE-NW-4-1" WITH SE 8244 POWER
METER, OR APPROVED EQUAL, NETWORK SWITCH, AND
ALL REQUIRED APPURTENANCES OF EACH ATS. METER
ENCLOSURE SHALL RECEIVE POWER FROM EQUIPMENT IT IS
METERING; PROVIDE CPT AS REQUIRED. REFERENCE
SPECIFICATION 251010 FOR ADDITIONAL INFORMATION.
100-C-01B
100-P-52B100-C-05B100-C-22
765 SF
B1D-112
MECH. RM. CHILLER UNIT
BUSS FUSE ENCLOSURE
CABINETS
METERING
SYSTEM
CABINET
CONDUIT
UNIT SUBSTATION: USCP
CABINET
CABINETS
MECH. RM. CHILLER UNIT
BUSS FUSE
ENCLOSURE
UNIT SUBSTATION: USCP
METERING SYSTEM
CABINETS
CABINETS
CONDUIT
CABINETS
ACTIVE HARMONIC
FILTER "AHF-USCP 2"
ACTIVE HARMONIC
FILTER "AHF-USCP 1"
CABINETS
GENERAL NOTES
KEY NOTES
SCALE : 1/4" = 1'-0"
1 BLDG 100 - RM B1D-112 - USCP ENLARGED ELECTRICAL DEMOLITION PLAN
BLDG 100 - RM B1D-112 - USCP
ENLARGED ELECTRICAL PLANS
KEY PLAN
AREA OF WORK
B1D-112
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
100E-100
PROJECT
NORTH
PROJECT
NORTH
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED616 AND 100EP616 FOR
ADDITIONAL INFORMATION.
EXISTING CABINET TO BE RELOCATED. COORDINATE
WITH VA FOR EXACT LOCATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED616 AND 100EP616 FOR
ADDITIONAL INFORMATION.
ACTIVE HARMONIC FILTER COMMUNICATION FEED TO
TERMINATE IN SUBSTATION POWER METER LOCATION.
PROVIDE ADDITIONAL SWITCH AS REQUIRED. PROVIDE
CAT6A FROM PROVIDED SWITCH TO TERMINATE IN LOCAL
POWER METER ENCLOSURE.
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING
EQUIPMENT IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
0 4' 8'2'
SCALE : 1/4" = 1'-0"
2 BLDG 100 - RM B1D-112 - USCP ENLARGED ELECTRICAL PLAN
100E-100
PROJECT
NORTH
0 4' 8'2'
100E-400f
100-P-13 100-C-24
100-C-17
100-P-12
100-C-23
E-503 4
E-505
E-502
-23
PROVIDE NETWORK SWITCH WITH CONTROL POWER
TRANSFORMER (CPT) LOCATED INTERIOR TO EXISTING UNIT
SUBSTATION POWER METER CUBICLE; CPT SHALL USE
SUBSTATION AS SOURCE. PROVIDE DATA CABLES FROM
REPLACEMENT UNIT SUBSTATION CIRCUIT BREAKERS AND
ACTIVE HARMONIC FILTER (AHF) TO NETWORK SWITCH.
PROVIDE CAT6A CABLING FROM NETWORK SWITCH TO
EXTEND TO LOCAL PME ENCLOSURE NETWORK SWITCH.
PROVIDE PROGRAMMING AND INTEGRATION OF
REPLACEMENT CIRCUIT BREAKER AND AHF STATUS / DATA
TO EXISTING FACILITY PME NETWORK.
100-C-12
100-C-13
100-P-24
016-P-03100-C-23
348 SF
B1D-111
EMER. TRANS. SWITCH
348 SF
B1D-111
EMER. TRANS. SWITCH
GENERAL NOTES
KEY NOTES
SCALE : 1/2" = 1'-0"
2 BLDG 100 - RM B1D-111 - ENLARGED ELECTRICAL PLAN
AREA OF WORK
KEY PLAN
MODIFIED EQUIPMENT. PROVIDE INTEGRAL
COMMUNICATION MODULE INTERIOR TO ATS, ASCO #5170,
OR APPROVED EQUAL. PROVIDE CT'S AND VOLTAGE
CONECCTIONS INTERIOR TO ATS AND CABLE TO NEW SE
8244 POWER METER ENCLOSURE, OR APPROVED EQUAL.
EQUIPMENT SHALL BE INSTALLED WITH ALL REQUIRED
WIRING, TERMINATIONS, AND APPURTENANCES AS
REQUIRED FOR A COMPLETE AND FULLY FUNCTIONAL
SYSTEM.
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED617 & 100EP617 FOR
ADDITIONAL INFORMATION.
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED614 & 100EP614 FOR
ADDITIONAL INFORMATION.
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED615 & 100EP615 FOR
ADDITIONAL INFORMATION.
PME ENCLOSURE "PME-LS-NW-2 & 3" WITH (1) SE 8244
POWER METERS EACH, OR APPROVED EQUAL, NETWORK
SWITCH, AND ALL REQUIRED APPURTENANCES OF EACH
ATS. EXTEND POWER CIRCUIT FROM EXISTING METERING
SYSTEM PANEL. REFERENCE SPECIFICATION 251010 FOR
ADDITIONAL INFORMATION.
CONTINUE TO LOCAL METERING SYSTEM PANEL LOCATED
IN ROOM B1D-109.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED617 & 100EP617 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED614 & 100EP614 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED615 & 100EP615 FOR ADDITIONAL
INFORMATION.
BLDG 100 - RM B1D-111 - ENLARGED
ELECTRICAL PLANS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
SWBD: B1-SDEC-G-3
ATS-DE-NW-1
PNL:B1LSH1-G-3
PNL: B1L1-G-3
ATS-CE-NW-2
ATS-LS-NW-3
ATS-DE-CP-3
SWBD: B1-SDE-F-4
XFMR "T-90"
XFMR (ABOVE) "T-54"
PNL:B1LSL1-G-3PNL : B1L2-G-3
SWBD: B1-SDLS-G-3
XFMR "T-9"
PNL : SP4-UPS
B1D-111
0' 1' 2' 4'
100E-100
100-C-01B
100-P-49A
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING
EQUIPMENT IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
100-C-02A
PROJECT
NORTH
PROJECT
NORTH
SCALE : 1/2" = 1'-0"
1 BLDG 100 - RM B1D-111 - ENLARGED ELECTRICAL DEMOLITION PLAN
SWBD: B1-SDEC-G-3
ATS-DE-NW-1
PNL:B1LSH1-G-3
PNL: B1L1-G-3
ATS-CE-NW-2
ATS-LS-NW-3
ATS-DE-CP-3
SWBD: B1-SDE-F-4
XFMR "T-90"
XFMR (ABOVE) "T-54"
PNL:B1LSL1-G-3PNL : B1L2-G-3
SWBD:
B1-SDLS-G-3
XFMR "T-9"
PNL : SP4-UPS
100E-100 0' 1' 2' 4'
PROJECT
NORTH
100E-400g
100-P-48A 100-C-01A
571 SF
1C-154
ELEC. ROOM
139 SF
1C-187
EXAM
553 SF
C1-49
CORRIDOR
194 SF
1C-188
TEAM
159 SF
1C-190a
CLEAN UTILITY
117 SF
1C-189
SOILED UTILITY
115 SF
1C-190
EXAM
GG
GG
GG
ElevatorElevator
Elevator Elevator
Elevator
Elevator
Elevator Elevator
Elevator
Elevator
BAY 14 BAY 15BAY 13
BAY 16BAY 17BAY 18BAY 19
BAY 5
BAY 4
BAY 1BAY 2BAY 3
BED A
BED AA
BED AAA
1436 SF
C1-8
CORRIDOR
1B-126
TREATMENT
112 SF
1B-125A
TREATMENT
112 SF
1B-125
TREATMENT
110 SF
1B-114A
TREATMENT
114 SF
1B-114
LARGE TREATMENT
131 SF
1B-113
LARGE TREATMENT
133 SF
BAY 12BAY 11BAY 10BAY 9BAY 8BAY 7
571 SF
1C-154
ELEC. ROOM
GENERAL NOTES
KEY NOTES
AREA OF WORK
KEY PLAN
PNL: 1DEL1-D-17
BLDG 100 - RM 1C-154 - ENLARGED
ELECTRICAL PLANS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
RM 1C-154
TRANSFORMER: "T-15"
EXISTING PANEL TO BE DEMOLISHED AND REPLACED.
EXISTING FEEDER AND BRANCH CIRCUITS TO BE REUSED.
EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 100ED619 & 100EP619 FOR
ADDITIONAL INFORMATION.
EXISTING TRANSFORMER SECONDARY TAP TO BE
DEMOLISHED.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED619 & 100EP619 FOR ADDITIONAL
INFORMATION.
PROVIDE PANELBOARD AS INDICATED. EXTEND CONDUIT
AND WIRE AS REQUIRED SEE ASSOCIATED BUILDING 100
PANELBOARD SCHEDULES FOR CIRCUITING INFORMATION.
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING
EQUIPMENT IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
PROJECT
NORTH
PNL: 100_1H1-D-17
1L1-D-17 SEC.1
1L1-D-17 SEC.2
1L2-D-17 SEC.1
1L3-D-17
1L2-E-17
1L1-E-17 SEC. 1
1L1-E-17 SEC. 2
1DEH1-E-17
1DEL1-E-17
1H1-E-17
1DEL2-E-17
UPS2
UPS1
DISC. UPS2
DISC. UPS1
T-42
SWBD: 1SDV-D-17
DISC. 1H1-D-17
DISC. T-42
FUSE CABINET
PNL: 1H1-F.1-19.6
1H1-E-17
T-1H
MCC-N-1-G-17
MCC-N--C-17
BUS DUCT RISER
TELECOMMUNICATIONS
ENCLOSURE
UNNAMED PANEL
FIRE ALARM PANELS
BATTERY RACK
TRANSFORMER:
100_1DEL1-E-17
100-P-39A
1 BLDG 100 - RM 1C-154 - ENLARGED ELECTRICAL DEMOLITION PLAN 0'
SCALE : 1/4" = 1'-0"100E-101
0' 4' 6'
PROJECT
NORTH
2' 2 BLDG 100 - RM 1C-154 - ENLARGED ELECTRICAL PLAN 0'
SCALE : 1/4" = 1'-0"100E-101
0' 4' 6'
PROJECT
NORTH
2'
100-P-39B
PNL: 1DEL1-D-17
TRANSFORMER: "T-15"
PNL: 100_1H1-D-17
1L1-D-17 SEC.1
1L1-D-17 SEC.2
1L2-D-17 SEC.1
1L3-D-17
1L2-E-17
1L1-E-17 SEC. 1
1L1-E-17 SEC. 2
1DEH1-E-17
1DEL1-E-17
1H1-E-17
1DEL2-E-17
UPS2
UPS1
DISC. UPS2
DISC. UPS1
T-42
SWBD: 1SDV-D-17
DISC. 1H1-D-17
DISC. T-42
FUSE CABINET
PNL: 1H1-F.1-19.6
1H1-E-17
T-1H
MCC-N-1-G-17
MCC-N--C-17
BUS DUCT RISER
TELECOMMUNICATIONS
ENCLOSURE
UNNAMED PANEL
FIRE ALARM PANELS
BATTERY RACK
1L2-D-17 SEC.2
1L2-D-17 SEC.2
100E-401a
248 SF
1B-133
ELEC. ROOM
139 SF
1C-187
EXAM
553 SF
C1-49
CORRIDOR
194 SF
1C-188
TEAM
159 SF
1C-190a
CLEAN UTILITY
117 SF
1C-189
SOILED UTILITY
115 SF
1C-190
EXAM
GG
GG
GG
ElevatorElevator
Elevator Elevator
Elevator
Elevator
Elevator Elevator
Elevator
Elevator
BAY 14 BAY 15BAY 13
BAY 16BAY 17BAY 18BAY 19
BAY 5
BAY 4
BAY 1BAY 2BAY 3
BED A
BED AA
BED AAA
1436 SF
C1-8
CORRIDOR
1B-126
TREATMENT
112 SF
1B-125A
TREATMENT
112 SF
1B-125
TREATMENT
110 SF
1B-114A
TREATMENT
114 SF
1B-114
LARGE TREATMENT
131 SF
1B-113
LARGE TREATMENT
133 SF
BAY 12BAY 11BAY 10BAY 9BAY 8BAY 7
248 SF
1B-133
ELEC. ROOM
GENERAL NOTES
KEY NOTES
AREA OF WORK
KEY PLAN
BLDG 100 - RM 1B-133 - ENLARGED
ELECTRICAL PLANS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
SWBD: 100-1SDN-M-17
PNL: 1DEL1-M-17
TRANSFORMER
T-169
TRANSFORMER
T-168
PNL: 100_1CL1-M-17
PNL: 100_1L1-M-17 SEC 1
PNL: 100_1L1-M-17 SEC 2
TRANSFORMER T-3
PNL: 1H1-M-17
RM 1B-133
EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 100ED606 & 100EP606 FOR
ADDITIONAL INFORMATION.
EXISTING EQUIPMENT TO BE DEMOLISHED AND REPLACED.
EXISTING FEEDER AND BRANCH CIRCUITS TO BE REUSED.
EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 100ED609 & 100EP609 FOR
ADDITIONAL INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED606 & 100EP606 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED609 & 100EP609 FOR ADDITIONAL
INFORMATION.
PROVIDE PANELBOARD AS INDICATED. EXTEND CONDUIT
AND WIRE AS REQUIRED. SEE ASSOCIATED BUILDING 100
PANELBOARD SCHEDULES FOR CIRCUITING INFORMATION.
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING
EQUIPMENT IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
PROJECT
NORTH
1CL2-M17
DISC. T-169
LIGHTNG CONTROLS
FIRE ALARM PANELS
T-4
SWBD: 100-1SDN-M-174
TRANSFORMER
XFMR: "T-4"
PNL: 100_1CL1-M-17
PNL: 100_1L1-M-17 SEC 1
PNL: 100_1L1-M-17 SEC 2
TRANSFORMER T-3
PNL: 1H1-M-17
100-P-26B
100-P-26A
1 BLDG 100 - RM 1B-133 - ENLARGED ELECTRICAL DEMOLITION PLAN 0'
SCALE : 1/2" = 1'-0"100E-101
0' 2' 4'
PROJECT
NORTH
1' 2 BLDG 100 - RM 1B-133 - ENLARGED ELECTRICAL PLAN 0'
SCALE : 1/2" = 1'-0"100E-101
0' 2' 4'
PROJECT
NORTH
1'
1CL2-M17
LIGHTING CONTROLS
TRANSFORMER
DISC. T-169
TRANSFORMER
FIRE ALARM PANELS
FIRE ALARM PANEL
PNL: 1DEL1-M-17
100E-401b
FIRE ALARM PANEL
261 SF
1D-156
ELEC. ROOM
GG
GG
GG
ElevatorElevator
Elevator Elevator
Elevator
Elevator
Elevator Elevator
Elevator
Elevator
BAY 14 BAY 15BAY 13
BAY 16BAY 17BAY 18BAY 19
BAY 5
BAY 4
BAY 1BAY 2BAY 3
BED A
BED AA
BED AAA
1436 SF
C1-8
CORRIDOR
1B-126
TREATMENT
112 SF
1B-125A
TREATMENT
112 SF
1B-125
TREATMENT
110 SF
1B-114A
TREATMENT
114 SF
1B-114
LARGE TREATMENT
131 SF
1B-113
LARGE TREATMENT
133 SF
BAY 12BAY 11BAY 10BAY 9BAY 8BAY 7
261 SF
1D-156
ELEC. ROOM
BLDG 100 - RM 1D-156 - ENLARGED
ELECTRICAL PLANS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
PNL: 100_1DEH1-M-3
PNL: 100_1DEL1-M-3 SEC 1
PNL: 100_1DEL1-M-3 SEC 2
PNL: 100_1L2-M-3
PNL: 100_1L1-M-3 SEC 2
PNL: 100_1L1-M-3 SEC 1
PNL: 100_1H1-M-3
PNL: 100_1L3-M-3
TRANSFORMER
"T-124"
PNL: 100_1L4-M-3
CONDUIT
J-BOX
PNL: 100_1H2-M-3
PNL: 100_1DEL2-M-3
PNL: 100_1LS1-M-3
TRANSFORMER
"T-52"(BELOW)
"T-75" (ABOVE)
TRANSFORMER
"T-76" (BELOW)
"T-77" (ABOVE)
TRANSFORMER "T-74"
PNL: 100_1DEH1-M-3
PNL: 100_1DEL1-M-3 SEC 1
PNL: 100_1DEL1-M-3 SEC 2
PNL: 100_1L2-M-3
PNL: 100_1L1-M-3 SEC 2
PNL: 100_1L1-M-3 SEC 1
PNL: 100_1H1-M-3
PNL: 100_1L3-M-3
TRANSFORMER
"T-124 (BELOW)
TRANSFORMER
"100_1DEL1-M-3 SEC 2 (ABOVE)
PNL: 100_1L4-M-3
CONDUIT
J-BOX
PNL: 100_1H2-M-3
PNL: 100_1DEL2-M-3
PNL: 100_1LS1-M-3
TRANSFORMER
"T-52"(BELOW)
"T-75" (ABOVE)
TRANSFORMER
"T-76" (BELOW)
"T-77" (ABOVE)
TRANSFORMER "T-74"
100-P-46
1 BLDG 100 - RM 1D-156 - ENLARGED ELECTRICAL DEMOLITION PLAN 0'
SCALE : 1/2" = 1'-0"100E-101
0' 2' 4'
PROJECT
NORTH
1' 2 BLDG 100 - RM 1D-156 - ENLARGED ELECTRICAL PLAN 0'
SCALE : 1/2" = 1'-0"100E-101
0' 2' 4'
PROJECT
NORTH
1'
CONTINUE FROM SHEET 100E-100
100-P-47A
100-P-47B
100E-401c
PROJECT
NORTH
GENERAL NOTES
KEY NOTES
EXISTING PANEL TO BE DEMOLISHED AND REPLACED.
EXISTING FEEDER AND BRANCH CIRCUITS TO BE REUSED.
REFERENCE ONE-LINE DIAGRAMS ON SHEETS 100ED611 &
100EP611 FOR ADDITIONAL INFORMATION.
EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 100ED621 & 100EP621
FOR ADDITIONAL INFORMATION.
EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 100ED611 & 100EP611
FOR ADDITIONAL INFORMATION.
EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 100ED617 & 100EP617
FOR ADDITIONAL INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED611 & 100EP611 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED621 & 100EP621 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED617 & 100EP617 FOR ADDITIONAL
INFORMATION.
PROVIDE PANELBOARD AS INDICATED. EXTEND CONDUIT
AND WIRE AS REQUIRED. SEE ASSOCIATED BUILDING 100
PANELBOARD SCHEDULES FOR CIRCUITING INFORMATION.
KEY PLAN
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT
IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
1D-156
AREA OF WORK
351 SF
2C-118c
LAB, MEDIA PREP.
STAIR
NO. 3
91 SF
C2-37
CORRIDOR
90 SF
2C-122
MACH. RM. STERIL.
523 SF
2C-118b
GLASSWARE & STERILIZE
266 SF
C2-36
CORRIDOR
559 SF
2C-121
ELEC. RM.
190 SF
NO.2
STAIR
91 SF
C2-35
CORRIDOR
2C-120a
LAB BALANCE & SOLUTION
351 SF
2C-118c
LAB, MEDIA PREP.
STAIR
NO. 3
91 SF
C2-37
CORRIDOR
90 SF
2C-122
MACH. RM. STERIL.
523 SF
2C-118b
GLASSWARE & STERILIZE
266 SF
C2-36
CORRIDOR
559 SF
2C-121
ELEC. RM.
190 SF
NO.2
STAIR
91 SF
C2-35
CORRIDOR
2C-120a
357 SF
2C-118a
LAB BALANCE & SOLUTION
VAC
VAC
G
G
TB
(E
48TB
(E
48TB
(E
LI
N
TB
TB LIN
TB
LIN LINTB TB TB
LIN LIN
(E
LI
N
(E
TB
TB
TB
LI
N
LI
N
LI
N
(E
TB
LI
N
2B -1
LI
N
TB
TB
LI
N
LIN
TB TB
R
EF
SCALE : 3/8" = 1'-0"
2 BLDG 100 - RM 2C-121 - ENLARGED ELECTRICAL PLAN
SWBD: 100_2SDN-D-1711
PANEL 2H1-F.1-19 BUSWAY SWITCH8
PNL: 100_2CL3-E-17 SECTION 110
BLDG 100 - RM 2C-121 - ENLARGED
ELECTRICAL PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
2'0 4' 6'
100E-102
PROJECT
NORTH
XFMR: T-44
BATTERY RACK
T-43
BUS DUCT DISCONNECT
T-18
T-17
BUS DUCT DISCONNECT
T-16
FUSE CABINET
BUS DUCT
BUS DUCT
TE
FIRE ALARM PANEL
XFMR: T-106
SCALE : 3/8" = 1'-0"
1 BLDG 100 - RM 2C-121 - ENLARGED ELECTRICAL DEMOLITION PLAN
2'0 4' 6'
100E-102
PROJECT
NORTH
SWBD: 100_2SDN-D-172
PANEL 2H1-F.1-19 BUSWAY SWITCH3
PNL: 100_2CL3-E-17 SECTION 15
UPS-2CL3-E-17 SEC 1
XFMR: T-44
BATTERY RACK
T-43
BUS DUCT DISCONNECT
T-18
T-17
BUS DUCT DISCONNECT
T-16
FUSE CABINET
BUS DUCT
BUS DUCT
TE
FIRE ALARM PANEL
XFMR: T-106
PNL: 100_2L1-E-17 SECTION 2
PNL: 100_2L3-E-17 SECTION 1
PNL: 100_2L3-E-17 SECTION 2
PNL: 100_2L1-E-17 SECTION 1
PNL: 100_2L2-E-17 SECTION 2
8PNL: 100_2L2-E-17 SECTION 1
PNL: 100_2H1-E-17 SECTION 2
PNL: 100_2H1-E-17 SECTION 1
PNL: 100_2CL1-E-17 SECTION 2
PNL: 100_2CL1-E-17 SECTION 1
9PNL: 100_2CH1-E-17
UPS
PNL: 100_2L2-D-17 SECTION 2
PNL: 100_2L2-D-17 SECTION 1
PNL: 100_2L1-D-17 SECTION 2
PNL: 100_2L1-D-17 SECTION 1
PNL: 100_2H1-D-17 7
PNL: 100_2DEL1-D-17 SECTION 1
PNL: 100_2DEL1-D-17 SECTION 2 6
PNL: 100_2CH1-D-17
PNL: 100_2DEL2-D-17
PNL: 100_2DEH1-D-17 6
PNL: 100_2L1-E-17 SECTION 2
PNL: 100_2L3-E-17 SECTION 1
PNL: 100_2L3-E-17 SECTION 2
PNL: 100_2L1-E-17 SECTION 1
PNL: 100_2L2-E-17 SECTION 2
3PNL: 100_2L2-E-17 SECTION 1
PNL: 100_2H1-E-17 SECTION 2
PNL: 100_2H1-E-17 SECTION 1
PNL: 100_2CL1-E-17 SECTION 2
PNL: 100_2CL1-E-17 SECTION 1
4PNL: 100_2CH1-E-17
UPS
PNL: 100_2L2-D-17 SECTION 2
PNL: 100_2L2-D-17 SECTION 1
PNL: 100_2L1-D-17 SECTION 2
PNL: 100_2L1-D-17 SECTION 1
PNL: 100_2H1-D-17 2
PNL: 100_2DEL1-D-17 SECTION 1
PNL: 100_2DEL1-D-17 SECTION 2 1
PNL: 100_2CH1-D-17
PNL: 100_2DEL2-D-17
PNL: 100_2DEH1-D-17 1
UPS-2CL3-E-17 SEC 1
100E-402a
PROJECT
NORTH
GENERAL NOTES
KEY NOTES
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED609 & 100EP609 FOR
ADDITIONAL INFORMATION.
EXISTING PANELBOARD TO BE DEMOLISHED AND
REPLACED; PRESERVE EXISTING FEEDER AND BRANCH
CIRCUITING FOR RETERMINATION. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED607 & 100EP607 FOR
ADDITIONAL INFORMATION.
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED605 & 100EP605 FOR
ADDITIONAL INFORMATION.
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED608 & 100EP608 FOR
ADDITIONAL INFORMATION.
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED610 & 100EP610 FOR
ADDITIONAL INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED609 & 100EP609 FOR ADDITIONAL
INFORMATION.
RETERMINATION EXISTING BRANCH CIRCUITS INTO
REPLACEMENT PANELBOARD. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED607 & 100EP607 FOR
ADDITIONAL INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED605 & 100EP605 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED608 & 100EP608 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED610 & 100EP610 FOR ADDITIONAL
INFORMATION.
EXISTING SWITCHBOARD WITH MAIN INCOMING LUGS AND
ANALOG METERING. PROVIDE FIELD MODIFICATIONS AS
REQUIRED TO REPLACE INCOMING LUGS AND ANALOG
METERING WITH MAIN CIRCUIT BREAKER AND INTEGRAL
POWER METER (SE 8244), RESPECTIVELY. MODIFIED
EQUIPMENT SHALL BE RE-CERTIFIED BY UL FIELD
ENGINEERS AS REQUIRED. COORDINATE SHUTDOWN AND
RE-CERTIFICATION WITH VA.
CONTINUE TO 100E-102.
KEY PLAN
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT
IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
2C-121
AREA OF WORK
E-502
101-P-02
NO.1
STAIR
56 SF
65 SF
C2-23
VESTIBULE
279 SF
2B-127
ELEC. ROOM
707 SF
2B-125
LAB, PROSTHETICS
NO.1
STAIR
56 SF
65 SF
C2-23
VESTIBULE
279 SF
2B-127
ELEC. ROOM
707 SF
2B-125
LAB, PROSTHETICS
VAC
VAC
G
G
TB
(E
48TB
(E
48TB
(E
LI
N
TB
TB LIN
TB
LIN LINTB TB TB
LIN LIN
(E
LI
N
(E
TB
TB
TB
LI
N
LI
N
LI
N
(E
TB
LI
N
2B -1
LI
N
TB
TB
LI
N
LIN
TB TB
R
EF
SCALE : 1/2" = 1'-0"
2 BLDG 100 - RM 2B-127 - ENLARGED ELECTRICAL PLAN
BLDG 100 - RM 2B-127 - ENLARGED
ELECTRICAL PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
PANEL: 100_2L2-M-17
SECTION 2
PANELBOARD
PNL: 100_2L1-M-18
PANEL: 100_1LSH-M-17
TRANSFORMER "100_T-5"
0' 1' 2' 4'
100E-102
100-P-27
PROJECT
NORTH
SCALE : 1/2" = 1'-0"
1 BLDG 100 - RM 2B-127 - ENLARGED ELECTRICAL DEMOLITION PLAN
-100E-102
2PNL: 100_2CH1-M-17
PNL: 100_2H1-M-17
PNL: 100_2CL1-M-17 SECTION 1
PNL: 100_2L1-M-17 SECTION 2
PANEL: 100_2L2-M-17
SECTION 2
PANEL: 100_1LSH-M-17
TRANSFORMER "100_T-5"5
PNL: 100_2L2-M-17 SECTION 1
PNL: 100_2CL1-M-17 SECTION 2
PNL: 100_2L1-M-17 SECTION 1
0' 1' 2' 4'
PROJECT
NORTH
100E-402b
PROJECT
NORTH
GENERAL NOTES
KEY NOTES
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED606 & 100EP606 FOR
ADDITIONAL INFORMATION.
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED609 & 100EP609 FOR
ADDITIONAL INFORMATION.
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED606 & 100EP606 FOR
ADDITIONAL INFORMATION.
EQUIPMENT TO BE MODIFIED. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED609 & 100EP609 FOR
ADDITIONAL INFORMATION.
EXISTING SECONDARY SIDE TAP AND DOWNSTREAM
FEEDERS TO BE DEMOLISHED. REFERENCE ONE-LINE
DIAGRAMS ON SHEET 100ED606 &100EP606 FOR
ADDITIONAL INFORMATION.
KEY PLAN
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT
IS BEING RELOCATED AND/OR MODIFIED.
4. IF NUISANCE TRIPPING OCCURS AFTER CIRCUIT
BREAKERS HAVE BEEN REPLACED AND/OR ADJUSTED,
IMMEDIATELY INFORM AND COORDINATE WITH VA AS
REQUIRED.
5. REFERENCE SPECIFICATION 01 00 00 FOR COORDINATION
OF ALL SHUTDOWNS.
6. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL
DIRECTORIES FOR ALL PANELS THAT CONTAINS CIRCUITS
IMPACTED BY THIS PROJECT.
2B-127
AREA OF WORK
PNL: 100_2CH1-M-17
PNL: 100_2H1-M-17
PNL: 100_2CL1-M-17 SECTION 1
PNL: 100_2L1-M-17 SECTION 2
PNL: 100_2L2-M-17 SECTION 1
PNL: 100_2CL1-M-17 SECTION 2
PNL: 100_2L1-M-17 SECTION 1 3
100-P-62
100-P-61
100-P-59
100-P-60
F
E
D
MCC: 100_MCC-E-3-G-17
185 S.F.
NO.3
STAIR
STAIR
NO. 2
601 SF
3C-112
OR #2 ORTHOPEDIC
47 SF
3C-113
CLOSET, TELE.
47 SF
3C-123
CLOSET, TELE.
89 SF
C3-29
98 SF
C3-28b
ALCOVE
41 SF
3C-116
CONTROL 40 SF
3C-149 H.A.C.
376 SF
3C-119
EQUIPMENT ROOM
579 SF
3C-120
OR #3 NEUROSURGERY
550 SF
3C-115
ELEC. ROOM
C3-28a
VESTIBULE
115 SF
3C-121
O2/LINEN STORAGE
79 SF
3C-120a
SUB-STERILE
588 SF
3C-124
OR #4 CARDIAC
/8UPS
PME
3CH2-D-17
T-46 T-51
BUS DUCT DISCONNECT
XFMR
UNKNOWN XFMR
T-45
BUS DUCT DISCONNECT
FUSE CABINET
ACCU-1 BUSWAY SWITCH
BUS DUCT DISCONNECT
PNL: 100_3DEL2-E-17
PNL: 100_3LSL1-E-17
XF: "T-19"
BUS DUCT
F20
BUS DUCT DISCONNECT
TE
FIRE ALARM
3CL2-E-17
PNL: 100_3L2-E-17
PNL: 100_3CL1-E-17
PNL: 100_3CH1-E-17
PNL: 100_3L1-E-17
PNL: 100_3H1-E-17
PNL: 100_3LSH1-E-17
PNL: 100_3DEL1-E-17
PNL: 100_3DEH1-E-17
3L2-D-17
3L1-D-17
PNL: 100_3H1-D-17
XFMR: T-138
PNL: 100_3H2-D-17
3L3-D-17
3CL1-D-17 SEC 2
3CL1-D-17 SEC 1
PNL: 100_3CH1-D-17 SEC 2
PNL: 100_3CH1-D-17 SEC 1
SURGERY UPS DISC.
3CH1-D-17-UPS
FIRE ALARM
TRANSFORMER T-21
F
MCC: 100_MCC-E-3-G-17
185 S.F.
NO.3
STAIR
STAIR
NO. 2
601 SF
3C-112
OR #2 ORTHOPEDIC
47 SF
3C-113
CLOSET, TELE.
47 SF
3C-123
CLOSET, TELE.
89 SF
C3-29
98 SF
C3-28b
ALCOVE
41 SF
3C-116
CONTROL 40 SF
3C-149 H.A.C.
376 SF
3C-119
EQUIPMENT ROOM
579 SF
3C-120
OR #3 NEUROSURGERY
550 SF
3C-115
ELEC. ROOM
C3-28a
VESTIBULE
115 SF
3C-121
O2/LINEN STORAGE
79 SF
3C-120a
SUB-STERILE
588 SF
3C-124
OR #4 CARDIAC
ENCLOSED CIRCUIT BREAKER
"CB: 100_XF 3L2-E-17"
100-P-25C
100-P-25B
100-P-25A
100-P-41A
100-P-40
100-P-41B
UPS
PME
3CH2-D-17
T-46 T-51
BUS DUCT DISCONNECT
BUS DUCT DISCONNECT
FUSE CABINET
ACCU-1 BUSWAY SWITCH
BUS DUCT DISCONNECT
PNL: 100_3DEL2-E-17
PNL: 100_3LSL1-E-17
XF: "T-19"
BUS DUCT
XF:100_3L2-E-17
(ABOVE)
BUS DUCT DISCONNECT
TE
FIRE ALARM
PNL: 100_3L2-E-17
PNL: 100_3CL1-E-17
PNL: 100_3CH1-E-17
PNL: 100_3L1-E-17
PNL: 100_3H1-E-17
PNL: 100_3LSH1-E-17
PNL: 100_3DEL1-E-17
PNL: 100_3DEH1-E-17
3L2-D-17
3L1-D-17
PNL: 100_3H1-D-17
XFMR: T-138
PNL: 100_3H2-D-17
3L3-D-17
3CL1-D-17 SEC 2
3CL1-D-17 SEC 1
PNL: 100_3CH1-D-17 SEC 2
PNL: 100_3CH1-D-17 SEC 1
SURGERY UPS DISC.
3CH1-D-17-UPS
FIRE ALARM
TRANSFORMER T-21
TRANSFORMER "100_3DEL2-E-17" 6
3CL2-E-17
SCALE : 1/4" = 1'-0"
1 BLDG 100 - RM 3C-115 - ENLARGED ELECTRICAL DEMOLITION PLAN
BLDG 100 - RM 3C-115 - ENLARGED
ELECTRICAL DEMOLITION PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
648-20-119
Date:Revisions:
Approved:
Approved:CHIEF, FACILITY MANAGEMENT SERVICE
MEDICAL CENTER DIRECTOR
CONSULTANT
VA PORTLAND HEALTH CARE SYSTEM - PORTLAND, OR
CORRECT ELECTRICAL FCA
DEFICIENCIES BLDGS - VAORA/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
(206) 590-2118
RAY SPEES, PRESIDENT
DCW/LRL JGD/JRB01/31/2025
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
100E-103
PROJECT
NORTH
SCALE : 1/4" = 1'-0"
2 BLDG 100 - RM 3C-115 - ENLARGED ELECTRICAL PLAN
100E-103
PROJECT
NORTH
0 4' 8'2' 0 4' 8'2'
100E-403a
PROJECT
NORTH
GENERAL NOTES
KEY NOTES
EXISTING EQUIPMENT TO BE DEMOLISHED AND REPLACED.
EXISTING FEEDER AND BRANCH CIRCUITS TO BE REUSED.
REFERENCE ONE-LINE DIAGRAMS SHEETS 100ED619 &
100EP619 FOR ADDITIONAL INFORMATION.
EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 100ED605 & 100EP605
FOR ADDITIONAL INFORMATION.
EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 100ED603 & 100EP603
FOR ADDITIONAL INFORMATION.
EXISTING EQUIPMENT TO BE MODIFIED. REFERENCE
ONE-LINE DIAGRAMS ON SHEETS 100ED608 & 100EP608
FOR ADDITIONAL INFORMATION.
EXISTING EQUIPMENT TO BE DEMOLISHED AND REPLACED.
REFERENCE ONE-LINE DIAGRAMS ON SHEETS 100ED619 &
100EP619 FOR ADDITIONAL INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED619 & 100EP619 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED605 & 100EP605 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED603 & 100EP603 FOR ADDITIONAL
INFORMATION.
MODIFIED EQUIPMENT. REFERENCE ONE-LINE DIAGRAMS
ON SHEETS 100ED608 & 100EP608 FOR ADDITIONAL
INFORMATION.
REPLACEMENT PANELBOARD. REFERENCE ONE-LINE
DIAGRAMS ON SHEETS 100ED619 & 100EP619 FOR
ADDITIONAL INFORMATION.
KEY PLAN
1. PLAN IS INCLUDED TO SHOW OVERALL FLOOR PLAN AND
ASSOCIATED EQUIPMENT. ALL EQUIPMENT MAY NOT BE
SHOWN FOR CLARITY.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS. ANY DISCREPANCIES FOUND SHALL BE
REPORTED TO COR.
3. EXISTING EQUIPMENT LOCATIONS ARE APPROXIMATE.
EXACT LOCATIONS SHALL BE FIELD VERIFIED AND
REDLINED VIA CONTRACTOR WHERE EXISTING EQUIPMENT
IS BEING…