Attachment 8 - Drawing Part 5 676-325 Renovate B404 - Electrical and Technology.pdf
PDF 8 MB Posted
- Attached to
- Y1DA--Minor Construction - Tomah VAMC 676-325 Expand and Renovate B404 for Outpatient Mental Health
- Solicitation number
- 36C77623B0050_1
About this file
This set of construction drawings and specifications is for a project to expand and renovate an outpatient mental health clinic at the Tomah VA Medical Center in Tomah, Wisconsin. The project involves renovations and additions to Building B404, including upgrades to electrical, lighting, power, and systems. Key project details include expanding group room and office spaces, upgrading mechanical and plumbing systems, and installing new data cabling, security, and audiovisual systems. The solicitation is seeking bids from contractors to complete the construction work according to the design documents. Relevant details include a bid due date of January 2023 and a projected award date in February 2023. Pricing will be fixed-firm for the base bid work. The contract set-aside is for Service-Disabled Veteran-Owned Small Businesses. The federal agency issuing the solicitation is the Department of Veterans Affairs.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LIGHTING FIXTURES
SYMBOL DESCRIPTION
ELECTRICAL SYMBOLS
(NOTE: NOT ALL SYMBOLS INDICATED ARE USED ON PLANS. COORDINATE SYMBOLS USED
WITH SYMBOLS LEGEND ACCORDINGLY.)
EMERGENCY LIGHTING UNIT
SWITCHES & CONTROL OUTLETS
SWITCHES - 46" AFF
GANG LIGHT SWITCHES INDICATED ADJACENT TO EACH OTHER IN A
MULTI-GANG BOX AND MULTI-GANG FACEPLATE UNLESS OTHERWISE
NOTED
2 = DOUBLE POLE, SINGLE THROW
3 = THREE WAY
4 = FOUR WAY
K = KEY OPERATED
C = MOMENTARY CONTACT, SPDT, CENTER OFF
P = OFF PILOT LIGHT
V = VACANCY
0 = OCCUPANCY
a
POWER DISTRIBUTION
POWER OUTLETS
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
SINGLE RECEPTACLE, MOUNTED AT 18"AFF, UON
SHADED SYMBOL - ON EMERGENCY POWER
PANELBOARD
DUPLEX RECEPTACLE, MOUNTED AT 18"AFF, UON
DOUBLE DUPLEX RECEPTACLE, MOUNTED AT 18"AFF, UON
SPECIAL RECEPTACLE - CONFIGURATION AS INDICATED
MOUNTED 18"AFF, UON
SHADED SYMBOL - ON EMERGENCY POWER
JUNCTION BOX, MOUNTED 18"AFF, UONJ
J
DUPLEX OR DOUBLE DUPLEX RECEPTACLE, FLUSH, CEILING
MOUNTED, UON
DUPLEX OR DOUBLE DUPLEX RECEPTACLE, FLUSH, FLOOR
MOUNTED, UON
JUNCTION BOX, SURFACE MOUNTED ABOVE CEILING OR EXPOSED IN
AREAS WITH EXPOSED CONDUIT, UON
J JUNCTION OR PULL BOX, FLUSH, FLOOR MOUNTED, UON
TELECOMMUNICATION OUTLETS
WALL TELEPHONE OUTLET, 54" AFF
DATA OUTLET, 18" AFF
VOICE/DATA OUTLET, 18" AFF
SAME AS INDICATED ABOVE EXCEPT CIRCULAR SYMBOLS
INDICATE CEILING MOUNTED AND SQUARE SYMBOLS INDICATE
FLUSH MOUNTED IN FLOOR
SUBSCRIPTS ON ELECTRICAL OUTLETS
NUMBER INDICATES MOUNTING HEIGHT AFF TO CENTER LINE OF DEVICE.
ABOVE COUNTER - MOUNT DEVICE 6" ABOVE COUNTER OR 36" AFF AT
WORKSTATIONS.
WEATHER PROOF - PROVIDE NEMA-3R RATED DEVICE OR ENCLOSURE
SUITABLE FOR EXTERIOR USE.
TELEVISION DEDICATED - COORDINATE EXACT MOUNTING HEIGHT WITH
EQUIPMENT INSTALLATION REQUIREMENTS.
EXPLOSION PROOF PER NEC 500 CLASS I, DIVISION 1.
EXISTING DEVICE OR EQUIPMENT.
CONNECTED TO AN EMERGENCY POWER SOURCE.
DEDICATED - PROVIDE ENGRAVED COVER PLATE.
HOSPITAL GRADE.
TAMPER RESISTANT.
CONNECTED TO UPS SYSTEM.
ISOLATED GROUND.
GFCI.
ELECTRICAL CONTRACTOR.
+44" =
AC =
WP =
TV =
EP =
EX =
EM =
D =
H =
T =
U =
IG =
G =
E.C. =
MOTOR CONTROL CENTER
DISTRIBUTION POWER PANEL OR SWITCHBOARD
ELECTRICAL CABINET - CONFIGURATION AS INDICATED
PULL BOX, SIZED IN ACCORDANCE WITH NEC ARTICLE 314
REQUIREMENTS OR LARGER, UONPB
DISCONNECT SWITCH
MOTOR STARTER WITH NEMA SIZE AS INDICATED
CONDUIT CONCEALED IN CEILING OR WALL
CONDUIT EXPOSED
CONDUIT CONCEALED BELOW SLAB
WIRING METHOD AND IDENTIFICATION ( NOTE: WITHOUT FURTHER
IDENTIFICATION SYMBOL INDICATED 1/2" CONDUIT WITH 2#12 AWG
CONDUCTORS. CROSS LINES INDICATE QUANTITY #12 AWG
CONDUCTORS AND EXTENDED CROSS LINE W/O DOT INDICATES
NEUTRAL CONDUCTOR, W/ DOT INDICATES HARD WIRE GROUND.
NOTE: INCREASE CONDUCTOR SIZES AS LISTED IN THE BRANCH
CIRCUIT HOMERUN CONDUCTOR SIZING SCHEDULE. INCREASE
CONDUIT SIZE TO ACCOMMODATE INCREASE IN CONDUCTOR SIZE AS
PER THE NEC.
PNL
1,3,5
CONDUIT UPWARD
CONDUIT DOWNWARD
AIR TERMINAL - REFER TO DETAILS
GROUND ROD
GROUNDING & LIGHTNING PROTECTION
EXOTHERMIC WELD TYPE GROUNDING CONNECTION
WALL MOUNTED GROUNDING BUSBAR
TV TELEVISION OUTLET 18" AFF UON
CEILING MOUNTED SPEAKER, UON
WALL MOUNTED SPEAKER, 7'-6" AFF, UON
VOLUME CONTROL MOUNTED 48" AFF, UON
INTERCOM STATION MOUNTED 48" AFF, UON
VC
I
S
S
WLAN WIRELESS ADAPTER, CEILING MOUNTED UONW
DIMMERD
LIGHT SENSOR / PHOTO CONTROLPC
AT OCCUPANCY SENSOR, CEILING MOUNTED
PUSH BUTTON, 48" AFF UON
CABLE TV & PUBLIC ADDRESS
SOUND CONTROL STATIONAMP
MOTOR OR EQUIPMENT CONNECTION
T TRANSFORMER
CONDUIT / WIRING
NURSE CALL
CORRIDOR DOME STATUS LIGHT, ON CEILING
CORRIDOR DOME STATUS LIGHT, 90" AFF UON
PATIENT BED SINGLE-STATION, 48" AFF UON
PATIENT BED DUAL-STATION, 48" AFF UON
EMERGENCY PULL CORD STATION, 36" AFF UON
STAFF STATION, 48" AFF UON
CODE BLUE STATION, 48" AFF UON
PATIENT MONITORING OUTLET, 48" AFF UON
NURSE CALL CONTROL PANEL
NL
NCCP
NL
SECURITY
VIDEO CAMERA DOME, CEILING MOUNTED UON
CARD READER, 48" AFF UON
VIDEO CAMERA, WALL MOUNTED 90" AFF UON
MASTER STATION, AT NURSE STATION, 48" AFF UON
CR
REQUEST TO EXIT MOTION DETECTORREX
ALARM KEYPADK
MOTION DETECTORMD
BALANCED MAGNETIC SWITCHBMS
ONE-LINE
SYMBOL DESCRIPTION
GROUND CONNECTION
GENERATOR
FUSE
CIRCUIT BREAKER
METER
CURRENT TRANSFORMER
LIGHTNING ARRESTOR
CAPACITOR
DISCONNECT SWITCH
G F
G
M
P
GROUND FAULT PROTECTOR
DRAWOUT CIRCUIT BREAKER
MAGNETIC MOTOR STARTER
MOTOR
CIRCUIT BREAKER PANELBOARD
(H-X = 277/480V) (L-X = 208/120V)
H-1
TRANSFER SWITCHEN
L
TRANSFORMER
OVERLOAD RELAY
N.O. CONTACT
N.C. CONTACT
KIRK KEY
K
LAMP
ONE-LINE SYMBOLS
PB
a RECTANGULAR LUMINAIRE a = SWITCH LEG INDICATOR
A1 = FIXTURE TYPE (SEE FIXTURE SCHEDULE)
1 = CIRCUIT NUMBER
EMERGENCY LUMINAIRE
EXIT SIGN, CEILING OR WALL MOUNTED
A1
INDUSTRIAL / STRIP TYPE LUMINAIRE
ROUND LUMINAIRE
WALL MOUNTED LUMINAIRE
PENDANT MOUNTED LUMINAIRE
TRACK LIGHTING - TRACK & LUMINAIRES (VERIFY TRACK LENGTH AND
LUMINAIRE QUANTITIES WITH PLANS)
POLE MOUNTED LUMINAIRE (NUMBER OF HEADS AS INDICATED
ON PLANS.)
W
3 CT'SSOLID-STATE
MULTI-FUNCTION
METER
R
OS
GFI RECEPTACLE, MOUNTED AT 18"AFF, UON
DOUBLE SHADED SYMBOL - ON EMERGENCY POWER
NM
N1
N2
NE
NS
CB
NP
DURESS ALARM SYSTEMDA
NURSE CALL DEVICE (PULL CORD)NC
TOUCH-LESS WAVE-TO-EXIT SENSOR, FLUSH MOUNTED AT 48", UON.
DURESS ALARM, 18" AFF UONDA
DOUBLE SHADED SYMBOL - ON EMERGENCY POWER
SINGLE SHADED SYMBOL - SWITCHED RECEPTACLE - TOP
RECEPTACLE SWITCHED BASED ON VACANCY. BOTTOM
RECEPTACLE ALWAYS ON.
SINGLE SHADED SYMBOL - SWITCHED RECEPTACLE - LEFT DUPLEX
SWITCHED BASED ON OCCUPANCY. RIGHT DUPLEX ALWAYS ON.
1. IN CONNECTION WITH THE ALTERATIONS TO THE EXISTING BUILDING, THERE WILL
BE CERTAIN REMOVALS AND RELOCATIONS OF THE EXISTING ELECTRICAL WORK
NECESSARY FOR THE SATISFACTORY PERFORMANCE OF THE GENERAL WORK.
THESE CHANGES SHOULD BE TAKEN INTO CONSIDERATION BY THE CONTRACTOR
IN PREPARING THEIR PROPOSAL FOR THIS WORK. CONTRACTOR SHALL VISIT AND
CAREFULLY EXAMINE THE EXISTING AREAS AFFECTED PRIOR TO SUBMITTING
HIS/HER PROPOSAL. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS
EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. IF DIFFICULTIES ARISE
DURING THE DEMOLITION WORK THAT ARE BEYOND THE CONTRACT DOCUMENTS
AND REQUIRES ADDITIONAL WORK, THE CONTRACTOR SHALL COORDINATE THIS
WITH THE GOVERNMENT AND RESOLVE THE ISSUE(S) PRIOR TO CONTINUING
DEMOLITION OF THE AFFECTED AREA(S).
2. ELECTRICAL ITEMS INSTALLED IN WALLS, FLOORS, OR CEILINGS THAT ARE TO BE
DEMOLISHED SHALL BE REMOVED IN THEIR ENTIRETY, UNLESS OTHERWISE
NOTED OR REQUIRED BY OTHER CONDITIONS IN THESE DOCUMENTS. THE
CONTRACTOR SHALL CUT BACK TO THE FLOOR, WALL OR CEILING AND PLUG
BOTH ENDS OF CONCEALED CONDUITS MADE OBSOLETE BY THIS ALTERATION.
EXPOSED CONDUITS, WIREWAYS, PULL BOXES, HANGERS, ETC., MADE OBSOLETE
BY THE ALTERATION WORK SHALL BE REMOVED, UNLESS OTHERWISE NOTED.
ELECTRICAL CIRCUITS THAT ARE TO BE REMOVED SHALL BE REMOVED IN THEIR
ENTIRETY. CONDUCTORS SHALL BE COMPLETELY REMOVED FROM THE ITEM TO
BE DEMOLISHED BACK TO THE SOURCE OVERCURRENT DEVICE. EXISTING
CONDUCTORS SHALL NOT BE REUSED UNLESS OTHERWISE NOTED. SEE
DRAWINGS OF ALL OTHER TRADES FOR EXTENT OF DEMOLITION WORK.
ELECTRICAL ITEMS SHALL INCLUDE POWER, LIGHTING, COMMUNICATIONS AND
SPECIAL SYSTEMS. REFER QUESTIONS TO THE CONTRACTING OFFICER PRIOR TO
BID FOR CLARIFICATION. ANY FIELD DECISIONS BY THE GOVERNMENT SHALL BE
BINDING.
3. PHASING OF ELECTRICAL DEMOLITION SHALL FOLLOW THAT OF THE GENERAL
CONTRACTOR. COORDINATE REMOVAL OF ELECTRICAL WORK WITH OTHER
CONSTRUCTION ACTIVITIES AND THE REQUIREMENTS OF THE GOVERNMENT.
4. ANY SPECIFIC ITEMS THAT THE GOVERNMENT WISHES TO SALVAGE ARE
INDICATED ON THE PLANS. SALVAGED ITEMS SHALL BE CAREFULLY REMOVED BY
THE CONTRACTOR AND STORED IN A LOCATION AS DIRECTED BY THE
GOVERNMENT. ALL OTHER ITEMS OF DEMOLITION SHALL BECOME THE PROPERTY
OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE SITE.
5. WHERE DEMOLITION WORK WILL INTERRUPT CIRCUIT CONTINUITY TO AREAS OF
THE FACILITY THAT ARE TO REMAIN IN OPERATION, PROVIDE RACEWAYS AND
WIRING AS APPROPRIATE TO MAINTAIN CIRCUITRY TO THESE AREAS. PROVIDE
TEMPORARY CONNECTIONS AS REQUIRED.
6. WHERE COMPLETION OF WORK WILL INTERFERE WITH THE NORMAL OPERATION
OF THE FACILITY, COORDINATION SHALL BE TAKEN TO COMPLETE THIS WORK
DURING "OFF HOURS". COORDINATE ANY ELECTRICAL SERVICE INTERRUPTIONS
WITH THE GOVERNMENT AND THE APPROPRIATE FACILITIES PERSONNEL 14 DAYS
PRIOR TO COMMENCING WORK AND PROVIDE PROVISIONS FOR TEMPORARY
POWER AS REQUIRED UNTIL THE WORK IS COMPLETE. REFER TO SPECIFICATION
SECTION "01 14 00 WORK RESTRICTIONS" FOR FURTHER DETAILS AND
REQUIREMENTS FOR SUBMITTING A WRITTEN REQUEST FOR SERVICE
INTERRUPTIONS.
7. ANY TASK THAT WILL CREATE EXCESSIVE NOISE PRODUCING ACTIVITY (ie. SAW
CUTTING, CORE DRILLING, HAMMER VIBRATION DRILLING, ETC. SHALL BE
COMPLETED DURING "OFF HOURS" COORDINATE WITH THE GOVERNMENT AND
THE APPROPRIATE FACILITIES PERSONNEL 14 DAYS PRIOR TO COMMENCING
WORK.
8. WHERE EXISTING DEVICE OR JUNCTION BOXES MUST REMAIN IN EXISTING WALLS
OR CEILINGS (SUCH AS FOR CIRCUITS THAT MUST BE MAINTAINED TO SERVE
OTHER AREAS), THEN THEY SHALL BE FITTED WITH BLANK COVERPLATES.
9. WHERE DISTRIBUTION OR BRANCH CIRCUIT EQUIPMENT (PANELBOARDS,
SWITCHBOARDS, ETC.) IS TO BE REMOVED, THEN ALL FEEDERS OR BRANCH
CIRCUITS WHICH SERVE ITEMS TO REMAIN SHALL BE RECONNECTED TO NEW
DISTRIBUTION OR BRANCH CIRCUIT EQUIPMENT AS INDICATED. REFER ALL
QUESTIONS TO OWNER/ARCHITECT FOR ANY CLARIFICATION.
10. COORDINATE WITH ELECTRICAL DEMOLITION PLANS AND VERIFY CIRCUITS TO BE
REMOVED WITH EXISTING FIELD CONDITIONS. ALL PANEL DIRECTORIES AFFECTED
BY THIS ALTERATION WORK SHALL BE MODIFIED TO REFLECT THE FINAL 'AS BUILT'
CONDITIONS WITH ROOM NUMBERS, ROOM NAME OR LOCATION OF WHERE EACH
CIRCUIT IS LOCATED. PROVIDE NEW PRINTED PANELBOARD DIRECTORIES FOR
ALL NEW AND MODIFIED PANELBOARDS.
11. IF HAZARDOUS MATERIALS (I.E. ASBESTOS, PCBs, ETC.) ARE ENCOUNTERED AT
ANY TIME DURING CONSTRUCTION IN THE WORK AREA, STOP WORK IMMEDIATELY
AND CONTACT THE GOVERNMENT.
12. DE-ENERGIZE EXISTING ELECTRICAL EQUIPMENT PRIOR TO PERFORMING ANY
DEMOLITION WORK.
ELECTRICAL DEMOLITION GENERAL NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
IJJTE
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
ELECTRICAL GENERAL NOTES AND
SYMBOLS
EJ-001
-3
E J
/3
/2
.p d f
SHEET INDEX
SHEET
NUMBER SHEET NAME
ELECTRICAL
EJ001 ELECTRICAL GENERAL NOTES AND SYMBOLS
EC101 ELECTRICAL SITE PLAN
ED100 ELECTRICAL DEMOLITION PLAN - BASEMENT
ED101 ELECTRICAL DEMOLITION PLAN - FIRST FLOOR
ED102 ELECTRICAL DEMOLITION PLAN - SECOND FLOOR
ED103 ELECTRICAL DEMOLITION PLAN - THIRD FLOOR
ED104 ELECTRICAL DEMOLITION PLAN - ATTIC
EL100 ELECTRICAL LIGHTING PLAN - BASEMENT
EL101 ELECTRICAL LIGHTING PLAN - FIRST FLOOR
EL102 ELECTRICAL LIGHTING PLAN - SECOND FLOOR
EL103 ELECTRICAL LIGHTING PLAN - THIRD FLOOR
EL104 ELECTRICAL LIGHTING PLAN - ATTIC
EP100 ELECTRICAL POWER PLAN - BASEMENT
EP101 ELECTRICAL POWER PLAN - FIRST FLOOR
EP102 ELECTRICAL POWER PLAN - SECOND FLOOR
EP103 ELECTRICAL POWER PLAN - THIRD FLOOR
EP104 ELECTRICAL POWER PLAN - ATTIC
ES101 ELECTRICAL SYSTEMS PLAN - FIRST FLOOR
ES102 ELECTRICAL SYSTEMS PLAN - SECOND FLOOR
ES103 ELECTRICAL SYSTEMS PLAN - THIRD FLOOR
EE500 EXISTING ELECTRICAL ONE-LINE DIAGRAM
EE501 NEW ELECTRICAL ONE-LINE DIAGRAM
EE600 ELECTRICAL SCHEDULES
EE700 ELECTRICAL DETAILS
EE800 ELECTRICAL PANEL SCHEDULES
EE801 ELECTRICAL PANEL SCHEDULES
EE802 ELECTRICAL PANEL SCHEDULES
EE803 ELECTRICAL PANEL SCHEDULES
EE804 ELECTRICAL PANEL SCHEDULES
EE805 ELECTRICAL PANEL SCHEDULES
EE106 ELECTRICAL BID EXCLUSIONS PLAN
EL103B ELECTRICAL LIGHTING PLAN - THIRD FLOOR - BD1
EP103B ELECTRICAL POWER PLAN - THIRD FLOOR - BD1
ES103B ELECTRICAL SYSTEMS PLAN - THIRD FLOOR - BD1
\1l lil at oc
DOI'IGIASW.
NEE.$EilI
E-4312t-6 tt t¡t trt tt I
,ro
\\12/30/2022 A R C H I T E C T S E N G I N E E R S
CB DESIGN
GROUP
204 237200 of 233200 of 233
JT
J T
DN
R
E
E
E
EXISTING
UTILITY
XFMR
EXISTING UTILITY
XFMR
EC01
EXISTING U/G FEEDER
EXISTING UTILITY
XFMR
EXISTING UTILITY
XFMR
1. ALL EXISTING EXTERIOR POST AND WALL-MOUNTED LIGHTING SHALL REMAIN
EXISTING AS-IS. RECONNECT EXISTING CIRCUITRY INTO NEW LIGHTING POWER
PANEL 'LPH-1'.
ELECTRICAL SITE GENERAL NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
IJJTE
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
ELECTRICAL SITE PLAN
EC-101
-3
E C
/1
/2
.p d f
SCALE: 1" = 20'-0"
ELECTRICAL SITE PLAN
KEYNOTE LEGEND
KEY DESCRIPTION
EC01 EXISTING ELECTRICAL UTILITY EQUIPMENT AND UNDERGROUND FEEDERS ARE TO
REMAIN AS INSTALLED. E.C. SHALL FIELD VERIFY SIZE AND LOCATION OF EXISTING
EQUIPMENT, AS WELL AS ANY FUTURE OBSTRUCTION WITH THE NEW ADDITION.
CLEARANCE BETWEEN UTILITY TRANSFORMERS AND ANY BUILDING WINDOWS AND
DOORS SHALL BE MAINTAINED AT 10' 0" AT ALL TIMES.
\1l lil at oc
DOI'IGIASW.
NEE.$EilI
E-4312t-6 tt t¡t trt tt I
,ro
\\12/30/2022 205 237
A R C H I T E C T S E N G I N E E R S
201 of 2332/15/2023 201 of 233
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
ED01
MCC-B-1
NP-1-B
C
D
E
F
H
E.8
C.3
G
ED11ED11ED11
ED11
1. IT IS THE INTENT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE SCOPE
OF DEMOLITION WORK AND THAT NOT ALL ITEMS OF ELECTRICAL DEMOLITION
ARE NECESSARILY SHOWN. ALL DEVICES AND EQUIPMENT SHOWN BOLD SHALL BE
REMOVED IN ITS ENTIRETY. ALL DEVICES AND EQUIPMENT SHOWN HALF-TONED IS
EXISTING TO REMAIN.
2. E.C. SHALL DURING PRE-BID SITE VISIT DETERMINE EXTENT OF DEMOLITION
SCOPE AND INCLUDE COST OF THIS WORK IN THEIR BID. DEMOLISH LIGHTING AND
POWER IN ALL ROOMS UNLESS OTHERWISE NOTED.
3. EXISTING EQUIPMENT THAT IS TO REMAIN BUT BECOME EXPOSED DUE TO NEW
WORK SHALL BE RELOCATED AND RECONNECTED.
4. ALL EQUIPMENT REMOVED DURING CONSTRUCTION THAT IS NOT DESIRED BY
OWNER SHALL BECOME A PROPERTY OF E.C. AND SHALL BE PROMPTLY REMOVED
FROM SITE.
5. E.C. SHALL SURVEY AND VERIFY LOCATIONS AND PHYSICAL SIZES OF ALL
EXISTING ITEMS THAT ARE TO REMAIN AND DETERMINE WHETHER RELOCATION
OR REROUTING WILL BE REQUIRED.
6. ELECTRICAL CIRCUITS THAT ARE TO BE REMOVED SHALL BE REMOVED IN THEIR
ENTIRETY. CONDUCTORS SHALL BE REMOVED FROM THE ITEM TO BE
DEMOLISHED TO THE SOURCE OVERCURRENT DEVICE. ALL OVERHEAD AND
EXPOSED RACEWAYS SHALL BE REMOVED.
7. ALL LOW VOLTAGE DATA CABLING IS TO REMAIN AND BE PROTECTED
THROUGHOUT DURATION OF CONSTRUCTION. BUNDLE CABLING FOR EXTENSION
AND RECONNECTION DURING THIS PROJECT.
ELECTRICAL DEMOLITION NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
IJJTE
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
ELECTRICAL DEMOLITION PLAN -
BASEMENT
ED-100
-3
E D
/3
/2
.p d f
SCALE: 1/8" = 1'-0"
ELECTRICAL POWER DEMOLITION PLAN - BASEMENT
KEYNOTE LEGEND
KEY DESCRIPTION
ED01 FRAMEWORK OF EXISTING MOTOR CONTROL CENTERS "MCC-B-1" AND "MCC-B-2" TO
REMAIN. EXISTING CIRCUIT BREAKERS, FEEDERS, RACEWAYS, MOTORS AND SAFETY
SWITCHES ARE TO BE REMOVED AND REPLACED. E.C. SHALL COORDINATE WITH
MECHANICAL, PLUMBING AND FIRE PROTECTION DRAWINGS THE SCOPE INTENT IN
THE RELATED SPACE. EXISTING PANEL "NP-1-B" TO BE REMOVED AND FEEDER TO BE
PULLED BACK TO POINT OF ORIGIN.
ED11 DISCONNECT AND REMOVE ALL EXISTING LIGHTING FIXTURES AND DISPOSE OF
PROPERLY. VERIFY WITH VA WHETHER SALVAGE OF ANY COMPONENTS IS
REQUIRED PRIOR TO REMOVAL.
\1l lil at oc
DOI'IGIASW.
NEE.$EilI
E-4312t-6 tt t¡t trt tt I
,ro
\\12/30/2022 206 237
A R C H I T E C T S E N G I N E E R S
202 of 233202 of 233
B
ATS-LS
T-480-EQ
NP-EQ-1 MD-480-EQ
MD-480
MD-208ED03
NP-1-1
NP-2-1
ED04
ED05
C
D
E
F
H
E.8
C.3
G
ED14
MD-208-LS
ATS-208-EQECB-208-LS
ECB-208-CR ECB-208-EQ
ECB-208-CLC
ATS-208-CR
MD-208-CR
ED15ED15
ED16 ED16
ED16ED16
ED16
1. IT IS THE INTENT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE SCOPE
OF DEMOLITION WORK AND THAT NOT ALL ITEMS OF ELECTRICAL DEMOLITION
ARE NECESSARILY SHOWN. ALL DEVICES AND EQUIPMENT SHOWN BOLD SHALL BE
REMOVED IN ITS ENTIRETY. ALL DEVICES AND EQUIPMENT SHOWN HALF-TONED IS
EXISTING TO REMAIN.
2. E.C. SHALL DURING PRE-BID SITE VISIT DETERMINE EXTENT OF DEMOLITION
SCOPE AND INCLUDE COST OF THIS WORK IN THEIR BID. DEMOLISH LIGHTING AND
POWER IN ALL ROOMS UNLESS OTHERWISE NOTED.
3. EXISTING EQUIPMENT THAT IS TO REMAIN BUT BECOME EXPOSED DUE TO NEW
WORK SHALL BE RELOCATED AND RECONNECTED.
4. ALL EQUIPMENT REMOVED DURING CONSTRUCTION THAT IS NOT DESIRED BY
OWNER SHALL BECOME A PROPERTY OF E.C. AND SHALL BE PROMPTLY REMOVED
FROM SITE.
5. E.C. SHALL SURVEY AND VERIFY LOCATIONS AND PHYSICAL SIZES OF ALL
EXISTING ITEMS THAT ARE TO REMAIN AND DETERMINE WHETHER RELOCATION
OR REROUTING WILL BE REQUIRED.
6. ELECTRICAL CIRCUITS THAT ARE TO BE REMOVED SHALL BE REMOVED IN THEIR
ENTIRETY. CONDUCTORS SHALL BE REMOVED FROM THE ITEM TO BE
DEMOLISHED TO THE SOURCE OVERCURRENT DEVICE. ALL OVERHEAD AND
EXPOSED RACEWAYS SHALL BE REMOVED.
7. ALL LOW VOLTAGE DATA CABLING IS TO REMAIN AND BE PROTECTED
THROUGHOUT DURATION OF CONSTRUCTION. BUNDLE CABLING FOR EXTENSION
AND RECONNECTION DURING THIS PROJECT.
ELECTRICAL DEMOLITION NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
IJJTE
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
ELECTRICAL DEMOLITION PLAN -
FIRST FLOOR
ED-101
-3
E D
/3
/2
.p d f
SCALE: 1/8" = 1'-0"
ELECTRICAL POWER DEMOLITION PLAN - FIRST FLOOR
KEYNOTE LEGEND
KEY DESCRIPTION
ED03 EXISTING DISTRIBUTION BOARDS "MD-480" AND "MD-208" ARE TO REMAIN AS
INSTALLED. E.C. SHALL REMOVE EXISTING PANEL "NP-EQ-1" AND PULL EXISTING
FEEDER BACK TO ORIGIN.
ED04 E.C. SHALL REMOVE EXISTING PANEL "NP-1-1" AND PULL EXISTING FEEDER BACK TO
ORIGIN.
ED05 E.C. SHALL REMOVE EXISTING PANEL "NP-2-1" AND PULL EXISTING FEEDER BACK TO
ORIGIN.
ED14 E.C. SHALL REMOVE EXISTING PANEL "NP-EQ-1" AND PULL EXISTING FEEDER BACK
TO ORIGIN.
ED15 RELOCATE ATS-208-CR AND MD-208-CR TO NEW WALL APPROXIMATELY 1'-6" NORTH
OF EXISTING WALL TO BE DEMOLISHED. EXTEND FEEDERS AS REQUIRED.
ED16 EXISTING POWER AND DATA TO REMAIN.
\1l lil at oc
DOI'IGIASW.
NEE.$EilI
E-4312t-6 tt t¡t trt tt I
,ro
\\12/30/2022 207 237
A R C H I T E C T S E N G I N E E R S
203 of 233203 of 233
B
ED06 ED07
CP-2-2
LS-2-2
NP-2-2
NP-1-2
LS-1-2
CP-1-2
C
D
E
F
H
E.8
C.3
G
1. IT IS THE INTENT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE SCOPE
OF DEMOLITION WORK AND THAT NOT ALL ITEMS OF ELECTRICAL DEMOLITION
ARE NECESSARILY SHOWN. ALL DEVICES AND EQUIPMENT SHOWN BOLD SHALL BE
REMOVED IN ITS ENTIRETY. ALL DEVICES AND EQUIPMENT SHOWN HALF-TONED IS
EXISTING TO REMAIN.
2. E.C. SHALL DURING PRE-BID SITE VISIT DETERMINE EXTENT OF DEMOLITION
SCOPE AND INCLUDE COST OF THIS WORK IN THEIR BID. DEMOLISH LIGHTING AND
POWER IN ALL ROOMS UNLESS OTHERWISE NOTED.
3. EXISTING EQUIPMENT THAT IS TO REMAIN BUT BECOME EXPOSED DUE TO NEW
WORK SHALL BE RELOCATED AND RECONNECTED.
4. ALL EQUIPMENT REMOVED DURING CONSTRUCTION THAT IS NOT DESIRED BY
OWNER SHALL BECOME A PROPERTY OF E.C. AND SHALL BE PROMPTLY REMOVED
FROM SITE.
5. E.C. SHALL SURVEY AND VERIFY LOCATIONS AND PHYSICAL SIZES OF ALL
EXISTING ITEMS THAT ARE TO REMAIN AND DETERMINE WHETHER RELOCATION
OR REROUTING WILL BE REQUIRED.
6. ELECTRICAL CIRCUITS THAT ARE TO BE REMOVED SHALL BE REMOVED IN THEIR
ENTIRETY. CONDUCTORS SHALL BE REMOVED FROM THE ITEM TO BE
DEMOLISHED TO THE SOURCE OVERCURRENT DEVICE. ALL OVERHEAD AND
EXPOSED RACEWAYS SHALL BE REMOVED.
7. ALL LOW VOLTAGE DATA CABLING IS TO REMAIN AND BE PROTECTED
THROUGHOUT DURATION OF CONSTRUCTION. BUNDLE CABLING FOR EXTENSION
AND RECONNECTION DURING THIS PROJECT.
ELECTRICAL DEMOLITION NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
IJJTE
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
ELECTRICAL DEMOLITION PLAN -
SECOND FLOOR
ED-102
-3
E D
/3
/2
.p d f
SCALE: 1/8" = 1'-0"
ELECTRICAL POWER DEMOLITION PLAN - SECOND FLOOR
KEYNOTE LEGEND
KEY DESCRIPTION
ED06 E.C. SHALL REMOVE EXISTING PANELS "NP-1-2" , "CP-1-2" AND "LS-1-2" AND PULL
EXISTING FEEDERS BACK TO ORIGIN.
ED07 E.C. SHALL REMOVE EXISTING PANELS "NP-2-2" , "CP-2-2" AND "LS-2-2" AND PULL
EXISTING FEEDERS BACK TO ORIGIN.
\1l lil at oc
DOI'IGIASW.
NEE.$EilI
E-4312t-6 tt t¡t trt tt I
,ro
\\12/30/2022 208 237
A R C H I T E C T S E N G I N E E R S
204 of 233204 of 233
B
ED09
NP-2-3NP-1-3
ED08
C
D
E
F
H
E.8
C.3
G
1. IT IS THE INTENT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE SCOPE
OF DEMOLITION WORK AND THAT NOT ALL ITEMS OF ELECTRICAL DEMOLITION
ARE NECESSARILY SHOWN. ALL DEVICES AND EQUIPMENT SHOWN BOLD SHALL BE
REMOVED IN ITS ENTIRETY. ALL DEVICES AND EQUIPMENT SHOWN HALF-TONED IS
EXISTING TO REMAIN.
2. E.C. SHALL DURING PRE-BID SITE VISIT DETERMINE EXTENT OF DEMOLITION
SCOPE AND INCLUDE COST OF THIS WORK IN THEIR BID. DEMOLISH LIGHTING AND
POWER IN ALL ROOMS UNLESS OTHERWISE NOTED.
3. EXISTING EQUIPMENT THAT IS TO REMAIN BUT BECOME EXPOSED DUE TO NEW
WORK SHALL BE RELOCATED AND RECONNECTED.
4. ALL EQUIPMENT REMOVED DURING CONSTRUCTION THAT IS NOT DESIRED BY
OWNER SHALL BECOME A PROPERTY OF E.C. AND SHALL BE PROMPTLY REMOVED
FROM SITE.
5. E.C. SHALL SURVEY AND VERIFY LOCATIONS AND PHYSICAL SIZES OF ALL
EXISTING ITEMS THAT ARE TO REMAIN AND DETERMINE WHETHER RELOCATION
OR REROUTING WILL BE REQUIRED.
6. ELECTRICAL CIRCUITS THAT ARE TO BE REMOVED SHALL BE REMOVED IN THEIR
ENTIRETY. CONDUCTORS SHALL BE REMOVED FROM THE ITEM TO BE
DEMOLISHED TO THE SOURCE OVERCURRENT DEVICE. ALL OVERHEAD AND
EXPOSED RACEWAYS SHALL BE REMOVED.
7. ALL LOW VOLTAGE DATA CABLING IS TO REMAIN AND BE PROTECTED
THROUGHOUT DURATION OF CONSTRUCTION. BUNDLE CABLING FOR EXTENSION
AND RECONNECTION DURING THIS PROJECT.
ELECTRICAL DEMOLITION NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
IJJTE
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
ELECTRICAL DEMOLITION PLAN -
THIRD FLOOR
ED-103
-3
E D
/3
/2
.p d f
SCALE: 1/8" = 1'-0"
ELECTRICAL POWER DEMOLITION PLAN - THIRD FLOOR
KEYNOTE LEGEND
KEY DESCRIPTION
ED08 E.C. SHALL REMOVE EXISTING PANEL "NP-1-3" AND PULL EXISTING FEEDER BACK TO
ORIGIN.
ED09 E.C. SHALL REMOVE EXISTING PANEL "NP-2-3" AND PULL EXISTING FEEDER BACK TO
ORIGIN.
\1l lil at oc
DOI'IGIASW.
NEE.$EilI
E-4312t-6 tt t¡t trt tt I
,ro
\\12/30/2022 209 237
A R C H I T E C T S E N G I N E E R S
205 of 233205 of 233
B
MCC-P1
MCC-P2C
D
E
F
H
E.8
C.3
G
ED12
1. IT IS THE INTENT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE SCOPE
OF DEMOLITION WORK AND THAT NOT ALL ITEMS OF ELECTRICAL DEMOLITION
ARE NECESSARILY SHOWN. ALL DEVICES AND EQUIPMENT SHOWN BOLD SHALL BE
REMOVED IN ITS ENTIRETY. ALL DEVICES AND EQUIPMENT SHOWN HALF-TONED IS
EXISTING TO REMAIN.
2. E.C. SHALL DURING PRE-BID SITE VISIT DETERMINE EXTENT OF DEMOLITION
SCOPE AND INCLUDE COST OF THIS WORK IN THEIR BID. DEMOLISH LIGHTING AND
POWER IN ALL ROOMS UNLESS OTHERWISE NOTED.
3. EXISTING EQUIPMENT THAT IS TO REMAIN BUT BECOME EXPOSED DUE TO NEW
WORK SHALL BE RELOCATED AND RECONNECTED.
4. ALL EQUIPMENT REMOVED DURING CONSTRUCTION THAT IS NOT DESIRED BY
OWNER SHALL BECOME A PROPERTY OF E.C. AND SHALL BE PROMPTLY REMOVED
FROM SITE.
5. E.C. SHALL SURVEY AND VERIFY LOCATIONS AND PHYSICAL SIZES OF ALL
EXISTING ITEMS THAT ARE TO REMAIN AND DETERMINE WHETHER RELOCATION
OR REROUTING WILL BE REQUIRED.
6. ELECTRICAL CIRCUITS THAT ARE TO BE REMOVED SHALL BE REMOVED IN THEIR
ENTIRETY. CONDUCTORS SHALL BE REMOVED FROM THE ITEM TO BE
DEMOLISHED TO THE SOURCE OVERCURRENT DEVICE. ALL OVERHEAD AND
EXPOSED RACEWAYS SHALL BE REMOVED.
7. ALL LOW VOLTAGE DATA CABLING IS TO REMAIN AND BE PROTECTED
THROUGHOUT DURATION OF CONSTRUCTION. BUNDLE CABLING FOR EXTENSION
AND RECONNECTION DURING THIS PROJECT.
ELECTRICAL DEMOLITION NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
IJJTE
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
ELECTRICAL DEMOLITION PLAN -
ATTIC
ED-104
-3
E D
/3
/2
.p d f
SCALE: 1/8" = 1'-0"
ELECTRICAL POWER DEMOLITION PLAN - ATTIC
KEYNOTE LEGEND
KEY DESCRIPTION
ED12 ALL EXISTING AIR HANDLING UNITS TO REMAIN.
\1l lil at oc
DOI'IGIASW.
NEE.$EilI
E-4312t-6 tt t¡t trt tt I
,ro
\\12/30/2022 210 237
A R C H I T E C T S E N G I N E E R S
206 of 233206 of 233
T
AT
AT
1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
XA
C
D
E
F
H
E.8
C.3
G
H
MECHANICAL
ROOM
B0405
ELEVATOR PIT
B0403
EAST STAIR
BS1
EL02
H
H
LS-L-1
LS-L-1
LS-L-1
P
62" 62"
62"
D1
D1
D1
D1
EL04
EL04
D1
OC
P
LS-L-1
62"
H
D
OC
D1
1. PROVIDE FIRE SEALS FOR INSERTS, CONDUIT PENETRATIONS, SLEEVES AND
ROUTINGS THROUGH RATED WALLS, CEILINGS AND FLOOR AS PER
SPECIFICATIONS.
2. PROVIDE SEPARATE CONDUITS FOR EMERGENCY LIGHTING.
3. OCCUPANCY SENSORS SHALL BE INSTALLED PER MANUFACTURERS
SPECIFICATIONS AND RECOMMENDATIONS. QUANTITIES AND LAYOUT SHALL BE
ADJUSTED PER MANUFACTURER'S RECOMMENDATIONS. E.C. SHALL INCLUDE IN
THEIR PRICE ALL NECESSARY DEVICES AND ACCESSORIES FOR A FULLY
FUNCTIONAL LIGHTING CONTROL SYSTEM, INCLUDING BUT NOT LIMITED TO
POWER PACKS, ROOM CONTROLLERS AND CABLING REQUIREMENTS.
4. PROVIDE OCCUPANCY SENSOR TYPES AND QUANTITIES AS REQUIRED TO
ACHIEVE 99% COVERAGE IN SPACE.
5. ALL LIGHT FIXTURES DESIGNATED AS EMERGENCY SHALL BE PROVIDED WITH A
UL 924 LISTED DEVICE FOR MONITORING AND SWITCHING BETWEEN NORMAL AND
EMERGENCY POWER SOURCES.
6. ALL LIGHTING FIXTURES DESIGNATED AS EMERGENCY AND ALL EXIT SIGNS SHALL
BE CIRCUITED TO LIFE SAFETY PANEL "LS-L-1".
7. EXTERIOR LIGHTING SHALL BE ROUTED THROUGH LIGHTING CONTACTOR.
PROVIDE UNSWITCHED HOT FOR FIXTURE BATTERY BACK-UP.
8. E.C. SHALL FURNISH AND INSTALL A PHOTO CELL AND CONNECT TO LIGHTING
CONTACTOR PANEL IN SECOND FLOOR BUILDING ELECTRICAL ROOM 20408.
9. ALL LIGHTING BRANCH CIRCUITS SHALL BE #10 AWG UNLESS OTHERWISE NOTED.
ELECTRICAL GENERAL NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
IJJTE
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
ELECTRICAL LIGHTING PLAN -
BASEMENT
EL-100
-3
E L
/3
/2
.p d f
SCALE: 1/8" = 1'-0"
ELECTRICAL LIGHTING PLAN - BASEMENT
KEYNOTE LEGEND
KEY DESCRIPTION
EL02 LIGHT FIXTURES TO BE CIRCUITED TO PANEL "NP-LLP-1". ALL LIGHT FIXTURES
DESIGNATED AS EMERGENCY SHALL BE CIRCUITED TO PNL "LS-L-1".
EL04 PROVIDE THREE-WAY SWITCH FOR CRAWL SPACE NEW LIGHTING. LOCATE NEW
LIGHTING IN EXISTING LIGHT LOCATIONS AND PROVIDE EVEN SPACED AND
ILLUMINATED CRAWL-WAY FROM STAIRS TO ACCESS DOOR IN BASEMENT.
\1l lil at oc
DOI'IGIASW.
NEE.$EilI
E-4312t-6 tt t¡t trt tt I
,ro
\\12/30/2022 211 237
A R C H I T E C T S E N G I N E E R S
207 of 233207 of 233
T
N
N
N
AT
AT
AT
AT
AT
AT
AT
AT AT AT
AT
AT
AT AT
AT
AT
AT
AT
AT
AT
ATAT
AT
AT
AT
ATAT
AT
AT
AT
AT
AT
AT
ATAT
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
MAIN
ELECTRICAL
10411
GROUP ROOM A
10435
RRTP VITALS &
LOCKERS
10416
BED BUG ZAPPER
10414
RRTP WAITING
10417
RRTP
COUNSELOR
10405
TESTING OFFICE
10401
GROUP TESTING
10400
RRTP
COUNSELOR
10404
ADMIN OFFICE
10420 VENDING
10422
WAITING
10424
MAIN CORRIDOR
1C05
INFO DESK
10442
FAMILY TOILET
10444
MOTHERS ROOM
10446
NURSE STATION
10452
SPECIMEN
TOILET
10454
TREATMENT
CIRCULATION
10450
TREATMENT
OBSERVATION
10453
TREATMENT
OBSERVATION
10451
BUILDING DATA
10449
GENDER
NEUTRAL TOILET
10447
GENDER
NEUTRAL TOILET
10445
GROUP ROOM C
10430
RECEPTION
10460
FAMILY WAITING
10465
MH CLINIC
OFFICE
10477
MH CLINIC
OFFICE
10479
MH CLINIC
OFFICE
10480
MH CLINIC
OFFICE (FUTURE
EXAM)
10478
STAFF TOILET
10476
MH CLINIC
OFFICE
10485
MH CLINIC
OFFICE
10487
MH CLINIC
TELEMED OFFICE
10489
MH CLINIC
TELEMED OFFICE
10488
MH CLINIC
TELEMED OFFICE
10486
MH CLINIC
TELEMED OFFICE
10484
MH CLINIC
MED/SUPPLY
10474
MH CLINIC
OFFICE
10472
MH CLINIC
OFFICE
10470
MH CLINIC
OFFICE
10471
MH CLINIC
OFFICE
10473
MH CLINIC
EXAM/VITALS
10475
WEST STAIR
1S2
LOUNGE
10425
ELEVATOR
LOBBY
1C06
EAST STAIR
1S1
GROUP ROOM B
10438
A
A
A
A
A
A
A
A
B2
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
B1
B1
B1
B1
A
A
A
A
A
A
A
A
A
A
A
A
A
B1
B1
B1
B1
B1
B1
B1
B1
B1 7
B1
B1
B1
A 5
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
B1
B1
B1
A
B
B
B
B
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
B2
A
A
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
D1
D1
D1
D1
D1
G
G
G
G
XA
XA
XA
XA
XA
XA
D1
D1
A
B1
B2
B2
B2
XA
XA
C
D
E
F
H
E.8
C.3
G
O/D
O/DD
O/D
O /D
O
D
O /D
O
O/D
D D
D
O O
/D
O
O
O
O /D
O /D
O /D
O /D
O
O/D
O/D O/D O/D
O/DO/D
O /D
O /D
O /D
O /D
O /D
D
D
O /D
OC
OC
OC
OC
OC
OC
OC
OC
OC OC
OCOC
OC OC
OC
OC
OC
OC
OCOC
OC
OC
OC
OC
F
F
F
F
F
AT ATAT
EL01
RECEIVING
10499
TRAM WALKWAY
1C20
VESTIBULE
10440
CORRIDOR
1C11
HALL
1C10
CORRIDOR
1C12
CORRIDOR
1C08STORAGE
10430A
STORAGE
10438A
CORRIDOR
1C04
CORRIDOR
1C02
G
D D
EL01
D1
D1
B1
B1
F
OC
EMR
10412
D1
WORKROOM
10466
HAC
10464
WAITING
10443
RRTP TOILET
10418
RRTP SECURITY
OFFICE
10419
STORAGE
10415
ELECTRICAL
10415A
RRTP OFFICES
10426
MAIN CORRIDOR
1C05
RRTP FOYER
10427
B
A
EL01
A
MAIN
ELECTRICAL
10411
OC
O/D
O/D
EL03
A
P
C
OC
OC
OC
OC
STORAGE
10476A
EL05
B1
B1
B1
D1
O
O
O
D1O
EL03
EL03
B1
B1 y yy17 C2
C2
C2 xx x
O /D y
OCOC
O
O
B
OC
D
NP-LLP-1EL06
XA
XA
a a aa bbb b b c c b d b b e f b b e e e f f e hh h hh hh hh h i i i i i i i i h hh h e e e e k ee m
OC
m mm mm mm mm m e e e e h h h h hh p p p h eee ss sss s s e t t t t t t t t t t t t t t t t t
EL09
D
D
D
D
DO
O
D1
G
XA
C i7 C i
D1
O z Dz
C
C h h
1. PROVIDE FIRE SEALS FOR INSERTS, CONDUIT PENETRATIONS, SLEEVES AND
ROUTINGS THROUGH RATED WALLS, CEILINGS AND FLOOR AS PER
SPECIFICATIONS.
2. PROVIDE SEPARATE CONDUITS FOR EMERGENCY LIGHTING.
3. OCCUPANCY SENSORS SHALL BE INSTALLED PER MANUFACTURERS
SPECIFICATIONS AND RECOMMENDATIONS. QUANTITIES AND LAYOUT SHALL BE
ADJUSTED PER MANUFACTURER'S RECOMMENDATIONS. E.C. SHALL INCLUDE IN
THEIR PRICE ALL NECESSARY DEVICES AND ACCESSORIES FOR A FULLY
FUNCTIONAL LIGHTING CONTROL SYSTEM, INCLUDING BUT NOT LIMITED TO
POWER PACKS, ROOM CONTROLLERS AND CABLING REQUIREMENTS.
4. PROVIDE OCCUPANCY SENSOR TYPES AND QUANTITIES AS REQUIRED TO
ACHIEVE 99% COVERAGE IN SPACE.
5. ALL LIGHT FIXTURES DESIGNATED AS EMERGENCY SHALL BE PROVIDED WITH A
UL 924 LISTED DEVICE FOR MONITORING AND SWITCHING BETWEEN NORMAL AND
EMERGENCY POWER SOURCES.
6. ALL LIGHTING FIXTURES DESIGNATED AS EMERGENCY AND ALL EXIT SIGNS SHALL
BE CIRCUITED TO LIFE SAFETY PANEL "LS-L-1".
7. EXTERIOR LIGHTING SHALL BE ROUTED THROUGH LIGHTING CONTACTOR.
PROVIDE UNSWITCHED HOT FOR FIXTURE BATTERY BACK-UP.
8. E.C. SHALL FURNISH AND INSTALL A PHOTO CELL AND CONNECT TO LIGHTING
CONTACTOR PANEL IN SECOND FLOOR BUILDING ELECTRICAL ROOM 20408.
9. ALL LIGHTING BRANCH CIRCUITS SHALL BE #10 AWG UNLESS OTHERWISE NOTED.
ELECTRICAL GENERAL NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
IJJTE
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
ELECTRICAL LIGHTING PLAN - FIRST
FLOOR
EL-101
-3
E L
/3
/2
.p d f
SCALE: 1/8" = 1'-0"
ELECTRICAL LIGHTING PLAN - LEVEL 1
KEYNOTE LEGEND
KEY DESCRIPTION
EL01 E.C. SHALL FURNISH AND INSTALL 5-SCENE PRE-SET LIGHTING SCENE CONTROLLER
WITH SETTINGS AT 10%, 25%, 50%, 75%, AND 100% LUMEN OUTPUT. SCENE
CONTROLLERS ON FIRST FLOOR SHALL HAVE OVERRIDE BUTTON TO CONTROL
GROUP ROOM A AND GROUP ROOM B LIGHTS SEPARATELY WHEN PARTITION IS
OPEN.
EL03 WALL MOUNT 4' LINEAR FIXTURE ABOVE DOOR CENTERED IN STORAGE ROOM.
EL05 IDENTIFY CIRCUITS SERVING EXISTING LIGHTING FIXTURES AND CONNECT TO
APPROPRIATE NEW NORMAL AND/OR EMERGENCY LIGHTING CIRCUITS IN ADJACENT
SPACES.
EL06 ALL NON-EMERGENCY LIGHTING CIRCUITS ON FIRST FLOOR SHALL BE FED BY PANEL
NP-LLP-1.
EL09 E.C. SHALL FURNISH AND INSTALL LEGRAND WATTSTOPPER PARTITION SENSOR OR
EQUAL AND CONNECT SCENE CONTROLLERS IN GROUP ROOM A AND GROUP ROOM
B. WHEN OPEN PARTITION IS DETECTED, ALL LIGHTS SHALL BE SET TO THE LESSER
LUMEN OUTPUT CURRENTLY SELECTED BETWEEN BOTH ROOMS, BUT NO LESS THAN
50%. BOTH SCENE CONTROLLERS SHALL SIMULTANEOUSLY CONTROL ALL LIGHT
FIXTURES IN BOTH ROOMS UNTIL PARTITION IS CLOSED OR OVERRIDE IS SELECTED.
\1l lil at oc
DOI'IGIASW.
NEE.$EilI
E-4312t-6 tt t¡t trt tt I
,ro
\\12/30/2022 212 237
A R C H I T E C T S E N G I N E E R S
208 of 233208 of 233
T
Range
AT AT
AT
AT
AT
AT
ATAT
AT
AT
AT
AT ATATAT
AT
AT
AT
AT
AT
AT
AT AT ATAT
AT
AT
AT
AT
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
GROUP ROOM C
20428
GROUP ROOM A
20431
STAFF BREAK
20449
BUILDING DATA
20447
GENDER
NEUTRAL TOILET
20445
GENDER
NEUTRAL TOILET
20443
RRTP
COUNSELOR
20410
RRTP
COUNSELOR
20411
RRTP
COUNSELOR
20409
BUILDING
ELECTRICAL
20408
RRTP
COUNSELOR
20419
RRTP
COUNSELOR
20407
RRTP
COUNSELOR
20417
RRTP
COUNSELOR
20415
RRTP
COUNSELOR
20416
RRTP
COUNSELOR
20418
STAFF TOILET
20405
RRTP
COUNSELOR
20420
RRTP
COUNSELOR
20403
CORRIDOR
2C02
RRTP
COUNSELOR
20404
RRTP
COUNSELOR
20406
RRTP
COUNSELOR
20402
RRTP
COUNSELOR
20401
RECP.
WORKROOM
20424
RECEPTION
20426
WAITING
20440
RRTP TEACHING
KITCHEN
20454
MH CLINIC
OFFICE
20458
MH CLINIC
OFFICE
20463
MH CLINIC
OFFICE
20461
MH CLINIC
OFFICE
20462
MH CLINIC
OFFICE
20460
MH CLINIC
OFFICE
20464
MH CLINIC
OFFICE
20474
MH CLINIC
OFFICE
20476
MH CLINIC
OFFICE
20478
MH CLINIC
OFFICE
20479
MH CLINIC
OFFICE
20477
MH CLINIC
OFFICE
20475
STAFF TOILET
20466
MH CLINIC
OFFICE
20468
MH CLINIC
OFFICE
20470
CORRIDOR
2C10
MH CLINIC
OFFICE
20469
MH CLINIC
OFFICE
20467
MH CLINIC TMS
20457
RRTP KITCHEN
OFFICE
20453
FAMILY TOILET
20444
HVAC
20442
A
A
A 16
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
B
B
B
B
B
B
B1
B1
B1
B1
A
A 13
A
A
A
A
A
A
A
A
A
A
A
A
B
B
B
B
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A25
A
A
A
A
A
A
A
A
A
A
A
A
A
A
B1
B1
B1
B1
B1
B1
B1
B1
B1
B1
A
B1
B1
D1
D1
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
B
B
B
B
B
B
B
B
B
B
B
B
A
A
A
A
A
A
B
B
XA
XA
XA
XA
XA
B2
B2
B2
B2
B2
B2
C
D
E
F
H
E.8
C.3
G
O/D
O/D O/D O/D
O O
/D O
/D
O /D
O /D
O /D
O/D
O /D
O/D O/D O/D
O /D
O /D
O /D
D
D
D
D
O
O
O O
O
O D
O /D
O /D
O /D
O /D
O
O/DO/DO/D
O/DO/DO/D
O /D
O /D
O
/DO
/D
D
O /D
O /D
D
OC OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC OC
OCOC
OC
OC
OC
OC
OC
AT
XA
F
F
F
F
F
B1
B1
EL01
OC OC
XA
F
CORRIDOR
2C12
CORRIDOR
2C11
B
B
A
ELEVATOR
LOBBY
2C06
CORRIDOR
2C05
RRTP
COUNSELOR
20422
WAITING
20427
CORRIDOR
2C07
CORRIDOR
2C08
CORRIDOR
2C04
CORRIDOR
2C03
EL01
GENDER
NEUTRAL TOILET
20448
STORAGE
20446 19
D1
EAST STAIR
2S1
STORAGE
20434A
STORAGE
20428A
STORAGE
20431A
HAC
20456
WEST STAIR
2S2
OC
OC
D1
D1EL03
P
GROUP ROOM B
20434
C
EL05
EL03
D1O
O
O
EL03
B1
B1 ff a
C2 C2C2 ggg f O
/D g
OC
O
EL07 NP-LLP-2
aa a a a a a a a a a a a a a a h h h h h h h h h h hh ee e e e e e e e e k e kk kk k i i i i i i i eeee t t t t t t t t t t t t e h i
OC
h k k e
OC
e e tt t t
D
D
OC OC
D
D
C i
CR1-2- 11
XA
LS-L-1
C
1. PROVIDE FIRE SEALS FOR INSERTS, CONDUIT PENETRATIONS, SLEEVES AND
ROUTINGS THROUGH RATED WALLS, CEILINGS AND FLOOR AS PER
SPECIFICATIONS.
2. PROVIDE SEPARATE CONDUITS FOR EMERGENCY LIGHTING.
3. OCCUPANCY SENSORS SHALL BE INSTALLED PER MANUFACTURERS
SPECIFICATIONS AND RECOMMENDATIONS. QUANTITIES AND LAYOUT SHALL BE
ADJUSTED PER MANUFACTURER'S RECOMMENDATIONS. E.C. SHALL INCLUDE IN
THEIR PRICE ALL NECESSARY DEVICES AND ACCESSORIES FOR A FULLY
FUNCTIONAL LIGHTING CONTROL SYSTEM, INCLUDING BUT NOT LIMITED TO
POWER PACKS, ROOM CONTROLLERS AND CABLING REQUIREMENTS.
4. PROVIDE OCCUPANCY SENSOR TYPES AND QUANTITIES AS REQUIRED TO
ACHIEVE 99% COVERAGE IN SPACE.
5. ALL LIGHT FIXTURES DESIGNATED AS EMERGENCY SHALL BE PROVIDED WITH A
UL 924 LISTED DEVICE FOR MONITORING AND SWITCHING BETWEEN NORMAL AND
EMERGENCY POWER SOURCES.
6. ALL LIGHTING FIXTURES DESIGNATED AS EMERGENCY AND ALL EXIT SIGNS SHALL
BE CIRCUITED TO LIFE SAFETY PANEL "LS-L-1".
7. EXTERIOR LIGHTING SHALL BE ROUTED THROUGH LIGHTING CONTACTOR.
PROVIDE UNSWITCHED HOT FOR FIXTURE BATTERY BACK-UP.
8. E.C. SHALL FURNISH AND INSTALL A PHOTO CELL AND CONNECT TO LIGHTING
CONTACTOR PANEL IN SECOND FLOOR BUILDING ELECTRICAL ROOM 20408.
9. ALL LIGHTING BRANCH CIRCUITS SHALL BE #10 AWG UNLESS OTHERWISE NOTED.
ELECTRICAL GENERAL NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
IJJTE
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
ELECTRICAL LIGHTING PLAN -
SECOND FLOOR
EL-102
-3
E L
/3
/2
.p d f
SCALE: 1/8" = 1'-0"
ELECTRICAL LIGHTING PLAN - LEVEL 2
KEYNOTE LEGEND
KEY DESCRIPTION
EL01 E.C. SHALL FURNISH AND INSTALL 5-SCENE PRE-SET LIGHTING SCENE CONTROLLER
WITH SETTINGS AT 10%, 25%, 50%, 75%, AND 100% LUMEN OUTPUT. SCENE
CONTROLLERS ON FIRST FLOOR SHALL HAVE OVERRIDE BUTTON TO CONTROL
GROUP ROOM A AND GROUP ROOM B LIGHTS SEPARATELY WHEN PARTITION IS
OPEN.
EL03 WALL MOUNT 4' LINEAR FIXTURE ABOVE DOOR CENTERED IN STORAGE ROOM.
EL05 IDENTIFY CIRCUITS SERVING EXISTING LIGHTING FIXTURES AND CONNECT TO
APPROPRIATE NEW NORMAL AND/OR EMERGENCY LIGHTING CIRCUITS IN ADJACENT
SPACES.
EL07 ALL NON-EMERGENCY LIGHTING CIRCUITS ON SECOND FLOOR SHALL BE FED BY
PANEL NP-LLP-2.
\1l lil at oc
DOI'IGIASW.
NEE.$EilI
E-4312t-6 tt t¡t trt tt I
,ro
\\12/30/2022 213 237
A R C H I T E C T S E N G I N E E R S
209 of 233209 of 233
T
AT
AT
AT
ATAT
AT
AT
AT
AT
AT AT
AT AT
AT AT
AT
AT
AT
AT
AT
AT AT
AT
AT
AT
AT
AT
ATAT
AT
AT AT
AT
AT
AT AT
AT
AT
AT
AT
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
B1
B1
B1
B1
B1
B1
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
B1
B1
B1
B1
B1
B1
B1
B1
B1 B1
B1
B1
A
A
A
A
A
A
A
A
A
A
A
A
B
A
A
A
A
A
A
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
A
A
A
A
A
A
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
A
A
B
A
B
A
B
B
B
B
B
B
B
B
B
A
A
A
A
A
B
B
B
B
B
B
C
C
C
C
C
C
C
C2
C
C
C
C
C
C
C
C
C
C
D1
D1
XA20
XA
XA 22
XA
XA
XA
B2
B2
B2
B2
B2
B2
C
D
E
F
H
E.8
C.3
G
D
O/D
O O
/D O
/D
O /D
O /D
O /D
O/D
O /D
O
O /D
O /D
O /D
O /D
O /D
O /D
O O
/D
O O
/D
O/D
O O
O
O
D
O
D
D D
O/DO/D
F
F
F
F
F
OC
OC
OC
OC
OC
EL01
OC
OC
OC OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
OC
ADMIN WAIT
30409
GROUP ROOM C
30436
STORAGE
30441A
STORAGE
30436A
GROUP ROOM A
30437
STORAGE
30437A
GROUP ROOM B
30441
CORRIDOR
3C07
ELEVATOR
LOBBY
3C05
BUILDING
ELECTRICAL
30416
BUILDING DATA
30451
STAFF BREAK
30453
GENDER
NEUTRAL TOILET
30449
FAMILY TOILET
30448
GENDER
NEUTRAL TOILET
30447
GENDER
NEUTRAL TOILET
30452
HVAC
30446
WAITING
30442
RRTP OFFICE
30428STAFF TOILET
30405
OFFICE
30457
MH CLINIC ADMIN
30464
STAFF TOILET
30472
CORRIDOR
3C10
ADMIN CUBICLES
30423
MHICM PRIVATE
COUNSEL
30476
LOUNGE
30443
CHIEF OFFICE
30417
ADMIN
CONFERENCE
30418
MHICM STORAGE
30471
MHICM PATIENT
CARE
30478
MHICM MED
ROOM
30473
MHICM CUBICLES
30479
CORRIDOR
3C11RECP.
WORKROOM
30430
RRTP OFFICE
30402
RRTP OFFICE
30404
RRTP OFFICE
30406
RRTP OFFICE
30401
RRTP OFFICE
30403
ADMIN RECP.
30415
ADMIN OFFICE
30426
CORRIDOR
3C02
MH CLINIC
OFFICE
30470
MH CLINIC
OFFICE
30468
MH CLINIC
OFFICE
30466
MH CLINIC
OFFICE
30465
MH CLINIC
OFFICE
30467
HAC
30462
RECEPTION
30432
WEST STAIR
3S2
EAST STAIR
3S1
CORRIDOR
3C03
CORRIDOR
3C04
CORRIDOR
3C06
CORRIDOR
3C08
CORRIDOR
3C12
OC
OC
OC
OC
OC
OC
OC
OCOC
XA
XA
ATAT OC
F
H
H
H
O/D
EL01
OFFICE
30461
OFFICE
30460
OFFICE
30459
OFFICE
30458
OFFICE
30456
OC
OCOC
O/DO/D
O/DO/D O/D
D
STORAGE
30450
EL03
D1
D1
P
C
LS-L-1
LS-L-1
LS-L-1
EL05
D1
D1O
STORAGE
30474
O
D1
O
OO
EL03
EL03
b bbb b b aaa a a a aaa x x ww x x x x x w w x x
B1
B1 kkk 9 C2
C2
C2 j j j j O
/D k
NP-LLP-3EL08
b b b b b b b b b b b b bb b b b g g g g i i i i i i i h h h h h h h h h h hh g g g g g g mmmm m m m m m g g g g t t t t t t t d d d a a a b b i
OC OC
h h g g g
OC
g g t t t w w
P
LS-L-1
H
96"
96"96"
96"
D
D
D
O
D
D
D130"
O
EL10
OC
C i
Db
Dw
C b m m m
1. PROVIDE FIRE SEALS FOR INSERTS, CONDUIT PENETRATIONS, SLEEVES AND
ROUTINGS THROUGH RATED WALLS, CEILINGS AND FLOOR AS PER
SPECIFICATIONS.
2. PROVIDE SEPARATE CONDUITS FOR EMERGENCY LIGHTING.
3. OCCUPANCY SENSORS SHALL BE INSTALLED PER MANUFACTURERS
SPECIFICATIONS AND RECOMMENDATIONS. QUANTITIES AND LAYOUT SHALL BE
ADJUSTED PER MANUFACTURER'S RECOMMENDATIONS. E.C. SHALL INCLUDE IN
THEIR PRICE ALL NECESSARY DEVICES AND ACCESSORIES FOR A FULLY
FUNCTIONAL LIGHTING CONTROL SYSTEM, INCLUDING BUT NOT LIMITED TO
POWER PACKS, ROOM CONTROLLERS AND CABLING REQUIREMENTS.
4. PROVIDE OCCUPANCY SENSOR TYPES AND QUANTITIES AS REQUIRED TO
ACHIEVE 99% COVERAGE IN SPACE.
5. ALL LIGHT FIXTURES DESIGNATED AS EMERGENCY SHALL BE PROVIDED WITH A
UL 924 LISTED DEVICE FOR MONITORING AND SWITCHING BETWEEN NORMAL AND
EMERGENCY POWER SOURCES.
6. ALL LIGHTING FIXTURES DESIGNATED AS EMERGENCY AND ALL EXIT SIGNS SHALL
BE CIRCUITED TO LIFE SAFETY PANEL "LS-L-1".
7. EXTERIOR LIGHTING SHALL BE ROUTED THROUGH LIGHTING CONTACTOR.
PROVIDE UNSWITCHED HOT FOR FIXTURE BATTERY BACK-UP.
8. E.C. SHALL FURNISH AND INSTALL A PHOTO CELL AND CONNECT TO LIGHTING
CONTACTOR PANEL IN SECOND FLOOR BUILDING ELECTRICAL ROOM 20408.
9. ALL LIGHTING BRANCH CIRCUITS SHALL BE #10 AWG UNLESS OTHERWISE NOTED.
ELECTRICAL GENERAL NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
IJJTE
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
ELECTRICAL LIGHTING PLAN - THIRD
FLOOR
EL-103
-3
E L
/3
/2
.p d f
SCALE: 1/8" = 1'-0"
ELECTRICAL LIGHTING PLAN LEVEL 3
KEYNOTE LEGEND
KEY DESCRIPTION
EL01 E.C. SHALL FURNISH AND INSTALL 5-SCENE PRE-SET LIGHTING SCENE CONTROLLER
WITH SETTINGS AT 10%, 25%, 50%, 75%, AND 100% LUMEN OUTPUT. SCENE
CONTROLLERS ON FIRST FLOOR SHALL HAVE OVERRIDE BUTTON TO CONTROL
GROUP ROOM A AND GROUP ROOM B LIGHTS SEPARATELY WHEN PARTITION IS
OPEN.
EL03 WALL MOUNT 4' LINEAR FIXTURE ABOVE DOOR CENTERED IN STORAGE ROOM.
EL05 IDENTIFY CIRCUITS SERVING EXISTING LIGHTING FIXTURES AND CONNECT TO
APPROPRIATE NEW NORMAL AND/OR EMERGENCY LIGHTING CIRCUITS IN ADJACENT
SPACES.
EL08 ALL NON-EMERGENCY LIGHTING CIRCUITS ON THIRD FLOOR SHALL BE FED BY PANEL
NP-LLP-3.
EL10 WALL MOUNT OCCUPANCY SENSOR 2' ABOVE DOOR. SENSOR SHALL CONTROL
STAIRCASE FIXTURE BETWEEN THIRD FLOOR AND ATTIC IN TANDEM WITH WALL
DEVICE AT BOTTOM OF STAIRS.
\1l lil at oc
DOI'IGIASW.
NEE.$EilI
E-4312t-6 tt t¡t trt tt I
,ro
\\12/30/2022 214 237
A R C H I T E C T S E N G I N E E R S
210 of 233210 of 233
AT
ATAT
AT
AT
AT
AT
ATATAT
AT AT
AT
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
C
D
E
F
H
E.8
C.3
G
XA
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
XA
XA
XA24
XA
G
OS
OS
OS
OS
OS
OS
a aa aa a a a a a aa
OC
OC
OC
OC
a a a a a a aa b b bb b b bb b b b b c c c c c c c c c c c c cc cc c c c d ddd d d
OCa OSc
O
OC
EL10130"
LS-L-1- 24
NP-LLP-3- 23
NP-LLP-3- 25
MD-480-P2
MD-480-P1
NP-LLP-3- 21
1. PROVIDE FIRE SEALS FOR INSERTS, CONDUIT PENETRATIONS, SLEEVES AND
ROUTINGS THROUGH RATED WALLS, CEILINGS AND FLOOR AS PER
SPECIFICATIONS.
2. PROVIDE SEPARATE CONDUITS FOR EMERGENCY LIGHTING.
3. OCCUPANCY SENSORS SHALL BE INSTALLED PER MANUFACTURERS
SPECIFICATIONS AND RECOMMENDATIONS. QUANTITIES AND LAYOUT SHALL BE
ADJUSTED PER MANUFACTURER'S RECOMMENDATIONS. E.C. SHALL INCLUDE IN
THEIR PRICE ALL NECESSARY DEVICES AND ACCESSORIES FOR A FULLY
FUNCTIONAL LIGHTING CONTROL SYSTEM, INCLUDING BUT NOT LIMITED TO
POWER PACKS, ROOM CONTROLLERS AND CABLING REQUIREMENTS.
4. PROVIDE OCCUPANCY SENSOR TYPES AND QUANTITIES AS REQUIRED TO
ACHIEVE 99% COVERAGE IN SPACE.
5. ALL LIGHT FIXTURES DESIGNATED AS EMERGENCY SHALL BE PROVIDED WITH A
UL 924 LISTED DEVICE FOR MONITORING AND SWITCHING BETWEEN NORMAL AND
EMERGENCY POWER SOURCES.
6. ALL LIGHTING FIXTURES DESIGNATED AS EMERGENCY AND ALL EXIT SIGNS SHALL
BE CIRCUITED TO LIFE SAFETY PANEL "LS-L-1".
7. EXTERIOR LIGHTING SHALL BE ROUTED THROUGH LIGHTING CONTACTOR.
PROVIDE UNSWITCHED HOT FOR FIXTURE BATTERY BACK-UP.
8. E.C. SHALL FURNISH AND INSTALL A PHOTO CELL AND CONNECT TO LIGHTING
CONTACTOR PANEL IN SECOND FLOOR BUILDING ELECTRICAL ROOM 20408.
9. ALL LIGHTING BRANCH CIRCUITS SHALL BE #10 AWG UNLESS OTHERWISE NOTED.
ELECTRICAL GENERAL NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
IJJTE
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
ELECTRICAL LIGHTING PLAN - ATTIC
EL-104
-3
E L
/3
/2
.p d f
SCALE: 1/8" = 1'-0"
ELECTRICAL LIGHTING PLAN - ATTIC
\1l lil at oc
DOI'IGIASW.
NEE.$EilI
E-4312t-6 tt t¡t trt tt I
,ro
\\12/30/2022 215 237
A R C H I T E C T S E N G I N E E R S
211 of 233211 of 233
B
MCC-B-1
NP-LPP-B
C
D
E
F
H
E.8
C.3
G
AHU-4
MCC-B-2- 2
MCC-B-2- 3
404-SP-02
404-RCP-01
404-RCP-02
NP-LPP-B- 6
MCC-B-2- 4
404-SP-01
404-HWP-02
404-HWP-01
NP-LPP-B
EP21
60"
NP-LPP-B
5EP22
EXISTING PUMP
EXISTING PUMP
EXISTING PUMP
EXISTING PUMP
404-HWP-01 DISCONNECT 404-HWP-02 DISCONNECT 404-SP-01 DISCONNECT
404-RCP-1B DISCONNECT
404-RCP-02 DISCONNECT404-RCP-1A DISCONNECT
NP-LPP-B
NP-LPP-B
EP28EP28
NP-LPP-B
NP-LPP-B
404-SP-01 STARTER404-HWP-01 STARTER 404-HWP-02 STARTER
51"51"51"
404-RCP-1B STARTER
404-RCP-1A STARTER 404-RCP-02 STARTER
51"51"
404-SP-02 DISCONNECT
404-SP-02 STARTER
51"
NP-LPP-B- 2,4
MCC-B-2
46"
46"
WP/G
1. E.C. SHALL INCLUDE IN THEIR BID POWERING AND INSTALLATION OF (5) 3HP, 208V,
3-PHASE HVAC PUMPS AND (1) 3HP, 208V, 3-PHASE HVAC COOLING UNIT.
2. CONTRACTOR SHALL CONFIRM ALL NEW MECHANICAL EQUIPMENT WITH
MECHANICAL AND PLUMBING DRAWINGS. PROVIDE NEW CONNECTIONS,
DISCONNECTS AND MOTOR STARTERS WHERE REQUIRED. ALL NEW POWER SHALL
BE SUPPLIED FROM MCC CABINETS 'MCC-B1' AND 'MCC-B2'.
ELECTRICAL GENERAL NOTES - BASEMENT
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
IJJTE
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
ELECTRICAL POWER PLAN -
BASEMENT
EP-1…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .