This document package includes construction drawings and specifications for an expansion and renovation project at the Tomah VA Medical Center in Tomah, Wisconsin. The project involves renovating space in Building 404 for outpatient mental health services, including adding new areas on the second and third floors. Fire protection, including sprinkler and alarm systems, will be upgraded throughout in accordance with NFPA standards. Bids are due by January 2023 for award in February, with work to be completed by December 2023. The total budget for the project is $5 million.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WF
VSVSVS
VS
WF
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
FX02
C
D
E
F
H
E.8
C.3
G
FX01
FX01
FD02
FD01
1. THE SCOPE OF DEMOLITION SHALL BE AS FOLLOWS
A. DEMO ALL SPRINKLERS, SPRINKLER PIPE, HANGERS, CONTROL VALVE
ASSEMBLIES AND ASSOCIATED APPURTENANCES ON EACH FLOOR WITH THE
EXCEPTION OF THE FOLLOWING:
a. EXISTING INCOMING WATER SHALL REMAIN
b. EXISTING BULK PIPE TO STANDPIPES SHALL REMAIN
c. EXISTING STANDPIPES SHALL REMAIN
d. EXISTING 2½" HOSE CONNECTIONS SHALL REMAIN
e. ALL FIRE SUPPRESSION SYSTEMS IN ATTIC TO REMAIN.
B. THE EXISTING CHECK VALVE AND CONTROL VALVE AT THE INCOMING WATER
LOCATION SHALL BE DEMOLISHED AND REPLACED WITH A NEW DOUBLE
CHECK BACK FLOW PREVENTER.
2. FOR GENERAL PHASING INFORMATION SEE ARCHITECTURAL DRAWINGS.
3. COORDINATE FIRE SPRINKLER DEMOLITION WITH OVERALL CONSTRUCTION
PHASING TO ENSURE NO OCCUPIED AREA OF THE BUILDING IS WITHOUT ACTIVE
FIRE SPRINKLER PROTECTION.
4. IT IS NOTED THAT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE
DEMOLITION SCOPE AND NOT ALL ITEMS ARE NECESSARILY SHOWN. THE
CONTRACTOR SHALL FIELD VERIFY SCOPE PRIOR TO STARTING WORK.
5. CAP PIPE AT LIMITS OF CONSTRUCTION WHEN APPLICABLE
FIRE SUPPRESSION DEMO NOTES
1. THE SCOPE OF DEMOLITION SHALL BE AS FOLLOWS
A. DEMO ALL FIRE ALARM DEVICES, PANELS, CONDUIT, HANGERS, AND
ASSOCIATED APPURTENANCES.
2. FOR GENERAL PHASING INFORMATION SEE ARCHITECTURAL DRAWINGS.
3. COORDINATE FIRE ALARM DEMOLITION WITH OVERALL CONSTRUCTION PHASING
TO ENSURE NO OCCUPIED AREA OF THE BUILDING IS WITHOUT ACTIVE AN FIRE
ALARM SYSTEM
4. IT IS NOTED THAT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE
DEMOLITION SCOPE AND NOT ALL ITEMS ARE NECESSARILY SHOWN. THE
CONTRACTOR SHALL FIELD VERIFY SCOPE PRIOR TO STARTING WORK.
FIRE ALARM DEMO NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
CSSDLO
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
FIRE PROTECTION DEMOLITION
PLAN - BASEMENT
FD-100
-3
F D
/2
/2
.p d f
SCALE: 1/8" = 1'-0"
FIRE PROTECTION DEMO PLAN - BASEMENT
N
KEYNOTE LEGEND
KEY DESCRIPTION
FD01 HATCH INDICATES TO DEMOLISH ALL INTERIOR SPRINKLER PIPING,
SPRINKLERS, AND ASSOCIATED HANGERS UNLESS NOTED OTHERWISE.
FD02 HATCH INDICATES TO DEMOLISH ALL INTERIOR FIRE ALARM SYSTEM DEVICES,
INCLUDING BUT NOT LIMITED TO THE FIRE ALARM PANEL, THE REMOTE
ANNUNCIATOR PANEL, NOTIFICATION DEVICES, SIGNALING DEVICES, AND
INITIATING DEVICES.
FX01 EXISTING STANDPIPES AND BULK FEED PIPING TO STANDPIPES SHALL REMAIN.
EXISTING 2-1/2" HOSE CONNECTIONS SHALL REMAIN
FX02 DEMOLISH EXISTING CHECK VALVE AND CONTROL VALVE AT INCOMING WATER
LOCATION. INSTALL NEW DOUBLE CHECK BACKFLOW PREVENTER WITH
SUPERVISED CONTROL VALVES.
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
12/30/2022 A R C H I T E C T S E N G I N E E R S
CB DESIGN
GROUP
128 241124 of 233124 of 233
WF WF
F A
C P
VS VS
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
FD04 FD04
FD01
FD04
FD03
C
D
E
F
H
E.8
C.3
G
1. THE SCOPE OF DEMOLITION SHALL BE AS FOLLOWS
A. DEMO ALL SPRINKLERS, SPRINKLER PIPE, HANGERS, CONTROL VALVE
ASSEMBLIES AND ASSOCIATED APPURTENANCES ON EACH FLOOR WITH THE
EXCEPTION OF THE FOLLOWING:
a. EXISTING INCOMING WATER SHALL REMAIN
b. EXISTING BULK PIPE TO STANDPIPES SHALL REMAIN
c. EXISTING STANDPIPES SHALL REMAIN
d. EXISTING 2½" HOSE CONNECTIONS SHALL REMAIN
e. ALL FIRE SUPPRESSION SYSTEMS IN ATTIC TO REMAIN.
B. THE EXISTING CHECK VALVE AND CONTROL VALVE AT THE INCOMING WATER
LOCATION SHALL BE DEMOLISHED AND REPLACED WITH A NEW DOUBLE
CHECK BACK FLOW PREVENTER.
2. FOR GENERAL PHASING INFORMATION SEE ARCHITECTURAL DRAWINGS.
3. COORDINATE FIRE SPRINKLER DEMOLITION WITH OVERALL CONSTRUCTION
PHASING TO ENSURE NO OCCUPIED AREA OF THE BUILDING IS WITHOUT ACTIVE
FIRE SPRINKLER PROTECTION.
4. IT IS NOTED THAT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE
DEMOLITION SCOPE AND NOT ALL ITEMS ARE NECESSARILY SHOWN. THE
CONTRACTOR SHALL FIELD VERIFY SCOPE PRIOR TO STARTING WORK.
5. CAP PIPE AT LIMITS OF CONSTRUCTION WHEN APPLICABLE
FIRE SUPPRESSION DEMO NOTES
1. THE SCOPE OF DEMOLITION SHALL BE AS FOLLOWS
A. DEMO ALL FIRE ALARM DEVICES, PANELS, CONDUIT, HANGERS, AND
ASSOCIATED APPURTENANCES.
2. FOR GENERAL PHASING INFORMATION SEE ARCHITECTURAL DRAWINGS.
3. COORDINATE FIRE ALARM DEMOLITION WITH OVERALL CONSTRUCTION PHASING
TO ENSURE NO OCCUPIED AREA OF THE BUILDING IS WITHOUT ACTIVE AN FIRE
ALARM SYSTEM
4. IT IS NOTED THAT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE
DEMOLITION SCOPE AND NOT ALL ITEMS ARE NECESSARILY SHOWN. THE
CONTRACTOR SHALL FIELD VERIFY SCOPE PRIOR TO STARTING WORK.
FIRE ALARM DEMO NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
CSSDLO
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
FIRE PROTECTION DEMOLITION
PLAN - FIRST FLOOR
FD-101
-3
F D
/2
/2
.p d f
SCALE: 1/8" = 1'-0"
FIRE PROTECTION DEMO PLAN - FIRST FLOOR
N
KEYNOTE LEGEND
KEY DESCRIPTION
FD01 HATCH INDICATES TO DEMOLISH ALL INTERIOR SPRINKLER PIPING,
SPRINKLERS, AND ASSOCIATED HANGERS UNLESS NOTED OTHERWISE.
FD03 REMOVE AND SALVAGE EXISTING FIRE ALARM PANEL. PANEL TO BE
RELOCATED AND REUSED. EXISTING PANEL IS A FARENHYT IFP-2100/ECS.
FD04 EXISTING STANDPIPES AND BULK FEEDS TO STANDPIPES ARE TO REMAIN.
EXISTING 2-1/2" HOSE CONNECTIONS SHALL REMAIN. DEMOLISH SPRINKLER
PIPING BACK TO STANDPIPE CONNECTION INCLUDING DEMOLISHING EXISTING
RISER ASSEMBLIES.
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
12/30/2022 A R C H I T E C T S E N G I N E E R S
129 241125 of 233125 of 233
WF WF
VS VS
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
FD04 FD04
FD01
FD02
C
D
E
F
H
E.8
C.3
G
1. THE SCOPE OF DEMOLITION SHALL BE AS FOLLOWS
A. DEMO ALL SPRINKLERS, SPRINKLER PIPE, HANGERS, CONTROL VALVE
ASSEMBLIES AND ASSOCIATED APPURTENANCES ON EACH FLOOR WITH THE
EXCEPTION OF THE FOLLOWING:
a. EXISTING INCOMING WATER SHALL REMAIN
b. EXISTING BULK PIPE TO STANDPIPES SHALL REMAIN
c. EXISTING STANDPIPES SHALL REMAIN
d. EXISTING 2½" HOSE CONNECTIONS SHALL REMAIN
e. ALL FIRE SUPPRESSION SYSTEMS IN ATTIC TO REMAIN.
B. THE EXISTING CHECK VALVE AND CONTROL VALVE AT THE INCOMING WATER
LOCATION SHALL BE DEMOLISHED AND REPLACED WITH A NEW DOUBLE
CHECK BACK FLOW PREVENTER.
2. FOR GENERAL PHASING INFORMATION SEE ARCHITECTURAL DRAWINGS.
3. COORDINATE FIRE SPRINKLER DEMOLITION WITH OVERALL CONSTRUCTION
PHASING TO ENSURE NO OCCUPIED AREA OF THE BUILDING IS WITHOUT ACTIVE
FIRE SPRINKLER PROTECTION.
4. IT IS NOTED THAT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE
DEMOLITION SCOPE AND NOT ALL ITEMS ARE NECESSARILY SHOWN. THE
CONTRACTOR SHALL FIELD VERIFY SCOPE PRIOR TO STARTING WORK.
5. CAP PIPE AT LIMITS OF CONSTRUCTION WHEN APPLICABLE
FIRE SUPPRESSION DEMO NOTES
1. THE SCOPE OF DEMOLITION SHALL BE AS FOLLOWS
A. DEMO ALL FIRE ALARM DEVICES, PANELS, CONDUIT, HANGERS, AND
ASSOCIATED APPURTENANCES.
2. FOR GENERAL PHASING INFORMATION SEE ARCHITECTURAL DRAWINGS.
3. COORDINATE FIRE ALARM DEMOLITION WITH OVERALL CONSTRUCTION PHASING
TO ENSURE NO OCCUPIED AREA OF THE BUILDING IS WITHOUT ACTIVE AN FIRE
ALARM SYSTEM
4. IT IS NOTED THAT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE
DEMOLITION SCOPE AND NOT ALL ITEMS ARE NECESSARILY SHOWN. THE
CONTRACTOR SHALL FIELD VERIFY SCOPE PRIOR TO STARTING WORK.
FIRE ALARM DEMO NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
CSSDLO
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
FIRE PROTECTION DEMOLITION
PLAN - SECOND FLOOR
FD-102
-3
F D
/2
/2
.p d f
SCALE: 1/8" = 1'-0"
FIRE PROTECTION DEMO PLAN - SECOND FLOOR
N
KEYNOTE LEGEND
KEY DESCRIPTION
FD01 HATCH INDICATES TO DEMOLISH ALL INTERIOR SPRINKLER PIPING,
SPRINKLERS, AND ASSOCIATED HANGERS UNLESS NOTED OTHERWISE.
FD02 HATCH INDICATES TO DEMOLISH ALL INTERIOR FIRE ALARM SYSTEM DEVICES,
INCLUDING BUT NOT LIMITED TO THE FIRE ALARM PANEL, THE REMOTE
ANNUNCIATOR PANEL, NOTIFICATION DEVICES, SIGNALING DEVICES, AND
INITIATING DEVICES.
FD04 EXISTING STANDPIPES AND BULK FEEDS TO STANDPIPES ARE TO REMAIN.
EXISTING 2-1/2" HOSE CONNECTIONS SHALL REMAIN. DEMOLISH SPRINKLER
PIPING BACK TO STANDPIPE CONNECTION INCLUDING DEMOLISHING EXISTING
RISER ASSEMBLIES.
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
12/30/2022 A R C H I T E C T S E N G I N E E R S
130 241126 of 233126 of 233
WF
WFVS
VS
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
FD04 FD04
FD01
C
D
E
F
H
E.8
C.3
G
FD02
1. THE SCOPE OF DEMOLITION SHALL BE AS FOLLOWS
A. DEMO ALL SPRINKLERS, SPRINKLER PIPE, HANGERS, CONTROL VALVE
ASSEMBLIES AND ASSOCIATED APPURTENANCES ON EACH FLOOR WITH THE
EXCEPTION OF THE FOLLOWING:
a. EXISTING INCOMING WATER SHALL REMAIN
b. EXISTING BULK PIPE TO STANDPIPES SHALL REMAIN
c. EXISTING STANDPIPES SHALL REMAIN
d. EXISTING 2½" HOSE CONNECTIONS SHALL REMAIN
e. ALL FIRE SUPPRESSION SYSTEMS IN ATTIC TO REMAIN.
B. THE EXISTING CHECK VALVE AND CONTROL VALVE AT THE INCOMING WATER
LOCATION SHALL BE DEMOLISHED AND REPLACED WITH A NEW DOUBLE
CHECK BACK FLOW PREVENTER.
2. FOR GENERAL PHASING INFORMATION SEE ARCHITECTURAL DRAWINGS.
3. COORDINATE FIRE SPRINKLER DEMOLITION WITH OVERALL CONSTRUCTION
PHASING TO ENSURE NO OCCUPIED AREA OF THE BUILDING IS WITHOUT ACTIVE
FIRE SPRINKLER PROTECTION.
4. IT IS NOTED THAT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE
DEMOLITION SCOPE AND NOT ALL ITEMS ARE NECESSARILY SHOWN. THE
CONTRACTOR SHALL FIELD VERIFY SCOPE PRIOR TO STARTING WORK.
5. CAP PIPE AT LIMITS OF CONSTRUCTION WHEN APPLICABLE
FIRE SUPPRESSION DEMO NOTES
1. THE SCOPE OF DEMOLITION SHALL BE AS FOLLOWS
A. DEMO ALL FIRE ALARM DEVICES, PANELS, CONDUIT, HANGERS, AND
ASSOCIATED APPURTENANCES.
2. FOR GENERAL PHASING INFORMATION SEE ARCHITECTURAL DRAWINGS.
3. COORDINATE FIRE ALARM DEMOLITION WITH OVERALL CONSTRUCTION PHASING
TO ENSURE NO OCCUPIED AREA OF THE BUILDING IS WITHOUT ACTIVE AN FIRE
ALARM SYSTEM
4. IT IS NOTED THAT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE
DEMOLITION SCOPE AND NOT ALL ITEMS ARE NECESSARILY SHOWN. THE
CONTRACTOR SHALL FIELD VERIFY SCOPE PRIOR TO STARTING WORK.
FIRE ALARM DEMO NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
CSSDLO
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
FIRE PROTECTION DEMOLITION
PLAN - THIRD FLOOR
FD-103
-3
F D
/2
/2
.p d f
SCALE: 1/8" = 1'-0"
FIRE PROTECTION DEMO PLAN - THIRD FLOOR
N
KEYNOTE LEGEND
KEY DESCRIPTION
FD01 HATCH INDICATES TO DEMOLISH ALL INTERIOR SPRINKLER PIPING,
SPRINKLERS, AND ASSOCIATED HANGERS UNLESS NOTED OTHERWISE.
FD02 HATCH INDICATES TO DEMOLISH ALL INTERIOR FIRE ALARM SYSTEM DEVICES,
INCLUDING BUT NOT LIMITED TO THE FIRE ALARM PANEL, THE REMOTE
ANNUNCIATOR PANEL, NOTIFICATION DEVICES, SIGNALING DEVICES, AND
INITIATING DEVICES.
FD04 EXISTING STANDPIPES AND BULK FEEDS TO STANDPIPES ARE TO REMAIN.
EXISTING 2-1/2" HOSE CONNECTIONS SHALL REMAIN. DEMOLISH SPRINKLER
PIPING BACK TO STANDPIPE CONNECTION INCLUDING DEMOLISHING EXISTING
RISER ASSEMBLIES.
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
12/30/2022 A R C H I T E C T S E N G I N E E R S
131 241127 of 233127 of 233
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
FD02
C
D
E
F
H
E.8
C.3
G
FX08
1. THE SCOPE OF DEMOLITION SHALL BE AS FOLLOWS
A. DEMO ALL SPRINKLERS, SPRINKLER PIPE, HANGERS, CONTROL VALVE
ASSEMBLIES AND ASSOCIATED APPURTENANCES ON EACH FLOOR WITH THE
EXCEPTION OF THE FOLLOWING:
a. EXISTING INCOMING WATER SHALL REMAIN
b. EXISTING BULK PIPE TO STANDPIPES SHALL REMAIN
c. EXISTING STANDPIPES SHALL REMAIN
d. EXISTING 2½" HOSE CONNECTIONS SHALL REMAIN
e. ALL FIRE SUPPRESSION SYSTEMS IN ATTIC TO REMAIN.
B. THE EXISTING CHECK VALVE AND CONTROL VALVE AT THE INCOMING WATER
LOCATION SHALL BE DEMOLISHED AND REPLACED WITH A NEW DOUBLE
CHECK BACK FLOW PREVENTER.
2. FOR GENERAL PHASING INFORMATION SEE ARCHITECTURAL DRAWINGS.
3. COORDINATE FIRE SPRINKLER DEMOLITION WITH OVERALL CONSTRUCTION
PHASING TO ENSURE NO OCCUPIED AREA OF THE BUILDING IS WITHOUT ACTIVE
FIRE SPRINKLER PROTECTION.
4. IT IS NOTED THAT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE
DEMOLITION SCOPE AND NOT ALL ITEMS ARE NECESSARILY SHOWN. THE
CONTRACTOR SHALL FIELD VERIFY SCOPE PRIOR TO STARTING WORK.
5. CAP PIPE AT LIMITS OF CONSTRUCTION WHEN APPLICABLE
FIRE SUPPRESSION DEMO NOTES
1. THE SCOPE OF DEMOLITION SHALL BE AS FOLLOWS
A. DEMO ALL FIRE ALARM DEVICES, PANELS, CONDUIT, HANGERS, AND
ASSOCIATED APPURTENANCES.
2. FOR GENERAL PHASING INFORMATION SEE ARCHITECTURAL DRAWINGS.
3. COORDINATE FIRE ALARM DEMOLITION WITH OVERALL CONSTRUCTION PHASING
TO ENSURE NO OCCUPIED AREA OF THE BUILDING IS WITHOUT ACTIVE AN FIRE
ALARM SYSTEM
4. IT IS NOTED THAT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE
DEMOLITION SCOPE AND NOT ALL ITEMS ARE NECESSARILY SHOWN. THE
CONTRACTOR SHALL FIELD VERIFY SCOPE PRIOR TO STARTING WORK.
FIRE ALARM DEMO NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
CSSDLO
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
FIRE PROTECTION DEMOLITION
PLAN - ATTIC
FD-104
-3
F D
/2
/2
.p d f
SCALE: 1/8" = 1'-0"
FIRE PROTECTION DEMO PLAN - ATTIC
N
KEYNOTE LEGEND
KEY DESCRIPTION
FD02 HATCH INDICATES TO DEMOLISH ALL INTERIOR FIRE ALARM SYSTEM DEVICES,
INCLUDING BUT NOT LIMITED TO THE FIRE ALARM PANEL, THE REMOTE
ANNUNCIATOR PANEL, NOTIFICATION DEVICES, SIGNALING DEVICES, AND
INITIATING DEVICES.
FX08 ALL FIRE SUPPRESSION SYSTEMS IN HATCHED PORTION OF ATTIC TO REMAIN.
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
12/30/2022 A R C H I T E C T S E N G I N E E R S
132 241128 of 233128 of 233
DH
DCL
F
F
S
CO
S
ID
S P
WF
VS
FAA
FACP
FATC
TPR
NAC
H R
CO
F S P
F S P
F S P
VSWF
VSWF
VSWF
VSWF
S
ID
VSWF
S P
H R
AIM
RL
H R
1. PROVIDE AND INSTALL A NEW FIRE ALARM SYSTEM THROUGHOUT THE BUILDING
PER THE VA FIRE PROTECTION DESIGN MANUAL AND NFPA 72.
2. THE NEW FIRE ALARM SYSTEM SHALL BE A VOICE EVACUATION TYPE SYSTEM.
WITH A MICROPHONE LOCATED AT THE FIRE ALARM PANEL FOR EMERGENCY
NOTIFICATION.
3. THE EXISTING FIRE ALARM PANEL SHALL BE REMOVED AND RELOCATED TO THE
ELECTRICAL ROOM AS INDICATED ON THE DRAWINGS. NEW NOTIFICATION AND
INITIATING DEVICES SHALL BE PROVIDED AND COMPATIBLE WITH THE EXISTING
PANEL.
4. THE FIRE ALARM SYSTEM SHALL BE ZONED PER FLOOR.
5. THE EXISTING CAMPUS FIRE ALARM PANEL IS A FARENHYT IFP-2100/ECS PANEL.
NEW FIRE ALARM SYSTEM COMPONENTS MUST BE COMPATIBLE WITH THIS.
6. THE FIRE ALARM SYSTEM SHALL REPORT TO THE CONSTANTLY ATTENDED
STATION AT THE VA TOMAH FIRE DEPARTMENT.
7. THE CONTRACTOR SHALL PROVIDE INSTALLATION SHOP DRAWINGS FOR REVIEW
BY OWNER AND A/E PRIOR TO INSTALLATION.
8. EXISTING FIRE ALARM DEVICES SHALL BE RETAINED AND SALVAGED FOR VA USE.
COORDINATE WITH VA COR.
9. PROVIDE FIRE SEAL FOR INSERTS, SLEEVES AND CONDUIT PENETRATIONS
THROUGH WALLS, CEILINGS AND FLOORS AS PER SPECIFICATIONS
10. COORDINATE FIRE ALARM SYSTEM DEVICE LOCATIONS WITH LIGHT FIXTURES,
STRUCTURAL MEMBERS, SPRINKLER HEADS AND PIPING, HVAC EQUIPMENT AND
DUCTWORK.
11. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL OPERATING SYSTEMS AS
INDICATED ON THE CONTRACT DOCUMENTS AND AS EVIDENTLY INTENDED. IT IS
NOTED THAT THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL
ARRANGEMENTS OF SYSTEMS AND WORK. THE CONTRACTOR SHALL FURNISH
AND INSTALL CONDUIT AND WIRING AS REQUIRED TO ACCOMPLISH THE
FUNCTIONS INDICATED. THE CONTRACTOR SHALL FURNISH AND INSTALL THE
REQUIRED QUANTITIES AND TYPES OF CABLES, CONDUCTORS, RACEWAYS,
REMOTE POWER SUPPLIES AND CONNECTIONS, SHIELDING REQUIREMENTS, ETC.,
AS REQUIRED BY THE SYSTEM MANUFACTURER, THE SPECIFICATIONS, AND ANY
APPLICABLE CODES. ALL WIRING SHOWN ON RISER DIAGRAMS SHALL ALSO BE
FURNISHED AND INSTALLED REGARDLESS OF WHETHER THESE ITEMS ARE
SHOWN ON THE FLOOR PLANS.
12. THE CONTRACTOR SHALL COORDINATE THE ELECTRICAL WORK WITH THE WORK
OF ALL OTHER TRADES AND EXISTING CONDITIONS SO AS TO AVOID CONFLICTS.
RESOLVE ALL CONFLICTS THROUGH THE A/E PRIOR TO ROUGH-IN. FAILURE TO
PROVIDE SUCH COORDINATION PRIOR TO WORK BEING INSTALLED SHALL NOT BE
CAUSE FOR ADDITIONAL COMPENSATION TO THE CONTRACTOR, AND MAY
RESULT IN REJECTION OF THE WORK.
13. ADDITIONAL DEVICES MAY BE REQUIRED. CONTRACTOR TO VERIFY FINAL DEVICE
LAYOUT.
14. ALL MATERIALS SHALL BE NEW, SHALL BE SUITABLE FOR THE APPLICATION
INTENDED, AND SHALL BEAR LABELS OR MARKINGS INDICATING THIRD PARTY
TESTING LABORATORY LISTINGS ACCEPTABLE TO THE AUTHORITY HAVING
JURISDICTION.
15. VERIFY LOCATIONS OF WIRING DEVICES IN FINISHED SPACES, MILLWORK, AND
CASEWORK WITH ARCHITECTURAL DRAWINGS, DETAILS, AND ELEVATIONS, AND
WITH THE OWNER'S EQUIPMENT AND FURNITURE LAYOUTS PRIOR TO ROUGH-IN.
16. ALL FIRE ALARM CABLES SHOULD BE INSTALLED IN RED METAL RACEWAYS.
17. ALL RACEWAY AND WIRING SHALL BE CONCEALED IN FINISHED SPACES AND MAY
BE EXPOSED IN UNFINISHED SPACES SUCH AS MECHANICAL AND ELECTRICAL
ROOMS. ALL RACEWAY AND WIRING SHALL BE ROUTED EITHER PERPENDICULAR
OR PARALLEL TO THE BUILDING'S STRUCTURAL COMPONENTS.
18. PROVIDE PULL AND JUNCTION BOXES AS REQUIRED TO MEET CODE AND
INSTALLATION REQUIREMENTS. PULL AND JUNCTION BOXES SHALL BE
CONCEALED IN FINISHED SPACES AND LOCATIONS SHALL BE COORDINATED WITH
THE WORK OF ALL OTHER TRADES SO AS TO AVOID CONFLICTS.
19. ALL CONDUCTORS SHALL BE IDENTIFIED AT EACH JUNCTION BOX, OUTLET BOX,
CABINET, PULL BOX, ETC., WITH VINYL SELF-ADHESIVE TAGS INDICATING PANEL
AND CIRCUIT NUMBER, CONTROL WIRE IDENTIFICATION NUMBER, OR OTHER
APPROPRIATE INFORMATION. ALL PULL AND JUNCTION BOXES SHALL BE LABELED
AS TO FUNCTION.
20. ALL EQUIPMENT SHALL BE SECURELY FASTENED BY MEANS OF ANCHORS, RODS,
HANGERS, SUPPORTS, GUIDES, SWAY BRACES, ETC., TO MAINTAIN ALIGNMENT
AND PREVENT EQUIPMENT MOVEMENT. ALL EQUIPMENT LOCATED IN SEISMIC
ZONES SHALL BE SECURED WITH MEANS APPROVED FOR THE SEISMIC
CLASSIFICATION ENCOUNTERED.
21. ALL PENETRATIONS OF FIRE OR SMOKE RATED CONSTRUCTION SHALL BE SEALED
WITH FIRESTOPPING MATERIALS APPROVED AND LISTED FOR THE RATING OF THE
CONSTRUCTION TO BE PENETRATED. PROVIDE DOCUMENTATION ON ALL SUCH
PENETRATION SEALING SYSTEMS FOR VERIFICATION OF PROPER INSTALLATION.
22. ALL PENETRATIONS OF ROOFS, EXTERIOR WALLS, FOUNDATIONS, OR OTHER
WATER OR MOISTURE PROOF CONSTRUCTION SHALL BE SEALED WITH
APPROPRIATE SEALING FITTINGS OR SEALED CONSTRUCTION TO PREVENT THE
INTRODUCTION OF MOISTURE INTO THE BUILDING.
23. WHERE EMPTY RACEWAYS ARE INSTALLED, THEY SHALL BE LABELED AT BOTH
ENDS AND FITTED WITH NYLON PULLSTRINGS FOR FUTURE USE.
24. ELECTRICAL WORK SHALL BE PERFORMED ON DE-ENERGIZED SYSTEMS ONLY TO
PREVENT PERSONNEL INJURY AND POTENTIAL SYSTEM FAILURE. WHERE WORK
ON EXISTING SYSTEMS WILL REQUIRE INTERRUPTION OF ELECTRICAL SERVICE,
THEN TEMPORARY PROVISIONS ACCEPTABLE TO THE OWNER FOR TEMPORARY
POWER SHALL BE UTILIZED UNTIL THE WORK IS COMPLETE.
25. WALL MOUNTED FIRE ALARM PULL STATIONS ARE TO BE LOCATED 46" A.F.F. AND
WITHIN 5' OF THE NEAREST ADJACENT EXIT DOOR FROM THE FLOOR OR
BUILDING.
26. WALL MOUNTED FIRE ALARM NOTIFICATION APPLIANCES, EITHER VISUAL, OR
COMBINATION AUDIO/VISUAL, SHALL BE LOCATED SUCH THAT THE ENTIRE LENS
OF THE VISUAL PORTION IS BETWEEN 80" AND 96" A.F.F. AUDIO ONLY APPLIANCES
SHALL BE LOCATED, NOT LESS THAN 90" A.F.F. TO TOP OF APPLIANCE, OR 6"
BELOW CEILING.
FIRE ALARM/MNS GENERAL NOTESFIRE ALARM SYMBOLS
DEVICES
COMBINATION OF SPEAKER/STROBE WALL MOUNTED
MANUAL PULL STATION
SPEAKER ONLY WALL MOUNTED
EXTERIOR BELL
STROBE ONLY CEILING MOUNTED
SYMBOL DESCRIPTION
DOOR HOLDER
DOOR CLOSER
DETECTORS
GAS DETECTOR - CARBON MONOXIDE
SMOKE DETECTOR - IN DUCT
SMOKE DETECTOR - PHOTOELECTRIC
FLOW DETECTOR/SWITCH
VALVE SUPERVISORY SWITCH
SWITCHES
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
FIRE ALARM TRANSPONDER CABINET
NOTIFICATION CIRCUIT POWER BOOSTER
PANELS
STROBE ONLY WALL MOUNTED
HEAT DETECTOR - RATE OF RISE
FIRE ALARM
CONTROL PANEL
FRONT LOBBY -
RM 10440
INITIATING DEVICES
BASEMENT LEVEL FIRE/SMOKE
BASEMENT
NOTE: REPRESENTS NUMBER OF DEVICES
ON THIS LEVEL. CONTRACTOR SHALL
VERIFY ALL NECESSARY DEVICE COUNTS
LEVEL 1
LEVEL 2
LEVEL 3
ATTIC
= 1
NOTIFICATION DEVICES
SECOND LEVEL FIRE/SMOKE
INITIATING DEVICES SECOND LEVEL
FIRE/SMOKE
= 24
= 2
= 7
= 1
NOTIFICATION DEVICES
FIRST LEVEL FIRE/SMOKE
INITIATING DEVICES FIRST LEVEL
FIRE/SMOKE
= 22
= 8
= 14
= 2
NOTIFICATION DEVICES
THIRD LEVEL FIRE/SMOKE
INITIATING DEVICES THIRD LEVEL
FIRE/SMOKE
= 25
= 2
= 7
= 2
NOTIFICATION DEVICES
ATTIC LEVEL FIRE/SMOKE
INITIATING DEVICES ATTIC LEVEL
FIRE/SMOKE
= 4= 1
= 2= 2
= 2= 2
= 2= 2
NOTE: REPRESENTS NUMBER OF DEVICES
ON THIS LEVEL. CONTRACTOR SHALL
VERIFY ALL NECESSARY DEVICE COUNTS
NOTE: REPRESENTS NUMBER OF DEVICES
ON THIS LEVEL. CONTRACTOR SHALL
VERIFY ALL NECESSARY DEVICE COUNTS
NOTE: REPRESENTS NUMBER OF DEVICES
ON THIS LEVEL. CONTRACTOR SHALL
VERIFY ALL NECESSARY DEVICE COUNTS
NOTE: REPRESENTS NUMBER OF DEVICES
ON THIS LEVEL. CONTRACTOR SHALL
VERIFY ALL NECESSARY DEVICE COUNTS
FIRE ALARM
TRANSPONDER CABINET
BUILDING ELECTRICAL
ROOM 336
BASEMENT
LEVEL 1
LEVEL 2
LEVEL 3
ATTIC
NOTIFICATION DEVICES
BASEMENT LEVEL FIRE/SMOKE
= 2
= 5
= 1= 1
= 7
= 2
= 2
= 4
= 4
= 1
DUCT SMOKE DETECTOR
AREA SMOKE DETECTOR
DOOR RELEASE SMOKE DETECTOR
S O
U N
D G
E N
E R
A L
B U
IL
D
IN
G
LA
R
M
X
X
N O
T
IF
Y N
E C
E S
S A
R Y
S T
A
X
INPUT
OUTPUT
N O
T
IF
Y F
IR
E
D E
P A
R M
E N
T
IN
IT
IA
T
E S
U P
E R
V
IS
O R
Y S
IG
N
A L
T O
A
4- H
O U
R M
A N
N E
D P
O
IN
O
R
IM
M E
D
IA
T E
R E
S P
O N
S E
X C
LO
S
E A
S S
O C
IA
T
E S
M O
K E
B
R
R
IE
R D
O O
R S
O N
T H
LO
O R
X
MANUAL PULL STATION
ELEVATOR MACHINE ROOM HEAT DETECTOR
SPRINKLER WATERFLOW SWITCH
X
X
X
X
X
X
X
X
X
ELEVATOR SMOKE DETECTOR X X X
X
X
C
LO
S E
D A
M P
E R
S O
N F
P
R O
X
IM
A T
E T
O D
E T
E C
T O
R
X
X
S H
U T
D O
W N
A U
R H
A N
D
LE
S
R V
E D
B Y
T H
E D
E T
E C
T O
R
X1
1. DO NOT PROVIDE DUCT DETECTORS IN DEDICATED (100%) EXHAUST FANS, THEY SHOULD CONTINUE TO RUN.
R E
C A
LL
E
LE
V
A T
O R
X
IN
IT
IA
T
E E
LE
V
A T
O R
S H
U
D
W
N A
N D
D
IS
C O
N N
E C
LE
V A
T O
R P
O W
E R
O P
E N
L O
C K
E D
E G
R E
O
R S
O N
F
LO
O R
O F
F
IR
IG
IN
X
X
X
FIRE ALARM MATRIX
CARBON MONOXIDE DETECTOR
S O
U N
D S
P E
C
IF
IC
C
A R
B
M
N O
X
ID
E A
LA
M
WATER CONTROL VALVE TAMPER X
X
X
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
CSSDLO
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
FIRE ALARM GENERAL NOTES AND
DETAILS
FA-001
-3
F A
/2
/2
.p d f
SCALE: 12" = 1'-0"
FIRE ALARM RISER DIAGRAM
12/30/2022 A R C H I T E C T S E N G I N E E R S
133 241129 of 233129 of 233
VS
CO
VS
VS
WF
VSVS
H R
H R
S P
S P
DH
DCL
F
F
S
CO
S
ID
S P
WF
VS
FAA
FACP
FATC
TPR
NAC
H R
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
C
D
E
F
H
E.8
C.3
G
MECHANICAL
ROOM
B0405
ELEVATOR PIT
B0403
CRAWL SPACE
B0400
EAST STAIR
BS1
INSULATE TO PREVENT
CONDENSATION AND DO NOT
MOUNT TO EXTERIOR WALL
FA02
FIRE ALARM SYMBOLS
DEVICES
COMBINATION OF SPEAKER/STROBE WALL MOUNTED
MANUAL PULL STATION
SPEAKER ONLY WALL MOUNTED
EXTERIOR BELL
STROBE ONLY CEILING MOUNTED
SYMBOL DESCRIPTION
DOOR HOLDER
DOOR CLOSER
DETECTORS
GAS DETECTOR - CARBON MONOXIDE
SMOKE DETECTOR - IN DUCT
SMOKE DETECTOR - PHOTOELECTRIC
FLOW DETECTOR/SWITCH
VALVE SUPERVISORY SWITCH
SWITCHES
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
FIRE ALARM TRANSPONDER CABINET
NOTIFICATION CIRCUIT POWER BOOSTER
PANELS
STROBE ONLY WALL MOUNTED
HEAT DETECTOR - RATE OF RISE
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
CSSDLO
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
FIRE ALARM PLAN - BASEMENT
FA-100
-3
F A
/2
/2
.p d f
SCALE: 1/8" = 1'-0"
FIRE ALARM PLAN - BASEMENT
N
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
KEYNOTE LEGEND
KEY DESCRIPTION
FA02 57 °C (135 °F) RATE COMPENSATION HEAT DETECTION REQUIRED 2 FT FROM
SPRINKLERS INSTALLED IN HOISTWAY PIT. SMOKE DETECTION ALSO REQUIRED AT
PIT.
12/30/2022 A R C H I T E C T S E N G I N E E R S
134 241130 of 233130 of 233
DN
P
F
F
F
F
F
FACP
S P
VS
WF
WF
VS
F
F
F
FAA
S P
H R
RL
RL
RL
RL
AIM
AIM
AIM
AIM
DH
DCL
F
F
S
CO
S
ID
S P
WF
VS
FAA
FACP
FATC
TPR
NAC
H R
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
RELOCATED FIRE ALARM PANEL
C
D
E
F
H
E.8
C.3
G
RRTP OFFICES
10426
WORKROOM
10466
MH CLINIC
EXAM/VITALS
10475
CORRIDOR
1C02
TREATMENT
OBSERVATION
10451
NURSE STATION
10452
GENDER
NEUTRAL TOILET
10447
MOTHERS ROOM
10446
GROUP ROOM C
10430
ELEVATOR
LOBBY
1C06
STORAGE
10438A
STORAGE
10430A
GROUP ROOM A
10435
STORAGE
10435A
HALL
1C10
FAMILY TOILET
10444
SPECIMEN
TOILET
10454
MH CLINIC
OFFICE
10479
STAFF TOILET
10476
MH CLINIC
OFFICE
10473
MH CLINIC
OFFICE
10471
MH CLINIC
OFFICE
10477
MH CLINIC
OFFICE
10480
MH CLINIC
MED/SUPPLY
10474
MH CLINIC
OFFICE
10470
MH CLINIC
OFFICE (FUTURE
EXAM)
10478
MH CLINIC
OFFICE
10485
MH CLINIC
OFFICE
10472
MH CLINIC
TELEMED OFFICE
10484
GENDER
NEUTRAL TOILET
10445
BUILDING DATA
10449
TREATMENT
OBSERVATION
10453
TREATMENT
CIRCULATION
10450
ADMIN OFFICE
10420
RRTP
COUNSELOR
10404
EAST STAIR
1S1
BED BUG ZAPPER
10414
RRTP SECURITY
OFFICE
10419
RRTP
COUNSELOR
10405
RRTP VITALS &
LOCKERS
10416
RRTP WAITING
10417
MAIN
ELECTRICAL
10411
WEST STAIR
1S2
MAIN CORRIDOR
1C05
GROUP ROOM B
10438
FAMILY WAITING
10465
WAITING
10424
LOUNGE
10425
VENDING
10422
INFO DESK
10442
RECEPTION
10460
VESTIBULE
10440
TRAM WALKWAY
1C20
TESTING OFFICE
10401
GROUP TESTING
10400
MH CLINIC
TELEMED OFFICE
10486
MH CLINIC
TELEMED OFFICE
10488
MH CLINIC
TELEMED OFFICE
10489
MH CLINIC
OFFICE
10487
WAITING
10443
CORRIDOR
1C04
CORRIDOR
1C07
CORRIDOR
1C08
CORRIDOR
1C11
CORRIDOR
1C12
RECEIVING
10499
EMR
10412
ELECTRICAL
CLOSET
10413
STORAGE
10415
ELECTRICAL
10415A
RRTP TOILET
10418
HAC
10464
RRTP FOYER
10427
MAIN
ELECTRICAL
10411
NEW FIRE ALARM ANNUNCIATOR
FA02
FA03
FIRE ALARM SYMBOLS
DEVICES
COMBINATION OF SPEAKER/STROBE WALL MOUNTED
MANUAL PULL STATION
SPEAKER ONLY WALL MOUNTED
EXTERIOR BELL
STROBE ONLY CEILING MOUNTED
SYMBOL DESCRIPTION
DOOR HOLDER
DOOR CLOSER
DETECTORS
GAS DETECTOR - CARBON MONOXIDE
SMOKE DETECTOR - IN DUCT
SMOKE DETECTOR - PHOTOELECTRIC
FLOW DETECTOR/SWITCH
VALVE SUPERVISORY SWITCH
SWITCHES
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
FIRE ALARM TRANSPONDER CABINET
NOTIFICATION CIRCUIT POWER BOOSTER
PANELS
STROBE ONLY WALL MOUNTED
HEAT DETECTOR - RATE OF RISE
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
CSSDLO
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
FIRE ALARM PLAN - FIRST FLOOR
FA-101
-3
F A
/2
/2
.p d f
SCALE: 1/8" = 1'-0"
FIRE ALARM PLAN - FIRST FLOOR
N
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
KEYNOTE LEGEND
KEY DESCRIPTION
FA02 57 °C (135 °F) RATE COMPENSATION HEAT DETECTION REQUIRED 2 FT FROM
SPRINKLERS INSTALLED IN HOISTWAY PIT. SMOKE DETECTION ALSO REQUIRED AT
PIT.
FA03 PROVIDE NECESSARY RELAYS AND MONITOR MODULES FOR PRIMARY AND
SECONDARY ELEVATOR RECALL, SHUNT TRIP (IF NECESSARY), AND FIREMAN'S HAT.
12/30/2022 A R C H I T E C T S E N G I N E E R S
135 241131 of 233131 of 233
W
Range
S P
F F
VS
WF
VS
WF
DH
DCL
F
F
S
CO
S
ID
S P
WF
VS
FAA
FACP
FATC
TPR
NAC
H R
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
CORRIDOR
2C02
GROUP ROOM C
20428
STORAGE
20434A
STORAGE
20428A
GROUP ROOM A
20431
STORAGE
20431A
WAITING
20427
ELEVATOR
LOBBY
2C06
BUILDING
ELECTRICAL
20408
BUILDING DATA
20447
STAFF BREAK
20449
GENDER
NEUTRAL TOILET
20445
FAMILY TOILET
20444
GENDER
NEUTRAL TOILET
20443
GENDER
NEUTRAL TOILET
20448
HVAC
20442
WAITING
20440
RECP.
WORKROOM
20424STAFF TOILET
20405
MH CLINIC
OFFICE
20478
STAFF TOILET
20466
RRTP TEACHING
KITCHEN
20454
MH CLINIC TMS
20457
RRTP KITCHEN
OFFICE
20453
MH CLINIC
OFFICE
20476
MH CLINIC
OFFICE
20474
MH CLINIC
OFFICE
20464
MH CLINIC
OFFICE
20462
MH CLINIC
OFFICE
20460
MH CLINIC
OFFICE
20461
MH CLINIC
OFFICE
20463
MH CLINIC
OFFICE
20458
MH CLINIC
OFFICE
20467
MH CLINIC
OFFICE
20469
MH CLINIC
OFFICE
20470
MH CLINIC
OFFICE
20468
MH CLINIC
OFFICE
20477
MH CLINIC
OFFICE
20479
MH CLINIC
OFFICE
20475
RRTP
COUNSELOR
20411
RRTP
COUNSELOR
20410
RRTP
COUNSELOR
20409
RRTP
COUNSELOR
20407
RRTP
COUNSELOR
20419
RRTP
COUNSELOR
20417
RRTP
COUNSELOR
20415
RRTP
COUNSELOR
20420
RRTP
COUNSELOR
20418
RRTP
COUNSELOR
20416
RRTP
COUNSELOR
20403
RRTP
COUNSELOR
20401
RRTP
COUNSELOR
20402
RRTP
COUNSELOR
20404
RRTP
COUNSELOR
20406
RRTP
COUNSELOR
20422
CORRIDOR
2C10
RECEPTION
20426
C
D
E
F
H
E.8
C.3
G
CORRIDOR
2C04
STORAGE
20446
HAC
20456
CORRIDOR
2C11
CORRIDOR
2C12
CORRIDOR
2C08
CORRIDOR
2C07
CORRIDOR
2C05
CORRIDOR
2C03
GROUP ROOM B
20434
FIRE ALARM SYMBOLS
DEVICES
COMBINATION OF SPEAKER/STROBE WALL MOUNTED
MANUAL PULL STATION
SPEAKER ONLY WALL MOUNTED
EXTERIOR BELL
STROBE ONLY CEILING MOUNTED
SYMBOL DESCRIPTION
DOOR HOLDER
DOOR CLOSER
DETECTORS
GAS DETECTOR - CARBON MONOXIDE
SMOKE DETECTOR - IN DUCT
SMOKE DETECTOR - PHOTOELECTRIC
FLOW DETECTOR/SWITCH
VALVE SUPERVISORY SWITCH
SWITCHES
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
FIRE ALARM TRANSPONDER CABINET
NOTIFICATION CIRCUIT POWER BOOSTER
PANELS
STROBE ONLY WALL MOUNTED
HEAT DETECTOR - RATE OF RISE
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
CSSDLO
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
FIRE ALARM PLAN - SECOND FLOOR
FA-102
-3
F A
/2
/2
.p d f
SCALE: 1/8" = 1'-0"
FIRE ALARM PLAN - SECOND FLOOR
N
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
12/30/2022 A R C H I T E C T S E N G I N E E R S
136 241132 of 233132 of 233
R
S P
S P
F F
VS
WF
VS
WF
DH
DCL
F
F
S
CO
S
ID
S P
WF
VS
FAA
FACP
FATC
TPR
NAC
H R
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
ADMIN WAIT
30409
GROUP ROOM C
30436
STORAGE
30441A
STORAGE
30436A
GROUP ROOM A
30437
STORAGE
30437A
GROUP ROOM B
30441
CORRIDOR
3C07
ELEVATOR
LOBBY
3C05
BUILDING
ELECTRICAL
30416
BUILDING DATA
30451
STAFF BREAK
30453
GENDER
NEUTRAL TOILET
30449
FAMILY TOILET
30448
GENDER
NEUTRAL TOILET
30447
GENDER
NEUTRAL TOILET
30452
HVAC
30446
WAITING
30442
RRTP OFFICE
30428
STAFF TOILET
30405
OFFICE
30459
OFFICE
30457
MH CLINIC ADMIN
30464
STAFF TOILET
30472
CORRIDOR
3C10
ADMIN CUBICLES
30423
MHICM PRIVATE
COUNSEL
30476
LOUNGE
30443
CHIEF OFFICE
30417
ADMIN
CONFERENCE
30418
MHICM STORAGE
30471
MHICM PATIENT
CARE
30478
MHICM MED
ROOM
30473
MHICM CUBICLES
30479
CORRIDOR
3C11
RECP.
WORKROOM
30430
RRTP OFFICE
30402
RRTP OFFICE
30404
RRTP OFFICE
30406
RRTP OFFICE
30401
RRTP OFFICE
30403
ADMIN RECP.
30415
ADMIN OFFICE
30426
CORRIDOR
3C02
MH CLINIC
OFFICE
30470
MH CLINIC
OFFICE
30468
MH CLINIC
OFFICE
30466
MH CLINIC
OFFICE
30465
MH CLINIC
OFFICE
30467
HAC
30462
RECEPTION
30432
FIRE ALARM TRANSPONDER CABINET
C
D
E
F
H
E.8
C.3
G
WEST STAIR
3S2
EAST STAIR
3S1
CORRIDOR
3C03
CORRIDOR
3C04
CORRIDOR
3C06
CORRIDOR
3C08
CORRIDOR
3C12
OFFICE
30461
OFFICE
30460
OFFICE
30456
OFFICE
30458
STORAGE
30450
FIRE ALARM SYMBOLS
DEVICES
COMBINATION OF SPEAKER/STROBE WALL MOUNTED
MANUAL PULL STATION
SPEAKER ONLY WALL MOUNTED
EXTERIOR BELL
STROBE ONLY CEILING MOUNTED
SYMBOL DESCRIPTION
DOOR HOLDER
DOOR CLOSER
DETECTORS
GAS DETECTOR - CARBON MONOXIDE
SMOKE DETECTOR - IN DUCT
SMOKE DETECTOR - PHOTOELECTRIC
FLOW DETECTOR/SWITCH
VALVE SUPERVISORY SWITCH
SWITCHES
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
FIRE ALARM TRANSPONDER CABINET
NOTIFICATION CIRCUIT POWER BOOSTER
PANELS
STROBE ONLY WALL MOUNTED
HEAT DETECTOR - RATE OF RISE
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
CSSDLO
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
FIRE ALARM PLAN - THIRD FLOOR
FA-103
-3
F A
/2
/2
.p d f
SCALE: 1/8" = 1'-0"
FIRE ALARM PLAN - THIRD FLOOR
N
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
12/30/2022 A R C H I T E C T S E N G I N E E R S
137 241133 of 233133 of 233
WF VS
ID
S
ID
S
ID
S
ID
S
ID
DH
DCL
F
F
S
CO
S
ID
S P
WF
VS
FAA
FACP
FATC
TPR
NAC
H R
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
A
B
C
D
E
F
H
E.8
C.3
G
MECHANICAL
40401
FA01
FA01
FA01
FA01
FA01
FIRE ALARM SYMBOLS
DEVICES
COMBINATION OF SPEAKER/STROBE WALL MOUNTED
MANUAL PULL STATION
SPEAKER ONLY WALL MOUNTED
EXTERIOR BELL
STROBE ONLY CEILING MOUNTED
SYMBOL DESCRIPTION
DOOR HOLDER
DOOR CLOSER
DETECTORS
GAS DETECTOR - CARBON MONOXIDE
SMOKE DETECTOR - IN DUCT
SMOKE DETECTOR - PHOTOELECTRIC
FLOW DETECTOR/SWITCH
VALVE SUPERVISORY SWITCH
SWITCHES
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
FIRE ALARM TRANSPONDER CABINET
NOTIFICATION CIRCUIT POWER BOOSTER
PANELS
STROBE ONLY WALL MOUNTED
HEAT DETECTOR - RATE OF RISE
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
CSSDLO
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
FIRE ALARM PLAN - ATTIC
FA-104
-3
F A
/2
/2
.p d f
SCALE: 1/8" = 1'-0"
FIRE ALARM PLAN - ATTIC
N
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
KEYNOTE LEGEND
KEY DESCRIPTION
FA01 PROVIDE DUCT SMOKE DETECTORS AT SUPPLY SYSTEMS HAVING CAPACITIES
GREATER THAN 2,000 CFM AND AT RETURN SYSTEMS HAVING CAPACITIES GREATER
THAN 15,000 CFM.
12/30/2022 A R C H I T E C T S E N G I N E E R S
138 241134 of 233134 of 233
B
FX01
FX03
C
D
E
F
H
E.8
C.3
G
6" F
6" F
6" F
UP TO SPRINKLER RISER
UP TO SPRINKLER RISER
FX01
FX05
FX07 FX07
FX07
FX07
FX09
SPRINKLER PROVIDED
UNDERNEATH ACCESSIBLE
LANDING
FX12
FX12
1. THIS FACILITY IS TO BE PROTECTED THROUGHOUT WITH AN AUTOMATIC WET-PIPE
SPRINKLER SYSTEM PER THE PROJECT REQUIREMENTS BY THE OWNER.
2. THE DESIGN AND INSTALLATION OF THE WET-PIPE SPRINKLER SYSTEM SHALL BE
IN ACCORDANCE WITH NFPA 13 (2019 EDITION), NFPA 14 (2016 EDITION), NFPA 24
(2019 EDITION), THE VA FIRE PROTECTION DESIGN MANUAL, AND THE DESIGN
DOCUMENTS.
3. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ALL PIPE ROUTING AND
DETAILS SHOWN SHALL BE CONFIRMED BY THE FIRE PROTECTION CONTRACTOR
AND FULLY COORDINATED WITH ALL DISCIPLINES. THE FIRE PROTECTION
CONTRACTOR SHALL FURNISH COMPLETE CONSTRUCTION SHOP DRAWINGS
SHOWING ALL SPRINKLER, PIPE, VALVE AND DRAIN LOCATIONS.
4. THERE ARE TWO SPRINKLER ZONES PER OCCUPIED FLOOR AND ONE IN THE
ATTIC. THE ZONE LAYOUT WILL REMAIN AND BE ALTERED TO ACCOMMODATE THE
ADDITION.
5. SPRINKLER SYSTEMS SHALL BE HYDRAULICALLY CALCULATED IN ACCORDANCE
WITH NFPA 13.
6. EXISTING WET-MANUAL CLASS I STANDPIPES AND SPRINKLER RISERS ARE
LOCATED IN THE EXIT STAIRWELLS. EXISTING STANDPIPES AND HOSE VALVE
LOCATIONS SHALL REMAIN.
7. A NEW DOUBLE CHECK BACKFLOW PREVENTER SHALL BE INSTALLED IN THE SUB-
BASEMENT AT THE LOCATION OF THE INCOMING WATER.
8. CHROME QUICK RESPONSE SEMI-RECESSED PENDENT SPRINKLERS SHALL BE
INSTALLED IN ALL AREAS WITH FINISHED CEILINGS. IN AREAS WITHOUT FINISHED
CEILINGS BRASS UPRIGHT SPRINKLERS SHALL BE INSTALLED.
9. SPRINKLERS ARE SHOWN IN AREAS WITH FINISHED CEILINGS FOR COORDINATION
PURPOSES. INSTALLING CONTRACTOR TO VERIFY FINAL LAYOUT COMPLIANT WITH
VA STANDARDS AND NFPA 13.
10. IN LOCATIONS WITH ACOUSTICAL CEILING TILES SPRINKLERS SHALL BE LOCATED
IN THE CENTER OF TILES.
11. THE MAXIMUM COVERAGE PER SPRINKLER IS 225 SQUARE FEET FOR LIGHT
HAZARD AREAS AND 130 SQUARE FEET FOR ORDINARY HAZARD AREAS.
12. ALL HANGERS SHALL BE PROVIDED AND INSTALLED IN ACCORDANCE WITH NFPA
13.
13. ALL VALVES (DRAIN, INSPECTOR'S TEST, CONTROL) SHALL BE IDENTIFIED AS
REQUIRED BY NFPA 13.
14. PROVISIONS FOR DRAINING OF SPRINKLER PIPING SHALL BE PROVIDED IN
ACCORDANCE WITH NFPA 13.
15. ALL DRAINS AND TEST CONNECTIONS SHALL DISCHARGE TO A SAFE LOCATION
OUTSIDE THE BUILDING.
16. LOCATIONS SUBJECT TO FREEZING SHALL BE PROTECTED WITH LISTED DRY
SPRINKLER ASSEMBLIES.
17. THE ATTIC SPACE IS TO BE CONDITIONED AND PROTECTED WITH A WET PIPE
SYSTEM.
18. SPRINKLER TEMPERATURE RATINGS NEAR HVAC DIFFUSERS SHALL BE IN
ACCORDANCE WITH NFPA 13, SECTION 8.3.2.
19. COMMUNICATIONS ROOMS AND MECHANICAL ROOMS SHALL BE PROTECTED
USING INTERMEDIATE TEMPERATURE RATED SPRINKLERS.
20. PIPE 2" AND LESS IN DIAMETER SHALL BE SCHEDULE 40, PIPE GREATER THAN 2" IN
DIAMETER SHALL BE SCHEDULE 10.
21. PIPE SIZES INDICATED ON DRAWINGS ARE PRELIMINARY. FINAL SIZES SHALL BE
DETERMINED BY INSTALLING CONTRACTOR HYDRAULIC CALCULATIONS.
22. TO AID IN PREVENTION OF PIPE CORROSION INSTALL AUTOMATIC AIR VENTING
NEAR A HIGH POINT ON EACH SYSTEM PER NFPA 13.
23. THE CONTRACTOR SHALL PERFORM A HYDRANT FLOW TEST PRIOR TO SYSTEM
CALCULATION TO DETERMINE AVAILABLE WATER PRESSURE AND FLOW BUT,
SHALL USE THE FOLLOWING FLOW TEST DATA AS THE BASIS OF THEIR DESIGN
UNLESS THE CONFIRMING FLOW TEST DATA IS WORSE:
STATIC: 87 PSI
RESIDUAL: 62 PSI
FLOW: 1033 GPM
TEST DATE: FALL 2018 BY TOMAH VA F.D.
FIRE SUPPRESSION GENERAL NOTES
FIRE SUPPRESSION HATCH LEGEND
ORDINARY HAZARD I
DENSITY: 0.15 GPM/SQFT OVER 1500 SQFT
LIGHT HAZARD
DENSITY: 0.10 GPM/SQFT OVER 1500 SQFT
ORDINARY HAZARD II
DENSITY: 0.20 GPM/SQFT OVER 1500 SQFT
SPRINKLER HEAD - CONCEALED PENDANT
SPRINKLER HEAD - UPRIGHT
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
CSSDLO
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
FIRE SUPPRESSION PLAN -
BASEMENT
FX-100
-3
F X
/2
/2
.p d f
SCALE: 1/8" = 1'-0"
FIRE SUPPRESSION PLAN - BASEMENT
N
KEYNOTE LEGEND
KEY DESCRIPTION
FX01 EXISTING STANDPIPES AND BULK FEED PIPING TO STANDPIPES SHALL REMAIN.
EXISTING 2-1/2" HOSE CONNECTIONS SHALL REMAIN
FX03 EXISTING PIPING TO REMOTE FIRE DEPARTMENT CONNECTION TO REMAIN.
FX05 INSTALL DOUBLE CHECK BACKFLOW PREVENTER AT LOCATION OF PREVIOUS
VALVES.
FX07 NO SPRINKLER PROTECTION REQUIRED IN GREY SHADED AREA OF BASEMENT.
LIMITED ACCESS NON-COMBUSTIBLE SPACES.
FX09 INSTALL NEW SPRINKLERS AND ASSOCIATED PIPING IN BASEMENT. INSTALL
SPRINKLERS UNDER OBSTRUCTIONS PER NFPA 13.
FX12 SPRINKLER PROTECTION REQUIRED AT ELEVATOR HOISTWAY PIT. RATE HEAT
DETECTION REQUIRED 2 FT FROM SPRINKLERS.
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
12/30/2022 A R C H I T E C T S E N G I N E E R S
205 241135 of 233135 of 233
DN
A
B
EAST SPRINKLER ZONE WEST SPRINKLER ZONE
FX01
FX01
C
D
E
F
H
E.8
C.3
G
3" F
1 1/2" F
1 1/2" F
3" F
3" F
1 1/2" F
1 1/2" F
1 1/2" F
3" F
FX06
FX06
RRTP OFFICES
10426
WORKROOM
10466
MH CLINIC
EXAM/VITALS
10475
CORRIDOR
1C02
TREATMENT
OBSERVATION
10451
NURSE STATION
10452
GENDER
NEUTRAL TOILET
10447
MOTHERS ROOM
10446
GROUP ROOM C
10430
ELEVATOR
LOBBY
1C06
STORAGE
10438A
STORAGE
10430A
GROUP ROOM A
10435
STORAGE
10435A
HALL
1C10
FAMILY TOILET
10444
SPECIMEN
TOILET
10454
MH CLINIC
OFFICE
10479
STAFF TOILET
10476
MH CLINIC
OFFICE
10473
MH CLINIC
OFFICE
10471
MH CLINIC
OFFICE
10477
MH CLINIC
OFFICE
10480
MH CLINIC
MED/SUPPLY
10474
MH CLINIC
OFFICE
10470
MH CLINIC
OFFICE (FUTURE
EXAM)
10478
MH CLINIC
OFFICE
10485
MH CLINIC
OFFICE
10472
MH CLINIC
TELEMED OFFICE
10484
GENDER
NEUTRAL TOILET
10445
BUILDING DATA
10449
TREATMENT
OBSERVATION
10453
TREATMENT
CIRCULATION
10450
ADMIN OFFICE
10420
RRTP
COUNSELOR
10404
EAST STAIR
1S1
BED BUG ZAPPER
10414
RRTP SECURITY
OFFICE
10419
RRTP
COUNSELOR
10405
RRTP VITALS &
LOCKERS
10416
RRTP WAITING
10417
MAIN
ELECTRICAL
10411
WEST STAIR
1S2
MAIN CORRIDOR
1C05
GROUP ROOM B
10438
FAMILY WAITING
10465
WAITING
10424
LOUNGE
10425
VENDING
10422
INFO DESK
10442
RECEPTION
10460
VESTIBULE
10440
TRAM WALKWAY
1C20
TESTING OFFICE
10401
GROUP TESTING
10400
MH CLINIC
TELEMED OFFICE
10486
MH CLINIC
TELEMED OFFICE
10488
MH CLINIC
TELEMED OFFICE
10489
MH CLINIC
OFFICE
10487
WAITING
10443
CORRIDOR
1C04
CORRIDOR
1C07
CORRIDOR
1C08
CORRIDOR
1C11
CORRIDOR
1C12
RECEIVING
10499
EMR
10412
ELECTRICAL
CLOSET
10413
STORAGE
10415
ELECTRICAL
10415A
RRTP TOILET
10418
HAC
10464
RRTP FOYER
10427
MAIN
ELECTRICAL
10411
SPRINKLER PROVIDED
UNDERNEATH ACCESSIBLE
LANDING
FX12
FX12
FX13
FX13
FX13
FX13
FX13
FX13
FIRE SUPPRESSION HATCH LEGEND
ORDINARY HAZARD I
DENSITY: 0.15 GPM/SQFT OVER 1500 SQFT
LIGHT HAZARD
DENSITY: 0.10 GPM/SQFT OVER 1500 SQFT
ORDINARY HAZARD II
DENSITY: 0.20 GPM/SQFT OVER 1500 SQFT
SPRINKLER HEAD - CONCEALED PENDANT
SPRINKLER HEAD - UPRIGHT
1. THIS FACILITY IS TO BE PROTECTED THROUGHOUT WITH AN AUTOMATIC WET-PIPE
SPRINKLER SYSTEM PER THE PROJECT REQUIREMENTS BY THE OWNER.
2. THE DESIGN AND INSTALLATION OF THE WET-PIPE SPRINKLER SYSTEM SHALL BE
IN ACCORDANCE WITH NFPA 13 (2019 EDITION), NFPA 14 (2016 EDITION), NFPA 24
(2019 EDITION), THE VA FIRE PROTECTION DESIGN MANUAL, AND THE DESIGN
DOCUMENTS.
3. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ALL PIPE ROUTING AND
DETAILS SHOWN SHALL BE CONFIRMED BY THE FIRE PROTECTION CONTRACTOR
AND FULLY COORDINATED WITH ALL DISCIPLINES. THE FIRE PROTECTION
CONTRACTOR SHALL FURNISH COMPLETE CONSTRUCTION SHOP DRAWINGS
SHOWING ALL SPRINKLER, PIPE, VALVE AND DRAIN LOCATIONS.
4. THERE ARE TWO SPRINKLER ZONES PER OCCUPIED FLOOR AND ONE IN THE
ATTIC. THE ZONE LAYOUT WILL REMAIN AND BE ALTERED TO ACCOMMODATE THE
ADDITION.
5. SPRINKLER SYSTEMS SHALL BE HYDRAULICALLY CALCULATED IN ACCORDANCE
WITH NFPA 13.
6. EXISTING WET-MANUAL CLASS I STANDPIPES AND SPRINKLER RISERS ARE
LOCATED IN THE EXIT STAIRWELLS. EXISTING STANDPIPES AND HOSE VALVE
LOCATIONS SHALL REMAIN.
7. A NEW DOUBLE CHECK BACKFLOW PREVENTER SHALL BE INSTALLED IN THE SUB-
BASEMENT AT THE LOCATION OF THE INCOMING WATER.
8. CHROME QUICK RESPONSE SEMI-RECESSED PENDENT SPRINKLERS SHALL BE
INSTALLED IN ALL AREAS WITH FINISHED CEILINGS. IN AREAS WITHOUT FINISHED
CEILINGS BRASS UPRIGHT SPRINKLERS SHALL BE INSTALLED.
9. SPRINKLERS ARE SHOWN IN AREAS WITH FINISHED CEILINGS FOR COORDINATION
PURPOSES. INSTALLING CONTRACTOR TO VERIFY FINAL LAYOUT COMPLIANT WITH
VA STANDARDS AND NFPA 13.
10. IN LOCATIONS WITH ACOUSTICAL CEILING TILES SPRINKLERS SHALL BE LOCATED
IN THE CENTER OF TILES.
11. THE MAXIMUM COVERAGE PER SPRINKLER IS 225 SQUARE FEET FOR LIGHT
HAZARD AREAS AND 130 SQUARE FEET FOR ORDINARY HAZARD AREAS.
12. ALL HANGERS SHALL BE PROVIDED AND INSTALLED IN ACCORDANCE WITH NFPA
13.
13. ALL VALVES (DRAIN, INSPECTOR'S TEST, CONTROL) SHALL BE IDENTIFIED AS
REQUIRED BY NFPA 13.
14. PROVISIONS FOR DRAINING OF SPRINKLER PIPING SHALL BE PROVIDED IN
ACCORDANCE WITH NFPA 13.
15. ALL DRAINS AND TEST CONNECTIONS SHALL DISCHARGE TO A SAFE LOCATION
OUTSIDE THE BUILDING.
16. LOCATIONS SUBJECT TO FREEZING SHALL BE PROTECTED WITH LISTED DRY
SPRINKLER ASSEMBLIES.
17. THE ATTIC SPACE IS TO BE CONDITIONED AND PROTECTED WITH A WET PIPE
SYSTEM.
18. SPRINKLER TEMPERATURE RATINGS NEAR HVAC DIFFUSERS SHALL BE IN
ACCORDANCE WITH NFPA 13, SECTION 8.3.2.
19. COMMUNICATIONS ROOMS AND MECHANICAL ROOMS SHALL BE PROTECTED
USING INTERMEDIATE TEMPERATURE RATED SPRINKLERS.
20. PIPE 2" AND LESS IN DIAMETER SHALL BE SCHEDULE 40, PIPE GREATER THAN 2" IN
DIAMETER SHALL BE SCHEDULE 10.
21. PIPE SIZES INDICATED ON DRAWINGS ARE PRELIMINARY. FINAL SIZES SHALL BE
DETERMINED BY INSTALLING CONTRACTOR HYDRAULIC CALCULATIONS.
22. TO AID IN PREVENTION OF PIPE CORROSION INSTALL AUTOMATIC AIR VENTING
NEAR A HIGH POINT ON EACH SYSTEM PER NFPA 13.
23. THE CONTRACTOR SHALL PERFORM A HYDRANT FLOW TEST PRIOR TO SYSTEM
CALCULATION TO DETERMINE AVAILABLE WATER PRESSURE AND FLOW BUT,
SHALL USE THE FOLLOWING FLOW TEST DATA AS THE BASIS OF THEIR DESIGN
UNLESS THE CONFIRMING FLOW TEST DATA IS WORSE:
STATIC: 87 PSI
RESIDUAL: 62 PSI
FLOW: 1033 GPM
TEST DATE: FALL 2018 BY TOMAH VA F.D.
FIRE SUPPRESSION GENERAL NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Todd Thelen
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
CSSDLO
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
FIRE SUPPRESSION PLAN - FIRST
FLOOR
FX-101
-3
F X
/0
/2
.p d f
SCALE: 1/8" = 1'-0"
FIRE SUPPRESSION PLAN - FIRST FLOOR
N
KEYNOTE LEGEND
KEY DESCRIPTION
FX01 EXISTING STANDPIPES AND BULK FEED PIPING TO STANDPIPES SHALL REMAIN.
EXISTING 2-1/2" HOSE CONNECTIONS SHALL REMAIN
FX06 INSTALL NEW FLOOR CONTROL ASSEMBLIES AT EACH SYSTEM.
FX12 SPRINKLER PROTECTION REQUIRED AT ELEVATOR HOISTWAY PIT. RATE HEAT
DETECTION REQUIRED 2 FT FROM SPRINKLERS.
FX13 CEILING IN THIS ROOM TO REMAIN, CONTRACTOR TO REMOVE AND REPLACE
TILES AS NECESSARY TO INSTALL NEW SPRINKLER HEADS.
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
12/30/2022 A R C H I T E C T S E N G I N E E R S
140 241136 of 233136 of 233
B
FX01
FX01
EAST SPRINKLER ZONE WEST SPRINKLER ZONE
C
D
E
F
H
E.8
C.3
G
3" F
1 1/2" F 3" F
3" F
1 1/2" F
3" F
1 1/2" F
3" F
1 1/2" F
3" F
FX06
FX06
CORRIDOR
2C02
GROUP ROOM C
20428
STORAGE
20434A
STORAGE
20428A
GROUP ROOM A
20431
STORAGE
20431A
WAITING
20427
ELEVATOR
LOBBY
2C06
BUILDING
ELECTRICAL
20408
BUILDING DATA
20447
STAFF BREAK
20449
GENDER
NEUTRAL TOILET
20445
FAMILY TOILET
20444
GENDER
NEUTRAL TOILET
20443
GENDER
NEUTRAL TOILET
20448
HVAC
20442
WAITING
20440
RECP.
WORKROOM
20424
STAFF TOILET
20405
MH CLINIC
OFFICE
20478
STAFF TOILET
20466
RRTP TEACHING
KITCHEN
20454
MH CLINIC TMS
20457
RRTP KITCHEN
OFFICE
20453
MH CLINIC
OFFICE
20476
MH CLINIC
OFFICE
20474
MH CLINIC
OFFICE
20464
MH CLINIC
OFFICE
20462
MH CLINIC
OFFICE
20460
MH CLINIC
OFFICE
20461
MH CLINIC
OFFICE
20463
MH CLINIC
OFFICE
20458
MH CLINIC
OFFICE
20467
MH CLINIC
OFFICE
20469
MH CLINIC
OFFICE
20470
MH CLINIC
OFFICE
20468
MH CLINIC
OFFICE
20477
MH CLINIC
OFFICE
20479
MH CLINIC
OFFICE
20475
RRTP
COUNSELOR
20411 RRTP
COUNSELOR
20410
RRTP
COUNSELOR
20409
RRTP
COUNSELOR
20407
RRTP
COUNSELOR
20419
RRTP
COUNSELOR
20417
RRTP
COUNSELOR
20415
RRTP
COUNSELOR
20420
RRTP
COUNSELOR
20418
RRTP
COUNSELOR
20416
RRTP
COUNSELOR
20403
RRTP
COUNSELOR
20401
RRTP
COUNSELOR
20402
RRTP
COUNSELOR
20404
RRTP
COUNSELOR
20406 RRTP
COUNSELOR
20422
CORRIDOR
2C10
RECEPTION
204…