Attachment 13 - Drawing Part 10 676-325 Renovate B404 - Plumbing.pdf
PDF 4 MB Posted
- Attached to
- Y1DA--Minor Construction - Tomah VAMC 676-325 Expand and Renovate B404 for Outpatient Mental Health
- Solicitation number
- 36C77623B0050_1
About this file
This set of construction documents outlines the scope of work for a plumbing renovation project at the Tomah VA Medical Center in Tomah, Wisconsin. The project involves expanding and renovating building B404 for outpatient mental health services.
The documents include plumbing plans, schedules, details and riser diagrams. They specify fixture types and locations, pipe sizes and routing, and equipment such as pumps and water heaters. Bidders will demolish existing plumbing and install new systems to serve additional exam rooms, counseling offices and support spaces. Storm and sanitary drainage will be upgraded. Hot water circulation will be improved with a new recirculation system.
The documents also describe bid deduct options to remove proposed additions and renovations in certain areas. This will allow the VA to adjust the project scope as needed. Construction is scheduled to begin in early 2023.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. FIELD VERIFY EXISTING CONDITIONS PRIOR TO START OF ANY WORK. EXISTING
EQUIPMENT, PIPING AND ACCESSORIES ARE SHOWN FOR REFERENCE ONLY.
2. WHERE FLOOR DRAINS OCCUR WITHIN THE LIMITS OF CONSTRUCTION, PREVENT
CONSTRUCTION DEBRIS FROM ENTERING DRAIN BODY BY SEALING DRAIN
OPENING PRIOR TO START OF WORK. UNSEAL DRAINS AT COMPLETION OF
CONSTRUCTION.
3. PIPE SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF FLOW UNTIL
ANOTHER SIZE IS SHOWN.
4. UNUSED EXISTING SANITARY VENT THROUGH ROOF AND ALL ASSOCIATED PIPING
TO BE REMOVED. COORDIANTE ROOF PATCHING WITH GENERAL CONTRACTOR.
PLUMBING DEMOLITION GENERAL NOTES
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 43
A
B
C
C.3
D
E
E.8
F
G
H
6" SANITARY WASTE
I.E.=94'-5".
4" CW
I.E.=92'-4".
A.8
7.66.4
PD02
PD01 PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD03
PD03
PD03
PD03
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD05 PD05
PD01
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
AAKGJH
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
PLUMBING DEMOLITION PLAN
UNDERFLOOR AND BASEMENT
PD-100
-3
P D
/1
/2
.p d f
KEYNOTE LEGEND
KEY DESCRIPTION
PD01 DEMOLISH EXISTING PLUMBING FIXTURES AND ASSOCIATED WASTE, VENT,
DOMESTIC WATER PIPING AND ACCESSORIES.
PD02 DEMOLISH EXISTING STEAM WATER HEATER AND ALL ASSOCIATED PIPING
CONNECTIONS.
PD03 EXISTING PLUMBING FIXTURE TO REMAIN. DEMOLISH ASSOCIATED WASTE, VENT,
DOMESTIC WATER PIPING AND ACCESSORIES.
PD04 DEMOLISH EXISTING STORM DRAINAGE RISER PIPING. EXISTING GUTTER ROUGH-IN
ON THE ROOF TO REMAIN FOR CONNECTION OF NEW PIPING AS SHOWN ON THE
CONSTRUCTION DRAWINGS.
PD05 DEMOLISH EXISTING STORM DRAINAGE PIPING IN CRAWL SPACE. TO EXISTING
STORM DRAINAGE CONNECTION OUTSIDE OF BUILDING.
8'
SCALE : 1/16" = 1'-0"
0 16' 32'
1/8" = 1'-0"PD100
1 PLUMBING DEMOLITION PLAN - UNDERFLOOR AND BASEMENT
CALENN
HEPPNER
E-48270
12/30/2022 A R C H I T E C T S E N G I N E E R S
CB DESIGN
GROUP
183 237 179 of 233179 of 233
2. WHERE FLOOR DRAINS OCCUR WITHIN THE LIMITS OF CONSTRUCTION, PREVENT
CONSTRUCTION DEBRIS FROM ENTERING DRAIN BODY BY SEALING DRAIN
OPENING PRIOR TO START OF WORK. UNSEAL DRAINS AT COMPLETION OF
CONSTRUCTION.
3. PIPE SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF FLOW UNTIL
ANOTHER SIZE IS SHOWN.
4. UNUSED EXISTING SANITARY VENT THROUGH ROOF AND ALL ASSOCIATED PIPING
TO BE REMOVED. COORDIANTE ROOF PATCHING WITH GENERAL CONTRACTOR.
PLUMBING DEMOLITION GENERAL NOTES
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 43
A
B
C
C.3
D
E
E.8
F
G
H
A.8
7.66.4
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01 PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD03
PD03
PD03
PD03
PD01
PD01
PD04
PD04
PD04
PD04
PD04
PD04
PD04 PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
AAKGJH
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
PLUMBING DEMOLITION PLAN
LEVEL 1
PD-101
-3
P D
/1
/2
.p d f
KEYNOTE LEGEND
KEY DESCRIPTION
PD01 DEMOLISH EXISTING PLUMBING FIXTURES AND ASSOCIATED WASTE, VENT,
DOMESTIC WATER PIPING AND ACCESSORIES.
PD03 EXISTING PLUMBING FIXTURE TO REMAIN. DEMOLISH ASSOCIATED WASTE, VENT,
DOMESTIC WATER PIPING AND ACCESSORIES.
PD04 DEMOLISH EXISTING STORM DRAINAGE RISER PIPING. EXISTING GUTTER ROUGH-IN
ON THE ROOF TO REMAIN FOR CONNECTION OF NEW PIPING AS SHOWN ON THE
CONSTRUCTION DRAWINGS.
8'
SCALE : 1/16" = 1'-0"
0 16' 32'
1/8" = 1'-0"PD101
1 PLUMBING DEMOLITION PLAN - LEVEL 1
CALENN
HEPPNER
E-48270
12/30/2022 A R C H I T E C T S E N G I N E E R S
184 237 180 of 233180 of 233
2. WHERE FLOOR DRAINS OCCUR WITHIN THE LIMITS OF CONSTRUCTION, PREVENT
CONSTRUCTION DEBRIS FROM ENTERING DRAIN BODY BY SEALING DRAIN
OPENING PRIOR TO START OF WORK. UNSEAL DRAINS AT COMPLETION OF
CONSTRUCTION.
3. PIPE SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF FLOW UNTIL
ANOTHER SIZE IS SHOWN.
4. UNUSED EXISTING SANITARY VENT THROUGH ROOF AND ALL ASSOCIATED PIPING
TO BE REMOVED. COORDIANTE ROOF PATCHING WITH GENERAL CONTRACTOR.
PLUMBING DEMOLITION GENERAL NOTES
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 43
A
B
C
C.3
D
E
E.8
F
G
H
A.8
7.66.4
PD01
PD01
PD01
PD01
PD01PD01PD01
PD01
PD01 PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01 PD01
PD01
PD01
PD01 PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01 PD01
PD01
PD01
PD01 PD01
PD01
PD01
PD01
PD01
PD01
PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04 PD04
PD04
PD01
PD04
PD04
PD04
PD04
PD04
PD04
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
AAKGJH
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
PLUMBING DEMOLITION PLAN
LEVEL 2
PD-102
-3
P D
/1
/2
.p d f
KEYNOTE LEGEND
KEY DESCRIPTION
PD01 DEMOLISH EXISTING PLUMBING FIXTURES AND ASSOCIATED WASTE, VENT,
DOMESTIC WATER PIPING AND ACCESSORIES.
PD04 DEMOLISH EXISTING STORM DRAINAGE RISER PIPING. EXISTING GUTTER ROUGH-IN
ON THE ROOF TO REMAIN FOR CONNECTION OF NEW PIPING AS SHOWN ON THE
CONSTRUCTION DRAWINGS.
8'
SCALE : 1/16" = 1'-0"
0 16' 32'
1/8" = 1'-0"PD102
1 PLUMBING DEMOLITION PLAN - LEVEL 2
CALENN
HEPPNER
E-48270
12/30/2022 A R C H I T E C T S E N G I N E E R S
185 237 181 of 233181 of 233
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 43
A
B
C
C.3
D
E
E.8
F
G
H
A.8
7.66.4
PD01
PD01
PD01
PD01
PD01PD01PD01
PD03
PD01
PD01
PD01 PD01
PD01
PD01PD01
PD01
PD03
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD03
PD03
PD01
PD01
PD01
PD01
PD03
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD03
PD01 PD01
PD01
PD01
PD01PD01
PD04
PD04
PD04
PD04
PD04
PD04 PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD01
PD04
PD04
PD01
1. FIELD VERIFY EXISTING CONDITIONS PRIOR TO START OF ANY WORK. EXISTING
EQUIPMENT, PIPING AND ACCESSORIES ARE SHOWN FOR REFERENCE ONLY.
2. WHERE FLOOR DRAINS OCCUR WITHIN THE LIMITS OF CONSTRUCTION, PREVENT
CONSTRUCTION DEBRIS FROM ENTERING DRAIN BODY BY SEALING DRAIN
OPENING PRIOR TO START OF WORK. UNSEAL DRAINS AT COMPLETION OF
CONSTRUCTION.
3. PIPE SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF FLOW UNTIL
ANOTHER SIZE IS SHOWN.
4. UNUSED EXISTING SANITARY VENT THROUGH ROOF AND ALL ASSOCIATED PIPING
TO BE REMOVED. COORDIANTE ROOF PATCHING WITH GENERAL CONTRACTOR.
PLUMBING DEMOLITION GENERAL NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
AAKGJH
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
PLUMBING DEMOLITION PLAN
LEVEL 3
PD-103
-3
P D
/1
/2
.p d f
KEYNOTE LEGEND
KEY DESCRIPTION
PD01 DEMOLISH EXISTING PLUMBING FIXTURES AND ASSOCIATED WASTE, VENT,
DOMESTIC WATER PIPING AND ACCESSORIES.
PD03 EXISTING PLUMBING FIXTURE TO REMAIN. DEMOLISH ASSOCIATED WASTE, VENT,
DOMESTIC WATER PIPING AND ACCESSORIES.
PD04 DEMOLISH EXISTING STORM DRAINAGE RISER PIPING. EXISTING GUTTER ROUGH-IN
ON THE ROOF TO REMAIN FOR CONNECTION OF NEW PIPING AS SHOWN ON THE
CONSTRUCTION DRAWINGS.
8'
SCALE : 1/16" = 1'-0"
0 16' 32'
1/8" = 1'-0"PD103
1 PLUMBING DEMOLITION PLAN - LEVEL 3
CALENN
HEPPNER
E-48270
12/30/2022 A R C H I T E C T S E N G I N E E R S
186 237 182 of 233182 of 233
B
C
C.3
D
E
E.8
F
G
H
A.8
7.66.4
PD01
PD01
PD01
PD01
PD01
PD01
PD01
PD04
PD04
PD04
PD04
PD04
PD04 PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04
PD04PD04
PD04
PD04
1. FIELD VERIFY EXISTING CONDITIONS PRIOR TO START OF ANY WORK. EXISTING
EQUIPMENT, PIPING AND ACCESSORIES ARE SHOWN FOR REFERENCE ONLY.
2. WHERE FLOOR DRAINS OCCUR WITHIN THE LIMITS OF CONSTRUCTION, PREVENT
CONSTRUCTION DEBRIS FROM ENTERING DRAIN BODY BY SEALING DRAIN
OPENING PRIOR TO START OF WORK. UNSEAL DRAINS AT COMPLETION OF
CONSTRUCTION.
3. PIPE SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF FLOW UNTIL
ANOTHER SIZE IS SHOWN.
4. UNUSED EXISTING SANITARY VENT THROUGH ROOF AND ALL ASSOCIATED PIPING
TO BE REMOVED. COORDIANTE ROOF PATCHING WITH GENERAL CONTRACTOR.
PLUMBING DEMOLITION GENERAL NOTES
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
AAKGJH
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
PLUMBING DEMOLITION PLAN
ATTIC & ROOF
PD-104
-3
P D
/3
/2
.p d f
1/8" = 1'-0"PD104
1 PLUMBING PLAN - ATTIC
KEYNOTE LEGEND
KEY DESCRIPTION
PD01 DEMOLISH EXISTING PLUMBING FIXTURES AND ASSOCIATED WASTE, VENT,
DOMESTIC WATER PIPING AND ACCESSORIES.
PD04 DEMOLISH EXISTING STORM DRAINAGE RISER PIPING. EXISTING GUTTER ROUGH-IN
ON THE ROOF TO REMAIN FOR CONNECTION OF NEW PIPING AS SHOWN ON THE
CONSTRUCTION DRAWINGS.
8'
SCALE : 1/16" = 1'-0"
0 16' 32'
CALENN
HEPPNER
E-48270
12/30/2022 A R C H I T E C T S E N G I N E E R S
187 237 183 of 233183 of 233
1. FIELD VERIFY ALL NEW WATER, WASTE, AND VENT PIPING CONNECTIONS AND
PROVIDE NEW CONNECTIONS AS REQUIRED FOR PROPERLY OPERATING
SYSTEMS.
2. FIELD VERIFY LOCATION AND INVERTS OF SITE UTILITIES PRIOR TO INSTALLATION.
3. PROVIDE CLEANOUT IN ACCESSIBLE LOCATION AT THE BASE OF ALL PLUMBING
RISERS AND AT ALL CHANGES OF DIRECTION.
4. ROUTE DOMESTIC WATER AND SANITARY SEWER SERVICES TO SITE UTILITIES
5'-0" FROM BUILDING UNLESS NOTED OTHERWISE. REFER TO CIVIL PLANS.
5. MINIMUM SIZE OF PLUMBING VENT THRU ROOF SHALL BE 4' AND LOCATED A
MINIMUM OF 24" FROM ANY WALL OR VERTICAL SURFACE. A MINIMUM OF 12"
ABOVE FINISHED ROOF MATERIAL, AND A MINIMUM OF 12' FROM FRESH AIR
INTAKES.
6. INSTALL WATER HAMMER ARRESTORS IN WATER LINES AT CONNECTIONS TO ANY
QUICK CLOSING VALVES LIKE FIXTURES.
7. WASTE AND VENT PIPING BELOW FLOOR AND THROUGH FLOOR SHALL BE 2"
MINIMUM.
8. REFER TO PLUMBING DETAILS FOR ACCESSORIES AND FINAL CONNECTIONS TO
PLUMBING EQUIPMENT.
9. PITCH UNDERFLOOR SANITARY WASTE PIPING 4" AND GREATER AT 1/8" PER FOOT,
UNLESS NOTED OTHERWISE. PITCH ALL OTHER SANITARY WASTE PIPING AT 1/4"
PER FOOT UNLESS NOTED OTHERWISE.
10. INSTALL HORIZONTAL SANITARY VENT PIPING SLOPED AT 1/8" PER FOOT.
11. INSTALL HORIZONTAL STORM DRAINAGE PIPING SLOPED AT 1/4" PER FOOT.
12. MINIMIZE DOMESTIC WATER DEAD LEG PIPING TO 6" OR LESS.
13. REFER TO PLUMBING RISER DIAGRAMS FOR ADDITIONAL ROUTING AND PIPE
SIZING INFORMATION.
14. INSTALL EXTERIOR WALL HYDRANTS 1'- 6" ABOVE FINISHED FLOOR ELEVATION.
PLUMBING GENERAL NOTES
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 43
A
B
C
C.3
D
E
E.8
F
G
H
ROUTE 6" SS TO EXISTING SANITARY
SEWER CONNECTION. I.E. = 94'-5".
VERIFY SIZE, LOCATION, AND
INVERT ELEVATION.
4" CW
I.E.=92'-4".ROUTE 6" SD TO EXISTING STORM
DRAINAGE CONNECTION. I.E. = 93'-0".
VERIFY SIZE, LOCATION, AND
INVERT ELEVATION.
A.8
7.66.4
6" SD
6" SD
6" SD
6" SD 6" SD 4" SD
4" SD
6" SD 6" SD
6" SD
4" SD
4" SS
4" SS
6" SS
6" SS
6" SS
4" SS
4" SS
404-SP-02
CRAWL SPACE
B0400
CRAWL SPACE
B0400
CRAWL SPACE
B0400
CRAWL SPACE
B0400
CRAWL SPACE
B0400
CRAWL SPACE
B0400
CRAWL SPACE
B0400
CRAWL SPACE
B0400
CRAWL SPACE
B0400
PP201
CONNECT TO EXISTING CIVIL
STORM DRAIN CONNECTION
4" SD UP
TO FCO
3" SD UP
6" SD UP
4" SD UP
TO FCO
4" SD UP
3" SD UP
3" SD UP
3" SD UP
4" SD UP
TO FCO
4" SD UP
TO 4" STANDPIPE
4" SD UP
4" SD UP
TO FCO
3" SD UP
4" SD UP
TO FCO
3" SD UP
3" SD UP
4" SD UP
3" SD UP
3" SD UP
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
4" SS UP
TO FCO
2" SS UP
4" SS UP
TO FCO
4" SS UP 2" SS UP
4" SS UP
TO FCO
2" SS UP
4" SS UP
4" SS UP
4" SS UP
2" SS UP
2" SS UP
2" SS UP
4" SS UP
4" SS UP
2" SS UP
2" SS UP
2" SS UP
2 1/2" PD UP
4" SS 4" SS
4" SS
4" SS UP
2" SS UP
2" SS UP
2" SS UP
4" SS UP
TO FCO
4" SD
6" SD
4" SD
4" SD
4" SD
4" SD
4" SD
4" SD
4" SD
4" SD
4" SD
2" SS UP
4" SS
3" SS UP
2" V UP
3" SS UP
TO FCO
3" SS UP
4" SS
3" SS
MECHANICAL
ROOM
B0405
2 1/2" PD
4" SS
4" SS UP
4" SS UP
6" SD
ROUTE STORM DRAIN TO
UNDERGROUND RAIN WATER
COLLECTION TANK TO SERVE
RAIN GARDEN.
MP21
MP22
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
AAKGJH
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
PLUMBING PLAN - UNDERFLOOR
AND BASEMENT
PP-100
-3
P P
/1
/2
.p d f
1/8" = 1'-0"PP100
1 PLUMBING PLAN - UNDERFLOOR AND BASEMENT
8'
SCALE : 1/16" = 1'-0"
0 16' 32'
KEYNOTE LEGEND
KEY DESCRIPTION
MP04 ROUTE NEW STORM DRAINAGE PIPING SYSTEM AND RISERS TO FOLLOW EXISTING
STORM DRAINAGE PIPING ROUTE UP TO EXISTING ROOF GUTTER OUTLET.
MP21 PROVIDE COMPETE PACKAGED RAIN HARVESTING, COLLECTION SYSTEM INCLUDING
TANK, PUMP, INLET CONNECTIONS, OUTLET CONNECTIONS, ALARM AND
ELECTRICAL ACCESSORIES FOR A COMPLETE SYSTEM. COORDINATE SYSTEM WITH
EC, AND MECHANICAL AND CIVIL ENGINEERS, AS NECESSARY
MP22 PROVIDE AND INSTALL DIVERTER VALVE TO AUTOMATICALLY SEND STORM WATER
TO THE CIVIL STORM CONNECTION WHEN RAIN HARVESTING TANK IS 85% FULL
(ADJUSTABLE). BAS SHALL SHOW STATUS OF DIVERTER VALVE, LEVEL OF
RAINWATER TANK. PUMP STATUS, AND ALLOW PUMP AND VALVE CONTROL VIA BAS.
CALENN
HEPPNER
E-48270
12/30/2022 A R C H I T E C T S E N G I N E E R S
188 237 184 of 233184 of 233
DN
PROVIDE NEW CONNECTIONS AS REQUIRED FOR PROPERLY OPERATING
SYSTEMS.
2. FIELD VERIFY LOCATION AND INVERTS OF SITE UTILITIES PRIOR TO INSTALLATION.
3. PROVIDE CLEANOUT IN ACCESSIBLE LOCATION AT THE BASE OF ALL PLUMBING
RISERS AND AT ALL CHANGES OF DIRECTION.
4. ROUTE DOMESTIC WATER AND SANITARY SEWER SERVICES TO SITE UTILITIES
5'-0" FROM BUILDING UNLESS NOTED OTHERWISE. REFER TO CIVIL PLANS.
5. MINIMUM SIZE OF PLUMBING VENT THRU ROOF SHALL BE 4' AND LOCATED A
MINIMUM OF 24" FROM ANY WALL OR VERTICAL SURFACE. A MINIMUM OF 12"
ABOVE FINISHED ROOF MATERIAL, AND A MINIMUM OF 12' FROM FRESH AIR
INTAKES.
6. INSTALL WATER HAMMER ARRESTORS IN WATER LINES AT CONNECTIONS TO ANY
QUICK CLOSING VALVES LIKE FIXTURES.
7. WASTE AND VENT PIPING BELOW FLOOR AND THROUGH FLOOR SHALL BE 2"
MINIMUM.
8. REFER TO PLUMBING DETAILS FOR ACCESSORIES AND FINAL CONNECTIONS TO
PLUMBING EQUIPMENT.
9. PITCH UNDERFLOOR SANITARY WASTE PIPING 4" AND GREATER AT 1/8" PER FOOT,
UNLESS NOTED OTHERWISE. PITCH ALL OTHER SANITARY WASTE PIPING AT 1/4"
PER FOOT UNLESS NOTED OTHERWISE.
10. INSTALL HORIZONTAL SANITARY VENT PIPING SLOPED AT 1/8" PER FOOT.
11. INSTALL HORIZONTAL STORM DRAINAGE PIPING SLOPED AT 1/4" PER FOOT.
12. MINIMIZE DOMESTIC WATER DEAD LEG PIPING TO 6" OR LESS.
13. REFER TO PLUMBING RISER DIAGRAMS FOR ADDITIONAL ROUTING AND PIPE
SIZING INFORMATION.
14. INSTALL EXTERIOR WALL HYDRANTS 1'- 6" ABOVE FINISHED FLOOR ELEVATION.
PLUMBING GENERAL NOTES
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 43
A
B
C
C.3
D
E
E.8
F
G
H
P-408
P-512
P-408
P-408
P-512
A.8
7.66.4
P-102
P-102
P-102
P-604
P-102
P-408
1 1/4" HW
2" CW
2" CW
2" CW
1 1/2" CW
1 1/2" CW
1 1/2" CW
1 1/2" CW
1 1/2" CW
1 1/2" CW
1" HW
2" CW
1" HW
1" HW-R
1 1/4" HW
1 1/4" HW
1 1/2" HW1 1/4" HW
1 1/2" HW
2" V
2" V
4" SS
2" V
2" V 2" V UP
4" SS DN
2" V UP
3/4" CW
3/4" CW
3/4" CW
P-801
2" CW
CORRIDOR
1C04
EAST STAIR
1S1
MAIN CORRIDOR
1C05
CORRIDOR
1C02
TESTING OFFICE
10401
GROUP TESTING
10400
RRTP
COUNSELOR
10405
RRTP
COUNSELOR
10404
ADMIN OFFICE
10420
VENDING
10422
WAITING
10424
GROUP ROOM C
10430
ELEVATOR
LOBBY
1C06
GROUP ROOM A
10435
GROUP ROOM B
10438
STORAGE
10438A
LOUNGE
10425
RECEIVING
10499
TRAM WALKWAY
1C20
TREATMENT
OBSERVATION
10453
TREATMENT
OBSERVATION
10451
SPECIMEN
TOILET
10454
TREATMENT
CIRCULATION
10450
NURSE STATION
10452
CORRIDOR
1C08
BUILDING DATA
10449
GENDER
NEUTRAL
TOILET
10447
GENDER
NEUTRAL
TOILET
10445
MOTHERS ROOM
10446
FAMILY TOILET
10444
MAIN CORRIDOR
1C05
WAITING
10443
CORRIDOR
1C07
INFO DESK
10442
VESTIBULE
10440
FAMILY WAITING
10465
RECEPTION
10460
WORKROOM
10466
MAIN CORRIDOR
1C05
MH CLINIC
OFFICE
10479 MH CLINIC
OFFICE
10480
MH CLINIC
OFFICE (FUTURE
EXAM)
10478
MH CLINIC
OFFICE
10477
CORRIDOR
1C12
HALL
1C10
STAFF TOILET
10476
MH CLINIC
OFFICE
10471
MH CLINIC
OFFICE
10470
CORRIDOR
1C11
MH CLINIC
OFFICE
10473
MH CLINIC
OFFICE
10472
MH CLINIC
TELEMED
OFFICE
10488
MH CLINIC
TELEMED
OFFICE
10489
MH CLINIC
OFFICE
10487
MH CLINIC
TELEMED
OFFICE
10486MH CLINIC
TELEMED
OFFICE
10484
MH CLINIC
OFFICE
10485
MH CLINIC
MED/SUPPLY
10474
MH CLINIC
EXAM/VITALS
10475
WEST STAIR
1S2
MP01
MP02
MP01
3/4" CW DN
MP01
MP01
3/4" CW
4" SS DN
4 SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
4" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
4" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
3/4" CW
P-512
P-514
MP05
MP05
MP05
MP05
MP06
3/4" CW DN
2" V DN
3/4" HW DN
1/2" CW DN
1/2" HW DN
1 1/4" CW DN
1/2" HW DN
1/2" CW DN
2" V
1/2" HW DN
3/4" HW
2" V
3/4" CW
2" V DN
1/2" CW DN 2" V DN
1 1/4" CW DN
1/2" HW DN
2" V DN
3/4" HW DN
2" V DN
3/4" CW DN
2" SS UP
4" SS UP
4" SS UP
2" SS UP
4" SS UP
4" SS UP & DN
2" SS UP
4" WCO
1 1/4" CW DN
4" SS UP
2" SS UP
4" SS UP
2" SS UP
4" SS UP
4" SS UP
2" SS UP
4" WCO
4" SS UP
2" SS UP
2" SS UP
6" OSD UP
6" SD UP & DN
2" SS UP
6" OSD
6" DOWNSPOUT
NOZZLE
3,820 SF
MP07
MP14
1" HW
1" CW
3/4" HW
2" V
3/4" CW DN
2" V
1/2" HW
2" V
1/2" CW
4" SS UP
& DN
1 1/2" CW
P-408
P-514
MP05
3/4" CW
2" CW
STORAGE
10415
ELECTRICAL
10415A
RRTP WAITING
10417
BED BUG
ZAPPER
10414
RRTP VITALS &
LOCKERS
10416
ELECTRICAL
CLOSET
10413
3/4" CW
3/4" HW
3/4" CW DN
1 1/4" HW
P-528
4" FCO
4" FCO
4" FCO
4" FCO
4" FCO
4" FCO
4" FCO
4" FCO
2" V UP
4" FCO
BALANCE VALVE
3.1 GPM
P-408
P-102
MP05
4" WCO
HAC
10464
P-501 3/4" CW
3/4" HW
2" V
1" HW
4" WCO
3" FCO
3" SS UP
2" V UP
3" SS UP
4" SS UP
TO FCO
3/4" CW
1 1/2" CW
3/4" CW
3/4" HW
3" SS UPRRTP SECURITY
OFFICE
10419
RRTP FOYER
10427
STORAGE
10430A
RRTP OFFICES
10426
RRTP TOILET
10418
1" HW
1 1/4" HW
1 1/4" HW
4" SS
4" SS
4" SS DN
2" V
1 1/4" CW
2" V
1/2" HW
1/2" CW
2" V
1 1/2" CW
2" V UP
2" V
2" V
2" V UP
1/2" CW
1 1/2" HW
1/2" CW
4" SS
1 1/2" HW
2" CW
2 1/2" CW
2" V UP & DN
4" CW DN &
3" CW UP
2" HW DN &
1 1/2" HW UP
1 1/2" RHW DN &
1 1/4" RHW UP1 1/2" HW
1" HW-R
1" HW
3/4" CW
2" V UP
3/4" CW
3/4" HW
1 1/4" CW
2" V
3/4" HW
2" V
3/4" CW
MP19
2" SS
2" SS UP
STORAGE
10476A
P-512
MAIN
ELECTRICAL
10411
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
AAKGJH
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
PLUMBING PLAN - LEVEL 1
PP-101
-3
P P
/1
/2
.p d f
8'
SCALE : 1/16" = 1'-0"
0 16' 32'
1/8" = 1'-0"PP101
1 PLUMBING PLAN - LEVEL 1
KEYNOTE LEGEND
KEY DESCRIPTION
MP01 ROUTE 3/4" CW WITH WINTER DRAIN DOWN SHUT-OFF VALVE TO EXISTING WALL
HYDRANT.
MP02 PROVIDE WINTER DRAIN DOWN SHUT-OFF VALVE FOR EXTERIOR WALL HYDRANT.
MP05 PROVIDE BRANCH LINE SHUT OFF VALVE TO WATER SUPPLY FOR EACH BATHROOM.
MP06 PROVIDE DOMESTIC RECIRCULATING HOT WATER CALIBRATED BALANCE SET. SET
TEMPERATURE OF 130° F.
MP07 DISCHARGE 2 1/2" PD TO 4" VENTED STAND PIPE WITH 6X4 HUB DRAIN. CONNECT
STAND PIPE DRAIN TO BUILDING STORM DRAINAGE SYSTEM PER CODE
REQUIREMENTS.
MP14 INSTALL OVERFLOW RAINWATER LEADER DOWNSPOUT NOZZLES AT EXTERIOR OF
BUILDING 1'-4" ABOVE FINISHED FLOOR ELEVATION. REFER LOCATION TO
ARCHITECTURAL DETAIL.
MP19 PROVIDE QUICK ACTING, SWITCH ACTIVATED, SOLENOID VALVES TO SHUT OFF
LAVATORY CW AND HW AND TOILET CW SUPPLIES. DURING DURG TESTING. SWITCH
SHALL BE LOCATING IN NURSES STATION. COORDINATE SWITCH, SWITCH LOCATION,
AND POWER REQUIREMENTS WITH E.C.
CALENN
HEPPNER
E-48270
12/30/2022 A R C H I T E C T S E N G I N E E R S
189 237 185 of 233185 of 233
D W
Range
1. FIELD VERIFY ALL NEW WATER, WASTE, AND VENT PIPING CONNECTIONS AND
PROVIDE NEW CONNECTIONS AS REQUIRED FOR PROPERLY OPERATING
SYSTEMS.
2. FIELD VERIFY LOCATION AND INVERTS OF SITE UTILITIES PRIOR TO INSTALLATION.
3. PROVIDE CLEANOUT IN ACCESSIBLE LOCATION AT THE BASE OF ALL PLUMBING
RISERS AND AT ALL CHANGES OF DIRECTION.
4. ROUTE DOMESTIC WATER AND SANITARY SEWER SERVICES TO SITE UTILITIES
5'-0" FROM BUILDING UNLESS NOTED OTHERWISE. REFER TO CIVIL PLANS.
5. MINIMUM SIZE OF PLUMBING VENT THRU ROOF SHALL BE 4' AND LOCATED A
MINIMUM OF 24" FROM ANY WALL OR VERTICAL SURFACE. A MINIMUM OF 12"
ABOVE FINISHED ROOF MATERIAL, AND A MINIMUM OF 12' FROM FRESH AIR
INTAKES.
6. INSTALL WATER HAMMER ARRESTORS IN WATER LINES AT CONNECTIONS TO ANY
QUICK CLOSING VALVES LIKE FIXTURES.
7. WASTE AND VENT PIPING BELOW FLOOR AND THROUGH FLOOR SHALL BE 2"
MINIMUM.
8. REFER TO PLUMBING DETAILS FOR ACCESSORIES AND FINAL CONNECTIONS TO
PLUMBING EQUIPMENT.
9. PITCH UNDERFLOOR SANITARY WASTE PIPING 4" AND GREATER AT 1/8" PER FOOT,
UNLESS NOTED OTHERWISE. PITCH ALL OTHER SANITARY WASTE PIPING AT 1/4"
PER FOOT UNLESS NOTED OTHERWISE.
10. INSTALL HORIZONTAL SANITARY VENT PIPING SLOPED AT 1/8" PER FOOT.
11. INSTALL HORIZONTAL STORM DRAINAGE PIPING SLOPED AT 1/4" PER FOOT.
12. MINIMIZE DOMESTIC WATER DEAD LEG PIPING TO 6" OR LESS.
13. REFER TO PLUMBING RISER DIAGRAMS FOR ADDITIONAL ROUTING AND PIPE
SIZING INFORMATION.
14. INSTALL EXTERIOR WALL HYDRANTS 1'- 6" ABOVE FINISHED FLOOR ELEVATION.
PLUMBING GENERAL NOTES
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 43
A
B
C
C.3
D
E
E.8
F
G
H
P-524
P-408
P-408
P-524
P-408
GROUP ROOM C
20428
STORAGE
20434A
STORAGE
20428A
GROUP ROOM A
20431?
WAITING
20427
ELEVATOR
LOBBY
2C06
BUILDING
ELECTRICAL
20408
BUILDING DATA
20447
STAFF BREAK
20449
GENDER
NEUTRAL
TOILET
20445
FAMILY TOILET
20444
GENDER
NEUTRAL
TOILET
20443
HVAC
20442
WAITING
20440
RECP.
WORKROOM
20424
STAFF TOILET
20405
MH CLINIC
OFFICE
20478
STAFF TOILET
20466
RRTP TEACHING
KITCHEN
20454
MH CLINIC TMS
20457
RRTP KITCHEN
OFFICE
20453
MH CLINIC
OFFICE
20476
MH CLINIC
OFFICE
20474
MH CLINIC
OFFICE
20464
MH CLINIC
OFFICE
20462
MH CLINIC
OFFICE
20460
MH CLINIC
OFFICE
20461
MH CLINIC
OFFICE
20463
MH CLINIC
OFFICE
20458
MH CLINIC
OFFICE
20467
MH CLINIC
OFFICE
20469
MH CLINIC
OFFICE
20470
MH CLINIC
OFFICE
20468
MH CLINIC
OFFICE
20477
MH CLINIC
OFFICE
20479
MH CLINIC
OFFICE
20475
RRTP
COUNSELOR
20411
RRTP
COUNSELOR
20410
RRTP
COUNSELOR
20409
RRTP
COUNSELOR
20407
RRTP
COUNSELOR
20419
RRTP
COUNSELOR
20417
RRTP
COUNSELOR
20415
RRTP
COUNSELOR
20420
RRTP
COUNSELOR
20418
RRTP
COUNSELOR
20416
RRTP
COUNSELOR
20403
RRTP
COUNSELOR
20401
RRTP
COUNSELOR
20402
RRTP
COUNSELOR
20404
RRTP
COUNSELOR
20406
RRTP
COUNSELOR
20422
CORRIDOR
2C10
RECEPTION
20426
A.8
7.66.4
P-102
P-102
P-408
P-102
P-408
P-102
P-604
2" CW
2" CW
2" CW
2" CW
1 1/2" CW
1 1/2" CW
1 1/2" CW
2" CW 1 1/2" CW
1 1/4" HW1 1/4" HW
1 1/4" HW
1" HW
1" HW
1" HW
1" HW
1" HW
1" HW-R
2" V
3" V
2" SS
3" V UP
4" SS DN
2" V DN
2" V DN & 3" V UP
2" V DN &
3" V UP
2" CW
CORRIDOR
2C04
CORRIDOR
2C03
CORRIDOR
2C02
EAST STAIR
2S1
CORRIDOR
2C05
CORRIDOR
2C08
CORRIDOR
2C07
WEST STAIR
2S2
CORRIDOR
2C11
4 SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
4" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
4" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
1 1/4" CW DN
2" V DN
2" V DN
1/2" HW DN
2" V DN
1/2" CW DN
P-408
P-102
MP05
MP05
MP05
MP05
MP05
MP06
4" WCO
4" WCO
4" WCO
2" V DN
3/4" CW DN
3/4" HW DN
1/2" HW DN
4" SS DN
2" V DN
1 1/4" CW DN
1 1/4" CW DN
1/2" CW DN
1/2" HW DN
3/4" CW DN
3/4" HW DN
2" V DN
4" SS DN
1/2" HW DN
1/2" CW DN
2" SS UP
4" SS UP
2" SS UP
1 1/4" CW DN
2" V DN
1 1/4" CW DN
2" V DN
4" SS UP
2" SS UP
2" SS UP
2" SS UP
4" SS UP
2" SS UP
4" SS UP
3" V UP
4" SS UP
2" SS UP
4" SS UP
3" W UP & DN
6" OSD UP 6" SD UP
2" V DN
1 1/4" HW
2" V DN
BALANCE VALVE
2.8 GPM
4" WCO
P-501
3/4" CW
3/4" HW
2" V
2" V
1/2" CW
1/2" HW
2" V
4" SS UP & DN
2" SS UP
2" V
1/2" CW
3" SS DN
2" V DN &
3" V UP
2" V
HAC
20456
MP08
MP08
GENDER
NEUTRAL
TOILET
20448
STORAGE
20446
4" FCO
2" V UP &
DN
1/2" HW
1/2" CW
2" V
4" SS UP
1 1/2" CW
1/2" CW
2" V
1/2" HW
2" V
4" SS
MP05
4" SS
1 1/2" CW
1 1/4" HW
2" V
3/4" CW 2" CW
1" HW-R
1 1/4" HW
1" HW-R1 1/4" HW 3" CW DN &
2" CW UP
1 1/2" HW DN &
1 1/4" HW UP
1 1/4" RHW DN &
1" RHW UP
4" SS UP
TO FCO
1 1/4" CW
3/4" HW
3/4" CW
2" V
2 1/2" CW
3/4" HW
P-408
2" S
S
2" SS UP
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
AAKGJH
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
PLUMBING PLAN - LEVEL 2
PP-102
-3
P P
/1
/2
.p d f
8'
SCALE : 1/16" = 1'-0"
0 16' 32'
1/8" = 1'-0"PP102
1 PLUMBING PLAN - LEVEL 2
KEYNOTE LEGEND
KEY DESCRIPTION
MP05 PROVIDE BRANCH LINE SHUT OFF VALVE TO WATER SUPPLY FOR EACH BATHROOM.
MP06 PROVIDE DOMESTIC RECIRCULATING HOT WATER CALIBRATED BALANCE SET. SET
TEMPERATURE OF 130° F.
MP08 PROVIDE 1/2" HW SUPPLY CONNECTION TO DISHWASHER. PROVIDE SHUT OFF VALVE
AND CODE APPROVED BACKFLOW PREVENTER. DISCHARGE DISHWASHER DRAIN
INTO NEARBY SINK TAILPIECE THROUGH AN AIR BREAK/AIR GAP.
CALENN
HEPPNER
E-48270
12/30/2022 A R C H I T E C T S E N G I N E E R S
190 27 186 of 233186 of 233
SYSTEMS.
2. FIELD VERIFY LOCATION AND INVERTS OF SITE UTILITIES PRIOR TO INSTALLATION.
3. PROVIDE CLEANOUT IN ACCESSIBLE LOCATION AT THE BASE OF ALL PLUMBING
RISERS AND AT ALL CHANGES OF DIRECTION.
4. ROUTE DOMESTIC WATER AND SANITARY SEWER SERVICES TO SITE UTILITIES
5'-0" FROM BUILDING UNLESS NOTED OTHERWISE. REFER TO CIVIL PLANS.
5. MINIMUM SIZE OF PLUMBING VENT THRU ROOF SHALL BE 4' AND LOCATED A
MINIMUM OF 24" FROM ANY WALL OR VERTICAL SURFACE. A MINIMUM OF 12"
ABOVE FINISHED ROOF MATERIAL, AND A MINIMUM OF 12' FROM FRESH AIR
INTAKES.
6. INSTALL WATER HAMMER ARRESTORS IN WATER LINES AT CONNECTIONS TO ANY
QUICK CLOSING VALVES LIKE FIXTURES.
7. WASTE AND VENT PIPING BELOW FLOOR AND THROUGH FLOOR SHALL BE 2"
MINIMUM.
8. REFER TO PLUMBING DETAILS FOR ACCESSORIES AND FINAL CONNECTIONS TO
PLUMBING EQUIPMENT.
9. PITCH UNDERFLOOR SANITARY WASTE PIPING 4" AND GREATER AT 1/8" PER FOOT,
UNLESS NOTED OTHERWISE. PITCH ALL OTHER SANITARY WASTE PIPING AT 1/4"
PER FOOT UNLESS NOTED OTHERWISE.
10. INSTALL HORIZONTAL SANITARY VENT PIPING SLOPED AT 1/8" PER FOOT.
11. INSTALL HORIZONTAL STORM DRAINAGE PIPING SLOPED AT 1/4" PER FOOT.
12. MINIMIZE DOMESTIC WATER DEAD LEG PIPING TO 6" OR LESS.
13. REFER TO PLUMBING RISER DIAGRAMS FOR ADDITIONAL ROUTING AND PIPE
SIZING INFORMATION.
14. INSTALL EXTERIOR WALL HYDRANTS 1'- 6" ABOVE FINISHED FLOOR ELEVATION.
PLUMBING GENERAL NOTES
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 43
A
B
C
C.3
D
E
E.8
F
G
H
P-408
P-408
P-408
P-524
P-408
ADMIN WAIT
30409
GROUP ROOM C
30436
STORAGE
30441A
STORAGE
30436A
GROUP ROOM A
30437?
GROUP ROOM B
30441
CORRIDOR
3C07
ELEVATOR
LOBBY
3C05
BUILDING
ELECTRICAL
30416
BUILDING DATA
30451
STAFF BREAK
30453
FAMILY TOILET
30448
GENDER
NEUTRAL
TOILET
30447
GENDER
NEUTRAL
TOILET
30452
HVAC
30446
WAITING
30442
RRTP OFFICE
30428
STAFF TOILET
30405
OFFICE
30457
MH CLINIC
ADMIN
30464
STAFF TOILET
30472
CORRIDOR
3C10
ADMIN
CUBICLES
30423
MHICM PRIVATE
COUNSEL
30476
LOUNGE
30443
CHIEF OFFICE
30417
ADMIN
CONFERENCE
30418
MHICM
STORAGE
30471
MHICM MED
ROOM
30473
MHICM
CUBICLES
30479
CORRIDOR
3C11
RECP.
WORKROOM
30430
RRTP OFFICE
30402
RRTP OFFICE
30404
RRTP OFFICE
30406
RRTP OFFICE
30401
RRTP OFFICE
30403
ADMIN RECP.
30415
ADMIN OFFICE
30426
MH CLINIC
OFFICE
30470
MH CLINIC
OFFICE
30468
MH CLINIC
OFFICE
30466
MH CLINIC
OFFICE
30465
MH CLINIC
OFFICE
30467
HAC
30462
RECEPTION
30432
A.8
7.66.4
P-102
P-102
P-408
P-102
P-408
P-102
P-604
P-102
2" CW
2" CW
2" CW
1 1/2" CW
1 1/2" CW
1 1/2" CW
1 1/2" CW
1 1/4" HW
1 1/4" HW
1 1/4" HW
1" HW
1" HW
1" HW-R
2" CW
2" V
3" V
3" V DN
3" V UP
3" V UP
3" V DN
3" V DN
3" V DN &
3" V UP
3" SD UP
2" CW
CORRIDOR
3C03
CORRIDOR
3C04
CORRIDOR
3C02
CORRIDOR
3C06
CORRIDOR
3C07
CORRIDOR
3C12
4" OSD UP
4" SD UP
4" OSD UP
4" SD UP
6" SD DN6" OSD DN
4" WCO
4" WCO
4" WCO
3" SD UP &
4" SD DN
3" SD UP &
4" SD DN
3" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
3" SD UP
3" SD UP
& DN
3" SD UP &4" SD N
3" SD UP
& DN
3" SD UP
& DN
3" SD UP
& DN
P-102
MP05
4" WCO
MP05
MP05
MP05
MP06
1 1/4" CW DN
2" V DN
4" SS DN
1/2" HW
2" V
1/2" CW
1/2" CW DN
1 1/4" CW DN
3" SS DN
1 1/4" CW DN
1/2" CW DN
2" V DN
1/2" HW DN
3/4" HW DN
3/4" CW DN
2" V DN
1/2" HW
1/2" CW DN
4" SS DN
2" V DN1/2" HW DN
1 1/4" CW DN
2" V DN
1 1/4" CW DN
2" V DN
4" SS DN
4" SS DN
3" SS UP
2" V UP
3" SS UP
2" V UP
3" V UP
3" SS UP
2" V UP
3" SS UP
2" V UP
3" SS UP
TO FCO
4" SS UP
2" V UP
3" SS UP
3" V UP
3" SS UP
6" SD
6" OSD
MP171/2" CW
1/2" CW
1/2" CW
MP17
1/2" CW
MP17
1/2" CW
1/2" CW
MP17
1/2" CW
1/2" CW
4" SS UP
TO FCO
4" SS UP
TO FCO
3" FCO
BALANCE VALVE
2.8 GPM
4" OSD
UP TO FCO
4" SD
UP TO FCO
1" HW
1" HW
EAST STAIR
3S1
WEST STAIR
3S2
1" HW
1/2" HW
2" V
3" SS
2" V
1/2" CW
2" V
3" V DN
2" V
1/2" CW
3/4" CW
3/4" HW
P-501
2" V
2" V UP
MP08
GENDER
NEUTRAL
TOILET
30449
STORAGE
30450
OFFICE
30460
OFFICE
30461
OFFICE
30459
OFFICE
30458OFFICE
30456
1 1/2" CW
1" HW
1" HW
MP17
1/2" CW
3" SS
2" V UP & DN
2" V 2" V
2" V
1 1/2" CW
1 1/4" HW
MP05
1 1/4" HW
1 1/4" HW
1" HW-R DN
1 1/4" HW DN
2 1/2" CW DN
1" HW-R
1 1/4" HW
2 1/2" CW
1" HW-R
2" CW
1" HW
1/2" HW
2" V
1/2" CW
1 1/4" CW
2" V
3" V DN
3" SS
3" V
MP05
1/2" HW
2" V
1/2" CW
P-528
MHICM PATIENT
CARE
30478
3/4" CW UP
3/4" CW
3/4" CW UP
3" SS UP
2" V UP
3" SS UP
2" V UP MP20
MP20
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
AAKGJH
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
PLUMBING PLAN - LEVEL 3
PP-103
-3
P P
/1
/2
.p d f
8'
SCALE : 1/16" = 1'-0"
0 16' 32'
1/8" = 1'-0"PP103
1 PLUMBING PLAN - LEVEL 3
KEYNOTE LEGEND
KEY DESCRIPTION
MP05 PROVIDE BRANCH LINE SHUT OFF VALVE TO WATER SUPPLY FOR EACH BATHROOM.
MP06 PROVIDE DOMESTIC RECIRCULATING HOT WATER CALIBRATED BALANCE SET. SET
TEMPERATURE OF 130° F.
MP08 PROVIDE 1/2" HW SUPPLY CONNECTION TO DISHWASHER. PROVIDE SHUT OFF VALVE
AND CODE APPROVED BACKFLOW PREVENTER. DISCHARGE DISHWASHER DRAIN
INTO NEARBY SINK TAILPIECE THROUGH AN AIR BREAK/AIR GAP.
MP17 ROUTE 1/2" CW TO TRAP PRIMER (TP-1) FOR SUPPLY CONNECTION TO FLOOR DRAIN /
SINK TRAP.
MP20 EXTEND NEAREST TRAP PRIMER SYSTEM TO SUPPLY CONNECTION OF FLOOR
DRAIN.
CALENN
HEPPNER
E-48270
12/30/2022 A R C H I T E C T S E N G I N E E R S
191 237 187 of 233187 of 233
SYSTEMS.
2. FIELD VERIFY LOCATION AND INVERTS OF SITE UTILITIES PRIOR TO INSTALLATION.
3. PROVIDE CLEANOUT IN ACCESSIBLE LOCATION AT THE BASE OF ALL PLUMBING
RISERS AND AT ALL CHANGES OF DIRECTION.
4. ROUTE DOMESTIC WATER AND SANITARY SEWER SERVICES TO SITE UTILITIES
5'-0" FROM BUILDING UNLESS NOTED OTHERWISE. REFER TO CIVIL PLANS.
5. MINIMUM SIZE OF PLUMBING VENT THRU ROOF SHALL BE 4' AND LOCATED A
MINIMUM OF 24" FROM ANY WALL OR VERTICAL SURFACE. A MINIMUM OF 12"
ABOVE FINISHED ROOF MATERIAL, AND A MINIMUM OF 12' FROM FRESH AIR
INTAKES.
6. INSTALL WATER HAMMER ARRESTORS IN WATER LINES AT CONNECTIONS TO ANY
QUICK CLOSING VALVES LIKE FIXTURES.
7. WASTE AND VENT PIPING BELOW FLOOR AND THROUGH FLOOR SHALL BE 2"
MINIMUM.
8. REFER TO PLUMBING DETAILS FOR ACCESSORIES AND FINAL CONNECTIONS TO
PLUMBING EQUIPMENT.
9. PITCH UNDERFLOOR SANITARY WASTE PIPING 4" AND GREATER AT 1/8" PER FOOT,
UNLESS NOTED OTHERWISE. PITCH ALL OTHER SANITARY WASTE PIPING AT 1/4"
PER FOOT UNLESS NOTED OTHERWISE.
10. INSTALL HORIZONTAL SANITARY VENT PIPING SLOPED AT 1/8" PER FOOT.
11. INSTALL HORIZONTAL STORM DRAINAGE PIPING SLOPED AT 1/4" PER FOOT.
12. MINIMIZE DOMESTIC WATER DEAD LEG PIPING TO 6" OR LESS.
13. REFER TO PLUMBING RISER DIAGRAMS FOR ADDITIONAL ROUTING AND PIPE
SIZING INFORMATION.
14. INSTALL EXTERIOR WALL HYDRANTS 1'- 6" ABOVE FINISHED FLOOR ELEVATION.
PLUMBING GENERAL NOTES
1 1A 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 43
A
B
C
C.3
D
E
E.8
F
G
H
A.8
7.66.4
1575 SF
4" RD-1
4" V UP
TO 4" VTR
4" V UP
TO 4" VTR
3" SD DN
& UP TO G.O.
646 SF
3" SD DN &
& UP TO RD
606 SF
3" SD DN &
& UP TO G.O.
858 SF
3" SD DN &
& UP TO G.O.
873 SF
3" SD DN &
& UP TO G.O.
599 SF
3" SD DN &
& UP TO G.O.
646 SF
3" SD DN &
& UP TO RD
607 SF
3" SD DN &
& UP TO G.O.
599 SF
3" SD DN &
& UP TO G.O.
801 SF
3" SD DN &
& UP TO G.O.
408 SF
3" SD DN &
& UP TO G.O.
408 SF
3" SD DN &
& UP TO G.O.
801 SF
3" SD DN &
& UP TO G.O.
599 SF
3" V DN
3" V DN
2245 SF
4" RD-1
3" SD DN &
& UP TO G.O.
647 SF
3" SD DN &
& UP TO G.O.
646 SF
2" V UP
TO 3" VTR
3" FS-1
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
3" FS-1
3" FS-1
3" FS-1
3" FS-1
2" V DN
2" V DN
3" V DN
3" V DN
2" V DN
2" V DN
3" V DN
2" V DN3" V UP
TO 4" VTR
2" V UP
TO 3" VTR
MP09
MP092" V DN &
UP TO 3" VTR
3" V
MP09
3" FS-1 MP13
MP13
MP13
MP13
MP13
2" V DN
TP-1
TP-1
TP-1
TP-1
1/2" CW DN
1/2" CW DN
1/2" CW DN
1/2" CW DN
3" FCO
4" FCO
3" FCO
3" FCO
3" FCO
4" FCO
4" FCO
P-804
P-804
P-804
3" FD
2" V
3" FD
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
AAKGJH
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
PLUMBING PLAN - ATTIC & ROOF
PP-104
-3
P P
/1
/2
.p d f
8'
SCALE : 1/16" = 1'-0"
0 16' 32'
1/8" = 1'-0"PP104
1 PLUMBING PLAN - ATTIC
KEYNOTE LEGEND
KEY DESCRIPTION
MP04 ROUTE NEW STORM DRAINAGE PIPING SYSTEM AND RISERS TO FOLLOW EXISTING
STORM DRAINAGE PIPING ROUTE UP TO EXISTING ROOF GUTTER OUTLET.
MP09 UTILIZE EXISTING VENT THROUGH ROOF PENETRATION FOR NEW VENT PIPING
ROUTE TO VTR.
MP13 NEW FLOOR DRAIN TO REPLACE EXISTING FLOOR DRAIN AT SIMILAR LOCATION.
CALENN
HEPPNER
E-48270
12/30/2022 A R C H I T E C T S E N G I N E E R S
192 237 188 of 233188 of 233
SYSTEMS.
2. FIELD VERIFY LOCATION AND INVERTS OF SITE UTILITIES PRIOR TO INSTALLATION.
3. PROVIDE CLEANOUT IN ACCESSIBLE LOCATION AT THE BASE OF ALL PLUMBING
RISERS AND AT ALL CHANGES OF DIRECTION.
4. ROUTE DOMESTIC WATER AND SANITARY SEWER SERVICES TO SITE UTILITIES
5'-0" FROM BUILDING UNLESS NOTED OTHERWISE. REFER TO CIVIL PLANS.
5. MINIMUM SIZE OF PLUMBING VENT THRU ROOF SHALL BE 4' AND LOCATED A
MINIMUM OF 24" FROM ANY WALL OR VERTICAL SURFACE. A MINIMUM OF 12"
ABOVE FINISHED ROOF MATERIAL, AND A MINIMUM OF 12' FROM FRESH AIR
INTAKES.
6. INSTALL WATER HAMMER ARRESTORS IN WATER LINES AT CONNECTIONS TO ANY
QUICK CLOSING VALVES LIKE FIXTURES.
7. WASTE AND VENT PIPING BELOW FLOOR AND THROUGH FLOOR SHALL BE 2"
MINIMUM.
8. REFER TO PLUMBING DETAILS FOR ACCESSORIES AND FINAL CONNECTIONS TO
PLUMBING EQUIPMENT.
9. PITCH UNDERFLOOR SANITARY WASTE PIPING 4" AND GREATER AT 1/8" PER FOOT,
UNLESS NOTED OTHERWISE. PITCH ALL OTHER SANITARY WASTE PIPING AT 1/4"
PER FOOT UNLESS NOTED OTHERWISE.
10. INSTALL HORIZONTAL SANITARY VENT PIPING SLOPED AT 1/8" PER FOOT.
11. INSTALL HORIZONTAL STORM DRAINAGE PIPING SLOPED AT 1/4" PER FOOT.
12. MINIMIZE DOMESTIC WATER DEAD LEG PIPING TO 6" OR LESS.
13. REFER TO PLUMBING RISER DIAGRAMS FOR ADDITIONAL ROUTING AND PIPE
SIZING INFORMATION.
14. INSTALL EXTERIOR WALL HYDRANTS 1'- 6" ABOVE FINISHED FLOOR ELEVATION.
PLUMBING GENERAL NOTES
10 11 12 13 14
C
C.3
D
E
404-WH-01
404-WH-02
404-ST-01
P-707
4" FD-1
404-ET-01
404-RCP-1A
404-RCP-02
404-SP-01
2" CW
404-TMV-01
1/2" CW 2 1/2" CW
1 1/2" HW-R
2" HW
2" HW
2" HW
2" CW
2" CW
1" HW 2" HW
2" CW
2" CW
1 1/2" HW-R
1" HW-R
2" V
MP03
MP10
MP12
MP13
4" FD-1
4" FD-1
FD-1
4" FD-1
2" V DN
2" V DN
2" V DN
2" PD DN
3" SD UP
2" V
2" PD
4" SS4" SS4" SS
4" SS
MP11
4" V
6" V 3" V
6" V
4" V
MP17
TP-1
TP-1
TP-1
MP17
MP17
4" FCO
4" FCO
2" V UP
2" V DN
SEE PLAN 1/PP100
FOR CONTINUATION.
SEE PLAN 1/PP100
FOR CONTINUATION.
SEE PLAN 1/PP100
FOR CONTINUATION.
SEE PLAN 1/PP100
FOR CONTINUATION.
SEE PLAN 1/PP100
FOR CONTINUATION.
SEE PLAN 1/PP100
FOR CONTINUATION.
404-RCP-1B
MECHANICAL
ROOM
B0405
6" V
6" V
1 1/2" HW-R
2" HW
2" HW
4" CW
1 1/2" HW-R
2" HW
4" CW
1 1/4" CW
1 1/4" HW
2" V
1 1/2" HW-R UP
2" HW UP
4" CW UP
PROVIDE HOSE BIB
(WOODFORD MODEL 19 OR
SIMILAR) MOUNTED TO
BASEMENT WALL
10 11 12 13 14
C
C.3
D
E
404-SP-01
4" SS
4" SS UP
TO FCO
4" SS UP
2" V UP
2" V UP
4" SS UP
4" SS UP
4" SS UP
2" V UP
4" SS UP
TO FCO4" SS
4" SS
2" V UP1/2" CW UP
4" SS
1/2" CW
1/2" CW UP
1/2" CW UP
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
AAKGJH
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
ENLARGED PLUMBING PLANS
PP-201
-3
P P
/1
/2
.p d f
KEYNOTE LEGEND
KEY DESCRIPTION
MP03 ROUTE 2" VENT DOWN TO CONDENSATE RECEIVER AND PUMP TRAP.
MP10 ROUTE 4" VENT DOWN TO PRESSURE SAFETY VALVE CONNECTION AT EXISTING
PRESSURE REDUCING VALVE STATION.
MP11 EXTEND VENT PIPING THROUGH EXTERIOR WALL WITH SCREENED ELBOW LOOKING
DOWN. TERMINATE PAST BUILDING OVERHANG.
MP12 PROVIDE 1 1/4" HW & 1 1/4" CW CONNECTIONS TO THERMOSTATIC MIXING VALVE IN
ACCESSIBLE LOCATION FOR EMERGENCY SHOWER & EYE/FACE WASH.
MP13 NEW FLOOR DRAIN TO REPLACE EXISTING FLOOR DRAIN AT SIMILAR LOCATION.
MP17 ROUTE 1/2" CW TO TRAP PRIMER (TP-1) FOR SUPPLY CONNECTION TO FLOOR DRAIN /
SINK TRAP.
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
1/4" = 1'-0"PP201
1 ENLARGED PLUMBING PLAN - BASEMENT MECHANICAL ROOM
1/4" = 1'-0"PP201
2 ENLARGED PLUMBING PLAN - BASEMENT MECHANICAL ROOM UNDERFLOOR
CALENN
HEPPNER
E-48270
12/30/2022 A R C H I T E C T S E N G I N E E R S
193 237 189 of 233189 of 233
SYSTEMS.
2. PROVIDE ISOLATION VALVES ON ALL PLUMBING PIPING RUNOUTS FROM
PLUMBING MAINS AND BRANCH MAINS.
3. PROVIDE CLEANOUT IN ACCESSIBLE LOCATION AT THE BASE OF ALL PLUMBING
RISERS.
4. MINIMUM SIZE OF VENT THROUGH ROOF SHALL BE 3" AND LOCATED A MINIMUM
OF 24" FROM ANY WALL OR VERTICAL SURFACE. A MINIMUM OF 12" ABOVE
FINISHED ROOF MATERIAL, AND A MINIMUM OF 12' FROM FRESH AIR INTAKES.
5. INSTALL WATER HAMMER ARRESTORS IN WATER LINES AT CONNECTIONS TO ANY
QUICK CLOSING VALVES LIKE FIXTURES.
6. ALL SANITARY VENT PIPING IS 2" UNLESS NOTED OTHERWISE.
PLUMBING RISER GENERAL NOTES
3/4" CW
1" HW
1/2" CW
1/2" HW
3/4" CW
P-514
1 1/2" CW
1" HW-R
1" HW
3/4" HW
3/4" CW
3/4" CW
1" CW
2" HW
1/2" CW
2" CW
2" HW
1 1/2" HW-R
3/4" CW
3/4" HW
3/4" CW 1 1/2" CW
1" HW
1" HW-R
1 1/2" CW
1" HW
P-408
P-102
P-102
P-512
P-524
3/4" HW
3/4" CW
P-524
3/4" HW
3/4" CW
P-512
P-102
P-102
P-102
P-102
1 1/4" HW
3/4" CW
2" CW
1 1/2" CW
1 1/4" HW
1" HW
P-604
P-604
P-408
P-102
P-102
P-102
P-102
1 1/4" HW
1" HW
1 1/2" CW
1/2" HW
1/2" CW
1" HW
1" HW
P-512
3/4" HW
3/4" CW
1/2" HW
1/2" CW
P-102
1 1/4" CW P-408
1/2" HW
1/2" CW
1/2" HW
3/4" HW
3/4" CW
1/2" CW
1/2" HW
3/4" CW
3/4" CW
3/4" HW
EXISTING 4" CW
INTO BUILDING
P-528
MP01
P-102
P-408
P-408
P-102
P-102
P-408
P-604
P-408
P-408
P-408
P-524
P-408
P-408
P-408
P-801
P-408
P-408MP02
MP01
MP01
MP01
P-707
TP-1
1/2" CW
1/2" CW
1/2" CW
1 1/4" HW
1 1/4" CW
MP12
P-514
P-514
P-408
P-408
P-514
P-514
MP16
TP-1
TP-1
1/2" CW
TP-1
TP-1
TP-1
1/2" CWTP-1
1/2" CW
1 1/2" HW-R
1 1/4" CW
1 1/4" CW
1 1/4" CW
2" CW
1 1/2" CW
1/2" CW
3/4" CW
3/4" CW
1/2" CW
1 1/2" CW1 1/2" CW
1 1/2" CW
3/4" CW3/4" CW
3/4" CW
2" CW
1/2" CW
1/2" HW
1 1/2" HW
3/4" HW
1 1/2" HW
1 1/2" HW1 1/4" HW
1 1/4" HW
1/2" CW
1/2" HW
1/2" CW
1/2" HW
1 1/4" HW1" HW
1" HW
3/4" HW
1" HW
1/2" HW
1" HW
2" CW
2" CW
1 1/2" CW
1 1/4" CW
1/2" CW
1/2" CW
3/4" CW
1 1/2" CW
1 1/2" CW
1 1/4" CW
1 1/4" CW
1 1/4" HW
1/2" HW
1 1/4" HW
1 1/2" CW
1 1/4" CW
1 1/2" CW
1/2" CW
1 1/4" HW
1/2" HW
1" HW
1" HW
1" HW
3/4" HW
MP08
1" HW
1" HW
MP06
MP06
MP06
BALANCE VALVE
3.1 GPM
BALANCE VALVE
2.8 GPM
BALANCE VALVE
2.8 GPM
P-102
1 1/4" CW
3/4" CW
P-408
1/2" HW
1/2" CW
1 1/4" HW
P-501
4" CW
3/4" CW
3/4" HW
P-501
1" HW
1 1/4" CW
2" CW
1" HW-R
1" HW
1/2" HW
1/2" CW
3/4" CW
3/4" HW
P-501
1" HW
1" HW
1" HW
1" HW
1/2" HW
1/2" CW
1 1/4" HW
1 1/4" HW
1/2" HW
1/2" CW
2" CW
2" CW
1 1/2" CW
1 1/4" CW
1 1/4" CW
1/2" CW
1/2" CW
1/2" CW
1/2" CW
2" CW
1/2" CW
1/2" CW
1/2" CW
2" CW
1 1/2" CW
1 1/4" HW
1 1/2" CW
1 1/2" CW
1 1/4" CW
1/2" CW
1/2" CW
1 1/2" CW
1 1/2" CW
1 1/4" CW
MP08
MP08
1 1/4" HW
1 1/4" HW
1" HW
1 1/2" CW
1" HW
1" HW
1/2" CW
TP-1
2" HW
1 1/2" HW-R
2" CW
2" CW
2 1/2" CW
3/4" CW
3/4" HW
4" CW
4" CW
2" HW
1 1/2" HW-R
1" HW
1 1/2" HW-R
2" HW
4" CW
1 1/4" HW-R
1 1/2" HW
3" CW
2 1/2" CW
1" HW-R
1 1/4" HW
1" HW
1 1/2" CW
2 1/2" CW
2" CW
2" CW
2" CW
2" CW
1 1/2" CW
1 1/2" CW
3/4" CW
2" CW
1 1/2" CW
1 1/4" HW
1 1/2" CW
2 1/2" CW
2" CW
2" CW
2" CW
1 1/4" CW
1/2" HW
1/2" CW
1 1/4" HW
2 1/2" CW
2" CW
1 1/2" CW
P-408
1" HW-R
P-102
2" CW
1 1/2" CW
1 1/2" HW
1 1/2" HW
1 1/2" HW
1" HW-R
1 1/4" HW
1" HW-R
1 1/4" HW
1 1/4" HW
1 1/4" HW
1" HW-R
1 1/4" HW
1 1/4" HW
1/2" HW
1/2" CW
1" HW
1" HW
1" HW
1" HW-R
P-804
3/4" CW
P-804
3/4" CW
P-804
3/4" CW
WALL MOUNTED HOSE BIB
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
AAKGJH
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
DOMESTIC WATER RISER
DIAGRAM
PP-301
-3
P P
/1
/2
.p d f
KEYNOTE LEGEND
KEY DESCRIPTION
MP01 ROUTE 3/4" CW WITH WINTER DRAIN DOWN SHUT-OFF VALVE TO EXISTING WALL
HYDRANT.
MP02 PROVIDE WINTER DRAIN DOWN SHUT-OFF VALVE FOR EXTERIOR WALL HYDRANT.
MP06 PROVIDE DOMESTIC RECIRCULATING HOT WATER CALIBRATED BALANCE SET. SET
TEMPERATURE OF 130° F.
MP08 PROVIDE 1/2" HW SUPPLY CONNECTION TO DISHWASHER. PROVIDE SHUT OFF VALVE
AND CODE APPROVED BACKFLOW PREVENTER. DISCHARGE DISHWASHER DRAIN
INTO NEARBY SINK TAILPIECE THROUGH AN AIR BREAK/AIR GAP.
MP12 PROVIDE 1 1/4" HW & 1 1/4" CW CONNECTIONS TO THERMOSTATIC MIXING VALVE IN
ACCESSIBLE LOCATION FOR EMERGENCY SHOWER & EYE/FACE WASH.
MP16 CROSS 1/2" CW AND 1/2" HW UNDER LAVATORY FOR CORRECT CONNECTION TO
SINK.
PP301
1 DOMESTIC WATER RISER DIAGRAM
CALENN
HEPPNER
E-48270
12/30/2022 A R C H I T E C T S E N G I N E E R S
194 237 190 of 233190 of 233
SYSTEMS.
2. PROVIDE ISOLATION VALVES ON ALL PLUMBING PIPING RUNOUTS FROM
PLUMBING MAINS AND BRANCH MAINS.
3. PROVIDE CLEANOUT IN ACCESSIBLE LOCATION AT THE BASE OF ALL PLUMBING
RISERS.
4. MINIMUM SIZE OF VENT THROUGH ROOF SHALL BE 3" AND LOCATED A MINIMUM
OF 24" FROM ANY WALL OR VERTICAL SURFACE. A MINIMUM OF 12" ABOVE
FINISHED ROOF MATERIAL, AND A MINIMUM OF 12' FROM FRESH AIR INTAKES.
5. INSTALL WATER HAMMER ARRESTORS IN WATER LINES AT CONNECTIONS TO ANY
QUICK CLOSING VALVES LIKE FIXTURES.
6. ALL SANITARY VENT PIPING IS 2" UNLESS NOTED OTHERWISE.
PLUMBING RISER GENERAL NOTES
4" SS
2" SS
P-514
4" SS
P-514
P-514
P-102
3" SS
4" SS
FS-1
3" V
4" VTR
404-SP-01
2" PD
FD-1
4" SS
2" V
FD-1
2" V
FD-1
4" SS
4" V
6" V
3" V
4" V
4" SS
4" FCO
FD-14" SS
P-102
P-408
4" FCO
4" SS
P-524
3" V4" SS
P-102
3" V
P-408
P-524 6" SS
P-102
2" SS
2" SS
3" V
2" SS
2" SS
P-604
P-102 P-102
4" SS
2" SS
2" V
4" FCO
P-408
P-102
P-102
2" V
4" SS
P-102 P-102
4" SS
2" V
FS-1
4" VTR
4" V
3" SS
3" FCO
3" VTR
2" V
FS-1 3" SS
2" SS
P-512
4" SS
P-102
2" SS
4" SS
3" SS
3" V
4" VTR
3" V
4" V
4" V
P-512
3" SS
2" SS
4" SS
P-102
P-408
P-528
P-408
4" FCO
4" WCO
P-408
4" WCO
FS-1
P-408
4" WCO
P-408
P-6044" WCOP-408
4" WCO
P-524 P-408
P-408
P-102
P-102
4" WCO
P-408
P-604
P-102
4" WCO
FS-1
P-408
4" FCO
P-408
4" WCO
2" SS
P-512
3" V
404-SP-02
3" SS
FS-1
P-408
4" WCO
4" WCO
P-514
P-408
P-4084" WCO
4" FCO
P-514
4" FCO
P-707
PT-1
6" SS
4" SS
2" SS
2" V
2" V
2" SS
4" SS
4" SS
4" SS
6" SS
4" SS
2" SS
4" SS
4" SS
3" SS
2" SS
P-501
4" SS 2" SS
4" SS
MP11
MP10
MP03
6" SS
P-408
4" WCO
P-102
4" SS
4" SS
4" SS
2" SS
2" SS
2 1/2" PD
MP07
3" SS
3" FCO
4" SS
4" SS
2" SS
3" V
4" V
3" FCO
3" SS
4" SS
2" SS
4" SS
2" SS4" SS
4" SS
4" SS
3" SS
3" SS
3" FCO
P-501
3" SS
P-501
3" V
4" SS
4" SS
3" V
2" V 2" V
3" V
2" V
6" V 6" V
2" V
2" SS
4" SS
4" SS
4" SS
4" SS
4" SS
2" SS 4" SS
2" SS
4" SS
2" SS
4" SS
3" FCO
3" SS
3" VTR
3" V
3" V 4" V
2" SS
2" SS
4" SS
2" SS
4" SS
4" SS
2" SS
2" SS
4" SS
4" SS
2" SS
2" SS
4" SS
4" SS
4" SS
2" SS
4" SS
2" SS
3" V
2" V
2" V
2" V
4" FCO
4" SS
4" SS
3" V
3" V
2 1/2" PD
4" SS
4" SS
2" SS
2" V
3" V
2" V
2" V
2" V
3" V
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
AAKGJH
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
SANITARY WASTE & VENT RISER
DIAGRAMS
PP-302
-3
P P
/1
/2
.p d f
KEYNOTE LEGEND
KEY DESCRIPTION
MP03 ROUTE 2" VENT DOWN TO CONDENSATE RECEIVER AND PUMP TRAP.
MP07 DISCHARGE 2 1/2" PD TO 4" VENTED STAND PIPE WITH 6X4 HUB DRAIN. CONNECT
STAND PIPE DRAIN TO BUILDING STORM DRAINAGE SYSTEM PER CODE
REQUIREMENTS.
MP10 ROUTE 4" VENT DOWN TO PRESSURE SAFETY VALVE CONNECTION AT EXISTING
PRESSURE REDUCING VALVE STATION.
MP11 EXTEND VENT PIPING THROUGH EXTERIOR WALL WITH SCREENED ELBOW LOOKING
DOWN. TERMINATE PAST BUILDING OVERHANG.
PP302
1 SANITARY WASTE & VENT RISER DIAGRAMS
CALENN
HEPPNER
E-48270
12/30/2022 A R C H I T E C T S E N G I N E E R S
195 237 191 of 233191 of 233
6" SD
4" SD
4" SD
6" SD
6" SD
3" SD
3" SD
4" SD
3" SD
3" SD
4" SD
3" SD
6" SD
4" SD
4" SD
3" SD
4" FCO
3" SD
4" SD
4" FCO
3" SD
4" SD
6" OSD
4" OSDRD-1
RD-1
4" SD
4" OSD
6" SD
4" SD
6" SD
3" SD
4" FCO
4" SD
4" SD
3" SD
4" SD
6" SD
4" SD
6" SD
3" SD
3" SD
4" FCO
6" SD
6" SD
4" SD
3" SD
6" SD
4" FCO
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP04
MP07
6" DOWNSPOUT
NOZZLE
3,820 SF
4" SD
6" OSD
6" SD
6" OSD
4" FCO
4" FCO
MP18
MP18
MP18
MP18 MP18
MP18
MP18
MP18
MP18
MP18
MP18
MP18
MP18
MP18
6" SD
4" SD
6" SD
6" SD
3" SD
4" SD
4" SD
4" SD
Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:PROFESSIONAL SEAL:
Revisions: Date: CONSULTANT:
23456789101112131415
B
C
D
E
F
G
H
I
J
123456789101112131415
/8
/4
/8
/2
/4
-1
/2
Drawing of
Architect:
CB DESIGN GROUP, INC
421 King St., Suite 301 Alexcandria, VA 22314 POC: Wes Bridges, AIA 703.772.4213
Consultant:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
A R C H I T E C T S E N G I N E E R S
TOMAH VAMC
TOMAH, WISCONSIN
DECEMBER 15, 2022
676-325
AAKGJH
EXPAND AND RENOVATE B404 FOR
OUTPATIENT MENTAL HEALTH
BID SET
STORM DRAINAGE RISER
DIAGRAM
PP-303
-3
P P
/1
/2
.p d f
PP303
1 STORM DRAINAGE RISER DIAGRAM
KEYNOTE LEGEND
KEY DESCRIPTION
MP04 ROUTE NEW STORM DRAINAGE PIPING SYSTEM AND RISERS TO FOLLOW EXISTING
STORM DRAINAGE PIPING ROUTE UP TO EXISTING ROOF GUTTER OUTLET.
MP07 DISCHARGE 2 1/2" PD TO 4" VENTED STAND PIPE WITH 6X4 HUB DRAIN. CONNECT
STAND PIPE DRAIN TO BUILDING STORM DRAINAGE SYSTEM PER CODE
REQUIREMENTS.
MP18 PROVIDE CLEANOUTS AT THE BOTTOM OF EACH STORM DRAINAGE RISER.
CALENN
HEPPNER
E-48270
12/30/2022 A R C H I T E C T S E N G I N E E R S
196 237 192 of 233192 of 233
M
M
REFER TO CONTROL
VALVE DETAIL (TYP)
REFER TO MASTER
MIXING VALVES DETAIL
REFER TO IN-LINE
RECIRULATION PUMP
DETAIL
140 F RHW FROM BUILDING
HOT WATER RECIRCULATING
SYST…