This document is a summary of a federal contract opportunity to expand and renovate space at the Tomah VA Medical Center in Wisconsin. The Department of Veterans Affairs Technology Acquisition Center Austin is soliciting proposals under solicitation number 36C77623B0050_1 to complete minor construction work expanding and renovating room B404 for outpatient mental health services. Specifically, the project involves replacing the HVAC and AC system as well as other renovations as outlined in Attachment 32 of the solicitation documents. Proposals are due by the date specified in the solicitation for the design and execution of this construction project at the Tomah VAMC.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT NO.: 676-16-102
LOCATION MAP
PROJECT TEAM
PROJECT LEADER/ARCHITECT
ELECTRICAL
FIRE PROTECTION
PENN CONSTRUCTION GROOP
MILWAUKEE, WI
309 N. WATER ST.,
SUITE 650
MILWAUKEE, WI 53202
PHONE: (414) 391-2797
VETERANS AFFAIRS MEDICAL CENTER
500 E VETERANS ST
TOMAH, WI 54660
CAMPUS MAP SHEET INDEX
IN THE CASE OF CONFLICTS OR DISCREPANCIES
WITHIN OR AMONG THE CONTRACT DRAWINGS, THE
BETTER QUALITY, MORE STRINGENT REQUIREMENTS
OR GREATER QUANTITY OF WORK, AS DETERMINED
BY THE GOVERNMENT, SHALL BE PROVIDED.
MECHANICAL
PENN CONSTRUCTION GROUP
MILWAUKEE, WI
309 N. WATER ST.
SUITE 650
MILWAUKEE, WI 53202
PLUMBING
REPLACE HVAC & AC B404
SHEET NUMBER SHEET NAME
ISSUED FOR
35% SDs
09/06/2017
ARCHITECTURAL
A001 ARCHITECTURAL LEGEND, ABBREVIATIONS, SCHEDULES,
AND DETAILS
X
AD101 ARCHITECTURAL DEMOLITION X
AS101 ARCHITECTURAL NEW WORK X
A401 ARCHITECTURAL ELEVATIONS
MECHANICAL
M001 MECHANICAL LEGEND, ABBREVIATIONS, AND NOTES X
X
X
X
X
X
X
X
X
M501 MECHANICAL DETAILS AND DIAGRAMS
M502
PLUMBING
P001 PLUMBING LEGEND, ABBREVIATIONS, AND DIAGRAMS X
XPD101 PLUMBING DEMOLITION
XPL101 PLUMBING NEW WORK - THIRD FLOOR X
FIRE PROTECTION
F001 FIRE PROTECTION LEGEND, ABBREVIATIONS, SCHEDULES
AND DETAILS
X
FD102 FIRE PROTECTION DETECTION AND ALARM DEMOLITION
XFD101 FIRE PROTECTION SUPPRESSION DEMOLITION
ELECTRICAL
E001 ELECTRICAL LEGEND, ABBREVIATIONS, AND SCHEDULE
ED101 ELECTRICAL DEMOLITION
ISSUED FOR
65% DDs
11/03/2017
MECHANICAL DETAILS AND DIAGRAMS
M601 MECHANICAL SCHEDULES
PENN CONSTRUCTION GROUP
MILWAUKEE, WI
309 N. WATER ST.
SUITE 650
MILWAUKEE, WI 53202
PENN CONSTRUCTION GROUP
MILWAUKEE, WI
309 N. WATER ST.
SUITE 650
MILWAUKEE, WI 53202
PENN CONSTRUCTION GROUP
MILWAUKEE, WI
309 N. WATER ST.
SUITE 650
MILWAUKEE, WI 53202
GENERAL INFORMATION
GI001 TITLE SHEET X
ISSUED FOR
95% CDs
12/22/17
ISSUED FOR
100% CDs
02/09/18
ES101 ELECTRICAL NEW WORK
E301 ELECTRICAL MCC ELEVATIONS
E302 ELECTRICAL MCC ELEVATIONS
M701
M703
M704
MECHANICAL CONTROL DIAGRAMS
MECHANICAL AIR FLOW DIAGRAMS
MECHANICAL FLOW DIAGRAMS
FA101 FIRE PROTECTION DETECTION AND ALARM NEW WORK
M301 MECHANICAL SECTIONS
FIRE PROTECTION SUPPRESSION NEW WORKFX101
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
PROJECT LEADER:
B
A
C
D
E
F
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Tomah, Wisconsin
676-16-102
Office of
Facilities
Management
RECORD DRAWINGS
January 13, 2023
CONSULTANTS:
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
Replace HVAC & AC B404
309 N. Water St Suite 650 Milwaukee, Wisconsin 53202
GI001
MDG
TITLE SHEET
HFB
X
X
X
MD101 MECHANICAL BASEMENT DEMOLITION X
MD102-A MECHANICAL PARTIAL ATTIC DEMOLITION - DUCTWORK X
MD102-B MECHANICAL PARTIAL ATTIC DEMOLITION - DUCTWORK X
MD102-C MECHANICAL PARTIAL ATTIC DEMOLITION - DUCTWORK X
MD103-A MECHANICAL PARTIAL ATTIC DEMOLITION - PIPING X
MD103-B MECHANICAL PARTIAL ATTIC DEMOLITION - PIPING X
MD103-C MECHANICAL PARTIAL ATTIC DEMOLITION - PIPING X
X
MH101 MECHANICAL BASEMENT NEW WORK
MH102-A MECHANICAL PARTIAL ATTIC NEW WORK - DUCTWORK
MH102-B MECHANICAL PARTIAL ATTIC NEW WORK - DUCTWORK
MH102-C MECHANICAL PARTIAL ATTIC NEW WORK - DUCTWORK
MP102-A MECHANICAL PARTIAL ATTIC NEW WORK - PIPING
MP102-B MECHANICAL PARTIAL ATTIC NEW WORK - PIPING
MP102-C MECHANICAL PARTIAL ATTIC NEW WORK - PIPING
GC101 PHASING DEMOLITION X
GC102 PHASING NEW WORK X
X
X
X
X
X
A402 ARCHITECTURAL ELEVATIONS
X
X
GC104
INFECTION CONTROL GENERAL NOTES AND DETAILS
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
XX
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
GC103
X
PL102 PLUMBING NEW WORK - ATTIC X
X
X
AS201 ARCHITECTURAL REFLECTED CEILING PLAN
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
XX
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
INFECTION CONTROL PLANS X
X
X
M702 MECHANICAL CONTROL DIAGRAMS X
M302 MECHANICAL SECTIONS X X X
CIVIL
C001 SITE DETAILS
C101 SITE STAGING AND EQUIPMENT LAYOUT PLAN X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
XX
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
PROJECT
LOCATION
ISSUED FOR
CONSTRUCTION
07/09/21
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
XX
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231, OCT 1978
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
PROJECT LEADER:
B
A
C
D
E
F
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Tomah, Wisconsin
676-16-102
Office of
Facilities
Management
RECORD DRAWINGS
January 13, 2023
ATTIC KEY PLAN
CONSULTANTS:
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
Replace HVAC & AC B404
309 N. Water St Suite 650 Milwaukee, Wisconsin 53202
GC101
JMD
PHASING DEMOLITION
HFB
1/8" = 1'-0"
ATTIC PLAN
AutoCAD SHX Text
AutoCAD SHX Text 1A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 17A
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text F
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text F
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ATTIC
AutoCAD SHX Text
AREA
AutoCAD SHX Text
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text 20X20
AutoCAD SHX Text 30X14
AutoCAD SHX Text
AutoCAD SHX Text
PLENUM
AutoCAD SHX Text M
AutoCAD SHX Text 16X10
AutoCAD SHX Text
DN
AutoCAD SHX Text 16X10
AutoCAD SHX Text 16X12
AutoCAD SHX Text 16X12
AutoCAD SHX Text
DN
AutoCAD SHX Text 52X18
AutoCAD SHX Text 16X12
AutoCAD SHX Text 14X16
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text
16X10 ABOVE 16X12 BELOW
AutoCAD SHX Text
AutoCAD SHX Text 26X16
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text 22X24
AutoCAD SHX Text 26X16
AutoCAD SHX Text M
AutoCAD SHX Text 30X16
AutoCAD SHX Text M
AutoCAD SHX Text 22X24
AutoCAD SHX Text 22X24
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text 22X24
AutoCAD SHX Text 22X48
AutoCAD SHX Text 42X14
AutoCAD SHX Text M
AutoCAD SHX Text 22X24
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text 22X24
AutoCAD SHX Text 14X16
AutoCAD SHX Text 14X16
AutoCAD SHX Text 36X20
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 56X14
AutoCAD SHX Text 36X20
AutoCAD SHX Text 16X12
AutoCAD SHX Text 16X10
AutoCAD SHX Text 14X16
AutoCAD SHX Text 10X12
AutoCAD SHX Text 10X12
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text 48X18
AutoCAD SHX Text 42X14
AutoCAD SHX Text 36X24
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text 56X14
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text 30X16
AutoCAD SHX Text 30X14
AutoCAD SHX Text 24X22
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text 24X22
AutoCAD SHX Text M
AutoCAD SHX Text 16X14
AutoCAD SHX Text 16X14
AutoCAD SHX Text
AutoCAD SHX Text 30X26
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text 56X14
AutoCAD SHX Text 42X14
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text 26X14
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text 18X22
AutoCAD SHX Text 20X20
AutoCAD SHX Text
AutoCAD SHX Text 20X20
AutoCAD SHX Text
AutoCAD SHX Text 16X26
AutoCAD SHX Text M
AutoCAD SHX Text 24X18
AutoCAD SHX Text 24X22
AutoCAD SHX Text 22X40
AutoCAD SHX Text
404-EF-2-2
AutoCAD SHX Text
404-EF-8
AutoCAD SHX Text
404-EF-3-1
AutoCAD SHX Text 16X24
AutoCAD SHX Text PHASE 1 - REPLACE EXHAUST FANS EF-1, EF-3-1, AND EF-3-2 DEMOLITION. - EXISTING DUCTWORK PARTIALLY BLOCKS EXISTING ACCESS DOORS. EXISTING DUCTWORK PARTIALLY BLOCKS EXISTING ACCESS DOORS. - CUT NEW TEMPORARY OPENING IN EAST WALL. SALVAGE EXISTING CUT NEW TEMPORARY OPENING IN EAST WALL. SALVAGE EXISTING BRICK FOR RE-USE. - PROVIDE A TEMPORARY EXHAUST FAN AND EXHAUST THROUGH THE PROVIDE A TEMPORARY EXHAUST FAN AND EXHAUST THROUGH THE NEW TEMPORARY OPENING IN EAST WALL. EC TO PROVIDE A TEMPORARY POWER FEEDER TO THE EXHAUST FAN FROM EXISTING MCC-2. EC TO PROVIDE A NEW FUSED SWITCH IN EXISTING BUSSED CUBICLE SPACE IN MCC-2. - PROVIDE SCREENED OUTLET FOR EXHAUST AND SEAL ALL AROUND PROVIDE SCREENED OUTLET FOR EXHAUST AND SEAL ALL AROUND EXHAUST DUCT. - REMOVE/DEMOLISH EXISTING EXHAUST FANS, EF-1, EF-3-1 AND REMOVE/DEMOLISH EXISTING EXHAUST FANS, EF-1, EF-3-1 AND EF-3-2. CONDUIT, POWER CONDUCTORS, CONTROLS AND DISCONNECT SWITCHES SHALL BE REMOVED BACK TO POWER DISTRIBUTION SOURCE(S) SERVING EACH SYSTEM. - INSTALL NEW EXHAUST FAN EF-1, ENERGY RECOVERY COIL, INSTALL NEW EXHAUST FAN EF-1, ENERGY RECOVERY COIL, DUCTWORK, AND RELATED ACCESSORIES. PROVIDE NEW CONDUIT, POWER CONDUCTORS AND LOCAL DISCONNECT SWITCH AS REQUIRED. EF-1 SHALL BE FED FROM EXISTING MCC-2. - REMOVE TEMPORARY FAN AND DUCTWORK. DISCONNECT AND REMOVE REMOVE TEMPORARY FAN AND DUCTWORK. DISCONNECT AND REMOVE TEMPORARY POWER FEEDER TO EXHAUST FAN. TEMPORARY FUSED SWITCH USED FOR EXHAUST FAN TO REMAIN. - INFILL TEMPORARY OPENING IN EAST WALL TO MATCH EXISTING INFILL TEMPORARY OPENING IN EAST WALL TO MATCH EXISTING CONSTRUCTION. RE-USE SALVAGED BRICK OR PROVIDE NEW BRICK TO MATCH EXISTING. PHASE 2 - OPEN EXISTING WEST WALL AND INSTALL NEW 6 FT BY 6 FT OPENING FOR ACCESS DOORS, REPLACE EXHAUST FANS. - EXISTING DUCTS COVER THE WEST WALL MAKING ACCESS EXISTING DUCTS COVER THE WEST WALL MAKING ACCESS IMPOSSIBLE. - CUT NEW OPENINGS IN THE EXISTING WEST WALL FOR NEW CUT NEW OPENINGS IN THE EXISTING WEST WALL FOR NEW DOORWAY AND A TEMPORARY OPENING. SALVAGE EXISTING BRICK FOR RE-USE. - PROVIDE TEMPORARY EXHAUST FAN AND EXHAUST THROUGH PROVIDE TEMPORARY EXHAUST FAN AND EXHAUST THROUGH TEMPORARY OPENING IN WEST WALL. EC TO PROVIDE A TEMPORARY POWER FEEDER TO THE EXHAUST FAN FROM EXISTING MCC-3. EC TO PROVIDE A NEW FUSED SWITCH IN EXISTING BUSSED CUBICLE SPACE IN MCC-3. - PROVIDE SCREENED OUTLET FOR EXHAUST AND SEAL ALL AROUND PROVIDE SCREENED OUTLET FOR EXHAUST AND SEAL ALL AROUND EXHAUST DUCT. - PROVIDE NEW EXHAUST DUCT CONNECTIONS TO THE NEW LOUVER(S) PROVIDE NEW EXHAUST DUCT CONNECTIONS TO THE NEW LOUVER(S) TO NEW EXHAUST FAN(S). - REMOVE/DEMOLISH EXISTING EXHAUST FANS, EF-2-3, EF-5-1 AND REMOVE/DEMOLISH EXISTING EXHAUST FANS, EF-2-3, EF-5-1 AND EF-5-2. CONDUIT, POWER CONDUCTORS, CONTROLS AND DISCONNECT SWITCHES SHALL BE REMOVED BACK TO POWER DISTRIBUTION SOURCE(S) SERVING EACH SYSTEM. - INSTALL NEW EXHAUST FAN EF-5, ENERGY RECOVERY COIL, INSTALL NEW EXHAUST FAN EF-5, ENERGY RECOVERY COIL, DUCTWORK, AND RELATED ACCESSORIES. PROVIDE NEW CONDUIT, POWER CONDUCTORS AND LOCAL DISCONNECT SWITCH. EF-5 SHALL BE FED FROM EXISTING MCC-3. - REMOVE TEMPORARY FAN AND DUCTWORK. DISCONNECT AND REMOVE REMOVE TEMPORARY FAN AND DUCTWORK. DISCONNECT AND REMOVE TEMPORARY POWER FEEDER TO EXHAUST FAN. TEMPORARY FUSED SWITCH USED FOR EXHAUST FAN TO REMAIN. - PROVIDE NEW 6 FT BY 6 FT DOORS IN WEST WALL. PROVIDE NEW 6 FT BY 6 FT DOORS IN WEST WALL. - INFILL TEMPORARY OPENING IN WEST WALL TO MATCH EXISTING INFILL TEMPORARY OPENING IN WEST WALL TO MATCH EXISTING CONSTRUCTION. RE-USE SALVAGED BRICK OR PROVIDE NEW BRICK TO MATCH EXISTING. PHASE 3 - AHU 1 AND 3 REMOVAL AND REPLACEMENT - ALL WORK SHALL BE COMPLETED BETWEEN THE DATES NOVEMBER 1 ALL WORK SHALL BE COMPLETED BETWEEN THE DATES NOVEMBER 1 AND APRIL 1. DURING THIS TIME IT IS EXPECTED THE AHU OPERATE AT MINIMUM AIRFLOWS. PHASE 3A - PROVIDE TEMPORARY SUPPLY AND RETURN DUCT CONNECTIONS PROVIDE TEMPORARY SUPPLY AND RETURN DUCT CONNECTIONS BETWEEN AHU-3 AND AHU-1. - REMOVE SUPPLY AND RETURN DUCTWORK FOR AHU-1. REMOVE SUPPLY AND RETURN DUCTWORK FOR AHU-1. - REMOVE CHILLED WATER, STEAM, AND CONDENSATE PIPING AT REMOVE CHILLED WATER, STEAM, AND CONDENSATE PIPING AT AHU-1. - COMPLETELY REMOVE EXISTING AHU-1 AND RF-1. CONDUIT, POWER COMPLETELY REMOVE EXISTING AHU-1 AND RF-1. CONDUIT, POWER CONDUCTORS, CONTROLS AND DISCONNECT SWITCHES SHALL BE REMOVED BACK TO POWER DISTRIBUTION SOURCE(S) SERVING SYSTEM. PHASE 3C - REMOVE CHILLED WATER, STEAM, AND CONDENSATE PIPING AT REMOVE CHILLED WATER, STEAM, AND CONDENSATE PIPING AT EXISTING AHU-3. - COMPLETELY REMOVE EXISTING AHU-3 AND RF-3. CONDUIT, POWER COMPLETELY REMOVE EXISTING AHU-3 AND RF-3. CONDUIT, POWER CONDUCTORS, CONTROLS AND DISCONNECT SWITCHES SHALL BE REMOVED BACK TO POWER DISTRIBUTION SOURCE(S) SERVING SYSTEM. PHASE 4 - AHU 2 AND 5 REMOVAL AND REPLACEMENT - ALL WORK SHALL BE COMPLETED BETWEEN THE DATES NOVEMBER 1 ALL WORK SHALL BE COMPLETED BETWEEN THE DATES NOVEMBER 1 AND APRIL 1. DURING THIS TIME IT IS EXPECTED THE AHU OPERATE MINIMUM AIRFLOWS. PHASE 4A - PROVIDE TEMPORARY SUPPLY AND RETURN DUCT CONNECTIONS PROVIDE TEMPORARY SUPPLY AND RETURN DUCT CONNECTIONS BETWEEN AHU-5 AND AHU-2. PROVIDE A TEMPORARY CONNECTION BETWEEN THE DISCHARGE OF RF-2 AND THE RETURN DUCTWORK OF AHU-5. - REMOVE SUPPLY AND RETURN DUCTWORK FOR AHU-2. REMOVE SUPPLY AND RETURN DUCTWORK FOR AHU-2. - REMOVE CHILLED WATER, STEAM, AND CONDENSATE PIPING AHU-2. REMOVE CHILLED WATER, STEAM, AND CONDENSATE PIPING AHU-2. - COMPLETELY REMOVE EXISTING AHU-2. CONDUIT, POWER COMPLETELY REMOVE EXISTING AHU-2. CONDUIT, POWER CONDUCTORS, CONTROLS AND DISCONNECT SWITCHES SHALL BE REMOVED BACK TO POWER DISTRIBUTION SOURCE(S) SERVING SYSTEM. PHASE 4B - DEMO EXISTING RF-5. CONDUIT, POWER CONDUCTORS, CONTROLS DEMO EXISTING RF-5. CONDUIT, POWER CONDUCTORS, CONTROLS AND DISCONNECT SWITCHES SHALL BE REMOVED BACK TO POWER DISTRIBUTION SOURCE(S) SERVING SYSTEM. PROVIDE TEMPORARY INLINE FAN IN DUCTWORK TO REPLACE RF-5. EC TO PROVIDE A TEMPORARY POWER FEEDER TO THE INLINE FAN FROM EXISTING MCC-2. EC TO PROVIDE A NEW FUSED SWITCH IN EXISTING BUSSED SPACE IN MCC-2. - DEMO EXISTING EF-9. CONDUIT, POWER CONDUCTORS, CONTROLS DEMO EXISTING EF-9. CONDUIT, POWER CONDUCTORS, CONTROLS AND DISCONNECT SWITCHES SHALL BE REMOVED BACK TO POWER DISTRIBUTION SOURCE(S) SERVING SYSTEM. PHASE 4D - REMOVE CHILLED WATER, STEAM, AND CONDENSATE PIPING AHU-5. REMOVE CHILLED WATER, STEAM, AND CONDENSATE PIPING AHU-5. - COMPLETELY REMOVE EXISTING AHU-5, RF-2, AND TEMPORARY COMPLETELY REMOVE EXISTING AHU-5, RF-2, AND TEMPORARY INLINE FAN. RECONNECT RETURN DUCTS WHERE FANS WERE REMOVED. CONDUIT, POWER CONDUCTORS, CONTROLS AND DISCONNECT SWITCHES SHALL BE REMOVED BACK TO POWER DISTRIBUTION SOURCE(S) SERVING SYSTEM. PHASE 5 - AHU-4 REMOVAL AND REPLACEMENT - PHASE 5 WORK SHALL BE COMPLETED ONLY AFTER PHASES 1 PHASE 5 WORK SHALL BE COMPLETED ONLY AFTER PHASES 1 THROUGH 4 ARE COMPLETED. PHASE 5A - PROVIDE TEMPORARY OPENING IN THE SOUTH WALL. OPENING IS PROVIDE TEMPORARY OPENING IN THE SOUTH WALL. OPENING IS FOR REMOVAL OF EXISTING AHU-4 AND NEW AHU-4 IN PLACE. PROVIDE FALL PROTECTION AT OPENING AND PROVIDE A TEMPORARY REMOVABLE STUD WALL WITH VISQUEEN COVER TO PROTECT ATTIC FROM WEATHER, RAIN, WIND AND SNOW. - SALVAGE ALL EXTERIOR MATERIALS FOR REPLACEMENT. SALVAGE ALL EXTERIOR MATERIALS FOR REPLACEMENT. - PROVIDE A TEMPORARY UNIT WITH STEAM HEATING AND PROVIDE PROVIDE A TEMPORARY UNIT WITH STEAM HEATING AND PROVIDE TEMPORARY SUPPLY AND RETURN DUCT CONNECTIONS. EC TO PROVIDE A TEMPORARY POWER FEEDER TO NEW UNIT FROM EXISTING MCC-2. EC TO PROVIDE A NEW FUSED SWITCH IN EXISTING BUSSED SPACE IN MCC-2. PHASE 5B - REMOVE SUPPLY DUCTWORK FOR AHU-4. KEEP EXISTING RETURN REMOVE SUPPLY DUCTWORK FOR AHU-4. KEEP EXISTING RETURN DUCTWORK WHILE TEMPORARY UNIT IS REQUIRED. - REMOVE CHILLED WATER, STEAM, AND CONDENSATE PIPING AT REMOVE CHILLED WATER, STEAM, AND CONDENSATE PIPING AT AHU-4. - COMPLETELY REMOVE EXISTING AHU-4 AND RF-4. CONDUIT, POWER COMPLETELY REMOVE EXISTING AHU-4 AND RF-4. CONDUIT, POWER CONDUCTORS, CONTROLS AND DISCONNECT SWITCHES SHALL BE REMOVED BACK TO POWER DISTRIBUTION SOURCE(S) SERVING SYSTEM. PHASE 5C - PROVIDE NEW AHU-4 IN LOCATION OF DEMOLISHED AHU-4. PROVIDE PROVIDE NEW AHU-4 IN LOCATION OF DEMOLISHED AHU-4. PROVIDE NEW CONDUIT, POWER CONDUCTORS AND LOCAL DISCONNECT SWITCH AS REQUIRED. AHU-4 SHALL BE FED FROM EXISTING MCC-3. EC TO REUSE EXISTING FUSED SWITCH IN MCC-2 AND PROVIDE NEW FUSES AS REQUIRED. - PROVIDE CHILLED WATER, STEAM AND CONDENSATE PIPING TO NEW PROVIDE CHILLED WATER, STEAM AND CONDENSATE PIPING TO NEW AHU-4. - PROVIDE PERMANENT CONNECTIONS TO SUPPLY AND RETURN DUCTS PROVIDE PERMANENT CONNECTIONS TO SUPPLY AND RETURN DUCTS FOR AHU-4. - REMOVE TEMPORARY UNIT. DEMO RETURN DUCTWORK NOT REMOVED REMOVE TEMPORARY UNIT. DEMO RETURN DUCTWORK NOT REMOVED DURING PHASE 5B. TEMPORARY FUSED SWITCH USED FOR AHU UNIT TO REMAIN IN MCC-3. - INFILL TEMPORARY OPENING IN SOUTH WALL TO MATCH EXISTING INFILL TEMPORARY OPENING IN SOUTH WALL TO MATCH EXISTING CONSTRUCTION. RE-USE SALVAGED BRICK OR PROVIDE NEW BRICK TO MATCH EXISTING.
AutoCAD SHX Text NOTES: 1. USE EXISTING FANS ABD EQUIPMENT AS LONG AS POSSIBLE. USE EXISTING FANS ABD EQUIPMENT AS LONG AS POSSIBLE. 2. NEW EXHAUST FANS SET IN PLACE MAY ELIMINATE THE NEED FOR NEW EXHAUST FANS SET IN PLACE MAY ELIMINATE THE NEED FOR TEMPORARY EXHAUST FANS. 3. TEMPORARY EXHAUST FAN #1 FOR EF-1, EF-3-1 AND EF-3-2 TEMPORARY EXHAUST FAN #1 FOR EF-1, EF-3-1 AND EF-3-2 USE GREENHECK BSQ-240HP OR EQUIVALENT. 4. TEMPORARY EXHAUST FAN #2 FOR EF-5-1, EF-5-2 AND EF-2-3 TEMPORARY EXHAUST FAN #2 FOR EF-5-1, EF-5-2 AND EF-2-3 USE GREENHECK BSQ-300HP OR EQUIVALENT. 5. MOUNTING AND CONNECTIONS PER SPECIFICATIONS, DETAILS, AND MOUNTING AND CONNECTIONS PER SPECIFICATIONS, DETAILS, AND REQUIRED SMACNA STANDARDS. 6. TEMPORARY RETURN FAN #5 FOR USE GREENHECK BSQ-240HP OR TEMPORARY RETURN FAN #5 FOR USE GREENHECK BSQ-240HP OR EQUIVALENT. 7. TEMPORARY AHU-4, 4230CFM SUPPLY AIR, 2200 OUTDOOR AIR, TEMPORARY AHU-4, 4230CFM SUPPLY AIR, 2200 OUTDOOR AIR, STEAM HEATING COIL FOR 4230 CFM AT 160 MBH, HUMIDIFIER SECTION AT 208 LB/HR, PREFILTERS, FINAL FILTERS, AND VFD'S. USE JCI SOLUTION MODEL OR EQUIVALENT.
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
PROJECT LEADER:
B
A
C
D
E
F
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Tomah, Wisconsin
676-16-102
Office of
Facilities
Management
RECORD DRAWINGS
January 13, 2023
ATTIC KEY PLAN
CONSULTANTS:
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
Replace HVAC & AC B404
309 N. Water St Suite 650 Milwaukee, Wisconsin 53202
GC102
JMD
PHASING NEW WORK
HFB
1/8" = 1'-0"
ATTIC PLAN
AutoCAD SHX Text
AutoCAD SHX Text 1A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 17A
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text F
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text F
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
ATTIC
AutoCAD SHX Text
AREA
AutoCAD SHX Text
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text PHASE 1 - REPLACE EXHAUST FANS EF-1, EF-3-1, AND EF-3-2 NEW WORK. - INSTALL NEW EXHAUST FAN EF-1, ENERGY RECOVERY COIL, DUCTWORK, INSTALL NEW EXHAUST FAN EF-1, ENERGY RECOVERY COIL, DUCTWORK, AND RELATED ACCESSORIES. PROVIDE NEW CONDUIT, POWER CONDUCTORS AND LOCAL DISCONNECT SWITCH AS REQUIRED. EF-1 SHALL BE FED FROM EXISTING MCC-2. - REMOVE TEMPORARY FAN AND DUCTWORK. DISCONNECT AND REMOVE REMOVE TEMPORARY FAN AND DUCTWORK. DISCONNECT AND REMOVE TEMPORARY POWER FEEDER TO EXHAUST FAN. TEMPORARY FUSED SWITCH USED FOR EXHAUST FAN TO REMAIN. - INFILL TEMPORARY OPENING IN EAST WALL TO MATCH EXISTING INFILL TEMPORARY OPENING IN EAST WALL TO MATCH EXISTING CONSTRUCTION. RE-USE SALVAGED BRICK OR PROVIDE NEW BRICK TO MATCH EXISTING. PHASE 2 - OPEN EXISTING WEST WALL AND INSTALL NEW 6 FT BY 6 FT OPENING FOR ACCESS DOORS, REPLACE EXHAUST FANS. - INSTALL NEW EXHAUST FAN EF-5, ENERGY RECOVERY COIL, DUCTWORK, INSTALL NEW EXHAUST FAN EF-5, ENERGY RECOVERY COIL, DUCTWORK, AND RELATED ACCESSORIES. PROVIDE NEW CONDUIT, POWER CONDUCTORS AND LOCAL DISCONNECT SWITCH. EF-5 SHALL BE FED FROM EXISTING MCC-3. - REMOVE TEMPORARY FAN AND DUCTWORK. DISCONNECT AND REMOVE REMOVE TEMPORARY FAN AND DUCTWORK. DISCONNECT AND REMOVE TEMPORARY POWER FEEDER TO EXHAUST FAN. TEMPORARY FUSED SWITCH USED FOR EXHAUST FAN TO REMAIN. - PROVIDE NEW 6 FT BY 6 FT DOORS IN WEST WALL. PROVIDE NEW 6 FT BY 6 FT DOORS IN WEST WALL. - INFILL TEMPORARY OPENING IN WEST WALL TO MATCH EXISTING INFILL TEMPORARY OPENING IN WEST WALL TO MATCH EXISTING CONSTRUCTION. RE-USE SALVAGED BRICK OR PROVIDE NEW BRICK TO MATCH EXISTING. PHASE 3 - AHU 1 AND 3 REMOVAL AND REPLACEMENT - ALL WORK SHALL BE COMPLETED BETWEEN THE DATES NOVEMBER 1 AND ALL WORK SHALL BE COMPLETED BETWEEN THE DATES NOVEMBER 1 AND APRIL 1. DURING THIS TIME IT IS EXPECTED THE AHU OPERATE AT MINIMUM AIRFLOWS. PHASE 3B - PROVIDE NEW AHU-3 IN LOCATION OF DEMOLISHED AHU-1. PROVIDE NEW PROVIDE NEW AHU-3 IN LOCATION OF DEMOLISHED AHU-1. PROVIDE NEW CONDUIT, POWER CONDUCTORS AND LOCAL DISCONNECT SWITCH AS REQUIRED. AHU-3 SHALL BE FED FROM EXISTING MCC-2. EC TO REUSE EXISTING FUSED SWITCH IN MCC-2 AND PROVIDE NEW FUSES AS REQUIRED. - PROVIDE CHILLED WATER, STEAM AND CONDENSATE PIPING TO NEW AHU-3. PROVIDE CHILLED WATER, STEAM AND CONDENSATE PIPING TO NEW AHU-3. - PROVIDE TEMPORARY DISCHARGE PLENUM FOR AHU-3. PROVIDE TEMPORARY DISCHARGE PLENUM FOR AHU-3. - PROVIDE TEMPORARY SUPPLY AND RETURN DUCTS FROM AHU-3 TO PROVIDE TEMPORARY SUPPLY AND RETURN DUCTS FROM AHU-3 TO EXISTING DUCT RISERS. KEEP CROSS CONNECTIONS TO AHU-1. PHASE 3D - PROVIDE NEW AHU-1 IN THE LOCATION WHERE EXISTING AHU-3 PROVIDE NEW AHU-1 IN THE LOCATION WHERE EXISTING AHU-3 WAS. PROVIDE NEW CONDUIT, POWER CONDUCTORS AND LOCAL DISCONNECT SWITCH AS REQUIRED. AHU-1 SHALL BE FED FROM EXISTING MCC-2. EC TO REUSE EXISTING FUSED SWITCH IN MCC-2 AND PROVIDE NEW FUSES AS REQUIRED. - INSTALL PERMANENT DISCHARGE PLENUM AND FINAL FILTERS FOR AHU-3. INSTALL PERMANENT DISCHARGE PLENUM AND FINAL FILTERS FOR AHU-3. - PROVIDE PERMANENT CONNECTIONS TO SUPPLY AND RETURN DUCTS. PROVIDE PERMANENT CONNECTIONS TO SUPPLY AND RETURN DUCTS. - PROVIDE PERMANENT CHILLED WATER, STEAM AND CONDENSATE PROVIDE PERMANENT CHILLED WATER, STEAM AND CONDENSATE CONNECTIONS TO NEW AHU-1. PHASE 4 - AHU 2 AND 5 REMOVAL AND REPLACEMENT - ALL WORK SHALL BE COMPLETED BETWEEN THE DATES NOVEMBER 1 AND ALL WORK SHALL BE COMPLETED BETWEEN THE DATES NOVEMBER 1 AND APRIL 1. DURING THIS TIME IT IS EXPECTED THE AHU OPERATE MINIMUM AIRFLOWS. PHASE 4C - PROVIDE NEW AHU-5 NEAR THE LOCATION OF DEMOLISHED AHU-2 BUT PROVIDE NEW AHU-5 NEAR THE LOCATION OF DEMOLISHED AHU-2 BUT PERPENDICULAR. PROVIDE NEW CONDUIT, POWER CONDUCTORS AND LOCAL DISCONNECT SWITCH AS REQUIRED. AHU-5 SHALL BE FED FROM EXISTING MCC-3. EC TO REUSE EXISTING FUSED SWITCH IN MCC-3 AND PROVIDE NEW FUSES AS REQUIRED. - PROVIDE TEMPORARY DISCHARGE PLENUM FOR AHU-5. PROVIDE TEMPORARY DISCHARGE PLENUM FOR AHU-5. - PROVIDE TEMPORARY SUPPLY AND RETURN DUCTS FROM AHU-5 TO PROVIDE TEMPORARY SUPPLY AND RETURN DUCTS FROM AHU-5 TO EXISTING DUCT RISERS. - PROVIDE CHILLED WATER, STEAM AND CONDENSATE PIPING TO NEW AHU-5. PROVIDE CHILLED WATER, STEAM AND CONDENSATE PIPING TO NEW AHU-5. PHASE 4E - PROVIDE NEW AHU-2 IN THE LOCATION WHERE EXISTING AHU-5 WAS. PROVIDE NEW AHU-2 IN THE LOCATION WHERE EXISTING AHU-5 WAS. PROVIDE NEW CONDUIT, POWER CONDUCTORS AND LOCAL DISCONNECT SWITCH AS REQUIRED. AHU-2 SHALL BE FED FROM EXISTING MCC-3. EC TO REUSE EXISTING FUSED SWITCH IN MCC-3 AND PROVIDE NEW FUSES AS REQUIRED. - PROVIDE PERMANENT CHILLED WATER, STEAM AND CONDENSATE PROVIDE PERMANENT CHILLED WATER, STEAM AND CONDENSATE CONNECTIONS TO NEW AHU-2. - INSTALL PERMANENT DISCHARGE PLENUM AND FINAL FILTERS FOR AHU-5. INSTALL PERMANENT DISCHARGE PLENUM AND FINAL FILTERS FOR AHU-5. - PROVIDE PERMANENT CONNECTIONS TO NEW AHU-2 SUPPLY AND RETURN PROVIDE PERMANENT CONNECTIONS TO NEW AHU-2 SUPPLY AND RETURN DUCTS. PHASE 5 - AHU-4 REMOVAL AND REPLACEMENT - PHASE 5 WORK SHALL BE COMPLETED ONLY AFTER PHASES 1 THROUGH 4 PHASE 5 WORK SHALL BE COMPLETED ONLY AFTER PHASES 1 THROUGH 4 ARE COMPLETED. PHASE 5A - PROVIDE TEMPORARY OPENING IN THE SOUTH WALL. OPENING IS FOR PROVIDE TEMPORARY OPENING IN THE SOUTH WALL. OPENING IS FOR REMOVAL OF EXISTING AHU-4 AND NEW AHU-4 IN PLACE. PROVIDE FALL PROTECTION AT OPENING AND PROVIDE A TEMPORARY REMOVABLE STUD WALL WITH VISQUEEN COVER TO PROTECT ATTIC FROM WEATHER, RAIN, WIND AND SNOW. - SALVAGE ALL EXTERIOR MATERIALS FOR REPLACEMENT. SALVAGE ALL EXTERIOR MATERIALS FOR REPLACEMENT. - PROVIDE A TEMPORARY UNIT WITH STEAM HEATING AND PROVIDE TEMPORARY PROVIDE A TEMPORARY UNIT WITH STEAM HEATING AND PROVIDE TEMPORARY SUPPLY AND RETURN DUCT CONNECTIONS. EC TO PROVIDE A TEMPORARY POWER FEEDER TO NEW UNIT FROM EXISTING MCC-2. EC TO PROVIDE A NEW FUSED SWITCH IN EXISTING BUSSED SPACE IN MCC-2. PHASE 5C - PROVIDE NEW AHU-4 IN LOCATION OF DEMOLISHED AHU-4. PROVIDE NEW PROVIDE NEW AHU-4 IN LOCATION OF DEMOLISHED AHU-4. PROVIDE NEW CONDUIT, POWER CONDUCTORS AND LOCAL DISCONNECT SWITCH AS REQUIRED. AHU-4 SHALL BE FED FROM EXISTING MCC-3. EC TO REUSE EXISTING FUSED SWITCH IN MCC-2 AND PROVIDE NEW FUSES AS REQUIRED. - PROVIDE CHILLED WATER, STEAM AND CONDENSATE PIPING TO NEW AHU-4. PROVIDE CHILLED WATER, STEAM AND CONDENSATE PIPING TO NEW AHU-4. - PROVIDE PERMANENT CONNECTIONS TO SUPPLY AND RETURN DUCTS FOR PROVIDE PERMANENT CONNECTIONS TO SUPPLY AND RETURN DUCTS FOR AHU-4. - REMOVE TEMPORARY UNIT. DEMO RETURN DUCTWORK NOT REMOVED REMOVE TEMPORARY UNIT. DEMO RETURN DUCTWORK NOT REMOVED DURING PHASE 5B. TEMPORARY FUSED SWITCH USED FOR AHU UNIT TO REMAIN IN MCC-3. - INFILL TEMPORARY OPENING IN SOUTH WALL TO MATCH EXISTING INFILL TEMPORARY OPENING IN SOUTH WALL TO MATCH EXISTING CONSTRUCTION. RE-USE SALVAGED BRICK OR PROVIDE NEW BRICK TO MATCH EXISTING.
AutoCAD SHX Text
EA
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text
BDD
AutoCAD SHX Text
BDD
AutoCAD SHX Text
AFMD
AutoCAD SHX Text
AFMD
AutoCAD SHX Text
AFMD
AutoCAD SHX Text
BDD
AutoCAD SHX Text
BDD
AutoCAD SHX Text
VSMC
AutoCAD SHX Text
404-EF-4
AutoCAD SHX Text
VSMC
AutoCAD SHX Text
404-AHU-2-SF
AutoCAD SHX Text
VSMC
AutoCAD SHX Text
404-EF-6
AutoCAD SHX Text
VSMC
AutoCAD SHX Text
404-EF-9
AutoCAD SHX Text
VSMC
AutoCAD SHX Text
404-EF-5
AutoCAD SHX Text
VSMC
AutoCAD SHX Text
404-AHU-2-RF
AutoCAD SHX Text
VSMC
AutoCAD SHX Text
404-AHU-2-RF
AutoCAD SHX Text
VSMC
AutoCAD SHX Text
404-AHU-2-SF
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text
BDD
AutoCAD SHX Text
BDD
AutoCAD SHX Text M
AutoCAD SHX Text
AFMD
AutoCAD SHX Text
AFMD
AutoCAD SHX Text
AFMD
AutoCAD SHX Text
BDD
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text
VSMC
AutoCAD SHX Text
VSMC
AutoCAD SHX Text
VSMC
AutoCAD SHX Text
404-EF-2
AutoCAD SHX Text
404-AHU-1-RF
AutoCAD SHX Text
404-AHU-1-SF
AutoCAD SHX Text
VSMC
AutoCAD SHX Text
404-AHU-3-RF
AutoCAD SHX Text
VSMC
AutoCAD SHX Text
404-AHU-3-SF
AutoCAD SHX Text
VSMC
AutoCAD SHX Text
404-EF-8
AutoCAD SHX Text
VSMC
AutoCAD SHX Text
404-EF-1
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
GC103
KAB
INFECTION CONTROL
GENERAL NOTES AND
DETAILS
BAM
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
PROJECT LEADER:
B
A
C
D
E
F
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Tomah, Wisconsin
676-16-102
Office of
Facilities
Management
RECORD DRAWINGS
January 13, 2023
CONSULTANTS:
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
Replace HVAC & AC B404
309 N. Water St Suite 650 Milwaukee, Wisconsin 53202
INFECTION CONTROL GENERAL NOTES:
INFECTION CONTROL DESIGN NOTES:
1/2" = 1'-0"
1 HOUR CONSTRUCTION (UL #465) & INFECTION CONTROL BARRIER
ICB-1
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231, OCT 1978
AutoCAD SHX Text
1. SEE SPECIFICATION SECTIONS 010000-IC AND 013526 FOR INFECTION CONTROL SEE SPECIFICATION SECTIONS 010000-IC AND 013526 FOR INFECTION CONTROL DESIGN REQUIREMENTS. 2. THE INTENT OF INFECTION CONTROL (IC) ISOLATION IS TO PROTECT PATIENTS IN THE INTENT OF INFECTION CONTROL (IC) ISOLATION IS TO PROTECT PATIENTS IN THE HOSPITAL WHO HAVE LOW IMMUNE LEVELS. THEREFORE, CONSTRUCTION OPERATIONS NEED TO BE DIRECTED TO CONTAIN DUST AND PARTICULATE MATTER TO THE CONSTRUCTION AREA. 3. PROVIDE TRIATEK ISOLATION MONITORS DURING CLASS III OR CLASS IV PROVIDE TRIATEK ISOLATION MONITORS DURING CLASS III OR CLASS IV CONSTRUCTION OPERATIONS. EACH AREA TO BE UNDER NEGATIVE PRESSURE (0.02"WC) DURING THESE OPERATIONS. MONITOR TO MEASURE PRESSURE DIFFERENTIAL BETWEEN CONSTRUCTION AREA AND ADJACENT CORRIDOR OR ROOM AS DIRECTED BY VA COR 4. DURING CONSTRUCTION OPERATIONS IN EACH ENCLOSED AREA USE TRIATEK DURING CONSTRUCTION OPERATIONS IN EACH ENCLOSED AREA USE TRIATEK ISOLATION MONITORS, MINIMUM (1) ONE IN AREAS LESS THAN 1000 SF, (2) TWO MINIMUM IN AREAS BETWEEN 1000 SF AND 5000 SF, AND (3) THREE FOR AREAS BETWEEN 5000 SF AND 10000 SF. CONTRACTOR SHALL PROVIDE EXISTING POWER CONNECTIONS FOR TRIATEK ISOLATION MONITORS OR PROVIDE TEMPORARY POWER TO TRIATEK ISOLATION MONITORS DURING CONSTRUCTION. 5. PROVIDE BALANCING DAMPER IN THE BRANCH SUPPLY & EXHAUST DUCT WORK PROVIDE BALANCING DAMPER IN THE BRANCH SUPPLY & EXHAUST DUCT WORK SERVING THE AFFECTED AREA. TEMPORARILY BALANCE AIR FLOW TO PROVIDE NEGATIVE AIR FLOW IN CONSTRUCTION ZONE AT ALL TIMES AS INDICATED IN NOTE BELOW. DAMPERS TO REMAIN IN DUCT AFTER CONSTRUCTION IS COMPLETE AND IS TO BE SECURED IN FINAL BALANCING POSITION PRIOR TO TURNING SYSTEM OVER FOR OCCUPANCY. 6. THE CONTRACTOR SHALL PROVIDE ENOUGH NEGATIVE AIR MACHINES TO THE CONTRACTOR SHALL PROVIDE ENOUGH NEGATIVE AIR MACHINES TO COMPLETELY EXCHANGE THE REGULATED AREA AIR VOLUME (4) FOUR ACTUAL TIMES PER HOUR. THE COMPETENT PERSON SHALL DETERMINE THE NUMBER OF UNITS NEEDED FOR EACH REGULATED AREA BY DIVIDING THE CUBIC FEET IN THE REGULATED AREA BY (15) FIFTEEN AND THEN DIVIDING THAT RESULT BY THE ACTUAL CUBIC FEET PER MINUTE (CFM) FOR EACH UNIT TO DETERMINE THE NUMBER OF UNITS NEEDED TO EFFECT (4) FOUR AIR CHANGES PER HOUR. PROVIDE A STANDBY UNIT IN THE EVENT OF MACHINE FAILURE AND/OR EMERGENCY IN AN ADJACENT AREA. 7. AS CONSTRUCTION PROGRESSES FROM TYPE D TO TYPE C (SEE SPECIFICATION AS CONSTRUCTION PROGRESSES FROM TYPE D TO TYPE C (SEE SPECIFICATION SECTION 013526 "SAFETY REQUIREMENTS") AND THEREON, REQUEST A NEW "INFECTION CONTROL CONSTRUCTION PERMIT" FROM THE VA INFECTION CONTROL NURSE. UPON AUTHORIZATION, PROCEED TO NEXT TYPE OF CONSTRUCTION. PROVIDE AT LEAST 10 DAYS NOTICE FOR EACH PERMIT. 8. CONSTRUCT IC (INFECTION CONTROL) CONSTRUCTION BARRIER FROM FLOOR TO CONSTRUCT IC (INFECTION CONTROL) CONSTRUCTION BARRIER FROM FLOOR TO DECK/FLOOR ABOVE. SEE DETAIL 3/GC104 & SPECIFICATION SECTION 013526. EXCEPTION: IF BARRIER IS ADJACENT TO A SMOKE, FIRE, OR EXISTING WALL CONSTRUCTION WHICH WILL NOT BE DEMOLISHED AND TERMINATES TO FLOOR OR DECK ABOVE, THEN CONSTRUCT IC BARRIER FROM FLOOR TO ABOVE CORRIDOR CEILING WITH 6 MIL POLY BEING SEALED ON ALL EDGES: FLOOR, TOP OF WALL, SIDES, AND ALL PENETRATIONS. 9. GENERAL CONTRACTOR SHALL PROVIDE NEW YELLOW CONSTRUCTION ACCESS GENERAL CONTRACTOR SHALL PROVIDE NEW YELLOW CONSTRUCTION ACCESS DOORS AND PROXIMITY CARD READERS AT ALL BARRIERS. MAINTAIN ALL INFECTION CONTROL STANDARDS. CONTROL BARRIERS ARE TO BE INSTALLED AND REMOVED ONLY BEFORE 7:00 A.M. AND AFTER 8:00 P.M. IN OCCUPIED AREAS. 12. EGRESS IS TO BE MAINTAINED TO THE STAIRWELLS AT ALL TIMES. 13. PRIOR TO ANY REMOVAL OF SMOKE BARRIER FIRE RATED WALLS, CONSTRUCT NEW SMOKE BARRIER/APPROPRIATE FIRE RATED WALLS PER NEW PLANS OR CONSTRUCT INFECTION CONTROL BARRIER TO ACT AS SMOKE BARRIER. 14. A PORTION OF THE CORRIDOR MAY BE MADE AVAILABLE TO CREATE AN INFECTION CONTROL AREA; HOWEVER, A MINIMUM OF 4 FT MUST BE MAINTAINED OPEN FOR THE MOVEMENT OF PERSONNEL. THE CORRIDOR WILL NOT BE CLOSED OFF.
AutoCAD SHX Text %%uOCCUPIED SIDE OF BARRIER
AutoCAD SHX Text %%u"WORK" SIDE OF BARRIER
AutoCAD SHX Text
EXISTING CEILING
AutoCAD SHX Text
CONTINUOUS MUD AND TAPE EACH SIDE
AutoCAD SHX Text
COMPRESSIBLE INSULATION
AutoCAD SHX Text
CONTINUOUS MUD AND TAPE EACH SIDE
AutoCAD SHX Text
EXISTING FINISHED FLOOR
AutoCAD SHX Text
3 5/8" STEEL STUDS @ 16" OC WITH FULL BATT SOUND ATTENUATING INSULATION
AutoCAD SHX Text
(1) LAYER 5/8" GYP BD EACH SIDE. 1 HOUR RATED WALL TO COMPLY WITH UL # U465.
AutoCAD SHX Text
CAP DUCTS
AutoCAD SHX Text SEAL ALL JOINTS, PENETRATIONS AND ENTIRE PERIMETER OF BARRIER w/ CONTINUOUS MUD AND TAPE
AutoCAD SHX Text
6 MIL POLY WITH TAPED SEAMS
6 MIL POLY WITH TAPED SEAMS
GC104
INFECTION CONTROL
PLANS
BAM
3/32" = 1'-0"
ATTIC PLAN
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
PROJECT LEADER:
B
A
C
D
E
F
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Tomah, Wisconsin
676-16-102
Office of
Facilities
Management
RECORD DRAWINGS
January 13, 2023
CONSULTANTS:
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
Replace HVAC & AC B404
309 N. Water St Suite 650 Milwaukee, Wisconsin 53202
BASEMENT KEY PLAN
3/32" = 1'-0"
BASEMENT PLAN
3/32" = 1'-0"
THIRD FLOOR PLAN
ATTIC KEY PLAN
THIRD FLOOR KEY PLAN
AutoCAD SHX Text
AutoCAD SHX Text 1A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 17A
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text F
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text F
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ATTIC
AutoCAD SHX Text
AREA
AutoCAD SHX Text
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
FLOOR HATCH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text
SUMP
AutoCAD SHX Text
BASEMENT
AutoCAD SHX Text
AutoCAD SHX Text
CLASS IV INFECTION CONTROL
AutoCAD SHX Text
INFECTION CONTROL - LEGEND
AutoCAD SHX Text
INFECTION CONTROL BARRIER PER CLASS
AutoCAD SHX Text
REQUIREMENTS; SEE INFECTION CONTROL
AutoCAD SHX Text
DESIGN NOTES ON SHEET GC103.
AutoCAD SHX Text
AutoCAD SHX Text 1A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 17A
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text F
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text H
AutoCAD SHX Text F
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 3460A
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 3460B
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICES
AutoCAD SHX Text
AutoCAD SHX Text
CONFERENCE
AutoCAD SHX Text
AutoCAD SHX Text
KITCHEN
AutoCAD SHX Text
AutoCAD SHX Text
MENS
AutoCAD SHX Text
RESTROOM/
AutoCAD SHX Text
SHOWER
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 3453A
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 4C37
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 4C31
AutoCAD SHX Text
CLASS IV IC
AutoCAD SHX Text
CLASS IV IC
AutoCAD SHX Text
CLASS IV IC
AutoCAD SHX Text
CLASS IV IC
AutoCAD SHX Text
CLASS IV IC
AutoCAD SHX Text
CLASS IV IC
AutoCAD SHX Text
CLASS IV IC
AutoCAD SHX Text
CLASS IV IC
AutoCAD SHX Text
CLASS IV IC
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
SILT FENCE INLET SEDIMENT BARRIER
SCALE: NOT TO SCALE
C001
JMD
SITE DETAILS
HFB
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
PROJECT LEADER:
B
A
C
D
E
F
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Tomah, Wisconsin
676-16-102
Office of
Facilities
Management
RECORD DRAWINGS
January 13, 2023
CONSULTANTS:
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
Replace HVAC & AC B404
309 N. Water St Suite 650 Milwaukee, Wisconsin 53202
AutoCAD SHX Text
PIPE SPACING, 10FT ON CENTER
AutoCAD SHX Text
2-1/4", 11-1/2 GAUGE CHAIN LINK FENCE
AutoCAD SHX Text
WIRE TO SECURE CHAIN TO FENCE POST, SPACE EVERY 15" TYP
AutoCAD SHX Text
84" LONG, 1-5/8" DIA STEEL PIPE DRIVEN 24" BELOW GRADE
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
72" LONG, 1-5/8" DIA STEEL PIPE SET ON STEEL SURFACE STAND, OR COMPARABLE
AutoCAD SHX Text
WIRE TO SECURE CHAIN TO FENCE POST
AutoCAD SHX Text SURFACE STAND, TO BE IMPLEMENTED ON IMPERVIOUS SURFACES TO REMAIN. GENERIC DESIGN, CONTRACTOR TO COORDINATE WITH ENGINEER/COTR
AutoCAD SHX Text NOTES: 1. CHAIN LINK CONSTRUCTION FENCING IS TO BE INSTALLED PRIOR TO COMMENCING CONSTRUCTION ACTIVITIES. 2. CHAIN LINK CONSTRUCTION FENCE SHALL BE A MINIMUM OF 84" ABOVE GRADE. 3. CHAIN LINK CONSTRUCTION FENCE SHALL HAVE THE FOLLOWING PROPERTIES: FENCE SHALL BE INSPECTED DAILY AFTER CONSTRUCTION ACTIVITIES HAVE BEEN COMPLETED FOR THE DAY. IF DAMAGED, FENCING SHALL BE REPAIRED IMMEDIATELY. WHERE CHAIN LINK CONSTRUCTION FENCE IS SHOWN ON IMPERVIOUS SURFACES, SUCH AS THE EXISTING BRICK PAVERS IN THE COURTYARD AREA, POST ARE TO BE ANCHORED ON SURFACE STANDS. STEEL PIPE IS NOT TO BE DRIVEN BELOW GRADE ON IMPERVIOUS SURFACES TO REMAIN.
AutoCAD SHX Text
%%UELEVATION
AutoCAD SHX Text
18" HIGH BUT LESS THAN 36" HIGH.
AutoCAD SHX Text
FILTER FABRIC SHALL BE @ LEAST
AutoCAD SHX Text
GUAGE WELDED WIRE FENCE OR
AutoCAD SHX Text
FILTER FABRIC SUPPORTED BY HEAVY
AutoCAD SHX Text
2 OR 3 LAYERS OF 8" CONCRETE BLOCKS
AutoCAD SHX Text %%uNOTE:
AutoCAD SHX Text
FABRIC, TYPICAL
AutoCAD SHX Text
GRAVEL
AutoCAD SHX Text
OF 8" CONCRETE
AutoCAD SHX Text
OR 2 OR 3 LAYERS
AutoCAD SHX Text
WELDED WIRE FENCE
AutoCAD SHX Text
HEAVY GUAGE
AutoCAD SHX Text
SUPPORTED BY
AutoCAD SHX Text
FILTER FABRIC
AutoCAD SHX Text
WRAP IN FILTER
AutoCAD SHX Text
STORM SEWER INLET
AutoCAD SHX Text
GRAVEL
AutoCAD SHX Text
BLOCKS
AutoCAD SHX Text
AutoCAD SHX Text
STORM INLET PROTECTION DETAIL
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
FLOW
AutoCAD SHX Text
EXCESS FABRIC
AutoCAD SHX Text
GEOTEXTILE FABRIC
AutoCAD SHX Text
SILT FENCE
AutoCAD SHX Text
ANCHOR STAKE MIN. 18" LONG
AutoCAD SHX Text
TIEBACK BETWEEN FENCE POST AND ANCHOR
AutoCAD SHX Text
GEOTEXTILE FABRIC ONLY
AutoCAD SHX Text WOOD POST SHALL BE A MINIMUM SIZE OF 1 1/8" x 1 1/8" OF OAK OR HICKORY
AutoCAD SHX Text FABRIC. FOLD MATERIAL TO FIT TRENCH AND BACKFILL AND COMPACT TRENCH WITH EXCAVATED
AutoCAD SHX Text TRENCH SHALL BE A MINIMUM OF 4" WIDE AND 6" DEEP TO BURY AND ANCHOR THE GEOTEXTILE
AutoCAD SHX Text HORIZONTAL BRACE WITH 2" x 4" WOODEN FRAME OR EQUIVALENT AT TOP OF POSTS AS DIRECTED
AutoCAD SHX Text
REQUIREMENTS OF THE STANDARD SPECIFICATIONS AND APPLICABLE SPECIAL PROVISIONS.
AutoCAD SHX Text
DETAILS OF CONSTRUCTION NOT SHOWN ON THIS DRAWING SHALL CONFORM TO THE PERTINENT
AutoCAD SHX Text
%%USILT FENCE @ UNPAVED SURFACE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
BY THE ENGINEER.
AutoCAD SHX Text
SOIL.
AutoCAD SHX Text
ADDITIONAL POST DEPTH OR THE BACKS MAY BE REQUIRED IN UNSTABLE SOILS
AutoCAD SHX Text
BACKFILL AND COMPACT TRENCH WITH EXCAVATED SOIL
AutoCAD SHX Text %%uNOTE:
AutoCAD SHX Text
(NON-REINFORCED)
AutoCAD SHX Text %%uGENERAL NOTES:
AutoCAD SHX Text
LATH AND NAILS
AutoCAD SHX Text
STAPLES OR WOODEN
AutoCAD SHX Text
THE POSTS WITH WIRE
AutoCAD SHX Text
ATTACH THE FABRIC TO
AutoCAD SHX Text
AutoCAD SHX Text
WOOD POSTS LENGTH 4'-0" MIN. 2'-0" MIN. DEPTH IN GROUND
AutoCAD SHX Text
AutoCAD SHX Text
GEOTEXTILE FABRIC
AutoCAD SHX Text
SUPPORT CORD
AutoCAD SHX Text
8'-0" POST SPACING ALLOWED IF A WOVEN GEOTEXTILE FABRIC IS USED.
AutoCAD SHX Text
FLOW
AutoCAD SHX Text %%uNOTE:
AutoCAD SHX Text
3" MAX.
AutoCAD SHX Text
FOLD
AutoCAD SHX Text
%%USILT FENCE TIE BACK
AutoCAD SHX Text
(WHEN REQUIRED BY THE ENGINEER)
AutoCAD SHX Text
FLOW
AutoCAD SHX Text
%%UTRENCH DETAIL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TEMPORARY SILT FENCE, SPECIAL (TOE-IN METHOD)
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
INSTALLATION NOTES
AutoCAD SHX Text
GEOTEXTILE FABRIC, MONOFILAMENT IN BOTH DIRECTIONS
AutoCAD SHX Text WOOD 2" x 4" EXTENDS 8" BEYOND GRATE WIDTH ON BOTH SIDES, LENGTH VARIES. SECURE TO GRATE WITH WIRE OR PLASTIC TIES
AutoCAD SHX Text TRIM EXCESS FABRIC IN THE FLOW LINE TO WITHIN 3" OF THE GRATE. THE CONTRACTOR SHALL DEMONSTRATE A METHOD OF MAINTENANCE, USING A SEWN FLAP, HAND HOLDS OR OTHER METHOD TO PREVENT ACCUMULATED SEDIMENT FROM ENTERING THE INLET.
AutoCAD SHX Text WHEN REMOVING OR MAINTAINING INLET PROTECTION, CARE SHALL BE TAKEN SO THAT THE SEDIMENT TRAPPED ON THE GEOTEXTILE FABRIC DOES NOT FALL INTO THE INLET. ANY MATERIAL FALLING INTO THE INLET SHALL BE REMOVED IMMEDIATELY.
AutoCAD SHX Text FINISHED SIZE, INCLUDING FLAP POCKETS WHERE REQUIRED, SHALL EXTEND A MINIMUM OF 10" AROUND THE PERIMETER TO FACILITATE MAINTENANCE OR REMOVAL.
AutoCAD SHX Text FOR INLET PROTECTION, CURB TYPE, AN ADDITIONAL 18" OF FABRIC IS WRAPPED AROUND THE WOOD AND SECURED WITH STAPLES. THE WOOD SHALL NOT BLOCK THE ENTIRE HEIGHT OF THE CURB BOX OPENING.
AutoCAD SHX Text
AutoCAD SHX Text
TEMPORARY CHAIN LINK FENCE DETAIL
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
C101
JMD
SITE STAGING AND
EQUIPMENT LAYOUT
PLAN
HFB
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
PROJECT LEADER:
B
A
C
D
E
F
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Tomah, Wisconsin
676-16-102
Office of
Facilities
Management
RECORD DRAWINGS
January 13, 2023
CONSULTANTS:
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
Replace HVAC & AC B404
309 N. Water St Suite 650 Milwaukee, Wisconsin 53202
1/16" = 1'-0"
SITE PLAN
1/16" = 1'-0"
PARTIAL SITE PLAN
NORTH
NORTH
AutoCAD SHX Text
BUILDING 404
AutoCAD SHX Text
EXISTING GRASS AREA
AutoCAD SHX Text
EXISTING PARKING AREA
AutoCAD SHX Text
EXISTING COVERED TRAMWAY
AutoCAD SHX Text
EXISTING COVERED TRAMWAY
AutoCAD SHX Text
EXISTING GARDEN AREA DO NOT DISTURB
AutoCAD SHX Text
CONTRACTOR STAGING AREA
AutoCAD SHX Text
CRANE LIFT AREA 1 FOR ACCESS TO EAST HALF OF ATTIC DEMOLITION AND NEW WORK
AutoCAD SHX Text
CRANE LIFT AREA 2 FOR ACCESS TO WEST HALF OF ATTIC DEMOLITION AND NEW WORK.
AutoCAD SHX Text CRANE LIFT AREA 3 FOR ACCESS TO SOUTH/MIDDLE PORTION OF ATTIC DEMOLITION AND NEW WORK.
AutoCAD SHX Text
EXISTING GRASS AREA
AutoCAD SHX Text
EXISTING AIR COOLED CHILLER
AutoCAD SHX Text
EXISTING PARKING AREA
AutoCAD SHX Text FRONT OF BUILDING 404 - MAIN ENTRANCE, NO EQUIPMENT OR CONSTRUCTION ALONG THE ENTIRE FRONT ELEVATION.
AutoCAD SHX Text TRAMWAY ACCESS - DO NOT BLOCK, NO EQUIPMENT OR CONSTRUCTION WITHIN 8 FEET OF ENTRANCE, ACCESS MUST BE MAINTAINED THROUGHOUT PROJECT.
AutoCAD SHX Text
EXISTING AIR COOLED CHILLER(S)
AutoCAD SHX Text
TRAMWAY ACCESS TO BUILDING 404
AutoCAD SHX Text
EXISTING GRASS AREA
AutoCAD SHX Text
DUMPSTER LOCATION
AutoCAD SHX Text
DUMPSTER LOCATION
AutoCAD SHX Text
DUMPSTER LOCATION
AutoCAD SHX Text
CONSTRUCTION WASTE CHUTE
AutoCAD SHX Text
CONSTRUCTION WASTE CHUTE
AutoCAD SHX Text
CONSTRUCTION WASTE CHUTE
AutoCAD SHX Text
CONTRACTOR TRAILER PARKING LOCATION
AutoCAD SHX Text
TRASH REMOVAL PATH, KEEP CLEAR
AutoCAD SHX Text
EMERGENCY EXIT PATHWAY FOR OCCUPANTS
AutoCAD SHX Text
BUILDING 405
AutoCAD SHX Text
4TH STREET
AutoCAD SHX Text
TEMPORARY CONSTRUCTION FENCE REQUIRED TYP
AutoCAD SHX Text
CONTRACTOR STAGING AREA
AutoCAD SHX Text
CONTRACTOR STAGING AREA
AutoCAD SHX Text
EXISTING CONNECTOR WALKWAY
AutoCAD SHX Text
COVERED LOADING DOCK AREA, KEEP CLEAR
AutoCAD SHX Text
12' CONSTRUCTION GATE, TYP
AutoCAD SHX Text PROVIDE TEMPORARY RECYCLED RUBBER CURB RAMP DURING CONSTRUCTION, SIMILAR TO OR EQUAL TO GUARDIAN RUBBER CURB RAMP MODEL KR01, SECURE TO EXISTING ROADWAY WHILE IN USE
AutoCAD SHX Text
PROVIDE SILT FENCE AROUND GRASS AREAS, TYP
AutoCAD SHX Text
PROVIDE SILT FENCE AROUND GRASS AREAS, TYP
AutoCAD SHX Text
PROVIDE SILT FENCE AROUND GRASS AREAS, TYP
AutoCAD SHX Text CONSTRUCTION WASHOUT AREA, 50' x 18'
AutoCAD SHX Text
CONSTRUCTION MAT REQUIRED AS SHOWN, MINIMUM
AutoCAD SHX Text
CONSTRUCTION MAT REQUIRED AS SHOWN, MINIMUM
AutoCAD SHX Text CONSTRUCTION MAT REQUIRED AS SHOWN, MINIMUM (ENTIRE CONSTRUCTION AREA EXCEPT DIRECTLY UNDER THE EXISTING TREE)
AutoCAD SHX Text NOTE: TREE REMOVAL FOR CRANE LIFT AREA AT CONTRACTORS EXPENSE. VA COR APPROVAL REQUIRED BEFORE REMOVAL.
AutoCAD SHX Text NOTE: TREE REMOVAL FOR CRANE LIFT AREA AT CONTRACTORS EXPENSE. VA COR APPROVAL REQUIRED BEFORE REMOVAL.
AutoCAD SHX Text
EXISTING PARKING AREA
AutoCAD SHX Text CONTRACTOR AND SUB-CONTRACTOR PARKING ALONG NORTH ROW IN EXISTING PARKING LOT ACROSS FROM BUILDING 405
AutoCAD SHX Text
EXISTING PARKING AREA
AutoCAD SHX Text
1. ALL DISTURBED GRASS SHALL BE RE-SODDED AT END OF THE PHASE. ALL DISTURBED GRASS SHALL BE RE-SODDED AT END OF THE PHASE. CONTRACTOR SHALL PROVIDE 3" BROWN SIFTED TOPSOIL. GRADE TO MATCH EXISTING. SLOPE NEW GRADE AWAY FROM BUILDING 404. CONTRACTOR SHALL PROVIDE WATERING OF NEW SOD FOR 4 TIMES PER WEEK FOR 8 WEEKS. 2. CONSTRUCTION STAGING AREA SHALL BE COMPLETELY FENCED IN AND CONSTRUCTION STAGING AREA SHALL BE COMPLETELY FENCED IN AND LOCKED DURING OFF HOURS. ADDITIONAL SPACE IF REQUIRED SHALL BE COORDINATED WITH THE VA CONSTRUCTION MANAGER. 3.