Attachment 7 - Final Drawing Set - 6 of 8.pdf

PDF 7 MB Posted

Attached to
Project 573A4-21-700 EHRM Infrastructure Upgrades construction project at the Lake City, FL VAMC
Solicitation number
36C77625B0006
Issued by

About this file

The files are telecommunications infrastructure design drawings for the Lake City VA Medical Center's EHRM Infrastructure Upgrades construction project. The documents detail comprehensive telecommunications upgrades across multiple building floors (second through fourth), involving the replacement and installation of new network infrastructure including fiber optic backbone cabling, Category 6A horizontal cabling, network outlets, WiFi access points, and security cameras.

The project is a Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside with a construction value between $20-50 million, solicited under contract number 36C77625B0006 by the Department of Veterans Affairs Technology Acquisition Center Austin. The technical specifications mandate systematic removal of existing network equipment, reinstallation of analog telephone ports, routing of new cabling using J-hook systems, maintaining fire barrier ratings, and connecting various data outlets, WiFi devices, and security cameras to new patch panels in designated telecommunication rooms across different building zones, with careful coordination to minimize network downtime.

View the file

Other files

File Type Posted
Online Bid Opening Meeting Info.docx DOCX document
Amendment 5 - 36C77625B0006 0005 6-30-25.pdf PDF
Construction Wage Rates - Columbia 6-27-2025.pdf PDF
Brand Name Justification - Lake City - Rev 2 0 - Redacted.pdf PDF
Amendment 4 - 36C77625B0006 0004 6-25-25.pdf PDF
Brand Name Justification - Lake City EHRM - SIGNED_Redacted.pdf PDF
Amendment 3 - 36C77625B0006 0003 6-11-25.pdf PDF
573A4-21-700 Lake City - RFI TRACKING SHEET REV2 36C77625B0006 6-10-25.xlsx XLSX spreadsheet
573A4-21-700 Lake City - Addendum No. 1.pdf PDF
260526-EDITED Grnd shop marked up.docx DOCX document
260533-EDITED Raceway shop marked up.docx DOCX document
260519-EDITED Low Volt cond cab shop marked updocx.docx DOCX document
262726-EDITED Wire Dev shop marked up.docx DOCX document
Construction Wage Rates - Columbia 5-2-2025.pdf PDF
262416-EDITED Panelboards shop marked up.docx DOCX document
Amendment 2 - 36C77625B0006 0002 5-27-2025.pdf PDF
Site Visit Sign-in - 573A4-21-700 Attendance 250423.pdf PDF
Amendment 1 - 36C77625B0006 0001 4-24-25.pdf PDF
Attachment 15 - Construction Wage Rates - Columbia.pdf PDF
Attachment 8 - Final Drawing Set - 7a of 8.pdf PDF
Attachment 4 - Final Drawing Set - 3 of 8.pdf PDF
Attachment 14 - PreConstruction Risk Assessment - Lake City.docx DOCX document
Attachment 5 - Final Drawing Set - 4 of 8.pdf PDF
Attachment 9 - Final Drawing Set - 7b of 8.pdf PDF
Attachment 10 - Final Drawing Set - 7c of 8.pdf PDF
Attachment 6 - Final Drawing Set - 5 of 8.pdf PDF
Attachment 12 - Final Drawing Set - 8 of 8.pdf PDF
Attachment 1 - Final Specs Set - R4.pdf PDF
Attachment 13 - Asbestos and Lead Paint Survey Report.pdf PDF
Attachment 11 - Final Drawing Set - 7d of 8.pdf PDF
Attachment 17 - Site Visit Instructions.pdf PDF
Attachment 3 - Final Drawing Set - 2 of 8.pdf PDF
Attachment 16 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 2 - Final Drawing Set - 1 of 8.pdf PDF
IFB 36C77625B0006.pdf PDF
Attachment 18 - RFI TRACKING SHEET - SOLICITATION 36C77625B0006 - Project 573A4-21-700.xlsx XLSX spreadsheet
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TELECOM RM

B207

TELECOM RM

TELECOM RM

TELECOM RM

227A

TELECOM RM

TELECOM RM

B217A

TELECOM RM

TELECOM RM

C225

TELECOM RM

57a

S1

Q1RST

TR 317

TR 216

TR 201

TR B207

TR 227A

2 43 51 6

2 4

B62[12]

B64-A[3] B64-B[2]

B82[9]

B82[8]

B64-2[1]B64-A[4]

B38[5]

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:5

:4

A

M

TN1.2

SECOND FLOOR - ZONES - NEW LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

STATION CHIEF - EDWIN BURNETT

10/25/2024 BMS CVM

100% CONSTRUCTION

DOCUMENTS

CHRISTOPHER VAN METER

RCDD Reg. No. 285002

NN

0 15' 30' 60' 90'

1" = 30'

1" = 30'-0"

SECOND FLOOR - ZONES - NEW

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523

CODED NOTES:

DRAWING NOTES:

1. LOCATIONS WHERE CORE-A AND CORE-B FIBER OPTIC CABLES ARE ROUTED IN THE SAME

CORRIDOR, CORE-A CABLES MUST BE ROUTED ON OPPOSITE SIDE OF CORRIDOR FROM CORE-B.

2. INDOOR FIBER OPTIC CABLE ROUTED ABOVE CEILING, UNLESS OTHERWISE NOTED. ROUTING INDICATED ON THIS PLAN IS DIAGRAMATIC. CONTRACTOR TO COORDINATE EXACT ROUTING OF FIBER

OPTIC CABLES WITH EXISTING CONDITIONS.

3. COORDINATE EXACT LOCATION OF PENETRATION TO FLOOR ABOVE/BELOW WITH EXISTING

CONDITIONS AND FLOOR SPACE ABOVE/BELOW.

4. ARMORED FIBER OPTIC CABLES TO BE ROUTED IN EMT UNLESS ROUTED CONCEALED ABOVE

CEILINGS.

CORE-A FIBER OPTIC CABLES ROUTED UP FROM FLOOR BELOW. REFER TO FIBER BACKBONE RISER

DIAGRAM ON SHEET T-601 FOR ADDITIONAL INFORMATION.

CORE-B FIBER OPTIC CABLES ROUTED UP FROM FLOOR BELOW. REFER TO FIBER BACKBONE RISER

DIAGRAM ON SHEET T-601 FOR ADDITIONAL INFORMATION.

CORE-A FIBER OPTIC CABLES ROUTED UP TO FLOOR ABOVE. REFER TO FIBER BACKBONE RISER

DIAGRAM ON SHEET T-601 FOR ADDITIONAL INFORMATION.

CORE-B FIBER OPTIC CABLES ROUTED UP TO FLOOR ABOVE. REFER TO FIBER BACKBONE RISER

DIAGRAM ON SHEET T-601 FOR ADDITIONAL INFORMATION.

TERMINATE CORE-A FIBER OPTIC CABLES IN TR. REFER TO FIBER BACKBONE RISER DIAGRAM ON SHEET

T-601 FOR ADDITIONAL INFORMATION.

TERMINATE CORE-B FIBER OPTIC CABLES IN TR. REFER TO FIBER BACKBONE RISER DIAGRAM ON SHEET

T-601 FOR ADDITIONAL INFORMATION.

HORIZONTAL CAT6A CABLING NOT IN SCOPE FOR THIS AREA, TO BE COMPLETED AS A PART OF

SEPARATE PROJECT, NUMBER 573-A4-18-603.

Revisions Date

10/25/202412/31/2024

E X

OFFICE -

NURSE

MANAGER

C228

OFFICE -

SUPERVISOR

AMBULATORY

CARE

C231

MEDICATION

ROOM

C233

OFFICE -

NURSE

C238

SOIL HOLD

C240

OFFICE -

NURSE

C242

COPY ROOM

C244

OFFICE -

NURSE

C246

OFFICE -

PACT, ER,

SOCIAL WORK

C248

TOILET

C249

TRIAGE

OFFICE

C250

VESTIBULE

C-251

PROCEDURE

ROOM

C251

OFFICE

C252

CLERKS

C253

OFFICE -

SOCIAL

WORKER

C201

OFFICE -

CONSULTATION

C202

OFFICE -

NURSE

C204

TOILET

C205

EXAM ROOM

#2

C208

EXAM ROOM

#1

C209

OFFICE -

HEALTH

COACH

C211

EXAM ROOM

#7

C213

EXAM ROOM

#6

C214

MEDICATION

ROOM

C216

CONFERENCE

ROOM

C221

BREAKROOM

C222

ELEC

C224

EQUIPMENT

C225

ELEC

C226

ELEC

C227

OFFICE -

BEHAVIORAL

HEALTH

C229

TOILET

C230

OFFICE -

NURSE

C232

OFFICE -

NURSE

C239

EXAM ROOM

C241

EXAM ROOM

C243

EXAM ROOM

#3

C245

EXAM ROOM

C247

CLOSET

C218

TOILET STAFF

C219

PHARMACY

CONSULT

C217

STORAGE

C220

H.A.C.

C223

OFFICE -

NURSE

C215

EXAM ROOM

#5

C206

EXAM ROOM

#4

C207

OFFICE -

NURSE

C210

OFFICE -

NURSE

C212

WAITING

C200A

CORRIDOR

C2-4

CORRIDOR

C2-3

CORRIDOR

C2-1

ALCOVE

C201D

PHARMACIST

C234

ELEVATOR

LOBBY

C-200

VESTIBULE

C235

TOILET MALE

C237

TOILET

FEMALE

C236

CORRIDOR

C2-7

CORRIDOR

C2-2

CORRIDOR

C2-5

CORRIDOR

C2-8

OFFICE -

NURSE

C203

OFFICE -

HEALTH

COACH

C228A

WORKSTATIONS

C200B

STAIR #7

S7.2

ELEVATOR

PASSENGER

P-7.2/64

ELEVATOR

PASSENGER

P-6.2/64

CORRIDOR

C2-2

OFFICE

XXX

TD403

2D 1V

2D 1V

2D 1V

2D 1V

2D 1V

2D 1V

2D 1V

2D 2D

2D

2D

2D 2D 1V

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D 2D 2D

2D

2D

2D

2D 2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D 2D

2D

1/ TN1.2.2

1/ TN1.2.4

1/ TN1.2.4

1/ TN1.2.2

TYPICAL FOR ALL

NETWORK OUTLETS

2D

2D

2D

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:5

:5

A

M

TN1.2.1

BLDG 64 - LV 2 - ZONE 1 - NEW LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

64-2

STATION CHIEF - EDWIN BURNETT

10/25/2024 BMS CVM

100% CONSTRUCTION

DOCUMENTS

CHRISTOPHER VAN METER

RCDD Reg. No. 285002

NN

0 4' 8' 16' 24'

1/8" = 1'-0"

1/8" = 1'-0"

SECOND FLOOR - B64-2(1) - NEW

CODED NOTES:

DRAWING NOTES:

1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE NEW IN SAME LOCATION. NUMBER OF PORTS INDICATED IS FOR NEW WORK. CONTRACTOR TO VERIFY EXACT LOCATION AND QUANTITIES OF DATA OUTLETS

PRIOR TO CONSTRUCTION. EXISTING DATA OUTLET LOCATIONS INDICATED ON THIS DRAWING

OBTAINED BY LIMITED SITE INVESTIGATION. CONTRACTOR TO DOCUMENT VARIANCES ON AS-BUILT

DRAWINGS.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING CONDITIONS FROM DAMAGE

DURING CONSTRUCTION. ANY MATERIALS, SYSTEMS, COMPONENTS, FINISHES, ETC. THAT ARE

DAMAGED DURING CONSTRUCTION MUST BE REPAIRED OR REPLACED AT CONTRACTORS EXPENSE

TO THE APPROVAL OF THE VA.

3. TELECOMMUNICATIONS OUTLET UPGRADE INCLUDES, BUT IS NOT LIMITED TO, REMOVAL OF EXISTING DEVICES AND ASSOCIATED NETWORK CABLING BACK TO PATCH PANEL, PROVIDING ALL MATERIALS, TOOLS, LABOR, TESTING INSTRUMENTS, ETC. REQUIRED FOR THE COMPLETE UPGRADE TO A FULLY FUNCTIONAL CATEGORY 6A, 8P8C PORT WITH THE PORT QUANTITY INDICATED FOR EACH OUTLET

LOCATION.

4. EXISTING POTS (ANALOG TELEPHONE) RJ11 PORTS AND ASSOCIATED CABLING IS NOT IN SCOPE.

EXISTING POTS PORTS LOCATED IN TELE/DATA OUTLETS RECEIVING TELECOMMUNICATIONS

UPGRADE SHALL BE REMOVED FROM OUTLET AND MAINTAINED FOR REINSTALLATION INTO NEW

OUTLET, UNLESS OTHERWISE NOTED.

5. PROVIDE ALL CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING OF FIBER OPTIC BACKBONE CABLING AND CAT6A HORIZONTAL CABLING. REFER TO CONDUIT FILL CHARTS ON SHEET T-001 FOR

ADDITIONAL INFORMATION.

6. INTERIOR FIRE WALL PENETRATIONS - CONTRACTOR SHALL PROVIDE APPROVED UL LISTED 4" SLEEVES AND FIRE RATED ASSEMBLY OR SYSTEM TO MAINTAIN FIRE RATING OF EXISTING FIRE

BARRIER. REFER TO CONDUIT FILL CHARTS FOR NUMBER OF SLEEVES REQUIRED.

7. NEW CAT6A CABLING SHALL BE ROUTED ABOVE ACCESSIBLE CEILINGS USING NEW AND EXISTING J- HOOK SYSTEMS. CONTRACTOR TO PROVIDE NEW 2" J-HOOKS AS REQUIRED FOR INSTALLATION OF NEW CAT6A CABLING. J-HOOK BASIS OF DESIGN IS NVENT CADDY CAT HP J-HOOK TREE. MAX CABLE FILL IS (35) CAT6A CABLES PER 2" J-HOOK (CABLE BASIS OF DESIGN - 0.35" NOMINAL OUTTER CABLE DIAMETER). CONTRACTOR SHALL PROVIDE CONDUIT FOR ROUTING OF NEW CAT6A CABLING ABOVE

HARD CEILINGS. REFER TO CABLE FILL CHARTS ON SHEET T-001 FOR CONDUIT FILL.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100FT INTERVALS FOR STRAIGHT CONDUIT RUNS, OR AT MAXIMUM CUMULATIVE OF 180 DEGREES OF CONDUIT BENDS.

9. DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING BUT NOT

LIMITED TO NURSE CALL, FIRE ALARM, SECURITY AND SSTV. DATA CABLING SHALL HAVE ITS OWN

RACEWAY WHEN ROUTED THROUGH CONDUIT.

10. SSTV CAMERAS, WAP DEVICES AND DATA OUTLETS ON THIS SHEET SHALL BE CONNECTED BACK TO

NEW PATCH PANELS IN TR B207.

DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH

PANEL. EXISTING BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION.

CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE.

PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE

DOWNTIME.

DISCONNECT EXISTING CEILING MOUNTED VA AND GUEST WIFI WAP DEVICES. MEDICAL WIFI NETWORK, ASSOCIATED DEVICES AND CABLING ARE NOT IN SCOPE. ALL MEDICAL WIFI NETWORK DEVICES, CABLING AND EQUIPMENT ARE COVERED UNDER THE NATIONAL WIFI CONTRACT. EXISTING MEDICAL WIFI WAP DEVICE TO REMAIN AS INSTALLED. REMOVE EXISTING VA AND GUEST WIFI CABLING BACK TO SOURCE.

PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE DOWNTIME. PROVIDE

ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 10 WAP DEVICES FOR AREA SHOWN ON THIS

DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND LOCATIONS OF WAP DEVICES PRIOR TO

COMMENCEMENT OF WORK.

DISCONNECT EXISTING SSTV CAMERAS. EXISTING CAMERA TO REMAIN AS INSTALLED. REMOVE EXISTING

CABLING BACK TO SOURCE. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL.

CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW

CABLING TO MINIMIZE DOWNTIME. PROVIDE ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 14 CAMERAS FOR AREA SHOWN ON THIS DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND

LOCATIONS OF CAMERAS PRIOR TO COMMENCEMENT OF WORK.

DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH

PANEL. EXISTING FLOOR BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION. CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE. PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE

DOWNTIME.

PROVIDE PATCH CABLES FROM EXISTING NOT IN CONTRACT EQUIPMENT TO NEW HORIZONTAL

DISTRIBUTION EQUIPMENT LOCATED IN ROOM B207. REFER TO 6/TD403 FOR ADDITIONAL INFORMATION.

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523

Revisions Date

EX

B207

CORRIDOR

C2-8

TOILET

B211A

RECEPTION

B211B

EQUIPMENT

STORAGE

B212B

WAITING

B211

OFFICE #1

B213

OFFICE #2

B214

OFFICE #4

B215

TREATMENT

#3

B212C

COPY ROOM

B212A

TREATMENT /

EMG

B212D

TREATMENT

B216

TREATMENT

B215A

BATH

B212E

TREATMENT

B216AHAND

THERAPY

B217D

EXERCISE

AREA

B217

BREAKROOM

B217C

STORAGE

B217B

F.E.C.

B218

CORRIDOR

B212

STORAGE

ALCOVE

B213A

OFFICE -

CARDIOPULMONARY

EEG

SUPERVISOR

A281

RECEPTION

AREA -

CARDIOPULMONARY

A282

TOILET

B200

H.A.C.

B202

LOCKERS

A285

EKG

A285A

EKG #2

B201

ECHO ROOM

B203

OFFICE -

HOME

OXYGEN

B205

PULMONARY

LAB

B206

STORAGE

B206A

ELEC

B208

F.E.C.

B209

OFFICE

B219C

TOILET

B219B

POLICE

TRAINING

B219

STORAGE

B219A

STAIR #4

S4.2

STAIR #5

S5.2

CORRIDOR

C2-9

MECHANICAL

SPACE

B205

EQUIPMENT

B217A

T-406

TD403

2D2D2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D 2D 2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D 1V

2D

2D 1V

2D 2D

2D

2D

2D

2D 1V

2D

2D

2D

2D

2D

2D2D

2D

2D 2D 2D

2D

2D

2D

2D

2D 2D

2D

2D 2D

2D

2D

2D 2D

1/ TN1.2.1

1/ TN1.2.1

1/ TN1.2.9

1/ TN1.2.4

1/ TN1.2.3

1/ TN1.2.3

1/ TN1.2.9

TYPICAL FOR ALL

NETWORK OUTLETS

2D

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:5

:0

A

M

TN1.2.2

BLDG 64 - LV 2 - ZONE 2 - NEW LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

64-B

STATION CHIEF - EDWIN BURNETT

10/25/2024 BMS CVM

100% CONSTRUCTION

DOCUMENTS

CHRISTOPHER VAN METER

RCDD Reg. No. 285002

NN

0 4' 8' 16' 24'

1/8" = 1'-0" 1/8" = 1'-0"1

SECOND FLOOR - B64-B(2) - NEW

CODED NOTES:

DRAWING NOTES:

1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE NEW IN SAME LOCATION. NUMBER OF PORTS INDICATED IS FOR NEW WORK. CONTRACTOR TO VERIFY EXACT LOCATION AND QUANTITIES OF DATA OUTLETS

PRIOR TO CONSTRUCTION. EXISTING DATA OUTLET LOCATIONS INDICATED ON THIS DRAWING

OBTAINED BY LIMITED SITE INVESTIGATION. CONTRACTOR TO DOCUMENT VARIANCES ON AS-BUILT

DRAWINGS.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING CONDITIONS FROM DAMAGE

DURING CONSTRUCTION. ANY MATERIALS, SYSTEMS, COMPONENTS, FINISHES, ETC. THAT ARE

DAMAGED DURING CONSTRUCTION MUST BE REPAIRED OR REPLACED AT CONTRACTORS EXPENSE

TO THE APPROVAL OF THE VA.

3. TELECOMMUNICATIONS OUTLET UPGRADE INCLUDES, BUT IS NOT LIMITED TO, REMOVAL OF EXISTING DEVICES AND ASSOCIATED NETWORK CABLING BACK TO PATCH PANEL, PROVIDING ALL MATERIALS, TOOLS, LABOR, TESTING INSTRUMENTS, ETC. REQUIRED FOR THE COMPLETE UPGRADE TO A FULLY FUNCTIONAL CATEGORY 6A, 8P8C PORT WITH THE PORT QUANTITY INDICATED FOR EACH OUTLET

LOCATION.

4. EXISTING POTS (ANALOG TELEPHONE) RJ11 PORTS AND ASSOCIATED CABLING IS NOT IN SCOPE.

EXISTING POTS PORTS LOCATED IN TELE/DATA OUTLETS RECEIVING TELECOMMUNICATIONS

UPGRADE SHALL BE REMOVED FROM OUTLET AND MAINTAINED FOR REINSTALLATION INTO NEW

OUTLET, UNLESS OTHERWISE NOTED.

5. PROVIDE ALL CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING OF FIBER OPTIC BACKBONE CABLING AND CAT6A HORIZONTAL CABLING. REFER TO CONDUIT FILL CHARTS ON SHEET T-001 FOR

ADDITIONAL INFORMATION.

6. INTERIOR FIRE WALL PENETRATIONS - CONTRACTOR SHALL PROVIDE APPROVED UL LISTED 4" SLEEVES AND FIRE RATED ASSEMBLY OR SYSTEM TO MAINTAIN FIRE RATING OF EXISTING FIRE

BARRIER. REFER TO CONDUIT FILL CHARTS FOR NUMBER OF SLEEVES REQUIRED.

7. NEW CAT6A CABLING SHALL BE ROUTED ABOVE ACCESSIBLE CEILINGS USING NEW AND EXISTING J- HOOK SYSTEMS. CONTRACTOR TO PROVIDE NEW 2" J-HOOKS AS REQUIRED FOR INSTALLATION OF NEW CAT6A CABLING. J-HOOK BASIS OF DESIGN IS NVENT CADDY CAT HP J-HOOK TREE. MAX CABLE FILL IS (35) CAT6A CABLES PER 2" J-HOOK (CABLE BASIS OF DESIGN - 0.35" NOMINAL OUTTER CABLE DIAMETER). CONTRACTOR SHALL PROVIDE CONDUIT FOR ROUTING OF NEW CAT6A CABLING ABOVE

HARD CEILINGS. REFER TO CABLE FILL CHARTS ON SHEET T-001 FOR CONDUIT FILL.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100FT INTERVALS FOR STRAIGHT CONDUIT RUNS, OR AT MAXIMUM CUMULATIVE OF 180 DEGREES OF CONDUIT BENDS.

9. DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING BUT NOT

LIMITED TO NURSE CALL, FIRE ALARM, SECURITY AND SSTV. DATA CABLING SHALL HAVE ITS OWN

RACEWAY WHEN ROUTED THROUGH CONDUIT.

10. SSTV CAMERAS, WAP DEVICES AND DATA OUTLETS ON THIS SHEET SHALL BE CONNECTED BACK TO

NEW PATCH PANELS IN TR B207.

DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH

PANEL. EXISTING BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION.

CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE.

PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE

DOWNTIME.

DISCONNECT EXISTING CEILING MOUNTED VA AND GUEST WIFI WAP DEVICES. MEDICAL WIFI NETWORK, ASSOCIATED DEVICES AND CABLING ARE NOT IN SCOPE. ALL MEDICAL WIFI NETWORK DEVICES, CABLING AND EQUIPMENT ARE COVERED UNDER THE NATIONAL WIFI CONTRACT. EXISTING MEDICAL WIFI WAP DEVICE TO REMAIN AS INSTALLED. REMOVE EXISTING VA AND GUEST WIFI CABLING BACK TO SOURCE.

PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE DOWNTIME. PROVIDE

ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 10 WAP DEVICES FOR AREA SHOWN ON THIS

DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND LOCATIONS OF WAP DEVICES PRIOR TO

COMMENCEMENT OF WORK.

DISCONNECT EXISTING SSTV CAMERAS. EXISTING CAMERA TO REMAIN AS INSTALLED. REMOVE EXISTING

CABLING BACK TO SOURCE. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL.

CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW

CABLING TO MINIMIZE DOWNTIME. PROVIDE ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 8 CAMERAS FOR AREA SHOWN ON THIS DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND

LOCATIONS OF CAMERAS PRIOR TO COMMENCEMENT OF WORK.

PROVIDE PATCH CABLES FROM EXISTING NOT IN CONTRACT EQUIPMENT TO NEW HORIZONTAL

DISTRIBUTION EQUIPMENT LOCATED IN ROOM B207. REFER TO 7/TD403 FOR ADDITIONAL INFORMATION.

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523

Revisions Date

Q1RST

T-406

2D 2D

2D 2D

2D 2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D

2D 2D

2D

1/ TN1.2.4

1/ TN1.2.1

2D

2D

2D

2D 2D

2D

TD403

AREA NOT IN SCOPE

AREA NOT IN SCOPE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:5

:0

A

M

TN1.2.3

BLDG 64 - LV 2 - ZONE 3 - NEW LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

64-A

STATION CHIEF - EDWIN BURNETT

10/25/2024 BMS CVM

100% CONSTRUCTION

DOCUMENTS

CHRISTOPHER VAN METER

RCDD Reg. No. 285002

NN

0 4' 8' 16' 24'

1/8" = 1'-0" 1/8" = 1'-0"

SECOND FLOOR - B64-A(3) - NEW

CODED NOTES:

DRAWING NOTES:

1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE NEW IN SAME LOCATION. NUMBER OF PORTS INDICATED IS FOR NEW WORK. CONTRACTOR TO VERIFY EXACT LOCATION AND QUANTITIES OF DATA OUTLETS

PRIOR TO CONSTRUCTION. EXISTING DATA OUTLET LOCATIONS INDICATED ON THIS DRAWING

OBTAINED BY LIMITED SITE INVESTIGATION. CONTRACTOR TO DOCUMENT VARIANCES ON AS-BUILT

DRAWINGS.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING CONDITIONS FROM DAMAGE

DURING CONSTRUCTION. ANY MATERIALS, SYSTEMS, COMPONENTS, FINISHES, ETC. THAT ARE

DAMAGED DURING CONSTRUCTION MUST BE REPAIRED OR REPLACED AT CONTRACTORS EXPENSE

TO THE APPROVAL OF THE VA.

3. TELECOMMUNICATIONS OUTLET UPGRADE INCLUDES, BUT IS NOT LIMITED TO, REMOVAL OF EXISTING DEVICES AND ASSOCIATED NETWORK CABLING BACK TO PATCH PANEL, PROVIDING ALL MATERIALS, TOOLS, LABOR, TESTING INSTRUMENTS, ETC. REQUIRED FOR THE COMPLETE UPGRADE TO A FULLY FUNCTIONAL CATEGORY 6A, 8P8C PORT WITH THE PORT QUANTITY INDICATED FOR EACH OUTLET

LOCATION.

4. EXISTING POTS (ANALOG TELEPHONE) RJ11 PORTS AND ASSOCIATED CABLING IS NOT IN SCOPE.

EXISTING POTS PORTS LOCATED IN TELE/DATA OUTLETS RECEIVING TELECOMMUNICATIONS

UPGRADE SHALL BE REMOVED FROM OUTLET AND MAINTAINED FOR REINSTALLATION INTO NEW

OUTLET, UNLESS OTHERWISE NOTED.

5. PROVIDE ALL CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING OF FIBER OPTIC BACKBONE CABLING AND CAT6A HORIZONTAL CABLING. REFER TO CONDUIT FILL CHARTS ON SHEET T-001 FOR

ADDITIONAL INFORMATION.

6. INTERIOR FIRE WALL PENETRATIONS - CONTRACTOR SHALL PROVIDE APPROVED UL LISTED 4" SLEEVES AND FIRE RATED ASSEMBLY OR SYSTEM TO MAINTAIN FIRE RATING OF EXISTING FIRE

BARRIER. REFER TO CONDUIT FILL CHARTS FOR NUMBER OF SLEEVES REQUIRED.

7. NEW CAT6A CABLING SHALL BE ROUTED ABOVE ACCESSIBLE CEILINGS USING NEW AND EXISTING J- HOOK SYSTEMS. CONTRACTOR TO PROVIDE NEW 2" J-HOOKS AS REQUIRED FOR INSTALLATION OF NEW CAT6A CABLING. J-HOOK BASIS OF DESIGN IS NVENT CADDY CAT HP J-HOOK TREE. MAX CABLE FILL IS (35) CAT6A CABLES PER 2" J-HOOK (CABLE BASIS OF DESIGN - 0.35" NOMINAL OUTTER CABLE DIAMETER). CONTRACTOR SHALL PROVIDE CONDUIT FOR ROUTING OF NEW CAT6A CABLING ABOVE

HARD CEILINGS. REFER TO CABLE FILL CHARTS ON SHEET T-001 FOR CONDUIT FILL.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100FT INTERVALS FOR STRAIGHT CONDUIT RUNS, OR AT MAXIMUM CUMULATIVE OF 180 DEGREES OF CONDUIT BENDS.

9. DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING BUT NOT

LIMITED TO NURSE CALL, FIRE ALARM, SECURITY AND SSTV. DATA CABLING SHALL HAVE ITS OWN

RACEWAY WHEN ROUTED THROUGH CONDUIT.

10. SSTV CAMERAS, WAP DEVICES AND DATA OUTLETS ON THIS SHEET SHALL BE CONNECTED BACK TO

NEW PATCH PANELS IN TR 201.

DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH

PANEL. EXISTING BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION.

CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE.

PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE

DOWNTIME.

DISCONNECT EXISTING SSTV CAMERAS. EXISTING CAMERA TO REMAIN AS INSTALLED. REMOVE EXISTING

CABLING BACK TO SOURCE. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL.

CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW

CABLING TO MINIMIZE DOWNTIME. PROVIDE ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 2 CAMERAS FOR AREA SHOWN ON THIS DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND

LOCATIONS OF CAMERAS PRIOR TO COMMENCEMENT OF WORK.

DISCONNECT EXISTING CEILING MOUNTED VA AND GUEST WIFI WAP DEVICES. MEDICAL WIFI NETWORK, ASSOCIATED DEVICES AND CABLING ARE NOT IN SCOPE. ALL MEDICAL WIFI NETWORK DEVICES, CABLING AND EQUIPMENT ARE COVERED UNDER THE NATIONAL WIFI CONTRACT. EXISTING MEDICAL WIFI WAP DEVICE TO REMAIN AS INSTALLED. REMOVE EXISTING VA AND GUEST WIFI CABLING BACK TO SOURCE.

PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE DOWNTIME. PROVIDE

ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 10 WAP DEVICES FOR AREA SHOWN ON THIS

DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND LOCATIONS OF WAP DEVICES PRIOR TO

COMMENCEMENT OF WORK.

TYPICAL FOR ALL

NETWORK OUTLETS

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523

RECORDS

OFFICE-

PROSTHETICS

A280

2D

2D2D

2D

2D

2D2D

2D 2D

2D

2D 2D

2D

2D

2D

2D

1/ TN1.2.3

1/ TN1.2.2

1/ TN1.2.2

1/ TN1.2.5

TYPICAL FOR ALL

NETWORK OUTLETS

2D

2D

2D 2D

2D 2D

2D 2D

2D

2 3

2D

2D 2D

2D

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:5

:1

A

M

TN1.2.4

BLDG 64 - LV 2 - ZONE 4 - NEW LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

64-A

STATION CHIEF - EDWIN BURNETT

10/25/2024 BMS CVM

100% CONSTRUCTION

DOCUMENTS

CHRISTOPHER VAN METER

RCDD Reg. No. 285002

NN

0 4' 8' 16' 24'

1/8" = 1'-0"

1/8" = 1'-0"

SECOND FLOOR - B64-A(4) - NEW

CODED NOTES:

DRAWING NOTES:

1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE NEW IN SAME LOCATION. NUMBER OF PORTS INDICATED IS FOR NEW WORK. CONTRACTOR TO VERIFY EXACT LOCATION AND QUANTITIES OF DATA OUTLETS

PRIOR TO CONSTRUCTION. EXISTING DATA OUTLET LOCATIONS INDICATED ON THIS DRAWING

OBTAINED BY LIMITED SITE INVESTIGATION. CONTRACTOR TO DOCUMENT VARIANCES ON AS-BUILT

DRAWINGS.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING CONDITIONS FROM DAMAGE

DURING CONSTRUCTION. ANY MATERIALS, SYSTEMS, COMPONENTS, FINISHES, ETC. THAT ARE

DAMAGED DURING CONSTRUCTION MUST BE REPAIRED OR REPLACED AT CONTRACTORS EXPENSE

TO THE APPROVAL OF THE VA.

3. TELECOMMUNICATIONS OUTLET UPGRADE INCLUDES, BUT IS NOT LIMITED TO, REMOVAL OF EXISTING DEVICES AND ASSOCIATED NETWORK CABLING BACK TO PATCH PANEL, PROVIDING ALL MATERIALS, TOOLS, LABOR, TESTING INSTRUMENTS, ETC. REQUIRED FOR THE COMPLETE UPGRADE TO A FULLY FUNCTIONAL CATEGORY 6A, 8P8C PORT WITH THE PORT QUANTITY INDICATED FOR EACH OUTLET

LOCATION.

4. EXISTING POTS (ANALOG TELEPHONE) RJ11 PORTS AND ASSOCIATED CABLING IS NOT IN SCOPE.

EXISTING POTS PORTS LOCATED IN TELE/DATA OUTLETS RECEIVING TELECOMMUNICATIONS

UPGRADE SHALL BE REMOVED FROM OUTLET AND MAINTAINED FOR REINSTALLATION INTO NEW

OUTLET, UNLESS OTHERWISE NOTED.

5. PROVIDE ALL CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING OF FIBER OPTIC BACKBONE CABLING AND CAT6A HORIZONTAL CABLING. REFER TO CONDUIT FILL CHARTS ON SHEET T-001 FOR

ADDITIONAL INFORMATION.

6. INTERIOR FIRE WALL PENETRATIONS - CONTRACTOR SHALL PROVIDE APPROVED UL LISTED 4" SLEEVES AND FIRE RATED ASSEMBLY OR SYSTEM TO MAINTAIN FIRE RATING OF EXISTING FIRE

BARRIER. REFER TO CONDUIT FILL CHARTS FOR NUMBER OF SLEEVES REQUIRED.

7. NEW CAT6A CABLING SHALL BE ROUTED ABOVE ACCESSIBLE CEILINGS USING NEW AND EXISTING J- HOOK SYSTEMS. CONTRACTOR TO PROVIDE NEW 2" J-HOOKS AS REQUIRED FOR INSTALLATION OF NEW CAT6A CABLING. J-HOOK BASIS OF DESIGN IS NVENT CADDY CAT HP J-HOOK TREE. MAX CABLE FILL IS (35) CAT6A CABLES PER 2" J-HOOK (CABLE BASIS OF DESIGN - 0.35" NOMINAL OUTTER CABLE DIAMETER). CONTRACTOR SHALL PROVIDE CONDUIT FOR ROUTING OF NEW CAT6A CABLING ABOVE

HARD CEILINGS. REFER TO CABLE FILL CHARTS ON SHEET T-001 FOR CONDUIT FILL.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100FT INTERVALS FOR STRAIGHT CONDUIT RUNS, OR AT MAXIMUM CUMULATIVE OF 180 DEGREES OF CONDUIT BENDS.

9. DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING BUT NOT

LIMITED TO NURSE CALL, FIRE ALARM, SECURITY AND SSTV. DATA CABLING SHALL HAVE ITS OWN

RACEWAY WHEN ROUTED THROUGH CONDUIT.

10. WAP DEVICES AND DATA OUTLETS ON THIS SHEET SHALL BE CONNECTED BACK TO NEW PATCH

PANELS IN TR 201.

DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH

PANEL. EXISTING BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION.

CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE.

PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE

DOWNTIME.

DISCONNECT EXISTING SSTV CAMERAS. EXISTING CAMERA TO REMAIN AS INSTALLED. REMOVE EXISTING

CABLING BACK TO SOURCE. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL.

CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW

CABLING TO MINIMIZE DOWNTIME. PROVIDE ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 2 CAMERAS FOR AREA SHOWN ON THIS DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND

LOCATIONS OF CAMERAS PRIOR TO COMMENCEMENT OF WORK.

DISCONNECT EXISTING CEILING MOUNTED VA AND GUEST WIFI WAP DEVICES. MEDICAL WIFI NETWORK, ASSOCIATED DEVICES AND CABLING ARE NOT IN SCOPE. ALL MEDICAL WIFI NETWORK DEVICES, CABLING AND EQUIPMENT ARE COVERED UNDER THE NATIONAL WIFI CONTRACT. EXISTING MEDICAL WIFI WAP DEVICE TO REMAIN AS INSTALLED. REMOVE EXISTING VA AND GUEST WIFI CABLING BACK TO SOURCE.

PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE DOWNTIME. PROVIDE

ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 5 WAP DEVICES FOR AREA SHOWN ON THIS

DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND LOCATIONS OF WAP DEVICES PRIOR TO

COMMENCEMENT OF WORK.

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523 Revisions Date

EXB38 [5]

B64-A[4] B64-2[1]B64-A[4]

TELECOM RM

OFFICE

OFFICE

WOMENS

TOILET

TOILET

218E

ICE MACHINE

218D

MED ROOM

ELECTRICAL

ROOM

RN, SUICIDE

PREVENTION

STAIR 2 (38)

S201

ELEV.

P-2

ELEV. LOBBY

C2-3

H.A.C.

MENS TOILET

SOCIAL

WORKER

CONFERENCE

ROOM

CORRIDOR

C2-4

GNP,

DIRECTOR

STAFF

ASSISTANT

OFFICE

TRAINING

SPECIALIST

EDUCATION

PROGRAM

SPECIALIST

WAITING

OFFICE

218A

RECEPTION

218B

WORKROOM /

OFFICE

218C

CLINICAL

PHARMACIST

OFFICE

CORRIDOR

C2-5

SUNSHINE

TRAINING

CENTER

SOCIAL WORK

SOCIAL WORK

CORRIDOR

C2-6

ELEV.

P-1

SUPERVISOR

STAFF

PSYCHIATRIST

H.A.C.

OFFICE

OFFICE

ARNP SECIAL

PROJECTS

MANAGER

CONFERENCE

ROOM

STAIR 1

S203

EQUIPMENT

STAFF ARNP

STAFF ARNP

OFFICE

STAFF

LOUNGE

CORRIDOR

C2-2

COPY ROOM

STAFF

PSYCHIATRIST

SECRETARY

METABOLIC

RN

STAIR 2

S202

FIRE

SUPPRESSION

BATH

238A

STORAGE

OFFICE

ELEVATOR

LOBBY

C2-1

T-406

TD403

2D2D 2D

2D

2D 1V

2D 1V

2D

2D

2D

2D 1V

2D

2D

2D

2D

2D

2D

2D 2D

2D

2D

2D

2D 1V2D

1V 2D 1V

2D

2D 1V

2D 1V

2D 1V

2D 1V

2D 1V

2D

2D

2D

2D

2D 2D

1/ TN1.2.4 1/ TN1.2.4

TYPICAL FOR ALL

NETWORK OUTLETS

2D

2D

2D

2D

2D

2D

CH CH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:5

:2

A

M

TN1.2.5

BLDG 38 - LV 2 - ZONE 5 NEW LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

STATION CHIEF - EDWIN BURNETT

10/25/2024 BMS CVM

100% CONSTRUCTION

DOCUMENTS

CHRISTOPHER VAN METER

RCDD Reg. No. 285002

NN

0 4' 8' 16' 24'

1/8" = 1'-0"

1/8" = 1'-0"1

SECOND FLOOR - B38(5) - NEW

CODED NOTES:

DRAWING NOTES:

1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE NEW IN SAME LOCATION. NUMBER OF PORTS INDICATED IS FOR NEW WORK. CONTRACTOR TO VERIFY EXACT LOCATION AND QUANTITIES OF DATA OUTLETS

PRIOR TO CONSTRUCTION. EXISTING DATA OUTLET LOCATIONS INDICATED ON THIS DRAWING

OBTAINED BY LIMITED SITE INVESTIGATION. CONTRACTOR TO DOCUMENT VARIANCES ON AS-BUILT

DRAWINGS.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING CONDITIONS FROM DAMAGE

DURING CONSTRUCTION. ANY MATERIALS, SYSTEMS, COMPONENTS, FINISHES, ETC. THAT ARE

DAMAGED DURING CONSTRUCTION MUST BE REPAIRED OR REPLACED AT CONTRACTORS EXPENSE

TO THE APPROVAL OF THE VA.

3. TELECOMMUNICATIONS OUTLET UPGRADE INCLUDES, BUT IS NOT LIMITED TO, REMOVAL OF EXISTING DEVICES AND ASSOCIATED NETWORK CABLING BACK TO PATCH PANEL, PROVIDING ALL MATERIALS, TOOLS, LABOR, TESTING INSTRUMENTS, ETC. REQUIRED FOR THE COMPLETE UPGRADE TO A FULLY FUNCTIONAL CATEGORY 6A, 8P8C PORT WITH THE PORT QUANTITY INDICATED FOR EACH OUTLET

LOCATION.

4. EXISTING POTS (ANALOG TELEPHONE) RJ11 PORTS AND ASSOCIATED CABLING IS NOT IN SCOPE.

EXISTING POTS PORTS LOCATED IN TELE/DATA OUTLETS RECEIVING TELECOMMUNICATIONS

UPGRADE SHALL BE REMOVED FROM OUTLET AND MAINTAINED FOR REINSTALLATION INTO NEW

OUTLET, UNLESS OTHERWISE NOTED.

5. PROVIDE ALL CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING OF FIBER OPTIC BACKBONE CABLING AND CAT6A HORIZONTAL CABLING. REFER TO CONDUIT FILL CHARTS ON SHEET T-001 FOR

ADDITIONAL INFORMATION.

6. INTERIOR FIRE WALL PENETRATIONS - CONTRACTOR SHALL PROVIDE APPROVED UL LISTED 4" SLEEVES AND FIRE RATED ASSEMBLY OR SYSTEM TO MAINTAIN FIRE RATING OF EXISTING FIRE

BARRIER. REFER TO CONDUIT FILL CHARTS FOR NUMBER OF SLEEVES REQUIRED.

7. NEW CAT6A CABLING SHALL BE ROUTED ABOVE ACCESSIBLE CEILINGS USING NEW AND EXISTING J- HOOK SYSTEMS. CONTRACTOR TO PROVIDE NEW 2" J-HOOKS AS REQUIRED FOR INSTALLATION OF NEW CAT6A CABLING. J-HOOK BASIS OF DESIGN IS NVENT CADDY CAT HP J-HOOK TREE. MAX CABLE FILL IS (35) CAT6A CABLES PER 2" J-HOOK (CABLE BASIS OF DESIGN - 0.35" NOMINAL OUTTER CABLE DIAMETER). CONTRACTOR SHALL PROVIDE CONDUIT FOR ROUTING OF NEW CAT6A CABLING ABOVE

HARD CEILINGS. REFER TO CABLE FILL CHARTS ON SHEET T-001 FOR CONDUIT FILL.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100FT INTERVALS FOR STRAIGHT CONDUIT RUNS, OR AT MAXIMUM CUMULATIVE OF 180 DEGREES OF CONDUIT BENDS.

9. DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING BUT NOT

LIMITED TO NURSE CALL, FIRE ALARM, SECURITY AND SSTV. DATA CABLING SHALL HAVE ITS OWN

RACEWAY WHEN ROUTED THROUGH CONDUIT.

10. SSTV CAMERAS, WAP DEVICES AND DATA OUTLETS ON THIS SHEET SHALL BE CONNECTED BACK TO

NEW PATCH PANELS IN TR 216.

DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH

PANEL. EXISTING BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION.

CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE.

PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE

DOWNTIME.

DISCONNECT EXISTING CEILING MOUNTED VA AND GUEST WIFI WAP DEVICES. MEDICAL WIFI NETWORK, ASSOCIATED DEVICES AND CABLING ARE NOT IN SCOPE. ALL MEDICAL WIFI NETWORK DEVICES, CABLING AND EQUIPMENT ARE COVERED UNDER THE NATIONAL WIFI CONTRACT. EXISTING MEDICAL WIFI WAP DEVICE TO REMAIN AS INSTALLED. REMOVE EXISTING VA AND GUEST WIFI CABLING BACK TO SOURCE.

PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE DOWNTIME. PROVIDE

ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 10 WAP DEVICES FOR AREA SHOWN ON THIS

DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND LOCATIONS OF WAP DEVICES PRIOR TO

COMMENCEMENT OF WORK.

DISCONNECT EXISTING SSTV CAMERAS. EXISTING CAMERA TO REMAIN AS INSTALLED. REMOVE EXISTING

CABLING BACK TO SOURCE. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL.

CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW

CABLING TO MINIMIZE DOWNTIME. PROVIDE ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 4 CAMERAS FOR AREA SHOWN ON THIS DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND

LOCATIONS OF CAMERAS PRIOR TO COMMENCEMENT OF WORK.

PROVIDE PATCH CABLES FROM EXISTING NOT IN CONTRACT EQUIPMENT TO NEW HORIZONTAL

DISTRIBUTION EQUIPMENT LOCATED IN ROOM 216. REFER TO 8/TD403 FOR ADDITIONAL INFORMATION.

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523

Revisions Date

EQUIPMENT

STAIRS

S3-1A

EQUIPMENT

341B

PATIENT

TOILET

341C

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

H.A.C.

PATIENT

BATROOM

332A

PATIENT

TOILET

333A

CLEAN LINEN

SPD

PATIENT

TOILET

337A

PATIENT

TOILET

339A

ALCOVE

341C

ALCOVE

340A

ALCOVE

339B

ALCOVE

338A

ALCOVE

337B

ALCOVE

C3-17

ALCOVE

336A

ALCOVE

333B

ALCOVE

332B

ALCOVE

C3-16

PATIENT

TOILET

348A

PATIENT

TOILET

346A

PATIENT

TOILET

344A

STORAGE

PATIENT

TOILET

343A

PATIENT

TOILET

371A

PATIENT

TOILET

373A

PATIENT

TOILET

364A

PATIENT

TOILET

366A

PATIENT

TOILET

368A

STORAGE

OXYGEN RM

333W

CLEAN LINEN

361PATIENT

TOILET

375A

STORAGE

370C

PAT.

BATHROOM

359A

H.A.C.

DATA

ELECT.

ELECT.

CLEAN

UTILITY

CORRIDOR

C3-11

QUIET RM.

TOILET

TRASH ROOM

STORAGE

324A

MED.

STORAGE

SHOWERS

SOILED

UTILITY

NOURISHMENT

HEAD NURSE

WARD

STORAGE

SOILED LINEN

PAT. TOILET

377A

EQUIPMENT

STORAGE

RESIDENTIAL

LAUNDRY

PATIENT

TOILET

370A

PATIENT

TOILET

360A

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

CONG. TOILET

CONG. BATH

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

TREATMENT

CORRIDOR

C3-9

ALCOVE

343B

ALCOVE

344B

ALCOVE

345A

ALCOVE

346B

ALCOVE

347A

ALCOVE

348B

ALCOVE

349A

CORRIDOR

ALCOVE

C3-8

ALCOVE

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

PATIENT

BEDROOM

ALCOVE

368B

ALCOVE

367A

ALCOVE

366B

ALCOVE

365A

ALCOVE

364B

ALCOVE

C3-21

ALCOVE

C3-20

CORRIDOR

C3-19

PATIENT

BEDROOM

ALCOVE

377B

ALCOVE

376A

ALCOVE

375B

ALCOVE

374A

ALCOVE

373B

ALCOVE

372A

ALCOVE

371B

ALCOVE

370B

ALCOVE

C3-22

CORRIDOR

C3-10

CORRIDOR

C3-6

NURSES

STATION

C3-6

TD404

2D 1V

2D

2D 1V 2D

1V 2D 1V

2D 1V

2D

2D 1V

2D 2V

2D

2D

2D

2D

2D 2V

2D

2D 2V 2D

2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V 2D

2V

2D 2V 2D

2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

2D 2V

1/ TN1.2.9

1/ TN1.2.9

TYPICAL FOR ALL

NETWORK OUTLETS

2D 2V

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:5

:2

A

M

TN1.2.8

BLDG 82 - LV 2 - ZONE 8 - NEW LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

STATION CHIEF - EDWIN BURNETT

10/25/2024 BMS CVM

100% CONSTRUCTION

DOCUMENTS

CHRISTOPHER VAN METER

RCDD Reg. No. 285002

NN

0 4' 8' 16' 24'

1/8" = 1'-0"1/8" = 1'-0"1

SECOND FLOOR - B82(8) - NEW

CODED NOTES:

DRAWING NOTES:

1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE NEW IN SAME LOCATION. NUMBER OF PORTS INDICATED IS FOR NEW WORK. CONTRACTOR TO VERIFY EXACT LOCATION AND QUANTITIES OF DATA OUTLETS

PRIOR TO CONSTRUCTION. EXISTING DATA OUTLET LOCATIONS INDICATED ON THIS DRAWING

OBTAINED BY LIMITED SITE INVESTIGATION. CONTRACTOR TO DOCUMENT VARIANCES ON AS-BUILT

DRAWINGS.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING CONDITIONS FROM DAMAGE

DURING CONSTRUCTION. ANY MATERIALS, SYSTEMS, COMPONENTS, FINISHES, ETC. THAT ARE

DAMAGED DURING CONSTRUCTION MUST BE REPAIRED OR REPLACED AT CONTRACTORS EXPENSE

TO THE APPROVAL OF THE VA.

3. TELECOMMUNICATIONS OUTLET UPGRADE INCLUDES, BUT IS NOT LIMITED TO, REMOVAL OF EXISTING DEVICES AND ASSOCIATED NETWORK CABLING BACK TO PATCH PANEL, PROVIDING ALL MATERIALS, TOOLS, LABOR, TESTING INSTRUMENTS, ETC. REQUIRED FOR THE COMPLETE UPGRADE TO A FULLY FUNCTIONAL CATEGORY 6A, 8P8C PORT WITH THE PORT QUANTITY INDICATED FOR EACH OUTLET

LOCATION.

4. EXISTING POTS (ANALOG TELEPHONE) RJ11 PORTS AND ASSOCIATED CABLING IS NOT IN SCOPE.

EXISTING POTS PORTS LOCATED IN TELE/DATA OUTLETS RECEIVING TELECOMMUNICATIONS

UPGRADE SHALL BE REMOVED FROM OUTLET AND MAINTAINED FOR REINSTALLATION INTO NEW

OUTLET, UNLESS OTHERWISE NOTED.

5. PROVIDE ALL CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING OF FIBER OPTIC BACKBONE CABLING AND CAT6A HORIZONTAL CABLING. REFER TO CONDUIT FILL CHARTS ON SHEET T-001 FOR

ADDITIONAL INFORMATION.

6. INTERIOR FIRE WALL PENETRATIONS - CONTRACTOR SHALL PROVIDE APPROVED UL LISTED 4" SLEEVES AND FIRE RATED ASSEMBLY OR SYSTEM TO MAINTAIN FIRE RATING OF EXISTING FIRE

BARRIER. REFER TO CONDUIT FILL CHARTS FOR NUMBER OF SLEEVES REQUIRED.

7. NEW CAT6A CABLING SHALL BE ROUTED ABOVE ACCESSIBLE CEILINGS USING NEW AND EXISTING J- HOOK SYSTEMS. CONTRACTOR TO PROVIDE NEW 2" J-HOOKS AS REQUIRED FOR INSTALLATION OF NEW CAT6A CABLING. J-HOOK BASIS OF DESIGN IS NVENT CADDY CAT HP J-HOOK TREE. MAX CABLE FILL IS (35) CAT6A CABLES PER 2" J-HOOK (CABLE BASIS OF DESIGN - 0.35" NOMINAL OUTTER CABLE DIAMETER). CONTRACTOR SHALL PROVIDE CONDUIT FOR ROUTING OF NEW CAT6A CABLING ABOVE

HARD CEILINGS. REFER TO CABLE FILL CHARTS ON SHEET T-001 FOR CONDUIT FILL.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100FT INTERVALS FOR STRAIGHT CONDUIT RUNS, OR AT MAXIMUM CUMULATIVE OF 180 DEGREES OF CONDUIT BENDS.

9. DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING BUT NOT

LIMITED TO NURSE CALL, FIRE ALARM, SECURITY AND SSTV. DATA CABLING SHALL HAVE ITS OWN

RACEWAY WHEN ROUTED THROUGH CONDUIT.

10. SSTV CAMERAS, WAP DEVICES AND DATA OUTLETS ON THIS SHEET SHALL BE CONNECTED BACK TO

NEW PATCH PANELS IN TR 317.

DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH

PANEL. EXISTING BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION.

CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE.

PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE

DOWNTIME.

DISCONNECT EXISTING CEILING MOUNTED VA AND GUEST WIFI WAP DEVICES. MEDICAL WIFI NETWORK, ASSOCIATED DEVICES AND CABLING ARE NOT IN SCOPE. ALL MEDICAL WIFI NETWORK DEVICES, CABLING AND EQUIPMENT ARE COVERED UNDER THE NATIONAL WIFI CONTRACT. EXISTING MEDICAL WIFI WAP DEVICE TO REMAIN AS INSTALLED. REMOVE EXISTING VA AND GUEST WIFI CABLING BACK TO SOURCE.

PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE DOWNTIME. PROVIDE

ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 10 WAP DEVICES FOR AREA SHOWN ON THIS

DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND LOCATIONS OF WAP DEVICES PRIOR TO

COMMENCEMENT OF WORK.

DISCONNECT EXISTING SSTV CAMERAS. EXISTING CAMERA TO REMAIN AS INSTALLED. REMOVE EXISTING

CABLING BACK TO SOURCE. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL.

CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW

CABLING TO MINIMIZE DOWNTIME. PROVIDE ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 7 CAMERAS FOR AREA SHOWN ON THIS DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND

LOCATIONS OF CAMERAS PRIOR TO COMMENCEMENT OF WORK.

PROVIDE PATCH CABLES FROM EXISTING NOT IN CONTRACT EQUIPMENT TO NEW HORIZONTAL

DISTRIBUTION EQUIPMENT LOCATED IN ROOM 317. REFER TO 1/TD404 FOR ADDITIONAL INFORMATION.

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523

Revisions Date

ELEVATOR

P-1/82

ELEVATOR

P-2/82

ELEVATOR

P-3/82

ELEVATOR

P-4/82

H.A.C.

OFFICE

MENS TOILET

WOMENS

TOILET

ELEC

LOUNGE

WOMENS

TOILET

MENS TOILET

STORAGE

LOCKERS

LOCKERS

STAIR 3

S3-3A

PORCH

DINING /

RECREATION

BATTERY RM

LOBBY

C3-1

CORRIDOR

C3-5

CORRIDOR

CORRIDOR

C3-3

CORRIDOR

C3-14

GEN.STORAGE

MECHANICAL

ALCOVE

C3-16

T-406

2D

2D

2D

2D

1/ TN1.2.8

1/ TN1.2.8

1/ TN1.2.2

1/ TN1.2.2

1TYPICAL FOR ALL

NETWORK OUTLETS

2D

2 3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:5

:3

A

M

TN1.2.9

BLDG 82 - LV 2 - ZONE 9 - NEW LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

STATION CHIEF - EDWIN BURNETT

10/25/2024 BMS CVM

100% CONSTRUCTION

DOCUMENTS

CHRISTOPHER VAN METER

RCDD Reg. No. 285002

NN

0 4' 8' 16' 24'

1/8" = 1'-0" 1/8" = 1'-0"

SECOND FLOOR - B82(9) - NEW

CODED NOTES:

DRAWING NOTES:

1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE NEW IN SAME LOCATION. NUMBER OF PORTS INDICATED IS FOR NEW WORK. CONTRACTOR TO VERIFY EXACT LOCATION AND QUANTITIES OF DATA OUTLETS

PRIOR TO CONSTRUCTION. EXISTING DATA OUTLET LOCATIONS INDICATED ON THIS DRAWING

OBTAINED BY LIMITED SITE INVESTIGATION. CONTRACTOR TO DOCUMENT VARIANCES ON AS-BUILT

DRAWINGS.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING CONDITIONS FROM DAMAGE

DURING CONSTRUCTION. ANY MATERIALS, SYSTEMS, COMPONENTS, FINISHES, ETC. THAT ARE

DAMAGED DURING CONSTRUCTION MUST BE REPAIRED OR REPLACED AT CONTRACTORS EXPENSE

TO THE APPROVAL OF THE VA.

3. TELECOMMUNICATIONS OUTLET UPGRADE INCLUDES, BUT IS NOT LIMITED TO, REMOVAL OF EXISTING DEVICES AND ASSOCIATED NETWORK CABLING BACK TO PATCH PANEL, PROVIDING ALL MATERIALS, TOOLS, LABOR, TESTING INSTRUMENTS, ETC. REQUIRED FOR THE COMPLETE UPGRADE TO A FULLY FUNCTIONAL CATEGORY 6A, 8P8C PORT WITH THE PORT QUANTITY INDICATED FOR EACH OUTLET

LOCATION.

4. EXISTING POTS (ANALOG TELEPHONE) RJ11 PORTS AND ASSOCIATED CABLING IS NOT IN SCOPE.

EXISTING POTS PORTS LOCATED IN TELE/DATA OUTLETS RECEIVING TELECOMMUNICATIONS

UPGRADE SHALL BE REMOVED FROM OUTLET AND MAINTAINED FOR REINSTALLATION INTO NEW

OUTLET, UNLESS OTHERWISE NOTED.

5. PROVIDE ALL CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING OF FIBER OPTIC BACKBONE CABLING AND CAT6A HORIZONTAL CABLING. REFER TO CONDUIT FILL CHARTS ON SHEET T-001 FOR

ADDITIONAL INFORMATION.

6. INTERIOR FIRE WALL PENETRATIONS - CONTRACTOR SHALL PROVIDE APPROVED UL LISTED 4" SLEEVES AND FIRE RATED ASSEMBLY OR SYSTEM TO MAINTAIN FIRE RATING OF EXISTING FIRE

BARRIER. REFER TO CONDUIT FILL CHARTS FOR NUMBER OF SLEEVES REQUIRED.

7. NEW CAT6A CABLING SHALL BE ROUTED ABOVE ACCESSIBLE CEILINGS USING NEW AND EXISTING J- HOOK SYSTEMS. CONTRACTOR TO PROVIDE NEW 2" J-HOOKS AS REQUIRED FOR INSTALLATION OF NEW CAT6A CABLING. J-HOOK BASIS OF DESIGN IS NVENT CADDY CAT HP J-HOOK TREE. MAX CABLE FILL IS (35) CAT6A CABLES PER 2" J-HOOK (CABLE BASIS OF DESIGN - 0.35" NOMINAL OUTTER CABLE DIAMETER). CONTRACTOR SHALL PROVIDE CONDUIT FOR ROUTING OF NEW CAT6A CABLING ABOVE

HARD CEILINGS. REFER TO CABLE FILL CHARTS ON SHEET T-001 FOR CONDUIT FILL.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100FT INTERVALS FOR STRAIGHT CONDUIT RUNS, OR AT MAXIMUM CUMULATIVE OF 180 DEGREES OF CONDUIT BENDS.

9. DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING BUT NOT

LIMITED TO NURSE CALL, FIRE ALARM, SECURITY AND SSTV. DATA CABLING SHALL HAVE ITS OWN

RACEWAY WHEN ROUTED THROUGH CONDUIT.

10. SSTV CAMERAS, WAP DEVICES AND DATA OUTLETS ON THIS SHEET SHALL BE CONNECTED BACK TO

NEW PATCH PANELS IN TR 317.

DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH

PANEL. EXISTING BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION.

CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE.

PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE

DOWNTIME.

DISCONNECT EXISTING CEILING MOUNTED VA AND GUEST WIFI WAP DEVICES. MEDICAL WIFI NETWORK, ASSOCIATED DEVICES AND CABLING ARE NOT IN SCOPE. ALL MEDICAL WIFI NETWORK DEVICES, CABLING AND EQUIPMENT ARE COVERED UNDER THE NATIONAL WIFI CONTRACT. EXISTING MEDICAL WIFI WAP DEVICE TO REMAIN AS INSTALLED. REMOVE EXISTING VA AND GUEST WIFI CABLING BACK TO SOURCE.

PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE DOWNTIME. PROVIDE

ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 10 WAP DEVICES FOR AREA SHOWN ON THIS

DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND LOCATIONS OF WAP DEVICES PRIOR TO

COMMENCEMENT OF WORK.

DISCONNECT EXISTING SSTV CAMERAS. EXISTING CAMERA TO REMAIN AS INSTALLED. REMOVE EXISTING

CABLING BACK TO SOURCE. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL.

CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW

CABLING TO MINIMIZE DOWNTIME. PROVIDE ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 6 CAMERAS FOR AREA SHOWN ON THIS DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND

LOCATIONS OF CAMERAS PRIOR TO COMMENCEMENT OF WORK.

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523

X

DATA

NURSE

STATION

235C

TOILET

STORAGE

KITCHEN

DAV

216A

TD404

2D 2V

2D

2D

2D

2D

2D

2D

2D 1V

2D 1V

2D 1V

2D

2D

2D

2D 1V 2D

2/ TN1.2.12

TYPICAL FOR ALL

NETWORK OUTLETS

2D

2D

2D2D

NURSE

STATION

235C

TOILET

STORAGE

DAY ROOM

DINING ROOM

OT OFFICE

GROUP ROOM

RESIDENT

SUITE

TOILET

229A

SHOWER

229B

SHOWER

228B

TOILET

228A

RESIDENT

SUITE

OFFICE

MENS TOILET

SHOWER

226B

SHOWER

226A

OFFICE

H. A. C.

STRETCHER

ALCOVE

SHOWER

221A

TOILET

223A

RESIDENT

SUITE

RESIDENT

SUITE

RESIDENT

SUITE

TOILET

220A

SHOWER

220B

SOILED LINEN

KITCHEN

CORRIDOR

STAIR 3

239B

DAV

216A

TELECOM RM

227A T-407

2D 1V

2D 1V

2D 1V

2D 1V

2D

2D

2D2D 1V

2D 1V

2D

2D 2V

2D

2D 1V

2D

2D

2D

1/ TN1.2.121/ TN1.2.12

TYPICAL FOR ALL

NETWORK OUTLETS

2D 1V

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:5

:4

A

M

TN1.2.12

BLDG 62 - LV 2 - ZONE 12 - NEW LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

STATION CHIEF - EDWIN BURNETT

10/25/2024 BMS CVM

100% CONSTRUCTION

DOCUMENTS

CHRISTOPHER VAN METER

RCDD Reg. No. 285002

NN

0 4' 8' 16' 24'

1/8" = 1'-0"

1/8" = 1'-0"

SECOND FLOOR - B62(12a) - NEW 1/8" = 1'-0"

SECOND FLOOR - B62(12b) - NEW

CODED NOTES:

DRAWING NOTES:

1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE…