Attachment 7 - Final Drawing Set - 6 of 8.pdf
PDF 7 MB Posted
- Attached to
- Project 573A4-21-700 EHRM Infrastructure Upgrades construction project at the Lake City, FL VAMC
- Solicitation number
- 36C77625B0006
About this file
The files are telecommunications infrastructure design drawings for the Lake City VA Medical Center's EHRM Infrastructure Upgrades construction project. The documents detail comprehensive telecommunications upgrades across multiple building floors (second through fourth), involving the replacement and installation of new network infrastructure including fiber optic backbone cabling, Category 6A horizontal cabling, network outlets, WiFi access points, and security cameras.
The project is a Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside with a construction value between $20-50 million, solicited under contract number 36C77625B0006 by the Department of Veterans Affairs Technology Acquisition Center Austin. The technical specifications mandate systematic removal of existing network equipment, reinstallation of analog telephone ports, routing of new cabling using J-hook systems, maintaining fire barrier ratings, and connecting various data outlets, WiFi devices, and security cameras to new patch panels in designated telecommunication rooms across different building zones, with careful coordination to minimize network downtime.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TELECOM RM
B207
TELECOM RM
TELECOM RM
TELECOM RM
227A
TELECOM RM
TELECOM RM
B217A
TELECOM RM
TELECOM RM
C225
TELECOM RM
57a
S1
Q1RST
TR 317
TR 216
TR 201
TR B207
TR 227A
2 43 51 6
2 4
B62[12]
B64-A[3] B64-B[2]
B82[9]
B82[8]
B64-2[1]B64-A[4]
B38[5]
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
L a k e
C it y V
A /0
V
A L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
M
E P
F P
T .r v t
/2 /2
:5
:4
A
M
TN1.2
SECOND FLOOR - ZONES - NEW LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 BMS CVM
100% CONSTRUCTION
DOCUMENTS
CHRISTOPHER VAN METER
RCDD Reg. No. 285002
NN
0 15' 30' 60' 90'
1" = 30'
1" = 30'-0"
SECOND FLOOR - ZONES - NEW
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
CODED NOTES:
DRAWING NOTES:
1. LOCATIONS WHERE CORE-A AND CORE-B FIBER OPTIC CABLES ARE ROUTED IN THE SAME
CORRIDOR, CORE-A CABLES MUST BE ROUTED ON OPPOSITE SIDE OF CORRIDOR FROM CORE-B.
2. INDOOR FIBER OPTIC CABLE ROUTED ABOVE CEILING, UNLESS OTHERWISE NOTED. ROUTING INDICATED ON THIS PLAN IS DIAGRAMATIC. CONTRACTOR TO COORDINATE EXACT ROUTING OF FIBER
OPTIC CABLES WITH EXISTING CONDITIONS.
3. COORDINATE EXACT LOCATION OF PENETRATION TO FLOOR ABOVE/BELOW WITH EXISTING
CONDITIONS AND FLOOR SPACE ABOVE/BELOW.
4. ARMORED FIBER OPTIC CABLES TO BE ROUTED IN EMT UNLESS ROUTED CONCEALED ABOVE
CEILINGS.
CORE-A FIBER OPTIC CABLES ROUTED UP FROM FLOOR BELOW. REFER TO FIBER BACKBONE RISER
DIAGRAM ON SHEET T-601 FOR ADDITIONAL INFORMATION.
CORE-B FIBER OPTIC CABLES ROUTED UP FROM FLOOR BELOW. REFER TO FIBER BACKBONE RISER
DIAGRAM ON SHEET T-601 FOR ADDITIONAL INFORMATION.
CORE-A FIBER OPTIC CABLES ROUTED UP TO FLOOR ABOVE. REFER TO FIBER BACKBONE RISER
DIAGRAM ON SHEET T-601 FOR ADDITIONAL INFORMATION.
CORE-B FIBER OPTIC CABLES ROUTED UP TO FLOOR ABOVE. REFER TO FIBER BACKBONE RISER
DIAGRAM ON SHEET T-601 FOR ADDITIONAL INFORMATION.
TERMINATE CORE-A FIBER OPTIC CABLES IN TR. REFER TO FIBER BACKBONE RISER DIAGRAM ON SHEET
T-601 FOR ADDITIONAL INFORMATION.
TERMINATE CORE-B FIBER OPTIC CABLES IN TR. REFER TO FIBER BACKBONE RISER DIAGRAM ON SHEET
T-601 FOR ADDITIONAL INFORMATION.
HORIZONTAL CAT6A CABLING NOT IN SCOPE FOR THIS AREA, TO BE COMPLETED AS A PART OF
SEPARATE PROJECT, NUMBER 573-A4-18-603.
Revisions Date
10/25/202412/31/2024
E X
OFFICE -
NURSE
MANAGER
C228
OFFICE -
SUPERVISOR
AMBULATORY
CARE
C231
MEDICATION
ROOM
C233
OFFICE -
NURSE
C238
SOIL HOLD
C240
OFFICE -
NURSE
C242
COPY ROOM
C244
OFFICE -
NURSE
C246
OFFICE -
PACT, ER,
SOCIAL WORK
C248
TOILET
C249
TRIAGE
OFFICE
C250
VESTIBULE
C-251
PROCEDURE
ROOM
C251
OFFICE
C252
CLERKS
C253
OFFICE -
SOCIAL
WORKER
C201
OFFICE -
CONSULTATION
C202
OFFICE -
NURSE
C204
TOILET
C205
EXAM ROOM
#2
C208
EXAM ROOM
#1
C209
OFFICE -
HEALTH
COACH
C211
EXAM ROOM
#7
C213
EXAM ROOM
#6
C214
MEDICATION
ROOM
C216
CONFERENCE
ROOM
C221
BREAKROOM
C222
ELEC
C224
EQUIPMENT
C225
ELEC
C226
ELEC
C227
OFFICE -
BEHAVIORAL
HEALTH
C229
TOILET
C230
OFFICE -
NURSE
C232
OFFICE -
NURSE
C239
EXAM ROOM
C241
EXAM ROOM
C243
EXAM ROOM
#3
C245
EXAM ROOM
C247
CLOSET
C218
TOILET STAFF
C219
PHARMACY
CONSULT
C217
STORAGE
C220
H.A.C.
C223
OFFICE -
NURSE
C215
EXAM ROOM
#5
C206
EXAM ROOM
#4
C207
OFFICE -
NURSE
C210
OFFICE -
NURSE
C212
WAITING
C200A
CORRIDOR
C2-4
CORRIDOR
C2-3
CORRIDOR
C2-1
ALCOVE
C201D
PHARMACIST
C234
ELEVATOR
LOBBY
C-200
VESTIBULE
C235
TOILET MALE
C237
TOILET
FEMALE
C236
CORRIDOR
C2-7
CORRIDOR
C2-2
CORRIDOR
C2-5
CORRIDOR
C2-8
OFFICE -
NURSE
C203
OFFICE -
HEALTH
COACH
C228A
WORKSTATIONS
C200B
STAIR #7
S7.2
ELEVATOR
PASSENGER
P-7.2/64
ELEVATOR
PASSENGER
P-6.2/64
CORRIDOR
C2-2
OFFICE
XXX
TD403
2D 1V
2D 1V
2D 1V
2D 1V
2D 1V
2D 1V
2D 1V
2D 2D
2D
2D
2D 2D 1V
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D 2D 2D
2D
2D
2D
2D 2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D 2D
2D
1/ TN1.2.2
1/ TN1.2.4
1/ TN1.2.4
1/ TN1.2.2
TYPICAL FOR ALL
NETWORK OUTLETS
2D
2D
2D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
L a k e
C it y V
A /0
V
A L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
M
E P
F P
T .r v t
/2 /2
:5
:5
A
M
TN1.2.1
BLDG 64 - LV 2 - ZONE 1 - NEW LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
64-2
STATION CHIEF - EDWIN BURNETT
10/25/2024 BMS CVM
100% CONSTRUCTION
DOCUMENTS
CHRISTOPHER VAN METER
RCDD Reg. No. 285002
NN
0 4' 8' 16' 24'
1/8" = 1'-0"
1/8" = 1'-0"
SECOND FLOOR - B64-2(1) - NEW
CODED NOTES:
DRAWING NOTES:
1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE NEW IN SAME LOCATION. NUMBER OF PORTS INDICATED IS FOR NEW WORK. CONTRACTOR TO VERIFY EXACT LOCATION AND QUANTITIES OF DATA OUTLETS
PRIOR TO CONSTRUCTION. EXISTING DATA OUTLET LOCATIONS INDICATED ON THIS DRAWING
OBTAINED BY LIMITED SITE INVESTIGATION. CONTRACTOR TO DOCUMENT VARIANCES ON AS-BUILT
DRAWINGS.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING CONDITIONS FROM DAMAGE
DURING CONSTRUCTION. ANY MATERIALS, SYSTEMS, COMPONENTS, FINISHES, ETC. THAT ARE
DAMAGED DURING CONSTRUCTION MUST BE REPAIRED OR REPLACED AT CONTRACTORS EXPENSE
TO THE APPROVAL OF THE VA.
3. TELECOMMUNICATIONS OUTLET UPGRADE INCLUDES, BUT IS NOT LIMITED TO, REMOVAL OF EXISTING DEVICES AND ASSOCIATED NETWORK CABLING BACK TO PATCH PANEL, PROVIDING ALL MATERIALS, TOOLS, LABOR, TESTING INSTRUMENTS, ETC. REQUIRED FOR THE COMPLETE UPGRADE TO A FULLY FUNCTIONAL CATEGORY 6A, 8P8C PORT WITH THE PORT QUANTITY INDICATED FOR EACH OUTLET
LOCATION.
4. EXISTING POTS (ANALOG TELEPHONE) RJ11 PORTS AND ASSOCIATED CABLING IS NOT IN SCOPE.
EXISTING POTS PORTS LOCATED IN TELE/DATA OUTLETS RECEIVING TELECOMMUNICATIONS
UPGRADE SHALL BE REMOVED FROM OUTLET AND MAINTAINED FOR REINSTALLATION INTO NEW
OUTLET, UNLESS OTHERWISE NOTED.
5. PROVIDE ALL CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING OF FIBER OPTIC BACKBONE CABLING AND CAT6A HORIZONTAL CABLING. REFER TO CONDUIT FILL CHARTS ON SHEET T-001 FOR
ADDITIONAL INFORMATION.
6. INTERIOR FIRE WALL PENETRATIONS - CONTRACTOR SHALL PROVIDE APPROVED UL LISTED 4" SLEEVES AND FIRE RATED ASSEMBLY OR SYSTEM TO MAINTAIN FIRE RATING OF EXISTING FIRE
BARRIER. REFER TO CONDUIT FILL CHARTS FOR NUMBER OF SLEEVES REQUIRED.
7. NEW CAT6A CABLING SHALL BE ROUTED ABOVE ACCESSIBLE CEILINGS USING NEW AND EXISTING J- HOOK SYSTEMS. CONTRACTOR TO PROVIDE NEW 2" J-HOOKS AS REQUIRED FOR INSTALLATION OF NEW CAT6A CABLING. J-HOOK BASIS OF DESIGN IS NVENT CADDY CAT HP J-HOOK TREE. MAX CABLE FILL IS (35) CAT6A CABLES PER 2" J-HOOK (CABLE BASIS OF DESIGN - 0.35" NOMINAL OUTTER CABLE DIAMETER). CONTRACTOR SHALL PROVIDE CONDUIT FOR ROUTING OF NEW CAT6A CABLING ABOVE
HARD CEILINGS. REFER TO CABLE FILL CHARTS ON SHEET T-001 FOR CONDUIT FILL.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100FT INTERVALS FOR STRAIGHT CONDUIT RUNS, OR AT MAXIMUM CUMULATIVE OF 180 DEGREES OF CONDUIT BENDS.
9. DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING BUT NOT
LIMITED TO NURSE CALL, FIRE ALARM, SECURITY AND SSTV. DATA CABLING SHALL HAVE ITS OWN
RACEWAY WHEN ROUTED THROUGH CONDUIT.
10. SSTV CAMERAS, WAP DEVICES AND DATA OUTLETS ON THIS SHEET SHALL BE CONNECTED BACK TO
NEW PATCH PANELS IN TR B207.
DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH
PANEL. EXISTING BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION.
CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE.
PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE
DOWNTIME.
DISCONNECT EXISTING CEILING MOUNTED VA AND GUEST WIFI WAP DEVICES. MEDICAL WIFI NETWORK, ASSOCIATED DEVICES AND CABLING ARE NOT IN SCOPE. ALL MEDICAL WIFI NETWORK DEVICES, CABLING AND EQUIPMENT ARE COVERED UNDER THE NATIONAL WIFI CONTRACT. EXISTING MEDICAL WIFI WAP DEVICE TO REMAIN AS INSTALLED. REMOVE EXISTING VA AND GUEST WIFI CABLING BACK TO SOURCE.
PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE DOWNTIME. PROVIDE
ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 10 WAP DEVICES FOR AREA SHOWN ON THIS
DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND LOCATIONS OF WAP DEVICES PRIOR TO
COMMENCEMENT OF WORK.
DISCONNECT EXISTING SSTV CAMERAS. EXISTING CAMERA TO REMAIN AS INSTALLED. REMOVE EXISTING
CABLING BACK TO SOURCE. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL.
CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW
CABLING TO MINIMIZE DOWNTIME. PROVIDE ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 14 CAMERAS FOR AREA SHOWN ON THIS DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND
LOCATIONS OF CAMERAS PRIOR TO COMMENCEMENT OF WORK.
DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH
PANEL. EXISTING FLOOR BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION. CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE. PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE
DOWNTIME.
PROVIDE PATCH CABLES FROM EXISTING NOT IN CONTRACT EQUIPMENT TO NEW HORIZONTAL
DISTRIBUTION EQUIPMENT LOCATED IN ROOM B207. REFER TO 6/TD403 FOR ADDITIONAL INFORMATION.
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
Revisions Date
EX
B207
CORRIDOR
C2-8
TOILET
B211A
RECEPTION
B211B
EQUIPMENT
STORAGE
B212B
WAITING
B211
OFFICE #1
B213
OFFICE #2
B214
OFFICE #4
B215
TREATMENT
#3
B212C
COPY ROOM
B212A
TREATMENT /
EMG
B212D
TREATMENT
B216
TREATMENT
B215A
BATH
B212E
TREATMENT
B216AHAND
THERAPY
B217D
EXERCISE
AREA
B217
BREAKROOM
B217C
STORAGE
B217B
F.E.C.
B218
CORRIDOR
B212
STORAGE
ALCOVE
B213A
OFFICE -
CARDIOPULMONARY
EEG
SUPERVISOR
A281
RECEPTION
AREA -
CARDIOPULMONARY
A282
TOILET
B200
H.A.C.
B202
LOCKERS
A285
EKG
A285A
EKG #2
B201
ECHO ROOM
B203
OFFICE -
HOME
OXYGEN
B205
PULMONARY
LAB
B206
STORAGE
B206A
ELEC
B208
F.E.C.
B209
OFFICE
B219C
TOILET
B219B
POLICE
TRAINING
B219
STORAGE
B219A
STAIR #4
S4.2
STAIR #5
S5.2
CORRIDOR
C2-9
MECHANICAL
SPACE
B205
EQUIPMENT
B217A
T-406
TD403
2D2D2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D 2D 2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D 1V
2D
2D 1V
2D 2D
2D
2D
2D
2D 1V
2D
2D
2D
2D
2D
2D2D
2D
2D 2D 2D
2D
2D
2D
2D
2D 2D
2D
2D 2D
2D
2D
2D 2D
1/ TN1.2.1
1/ TN1.2.1
1/ TN1.2.9
1/ TN1.2.4
1/ TN1.2.3
1/ TN1.2.3
1/ TN1.2.9
TYPICAL FOR ALL
NETWORK OUTLETS
2D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
L a k e
C it y V
A /0
V
A L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
M
E P
F P
T .r v t
/2 /2
:5
:0
A
M
TN1.2.2
BLDG 64 - LV 2 - ZONE 2 - NEW LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
64-B
STATION CHIEF - EDWIN BURNETT
10/25/2024 BMS CVM
100% CONSTRUCTION
DOCUMENTS
CHRISTOPHER VAN METER
RCDD Reg. No. 285002
NN
0 4' 8' 16' 24'
1/8" = 1'-0" 1/8" = 1'-0"1
SECOND FLOOR - B64-B(2) - NEW
CODED NOTES:
DRAWING NOTES:
1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE NEW IN SAME LOCATION. NUMBER OF PORTS INDICATED IS FOR NEW WORK. CONTRACTOR TO VERIFY EXACT LOCATION AND QUANTITIES OF DATA OUTLETS
PRIOR TO CONSTRUCTION. EXISTING DATA OUTLET LOCATIONS INDICATED ON THIS DRAWING
OBTAINED BY LIMITED SITE INVESTIGATION. CONTRACTOR TO DOCUMENT VARIANCES ON AS-BUILT
DRAWINGS.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING CONDITIONS FROM DAMAGE
DURING CONSTRUCTION. ANY MATERIALS, SYSTEMS, COMPONENTS, FINISHES, ETC. THAT ARE
DAMAGED DURING CONSTRUCTION MUST BE REPAIRED OR REPLACED AT CONTRACTORS EXPENSE
TO THE APPROVAL OF THE VA.
3. TELECOMMUNICATIONS OUTLET UPGRADE INCLUDES, BUT IS NOT LIMITED TO, REMOVAL OF EXISTING DEVICES AND ASSOCIATED NETWORK CABLING BACK TO PATCH PANEL, PROVIDING ALL MATERIALS, TOOLS, LABOR, TESTING INSTRUMENTS, ETC. REQUIRED FOR THE COMPLETE UPGRADE TO A FULLY FUNCTIONAL CATEGORY 6A, 8P8C PORT WITH THE PORT QUANTITY INDICATED FOR EACH OUTLET
LOCATION.
4. EXISTING POTS (ANALOG TELEPHONE) RJ11 PORTS AND ASSOCIATED CABLING IS NOT IN SCOPE.
EXISTING POTS PORTS LOCATED IN TELE/DATA OUTLETS RECEIVING TELECOMMUNICATIONS
UPGRADE SHALL BE REMOVED FROM OUTLET AND MAINTAINED FOR REINSTALLATION INTO NEW
OUTLET, UNLESS OTHERWISE NOTED.
5. PROVIDE ALL CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING OF FIBER OPTIC BACKBONE CABLING AND CAT6A HORIZONTAL CABLING. REFER TO CONDUIT FILL CHARTS ON SHEET T-001 FOR
ADDITIONAL INFORMATION.
6. INTERIOR FIRE WALL PENETRATIONS - CONTRACTOR SHALL PROVIDE APPROVED UL LISTED 4" SLEEVES AND FIRE RATED ASSEMBLY OR SYSTEM TO MAINTAIN FIRE RATING OF EXISTING FIRE
BARRIER. REFER TO CONDUIT FILL CHARTS FOR NUMBER OF SLEEVES REQUIRED.
7. NEW CAT6A CABLING SHALL BE ROUTED ABOVE ACCESSIBLE CEILINGS USING NEW AND EXISTING J- HOOK SYSTEMS. CONTRACTOR TO PROVIDE NEW 2" J-HOOKS AS REQUIRED FOR INSTALLATION OF NEW CAT6A CABLING. J-HOOK BASIS OF DESIGN IS NVENT CADDY CAT HP J-HOOK TREE. MAX CABLE FILL IS (35) CAT6A CABLES PER 2" J-HOOK (CABLE BASIS OF DESIGN - 0.35" NOMINAL OUTTER CABLE DIAMETER). CONTRACTOR SHALL PROVIDE CONDUIT FOR ROUTING OF NEW CAT6A CABLING ABOVE
HARD CEILINGS. REFER TO CABLE FILL CHARTS ON SHEET T-001 FOR CONDUIT FILL.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100FT INTERVALS FOR STRAIGHT CONDUIT RUNS, OR AT MAXIMUM CUMULATIVE OF 180 DEGREES OF CONDUIT BENDS.
9. DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING BUT NOT
LIMITED TO NURSE CALL, FIRE ALARM, SECURITY AND SSTV. DATA CABLING SHALL HAVE ITS OWN
RACEWAY WHEN ROUTED THROUGH CONDUIT.
10. SSTV CAMERAS, WAP DEVICES AND DATA OUTLETS ON THIS SHEET SHALL BE CONNECTED BACK TO
NEW PATCH PANELS IN TR B207.
DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH
PANEL. EXISTING BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION.
CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE.
PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE
DOWNTIME.
DISCONNECT EXISTING CEILING MOUNTED VA AND GUEST WIFI WAP DEVICES. MEDICAL WIFI NETWORK, ASSOCIATED DEVICES AND CABLING ARE NOT IN SCOPE. ALL MEDICAL WIFI NETWORK DEVICES, CABLING AND EQUIPMENT ARE COVERED UNDER THE NATIONAL WIFI CONTRACT. EXISTING MEDICAL WIFI WAP DEVICE TO REMAIN AS INSTALLED. REMOVE EXISTING VA AND GUEST WIFI CABLING BACK TO SOURCE.
PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE DOWNTIME. PROVIDE
ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 10 WAP DEVICES FOR AREA SHOWN ON THIS
DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND LOCATIONS OF WAP DEVICES PRIOR TO
COMMENCEMENT OF WORK.
DISCONNECT EXISTING SSTV CAMERAS. EXISTING CAMERA TO REMAIN AS INSTALLED. REMOVE EXISTING
CABLING BACK TO SOURCE. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL.
CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW
CABLING TO MINIMIZE DOWNTIME. PROVIDE ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 8 CAMERAS FOR AREA SHOWN ON THIS DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND
LOCATIONS OF CAMERAS PRIOR TO COMMENCEMENT OF WORK.
PROVIDE PATCH CABLES FROM EXISTING NOT IN CONTRACT EQUIPMENT TO NEW HORIZONTAL
DISTRIBUTION EQUIPMENT LOCATED IN ROOM B207. REFER TO 7/TD403 FOR ADDITIONAL INFORMATION.
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
Revisions Date
Q1RST
T-406
2D 2D
2D 2D
2D 2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D 2D
2D
1/ TN1.2.4
1/ TN1.2.1
2D
2D
2D
2D 2D
2D
TD403
AREA NOT IN SCOPE
AREA NOT IN SCOPE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
L a k e
C it y V
A /0
V
A L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
M
E P
F P
T .r v t
/2 /2
:5
:0
A
M
TN1.2.3
BLDG 64 - LV 2 - ZONE 3 - NEW LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
64-A
STATION CHIEF - EDWIN BURNETT
10/25/2024 BMS CVM
100% CONSTRUCTION
DOCUMENTS
CHRISTOPHER VAN METER
RCDD Reg. No. 285002
NN
0 4' 8' 16' 24'
1/8" = 1'-0" 1/8" = 1'-0"
SECOND FLOOR - B64-A(3) - NEW
CODED NOTES:
DRAWING NOTES:
1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE NEW IN SAME LOCATION. NUMBER OF PORTS INDICATED IS FOR NEW WORK. CONTRACTOR TO VERIFY EXACT LOCATION AND QUANTITIES OF DATA OUTLETS
PRIOR TO CONSTRUCTION. EXISTING DATA OUTLET LOCATIONS INDICATED ON THIS DRAWING
OBTAINED BY LIMITED SITE INVESTIGATION. CONTRACTOR TO DOCUMENT VARIANCES ON AS-BUILT
DRAWINGS.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING CONDITIONS FROM DAMAGE
DURING CONSTRUCTION. ANY MATERIALS, SYSTEMS, COMPONENTS, FINISHES, ETC. THAT ARE
DAMAGED DURING CONSTRUCTION MUST BE REPAIRED OR REPLACED AT CONTRACTORS EXPENSE
TO THE APPROVAL OF THE VA.
3. TELECOMMUNICATIONS OUTLET UPGRADE INCLUDES, BUT IS NOT LIMITED TO, REMOVAL OF EXISTING DEVICES AND ASSOCIATED NETWORK CABLING BACK TO PATCH PANEL, PROVIDING ALL MATERIALS, TOOLS, LABOR, TESTING INSTRUMENTS, ETC. REQUIRED FOR THE COMPLETE UPGRADE TO A FULLY FUNCTIONAL CATEGORY 6A, 8P8C PORT WITH THE PORT QUANTITY INDICATED FOR EACH OUTLET
LOCATION.
4. EXISTING POTS (ANALOG TELEPHONE) RJ11 PORTS AND ASSOCIATED CABLING IS NOT IN SCOPE.
EXISTING POTS PORTS LOCATED IN TELE/DATA OUTLETS RECEIVING TELECOMMUNICATIONS
UPGRADE SHALL BE REMOVED FROM OUTLET AND MAINTAINED FOR REINSTALLATION INTO NEW
OUTLET, UNLESS OTHERWISE NOTED.
5. PROVIDE ALL CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING OF FIBER OPTIC BACKBONE CABLING AND CAT6A HORIZONTAL CABLING. REFER TO CONDUIT FILL CHARTS ON SHEET T-001 FOR
ADDITIONAL INFORMATION.
6. INTERIOR FIRE WALL PENETRATIONS - CONTRACTOR SHALL PROVIDE APPROVED UL LISTED 4" SLEEVES AND FIRE RATED ASSEMBLY OR SYSTEM TO MAINTAIN FIRE RATING OF EXISTING FIRE
BARRIER. REFER TO CONDUIT FILL CHARTS FOR NUMBER OF SLEEVES REQUIRED.
7. NEW CAT6A CABLING SHALL BE ROUTED ABOVE ACCESSIBLE CEILINGS USING NEW AND EXISTING J- HOOK SYSTEMS. CONTRACTOR TO PROVIDE NEW 2" J-HOOKS AS REQUIRED FOR INSTALLATION OF NEW CAT6A CABLING. J-HOOK BASIS OF DESIGN IS NVENT CADDY CAT HP J-HOOK TREE. MAX CABLE FILL IS (35) CAT6A CABLES PER 2" J-HOOK (CABLE BASIS OF DESIGN - 0.35" NOMINAL OUTTER CABLE DIAMETER). CONTRACTOR SHALL PROVIDE CONDUIT FOR ROUTING OF NEW CAT6A CABLING ABOVE
HARD CEILINGS. REFER TO CABLE FILL CHARTS ON SHEET T-001 FOR CONDUIT FILL.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100FT INTERVALS FOR STRAIGHT CONDUIT RUNS, OR AT MAXIMUM CUMULATIVE OF 180 DEGREES OF CONDUIT BENDS.
9. DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING BUT NOT
LIMITED TO NURSE CALL, FIRE ALARM, SECURITY AND SSTV. DATA CABLING SHALL HAVE ITS OWN
RACEWAY WHEN ROUTED THROUGH CONDUIT.
10. SSTV CAMERAS, WAP DEVICES AND DATA OUTLETS ON THIS SHEET SHALL BE CONNECTED BACK TO
NEW PATCH PANELS IN TR 201.
DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH
PANEL. EXISTING BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION.
CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE.
PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE
DOWNTIME.
DISCONNECT EXISTING SSTV CAMERAS. EXISTING CAMERA TO REMAIN AS INSTALLED. REMOVE EXISTING
CABLING BACK TO SOURCE. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL.
CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW
CABLING TO MINIMIZE DOWNTIME. PROVIDE ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 2 CAMERAS FOR AREA SHOWN ON THIS DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND
LOCATIONS OF CAMERAS PRIOR TO COMMENCEMENT OF WORK.
DISCONNECT EXISTING CEILING MOUNTED VA AND GUEST WIFI WAP DEVICES. MEDICAL WIFI NETWORK, ASSOCIATED DEVICES AND CABLING ARE NOT IN SCOPE. ALL MEDICAL WIFI NETWORK DEVICES, CABLING AND EQUIPMENT ARE COVERED UNDER THE NATIONAL WIFI CONTRACT. EXISTING MEDICAL WIFI WAP DEVICE TO REMAIN AS INSTALLED. REMOVE EXISTING VA AND GUEST WIFI CABLING BACK TO SOURCE.
PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE DOWNTIME. PROVIDE
ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 10 WAP DEVICES FOR AREA SHOWN ON THIS
DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND LOCATIONS OF WAP DEVICES PRIOR TO
COMMENCEMENT OF WORK.
TYPICAL FOR ALL
NETWORK OUTLETS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
RECORDS
OFFICE-
PROSTHETICS
A280
2D
2D2D
2D
2D
2D2D
2D 2D
2D
2D 2D
2D
2D
2D
2D
1/ TN1.2.3
1/ TN1.2.2
1/ TN1.2.2
1/ TN1.2.5
TYPICAL FOR ALL
NETWORK OUTLETS
2D
2D
2D 2D
2D 2D
2D 2D
2D
2 3
2D
2D 2D
2D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
L a k e
C it y V
A /0
V
A L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
M
E P
F P
T .r v t
/2 /2
:5
:1
A
M
TN1.2.4
BLDG 64 - LV 2 - ZONE 4 - NEW LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
64-A
STATION CHIEF - EDWIN BURNETT
10/25/2024 BMS CVM
100% CONSTRUCTION
DOCUMENTS
CHRISTOPHER VAN METER
RCDD Reg. No. 285002
NN
0 4' 8' 16' 24'
1/8" = 1'-0"
1/8" = 1'-0"
SECOND FLOOR - B64-A(4) - NEW
CODED NOTES:
DRAWING NOTES:
1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE NEW IN SAME LOCATION. NUMBER OF PORTS INDICATED IS FOR NEW WORK. CONTRACTOR TO VERIFY EXACT LOCATION AND QUANTITIES OF DATA OUTLETS
PRIOR TO CONSTRUCTION. EXISTING DATA OUTLET LOCATIONS INDICATED ON THIS DRAWING
OBTAINED BY LIMITED SITE INVESTIGATION. CONTRACTOR TO DOCUMENT VARIANCES ON AS-BUILT
DRAWINGS.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING CONDITIONS FROM DAMAGE
DURING CONSTRUCTION. ANY MATERIALS, SYSTEMS, COMPONENTS, FINISHES, ETC. THAT ARE
DAMAGED DURING CONSTRUCTION MUST BE REPAIRED OR REPLACED AT CONTRACTORS EXPENSE
TO THE APPROVAL OF THE VA.
3. TELECOMMUNICATIONS OUTLET UPGRADE INCLUDES, BUT IS NOT LIMITED TO, REMOVAL OF EXISTING DEVICES AND ASSOCIATED NETWORK CABLING BACK TO PATCH PANEL, PROVIDING ALL MATERIALS, TOOLS, LABOR, TESTING INSTRUMENTS, ETC. REQUIRED FOR THE COMPLETE UPGRADE TO A FULLY FUNCTIONAL CATEGORY 6A, 8P8C PORT WITH THE PORT QUANTITY INDICATED FOR EACH OUTLET
LOCATION.
4. EXISTING POTS (ANALOG TELEPHONE) RJ11 PORTS AND ASSOCIATED CABLING IS NOT IN SCOPE.
EXISTING POTS PORTS LOCATED IN TELE/DATA OUTLETS RECEIVING TELECOMMUNICATIONS
UPGRADE SHALL BE REMOVED FROM OUTLET AND MAINTAINED FOR REINSTALLATION INTO NEW
OUTLET, UNLESS OTHERWISE NOTED.
5. PROVIDE ALL CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING OF FIBER OPTIC BACKBONE CABLING AND CAT6A HORIZONTAL CABLING. REFER TO CONDUIT FILL CHARTS ON SHEET T-001 FOR
ADDITIONAL INFORMATION.
6. INTERIOR FIRE WALL PENETRATIONS - CONTRACTOR SHALL PROVIDE APPROVED UL LISTED 4" SLEEVES AND FIRE RATED ASSEMBLY OR SYSTEM TO MAINTAIN FIRE RATING OF EXISTING FIRE
BARRIER. REFER TO CONDUIT FILL CHARTS FOR NUMBER OF SLEEVES REQUIRED.
7. NEW CAT6A CABLING SHALL BE ROUTED ABOVE ACCESSIBLE CEILINGS USING NEW AND EXISTING J- HOOK SYSTEMS. CONTRACTOR TO PROVIDE NEW 2" J-HOOKS AS REQUIRED FOR INSTALLATION OF NEW CAT6A CABLING. J-HOOK BASIS OF DESIGN IS NVENT CADDY CAT HP J-HOOK TREE. MAX CABLE FILL IS (35) CAT6A CABLES PER 2" J-HOOK (CABLE BASIS OF DESIGN - 0.35" NOMINAL OUTTER CABLE DIAMETER). CONTRACTOR SHALL PROVIDE CONDUIT FOR ROUTING OF NEW CAT6A CABLING ABOVE
HARD CEILINGS. REFER TO CABLE FILL CHARTS ON SHEET T-001 FOR CONDUIT FILL.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100FT INTERVALS FOR STRAIGHT CONDUIT RUNS, OR AT MAXIMUM CUMULATIVE OF 180 DEGREES OF CONDUIT BENDS.
9. DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING BUT NOT
LIMITED TO NURSE CALL, FIRE ALARM, SECURITY AND SSTV. DATA CABLING SHALL HAVE ITS OWN
RACEWAY WHEN ROUTED THROUGH CONDUIT.
10. WAP DEVICES AND DATA OUTLETS ON THIS SHEET SHALL BE CONNECTED BACK TO NEW PATCH
PANELS IN TR 201.
DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH
PANEL. EXISTING BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION.
CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE.
PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE
DOWNTIME.
DISCONNECT EXISTING SSTV CAMERAS. EXISTING CAMERA TO REMAIN AS INSTALLED. REMOVE EXISTING
CABLING BACK TO SOURCE. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL.
CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW
CABLING TO MINIMIZE DOWNTIME. PROVIDE ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 2 CAMERAS FOR AREA SHOWN ON THIS DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND
LOCATIONS OF CAMERAS PRIOR TO COMMENCEMENT OF WORK.
DISCONNECT EXISTING CEILING MOUNTED VA AND GUEST WIFI WAP DEVICES. MEDICAL WIFI NETWORK, ASSOCIATED DEVICES AND CABLING ARE NOT IN SCOPE. ALL MEDICAL WIFI NETWORK DEVICES, CABLING AND EQUIPMENT ARE COVERED UNDER THE NATIONAL WIFI CONTRACT. EXISTING MEDICAL WIFI WAP DEVICE TO REMAIN AS INSTALLED. REMOVE EXISTING VA AND GUEST WIFI CABLING BACK TO SOURCE.
PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE DOWNTIME. PROVIDE
ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 5 WAP DEVICES FOR AREA SHOWN ON THIS
DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND LOCATIONS OF WAP DEVICES PRIOR TO
COMMENCEMENT OF WORK.
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523 Revisions Date
EXB38 [5]
B64-A[4] B64-2[1]B64-A[4]
TELECOM RM
OFFICE
OFFICE
WOMENS
TOILET
TOILET
218E
ICE MACHINE
218D
MED ROOM
ELECTRICAL
ROOM
RN, SUICIDE
PREVENTION
STAIR 2 (38)
S201
ELEV.
P-2
ELEV. LOBBY
C2-3
H.A.C.
MENS TOILET
SOCIAL
WORKER
CONFERENCE
ROOM
CORRIDOR
C2-4
GNP,
DIRECTOR
STAFF
ASSISTANT
OFFICE
TRAINING
SPECIALIST
EDUCATION
PROGRAM
SPECIALIST
WAITING
OFFICE
218A
RECEPTION
218B
WORKROOM /
OFFICE
218C
CLINICAL
PHARMACIST
OFFICE
CORRIDOR
C2-5
SUNSHINE
TRAINING
CENTER
SOCIAL WORK
SOCIAL WORK
CORRIDOR
C2-6
ELEV.
P-1
SUPERVISOR
STAFF
PSYCHIATRIST
H.A.C.
OFFICE
OFFICE
ARNP SECIAL
PROJECTS
MANAGER
CONFERENCE
ROOM
STAIR 1
S203
EQUIPMENT
STAFF ARNP
STAFF ARNP
OFFICE
STAFF
LOUNGE
CORRIDOR
C2-2
COPY ROOM
STAFF
PSYCHIATRIST
SECRETARY
METABOLIC
RN
STAIR 2
S202
FIRE
SUPPRESSION
BATH
238A
STORAGE
OFFICE
ELEVATOR
LOBBY
C2-1
T-406
TD403
2D2D 2D
2D
2D 1V
2D 1V
2D
2D
2D
2D 1V
2D
2D
2D
2D
2D
2D
2D 2D
2D
2D
2D
2D 1V2D
1V 2D 1V
2D
2D 1V
2D 1V
2D 1V
2D 1V
2D 1V
2D
2D
2D
2D
2D 2D
1/ TN1.2.4 1/ TN1.2.4
TYPICAL FOR ALL
NETWORK OUTLETS
2D
2D
2D
2D
2D
2D
CH CH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
L a k e
C it y V
A /0
V
A L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
M
E P
F P
T .r v t
/2 /2
:5
:2
A
M
TN1.2.5
BLDG 38 - LV 2 - ZONE 5 NEW LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 BMS CVM
100% CONSTRUCTION
DOCUMENTS
CHRISTOPHER VAN METER
RCDD Reg. No. 285002
NN
0 4' 8' 16' 24'
1/8" = 1'-0"
1/8" = 1'-0"1
SECOND FLOOR - B38(5) - NEW
CODED NOTES:
DRAWING NOTES:
1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE NEW IN SAME LOCATION. NUMBER OF PORTS INDICATED IS FOR NEW WORK. CONTRACTOR TO VERIFY EXACT LOCATION AND QUANTITIES OF DATA OUTLETS
PRIOR TO CONSTRUCTION. EXISTING DATA OUTLET LOCATIONS INDICATED ON THIS DRAWING
OBTAINED BY LIMITED SITE INVESTIGATION. CONTRACTOR TO DOCUMENT VARIANCES ON AS-BUILT
DRAWINGS.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING CONDITIONS FROM DAMAGE
DURING CONSTRUCTION. ANY MATERIALS, SYSTEMS, COMPONENTS, FINISHES, ETC. THAT ARE
DAMAGED DURING CONSTRUCTION MUST BE REPAIRED OR REPLACED AT CONTRACTORS EXPENSE
TO THE APPROVAL OF THE VA.
3. TELECOMMUNICATIONS OUTLET UPGRADE INCLUDES, BUT IS NOT LIMITED TO, REMOVAL OF EXISTING DEVICES AND ASSOCIATED NETWORK CABLING BACK TO PATCH PANEL, PROVIDING ALL MATERIALS, TOOLS, LABOR, TESTING INSTRUMENTS, ETC. REQUIRED FOR THE COMPLETE UPGRADE TO A FULLY FUNCTIONAL CATEGORY 6A, 8P8C PORT WITH THE PORT QUANTITY INDICATED FOR EACH OUTLET
LOCATION.
4. EXISTING POTS (ANALOG TELEPHONE) RJ11 PORTS AND ASSOCIATED CABLING IS NOT IN SCOPE.
EXISTING POTS PORTS LOCATED IN TELE/DATA OUTLETS RECEIVING TELECOMMUNICATIONS
UPGRADE SHALL BE REMOVED FROM OUTLET AND MAINTAINED FOR REINSTALLATION INTO NEW
OUTLET, UNLESS OTHERWISE NOTED.
5. PROVIDE ALL CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING OF FIBER OPTIC BACKBONE CABLING AND CAT6A HORIZONTAL CABLING. REFER TO CONDUIT FILL CHARTS ON SHEET T-001 FOR
ADDITIONAL INFORMATION.
6. INTERIOR FIRE WALL PENETRATIONS - CONTRACTOR SHALL PROVIDE APPROVED UL LISTED 4" SLEEVES AND FIRE RATED ASSEMBLY OR SYSTEM TO MAINTAIN FIRE RATING OF EXISTING FIRE
BARRIER. REFER TO CONDUIT FILL CHARTS FOR NUMBER OF SLEEVES REQUIRED.
7. NEW CAT6A CABLING SHALL BE ROUTED ABOVE ACCESSIBLE CEILINGS USING NEW AND EXISTING J- HOOK SYSTEMS. CONTRACTOR TO PROVIDE NEW 2" J-HOOKS AS REQUIRED FOR INSTALLATION OF NEW CAT6A CABLING. J-HOOK BASIS OF DESIGN IS NVENT CADDY CAT HP J-HOOK TREE. MAX CABLE FILL IS (35) CAT6A CABLES PER 2" J-HOOK (CABLE BASIS OF DESIGN - 0.35" NOMINAL OUTTER CABLE DIAMETER). CONTRACTOR SHALL PROVIDE CONDUIT FOR ROUTING OF NEW CAT6A CABLING ABOVE
HARD CEILINGS. REFER TO CABLE FILL CHARTS ON SHEET T-001 FOR CONDUIT FILL.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100FT INTERVALS FOR STRAIGHT CONDUIT RUNS, OR AT MAXIMUM CUMULATIVE OF 180 DEGREES OF CONDUIT BENDS.
9. DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING BUT NOT
LIMITED TO NURSE CALL, FIRE ALARM, SECURITY AND SSTV. DATA CABLING SHALL HAVE ITS OWN
RACEWAY WHEN ROUTED THROUGH CONDUIT.
10. SSTV CAMERAS, WAP DEVICES AND DATA OUTLETS ON THIS SHEET SHALL BE CONNECTED BACK TO
NEW PATCH PANELS IN TR 216.
DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH
PANEL. EXISTING BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION.
CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE.
PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE
DOWNTIME.
DISCONNECT EXISTING CEILING MOUNTED VA AND GUEST WIFI WAP DEVICES. MEDICAL WIFI NETWORK, ASSOCIATED DEVICES AND CABLING ARE NOT IN SCOPE. ALL MEDICAL WIFI NETWORK DEVICES, CABLING AND EQUIPMENT ARE COVERED UNDER THE NATIONAL WIFI CONTRACT. EXISTING MEDICAL WIFI WAP DEVICE TO REMAIN AS INSTALLED. REMOVE EXISTING VA AND GUEST WIFI CABLING BACK TO SOURCE.
PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE DOWNTIME. PROVIDE
ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 10 WAP DEVICES FOR AREA SHOWN ON THIS
DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND LOCATIONS OF WAP DEVICES PRIOR TO
COMMENCEMENT OF WORK.
DISCONNECT EXISTING SSTV CAMERAS. EXISTING CAMERA TO REMAIN AS INSTALLED. REMOVE EXISTING
CABLING BACK TO SOURCE. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL.
CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW
CABLING TO MINIMIZE DOWNTIME. PROVIDE ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 4 CAMERAS FOR AREA SHOWN ON THIS DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND
LOCATIONS OF CAMERAS PRIOR TO COMMENCEMENT OF WORK.
PROVIDE PATCH CABLES FROM EXISTING NOT IN CONTRACT EQUIPMENT TO NEW HORIZONTAL
DISTRIBUTION EQUIPMENT LOCATED IN ROOM 216. REFER TO 8/TD403 FOR ADDITIONAL INFORMATION.
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
Revisions Date
EQUIPMENT
STAIRS
S3-1A
EQUIPMENT
341B
PATIENT
TOILET
341C
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
H.A.C.
PATIENT
BATROOM
332A
PATIENT
TOILET
333A
CLEAN LINEN
SPD
PATIENT
TOILET
337A
PATIENT
TOILET
339A
ALCOVE
341C
ALCOVE
340A
ALCOVE
339B
ALCOVE
338A
ALCOVE
337B
ALCOVE
C3-17
ALCOVE
336A
ALCOVE
333B
ALCOVE
332B
ALCOVE
C3-16
PATIENT
TOILET
348A
PATIENT
TOILET
346A
PATIENT
TOILET
344A
STORAGE
PATIENT
TOILET
343A
PATIENT
TOILET
371A
PATIENT
TOILET
373A
PATIENT
TOILET
364A
PATIENT
TOILET
366A
PATIENT
TOILET
368A
STORAGE
OXYGEN RM
333W
CLEAN LINEN
361PATIENT
TOILET
375A
STORAGE
370C
PAT.
BATHROOM
359A
H.A.C.
DATA
ELECT.
ELECT.
CLEAN
UTILITY
CORRIDOR
C3-11
QUIET RM.
TOILET
TRASH ROOM
STORAGE
324A
MED.
STORAGE
SHOWERS
SOILED
UTILITY
NOURISHMENT
HEAD NURSE
WARD
STORAGE
SOILED LINEN
PAT. TOILET
377A
EQUIPMENT
STORAGE
RESIDENTIAL
LAUNDRY
PATIENT
TOILET
370A
PATIENT
TOILET
360A
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
CONG. TOILET
CONG. BATH
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
TREATMENT
CORRIDOR
C3-9
ALCOVE
343B
ALCOVE
344B
ALCOVE
345A
ALCOVE
346B
ALCOVE
347A
ALCOVE
348B
ALCOVE
349A
CORRIDOR
ALCOVE
C3-8
ALCOVE
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
PATIENT
BEDROOM
ALCOVE
368B
ALCOVE
367A
ALCOVE
366B
ALCOVE
365A
ALCOVE
364B
ALCOVE
C3-21
ALCOVE
C3-20
CORRIDOR
C3-19
PATIENT
BEDROOM
ALCOVE
377B
ALCOVE
376A
ALCOVE
375B
ALCOVE
374A
ALCOVE
373B
ALCOVE
372A
ALCOVE
371B
ALCOVE
370B
ALCOVE
C3-22
CORRIDOR
C3-10
CORRIDOR
C3-6
NURSES
STATION
C3-6
TD404
2D 1V
2D
2D 1V 2D
1V 2D 1V
2D 1V
2D
2D 1V
2D 2V
2D
2D
2D
2D
2D 2V
2D
2D 2V 2D
2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V 2D
2V
2D 2V 2D
2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
2D 2V
1/ TN1.2.9
1/ TN1.2.9
TYPICAL FOR ALL
NETWORK OUTLETS
2D 2V
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
L a k e
C it y V
A /0
V
A L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
M
E P
F P
T .r v t
/2 /2
:5
:2
A
M
TN1.2.8
BLDG 82 - LV 2 - ZONE 8 - NEW LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 BMS CVM
100% CONSTRUCTION
DOCUMENTS
CHRISTOPHER VAN METER
RCDD Reg. No. 285002
NN
0 4' 8' 16' 24'
1/8" = 1'-0"1/8" = 1'-0"1
SECOND FLOOR - B82(8) - NEW
CODED NOTES:
DRAWING NOTES:
1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE NEW IN SAME LOCATION. NUMBER OF PORTS INDICATED IS FOR NEW WORK. CONTRACTOR TO VERIFY EXACT LOCATION AND QUANTITIES OF DATA OUTLETS
PRIOR TO CONSTRUCTION. EXISTING DATA OUTLET LOCATIONS INDICATED ON THIS DRAWING
OBTAINED BY LIMITED SITE INVESTIGATION. CONTRACTOR TO DOCUMENT VARIANCES ON AS-BUILT
DRAWINGS.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING CONDITIONS FROM DAMAGE
DURING CONSTRUCTION. ANY MATERIALS, SYSTEMS, COMPONENTS, FINISHES, ETC. THAT ARE
DAMAGED DURING CONSTRUCTION MUST BE REPAIRED OR REPLACED AT CONTRACTORS EXPENSE
TO THE APPROVAL OF THE VA.
3. TELECOMMUNICATIONS OUTLET UPGRADE INCLUDES, BUT IS NOT LIMITED TO, REMOVAL OF EXISTING DEVICES AND ASSOCIATED NETWORK CABLING BACK TO PATCH PANEL, PROVIDING ALL MATERIALS, TOOLS, LABOR, TESTING INSTRUMENTS, ETC. REQUIRED FOR THE COMPLETE UPGRADE TO A FULLY FUNCTIONAL CATEGORY 6A, 8P8C PORT WITH THE PORT QUANTITY INDICATED FOR EACH OUTLET
LOCATION.
4. EXISTING POTS (ANALOG TELEPHONE) RJ11 PORTS AND ASSOCIATED CABLING IS NOT IN SCOPE.
EXISTING POTS PORTS LOCATED IN TELE/DATA OUTLETS RECEIVING TELECOMMUNICATIONS
UPGRADE SHALL BE REMOVED FROM OUTLET AND MAINTAINED FOR REINSTALLATION INTO NEW
OUTLET, UNLESS OTHERWISE NOTED.
5. PROVIDE ALL CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING OF FIBER OPTIC BACKBONE CABLING AND CAT6A HORIZONTAL CABLING. REFER TO CONDUIT FILL CHARTS ON SHEET T-001 FOR
ADDITIONAL INFORMATION.
6. INTERIOR FIRE WALL PENETRATIONS - CONTRACTOR SHALL PROVIDE APPROVED UL LISTED 4" SLEEVES AND FIRE RATED ASSEMBLY OR SYSTEM TO MAINTAIN FIRE RATING OF EXISTING FIRE
BARRIER. REFER TO CONDUIT FILL CHARTS FOR NUMBER OF SLEEVES REQUIRED.
7. NEW CAT6A CABLING SHALL BE ROUTED ABOVE ACCESSIBLE CEILINGS USING NEW AND EXISTING J- HOOK SYSTEMS. CONTRACTOR TO PROVIDE NEW 2" J-HOOKS AS REQUIRED FOR INSTALLATION OF NEW CAT6A CABLING. J-HOOK BASIS OF DESIGN IS NVENT CADDY CAT HP J-HOOK TREE. MAX CABLE FILL IS (35) CAT6A CABLES PER 2" J-HOOK (CABLE BASIS OF DESIGN - 0.35" NOMINAL OUTTER CABLE DIAMETER). CONTRACTOR SHALL PROVIDE CONDUIT FOR ROUTING OF NEW CAT6A CABLING ABOVE
HARD CEILINGS. REFER TO CABLE FILL CHARTS ON SHEET T-001 FOR CONDUIT FILL.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100FT INTERVALS FOR STRAIGHT CONDUIT RUNS, OR AT MAXIMUM CUMULATIVE OF 180 DEGREES OF CONDUIT BENDS.
9. DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING BUT NOT
LIMITED TO NURSE CALL, FIRE ALARM, SECURITY AND SSTV. DATA CABLING SHALL HAVE ITS OWN
RACEWAY WHEN ROUTED THROUGH CONDUIT.
10. SSTV CAMERAS, WAP DEVICES AND DATA OUTLETS ON THIS SHEET SHALL BE CONNECTED BACK TO
NEW PATCH PANELS IN TR 317.
DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH
PANEL. EXISTING BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION.
CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE.
PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE
DOWNTIME.
DISCONNECT EXISTING CEILING MOUNTED VA AND GUEST WIFI WAP DEVICES. MEDICAL WIFI NETWORK, ASSOCIATED DEVICES AND CABLING ARE NOT IN SCOPE. ALL MEDICAL WIFI NETWORK DEVICES, CABLING AND EQUIPMENT ARE COVERED UNDER THE NATIONAL WIFI CONTRACT. EXISTING MEDICAL WIFI WAP DEVICE TO REMAIN AS INSTALLED. REMOVE EXISTING VA AND GUEST WIFI CABLING BACK TO SOURCE.
PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE DOWNTIME. PROVIDE
ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 10 WAP DEVICES FOR AREA SHOWN ON THIS
DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND LOCATIONS OF WAP DEVICES PRIOR TO
COMMENCEMENT OF WORK.
DISCONNECT EXISTING SSTV CAMERAS. EXISTING CAMERA TO REMAIN AS INSTALLED. REMOVE EXISTING
CABLING BACK TO SOURCE. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL.
CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW
CABLING TO MINIMIZE DOWNTIME. PROVIDE ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 7 CAMERAS FOR AREA SHOWN ON THIS DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND
LOCATIONS OF CAMERAS PRIOR TO COMMENCEMENT OF WORK.
PROVIDE PATCH CABLES FROM EXISTING NOT IN CONTRACT EQUIPMENT TO NEW HORIZONTAL
DISTRIBUTION EQUIPMENT LOCATED IN ROOM 317. REFER TO 1/TD404 FOR ADDITIONAL INFORMATION.
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
Revisions Date
ELEVATOR
P-1/82
ELEVATOR
P-2/82
ELEVATOR
P-3/82
ELEVATOR
P-4/82
H.A.C.
OFFICE
MENS TOILET
WOMENS
TOILET
ELEC
LOUNGE
WOMENS
TOILET
MENS TOILET
STORAGE
LOCKERS
LOCKERS
STAIR 3
S3-3A
PORCH
DINING /
RECREATION
BATTERY RM
LOBBY
C3-1
CORRIDOR
C3-5
CORRIDOR
CORRIDOR
C3-3
CORRIDOR
C3-14
GEN.STORAGE
MECHANICAL
ALCOVE
C3-16
T-406
2D
2D
2D
2D
1/ TN1.2.8
1/ TN1.2.8
1/ TN1.2.2
1/ TN1.2.2
1TYPICAL FOR ALL
NETWORK OUTLETS
2D
2 3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
L a k e
C it y V
A /0
V
A L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
M
E P
F P
T .r v t
/2 /2
:5
:3
A
M
TN1.2.9
BLDG 82 - LV 2 - ZONE 9 - NEW LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 BMS CVM
100% CONSTRUCTION
DOCUMENTS
CHRISTOPHER VAN METER
RCDD Reg. No. 285002
NN
0 4' 8' 16' 24'
1/8" = 1'-0" 1/8" = 1'-0"
SECOND FLOOR - B82(9) - NEW
CODED NOTES:
DRAWING NOTES:
1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE NEW IN SAME LOCATION. NUMBER OF PORTS INDICATED IS FOR NEW WORK. CONTRACTOR TO VERIFY EXACT LOCATION AND QUANTITIES OF DATA OUTLETS
PRIOR TO CONSTRUCTION. EXISTING DATA OUTLET LOCATIONS INDICATED ON THIS DRAWING
OBTAINED BY LIMITED SITE INVESTIGATION. CONTRACTOR TO DOCUMENT VARIANCES ON AS-BUILT
DRAWINGS.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL EXISTING CONDITIONS FROM DAMAGE
DURING CONSTRUCTION. ANY MATERIALS, SYSTEMS, COMPONENTS, FINISHES, ETC. THAT ARE
DAMAGED DURING CONSTRUCTION MUST BE REPAIRED OR REPLACED AT CONTRACTORS EXPENSE
TO THE APPROVAL OF THE VA.
3. TELECOMMUNICATIONS OUTLET UPGRADE INCLUDES, BUT IS NOT LIMITED TO, REMOVAL OF EXISTING DEVICES AND ASSOCIATED NETWORK CABLING BACK TO PATCH PANEL, PROVIDING ALL MATERIALS, TOOLS, LABOR, TESTING INSTRUMENTS, ETC. REQUIRED FOR THE COMPLETE UPGRADE TO A FULLY FUNCTIONAL CATEGORY 6A, 8P8C PORT WITH THE PORT QUANTITY INDICATED FOR EACH OUTLET
LOCATION.
4. EXISTING POTS (ANALOG TELEPHONE) RJ11 PORTS AND ASSOCIATED CABLING IS NOT IN SCOPE.
EXISTING POTS PORTS LOCATED IN TELE/DATA OUTLETS RECEIVING TELECOMMUNICATIONS
UPGRADE SHALL BE REMOVED FROM OUTLET AND MAINTAINED FOR REINSTALLATION INTO NEW
OUTLET, UNLESS OTHERWISE NOTED.
5. PROVIDE ALL CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING OF FIBER OPTIC BACKBONE CABLING AND CAT6A HORIZONTAL CABLING. REFER TO CONDUIT FILL CHARTS ON SHEET T-001 FOR
ADDITIONAL INFORMATION.
6. INTERIOR FIRE WALL PENETRATIONS - CONTRACTOR SHALL PROVIDE APPROVED UL LISTED 4" SLEEVES AND FIRE RATED ASSEMBLY OR SYSTEM TO MAINTAIN FIRE RATING OF EXISTING FIRE
BARRIER. REFER TO CONDUIT FILL CHARTS FOR NUMBER OF SLEEVES REQUIRED.
7. NEW CAT6A CABLING SHALL BE ROUTED ABOVE ACCESSIBLE CEILINGS USING NEW AND EXISTING J- HOOK SYSTEMS. CONTRACTOR TO PROVIDE NEW 2" J-HOOKS AS REQUIRED FOR INSTALLATION OF NEW CAT6A CABLING. J-HOOK BASIS OF DESIGN IS NVENT CADDY CAT HP J-HOOK TREE. MAX CABLE FILL IS (35) CAT6A CABLES PER 2" J-HOOK (CABLE BASIS OF DESIGN - 0.35" NOMINAL OUTTER CABLE DIAMETER). CONTRACTOR SHALL PROVIDE CONDUIT FOR ROUTING OF NEW CAT6A CABLING ABOVE
HARD CEILINGS. REFER TO CABLE FILL CHARTS ON SHEET T-001 FOR CONDUIT FILL.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100FT INTERVALS FOR STRAIGHT CONDUIT RUNS, OR AT MAXIMUM CUMULATIVE OF 180 DEGREES OF CONDUIT BENDS.
9. DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS INCLUDING BUT NOT
LIMITED TO NURSE CALL, FIRE ALARM, SECURITY AND SSTV. DATA CABLING SHALL HAVE ITS OWN
RACEWAY WHEN ROUTED THROUGH CONDUIT.
10. SSTV CAMERAS, WAP DEVICES AND DATA OUTLETS ON THIS SHEET SHALL BE CONNECTED BACK TO
NEW PATCH PANELS IN TR 317.
DISCONNECT AND REMOVE DATA/TELECOMM OUTLET. REMOVE NETWORK CABLING BACK TO PATCH
PANEL. EXISTING BOX AND CONDUIT SHALL REMAIN FOR REUSE. EXISTING RJ-11 ANALOG TELEPHONE CABLE (IF PRESENT) IS TO REMAIN FOR REINSTALLATION INTO NEW OUTLET AT SAME LOCATION.
CONTRACTOR TO PROVIDE NEW RJ-11 PORT AS REQUIRED FOR INSTALLATION INTO NEW FACEPLATE.
PROVIDE NEW FACEPLATE, AND CAT6A DATA PORTS FOR NEW DATA/TELECOMM OUTLET AT EXISTING LOCATION. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE
DOWNTIME.
DISCONNECT EXISTING CEILING MOUNTED VA AND GUEST WIFI WAP DEVICES. MEDICAL WIFI NETWORK, ASSOCIATED DEVICES AND CABLING ARE NOT IN SCOPE. ALL MEDICAL WIFI NETWORK DEVICES, CABLING AND EQUIPMENT ARE COVERED UNDER THE NATIONAL WIFI CONTRACT. EXISTING MEDICAL WIFI WAP DEVICE TO REMAIN AS INSTALLED. REMOVE EXISTING VA AND GUEST WIFI CABLING BACK TO SOURCE.
PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL. CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW CABLING TO MINIMIZE DOWNTIME. PROVIDE
ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 10 WAP DEVICES FOR AREA SHOWN ON THIS
DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND LOCATIONS OF WAP DEVICES PRIOR TO
COMMENCEMENT OF WORK.
DISCONNECT EXISTING SSTV CAMERAS. EXISTING CAMERA TO REMAIN AS INSTALLED. REMOVE EXISTING
CABLING BACK TO SOURCE. PROVIDE NEW CAT6A CABLING FROM DESIGNATED PATCH PANEL.
CONTRACTOR SHALL COORDINATE REMOVAL OF EXISTING CABLING AND INSTALLATION OF NEW
CABLING TO MINIMIZE DOWNTIME. PROVIDE ALLOWANCE FOR NEW CABLING OF APPROXIMATELY 6 CAMERAS FOR AREA SHOWN ON THIS DRAWING. CONTRACTOR TO VERIFY EXACT QUANTITIES AND
LOCATIONS OF CAMERAS PRIOR TO COMMENCEMENT OF WORK.
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
X
DATA
NURSE
STATION
235C
TOILET
STORAGE
KITCHEN
DAV
216A
TD404
2D 2V
2D
2D
2D
2D
2D
2D
2D 1V
2D 1V
2D 1V
2D
2D
2D
2D 1V 2D
2/ TN1.2.12
TYPICAL FOR ALL
NETWORK OUTLETS
2D
2D
2D2D
NURSE
STATION
235C
TOILET
STORAGE
DAY ROOM
DINING ROOM
OT OFFICE
GROUP ROOM
RESIDENT
SUITE
TOILET
229A
SHOWER
229B
SHOWER
228B
TOILET
228A
RESIDENT
SUITE
OFFICE
MENS TOILET
SHOWER
226B
SHOWER
226A
OFFICE
H. A. C.
STRETCHER
ALCOVE
SHOWER
221A
TOILET
223A
RESIDENT
SUITE
RESIDENT
SUITE
RESIDENT
SUITE
TOILET
220A
SHOWER
220B
SOILED LINEN
KITCHEN
CORRIDOR
STAIR 3
239B
DAV
216A
TELECOM RM
227A T-407
2D 1V
2D 1V
2D 1V
2D 1V
2D
2D
2D2D 1V
2D 1V
2D
2D 2V
2D
2D 1V
2D
2D
2D
1/ TN1.2.121/ TN1.2.12
TYPICAL FOR ALL
NETWORK OUTLETS
2D 1V
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
L a k e
C it y V
A /0
V
A L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
M
E P
F P
T .r v t
/2 /2
:5
:4
A
M
TN1.2.12
BLDG 62 - LV 2 - ZONE 12 - NEW LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 BMS CVM
100% CONSTRUCTION
DOCUMENTS
CHRISTOPHER VAN METER
RCDD Reg. No. 285002
NN
0 4' 8' 16' 24'
1/8" = 1'-0"
1/8" = 1'-0"
SECOND FLOOR - B62(12a) - NEW 1/8" = 1'-0"
SECOND FLOOR - B62(12b) - NEW
CODED NOTES:
DRAWING NOTES:
1. DATA OUTLET LOCATIONS INDICATED ON THIS SHEET ARE APPROXIMATE LOCATIONS OF EXISTING OUTLETS. CONTRACTOR IS TO REMOVE EXISTING OUTLET IN ACCORDANCE WITH THE FOLLOWING GENERAL AND CODED NOTES, AND PROVIDE…
This is the start of the file's text. The full file is on GovTribe.