Attachment 3 - Final Drawing Set - 2 of 8.pdf
PDF 13 MB Posted
- Attached to
- Project 573A4-21-700 EHRM Infrastructure Upgrades construction project at the Lake City, FL VAMC
- Solicitation number
- 36C77625B0006
About this file
The provided document is a set of structural and fire protection engineering drawings for the Lake City VAMC EHRM Infrastructure Upgrades Design project. The drawing set includes detailed plans for multiple buildings (numbered 06, 18, 27, 37, 38, 42, 44, 62, 64, 66, 74, 82, 91, and 92) across basement, first, second, third, and fourth floor levels. The drawings provide comprehensive structural foundation plans, fire protection zoning layouts, and technical details for telecom rooms, mechanical spaces, and other critical infrastructure areas.
Key technical specifications include structural steel requirements (conforming to ASTM A500 Grade C and A36 standards), design codes (VA Design Manual, International Building Code 2021, ASCE 7-22), and specific design loads such as roof live load (20 PSF), wind design speed (133 MPH), and seismic design parameters. The fire protection plans outline new and demolition work for sprinkler systems, including detailed zoning for telecom rooms across different buildings and floors, with specific attention to installation requirements, device placements, and compliance with NFPA standards.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STEEL:
1. STRUCTURAL STEEL FOR TUBES SHALL CONFORM TO ASTM
SPECIFICATION A500 GRADE C. ALL OTHER STEEL SHALL CONFORM TO
ASTM SPECIFICATION A36. MILL TEST REPORTS SHALL BE SUBMITTED
TO THE ARCHITECT. ALL STEEL SHALL BE DETAILED, FABRICATED AND
ERECTED IN ACCORDANCE WITH THE AISC MANUAL, AISC
SPECIFICATION AND AISC CODE OF STANDARD PRACTICE. IN
GENERAL, FIELD CONNECTIONS SHALL BE MADE WITH 3/4" DIAMETER
A325 BOLTS UNLESS OTHERWISE NOTED AND SHOP CONNECTIONS
SHALL BE WELDED.
2. BOLTS, EXCEPT AS NOTED, NEED ONLY BE INSTALLED TO THE "SNUG
TIGHT" CONDITION AS DEFINED IN THE RCSC "SPECIFICATION FOR
STRUCTURAL JOINTS." BOLTS IN BEAM TO COLUMN CONNECTIONS
THAT HAVE SLOTTED HOLES SHALL BE FULLY PRE-TENSIONED IN
ACCORDANCE WITH THE "SPECIFICATION FOR STRUCTURAL JOINTS".
3. WELDS SHALL BE MADE WITH E70XX LOW HYDROGEN ELECTRODES.
4. ALL GROOVE WELDS SHALL BE FULL PENETRATION GROOVE WELDS IN
ACCORDANCE WITH ANSI/AWS D1.1, "STRUCTURAL WELDING CODE".
THESE WELDS SHALL BE MADE ONLY BY OPERATORS QUALIFIED BY
PRESCRIBED TESTS IN THE "STRUCTURAL WELDING CODE."
ACCEPTANCE SHALL BE SUBJECT TO THE INSPECTION AND REVIEW OF
AN INDEPENDENT INSPECTION AGENCY. ALL FULL PENETRATION
WELDS SHALL BE ULTRASONICALLY TESTED.
5. HOLES AND OPENINGS REQUIRED IN STRUCTURAL STEEL MEMBERS
FOR THE WORK OF OTHER TRADES SHALL BE SHOWN ON THE SHOP
DRAWINGS SUBMITTED FOR REVIEW.
6. FIELD MODIFICATION OF THE STRUCTURAL STEEL IS NOT ALLOWED
WITHOUT PRIOR REVIEW BY THE ARCHITECT AND STRUCTURAL
ENGINEER.
7. WELDING SEQUENCE AND TECHNIQUE SHALL BE SUCH THAT
DISTORTION OF STEEL MEMBERS IS MINIMIZED AND UNDUE
DISTORTION IS AVOIDED.
8. ALL STRUCTURAL STEEL SHALL BE SHOP PAINTED WITH A RUST
INHIBITIVE PRIMER. ALL EXPOSED STEEL AND LINTELS IN EXTERIOR
WALLS SHALL BE HOT-DIPPED GALVANIZED. REFER TO
ARCHITECTURAL DRAWINGS FOR GALVANIZED STEEL THAT SHALL
RECEIVE A PAINTED FINISH COAT.
GENERAL:
1. CONTRACTOR IS SOLELY RESPONSIBLE FOR MEANS AND METHODS
DURING THE COURSE OF THE WORK. DO NOT DAMAGE OR
ENDANGER THE STRUCTURAL INTEGRITY OF THE WORK.
2. LOADS GREATER THAN THE DESIGN LIVE LOADS SHALL NOT BE
PLACED ON THE STRUCTURE.
3. NOTIFY ENGINEER IN CASE OF DISCREPANCIES BETWEEN DRAWINGS,
THESE NOTES, AND PROJECT MANUAL BEFORE PROCEEDING WITH
THE WORK.
4. USE ARCHITECTURAL DRAWINGS AND DRAWINGS OF OTHER TRADES
IN CONJUNCTION WITH THE STRUCTURAL DRAWINGS TO PROPERLY
PERFORM THE WORK.
5. IF CONDITIONS DISCLOSED DURING EXCAVATION REVEAL
UNFORESEEN CONDITIONS, PROMPTLY REQUEST DIRECTION FROM
ENGINEER BEFORE PROCEEDING.
6. CONTRACTOR IS RESPONSIBLE FOR COORDINATING BETWEEN
TRADES.
7. DO NOT SCALE DRAWINGS.
8. FIELD DIMENSIONS: IF STRUCTURAL DRAWINGS ARE USED FOR
LAYING OUT COLUMN CENTERS AND WALL LINES, ALL DIMENSIONS
SHALL FIRST BE VERIFIED WITH THE ARCHITECTURAL DRAWINGS.
LAYOUT SHALL BE CHECKED BEFORE WORK IS BEGUN.
9. SECTIONS AND DETAILS SHOWN, WHILE DRAWN FOR SPECIFIC
LOCATIONS, ARE INTENDED TO ESTABLISH THE GENERAL TYPES OF
DETAILS WILL APPLY TO OTHER LOCATIONS.
10. THE ENGINEER'S REVIEW OF A SUBMITTAL SHALL NOT RELIEVE THE
CONTRACTOR OF THEIR RESPONSIBILITY TO FOLLOW THE INTENT OF
THE CONTRACT DRAWINGS.
11. REPRODUCTION OF CONTRACT DOCUMENTS WILL NOT BE ACCEPTED
AS SHOP DRAWINGS.
GENERAL NOTES
EXISTING CONSTRUCTION:
1. ABOVE GROUP, INC. HAS PREPARED THESE PLANS BASED ON A
LIMITED AMOUNT OF FIELD EXPLORATION AND ON THE STRUCTURAL
INFORMATION SHOWN ON EXISTING DRAWINGS. FOR BUILDING 66,
THE DRAWINGS ARE A2-A5, A7 & S1 PREPARED BY CLEMONS,
RUTHERFORD & ASSOCIATES, INC. DATED JULY 19, 1987 AND THE
EXISTING STRUCTURE IS A PRE-ENGINEERED METAL BUILDING (PEMB)
FOR WHICH SHOP DRAWINGS ARE NOT AVAILABLE. FOR BUILDING 91,
THE DRAWINGS ARE 6, S-1 DATED FEBRUARY 7, 1983. THE DRAWINGS
ARE THE EXISTING MEMBERS ARE NOTED (E) AND ARE SHOWN IN THE
PLANS. THE CONTRACTOR SHALL VERIFY THAT THE EXISTING
MEMBERS SHOWN IN THE PLANS MATCH EXISTING AS BUILT
CONDITIONS PRIOR TO PREPARING SHOP DRAWINGS. IF THE AS BUILT
CONDITIONS DO NOT CONFORM TO THE INFORMATION SHOWN IN THE
PLANS, OR IF ANY STRUCTURAL MEMBER IS FOUND TO BE IN POOR
CONDITION, THE CONTRACTOR SHALL INFORM ENGINEER OF THE
ACTUAL SIZES AND/OR CONDITION. RE-DESIGN AND ADDITIONAL
FRAMING MAY BE REQUIRED IN THAT CASE.
2. NEW DUCTWORK, PIPING, AND CONDUIT SHALL ONLY BE HUNG FROM
THE NEW STRUCTURAL STEEL TUBE FRAMING. NO ADDITIONAL
LOADING IS TO BE IMPOSED ON THE EXISTING PEMB PURLINS OR
RIGID FRAMES.
3. NO MECHANICAL UNITS SHALL BE PLACED ON OR HUNG FROM THE
STRUCTURE WITHOUT THE APPROVAL OF THE ENGINEER.
4. ALL NEW PENETRATIONS THROUGH THE EXISTING ROOFS AND WALLS
SHALL BE ACCURATELY LOCATED BY THE CONTRACTOR. THE
CONTRACTOR SHALL PREPARE SHOP DRAWINGS SHOWING ALL
PROPOSED OPENINGS AND SHALL SUBMIT THESE FOR REVIEW AND
APPROVAL PRIOR TO CUTTING ANY OPENINGS.
DESIGN CODES:
VA DESIGN MANUAL STRUCTURAL:
PG-18-10 (OCTOBER 1, 2022 REV JULY 1, 2023)
VA SEISMIC DESIGN REQUIREMENTS:
H18-8 (JULY 1, 2023)
INTERNATIONAL BUILDING CODE:
IBC 2021
INTERNATIONAL EXISTING BUILDING CODE:
IEBC 2021
MINIMUM BUILDING DESIGN LOADS AND ASSOCIATED CRITERIA FOR
BUILDINGS AND OTHER STRUCTURES:
ASCE 7-22
SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS:
AISC 14TH EDITION 360-16
SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS:
AISC 341-16
DESIGN LOADS:
RISK CATEGORY IV
ROOF LOADS:
LIVE LOAD = 20 PSF
GROUND SNOW LOAD, pg = 7 PSF (5 PSF) FLAT ROOF SNOW LOAD, pf = 6 PSF (5 PSF) MINIMUM ROOF SNOW LOAD pm= 7 PSF SNOW EXPOSURE FACTOR, Ce = 1.0 THERMAL FACTOR, Ct = 1.2
CEILING LOADS:
2200 LBS AT 8'-0" O.C. EACH WAY
WIND LOADS:
DESIGN WIND SPEED:
Vult = 133 MPH (3 SECOND GUST)
WIND EXPOSURE B
INTERNAL PRESSURE COEFFICIENT, GCpi = +/-0.18
SEISMIC DESIGN DATA:
SOIL SITE CLASS ASSUMED 'D'
SEISMIC DESIGN CATEGORY C
SEISMIC IMPORTANCE FACTOR, Ie = 1.5
MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS:
Ss = 0.130g S1 = 0.059g
DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS:
Sds = 0.110g Sd1 = 0.084g
SUPPORT FOR DUCTWORK, PIPING AND MECHANICAL UNITS:
1. NO MECHANICAL UNITS SHALL BE PLACED ON OR HUNG FROM JOISTS
WITHOUT THE APPROVAL OF THE ENGINEER.
2. DUCTWORK AND PIPING SHALL ONLY BE HUNG FROM THE STEEL
FRAMING. AT JOISTS, HANGERS SHALL BE SUPPORTED FROM THE
PANEL POINT AND THE LOAD ON INDIVIDUAL HANGERS SHALL NOT
EXCEED 300 POUNDS.
3. PIPE RISERS SHALL BE SUPPORTED FROM THE FLOOR SLAB BELOW
WITH A CLAMP OR STANCHION.
4. THE MAXIMUM TOTAL HUNG LOAD ON ANY SINGLE JOIST FROM
MULTIPLE HANGERS SHALL NOT EXCEED 900 POUNDS.
AB ANCHOR BOLT
ABV ABOVE
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADH ADHESIVE
ADJ ADJACENT, ADJUSTMENT
A/E ARCHITECT/ENGINEER
AESS ARCHITECTURALLY EXPOSED STRUCTURAL STEEL
AFF ABOVE FINISHED FLOOR
AGG AGGREGATE
AHJ AUTHORITY HAVING JURISDICTION
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
AISI AMERICAN IRON AND STEEL INSTITUTE
ALT ALTERNATE
ANCH ANCHOR
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APA ENGINEERED WOOD ASSOCIATION
APRX APPROXIMATE
AR ANCHOR ROD
ARCH ARCHITECT(URAL)
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASD ALLOWABLE STRESS DESIGN
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AWC AMERICAN WOOD COUNCIL
AWPA AMERICAN WOOD PROTECTION AGENCY
AWS AMERICAN WELDING SOCIETY
AVG AVERAGE
B BOTTOM
B/ BOTTOM OF
B-B BACK-TO-BACK
BAL BALANCE
BEL BELOW
BF BRACED FRAME
BLDG BUILDING
BLK(G) BLOCK(ING)
BM BEAM
BOT BOTTOM
BP BASE PLATE, BEARING PLATE
BR BRACE(ING)
BRDG BRIDGING
BRG BEARING
BRK BRICK
BRKT BRACKET
BS BOTH SIDES
BSMT BASEMENT
BT BENT
BTWN BETWEEN
BYD BEYOND
C STEEL CHANNEL
CAIS CAISSON
CALC CALCULATION
CANT CANTILEVER
CAP CAPACITY
C-C CENTER-TO-CENTER
CE CONCRETE ENCASED
CFM COLD FORMED METAL
CHAM CHAMFER
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL/CONTRACTION JOINT
CL CENTERLINE, COLUMN LINE
CLG CEILING
CLR CLEAR
CM CONSTRUCTION MANAGER
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMB COMBINED
COMP COMPOSITE
CONC CONCRETE
COND CONDITION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COV COVER
CP CAP PLATE
CRSI CONCRETE REINFORCING STEEL INSTITUTE
CSK COUNTERSUNK
CTR CENTER(ED)
CY CUBIC YARD
CYL CYLINDER
d PENNY (AS IN NAIL, Id)
DBL DOUBLE
DD DESIGN DEVELOPMENT
DEF DEFLECTION
DEG DEGREE
DEMO DEMOLITION/DEMOLISH
DEPR DEPRESS(ED)/DEPRESSION
DET(S) DETAIL(S)
DEV DEVELOP/DEVELOPMENT
DIA DIAMETER
DIAG DIAGONAL
DIM(S) DIMENSION(S)
DIR DIRECTION
DK DECK
DL DEAD LOAD
DN DOWN
do DITTO
DP DEEP
DWG(S) DRAWING(S)
DWL DOWEL
(E) EXISTING
E EAST
EA EACH
EF EACH FACE
EIFS EXTERIOR INSULATION FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EMBED EMBEDMENT/EMBEDDED
ENGR ENGINEER
EO EDGE OF
EOD EDGE OF DECK
EOM EDGE OF MASONRY
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
ES EACH SIDE
STRUCTURAL ABBREVIATIONS
ES EACH SIDE
EXCAV EXCAVATE/EXCAVATION
EXP EXPANSION
EXT EXTERIOR
EXIST EXISTING
EW EACH WAY
F/ FACE OF
FAB FABRICATE
FB FLAT BAR
FBO FURNISHED BY OTHERS
FDN FOUNDATION
FFE FINISHED FLOOR ELEVATION
FIN FINISH(ED)
FL(R) FLOOR
FLG FLANGE
FND FOUNDATION
FO FACE OF
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FP FIREPROOFING
FRMG FRAMING
FRP FIBER-REINFORCED POLYMER
FRT FIRE RETARDANT TREATED
FS FAR SIDE
FT FEET
FTG FOOTING
FUT FUTURE
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZE(D)
GB GRADE BEAM
GC GENERAL CONTRACTOR
GLB GLUE LAMINATED BEAM
GR GRADE
GYP GYPSUM
HD HEAVY DUTY
HDR HEADER
HEF HORIZONTAL EACH FACE
HGR HANGER
HI HIGH
HIF HORIZONTAL INSIDE FACE
HK HOOK(ED)
HOF HORIZONTAL OUTSIDE FACE
HORIZ HORIZONTAL
HP HIGH POINT
HS HIGH STRENGTH
HT HEIGHT
H&V HORIZONTAL & VERTICAL
HVAC HEATING, VENTILATING & AIR CONDITIONING
IBC INTERNATIONAL BUILDING COUNCIL
ICC INTERNATIONAL CODE COUNCIL
ID INSIDE DIAMETER
IF INSIDE FACE
IFC ISSUE FOR CONSTRUCTION
IN INCH
INCL INCLUDE(D)(ING)
INFO INFORMATION
INSTL INSTALL/INSTALLATION
INSUL INSULATION
INT INTERIOR
INV INVERT(ED)
JST(S) JOIST(S)
JT JOINT
k KIP (THOUSAND POUNDS)
KB KNEE BRACE
KSI KIPS PER SQUARE INCH
LB, # POUND
LDGR LEDGER (BOARD)
LEN LENGTH
LG LONG
LL LIVE LOAD
LLBB LONG LEGS BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOCN LOCATION
LONGIT LONGITUDINAL
LP LOW POINT
LRFD LOAD AND RESISTANCE FACTOR DESIGN
LSL LONG SLOTTED HOLE,
LAMINATED STRAND LUMBER
LVL LAMINATED VENEER LUMBER
LW LONG WAY
LWC LIGHT WEIGHT CONCRETE
M MOMENT
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL & PLUMBING
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MONO MONOLITHIC
MPH MILES PER HOUR
MTL METAL
NA NOT APPLICABLE
NDS NATIONAL DESIGN SPECIFICATION FOR WOOD
CONSTRUCTION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
O-O OUT-TO-OUT
OPG OPENING
OPP OPPOSITE
OSB ORIENTED STRAND BOARD
OSHA OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION
OSL OUTSTANDING LEG,
ORIENTED STRAND LUMBER
OVS OVERSIZED HOLE
PAF POWDER ACTUATED FASTENER
PC PRECAST CONCRETE, PIECE
PCF POUNDS PER CUBIC FOOT
PED PEDESTAL
PERP PERPENDICULAR
PREFAB PREFABRICATE(D)
PL PLATE
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PMF PREMOLDED FILLER
PROJ PROJECT(ION)
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PT PRESERVATIVE-TREATED,
POST-TENSIONED
PVC POLYVINYL CHLORIDE
QTY QUANTITY
R RADIUS
RCMU REINFORCED CONCRETE MASONRY UNIT
RCSC RESEARCH COUNCIL ON STRUCTURAL
CONNECTIONS
RD ROOF DRAIN
RDK ROOF DECK
REF REFERENCE
REINF REINFORCE(D)/REINFORCEMENT
REQ(D) REQUIRE(D)
RET RETAINING
REV REVISE(D)/REVISION
RO ROUGH OPENING
RQMT(S) REQUIREMENT(S)
RTU ROOFTOP UNIT
RXN REACTION
SAN SANITARY
SC SLIP-CRITICAL (CONNECTION)
SCHED SCHEDULE
SECT SECTION
SD STORM DRAIN
SDI STEEL DECK INSTITUTE
SF SQUARE FOOT
SHRG SHORING
SHTHG SHEATHING
SIM SIMILAR
SL SLOPE(D)
SLBB SHORT LEGS BACK TO BACK
SLV SLEEVE
SOD SLAB ON DECK
SOG SLAB ON GRADE
SPA SPACE(S)/SPACING
SPEC(S) SPECIFICATION(S)
SQ SQUARE
SS STAINLESS STEEL
SSL SHORT SLOTTED HOLE
STD STANDARD
STIFF STIFFENER
STIR STIRRUP
STL STEEL
STRUC STRUCTURAL
SUPT SUPPORT
SW SHORT WAY, SHEAR WALL
SYM SYMMETRICAL
T TOP
T/ TOP OF
T&B TOP AND BOTTOM
TB TRUSS BEARING
TC TERRA COTTA
TEMP TEMPORARY,TEMPERATURE
T&G TONGUE AND GROOVE
THD THREAD(ED)
THK THICK(NESS)
TMS THE MASONRY SOCIETY
TOS TOP OF SLAB
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
U-P UNDERPINNING
V SHEAR
VAR VARIES
VB VAPOR BARRIER
VEF VERTICAL EACH FACE
VERT VERTICAL
VIF VERTICAL INSIDE FACE,
VERIFY IN FIELD
VOF VERTICAL OUTSIDE FACE
VR VAPOR RETARDER
W/ WITH
W/O WITHOUT
WD WOOD
WI WROUGHT IRON
WP WORK POINT, WATERPROOFING
WT WEIGHT
WWF WELDED WIRE FABRIC
XS EXTRA STRONG
XXS DOUBLE EXTRA STRONG
∅ DIAMETER
± PLUS OR MINUS
ABBR. DESCRIPTION ABBR. DESCRIPTION ABBR. DESCRIPTION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /F lo ri d a
L a k e
C it y V
A /0
V A
L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
S
.r v t
/2 /2
:4
:2
A M
S-001
STRUCTURAL GENERAL NOTES
AND ABBREVIATIONS
LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 RAS SLS
100% CONSTRUCTION
DOCUMENTS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
SHEET LIST
Sheet Number Sheet Name
S-001 STRUCTURAL GENERAL NOTES AND ABBREVIATIONS
SS1.B.3 BLDG 64A - LV B - ZONE 3 - STRUCTURAL FOUNDATION PLAN
SS1.B.11A BLDG 64A - LV B - ZONE 11 - STRUCTURAL FOUNDATION
PLAN
SS1.B.11B BLDG 66 - LV B - ZONE 11 - STRUCTURAL FOUNDATION PLAN
SS1.B.12B BLDG 62 - LV B - ZONE 12B - STRUCTURAL FOUNDATION
PLAN
SS1.B.13 BLDG 74 - LV B - ZONE 13 - STRUCTURAL FOUNDATION PLAN
SS1.1.11 BLDG 06 - LV 1 - ZONE 11 - STRUCTURAL FOUNDATION PLAN
SS1.1.14A BLDG 27 - LV 1 - ZONE 14 - STRUCTURAL FOUNDATION
SS1.1.14B BLDG 37 - LV 1 - ZONE 14 - STRUCTURAL FOUNDATION PLAN
SS1.1.15 BLDG 18, 42, 44, & 92 - LV1 - ZONE 15 - STRUCT FOUNDATION
PLAN
SS1.2.3 BLDG 91 - LV 2 - ZONE 3 - STRUCTURAL FRAMING PLAN
SS1.2.11 BLDG 66 - LV 2 - ZONE 11 STRUCTURAL CEILING SUPPORT
S-301 DETAILS AND SECTIONS
Revisions Date 12/31/2024
Y X
1 2
[-2.09'] (-17.00')
T/ COLUMN FOOTING
B/FOUNDATION WALL
T/ COLUMN FOOTING
TELECOM DUCT BANK
ESTIMATED GRADE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /F lo ri d a
L a k e
C it y V
A /0
V A
L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
S
.r v t
/2 /2
:4
:4
A M
SS1.B.3
BLDG 64A - LV B - ZONE 3 -
STRUCTURAL FOUNDATION PLAN
LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
64A
STATION CHIEF - EDWIN BURNETT
10/25/2024 RAS SLS
100% CONSTRUCTION
DOCUMENTS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
CODED NOTES:
DRAWING NOTES:
1. TOP OF FOOTING ELEVATION SHALL BE MEASURED FROM TOP OF FIRST FLOOR (DATUM 106.00'). TOP OF FOOTING IS NOTED THUS (....) ON PLAN BASED ON ORIGINAL CONSTRUCTION DOCUMENTATION.
ESTIMATED EXISTING TOP OF EXTERIOR GRADE IS NOTED THUS: [....] ON PLAN BASED ON ORIGINAL
CONSTRUCTION. CONTRACTOR TO CONFIRM EXISTING CONDITIONS PRIOR TO CREATING
PENETRATION IN EXISTING STRUCTURE AND NOTIFY COR IF CONDITIONS ARE NOT AS SHOWN.
NN
0 2' 4' 8' 12'
1/4" = 1'-0"
TELECOM DUCT BANK, REFER TO TELECOM DRAWINGS.1
DUCTBANK TO BE INSTALLED THROUGH CONCRETE FOUNDATION WALL,12" CONCRETE FOUNDATION WALL REINFORCED W/ #4 AT 12" HORIZONTAL EACH FACE & #8 AT 5.5" O.C. VERTICAL EACH FACE.
Revisions Date
1/4" = 1'-0"1
LOWER LEVEL - B64-A(3) - STRUCTURAL FOUNDATION PLAN
1/4" = 1'-0"2
BUILDING 64A - SOUTH ELEVATION
6.
.0 0'
T/ COLUMN FOOTING VARIES
T/ FOUNDATION WALL
B/FOUNDATION WALL
ESTIMATED GRADE
TELECOM DUCT BANK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /F lo ri d a
L a k e
C it y V
A /0
V A
L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
S
.r v t
/2 /2
:4
:4
A M
SS1.B.11A
BLDG 64A - LV B - ZONE 11 -
STRUCTURAL FOUNDATION PLAN
LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
64A
STATION CHIEF - EDWIN BURNETT
10/25/2024 RAS SLS
100% CONSTRUCTION
DOCUMENTS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
1/4" = 1'-0"1
LOWER LEVEL - B64-A(11) - STRUCTURAL FOUNDATION PLAN
CODED NOTES:
DRAWING NOTES:
1. TOP OF FOOTING ELEVATION SHALL BE MEASURED FROM TOP OF FIRST FLOOR (DATUM 106.00'). TOP OF FOOTING IS NOTED THUS (....) ON PLAN BASED ON ORIGINAL CONSTRUCTION DOCUMENTATION.
ESTIMATED EXISTING TOP OF EXTERIOR GRADE IS NOTED THUS: [....] ON PLAN BASED ON ORIGINAL
CONSTRUCTION. CONTRACTOR TO CONFIRM EXISTING CONDITIONS PRIOR TO CREATING
PENETRATION IN EXISTING STRUCTURE AND NOTIFY COR IF CONDITIONS ARE NOT AS SHOWN.
NN
0 2' 4' 8' 12'
1/4" = 1'-0"
TELECOM DUCT BANK, REFER TO TELECOM DRAWINGS.1
DUCTBANK TO BE INSTALLED THROUGH CONCRETE FOUNDATION WALL, 12" CONCRETE
FOUNDATION WALL REINFORCED W/ #4 AT 12" HORIZONTAL EACH FACE & #8 AT 5.5" O.C. VERTICAL
EACH FACE.
Revisions Date
1/4" = 1'-0"2
BUILDING 64A - WEST ELEVATION
U @ CC
2.
5.
3.
5.
T Y
P
3'
B/FOUNDATION WALLT/COLUMN FOOTING
ESTIMATED GRADE
ESTIMATED GRADE
TELECOM DUCT BANK
TELECOM DUCT BANK
DETAIL .5/ S-301
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /F lo ri d a
L a k e
C it y V
A /0
V A
L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
S
.r v t
/2 /2
:4
:5
A M
SS1.B.11B
BLDG 66 - LV B - ZONE 11 -
STRUCTURAL FOUNDATION PLAN
LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 RAS SLS
100% CONSTRUCTION
DOCUMENTS
DRAWING NOTES:
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
NN
0 2' 4' 8' 12'
1/4" = 1'-0"
1/4" = 1'-0"1
LOWER LEVEL - B66(11) - STRUCTURAL FOUNDATION PLAN
DUCTBANK TO BE INSTALLED THROUGH CMU FOUNDATION WALL, 8" CMU FOUNDATION WALLS
REINFORCED W/ #5 AT 32" O.C. DUCT BANKS TO BE INSTALLED THROUGH WALLS ABOVE EXISTING
FOOTING.
MECHANICAL UNIT, REFER TO MECHANICAL DRAWINGS.4
1. TOP OF FOOTING ELEVATION SHALL BE MEASURED FROM TOP OF FIRST FLOOR (DATUM 91.00'). TOP OF FOOTING IS NOTED THUS (....) ON PLAN BASED ON ORIGINAL CONSTRUCTION DOCUMENTATION.
ESTIMATED EXISTING TOP OF EXTERIOR GRADE IS NOTED THUS: [....] ON PLAN BASED ON ORIGINAL
CONSTRUCTION. CONTRACTOR TO CONFIRM EXISTING CONDITIONS PRIOR TO CREATING
PENETRATION IN EXISTING STRUCTURE AND NOTIFY COR IF CONDITIONS ARE NOT AS SHOWN.
CODED NOTES:
TELECOM DUCT BANK, REFER TO TELECOM DRAWINGS.1
Revisions Date
1/4" = 1'-0"2
BUILDING 66 - EAST ELEVATION
CONCRETE HOUSEKEEPING PAD, REFER TO5
6 12" CONCRETE PAD REINFORCED W/ EPOXY COATED #5 AT 12" O.C. TOP & BOTTOM.
DUCTBANK TO GO UNDER EXISTING WALL FOOTING.3
.3 0'
.1
7'
B/FOUNDATION WALLT/COLUMN FOOTING
ESTIMATED GRADE
TELECOM DUCT BANK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /F lo ri d a
L a k e
C it y V
A /0
V A
L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
S
.r v t
/2 /2
:4
:5
A M
SS1.B.12B
BLDG 62 - LV B - ZONE 12B -
STRUCTURAL FOUNDATION PLAN
LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 RAS SLS
100% CONSTRUCTION
DOCUMENTS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
1/4" = 1'-0"
LOWER LEVEL - B62(12B) - STRUCTURAL FOUNDATION PLAN
CODED NOTES:
DRAWING NOTES:
1. TOP OF FOOTING ELEVATION SHALL BE MEASURED FROM TOP OF FIRST FLOOR (DATUM 107.00'). TOP OF FOOTING IS NOTED THUS (....) ON PLAN BASED ON ORIGINAL CONSTRUCTION DOCUMENTATION.
ESTIMATED EXISTING TOP OF EXTERIOR GRADE IS NOTED THUS: [....] ON PLAN BASED ON ORIGINAL
CONSTRUCTION. CONTRACTOR TO CONFIRM EXISTING CONDITIONS PRIOR TO CREATING
PENETRATION IN EXISTING STRUCTURE AND NOTIFY COR IF CONDITIONS ARE NOT AS SHOWN.
NN
0 2' 4' 8' 12'
1/4" = 1'-0"
TELECOM DUCT BANK, REFER TO TELECOM DRAWINGS.1
DUCTBANK TO GO UNDER BOTTOM OF FOUNDATION WALL.2
1/4" = 1'-0"
BUILDING 62 - EAST ELEVATION
1.
.8 3'
B/FOUNDATION WALL
ESTIMATED GRADE
TELECOM DUCT BANK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /F lo ri d a
L a k e
C it y V
A /0
V A
L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
S
.r v t
/2 /2
:4
:5
A M
SS1.B.13
BLDG 74 - LV B - ZONE 13 -
STRUCTURAL FOUNDATION PLAN
LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 RAS SLS
100% CONSTRUCTION
DOCUMENTS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
1/4" = 1'-0"
LOWER LEVEL - B74(13) - STRUCTURAL FOUNDATION PLAN
CODED NOTES:
DRAWING NOTES:
1. TOP OF FOOTING ELEVATION SHALL BE MEASURED FROM TOP OF FIRST FLOOR (DATUM 179.50'). TOP OF FOOTING IS NOTED THUS (....) ON PLAN BASED ON ORIGINAL CONSTRUCTION DOCUMENTATION.
ESTIMATED EXISTING TOP OF EXTERIOR GRADE IS NOTED THUS: [....] ON PLAN BASED ON ORIGINAL
CONSTRUCTION. CONTRACTOR TO CONFIRM EXISTING CONDITIONS PRIOR TO CREATING
PENETRATION IN EXISTING STRUCTURE AND NOTIFY COR IF CONDITIONS ARE NOT AS SHOWN.
NN
0 2' 4' 8' 12'
1/4" = 1'-0"
TELECOM DUCT BANK, REFER TO TELECOM DRAWINGS.1
1/4" = 1'-0"
BUILDING 74 - WEST ELEVATION
Revisions Date
DUCTBANK TO BE INSTALLED THROUGH CONCRETE FOUNDATION WALL, 12 3/8" CONCRETE
FOUNDATION WALL REINFORCED W/ #4 AT 12" O.C. EACH FACE HORIZONTAL, #7 AT 10" O.C. EACH
FACE VERTICAL.
8" HOLLOW CORE PLANK FLOOR W/ PRESTRESSED STRANDS. PERFORM GPR SCAN OF FIRST FLOOR TO DETERMINE LOCATION OF PRESTRESSED STRANDS PRIOR TO DRILLING HOLES FOR CONDUIT.
2.
3.
[-2.00'] ~(-3.00')
B/FOUNDATION WALL
ESTIMATED GRADE
TELECOM DUCT BANK
B/FOUNDATION WALL
ESTIMATED GRADE
TELECOM DUCT BANK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /F lo ri d a
L a k e
C it y V
A /0
V A
L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
S
.r v t
/2 /2
:4
:2
A M
SS1.1.11
BLDG 06 - LV 1 - ZONE 11 -
STRUCTURAL FOUNDATION PLAN
LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 RAS SLS
100% CONSTRUCTION
DOCUMENTS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
1/4" = 1'-0"1
FIRST FLOOR - B06(11) - STRUCTURAL FOUNDATION PLAN
CODED NOTES:
DRAWING NOTES:
1. TOP OF FOOTING ELEVATION SHALL BE MEASURED FROM TOP OF FIRST FLOOR (DATUM UNKNOWN APPROXIMATELY 106.00'). TOP OF FOOTING IS NOTED THUS (....) ON PLAN BASED ON ORIGINAL CONSTRUCTION DOCUMENTATION. ESTIMATED EXISTING TOP OF EXTERIOR GRADE IS NOTED THUS:
[....] ON PLAN BASED ON ORIGINAL CONSTRUCTION. CONTRACTOR TO CONFIRM EXISTING
CONDITIONS PRIOR TO CREATING PENETRATION IN EXISTING STRUCTURE AND NOTIFY COR IF
CONDITIONS ARE NOT AS SHOWN.
NN
0 2' 4' 8' 12'
1/4" = 1'-0"
TELECOM DUCT BANK, REFER TO TELECOM DRAWINGS.1
DUCT BANK TO GO UNDER EXISTING WALL FOOTING.2
1/4" = 1'-0"2
BUILDING 06 - EAST ELEVATION
1/4" = 1'-0"
BUILDING 06 - NORTH ELEVATION
6.
.5 0'
[-12.50'] (-13.50')
B/FOUNDATION WALL
TELECOM DUCT BANK
ESTIMATED GRADE
B/FOUNDATION WALL
TELECOM DUCT BANK
ESTIMATED GRADE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /F lo ri d a
L a k e
C it y V
A /0
V A
L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
S
.r v t
/2 /2
:4
:2
A M
SS1.1.14A
BLDG 27 - LV 1 - ZONE 14 -
STRUCTURAL FOUNDATION
LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 RAS SLS
100% CONSTRUCTION
DOCUMENTS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
1/4" = 1'-0"
FIRST FLOOR - B27(14) - STRUCTURAL FOUNDATION PLAN
CODED NOTES:
TELECOM DUCT BANK, REFER TO TELECOM DRAWINGS.
DRAWING NOTES:
1. TOP OF FOOTING ELEVATION SHALL BE MEASURED FROM TOP OF FIRST FLOOR (DATUM 89.50'). TOP OF FOOTING IS NOTED THUS (....) ON PLAN BASED ON ORIGINAL CONSTRUCTION DOCUMENTATION.
ESTIMATED EXISTING TOP OF EXTERIOR GRADE IS NOTED THUS: [....] ON PLAN BASED ON ORIGINAL
CONSTRUCTION. CONTRACTOR TO CONFIRM EXISTING CONDITIONS PRIOR TO CREATING
PENETRATION IN EXISTING STRUCTURE AND NOTIFY COR IF CONDITIONS ARE NOT AS SHOWN.
N 0 2' 4' 8' 12'
1/4" = 1'-0"
DUCTBANK TO BE INSTALLED THROUGH CONCRETE FOUNDATION WALL, 13" CONCRETE FOUNDATION WALL REINFORCED W/ #4 AT 12" O.C. EACH FACE STAGGERED HORIZONTAL & VERTICAL. DUCT BANKS
TO BE PLACED THROUGH WALL ABOVE EXISTING FOOTING.
1/4" = 1'-0"
BUILDING 27 - SOUTH ELEVATION
1/4" = 1'-0"3
BUILDING 27 - WEST ELEVATION
DUCTBANK TO GO UNDER EXISTING WALL FOOTING.3
[14.17'] (-0.50')
[9 .5
0'
1.
B/FOUNDATION WALL
TELECOM DUCT BANK
ESTIMATED GRADE
B/FOUNDATION WALL
TELECOM DUCT BANK
ESTIMATED GRADE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /F lo ri d a
L a k e
C it y V
A /0
V A
L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
S
.r v t
/2 /2
:4
:2
A M
SS1.1.14B
BLDG 37 - LV 1 - ZONE 14 -
STRUCTURAL FOUNDATION PLAN
LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 RAS SLS
100% CONSTRUCTION
DOCUMENTS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
1/4" = 1'-0"
FIRST FLOOR - B37(14) - STRUCTURAL FOUNDATION PLAN
CODED NOTES:
TELECOM DUCT BANK, REFER TO TELECOM DRAWINGS.
DRAWING NOTES:
1. TOP OF FOOTING ELEVATION SHALL BE MEASURED FROM TOP OF BOILER ROOM FLOOR (DATUM 62.50'). TOP OF FOOTING IS NOTED THUS (....) ON PLAN BASED ON ORIGINAL CONSTRUCTION DOCUMENTATION. ESTIMATED EXISTING TOP OF EXTERIOR GRADE IS NOTED THUS: [....] ON PLAN BASED ON ORIGINAL CONSTRUCTION. CONTRACTOR TO CONFIRM EXISTING CONDITIONS PRIOR TO CREATING PENETRATION IN EXISTING STRUCTURE AND NOTIFY COR IF CONDITIONS ARE NOT AS
SHOWN.
N 0 2' 4' 8' 12'
1/4" = 1'-0"
DUCTBANK TO BE INSTALLED THROUGH CONCRETE FOUNDATION WALL, 13" CONCRETE FOUNDATION WALL REINFORCED W/ #4 AT 24" O.C. HORIZONTAL OUTSIDE FACE, #4 AT 12" O.C. HORIZONTAL
OUTSIDE FACE, #4 AT 24" O.C. VERTICAL EACH FACE.
1/4" = 1'-0"2
BUILDING 37 - EAST ELEVATION
1/4" = 1'-0"3
BUILDING 37 - NORTH ELEVATION
5.
7.
B/FOUNDATION WALL
ESTIMATED GRADE
TELECOM DUCT BANK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /F lo ri d a
L a k e
C it y V
A /0
V A
L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
S
.r v t
/2 /2
:4
:3
A M
SS1.1.15
BLDG 18, 42, 44, & 92 - LV1 - ZONE
15 - STRUCT FOUNDATION PLAN
LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
18, 42, 44, 92
STATION CHIEF - EDWIN BURNETT
10/25/2024 RAS SLS
100% CONSTRUCTION
DOCUMENTS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
1/4" = 1'-0"1
FIRST FLOOR - B18(15) - STRUCTURAL FOUNDATION PLAN
CODED NOTES:
DRAWING NOTES:
1. TOP OF FOOTING ELEVATION SHALL BE MEASURED FROM TOP OF FIRST FLOOR (DATUM 86.00'). TOP OF FOOTING IS NOTED THUS (....) ON PLAN BASED ON ORIGINAL CONSTRUCTION DOCUMENTATION.
ESTIMATED EXISTING TOP OF EXTERIOR GRADE IS NOTED THUS: [....] ON PLAN BASED ON ORIGINAL
CONSTRUCTION. CONTRACTOR TO CONFIRM EXISTING CONDITIONS PRIOR TO CREATING
PENETRATION IN EXISTING STRUCTURE AND NOTIFY COR IF CONDITIONS ARE NOT AS SHOWN.
N 0 2' 4' 8' 12'
1/4" = 1'-0"
TELECOM DUCT BANK, REFER TO TELECOM DRAWINGS.1
DUCTBANK TO GO UNDER EXISTING WALL FOOTING.2
1/4" = 1'-0"2
BUILDING 18 - EAST ELEVATION
Revisions Date
NN
0 4' 8' 16' 24'
1/8" = 1'-0"
1/8" = 1'-0"
FIRST FLOOR - B42(15) - STRUCTURAL FOUNDATION PLAN
1/8" = 1'-0"4
FIRST FLOOR - B44(15) - STRUCTURAL FOUNDATION PLAN
1/8" = 1'-0"5
FIRST FLOOR - B92(15) - STRUCTURAL FOUNDATION PLAN
BUILDING 42, 44 & 92
BUILDING 18
NO EXISTING INFORMATION AVAILABLE FOR THE CONSTRUCTION OF BUILDINGS 42, 44 & 92.
CONTRACTOR TO NOTIFY COR OF FOUNDATION COMPOSITION AND PENETRATION LOCATION PRIOR
TO DRILLING FOR DUCTBANK PENETRATION.
A B
3' - 6" (E) 4' - 7 1/2" (E) 4' - 7 1/2" (E) 4' - 7 1/2" (E) 4' - 7 1/2" (E) 3' - 0" (E)
W12X26 (E)
14K4 (E)
14K4 (E)
14K4 (E)
14K4 (E)
K
(E
K
(E
K
(E
K
(E
K
(E
K
(E
K
(E
W
X
E
W
X
E
JOIST BEARING 14.75', TYP.
JOIST BEARING 14.75', TYP.
DETAIL .2/ S-301
DETAIL .4/ S-301
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /F lo ri d a
L a k e
C it y V
A /0
V A
L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
S
.r v t
/2 /2
:4
:3
A M
SS1.2.3
BLDG 91 - LV 2 - ZONE 3 -
STRUCTURAL FRAMING PLAN
LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 RAS SLS
100% CONSTRUCTION
DOCUMENTS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
1/4" = 1'-0"2
SECOND FLOOR - B91 (3) - STRUCTURAL ROOF FRAMING PLAN
CODED NOTES:
DRAWING NOTES:
1. JOIST BEARING NOTED ON PLAN MEASURED FROM TOP OF FIRST FLOOR SLAB ( DATUM 187.25').
N
0 2' 4' 8' 12'
1/4" = 1'-0"
1. INFILL EXISTING DUCT PENETRATION, REFER TO
2 ROOF TOP MECHANICAL UNIT REINFORCE JOISTS AS NEEDED, REFER TO
C P
CP
C P
U @ CC T @ CC Q1S
57a
HSS8X8X3/8
HSS8X8X3/8
HSS8X8X3/8
HSS8X8X3/8
HSS8X8X3/8
H S
S 8X
8X 3/
H S
S 8X
8X 3/
H S
S 8X
8X 3/
H S
S 8X
8X 3/
H S
S 8X
8X 3/
H
S S
8X 8X
3/
H S
S 8X
8X 3/
H S
S 8X
8X 3/
H S
S 8X
8X 3/
H
S S
8X 8X
3/
H S
S 8X
8X 3/
H S
S 8X
8X 3/
H S
S 8X
8X 3/
H
S S
8X 8X
3/
H S
S 8X
8X 3/
H
S S
8X 8X
3/
H S
S 8X
8X 3/
H S
S 8X
8X 3/
H S
S 8X
8X 3/
H S
S 8X
8X 3/
H
S S
8X 8X
3/
H S
S 8X
8X 3/
H
S S
8X 8X
3/
H S
S 8X
8X 3/
8HSS8X8X3/8
7'
/8
8'
/8
7'
7'
7'
3'
/8
1'
/2
(E
(E
(E
2'
(E
9' - 4" (E) 4' - 10 1/2" (E) 8' - 1" (E) 18' - 0" (E)
10" 7' - 7 1/8" 7' - 8 3/8" 7' - 9" 4' - 5". 10"
.5
.8
.1
9.
9.
.8
.5
.1
9.
9.
S1
HSS8X8X3/8 HSS8X8X3/8 HSS8X8X3/8
HSS8X8X3/8
HSS8X8X3/8
HSS8X8X3/8
HSS8X8X3/8 RIGID FRAME (E)
RIGID FRAME (E)
RIGID FRAME (E)
RIGID FRAME (E)
S-301
8" M
E T
A L
R O
O F
U R
LI
N
S
E
T Y
P , E
A C
H B
A Y
S-301
S-301
TYP.
1'
T Y
P
HSS8X8X3/8
HSS8X8X3/8 HSS8X8X3/8 HSS8X8X3/8
DETAIL .3/ S-301
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /F lo ri d a
L a k e
C it y V
A /0
V A
L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
S
.r v t
/2 /2
:4
:4
A M
SS1.2.11
BLDG 66 - LV 2 - ZONE 11
STRUCTURAL CEILING SUPPORT
LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 RAS SLS
100% CONSTRUCTION
DOCUMENTS
CODED NOTES:
EXISTING 1 1/4" METAL ROOF DECK
DRAWING NOTES:
1. TOP OF STEEL IS TO BE 2" BELOW TOP OF PEMB GIRDER, DENOTED THUS: (....) ON PLAN MEASURED
FROM TOP OF RAISED ACCESS PLATFORM (DATUM 175.00').
2. COORDINATION OF LOCATION OF HSS TUBES IS REQUIRED WITH FINAL CEILING GRID SELECTION, EQUIPMENT, AND RAISED ACCESS FLOOR, REFER TO ARCHITECTURAL AND TELECOM DRAWINGS.
3. HSS TUBES ARE DESIGNED TO SUPPORT A MAXIMUM 2200 LBS AT 8'-0" O.C. EACH WAY.
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
NN
0 2' 4' 8' 12'
1/4" = 1'-0"
1/4" = 1'-0"
SECOND FLOOR - B66(11) - DATA CENTER STRUCTURAL CEILING SUPPORT FRAMING PLAN
ELECTRICAL TRANSFORMER HUNG FROM FIRST FLOOR SLAB ABOVE, REFER TO2
3/16"
3 SIDES TYP.
10 1/4"
EXISTING CONCRETE COLUMN
EXISTING RIGID FRAME
EXISTING WELD PLATE
ANCHORED TO COLUMN
EXISTING PURLINS
EXISTING METAL DECK
HSS TUBE, REFER TO PLAN
EXISTING EXTERIOR WALL AND
INTERIOR FINISH, REFER TO
ARCHITECTURAL DRAWINGS
6"x4"x3/8"x 6" LONG
CLIP ANGLE, EACH
SIDE OF HSS TUBE
(2) 3/4" DIA. A325N
THROUGH BOLTS
T
3/16"
3 SIDES TYP.
EXISTING STEEL COLUMN
EXISTING RIGID FRAME
EXISTING PURLINS
EXISTING METAL DECK
HSS TUBE, REFER TO PLAN
EXISTING EXTERIOR WALL AND
INTERIOR FINISH, REFER TO
ARCHITECTURAL DRAWINGS
6"x4"x3/8"x 6" LONG
CLIP ANGLE, EACH
SIDE OF HSS TUBE
(2) 3/4" DIA. A325N
THROUGH BOLTS
Q1
10"
6"
1/
2" 3"
1/
2"
6"x4"x3/8"x 6" LONG
CLIP ANGLE, EACH
SIDE OF BEAM
(2) 3/4" DIA. A325-N THROUGH
BOLTS IN SHORT SLOTTED HOLES,
EACH SIDE OF BEAM
1/2" MIN., 2" MAX.
3"
HSS TUBE, REFER TO PLAN
3/16"
TYP.
3/16"
TYP.
LOAD
LOAD
3/16" 1 1/2"
TYP.
STEEL JOIST,
REFER TO PLAN
WHERE THE LOAD DOES NOT OCCUR WITHIN 6" OF PANEL
POINT FIELD INSTALL (2) STRUT ANGLES AS SHOWN:
AT K-SERIES JOISTS 1 1/2"x1 1/2"x1/4" AT LH-SERIES JOISTS 2"x2"x1/4"
STRUT ANGLE
EACH SIDE
PANEL POINT
EXISTING CONCRETE SLAB
4" M
IN
3/8" THREADED ROD
Pmax=140 lbs
HILTI HDI-P TZ DROP
IN ANCHOR
NOTE:
DETAIL MAY ALSO APPLY TO THE BOTTOM OF CONCRETE BEAMS.
EXISTING 3" CONCRETE
SLAB ON 9/16" METAL
FORM DECK
REMOVE EXISTING SHEET
METAL FAN CURB DOWN TO
TOP OF SLAB
DEMO
NEW WORK
METAL ROOF DECK, REFER TO
GENERAL NOTES
PROVIDE 1 1/2"x1 1/2"x1/4" ANGLES AT
EDGE OF OPENINGS, TACK WELDED TO
SUPPORTING ANGLES
3"x3"x1/4" ANGLE, GALVANIZED
EXISTING STEEL JOIST
EXISTING 3"x3"x1/4" ROOF
ANGLE FRAME
3/16" TYP.CONCRETE INFILL, f'c=3000psi
3/4" CHAMFER
EXISTING CONCRETE SLAB
CONCRETE HOUSEKEEPING PAD
#3 AT 8" O.C.#3 AT 8" O.C.
EDGE OF EQUIPMENT
6" MIN.
#3 AT 8" O.C. HOOKED DOWEL,
GROUTED INTO EXISTING
CONCRETE SLAB WITH HILTI
HIT HY-200 ADHESIVE
3"
1/ 2"
4 1/2"
NOTE:
THE SLAB JOINTS SHALL BE SPACED AS SHOWN ON PLANS AND/OR AS INDICATED IN THE GENERAL NOTES.
THE CONTRACTOR MAY PROVIDE A SAW CUT CONTROL JOINT AND/OR CONSTRUCTION JOINT AS NEEDED.
SAW CUT JOINTS SHALL BE 1/4 OF THE SLAB THICKNESS IN DEPTH AND SHALL BE CUT AS SOON AS THE
CONCRETE IS FIRM ENOUGH NOT TO BE TORN OR DAMAGED BY THE BLADE AND BEFORE RANDOM
SHRINKAGE CRACKS CAN FORM IN THE CONCRETE SLAB.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /F lo ri d a
L a k e
C it y V
A /0
V A
L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
S
.r v t
/2 /2
:4
:2
A M
S-301
DETAILS AND SECTIONS LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 RAS SLS
100% CONSTRUCTION
DOCUMENTS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
1" = 1'-0"
SECTION
1" = 1'-0"
SECTION
N.T.S.
HSS BEAM CONNECTION DETAIL
1N.T.S.
JOIST LOAD STRUT DETAIL
N.T.S.
SECURE HANGING RODS IN CONCRETE
N.T.S.
EXISTING ROOF OPENING INFILL DETAIL
Revisions Date
N.T.S.
CONCRETE HOUSEKEEPING PAD DETAIL ON EXISTING
FIRE ALARM ABBREVIATIONS
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
ALT ALTERNATE
AMB OR A AMBIENT
ARCH ARCHITECT
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
SSTV CLOSED CIRCUIT TELEVISION
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
OC ON CENTER
OD OUTSIDE DIAMETER
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
REQD REQUIRED
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SURF SURFACE
SW SWITCH
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VEWFD VERY EARLY WARNING FIRE DETECTION
WP WEATHERPROOF
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISTR DISTRIBUTION
DN DOWN
DRSW DOOR SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
EXIST EXISTING
FLEX FLEXIBLE METALLIC CONDUIT
FOUTT TELEPHONE FLOOR OUTLET
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
G OR GND GROUND OR GENERATOR
GEN GENERATOR
GTB GROUND TERMINAL BOX
HOA HAND-OFF-AUTOMATIC
HT HEIGHT
HZ HERTZ
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
J-BOX JUNCTION BOX
LF LINEAR FEET (FOOT)
LTNG LIGHTING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MT MOUNT
MTD MOUNTED
MTG MOUNTING
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEUT OR N NEUTRAL
NIC NOT IN CONTRACT
NS NO SCALE
NTS NOT TO SCALE
ABBR. DESCRIPTION ABBR. DESCRIPTION ABBR. DESCRIPTION
FA1. ALL FIRE ALARM EQUIPMENT IS TO BE NEW, UL LISTED FOR FIRE SERVICE,
AND SHALL BE COMPATIBLE WITH THE EXISTING NOTIFIER FIRE ALARM
SYSTEM.
FA2. ALL WIRING AND CONDUIT IS TO CONFORM TO NEC ARTICLE 760. WIRING
SHALL BE UL LISTED, MINIMUM 300V TYPE FPLP PLENUM RATED SOLID
COPPER OR STANDARD COPPER WITH MAXIMUM 19 STRANDS.
FA3. LOW VOLTAGE CONDUCTORS: PROVIDE CONDUCTORS IN ACCORDANCE WITH
NFPA 70 AND NFPA 72, AND AS RECOMMENDED BY THE FIRE ALARM SYSTEM
MANUFACTURER. CONDUCTORS SHALL BE COPPER, MINIMUM NO. 14 AWG,
TWISTED SHIELDED PAIR.
FA4. SURVIVABILITY: PER AUTHORITY HAVING JURISDICTION, WIRING INSTALLED IN
METAL RACEWAY WITHIN BUILDINGS THAT ARE PROTECTED THROUGHOUT BY
SPRINKLERS SHALL BE CONSIDERED TO MEET THE REQUIREMENTS FOR
PATHWAY SURVIVABILITY LEVEL 2 IN ACCORDANCE WITH NFPA 72 (2010) AS A
2-HOUR PERFORMANCE ALTERNATIVE.
FA5. ALL FIRE ALARM POWER CIRCUITS SHALL HAVE A DEDICATED 120V 20A
BREAKER THAT SHALL BE RED IN COLOR AND MECHANICALLY PROTECTED
(LOCKABLE IN THE "ON" POSITION), MARKED AS "FIRE ALARM CIRCUIT".
FA6. MINIMUM CANDELA RATING OF STROBES IS 15CD UNLESS NOTED OTHERWISE;
"##" ADJACENT TO DEVICE INDICATES THE CANDELA RATING. PROVIDE
SYNCHRONIZATION OF STROBES IN ALL ADJACENT AREAS WHERE STROBES
ARE VISIBLE TO EACH OTHER.
FA7. FIRE ALARM DESIGN IS IN ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA 72) AND NATIONAL FIRE CODES (NFC).
WHERE A FIRE ALARM RISER IS INDICATED, IT IS DIAGRAMMATIC IN NATURE
AND NOT INTENDED TO REPRESENT A COMPLETE WIRING AND DEVICE
DISPLAY. ALL WIRING AND DEVICES SHALL BE IN ACCORDANCE WITH
SELECTED VENDOR'S POINT-BY-POINT WIRING DIAGRAM. REFER TO FLOOR
PLAN FOR DESIGN INTENT AND PROPOSED QUANTITY OF FIRE ALARM SYSTEM
COMPONENTS.
FA8. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO
SHOW ALL POSSIBLE CONDITIONS. IT IS INTENDED THAT A COMPLETE FIRE
ALARM SYSTEM BE PROVIDED WITH ALL THE NECESSARY EQUIPMENT,
WIRING, CONDUIT, AND CONTROLS, COMPLETELY COORDINATED WITH ALL
DISCIPLINES. ANY ITEMS AND LABOR REQUIRED FOR A COMPLETE FIRE
ALARM SYSTEM, IN ACCORDANCE WITH ALL APPLICABLE CODES, STANDARDS,
LOCAL AUTHORITIES AND THESE CONTRACT DOCUMENTS SHALL BE
FURNISHED AT NO ADDITIONAL COST TO THE OWNER. THE FIRE ALARM
CONTRACTOR SHALL CAREFULLY REVIEW ALL CONTRACT DOCUMENTS AND
THE DESIGN OF OTHER TRADES BEFORE PREPARING SHOP DRAWINGS.
FA9. FIRE ALARM CONTRACTOR SHALL BE AWARE OF THE TYPE OF FINISHES,
DECOR AND OCCUPANCY. COORDINATION WITH THE STAKEHOLDERS(S)
SHALL BE PERFORMED BY THE FIRE ALARM CONTRACTOR FOR PLACEMENT
OF FIRE ALARM DEVICES.
FA10. FIRE ALARM SYSTEM SHALL COMPLY WITH NFPA 70 AND 72 FOR PROPER
INSTALLATION PRACTICES.
FA11. FIRE ALARM PATHWAYS IN ALL AREAS SHALL BE IN 3/4" EMT, AND SHALL BE
PAINTED RED. ALL FIRE ALARM WIRING SHALL BE ROUTED THROUGH CONDUIT
THAT IS STRICTLY DEDICATED FOR FIRE ALARM. NO OTHER SYSTEMS MAY
UTILIZE FIRE ALARM WIRING CONDUIT OR EMT.
FA12. ALL FIRE ALARM JUNCTION BOX AND PULL BOX COVERS SHALL BE PAINTED
RED.
FA13. PERFORM RE-ACCEPTANCE TESTING IN ACCORDANCE WITH NFPA 72.
FA14. FIRE ALARM CIRCUITS SHALL NOT HAVE SPLICES. CIRCUITS SHALL BE
EXTENDED FROM DEVICE AND APPLIANCE SCREW TERMINALS.
FIRE ALARM SYSTEM NOTES
ELECTRONIC SAFETY AND SECURITY SYMBOLS
SYMBOL DESCRIPTION
ALARM, CHECK VALVE
ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:
FACP = CONTROL PANEL
ALARM, SPEAKER/LIGHT, ONE ASSEMBLY. ADJUSTABLE
15CD, 30CD, 75CD UNLESS OTHERWISE NOTED
ALARM, SPEAKER/LIGHT, SEPARATE ASSEMBLY. ADJUSTABLE
15CD, 30CD, 75CD UNLESS OTHERWISE NOTED
ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE. ADJUSTABLE
15CD, 30CD, 75CD UNLESS OTHERWISE NOTED
ALARM, TAMPER SWITCH
DETECTOR, HEAT
FACP
TS
HD
S SPEAKER, CEILING MOUNTED FIRE ALARM VOICE EVACUATION .
DETECTOR, SMOKESD
ALARM, FLOW SWITCHFS
S SPEAKER, WALL MOUNTED FIRE ALARM VOICE EVACUATION .
FIRE PROTECTION SPRINKLER ACTIVATION HORN.
DETECTOR, CARBON DIOXIDECD
REMOTE TEST SWITCHRTS
DETECTOR, SMOKE, FOR DUCT
FIRE ALARM STATION, MANUAL PULLP
VESDA SAMPLE POINTSP
1'-0" MAX.
FINISHED
FLOOR
SPEAKER
DEVICE
7'-6" TO TOP
OF DEVICE,
OR
0'-6" BELOW
FINISHED CEILING,
WHICHEVER IS
LOWER
6'-8" MIN. TO 8'-0" MAX.
FROM STROBE LENS TO
FLOOR, OR
WITHIN 0'-6" OF
FINISHED CEILING,
WHICHEVER IS
LOWER
STROBE
DEVICE
SPEAKER/STROBE
COMBINATION
DEVICE
FIRE ALARM CONTROL
PANEL OR EMERGENCY
VOICE PANEL
ANNUCIATOR
PANEL OR
TERMINAL
CABINET
MANUAL PULL
STATION
5'-6"
3'-10" FROM
OPERATING
HANDLE
TO FLOOR
5'-0" MAX.
FROM EXIT OPENING
0'-4" MIN. 3'-0" MIN.
SMOKE/HEAT
DETECTOR
MOUNT DETECTOR
ON APPROVED BOX 6'-0" MAX. LENGTH FLEXIBLE
RACEWAY TO DEVICE
MOUNTED ON SUSPENDED
CEILING
AIR SUPPLY DIFFUSER OR
RETURN AIR OPENING
JUNCTION BOX
CONDUIT
INSTALL PER NATIONAL
ELECTRIC CODE
FLOOR-CEILING
ASSEMBLY
SUSPENDED
CEILING
SMOKE
DETECTOR
1'-0" MAX.
FINISHED
FLOOR
SUSPENDED
CEILING
HEAT
DETECTOR
0'-4" MIN.
0'-4" MIN
HEAT
DETECTOR
DO NOT LOCATE
DETECTOR WITHIN
THIS AREA
HEAT DETECTOR MOUNTING
PLACEMENT REQUIREMENTSNOTE: MOUNT FIRE ALARM DEVICES ON APPROVED BOXES.
ABOVE CEILIGN SMOKE
DETECTOR
MOUNT DETECTOR
ON APPROVED BOX
6'-0" MAX. LENGTH FLEXIBLE
RACEWAY TO DEVICE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
L a k e
C it y V
A /0
V
A L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
M
E P
F P
T .r v t
/1 /2
:2
:0
P M
FA001
FIRE ALARM LEGENDS &
SYMBOLS
LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
12/31/2024 CJM CVM
100% CONSTRUCTION
DOCUMENTS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
N.T.S.1
FIRE ALARM DEVICE MOUNTING DETAIL
SHEET LIST
SHEET NUMBER SHEET NAME
FA001 FIRE ALARM LEGENDS & SYMBOLS
FA101 BASEMENT - ZONES - NEW
FA400 ENLARGED DATA CENTER
1 REVISED 100% 12/31/2024 12/31/2024
B62[12A]
B74[13]
B66[11]
B64-A[3]
B64-B[2] B82[9]
B82[8]
B64-D[10]
B19[7]
B64-2[1]B64-A[4]
B64-2[6]
B38[5]
B64-A[11]
FA400
FA400
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
L a k e
C it y V
A /0
V
A L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
M
E P
F P
T .r v t
/2 /2
:0
:0
P
M
FA101
BASEMENT - ZONES - NEW LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
10/25/2024 TDB CVM
100% CONSTRUCTION
DOCUMENTS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
1" = 30'-0"1
FIRE ALARM - LOWER LEVEL - ZONES - NEW
NN
0 15' 30' 60' 90'
1" = 30'
CODED NOTES:
EXISTING FIRE ALARM CONTROL PANEL LOCATION.1
P
P
P
P
SD
F A
T C
1 TYPICAL
30CD
30CD
30CD
15CD
15CD
V E
W F
D
30CD
30CD
30CD
30CD
30CD
30CD
30CD
T-300
SP SP SP
SP SP SP
SP SP SP
SP SP SP
SP SP SP
3 3
5 5
15CD
EXISTING NOTIFIER FIRE
ALARM CONTROL PANEL
"FACP"
GROUND FLOOR
DATA CENTER
FIRE ALARM
SUB-PANEL
"FATC"
SS
R R
P
TYPICAL CONTROL RELAYS
INDICATING DEVICES
TYPICAL INITIATION DEVICES
SECOND FLOOR
TO DATA CENTER
CLEAN AGENT FIRE
SUPPRESSION SYSTEM
NEW FIBER OPTIC CONNECTION TO
EXISTING FIRE ALARM NETWORK.
COORDINATE CONNECTION
REQUIREMENTS WITH EXISTING FACP.
CABLING PER
MANUFACTURER
RECOMMENDATIONS
CABLING PER
MANUFACTURER
RECOMMENDATIONS
VEWFD SYSTEM
CABINET
SD
AIR SAMPLING PORT
DATA CENTER MANUAL PULL STATION
SYSTEM ABORT
KEY DISCONNECT SWITCH
EXPIRATION OF THE 30 SEC. TIME DELAY
ACTUATION LIMIT SWITCH SUPERVISORY
CLEAN AGENT DISCHARGE
INPUTS
A C
T U
A T
E A
LA
R
M S
IG
N
A L
T O
S U
P P
R E
S S
IO
N
P A
N E
L
A C
T U
A T
E S
U P
E R
V
IS
O R
Y T
O S
U P
P R
E S
S
IO
N P
A N
E L
A C
T U
A T
E A
U D
IB
LE
S U
P E
R V
IS
O
R Y
S
IG
N A
L
A C
T U
A T
E T
R O
U B
LE
T
O S
U P
P R
E S
S
IO
N P
A N
E L
A C
T U
A T
E A
U D
IB
LE
T R
O U
B
LE
S
IG
N A
L
E Q
U
IP
M E
N T
P O
W E
R S
H U
T D
O W
N
H V
A C
S H
U T
D O
W N
A
H U
-1 S
H U
T D
O W
N
A
LL
M O
T O
R
IZ
E D
D A
M P
E R
S C
LO
S
E
T H
E P
R O
G R
A M
M E
D
S
E C
T
IM
E D
E
LA
Y W
IL
L
B E
G
IN
F
IR
E A
LA
R
M S
IG
N
A L
T O
B U
IL
D
IN
G
F
IR
E A
LA
R
M
S U
P E
R V
IS
O
R Y
S
IG
N A
L T
O B
U
IL
D
IN
G F
IR
E
A
LA
R M
S Y
S T
E M
T R
O U
B
LE
S
IG
N A
L T
O B
U
IL
D
IN
G F
IR
E
A
LA
R M
OUTPUTS
C
LE
A N
A G
E N
T D
IS
C
H A
R G
E
A B
O R
T S
W
IT
C H
O V
E R
R
ID
E
A B C D E F G H I J K L M N O P
X
NOTE: THIS MATRIX IS ONLY INTENDED TO SHOW THE MAJOR SYSTEM FUNCTIONS. SYSTEM SHALL ALSO PERFORM INPUTS/OUTPUTS REQUIRED BY NFPA 72 AND THE MANUFACTURER. PROVIDE PROGRAMMING AS REQUIRED FOR VEWFD SYSTEM TO RESPOND AS NOTED IN MATRIX. INTENT IS LEVEL 1 DETECTION PROVIDE SUPERVISORY SIGNAL AT BUILDING AND CLEAN AGENT FIRE PANELS. LEVEL 2 PROVIDES GENERAL ALARM FOR BUILDING FIRE ALARM PER CURRENT ZONING AND PROVIDE RELEASE SIGNAL TO CLEAN AGENT SYSTEM.
H O
R N
/S T
R O
B E
W
IL
L O
P E
R A
T E
FIRE ALARM SYSTEM AC POWER FAILURE
FIRE ALARM SYSTEM LOW BATTERY
OPEN CIRCUIT
GROUND FAULT
NOTIFICATION APPLIANCE CIRCUIT SHORT
A C
T U
A T
E A
U D
IB
LE
A
LA
R M
S
IG
N A
L
S Y
S T
E M
D
IS
C H
A R
G E
S T
R O
B E
W
IL
L O
P E
R A
T E
R S T U V W X
X X
X X X
X X X
X X X
X X X
VEWFD VEP ALERT LEVEL
VEWFD VEP FIRE ALARM LEVEL 1
VEWFD VEP FIRE ALARM LEVEL 2
VEWFD VEP FAULT
X X X X X
X X
X X X X X X
X X
X
X X X
X
V E
W F
D F
A U
LT
S
IG
N
A L
T O
B U
IL
D
IN
G
F
IR
E A
LA
R
M
O .K
. L E
D W
IL
L
T U
R N
O F
F , V
E P
U N
IT
W
IL
L
B E
E P
A
LE
R T
L E
D W
IL
L
F
LA
S H
O N
V E
P D
E T
E C
T O
R
F
IR
E
L E
D W
IL
L
F
LA
S H
O N
V E
P D
E T
E C
T O
R
F
IR
E
L E
D W
IL
L
F
LA
S H
O N
V E
P D
E T
E C
T O
R
X X
X X
Q
X X X X
X
XXXXX
X
X X X
X X
2 TYPICAL
SP SP SP
SP SP SP
SP SP SP
SP SP SP
SP SP SP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s
/F lo ri d a
L a k e
C it y V
A /0
V
A L a k e
C it y
E H
R M
I n fr a s tr u c tu re
R
M
E P
F P
T .r v t
/1 /2
:3
:0
A M
FA400
ENLARGED DATA CENTER LAKE CITY VAMC EHRM
INFRASTRUCTURE
UPGRADES DESIGN
LAKE CITY FL
573A4-21-700
STATION CHIEF - EDWIN BURNETT
12/31/2024 CJM CVM
100% CONSTRUCTION
DOCUMENTS
524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523
1/4" = 1'-0"1
DATA CENTER FIRE ALARM
N.T.S4
FIRE ALARM RISER…
This is the start of the file's text. The full file is on GovTribe.