Attachment 4 - Final Drawing Set - 3 of 8.pdf

PDF 12 MB Posted

Attached to
Project 573A4-21-700 EHRM Infrastructure Upgrades construction project at the Lake City, FL VAMC
Solicitation number
36C77625B0006
Issued by

About this file

This document is a comprehensive mechanical (HVAC) design drawing set for the Lake City VA Medical Center's EHRM Infrastructure Upgrades project. The drawings detail mechanical system replacements across multiple buildings, focusing on replacing existing HVAC equipment in telecom rooms with new ductless split systems, fan coil units, and computer room air conditioning (CRAC) units. The project involves installing numerous Mitsubishi ductless split system units with wall-mounted indoor units and outdoor condensing units, ranging from 12,000 to 36,000 BTU capacities, across basement, first, second, third, and fourth floor locations in buildings B18, B19, B37, B38, B42, B44, B62, B64, B74, B82, B91, and B92.

The solicitation is a Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside competitive procurement with a construction value between $20 million and $50 million. The project requires comprehensive HVAC infrastructure upgrades, including removing existing equipment, routing new refrigerant and condensate piping, installing new air handling units, and integrating systems with the building automation system. The mechanical designs specify detailed requirements for equipment mounting, piping routing, control systems, and compliance with various codes including VA design manuals, International Building Code, and ASHRAE standards. The project is being managed by the Department of Veterans Affairs Technology Acquisition Center Austin and is located at 619 South Marion Avenue, Lake City, FL.

View the file

Other files

File Type Posted
Online Bid Opening Meeting Info.docx DOCX document
Amendment 5 - 36C77625B0006 0005 6-30-25.pdf PDF
Construction Wage Rates - Columbia 6-27-2025.pdf PDF
Brand Name Justification - Lake City - Rev 2 0 - Redacted.pdf PDF
Amendment 4 - 36C77625B0006 0004 6-25-25.pdf PDF
Brand Name Justification - Lake City EHRM - SIGNED_Redacted.pdf PDF
Amendment 3 - 36C77625B0006 0003 6-11-25.pdf PDF
573A4-21-700 Lake City - RFI TRACKING SHEET REV2 36C77625B0006 6-10-25.xlsx XLSX spreadsheet
573A4-21-700 Lake City - Addendum No. 1.pdf PDF
260526-EDITED Grnd shop marked up.docx DOCX document
260533-EDITED Raceway shop marked up.docx DOCX document
260519-EDITED Low Volt cond cab shop marked updocx.docx DOCX document
262726-EDITED Wire Dev shop marked up.docx DOCX document
Construction Wage Rates - Columbia 5-2-2025.pdf PDF
262416-EDITED Panelboards shop marked up.docx DOCX document
Amendment 2 - 36C77625B0006 0002 5-27-2025.pdf PDF
Site Visit Sign-in - 573A4-21-700 Attendance 250423.pdf PDF
Amendment 1 - 36C77625B0006 0001 4-24-25.pdf PDF
Attachment 15 - Construction Wage Rates - Columbia.pdf PDF
Attachment 8 - Final Drawing Set - 7a of 8.pdf PDF
Attachment 14 - PreConstruction Risk Assessment - Lake City.docx DOCX document
Attachment 5 - Final Drawing Set - 4 of 8.pdf PDF
Attachment 9 - Final Drawing Set - 7b of 8.pdf PDF
Attachment 10 - Final Drawing Set - 7c of 8.pdf PDF
Attachment 7 - Final Drawing Set - 6 of 8.pdf PDF
Attachment 6 - Final Drawing Set - 5 of 8.pdf PDF
Attachment 12 - Final Drawing Set - 8 of 8.pdf PDF
Attachment 1 - Final Specs Set - R4.pdf PDF
Attachment 13 - Asbestos and Lead Paint Survey Report.pdf PDF
Attachment 11 - Final Drawing Set - 7d of 8.pdf PDF
Attachment 17 - Site Visit Instructions.pdf PDF
Attachment 3 - Final Drawing Set - 2 of 8.pdf PDF
Attachment 16 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 2 - Final Drawing Set - 1 of 8.pdf PDF
IFB 36C77625B0006.pdf PDF
Attachment 18 - RFI TRACKING SHEET - SOLICITATION 36C77625B0006 - Project 573A4-21-700.xlsx XLSX spreadsheet
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPIN-IN TAKE-OFF

RECTANGLE-TO-ROUND TAKE-OFF

DNUP

CEILING EXHAUST

CEILING RETURN

STANDARD BRANCH TAKE-OFF

FLEXIBLE DUCT

CHANGE OF ELEVATION

TRANSITION, CONCENTRIC

RECTANGULAR/ROUND BRANCH TAKE-OFF

OR ROUND/ROUND BRANCH TAKE-OFF

SUPPLY DIFFUSER OR GRILLE (VERTICAL

MOUNT, SIDEWALL)

RETURN/EXHAUST REGISTER OR GRILLE

(VERTICAL MOUNT, SIDEWALL)

CEILING DIFFUSER, ROUND NECK

(CEILING DIFFUSERS ARE 4-WAY THROW UNO)

CEILING DIFFUSER, RECTANGULAR OR SQUARE

NECK (CEILING DIFFUSERS ARE 4-WAY THROW

UNO)

HVAC ABBREVIATIONSHVAC SYMBOL LEGEND

SYMBOLSYMBOL DESCRIPTION SYMBOL SYMBOL DESCRIPTION

CONDENSATE

CHILLED WATER RETURN

HEATING HOT WATER SUPPLY

CHILLED WATER SUPPLY

HEATING HOT WATER RETURN

PIPING LEGEND

SYMBOLSYMBOL DESCRIPTION

HHWS

HHWR

CHWS

CHWR

CND

ELBOW, TURNED DOWN

CAP

ELBOW, 90°

ELBOW, TURNED UP

TEE, OUTLET DOWN

ELBOW, 45°

TEE, OUTLET UP

45° PIPE RISE (R)/DROP (D)

CONCENTRIC REDUCER

R R

FLANGES

FLOW DIRECTION

UNION

THERMOMETER

MANUAL VENT

EQUIP. P-TRAP

CONTROLS LEGEND

FLOW SWITCH

PRESSURE SWITCH

AUTOMATIC AIR VENT

MANUAL BALANCING DAMPER

DOOR GRILLE

UNDERCUT DOOR

DUCT ELBOW, RETURN AIR

DUCT ELBOW, EXHAUST AIR

DUCT ELBOW, SUPPLY OR OUTSIDE AIR

NEW DUCTWORK, FIRST DIMENSION IS

SIDE SHOWN

TEMPERATURE SENSOR

MOTORIZED CONTROL DAMPER

HUMIDISTAT / HUMIDITY SENSOR

THERMOSTAT / TEMPERATURE SENSOR

STATIC PRESSURE SENSOR

DUCT SMOKE DETECTOR

BACKDRAFT DAMPER

CEILING MOUNTED ACCESS DOOR

T

H

DOWN UP

UC

M

T

SP

BD

HUMIDITY SENSOR (DUCT MOUNTED)H

1. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS. PROVIDE

COMPONENTS INDICATED IN DETAILS, RISER DIAGRAMS, CONTROL DIAGRAMS, AND/OR FLOW

DIAGRAMS WHETHER OR NOT INDICATED ON PLANS AND VICE VERSA. WHERE A DISCREPANCY OR

CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR BETWEEN A DRAWING AND

APPLICABLE SPECIFICATIONS, NOTIFY THE COR IMMEDIATELY IN WRITTEN FORM. IN GENERAL, THE

MOST STRINGENT REQUIREMENT SHALL GOVERN UNLESS THE DISCREPANCY CONFLICTS WITH

APPLICABLE CODES OR OWNER'S DESIGN STANDARDS, WHEREIN THE CODE OR OWNER'S DESIGN

STANDARDS SHALL GOVERN.

2. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED DRAWINGS.

TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR EQUIPMENT FURNISHED.

3. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR

FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS

SUCH AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO

OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST.

4. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE SMACNA HVAC

DUCT CONSTRUCTION STANDARD.

5. PROVIDE 1.5R ELBOWS IN DUCTWORK AS INDICATED. IF 1.5R ELBOWS DO NOT FIT, PROVIDE 1.0R ELBOWS. IF 1.0R ELBOWS DO NOT FIT, PROVIDE 90 DEGREE RECTANGULAR DUCT ELBOWS WITH

TURNING VANES.

6. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, AND HUMIDITY SENSORS AT 48" +/- 6" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER

EQUIPMENT, FURNITURE, AND DOOR SWINGS.

7. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED.

PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID

INSTALLATION.

8. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.

9. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.

10. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED FOR

PROPER DRAINAGE TO SUIT EQUIPMENT FURNISHED.

11. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR

OPERATION, BALANCING OR MAINTENANCE OF ALL MECHANICAL EQUIPMENT.

12. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING

VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL

TRANSITION TO FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT.

13. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO FANS, AIR HANDLING

UNITS, AND FAN COIL UNITS.

14. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF FLEX DUCTS TO BE

CONNECTED.

15. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS.

16. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC., AND

ALL FIRE RATED AND FIRE/SMOKE RATED PARTITIONS, TO ALLOW FOR INSPECTIONS OF RATED

WALLS.

17. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS SHALL BE INDEPENDENTLY PIPED

FULL SIZE TO THE NEAREST PLUMBING DRAIN.

MECHANICAL GENERAL NOTES

AIRFLOW SENSOR/STATIONF

24x12

VD

APPLICABLE CODES

1. VA HVAC DESIGN MANUAL - MAY 1, 2023 EDITION

2. VA PLUMBING DESIGN MANUAL - JAN 1, 2023 EDITION

3. VA FIRE PROTECTION DESIGN MANUAL - JUNE 1, 2021 EDITION

4. VA INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES - JUNE 1, 2023 EDITION

5. GENERIC SMALL CAMPUS SUPPORT CENTER DESIGN PORTFOLIO - MAY 17, 2021

6. HEFP SEP (SOCAMES 6) DESIGN ALERT 8

7. INTERNATIONAL BUILDING CODE (IBC) 2021 EDITION

8. INTERNATIONAL MECHANICAL CODE (IMC) 2021 EDITION

9. INTERNATIONAL PLUMBING CODE (IPC) 2021 EDITION

10. INTERNATIONAL FUEL AND GAS CODE (IFGC) 2021 EDITION

11. INTERNATIONAL ENERGY CONSERVATION CODE (IECC) 2021 EDITION

12. AMERICAN SOCIETY OF HEATING, REFRIGERATION AND AIR-CONDITIONING ENGINEERS (ASHRAE):

A. SAFETY STANDARD FOR REFRIGERATION SYSTEMS (ASHRAE 15 & 34) 2022 EDITION

B. VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY (ASHRAE 62.1) 2022 EDITION

C. ENERGY STANDARD FOR BUILDINGS (ASHRAE 90.1) 2022 EDITION

D. VENTILATION OF HEALTH CARE FACILITIES (ASHRAE 170) 2021 2017 EDITION

13. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), INCLUDING (BUT NOT LIMITED TO):

A. COMPRESSED GASES AND CRYOGENIC FLUIDS CODE, NFPA 55 2023 EDITION

B. NATIONAL ELECTRICAL CODE (NEC) 2023 EDITION

C. NATIONAL FIRE ALARM CODE (NFPA 72) 2022 EDITION

D. STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS (NFPA

90A) 2021 EDITION

E. HEALTH CARE FACILITIES CODE (NFPA 99) 2021 EDITION

F. LIFE SAFETY CODE (NFPA 101) 2021 EDITION

G. CLEAN AGENT FIRE EXTINGUISHING SYSTEMS (NFPA 2001) 2022 EDITION

14. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), INCLUDING (BUT NOT LIMITED TO):

A. OCCUPATIONAL HEALTH AND SAFETY MANAGEMENT SYSTEMS (Z10) 2019 EDITION

15. SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION (SMACNA)

16. OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)

17. AMERICANS WITH DISABILITIES ACT (ADA)

18. AMERICAN SOCIETY OF TESTING AND MATERIALS (ASTM)

19. AIR MOVEMENT AND CONTROL ASSOCIATION (AMCA)

20. APPLICABLE STANDARDS, REGULATIONS, AND PRACTICES OF THE VA SUSTAINABLE DESIGN

MANUAL 2017 EDITION

DESCRIPTIONDESCRIPTION

ADA -AMERICANS WITH DISABILITIES ACT

AFF -ABOVE FINISHED FLOOR

AFR -ABOVE FINISHED ROOF

AHU -AIR HANDLING UNIT

AP -ACCESS PANEL

APPROX -APPROXIMATE

ASTM -AMERICAN STANDARDS TESTING MATERIALS

BAS -BUILDING AUTOMATION SYSTEM

BOP -BOTTOM OF PIPE

BHP -BRAKE HORSEPOWER

BFV -BUTTERFLY VALVE

BTU -BRITISH THERMAL UNIT

CAV -CONSTANT AIR VOLUME

CFM -CUBIC FEET PER MINUTE

CD -CONDENSATE

CL -CENTER LINE

CO -CLEAN OUT

COR -CONTRACTING OFFICER'S REPRESENTATIVE

CRAC -COMPUTER ROOM AIR CONDITIONER

CU -CONDENSING UNIT

DB -DRY BULB

DDC -DIRECT DIGITAL CONTROLS

DN -DOWN

EA -EXHAUST AIR

EAT -ENTERING AIR TEMPERATURE

ECC -ENGINEERING CONTROL CENTER

EER -ENERGY EFFICIENCY RATING

EQUIP -EQUIPMENT

ESP -EXTERNAL STATIC PRESSURE

ETR -EXISTING TO REMAIN

EWT -ENTERING WATER TEMPERATURE

EX -EXISTING

ºF -DEGREES FAHRENHEIT

FAS -FIRE ALARM SYSTEM

FCU -FAN COIL UNIT

FD -FLOOR DAMPER

FE -FLUE EXHAUST

FLA -FULL LOAD AMPS

FPM -FEET PER MINUTE

FT -FEET

GPM -GALLONS PER MINUTE

HP -HORSEPOWER

HR -HOUR

HZ -HERTZ

IDU -INDOOR UNIT

IPLV -INTEGRATED PART-LOAD VALUE

IN -INCHES

KW -KILOWATT

LAT -LEAVING AIR TEMPERATURE

LWT -LEAVING WATER TEMPERATURE

MAX -MAXIMUM

MBH -THOUSAND BTUs PER HOUR

MCA -MINIMUM CIRCUIT AMPS

MIN -MINIMUM

MOCP -MAXIMUM OVER CURRENT PROTECTION

MOD -MOTORIZED CONTROL DAMPER

NA -NOT APPLICABLE

NC -NORMALLY CLOSED

NIC -NOT IN CONTRACT

NO -NORMALLY OPEN

NTS -NOT TO SCALE

OA -OUTSIDE AIR

OAT -OUTSIDE AIR TEMPERATURE

ODU -OUTDOOR UNIT

PH -PHASE

PRV -PRESSURE REDUCING VALVE

PRS -PRESSURE REDUCING STATION

PSI -POUNDS PER SQUARE INCH

PSIG -PSI GAUGE

PTAC -PACKAGED TERMINAL AIR CONDITIONER

PVC -POLYVINYL CHLORIDE PIPE

RA -RETURN AIR

RH -RELATIVE HUMIDITY

RHP -ROOFTOP HEAT PUMP

RPM -REVOLUTIONS PER MINUTE

RS/L -REFRIGERANT SUCTION & LIQUID LINES

RTU -ROOFTOP AIR CONDITIONING UNIT

RX -REMOVE EXISTING

SA -SUPPLY AIR

SF -SQUARE FEET

SP -STATIC PRESSURE

SPEC -SPECIFICATION

SS -STAINLESS STEEL

STD -STANDARD

TA -TRANSFER AIR

TDH -TOTAL DYNAMIC HEAD

TEMP -TEMPERATURE

TSP -TOTAL STATIC PRESSURE

TU -TERMINAL UNIT

TYP -TYPICAL

UL -UNDERWRITER'S LABORATORY

U/G -UNDERGROUND

UNO -UNLESS NOTED OTHERWISE

V/PH -VOTS/PHASE

VA -U.S. DEPARTMENT OF VETERANS AFFAIRS

VAV -VARIABLE AIR VOLUME

VFD -VARIABLE FREQUENCY DRIVE

VRF -VARIABLE REFRIGERANT FLOW

W -WATTS

W/ -WITH

WB -WET BULB

NOTE: SOME SYMBOLS SHOWN MAY NOT PERTAIN TO THIS PROJECT

DOMESTIC COLD WATERCW

TEE, SIDE CONNECTION

CIRCUIT SETTER VALVE

CHECK VALVE

GATE VALVE

BALL VALVE

GLOBE VALVE

MOTORIZED ACTUATOR

SOLENOID VALVE (2-POSTION

W/ ACTUATOR)

STRAINER

DESCRIPTION

REFRIGERANT SENSORR

BASIC MATERIALS

EXISTING TO BE REMOVED (HEAVY, DASHED LINE)

EXISTING TO REMAIN (THIN, HALFTONED, SOLID LINE)

NEW (HEAVY, SOLID LINE)

1. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS. PROVIDE COMPONENTS INDICATED IN DETAILS AND/OR RISER DIAGRAMS WHETHER OR NOT INDICATED ON PLANS AND VICE VERSA. WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING

AND ANOTHER, OR BETWEEN A DRAWING AND APPLICABLE SPECIFICATIONS, NOTIFY THE COR

IMMEDIATELY IN WRITTEN FORM. IN GENERAL, THE MOST STRINGENT REQUIREMENT SHALL GOVERN UNLESS THE DISCREPANCY CONFLICTS WITH APPLICABLE CODES OR OWNER'S DESIGN STANDARDS, WHEREIN THE CODE OR OWNER'S DESIGN STANDARDS SHALL GOVERN.

2. LOCATE VALVES IN ACCESSIBLE AREAS WHERE NECESSARY. (12"X12" MIN.)

3. COORDINATE ACTUAL LOCATIONS OF MECHANICAL FLOOR DRAINS WITH FINAL EQUIPMENT

LOCATIONS ON SHOP DRAWINGS.

4. VENT PIPING SHOWN IS ONLY FOR DIAGRAMMATIC PURPOSES. COORDINATE VTRS WITH HVAC AIR

INTAKES.

5. PROVIDE BACKWATER VALVES FOR CONDENSATE PIPING CONNECTIONS TO STORM SEWER.

6. PROVIDE PIPE MARKER FOR ALL PIPING ABOVE THE CEILING SPACES IN ACCORDANCE WITH DIVISION

22 SPECIFICATION SECTION. "IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT".

7. LABEL VALVES ABOVE CEILINGS AND IN CONCEALED SPACES AT CEILING TILE WITH METAL CEILING

TACKS INDICATING VALVE # AND TYPE OF WATER. (i.e.; BLUE= COLD WATER, LETTERING CW

VLV1-001).

8. FIRE CAULK AND SLEEVE PENETRATIONS THROUGH FIRE RATED ASSEMBLIES. REFER TO LIFE SAFETY PLANS FOR RATED ASSEMBLY LOCATIONS. REFER TO ARCHITECTURAL SHEETS FOR DETAILS AND UL

ASSEMBLY NUMBERS.

9. VALVES AND FITTINGS SHALL BE THE SAME SIZE AS THE PIPING WHERE THEY ARE LOCATED UNLESS

NOTED OTHERWISE.

10. PROVIDE ALL NECESSARY SUPPORTING DEVICES FOR FIXTURES PER MANUFACTURER INSTALLATION

INSTRUCTIONS.

11. SHOP DRAWING SUBMITTALS SHALL BE FULLY COORDINATED PRIOR TO SUBMITTAL.

PLUMBING NOTES

FIRE MAINFM

REFRIGERANT LIQUID AND SUCTION LINESRL/RS

DOMESTIC HOT WATERHW

DOMESTIC HOT WATER RETURNHWR

SANITARY VENTV

SANITARY WASTESAN

STORM DRAINST

ABBREVIATIONS

ADJ ADJUSTABLE

AI ANALOG INPUT

AO ANALOG OUTPUT

AV ANALOG VIRTUAL

AFS AIRFLOW STATION

AF AFTER FILTER

BAS BUILDING AUTOMATION SYSTEM

BI BINARY INPUT

BO BINARY OUTPUT

BV BINARY VIRTUAL

BP BUILDING PRESSURE

BPC BUILDING PRESSURE CONTROL

CC COOLING COIL

CP CIRCULATING PUMP

CT CURRENT TRANSMITTER

DD DIRECT DRIVE

DX DIRECT EXPANSION

DP DIFFERENTIAL PRESSURE

EAT ENTERING AIR TEMPERATURE

ECM ELECTRONICALLY COMMUTATED MOTOR

EF EXHAUST FAN

ER ENERGY RECOVERY

FF FINAL FILTER

FSD FIRE SMOKE DAMPER

HC HEATING COIL

IFB INTEGRAL FACE AND BYPASS

LAT LEAVING AIR TEMPERATURE

LWT LEAVING WATER TEMPERATURE

MAT MIXED AIR TEMPERATURE

MOA MINIMUM OUTSIDE AIR

OBC ON BOARD CONTROLS

OCC OCCUPANCY

PF PREFILTER

PHC PREHEAT COIL

RA RETURN AIR

RF RETURN FAN

RHC REHEAT COIL

R/E RETURN/EXHAUST

R/R RETURN/RELIEF

SF SUPPLY FAN

SD SMOKE DAMPER

TCC TEMPERATURE CONTROL CONTRACTOR

TCP TEMPERATURE CONTROL PANEL

TMV THERMOSTATIC MIXING VALVE

TCV TEMPERATURE CONTROL VALVE

UV ULTRAVIOLET

HUMIDIFIER DISPERSION GRID

FILTER

BLOWER FAN

XX XXXX

POINT TYPE

POINT NAME

T - ZONE TEMPERATURE SENSOR

H - ZONE HUMIDITY SENSOR

O - ZONE OCCUPANCY SENSORT

SD

AFS

T

H

H

L

H

L

FRZ

H L

SUPPLY AIR DUCT STATIC PRESSURE

SENSOR

RETURN/EXHAUST AIR DUCT STATIC

PRESSURE SENSOR

DIFFERENTIAL PRESSURE SENSOR

DAMPER POSITION INDICATOR

HUMIDITY SENSOR

FREEZESTAT

TEMPERATURE SENSOR

SMOKE DETECTOR

AIRFLOW STATION

AIRFLOW SENSOR

MODULATING VAV CONTROL

DAMPER

M

DIRECT EXPANSION COOLING COILD

X

CC / HC

CHILLED WATER COOLING /

HEATING HOT WATER COIL

M MOTORIZED CONTROL VALVE

DESIGN CRITERIA

LOCATION -LAKE CITY, FL

WEATHER STATION -GAINESVILLE REGIONAL AP

SUMMER DESIGN (0.4%) -93.4°F DB / 76.4°F WB

DEHUMIDIFICATION (0.4%) -82.8°F DB / 77.3°F DP

WINTER DESIGN (99.6%) -29.6°F DB

ANNUAL EXTREME (MEAN) -97.3°F DB MAX. / 23.4°F DB MIN.

INDOOR RELATIVE HUMIDITY -60% MAX. / 30% MIN.

TELECOM ROOM SETPOINTS -81°F DB MAX. / 64°F DB MIN.

TELEPHONE ROOM SETPOINTS -81°F DB MAX. / 64°F DB MIN.

DATA CENTER SETPOINTS -79°F DB MAX. / 72°F DB MIN.

CONNECT TO EXISTING

DEMOLISH TO POINT INDICATED

B64-3-IDU-1-300

B19-TU-8-1-200

VIEW NUMBER

DRAWING NUMBER WHERE SHOWN

SECTION LETTER

TYPICAL UNIT NUMBER; IDU NO. 1, SERVING ROOM 300, LOCATED ON

LEVEL 3, LOCATED IN BLDG. 2

BUILDING NO. WHERE EQUIPMENT IS LOCATED.

ROOM NUMBER

EQUIPMENT ABBREVIATION. AN "EX" SHOWN IN FRONT OF EQUIPMENT

TAGS NOTIFIES THAT EQUIPMENT IS EXISTING.

ROOM NUMBER

ITEM (TERMINAL UNIT SHOWN)

BUILDING NO. WHERE EQUIPMENT IS LOCATED

H1

H1

A

SHEET NUMBER

S1 200

DEVICE MARK AND NUMBER (S = SUPPLY, R = RETURN, E = EXHAUST)

DEVICE FLOW RATE (CFM)

12X10 SA

DUCT DIMENSION (INCHES). FIRST DIMENSION IS SIDE SHOWN.

TYPICAL AIR DISTRIBUTION DEVICE TAG

TYPICAL DUCTWORK TAG

SYSTEM TYPE (SA = SUPPLY AIR , RA = RETURN AIR, OA = OUTSIDE AIR,

EA = EXHAUST AIR)

LEVEL EQUIPMENT LOCATED ON / LEVEL IT SERVES

DRAWING SYMBOLS

REVISION REFERENCE1

SHEET NOTE CALLOUT1

SERVED BY AIR HANDLER UNIT NO. 8

ITEM NUMBER (TERMINAL UNIT NO. 1)

TYPICAL UNIT NUMBER; TU NO. 1, SERVING ROOM 200, SERVED BY

AHU-8, LOCATED IN BLDG. 19

UNIT NUMBER

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

SHEET LIST

SHEET NUMBER SHEET NAME

M-001 MECHANICAL NOTES, LEGENDS, & SYMBOLS

MH1.B BASEMENT - ZONES - MECHANICAL

MH1.B.1 BLDG 64 - LV B - ZONES 2 & 3 - MECHANICAL PLANS

MH1.B.2 BLDG 19 & 64 - LV B - ZONES 6 & 7 - MECHANICAL PLANS

MH1.B.3 BLDG 74 & 82 - LV B - ZONES 9 & 12a - MECHANICAL PLANS

MH1.B.4 BLDG 66 - LV B - ZONE 11 - MECHANICAL PLANS

MH1.1 FIRST FLOOR - ZONES - MECHANICAL

MH1.1.1 BLDG 64-A, B, & 91 - LV 1 - ZONE 2 & 3 - MECHANICAL PLANS

MH1.1.2 BLDG 38 & 64 - LV 1 - ZONE 5 & 6 - MECHANICAL PLANS

MH1.1.3 BLDG 19 & 82 - LV 1 - ZONE 7 & 9 - MECHANICAL PLANS

MH1.1.4 BLDG 6, 27, 37, 62 - LV 1 - ZONES 11, 12, 14 - MECHANICAL PLANS

MH1.1.5 BLDG 18, 42, 44, 92 - LV 1 - ZONE 15 - MECHANICAL PLANS

MH1.2 SECOND FLOOR - ZONES - MECHANICAL

MH1.2.1 BLDG 64 - LV 2 - ZONE 2 & 3 - MECHANICAL PLANS

MH1.2.2 BLDG 38, 62, 82 - LV 2 - ZONES 5, 9, 12 - MECHANICAL PLANS

MH1.3 THIRD FLOOR - ZONES - MECHANICAL

MH1.3.1 BLDG 38, 64, 82 - LV 3 - ZONES 3, 5, 9 - MECHANICAL PLANS

MH1.4 FOURTH FLOOR - ZONES - MECHANICAL

MH1.4.1 BLDG 64 - LV 4 - ZONE 2 - MECHANICAL PLANS

M-501 MECHANICAL DETAILS

M-502 MECHANICAL DETAILS

M-701 MECHANICAL CONTROLS

M-801 MECHANICAL SCHEDULES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:0

:3

P

M

M-001

MECHANICAL NOTES, LEGENDS, &

SYMBOLS

LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

STATION CHIEF - EDWIN BURNETT

10/25/2024 GSC CSC

100% CONSTRUCTION

DOCUMENTS

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523 Revisions Date

12/31/2024

57a

S1

Q1RST

MH1.B.4

MH1.B.3

MH1.B.2

MH1.B.1

MH1.B.1

MH1.B.2

B38 [5]

B64-A[4]

B64-2[6]

B64-2 [1]

B64-B [2] B64-A [3]

B82 [9] B82 [8]

B19 [7]

B64-D[10]

B66 [11]

B74 [13]

B62 [12B]

B62 [12A]

MH1.B.2

MH1.B.2

MH1.B.1

MH1.B.1

MH1.B.3

MH1.B.4

TELECOM RM

BB01

TELECOM RM

TELECOM RM

6B

TELECOM RM

B-10

TELECOM RM

164D

DATA CENTER

AB18H

MH1.B.3

MH1.B.3

ELECTRICAL

B2

MECHANICAL

B1

STAIR 1

4A1

B82 [8]

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:0

:5

P

M

MH1.B

BASEMENT - ZONES -

MECHANICAL

LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

STATION CHIEF - EDWIN BURNETT

10/25/2024 GSC CSC

100% CONSTRUCTION

DOCUMENTS

NN

0 15' 30' 60' 90'

1" = 30'

DRAWING NOTES:

1. FLOOR PLAN SHOWN FOR INFORMATIONAL PURPOSES ONLY. REFER TO ENLARGED PLANS FOR

ADDITIONAL INFORMATION.

1" = 30'-0"

LOWER LEVEL - ZONES - MECHANICAL

1" = 30'-0"2

B82 - ZONE 8 - BASEMENT - MECHANICAL

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523

KEY PLAN

B38

B19

B62

B74

B82

B64A

B64B

B64D

B64-2

B64-66

T/H

B64-IDU-B-AB02A

B64-A[4]

B64-A[3]

EX 14x14 SA

EX 18x10 RA

RL

RS

1" CND

T T-05

T

MECH

AB09E

OFFICE

AB09B

EMS STORAGE

AB01

TELECOM RM

AB02A

FA SYSTEM/ENG

STOR

AB02

CORRIDOR

CB-3

CORRIDOR

CB-3

ELEC

AB03

ELEC

AB24

MECH EQUIP

AB05

3/4" CND

TOILET MEN

BB02

TOILET WOMEN

BB04

CORRIDOR

CB-7

H.A.C.

BB05

ELEVATOR LOBBY

CB-8

M.S.D. STORAGE

BB07

EQUIPMENT

CB2A

TOILET MEN

CB4

TOILET WOMEN

CB5

CORRIDOR

CB-2

ELEVATOR LOBBY

CB-1

T/H

EX 2" STM

EX 2" CHWS

EX 2" CHWR

EX 2" HHWR

EX 2" HHWS

B64-FCU-B-BB01

B64-2[1]

B64-B[2]

1" CHWS

1" CHWR

1" CND

T

1" CND

S

TELECOM RM

BB01

1" HW

1 1/2" CW

1 1/2" HW

TOILET MEN

BB02

TOILET WOMEN

BB04

CORRIDOR

CB-7

H.A.C.

BB05

ELEVATOR LOBBY

CB-8

M.S.D. STORAGE

BB07

CONFERENCE ROOM

& TRAINING

BB01

EQUIPMENT

CB2A

TOILET MEN

CB4

TOILET WOMEN

CB5

CORRIDOR

CB-2

ELEVATOR LOBBY

CB-1

B64-2[1]

B64-B[2]

R X

3/ 4"

R X

3/ 4"

RX 1 1/2"

RX 1 1/2"

EX 2" STM

EX 2" CHWS

EX 2" CHWR

EX 2" HHWS

EX 2" HHWR103

128 RX 1"

RX 1"

1" CW

1" HW

1" CW

CORRIDOR

CORRIDOR

EMS STORAGE

AB01OFFICE

AB09B

ELEC

AB03

T T-05

B64-A[4]

B64-A[3]

FIRE ALARM

SYSTEM /

ENGINEERING

STORAGE

AB02

EX 3/4" CND

MECH

AB09E

B66[11]

B64-A[3]

B64-A[4]

B64-B[2]

B64-2[1] B64-D[10]

B64-2[6]

B19[7]

B82[9]

B82[8]

B38 [5]

B74[13]

B62[12A]

B62[12B]

DRAWING NOTES:

1. FINAL TESTING, ADJUSTING, AND BALANCING (TAB) FOR HVAC SHALL INCLUDE ALL HYDRONIC AND AIR SYSTEMS SHOWN IN DRAWINGS. REFER TO SECTION 23 05 93 FOR ADDITIONAL TAB REQUIREMENTS.

2. SPACE TEMPERATURE AND HUMIDITY SENSORS SHALL BE 48" +/- 6" AFF.

3. A SINGLE LINE IS USED TO INDICATE ALL REFRIGERANT PIPING ROUTED BETWEEN THE INDOOR AND OUTDOOR UNIT(S). THIS SINGLE LINE REPRESENTS ALL PIPING REQUIRED TO PROVIDE A COMPLETE

AND FUNCTIONING SYSTEM.

4. ROUTE ALL PIPING CONCEALED IN WALLS, CHASES, OR CEILING SPACES.

5. UNLESS OTHERWISE INDICATED, DEMOLITION OF EXISTING PIPING SHALL INCLUDE ALL DEVICES, HANGERS, SUPPORTS, ETC. ALL EXISTING PIPING WHICH WILL NO LONGER REMAIN IN SERVICE SHALL BE REMOVED. ALL EXISTING PIPING TO REMAIN IN SERVICE SHALL BE CAPPED WHERE INDICATED. NO EXISTING PIPING SHALL BE LEFT OPEN. ANY IDENTIFIED DEADEND PIPING SHALL BE REMOVED BACK TO

THE MAINS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:0

:0

P

M

MH1.B.1

BLDG 64 - LV B - ZONES 2 & 3 -

MECHANICAL PLANS

LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

B64

STATION CHIEF - EDWIN BURNETT

10/25/2024 GSC CSC

100% CONSTRUCTION

DOCUMENTS

NN

0 4' 8' 12' 16'

3/16" = 1'-0"

3/16" = 1'-0"4

B64 ZONE 3 - LEVEL B - TELECOM RM AB02A - MECHANICAL - NEW

3/16" = 1'-0"

B64 ZONE 2 - LEVEL B - TELECOM RM BB01 - NEW

3/16" = 1'-0"

B64 ZONE 2 - LEVEL B - CONFERENCE RM BB01 - DEMOLITION

3/16" = 1'-0"3

B64 ZONE 3 - LEVEL B - TELECOM RM AB02A - DEMOLITION

CODED NOTES:

102 PROVIDE DRAIN PANS WITH OVERFLOW SWITCH BENEATH ALL EXPOSED PIPING INSIDE DATA / TELECOM

ROOMS. FABRICATE DRAIN PANS SO THEY SLOPE TO THE HORIZONTAL CONNECTION POINT SHOWN.

CONDENSATE ROUTING AND TERMINATION SHALL BE AS SHOWN AND/OR NOTED ON DRAWINGS. SEE DRAIN

PAN DETAIL 8/M-501.

103 REMOVE EXISTING PIPING ROUTED THROUGH DATA / TELECOM ROOM AND REROUTE WITH NEW PIPING AS SHOWN. COORDINATE THE SHUTDOWN OF SYSTEMS AND SPACES AFFECTED WITH THE VA CONSTRUCTION

REPRESENTATIVE. ROUTE ALL RELOCATED PIPING CONCEALED ABOVE CEILING.

104 ROUTE CONDENSATE PIPING TO NEAREST FLOOR DRAIN. REFER TO DETAIL 11/M-501.

105 ROUTE REFRIGERANT PIPING UP TO CONDENSING UNIT ON ROOF OF B91. ROUTE ABOVE EXISTING DUCT INTO CHASE AND UP THROUGH ROOF. INSTALL, ROUTE, AND SIZE LINESET PER MANUFACTURER'S

RECOMMENDATIONS.

109 CONNECT NEW CHILLED WATER PIPING TO EXISTING PIPING IN WALL OR ABOVE CEILING. PROVIDE

ISOLATION VALVES AT CONNECTION TO EXISTING. REFER TO DETAILS FOR COIL CONNECTION

INFORMATION.

125 ROUTE CONDENSATE PIPING TO MOP SINK. SEE CONDENSATE MOP SINK DETAIL 5/M-502.

126 PROVIDE A WATER SENSOR AT THE LOWEST POINT OF THE DRAIN PAN. SENSOR SHALL ALARM TO THE BAS

IF WATER IS DETECTED. SEE DRAIN PAN DETAIL 8/M-501.

128 REMOVE EXISTING SUPPLY/RETURN/EXHAUST GRILLE AND ASSOCIATED DUCTWORK BACK TO ACTIVE MAIN.

CAP AND SEAL DUCTWORK AT POINT OF REMOVAL.

133 INSTALL BOTTOM OF DUCTLESS SPLIT INDOOR UNIT 88" ABOVE FINISHED FLOOR. COORDINATE EXACT

LOCATION WITH TELECOM CONTRACTOR.

134 INSTALL FAN COIL UNIT 24" ABOVE FINISHED FLOOR. ROUTE CHILLED WATER PIPING DOWN IN WALL TO FCU CHILLED WATER PIPING CONNECTIONS. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. ROUTE 1"

CONDENSATE FROM INTEGRAL CONDENSATE PUMP TO LOCATION SHOWN.

158 EXISTING CONDENSATE PIPING IS TO REMAIN AND IS ROUTED AT APPROXIMATELY 36" AFF.

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523

H.A.C.

CB13

ELEC

CB14

CORRIDOR

CB-6

CORRIDOR

CB-5

PHARMACY SUPPLY

CB11

LABOR RELATIONS

CB12

MECHANICAL ROOM

CB10

T/H

T

S126 ø

S A x1

R

A

B64-FCU-C10B

COMPUTER

STORAGE

C10A

TELECOM RM

6B

1" CND

EX 3" CW

H.A.C.

CB13

ELEC

CB14

CORRIDOR

CB-6

CORRIDOR

CB-5

PHARMACY SUPPLY

CB11

LABOR RELATIONS

CB12

MECHANICAL ROOM

CB10

RX FCU-66

E X

8ø

S A

COMPUTER

STORAGE

C10A

E X

6x

R

A

1 1/2" HW

2" CW

EX 3" CW

TELECOM RM

B-10

A&B SECTION

B-11

OFFICE

B-11A

OFFICE

B-9

TELECOM RM

B-9B

OFFICE

B-8

OFFICE

B-7

CORRIDOR

OFFICE

B-6

STORAGE RM

B-9A

CORRIDOR

T

T/H

T x1

S

A x1

R

A

1" CHWS

B19-FCU-B-B10

1" CHWR 1" CND

1" HHWR

1" HHWS

A&B SECTION

B-11

OFFICE

B-11A

OFFICE

B-9

TELECOM RM

B-9B

OFFICE

B-8

OFFICE

B-7

CORRIDOR

OFFICE

B-6

STORAGE RM

B-9A

CORRIDOR

OFFICE

B-10

B19-XFCU-B11

x1

S

A x1

R

A 141

1" CND

1" HHWR

1" HHWS

1" CHWR

1" CHWS

B66[11]

B64-A[3]

B64-A[4]

B64-B[2]

B64-2[1] B64-D[10]

B64-2[6]

B19[7]

B82[9]

B82[8]

B38 [5]

B74[13]

B62[12A]

B62[12B]

DRAWING NOTES:

1. FINAL TESTING, ADJUSTING, AND BALANCING (TAB) FOR HVAC SHALL INCLUDE ALL HYDRONIC AND AIR SYSTEMS SHOWN IN DRAWINGS. REFER TO SECTION 23 05 93 FOR ADDITIONAL TAB REQUIREMENTS.

2. SPACE TEMPERATURE AND HUMIDITY SENSORS SHALL BE 48" +/- 6" AFF.

3. A SINGLE LINE IS USED TO INDICATE ALL REFRIGERANT PIPING ROUTED BETWEEN THE INDOOR AND OUTDOOR UNIT(S). THIS SINGLE LINE REPRESENTS ALL PIPING REQUIRED TO PROVIDE A COMPLETE

AND FUNCTIONING SYSTEM.

4. ROUTE ALL PIPING CONCEALED IN WALLS, CHASES, OR CEILING SPACES.

5. UNLESS OTHERWISE INDICATED, DEMOLITION OF EXISTING PIPING SHALL INCLUDE ALL DEVICES, HANGERS, SUPPORTS, ETC. ALL EXISTING PIPING WHICH WILL NO LONGER REMAIN IN SERVICE SHALL BE REMOVED. ALL EXISTING PIPING TO REMAIN IN SERVICE SHALL BE CAPPED WHERE INDICATED. NO EXISTING PIPING SHALL BE LEFT OPEN. ANY IDENTIFIED DEADEND PIPING SHALL BE REMOVED BACK TO

THE MAINS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:0

:1

P

M

MH1.B.2

BLDG 19 & 64 - LV B - ZONES 6 & 7 -

MECHANICAL PLANS

LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

B19, B64

STATION CHIEF - EDWIN BURNETT

10/25/2024 GSC CSC

100% CONSTRUCTION

DOCUMENTS

NN

0 4' 8' 12' 16'

3/16" = 1'-0"

3/16" = 1'-0"2

B64 ZONE 6 - LEVEL B - TELECOM RM C10B - NEW

3/16" = 1'-0"1

B64 ZONE 6 - LEVEL B - COMPUTER STORAGE C10 - DEMOLITION

3/16" = 1'-0"4

B19 ZONE 7 - LEVEL B - TELECOM RM B-10 - NEW

3/16" = 1'-0"3

B19 ZONE 7 - LEVEL B - TELECOM RM B-9B - DEMOLITION

CODED NOTES:

102 PROVIDE DRAIN PANS WITH OVERFLOW SWITCH BENEATH ALL EXPOSED PIPING INSIDE DATA / TELECOM

ROOMS. FABRICATE DRAIN PANS SO THEY SLOPE TO THE HORIZONTAL CONNECTION POINT SHOWN.

CONDENSATE ROUTING AND TERMINATION SHALL BE AS SHOWN AND/OR NOTED ON DRAWINGS. SEE DRAIN

PAN DETAIL 8/M-501.

125 ROUTE CONDENSATE PIPING TO MOP SINK. SEE CONDENSATE MOP SINK DETAIL 5/M-502.

126 PROVIDE A WATER SENSOR AT THE LOWEST POINT OF THE DRAIN PAN. SENSOR SHALL ALARM TO THE BAS

IF WATER IS DETECTED. SEE DRAIN PAN DETAIL 8/M-501.

128 REMOVE EXISTING SUPPLY/RETURN/EXHAUST GRILLE AND ASSOCIATED DUCTWORK BACK TO ACTIVE MAIN.

CAP AND SEAL DUCTWORK AT POINT OF REMOVAL.

134 INSTALL FAN COIL UNIT 24" ABOVE FINISHED FLOOR. ROUTE CHILLED WATER PIPING DOWN IN WALL TO FCU CHILLED WATER PIPING CONNECTIONS. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. ROUTE 1"

CONDENSATE FROM INTEGRAL CONDENSATE PUMP TO LOCATION SHOWN.

141 RECORD EXISTING SUPPLY/RETURN/EXHAUST AIRFLOW AT EACH GRILLE PRIOR TO DEMOLITION.

142 REBALANCE EXISITNG SUPPLY/RETURN/EXHAUST GRILLES TO VALUE RECORDED IN PRE-DEMOLITION TEST

AND BALANCE.

151 REMOVE EXISITNG FAN COIL UNIT AND ALL ASSOCIATED PIPING, DUCTWORK, AND CONTROLS. PREPARE CHILLED WATER AND CONDENSATE PIPING IN WALL FOR CONNECTION TO NEW FCU IN NEW WORK PHASE.

157 INSTALL FAN COIL UNIT IN PLACE OF EXISTING FAN COIL UNIT TO BE REMOVED IN DEMOLITION PHASE.

CONNECT 1" CHILLED WATER AND 1" CONDENSATE PIPING TO PIPING PREPARED IN WALL IN DEMOLITION

PHASE. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

159 REMOVE EXISTING CHILLED AND HEATING WATER AND CONDENSATE PIPING BACK TO POINT INDICATED.

PROVIDE ISOLATION VALVES AND 6" PIPE STUB WITH CAP WHILE NEW PIPING IS BEING ROUTED.

COORDINATE UTILITY SHUTDOWN WITH COR PRIOR TO COMENCEMENT OF WORK IN THIS AREA.

160 PROVIDE NEW PIPING AND VALVE PACKAGES, TO INCLUDE CONTROL VALVES, FOR CHILLED AND HEATING WATER CONNECTIONS TO EXISTING FCU. REFER TO DETAIL 5/M-501 FOR COIL PIPING DETAIL.

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523

CORRIDOR

OCCUPATIONAL

ACTIVITIES

ALCOVE

LOBBY

CORRIDOR

TRASH ROOM

MEDICATION RM

SOILED LINENH.A.C.

ALCOVE

OFFICE

STORAGE

NURSES STATION

ELEVATOR

P-4/82

ELEVATOR

P-3/82

TELECOM RM

TELECOM RM

T/H

EX 1 1/2" HHWR

EX 1 1/2" HHWS

EX 2" CHWR

EX 2" CHWS

B82[9]

B82[8]

B82[9] B82[8]

2 1/2" CW

2 1/2" HW

2" HWR

1/2" CW

1/2" HW

EX 1/2" CW

EX 1/2" HW

T

B82-FCU-B-164D

1" CND

S 126

B82-ODU-1-251A

MH1.B.3

CONTRACTOR SHALL FIELD VERIFY SPACE

ABOVE CEILING (SPECIFICALLY TRASH

CHUTES) AND COORDINATE THE WALL

PENETRATIONS TO AVOID OBSTACLES.

CORRIDOR

OCCUPATIONAL

ACTIVITIES

STORAGE

ALCOVE

LOBBY

CORRIDOR

TRASH ROOM

MEDICATION RM

CORRIDOR

C1-04

SOILED LINEN

H.A.C.

ALCOVE OFFICE

STORAGE

NURSES STATION

ELEVATOR

P-4/82

ELEVATOR

P-3/82T

EX 1 1/2" HHWR

EX 1 1/2" HHWS

EX 2" CHWR

EX 2" CHWS

B82[9]

B82[8]

B82[9] B82[8]

EX 2 1/2" CW

EX 2 1/2" HW

EX 2" HWR

EX 1/2" CW

EX 1/2" HW

RX FCU

CLEAN STORAGE

TELECOM RM

110A

MECHANICAL

EQUIPMENT

EX 16x16 SA

E X

6x

S

A

16x16 SA x1

S

A

B74-IDU-1-110A

B74-ODU-1-110A

RL

RS

CLEAN STORAGE

MECHANICAL

EQUIPMENT

EX 16x16 SA

EX 16x16 SA

B82-ODU-1-251A

RL

RS

B66[11]

B64-A[3]

B64-A[4]

B64-B[2]

B64-2[1] B64-D[10]

B64-2[6]

B19[7]

B82[9]

B82[8]

B38 [5]

B74[13]

B62[12A]

B62[12B]

DRAWING NOTES:

1. FINAL TESTING, ADJUSTING, AND BALANCING (TAB) FOR HVAC SHALL INCLUDE ALL HYDRONIC AND AIR SYSTEMS SHOWN IN DRAWINGS. REFER TO SECTION 23 05 93 FOR ADDITIONAL TAB REQUIREMENTS.

2. SPACE TEMPERATURE AND HUMIDITY SENSORS SHALL BE 48" +/- 6" AFF.

3. A SINGLE LINE IS USED TO INDICATE ALL REFRIGERANT PIPING ROUTED BETWEEN THE INDOOR AND OUTDOOR UNIT(S). THIS SINGLE LINE REPRESENTS ALL PIPING REQUIRED TO PROVIDE A COMPLETE

AND FUNCTIONING SYSTEM.

4. ROUTE ALL PIPING CONCEALED IN WALLS, CHASES, OR CEILING SPACES.

5. UNLESS OTHERWISE INDICATED, DEMOLITION OF EXISTING PIPING SHALL INCLUDE ALL DEVICES, HANGERS, SUPPORTS, ETC. ALL EXISTING PIPING WHICH WILL NO LONGER REMAIN IN SERVICE SHALL BE REMOVED. ALL EXISTING PIPING TO REMAIN IN SERVICE SHALL BE CAPPED WHERE INDICATED. NO EXISTING PIPING SHALL BE LEFT OPEN. ANY IDENTIFIED DEADEND PIPING SHALL BE REMOVED BACK TO

THE MAINS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:0

:2

P

M

MH1.B.3

BLDG 74 & 82 - LV B - ZONES 9 &

12a - MECHANICAL PLANS

LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

B62, B82

STATION CHIEF - EDWIN BURNETT

10/25/2024 GSC CSC

100% CONSTRUCTION

DOCUMENTS

NN

0 4' 8' 12' 16'

3/16" = 1'-0"

3/16" = 1'-0"2

B82 - ZONE 9 - LOWER LEVEL - TELECOM RM 164D - MECHANICAL - NEW

3/16" = 1'-0"1 B82 - ZONE 9 - LOWER LEVEL - OCCUPATIONAL ACTIVITIES 164 - MECHANICAL - DEMOLITION

CODED NOTES:

102 PROVIDE DRAIN PANS WITH OVERFLOW SWITCH BENEATH ALL EXPOSED PIPING INSIDE DATA / TELECOM

ROOMS. FABRICATE DRAIN PANS SO THEY SLOPE TO THE HORIZONTAL CONNECTION POINT SHOWN.

CONDENSATE ROUTING AND TERMINATION SHALL BE AS SHOWN AND/OR NOTED ON DRAWINGS. SEE

DRAIN PAN DETAIL 8/M-501.

103 REMOVE EXISTING PIPING ROUTED THROUGH DATA / TELECOM ROOM AND REROUTE WITH NEW PIPING AS

SHOWN. COORDINATE THE SHUTDOWN OF SYSTEMS AND SPACES AFFECTED WITH THE VA

CONSTRUCTION REPRESENTATIVE. ROUTE ALL RELOCATED PIPING CONCEALED ABOVE CEILING.

109 CONNECT NEW CHILLED WATER PIPING TO EXISTING PIPING IN WALL OR ABOVE CEILING. PROVIDE

ISOLATION VALVES AT CONNECTION TO EXISTING. REFER TO DETAILS FOR COIL CONNECTION

INFORMATION.

112 ROUTE CONDENSATE PIPING DOWN EXTERIOR WALL AND TERMINATE AT SPLASHBLOCK. REFER TO DETAIL 4/M-501.

113 DROP REFRIGERANT PIPING DOWN THROUGH FLOOR TO CEILING OF TR BELOW. ROUTE PIPING ABOVE

CEILING TO WALL MOUNTED OUTDOOR UNITS. REFER TO 3/MH1.B.3.

122 TIE CONDENSATE PIPING TO EXISTING CONDENSATE LINE FROM REMOVED FAN COIL UNIT.

126 PROVIDE A WATER SENSOR AT THE LOWEST POINT OF THE DRAIN PAN. SENSOR SHALL ALARM TO THE BAS

IF WATER IS DETECTED. SEE DRAIN PAN DETAIL 8/M-501.

131 REMOVE EXISITNG FAN COIL UNIT AND ALL ASSOCIATED PIPING, DUCTWORK, AND CONTROLS. REMOVE

PIPING BACK TO ACTIVE MAIN. CAP AND SEAL EXISTING DUCTWORK AT POINT OF REMOVAL.

134 INSTALL FAN COIL UNIT 24" ABOVE FINISHED FLOOR. ROUTE CHILLED WATER PIPING DOWN IN WALL TO FCU CHILLED WATER PIPING CONNECTIONS. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. ROUTE

1" CONDENSATE FROM INTEGRAL CONDENSATE PUMP TO LOCATION SHOWN.

137 INSTALL NEW REFRIGERANT LINESET AND SIZE PER MANUFACTURER'S REQUIREMENTS.

156 ROUTE REFRIGERANT PIPING DOWN TO WALL MOUNTED CONDENSING UNIT. COORDINATE PIPING

INSULATION COLOR WITH ARCHITECT. SEE SECTION VIEW 5 ON SHEET MH1.B.3.

161 DETERMINE AIRFLOW OF EXISTING AIR DEVICE. REMOVE DUCT TAP AND DUCT RUN-OUT TO EXISTING

SUPPLY GRILLE. RETAIN AND RE-USE EXISTING GRILLE IN NEW DUCT LAYOUT.

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523

3/16" = 1'-0"5

B74 - ZONE 13 - LOWER LEVEL - TELECOM RM 110A - MECHANICAL - NEW

3/16" = 1'-0"4

B74 - ZONE 13 - LOWER LEVEL - TELECOM RM 110A - MECHANICAL - DEMOLITION

3/16" = 1'-0"3

B82 - OUTDOOR UNIT SECTION

DATA CENTER

AB18H

WORKROOM

AB18G

CORRIDOR

AB18F

MECH

AB18K

U. P. S.

AB18J

RX

AHU-1

RX

AHU-2

T

T

T

EX

FCU

RX

AHU-5

RX

AHU-4

EX 1 1/2" FM

EX 1" FM

RX-CU-2

RX-CU-1

RX-CU-5

EXISTING CARDBOARD

COMPACTOR

MH1.B.4

EX 1 1/2" HHWR

EX 1 1/2" HHWS

EX 1 1/2" CHWR

EX 1 1/2" CHWS

EX 1" FM

EXISTING

AREA DRAIN

EXISTING AREA

DRAIN

REMOVE ABANDONED

LIGHT POLE AND BASE

EXISTING STEAM

TUNNEL

REMOVE EXISTING

TREE STUMP

R X

6x

R

X

6x

EX 16x16

EX 8ø

EX 1" FM

P2

P1

RX

EF

PATCH AND

REPAIR WALL

TEMPORARY

WALL

P2

P2

EX 3/4" CHWS

EX 3/4" CHWR

57a

S1

B66-CRAC-B-AB18HA

B66-CRAC-B-AB18HB

DATA CENTER

AB18H

B66-ACU-B-AB18HA

EX

FCU

SECT. / RECPT.

AB20

CHIEF EMS

AB20A

1" CND

SP1 800

SP1 800

SP1 800

SP1 800

SP1 800

SP1 800

SP1 800

SP1 800

SP1 800

SP1 800

SP1 800

SP1 800

SP1 800

SP1 800

SP1 800

SP1 800

EX 1 1/2" HHWR

EX 1 1/2" HHWS

EX 1 1/2" CHWS

EX 1 1/2" CHWR

EXISTING CARDBOARD

COMPACTOR

1" CND

MH1.B.4

OFFICE

AB18

1" CND

1" CND

1/4" CW

1/2" CW

1/2" CW

CONNECT NEW 1/2" DOMESTIC WATER LINE TO EXISTING

COLD WATER PIPING ABOVE CEILING IN TOILET 107A, IN B74

APPROXIMATELY 100 FEET AWAY.

UPS

AB18F

B66-ODU-B-AB18FA

SP1 800

SP1 800

SP1 800

SP1 800

RS

RL

B66-IDU-B-AB18FA

B66-IDU-B-AB18FB

B66-ODU-B-AB18FB

T/H

T/H

B66-EF-01

8x8 EA

S

TR 280

TR 280

EXISTING AREA

DRAIN

EXISTING AREA

DRAIN

EXISTING STEAM

TUNNEL

10ø SA

3/4" CND 1" CND

3/4" CND

RS

RL

NEW CONCRETE

EQUIPMENT PAD

NEW CONCRETE

EQUIPMENT PAD

B66-ACU-B-AB18HB

STORAGE

AB18JVEST

AB18L

MECH

AB18K

EX 3/4" CHWR

EX 3/4" CHWS

SD4 150

SD4 100

SD4 150

10x10 SA

T

B66-IDU-B-AB18K

B66-ODU-B-AB18K

P3

57a

S1

B66 - LOWER

LEVEL

132' - 10 7/16"

B66-CRAC-B-AB18HB

ABOVE CEILING

RETURN AIR PLENUM

UNDERFLOOR AIR

DISTRIBUTION

FLOOR DIFFUSER

RACK DISCHARGE FLUE

DUCT CONNECTION

FROM CRAC TO PLENUM

EH-1

B66[11]

B64-A[3]

B64-A[4]

B64-B[2]

B64-2[1] B64-D[10]

B64-2[6]

B19[7]

B82[9]

B82[8]

B38 [5]

B74[13]

B62[12A]

B62[12B]

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:4

:2

P

M

MH1.B.4

BLDG 66 - LV B - ZONE 11 -

MECHANICAL PLANS

LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

B66

STATION CHIEF - EDWIN BURNETT

10/25/2024 GSC CSC

100% CONSTRUCTION

DOCUMENTS

NN

0 4' 8' 12' 16'

3/16" = 1'-0"

DRAWING NOTES:

1. FINAL TESTING, ADJUSTING, AND BALANCING (TAB) FOR HVAC SHALL INCLUDE ALL HYDRONIC AND

AIR SYSTEMS SHOWN IN DRAWINGS. REFER TO SECTION 23 05 93 FOR ADDITIONAL TAB

REQUIREMENTS.

2. SPACE TEMPERATURE AND HUMIDITY SENSORS SHALL BE 48" +/- 6" AFF.

3. CRAC UNITS SHALL MAINTAIN AN AVERAGE RACK-FACE INLET TEMPERATURE RANGE OF 72°F TO 80.6°F. TOP (12" FROM TOP OF CABINET), MIDDLE (48" +/- 6" AFF), AND BOTTOM (12" AFF) SENSORS

MEASURING 2" FROM THE EQUIPMENT INLET SHALL BE AVERAGED TO MAINTAIN RACK INLET

TEMPERATURE.

4. A SINGLE LINE IS USED TO INDICATE ALL REFRIGERANT PIPING ROUTED BETWEEN THE INDOOR AND OUTDOOR UNIT(S). THIS SINGLE LINE REPRESENTS ALL PIPING REQUIRED TO PROVIDE A COMPLETE

AND FUNCTIONING SYSTEM.

5. ROUTE ALL PIPING CONCEALED IN WALLS, CHASES, OR CEILING SPACES.

3/16" = 1'-0"

B66 - LOWER LEVEL - COMPUTER RM AB18H - MECHANICAL - DEMOLITION

3/16" = 1'-0"

B66 - LOWER LEVEL - COMPUTER RM AB18H - MECHANICAL - NEW

CODED NOTES:

104 ROUTE CONDENSATE PIPING TO NEAREST FLOOR DRAIN. REFER TO DETAIL 11/M-501.

112 ROUTE CONDENSATE PIPING DOWN EXTERIOR WALL AND TERMINATE AT SPLASHBLOCK. REFER TO DETAIL 4/M-501.

117 PROVIDE HYDROGEN GAS MONITOR SIMILAR TO CTI CALIBRATION TECHNOLOGIES MODEL: GG-H2-EC-10000 ELECTROCHEMICAL. INTERLOCK GAS SENSOR WITH EXHAUST FAN (B66-EF-01) TO OPERATE WHEN HYDROGEN GAS LEVELS REACH 1% OF THE TOTAL VOLUME OF THE UPS ROOM PER NFPA 1, CHAPTER

52.3.6. INTERLOCK CONTROL DAMPER IN TRANSFER AIR DUCT TO OPEN WHEN EXHAUST FAN IS IN

OPERATION.

118 CLEAN AGENT FIRE PROTECTION PRESSURE RELIEF BACKDRAFT DAMPER AND ASSOCIATED DUCTWORK UP TO RELIEF AIR VENT ON ROOF. INITIAL BACKDRAFT DAMPER SHALL BE SET TO 0.2"WC. FINAL SETTING SHALL BE ADJUSTED AS DETERMINED BY THE TAB CONTRACTOR. RELIEF DAMPER TO MEET ALL NFPA

REQUIREMENTS.

121 INSTALL NEW REFRIGERANT LINESET AND SIZE PER MANUFACTURER'S REQUIREMENTS. ROUTE REFRIGERANT PIPING CONCEALED ABOVE CEILING. ROUTE CONDENSATE PIPING TO NEAREST FLOOR

DRAIN.

146 REMOVE EXISTING AIR HANDLING UNIT AND ALL ASSOCIATED PIPING, CONTROLS, AND OUTDOOR UNIT.

PATCH EXTERIOR PENETRATIONS TO MATCH EXISTING MATERIALS AND COLORS.

148 REMOVE ALL EXISTING DIFFUSERS/GRILLES, DUCTWORK, AIR HANDLERS, AND PIPING SERVING THE DATA CENTER. RELOCATE ALL EXISTING SERVICES PASSING THROUGH DATA CENTER OUTSIDE OF NEW DATA CENTER. EXISTING UNDERFLOOR DISTRIBUTION TO REMAIN FOR REUSE IN NEW WORK PHASE. REPARE

AND PATCH UNDERFLOOR DISTRIBUTION PLENUM AS NECESSARY.

149 INSTALL CRAC UNIT TO DISCHARGE AIR INTO UNDERFLOOR AIR DISTRIBUTION SYSTEM AND INTAKE AIR FROM ABOVE CEILING RETURN PLENUM. SIZE AND ROUTE REFRIGERANT PIPING TO CORRESPONDING CONDENSING UNIT PER MANUFACTURER'S RECOMMENDATIONS. DO NOT ROUTE PIPING DIRECTLY ABOVE

RACKS. SEE CRAC DOWNFLOW DETAIL 2/M-501.

150 RACK MOUNTED WIRED THERMOSTAT. PROVIDE ONE THERMOSTAT PER RACK. COORDINATE WITH

TELECOM CONTRACTOR.

163 REMOVE CHILLED WATER PIPING BACK TO THIS APPROXIMATE LOCATION AND CAP. PIPING TO EXISTING

FAN COIL UNIT IS TO REMAIN.

164 DUE TO LIMITED ACCESS, EXCAVATION FOR EQUIPMENT PAD PREPARATION SHALL BE DONE BY HAND.

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523

3/16" = 1'-0"3

B66 0 COMPUTER RM AB18H - SECTION VIEW - MECHANICAL - NEW

Revisions Date

PHASING NOTES:

REMOVE AHU-1 AND AHU-2 AFTER RACKS ARE RELOCATED INSIDE TEMPORARY WALL. AHU-4 AND

AHU-5 SHALL REMAIN TO CONDITION TEMPORARY SPACE.

CAP EXISTING DUCT AND REDISTRIBUTE AIR TO EXISTING AIR DEVICES REMAINING INSIDE TEMPORARY WALL. REMOVE AHU-4 AND AHU-5 ONLY AFTER CRAC UNIT B66-CRAC-B-AB18HA HAS BEEN INSTALLED

AND THE TEMPORARY WALL HAS BEEN REMOVED.

IN ADDITION TO THE EXISTING HVAC UNITS TO REMAIN IN SERVICE DURING THE RELOCATION OF EXISTING RACKS AND INSTALLATION OF NEW RACKS, PROVIDE A TEMPORARY PORTABLE HVAC UNIT.

P1

P2

P3

UP

MH1.1.2

MH1.1.2

MH1.1.3

MH1.1.1

MH1.1.1

MH1.1.3

B38 [5]

B64-A[4]

B64-2[6]

B64-2 [1]

B64-B [2] B64-A [3]

B82 [9] B82 [8]

B19 [7] B64-D[10]

B74 [13]

B62 [12B]

B62 [12A]

MH1.1.1

MH1.1.2

MH1.1.2

MH1.1.3

MH1.1.1

MH1.1.3

MH1.1.4

MH1.1.4

B6 [11]

TELECOM RM

B103

TELECOM RM

BH101

TELECOM RM

TELECOM RM

C128

TELECOM RM

TELECOM RM

251A

TELECOM RM

128A

B91-1[3]

5757a

S1

MH1.1.4

MH1.1.4

TELECOM ROOM

MH1.1.4

MH1.1.4

TELECOM ROOM

MH1.1.5

MH1.1.5

TELECOM RM

6A

MH1.1.5

MH1.1.5

4TELECOM RM

MH1.1.5

MH1.1.5

TELECOM ROOM

MH1.1.5

MH1.1.5

TELECOM RM

112C

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:0

:0

P

M

MH1.1

FIRST FLOOR - ZONES -

MECHANICAL

LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

STATION CHIEF - EDWIN BURNETT

10/25/2024 GSC CSC

100% CONSTRUCTION

DOCUMENTS

NN

0 15' 30' 60' 90'

1" = 30'

1" = 30'-0"

FIRST FLOOR - ZONES - MECHANICAL

DRAWING NOTES:

1. FLOOR PLAN SHOWN FOR INFORMATIONAL PURPOSES ONLY. REFER TO ENLARGED PLANS FOR

ADDITIONAL INFORMATION.

1" = 30'-0"

B27 - ZONE 14 - FIRST FLOOR - MECHANICAL

1" = 30'-0"

B37 - ZONE 14 - FIRST FLOOR - MECHANICAL

NN

N N

1" = 30'-0"4

B18 - ZONE 15 - FIRST FLOOR - MECHANICAL

N

1" = 30'-0"

B42 - ZONE 15 - FIRST FLOOR - MECHANICAL

NN

B27 & B37[14]

B18, B42, B44 & B92[15]

1" = 30'-0"

B44 - ZONE 15 - FIRST FLOOR - MECHANICAL

NN

1" = 30'-0"

B92 - ZONE 15 - FIRST FLOOR - MECHANICAL

NN

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523

KEY PLAN

B38

B06

B18

B19

B27

B37

B42

B44

B62

B74

B82

B91

B92

B64A

B64B

B64-2

EQUIPMENT

STORAGE

C138N

ELEC

C143

DATA

C141

EQUIPMENT

C143A

CORRIDOR

C1-19

OFFICE

B101

PROGRAM SUPPORT

ASSISTANT

B102

TELECOM RM

B103

ELEC

B104

STAIR #5

S5.1

CORRIDOR

6Q CORRIDOR

C1-16

T/H

B64-2 [1]

B64-B[2]

EX 2" CHWS

EX 2" CHWR

EX 1 1/2" V

EX 1/2" HW

EX 1/2" CW

B64-FCU-1-B103

T

122S

1" CND

EX 2" CND

EQUIPMENT

STORAGE

C138N

ELEC

C143

DATA

C141

EQUIPMENT

C143A

CORRIDOR

C1-19

OFFICE

B101

PROGRAM SUPPORT

ASSISTANT

B102

ELEC

B104

STAIR #5

S5.1

CORRIDOR

6Q CORRIDOR

C1-16

CHIEF, NUTRITION &

FOOD SERVICE

B103

EX 2" CHWR

EX 2" CHWS

B64-2 [1]

B64-B[2]

RX 14x14

CONFERENCE ROOM

A123

OFFICE

A119

OFFICE

A122

OFFICE

A121

T/H

B64-A[4]

B64-A[3]

TELECOM RM

BH101

B91-IDU-1-BH101B

T/H T/H T/H

B91-IDU-1-BH101C

B91-IDU-1-BH101A

B91-IDU-1-BH101D

1" CND

3/4" CND

3/4" CND

3/4" CND

1" CND

1" CND

3/4" CND

RL

RS

RL

RS

RS

RL

RS

RL

CONFERENCE ROOM

A123

OFFICE

A119

OFFICE

A122

OFFICE

A121

WAITING ROOM

A125

T

B64-A[4]

B64-A[3]EXIST

AHU-10

EXIST

AHU-9

TELECOM

BH101

RX-RTU-2

RX-RTU-1

RX-CU-AHU-10

B64-ODU-B-AB02A

B91-ODU-1-BH101A

B91-ODU-1-BH101B

B91-ODU-1-BH101C

B91-ODU-1-BH101D

RS

RL

B66[11]

B64-A[3]

B64-A[4]

B64-B[2]

B64-2[1] B64-D[10]

B64-2[6]

B19[7]

B82[9]

B82[8]

B38 [5]

B74[13]

B62[12A]

B62[12B]

B91[3]

DRAWING NOTES:

1. FINAL TESTING, ADJUSTING, AND BALANCING (TAB) FOR HVAC SHALL INCLUDE ALL HYDRONIC AND AIR SYSTEMS SHOWN IN DRAWINGS. REFER TO SECTION 23 05 93 FOR ADDITIONAL TAB REQUIREMENTS.

2. SPACE TEMPERATURE AND HUMIDITY SENSORS SHALL BE 48" +/- 6" AFF.

3. A SINGLE LINE IS USED TO INDICATE ALL REFRIGERANT PIPING ROUTED BETWEEN THE INDOOR AND OUTDOOR UNIT(S). THIS SINGLE LINE REPRESENTS ALL PIPING REQUIRED TO PROVIDE A COMPLETE

AND FUNCTIONING SYSTEM.

4. ROUTE ALL PIPING CONCEALED IN WALLS, CHASES, OR CEILING SPACES.

5. UNLESS OTHERWISE INDICATED, DEMOLITION OF EXISTING PIPING SHALL INCLUDE ALL DEVICES, HANGERS, SUPPORTS, ETC. ALL EXISTING PIPING WHICH WILL NO LONGER REMAIN IN SERVICE SHALL BE REMOVED. ALL EXISTING PIPING TO REMAIN IN SERVICE SHALL BE CAPPED WHERE INDICATED. NO EXISTING PIPING SHALL BE LEFT OPEN. ANY IDENTIFIED DEADEND PIPING SHALL BE REMOVED BACK TO

THE MAINS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:0

:1

P

M

MH1.1.1

BLDG 64-A, B, & 91 - LV 1 - ZONE 2

& 3 - MECHANICAL PLANS

LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

B64-A, B64-B

STATION CHIEF - EDWIN BURNETT

10/25/2024 GSC CSC

100% CONSTRUCTION

DOCUMENTS

NN

0 4' 8' 12' 16'

3/16" = 1'-0"

3/16" = 1'-0"

B64-B ZONE 2 - FIRST FLOOR - TELECOM RM B103 - MECHANICAL - NEW

3/16" = 1'-0"

B64-B ZONE 2 - FIRST FLOOR - TELECOM RM B103 - MECHANICAL - DEMOLITION

3/16" = 1'-0"4

B91 ZONE 3 - FIRST FLOOR - TELECOM RM A120 - MECHANICAL - NEW

3/16" = 1'-0"3

B91 ZONE 3 - FIRST FLOOR - TELECOM RM A120 - MECHANICAL - DEMOLITION

CODED NOTES:

102 PROVIDE DRAIN PANS WITH OVERFLOW SWITCH BENEATH ALL EXPOSED PIPING INSIDE DATA / TELECOM

ROOMS. FABRICATE DRAIN PANS SO THEY SLOPE TO THE HORIZONTAL CONNECTION POINT SHOWN.

CONDENSATE ROUTING AND TERMINATION SHALL BE AS SHOWN AND/OR NOTED ON DRAWINGS. SEE

DRAIN PAN DETAIL 8/M-501.

105 ROUTE REFRIGERANT PIPING UP TO CONDENSING UNIT ON ROOF OF B91. ROUTE ABOVE EXISTING DUCT INTO CHASE AND UP THROUGH ROOF. INSTALL, ROUTE, AND SIZE LINESET PER MANUFACTURER'S

RECOMMENDATIONS.

114 REPAIR HOLE IN WALL AND PATCH TO MATCH EXISTING EXTERIOR FINISHES.

122 TIE CONDENSATE PIPING TO EXISTING CONDENSATE LINE FROM REMOVED FAN COIL UNIT.

126 PROVIDE A WATER SENSOR AT THE LOWEST POINT OF THE DRAIN PAN. SENSOR SHALL ALARM TO THE BAS

IF WATER IS DETECTED. SEE DRAIN PAN DETAIL 8/M-501.

127 EXISTING CHILLED WATER SUPPLY AND RETURN PIPING UP TO FLOOR ABOVE WITH ISOLATION VALVES TO

REMAIN.

128 REMOVE EXISTING SUPPLY/RETURN/EXHAUST GRILLE AND ASSOCIATED DUCTWORK BACK TO ACTIVE

MAIN. CAP AND SEAL DUCTWORK AT POINT OF REMOVAL.

129 REMOVE EXISITNG FAN COIL UNIT AND ALL ASSOCIATED PIPING AND CONTROLS. REMOVE PIPING BACK TO

ACTIVE MAIN. CAP AND SEAL EXISTING DUCTWORK AT POINT OF REMOVAL.

145 REMOVE EXISTING ROOFTOP UNIT AND ASSOCIATED CONTROLS, DUCTWORK, AND DIFFUSERS/GRILLES.

PROVIDE WEATHER TIGHT CAPS FOR EXISTING ABANDONED CURBS.

146 REMOVE EXISTING AIR HANDLING UNIT AND ALL ASSOCIATED PIPING, CONTROLS, AND OUTDOOR UNIT.

PATCH EXTERIOR PENETRATIONS TO MATCH EXISTING MATERIALS AND COLORS.

147 ROUTE NEW REFRIGERANT PIPING UP THROUGH NEW CURB CAP. UTILIZE CURB CAP AS PITCH PAN FOR

NEW REFRIGERANT PIPING UP TO NEW OUTDOOR UNITS.

151 REMOVE EXISITNG FAN COIL UNIT AND ALL ASSOCIATED PIPING, DUCTWORK, AND CONTROLS. PREPARE CHILLED WATER AND CONDENSATE PIPING IN WALL FOR CONNECTION TO NEW FCU IN NEW WORK PHASE.

157 INSTALL FAN COIL UNIT IN PLACE OF EXISTING FAN COIL UNIT TO BE REMOVED IN DEMOLITION PHASE.

CONNECT 1" CHILLED WATER AND 1" CONDENSATE PIPING TO PIPING PREPARED IN WALL IN DEMOLITION

PHASE. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

524 Fernwood Drive, Altamonte Springs, Florida 32701 |www.rdcjpa.com| 800.362.1523

3/16" = 1'-0"5

B91 ZONE 3 - ROOF - TELECOM RM A120 - MECHANICAL - NEW

OFFICE

OFFICE

ICE MACHINE

CORRIDOR

T/H

EX 1" HHWS

EX 1" HHWR

EX 1" CHWS

EX 1" CHWR

T

B38-FCU-1-115

1" CND

S

1" CHWS

1" CHWR

TELECOM RM

OFFICE

OFFICE

OFFICE

ICE MACHINE

CORRIDOR

RX 18x10

EX 1" HHWS

EX 1" HHWR EX 1" CHWR

EX 1" CHWS

RX 18x6

B64-IDU-1-C128

T/H

B64-ODU-1-C128

RL

RS

EX 1/2" CW

EX 1/2" HW

T

1" CNDS

B64-2-VAV-C130

10x12 SA x1

S

A

OPTICAL SHOP

C131

EXAM #20

C120

CORR

C1-5

SUPPLY RM

C121

TLT STAFF

C122

TOILET

C123A

WORKROOM

C123

CORR

C1-5

SATELLITE LAB

C130

TELECOM RM

C128

EX 12x12 EA

T

EX 1/2" HW

EX 1/2" CW

RX 8ø

OPTICAL SHOP

C131

EXAM #20

C120

CORR

C1-5

SUPPLY RM

C121

TLT STAFF

C122

TOILET

C123A

WORKROOM

C123

SATELLITE LAB

C130

B64-2-VAV-C130

10x12 SA x1

S

A

T

152 EX 2" V

141 C128

DATA

B66[11]

B64-A[3]

B64-A[4]

B64-B[2]

B64-2[1] B64-D[10]

B64-2[6]

B19[7]

B82[9]

B82[8]

B38 [5]

B74[13]

B62[12A]

B62[12B]

B91[3]

DRAWING NOTES:

1. FINAL TESTING, ADJUSTING, AND BALANCING (TAB) FOR HVAC SHALL INCLUDE ALL HYDRONIC AND AIR SYSTEMS SHOWN IN DRAWINGS. REFER TO SECTION 23 05 93 FOR ADDITIONAL TAB REQUIREMENTS.

2. SPACE TEMPERATURE AND HUMIDITY SENSORS SHALL BE 48" +/- 6" AFF.

3. A SINGLE LINE IS USED TO INDICATE ALL REFRIGERANT PIPING ROUTED BETWEEN THE INDOOR AND OUTDOOR UNIT(S). THIS SINGLE LINE REPRESENTS ALL PIPING REQUIRED TO PROVIDE A COMPLETE

AND FUNCTIONING SYSTEM.

4. ROUTE ALL PIPING CONCEALED IN WALLS, CHASES, OR CEILING SPACES.

5. UNLESS OTHERWISE INDICATED, DEMOLITION OF EXISTING PIPING SHALL INCLUDE ALL DEVICES, HANGERS, SUPPORTS, ETC. ALL EXISTING PIPING WHICH WILL NO LONGER REMAIN IN SERVICE SHALL BE REMOVED. ALL EXISTING PIPING TO REMAIN IN SERVICE SHALL BE CAPPED WHERE INDICATED. NO EXISTING PIPING SHALL BE LEFT OPEN. ANY IDENTIFIED DEADEND PIPING SHALL BE REMOVED BACK TO

THE MAINS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

A u to d e s k D o c s

/F lo ri d a

L a k e

C it y V

A /0

V

A L a k e

C it y

E H

R M

I n fr a s tr u c tu re

R

M

E P

F P

T .r v t

/2 /2

:0

:3

P

M

MH1.1.2

BLDG 38 & 64 - LV 1 - ZONE 5 & 6 -

MECHANICAL PLANS

LAKE CITY VAMC EHRM

INFRASTRUCTURE

UPGRADES DESIGN

LAKE CITY FL

573A4-21-700

B38, B64-2

STATION CHIEF - EDWIN BURNETT

10/25/2024 GSC CSC

100% CONSTRUCTION

DOCUMENTS

NN

0 4' 8' 12' 16'

3/16" = 1'-0"

3/16" = 1'-0"

B38 ZONE 5 - FIRST FLOOR - TELECOM RM 115 - MECHANICAL - NEW

3/16" = 1'-0"

B38 ZONE 5 - FIRST FLOOR - TELECOM RM 115 - MECHANICAL - DEMOLITION

3/16" = 1'-0"

B64-2 ZONE 6 - FIRST FLOOR - TELECOM RM C128 - MECHANICAL - NEW

3/16" = 1'-0"

B64-2 ZONE 6 - FIRST FLOOR - TELECOM RM C128 - MECHANICAL - DEMOLITION

CODED NOTES:

102 PROVIDE DRAIN PANS WITH OVERFLOW SWITCH BENEATH ALL EXPOSED PIPING INSIDE DATA / TELECOM

ROOMS. FABRICATE DRAIN PANS SO THEY SLOPE TO THE HORIZONTAL CONNECTION POINT SHOWN.

CONDENSATE ROUTING AND TERMINATION SHALL BE AS SHOWN AND/OR NOTED ON DRAWINGS. SEE

DRAIN PAN DETAIL 8/M-501.

107 INSTALL NEW REFRIGERANT LINESET AND SIZE PER MANUFACTURER'S REQUIREMENTS. ROUTE REFRIGERANT PIPING CONCEALED ABOVE CEILING. ROUTE CONDENSATE PIPING TO MOP SINK OR WYE

BRANCH TAIL PIECE.

109 CONNECT NEW CHILLED WATER PIPING TO EXISTING PIPING IN WALL OR ABOVE CEILING. PROVIDE

ISOLATION VALVES AT CONNECTION TO EXISTING. REFER TO DETAILS FOR COIL CONNECTION

INFORMATION.

123 ROUTE CONDENSATE PIPING TO FLOOR DRAIN IN ICE MACHINE ROOM. SEE CONDENSATE FLOOOR DRAIN

DETAIL 11/M-501.

126 PROVIDE A WATER SENSOR AT THE LOWEST POINT OF THE DRAIN PAN. SENSOR SHALL ALARM TO THE BAS

IF WATER IS DETECTED. SEE DRAIN PAN DETAIL 8/M-501.

128 REMOVE EXISTING SUPPLY/RETURN/EXHAUST GRILLE AND ASSOCIATED DUCTWORK BACK TO ACTIVE

MAIN. CAP AND SEAL DUCTWORK AT POINT OF REMOVAL.

133 INSTALL BOTTOM OF DUCTLESS SPLIT INDOOR UNIT 88" ABOVE FINISHED FLOOR. COORDINATE EXACT

LOCATION WITH TELECOM CONTRACTOR.

134 INSTALL FAN COIL UNIT 24" ABOVE FINISHED FLOOR. ROUTE CHILLED WATER PIPING DOWN IN WALL TO FCU CHILLED WATER PIPING CONNECTIONS. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. ROUTE

1" CONDENSATE FROM INTEGRAL CONDENSATE PUMP TO LOCATION SHOWN.

141 RECORD EXISTING SUPPLY/RETURN/EXHAUST AIRFLOW AT EACH GRILLE PRIOR TO DEMOLITION.

142 REBALANCE EXISITNG SUPPLY/RETURN/EXHAUST GRILLES TO VALUE RECORDED IN PRE-DEMOLITION TEST

AND BALANCE.

143 INSTALL CONDENSING UNIT ON 3" THICK PREFABRICATED CONCRETE PAD. SECURE UNIT PER FLORIDA

HURRICANE REQUIREMENTS. SEE SPECIFICATIONS.

152 RELOCATE EXISTING THERMOSTAT / TEMPERATURE SENSOR TO LOCATION SHOWN ON PLANS.

155 ROUTE PIPING THROUGH EXTERIOR WALL. SEE PIPING EXTERIOR BIRCK WALL PENETRATION DETAIL 6/M-502.

524…