Attachment 23 - 27 20 00 COMPUTER-TELEPHONE SYSTEMS May 2010.pdf

PDF 93 KB Posted

Attached to
Multiple Award Construction Contract (MACC)/Indefinite-Delivery Indefinite-Quantity (IDIQ) Little Rock AFB, AR Federal contract opportunity
Solicitation number
FA446021R0009
Issued by
Department of the Air Force Air Mobility Command

About this file

This document provides specifications for a computer-telephone systems project and an associated federal contract opportunity solicitation. The specifications call for installing a complete computer/telephone system including terminal boards, outlets, Category 6 cable in four twisted pairs, system equipment, interior distribution centers, cable supports, and related components. The specifications provide detailed requirements for support systems, cable and conduit runs, cable trays, jacks and covers, elbows, marking and labeling, terminations, identification labels, universal wiring plans, cable supports, testing, test plans, procedures, and service entrance. The associated federal contract opportunity is a solicitation for a multiple award construction contract/indefinite delivery indefinite quantity contract to support sustainment, restoration and modernization projects at Little Rock Air Force Base, including new construction, alteration, repair, demolition, and miscellaneous construction services for facilities such as administrative, industrial, maintenance, and medical buildings.

View the file

Other files for this federal contract opportunity

Other files attached to Multiple Award Construction Contract (MACC)/Indefinite-Delivery Indefinite-Quantity (IDIQ) Little Rock AFB, AR, newest first.
File Type Posted
Amend 05 -Solicitation Amendment - FA446021R00090005.pdf PDF
Amend 05 -Attachment 38 Questions and Answers after 3rd Site visit.pdf PDF
Amend 05 -Updated Attachment 30 - Past Performance Package..docx DOCX document
Amend 05 -Attachment 32 Convert Mission Planning Cell B-380 (Seed Project).zip ZIP file
Amend 05 -Attachment 13 - Statement of Work for MACC Rev 1.pdf PDF
Solicitation Amendment FA446021R00090004 SF 30.pdf PDF
Amend 04 -Attachment 36 - Site Visit Sign-in-Sheet 6-15-21.pdf PDF
Solicitation Amendment - FA446021R00090004.pdf PDF
Amend 04 -Attachment 32 Convert Mission Planning Cell B-380 (Seed Project).zip ZIP file
Amend 04 -Attachment 37 - 2nd Site Visit Sign-in-Sheet 6-23-21.pdf PDF
Solicitation Amendment FA446021R00090003 SF 30.pdf PDF
Attachment 32 Convert Mission Planning Cell B-380 (Seed Project).zip ZIP file
Updated Attachment 30 - Past Performance Package.docx DOCX document
Attachment 34 - PPI Tool Download Instructions.pdf PDF
Solicitation Amendment FA446021R00090002 SF 30.pdf PDF
Solicitation Amendment FA446021R00090001 SF 30.pdf PDF
Attachment 32 - Convert Mission Planning Cell B-380 Seed Project Amend 1.zip ZIP file
Amend 0001-Solicitation - FA446021R0009 Rel.pdf PDF
Attachment 28 - Financial Institution Reference Sheet.pdf PDF
Attachment 12 - Scheduled Government Furnished Property.pdf PDF
Attachment 1 - EMIS Instruction Guide.pdf PDF
Attachment 22 - 26 05 04 RACEWAYS.pdf PDF
Attachment 32 - Convert Mission Planning Cell B-380 (Seed Project).zip ZIP file
Attachment 29 - Maintainability Review Checklist FORM - Design Team.docx DOCX document
Attachment 27 - EZSource PresentPast Performance Relevancy Table .docx DOCX document
Attachment 26 - Design Review Checklist including constructability review 2013 07 30.docx DOCX document
Attachment 20 - 10 14 02 INTERIOR SIGNAGE.pdf PDF
Attachment 18 - 08 71 00 DOOR HARDWARE.pdf PDF
Attachment 16 - 00 00 02 LRAFB SPECIFICATIONS FORMAT STANDARD.pdf PDF
Attachment 9 - LRAFB Architectural Design Guide Supplement.pdf PDF
Attachment 7 - LRAFB Mechanical Design Criteria.pdf PDF
Attachment 30 - Past Performance Package.docx DOCX document
Attachment 25 - 28 31 00 FIRE DETECTION AND ALARM SYSTEMS.pdf PDF
Attachment 24 - 27 51 16 BUILDING MASS NOTIFICATION SYSTEM.pdf PDF
Attachment 19 - 09 06 89 TYPICAL FINISH SCHEDULE.pdf PDF
Attachment 17 - 01 57 22 TREE PRESERVATION.pdf PDF
Attachment 14 - ETL 07-04 AIR FORCE CARPET STANDARD.pdf PDF
Attachment 13 - Statement of Work for MACC.pdf PDF
Attachment 11 - LRAFB Arch Design Guide Supplement 6 Aug 20.pdf PDF
Attachment 10 - LRAFB Arch Compatibility Guide.pdf PDF
Attachment 8 - LRAFB Telecommunications Systems Design.pdf PDF
Attachment 3 - CandD Report.pdf PDF
Attachment 2 - Environmental MOA.pdf PDF
Attachment 33- SubKTR_Consent_Form.pdf PDF
Attachment 21 - 10 44 16 FIRE EXTINGUISHERS - CABINETS.pdf PDF
Attachment 15 - UFC 4-010-01 DoD Minimum Antiterrorism Standards for Buildings.pdf PDF
Attachment 6 - LRAFB Electrical Design Standards.pdf PDF
Attachment 5 - LRAFB Information.pdf PDF
Attachment 4 - LRAFB Civil Design Criteria.pdf PDF
Released Solicitation - FA446021R0009.pdf PDF
Show all 50

Multiple Award Construction Contract (MACC)/Indefinite-Delivery Indefinite-Quantity (IDIQ) Little Rock AFB, AR has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMPUTER-TELEPHONE SYSTEMS 27 20 00 - 1

SECTION 27 20 00 - COMPUTER/TELEPHONE SYSTEMS

PART 1 - GENERAL

1.01 SCOPE:

Includes furnishing and installing a complete computer/telephone system as described in the Contract Documents and as indicated on the drawings.

1.02 RELATED WORK SPECIFIED ELSEWHERE:

A. General Electrical Provisions - Section 26 00 05.

B. Raceways - Section 26 05 04.

C. Electrical Boxes and Fittings – Section 26 05 12.

D. Wiring Devices - Section 16 27 26.

1.03 APPLICABLE PUBLICATIONS:

A. UFC 3-580-01 Telecommunications Building Cabling Systems Planning and Design B. National Fire Protection Association (NFPA) Standards: (Use latest editions)

1. No. 70 – National Electrical Code

2. No. 75 – Standard for the Protection of Electronic Computer/Data Processing Equipment

1.04 SUBMITTALS:

A. Product Data: Submit manufacturer’s product specifications and installation instructions for each identification material and device required. Include data substantiating that materials comply with requirements.

B. Post installation tests required by UFC 3-580-01 and referred to in PART 3 of this specification shall be submitted at least one week prior to the pre-final inspection.

PART 2 - PRODUCTS

2.01 TERMINAL BOARDS

The new terminal boards shall be ¾ inch by 4-‘0” by 8’-0” plywood board coated with two (2) coats of insulation varnish. All walls of the telephone room shall be covered with plywood.

All cables, LAN and phone, shall be terminated on floor mounted racks. Each telephone or data terminal location shall have a dedicated circuit, 120V duplex receptacle.

2.02 OUTELETS

Outlets shall be a quad combination with a telephone RJ45 and three computer RJ45 jacks.

Outlets shall be of the modular construction with male jacks that insert into female adapters.

Outlets shall be capable of removal and replacement of jacks without having to disconnect wiring. Telephone cover plates shall match wiring device plates. Amp or approved equal.

2.03 CABLE

Computer/telephone cable shall be Category 6, 24 AWG, 4 pair solid copper, unshielded twisted pair, rated at 250 MHz megabits per second. Wire shall be color coded as follows:

A. Pair 1 White/Blue, Blue/White B. Pair 2 White/Orange, Orange/White C. Pair 3 White/Green, Green/White

COMPUTER-TELEPHONE SYSTEMS 27 20 00 - 2

D. Pair 4 White/Brown, Brown/White

2.04 SYSTEM EQUIPMENT

The system equipment shall include equipment racks, cabinets, terminal termination patch panels, station jacks, grounding, interior cables, outlet boxes, power supplies, conduits, and other such materials and equipment as required for a complete telephone and LAN system.

Switches shall be provided by the government and installed by the contractor. Grounding shall be made via a ground rod and be bonded to the electrical grounding system. A minimum clearance of 12 inches shall be maintained between runs of communication and power conduits.

2.05 INTERIOR DISTRIBUTION CENTERS

Cables which interconnect interior distribution centers shall conform to ICEA S-80-576.

Where required, cable shall be UL classified low smoke and low flame for use in air plenums in accordance with NFPA-70. Cables which terminate at each station jack shall conform to ICEA S-80-576. Where required, cable shall be UL classified low smoke and low flame for use in air plenums in accordance with NFPA 70.

2.06 CABLE SUPPORT

Cable supports shall be approved for the purpose. Cable supports shall allow removal of existing cables and installation of new cables without replacing cable supports. Cable supports shall be Caddy CAT425 or approved equal.

PART 3 - EXECUTION

3.01 SUPPORT SYSTEMS

The contractor shall install telephone/computer support systems connecting all outlets.

3.02 CABLE AND CONDUIT RUNS

Install Category 6, 4 pair cable from each outlet to the patch panels for all circuits. Phone circuit cables shall be terminated on separate patch panels in a separate rack from LAN cables. Locations shall be as shown on the drawings.

3.03 CABLE TRAYS

Install conduit from outlet location to above wall top or above ceiling. Conduit shall extend to cable tray if tray is less than 6’ away. If tray is further away then properly support cables from end of conduit to cable tray meeting manufactures support recommendation or as shown on drawing.

3.04 JACKS AND COVERS

Provide RJ-45type station jacks and cover plates for all computer/telephone outlets.

3.05 ELBOWS

All raceway elbows shall be long radius elbows as required.

3.06 MARKING AND LABELING

Category 6 cables pulled to the patch panels will be marked and neatly secured. Cables shall be terminated at the patch panel in a floor mounted patch panel with RJ-45 modular jack. See 3.08 “ID LABLES”.

COMPUTER-TELEPHONE SYSTEMS 27 20 00 - 3

3.07 TERMINATIONS

All telephone and Data cables shall be terminated and marked at the equipment racks. Data cables shall be terminated with outlets capable of modular jack replacement without disconnecting wires. Outlets shall be as manufactured by “AMP” or approved equal. Patch panels will be provided by the contractor and shall have capacity for 25% more cables to be added in the future.

3.08 ID LABELS

Identification labels: The contractor shall provide identification labels at both ends of communications cable. Outlets and LAN rack jacks shall be clearly labeled with same identification as the cable. Label identifier for telephone circuits shall start with letter T and end with room number. Label identifier for data circuits shall start with the letter D and end with room number. If there is more than one outlet in a room then add a suffix .1, .2, .3, etc.

3.09 COMPONENTS AND APPURTENANCES

All system components and appurtenances shall be installed in accordance with the manufacturer’s instructions as specified and indicated. All installation work must be done in accordance with the safety requirements set forth in the general requirements of the latest revision of ANSI C2 and NFPA 70.

3.10 UNIVERSAL WIRING PLAN

Interior wiring shall be installed and terminated at all station locations as indicated. Wiring shall take the form of a “Universal Wiring Plan” where station cables are wired directly, homerun fashion, from a distribution point to the appropriate modular jack plate, jack assembly, or floor jack to support the use of single line type sets and electronic sets.

Contractor shall verify that the length of cable runs are no longer than 300’. If contractor’s routing of cable increases the length of cable runs beyond the 300’, then contractor shall provide, at no additional cost, cross connect blocks/data hubs necessary to reduce cable run length to under 300’. Station cables shall not be installed in the same cable tray, utility pole compartment or floor trench compartment with AC power cables. Station cables not installed in conduit or wireways shall be properly secured and neat in appearance.

3.11 CABLE SUPPORTS

Cable supports shall be spaced in accordance with manufacturer’s instructions not exceeding 5 feet.

3.12 TESTING

The contractor shall provide all personnel, equipment, instrumentation, and supplies necessary to perform the required testing. Notification of any planned testing shall be given to the Contracting Officer at least 14 days prior to any test.

3.13 TEST PLANS

The contractor shall develop the Test Plans defining all the tests required to ensure that the system meets technical, operational, and performance specifications. The Test Plans shall define milestones for each test, equipment, personnel, facilities and supplies required. The Test Plans shall identify the capabilities and functions to be tested.

3.14 TEST PROCEDURES

The test procedures shall be developed from the test plan and design documentation. The procedures shall consist of detailed instructions for the best setup, execution and inspection.

Visual operations can begin at any period during installation and are used to list al newly

COMPUTER-TELEPHONE SYSTEMS 27 20 00 - 4

installed equipment. Reports shall be delivered to the Contracting Officer within seven (7) days after completion.

3.15 CABLE TRAY

Provide cable tray in the corridor (above accessible ceiling) for all telephone and computer cable. Cable tray may be used in lieu of conduit in other areas. Cable tray to be mounted above ceiling, a minimum of 10 inches above ceiling in corridor. Cable tray to be equal to B- Line Cent-R-Rail Data-Track with 12” bottom rail or approved equal. See drawing for areas where size may be different.

3.16 SERVICE ENTRANCE

Service entrance for communications shall utilize the number of conduits as shown on drawings. One of these 4 inch conduit shall have innerduct installed inside the conduit.

Maxcell—3” 3 cell packs for total of 9 innerducts http://www.maxcellinnerduct.com/ with pull strings.

3.17 MANHOLES AND DUCTS

Manholes and ducts shall be designed and installed IAW REA TE&CM 643, REA Form 515c, Technical Order (T.O.) 31W3-10-22, National Electrical Manufacturers Association TC-2, and NEMA TC-10.

END OF SECTION – COMPUTER-TELEPHONE SYSTEMS

http://www.maxcellinnerduct.com/

SECTION 27 20 00 - COMPUTER/TELEPHONE SYSTEMS
PART 1 - GENERAL
1.01 SCOPE:
1.02 RELATED WORK SPECIFIED ELSEWHERE:
A. General Electrical Provisions - Section 26 00 05.
B. Raceways - Section 26 05 04.
C. Electrical Boxes and Fittings – Section 26 05 12.
D. Wiring Devices - Section 16 27 26.
1.03 APPLICABLE PUBLICATIONS:
A. UFC 3-580-01 Telecommunications Building Cabling Systems Planning and Design
B. National Fire Protection Association (NFPA) Standards: (Use latest editions)
1. No. 70 – National Electrical Code
2. No. 75 – Standard for the Protection of Electronic Computer/Data Processing Equipment
1.04 SUBMITTALS:
A. Product Data: Submit manufacturer’s product specifications and installation instructions for each identification material and device required. Include data substantiating that materials comply with requirements.
B. Post installation tests required by UFC 3-580-01 and referred to in PART 3 of this specification shall be submitted at least one week prior to the pre-final inspection.
PART 2 - PRODUCTS
2.01 TERMINAL BOARDS
2.02 OUTELETS
2.03 CABLE
A. Pair 1 White/Blue, Blue/White
B. Pair 2 White/Orange, Orange/White
C. Pair 3 White/Green, Green/White
D. Pair 4 White/Brown, Brown/White
2.04 SYSTEM EQUIPMENT
2.05 INTERIOR DISTRIBUTION CENTERS
2.06 CABLE SUPPORT
PART 3 - EXECUTION
3.01 SUPPORT SYSTEMS
3.02 CABLE AND CONDUIT RUNS
3.03 CABLE TRAYS
3.04 JACKS AND COVERS
3.05 ELBOWS
3.06 MARKING AND LABELING
3.07 TERMINATIONS
3.08 ID LABELS
3.09 COMPONENTS AND APPURTENANCES
3.10 UNIVERSAL WIRING PLAN
3.11 CABLE SUPPORTS
3.12 TESTING
3.13 TEST PLANS
3.14 TEST PROCEDURES
3.15 CABLE TRAY
3.16 SERVICE ENTRANCE
3.17 MANHOLES AND DUCTS