The solicitation number is 36C25024B0031_1 and the contract opportunity ID is 86c3f49d88f34f769ef0f08cbd641801. The federal agency involved is the Department of Veterans Affairs Technology Acquisition Center in Austin. The attachment includes drawings, specifications, and technical details related to the telecommunications, technology, and security systems required for the construction project. It outlines the types of outlets, cabling, equipment, and other technology infrastructure that must be installed. The document also includes several bid deduct alternates that could potentially reduce the scope of the project. Overall, this attachment provides comprehensive technical information to support the federal contract opportunity.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T2
B
T2
DETAIL: B = DETAIL DESIGNATION
T2 = SHEET WHERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
T2 = SHEET WHERE SECTION IS LOCATED
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
GENERAL FLOOR PLAN NOTES
CONDUIT RUN IN WALL OR ABOVE CEILING PER DIV 26.
CONDUIT RUN IN SLAB OR UNDERGROUND PER DIV 26.
CABLE MANAGEMENT SYSTEM PATHWAY PER DIV 27 / DIV 28.
LADDER TRAY PER DIV 26, 12" x 4" DEEP UNLESS NOTED OTHERWISE.
CM
ABBREVIATIONS
AAP - AREA ALARM PANEL - MEDICAL GAS
ACC - ACCESS
ADJ - ADJUSTABLE
AF - ARC FAULT CIRCUIT INTERRUPTER
AFCI - ARC FAULT CIRCUIT INTERRUPTER
AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM
AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATS - AUTOMATIC TRANSFER SWITCH
BLDG - BUILDING
BOE - BOTTOM OF EQUIPMENT
BOT - BOTTOM
BTWN - BETWEEN
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CKT - CIRCUIT
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CONN - CONNECT OR CONNECTION
CORR - CORRIDOR
CTR - CENTER
D - DEPTH
DET - DETAIL
DIA - DIAMETER
DIM - DIMENSION
DIV - DIVISION
DN - DOWN
DWG - DRAWING
EA - EACH
EC - ELECTRICAL (DIVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATION OR ELEVATOR
EM - EMERGENCY
EQ - EQUAL
EQS - EQUIPMENT SUPPLIER
EQUIP - EQUIPMENT
ETR - EXISTING TO REMAIN
EX - EXISTING
EXP - EXPANSION
EXT - EXTERIOR
FCE - FIRE CONTROL EQUIPMENT
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
GC - GENERAL CONTRACTOR
GF - GROUND FAULT CIRCUIT INTERRUPTER
GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT
FURNISHED CONTRACTOR INSTALLED
GFFT - GROUND FAULT FEED THRU
HC - HVAC (DIVISION 23)
HP - HORSE POWER OR HIGH POINT
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
IN - INCHES
KEC - KITCHEN EQUIPMENT
L - LENGTH
LBS - POUNDS
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
NIC - NOT IN CONTRACT
NOM - NOMINAL
NTS - NOT TO SCALE
OD - OUTSIDE DIAMETER
OFCI - OWNER FURNISHED CONTRACTOR INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
PC - PLUMBING (DIVISION 22)
PLBG - PLUMBING
RAD - RADIUS
REC - RECESSED
REQD - REQUIRED
RI - ROUGH-IN
S - SURFACE MOUNTED
SC - SECURITY
SCH - SCHEDULE
SHT - SHEET
SMS - SECURITY MANAGEMENT SYSTEM
SPEC - SPECIFICATIONS
SQ - SQUARE
SS - STAINLESS STEEL
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY
TC - TECHNOLOGY
TEMP - TEMPERATURE
TOE - TOP OF EQUIPMENT
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
VFD - VARIABLE FREQUENCY DRIVE
VOL - VOLUME
W/ - WITH
W/O - WITHOUT
WP - WEATHERPROOF
ZVC - ZONE VALVE CABINET
1. ALL OUTLET BOXES AND CONDUIT/RACEWAYS ASSOCIATED WITH OUTLET BOXES TO BE PER DIVISION 26. ALL CABLE MANAGEMENT SYSTEMS WHERE
OPEN WIRING IS INSTALLED SHALL BE PER DIVISION 27.
2. ALL CONDUIT SLEEVES SHOWN ON BID DOCUMENTS TO BE PER DIVISION 26. ALL CONDUIT SLEEVES THRU WALLS AND FLOORS, NOT SPECIFICALLY SHOWN ON DRAWINGS BUT REQUIRED FOR COMPLIANT INSTALLATION OF CABLING SHALL BE PER DIVISION 27.
3. ALL FIRE STOPPING OF CONDUIT SLEEVES AND CABLE TRAY PENETRATIONS SHALL BE PER DIVISION 27.
4. DIVISION 27 SHALL BE COMPLETELY AND THOROUGHLY COORDINATED WITH ALL PATHWAYS BEING PROVIDED PER DIVISION 26. ANY PATHWAYS THAT ARE PROVIDED THAT CAUSE CABLING INSTALLATION TO BE NON-COMPLIANT SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO THE
INSTALLATION OF CABLING.
5. PER DIVISION 27, COORDINATE ALL POWER REQUIREMENTS WITHIN THE TECHNOLOGY ROOM(S) WITH THE DIVISION 26 PRIOR TO ROUGH-INS AND BUILD- OUT OF EACH TECH ROOM. PER DIVISION 27, PROVIDE SIGNED-OFF DETAILED COORDINATION DRAWINGS INCLUDING ALL FIRE SUPPRESSION, PLUMBING, HVAC, ELECTRICAL, AND TECHNOLOGY WORK WITHIN THE ROOM(S). THE COORDINATION DRAWINGS SHALL SHOW FLOOR PLANS AND WALL ELEVATIONS INCLUDING ALL TRADES' WORK WITHIN THE SPACE(S) PRIOR TO ANY TRADES WORKING WITHIN THE SPACE(S).
6. THE DRAWINGS INDICATE THE QUANTITY, TYPE AND GENERAL LOCATION OF VOICE/DATA/CATV/VIDEO OUTLETS REQUIRED IN EACH SPACE. A FINAL DEVICE LOCATION PLAN FOR EACH SPACE WILL BE ISSUED PRIOR TO START OF THE INSTALLATION. INCLUDE IN THE BID ANY COSTS ASSOCIATED WITH FINAL
DEVICE LOCATIONS AS THERE WILL BE NO ALLOWANCE AFTER AWARD OF CONTRACT.
7. PROVIDE THE CABLING PATHWAYS AND POWER FOR TECHNOLOGY SYSTEMS. INCLUDE IN THE BID, COSTS TO OBTAIN AND REVIEW THE FINAL ELECTRICAL DRAWINGS AND TO HAVE DEDICATED PRE-CONSTRUCTION MEETINGS WITH THE ELECTRICAL AND CONSTRUCTION MANAGER. THE PURPOSE IS TO VERIFY AND CONFIRM THAT THE ELECTRICAL MEANS AND METHODS ARE COORDINATED WITH THE TECHNOLOGY INSTALLATION METHODS PRIOR TO START OF CONSTRUCTION. IMMEDIATELY BRING ANY ISSUES TO THE ATTENTION OF THE CONSTRUCTION MANAGER. IN ADDITION, INCLUDE COST TO WALK THROUGH EACH BUILDING DURING THE PATHWAY ROUGH-IN PHASE TO VERIFY INSTALLATION WILL ACCOMMODATE THE CABLING PHASE OF THE
PROJECT.
8. A 3.5" DEEP MASONRY BOX (PROVIDED PER DIVISION 26) SHALL BE USED IN CMU WALLS.
9. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATIONS AND MOUNTING HEIGHTS OF OUTLET AND DEVICES.
GENERAL NOTES
SECURITY SYMBOLS
CC
1 CCTV SYSTEM CEILING MOUNTED CAMERA. REFER TO CAMERA SCHEDULE FOR MOUNTING HEIGHT AND CAMERA
SPECIFICATIONS. SUBSCRIPT "X" INDICATES ENTRY IN CAMERA SCHEDULE.
IM DESK MOUNTED INTERCOM MASTER STATION.
CE PROVIDE INTERFACE FROM CARD ACCESS SYSTEM INTO ELEVATOR CONTROLLER INCLUDING ALL NECESSARY
HARDWARE, PROGRAMMING AND CABLING AS COORDINATED WITH ELEVATOR CONTRACTOR.
MD CEILING MOUNTED MOTION DETECTOR.
PB DESK MOUNTED PUSH BUTTON FOR LOCAL ELECTRONIC DOOR RELEASE.
JS CCTV SYSTEM REMOTE JOYSTICK/CONTROLLER AND KEYPAD OPERATOR'S STATION.
GLASS BREAK.GB
X
PP DESK MOUNTED PANIC/DURESS BUTTON.
SECURITY SYMBOLS WITH ELECTRICAL REQUIREMENTS
CC
CCTV SYSTEM WALL MOUNTED CAMERA (REFER TO CAMERA SCHEDULE FOR MOUNTING HEIGHT AND CAMERA SPECIFICATIONS). SUBSCRIPT "X" INDICATES ENTRY IN CAMERA SCHEDULE. 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE
ACCESSIBLE CEILING PER DIV 26. CAMERA AND CABLING PER DIV 28.
PS
LOCAL LOW VOLTAGE POWER SUPPLY FOR EXTERIOR CAMERA. SUBSCRIPT "X" INDICATES ASSOCIATED CAMERA. 120V POWER INTO LOCAL JUNCTION BOX ABOVE CEILING AND CONNECTION TO POWER SUPPLY PER DIV 26. POWER SUPPLY
MOUNTED ABOVE CEILING AND LOW VOLTAGE WIRING TO LOCAL CAMERA PER DIV 28.
IC
WALL MOUNTED INTERCOM DOOR STATION (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO
ABOVE ACCESSIBLE CEILING PER DIV 26. INTERCOM AND CABLING PER DIV 28.
DM
DOOR POSITION SWITCH WITH WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. PROVIDE ONE CONTACT FOR EACH LEAF IN MULTI-DOOR
OPENINGS. REFER TO SECURITY ROUGH-IN DETAILS.
EL
ELECTRONIC DOOR LOCK AND INSTALLATION BY OTHERS. LOW VOLTAGE WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY
ROUGH-IN DETAILS.
EM
ELECTRONIC MAG LOCK AND INSTALLATION BY OTHERS. LOW VOLTAGE WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY ROUGH-IN
DETAILS.
ES
ELECTRONIC STRIKE AND INSTALLATION BY OTHERS. LOW VOLTAGE WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY ROUGH-IN
DETAILS.
LB
RX
REQUEST TO EXIT SWITCH IN DOOR HARDWARE BY OTHERS. LOW VOLTAGE WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY
ROUGH-IN DETAILS.
HD
HANDICAP DOOR OPERATOR MOTOR ASSEMBLY BY OTHERS. 120V POWER CONNECTION AND CONDUIT FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. LOW VOLTAGE WIRING AND INTERFACE WITH SMS AND DOOR ACTUATOR BUTTONS PER DIV 28. REFER TO SECURITY ROUGH-IN DETAILS.
HA
WALL/PEDESTAL MOUNT HANDICAP DOOR ACTUATOR BUTTON, FURNISHED BY OTHERS. BOX AS REQUIRED BY SYSTEM MANUFACTURER WITH INSTALLATION AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. ALL LOW VOLTAGE WIRING AND INTERFACE WITH SMS AND DOOR MOTOR PER DIV 28. REFER TO SECURITY
ROUGH-IN DETAILS.
HO
FA
WALL/FLOOR MOUNTED ELECTROMAGNETIC DOOR HOLD OPEN WITH POWER SUPPLY INSTALLED BY OTHERS. 120V POWER AND CONNECTION, BOX AS REQUIRED BY MANUFACTURER AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. LOW VOLTAGE WIRING FROM POWER SUPPLY TO HOLD OPEN AND INTERFACE WITH SMS PER DIV 28. SUBSCRIPT "FA" INDICATES DEVICES POWERED FROM FIRE ALARM SYSTEM AND INTERFACE FROM SMS TO FIRE ALARM SYSTEM REQUIRED FOR DOOR RELEASE PER DIV 28. REFER TO SECURITY ROUGH-IN DETAILS.
CR
WALL MOUNTED PROXIMITY CARD READER (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. CARD READER AND CABLING PER DIV 28. REFER
TO SECURITY ROUGH-IN DETAILS.
CR EL
ELEVATOR CAB MOUNTED CARD READER. READER TO BE INSTALLED IN ELEVATOR CAB AS COORDINATED WITH ELEVATOR CONTRACTOR. WIRING FROM CAB THRU TRAVELING CABLE TO ELEVATOR CONTROLLER IN ELEVATOR MACHINE ROOM AND INTERFACE WITH ELEVATOR CONTROLLER AND SMS PER DIV 28, COORDINATE WITH ELEVATOR
CONTRACTOR. REFER TO SECURITY ROUGH-IN DETAILS.
KC
WALL MOUNTED COMBINATION KEYPAD/CARDREADER (46" MH UNLESS NOTED OTHERWISE). 2-GANG BOX WITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. DEVICE AND CABLING PER DIV 28.
K WALL MOUNTED SECURITY KEYPAD ENTRY STATION (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. KEYPAD AND CABLING PER DIV 28.
MD
WALL MOUNTED MOTION DETECTOR (90" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. MOTION DETECTOR, WALL MOUNT HARDWARE, AND CABLING PER DIV 28.
PP W
WALL MOUNTED PANIC/DURESS BUTTON (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO
ABOVE ACCESSIBLE CEILING PER DIV 26. BUTTON AND CABLING PER DIV 28.
X WALL MOUNTED SECURITY SYSTEM WIRING OUTLET MOUNTED BELOW COUNTER TOP. 2-GANG BOX WITH 2-1" CONDUITS TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. GROMMETED FACEPLATE AND SECURITY
SYSTEM CABLING PER DIV 28.
CM
WALL MOUNTED MONITOR OUTLET FOR CCTV SYSTEM (84" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 1" CONDUIT TO ABOVE CORRIDOR CEILING PER DIV 26. JACK, FACEPLATE AND CABLING PER DIV 28.
MIC
CEILING MOUNTED SECURITY/CCTV SYSTEM AUDIO MICROPHONE. 1-GANG BOX MOUNTED IN CEILING PER DIV 26.
MICROPHONE AND CABLING PER DIV 28.
BR
WALL MOUNTED BIOMETRIC READER (46" MH UNLESS NOTED OTHERWISE). 2-GANG BOX WITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. READER AND CABLING PER DIV 28. REFER TO
SECURITY ROUGH-IN DETAILS.
X
X
MD
PB W
WALL MOUNTED PUSH BUTTON FOR LOCAL ELECTRONIC DOOR RELEASE (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. BUTTON AND CABLING PER DIV 28.
ELECTRONIC LATCH BOLT MONITORING. HARDWARE AND INSTALLATION BY OTHERS. LOW VOLTAGE WIRING PER DIV 28.
CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SECURITY JUNCTION BOX ABOVE CEILING PER DIV 26. REFER TO
SECURITY ROUGH-IN DETAILS.
CEILING MOUNTED MOTION DETECTOR. 1-GANG BOX MOUNTED IN CEILING PER DIV 26. DETECTOR AND CABLING PER
DIV 28.
DC
LOCAL IP BASED 2-DOOR ACCESS CONTROL PANEL SERVING LOCAL CARD READER/SECURITY CONTROLLED DOORS.
LOCATE ABOVE ADJACENT ACCESSIBLE CEILING. PROVIDE DATA DROP IN 0.75" CONDUIT TO LOCAL DATA CLOSET.
EXTEND 1" CONDUIT WITH DOOR SECURITY WIRING TO LOCAL SECURITY SYSTEM JUNCTION BOX. REFER TO SECURITY
ROUGH-IN DETAILS.
JB M
SECURITY SYSTEM JUNCTION BOX TO BE LOCATED ABOVE ACCESSIBLE CEILING (MIN 6"X6"X4"). ROUTE LOCAL DOOR SECURITY WIRING CONDUITS/RACEWAYS TO JUNCTION BOX. EXTEND 1" CONDUIT WITH DOOR SECURITY WIRING TO LOCAL 2-DOOR CONTROL PANEL/REMOTE DOOR CONTROL PANEL AS INDICATED ON DRAWINGS. REFER TO SECURITY
ROUGH-IN DETAILS.
PL
SITE POLE FOR MOUNTING SECURITY CAMERAS (REFER TO SPECIFICATIONS FOR SIZE/TYPE). PROVIDE POLE WITH CONCRETE BASE AS INDICATED ON PLANS. EXTEND AND CONNECT TO SITE CONDUIT SYSTEM AS INDICATED ON PLANS.
PROVIDE NEMA 3R JUNCTION BOX AT BASE OF POLE FOR CAMERA EQUIPMENT (120V POWER SUPPLY, FIBER
CONVERTERS, ETC.). REFER TO SECURITY ROUGH-IN DETAILS.
TECHNOLOGY SYMBOLS
AP
X
CEILING MOUNTED WIRELESS ACCESS POINT WITH DATA DROP ABOVE CEILING. PROVIDE 20' COIL IN DATA CABLE TO FACILITATE RELOCATION/ADJUSTMENT OF WAP. OWNER TO PROVIDE WAP AND OBERON BOX FOR MOUNTING.
SUBSCRIPT "X" INDICATES "G" FOR GUEST AND "VA" INDICATES IN HOUSE WAP.
RA REMOTE PATCH ANTENNA FOR LOCAL WIRELESS ACCESS POINT.
DSS TELEPHONE SYSTEM MULTI-BUTTON DIRECT SELECTION STATION.
ATEL TELEPHONE SYSTEM ATTENDANT CONSOLE.
W DTEL TELEPHONE SYSTEM OFFICE TELEPHONE HANDSET. SUBSCRIPT "W" INDICATES WIRELESS BASE STATION AND HANDSET.
STEL
W TELEPHONE SYSTEM CLASSROOM DESK MOUNT TYPE HANDSET. SUBSCRIPT "W" INDICATES WALL MOUNT (46" MH
UNLESS NOTED OTHERWISE).
AV SYMBOLS
FLAT PANEL DISPLAY WITH WALL MOUNTING HARDWARE (84" MH UNLESS NOTED OTHERWISE). # INDICATES NOMINAL
SCREEN DIAGONAL SIZE.
AV AV SYSTEM CONTROLLER.
DV
W
BLU-RAY/DVD PLAYER WITH CONNECTION TO LOCAL OUTLET. SUBSCRIPT "W" INDICATES WALL MOUNTED ON SHELF.
SB
W
VIDEO ON DEMAND SET TOP BOX. SUBSCRIPT "W" INDICATES WALL MOUNTED ON SHELF.
PC LOCAL RS-232/IP PROJECTOR CONTROLLER.
PS WALL MOUNTED MANUAL PROJECTION SCREEN.
PS CEILING MOUNTED MANUAL PROJECTION SCREEN.
SF SOUNDFIELD SYSTEM CEILING SPEAKER.
IR
SOUNDFIELD SYSTEM CEILING IR SENSOR. LOCATION SHOWN FOR ESTIMATING PURPOSES ONLY. EACH SYMBOL REPRESENTS A QUANTITY OF TWO (2) SENSORS TO BE LOCATED FOR OPTIMUM DROP-FREE RECEPTION.
SC CEILING MOUNTED PAGING/INTERCOM SYSTEM SPEAKER.
W
SINGLE FACED, WALL MOUNTED CLOCK (102" MH UNLESS NOTED OTHERWISE). 12" DIAMETER FACE UNLESS SUBSCRIPT
"15" FOR 15" DIAMETER FACE. SUBSCRIPT "W" INDICATES WIREGUARD.
15 DOUBLE FACED, WALL MOUNTED CLOCK (102" MH UNLESS NOTED OTHERWISE). 12" DIAMETER FACE UNLESS SUBSCRIPT
"15" FOR 15" DIAMETER FACE.
INTERACTIVE WHITE BOARD.IW
TECHNOLOGY SYMBOLS WITH ELEC. REQUIREMENTS
P WALL MOUNTED PHONE OUTLET (46" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. JACKS, FACEPLATE AND CABLE PER DIV 27. REFER TO FACEPLATE DETAILS.
X R
WALL MOUNTED AV OUTLET (84" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES ALTERNATE CONFIGURATION.
X V
WALL MOUNTED AV OUTLET (44" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES ALTERNATE CONFIGURATION.
CONDUIT SLEEVE / FIRE RATED SLEEVE ASSEMBLY THRU WALL (1-2" SLEEVE UNLESS NOTED OTHERWISE) PER DIV 26.
J TELECOM BOX AND CONDUIT PER DIV 26, REFER TO PLANS.
D WALL MOUNTED VOICE/DATA OUTLET (18" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT(S) TO ABOVE CORRIDOR CEILING PER DIV 26. JACKS, FACEPLATE AND CABLE PER DIV 27. REFER TO FACEPLATE DETAILS.
X I
WALL MOUNTED AV OUTLET (18" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUITS TO ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO FACEPLATE DETAILS. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES
ALTERNATE CONFIGURATION.
AP
X
WALL MOUNTED WIRELESS ACCESS POINT (96" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. CABLE PER DIV 27. OWNER TO PROVIDE WAP. SUBSCRIPT "X" INDICATES "G" FOR GUEST
AND "VA" INDICATES IN HOUSE WAP.
AV SYMBOLS WITH ELECTRICAL REQUIREMENTS
W
CS
CLASSROOM SOUNDFIELD SYSTEM RECEIVER/AMPLIFIER/MIXER AND WALL OUTLET (44" MH UNLESS NOTED OTHERWISE).
TWO 1-GANG BOXES WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. SUBSCRIPT "W" INDICATES WALL MOUNTED ON SHELF. SOUNDFIELD SYSTEM, GROMMETED FACEPLATES AND CABLING PER DIV 27.
S H
SURFACE MOUNTED PAGING/INTERCOM SPEAKER (90" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "H" INDICATES HANGING CEILING SPEAKER. 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. SPEAKER, INSTALLATION AND CABLING PER DIV 27.
MUSIC PLAY BACK SPEAKER (102" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. GROMMETED FACEPLATE, SPEAKER, INSTALLATION ADJACENT TO BOX AND WIRING PER
DIV 27.
S M
S HORN TYPE PAGING/INTERCOM SYSTEM SPEAKER (90" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. GROMMETED FACEPLATE, SPEAKER, INSTALLATION AND WIRING PER DIV 27.
V PAGING/INTERCOM SYSTEM WALL MOUNTED SPEAKER VOLUME CONTROLLER (46" MH UNLESS NOTED OTHERWISE). 1- GANG BOX AND 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. VOLUME CONTROLLER WITH FACEPLATE, INSTALLATION AND WIRING PER DIV 27.
M# X
MICROPHONE JACKPLATE (18" MH UNLESS NOTED OTHERWISE). "#"=NUMBER OF GANG, "X"=NUMBER OF JACKS IF OTHER THAN TWO (2). PROVIDE 0.75" CONDUIT FOR 1-GANG BOX OR 1" CONDUIT FOR 2-GANG AND LARGER BOX TO ABOVE
ACCESSIBLE CEILING PER DIV 26. JACKS, FACEPLATE AND CABLING PER DIV 27.
WC X
WALL MOUNTED AV SYSTEM CONTROL INTERFACE. SUBSCRIPT "X" INDICATES TYPE. REFER TO SYSTEM DIAGRAMS.
BACKBOX (46" MH UNLESS NOTED OTHERWISE) WITH 1" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26.
CONTROLLER WITH CABLING PER DIV 27.
SR X
Z
LOCAL SOUND REINFORCEMENT SYSTEM SPEAKER. SUBSCRIPT "X" INDICATES TYPE. REFER TO SYSTEM DIAGRAMS.
SJ
SPEAKER JACKPLATE (18" MH UNLESS NOTED OTHERWISE). 3-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE
CEILING PER DIV 26.
WSF
WALL MOUNTED SOUNDFIELD SYSTEM SPEAKER. 1-GANG BOX WITH 1" CONDUIT TO ABOVE CEILING PER DIV 26.
SPEAKER AND CABLING PER DIV 27.
PR
X
WALL MOUNTED PROJECTOR. BACKBOX WITH 1-1.25" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. PROJECTOR, MOUNT AND CABLING PER DIV 27. SUBSCRIPT "X" INDICATES CONFIGURATION TYPE, REFER TO FACEPLATE DETAILS.
WALL MOUNT ELECTRIC PROJECTION SCREEN. 1-GANG BOX WITH 1" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV
26. SCREEN AND LOW VOLTAGE CONTROL PER DIV 27.
PS
E
CEILING MOUNT ELECTRIC PROJECTION SCREEN. 1-GANG BOX WITH 1" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV
26. SCREEN AND LOW VOLTAGE CONTROL PER DIV 27.
PS
E
LOCAL SOUND SYSTEM SENSING MICROPHONE. 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. MICROPHONE WITH GROMMETED FACEPLATE, INSTALLATION AND WIRING PER DIV 27.SM
HM (x) HANGING MICROPHONE OUTLET. 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. SUBSCRIPT "X" INDICATES QUANTITY OF MICROPHONES IF MORE THAN ONE (1). MICROPHONE, JACK, FACEPLATE AND WIRING PER DIV 27.
MA
MIC/AUX WALL MOUNTED INPUT (18" MH UNLESS NOTED OTHERWISE). 2-GANG BOX WITH 0.75" CONDUIT TO ABOVE
ACCESSIBLE CEILING PER DIV 26. JACKS, FACEPLATE AND CABLING PER DIV 27.
MS
MICROPHONE/SPEAKER WALL MOUNTED JACKPLATE (18" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. JACKS, FACEPLATE AND CABLING PER DIV 27.
ME
MONITOR/EFFECTS WALL OUTLET (18" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE
ACCESSIBLE CEILING PER DIV 26. JACKS, FACEPLATE AND WIRING PER DIV 27.
MULTI-PIN CONNECTOR WALL OUTLET (18" MH UNLESS NOTED OTHERWISE). NEMA BOX FOR 8"x8" PLATE WITH 2" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. 8"x8" PLATE WITH CONNECTORS AND WIRING PER DIV 27.
MP
REMOTE POWER SWITCH OUTLET (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE
ACCESSIBLE CEILING PER DIV 26. SWITCH, FACEPLATE AND WIRING PER DIV 27.
R
P PROGRAM SOURCE CABINET FOR PAGING/INTERCOM SYSTEM. TWO 1-GANG BOXES WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. GROMMETED FACEPLATES, CABINET, INSTALLATION AND WIRING PER DIV 27.
CA
WALL MOUNTED CALL ANNUNCIATOR FOR PAGING/INTERCOM SYSTEM (90" MH UNLESS NOTED OTHERWISE). CUSTOM BACKBOX FURNISHED PER DIV 27, INSTALLED WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26.
ANNUNCIATOR, INSTALLATION AND WIRING PER DIV 27.
CO WALL MOUNTED CALL ORIGINATION SWITCH FOR PAGING/INTERCOM SYSTEM (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. CALL SWITCH, FACEPLATE AND WIRING PER DIV 27.
W
SINGLE FACED WALL MOUNTED CLOCK (102” MH UNLESS NOTED OTHERWISE). 12” DIAMETER FACE ANALOG CLOCK UNLESS SUBSCRIPT “15” FOR 15” DIAMETER FACE ANALOG CLOCK OR “LED” FOR LED DIGITAL CLOCK. SUBSCRIPT “W” INDICATES WIREGUARD. 1-GANG BOX WITH 0.75” CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26.
15 DOUBLE FACED WALL MOUNTED CLOCK (102” MH UNLESS NOTED OTHERWISE). 12” DIAMETER FACE ANALOG CLOCK UNLESS SUBSCRIPT “15” FOR 15” DIAMETER FACE ANALOG CLOCK OR “LED” FOR LED DIGITAL CLOCK. 1-GANG BOX WITH
0.75” CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26.
ROOF MOUNTED ANTENNA. REFER TO ANTENNA MOUNTING DETAIL FOR MORE INFORMATION. SUBSCRIPT INDICATES
TYPE.
A X
PR
X
CEILING MOUNTED PROJECTOR. SUBSCRIPT "X" INDICATES CONFIGURATION TYPE, REFER TO FACEPLATE DETAILS.
WIREMOLD RACEWAY, AS NOTED ON PLANS.
WALL MOUNTED DOORBELL.DB
4"
4"
CABLE TRAY PER DIV 26, 12" x 4" DEEP UNLESS NOTED OTHERWISE.
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.
AR AREA OF REFUGE / AREA OF RESCUE REMOTE CALL STATION (46" MH UNLESS NOTED OTHERWISE).
AP AREA OF REFUGE / AREA OF RESCUE POWER SUPPLY WITHIN A WALL MOUNTED ENCLOSURE.
AM W
AE AREA OF REFUGE / AREA OF RESCUE EXPANSION SWITCH WITHIN A WALL MOUNTED ENCLSURE.
AREA OF REFUGE / AREA OF RESCUE MAIN CONTROL PANEL. "W" INDICATES WALL MOUNTED WITHIN AN ENCLOSURE, OTHERWISE DESKTOP UNIT.
CUSTOM OUTLET IN SURFACE RACEWAY. SURFACE RACEWAY PER DIV 26. OUTLET JACKS, FACEPLATE AND CABLING
PER DIV 27.
T2 1 ELEVATION: 1 = ELEVATION DESIGNATION
T2 = SHEET WHERE ELEVATION IS LOCATED
W
FLOOR BOX PER DIV 26. # INDICATES TYPE, REFER TO FLOOR BOX (FB) SCHEDULE. SUBSCRIPT "X" INDICATES TECHNOLOGY
DEVICE(S), REFER TO TECHNOLOGY DETAILS.
X
POKE-THRU PER DIV 26. # INDICATES TYPE, REFER TO POKE-THRU (PT) SCHEDULE. SUBSCRIPT "X" INDICATES TECHNOLOGY
DEVICE(S), REFER TO TECHNOLOGY DETAILS.
X
EDC
X ELECTRONIC DOOR CONTROL. SUBSCRIPT "X" INDICATES SPECIFIC DOOR. REFER TO ELECTRONIC DOOR CONTROL
SCHEDULE FOR REQUIREMENTS.
N
N
N B
N Z
NC
NS
ND
N
W
NM
N T
N E
N B
NCCP
C
NS
P
NS
NURSE CALL SYMBOLS
NURSE CALL DESK MOUNTED MASTER CONTROL STATION (OUTLET AT 18" MH UNLESS NOTED OTHERWISE). SUBSCRIPT
"W" INDICATES WALL MOUNT (46" MH UNLESS NOTED OTHERWISE).
NURSE CALL CONTROL PANEL.
NURSE CALL STAFF STATION (46" MH UNLESS NOTED OTHERWISE).
NURSE CALL DUTY STATION (46" MH UNLESS NOTED OTHERWISE).
EMERGENCY NURSE CALL STATION WITH PULL CORD FOR PATIENT USE (46” MH AND TO SIDE AND WITHIN 12” FROM FRONT OF TOILET BOWL IN TOILET ROOMS, 66” MH IN SHOWERS AND WET AREAS, 46” MH UNLESS NOTED OTHERWISE IN
ALL OTHER AREAS).
ENHANCED SINGLE PATIENT STATION (46" MH UNLESS NOTED OTHERWISE).
PATIENT NURSE CALL STATION (ONE OR TWO CORDS AS INDICATED, 46" MH UNLESS NOTED OTHERWISE).
CEILING MOUNTED NURSE CALL DOME LIGHT.
WALL MOUNTED NURSE CALL DOME LIGHT (90" MH UNLESS NOTED OTHERWISE).
CEILING MOUNTED COMBINATION DOME LIGHT AND BUZZER.
CEILING MOUNTED NURSE CALL ZONE LIGHT.
NURSE CALL EMERGENCY BUTTON (46" MH UNLESS NOTED OTHERWISE).
STAFF ASSIST/CODE STATION EMERGENCY CODE BLUE BUTTON (46" MH UNLESS NOTED OTHERWISE).
NURSE CALL MULTI-PIN CATV JACK (84" AFF UNLESS NOTED OTHERWISE).
NURSE CALL STAFF PRESENCE STATION (60" AFF UNLESS NOTED OTHERWISE).
N S
ENHANCED PATIENT NURSE CALL TO STRYKER BED 37 PIN CONNECTOR (30" MH UNLESS NOTED OTHERWISE).
COLOR USAGE
YELLOW WiFi VA - SECURE
PINK WiFi - GUEST/PUBLIC
BLUE DATA
GREY EVIDION PATIENT MONITOR
GREEN MEDICAL
RED SECURITY
PURPLE NURSE CALL
WHITE ANALOG VOICE
NOTES
ELOPEMENT
PLAIN OI TELEPHONE (POTS LINE)
COLOR CODE: PROVIDE THE FOLLOWING COLOR MARKERS FOR
SERVICE IDENTIFICATION.
COLOR SERVICE
RED SPRINKLER SYSTEM: VALVES AND CONTROLS
GREEN DOMESTIC WATER: VALVES AND CONTROLS
YELLOW CHILLED WATER AND HEATING WATER
ORANGE DUCTWORK: FIRE DAMPERS
BLUE DUCTWORK: DAMPERS AND CONTROLS
BLACK GAS: LABORATORY, MEDICAL, AIR AND VACUUM
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:3
:0
A
M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
ABBREVIATION, SYMBOLS & INDEX
OF DRAWINGS
T001
GESJCM
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
INDEX OF DRAWINGS - TECHNOLOGY
Sheet Number Sheet Name
T001 ABBREVIATION, SYMBOLS & INDEX OF DRAWINGS
T002 BID DEDUCT ALTERNATES 01 & 02
T003 BID DEDUCT ALTERNATES 03 & 04
TD103 PARTIAL THIRD FLOOR PLAN - REMOVALS
TD104 PARTIAL FOURTH FLOOR PLAN - REMOVALS
TD105 PARTIAL FIFTH FLOOR PLAN - REMOVALS
TA103 PARTIAL THIRD FLOOR PLAN - TECHNOLOGY
TA104 PARTIAL FOURTH FLOOR PLAN - TECHNOLOGY
TA105 PARTIAL FIFTH FLOOR PLAN - TECHNOLOGY
TA106 FIRST FLOOR PLAN BUILDING 28 - TECHNOLOGY
TY103 PARTIAL THIRD FLOOR PLAN - TECHNOLOGY SECURITY
TY104 PARTIAL FOURTH FLOOR PLAN - TECHNOLOGY SECURITY
TY105 PARTIAL FIFTH FLOOR PLAN - TECHNOLOGY SECURITY
T401 ENLARGED PLANS
T402 ENLARGED PLANS
T501 TECHNOLOGY DETAILS
T502 TECHNOLOGY DETAILS & SCHEDULES
CAT6/CAT6A COLOR CODES
CEILING IDENTIFICATION MARKERS
Revisions Date
D
D D
DATA
B306C
DATA
B370
COMMON
SPACE
A317A
STORAGE
307A
STORAGE
HEALTHY
TEACHING
KITCHEN
OPEN
OFFICE
C3-B-1
CORRIDOR-1
C3-B-2
CORRIDOR-2
OPEN
OFFICE
OPEN
OFFICE
CHAPEL
LOBBY
SPACE
01 - DEDUCT ALTERNATE 01:
OMIT ALL NEW WORK RELATED TO THE
OPEN OFFICES AND CHAPEL.
SPACE WILL BE UNFINISHED STORAGE.
STAIR 1
S-01
MECHANICAL
ROOM
ELECTRICAL
SHOP
A474
ELECTRICAL
A470
DATA
A432A
DATA
S-4-4
MECHANICAL
401A
OFFICE
02 - DEDUCT ALTERNATE 02:
OMIT ALL NEW WORK RELATED TO THE
ELECTRICAL SHOP.
SPACE WILL BE UNFINISHED STORAGE.
ELECTRICAL
SHOP
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:3
:1
A
M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
BID DEDUCT ALTERNATES 01 & 02
T002
GESJCM
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
Scale: 1/8" = 1'-0"1
BID DEDUCT 01 - REMOVE THIRD FLOOR OFFICES AND
CHAPEL
Scale: 1/8" = 1'-0"2
BID DEDUCT 02 - REMOVE FOURTH FLOOR
ELECTRICAL SHOP
B F
BF
SC
DATA
B306C
DATA
B370
COMMON
SPACE
A317A
STORAGE
307A
STORAGE
HEALTHY
TEACHING
KITCHEN
OPEN
OFFICE
C3-B-1
CORRIDOR-1
C3-B-2
CORRIDOR-2
OPEN
OFFICE
OPEN
OFFICE
CHAPEL
LOBBY
SPACE
03 - DEDUCT ALTERNATE 03:
OMIT ALL NEW WORK RELATED TO THE
TEACHING KITCHEN.
EXISTING OFFICE CONSTRUCTION
TO REMAIN.
SPACE WILL BE UNFINISHED STORAGE.
514 513
C5-50A
C5-51B
C5-50B
CORRIDOR
C5-09
CORRIDOR-1
A535-1
LOUNGE
NS-503
NURSE
STATION
STAFF
LOUNGE
A513
2BR
SOILED
HOLD
1BR
ISOLATION
ROOM #1
505A
BATH
507A
BATH
1BR
PATIENT
ROOM #2
522D
FEMALE
LAV
522B
MALE
LAV
CLEAN
UTILITY
EQUIPMENT
STORAGE
505B
ANTE
OFFICE
CLEAN
LINEN
522A
LOCKERS
522C
LOCKERS
NS-500
NURSE
STATION
SPACE
WHEEL
CHAIR/
STRETCHER
MED
ROOM
1BR
PATIENT
ROOM #3509A
BATH
1BR
PATIENT
ROOM #4
515A
BATH
517A
BATH
519A
BATH
NS-501
NURSE
STATION
NUTRITION
1 BR
PATIENT
ROOM #7
1 BR
PATIENT
ROOM #8
524A
BATH
1 BR
PATIENT
ROOM #9
525A
BATH
523A
BATH
ALCOVE
1BR
PATIENT
ROOM #5
1BR
PATIENT
ROOM #6
NS-502
NURSE
STATION
C5-51
CORRIDOR
B511
2BR
B509
2BR
A511
ELEC
A578
ELEC
A575
DATA
A525
DATA
C5-50
CORRIDOR
C5-52
CORRIDOR
C5-13
CORRIDOR
04 - DEDUCT ALTERNATE 04:
OMIT ALL NEW WORK RELATED TO THE
NEW LOUNGE AND LOCKER ROOMS.
EXISTING LOCKERS, HAC, SOILED
UTILITY AND OFFICE TO REMAIN.
04 - DEDUCT ALTERNATE 04:
EXISTING OFFICE TO BECOME CLEAN
LINEN ROOM.
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:3
:3
A
M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
BID DEDUCT ALTERNATES 03 & 04
T003
GESJCM
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
Scale: 1/8" = 1'-0"1
BID DEDUCT 03 - REMOVE THIRD FLOOR TEACHING
KITCHEN
Scale: 1/8" = 1'-0"2
BID DEDUCT 04 - RETAIN EXISTING FIFTH FLOOR
LOCKERS AND RESTROOMS
D D
D D
D
D
D
D
AP
G
AP
G
AP
VA
AP
VA
SC
SC
SC SC
N
N
AP
G
AP
VA
AP
VA
D
D
D
D
D
B01W
B01E
H.2 H.7
A C
F G I J
L
E
DATA
A370
NURSES
STATION
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:4
:2
A
M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
PARTIAL THIRD FLOOR PLAN -
REMOVALS
TD103
GESJCM
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
N Scale: 1/8" = 1'-0"
PARTAIL THIRD FLOOR PLAN - REMOVALS
KEYPLAN
GENERAL NOTES
A. WHERE CEILINGS ARE BEING REPLACED PROTECT CEILING MOUNTED
DEVICES OR RE-INSTALL IN NEW CEILING.
B. INSURE CEILING MOUNTED SPEAKER CIRCUITS OPERATION MUST BE
MAINTAINED FOR OPERATION INTO OTHER AREAS.
C. EXISTING CABLE TRAY ABOVE CEILING TO BE MAINTAINED.
NOTES
1. EXISTING SIGNALS AND EQUIPMENT CLOSETS. NEW DATA AND DEVICES SHALL
BE SERVED FROM EXISTING LOCATIONS.
B01W
B01E
H.2 H.7
A C
F G I J
L
E
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:4
:2
A
M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
PARTIAL FOURTH FLOOR PLAN -
REMOVALS
TD104
GESJCM
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
N Scale: 1/8" = 1'-0"
PARTIAL FOURTH FLOOR PLAN - REMOVALS
KEYPLAN
GENERAL NOTES
A. NO DEMOLITION WORK IS TO BE DONE ON THIS FLOOR.
D
D
D
D
D
N N
NC
NC
ND
N B
N
N
AP
G
AP
VA
AP
VA
SC
SCSCSC
SC
SC
AP
VA
AP
VA
AP
VA
AP
G
AP
G
AP
D
D
D
D
N D
ND
ND
ND
N N
N N N
N D
N D
ND
ND
N D
N C
N C
NC
NC NC
N
N
NN
N
N
N
N
D
D D
D D
D D
D D
D
D
D
D D
D
AP
VA
AP
G
AP
G
SC SC SC
SC
V X
D
B01W
B01E
H.2 H.7
A C
F G I J
L
E
A575
DATA
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:4
:3
A
M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
PARTIAL FIFTH FLOOR PLAN -
REMOVALS
TD105
GESJCM
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
N Scale: 1/8" = 1'-0"
PARTIAL FIFTH FLOOR PLAN - REMOVALS
KEYPLAN
GENERAL NOTES
A. WHERE CEILINGS ARE BEING REPLACED PROTECT CEILING MOUNTED
DEVICES OR RE-INSTALL IN NEW CEILING.
B. INSURE CEILING MOUNTED SPEAKER CIRCUITS OPERATION MUST BE
MAINTAINED FOR OPERATION INTO OTHER AREAS.
NOTES
1. EXISTING SIGNALS AND EQUIPMENT CLOSETS. NEW DATA AND DEVICES SHALL
BE SERVED FROM EXISTING LOCATIONS.
AP
G
AP
G
AP
VA
SC
SC SC
N
N
AP
G
AP
VA
SC
84" MH
V
SC
SC
SC
SC
SC
SC
SC
SC SC
SC
SC
SC
SC
AP
G
AP
G
48" MH
V
48" MH
D
48" MH
V
SC
46" MH
D
46" MH
D
N T
N T
48" MH
I
D
48" MH
D
D
D
D
D
D
D
D
D
D
D
D
V
AP
AP
AP
AP
B01W
B01E
H.2 H.7
A C
F G I J
L
E
DATA B306C
DATA B370
T401
T401
DATA
B306C
DATA
A370
COMMON
SPACE
A317A
STORAGE
307A
STORAGE
HEALTHY
TEACHING
KITCHEN
OPEN
OFFICE
C3-B-1
CORRIDOR-1
C3-B-2
CORRIDOR-2
OPEN
OFFICE
OPEN
OFFICE
CHAPEL
LOBBY
SPACE
1-4"C.
1-4"C.
12"x4"
"x
307B
307C
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:4
:0
A
M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
PARTIAL THIRD FLOOR PLAN -
TECHNOLOGY
TA103
GESJCM
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
N Scale: 1/8" = 1'-0"
PARTIAL THIRD FLOOR PLAN
KEYPLAN
NOTES
1. EXISTING SIGNALS AND EQUIPMENT CLOSETS. NEW DATA AND DEVICES SHALL
BE SERVED FROM EXISTING LOCATIONS. SEE SHEET T401 FOR ADDITIONAL
INFORMATION.
2. EXISTING CABLE TRAY. SEE SHEET TD103 FOR EXISTING CABLE TRAY ROUTING.
3. NEW CABLE TRAY.
GENERAL NOTES
A. INSTALL EXISTING DEVICES FROM ROOM F111 SHEET TA106 IN NEW CHAPEL
ROOM 308. TEST DEVICES AFTER REINSTALLING TO ENSURE PROPER
OPERATION AND DOCUMENT RESULTS.
AP
D DD D D D D
46" MH
D
D
46" MH
D
46" MH
D
46" MH
D
46" MH
D
46" MH
D
DD
B01W
B01E
H.2 H.7
A C
F
F
G
G
I J LE
M
T401
S-01-4A STAIR 1
S-01
DATA
A437
MECHANICAL
ROOM
ELECTRICAL
SHOP
A474
ELECTRICAL
A470
DATA
A432A
DATA
S-4-4
MECHANICAL
401A
OFFICE
1-4"C.
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:4
:1
A
M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
PARTIAL FOURTH FLOOR PLAN -
TECHNOLOGY
TA104
GESJCM
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
N Scale: 1/8" = 1'-0"
PARTIAL FOURTH FLOOR PLAN
KEYPLAN
NOTES
1. EXISTING SIGNALS AND EQUIPMENT CLOSETS. NEW DATA AND DEVICES SHALL
BE SERVED FROM EXISTING LOCATIONS. SEE SHEET T401 FOR ADDITIONAL INFORMATION.
GENERAL NOTES
A. CONDUIT TO COORIDOR SHALL TRANSITION TO J-HOOK.
J-HOOK SPACING NOT TO EXCEED 5'-0".
B F
BF
D
AP
G
AP
VA
AP
VA
SC
SCSCSC
SC
SC
AP
VA
AP
VA
AP
G
AP
G
AP
AP
VA
AP
G
AP
G
SC
SC
V X
D
D
D
D
D
D
D
D
D
D
D
D
D
D D
D D
DD
D
ND ND
ND
ND
SCSC
SC
SC
SC
SC
SC
SC
SC
SC
D
D
D
D
D
NM
NM
NM
AP
AP
AP AP
AP
AP
AP
AP
AP
AP
AP AP
D
ND
NM
ND
D
D
84" MH
D
D
D
D
D
D
78" MH
D
78" MH
D
78" MH
B01W
B01E
H.2 H.7
A C
F
F
G I J
L
E
T402
DATA A525
DATA A575
T402
T402
T402
T402
T402
T402
T402
T402
514 513
T401
T401
C5-50A
C5-51B
C5-50B
CORRIDOR
C5-09
CORRIDOR-1
A535-1
LOUNGE
NS-503
NURSE
STATION
STAFF
LOUNGE
A513
2BR
SOILED
HOLD
1BR
ISOLATION
ROOM #1
505A
BATH
507A
BATH
1BR
PATIENT
ROOM #2
522D
FEMALE
LAV
522B
MALE
LAV
CLEAN
UTILITY
EQUIPMENT
STORAGE
505B
ANTE
OFFICE
CLEAN
LINEN
522A
LOCKERS
522C
LOCKERS
NS-500
NURSE
STATION
SPACE
WHEEL
CHAIR/
STRETCHER
MED
ROOM
1BR
PATIENT
ROOM #3509A
BATH
1BR
PATIENT
ROOM #4
515A
BATH
517A
BATH
519A
BATH
NS-501
NURSE
STATION
NUTRITION
1 BR
PATIENT
ROOM #7
1 BR
PATIENT
ROOM #8
524A
BATH
1 BR
PATIENT
ROOM #9
525A
BATH
523A
BATH
ALCOVE
1BR
PATIENT
ROOM #5
1BR
PATIENT
ROOM #6
NS-502
NURSE
STATION
C5-51
CORRIDOR
B511
2BR
B509
2BR
A511
ELEC
A578
ELEC
A575
DATA
A525
DATA
C5-50
CORRIDOR
C5-52
CORRIDOR
C5-13
CORRIDOR
12"x4"
"x
"x
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:4
:1
A
M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
PARTIAL FIFTH FLOOR PLAN -
TECHNOLOGY
TA105
GESJCM
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
N Scale: 1/8" = 1'-0"
PARTIAL FIFTH FLOOR PLAN
KEYPLAN
NOTES
1. EXISTING SIGNALS AND EQUIPMENT CLOSETS. NEW DATA AND DEVICES SHALL
BE SERVED FROM EXISTING LOCATIONS. SEE SHEET T401 FOR ADDITIONAL INFORMATION.
2. EXISTING NURSE CALL (RAULAND RESPONDER) POWER SUPPLIES AND NETWORK
SWITCH CABINET.
3. UTILIZE COLUMN TO ROUTE DATA CABLING AT WORKSTATIONS.
FG66
FG68 FG70
FG72
FG74
FG76
FG63A
FG71
FG69
FG65
FG67
FG78
FG64
FG62
FG60
FG58
FG63
FG61 FG81
FG83
FG59
FG80
FG82
FG84
FG56
FG54
FG52
FG57 FG85
FG55
FG53
FG51
FG86
F188
FG88A
FG32
FG49
FG23
FG25
FG27 FG29
FG31 FG33 FG35
FG37 FG39 FG41 FG43 FG45 FG47
FG46FG44FG42
FG40
FG38
F134
F136
F188b
A180
CC
CC
48" MH
I
CHAPEL
F111
OUTLET TYPE "I"
AV OUTLET
1-POSITION DOUBLE GANG STAINLESS STEEL:
• ONE (1) HDMI COUPLER.
• ONE (1) LIGHTED BUTTON.
MOUNTING HEIGHT = 48" AFF UNLESS OTHERWISE NOTED
ROUTING = 1" CONDUIT AND BACKBOX WITH BUSHING TO
ABOVE ACCESSIBLE CEILING. HDMI CABLE TO LOCAL
CAMERA.
I
1" CONDUIT
CAMERA MOUNTING DETAIL NOTES
INTERIOR - CEILING RECESSED
1. CAMERA AS SHOWN ON THE PLANS.
2. 0.75" CONDUIT TO BE ROUTED TO ACCESSIBLE INTERIOR JUNCTION BOX.
3. JUNCTION BOX ABOVE ACCESSIBLE CEILING.
4. 1-DATA OUTLET UTILIZING SURFACE MOUNT "BISCUIT" FOR TERMINATION
OF DATA DROP INTO RJ-45 OUTLET.
5. PROVIDE PATCH CABLE WITH CONNECTIONS.
6. 15' COIL OF CABLE MANAGED ABOVE CEILING.
5 4 6
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:4
:1
A
M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
FIRST FLOOR PLAN BUILDING 28 -
TECHNOLOGY
TA106
GESJCM
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
N Scale: 3/32" = 1'-0"
PARTIAL FIRST FLOOR PLAN
B28
SCALE: NONE
VIDEO STREAMING FACEPLATE
NOTES
1. CEILING MOUNTED PANASONIC CAMERA TO REMAIN, NO WORK.
2. CEILING MOUNTED SONY IPELA CAMERA TO BE CAREFULLY REMOVED AND
REINSTALLED ON THE CEILING OF 3RD FLOOR ROOM 308 "CHAPEL" SEE SHEET TY103.
3. REMOVE COVER PLATE AND BLANK OFF, DISCONNECT CABLING AND PULL BACK FOR
REMOVAL.
GENERAL NOTES
A. TEST DEVICES BEFORE WORK IS STARTED TO ENSURE OPERATION AND
DOCUMENT RESULTS. CAREFULLY REMOVE DEVICES AND STORE FOR
REINSTALLATION IN NEW CHAPEL ROOM 308 SHOWN ON SHEET TA103.
SCALE: 1/8" = 1'-0"
EXISTING CAMERA MOUNTING DETAIL
CC
CC
K
CC
CC
CC
CC
EDC
EDC
CR
CR
CC
B01W
B01E
H.2 H.7
A C
F
F
G
G
I J
L
E
DATA B306C
DATA B370
307B
DATA
B306C
DATA
A370
307C
COMMON
SPACE
A317A
STORAGE
307A
STORAGE
HEALTHY
TEACHING
KITCHEN
OPEN
OFFICE
C3-B-1
CORRIDOR-1
C3-B-2
CORRIDOR-2
OPEN
OFFICE
OPEN
OFFICE
CHAPEL
LOBBY
SPACE
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:4
:3
A
M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
PARTIAL THIRD FLOOR PLAN -
TECHNOLOGY SECURITY
TY103
GESJCM
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
N Scale: 1/8" = 1'-0"
PARTIAL THIRD FLOOR PLAN
KEYPLAN
NOTES
1. CEILING MOUNTED SONY IPELA CAMERA TO BE CAREFULLY REINSTALLED ON THE
CEILING OF 3RD FLOOR ROOM 308. VERIFY LOCATION OF RELOCATED CAMERA WITH
OWNER.
EDC
CC
CR
B01W
B01E
H.2 H.7
A C
F
F
G
G
I J LE
M
S-01-4A STAIR 1
S-01
DATA
A437
MECHANICAL
ROOM
ELECTRICAL
SHOP
A474
ELECTRICAL
A470
DATA
A432A
DATA
S-4-4
MECHANICAL
401A
OFFICE
DATA A437
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:4
:3
A
M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
PARTIAL FOURTH FLOOR PLAN -
TECHNOLOGY SECURITY
TY104
GESJCM
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
N Scale: 1/8" = 1'-0"
PARTIAL FOURTH FLOOR PLAN
KEYPLAN
NOTES
1. NEW DATA AND DEVICES SHALL BE SERVED FROM A437.
B F
BF
K
CC
CC
CC
CC
CC
K
CR
EDC
CR CR
EDC
EDC
CR
EDC
CC
CC
CC
EDC
4CR
CC
CC
CC
CC
EDC
EDC
EDC
CRHA
HA
CR
CC
HA
CR
B01W
B01E
H.2 H.7
A C
F
F
G
G
I J
L
E
DATA A525
DATA A575
514 513
C5-50A
C5-51B
C5-50B
CORRIDOR
C5-09
CORRIDOR-1
A535-1
LOUNGE
NS-503
NURSE
STATION
STAFF
LOUNGE
A513
2BR
SOILED
HOLD
1BR
ISOLATION
ROOM #1
505A
BATH
507A
BATH
1BR
PATIENT
ROOM #2
522D
FEMALE
LAV
522B
MALE
LAV
CLEAN
UTILITY
EQUIPMENT
STORAGE
505B
ANTE
OFFICE
CLEAN
LINEN
522A
LOCKERS
522C
LOCKERS
NS-500
NURSE
STATION
SPACE
WHEEL
CHAIR/
STRETCHER
MED
ROOM
1BR
PATIENT
ROOM #3
509A
BATH
1BR
PATIENT
ROOM #4
515A
BATH
517A
BATH
519A
BATH
NS-501
NURSE
STATION
NUTRITION
1 BR
PATIENT
ROOM #7
1 BR
PATIENT
ROOM #8524A
BATH
1 BR
PATIENT
ROOM #9
525A
BATH
523A
BATH
ALCOVE
1BR
PATIENT
ROOM #5
1BR
PATIENT
ROOM #6
NS-502
NURSE
STATION
C5-51
CORRIDOR
B511
2BR
B509
2BR
A511
ELEC
A578
ELEC
A575
DATA
A525
DATA
C5-50
CORRIDOR
C5-52
CORRIDOR
C5-13
CORRIDOR
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:4
:4
A
M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
PARTIAL FIFTH FLOOR PLAN -
TECHNOLOGY SECURITY
TY105
GESJCM
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
N Scale: 1/8" = 1'-0"
PARTIAL FIFTH FLOOR PLAN
KEYPLAN
J
T401
DATA
A370
J
T401
DATA
B306C
T401
DATA
A525
J
T401DATA
A575
1 1
H.7
1 1
M
T401
DATA
A437
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:3
:5
A
M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
ENLARGED PLANS
T401
GESJCM
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
SCALE: 1/2" = 1'-0"
THIRD FLOOR-TECH - DATA A370
SCALE: 1/2" = 1'-0"
THIRD FLOOR-TECH - DATA B306C
SCALE: 1/2" = 1'-0"
FIFTH FLOOR-TECH - DATA A525
SCALE: 1/2" = 1'-0"
FIFTH FLOOR-TECH - DATA A575
SCALE: 1 1/2" = 1'-0"
RACK ELEVATION - DATA A370
SCALE: 1 1/2" = 1'-0"
RACK ELEVATION - DATA B306C
SCALE: 1 1/2" = 1'-0"
RACK ELEVATION - DATA A525
9 SCALE: 1 1/2" = 1'-0"
RACK ELEVATION - DATA A575
SCALE: 1/2" = 1'-0"
FOURTH FLOOR-TECH - DATA A437
SCALE: 1 1/2" = 1'-0"
RACK ELEVATION - DATA A437
PLAN NOTES:
1. EXISTING RELAY RACK.
2. NEW 24 PORT ANGLED PATCH PANEL.
3. NEW 24 PORT NETWORK SWITCH.
4. NEW 2RU FRONT AND REAR HORIZONTAL WIRE MANAGER.
N T
N T
N
NC
66" MH
V
72" MH
D
18" MH
D
18" MH
D
AP
54" MH
D
N B
54" MH
D
N B
N B
F G
E
T402
507A
BATH
1BR
PATIENT
ROOM #2
S
37 PIN BED
CONNECTOR
FFFFF
CODE BLUE
PATIENT MONITORINGPATIENT MONITORING
32 PIN BED CONNECTOR
ENHANCED SINGLE
PATIENT STATION
D
D D
D
N B
N B
NC
N
BS
E
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:3
:5
A
M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
ENLARGED PLANS
T402
GESJCM
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
N Scale: 1/2" = 1'-0"2
TYPICAL PATIENT ROOM - TECHNOLOGY
Scale: 1/2" = 1'-0"1
PATIENT HEADWALL - TECHNOLOGY ELEVATION
1 2
3 4
02-220-01
02-TR-02NE
FACEPLATE ID
XX XXX XX
FACEPLATE NUMBER IN ROOM
ROOM NUMBER
BUILDING/FLOOR IDENTIFIER
TELECOMMUNICATIONS ROOM ID
XX XX-XXXX
TR NUMBER ON FLOOR
BUILDING/FLOOR IDENTIFIER
NOTES:
1. EACH "TO" SHALL BE LABELED AS SHOWN. THE CONTRACTOR SHALL BE RESPONSIBLE
FOR INSTALLING A MACHINE-PRINTED LABEL WITH THE CORRECT "TO" NUMBER AND TR ID.
2. CABLE JACKET COLOR SHALL MATCH THE JACK COLOR.
OUTLET TYPE "D"
DUPLEX (VOICE/DATA)
2-POSITION SINGLE GANG FACEPLATE
WITH CLEAR LABEL WINDOWS:
• TWO (2) MODULAR 8-POSITION JACKS "BLUE"
• TWO (2) 4-PAIR CATEGORY UTP CABLES "BLUE"
MOUNTING HEIGHT = 18" AFF
ROUTING = 1" CONDUIT AND BACKBOX WITH BUSHING
TO CORRIDOR CABLE TRAY.
OUTLET TYPE "J1"
SYSTEMS FURNITURE FEED
SINGLE GANG FACEPLATE WITH GROMETTED
OPENING.
MOUNTING HEIGHT = 18" AFF
ROUTING = 1" CONDUIT AND BACKBOX WITH
BUSHING TO CORRIDOR CABLE TRAY.
TELECOMMUNICATIONS OUTLET LABELING SCHEME
3 FT., MIN. SLACK COIL 3 FT., MIN. SLACK COIL
OUTLET TYPE "D4"
QUADPLEX (VOICE/DATA)
4-POSITION SINGLE GANG FACEPLATE
WITH CLEAR LABEL WINDOWS:
• FOUR (4) MODULAR 8-POSITION JACK "BLUE"
• FOUR (4) 4-PAIR CATEGORY UTP CABLES "BLUE"
MOUNTING HEIGHT = 18" AFF
ROUTING = 1.25" CONDUIT AND BACKBOX WITH BUSHING
TO CORRIDOR CABLE TRAY.
3 FT., MIN. SLACK COIL
D
D
J
CEILING LINE
1-POSITION SURFACE BOX "BISCUIT":
• ONE (1) MODULAR 8-POSITION JACK "YELLOW"
• ONE (1) CATEGORY UTP CABLES "YELLOW"
CONTRACTOR SHALL FURNISH AND TERMINATE CABLES WITH A 15 FT. SLACK
COIL AT EACH LOCATION.
25 FT. SLACK COIL
WIRELESS DEVICE
ACCESS POINT (AP)
(LAY-IN CEILING)
AP
CEILING LINE
1-POSITION SURFACE BOX "BISCUIT":
• ONE (1) MODULAR 8-POSITION JACK "RED"
• ONE (1) CATEGORY UTP CABLES "RED"
CONTRACTOR TO FOLLOW THE INSTALLATION DETAILS ON DRAWING T502.
25 FT. SLACK COIL
CCTV CAMERA (CC)
(LAY-IN CEILING)
CC
37 PIN BED CONNECTOR
SIZE 2"x4", 2.125"D, 2-GANG OPENING
POWER
MOUNTING
24VDC, 1/2 WATT PER LAMP
RACO #191 W/ 2-GANG RING OR EQUAL
OTHER (2) LED & (6) LED
EMERGENCY STATION W/ PULL CORD
SIZE
POWER
MOUNTING
OTHER
2"x4", 2.125"D, 1-GANG OPENING
24VDC, 1/2 WATT
RACO #191 W/ 1-GANG RACO #768
PLASTER RING OR EQUAL
ENHANCED PATIENT STATION
SIZE 3-GANG 4.5"H X 6.38"W X 2.0"D
POWER
MOUNTING
24VDC, 3 WATTS
3-GANG STEEL CITY H3BD W. 3GC 3/4"
COVER, OR EQUAL
OTHERINCL. 6' PULL CORD
N T
NC
3/4 IN. BUSHED CONDUIT 3/4 IN. BUSHED CONDUIT 3/4" IN. BUSHED CONDUIT
N
CEILING MOUNTED DOME LIGHT
SIZE 2"x4", .5"D, 1-GANG OPENING
POWER
MOUNTING
24VDC, 1/2 WATT PER LAMP
RACO #191 W/ 2-GANG RING OR EQUAL
OTHER (2) LED & (6) LED
MANUFACTURER
SPECIFIED BOX
3/4 IN. BUSHED CONDUIT
MANUFACTURER
SPECIFIED BOX
MANUFACTURER
SPECIFIED BOX
MANUFACTURER
SPECIFIED BOX
CEILING LINE
STAFF ASSIST/CODE STATION
SIZE
POWER
MOUNTING
OTHER
2"x4" , 3.5"D, 1-GANG OPENING
24VDC, 1/2 WATT
RACO #191 W/ 1-GANG RACO #768
PLASTER RING OR EQUAL
ADAPTOR PLATE INCLUDED
3/4 IN. BUSHED CONDUIT
MANUFACTURER
SPECIFIED BOX
N B
1" CONDUIT 1.25" CONDUIT 1" CONDUIT
BASIS OF DESIGN FOR DATA CABLING IS COMMSCOPE
1 2
OUTLET TYPE "NS"
32 PIN BED CONNECTOR
• ONE (1) 4-PAIR CATEGORY UTP CABLES "PURPLE"
MOUNTING HEIGHT = 43" AFF
ROUTING = 3/4" CONDUIT AND BACKBOX WITH
BUSHING. TO NURSE CALL PATIENT STATION
CAT6A TO NURSE CALL
PATIENT STATION
3/4" CONDUIT
N S
RAULAND - IP68 WATERPROOF PULL CORD STATION 354001WPRAULAND - STAFF ASSIST/CODE STATION 354015
N S
RAULAND - RESPONDER BED RECEPTACLE - 37 PIN NCBED5 RAULAND - CORRIDOR LIGHT 352011
STAFF/DUTY STATION
SIZE 3-GANG 4.5"H X 6.38"W X 2.0"D
POWER
MOUNTING
24VDC, 3 WATTS
3-GANG STEEL CITY H3BD W. 3GC 3/4"
COVER, OR EQUAL
OTHER
ND
3/4" IN. BUSHED CONDUIT
MANUFACTURER
SPECIFIED BOX
RAULAND ENHANCED SINGLE PATIENT STATION 353001 RAULAND DUTY STATION 353100
ADAPTOR PLATE INCLUDED ADAPTOR PLATE INCLUDED
VoIP NURSE CONSOLE
SIZE 9.2"H X 10.4"W X 1.9"D
POWER
MOUNTING
24VDC, 3 WATTS
3-GANG STEEL CITY H3BD W. 3GC 3/4"
COVER, OR EQUAL
OTHER
NM
RAULAND VoIP NURSE CONSOLE 351205
DATA
RF
DETAIL NOTES
1. RF TYPE "F" COAXIAL CONNECTOR WITH RF CABLING (RG-6) FOR CATV BACK TO THE
TR. CONNECT TO RF DISTRIBUTION SYSTEM.
2.…