Attachment 10 - Drawings - Structural.pdf
PDF 3 MB Posted
- Solicitation number
- 36C25024B0031_1
About this file
This document is a set of Structural Drawings and General Structural Notes for the "Construct Private In-Patient Rooms and Primary Clinics" federal contract opportunity, Solicitation Number 36C25024B0031_1.
The key details include:
- Structural design criteria such as building codes, design loads, material specifications, and construction requirements for concrete, steel, and metal deck
- Framing plans for the 3rd through 5th floors and roof, showing beam and column sizes, locations, and connections
- Structural details for connections, bracing, openings, and specialty items like patient lift supports
- A steel column schedule with new column sizes and attachment to existing structure
- Supplemental framing elevations and details for the west building façade
This comprehensive set of structural drawings and notes provides the technical requirements for the structural system of the new building addition and renovations.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A. CODES AND SPECIFICATIONS
1. 2021 INTERNATIONAL BUILDING CODE.
2. VA SEISMIC DESIGN REQUIREMENTS H 18-8 (MAY 2020).
3. VA PHYSICAL SECURITY AND RESILIENCE DESIGN MANUAL (PSRDM) OCTOBER 2020, REVISED JUNE 2023.
4. ASCE/SEI 7-16, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES.
5. ACI 301-16, SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS AS MODIFIED BY THE CONSTRUCTION DOCUMENTS.
6. ANSI/AISC 303-16, CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES AS MODIFIED BY THE CONSTRUCTION DOCUMENTS.
7. ANSI/AWS D1.1, STRUCTURAL WELDING CODE – STEEL.
8. ADDITIONAL TECHNICAL SPECIFICATIONS IN THE PROJECT MANUAL.
B. DESIGN LOADS
1. FLOOR LOAD:
TYPICAL FLOOR LIVE LOAD: 100 PSF, 2000 LBS CONCENTRATED
STAIRS AND LOBBY LIVE LOAD: 100 PSF
MECHANICAL ROOM LIVE LOAD: 150 PSF (NR), MIN. 2000 LBS CONCENTRATED
CEILING AND MECHANICAL ALLOWANCE
ABOVE TYPICAL FLOOR AREAS: 10 PSF
ABOVE MECHANICAL ROOMS: 25 PSF
PARTITION ALLOWANCE (LL < 80 PSF): 15 PSF
2. ROOF LOAD:
ROOF LIVE LOAD, MINIMUM: 20 PSF - (NR)
CEILING AND MECHANICAL ALLOWANCE
ABOVE TYPICAL FLOOR AREAS: 10 PSF
ABOVE MECHANICAL ROOMS: 25 PSF
ROOFING AND BALLAST ALLOWANCE: 15 PSF
CONCENTRATED LOAD ON ROOF: 300 LBS
RTU DEAD LOADS: NOTED ON ROOF FRAMING PLAN
(NR) INDICATES LIVE LOADS ARE NOT REDUCED. OTHERWISE DESIGN LIVE LOADS FOR SLABS, BEAMS, COLUMNS, AND FOUNDATIONS ARE
REDUCED PER CODE.
ROOF LIVE LOADS ARE INCREASED FOR SNOW DRIFT AND PONDING PER ASCE-7. WATER DEPTH ON DEFLECTED STRUCTURE 6" MAXIMUM.
3. SNOW LOAD:
GROUND SNOW LOAD: Pg = 20 PSF FLAT ROOF SNOW LOAD: Pf = 17 PSF MINIMUM SNOW LOAD: Pm = 24 PSF SNOW EXPOSURE FACTOR: Ce = 1.0 SNOW LOAD IMPORTANCE FACTOR: Is = 1.2 THERMAL FACTOR: Ct = 1.0
DRIFT SURCHARGE LOAD AT INTERFACES WITH EXISTING BUILDING:
AT NORTH AND SOUTH INTERFACES: Pd = 39 PSF, W = 9.32' AT EAST INTERFACE: Pd = 51.5 PSF, W = 12.4'
4. WIND LOAD:
DESIGN WIND SPEED (3-SECOND GUST): Vult = 120 MPH; [Vasd = 93 MPH]
RISK CATEGORY: IV
WIND EXPOSURE: C
INTERNAL PRESSURE COEFFICIENT: ENCLOSED BUILDING, GCpi = +/- 0.18
ROOF HEIGHT H= 56 FT.
COMPONENTS AND CLADDING – ULTIMATE STRENGTH DESIGN:
FACTORED LOADS PSF (ult)
EFFECTIVE WIND AREA: 10SF 50SF 100SF
1 ROOF, TYPICAL AREAS +16.5/-65.7 +16.0/-55.5 +16.0/-51.2
2 ROOF WITHIN 33.5 FEET OF EDGES +16.5/-86.5 +16.0/-73.6 +16.0/-68.1
3 ROOF WITHIN 33.5 FEET OF CORNERS +16.5/-118 +16.0/-92.1 +16.0/-80.9
4 WALLS, TYPICAL AREAS +41.2/-44.7 +36.9/-40.4 +35.0/-38.5
5 WALLS WITHIN 33.5 FT OF CORNERS +41.2/-55.2 +36.9/-46.6 +35.0/-42.8
COMPONENTS AND CLADDING – ALLOWABLE STRESS DESIGN:
WORKING LOADS PSF (asd)
EFFECTIVE WIND AREA: 10SF 50SF 100SF
1 ROOF, TYPICAL AREAS +10.5/-39.4 +10.0/-33.3 +10.0/-30.7
2 ROOF WITHIN 33.5 FEET OF EDGES +10.0/-51.9 +10.0/-44.2 +10.0/-22.3
3 ROOF WITHIN 33.5 FEET OF CORNERS +10.0/-70.8 +10.0/-55.3 +10.0/-48.5
4 WALLS, TYPICAL AREAS +24.7/-26.8 +22.1/-24.2 +21.0/-23.1
5 WALLS WITHIN 33.5 FT OF CORNERS +24.7/-33.1 +22.1/-28.0 +21.0/-25.7
EARTHQUAKE DESIGN DATA:
RISK CATEGORY: IV
SEISMIC IMPORTANCE FACTOR: Ie = 1.5 MAPPED SPECTRAL RESPONSE ACCELERATION: Ss = 0.103, S1 = 0.048
SITE CLASS: C
DESIGN SPECTRAL RESPONSE COEFFICIENT: Sds = 0.09, Sd1 = 0.048
SEISMIC DESIGN CATEGORY: A
BASIC SEISMIC FORCE RESISTING SYSTEM: STEEL SYSTEMS NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE
RESPONSE MODIFICATION FACTOR: R = 3
SEISMIC RESPONSE COEFFICIENT: Cs = 0.045
DESIGN BASE SHEAR: 60 KIPS
ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE PER ASCE 7
C. CONCRETE
1. CONCRETE STRENGTHS:
a. TYPICAL CONCRETE UNLESS NOTED OTHERWISE: 4000 PSI
b. INTERIOR SLAB ON METAL DECK: 4000 PSI NORMAL WEIGHT AND LIGHTWEIGHT, REFER TO PLAN
2. MAXIMUM LENGTH OF SLAB POUR BETWEEN CONSTRUCTION JOINTS SHALL NOT EXCEED 120 FEET.
3. JOINTS NOT INDICATED ON STRUCTURAL DRAWINGS ARE NOT PERMITTED UNLESS APPROVED BY THE STRUCTURAL ENGINEER.
4. PLACE NO PERMANENT LOAD, SUCH AS MASONRY WALLS, ON SUPPORTED SLABS UNTIL CONCRETE HAS REACHED SPECIFIED STRENGTH AND ALL
SHORING HAS BEEN REMOVED.
5. PLACE NO OPENINGS, SLEEVES, INSERTS, ETC. IN CONCRETE WORK UNLESS CRITERIA INDICATED ON THE STRUCTURAL DRAWINGS IS MET, OR
SPECIFIC SIZE AND LOCATION IS APPROVED IN WRITING BY THE STRUCTURAL ENGINEER.
6. CONCRETE CONSTRUCTION TOLERANCES ARE AS SHOWN IN THE PROJECT SPECIFICATIONS.
7. SLABS ON METAL DECKS ARE TO BE CAST TO A CONSTANT THICKNESS OVER BEAMS, WITH MINIMUM THICKNESS AS SHOWN ON THE DRAWINGS.
ALLOW FOR MINIMUM EXTRA 1/2” OF CONCRETE TO ACCOUNT FOR METAL DECK DEFLECTION. PURLINS AND GIRDERS ARE UNSHORED DURING SLAB PLACEMENT. AFTER PLACEMENT, FINISH SLABS TO REQUIRED TOLERANCES PER THE PROJECT SPECIFICATIONS.
D. REINFORCING STEEL
1. ALL REINFORCING BARS: 60 KSI YIELD.
2. REINFORCE ALL SLABS AS FOLLOWS, U.N.O:
a. SLABS ON METAL DECK: 6x6-W2.9xW2.9 (42#) WWF.
3. FURNISH WWF IN FLAT SHEETS. LAP SHEETS 2 WIRES (1 FULL WIRE SPACE) PLUS 2” AT ALL EDGES. STAGGER ADJACENT SHEETS TO AVOID 4
CORNER LAPS.
4. PROVIDE TENSION SPLICES UNLESS NOTED OTHERWISE.
5. PLACE WITH MINIMUM CLEAR COVER BETWEEN REINFORCING STEEL AND CONCRETE SURFACES AS SHOWN. IF NOT SHOWN, PROVIDE CLEAR COVER PER ACI. ALL REINFORCING SHALL BE PLACED AS SHOWN AND DETAILED, AND WITHIN ACI TOLERANCE.
GENERAL STRUCTURAL NOTES:
E. STRUCTURAL STEEL
1. ALL WORK SHALL CONFORM TO AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) STANDARDS AND THE PROJECT SPECIFICATIONS.
2. FABRICATOR SHALL MEET AISC CERTIFICATION STANDARD FOR STEEL BUILDING STRUCTURES PER THE PROJECT SPECIFICATIONS.
3. MATERIAL:
a. WIDE FLANGE SHAPES: ASTM A992 (Fy 50 KSI).
b. STEEL PIPES: ASTM A53, GRADE B (Fy 35 KSI).
c. HOLLOW STRUCTURAL SECTIONS (HSS): ASTM A500, GRADE C (HSS ROUND Fy 46 KSI; HSS SQUARE AND RECTANGULAR Fy 50 KSI).
d. OTHER ROLLED SHAPES, PLATES AND BARS: ASTM A36 (Fy 36 KSI).
e. PLATES AND BARS NOTED GRADE 50: ASTM A572 (Fy 50 KSI).
f. HEADED SHEAR STUDS: ASTM A108, COMPLY WITH AWS D1.1, TYPE B.
g. BOLTS: ASTM A325, 3/4" MIN. DIA., U.N.O.
h. ANCHOR RODS: ASTM F1554 (Fy 36 KSI), U.N.O.
4. PROVIDE TENSION CONTROL A325-TC BOLTS OR F1852 ASSEMBLIES, OR F959 SELF INDICATING LOAD INDICATOR WASHERS AND PRETENSION ALL
BOLTS.
5. ALL WELDING MATERIALS, WELDING PROCEDURES AND OPERATORS PERFORMING WELDING TO BE QUALIFIED PER AWS D1.1.
6. FABRICATOR TO DESIGN CONNECTIONS NOT DETAILED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, THE AISC MANUAL, AND THE STRUCTURAL STEEL FRAMING PLANS, NOTES AND DETAILS OF THESE DRAWINGS.
FORCES INDICATED ON THE DRAWINGS ARE FACTORED FOR LRFD DESIGN, U.N.O.
7. CONNECTION CONFIGURATIONS INDICATED ON THE PLANS, NOTES AND DETAILS REPRESENT THE DESIGN INTENT. ITEMS SPECIFICALLY INDICATED, SUCH AS WELDS, STIFFENERS, BRACES, ETC., MUST BE PROVIDED AT MINIMUM AS SHOWN. ADDITIONAL DESIGN AND DETAILING OF CONNECTIONS, INCLUDING CONSIDERATION OF MEMBER THICKNESS, HOLES, CUTS, COPES AND THE EFFECTS OF CONCENTRATED FORCES, SHALL BE PROVIDED BY THE CONTRACTOR.
8. UNLESS NOTED OTHERWISE, ALL EXTERIOR WALL LINTELS, LEDGE ANGLES, MEMBERS ABOVE THE ROOF LINE AND STEEL EXPOSED TO WEATHER
SHALL BE HOT DIPPED GALVANIZED.
F. METAL DECK
1. ALL WORK SHALL CONFORM TO STEEL DECK INSTITUTE (SDI) STANDARDS AND THE PROJECT SPECIFICATIONS.
2. DECK MANUFACTURER SHALL BE A CURRENT MEMBER OF SDI.
3. MATERIAL, G-60 MINIMUM GALVANIZED STEEL:
a. 2" DEEP, 20 GAGE MIN. THICKNESS, COMPOSITE METAL FLOOR DECK.
b. 1.5" DEEP, 20 GAGE MIN. THICKNES, METAL ROOF DECK.
c. POUR STOPS, CLOSURES AND FILLERS, 18 GAGE MIN. THICKNESS.
d. FASTENERS: SUBMIT ICC ESR WITH DIAPHRAGM CAPACITY FOR APPROVAL.
4. MINIMUM ATTACHMENT OF FLOOR DECK: FASTEN TO ALL SUPPORTS WITH NOT LESS THAN 5/8" DIA. FUSION WELDS OR APPROVED FASTENERS SPACED 12" O.C. FASTEN SIDE LAPS OF DECK UNITS WITH #10 SCREWS OR BUTTON PUNCH AT 36" O.C. MAX.
5. PROVIDE SIDE CLOSURES AND FILLERS FOR DECK AND DIAPHRAGM CONTINUITY WITH THE STRUCTURE. ATTACH TO DECK AND STRUCTURE AS
REQUIRED FOR DIAPHRAGM SHEAR BUT NOT FARTHER THAN 12” O.C. MAX.
6. INSTALL DECK AND PROVIDE CLOSURES AND FILLERS TO ALLOW SHEAR STUD INSTALLATION WITH 1” MINIMUM LATERAL CONCRETE COVER TYPICALLY, AND 2” MINIMUM LATERAL COVER AT DECK MID-HEIGHT IN THE LOAD DIRECTION.
7. PROVIDE POUR STOPS AS REQUIRED TO FORM CONCRETE AT EDGES AND OPENINGS.
G. POST-INSTALLED ANCHORS AND ADHESIVE ANCHORING TO CONCRETE
1. POST-INSTALLED ANCHORS AND ADHESIVE ANCHORING SYSTEMS MUST BE TESTED AND APPROVED USING ICC EVALUATION SERVICE ACCEPTANCE CRITERIA, INCLUDING ICC-ES AC193: “MECHANICAL ANCHORS IN CONCRETE ELEMENTS” OR ICC-ES AC308: “POST-INSTALLED ADHESIVE ANCHORS IN CONCRETE ELEMENTS”. CONCRETE SHALL BE CONSIDERED CRACKED. SUBMIT MANUFACTURER’S DATA AND EVALUATION REPORT (ESR) FOR PROPOSED ANCHORS, ADHESIVES, AND ANCHORING SYSTEMS. INDICATE SPECIFIC PROJECT LOCATIONS AND CONDITIONS
WHERE PROPOSED FOR USE.
2. MECHANICAL ANCHORS TO CONCRETE SHALL BE AS SHOWN IN THE STRUCTURAL DETAILS. UNLESS NOTED OTHERWISE, USE ONE OF THE
FOLLOWING:
a. HILTI KWIK BOLT TZ EXPANSION ANCHORS.
b. POWERS POWER-STUD+ SD2 WEDGE EXPANSION ANCHORS.
c. SIMPSON STRONG-BOLT 2 WEDGE ANCHORS.
3. ADHESIVE ANCHORING OF RODS AND REBAR TO CONCRETE SHALL BE AS SHOWN IN THE STRUCTURAL DETAILS. UNLESS NOTED OTHERWISE, PROVIDE STANDARD HAS-E RODS AND USE ONE OF THE FOLLOWING:
a. HILTI HIT-HY 200 HYBRID ADHESIVE ANCHORING SYSTEM.
b. HILTI HIT-RE 500-V3 EPOXY ADHESIVE ANCHORING SYSTEM.
c. POWERS PE1000+ EPOXY ADHESIVE ANCHORING SYSTEM.
d. SIMPSON SET-XP EPOXY ANCHORING ADHESIVE.
e. OTHER PRODUCTS MAY BE REQUIRED FOR TEMPERATURE AND SPECIAL CONDITIONS.
4. ADHESIVE ANCHORING SHALL NOT BE USED IN OVERHEAD OR UPWARD CONDITIONS. USE HYBRID ADHESIVE WITH ESR FOR HORIZONTAL
CONDITIONS.
5. POST-INSTALLED ANCHORS SHALL ONLY BE USED AS SHOWN AND APPROVED; THEY SHALL NOT BE USED WHERE CAST-IN-PLACE ANCHORS ARE
REQUIRED.
6. ZINC COAT ANCHORS, RODS AND HARDWARE TYPICALLY. AT EXTERIOR USE HOT DIP GALVANIZED OR STAINLESS STEEL, UNLESS NOTED
OTHERWISE.
7. EMBEDMENT DEPTH, EDGE DISTANCES, AND SPACING ARE CRUCIAL. LOCATE AS SHOWN ON THE DRAWINGS. WHERE NOT SHOWN, EMBED REBAR 24 DIAMETERS AND EMBED ANCHORS AT LEAST 8 DIAMETERS, WITH EDGE DISTANCES AT LEAST 8 DIAMETERS, AND SPACING AT LEAST 12 DIAMETERS. USE MANUFACTURER’S DATA TO CALCULATE REDUCED CAPACITY FOR ACTUAL CONDITIONS AND CONFIRM AN ULTIMATE SAFETY
FACTOR OF AT LEAST 4.0.
8. HOLES INTO CONCRETE MUST NOT INTERFERE WITH REINFORCING BARS. THE CONTRACTOR SHALL REVIEW THE STRUCTURAL DRAWINGS AND USE FERRO-SCAN OR OTHER MEANS TO LOCATE REINFORCING BARS IN THE AREA. SPACE HOLES TO FIT AROUND REBAR, SET ANCHORS WITH A
TEMPLATE AND FABRICATE FIXTURE TO MATCH.
9. HOLES IN CONCRETE SHALL BE THE PROPER SIZE AND THOROUGHLY CLEANED WITH ALL DUST REMOVED. DRILL HOLES USING A HOLLOW BIT AND FUNCTIONING VACUUM SYSTEM, THEN BRUSH AND BLOW OUT REPEATEDLY WITH CLEAN, OIL FREE AND DRY, HIGH PRESSURE COMPRESSED AIR.
10. INSTALL INTO DRY CONCRETE IN CLEAN, DUST FREE HOLES USING METHOD AND PROCEDURE THAT MEETS MANUFACTURER’S RECOMMENDATIONS INCLUDING TEMPERATURE RANGE, HUMIDITY, INSTALLATION TIME AND CURE TIME. FOLLOW THE MANUFACTURER’S PRINTED
INSTALLATION INSTRUCTIONS.
11. PROVIDE STANDARD SIZE HOLES IN THE FASTENED STEEL ELEMENT (1/16” LARGER THAN THE ROD DIAMETER) TO MATCH TEMPLATE OF INSTALLED
ANCHORS. DO NOT OVERSIZE HOLES.
12. THE CONTRACTOR SHALL ARRANGE FOR A REPRESENTATIVE OF THE MANUFACTURER TO PROVIDE ONSITE INSTALLATION TRAINING FOR THEIR PRODUCTS. ADHESIVE ANCHOR INSTALLERS SHALL ALSO BE CERTIFIED BY A RECOGNIZED PROGRAM, SUCH AS BY ACI AND CRSI. SUBMIT DOCUMENTATION OF TRAINING AND CERTIFICATION OF PERSONNEL PRIOR TO PERFORMING SUCH WORK. PROVIDE COPY TO THE OWNER’S
INSPECTION AGENCY.
13. THE CONTRACTOR SHALL INSPECT AND PROOF TEST ANCHORS AS PART OF THE CONTRACTOR’S QUALITY CONTROL PROGRAM. INSPECT CONTINUOUSLY OR PERIODICALLY ACCORDING TO THE ESR. PROOF TEST 5% OF ALL ANCHORS AND REBAR IN EACH CONDITION, DISTRIBUTED THROUGHOUT THE PROJECT, AND TEST ALL ANCHORS IN EACH STEEL FRAMING CONNECTION. AMOUNT OF TESTING SHALL BE INCREASED IF FAILURES OCCUR. OWNER’S INSPECTION AGENCY WILL OBSERVE INSTALLATION FOR CONFORMANCE WITH MANUFACTURER’S
RECOMMENDATIONS AND WILL WITNESS CONTRACTOR’S PROOF TESTING.
H. FIREPROOFING
1. ALL LOAD BEARING METAL STRUCTURAL FRAMING REQUIRES SPRAY-ON FIREPROOFING OR FIRE RATED ENCLOSURE. REFER TO THE PROJECT
SPECIFICATION AND ARCHITECTURAL DRAWINGS FOR SPECIFIC REQUIREMENTS.
I. COORDINATION AND CONSTRUCTION
1. THE CONTRACTOR SHALL COMPLETE ALL WORK REQUIRED AND NECESSARY FOR THE PROJECT IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, DRAWINGS, AND REFERENCED STANDARDS. THE SPECIFICATIONS AND DRAWINGS COMPLEMENT EACH OTHER, THE
CONTRACTOR SHALL THOROUGHLY REVIEW BOTH BEFORE PROCEEDING WITH ANY WORK.
2. UNLESS OTHERWISE NOTED, DETAILS, SECTIONS AND NOTES ON THE STRUCTURAL DRAWINGS ARE INTENDED TO APPLY TO SIMILAR SITUATIONS
ELSEWHERE.
3. STRUCTURAL FRAMING PLANS ARE TYPICALLY DRAWN AS REFLECTED PLANS SHOWING BEAMS, WALLS, AND COLUMNS ON THE UNDERSIDE OF
THE LEVEL SHOWN.
4. ALL FRAMING MEMBERS PROVIDED FOR MECHANICAL TRADES, EQUIPMENT SUPPORT, ELEVATOR SUPPORT BEAMS, LINTELS, ROOF OPENINGS, ETC., ARE FOR BIDDING PURPOSES ONLY. SUBMIT MANUFACTURER'S DATA FOR THE ACTUAL PROPOSED EQUIPMENT TO STRUCTURAL ENGINEER
FOR VERIFICATION OR REDESIGN OF SUPPORTS PRIOR TO PREPARING SHOP DRAWINGS.
5. SEE ARCHITECTURAL AND MECHANICAL DRAWINGS FOR ADDITIONAL DETAILS, DIMENSIONS, EMBEDDED ITEMS, SLEEVES, FLOOR PITCHES, DEPRESSIONS AND FILLS. OPENING SIZES AND LOCATIONS FOR PIPES, DUCTS, ETC., WHEN SHOWN, ARE FOR GENERAL INFORMATION ONLY AND SHALL BE VERIFIED WITH MECHANICAL, ELECTRICAL, PLUMBING AND OTHER COORDINATION DRAWINGS AS APPLICABLE.
6. SHOP DRAWINGS AND INSTALLATION DRAWINGS SHALL BE PREPARED AND SUBMITTED FOR REVIEW. SUBMITTALS PREPARED BY SUPPLIERS AND SUB CONTRACTORS SHALL BE REVIEWED BY THE TRADE CONTRACTOR AND GENERAL CONTRACTOR OR CONSTRUCTION MANAGER PRIOR TO
SUBMITTING TO ARCHITECT/ENGINEER.
a. FIELD VERIFY ALL EXISTING DIMENSIONS, ELEVATIONS AND CONDITIONS WHICH AFFECT FABRICATION AND SHOW ON SHOP DRAWINGS.
b. VERIFY AND SHOW EXACT SIZE AND LOCATION OF ALL FLOOR, WALL AND ROOF OPENINGS, SLAB EDGES, EMBEDDED ANCHORS AND OTHER
ITEMS.
c. SHOW AND LOCATE ALL MECHANICAL SLEEVES, EMBEDS, DRAINS, ETC. ON COORDINATION DRAWINGS. ITEMS NOT SUBMITTED FOR REVIEW
TO THE STRUCTURAL ENGINEER ARE NOT PERMITTED IN OR THROUGH THE STRUCTURE.
d. SUBMIT COMPLETE SHOP DRAWINGS WITH MANUFACTURERS’ DATA, ETC. SHOW ALL CONNECTIONS AND DETAILS NECESSARY TO FULLY
DESCRIBE AND PROPERLY INSTALL THE WORK.
e. STRUCTURAL ENGINEER’S REVIEW SHALL BE FOR GENERAL ARRANGEMENT AND CONFORMANCE WITH THE STRUCTURAL INTENT ONLY.
7. THE SPECIFICATIONS AND STRUCTURAL DRAWINGS TYPICALLY REFER TO THE FINISHED STRUCTURE. UNLESS NOTED OTHERWISE, THEY DO NOT
PRESCRIBE THE METHOD OF CONSTRUCTION.
8. BRACE ENTIRE STRUCTURE AND PORTIONS THEREOF AS REQUIRED TO MAINTAIN STABILITY UNTIL COMPLETE AND FUNCTIONING AS THE
DESIGNED UNIT.
9. IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, CONTRACTOR SHALL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITIONS OF THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF THE WORK. THIS REQUIREMENT
SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO WORKING HOURS.
10. THE ARCHITECT’S AND ENGINEER’S OBSERVATION AND REVIEW OF CONTRACTORS’ PERFORMANCE DOES NOT INCLUDE REVIEW OF ADEQUACY OF
CONTRACTOR'S SAFETY MEASURES IN, ON, OR NEAR THE CONSTRUCTION SITE.
J. MECHANICAL AND OTHER ITEMS EMBEDDED IN OR SUPPORTED FROM STRUCTURE
1. PLACEMENT OF CONDUITS IN CONCRETE SHALL ADHERE TO THE FOLLOWING.
a. OUTSIDE DIAMETER OF CONDUITS SHALL BE 1" OR LESS WHERE EMBEDDED IN SLABS AND JOISTS, AND 1-1/2" OR LESS WHERE EMBEDDED IN
BEAMS, WALLS, OR COLUMNS.
b. BUNCHING OF CONDUITS IS NOT PERMITTED. CONDUITS SHALL BE SPACED 3 DIAMETERS OR GREATER ON CENTER, AND 6" MIN. AWAY FROM
COMPOSITE SHEAR STUD CONNECTORS.
c. MINIMUM CONCRETE COVER ON CONDUITS SHALL BE 1-1/2".
d. ALUMINUM CONDUITS, PIPES, OR SLEEVES ARE NOT PERMITTED.
2. ALL TRADE CONTRACTORS (MECHANICAL, STAIR, WALL, ENVELOPE, SPECIALTY, ETC.) ARE TO DESIGN THEIR SYSTEMS, INCLUDING ATTACHMENTS
TO THE BUILDING’S STRUCTURE WITHIN THE FOLLOWING LIMITATIONS.
a. LOADS ARE TO BE DISTRIBUTED TO THE STRUCTURE IN A MANNER THAT DOES NOT EXCEED THE LOAD ALLOWANCES NOTED UNDER DESIGN
LOADS AND SHALL NOT OVERLOAD OR DAMAGE THE STRUCTURE.
b. ANCHORS ARE TO HAVE AN ULTIMATE SAFETY FACTOR OF AT LEAST 4.0.
c. LOADS SUPPORTED BY WIDE FLANGE BEAMS ARE TO BE APPLIED IN A MANNER WHICH DOES NOT CAUSE TORSION ABOUT THE LONGITUDINAL
AXIS OF THE BEAM.
3. THE SIZE AND LOCATION OF EQUIPMENT, ROOF CURBS, ELEVATORS, AND OTHER ITEMS MUST BE COORDINATED WITH SUPPORTING STRUCTURE.
PROVIDE ADDITIONAL SUPPORTS AND ANGLE FRAMES WHERE NECESSARY. TRADE CONTRACTOR(S), GENERAL CONTRACTOR AND CONSTRUCTION MANAGER MUST ENSURE ACCURATE DIMENSIONAL INFORMATION IS PROVIDED TO STEEL FABRICATOR PRIOR TO FABRICATION.
4. UNLESS OTHERWISE NOTED, DO NOT HANG OR OTHERWISE SUPPORT ANY ITEMS FROM METAL DECKS. USE CONCRETE ANCHORS TO SUPPORT
FROM CONCRETE SLABS CAST ON METAL DECK.
K. QUALITY CONTROL AND ASSURANCE
1. THE CONTRACTOR SHALL PERFORM QUALITY CONTROL, TESTING AND INSPECTION OF ALL WORK AS REQUIRED BY THE CONTRACT DOCUMENTS, INCLUDING REFERENCED CODES, SPECIFICATIONS AND STANDARDS.
2. THE CONTRACTOR WILL EMPLOY A TESTING AND INSPECTION AGENCY TO PERFORM SERVICES INDICATED IN THE PROJECT SPECIFICATIONS
SPECIAL INSPECTIONS.
3. THE CONTRACTOR WILL ALSO EMPLOY QUALIFIED SPECIAL INSPECTORS TO PERFORM INSPECTIONS IN ACCORDANCE WITH CHAPTER 17 OF THE BUILDING CODE AND AS INDICATED IN THE PROJECT SPECIFICATIONS. THE CONTRACTOR IS RESPONSIBLE FOR SCHEDULING ALL INSPECTIONS
AND TESTS. ITEMS REQUIRING SPECIAL INSPECTION ON THIS PROJECT INCLUDE:
a. CONCRETE: ALL CONCRETE WORK.
b. REINFORCING STEEL: ALL REINFORCING STEEL.
c. STRUCTURAL STEEL: ALL WELDING AND HIGH STRENGTH BOLTING.
4. THE STRUCTURAL ENGINEER MAY GENERALLY OBSERVE THE PROGRESS OF THE WORK, BUT HIS OBSERVATION SHALL NOT BE CONSTRUED AS
INSPECTION.
STRUCTURAL STEEL FRAMING NOTES:
1. SEE S001 FOR GENERAL NOTES AND S002 FOR TYPICAL DETAILS.
2. UNDIMENSIONED MEMBERS TYPICALLY ARE EQUALLY SPACED BETWEEN DIMENSIONED MEMBERS.
3. COORDINATE SIZES AND LOCATIONS OF ALL FLOOR OPENINGS, ROOF OPENINGS, AND SLEEVES WITH ARCHITECTURAL AND MECHANICAL
REQUIREMENTS. SEE S002 FOR TYPICAL FLOOR AND ROOF OPENING DETAILS.
4. FABRICATOR TO COMPLETE THE DESIGN OF ALL CONNECTIONS. SEE GENERAL NOTES AND PROJECT SPECIFICATIONS.
5. ALL SHEAR CONNECTIONS TO COLUMNS ARE TO BE AISC DOUBLE ANGLE CONNECTIONS U.N.O. WITH THE MINIMUM ROWS OF BOLTS = BEAM
DEPTH IN INCHES DIVIDED BY 4.5 SPACED 3” MINIMUM O.C.
6. UNLESS INDICATED OTHERWISE, SHEAR CONNECTIONS AT PURLINS TO GIRDERS MAY BE AISC SINGLE-PLATE OR SINGLE-ANGLE CONNECTIONS WITH A MAXIMUM ECCENTRICITY OF 3” AND MINIMUM ROWS OF BOLTS = BEAM DEPTH IN INCHES DIVIDED BY 4, SPACED 3” MINIMUM O.C. SINGLE SHEAR CONNECTIONS SHALL HAVE HORIZONTAL SHORT SLOTTED HOLES TO THE SUPPORTED BEAM, STANDARD HOLES TO THE SUPPORTING
GIRDER OR MAY BE SHOP WELDED TO EITHER THE BEAM OR GIRDER.
7. FORCES INDICATED ON THE DRAWINGS ARE FACTORED FOR LRFD DESIGN, U.N.O. DESIGN BEAM CONNECTION FOR FORCES INDICATED ON THE PLANS. BRACING ELEVATIONS AND DETAILS MAY ALSO SHOW REQUIRED FORCES WHICH ARE ADDITIVE. FORCES ARE INDICATED AS:
A = AXIAL END REACTION, KIPS
V = VERTICAL END REACTION KIPS
M = END MOMENT, FOOT KIPS
FMC = FLEXIBLE MOMENT CONNECTION TYPE, SEE DETAILS
8. COMPOSITE SHEAR CONNECTORS ARE TO BE ¾” DIA. HEADED STUDS x 4” LONG U.N.O. PROVIDE ADDITIONAL STUDS SO THAT THE MAXIMUM INSTALLED SPACING DOES NOT EXCEED 24” REGARDLESS OF QUANTITY INDICATED. IF NONE ARE INDICATED, PROVIDE AT 24” O.C. ON ALL
BEAMS OVER 22 FEET LONG WITH CONCRETE SLABS.
9. W18X35 (16) – A SINGLE NUMBER GIVEN WITH A BEAM SIZE INDICATES TOTAL NUMBER OF STUDS EVENLY SPACED ALONG THE BEAM OR GIRDER.
WHERE BEAMS FRAME PERPENDICULAR, SPACE QUANTITY OF STUDS INDICATED BETWEEN INTERSECTING PURLINS/COLUMNS EVENLY OVER
THAT LENGTH.
10. INSTALL COMPOSITE SHEAR STUD CONNECTORS WITH 1” MINIMUM LATERAL CONCRETE COVER. INSTALL STUDS WITH 2” MINIMUM LATERAL COVER AT DECK MID-HEIGHT IN THE LOAD DIRECTION (TOWARD MID-SPAN OF THE BEAM) WHEN PLACED IN METAL DECK RIBS ORIENTED
PERPENDICULAR TO THE BEAM.
11. FABRICATE PURLINS AND GIRDERS WITH NATURAL CAMBER UP. NO CAMBER REQUIRED FOR ROOF BEAMS. CAMBER MEMBERS SUPPORTING
FLOOR SLABS AS NOTED "C = ON PLANS":
12. SCHEDULE ERECTION SEQUENCE AND/OR PROVIDE ADDITIONAL TEMPORARY VERTICAL BRACING SO THAT ALL PORTIONS OF THE STRUCTURAL FRAME ARE BRACED FOR LATERAL LOADS. HORIZONTAL DECK DIAPHRAGMS ARE TO BE COMPLETED BETWEEN STABILIZING BRACES PRIOR TO
CONCRETE PLACEMENT.
13. ROOF AND FLOOR DECK IS TO BE CONTINUOUSLY SUPPORTED AT EACH END OF DECK SPANS. PROVIDE ADDITIONAL L3X3X1/4 DECK SUPPORT
ANGLES WHERE REQUIRED.
14. ALL FRAMING CONNECTIONS, GROUTING OF COLUMN BASE PLATES, AND INSPECTIONS ARE TO BE COMPLETED PRIOR TO CASTING SLAB.
15. PURLINS AND GIRDERS ARE UNSHORED DURING CONCRETE SLAB PLACEMENT.
16. CONTRACTOR IS RESPONSIBLE TO PROVIDE A FINISHED SLAB EDGE WHICH IS STRAIGHT AND TRUE AND ACCURATELY LOCATED RELATIVE TO FINISH WALL LINES. GAGES SHOWN FOR CLOSURE ANGLES ARE THE MINIMUM REQUIRED. HEAVIER GAGE, STRAPS AND/OR A RETURN LIP AT TOP OF ANGLE MAY BE USED AT CONTRACTORS OPTION. FASTEN CLOSURE ANGLES TO DECK/BEAM AT 12” MAX. O.C. OR AS REQUIRED TO
PREVENT TORSIONAL DEFLECTION OF ANGLE.
17. ALL ANGLES, GIRTS AND OTHER MEMBERS SUPPORTING THE BUILDING FACADE, ARCHITECTURAL WALLS OF MASONRY OR GLASS, AND ITEMS NOTED “MASONRY SUPPORT” OR “CFMF SUPPORT” ARE CONSIDERED “ADJUSTABLE ITEMS” AND ARE TO BE LOCATED WITHIN 3/8” OF THEIR DESIGN VERTICAL AND HORIZONTAL LOCATION RELATIVE TO THE ESTABLISHED FINISH WALL LINE, FINISH FLOOR LINE, AND MASONRY
COURSING.
A.B. ANCHOR BOLT
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADJ ADJACENT
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT ALTERNATE
ALUM ALUMINUM
ARCH ARCHITECT
B.L. BUILDING LINE
BLDG BUILDING
BM(S) BEAM(S)
BTWN BETWEEN
C.L. CENTER LINE
C.J. CONSTRUCTION OR CONTROL JOINT
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
D.B. DECK BEARING
DET DETAIL
DWG(S) DRAWING(S)
E.E. EACH END
E.F. EACH FACE
E.S. EACH SIDE
E.W. EACH WAY
E.J. EXPANSION JOINT
ELEV ELEVATION OR ELEVATOR
EMBED EMBEDMENT
ENGR ENGINEER
EQ EQUAL
EXIST EXISTING
F.F. FAR FACE
FNDN FOUNDATION
FL FLOOR
FT FOOT OR FEET
FTG FOOTING
GALV GALVANIZED
H.P. HIGH POINT
HORIZ HORIZONTAL
I.F. INSIDE FACE
IN INCHES
JT JOINT
K KIP (1000 POUNDS)
L ANGLE
L.P. LOW POINT
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
ABBREVIATIONS:
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFGR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
N.F. NEAR FACE
NO NUMBER
O.C. ON CENTER
O.F. OUTSIDE FACE
OPNG OPENING
P.C. PRECAST
P.L. PROPERTY LINE
P.T. POST TENSIONING
PED PEDESTAL
PERP PERPENDICULAR
PL PLATE
PLF POUNDS PER LINEAR FOOT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
R RADIUS
R.D. ROOF DRAIN
R.J. RUSTICATION JOINT
REINF REINFORCED OR REINFORCEMENT
SECT SECTION
SHT SHEET
SIM SIMILAR
S.O.G. SLAB ON GRADE
SPECS SPECIFICATIONS
SQ SQUARE
STL STEEL
T&B TOP AND BOTTOM
T/CONC TOP OF CONCRETE
T/FTG TOP OF FOOTING
T/STL TOP OF STEEL
T/SLAB TOP OF SLAB
TEMP TEMPERATURE
t THICKNESS
TYP TYPICAL
U.N.O. UNLESS NOTED OTHERWISE
VERT VERTICAL
W.P. WORK POINT
# NUMBER
f'c SPECIFIED COMPRESSIVE STRENGTH
OF CONCRETE AT 28 DAYS
(C) COMPRESSION
(T) TENSION
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.25.2023
Bid Documents 100% TBD
Design Development 65% (Re-submittal) 11.15.2021
/1
4/
:1 8:
P
M
Construct Private In-Patient Rooms & Primary Clinics
TBD
GENERAL STRUCTURAL NOTES
S001
SETFJE
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS
20014.00
Revisions Date
C.P. TOP AND
BOTTOM FLANGE
NOTE: BEAMS FRAMING INTO COLUMN
WEB NOT SHOWN FOR CLARITY.
BEAM PER PLAN.BEAM PER PLAN.
T/STEEL
SEE PLAN
WF OR HSS COLUMN PER PLAN.
5/16" DOUBLE ANGLE
CONNECTION WITH MAX. ROWS
OF 3/4" DIA. BOLTS, TYPICAL.
TYPICAL MOMENT CONNECTION
FROM BEAM TO WF COLUMN FLANGE
COLUMN CONTINUES ABOVE.
1/4
5/16
T/STEEL
SEE PLAN
WF COLUMN.
WIDE FLANGE COLUMN
SUPPORTED ON BEAM BASE
BASE PLATE WITH
(4) 3/4" DIA BOLTS.
WF BEAM.
WHERE WF COLUMN IS ROTATED 90
DEGREES SUCH THAT COLUMN WEB IS
PERPENDICULAR TO BEAM WEB, PROVIDE
WT EACH SIDE OF BEAM WEB WELDED TO
BEAM FLANGE AND WEB. WT TO BE CUT
FROM MATCHING COLUMN SIZE AND
FITTED SUCH THAT WT AND COLUMN ARE
ALIGNED AND COLUMN BASE PLATE
BEARS ON WT FLANGES AND WEB.
STIFFENER PLATE EACH SIDE
ALIGNED WITH COLUMN FLANGE
AND SIZED TO MATCH.
FINISH COLUMN END AND BASE
PLATE PER AISC REQUIREMENTS.
FIT BASE PLATE TO BEAR.
1/ 2"
M A
X A
B O
V E
T O
E O
F F
IL
LE
T
3/4"
TYP
WWF PER GENERAL NOTES. SUPPORT
WWF CONTINUOUSLY PERPENDICULAR
TO DECK SPAN AT BEAMS AND AT 5'-0"
O.C. MAX. LAP 1 WIRE SPACE + 2".
3/4" DIA x 4" LONG HEADED STUDS
AT BEAMS AND GIRDERS.
SEE PLAN FOR QUANTITY.
COMPOSITE METAL FLOOR DECK.
CENTER DECK FLUTE ON BEAMS OR PROVIDE
CLOSURE PLATES EACH SIDE OF BEAM.
CONTINUOUS SUPPORT
BAR OR BOLSTER AT EACH
BEAM AND MAX 5'-0"
TYPICAL SUPPORTED SLAB
ON METAL DECK
SECTION A
O.C.
A
4"
1/
4" S
LA
B
NOTES:
1. LOCATION OF CONSTRUCTION JOINTS AT CONTRACTOR'S
OPTION, SUBJECT TO ARCHITECT'S AND/OR ENGINEER'S
APPROVAL. SUBMIT LOCATIONS OF ALL CONSTRUCTION JOINTS
TO ENGINEER FOR REVIEW AND ACCEPTANCE BEFORE FORMING.
2. SIZE AND LENGTH OF SLAB POURS NOT TO EXCEED CRITERIA IN
"GENERAL STRUCTURAL NOTES".
FIRST POUR SECOND POUR
3/4" DEEP x 1 1/4" HIGH
CONTINUOUS KEYED
CONSTRUCTION JOINT.
DECK AND WWF CONTINUOUS
THROUGH JOINT.
SLAB CONSTRUCTION JOINT
(PERPENDICULAR)
FLOOR BEAM ON
COLUMN LINE.
2'-0" MAXIMUM
1'-0" MINIMUM
NOTES:
1. LOCATION OF CONSTRUCTION JOINTS AT CONTRACTOR'S OPTION,
SUBJECT TO ARCHITECT'S AND/OR ENGINEER'S APPROVAL. SUBMIT
LOCATIONS OF ALL CONSTRUCTION JOINTS TO ENGINEER FOR REVIEW
AND ACCEPTANCE BEFORE FORMING.
2. SIZE AND LENGTH OF SLAB POURS NOT TO EXCEED CRITERIA IN
"GENERAL STRUCTURAL NOTES".
FIRST POUR SECOND POUR
3/4" DEEP x 1 1/4" HIGH
CONTINUOUS KEYED
CONSTRUCTION JOINT.
DECK AND WWF CONTINUOUS
THROUGH JOINT.
FLOOR BEAM ON
COLUMN LINE.
SLAB CONSTRUCTION JOINT
(PARALLEL)
#4 x 4'-0" AT 24" O.C.
2'-0" MAXIMUM
1'-0" MINIMUM
2'-0" 2'-0"
3/16
TYPICAL E.E.
L3x3x1/4 FOR DECK SUPPORT.
TYPICAL WHERE BEAM DOES
NOT FRAME INTO COLUMN.
#4 x 4'-0" UNDER WWF.
TYPICAL AT ALL COLUMNS.
SLAB AT COLUMN
D E
C K
S P
A N
NOTES:
1. BOX OUT OPENING. DO NOT CUT DECK UNTIL 7 DAYS AFTER SLAB IS CAST. GENERAL
CONTRACTOR IS RESPONSIBLE FOR COORDINATING PLACEMENT OF REINFORCEMENT
AND CUTTING OF DECK BY OTHER TRADES.
2. ROUGH OPENING SIZE EQUALS DUCT SIZE PLUS 2". REFER TO ARCHITECTURAL AND
MECHANICAL DRAWINGS FOR SIZE AND LOCATIONS OF OPENINGS.
3. "B" = OPENING LENGTH PERPENDICULAR TO SLAB SPAN OR DIAMETER FOR SLEEVES.
MAXIMUM "B" IS 3'-0". NO LENGTH RESTRICTIONS PARALLEL TO DECK SPAN.
4. MINIMUM CLEAR SPACING BETWEEN OPENINGS PERPENDICULAR TO DECK SPAN IS 2 x "B".
5. REINFORCEMENT:
B = 25" TO 36", USE 3 #5 EACH SIDE.
B = 13" TO 24", USE 2 #5 EACH SIDE.
B = 6" TO 12", USE 1 #5 EACH SIDE.
BAR LENGTH PARALLEL TO DECK SPAN EQUALS DECK SPAN "L" + 4".
BAR LENGTH PERPENDICULAR TO DECK SPAN EQUALS OPENING + 4'-0"
PLACE PARALLEL BAR IN BOTTOM OF FLUTE WITH 3/4" CHAIRS.
6. A CLUSTER OF OPENINGS THAT ARE SPACED AT NO LESS THAN 1'-0" CLEAR SHALL BE
TREATED AS ONE LARGE OPENING FOR DETAILING OF REINFORCEMENT, EXCEPT ADD 1 #5
BETWEEN INDIVIDUAL OPENINGS AT LENGTHS NOTED ABOVE.
ISOLATED SLAB OPENING
REINFORCE AND SPACE AS
OPENING "B" WHERE
MULTIPLE SLEEVES OCCUR.
#4 x 2'-0" DIAGONAL
AT EACH CORNER.
SCHEDULED
REINFORCEMENT
TYPICAL 4 SIDES.
B
L
D E
C K
S P
A N
C
LR
3/ 4"
ABOVE DECK
3/4" CLR
T Y
P
4"
C /C
B E
A M
S
D E
C K
S P
A N
BEAM
DEPTH *
(INCHES)
MINIMUM ROWS OF BOLTS BY CONNECTIONS
DOUBLE ANGLE
BOLT/WELD
DOUBLE ANGLE
BOLT/BOLT
SINGLE ANGLE
OR PLATE
8, 10 2 2 2
12 2 2 3
14 3 3 3
16 3 3 4
18 4 4 4
21 4 4 5
24 5 5 6
27 6 6 6
30 6 6 7
33 7 7 8
36 8 8 9
40 8 8 10
44 9 9 11
* EFFECTIVE BEAM DEPTH WHERE RAISED. SEE DETAIL AT RIGHT.
NOTE: FABRICATOR TO PROVIDE CONNECTION TYPES ABOVE AND DESIGN PER AISC MANUAL.
USE FORCES INDICATED ON PLAN OR SHEAR FROM UNIFORM LOAD TABLE AT BEAM SPANS
WHERE INDICATED. ROWS OF BOLTS NOT LESS THAN TABLE.
V
SHEAR CONNECTIONS BEAM TO BEAM
MAY BE DOUBLE OR SINGLE ANGLES; OR
SINGLE PLATE WITH HORIZONTAL SHORT
SLOTS WITH ECCENTRICITY BETWEEN
BOLTS AND WELDS NOT TO EXCEED 3".
SHEAR CONNECTIONS TO COLUMNS TO BE
DOUBLE ANGLES, PROVIDE ERECTION
SEATS OR STAGGER ANGLES AS REQUIRED.
AT SKEWED CONNECTIONS USE
3/8" BENT PLATE WELDED TO
BEAM, BOLT OUTSTANDING LEG.
BEAM SHEAR CONNECTIONS (NO AXIAL)
3" T
Y P
SLAB AND STRUCTURE
PER PLAN.
SLAB AND STRUCTURE
PER PLAN.
COORD WITH ARCH
AND/OR MEP DWGS.
ROUGH OPENING.
COORD WITH ARCH
AND/OR MEP DWGS.
JA
M
B M
E M
B E
R
R T
A B
LE
JA
M
B M
E M
B
R
R T
A B
LE
HORIZ MEMBER PER TABLE
HORIZ MEMBER PER TABLE
ELEVATION VIEW
CONNECTION OF HORIZ
AND JAMB MEMBERS
FRAMING AT EXTERIOR WALL WINDOWS AND LOUVERS
1/4
(1/4)
HORIZ MEMBER
JAMB MEMBER
CONNECTION TO SLAB /
DIAPHRAGM ABOVE WITH
GRAVITY SLIP CONNECTION
TO ALLOW FOR DEFLECTION
OF PRIMARY STRUCTURE.
BASE PLATE CONNECTION WITH
ADHESIVE ANCHORS TO SLAB.
ROUGH OPENING FOR DOUBLE OPENINGS
COORD WITH ARCH AND/OR MEP DWG'S
DIMENSION 'X' IN TABLE
(OCCURS AT INTERMEDIATE SUPPORT LOCATIONS OF
LOUVERS WITHIN LOUVER OPENINGS)
ROUGH OPENING FOR SINGLE OPNG
COORD WITH ARCH AND/OR MEP DWGS
DIMENSION "X" IN TABLE
FULL PEN
ALIGN BOTTOM OF
STIFFENER PLATE WITH
BOTTOM OF BEAM FLANGE.
SHEAR PLATE, 3/8" MIN
THICKNESS, PROVIDE MAX
ROWS OF 3/4" DIA BOLTS.
ALIGN CENTER OF
STIFFENER PL WITH
CENTER OF BEAM FLANGE.
PER DELEGATED
DESIGN
STIFFENERS TOP
AND BOT AS REQ'D.
BEAM WITH OR WITHOUT
MOMENT CONNECTION
MAY OCCUR THIS SIDE.
W
LD
k + 1 1/2"
NO WELD
k + 1 1/2"
NO WELD
3/4" MIN
PER DELEGATED
DESIGN
TOP PLATE MIN THICKNESS =
BEAM FLANGE THICKNESS + 1/4"
BOTTOM PLATE MIN THICKNESS =
BEAM FLANGE THICKNESS + 3/8"
TYPICAL MOMENT CONNECTION
BEAM TO COLUMN WEB
3/16 2 - 24
2 - 12
TYPICAL SLAB DETAIL AT
MECHANICAL SHAFT OPENING
5/16" BENT PLATE WITH
1/2" DIA x 6" LONG HEADED
STUDS AT 18" O.C.
#4 CONT.
WF BEAM.
DECK DIRECTION
VARIES, SEE PLAN.
T/SLAB
SEE PLAN
#4 x 4'-0" + 180° HOOK AT 18"
O.C. LOCATE AT EACH STUD.
INTERIOR FINISH
BY ARCH.
SEE PLAN
6" TYPICAL
3/ 4"
C
LR
2"
1/4 2 - 12
2 - 24
DECK DIRECTION VARIES.
5/16" CONTINUOUS BENT PLATE
WITH 1/2" DIA x 6" LONG
HEADED STUDS AT 18" O.C.
#4 CONTINUOUS.
METAL PANEL PER
ARCHITECTURAL DRAWINGS.
6" CFMF PER
ARCHITECTURAL DRAWINGS.
CFMF LATERAL CONNECTION TO
UNDERSIDE OF SLAB. ALLOW
FOR VERTICAL DEFLECTION.
6" CFMF PER
ARCHITECTURAL DRAWINGS.
#4 x 4'-0" + 180° HOOK
AT EACH STUD.
T/SLAB
SEE PLAN
SEE ARCH
2" MIN.
OVERLAP
SEE PLAN 1/2" ±1/2"
TOLERANCE
3/ 4"
C
LR
2"
TYPICAL SLAB DETAIL AT
EXTERIOR WALL
WALL OPENING REINFORCEMENT
ADD EQUIVALENT OF 1/2 INTERRUPTED
VERTICAL BARS EACH SIDE AND EACH
FACE OF OPENING AT 4" OC (MINIMUM
(1) #5 EACH SIDE, EACH FACE). PLACE 2"
CLEAR OF OPENING.
ADD (2) #6 x W + 6'-0" MINIMUM ABOVE AND BELOW
OPENING, 2" CLEAR.
STOP NORMAL WALL REINFORCING 2" CLEAR
ALL SIDES OF OPENING.
WHERE D IS LESS THAN 0.6W, ADD #4 AT
D/3 O.C. ABOVE OPENING AND (2) #6 x W + 6'-0" AT
TOP OF WALL.
(1) #5 x 4'-0" DIAGONAL EACH FACE AT
CORNERS, PLACED 2" CLEAR OF CORNER.
NOTES:
1. REINFORCE OPENINGS LESS THAN 8'-0" WIDE PER THIS DETAIL UNLESS NOTED OTHERWISE.
2. SLEEVED OPENINGS 14" AND SMALLER REQUIRE NO ADDITIONAL REINFORCEMENT. PLACE
NORMAL REINFORCEMENT (HORIZ AND VERTICAL) EACH SIDE OF SLEEVE, 2" CLEAR.
3. FOR SINGLE LAYER WALLS USE SINGLE BARS AS SHOWN.
TOP OF WALL PLACEMENT.
WHERE WALL EXTENDS
ABOVE, EXTEND VERT. BARS
TO LAP WITH BARS ABOVE.
W
D
NOTE: DETAIL APPLIES AT BOTH ELEVATED AND
SLABS ON GRADE.
TYPICAL BARS AT
SLAB CORNER
OPENING,
DEPRESSION,
OR RE-ENTRANT
SLAB CORNER.
2 #5 x 4'-0". TIE TO
UNDERSIDE OF SLAB TOP
BARS. WHERE THERE
ARE NO TOP BARS
SUPPORT 1 1/2" CLEAR
OF TOP OF SLAB.
T/MECH SLAB
SEE CIVIL
6x6-W2.9xW.9 WWF
TYPICAL EQUIPMENT
PAD ON GRADE
3/4" CHAMFER, TYP.
6"
2 #5 CONT, TYP.
8"
M
IN4"
1' -6
FINISH GRADE,
SEE CIVIL.
OUTSIDE FACE OF
MECH UNIT, TYP.
MIN
4"
6" CRUSHED STONE.
SLAB ON GRADE
PER PLAN.
T/SLAB
SEE PLAN
#3 AT 12"
APPLY BONDING COMPOUND PRIOR TO
PLACING EQUIPMENT PAD (SECOND POUR).
6x6-W2.9xW.9 WWF
MECHANICAL AND ELECTRICAL
EQUIPMENT PADS
U .N
.O
4"
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.25.2023
Bid Documents 100% TBD
Design Development 65% (Re-submittal) 11.15.2021
/1
4/
:1 8:
P
M
Construct Private In-Patient Rooms & Primary Clinics
TBD
TYPICAL DETAILS
S002
SETFJE
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS
20014.00
8'-1" TO 16'-0" HSS6X3X5/16 HSS6X3X5/16 N/A
LESS THAN 8'-0" HSS6X3X5/16 HSS6X3X1/4 N/A
DIMENSION "X" JAMB MEMBER SIZE HORIZ MEMBER SIZE NOTES
MEMBER SIZE TABLE
3 SIDES
STIFFENER TO
ANGLE, TYP.
7"
C BEAMLC BEAML
UNISTRUT AND BEAM CLAMP BY LIFT
MANUFACTURER.
EXISTING WF BEAM.
EXISTING FIREPROOFING.
REMOVE AS REQUIRED AND
RESTORE AFTER
INSTALLATION OF UNISTRUT,
REFER TO SPECIFICATION.
HSS SUPPORT BEAMS
BY CONTRACTOR.
HSS SUPPORT BEAM BY
CONTRACTOR.
ANGLE WITH (2) STIFFENERS, TYP BY
CONTRACTOR.
UNISTRUT RAIL AND HANGER BY
CONTRACTOR.
UNISTRUT AND BEAM CLAMP BY LIFT
MANUFACTURER.
EXISTING WF BEAM.
EXISTING FIREPROOFING.
REMOVE AS REQUIRED AND
RESTORE AFTER
INSTALLATION OF UNISTRUT,
REFER TO SPECIFICATION.
ANGLE TOP AND BOTTOM BY
LIFT MANUFACTURER.
UNISTRUT COLUMN INSERTS
AND TRACK BY LIFT
MANUFACTURER.
C BEAML
EXISTING WF BEAM.
UNISTRUT AND BEAM
CLAMP BY LIFT
MANUFACTURER.
UNISTRUT PER HOIST
MANUFACTURERS DRAWINGS.
HANGER DESIGN BY LIFT
MANUFACTURER. CENTER
CONNECTION UNDER EXISTING BEAM.
EXISTING FIREPROOFING.
REMOVE AS REQUIRED AND
RESTORE AFTER INSTALLATION
OF UNISTRUT, REFER TO
SPECIFICATIONS.
SCHEMATIC SUPPORT AT BEAMS
WITH SIMILAR DEPTH
SCHEMATIC SUPPORT AT BEAMS
WITH DISSIMILAR DEPTH
SCHEMATIC CONTRACTOR DESIGNED
SUPPLEMENTAL SUPPORT STEEL AND
UNI-STRUT RAIL CONNECTION
SCHEMATIC DIRECTION
CONNECTION TO BEAM
SCHEMATIC CONTRACTOR DESIGNED
HSS TO HSS CONNECTION
DESIGN OF PATIENT LIFT SUPPORTS ARE A DELEGATED DESIGN ITEM. DESIGN SUPPORTS IN ACCORDANCE WITH THE IBC, ASCE 7, AND VA H18-8 CHAPTER 4.0 -
ELEMENTS OF STRUCTURES, NONSTRUCTURAL COMPONENTS, AND EQUIPMENT SUPPORTED BY STRUCTURES FOR CRITICAL AND ESSENTIAL FACILITIES. THE
EXISTING STEEL AND DESIGNATED WOOD FRAMING IS CAPABLE OF SUPPORTING THE PATIENT LIFT LOADS WHEN ATTACHED TO THE STRUCTURE BY THE
CONTRACTOR.
REFER TO ARCHITECTURAL DRAWINGS FOR PATIENT LIFT EQUIPMENT LISTED AS BASIS OF DESIGN. ALL STRUCTURAL COMPONENTS REQUIRED TO SUPPORT
EQUIPMENT ARE TO BE DESIGNED BY THE CONTRACTOR. STRUCTURAL COMPONENTS INCLUDING UNISTRUT ARE TO BE SHOWN ON THE HVAC COORDINATION
DRAWINGS.
PROVIDE ENGINEERING OF LIFT SUPPORT FRAMEWORK PERFORMED BY A QUALIFIED PROFESSIONAL ENGINEER WHO IS LEGALLY QUALIFIED TO PRACTICE IN THE
JURISTICTION WHERE THE PROJECT IS LOCATED AND WHO IS EXPERIENCED IN PROVIDING ENGINEERING SERVICES OF THE KIND INDICATED. SUBMIT SEALED
ENGINEERING CALCULATIONS AND SHOP DRAWINGS FOR REVIEW.
TYPICAL UNISTRUT PATIENT LIFT SUPPORTS
F.P. OR PROVIDE F.P. WELD
OF BOLTED BOTTOM PLATE
TO GIRDER WEB
TOP AND BOTTOM WELDED
OR BOLTED PLATES.
FILL PLATE AS REQ'D.
WELD PLATE ALL AROUND.
SHEAR CONNECTION.
DO NOT ATTACH PLATE TO GIRDER
FLANGES TOP AND BOTTOM.
DO NOT ATTACH PLATE
TO GIRDER FLANGES.
TOP WELDED OR
BOLTED PLATE.
SHEAR CONNECTION.
BEAM
GIRDER
TYPICAL MOMENT CONNECTION
BEAM TO GIRDER
BOLTED BOTTOM PLATE
MAY BE USED AT
CONTRACTOR'S OPTION.
UNISTRUT ATTACHMENTS TO BE SIZED AND
DETAILED BY CONTRACTOR. HANGING LOADS
FROM UNISTRUT ATTACHMENTS NOT TO
EXCEED
EQUIVALENT OF 200 PLF ON INDIVIDUAL BEAMS,
NOR MAXIMUM POINT LOAD OF 2000 POUNDS.
UNISTRUT FRAMING AS
REQUIRED
TO SUPPORT UNISTRUT TRACKS
BELOW. DIAGONAL BRACING
REQUIRED IN BOTH DIRECTIONS.
CEILING.
UNISTRUT TRACKS MOUNTED FLUSH
TO CEILING. REFER TO EQUIPMENT
DRAWINGS FOR LOCATION,
SPACING,
LENGTH, LOADS AND TYPE OF
UNISTRUT REQUIRED.
OVERHEAD RAILS BY
EQUIPMENT
MANUFACTURER.
NOTES:
1. CONTRACTOR TO DESIGN AND DETAIL UNISTRUT FRAMING TO MEET EQUIPMENT MANUFACTURER'S CRITERIA.
SUBMIT DETAILS AND CALCULATIONS TO ARCHITECT FOR REVIEW. DESIGN TO BE PERFORMED AND STAMPED BY
A PROFESSIONAL ENGINEER REGISTERED IN STATE OF OHIO.
2. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF ROOMS THAT REQUIRE CEILING TRACKS.
EXTEND UNISTRUT DIAGONAL BRACING
TO
UNDERSIDE OF SLAB ON METAL DECK
WHERE BRACING IS PERPENDICULAR TO
BEAM.
TYPICAL UNISTRUT CEILING TRACK
SUPPORT AT MEDICAL EQUIPMENT
NOTES:
1. FOR LOADS NOT EXCEEDING 500 POUNDS.
2. REFER TO ARCH AND MECH DRAWINGS FOR SIZE AND LOCATIONS OF OPENINGS.
3. FOR OPENINGS SMALLER THAN 12"x12", REFER TO SPECIFICATION SECTION 053000
FOR REINFORCING OF ROOF DECK.
4. MAXIMUM OPENING SIZE: 4'-0"x4'-0".
5. BID TO BE BASED ON FABRICATING AND INSTALLING ____ ROOF OPENING FRAMES.
SHOW OPENINGS ON SHOP DRAWINGS.
BEAM.
L4x4x5/16
BEAM.
WELD DECK TO ANGLES
AT 6" O.C. ALL AROUND.
L4x4x1/4.
ROOF OPENING FRAME
TYPICAL
1" MAX
3/16 1-1/2
TYP
3/16
TYP
SEE PLAN FOR SPACING
5" 3"
EXISTING BRICK FACADE.
FLOOR
6" 6"
EXISTING CONCRETE
STRUCTURE.
3" VENT OR 6" HPS, REFER TO
MECHANICAL DRAWINGS FOR
LOCATION.
STANDARD PIPE CLAMP.
BASIS OF DESIGN: B-LINE 2400.
REMOVE AND REPLACE
EXISTING BRICK AS REQUIRED.
5/8" DIA EXPANSION
ANCHORS 4" MIN EMBED.
1/
2" 3"
5"
HSS3X2X1/4.
3/8" PLATE.
INSTALL COVE OF
URETHANE SEALANT
AROUND BRACKET.
EXISTING CONCRETE
STRUCTURE.
EXISTING.
3/16
TYP
12" AT SINGLE RISERS
18" AT MULTIPLE RISERS
PIPE SUPPORTS ON EXISTING BUILDING
SECTION PLAN VIEW
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.25.2023
Bid Documents 100% TBD
Design Development 65% (Re-submittal) 11.15.2021
/1
4/
:1 8:
P
M
Construct Private In-Patient Rooms & Primary Clinics
TBD
TYPICAL DETAILS
S003
SETFJE
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS
20014.00
D I
13.9
13.2
9.8
9.3
7.9A
H.1 H.7
E.3
W12X16 (12) V=15
W12X19 (12) V=30
W12X19 (12) V=30
W12X19 (12) V=25
W
X
(4
V
W
X
M =9
(2
4) V
=3
W12X19 (12) V=20
W12X19 (12) V=15
W12X19 (12) V=15
W
X
(4
V
W
X
A
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
M =1
V
W
X
M
=1
V
W
X
M =1
V
W
X
M =1
V
W
X
M
=1
V
W
X
M =9
(2
4) V
=3
W
X
M =9
(2
4) V
=3
W
X
M =9
(2
6) V
=3
W
X
M =1
V
W
X
M
=9
(2 6)
V =3
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
M =8
(2
4) V
=2
W
X
V
W
X
(4
V
A /S
E F G H
2'-11" ±
19'-6" ± 9'-8" ± 13'-0" ± 13'-0" ± 18'-11" ±
2'-8" ± 13'-0" ±
W
X
V
W
X
V
W
X
8)
V
2' -4
/2
'-3
/4
'-9
/4
'-3
'-3
'-2
2' -2
3' -2
7' -0
4' -0
'-3
2' -4
/4
E J
E J
4 TYP
4 TYP
T/SLAB= 860'-5"
W14X26 M=90 (24) V=25
W14X26 M=130 (24) V=35
W14X61 M=325 (44) V=70 W14X26 M=135 (24) V=35
W14X61 M=315 (44) V=70 W14X26 M=130 (24) V=35
W14X61 M=295 (44) V=75 W14X26 M=120 (24) V=35
W14X61 M=95 (20) V=25 W14X26 M=75 (24) V=25
W14X53W14X53 V=50
W14X53
W14X53
W14X53
W12X14 (4)
W12X14 (4)
W12X14 (4)
W12X14 (4)
W12X14 (4)
W12X14 (4)
W12X14 (4)
W12X14 (4)
W12X14 (4)
W12X14 (4)
W12X14 (4)
S104
B.1
ABOVE
S201
W
X
M =1
V
7'-0 1/4"
TYP AT
JAMBS
S201
S201
W14X61 M=285 (44) V=65W14X53 V=30
W
X
8)
V
A /S
7'-0 1/4"
1'-2" 5'-10 1/4"
1'-2" 5'-10 1/4"
TYP
S201
TYP
TYP
T R
A N
S F
E R
T R
U S
S
S501
TYPICAL AT
SUPPLEMENTAL FRAMING
W8X18
W8X18
W 8X
W8X18
W8X18
W 8X
W8X18
W12X14 (4)
W12X26
8'-1 1/2" 7'-6 1/2"
W8X18
W8X18
6'-5" EQ EQ
3'-6" EQ EQ
4' -0
/2
3' -1
/4
7'
-1
/4
2' -8
3'
-1
1/ 2"
4' -1
/2
3'
-1
/4
3'-5 1/4"
S201
D I
13.9
13.2
9.8
9.3
7.9A
H.1 H.7
E.3E F G H
2'-11" ±
19'-6" ± 9'-8" ± 13'-0" ± 13'-0" ± 18'-11" ±
2'-8" ± 13'-0" ±
2' -4
/2
'-3
/4
'-9
/4
'-3
'-3
'-2
2' -2
3' -2
7' -0
4' -0
'-3
2' -4
/4
EX W14X74 EX W14X74
EX W14X74 EX W14X74
EX W14X74 EX W14X74
EX W14X74 EX W14X74
EX W14X74 EX W14X74
EX W14X74 EX W14X74
EX W10X26
EX W10X26
E X
W
X
E X
W
X
EX W10X26
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
W
X
E X
C
X
EX W14X53
EX W14X43EX W14X43
E X
C
X
E X
C
X
E X
C
X
E X
C
X
EX W14X53
EX W14X53
EX W14X53
EX W14X53
E X
C 8X
.5
EX W10X15EX W10X15EX W10X15
E X
W
X
EX W10X30
E X
W
X
EX W10X26
E X
W
X
EX W10X15EX W10X15EX W10X15E
X
W
X
EXISTING 6 1/2"± SLAB
ON 2" METAL DECK.
T/SLAB = 849'-5"±.
EX W8X13
EX W8X13
EX W8X13
EX W8X13
EX W8X13
EX W8X13
5 TYP
W8X18
W 8X
13.9
E G
W14X30 M=185 V=40
W
X
M =7
(2
4) V
=2
W16X31 M=180 (16) V=40
W
X
V
W
X
V
W
X
M =8
(1
2) V
=3 0 1
4 TYP
W12X19 (12) V=15
W
X
V
W12X30 W12X30
T/SLAB= 863'-10 1/2"
SLAB STEP
BEAM SPLICE
DIRECTION OF DECK SPAN
INDICATES BEAM TOP OF STEEL ELEVATION U.N.O.[XXX'-XX"]
FRAMING PLAN LEGEND:
CANTILEVER MOMENT CONNECTION
MOMENT FRAME CONNECTION
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.25.2023
Bid Documents 100% TBD
Design Development 65% (Re-submittal) 11.15.2021
/1
4/
:1 9:
P
M
Construct Private In-Patient Rooms & Primary Clinics
TBD
THIRD AND FOURTH FLOORS
FRAMING PLANS
S104
SETFJE
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS
20014.00
DRAWING NOTES:
1. REFER TO S000 SERIES FOR GENERAL NOTES AND TYPICAL DETAILS .
2. REFER TO S200 SERIES FOR FRAMING DETAILS.
3. REFER TO S300 SERIES FOR TRUSS ELEVATION AND DETAILS.
4. REFER TO S400 SERIES FOR COLUMN SCHEDULE.
5. CONTRACTOR TO FIELD MEASURE ALL EXISTING DIMENSIONS AND VERIFY ALL EXISTING CONDITIONS RELATED TO THE WORK BEFORE SUBMITTING SHOP DRAWINGS. DIMENSIONS, ELEVATIONS, MEMBER SIZES, ETC. GIVEN FOR EXISTING STRUCTURE ARE BASED ON THE EXISTING DESIGN DRAWINGS AND ARE GIVEN FOR INFORMATION ONLY. NOTIFY ENGINEER IF CONDITIONS ARE DIFFERENT THAN THOSE SHOWN.
6. SEE TYPICAL DETAIL ON S003 FOR PATIENT LIFT SUPPORT INFORMATION. COORDINATE WITH ARCHITECT
AND PATIENT LIFT SUPPLIER FOR LOCATIONS AND ADDITIONAL INFORMATION.
PLAN NOTES:
1. SLAB ON METAL DECK: 3 1/4" LIGHTWEIGHT CONCRETE ON 2" COMPOSITE, GALVANIZED METAL DECK (5 1/4"
TOTAL SLAB THICKNESS). REINFORCED WITH 6X6-W2.9XW2.9 (42#).
2. COLUMN OR BEAM IS CONNECTED TO EXISTING STRUCTURE WITH HSS OR W10 SHORT BEAM. CHIP CONCRETE AT EXISTING STRUCTURAL STEEL TO ALLOW FOR CONNECTION TO EXISTING. COORDINATE WITH LIFE SAFETY
AND ARCH DWGS FOR REESTABLISHMENT OF FIREPROOFING, IF REQUIRED. REFER TO 3/S201.
3. EXPANSION JOINT, SEE ARCH.
4. W10 OUTRIGGER FOR SLAB EDGE SUPPORT. REFER TO 2/S201.
5. NEW COLUMN TO BE CENTERED ON EXISTING COLUMN. SEE S401 FOR SCHEDULE AND ATTACHMENT DETAIL TO EXISTING. NOTE THAT EXISTING SLAB ON METAL DECK WILL REQUIRE CUTTING/PATCHING TO INSTALL NEW
COLUMNS.
6. 8" THICK CONCRETE WALL ABOVE, REINFORCED WITH #4 AT 12" O.C. EACH WAY, EACH FACE. PROVIDE
DOWELS TO SUPPORTING SLAB TO MATCH VERTICAL REINFORCING.
7. CONCRETE WALL BELOW. POUR AROUND BEAMS AND UP TO UNDERSIDE OF DECK.
8. FRAMING FOR ARCHITECTURAL AND MECHANICAL OPENINGS, SEE S501.
9. INFILL EXISTING SLAB OPENING WITH SLAB ON METAL DECK. REMOVE EXISTING EDGE OF DECK STEEL, CHIP AWAY EXISTING SLAB AND REMOVE EXISTING DECK AS REQUIRED TO ALLOW FOR 1-1/2" MINIMUM BEARING OF NEW DECK. PROVIDE #4 x 1'-0" LONG DOWELS AT 12" O.C. MAX AT PERIMETER, DRILLED AND EPOXIED 6" INTO EXISTING, CENTERED VERTICALLY ON SLAB. PROVIDE SLAB ON METAL DECK PER PLAN NOTE 1 THIS SHEET.
10. NEW OPENING, COORDINATE WITH ARCH AND MEP DRAWINGS. INSTALL SPECIFIED STEEL PRIOR TO CUTTING OPENING. CORE CORNERS OF OPENING AND SAWCUT REMAINDER. DO NOT OVERCUT AT CORNERS.
11. SHORE EXISTING BEAM AND PROVIDE ATTACHMENT TO NEW STEEL AS REQUIRED.
12. 4" HOUSEKEEPING PAD, VERIFY SIZE. REFER TO MECHANICAL DRAWINGS AND A104D, A104N.
NORTH
1/8" = 1'-0"S104
B FOURTH FLOOR FRAMING PLAN
NORTH
1/8" = 1'-0"S104
A EXISTING THIRD FLOOR FRAMING PLAN
1/8" = 1'-0"S104
B.1 PARTIAL FRAMING PLAN
CHAPEL ROOF
13.9
13.2
9.8
9.3
7.9A
'-1
1/
8"
35'-6 3/8"
D I
13.9
13.2
9.8
9.3
7.9A
H.1 H.7
E.3
A /S
W14X61 M=175 (44) V=35 W14X26 M=75 (24) V=20
W14X61 M=225 (44) V=45 W14X26 M=100 (24) V=25
W14X61 M=225 (44) V=45 W14X26 M=100 (24) V=25
W14X61 M=215 (44) V=45 W14X26 M=100 (24) V=25
W14X61 M=200 (44) V=50 W14X26 M=85 (24) V=25
W14X61 M=75 (44) V=20 W14X26 M=60 (24) V=15
W12X19 (8) V=15
W12X19 (8) V=15
W12X19 (8) V=15
W12X19 (8) V=15
W
X
(4
V
W
X
M =6
(2
4) V
=2
W12X19 (8)
W12X19 (8) V=15
W12X19 (8) V=15
W
X
(4
V
W
X
A
=9
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
M =7
(2
4) V
=2
W
X
M =7
(2
4) V
=2
W
X
M =7
(2
4) V
=2
W
X
M =6
(2
4) V
=2
W
X
M =8
(2
4) V
=3
W
X
M =7
(2
4) V
=2
W
X
M =7
(2
4) V
=2
W
X
M =7
(2
4) V
=2
W
X
M =7
(2
4) V
=2
W
X
M =7
(2
4) V
=2
W
X
M =7
(2
4) V
=2
W
X
M =7
(2
4) V
=2
W
X
V
W
X
V
W
X
V
W
X
V
W
X
V
W
X
M =6
(2
4) V
=2
W
X
V
W
X
(4
V
E F G H
W14X53
W
X
-3
V
W
X
-3
V
W
X
-3
V
W
X
-3
V
2'-11" ±
19'-6" ± 9'-8" ± 13'-0" ± 13'-0" ± 18'-11" ±
2'-8" ± 13'-0" ±
2' -4
/2
'-3
/4
'-9
/4
'-3
'-3
'-2
2' -2
3' -2
7' -0
4' -0
'-3
2' -4
/4
E J
E J
4 TYP
4 TYP
T/SLAB= 873'-0 1/4"
S201
S201
W12X19 (4)
W8X18
W 8X
W8X18
W 8X
8TYP
TYP AT
JAMBS
W14X53 [-3"] V=25
W14X53 [-3"] V=25
W
X
-3
V
S201
S201
S201
S201
S201
S201
S201
W14X53 V=25
W14X53 . V=25
W14X53 V=55
W14X53 V=20
8TYP
8TYP
A /S
7'-0 1/4"
11 7/8" 6'-0 3/8"
7'-0 1/4"
11 7/8" 6'-0 3/8"
TYP
TYP
S201
TYP
T R
A N
S F
E R
T R
U S
S
S501
TYPICAL AT
SUPPLEMENTAL FRAMING 13
S201
D I
13.9
13.2
9.8
9.3
7.9A
H.1 H.7
E.3
A /S
W14X26 M=100 V=20 W14X22 M=60 V=15
W14X26 M=125 V=30 W14X22 M=70 V=20
W14X26 M=120 V=25 W14X22 M=65 V=20
W14X53 M=120 V=25 W14X30 M=65 V=20
W14X53 M=115 V=30 W14X30 M=65 V=20
W14X26 M=40 V=15 W14X22 M=45 V=15
W12X16 V=15
W12X16 V=15
W12X16 V=15
W12X16 V=15
W
X
V =1
W
X
M
V
=1
W
X
V =1
W12X16
W12X16
W12X16 V=15 W
X
V =1
W
X
V
=1
W
X
V =1
W
X
V
=1
W
X
M
V
=4
W
X
M
V
=1
W
X
M
V
=1
W
X
M
V
=2
W
X
M
V
=1
W
X
M
V
=1
W
X
M
V
=2
W
X
M
V
=1
W
X
M
V
=1
W
X
M
V
=1
W
X
M
V
=4
W
X
V =4
W
X
V =1
W
X
V =1
W
X
V =1
W
X
M
V
=1
E F G H
W14X26W14X26 V=25
W
X
V =1
2'-11" ±
19'-6" ± 9'-8" ± 13'-0" ± 13'-0" ± 18'-11" ±
2'-8" ± 13'-0" ±
2' -4
/2
'-3
/4
'-9
/4
'-3
'-3
'-2
2' -2
3' -2
7' -0
4' -0
'-3
2' -4
/4
E J
4 TYP
4 TYP
W14X26 V=15
W14X26 V=20
W14X26 V=20
W14X26 V=20
W14X26 V=15
W
X
V =1
W
X
V
=1
W
X
V =1
W12X16
W
X
V =1
D .B
5'
-7
/8
H .P
D .B
5'
-0
L.
P
D .B
5'
-7
/2
H .P
SLOPE DOWN SLOPE DOWN
W
X
M
V
=1
W
X
V =1
W8X18
W8X18
S201
W
X
V =1
W
X
V
=1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V
=1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V
=1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V
=1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V
=1
W
X
V =2
W
X
V
=1
W
X
V =1
S201
E J
E J
S201
ABOVE
S201
A /S
10 1/2" 6'-0 3/8"
6'-10 7/8"
W
X
V =1
W
X
V
=1
W
X
V =1
W
X
V =1
W
X
V =1
W
X
V =1
6'-10 7/8"
10 1/2" 6'-0 3/8"
TYP
TYP
TYP
S105
D.2
2' -3
/4
2'
-3
/4
S105
D.1
S201
S501
TYPICAL AT
SUPPLEMENTAL FRAMING
SLAB STEP
BEAM SPLICE
DIRECTION OF DECK SPAN
INDICATES BEAM TOP OF STEEL ELEVATION U.N.O.[XXX'-XX"]
FRAMING PLAN LEGEND:
CANTILEVER MOMENT CONNECTION
MOMENT FRAME CONNECTION
H.1E G
W14X43
W
X
W
X
W14X43 W
X
6" DIA STD PIPE POST, TYP.
(2) L3X3X3/8 KICKER, TYP.
L6 X6
X5 /1
L6X6X5/16L6 X6
X5 /1
NOTE: T/STEEL = 888'-8" U.N.O.
W
X
S201
TYP
S201
TYP
CONNECT TO WF BEAM
PER 11/S201, TYP.
11'-10 1/2"
34'-6 1/2"
'-2
B
A S
E
35'-0" BASE
2' -3
/4
'-8
/2
2' -3
/4
S201
H.1E G
22'-8" 17'-8"
'-3
2'-0"2'-0"
HSS10X8X1/4
H S
S
X 8X
1/
H S
S
X 8X
1/
H S
S
X 8X
1/
H S
S
X 8X
1/
H S
S
X 8X
1/
H S
S
X 8X
1/
HSS8X
8X
3/
HSS8X
8X
3/
HSS8X
8X
3/
HSS8X8X3/8
HSS8X8X3/8
HSS8X8X3/8
HSS10X8X1/4
NOTE: T/STEEL = 897'-8" U.N.O.
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.25.2023
Bid Documents 100% TBD
Design Development 65% (Re-submittal) 11.15.2021
/1
4/
:1 9:
P
M
Construct Private In-Patient Rooms & Primary Clinics
TBD
FIFTH FLOOR AND ROOF FRAMING
PLANS
S105
SETFJE
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS
20014.00
DRAWING NOTES:
1. REFER TO S000 SERIES FOR GENERAL NOTES AND TYPICAL DETAILS .
2. REFER TO S200 SERIES FOR FRAMING DETAILS.
3. REFER TO S300 SERIES FOR TRUSS ELEVATION AND DETAILS.
4. REFER TO S400 SERIES FOR COLUMN SCHEDULE.
5. CONTRACTOR TO FIELD MEASURE ALL EXISTING DIMENSIONS AND VERIFY ALL EXISTING CONDITIONS RELATED TO THE WORK BEFORE SUBMITTING SHOP DRAWINGS. DIMENSIONS, ELEVATIONS, MEMBER SIZES, ETC. GIVEN FOR EXISTING STRUCTURE ARE BASED ON THE EXISTING DESIGN DRAWINGS AND ARE GIVEN FOR INFORMATION ONLY. NOTIFY ENGINEER IF CONDITIONS ARE DIFFERENT THAN THOSE SHOWN.
6. SEE TYPICAL DETAIL ON S003 FOR PATIENT LIFT SUPPORT INFORMATION. COORDINATE WITH ARCHITECT
AND PATIENT LIFT SUPPLIER FOR LOCATIONS AND ADDITIONAL INFORMATION.
PLAN NOTES:
1. SLAB ON METAL DECK: 3 1/4" LIGHTWEIGHT CONCRETE ON 2" COMPOSITE, GALVANIZED METAL DECK (5 1/4"
TOTAL SLAB THICKNESS). REINFORCED WITH 6X6-W2.9XW2.9 (42#).
2. COLUMN OR BEAM IS CONNECTED TO EXISTING STRUCTURE WITH HSS OR W10 SHORT BEAM. CHIP CONCRETE AT EXISTING STRUCTURAL STEEL TO ALLOW FOR CONNECTION TO EXISTING. COORDINATE WITH LIFE SAFETY
AND ARCH DWGS FOR REESTABLISHMENT OF FIREPROOFING, IF REQUIRED. REFER TO 3/S201.
3. EXPANSION JOINT, SEE ARCH.
4. W10 OUTRIGGER FOR SLAB EDGE SUPPORT. REFER TO 2/S201.
5. SLAB ON METAL DECK: 2" LIGHTWEIGHT CONCRETE ON 2" COMPOSITE, GALVANIZED METAL DECK (4" TOTAL
SLAB THICKNESS). REINFORCED WITH 6X6-W2.9XW2.9 (42#).
6. FRAMING FOR ARCHITECTURAL AND MECHANICAL OPENINGS, SEE S501.
7. MECHANICAL UNIT ABOVE ROOF, COORDINATE WITH MECHANICAL DRAWINGS. PROVIDE SUPPORT FRAMING
PER PLAN D.1/S105.
8. DEPRESSION FOR SHOWER, COORDINATE WITH ARCH.
9. MECHANICAL OPENING, COORDINATE WITH ARCH AND MECH.
NORTH
1/8" = 1'-0"S105
C FIFTH FLOOR FRAMING PLAN
NORTH
1/8" = 1'-0"S105
D ROOF FRAMING PLAN
NOTE:
GALVANIZED STEEL AND ATTACHMENT ANCHORS FOR DUCT SUPPORT AND DUNNAGE FOR SUPPORT OF NEW MECHANICAL EQUIPMENT ON EXISTING ADJACENT BUILDING WILL BE REQUIRED. FOR PRICING, ASSUME 10 TONS OF GALVANIZED STEEL WITH ATTACHMENT THROUGH EXISTING FACADES / ROOFING / FINISHES / FIREPROOFING /
CONCRETE TO EXISTING STRUCTURAL STEEL AT ATTACHMENT POINTS.
1/8" = 1'-0"S105
D.1 MECHANICAL SUPPORT FRAMING
1/8" = 1'-0"S105
D.2 SCREENWALL FRAMING
G
H.2
13.9
7.9A
9.3
9.8
H.7
E.3 H.3
I
13.9
13.2
9.8
9.3
7.9A
H.1 H.7
E.3E F G H
EX 12WF27
EX 10WF25 EX 8WF17
E X
2W
F
E X
0W
F
E X
2W
F
EX 12WF27EX 10WF21
E X
W
F
E X
W
F
EX 10WF25
E X
0W
F
EX 10WF21EX 10WF21 EX 10WF21
E X
4W
F
EX 10WF21
E X
4W
F
E X
4W
F
EX 10WF21
E X
4W
F
EX 10WF21EX 8WF17EX 10WF21
E X
4W
F
EX 10WF21
E X
4W
F
E X
4W
F
EX 10WF21
E X
4W
F
EX 16WF40EX 12WF27EX 16WF40
E X
1W
F
EX 14WF30
E X
6W
F
EX 10WF21
E X
6W
F
EX 14WF30
E X
6W
F
EX 18WF55
E X
W
F
E X
4W
F