This document appears to be Attachment 05 - Drawings - Electrical related to the federal contract opportunity 506-334 – Construct Private In-Patient Rooms and Primary Clinics in Ann Arbor, MI. The solicitation, issued by the Department of Veterans Affairs Technology Acquisition Center Austin, calls for the construction of private in-patient rooms and primary clinics. The attachment provides detailed electrical drawings and specifications required for this construction project. No further details about the overall scope of work, pricing, or response requirements are included in this attachment.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL SYMBOLS
EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.
DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS WHERE
REQUIRED.
ELECTRICAL CONNECTION.
20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE).
SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.
20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERWISE) TWO GANG ASSEMBLY.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED
OTHERWISE).
20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERWISE) WITH
EXTRA DUTY COVER, VERTICAL MOUNT.
20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH
UNLESS NOTED OTHERWISE), WITH EXTRA DUTY COVER, VERTICAL MOUNT.
JUNCTION BOX. SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POWER.
MULTI-OUTLET RECEPTACLES ASSEMBLY, NEMA 5-15R (SINGLE OUTLETS ON 18" CENTERS) (46" MH UNLESS NOTED
OTHERWISE).
SINGLE POLE SWITCH (46" MH UNLESS NOTED OTHERWISE).
TWO POLE WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).
MULTI-WAY WALL SWITCH, # INDICATES NUMBER OF WAYS (46" MH UNLESS NOTED OTHERWISE).
LIGHTING DIMMER SWITCH (46" MH UNLESS NOTED OTHERWISE).
DISCONNECT SWITCH.
MOTOR STARTER.
COMBINATION MOTOR STARTER AND DISCONNECT SWITCH.
ELECTRIC MOTOR.
ELECTRICAL PANEL OR SWITCHBOARD PER DRAWINGS.
PULL BOX.
CORD REEL.
POWER POLE.
CEILING MOUNTED OCCUPANCY SENSOR.
WALL MOUNTED OCCUPANCY SENSOR.
CEILING MOUNTED DAYLIGHT SENSOR.
OCCUPANCY SENSOR POWER PACK.
GF
WP
WP/GF
J
D
PP
OS
OS
M
DS
OP
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (46" MH UNLESS NOTED OTHERWISE).
CR
P/B
LOW-VOLTAGE MOMENTARY WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).L
ABBREVIATIONS
AAP - AREA ALARM PANEL - MEDICAL GAS
ACC - ACCESS
ADJ - ADJUSTABLE
AF - ARC FAULT CIRCUIT INTERRUPTER
AFCI - ARC FAULT CIRCUIT INTERRUPTER
AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM
AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATS - AUTOMATIC TRANSFER SWITCH
BLDG - BUILDING
BOE - BOTTOM OF EQUIPMENT
BOT - BOTTOM
BTWN - BETWEEN
BW - BLANKET WARMER
CC - CART CHARGING
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CKT - CIRCUIT
CLG - CEILING
CM - COFFEE MAKER
CMU - CONCRETE MASONRY UNIT
CO - COPIER
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
CORR - CORRIDOR
CTR - CENTER
D - DEPTH
DET - DETAIL
DIA - DIAMETER
DIM - DIMENSION
DIV - DIVISION
DN - DOWN
DW - DISHWASHER
DWG - DRAWING
EA - EACH
EC - ELECTRICAL (DIVISION 26)
ECM - ELECTRONICALLY COMMUTATED MOTOR
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATION OR ELEVATOR
EM - EMERGENCY
EQ - EQUAL
EQS - EQUIPMENT SUPPLIER
EQUIP - EQUIPMENT
ETR - EXISTING TO REMAIN
EX - EXISTING
EXP - EXPANSION
EXT - EXTERIOR
FCE - FIRE CONTROL EQUIPMENT
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
GC - GENERAL TRADES (DIVISION 01)
GF - GROUND FAULT CIRCUIT INTERRUPTER
GFB - GROUND FAULT BREAKER
GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT
FURNISHED CONTRACTOR INSTALLED
GFFT - GROUND FAULT FEED THRU
HC - HVAC (DIVISION 23)
HP - HORSE POWER OR HIGH POINT
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ICE - ICE MACHINE
ID - INSIDE DIAMETER
IN - INCHES
KEC - KITCHEN EQUIPMENT
L - LENGTH
LBS - POUNDS
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MON - MONITOR
MTD - MOUNTED
MTG - MOUNTING
MW - MICROWAVE
NIC - NOT IN CONTRACT
NOM - NOMINAL
NTS - NOT TO SCALE
OC - OMNI-CELL
OD - OUTSIDE DIAMETER
OFCI - OWNER FURNISHED CONTRACTOR INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
PC - PLUMBING (DIVISION 22)
PLBG - PLUMBING
PR - PRINTER
RAD - RADIUS
REC - RECESSED
RF - REFRIGERATOR
REQD - REQUIRED
RI - ROUGH-IN
S - SURFACE MOUNTED
SC - SECURITY (DIVISION 28)
SCH - SCHEDULE
SHT - SHEET
SMS - SECURITY MANAGEMENT SYSTEM
SPEC - SPECIFICATIONS
SQ - SQUARE
SS - STAINLESS STEEL
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TC - TECHNOLOGY (DIVISION 27)
TEMP - TEMPERATURE
TOE - TOP OF EQUIPMENT
TV - TELEVISION
TYP - TYPICAL
UCR - UNDER COUNTER REFRIGERATOR
UNO - UNLESS NOTED OTHERWISE
VEND - VENDING MACHINE
VFD - VARIABLE FREQUENCY DRIVE
VOL - VOLUME
W/ - WITH
W/O - WITHOUT
WP - WEATHERPROOF
ZVC - ZONE VALVE CABINET
LUMINAIRE SYMBOLS
LIGHTING FIXTURE. CAPITAL LETTER DENOTES FIXTURE TYPE, LOWER CASE LETTER DENOTES
SWITCHING ARRANGEMENT.
LIGHTING FIXTURE ON NIGHT LIGHT OR LIFE SAFETY CIRCUIT.
EXIT LIGHTING FIXTURE, ARROWS AS INDICATED.
A a
WIREMOLD RACEWAY, AS NOTED ON PLANS.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH 2 INTEGRAL USB CHARGERS (18" MH UNLESS NOTED OTHERWISE).
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.
LIGHTING FIXTURE ON CRITICAL CIRCUIT.
SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POWER. SPECIFICATION IS SAME AS RESPECTIVE ROUND DEVICE.
J
KF
S
D
V
R W
SD
PS
AM
C/I
PIV
H
S S/R
S/R
FACP
FIRE ALARM SYMBOLS
FIRE ALARM CONTROL PANEL.
CEILING MOUNTED FIRE ALARM SPEAKER & SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE.
WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER
LOCATIONS.
FIRE ALARM MANUAL STATION (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "K" INDICATES KEY OPERATED.
CEILING MOUNTED SMOKE DETECTOR.
DUCT MOUNTED SMOKE DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.
DUCT MOUNTED HEAT DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.
ELECTRO-MAGNETIC DOOR HOLDER.
VALVE SUPERVISORY SWITCH.
CEILING MOUNTED REMOTE TEST STATION AND ALARM INDICATOR LIGHT FOR DUCT DETECTOR. SUBSCRIPT "W" INDICATES
WALL MOUNTED.
SMOKE DAMPER.
PRESSURE SWITCH.
ADDRESSABLE MODULE. SUBSCRIPT "I" INDICATES INPUT. SUBSCRIPT "C" INDICATES CONTROL.
POST INDICATOR VALVE.
REMOTE ANNUNCIATOR PANEL.
NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANEL.
RAP
NAC
S 15 F
E2
B
E2
DETAIL: B = DETAIL DESIGNATION
E2 = SHEET WHERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
E2 = SHEET WHERE SECTION IS LOCATED
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
GENERAL FLOOR PLAN NOTES
WIRE & CONDUIT IN WALL OR ABOVE CEILING.
WIRE & CONDUIT IN OR BELOW SLAB OR GRADE.
EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S) DENOTES
CIRCUIT(S).
EXISTING WIRE & CONDUIT TO REMAIN.EX
CONDUIT TO BE REMOVED.
X - 1,2
4"
4"
4"
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE).
CEILING MOUNTED FIRE ALARM SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
F
CEILING MOUNTED VACANCY SENSOR.OSVS
F
FIRE ALARM SPEAKER & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:3
:1
P M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
ABBREVIATIONS, SYMBOLS &
INDEX OF DRAWINGS
E001
JSFKMU
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
GENERAL NOTES
A. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.
B. CONTRACTOR SHALL THOROUGHLY STUDY DESIGN DRAWINGS AND ALL EXISTING CONDITIONS PRIOR TO STARTING PROPOSED
SCHEDULE.
C. SITE VISIT(S) SHALL BE AS OUTLINED IN PROJECT SPECIFICATIONS.
D. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING. REFER TO ARCHITECTURAL DRAWINGS AND GENERAL
REQUIREMENTS SECTION 01 00 00.
E. WHERE ROOFING WORK IS REQUIRED, THE EXISTING ROOFING MEMBRANE AND INSULATION SHALL BE CUT, REMOVED AND RESTORED AS REQUIRED TO ATTAIN A WATERTIGHT CONDITION. THE ROOFING SUB-CONTRACTOR SHALL BE A CERTIFIED
INSTALLER FOR SUCH INSTALLATION TO MAINTAIN THE EXISTING WARRANTY ON THE ROOF.
F. THE CONTRACTOR SHALL REFER TO ALL SPECIFICATION SECTIONS AND THESE DRAWINGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURE SPACE AND SATISFACTORY ARRANGEMENT FOR THEIR WORK. THE VARIOUS DRAWINGS COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED JOINTLY AT ALL TIMES. CONTRACTOR SHALL REFER TO THE GENERAL REQUIREMENTS OF THE CONTRACT. THE NOTES AND SYMBOLS INDICATED ON THE DRAWINGS ARE FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND MUST BE FOLLOWED TO EXECUTE THE WORK AS INTENDED. IF DISCREPANCIES OCCUR, CONTACT THE COR THRU THE CONTRACTING OFFICER FOR CLARIFICATION BEFORE PROCEEDING.
G. ALL WORK MUST BE COORDINATED WITH THE CONTRACTING OFFICER AND COR TO MAINTAIN OPERATION OF THE EXISTING FACILITY. COORDINATE ALL SHUT DOWNS A MINIMUM OF 21 DAYS BEFOREHAND. REVIEW WHICH LOADS WILL BE TAKEN DOWN, WHICH LOADS WILL REMAIN ON, AND OUTAGE START/END TIME.
H. ALL WORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE WITH ALL CURRENT GOVERNING CODES AND STANDARDS.
I. EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON AVAILABLE DRAWING INFORMATION, AND MAY BE AT VARIANCE WITH ACTUAL WORK IN PLACE. THE CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE WORK. ANY DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE CONTRACT DOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE WORK SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER IN WRITING FOR RESOLUTION BEFORE PROCEEDING WITH THE WORK.
J. REFER TO ARCHITECTURAL FIRE-RATED PARTITION PLAN(S) FOR LOCATIONS AND FIRE-RATINGS OF NEW AND EXISTING WALL ASSEMBLIES. ALL PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROTECTED AND/OR FIRE-STOPPED AS REQUIRED TO MAINTAIN FIRE-RATINGS INDICATED. COORDINATE WITH ALL TRADES TO ENSURE FIRE-RATED PENETRATION REQUIREMENTS
AND DETAILS ARE MET.
K. ANNULAR SPACE OF ALL PIPE, CONDUIT, DUCT & OTHER SIMILAR PENETRATIONS OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION, PENETRATIONS THROUGH 0-HOUR RATED WALLS & FLOORS SHALL BE FIRESTOPPED TO RETARD
PASSAGE OF FIRE & SMOKE.
L. ALL CONDUITS IN FINISHED ROOMS, CORRIDORS, ETC. SHALL BE CONCEALED IN A WALL OR ABOVE CEILING.
M. ACCESS PANELS IN NON ACCESSIBLE CEILINGS SHALL BE PROVIDED FOR ALL ELECTRICAL ITEMS REQUIRING ACCESS.
N. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF LUMINAIRES, SPEAKERS, NURSE CALL DEVICES, ETC.
O. REFER TO ARCHITECTURAL HEADWALL ELEVATIONS FOR EXACT LOCATION OF DEVICES.
P. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE INCLUDED IN THE CONTRACT. REFINISH ANY SURFACE
DISTURBED UNDER THIS WORK TO MATCH EXISTING.
Q. ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE VA. ITEMS NOT DESIRED BY THE VA SHALL BE REMOVED FROM THE
PREMISES AND DISPOSED OF PROPERLY BY THE CONTRACTOR.
R. THE CONTRACT DRAWINGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR HORIZONTAL OFFSET WHICH MAY BE NECESSARY TO COMPLETE THE SYSTEMS. COORDINATE WORK IN ADVANCE WITH ALL OTHER TRADES AND REPORT IMMEDIATELY AND
DIFFICULTIES WHICH CAN BE ANTICIPATED.
S. ALL ABANDONED EXTRANEOUS CONDUITS, WIRING, DEVICES, ETC. SHALL BE REMOVED.
T. REFER TO MECHANICAL/PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION CONCERNING EQUIPMENT THAT REQUIRES
ELECTRICAL CONNECTIONS.
U. BID ITEMS: REFER TO ARCHITECTURAL DESCRIPTION OF BID ITEMS, PLAN FOR AN OUTLINE OF BID ITEMS, AND TO SPECIFICATION
SECTION 01 00 00.
V. ACOUSTICAL CEILING ACCESS IDENTIFICATION MARKERS: COLORED MARKERS WITH PRESSURE SENSITIVE ADHESIVE ON ONE SIDE, PAPER OR PLASTIC, 6 TO 9 MM (1/4 TO 3/8 INCH) DIAMETER. REFER TO SPECIFICATION 09 51 00 SECTION 2.6.C.
1. COLOR CODE: PROVIDE THE FOLLOWING COLOR MARKERS FOR SERVICE IDENTIFICATION:
• RED - SPRINKLER SYSTEM: VALVES AND CONTROLS.
• GREEN - DOMESTIC WATER: VALVES AND CONTROLS.
• YELLOW - CHILLED WATER AND HEATING WATER.
• ORANGE - DUCTWORK: FIRE DAMPERS.
• BLUE - DUCTWORK: DAMPERS AND CONTROLS.
• BLACK - GAS: LABORATORY, MEDICAL, AIR AND VACUUM.
INDEX OF DRAWINGS - ELECTRICAL
SHEET NUMBER SHEET NAME
E001 ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS
E002 BID DEDUCT ALTERNATES
ED103 PARTIAL THIRD FLOOR PLAN - REMOVALS
ED105 PARTIAL FIFTH FLOOR PLAN - REMOVALS
EL103 PARTIAL THIRD FLOOR PLAN - LIGHTING
EL104 PARTIAL FOURTH FLOOR PLAN - LIGHTING
EL105 PARTIAL FIFTH FLOOR PLAN - LIGHTING
EP101 PARTIAL FIRST FLOOR PLAN - POWER
EP103 PARTIAL THIRD FLOOR PLAN - POWER
EP104 PARTIAL FOURTH FLOOR PLAN - POWER
EP105 PARTIAL FIFTH FLOOR PLAN - POWER
EP106 PARTIAL SIXTH FLOOR & ROOF PLAN - POWER
E401 ENLARGED PLANS
E501 SCHEDULES & DETAILS
E502 PANEL SCHEDULES
E503 PANEL SCHEDULES
E601 PARTIAL SINGLE LINE DIAGRAM
E602 PARTIAL SINGLE LINE DIAGRAM
E603 PARTIAL SINGLE LINE DIAGRAM
E604 PARTIAL SINGLE LINE DIAGRAM
Revisions Date
B01W
B01E
B01W
B01E
B01W
B01E
B01W
B01E
0.1 - DEDUCT ALTERNATE 01:
OMIT ALL WORK RELATED TO THE OPEN OFFICES AND CHAPEL.
SPACE WILL BE SHELLED, PROVIDE 37 C1a LUMINAIRES, 6
DUPLEX RECEPTACLES, 2 FA SPEAKER STROBES AND 3 FA
STROBES.
0.2 - DEDUCT ALTERNATE 02:
OMIT ALL WORK RELATED TO THE ELECTRICAL SHOP.
SPACE WILL BE SHELLED, PROVIDE 15 C1a LUMINAIRES, 1 LIGHTING TOGGLE SWITCH, 2 DUPLEX RECEPTACLES, 1 SPEAKER STROBES AND 1 STROBES.
0.3 - DEDUCT ALTERNATE 03:
OMIT ALL WORK RELATED TO THE TEACHING KITCHEN.
SPACE WILL BE SHELLED, PROVIDE 4 C1a LUMINAIRES, 2
LIGHTING TOGGLE SWITCH, 2 DUPLEX RECEPTACLES, 1
SPEAKER STROBE AND 1 STROBE.
0.4 - DEDUCT ALTERNATE 04:
OMIT ALL WORK RELATED TO CONSTRUCT
NEW LOUNGE AND LOCKER ROOMS.
RETAIN EXISTING LOCKER, RESTROOMS, HAC,
SOILED UTILITY AND OFFICE. EXISTING OFFICE
TO BECOME CLEAN LINEN ROOM.
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:3
:1
P M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
BID DEDUCT ALTERNATES
E002
JSFKMU
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
N Scale: 1" = 30'-0"
BID DEDUCT 01 - REMOVE THIRD FLOOR OFFICES AND
CHAPEL
N Scale: 1" = 30'-0"
BID DEDUCT 02 - REMOVE ELECTRICAL SHOP FOURTH
FLOOR
N Scale: 1" = 30'-0"
BID DEDUCT 03 - REMOVE TEACHING KITCHEN - THIRD
FLOOR
N Scale: 1" = 30'-0"
BID DEDUCT 04 - KEEP EXISTING FIFTH FLOOR
LOCKERS AND RESTROOMS
J J
GF
TV
/G
F
G F
J J
J
LIFT
LD
D
J
J
D
E401
1 1
507A
BATH
1BR
PATIENT
ROOM #2
MF1 MF1
V1 b d e f g a/b/c a/b/c
F4a g
F4a g g a a h i
F4a-WL h
F4b d
F4b d
F4b d
F4b d
NL e
F4b i
F4b i
F4b f
507A
BATH
1BR
PATIENT
ROOM #2
b,c
C1
C1
N1
N1
C1 C1 C1 C1
N1 N1 N1 N1
C2
N2
C2
N2
C2
N2
C2
N2
N2
N2
C2
C2
J J
N1 C1
J J
N1 C1
J J
N2 C2
J J
N2 C2
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:3
:2
P M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
ENLARGED PLANS
E401
JSFKMU
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
N Scale: 1/2" = 1'-0"
TYPICAL PATIENT ROOM - POWER
N Scale: 1/2" = 1'-0"
TYPICAL PATIENT ROOM - LIGHTING
Scale: 3/4" = 1'-0"1
PATIENT HEADWALL - POWER ELEVATION
NOTES
1 REFER TO OVERALL FLOOR PLAN ON SHEET EP105 FOR CIRCUIT INFORMATION.
2 REFER TO OVERALL FLOOR PLAN ON SHEET EL105 FOR CIRCUIT INFORMATION.
3 PROVIDE LOW VOLTAGE CONTROLLER TO ALLOW THE NURSE CALL PILLOW
SPEAKER CONTROL OF READING AND AMBIENT FUNCTIONS OF THE MF1 LUMINAIRE.
AMBIENT FUNCTION SHALL HAVE ON/OFF CONTROL UTILIZING PILLOW SPEAKER AND
LOW VOLTAGE ON/OFF CONTROL AT DOOR (SWITCH LEG "b". READING FUNCTION
SHALL HAVE ON/OFF CONTROL AT PILLOW SPEAKER.
4 PROVIDE LINE VOLTAGE 3-WAY SWITCHES TO CONTROL EXAM FUNCTION OF
PATIENT BED LUMINAIRES (SWITCH LEG "a").
5 SWITCHING DESIGNATION FOR PATIENT BED LUMINAIRES SHALL BE AS FOLLOWS: (a)
- EXAM FUNCTION, (b) - AMBIENT FUNCTION, (c) - READING FUNCTION.
6 PATIENT HEADWALL UNIT. EACH PATIENT HEADWALL UNIT SHALL HAVE (2)
DEDICATED CRITICAL POWER CIRCUITS AND (2) DEDICATED NORMAL POWER
CIRCUITS. REFER TO POWER ELEVATION ON THIS SHEET AND ARCHITECTURAL
ELEVATIONS FOR MORE INFORMATION.
7 PROVIDE RECEPTACLE IN CEILING FOR PATIENT LIFT. COORDINATE EXACT LOCATION
IN THE FIELD PER MANUFACTURER RECOMMENDATIONS.
8 PROVIDE 120V GF PROTECTED CIRCUIT TO POWER SUPPLY ABOVE ACCESSIBLE
CEILING FOR LOW-VOLTAGE POWER CONNECTION TO SHOWER CONTROLS. PROVIDE
.75" CONDUIT BETWEEN POWER SUPPLY AND DIGITAL MIXING VALVE UNIT FOR LOW
VOLTAGE WIRING. COORDINATE REQUIREMENTS WITH VENDOR.
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:3
:2
P M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
SCHEDULES & DETAILS
E501
JSFKMU
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
NOTES:
1. PROVIDE SINGLE POINT CONNECTION TO UNIT.
2. PROVIDE INTERLOCK BETWEEN VFD AND OUTDOOR DISCONNECT. VFD SHALL SHUTDOWN UPON OPENING OF DISCONNECT.
3. REFER TO SINGLE LINE FOR WIRE SIZE.
MOTORS, STARTERS, DISCONNECTS & CONTROLS
MARK
MOTOR STARTER DISCONNECT MEANS CONTROL FEEDER
S E
E N
O T
E
NAMEPLATE
CHARACTERISTICS LOCATION
N E
M A
S
IZ
E
TYPE LOCATION
F U
R N
IS
H
E D
B Y
TYPE LOCATION
F U
R N
IS
H
E D
B Y
I N
T E
R L O
C K
W
IT
H M
O T
O R
N O
B
Y E
.C
M A
N U
A L A
T S
T A
R T
E R
I N
T E
G R
A L
W
IT
H E
Q U
IP
M
E N
T
F U
R N
IS
H
E D
B Y
S E
E N
O T
E
N U
M B
E R
O F
C O
N D
U C
T O
R S
W
IR
E S
IZ
E
G R
O U
N D
S
IZ
E
C O
N D
U
IT
S
IZ
E
H O
R S
E P
O W
E R
H
P
L O
A D kV
A
V
-1 P
H
V
-1 P
H
V
-3 P
H
V
-1 P
H
V
-3 P
H
V
-1 P
H
V
-1 P
H
V
-3 P
H
R O
O M
N U
M B
E R
ROOM NAME M
A
N U
A L
M A
G N
E T
IC
E C
M
-S
P E
E D
V F
D
S E
E N
O T
E
N E
A R
M O
T O
R
M O
T O
R C
O N
T C
E N
T E
R
E Q
U
IP
C O
N T
P A
N E
L
R O
O M
N U
M B
E R
S E
E N
O T
E
D
IS
C S
W
IT
C H
M A
N U
A L S
T A
R T
E R
R E
C E
P T
A C
L E
T O
G G
L E
S W
IT
C
H
N E
M A
T Y
P E
D
IS
C S
IZ
E
F U
S E
S
IZ
E
N E
A R
M O
T O
R
M O
T O
R C
O N
T C
E N
T E
R
E Q
U
IP
C O
N T
P A
N E
L
P A
N E
L B
O A
R D
S E
E N
O T
E
1W-AHU21T TEMPORARY AIR HANDLING UNIT 21T SUPPLY: (4) - 5.2 HP,
RETURN (2) - 4 HP
120.62 ● ● DIV. 23 ● ● DIV. 26 DIV. 23 3 350
KCMIL
4 3"
1W-AHU22 RF 1W AIR HANDLER UNIT 22 - RETURN ARRAY (2) - 7 HP 13.72 ● 400 MECHANICAL
ROOM
● ● DIV. 23 ● ● DIV. 23 DIV. 23 3
1W-AHU22 SF 1W AIR HANDLER UNIT 22 - SUPPLY ARRAY (4) - 7.5 HP 27.73 ● 400 MECHANICAL
ROOM
● ● DIV. 23 ● ● DIV. 23 DIV. 23 3
1W-AHU23 RF 1W AIR HANDLER UNIT 23 - RETURN ARRAY (2) - 7 HP 13.72 ● 400 MECHANICAL
ROOM
● ● DIV. 23 ● ● DIV. 23 DIV. 23 3
1W-AHU23 SF 1W AIR HANDLER UNIT 23 - SUPPLY ARRAY (4) - 7.5 HP 27.69 ● 400 MECHANICAL
ROOM
● ● DIV. 23 ● ● DIV. 23 DIV. 23 3
1W-AHU-21 AIR HANDLER UNIT 21(RELOCATED) SUPPLY: (3) - 7.5 HP,
RETURN: (2) - 5 HP
45.73 ● EX/R EX/R DIV. 23 3
1W-EF1A 1W EXHAUST FAN 1A 1.5 HP 6.32 ● ● ● DIV. 26 ● 3R 30 NF ● DIV. 26 DIV. 23 3 12 12 0.75" 2
1W-EF1B 1W EXHAUST FAN 1B 1.5 HP 6.32 ● ● ● DIV. 26 ● 3R 30 NF ● DIV. 26 DIV. 23 3 12 12 0.75" 2
1W-EF2A 1W EXHAUST FAN 2A 20 HP 17.46 ● ● ● DIV. 26 ● 3R 60 NF DIV. 26 DIV. 23 3 6 10 1" 2
1W-EF2B 1W EXHAUST FAN 2B 20 HP 17.46 ● ● ● DIV. 26 ● 3R 60 NF DIV. 26 DIV. 23 3 6 10 1" 2
1W-EF3 1W EXHAUST FAN 3 .75 HP 1.83 ● ● DIV. 23 ● ● DIV. 23 DIV. 23 2 12 12 0.75"
1W-EF4 1W EXHAUST FAN 4 .75 HP 1.83 ● ● DIV. 23 ● ● DIV. 23 DIV. 23 2 12 12 0.75"
1W-EF5 1W EXHAUST FAN 5 .75 HP 1.83 ● ● DIV. 23 ● ● DIV. 23 DIV. 23 2 12 12 0.75"
1W-EF6 1W EXHAUST FAN 6 .75 HP 1.83 ● ● DIV. 23 ● ● DIV. 23 DIV. 23 2 12 12 0.75"
1W-EF7 1W EXHAUST FAN 7 0.5 HP 1.83 ● ● DIV. 23 ● ● DIV. 23 DIV. 23 2 12 12 0.75"
1W-EF8 1W EXHAUST FAN 8 2 HP 2.88 ● ● DIV. 23 ● ● DIV. 23 DIV. 23 2 10 10 0.75"
1W-EF9 1W EXHAUST FAN 9 1 HP 1.92 ● 401 ELECTRICAL
SHOP
● DIV. 23 ● ● DIV. 23 DIV. 23 2 10 10 0.75"
1W-EF10 1W EXHAUST FAN 10 .75 HP 1.92 ● 400 MECHANICAL
ROOM
● DIV. 23 ● ● DIV. 23 DIV. 23 2 10 10 0.75"
1W-P22 1W AHU-21 PREHEAT COIL RECIRC PUMP P-22 0.5 HP 1.18 ● 400 MECHANICAL
ROOM
0 ● ● DIV. 26 ● 1 30 NF ● DIV. 26 DIV. 23 2 12 12 0.75"
1W-P23 1W AHU-21 PREHEAT COIL RECIRC PUMP P-23 .75 HP 1.66 ● 400 MECHANICAL
ROOM
0 ● ● DIV. 26 ● 1 30 NF ● DIV. 26 DIV. 23 2 12 12 0.75"
UH-1 UNIT HEATER 1 0.12 ● 401 ELECTRICAL
SHOP
DIV. 23 ● ● DIV. 26 DIV. 23 2 12 12 0.75"
NOTES:
1. COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL DRAWINGS.
2. COORDINATE EXACT LENGTH WITH ARCHITECTURAL DRAWINGS.
LUMINAIRES
MARK Image
LAM
PS
L O
A D
V
A
F
IX
T U
R E
V O
L T
A G
E
MANUFACTURER CATALOG NO. DESCRIPTION
OTHER ACCEPTABLE
MANUFACTURERS DIFFUSING MEDIA
MOUNTING
S E
E N
O T
E
V A
L
IN
E
A R
F O
O T
S-SURFACE
R-RECESSED
SM-STEM MTD
WM-WALL MTD
C-CHAIN MTD
UC-UNDER CAB
CS-CEIL SURFACE
<varies
EXT1 10 277 LITHONIA WDGE1 LED P1 40K 80CRI VF MVOLT PE DS
DDBXD
ARCHITECTURAL WALL SCONCE APPROVED EQUAL S
F4a 24 277 LITHONIA LDN6-40/10-LO6AR-LSS-277-GZ10 6" DOWNLIGHT APPROVED EQUAL
F4a-WL 24 277 LITHONIA LDN6-40/10-LO6AR-LSS-277-GZ10 6" DOWNLIGHT WET LISTED APPROVED EQUAL
F4b 24 277 LITHONIA LDN6-40/10-LO6AR-LSS-277-GZ10 6" DOWNLIGHT APPROVED EQUAL
B1 37 277 LITHONIA 2RTL2-33L-GZ10-LP840 2X2 VOLUMETRIC LUMINAIRE APPROVED EQUAL R
B2a 29 277 LITHONIA 2RTL4-30L-GZ10-LP840 2X4 VOLUMETRIC LUMINAIRE - LOW OUTPUT APPROVED EQUAL R
B6b 3 <varies
277 FOCAL POINT FSM1-PD05-625LF-940K-1C-UNV-L11-XFF-WH-X LINEAR POP DOWN LENS - HIGH OUTPUT APPROVED EQUAL R
C1a 25 277 LITHONIA ZL1N L48 3000LM FST 277 40K 80CRI WH 4' STRIP LUMINAIRE APPROVED EQUAL C
C1b 34 277 LITHONIA ZL1N L48 5000LM FST 277 40K 80CRI WH 4' STRIP LUMINAIRE APPROVED EQUAL C
F1 11 277 LITHONIA LDN6-40/10-LO6AR-LSS-277-GZ10 6" DOWNLIGHT APPROVED EQUAL R 1
L2a 19 277 LITHONIA 2GTL2-20L-277-GZ10-LP840 2X2 LENSED TROFFER - LOW OUTPUT APPROVED EQUAL R
L2b 34 277 LITHONIA 2GTL2-40L-277-GZ10-LP840 2X2 LENSED TROFFER - HIGH OUTPUT APPROVED EQUAL R
NOTES:
1. COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL DRAWINGS.
2. COORDINATE EXACT LENGTH WITH ARCHITECTURAL DRAWINGS.
3. PROVIDE ALL REQUIRED ACCESSORIES FOR A COMPLETE, OPERATIONAL...
LUMINAIRES
MARK Image
LAM
PS
L O
A D
V
A
F
IX
T U
R E
V O
L T
A G
E
MANUFACTURER CATALOG NO. DESCRIPTION
OTHER ACCEPTABLE
MANUFACTURERS DIFFUSING MEDIA
MOUNTING
S E
E N
O T
E
V A
L
IN
E
A R
F O
O T
S-SURFACE
R-RECESSED
SM-STEM MTD
WM-WALL MTD
C-CHAIN MTD
UC-UNDER CAB
CS-CEIL SURFACE
L4a 23 277 LITHONIA 2GTL4-30L-277-GZ10-LP840 2X4 LENSED TROFFER - LOW OUTPUT APPROVED EQUAL R
L4b 36 277 LITHONIA 2GTL4-48L-277-GZ10-LP840 2X4 LENSED TROFFER - HIGH OUTPUT APPROVED EQUAL R
MF1 99 277 LITHONIA MAEC-48-F-38L/38L/6L-40K8-DIM1-277-HD-IB-XX PATIENT BED MULTI-FUNCTION LUMINAIRE APPROVED EQUAL R
NL 5 277 KENALL MCSL-VR-MW-2L40K-DV PATIENT ROOM NIGHT LIGHT APPROVED EQUAL WM
P3 10 277 SEED LIGHTING SLD-1010PC12-SHINY BRASS DECORATIVE PENDANT APPROVED EQUAL SM
UC1 8 120 AIREY THOMPSON 13HC-N-40K-12-2-3-AMS UNDER CABINET LIGHT APPROVED EQUAL UC
UC2 11 120 AIREY THOMPSON 13HC-N-40K-24-2-3-AMS UNDER CABINET LIGHT APPROVED EQUAL UC
UC3 11 120 AIREY THOMPSON 13HC-N-40K-36-2-3-AMS UNDER CABINET LIGHT APPROVED EQUAL UC
V1 17 277 LITHONIA FMVCSLS-24IN-MVOLT-30K35K40K-90CRI-BN 2' VANITY APPROVED EQUAL WM
X1 2 277 LITHONIA EDGR 1 RMR SINGLE FACE EXIT SIGN APPROVED EQUAL
X2 2 277 LITHONIA EDGR 2 RMR DOUBLE FACE EXIT SIGN APPROVED EQUAL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:3
:2
P M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
PANEL SCHEDULES
E502
JSFKMU
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
2.59 kVA 2.59 kVA (7 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: $ = NPROVIDE GROUND FAULT BREAKER.
Total Est. Demand: 7 A
Total Conn.: 7 A
Total Est. Demand: 2590 VA
Total Conn. Load: 2590 VA
Receptacle 2590 VA 100.00% 2590 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 0.72 kVA 1.51 kVA 0.36 kVA
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40
37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38
35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36
33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34
31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32
29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30
27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28
25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26
23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24
21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22
19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20
17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18
15 DISPOSER 20 A 1 1150... 0 VA 1 20 A Spare 16
13 Space -- 1 -- -- 1 -- Space 14
11 Space -- 1 -- -- 1 -- Space 12
9 Space -- 1 -- -- 1 -- Space 10
7 $ HOOD CONTROLS 20 A 1 360 VA -- 1 -- Space 8
5 $ HOOD CONTROLS 20 A 1 360 VA -- 1 -- Space 6
3 $ HOOD CONTROLS 20 A 1 360 VA -- 1 -- Space 4
1 $ HOOD CONTROLS 20 A 1 360 VA -- 1 -- Space 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB
Location: ELEC A311 Mounting: Surface A.I.C. Rating:
Panel: R3A-2
49.7 kVA 29.85 kVA (83 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: $ = PROVIDE GROUND FAULT BREAKER.
Total Est. Demand: 83 A
Total Conn.: 138 A
Total Est. Demand: 29850 VA
Total Conn. Load: 49700 VA
Receptacle 49700 VA 60.06% 29850 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 15.44 kVA 17.04 kVA 17.22 kVA
41 -- -- -- 1800... 180 VA 1 20 A Receptacle 42
39 $ COOKTOP 20 A 2 1800... 180 VA 1 20 A Receptacle 40
37 -- -- -- 1800... 180 VA 1 20 A Receptacle 38
35 $ COOKTOP 20 A 2 1800... 180 VA 1 20 A Receptacle HEALTHY... 36
33 -- -- -- 1800... 180 VA 1 20 A Receptacle HEALTHY... 34
31 $ COOKTOP 20 A 2 1800... 180 VA 1 20 A Receptacle HEALTHY... 32
29 -- -- -- 1800... 1600... -- -- -- 30
27 $ COOKTOP 20 A 2 1800... 1600... 2 20 A $ OVEN 28
25 -- -- -- 1800... 1600... -- -- -- 26
23 $ COOKTOP 20 A 2 1800... 1600... 2 20 A $ OVEN 24
21 -- -- -- 1800... 1600... -- -- -- 22
19 $ COOKTOP 20 A 2 1800... 1600... 2 20 A $ OVEN 20
17 -- -- -- 1800... 1600... -- -- -- 18
15 $ COOKTOP 20 A 2 1800... 1600... 2 20 A $ OVEN 16
13 -- -- -- 1800... 180 VA 1 20 A Receptacle OPEN... 14
11 $ COOKTOP 20 A 2 1800... 900 VA 1 20 A Receptacle OPEN... 12
9 -- -- -- 1800... 720 VA 1 20 A Receptacle OPEN... 10
7 $ COOKTOP 20 A 2 1800... 180 VA 1 20 A Receptacle OPEN... 8
5 Receptacle OPEN... 20 A 1 180 VA 180 VA 1 20 A Receptacle OPEN... 6
3 Receptacle OPEN... 20 A 1 180 VA 180 VA 1 20 A Receptacle OPEN... 4
1 Receptacle 20 A 1 540 VA 180 VA 1 20 A Receptacle Room C3-A 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB
Location: ELEC A373 Mounting: Surface A.I.C. Rating:
Panel: R3C-2 (EXISTING)(EXISTING)
27.72 kVA 18.86 kVA (52 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Est. Demand: 52 A
Total Conn.: 77 A
Total Est. Demand: 18860 VA
Total Conn. Load: 27720 VA
Receptacle 27720 VA 68.04% 18860 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 9.90 kVA 9.72 kVA 8.10 kVA
41 Receptacle 1BR... 20 A 1 900 VA 0 VA 1 20 A Spare 42
39 Receptacle 1BR... 20 A 1 1080... 0 VA 1 20 A Spare 40
37 Receptacle 1BR... 20 A 1 1080... 180 VA 1 20 A Receptacle 38
35 Receptacle 1BR... 20 A 1 900 VA 900 VA 1 20 A Receptacle 1BR... 36
33 Receptacle 1BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 34
31 Receptacle 1BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 32
29 Receptacle 1BR... 20 A 1 900 VA 900 VA 1 20 A Receptacle 1BR... 30
27 Receptacle 1BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 28
25 Receptacle 1BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 26
23 Receptacle 20 A 1 900 VA 900 VA 1 20 A Receptacle 1BR... 24
21 Receptacle 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 22
19 Receptacle 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 20
17 Receptacle 1 BR... 20 A 1 900 VA 900 VA 1 20 A Receptacle 18
15 Receptacle 1 BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1 BR... 16
13 Receptacle 1 BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1 BR... 14
11 Space -- 1 -- -- 1 -- Space 12
9 Space -- 1 -- -- 1 -- Space 10
7 Space -- 1 -- -- 1 -- Space 8
5 Space -- 1 -- -- 1 -- Space 6
3 Space -- 1 -- -- 1 -- Space 4
1 Space -- 1 -- -- 1 -- Space 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB
Location: ELEC A578 Mounting: Surface A.I.C. Rating:
Panel: R5C-2 (EXISTING)
34.16 kVA 22.08 kVA (61 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: $ = PROVIDE GROUND FAULT BREAKER.
Total Est. Demand: 61 A
Total Conn.: 95 A
Total Est. Demand: 22080 VA
Total Conn. Load: 34160 VA
Receptacle 34160 VA 64.64% 22080 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 11.40 kVA 10.72 kVA 12.04 kVA
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40
37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38
35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36
33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34
31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32
29 Spare 20 A 1 0 VA 1000... 1 20 A BLANKET WARMER 30
27 Receptacle ALCOVE... 20 A 1 180 VA 1000... 1 20 A BLANKET WARMER 28
25 Receptacle NUTRITIO... 20 A 1 1500... 26
23 $ Receptacle 1BR... 20 A 1 1440... 1440... 1 20 A $ Receptacle 1BR... 24
21 Receptacle 1BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 22
19 Receptacle 1BR... 20 A 1 1260... 1260... 1 20 A Receptacle 1BR... 20
17 $ Receptacle 1BR... 20 A 1 1440... 1440... 1 20 A $ Receptacle 1BR... 18
15 Receptacle 1BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 16
13 Receptacle 1BR... 20 A 1 1260... 1260... 1 20 A Receptacle 1BR... 14
11 $ Receptacle 1BR... 20 A 1 1440... 1440... 1 20 A $ Receptacle 1BR... 12
9 Receptacle 1BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 10
7 Receptacle 1BR... 20 A 1 1260... 1260... 1 20 A Receptacle 1BR... 8
5 Receptacle MED ROO... 20 A 1 1500... 900 VA 1 20 A Receptacle MED ROO... 6
3 Receptacle CLEAN... 20 A 1 1800... 1260... 1 20 A Receptacle NURSE... 4
1 $ Receptacle 2BR A513 20 A 1 1440... 900 VA 1 20 A $ Rec NURSE STATIO... 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB
Location: ELEC A578 Mounting: Surface A.I.C. Rating:
Panel: CR5C-2 (NEW)
15.84 kVA 12.92 kVA (36 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: $ = PROVIDE GROUND FAULT BREAKER.
Total Est. Demand: 36 A
Total Conn.: 44 A
Total Est. Demand: 12920 VA
Total Conn. Load: 15840 VA
Receptacle 15840 VA 81.57% 12920 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 5.22 kVA 5.04 kVA 5.58 kVA
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40
37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38
35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36
33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34
31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32
29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30
27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28
25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26
23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24
21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22
19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20
17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18
15 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 16
13 AAP 20 A 1 360 VA 180 VA 1 20 A P-TUBE STATION 14
11 $ Receptacle 20 A 1 1440... 1260... 1 20 A Receptacle NURSE... 12
9 Receptacle 20 A 1 1080... 1800... 1 20 A Receptacle 10
7 Receptacle 20 A 1 1260... 900 VA 1 20 A Receptacle 8
5 $ Receptacle 1 BR... 20 A 1 1440... 1440... 1 20 A $ Receptacle 6
3 Receptacle 1 BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1 BR... 4
1 Receptacle 1 BR... 20 A 1 1260... 1260... 1 20 A Receptacle 1 BR... 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB
Location: ELEC B520 Mounting: Surface A.I.C. Rating: 35KA
Panel: CR5B-2 (NEW)
35.17 kVA 27.74 kVA (77 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: $ = PROVIDE GROUND FAULT BREAKER.
Total Est. Demand: 77 A
Total Conn.: 98 A
Receptacle 25860 VA 69.33% 17930 VA Total Est. Demand: 27742 VA
Motor 9152 VA 105.00% 9610 VA Total Conn. Load: 35174 VA
Lighting 162 VA 125.00% 203 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 12.24 kVA 10.28 kVA 12.65 kVA
41 Receptacle HEALTHY... 20 A 1 180 VA 1080... 1 20 A Receptacle 42
39 Receptacle 20 A 1 180 VA 540 VA 1 20 A Receptacle 40
37 Receptacle ALCOVE... 20 A 1 360 VA 720 VA 1 20 A Receptacle NURSE... 38
35 REC 20 A 1 540 VA 900 VA 1 20 A Receptacle Room 526 36
33 Receptacle Room... 20 A 1 900 VA 900 VA 1 20 A Receptacle Room 518,... 34
31 Receptacle NURSE... 20 A 1 720 VA 1500... 1 20 A Receptacle MED ROO... 32
29 Receptacle NURSE... 20 A 1 720 VA 1124... 1 20 A Receptacle MED ROO... 30
27 Receptacle Room... 20 A 1 540 VA 720 VA 1 20 A Receptacle Room 522,... 28
25 Receptacle 20 A 1 1500... 900 VA 1 20 A Receptacle NURSE... 26
23 Receptacle Room 522,... 20 A 1 775 VA 1800... 1 20 A Receptacle CLEAN... 24
21 Receptacle NURSE... 20 A 1 720 VA 783 VA 1 20 A Receptacle Room 510,... 22
19 Receptacle Room... 20 A 1 540 VA 900 VA 1 20 A Receptacle Room... 20
17 Receptacle... 20 A 1 810 VA 1080... 1 20 A Receptacle Room... 18
15 Receptacle 2BR A513 20 A 1 720 VA 810 VA 1 20 A Receptacle EQUIPMEN... 16
13 Receptacle Room 503 20 A 1 900 VA 540 VA 1 20 A Receptacle 2BR A513 14
11 -- -- -- 915 VA 900 VA 1 20 A Receptacle 12
9 1W-EF7 20 A 2 915 VA 720 VA 1 20 A Receptacle OFFICE 503 10
7 -- -- -- 915 VA 915 VA -- -- -- 8
5 1W-EF5 20 A 2 915 VA 915 VA 2 20 A 1W-EF6 6
3 -- -- -- 915 VA 915 VA -- -- -- 4
1 1W-EF3 20 A 2 915 VA 915 VA 2 20 A 1W-EF4 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB
Location: ELEC B520 Mounting: Surface A.I.C. Rating: 35KA
Panel: RB5-3 (NEW)
0 kVA 0 kVA (0 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Est. Demand: 0 A
Total Conn.: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 0.00 kVA 0.00 kVA 0.00 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 150 A Supply From: T-4EPP2 Enclosure: Type 1 Mains Type: 150 A MB
Location: MECHANICAL ROOM 400 Mounting: Surface A.I.C. Rating: 35KA
Panel: 4EPP2(NEW) (NEW)
28.75 kVA 24.95 kVA (69 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Est. Demand: 69 A
Total Conn.: 80 A
Receptacle 19040 VA 76.26% 14520 VA Total Est. Demand: 24953 VA
Motor 9672 VA 107.44% 10392 VA Total Conn. Load: 28745 VA
Lighting 33 VA 125.00% 41 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 9.27 kVA 9.69 kVA 9.79 kVA
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40
37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38
35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36
33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34
31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32
29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30
27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28
25 Spare 20 A 1 0 VA 2667... -- -- -- 26
23 Spare 20 A 1 0 VA 2667... -- -- -- 24
21 2667... 3 30 A TEST TABLE 22
19 1920... 1 20 A Motor MECHANICAL... 20
17 Receptacle... 20 A 1 540 VA 1176... 1 20 A Motor MECHANICAL... 18
15 Receptacle... 20 A 1 540 VA 2880... 1 50 A 1W-EF8 16
13 Receptacle... 20 A 1 360 VA 14
11 Motor ELECTRICAL... 20 A 1 1920... 1656... 1 20 A 1W-P23 12
9 Receptacle... 20 A 1 900 VA 120 VA 1 20 A Motor ELECTRICAL... 10
7 Receptacle... 20 A 1 1080... 1080... 1 20 A Receptacle ELECTRIC... 8
5 Receptacle... 20 A 1 933 VA 900 VA 1 20 A Receptacle OFFICE... 6
3 Receptacle... 20 A 1 1080... 1500... 1 20 A Receptacle ELECTRIC... 4
1 Receptacle... 20 A 1 1080... 1080... 1 20 A Receptacle ELECTRIC... 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 150 A Supply From: T-4PP2 Enclosure: Type 1 Mains Type: 150 A MB
Location: MECHANICAL ROOM 400 Mounting: Surface A.I.C. Rating: 35KA
Panel: 4PP2
33.67 kVA 21.91 kVA (61 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: $ = PROVIDE GROUND FAULT BREAKER.
Total Est. Demand: 61 A
Total Conn.: 93 A
Total Est. Demand: 21914 VA
Receptacle 33560 VA 64.90% 21780 VA Total Conn. Load: 33667 VA
Lighting 107 VA 125.00% 134 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 10.16 kVA 11.96 kVA 11.55 kVA
41 Receptacle Room 307-1 20 A 1 750 VA 1500... 1 20 A Receptacle 42
39 Receptacle 20 A 1 1500... 977 VA 1 20 A Receptacle HEALTHY... 40
37 $ DISHWASHER 20 A 1 1500... 1500... 1 20 A Receptacle 38
35 $ DISHWASHER 20 A 1 1500... 1500... 1 20 A Receptacle 36
33 Receptacle HEALTHY... 20 A 1 1500... 1500... 1 20 A $ DISHWASHER 34
31 Receptacle OPEN... 20 A 1 540 VA 360 VA 1 20 A Receptacle OPEN... 32
29 Receptacle 20 A 1 1500... 540 VA 1 20 A Receptacle SPACE 300 30
27 $ MICROWAVE 20 A 1 1500... 1500... 1 20 A Receptacle 28
25 Receptacle HEALTHY... 20 A 1 1500... 1500... 1 20 A Receptacle HEALTHY... 26
23 Receptacle HEALTHY... 20 A 1 180 VA 1500... 1 20 A Receptacle HEALTHY... 24
21 Receptacle Room 307 20 A 1 720 VA 1500... 1 20 A $ MICROWAVE 22
19 Receptacle Room 307A 20 A 1 860 VA 1500... 1 20 A $ REFRIGERATOR 20
17 Receptacle SPACE 314 20 A 1 1080... 1500... 1 20 A $ DISHWASHER 18
15 Receptacle CHAPEL... 20 A 1 720 VA 540 VA 1 20 A Receptacle CHAPEL 308 16
13 Receptacle 20 A 1 900 VA 0 VA 1 20 A EXISTING 14
11 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 12
9 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 10
7 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 8
5 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 6
3 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 4
1 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB
Location: ELEC A373 Mounting: Surface A.I.C. Rating:
Panel: R3C-1 (EXISTING)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
Project Schedule Date
Schematic Design 15% 02.16.2021
Schematic Design 35% 04.16.2021
Design Development 65% 09.24.2021
Construction Documents 95% 10.26.2023
Bid Documents 100% 12.15.2023
Design Development 65% (Re-submittal) 11.15.2021
/1 /2
:3
:2
P M
Construct Private In-Patient Rooms & Primary Clinics
12.15.2023
PANEL SCHEDULES
E503
JSFKMU
506-334
Ann Arbor, Michigan (506)
B01W
JEFF MEANS
BID DOCUMENTS 100%
20014.00
1.03 kVA 1.29 kVA (2 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Est. Demand: 2 A
Total Conn.: 1 A
Total Est. Demand: 1293 VA
Total Conn. Load: 1034 VA
Lighting 1034 VA 125.00% 1293 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 0.00 kVA 0.00 kVA 1.03 kVA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Space -- 1 -- -- 1 -- Space 36
33 Space -- 1 -- -- 1 -- Space 34
31 Space -- 1 -- -- 1 -- Space 32
29 Space -- 1 -- -- 1 -- Space 30
27 Space -- 1 -- -- 1 -- Space 28
25 Space -- 1 -- -- 1 -- Space 26
23 Space -- 1 -- -- 1 -- Space 24
21 Space -- 1 -- -- 1 -- Space 22
19 Spare 20 A 1 0 VA -- 1 -- Space 20
17 Spare 20 A 1 0 VA -- 1 -- Space 18
15 Spare 20 A 1 0 VA -- 1 -- Space 16
13 Spare 20 A 1 0 VA -- 1 -- Space 14
11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12
9 EXISTING 20 A 1 0 VA 0 VA 1 20 A Spare 10
7 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 8
5 Lighting Room 307A,... 20 A 1 1034... 0 VA 1 20 A EXISTING 6
3 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 4
1 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 480/277 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB
Location: ELEC A373 Mounting: Surface A.I.C. Rating:
Panel: L3C-1
0 kVA 0 kVA (0 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Est. Demand: 0 A
Total Conn.: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 0.00 kVA 0.00 kVA 0.00 kVA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Space -- 1 -- -- 1 -- Space 36
33 Space -- 1 -- -- 1 -- Space 34
31 Space -- 1 -- -- 1 -- Space 32
29 Space -- 1 -- -- 1 -- Space 30
27 Space -- 1 -- -- 1 -- Space 28
25 Space -- 1 -- -- 1 -- Space 26
23 Space -- 1 -- -- 1 -- Space 24
21 Space -- 1 -- -- 1 -- Space 22
19 Space -- 1 -- -- 1 -- Space 20
17 Space -- 1 -- -- 1 -- Space 18
15 Space -- 1 -- -- 1 -- Space 16
13 Space -- 1 -- -- 1 -- Space 14
11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12
9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10
7 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 8
5 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 6
3 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 4
1 EXISTING 20 A 1 0 VA 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 480/277 Wye-3PH-4W Mains Rating: 100 A Supply From: Enclosure: Type 1 Mains Type: MLO
Location: ELECTRICAL A474 Mounting: Surface A.I.C. Rating: EXISTING
Panel: LS4C-1
2.83 kVA 3.53 kVA (4 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Est. Demand: 4 A
Total Conn.: 3 A
Total Est. Demand: 3532 VA
Other 0 VA 0.00% 0 VA Total Conn. Load: 2826 VA
Lighting 2826 VA 125.00% 3532 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 1.87 kVA 0.96 kVA 0.00 kVA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Space -- 1 -- -- 1 -- Space 36
33 Space -- 1 -- -- 1 -- Space 34
31 Space -- 1 -- -- 1 -- Space 32
29 Space -- 1 -- -- 1 -- Space 30
27 Space -- 1 -- -- 1 -- Space 28
25 Space -- 1 -- -- 1 -- Space 26
23 Space -- 1 -- -- 1 -- Space 24
21 Space -- 1 -- -- 1 -- Space 22
19 Space -- 1 -- -- 1 -- Space 20
17 Spare 20 A 1 0 VA -- 1 -- Space 18
15 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 16
13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14
11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12
9 Lighting Room 507, 50... 20 A 1 960 VA 0 VA 1 20 A Spare 10
7 Lighting Room 526,... 20 A 1 1194... 672 VA 1 20 A Room 519, 524, 523, 525 8
5 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 6
3 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 4
1 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 480/277 Wye-3PH-4W Mains Rating: 250 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB
Location: ELEC A578 Mounting: Surface A.I.C. Rating:
Panel: L5C-1
0 kVA 0 kVA (0 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Est. Demand: 0 A
Total Conn.: 0 A
Total Est. Demand: 0 VA
Total Conn. Load: 0 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 0.00 kVA 0.00 kVA 0.00 kVA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Space -- 1 -- -- 1 -- Space 36
33 Space -- 1 -- -- 1 -- Space 34
31 Space -- 1 -- -- 1 -- Space 32
29 Space -- 1 -- -- 1 -- Space 30
27 Space -- 1 -- -- 1 -- Space 28
25 Space -- 1 -- -- 1 -- Space 26
23 Space -- 1 -- -- 1 -- Space 24
21 Space -- 1 -- -- 1 -- Space 22
19 Space -- 1 -- -- 1 -- Space 20
17 Space -- 1 -- -- 1 -- Space 18
15 Space -- 1 -- -- 1 -- Space 16
13 Space -- 1 -- -- 1 -- Space 14
11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12
9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10
7 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 8
5 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 6
3 EXISTING 20 A 1 0 VA 0 VA 1 20 A Spare 4
1 EXISTING 20 A 1 0 VA 0 VA 1 20 A Spare 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 480/277 Wye-3PH-4W Mains Rating: 250 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB
Location: ELEC B520 Mounting: Surface A.I.C. Rating:
Panel: LS5B-1
0.31 kVA 0.39 kVA (0 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Est. Demand: 0 A
Total Conn.: 0 A
Total Est. Demand: 385 VA
Total Conn. Load: 308 VA
Lighting 308 VA 125.00% 385 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 0.00 kVA 0.00 kVA 0.31 kVA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Space -- 1 -- -- 1 -- Space 36
33 Space -- 1 -- -- 1 -- Space 34
31 Space -- 1 -- -- 1 -- Space 32
29 Space -- 1 -- -- 1 -- Space 30
27 Space -- 1 -- -- 1 -- Space 28
25 Space -- 1 -- -- 1 -- Space 26
23 Space -- 1 -- -- 1 -- Space 24
21 Space -- 1 -- -- 1 -- Space 22
19 Space -- 1 -- -- 1 -- Space 20
17 Space -- 1 -- -- 1 -- Space 18
15 Space -- 1 -- -- 1 -- Space 16
13 Space -- 1 -- -- 1 -- Space 14
11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12
9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10
7 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 8
5 Spare 20 A 1 0 VA 308 VA 1 20 A Lighting Room C5-50,... 6
3 Spare 20 A 1 0 VA 0 VA 1 20 A EXISITNG 4
1 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 480/277 Wye-3PH-4W Mains Rating: 250 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB
Location: ELEC A578 Mounting: Surface A.I.C. Rating:
Panel: LS5C-1
1.5 kVA 1.5 kVA (4 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: $ = PROVIDE GROUND FAULT BREAKER.
Total Est. Demand: 4 A
Total Conn.: 4 A
Total Est. Demand: 1500 VA
Total Conn. Load: 1500 VA
Receptacle 1500 VA 100.00% 1500 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 1.50 kVA 0.00 kVA 0.00 kVA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 EXISTING 20 A 1 0 VA -- 1 -- Space 38
35 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 36
33 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 34
31 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 32
29 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 30
27 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 28
25 $ MICROWAVE 20 A 1 1500... 0 VA 1 20 A EXISTING 26
23 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 24
21 Space -- 1 -- 0 VA 1 20 A EXISTING 22
19 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 20
17 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 18
15 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 16
13 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 14
11 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 12
9 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 10
7 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 8
5 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 6
3 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 4
1 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 100 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB
Location: ELEC B520 Mounting: Surface A.I.C. Rating:
Panel: RB5-1
Revisions Date
3.38 kVA 4.22 kVA (5 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Est. Demand: 5 A
Total Conn.: 4 A
Total Est. Demand: 4224 VA
Total Conn. Load: 3380 VA
Lighting 3380 VA 125.00% 4224 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 1.28 kVA 1.05 kVA 1.04 kVA
41 Space -- 1 -- -- 1 -- Space 42
39 Space -- 1 -- -- 1 -- Space 40
37 Space -- 1 -- -- 1 -- Space 38
35 Space -- 1 -- -- 1 -- Space 36
33 Space -- 1 -- -- 1 -- Space 34
31 Space -- 1 -- -- 1 -- Space 32
29 Space -- 1 -- -- 1 -- Space 30
27 Space -- 1 -- -- 1 -- Space 28
25 Space -- 1 -- -- 1 -- Space 26
23 Space -- 1 -- -- 1 -- Space 24
21 Space -- 1 -- -- 1 -- Space 22
19 Space -- 1 -- -- 1 -- Space 20
17 Space -- 1 -- -- 1 -- Space 18
15 Space -- 1 -- -- 1 -- Space 16
13 Space -- 1 -- -- 1 -- Space 14
11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12
9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10
7 Lighting Room 505,... 20 A 1 1284... 0 VA 1 20 A Spare 8
5 Lighting Room 526, 51... 20 A 1 1044... 0 VA 1 20 A Spare 6
3 EXISTING 20 A 1 0 VA 1052... 1 20 A Lighting Room 523, 52... 4
1 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 480/277 Wye-3PH-4W Mains Rating: 250 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB
Location: ELEC A578 Mounting: Surface A.I.C. Rating:
Panel: CL5C-1
2.59 kVA 2.59 kVA (7 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: $ = NPROVIDE GROUND FAULT BREAKER.
Total Est. Demand: 7 A
Total Conn.: 7 A
Total Est. Demand: 2590 VA
Total Conn. Load: 2590 VA
Receptacle 2590 VA 100.00% 2590 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total Load: 0.72 kVA 1.51 kVA 0.36 kVA
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40
37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38
35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36
33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34
31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32
29 Spare…