Attachment 05 - Drawings - Electrical.pdf

PDF 11 MB Posted

Attached to
506-334 – Construct Private In-Patient Rooms and Primary Clinics
Solicitation number
36C25024B0031_1
Issued by

About this file

This document appears to be Attachment 05 - Drawings - Electrical related to the federal contract opportunity 506-334 – Construct Private In-Patient Rooms and Primary Clinics in Ann Arbor, MI. The solicitation, issued by the Department of Veterans Affairs Technology Acquisition Center Austin, calls for the construction of private in-patient rooms and primary clinics. The attachment provides detailed electrical drawings and specifications required for this construction project. No further details about the overall scope of work, pricing, or response requirements are included in this attachment.

View the file

Other files

File Type Posted
Attachment 14 - Wage Determination Rev 6 - Washtenaw County - 7-26-24.pdf PDF
506-334 Solicitation Amendment 005 - 36C25024B0031 0005.docx DOCX document
Plumbing Drawings - Write Up.pdf PDF
506-334 Solicitation Amendment 004 36C25024B0031 0004.docx DOCX document
Round 2 Technical Questions - Ann Arbor - 506-334 - FINAL - 7-22-24.pdf PDF
Amended Drawings - 7-22-24.pdf PDF
506-334 Solicitation Amendment 003 - 36C25024B0031 0003.docx DOCX document
506-334 Solicitation Amendment 0002 -36C25024B0031 0002.docx DOCX document
5 West hallway renovation 506-334-100.pdf PDF
New building 5th floor ICRA 506-334-100.pdf PDF
New building west side 3rd floor ICRA 506-334-100.pdf PDF
221300 Sanitary and Vent.pdf PDF
New building west side 4th floor 506-334-100.pdf PDF
Amended Drawings.pdf PDF
Technical Questions - Ann Arbor - 506-334 - FINAL - 7-16-24.pdf PDF
506-334 - Solicitation Amendment 0001 - 36C25024B0031_1 0001.docx DOCX document
506-334 Construct Private In-Patient Beds - sign in sheet 20240701.pdf PDF
Attachment 08 - Drawings - Mechanical.pdf PDF
Attachment 10 - Drawings - Structural.pdf PDF
Attachment 11 - Drawings - Telecommunications.pdf PDF
Attachment 02 - Specifications Vol 2.pdf PDF
Attachment 14 - Wage Determination - Washtenaw County - 4-5-24.pdf PDF
S02 - 36C25024B0031_1.docx DOCX document
Attachment 06 - Drawings - Fire Protection.pdf PDF
Attachment 13 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 01 - Specifications Vol 1.pdf PDF
Attachment 12 - Brand Name JA - Ann Arbor - 506-334 - FINAL.pdf PDF
Attachment 09 - Drawings - Plumbing.pdf PDF
Attachment 04 - Drawings - Architectural - Vol 2.pdf PDF
Attachment 15 - Site Visit Instructions - Ann Arbor.docx DOCX document
Attachment 03 - Drawings - Architectural - Vol 1.pdf PDF
Attachment 07 - Drawings - General - Civil.pdf PDF
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL SYMBOLS

EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.

DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS WHERE

REQUIRED.

ELECTRICAL CONNECTION.

20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE).

SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.

20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERWISE) TWO GANG ASSEMBLY.

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED

OTHERWISE).

20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERWISE) WITH

EXTRA DUTY COVER, VERTICAL MOUNT.

20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH

UNLESS NOTED OTHERWISE), WITH EXTRA DUTY COVER, VERTICAL MOUNT.

JUNCTION BOX. SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POWER.

MULTI-OUTLET RECEPTACLES ASSEMBLY, NEMA 5-15R (SINGLE OUTLETS ON 18" CENTERS) (46" MH UNLESS NOTED

OTHERWISE).

SINGLE POLE SWITCH (46" MH UNLESS NOTED OTHERWISE).

TWO POLE WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).

MULTI-WAY WALL SWITCH, # INDICATES NUMBER OF WAYS (46" MH UNLESS NOTED OTHERWISE).

LIGHTING DIMMER SWITCH (46" MH UNLESS NOTED OTHERWISE).

DISCONNECT SWITCH.

MOTOR STARTER.

COMBINATION MOTOR STARTER AND DISCONNECT SWITCH.

ELECTRIC MOTOR.

ELECTRICAL PANEL OR SWITCHBOARD PER DRAWINGS.

PULL BOX.

CORD REEL.

POWER POLE.

CEILING MOUNTED OCCUPANCY SENSOR.

WALL MOUNTED OCCUPANCY SENSOR.

CEILING MOUNTED DAYLIGHT SENSOR.

OCCUPANCY SENSOR POWER PACK.

GF

WP

WP/GF

J

D

PP

OS

OS

M

DS

OP

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (46" MH UNLESS NOTED OTHERWISE).

CR

P/B

LOW-VOLTAGE MOMENTARY WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).L

ABBREVIATIONS

AAP - AREA ALARM PANEL - MEDICAL GAS

ACC - ACCESS

ADJ - ADJUSTABLE

AF - ARC FAULT CIRCUIT INTERRUPTER

AFCI - ARC FAULT CIRCUIT INTERRUPTER

AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM

AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

ATS - AUTOMATIC TRANSFER SWITCH

BLDG - BUILDING

BOE - BOTTOM OF EQUIPMENT

BOT - BOTTOM

BTWN - BETWEEN

BW - BLANKET WARMER

CC - CART CHARGING

CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CKT - CIRCUIT

CLG - CEILING

CM - COFFEE MAKER

CMU - CONCRETE MASONRY UNIT

CO - COPIER

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

CORR - CORRIDOR

CTR - CENTER

D - DEPTH

DET - DETAIL

DIA - DIAMETER

DIM - DIMENSION

DIV - DIVISION

DN - DOWN

DW - DISHWASHER

DWG - DRAWING

EA - EACH

EC - ELECTRICAL (DIVISION 26)

ECM - ELECTRONICALLY COMMUTATED MOTOR

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATION OR ELEVATOR

EM - EMERGENCY

EQ - EQUAL

EQS - EQUIPMENT SUPPLIER

EQUIP - EQUIPMENT

ETR - EXISTING TO REMAIN

EX - EXISTING

EXP - EXPANSION

EXT - EXTERIOR

FCE - FIRE CONTROL EQUIPMENT

FF - FINISHED FLOOR ELEVATION

FLR - FLOOR

FSC - FIRE SUPPRESSION (DIVISION 21)

FT - FEET

FTG - FOOTING

GC - GENERAL TRADES (DIVISION 01)

GF - GROUND FAULT CIRCUIT INTERRUPTER

GFB - GROUND FAULT BREAKER

GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT

FURNISHED CONTRACTOR INSTALLED

GFFT - GROUND FAULT FEED THRU

HC - HVAC (DIVISION 23)

HP - HORSE POWER OR HIGH POINT

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

ICE - ICE MACHINE

ID - INSIDE DIAMETER

IN - INCHES

KEC - KITCHEN EQUIPMENT

L - LENGTH

LBS - POUNDS

MAP - MASTER ALARM PANEL (MEDICAL GAS)

MAX - MAXIMUM

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM

MIN - MINIMUM OR MINUTE

MISC - MISCELLANEOUS

MON - MONITOR

MTD - MOUNTED

MTG - MOUNTING

MW - MICROWAVE

NIC - NOT IN CONTRACT

NOM - NOMINAL

NTS - NOT TO SCALE

OC - OMNI-CELL

OD - OUTSIDE DIAMETER

OFCI - OWNER FURNISHED CONTRACTOR INSTALLED

OFOI - OWNER FURNISHED OWNER INSTALLED

PC - PLUMBING (DIVISION 22)

PLBG - PLUMBING

PR - PRINTER

RAD - RADIUS

REC - RECESSED

RF - REFRIGERATOR

REQD - REQUIRED

RI - ROUGH-IN

S - SURFACE MOUNTED

SC - SECURITY (DIVISION 28)

SCH - SCHEDULE

SHT - SHEET

SMS - SECURITY MANAGEMENT SYSTEM

SPEC - SPECIFICATIONS

SQ - SQUARE

SS - STAINLESS STEEL

STD - STANDARD

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY CONTRACTOR

TC - TECHNOLOGY (DIVISION 27)

TEMP - TEMPERATURE

TOE - TOP OF EQUIPMENT

TV - TELEVISION

TYP - TYPICAL

UCR - UNDER COUNTER REFRIGERATOR

UNO - UNLESS NOTED OTHERWISE

VEND - VENDING MACHINE

VFD - VARIABLE FREQUENCY DRIVE

VOL - VOLUME

W/ - WITH

W/O - WITHOUT

WP - WEATHERPROOF

ZVC - ZONE VALVE CABINET

LUMINAIRE SYMBOLS

LIGHTING FIXTURE. CAPITAL LETTER DENOTES FIXTURE TYPE, LOWER CASE LETTER DENOTES

SWITCHING ARRANGEMENT.

LIGHTING FIXTURE ON NIGHT LIGHT OR LIFE SAFETY CIRCUIT.

EXIT LIGHTING FIXTURE, ARROWS AS INDICATED.

A a

WIREMOLD RACEWAY, AS NOTED ON PLANS.

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH 2 INTEGRAL USB CHARGERS (18" MH UNLESS NOTED OTHERWISE).

NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT

TO MODIFICATIONS ON OTHER DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT

NECESSARILY BE USED ON THIS PROJECT.

LIGHTING FIXTURE ON CRITICAL CIRCUIT.

SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POWER. SPECIFICATION IS SAME AS RESPECTIVE ROUND DEVICE.

J

KF

S

D

V

R W

SD

PS

AM

C/I

PIV

H

S S/R

S/R

FACP

FIRE ALARM SYMBOLS

FIRE ALARM CONTROL PANEL.

CEILING MOUNTED FIRE ALARM SPEAKER & SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE.

WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER

LOCATIONS.

FIRE ALARM MANUAL STATION (46" MH UNLESS NOTED OTHERWISE). SUBSCRIPT "K" INDICATES KEY OPERATED.

CEILING MOUNTED SMOKE DETECTOR.

DUCT MOUNTED SMOKE DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.

DUCT MOUNTED HEAT DETECTOR. SUBSCRIPT "S" INDICATES SUPPLY. SUBSCRIPT "R" INDICATES RETURN.

ELECTRO-MAGNETIC DOOR HOLDER.

VALVE SUPERVISORY SWITCH.

CEILING MOUNTED REMOTE TEST STATION AND ALARM INDICATOR LIGHT FOR DUCT DETECTOR. SUBSCRIPT "W" INDICATES

WALL MOUNTED.

SMOKE DAMPER.

PRESSURE SWITCH.

ADDRESSABLE MODULE. SUBSCRIPT "I" INDICATES INPUT. SUBSCRIPT "C" INDICATES CONTROL.

POST INDICATOR VALVE.

REMOTE ANNUNCIATOR PANEL.

NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANEL.

RAP

NAC

S 15 F

E2

B

E2

DETAIL: B = DETAIL DESIGNATION

E2 = SHEET WHERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION

E2 = SHEET WHERE SECTION IS LOCATED

PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

GENERAL FLOOR PLAN NOTES

WIRE & CONDUIT IN WALL OR ABOVE CEILING.

WIRE & CONDUIT IN OR BELOW SLAB OR GRADE.

EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S) DENOTES

CIRCUIT(S).

EXISTING WIRE & CONDUIT TO REMAIN.EX

CONDUIT TO BE REMOVED.

X - 1,2

4"

4"

4"

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE).

CEILING MOUNTED FIRE ALARM SIGNAL LIGHT. # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

F

CEILING MOUNTED VACANCY SENSOR.OSVS

F

FIRE ALARM SPEAKER & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

Project Schedule Date

Schematic Design 15% 02.16.2021

Schematic Design 35% 04.16.2021

Design Development 65% 09.24.2021

Construction Documents 95% 10.26.2023

Bid Documents 100% 12.15.2023

Design Development 65% (Re-submittal) 11.15.2021

/1 /2

:3

:1

P M

Construct Private In-Patient Rooms & Primary Clinics

12.15.2023

ABBREVIATIONS, SYMBOLS &

INDEX OF DRAWINGS

E001

JSFKMU

506-334

Ann Arbor, Michigan (506)

B01W

JEFF MEANS

BID DOCUMENTS 100%

20014.00

GENERAL NOTES

A. THESE NOTES APPLY EQUALLY TO THE FULL SET OF DOCUMENTS.

B. CONTRACTOR SHALL THOROUGHLY STUDY DESIGN DRAWINGS AND ALL EXISTING CONDITIONS PRIOR TO STARTING PROPOSED

SCHEDULE.

C. SITE VISIT(S) SHALL BE AS OUTLINED IN PROJECT SPECIFICATIONS.

D. INCLUDE ALL WORK NECESSARY TO ACCOMMODATE PHASING. REFER TO ARCHITECTURAL DRAWINGS AND GENERAL

REQUIREMENTS SECTION 01 00 00.

E. WHERE ROOFING WORK IS REQUIRED, THE EXISTING ROOFING MEMBRANE AND INSULATION SHALL BE CUT, REMOVED AND RESTORED AS REQUIRED TO ATTAIN A WATERTIGHT CONDITION. THE ROOFING SUB-CONTRACTOR SHALL BE A CERTIFIED

INSTALLER FOR SUCH INSTALLATION TO MAINTAIN THE EXISTING WARRANTY ON THE ROOF.

F. THE CONTRACTOR SHALL REFER TO ALL SPECIFICATION SECTIONS AND THESE DRAWINGS FOR DETAILS OF BUILDING CONSTRUCTION TO ENSURE SPACE AND SATISFACTORY ARRANGEMENT FOR THEIR WORK. THE VARIOUS DRAWINGS COMPRISING THE SET ARE INTERDEPENDENT AND MUST BE USED JOINTLY AT ALL TIMES. CONTRACTOR SHALL REFER TO THE GENERAL REQUIREMENTS OF THE CONTRACT. THE NOTES AND SYMBOLS INDICATED ON THE DRAWINGS ARE FOR THE GUIDANCE OF ALL TRADES INVOLVED IN THE PROJECT AND MUST BE FOLLOWED TO EXECUTE THE WORK AS INTENDED. IF DISCREPANCIES OCCUR, CONTACT THE COR THRU THE CONTRACTING OFFICER FOR CLARIFICATION BEFORE PROCEEDING.

G. ALL WORK MUST BE COORDINATED WITH THE CONTRACTING OFFICER AND COR TO MAINTAIN OPERATION OF THE EXISTING FACILITY. COORDINATE ALL SHUT DOWNS A MINIMUM OF 21 DAYS BEFOREHAND. REVIEW WHICH LOADS WILL BE TAKEN DOWN, WHICH LOADS WILL REMAIN ON, AND OUTAGE START/END TIME.

H. ALL WORK SHALL BE PERFORMED IN COMPLETE COMPLIANCE WITH ALL CURRENT GOVERNING CODES AND STANDARDS.

I. EXISTING CONDITIONS SHOWN HAVE BEEN BASED UPON AVAILABLE DRAWING INFORMATION, AND MAY BE AT VARIANCE WITH ACTUAL WORK IN PLACE. THE CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD VERIFY ALL CONDITIONS AFFECTING THE EXECUTION OF THE WORK. ANY DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE CONTRACT DOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE WORK SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER IN WRITING FOR RESOLUTION BEFORE PROCEEDING WITH THE WORK.

J. REFER TO ARCHITECTURAL FIRE-RATED PARTITION PLAN(S) FOR LOCATIONS AND FIRE-RATINGS OF NEW AND EXISTING WALL ASSEMBLIES. ALL PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROTECTED AND/OR FIRE-STOPPED AS REQUIRED TO MAINTAIN FIRE-RATINGS INDICATED. COORDINATE WITH ALL TRADES TO ENSURE FIRE-RATED PENETRATION REQUIREMENTS

AND DETAILS ARE MET.

K. ANNULAR SPACE OF ALL PIPE, CONDUIT, DUCT & OTHER SIMILAR PENETRATIONS OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION, PENETRATIONS THROUGH 0-HOUR RATED WALLS & FLOORS SHALL BE FIRESTOPPED TO RETARD

PASSAGE OF FIRE & SMOKE.

L. ALL CONDUITS IN FINISHED ROOMS, CORRIDORS, ETC. SHALL BE CONCEALED IN A WALL OR ABOVE CEILING.

M. ACCESS PANELS IN NON ACCESSIBLE CEILINGS SHALL BE PROVIDED FOR ALL ELECTRICAL ITEMS REQUIRING ACCESS.

N. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF LUMINAIRES, SPEAKERS, NURSE CALL DEVICES, ETC.

O. REFER TO ARCHITECTURAL HEADWALL ELEVATIONS FOR EXACT LOCATION OF DEVICES.

P. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE INCLUDED IN THE CONTRACT. REFINISH ANY SURFACE

DISTURBED UNDER THIS WORK TO MATCH EXISTING.

Q. ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE VA. ITEMS NOT DESIRED BY THE VA SHALL BE REMOVED FROM THE

PREMISES AND DISPOSED OF PROPERLY BY THE CONTRACTOR.

R. THE CONTRACT DRAWINGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR HORIZONTAL OFFSET WHICH MAY BE NECESSARY TO COMPLETE THE SYSTEMS. COORDINATE WORK IN ADVANCE WITH ALL OTHER TRADES AND REPORT IMMEDIATELY AND

DIFFICULTIES WHICH CAN BE ANTICIPATED.

S. ALL ABANDONED EXTRANEOUS CONDUITS, WIRING, DEVICES, ETC. SHALL BE REMOVED.

T. REFER TO MECHANICAL/PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION CONCERNING EQUIPMENT THAT REQUIRES

ELECTRICAL CONNECTIONS.

U. BID ITEMS: REFER TO ARCHITECTURAL DESCRIPTION OF BID ITEMS, PLAN FOR AN OUTLINE OF BID ITEMS, AND TO SPECIFICATION

SECTION 01 00 00.

V. ACOUSTICAL CEILING ACCESS IDENTIFICATION MARKERS: COLORED MARKERS WITH PRESSURE SENSITIVE ADHESIVE ON ONE SIDE, PAPER OR PLASTIC, 6 TO 9 MM (1/4 TO 3/8 INCH) DIAMETER. REFER TO SPECIFICATION 09 51 00 SECTION 2.6.C.

1. COLOR CODE: PROVIDE THE FOLLOWING COLOR MARKERS FOR SERVICE IDENTIFICATION:

• RED - SPRINKLER SYSTEM: VALVES AND CONTROLS.

• GREEN - DOMESTIC WATER: VALVES AND CONTROLS.

• YELLOW - CHILLED WATER AND HEATING WATER.

• ORANGE - DUCTWORK: FIRE DAMPERS.

• BLUE - DUCTWORK: DAMPERS AND CONTROLS.

• BLACK - GAS: LABORATORY, MEDICAL, AIR AND VACUUM.

INDEX OF DRAWINGS - ELECTRICAL

SHEET NUMBER SHEET NAME

E001 ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS

E002 BID DEDUCT ALTERNATES

ED103 PARTIAL THIRD FLOOR PLAN - REMOVALS

ED105 PARTIAL FIFTH FLOOR PLAN - REMOVALS

EL103 PARTIAL THIRD FLOOR PLAN - LIGHTING

EL104 PARTIAL FOURTH FLOOR PLAN - LIGHTING

EL105 PARTIAL FIFTH FLOOR PLAN - LIGHTING

EP101 PARTIAL FIRST FLOOR PLAN - POWER

EP103 PARTIAL THIRD FLOOR PLAN - POWER

EP104 PARTIAL FOURTH FLOOR PLAN - POWER

EP105 PARTIAL FIFTH FLOOR PLAN - POWER

EP106 PARTIAL SIXTH FLOOR & ROOF PLAN - POWER

E401 ENLARGED PLANS

E501 SCHEDULES & DETAILS

E502 PANEL SCHEDULES

E503 PANEL SCHEDULES

E601 PARTIAL SINGLE LINE DIAGRAM

E602 PARTIAL SINGLE LINE DIAGRAM

E603 PARTIAL SINGLE LINE DIAGRAM

E604 PARTIAL SINGLE LINE DIAGRAM

Revisions Date

B01W

B01E

B01W

B01E

B01W

B01E

B01W

B01E

0.1 - DEDUCT ALTERNATE 01:

OMIT ALL WORK RELATED TO THE OPEN OFFICES AND CHAPEL.

SPACE WILL BE SHELLED, PROVIDE 37 C1a LUMINAIRES, 6

DUPLEX RECEPTACLES, 2 FA SPEAKER STROBES AND 3 FA

STROBES.

0.2 - DEDUCT ALTERNATE 02:

OMIT ALL WORK RELATED TO THE ELECTRICAL SHOP.

SPACE WILL BE SHELLED, PROVIDE 15 C1a LUMINAIRES, 1 LIGHTING TOGGLE SWITCH, 2 DUPLEX RECEPTACLES, 1 SPEAKER STROBES AND 1 STROBES.

0.3 - DEDUCT ALTERNATE 03:

OMIT ALL WORK RELATED TO THE TEACHING KITCHEN.

SPACE WILL BE SHELLED, PROVIDE 4 C1a LUMINAIRES, 2

LIGHTING TOGGLE SWITCH, 2 DUPLEX RECEPTACLES, 1

SPEAKER STROBE AND 1 STROBE.

0.4 - DEDUCT ALTERNATE 04:

OMIT ALL WORK RELATED TO CONSTRUCT

NEW LOUNGE AND LOCKER ROOMS.

RETAIN EXISTING LOCKER, RESTROOMS, HAC,

SOILED UTILITY AND OFFICE. EXISTING OFFICE

TO BECOME CLEAN LINEN ROOM.

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

Project Schedule Date

Schematic Design 15% 02.16.2021

Schematic Design 35% 04.16.2021

Design Development 65% 09.24.2021

Construction Documents 95% 10.26.2023

Bid Documents 100% 12.15.2023

Design Development 65% (Re-submittal) 11.15.2021

/1 /2

:3

:1

P M

Construct Private In-Patient Rooms & Primary Clinics

12.15.2023

BID DEDUCT ALTERNATES

E002

JSFKMU

506-334

Ann Arbor, Michigan (506)

B01W

JEFF MEANS

BID DOCUMENTS 100%

20014.00

N Scale: 1" = 30'-0"

BID DEDUCT 01 - REMOVE THIRD FLOOR OFFICES AND

CHAPEL

N Scale: 1" = 30'-0"

BID DEDUCT 02 - REMOVE ELECTRICAL SHOP FOURTH

FLOOR

N Scale: 1" = 30'-0"

BID DEDUCT 03 - REMOVE TEACHING KITCHEN - THIRD

FLOOR

N Scale: 1" = 30'-0"

BID DEDUCT 04 - KEEP EXISTING FIFTH FLOOR

LOCKERS AND RESTROOMS

J J

GF

TV

/G

F

G F

J J

J

LIFT

LD

D

J

J

D

E401

1 1

507A

BATH

1BR

PATIENT

ROOM #2

MF1 MF1

V1 b d e f g a/b/c a/b/c

F4a g

F4a g g a a h i

F4a-WL h

F4b d

F4b d

F4b d

F4b d

NL e

F4b i

F4b i

F4b f

507A

BATH

1BR

PATIENT

ROOM #2

b,c

C1

C1

N1

N1

C1 C1 C1 C1

N1 N1 N1 N1

C2

N2

C2

N2

C2

N2

C2

N2

N2

N2

C2

C2

J J

N1 C1

J J

N1 C1

J J

N2 C2

J J

N2 C2

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

Project Schedule Date

Schematic Design 15% 02.16.2021

Schematic Design 35% 04.16.2021

Design Development 65% 09.24.2021

Construction Documents 95% 10.26.2023

Bid Documents 100% 12.15.2023

Design Development 65% (Re-submittal) 11.15.2021

/1 /2

:3

:2

P M

Construct Private In-Patient Rooms & Primary Clinics

12.15.2023

ENLARGED PLANS

E401

JSFKMU

506-334

Ann Arbor, Michigan (506)

B01W

JEFF MEANS

BID DOCUMENTS 100%

20014.00

N Scale: 1/2" = 1'-0"

TYPICAL PATIENT ROOM - POWER

N Scale: 1/2" = 1'-0"

TYPICAL PATIENT ROOM - LIGHTING

Scale: 3/4" = 1'-0"1

PATIENT HEADWALL - POWER ELEVATION

NOTES

1 REFER TO OVERALL FLOOR PLAN ON SHEET EP105 FOR CIRCUIT INFORMATION.

2 REFER TO OVERALL FLOOR PLAN ON SHEET EL105 FOR CIRCUIT INFORMATION.

3 PROVIDE LOW VOLTAGE CONTROLLER TO ALLOW THE NURSE CALL PILLOW

SPEAKER CONTROL OF READING AND AMBIENT FUNCTIONS OF THE MF1 LUMINAIRE.

AMBIENT FUNCTION SHALL HAVE ON/OFF CONTROL UTILIZING PILLOW SPEAKER AND

LOW VOLTAGE ON/OFF CONTROL AT DOOR (SWITCH LEG "b". READING FUNCTION

SHALL HAVE ON/OFF CONTROL AT PILLOW SPEAKER.

4 PROVIDE LINE VOLTAGE 3-WAY SWITCHES TO CONTROL EXAM FUNCTION OF

PATIENT BED LUMINAIRES (SWITCH LEG "a").

5 SWITCHING DESIGNATION FOR PATIENT BED LUMINAIRES SHALL BE AS FOLLOWS: (a)

- EXAM FUNCTION, (b) - AMBIENT FUNCTION, (c) - READING FUNCTION.

6 PATIENT HEADWALL UNIT. EACH PATIENT HEADWALL UNIT SHALL HAVE (2)

DEDICATED CRITICAL POWER CIRCUITS AND (2) DEDICATED NORMAL POWER

CIRCUITS. REFER TO POWER ELEVATION ON THIS SHEET AND ARCHITECTURAL

ELEVATIONS FOR MORE INFORMATION.

7 PROVIDE RECEPTACLE IN CEILING FOR PATIENT LIFT. COORDINATE EXACT LOCATION

IN THE FIELD PER MANUFACTURER RECOMMENDATIONS.

8 PROVIDE 120V GF PROTECTED CIRCUIT TO POWER SUPPLY ABOVE ACCESSIBLE

CEILING FOR LOW-VOLTAGE POWER CONNECTION TO SHOWER CONTROLS. PROVIDE

.75" CONDUIT BETWEEN POWER SUPPLY AND DIGITAL MIXING VALVE UNIT FOR LOW

VOLTAGE WIRING. COORDINATE REQUIREMENTS WITH VENDOR.

VA Project No.

RDC/JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

Project Schedule Date

Schematic Design 15% 02.16.2021

Schematic Design 35% 04.16.2021

Design Development 65% 09.24.2021

Construction Documents 95% 10.26.2023

Bid Documents 100% 12.15.2023

Design Development 65% (Re-submittal) 11.15.2021

/1 /2

:3

:2

P M

Construct Private In-Patient Rooms & Primary Clinics

12.15.2023

SCHEDULES & DETAILS

E501

JSFKMU

506-334

Ann Arbor, Michigan (506)

B01W

JEFF MEANS

BID DOCUMENTS 100%

20014.00

NOTES:

1. PROVIDE SINGLE POINT CONNECTION TO UNIT.

2. PROVIDE INTERLOCK BETWEEN VFD AND OUTDOOR DISCONNECT. VFD SHALL SHUTDOWN UPON OPENING OF DISCONNECT.

3. REFER TO SINGLE LINE FOR WIRE SIZE.

MOTORS, STARTERS, DISCONNECTS & CONTROLS

MARK

MOTOR STARTER DISCONNECT MEANS CONTROL FEEDER

S E

E N

O T

E

NAMEPLATE

CHARACTERISTICS LOCATION

N E

M A

S

IZ

E

TYPE LOCATION

F U

R N

IS

H

E D

B Y

TYPE LOCATION

F U

R N

IS

H

E D

B Y

I N

T E

R L O

C K

W

IT

H M

O T

O R

N O

B

Y E

.C

M A

N U

A L A

T S

T A

R T

E R

I N

T E

G R

A L

W

IT

H E

Q U

IP

M

E N

T

F U

R N

IS

H

E D

B Y

S E

E N

O T

E

N U

M B

E R

O F

C O

N D

U C

T O

R S

W

IR

E S

IZ

E

G R

O U

N D

S

IZ

E

C O

N D

U

IT

S

IZ

E

H O

R S

E P

O W

E R

H

P

L O

A D kV

A

V

-1 P

H

V

-1 P

H

V

-3 P

H

V

-1 P

H

V

-3 P

H

V

-1 P

H

V

-1 P

H

V

-3 P

H

R O

O M

N U

M B

E R

ROOM NAME M

A

N U

A L

M A

G N

E T

IC

E C

M

-S

P E

E D

V F

D

S E

E N

O T

E

N E

A R

M O

T O

R

M O

T O

R C

O N

T C

E N

T E

R

E Q

U

IP

C O

N T

P A

N E

L

R O

O M

N U

M B

E R

S E

E N

O T

E

D

IS

C S

W

IT

C H

M A

N U

A L S

T A

R T

E R

R E

C E

P T

A C

L E

T O

G G

L E

S W

IT

C

H

N E

M A

T Y

P E

D

IS

C S

IZ

E

F U

S E

S

IZ

E

N E

A R

M O

T O

R

M O

T O

R C

O N

T C

E N

T E

R

E Q

U

IP

C O

N T

P A

N E

L

P A

N E

L B

O A

R D

S E

E N

O T

E

1W-AHU21T TEMPORARY AIR HANDLING UNIT 21T SUPPLY: (4) - 5.2 HP,

RETURN (2) - 4 HP

120.62 ● ● DIV. 23 ● ● DIV. 26 DIV. 23 3 350

KCMIL

4 3"

1W-AHU22 RF 1W AIR HANDLER UNIT 22 - RETURN ARRAY (2) - 7 HP 13.72 ● 400 MECHANICAL

ROOM

● ● DIV. 23 ● ● DIV. 23 DIV. 23 3

1W-AHU22 SF 1W AIR HANDLER UNIT 22 - SUPPLY ARRAY (4) - 7.5 HP 27.73 ● 400 MECHANICAL

ROOM

● ● DIV. 23 ● ● DIV. 23 DIV. 23 3

1W-AHU23 RF 1W AIR HANDLER UNIT 23 - RETURN ARRAY (2) - 7 HP 13.72 ● 400 MECHANICAL

ROOM

● ● DIV. 23 ● ● DIV. 23 DIV. 23 3

1W-AHU23 SF 1W AIR HANDLER UNIT 23 - SUPPLY ARRAY (4) - 7.5 HP 27.69 ● 400 MECHANICAL

ROOM

● ● DIV. 23 ● ● DIV. 23 DIV. 23 3

1W-AHU-21 AIR HANDLER UNIT 21(RELOCATED) SUPPLY: (3) - 7.5 HP,

RETURN: (2) - 5 HP

45.73 ● EX/R EX/R DIV. 23 3

1W-EF1A 1W EXHAUST FAN 1A 1.5 HP 6.32 ● ● ● DIV. 26 ● 3R 30 NF ● DIV. 26 DIV. 23 3 12 12 0.75" 2

1W-EF1B 1W EXHAUST FAN 1B 1.5 HP 6.32 ● ● ● DIV. 26 ● 3R 30 NF ● DIV. 26 DIV. 23 3 12 12 0.75" 2

1W-EF2A 1W EXHAUST FAN 2A 20 HP 17.46 ● ● ● DIV. 26 ● 3R 60 NF DIV. 26 DIV. 23 3 6 10 1" 2

1W-EF2B 1W EXHAUST FAN 2B 20 HP 17.46 ● ● ● DIV. 26 ● 3R 60 NF DIV. 26 DIV. 23 3 6 10 1" 2

1W-EF3 1W EXHAUST FAN 3 .75 HP 1.83 ● ● DIV. 23 ● ● DIV. 23 DIV. 23 2 12 12 0.75"

1W-EF4 1W EXHAUST FAN 4 .75 HP 1.83 ● ● DIV. 23 ● ● DIV. 23 DIV. 23 2 12 12 0.75"

1W-EF5 1W EXHAUST FAN 5 .75 HP 1.83 ● ● DIV. 23 ● ● DIV. 23 DIV. 23 2 12 12 0.75"

1W-EF6 1W EXHAUST FAN 6 .75 HP 1.83 ● ● DIV. 23 ● ● DIV. 23 DIV. 23 2 12 12 0.75"

1W-EF7 1W EXHAUST FAN 7 0.5 HP 1.83 ● ● DIV. 23 ● ● DIV. 23 DIV. 23 2 12 12 0.75"

1W-EF8 1W EXHAUST FAN 8 2 HP 2.88 ● ● DIV. 23 ● ● DIV. 23 DIV. 23 2 10 10 0.75"

1W-EF9 1W EXHAUST FAN 9 1 HP 1.92 ● 401 ELECTRICAL

SHOP

● DIV. 23 ● ● DIV. 23 DIV. 23 2 10 10 0.75"

1W-EF10 1W EXHAUST FAN 10 .75 HP 1.92 ● 400 MECHANICAL

ROOM

● DIV. 23 ● ● DIV. 23 DIV. 23 2 10 10 0.75"

1W-P22 1W AHU-21 PREHEAT COIL RECIRC PUMP P-22 0.5 HP 1.18 ● 400 MECHANICAL

ROOM

0 ● ● DIV. 26 ● 1 30 NF ● DIV. 26 DIV. 23 2 12 12 0.75"

1W-P23 1W AHU-21 PREHEAT COIL RECIRC PUMP P-23 .75 HP 1.66 ● 400 MECHANICAL

ROOM

0 ● ● DIV. 26 ● 1 30 NF ● DIV. 26 DIV. 23 2 12 12 0.75"

UH-1 UNIT HEATER 1 0.12 ● 401 ELECTRICAL

SHOP

DIV. 23 ● ● DIV. 26 DIV. 23 2 12 12 0.75"

NOTES:

1. COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL DRAWINGS.

2. COORDINATE EXACT LENGTH WITH ARCHITECTURAL DRAWINGS.

LUMINAIRES

MARK Image

LAM

PS

L O

A D

V

A

F

IX

T U

R E

V O

L T

A G

E

MANUFACTURER CATALOG NO. DESCRIPTION

OTHER ACCEPTABLE

MANUFACTURERS DIFFUSING MEDIA

MOUNTING

S E

E N

O T

E

V A

L

IN

E

A R

F O

O T

S-SURFACE

R-RECESSED

SM-STEM MTD

WM-WALL MTD

C-CHAIN MTD

UC-UNDER CAB

CS-CEIL SURFACE

<varies

EXT1 10 277 LITHONIA WDGE1 LED P1 40K 80CRI VF MVOLT PE DS

DDBXD

ARCHITECTURAL WALL SCONCE APPROVED EQUAL S

F4a 24 277 LITHONIA LDN6-40/10-LO6AR-LSS-277-GZ10 6" DOWNLIGHT APPROVED EQUAL

F4a-WL 24 277 LITHONIA LDN6-40/10-LO6AR-LSS-277-GZ10 6" DOWNLIGHT WET LISTED APPROVED EQUAL

F4b 24 277 LITHONIA LDN6-40/10-LO6AR-LSS-277-GZ10 6" DOWNLIGHT APPROVED EQUAL

B1 37 277 LITHONIA 2RTL2-33L-GZ10-LP840 2X2 VOLUMETRIC LUMINAIRE APPROVED EQUAL R

B2a 29 277 LITHONIA 2RTL4-30L-GZ10-LP840 2X4 VOLUMETRIC LUMINAIRE - LOW OUTPUT APPROVED EQUAL R

B6b 3 <varies

277 FOCAL POINT FSM1-PD05-625LF-940K-1C-UNV-L11-XFF-WH-X LINEAR POP DOWN LENS - HIGH OUTPUT APPROVED EQUAL R

C1a 25 277 LITHONIA ZL1N L48 3000LM FST 277 40K 80CRI WH 4' STRIP LUMINAIRE APPROVED EQUAL C

C1b 34 277 LITHONIA ZL1N L48 5000LM FST 277 40K 80CRI WH 4' STRIP LUMINAIRE APPROVED EQUAL C

F1 11 277 LITHONIA LDN6-40/10-LO6AR-LSS-277-GZ10 6" DOWNLIGHT APPROVED EQUAL R 1

L2a 19 277 LITHONIA 2GTL2-20L-277-GZ10-LP840 2X2 LENSED TROFFER - LOW OUTPUT APPROVED EQUAL R

L2b 34 277 LITHONIA 2GTL2-40L-277-GZ10-LP840 2X2 LENSED TROFFER - HIGH OUTPUT APPROVED EQUAL R

NOTES:

1. COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL DRAWINGS.

2. COORDINATE EXACT LENGTH WITH ARCHITECTURAL DRAWINGS.

3. PROVIDE ALL REQUIRED ACCESSORIES FOR A COMPLETE, OPERATIONAL...

LUMINAIRES

MARK Image

LAM

PS

L O

A D

V

A

F

IX

T U

R E

V O

L T

A G

E

MANUFACTURER CATALOG NO. DESCRIPTION

OTHER ACCEPTABLE

MANUFACTURERS DIFFUSING MEDIA

MOUNTING

S E

E N

O T

E

V A

L

IN

E

A R

F O

O T

S-SURFACE

R-RECESSED

SM-STEM MTD

WM-WALL MTD

C-CHAIN MTD

UC-UNDER CAB

CS-CEIL SURFACE

L4a 23 277 LITHONIA 2GTL4-30L-277-GZ10-LP840 2X4 LENSED TROFFER - LOW OUTPUT APPROVED EQUAL R

L4b 36 277 LITHONIA 2GTL4-48L-277-GZ10-LP840 2X4 LENSED TROFFER - HIGH OUTPUT APPROVED EQUAL R

MF1 99 277 LITHONIA MAEC-48-F-38L/38L/6L-40K8-DIM1-277-HD-IB-XX PATIENT BED MULTI-FUNCTION LUMINAIRE APPROVED EQUAL R

NL 5 277 KENALL MCSL-VR-MW-2L40K-DV PATIENT ROOM NIGHT LIGHT APPROVED EQUAL WM

P3 10 277 SEED LIGHTING SLD-1010PC12-SHINY BRASS DECORATIVE PENDANT APPROVED EQUAL SM

UC1 8 120 AIREY THOMPSON 13HC-N-40K-12-2-3-AMS UNDER CABINET LIGHT APPROVED EQUAL UC

UC2 11 120 AIREY THOMPSON 13HC-N-40K-24-2-3-AMS UNDER CABINET LIGHT APPROVED EQUAL UC

UC3 11 120 AIREY THOMPSON 13HC-N-40K-36-2-3-AMS UNDER CABINET LIGHT APPROVED EQUAL UC

V1 17 277 LITHONIA FMVCSLS-24IN-MVOLT-30K35K40K-90CRI-BN 2' VANITY APPROVED EQUAL WM

X1 2 277 LITHONIA EDGR 1 RMR SINGLE FACE EXIT SIGN APPROVED EQUAL

X2 2 277 LITHONIA EDGR 2 RMR DOUBLE FACE EXIT SIGN APPROVED EQUAL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

Project Schedule Date

Schematic Design 15% 02.16.2021

Schematic Design 35% 04.16.2021

Design Development 65% 09.24.2021

Construction Documents 95% 10.26.2023

Bid Documents 100% 12.15.2023

Design Development 65% (Re-submittal) 11.15.2021

/1 /2

:3

:2

P M

Construct Private In-Patient Rooms & Primary Clinics

12.15.2023

PANEL SCHEDULES

E502

JSFKMU

506-334

Ann Arbor, Michigan (506)

B01W

JEFF MEANS

BID DOCUMENTS 100%

20014.00

2.59 kVA 2.59 kVA (7 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: $ = NPROVIDE GROUND FAULT BREAKER.

Total Est. Demand: 7 A

Total Conn.: 7 A

Total Est. Demand: 2590 VA

Total Conn. Load: 2590 VA

Receptacle 2590 VA 100.00% 2590 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 0.72 kVA 1.51 kVA 0.36 kVA

41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42

39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40

37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38

35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36

33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34

31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32

29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30

27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28

25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26

23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24

21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22

19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20

17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18

15 DISPOSER 20 A 1 1150... 0 VA 1 20 A Spare 16

13 Space -- 1 -- -- 1 -- Space 14

11 Space -- 1 -- -- 1 -- Space 12

9 Space -- 1 -- -- 1 -- Space 10

7 $ HOOD CONTROLS 20 A 1 360 VA -- 1 -- Space 8

5 $ HOOD CONTROLS 20 A 1 360 VA -- 1 -- Space 6

3 $ HOOD CONTROLS 20 A 1 360 VA -- 1 -- Space 4

1 $ HOOD CONTROLS 20 A 1 360 VA -- 1 -- Space 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB

Location: ELEC A311 Mounting: Surface A.I.C. Rating:

Panel: R3A-2

49.7 kVA 29.85 kVA (83 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: $ = PROVIDE GROUND FAULT BREAKER.

Total Est. Demand: 83 A

Total Conn.: 138 A

Total Est. Demand: 29850 VA

Total Conn. Load: 49700 VA

Receptacle 49700 VA 60.06% 29850 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 15.44 kVA 17.04 kVA 17.22 kVA

41 -- -- -- 1800... 180 VA 1 20 A Receptacle 42

39 $ COOKTOP 20 A 2 1800... 180 VA 1 20 A Receptacle 40

37 -- -- -- 1800... 180 VA 1 20 A Receptacle 38

35 $ COOKTOP 20 A 2 1800... 180 VA 1 20 A Receptacle HEALTHY... 36

33 -- -- -- 1800... 180 VA 1 20 A Receptacle HEALTHY... 34

31 $ COOKTOP 20 A 2 1800... 180 VA 1 20 A Receptacle HEALTHY... 32

29 -- -- -- 1800... 1600... -- -- -- 30

27 $ COOKTOP 20 A 2 1800... 1600... 2 20 A $ OVEN 28

25 -- -- -- 1800... 1600... -- -- -- 26

23 $ COOKTOP 20 A 2 1800... 1600... 2 20 A $ OVEN 24

21 -- -- -- 1800... 1600... -- -- -- 22

19 $ COOKTOP 20 A 2 1800... 1600... 2 20 A $ OVEN 20

17 -- -- -- 1800... 1600... -- -- -- 18

15 $ COOKTOP 20 A 2 1800... 1600... 2 20 A $ OVEN 16

13 -- -- -- 1800... 180 VA 1 20 A Receptacle OPEN... 14

11 $ COOKTOP 20 A 2 1800... 900 VA 1 20 A Receptacle OPEN... 12

9 -- -- -- 1800... 720 VA 1 20 A Receptacle OPEN... 10

7 $ COOKTOP 20 A 2 1800... 180 VA 1 20 A Receptacle OPEN... 8

5 Receptacle OPEN... 20 A 1 180 VA 180 VA 1 20 A Receptacle OPEN... 6

3 Receptacle OPEN... 20 A 1 180 VA 180 VA 1 20 A Receptacle OPEN... 4

1 Receptacle 20 A 1 540 VA 180 VA 1 20 A Receptacle Room C3-A 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB

Location: ELEC A373 Mounting: Surface A.I.C. Rating:

Panel: R3C-2 (EXISTING)(EXISTING)

27.72 kVA 18.86 kVA (52 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Est. Demand: 52 A

Total Conn.: 77 A

Total Est. Demand: 18860 VA

Total Conn. Load: 27720 VA

Receptacle 27720 VA 68.04% 18860 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 9.90 kVA 9.72 kVA 8.10 kVA

41 Receptacle 1BR... 20 A 1 900 VA 0 VA 1 20 A Spare 42

39 Receptacle 1BR... 20 A 1 1080... 0 VA 1 20 A Spare 40

37 Receptacle 1BR... 20 A 1 1080... 180 VA 1 20 A Receptacle 38

35 Receptacle 1BR... 20 A 1 900 VA 900 VA 1 20 A Receptacle 1BR... 36

33 Receptacle 1BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 34

31 Receptacle 1BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 32

29 Receptacle 1BR... 20 A 1 900 VA 900 VA 1 20 A Receptacle 1BR... 30

27 Receptacle 1BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 28

25 Receptacle 1BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 26

23 Receptacle 20 A 1 900 VA 900 VA 1 20 A Receptacle 1BR... 24

21 Receptacle 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 22

19 Receptacle 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 20

17 Receptacle 1 BR... 20 A 1 900 VA 900 VA 1 20 A Receptacle 18

15 Receptacle 1 BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1 BR... 16

13 Receptacle 1 BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1 BR... 14

11 Space -- 1 -- -- 1 -- Space 12

9 Space -- 1 -- -- 1 -- Space 10

7 Space -- 1 -- -- 1 -- Space 8

5 Space -- 1 -- -- 1 -- Space 6

3 Space -- 1 -- -- 1 -- Space 4

1 Space -- 1 -- -- 1 -- Space 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB

Location: ELEC A578 Mounting: Surface A.I.C. Rating:

Panel: R5C-2 (EXISTING)

34.16 kVA 22.08 kVA (61 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: $ = PROVIDE GROUND FAULT BREAKER.

Total Est. Demand: 61 A

Total Conn.: 95 A

Total Est. Demand: 22080 VA

Total Conn. Load: 34160 VA

Receptacle 34160 VA 64.64% 22080 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 11.40 kVA 10.72 kVA 12.04 kVA

41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42

39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40

37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38

35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36

33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34

31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32

29 Spare 20 A 1 0 VA 1000... 1 20 A BLANKET WARMER 30

27 Receptacle ALCOVE... 20 A 1 180 VA 1000... 1 20 A BLANKET WARMER 28

25 Receptacle NUTRITIO... 20 A 1 1500... 26

23 $ Receptacle 1BR... 20 A 1 1440... 1440... 1 20 A $ Receptacle 1BR... 24

21 Receptacle 1BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 22

19 Receptacle 1BR... 20 A 1 1260... 1260... 1 20 A Receptacle 1BR... 20

17 $ Receptacle 1BR... 20 A 1 1440... 1440... 1 20 A $ Receptacle 1BR... 18

15 Receptacle 1BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 16

13 Receptacle 1BR... 20 A 1 1260... 1260... 1 20 A Receptacle 1BR... 14

11 $ Receptacle 1BR... 20 A 1 1440... 1440... 1 20 A $ Receptacle 1BR... 12

9 Receptacle 1BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1BR... 10

7 Receptacle 1BR... 20 A 1 1260... 1260... 1 20 A Receptacle 1BR... 8

5 Receptacle MED ROO... 20 A 1 1500... 900 VA 1 20 A Receptacle MED ROO... 6

3 Receptacle CLEAN... 20 A 1 1800... 1260... 1 20 A Receptacle NURSE... 4

1 $ Receptacle 2BR A513 20 A 1 1440... 900 VA 1 20 A $ Rec NURSE STATIO... 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB

Location: ELEC A578 Mounting: Surface A.I.C. Rating:

Panel: CR5C-2 (NEW)

15.84 kVA 12.92 kVA (36 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: $ = PROVIDE GROUND FAULT BREAKER.

Total Est. Demand: 36 A

Total Conn.: 44 A

Total Est. Demand: 12920 VA

Total Conn. Load: 15840 VA

Receptacle 15840 VA 81.57% 12920 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 5.22 kVA 5.04 kVA 5.58 kVA

41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42

39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40

37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38

35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36

33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34

31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32

29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30

27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28

25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26

23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24

21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22

19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20

17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18

15 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 16

13 AAP 20 A 1 360 VA 180 VA 1 20 A P-TUBE STATION 14

11 $ Receptacle 20 A 1 1440... 1260... 1 20 A Receptacle NURSE... 12

9 Receptacle 20 A 1 1080... 1800... 1 20 A Receptacle 10

7 Receptacle 20 A 1 1260... 900 VA 1 20 A Receptacle 8

5 $ Receptacle 1 BR... 20 A 1 1440... 1440... 1 20 A $ Receptacle 6

3 Receptacle 1 BR... 20 A 1 1080... 1080... 1 20 A Receptacle 1 BR... 4

1 Receptacle 1 BR... 20 A 1 1260... 1260... 1 20 A Receptacle 1 BR... 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB

Location: ELEC B520 Mounting: Surface A.I.C. Rating: 35KA

Panel: CR5B-2 (NEW)

35.17 kVA 27.74 kVA (77 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: $ = PROVIDE GROUND FAULT BREAKER.

Total Est. Demand: 77 A

Total Conn.: 98 A

Receptacle 25860 VA 69.33% 17930 VA Total Est. Demand: 27742 VA

Motor 9152 VA 105.00% 9610 VA Total Conn. Load: 35174 VA

Lighting 162 VA 125.00% 203 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 12.24 kVA 10.28 kVA 12.65 kVA

41 Receptacle HEALTHY... 20 A 1 180 VA 1080... 1 20 A Receptacle 42

39 Receptacle 20 A 1 180 VA 540 VA 1 20 A Receptacle 40

37 Receptacle ALCOVE... 20 A 1 360 VA 720 VA 1 20 A Receptacle NURSE... 38

35 REC 20 A 1 540 VA 900 VA 1 20 A Receptacle Room 526 36

33 Receptacle Room... 20 A 1 900 VA 900 VA 1 20 A Receptacle Room 518,... 34

31 Receptacle NURSE... 20 A 1 720 VA 1500... 1 20 A Receptacle MED ROO... 32

29 Receptacle NURSE... 20 A 1 720 VA 1124... 1 20 A Receptacle MED ROO... 30

27 Receptacle Room... 20 A 1 540 VA 720 VA 1 20 A Receptacle Room 522,... 28

25 Receptacle 20 A 1 1500... 900 VA 1 20 A Receptacle NURSE... 26

23 Receptacle Room 522,... 20 A 1 775 VA 1800... 1 20 A Receptacle CLEAN... 24

21 Receptacle NURSE... 20 A 1 720 VA 783 VA 1 20 A Receptacle Room 510,... 22

19 Receptacle Room... 20 A 1 540 VA 900 VA 1 20 A Receptacle Room... 20

17 Receptacle... 20 A 1 810 VA 1080... 1 20 A Receptacle Room... 18

15 Receptacle 2BR A513 20 A 1 720 VA 810 VA 1 20 A Receptacle EQUIPMEN... 16

13 Receptacle Room 503 20 A 1 900 VA 540 VA 1 20 A Receptacle 2BR A513 14

11 -- -- -- 915 VA 900 VA 1 20 A Receptacle 12

9 1W-EF7 20 A 2 915 VA 720 VA 1 20 A Receptacle OFFICE 503 10

7 -- -- -- 915 VA 915 VA -- -- -- 8

5 1W-EF5 20 A 2 915 VA 915 VA 2 20 A 1W-EF6 6

3 -- -- -- 915 VA 915 VA -- -- -- 4

1 1W-EF3 20 A 2 915 VA 915 VA 2 20 A 1W-EF4 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB

Location: ELEC B520 Mounting: Surface A.I.C. Rating: 35KA

Panel: RB5-3 (NEW)

0 kVA 0 kVA (0 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Est. Demand: 0 A

Total Conn.: 0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 0.00 kVA 0.00 kVA 0.00 kVA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

11 12

9 10

7 8

5 6

3 4

1 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 150 A Supply From: T-4EPP2 Enclosure: Type 1 Mains Type: 150 A MB

Location: MECHANICAL ROOM 400 Mounting: Surface A.I.C. Rating: 35KA

Panel: 4EPP2(NEW) (NEW)

28.75 kVA 24.95 kVA (69 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Est. Demand: 69 A

Total Conn.: 80 A

Receptacle 19040 VA 76.26% 14520 VA Total Est. Demand: 24953 VA

Motor 9672 VA 107.44% 10392 VA Total Conn. Load: 28745 VA

Lighting 33 VA 125.00% 41 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 9.27 kVA 9.69 kVA 9.79 kVA

41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42

39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40

37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38

35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36

33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34

31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32

29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30

27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28

25 Spare 20 A 1 0 VA 2667... -- -- -- 26

23 Spare 20 A 1 0 VA 2667... -- -- -- 24

21 2667... 3 30 A TEST TABLE 22

19 1920... 1 20 A Motor MECHANICAL... 20

17 Receptacle... 20 A 1 540 VA 1176... 1 20 A Motor MECHANICAL... 18

15 Receptacle... 20 A 1 540 VA 2880... 1 50 A 1W-EF8 16

13 Receptacle... 20 A 1 360 VA 14

11 Motor ELECTRICAL... 20 A 1 1920... 1656... 1 20 A 1W-P23 12

9 Receptacle... 20 A 1 900 VA 120 VA 1 20 A Motor ELECTRICAL... 10

7 Receptacle... 20 A 1 1080... 1080... 1 20 A Receptacle ELECTRIC... 8

5 Receptacle... 20 A 1 933 VA 900 VA 1 20 A Receptacle OFFICE... 6

3 Receptacle... 20 A 1 1080... 1500... 1 20 A Receptacle ELECTRIC... 4

1 Receptacle... 20 A 1 1080... 1080... 1 20 A Receptacle ELECTRIC... 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 150 A Supply From: T-4PP2 Enclosure: Type 1 Mains Type: 150 A MB

Location: MECHANICAL ROOM 400 Mounting: Surface A.I.C. Rating: 35KA

Panel: 4PP2

33.67 kVA 21.91 kVA (61 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: $ = PROVIDE GROUND FAULT BREAKER.

Total Est. Demand: 61 A

Total Conn.: 93 A

Total Est. Demand: 21914 VA

Receptacle 33560 VA 64.90% 21780 VA Total Conn. Load: 33667 VA

Lighting 107 VA 125.00% 134 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 10.16 kVA 11.96 kVA 11.55 kVA

41 Receptacle Room 307-1 20 A 1 750 VA 1500... 1 20 A Receptacle 42

39 Receptacle 20 A 1 1500... 977 VA 1 20 A Receptacle HEALTHY... 40

37 $ DISHWASHER 20 A 1 1500... 1500... 1 20 A Receptacle 38

35 $ DISHWASHER 20 A 1 1500... 1500... 1 20 A Receptacle 36

33 Receptacle HEALTHY... 20 A 1 1500... 1500... 1 20 A $ DISHWASHER 34

31 Receptacle OPEN... 20 A 1 540 VA 360 VA 1 20 A Receptacle OPEN... 32

29 Receptacle 20 A 1 1500... 540 VA 1 20 A Receptacle SPACE 300 30

27 $ MICROWAVE 20 A 1 1500... 1500... 1 20 A Receptacle 28

25 Receptacle HEALTHY... 20 A 1 1500... 1500... 1 20 A Receptacle HEALTHY... 26

23 Receptacle HEALTHY... 20 A 1 180 VA 1500... 1 20 A Receptacle HEALTHY... 24

21 Receptacle Room 307 20 A 1 720 VA 1500... 1 20 A $ MICROWAVE 22

19 Receptacle Room 307A 20 A 1 860 VA 1500... 1 20 A $ REFRIGERATOR 20

17 Receptacle SPACE 314 20 A 1 1080... 1500... 1 20 A $ DISHWASHER 18

15 Receptacle CHAPEL... 20 A 1 720 VA 540 VA 1 20 A Receptacle CHAPEL 308 16

13 Receptacle 20 A 1 900 VA 0 VA 1 20 A EXISTING 14

11 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 12

9 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 10

7 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 8

5 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 6

3 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 4

1 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB

Location: ELEC A373 Mounting: Surface A.I.C. Rating:

Panel: R3C-1 (EXISTING)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

Project Schedule Date

Schematic Design 15% 02.16.2021

Schematic Design 35% 04.16.2021

Design Development 65% 09.24.2021

Construction Documents 95% 10.26.2023

Bid Documents 100% 12.15.2023

Design Development 65% (Re-submittal) 11.15.2021

/1 /2

:3

:2

P M

Construct Private In-Patient Rooms & Primary Clinics

12.15.2023

PANEL SCHEDULES

E503

JSFKMU

506-334

Ann Arbor, Michigan (506)

B01W

JEFF MEANS

BID DOCUMENTS 100%

20014.00

1.03 kVA 1.29 kVA (2 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Est. Demand: 2 A

Total Conn.: 1 A

Total Est. Demand: 1293 VA

Total Conn. Load: 1034 VA

Lighting 1034 VA 125.00% 1293 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 0.00 kVA 0.00 kVA 1.03 kVA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Space -- 1 -- -- 1 -- Space 34

31 Space -- 1 -- -- 1 -- Space 32

29 Space -- 1 -- -- 1 -- Space 30

27 Space -- 1 -- -- 1 -- Space 28

25 Space -- 1 -- -- 1 -- Space 26

23 Space -- 1 -- -- 1 -- Space 24

21 Space -- 1 -- -- 1 -- Space 22

19 Spare 20 A 1 0 VA -- 1 -- Space 20

17 Spare 20 A 1 0 VA -- 1 -- Space 18

15 Spare 20 A 1 0 VA -- 1 -- Space 16

13 Spare 20 A 1 0 VA -- 1 -- Space 14

11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12

9 EXISTING 20 A 1 0 VA 0 VA 1 20 A Spare 10

7 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 8

5 Lighting Room 307A,... 20 A 1 1034... 0 VA 1 20 A EXISTING 6

3 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 4

1 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 480/277 Wye-3PH-4W Mains Rating: 225 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB

Location: ELEC A373 Mounting: Surface A.I.C. Rating:

Panel: L3C-1

0 kVA 0 kVA (0 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Est. Demand: 0 A

Total Conn.: 0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 0.00 kVA 0.00 kVA 0.00 kVA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Space -- 1 -- -- 1 -- Space 34

31 Space -- 1 -- -- 1 -- Space 32

29 Space -- 1 -- -- 1 -- Space 30

27 Space -- 1 -- -- 1 -- Space 28

25 Space -- 1 -- -- 1 -- Space 26

23 Space -- 1 -- -- 1 -- Space 24

21 Space -- 1 -- -- 1 -- Space 22

19 Space -- 1 -- -- 1 -- Space 20

17 Space -- 1 -- -- 1 -- Space 18

15 Space -- 1 -- -- 1 -- Space 16

13 Space -- 1 -- -- 1 -- Space 14

11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12

9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10

7 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 8

5 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 6

3 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 4

1 EXISTING 20 A 1 0 VA 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 480/277 Wye-3PH-4W Mains Rating: 100 A Supply From: Enclosure: Type 1 Mains Type: MLO

Location: ELECTRICAL A474 Mounting: Surface A.I.C. Rating: EXISTING

Panel: LS4C-1

2.83 kVA 3.53 kVA (4 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Est. Demand: 4 A

Total Conn.: 3 A

Total Est. Demand: 3532 VA

Other 0 VA 0.00% 0 VA Total Conn. Load: 2826 VA

Lighting 2826 VA 125.00% 3532 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 1.87 kVA 0.96 kVA 0.00 kVA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Space -- 1 -- -- 1 -- Space 34

31 Space -- 1 -- -- 1 -- Space 32

29 Space -- 1 -- -- 1 -- Space 30

27 Space -- 1 -- -- 1 -- Space 28

25 Space -- 1 -- -- 1 -- Space 26

23 Space -- 1 -- -- 1 -- Space 24

21 Space -- 1 -- -- 1 -- Space 22

19 Space -- 1 -- -- 1 -- Space 20

17 Spare 20 A 1 0 VA -- 1 -- Space 18

15 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 16

13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14

11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12

9 Lighting Room 507, 50... 20 A 1 960 VA 0 VA 1 20 A Spare 10

7 Lighting Room 526,... 20 A 1 1194... 672 VA 1 20 A Room 519, 524, 523, 525 8

5 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 6

3 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 4

1 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 480/277 Wye-3PH-4W Mains Rating: 250 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB

Location: ELEC A578 Mounting: Surface A.I.C. Rating:

Panel: L5C-1

0 kVA 0 kVA (0 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Est. Demand: 0 A

Total Conn.: 0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 0.00 kVA 0.00 kVA 0.00 kVA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Space -- 1 -- -- 1 -- Space 34

31 Space -- 1 -- -- 1 -- Space 32

29 Space -- 1 -- -- 1 -- Space 30

27 Space -- 1 -- -- 1 -- Space 28

25 Space -- 1 -- -- 1 -- Space 26

23 Space -- 1 -- -- 1 -- Space 24

21 Space -- 1 -- -- 1 -- Space 22

19 Space -- 1 -- -- 1 -- Space 20

17 Space -- 1 -- -- 1 -- Space 18

15 Space -- 1 -- -- 1 -- Space 16

13 Space -- 1 -- -- 1 -- Space 14

11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12

9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10

7 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 8

5 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 6

3 EXISTING 20 A 1 0 VA 0 VA 1 20 A Spare 4

1 EXISTING 20 A 1 0 VA 0 VA 1 20 A Spare 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 480/277 Wye-3PH-4W Mains Rating: 250 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB

Location: ELEC B520 Mounting: Surface A.I.C. Rating:

Panel: LS5B-1

0.31 kVA 0.39 kVA (0 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Est. Demand: 0 A

Total Conn.: 0 A

Total Est. Demand: 385 VA

Total Conn. Load: 308 VA

Lighting 308 VA 125.00% 385 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 0.00 kVA 0.00 kVA 0.31 kVA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Space -- 1 -- -- 1 -- Space 34

31 Space -- 1 -- -- 1 -- Space 32

29 Space -- 1 -- -- 1 -- Space 30

27 Space -- 1 -- -- 1 -- Space 28

25 Space -- 1 -- -- 1 -- Space 26

23 Space -- 1 -- -- 1 -- Space 24

21 Space -- 1 -- -- 1 -- Space 22

19 Space -- 1 -- -- 1 -- Space 20

17 Space -- 1 -- -- 1 -- Space 18

15 Space -- 1 -- -- 1 -- Space 16

13 Space -- 1 -- -- 1 -- Space 14

11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12

9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10

7 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 8

5 Spare 20 A 1 0 VA 308 VA 1 20 A Lighting Room C5-50,... 6

3 Spare 20 A 1 0 VA 0 VA 1 20 A EXISITNG 4

1 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 480/277 Wye-3PH-4W Mains Rating: 250 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB

Location: ELEC A578 Mounting: Surface A.I.C. Rating:

Panel: LS5C-1

1.5 kVA 1.5 kVA (4 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: $ = PROVIDE GROUND FAULT BREAKER.

Total Est. Demand: 4 A

Total Conn.: 4 A

Total Est. Demand: 1500 VA

Total Conn. Load: 1500 VA

Receptacle 1500 VA 100.00% 1500 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 1.50 kVA 0.00 kVA 0.00 kVA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 EXISTING 20 A 1 0 VA -- 1 -- Space 38

35 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 36

33 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 34

31 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 32

29 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 30

27 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 28

25 $ MICROWAVE 20 A 1 1500... 0 VA 1 20 A EXISTING 26

23 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 24

21 Space -- 1 -- 0 VA 1 20 A EXISTING 22

19 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 20

17 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 18

15 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 16

13 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 14

11 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 12

9 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 10

7 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 8

5 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 6

3 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 4

1 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 100 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB

Location: ELEC B520 Mounting: Surface A.I.C. Rating:

Panel: RB5-1

Revisions Date

3.38 kVA 4.22 kVA (5 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Est. Demand: 5 A

Total Conn.: 4 A

Total Est. Demand: 4224 VA

Total Conn. Load: 3380 VA

Lighting 3380 VA 125.00% 4224 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 1.28 kVA 1.05 kVA 1.04 kVA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Space -- 1 -- -- 1 -- Space 34

31 Space -- 1 -- -- 1 -- Space 32

29 Space -- 1 -- -- 1 -- Space 30

27 Space -- 1 -- -- 1 -- Space 28

25 Space -- 1 -- -- 1 -- Space 26

23 Space -- 1 -- -- 1 -- Space 24

21 Space -- 1 -- -- 1 -- Space 22

19 Space -- 1 -- -- 1 -- Space 20

17 Space -- 1 -- -- 1 -- Space 18

15 Space -- 1 -- -- 1 -- Space 16

13 Space -- 1 -- -- 1 -- Space 14

11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12

9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10

7 Lighting Room 505,... 20 A 1 1284... 0 VA 1 20 A Spare 8

5 Lighting Room 526, 51... 20 A 1 1044... 0 VA 1 20 A Spare 6

3 EXISTING 20 A 1 0 VA 1052... 1 20 A Lighting Room 523, 52... 4

1 EXISTING 20 A 1 0 VA 0 VA 1 20 A EXISTING 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 480/277 Wye-3PH-4W Mains Rating: 250 A Supply From: Enclosure: Type 1 Mains Type: 225 A MB

Location: ELEC A578 Mounting: Surface A.I.C. Rating:

Panel: CL5C-1

2.59 kVA 2.59 kVA (7 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: $ = NPROVIDE GROUND FAULT BREAKER.

Total Est. Demand: 7 A

Total Conn.: 7 A

Total Est. Demand: 2590 VA

Total Conn. Load: 2590 VA

Receptacle 2590 VA 100.00% 2590 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals

Total Load: 0.72 kVA 1.51 kVA 0.36 kVA

41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42

39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40

37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38

35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36

33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34

31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32

29 Spare…