Attachment 1 - PDO Project Drawings.pdf

PDF 38 MB Posted

Attached to
Petersburg Office Consolidation
Solicitation number
1240BJ24R0018
Issued by

About this file

This document appears to be the Attachment 1 - PDO Project Drawings related to the federal contract opportunity for the Petersburg Office Consolidation project. The federal contract opportunity is a solicitation (Solicitation Number: 1240BJ24R0018) issued by the Department of Agriculture Forest Service for the PDO Consolidation and Work Center Replacement in Petersburg, AK; Tongass NF. Key details include:

The solicitation packet includes a virtual pre-proposal meeting scheduled for Thursday, July 25, 2024 from 1000 - 1200 (Alaska Time, ADT) via Microsoft Teams. Attendees must contact Logan Wild (logan.wild@usda.gov) by 2:00 pm ADT on 07/24/2024 to provide names and email addresses. The cut-off for questions (RFIs) to the solicitation will be close of business (1630 ADT) on Friday, August 9, 2024. No substitution requests will be considered prior to award, and offerors must respond as described in Sections L and M. Proposals that fail to provide a complete response to the Technical Evaluation Factors (Section M) may be rejected and not considered further.

View the file

Other files

File Type Posted
Attachment 17_AK0514ZZ 1988-06-14 - SPRINKLERS PLANS SECTION DETAIL.pdf PDF
Attachment 19_Addendum to model change for heat pumps.pdf PDF
Attachment 18_Wage Determination AK20240001 7.19.24.pdf PDF
Amendment 3 SF30 - 1240BJ24R0018.pdf PDF
Attachment 16_087100-DR-HDWR-SETS_REVISED_240813.pdf PDF
Attachment 15_RFIs_PDO Consolidation.pdf PDF
Attachment 14_Harris 100 percent drawings addendum.pdf PDF
Amendment 2 - Summary of Changes.pdf PDF
Amendment 2 SF30 - 1240BJ24R0018.pdf PDF
Attachment 13_Fram 100 percent drawings addendum.pdf PDF
1240BJ24R0018 Amendment 1 - Solicitation Packet.pdf PDF
Attachment 12 - Guiding Principles checklist for PDO_info only.pdf PDF
Attachment 9 - Drawings_Harris Bldg Renovation 100 Percent.pdf PDF
1240BJ24R0018 Amendment 1 - SF30.pdf PDF
Attachment 11 - 01 25 00-RIB-Substitution Procedures.pdf PDF
Attachment 10 - Drawings_Fram Parking Expansion 100 Percent.pdf PDF
Attachment 3a - Harris Project Drawings 90 Percent.pdf PDF
1240BJ24R0018 Solicitation Packet.pdf PDF
Attachment 6 - Past Performance.pdf PDF
Attachment 3b - Harris Drawings Addendum 90 Percent.pdf PDF
Attachment 8 - SF24 Bid Bond.pdf PDF
Attachment 5 - Wage Determination AK20240001.pdf PDF
Attachment 4 - Fram Project Drawings 90 Percent.pdf PDF
Attachment 2 - PDO Project Specifications.pdf PDF
Attachment 7 - RFI Template for PDO_Harris_Fram.xlsx XLSX spreadsheet
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOTIFICATION OF POTENTIAL HAZARDS

ASBESTOS, LEAD, AND OTHER HAZARDOUS MATERIALS ARE PRESENT IN THE BUILDING

AND MAY IMPACT THE WORK OF ALL TRADES. REGULATED AIR CONTAMINANTS,

INCLUDING ASBESTOS AND LEAD, ARE ALSO PRESENT IN SETTLED AND CONCEALED

DUST IN AND ON ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL

COMPONENTS OR SYSTEMS THROUGHOUT THE BUILDING. ALL TRADES SHALL

COORDINATE WITH OTHER TRADES AND CONDUCT THEIR WORK TO PREVENT WORKER

EXPOSURE OR SITE CONTAMINATION. REFER TO SPECIFICATION DIVISIONS 0, 1, AND 2

FOR SPECIFIC INFORMATION CONCERNING DISTURBING, REMOVING, AND DISPOSING OF

THESE MATERIALS AND THE INSTALLATION OF THE NEW MATERIALS OR COMPONENTS.

THIS NOTIFICATION IS PROVIDED IN ACCORDANCE WITH EPA AND OSHA REQUIREMENTS.

AK

SAL

AFOETATS

T

CETIHCRALANOISSEFOR

PDE

RE

TS

I

GE

R

No. A-140412

JUSTIN M. SCANIO

TH49

06.26.2024

N S

TR

EE

T, S

UI

TE

A N C

HO

RA

G E, A

LA

SK

A

7.

1.

E

CI

/H ye r, In c.

C

HE

C

KE

D

A

UT

HO

R:

PR

O

JE

C T N O

IS

SU

E D A

TE

RE

V

IS

IO

N

FULL SIZE PRINTED ON 22 x 34

G0.01

SH

EE

T I N

DE

X

-0 6.

C W R

JM

S

.2 6.

PE

TE

RS

BU

RG

O

FF

IC

E C O N

SO

LI

DA

TIO

N

W O

RK

C

EN

TE

R

RE

PL

A C

EM

EN

T - D

IS

TR

IC

T

O

FF

IC

E

C O N

ST

RU

C

TIO

N D O C

UM

EN

TS

0 - TITLESHEET

G0.00 TITLESHEET

1 - GENERAL

G0.01 SHEET INDEX

G1.01 GENERAL INFO & TYP MOUNTING HEIGHTS

G1.02 CODE ANALYSIS

G1.03 CODE PLANS

1 - HAZARDOUS MATERIALS

H0.1 HAZARDS ABATEMENT NOTES AND QUANTITIES

H1.0 HAZARDS ABATEMENT - PDO BUILDING FIRST FLOOR

H1.1 HAZARDS ABATEMENT - PDO BUILDING SECOND FLOOR

H1.2 HAZARDS ABATEMENT - ROOF AND PENTHOUSE

2 - CIVIL AND LANDSCAPE

C.0 PETERSBURG DISTRICT OFFICE EXISTING GENERAL NOTES, LEGEND, AND ABBREVIATIONS

C.1 PETERSBURG DISTRICT OFFICE EXISTING CONDITIONS AND DEMOLITION PLAN

C.2 PETERSBURG DISTRICT OFFICE SITE PLAN

C.3 PETERSBURG DISTRICT OFFICE GRADING PLAN

C.4 PETERSBURG DISTRICT OFFICE GRADING LAYOUT INFORMATION

C.5 PETERSBURG DISTRICT OFFICE CIVIL TYPICAL SECTIONS

C.6 PETERSBURG DISTRICT OFFICE CIVIL DETAILS (1 OF 3)

C.7 PETERSBURG DISTRICT OFFICE CIVIL DETAILS (2 OF 3)

C.8 PETERSBURG DISTRICT OFFICE CIVIL DETAILS (3 OF 3)

L1.01 SITE AND SOILS PLAN AND LANDSCAPE DEMO PLAN

L1.02 PLANTING PLAN

L5.01 DETAILS AND PLANTING SCHEDULES

L5.02 DETAILS

L5.03 DETAILS

3- STRUCTURAL

S0.01 STRUCTURAL GENERAL NOTES

S0.02 SPECIAL INSPECTIONS AND TESTING

S1.12 DEMO FLOOR FRAMING PLAN LEVEL 2

S2.13 FOUNDATION PLAN

S2.14 FLOOR FRAMING PLAN LEVEL 2

S2.15 ROOF FRAMING PLANS

S5.01 BUILDING SECTIONS

S6.01 INTERIOR CONCRETE DETAILS

S6.11 EXTERIOR CONCRETE DETAILS

S6.21 INTERIOR FRAMING DETAILS

S6.31 EXTERIOR FRAMING DETAILS

4 - ARCHITECTURAL

A1.01 ASSEMBLIES

A2.01 DEMO FLOOR PLAN LEVEL 1

A2.02 DEMO FLOOR PLAN LEVEL 2

A2.03 DEMO ROOF PLANS

A2.04 DEMO REFLECTED CEILING PLAN LEVEL 1

A2.05 DEMO REFLECTED CEILING PLAN LEVEL 2

A2.11 FLOOR PLAN LEVEL 1

A2.12 FLOOR PLAN LEVEL 2

A2.13 ROOF PLANS

A3.11 ENLARGED PLANS

A3.12 ENLARGED PLANS - TOILET ROOMS

A3.21 STAIR PLANS, SECTIONS & DETAILS

A3.22 STAIR PLANS, SECTIONS & RAILING DETAILS

A4.01 EXTERIOR ELEVATIONS EAST & WEST

A4.02 EXTERIOR ELEVATIONS NORTH & SOUTH

A5.01 BUILDING SECTIONS E-W

A5.02 BUILDING SECTIONS N-S

A6.01 WALL SECTIONS

A8.01 INTERIOR ELEVATIONS LEVEL 1

A8.02 INTERIOR ELEVATIONS LEVEL 1 CONT.

A8.03 INTERIOR ELEVATIONS LEVEL 2

A8.04 INTERIOR ELEVATIONS LEVEL 2 CONT.

A9.01 REFLECTED CEILING PLAN LEVEL 1

A9.02 REFLECTED CEILING PLAN LEVEL 2

A10.01 EXTERIOR & VESTIBULE DETAILS - SECTION

A10.02 EXTERIOR DETAILS - SECTION

A10.03 EXTERIOR DETAILS - SECTION

A10.04 EXTERIOR DETAILS - SECTION

A10.05 EXTERIOR DETAILS - SECTION

A10.11 EXTERIOR DETAILS - PLAN

A10.12 EXTERIOR DETAILS - PLAN

A10.21 EXTERIOR DETAILS - OPENINGS

A10.22 EXTERIOR DETAILS - OPENINGS

A11.01 INTERIOR DETAILS

A11.02 INTERIOR DETAILS

A11.03 INTERIOR DETAILS

A11.04 INTERIOR DETAILS

A12.01 DOOR SCHEDULE

A12.02 WINDOW SCHEDULE

A12.03 FINISH PLANS, INTERIOR ROOM AND MATERIAL SCHEDULES

A12.04 SIGNAGE AND EQUIPMENT SCHEDULE

A12.11 FURNITURE & SIGNAGE PLANS

5 - MECHANICAL

M0.01 MECHANICAL LEGEND

M0.02 MECHANICAL SCHEDULES

M0.03 MECHANICAL SCHEDULES

M0.04 MECHANICAL SCHEDULES

M1.00 UNDERFLOOR PLAN - MECHANICAL - DEMOLITION

M1.01 LEVEL 1 FLOOR PLAN - PLUMBING - DEMOLITION

M1.02 LEVEL 2 FLOOR PLAN - PLUMBING - DEMOLITION

M1.03 LEVEL 1 FLOOR PLAN - PIPING - DEMOLITION

M1.04 LEVEL 2 FLOOR PLAN - PIPING - DEMOLITION

M1.05 LEVEL 1 FLOOR PLAN - VENTILATION - DEMOLITION

M1.06 LEVEL 2 FLOOR PLAN - VENTILATION - DEMOLITION

M1.07 ROOF PLAN - MECHANICAL - DEMOLITION

M1.08 ENLARGED PENTHOUSE PLAN - DEMOLITION

M1.09 ENLARGED BOILER ROOM PLAN - DEMOLITION

M2.00 UNDERFLOOR PLAN - MECHANICAL

M2.01 LEVEL 1 FLOOR PLAN - PLUMBING

M2.02 LEVEL 2 FLOOR PLAN - PLUMBING

M2.03 LEVEL 1 FLOOR PLAN - PIPING

M2.04 LEVEL 2 FLOOR PLA N- PIPING

M2.05 LEVEL 1 FLOOR PLAN - VENTILATION

M2.06 LEVEL 2 FLOOR PLAN - VENTILATION

M2.07 ROOF PLAN - MECHANICAL

M2.08 ENLARGED PENTHOUSE PLAN

M2.09 ENLARGED BOILER ROOM PLAN

M2.10 ENLARGED PLUMBING PLANS

M3.01 DIAGRAMS - PLUMBING

M3.02 DIAGRAMS - PLUMBING

M3.03 DETAILS - PLUMBING

M3.04 DETAILS - PLUMBING

M4.01 DIAGRAMS - HEATING AND COOLING

M4.02 DIAGRAMS - HEATING AND COOLING

M4.03 DIAGRAMS - HEATING AND COOLING

M4.04 DETAILS - HEATING AND COOLING

M4.05 DETAILS - HEATING AND COOLING

M5.01 DIAGRAMS - VENTILATION

M5.02 DETAILS - VENTILATION

M5.03 DETAILS - VENTILATION

6 - ELECTRICAL

E0.01 ELECTRICAL LEGEND

E0.02 LIGHTING FIXTURES AND LIGHTING CONTROL SCHEDULES

E0.03 PANEL SCHEDULES - LEVEL 1 480V

E0.04 PANEL SCHEDULES - LEVEL 1 208V

E0.05 PANEL SCHEDULES - LEVEL 1 208V

E0.06 PANEL SCHEDULES - LEVEL 2 & PENTHOUSE

E1.00 SITE PLAN - ELECTRICAL

E1.10 OVERALL PLAN - ELECTRICAL

E1.11 OVERALL PLAN - PUBLIC ADDRESS

E1.20 LEVEL 1 FLOOR PLAN - LIGHTING - DEMO

E1.21 LEVEL 2 FLOOR PLAN - LIGHTING - DEMO

E1.30 LEVEL 1 FLOOR PLAN - POWER - DEMO

E1.31 LEVEL 2 FLOOR PLAN - POWER - DEMO

E1.40 LEVEL 1 FLOOR PLAN - SPECIAL SYSTEMS - DEMO

E1.41 LEVEL 2 FLOOR PLAN - SPECIAL SYSTEMS - DEMO

E2.00 LEVEL 1 FLOOR PLAN - LIGHTING

E2.01 LEVEL 2 FLOOR PLAN - LIGHTING

E3.00 LEVEL 1 FLOOR PLAN - POWER

E3.01 LEVEL 2 FLOOR PLAN - POWER

E4.00 LEVEL 1 FLOOR PLAN - SPECIAL SYSTEMS

E4.01 LEVEL 2 FLOOR PLAN - SPECIAL SYSTEMS

E5.01 ENLARGED PLAN - PENTHOUSE

E5.02 ENLARGED PLAN - ELECTRICAL

E6.00 DETAILS - ELECTRICAL

E7.01 DETAILS AND DIAGRAMS - SECURITY

E7.02 DIAGRAM - TELECOM ONE-LINE

E7.03 DIAGRAMS - PAGING SYSTEM

E7.04 DIAGRAMS - AV SYSTEM

E8.00 DIAGRAM - POWER ONE-LINE

SHEET INDEX

ABBREVIATIONS

ABV ABOVE

AFF ABOVE FINISH FLOOR

ALT ALTERNATE

ANO ANODIZED

ARCH ARCHITECTURAL

BD BOARD

BLDG BUILDING

BLK BLOCK

BLW BELOW

BO BOTTOM OF

BOF BOTTOM OF FINISH

BCS BABY CHANGING STATION

CIP CAST IN PLACE

CF CUBIC FOOT

CFOI CONTRACTOR FURNISHED OWNER INSTALLED

CL CENTERLINE

CONC CONCRETE

CONT CONTINUOUS

CTR CENTER

DIA DIAMETER

DIM DIMENSION

DWG DRAWING

EA EACH

EL ELEVATION

ELEC ELECTRICAL

EQ EQUAL

EQUIP EQUIPMENT

FAF FLUID APPLIED FLOORING

FD FRAME DIMENSION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FINISHED FLOOR

FO FACE OF

FOC FACE OF CONCRETE

FOF FACE OF FINISH

FOS FACE OF STUD

FRT FIRE RETARDANT TREATED

FT FOOT, FEET

FURR FURRING

GA GUAGE

GALV GALVANIZED

GB GRAB BAR

INCL INCLUDE, INCLUDED

INSUL INSULATION

INT INTERIOR

LSG LAMINATED SAFETY GLAZING

LH LEFT HAND

MAX MAXIMUM

MFR MANUFACTURER

MKBD MARKERBOARD

MIN MINIMUM

MIRR MIRROR

MTL METAL

NA NOT APPLICABLE

NIC NOT IN CONTRACT

OD OUTSIDE DIAMETER

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

OFOI OWNER FURNISHED OWNER INSTALLED

OH OVERHEAD

PAR PARTITION

PERF PERFORATED

PLAM PRESSURE TREATED LAMINATE

PLY PLYWOOD

PTD PAPER TOWEL DISPENSER

PT PAINT

RCP REFLECTED CEILING PLAN

REBAR/RB REINFORCING BARS

REF REFERENCE

REQD REQUIRED

RO ROUGH OPENING

SD SOAP DISPENSER

SECT SECTION

SCHED SCHEDULE

SIM SIMILAR

SND SANITARY NAPKIN DISPOSAL

SPEC SPECIFICATION

SS STAINLESS STEEL

GWB GYPSUM WALL BOARD

GYP GYPSUM WALL BOARD

HD HAND DRYER

HDWR HARDWARE

HR HOUR

HT HEIGHT

ID INSIDE DIAMETER

STD STANDARD

STL STEEL

STRUCT STRUCTURAL

TBD TO BE DETERMINED

TDWR TOWEL DISPENSER/WASTE RECEPTICAL

THERM THERMOSTAT

TOB TOP OF BEAM

TOC TOP OF CONCRETE

TOS TOP OF STEEL

TTD TOILET TISSUE DISPENSER

TSCD TOILET SEAT COVER DISPENSER

TYP TYPICAL

UL UNDERWRITERS LABORATORY CERTIFIED

UNFIN UNFINISHED

UNO UNLESS NOTED OTHERWISE

VIF VERIFY IN FIELD

WD WOOD

SYMBOLS

GRID LINE INDICATION

ROOM IDENTIFICATION

ROOM NAME

ROOM NUMBER

AREA / OCCUPANCY

A

INTERIOR / EXTERIOR ELEVATION

DASH INDICATES NO ELEVATION

BUILDING SECTION

SECTION NUMBER

SECTION SHEET

DETAIL

DETAIL NUMBER

DETAIL SHEET

DOOR NUMBER

REFER TO DOOR SCHEDULE

JJ

WINDOW TYPE

REFER TO WINDOW SCHEDULE

A1

WALL TYPE INDICATOR

REFER TO WALL LEGEND

WORK POINT

(CONTROL or DATUM POINT)

WALL SECTION

SECTION NUMBER

SECTION SHEET

FLOOR, CEILING, ROOF TYPE INDICATOR

REFER TO FLOOR, CEILING, ROOF LEGENDF1

KEYNOTE

REFER TO NOTES LISTED ON SHEET1

XXXX -

XX

XX

XX

XX

XX

XX

OFFICE

4 OCC

CEILING TYPE

REFER TO ASSEMBLIES; ELEVATION NOTED ABOVE SLAB10'-0"

C3

MATERIALS

METAL (SECTION)

WOOD, CONTINUOUS (SECTION)

WOOD, BLOCKING (SECTION)

FILL (SECTION)

PLYWOOD (SECTION)

EARTH (SECTION)

FINISH CARPENTRY (SECTION)

GYPSUM BOARD (SECTION)

INSULATION, BATT (PLAN & SECTION)

INSULATION, RIGID (PLAN & SECTION)

CONCRETE (SECTION)

STONE (PLAN)

MINERAL WOOD INSULATION (PLAN & SECTION)

1.

2.

A.

B.

C.

D.

E.

3.

4.

5.

6.

7.

8.

9.

CONSTRUCTION TO BE IN COMPLIANCE WITH ALL FEDERAL,

STATE, AND LOCAL BUILDING CODES AND REGULATIONS.

EXISTING CONDITIONS:

CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS

PRIOR TO COMMENCEMENT OF WORK AND NOTIFY

CONTRACTING OFFICER OF ANY DISCREPANCIES WITH

CONDITIONS AS SHOWN IN DOCUMENTS.

ALL DIMENSIONS OF EXISTING CONSTRUCTION SHOWN

ON THE DRAWINGS ARE INTENDED AS GUIDELINES ONLY

AND MUST BE VERIFIED.

THE EXISTING CONDITIONS SHOWN ON THE DRAWINGS

ARE BASED ON EITHER LIMITED AS-BUILTS AND/OR

LIMITED ORIGINAL DRAWINGS. IF THE EXISTING

CONDITIONS DO NOT CLOSELY MATCH THE CONDITIONS

SHOWN ON THE DRAWINGS, OR IF THE EXISTING

MATERIALS ARE OF QUESTIONABLE OR SUBSTANDARD

QUALITY, NOTIFY THE CONTRACTING OFFICER PRIOR TO

COMMENCING WORK.

PROTECT ANY EXISTING CONSTRUCTION FROM DAMAGE

AT ALL TIMES DURING WORK.

SALVAGE ALL ITEMS THAT ARE TO BE REMOVED BUT

NOT REPURPOSED AND THAT ARE IN GOOD CONDITION

ARE TO BE PROTECTED AND DONATED.

ALL DIMENSIONS ARE TO GRIDLINE OR FACE OF STUD UNLESS

OTHERWISE NOTED. "CLR" REFERS TO FACE OF FINISH EACH

SIDE.

WORK AREAS TO BE LEFT CLEAN AND FREE OF ANY DEBRIS AT

THE END OF EACH SHIFT.

PROVIDE CONCEALED FRAMING WHERE HEIGHT EXCEEDS

LIMITING HEIGHT OF STUD SIZE.

PROVIDE BACKING AS REQUIRED FOR CASEWORK AND OTHER

ITEMS THAT ARE WALL SUPPORTED.

SEE MECHANICAL AND PLUMBING DRAWINGS FOR LOCATION

AND TYPE OF PLUMBING FIXTURES.

IN CASE OF A CONFLICT IN THE DOCUMENTS, THE

CONTRACTOR SHALL ASSUME THE GREATER VALUE OF SUCH

CIRCUMSTANCES.

DOORS ROUGH OPENING SHALL BE LOCATED 6" FROM

ADJACENT WALL FINISH UNLESS NOTED OTHERWISE.

GENERAL NOTES & EXISTING

CONDITIONS

1.

2.

3.

PROVIDE SOLID BACKING FOR ALL ACCESSORIES.

ELEVATIONS SHOWN HEREIN REPRESENT TYPICAL

REQUIREMENTS.

INSTALLATION OF ALL SANITARY FACILITIES ACCESSIBLE

TO THE DISABLED SHALL COMPLY WITH THIS DETAIL &

APPLICABLE REGULATORY REQUIREMENTS.

MOUNTING HEIGHT NOTES

ABA MOUNTING HEIGHTS TOILET ROOM ACCESSORIES

ACCESSIBLE

LAVATORY

COUNTER WITH UNDERMOUNT SINK

SINK

HOOK

GB48

ACCESSIBLE TOILET STALL

GB36

WC

3'-6"

6"

GB18

3'-4"

G R

IP

S

U R

FA

C

E

M

AX

-3

6" T

O

" M

IN

M

AX

AB

A

4' -0

1'-6"

DISPENSER/

WASTE RECEPTACLE

TDWR

TSCD

" M

IN

SND

TTD 2'

-1

0"

1'-6" 1'-6"

PROVIDE SEMI RIGID SOUND

INSULATION AROUND TSCD,

TYP

TO

B

O

TT

O M

M

IR

R O

R M

AX

0"

2' -1

1/

2"

3' -9

/2

1.

5"

M

IN

12" MAX

THERM

THERM-

OSTAT

LIGHT SWITCH

FEC

ELEC/TEL/DATA

OUTLET @ DOOR

MP

E/DT E/DT

ELEC/TEL/DATA

OUTLET @

WALL

LS

FIRE

EXTINGUISHER

CABINET

3'

7" 5'

0"

4'

6" T

O F

E M

O U

N T

4'

0" M

AX

T

O H

D W

R

8"

3'

7"

1'

6"

3'

7"

1'

6"

TO

P

U

SH

B U

TT

O

N

SO

AP

D

IS

P.

" M

AX

2' -3

BABY CHANGING

STATION

MIRR

SD

MIRR

BCS

NOTIFICATION OF POTENTIAL HAZARDS

ASBESTOS, LEAD, AND OTHER HAZARDOUS MATERIALS ARE PRESENT IN THE BUILDING

AND MAY IMPACT THE WORK OF ALL TRADES. REGULATED AIR CONTAMINANTS,

INCLUDING ASBESTOS AND LEAD, ARE ALSO PRESENT IN SETTLED AND CONCEALED

DUST IN AND ON ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL

COMPONENTS OR SYSTEMS THROUGHOUT THE BUILDING. ALL TRADES SHALL

COORDINATE WITH OTHER TRADES AND CONDUCT THEIR WORK TO PREVENT WORKER

EXPOSURE OR SITE CONTAMINATION. REFER TO SPECIFICATION DIVISIONS 0, 1, AND 2

FOR SPECIFIC INFORMATION CONCERNING DISTURBING, REMOVING, AND DISPOSING OF

THESE MATERIALS AND THE INSTALLATION OF THE NEW MATERIALS OR COMPONENTS.

THIS NOTIFICATION IS PROVIDED IN ACCORDANCE WITH EPA AND OSHA REQUIREMENTS.

AK

SAL

AFOETATS

T

CETIHCRALANOISSEFOR

PDE

RE

TS

I

GE

R

No. A-140412

JUSTIN M. SCANIO

TH49

06.26.2024

N S

TR

EE

T, S

UI

TE

A N C

HO

RA

G E, A

LA

SK

A

7.

1.

E

CI

/H ye r, In c.

C

HE

C

KE

D

A

UT

HO

R:

PR

O

JE

C T N O

IS

SU

E D A

TE

RE

V

IS

IO

N

FULL SIZE PRINTED ON 22 x 34

G1.01

G

EN

ER

A L

IN

FO

TY

P M O

UN

TIN

G H

EI

G

HT

S

-0 6.

C W R

JM

S

.2 6.

PE

TE

RS

BU

RG

O

FF

IC

E C O N

SO

LI

DA

TIO

N

W O

RK

C

EN

TE

R

RE

PL

A C

EM

EN

T - D

IS

TR

IC

T

O

FF

IC

E

C O N

ST

RU

C

TIO

N D O C

UM

EN

TS

NOTIFICATION OF POTENTIAL HAZARDS

ASBESTOS, LEAD, AND OTHER HAZARDOUS MATERIALS ARE PRESENT IN THE BUILDING

AND MAY IMPACT THE WORK OF ALL TRADES. REGULATED AIR CONTAMINANTS,

INCLUDING ASBESTOS AND LEAD, ARE ALSO PRESENT IN SETTLED AND CONCEALED

DUST IN AND ON ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL

COMPONENTS OR SYSTEMS THROUGHOUT THE BUILDING. ALL TRADES SHALL

COORDINATE WITH OTHER TRADES AND CONDUCT THEIR WORK TO PREVENT WORKER

EXPOSURE OR SITE CONTAMINATION. REFER TO SPECIFICATION DIVISIONS 0, 1, AND 2

FOR SPECIFIC INFORMATION CONCERNING DISTURBING, REMOVING, AND DISPOSING OF

THESE MATERIALS AND THE INSTALLATION OF THE NEW MATERIALS OR COMPONENTS.

THIS NOTIFICATION IS PROVIDED IN ACCORDANCE WITH EPA AND OSHA REQUIREMENTS.

AK

SAL

AFOETATS

T

CETIHCRALANOISSEFOR

PDE

RE

TS

I

GE

R

No. A-140412

JUSTIN M. SCANIO

TH49

06.26.2024

N S

TR

EE

T, S

UI

TE

A N C

HO

RA

G E, A

LA

SK

A

7.

1.

E

CI

/H ye r, In c.

C

HE

C

KE

D

A

UT

HO

R:

PR

O

JE

C T N O

IS

SU

E D A

TE

RE

V

IS

IO

N

FULL SIZE PRINTED ON 22 x 34

G1.02

C O

DE

A N A

LY

SI

S

-0 6.

C W R

JM

S

.2 6.

PE

TE

RS

BU

RG

O

FF

IC

E C O N

SO

LI

DA

TIO

N

W O

RK

C

EN

TE

R

RE

PL

A C

EM

EN

T - D

IS

TR

IC

T

O

FF

IC

E

C O N

ST

RU

C

TIO

N D O C

UM

EN

TS

AUTHORITY HAVING JURISDICTION: US FOREST SERVICE

PROJECT DESCRIPTION: THIS PROJECT IS REPLACEMENT OF A

MECHANICAL SYSTEM, MODIFICATION OF EXTERIOR ENVELOPE, AND

INTERIOR REFINISHING AND RENOVATION IN A TWO-STORY BUILDING IN

DOWNTOWN PETERSBURG. THE BUILDING HAS A GROUP B OCCUPANCY,

IS TYPE V-B, AND FULLY SPRINKLERED.

OWNER: U.S. FOREST SERVICE

PROPERTY LEGAL DESCRIPTION: BLOCK 37 PETERSBURG TOWNSITE,

USSN 1252

PROPERTY ADDRESS: 12 N NORDIC DR, PETERSBURG, AK 99833

APPLICABLE CODES

PETERSBURG CITY CODE TITLE 19 - ZONING

2021 INTERNATIONAL BUILDING CODE

2021 INTERNATIONAL FIRE CODE

2021 INTERNATIONAL EXISTING BUILDING CODE

2021 INTERNATIONAL ENERGY CONSERVATION CODE

2021 INTERNATIONAL MECHANICAL CODE

2018 UNIFORM PLUMBING CODE

1968 ARCHITECTURAL BARRIERS ACT (GOVERNING), 2017 ICC/ANSI

A117.1, IBC CHAPTER 11 FOR ACCESSIBILITY, AND 2010 ADA

STANDARDS FOR ACCESSIBLE DESIGN

2021 NFPA

36 CFR PART 68 (SOI STANDARDS FOR THE TREATMENT OF

HISTORIC PROPERTIES)

CODE ANALYSIS

2021 INTERNATIONAL EXISTING BUILDING CODE

202 GENERAL DEFINITIONS:

ALTERATION. ANY CONSTRUCTION OR RENOVATION TO AN

EXISTING STRUCTURE OTHER THAN A REPAIR OR ADDITION. THIS

PROJECT INCLUDES ALTERATIONS TO THE EXISTING BUILDING.

PROJECT DOES NOT INCREASE BUILDING AREA CONSTITUTING AN

ADDITION.

202 GENERAL DEFINITIONS:

ALASKA SHPO HAS DETERMINED THE BUILDING IS ELIGIBLE FOR

LISTING ON THE NATIONAL REGISTER UNDER CRITERIA A AND C.

CRITERIA A:

SITES, BUILDINGS, STRUCTURES THAT ARE ASSOCIATED WITH

EVENTS THAT HAVE MADE A SIGNIFICANT CONTRIBUTION TO THE

BROAD PATTERNS OF OUR HISTORY.

CRITERIA C:

SITES, BUILDINGS, STRUCTURES THAT EMBODY THE DISTINCTIVE

CHARACTERISTICS OF A TYPE, PERIOD, OR METHOD OF

CONSTRUCTION, OR THAT REPRESENT THE WORK OF A MASTER,

OR THAT POSSESS HIGH ARTISTIC VALUES, OR THAT REPRESENT

A SIGNIFICANT AND DISTINGUISHABLE ENTITY WHOSE

COMPONENTS MAY LACK INDIVIDUAL DISTINCTION.

202 GENERAL DEFINITIONS:

REPAIR. THE RECONSTRUCTION, REPLACEMENT, OR RENEWAL OF

ANY PART OF AN EXISTING BUILDING FOR THE PURPOSE OF ITS

MAINTENANCE OR TO CORRECT DAMAGE.

THIS PROJECT CONSTITUTES REPAIRS TO EXTERIOR ELEMENTS

ON BUILDING. BROKEN OR MISSING ELEMENTS ARE BEING

REPLACED OR RECONSTRUCTED IN KIND AND EXISTING ELEMENTS

IN GOOD CONDITION ARE BEING RENEWED.

301.2 REPAIRS:

REPAIRS SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER

4. SEE DISCUSSION BELOW

301.3 ALTERATION, ADDITION, OR CHANGE OF OCCUPANCY:

PROJECT WILL USE PRESCRIPTIVE COMPLIANCE METHOD PER

301.3.1. SEE DISCUSSION BELOW.

302.3 EXISTING MATERIALS:

BUILDING CONTAINS HAZARDOUS MATERIALS. WORK WILL ONLY

DISTURB AND ABATE THOSE MATERIALS AS NECESSARY TO

COMPLETE THE WORK.

306.2 DESIGN:

BUILDING COMPLIES WITH ICC A117.1. SEE DISCUSSION BELOW.

306.3 MAINTENANCE AND REPAIR:

PROJECT WILL MAINTAIN EXISTING ACCESSIBILITY TO BUILDINGS.

SEE DISCUSSION BELOW.

TITLE 19

19.04.585 PARKING DISTRICT:

SITE IS WITHIN PARKING DISTRICT 2 - EAST AND REQUIRES 70% OF

47 PARKING SPACES BASED ON BUILDING SIZE, WHICH IS 33. SITE

PROVIDES MORE THAN MINIMUM NUMBER REQUIRED.

19.32.060 [C-1, COMMERCIAL 1 DISTRICT] LOT, YARD, AND HEIGHT:

LOT ABUTS C-1 AND C-2 ZONING DISTRICTS SO NEEDS TO ONLY

MEET REQUIRED OFF-STREET PARKING REQUIREMENTS. BUILDING

IS 27'-6" HIGH, MEASURED TO TOP OF COPING OF MECHANICAL

PENTHOUSE. BUILDING IS TWO STORIES WITH A MECHANICAL

PENTHOUSE.

19.32.080 OFF-STREET PARKING AND LOADING - OTHER REQUIREMENTS:

A. OFF-STREET PARKING AND LOADING REQUIREMENTS SHALL BE

SPECIFIED IN CHAPTER 19.64 OF THIS TITLE. B. OTHER

DEVELOPMENT REQUIREMENTS SHALL BE STATED IN CHAPTER

19.60 OF THIS TITLE (YARDS AND LOTS): SEE DISCUSSION BELOW.

19.48.020 [P-1 DISTRICT, PUBLIC USE DISTRICT] USES PERMITTED:

BUILDING HAS SOLE OCCUPANCY BY THE US FOREST SERVICE, A

DIVISION OF THE FEDERAL GOVERNMENT. SEE DISCUSSION

BELOW.

19.64.010 PARKING AREAS - REQUIREMENTS ACCORDING TO USE:

BUILDING HAS APPRAISED VALUE OF $3.734 MILLION. PROJECT

COST EXCEEDS 50% OF VALUE. BUILDING IS 11,605 SF AND

REQUIRES 47 OFF-STREET PARKING SPACES..

19.64.040 DESIGN STANDARDS:

A. EACH PARKING SPACE SHALL CONTAIN NOT LESS THAN 8 FT

WIDE BY 20 FT LONG IN AREA EXCLUSIVE OF ACCESS AND

CIRCULATION AISLES. […] C. ANY LIGHTING OF PARKING LOTS

SHALL BE ARRANGED TO REFLECT AWAY FROM PUBLIC RIGHTS-

OF-WAY AND FROM ANY ADJOINING RESIDENTIAL AREA. SEE SITE

PLAN

19.64.070 PARKING AREAS - ACCESS:

[…] NO DRIVEWAY, PARKING LOT OR CURB CUTS IN ANY DISTRICT

SHALL EXCEED […] FORTY FEET IN WIDTH FOR COMMERCIAL […]

STRUCTURES, AND DETAILED PLANS FOR ALL CURB CUTS SHALL

BE SUBMITTED TO THE CITY ENGINEERING DEPARTMENT OR

DESIGNATED REPRESENTATIVE FOR APPROVAL BEFORE A PERMIT

SHALL BE ISSUED THEREFORE. SEE SITE PLAN.

19.64.080 LOADING AREAS - WHERE REQUIRED

LOADING AREA PROVIDED.

19.64.100 LOADING AREAS - ACCESS

LOADING AREA ACCESS FROM STREET VIA PARKING AREA.

306.7 ALTERATIONS

ALL NEW WORK COMPLIES WITH CHAPTER 11 OF THE IBC, ICC

A117.1, AND THE 1968 ABA, WITH THE EXCEPTION OF THE

EXTERIOR DOORS AT ENTRANCES TO THE SECOND FLOOR WHICH

DO NOT PROVIDE THE REQUIRED MANEUVERING CLEARANCES

FOR OPERATION. DOOR WIDTHS ARE INCREASED TO PROVIDE THE

MINIMUM CLEAR WIDTH OF DOORWAYS AND MECHANICAL

OPENERS ARE INSTALLED FOR THE EXTERIOR DOORS. INTERIOR

VESTIBULE DOORS MEET REQUIREMENTS FOR APPLICABLE

STANDARDS. SEE DISCUSSION BELOW FOR PLATFORM LIFTS.

306.7.8 PLATFORM LIFTS

BUILDING HAS PLATFORM LIFT. NO CHANGES PROPOSED TO LIFT.

309.2 [EXTERIOR WALL COVERINGS] ADDITIONS AND REPLACEMENTS:

PROJECT INVOLVES MODIFICATION OF EXTERIOR WALL ENVELOPE

FOR ENTIRETY OF BUILDING. NEW MATERIALS WILL COMPLY WITH

CHAPTERS 14 AND 26 OF THE IBC.

402.1 GLAZING IN HAZARDOUS LOCATIONS:

COMPLIES. GLAZING REPLACED IN ACCORDANCE WITH IBC.

501.2 FIRE-RESISTIVE RATINGS:

BUILDING IS FULLY SPRINKLERED PER THE IBC. ALL OTHER

ELEMENTS AND MATERIALS COMPLY WITH THE IBC. SEE

DISCUSSION BELOW.

503.1 [ALTERATION] GENERAL:

ALL ALTERATIONS COMPLY WITH THE IBC. EXISTING STAIR DOES

NOT COMPLY WITH SECTION 1011 OF THE IBC AND EXISTING

SPACE AND CONSTRUCTION DOES NOT ALLOW FOR

MODIFICATION. BUILDING IS HISTORIC AND STAIRWAY

CONTRIBUTES TO HISTORIC INTEGRITY. HISTORIC HANDRAIL

REMAINS UNALTERED PER EXCEPTION #2 AND SECTION 507. SEE

DISCUSSION BELOW.507.1 HISTORIC BUILDINGS:

THE PROVISIONS OF THIS CODE THAT REQUIRE IMPROVEMENTS

RELATIVE TO A BUILDING'S EXISTING CONDITION [...] SHALL NOT BE

MANDATORY FOR HISTORIC BUILDINGS UNLESS SPECIFICALLY

REQUIRED BY THIS SECTION.

507.2 LIFE SAFETY HAZARDS:

INTERIOR STAIR IS HISTORIC AND DOES NOT SERVE AS A

COMPONENT OF EGRESS AND DOES NOT APPEAR TO CONSTITUTE

A DISTINCT LIFE SAFETY HAZARD.

2021 INTERNATIONAL BUILDING CODE

202 DEFINITIONS:

AREA, BUILDING. THE AREA INCLUDED WITHIN SURROUNDING

EXTERIOR WALLS EXCLUSIVE OF VENT SHAFTS AND COURTS.

AREAS OF THE BUILDING NOT PROVIDED WITH SURROUNDING

WALLS SHALL BE INCLUDED IN THE BUILDING AREA IF SUCH AREAS

ARE INCLUDED WITHIN THE HORIZONTAL PROJECTION OF THE

ROOF OR FLOOR ABOVE.

SEE BUILDING AREA SUMMARY

302.1 [OCCUPANCY CLASSIFICATION AND USE] GENERAL:

BUILDING CONTAINS GROUP B WITH S-2 ACCESSORY SPACES AND

OCCUPANCIES. SEE BUILDING AREA TABLE FOR OCCUPANCY

CLASSIFICATIONS.

303.1.1 SMALL BUILDINGS AND TENANT SPACES:

A […] TENANT SPACE USED FOR ASSEMBLY PURPOSES WITH AN

OCCUPANT LOAD OF LESS THAN 50 PERSONS SHALL BE

CLASSIFIED AS A GROUP B OCCUPANCY.

CONFERENCE AND MEETING ROOMS USED FOR ASSEMBLY

PURPOSES HAVE OCCUPANT LOADS LESS THAN 50 AND

CLASSIFIED AS GROUP B OCCUPANCY.

304.1 BUSINESS GROUP B:

BUSINESS GROUP B OCCUPANCY INCLUDES, AMONG OTHERS, THE

USE OF A BUILDING [FOR] PROFESSIONAL SERVICES.

BUILDINGS USED FOR OFFICE PURPOSES.

311.3 LOW-HAZARD STORAGE, GROUP S-2

STORAGE ROOMS CONTAIN PRODUCTS CONSTITUTING S-2.

STORAGE OCCUPANCIES ARE ACCESSORY TO GROUP B.

502.1 ADDRESS IDENTIFICATION:

SEE NOTE ON ELEVATIONS.

503.1.2 BUILDINGS ON SAME LOT:

SITE CONTAINS STORAGE SHED. SHED AND PRIMARY BUILDING

CONSIDERED TWO SEPARATE BUILDINGS.

504.3 HEIGHT IN FEET:

SEE TABLE 504.3. BUILDING COMPLIES WITH TABLE ALLOWANCES.

SEE ELEVATIONS FOR BUILDING HEIGHT.

504.4 NUMBER OF STORIES:

SEE TABLE 504.4. BUILDING COMPLIES WITH TABLE ALLOWANCES.

506.2 ALLOWABLE AREA DETERMINATION:

SEE TABLE 506.2. BUILDING COMPLIES WITH TABLE ALLOWANCES.

SEE BUILDING AREA SUMMARY AND CODE PLANS FOR LEVEL

AREAS.

506.2.1 SINGLE-OCCUPANCY BUILDINGS:

SEE TABULATION BELOW.

BUILDING AREA (IBC CODE)

AREA TYPE NAME GROSS AREA

LEVEL 1 INTERIOR BUSINESS 5029 SF

LEVEL 1 EXTERIOR BUSINESS 310 SF

LEVEL 1 EXTERIOR BUSINESS 482 SF

101-L1-(26.25')-(E)FF 5821 SF

LEVEL 2 INTERIOR BUSINESS 5343 SF

LEVEL 2 EXTERIOR BUSINESS 21 SF

LEVEL 2 EXTERIOR BUSINESS 19 SF

201-L2-(E)FF 5383 SF

Grand total 11204 SF

TABLE 504.3: ALLOWABLE BLDG HEIGHT IN FT ABOVE GRADE PLANE

OCC CLASS SPRINKLER TYPE VALUE

B S V-B 60

TABLE 504.4: ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE

OCC CLASS SPRINKLER TYPE VALUE

B S V-B 3

TABLE 506.2: ALLOWABLE AREA FACTOR (At) IN SQUARE FEET

OCC CLASS SPRINKLER TYPE VALUE

B SM V-B 27,000

506.2.1: MAXIMUM ALLOWABLE AREA AA IN SQUARE FEET

AA = 33,750 SF PER STORY

At = 27,000

NS = 9,000

If = 0.75

506.3.1 [FRONTAGE INCREASE] MINIMUM PERCENTAGE OF PERIMETER:

BUILDING IS 100% SURROUNDED BY OPEN SPACE OR PUBLIC WAY.

506.3.2 MINIMUM FRONTAGE DISTANCE:

ALL MINIMUM DISTANCES FOR (W) EXCEED 20 FT.

506.3.3 AMOUNT OF INCREASE:

THE AREA FACTOR INCREASE BASED ON FRONTAGE SHALL BE

DETERMINED IN ACCORDANCE WITH TABLE 506.3.3.

FACTOR IS EQUIVALENT TO 0.75.

508.2.1 [ACCESSORY] OCCUPANCY CLASSIFICATION:

BUILDING HAS STORAGE ROOMS WITH S-2 OCCUPANCIES.

PRIMARY OCCUPANCY CLASSIFICATION OF BUILDING IS GROUP B.

508.2.2 ALLOWABLE BUILDING HEIGHT:

ALLOWABLE HEIGHT AND NUMBER OF STORIES FOR GROUP B

USED PER SECTION 504.

508.2.3 ALLOWABLE BUILDING AREA:

ALLOWABLE AREA FOR GROUP B USED PER SECTION 506.

ACCESSORY OCCUPANCIES DO NOT CONSTITUTE GREATER THAN

10% OF THE FLOOR AREA OF EACH STORY AND DO NOT EXCEED

VALUES IN TABLE 506.2.

508.2.4 SEPARATION OF OCCUPANCIES:

NO SEPARATION PROVIDED.

509.2 [INCIDENTAL USES] OCCUPANCY CLASSIFICATION:

BUILDING CONTAINS INCIDENTAL USES. SEE DISCUSSION BELOW.

TABLE 509.1 INCIDENTAL USES:

BUILDING CONTAINS A BOILER ROOM REQUIRING SEPARATION.ZE

AUTOMATIC SPRINKLER PROVIDED FOR ROOM. SEE DISCUSSION

BELOW.

509.2 OCCUPANCY CLASSIFICATION:

INCIDENTAL USES CLASSIFIED AS GROUP B.

509.3 AREA LIMITATIONS:

SEE ARCHITECTURAL PLANS. INCIDENTAL USES ARE LESS THAN

10% OF BUILDING AREA OF THE STORY.

TABLE 803.13: INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY

OCCUPANCY (SPRINKLERED)

GROUP: INT EXIT EXIT ACCESS ROOMS STAIRS

EXIT STAIRS/RAMPS

B B C C

OCCUPANT LOAD CALCULATION SUMMARY:

RM OCC AREA OCC AREA OCC

CLASSIFICATION (SF) LOAD FACTOR TYPE LOAD

BUSINESS: 2755 150 GROSS 18.4

ASSEMBLY (TABLES/CHAIRS): 500 15 NET 33.3

MECH/STORAGE: 1797 300 GROSS 6.0

EXTERIOR AREAS: 792 300 GROSS 2.6

LEVEL 1 TOTAL: 5844 60.3

BUSINESS: 5337 150 GROSS 35.6

MECH/STORAGE: 31 300 GROSS 0.1

EXTERIOR AREAS: 40 300 GROSS 0.1

LEVEL 2 TOTAL: 5408 35.8

MECH/STORAGE: 625 300 GROSS 2.1

LEVEL 3 TOTAL: 625 2.1

BUILDING TOTAL: 99

804.4.2 [INTERIOR FLOOR FINISH] MINIMUM CRITICAL RADIANT FLUX:

INTERIOR FLOORS HAVE MINIMUM CRITICAL RADIANT FLUX OF NOT

LESS THAN CLASS II.

806.2 COMBUSTIBLE DECORATIVE MATERIALS:

SEE FINISH SCHEDULE AND INTERIOR ELEVATIONS. DECORATIVE

MATERIALS DO NOT EXCEED 10% OF WALL OR CEILING AREA.

806.7 INTERIOR TRIM:

INTERIOR TRIM HAS A MINIMUM CLASS C FLAME SPREAD INDEX.

TRIM DOES NOT EXCEED 10% OF WALL OR CEILING AREA.

806.8 INTERIOR FLOOR-WALL BASE:

FLOORS REQUIRED TO BE CLASS II; FLOOR BASE IS LESS THAN 6"

IN HEIGHT AND IS CLASS II.

906.1 [PORTABLE FIRE EXTINGUISHERS] WHERE REQUIRED:

PORTABLE FIRE EXTINGUISHERS SHALL BE INSTALLED IN THE

FOLLOWING LOCATIONS. 1. IN GROUP B OCCUPANCIES; […] 4. ON

EACH FLOOR OF STRUCTURES UNDER CONSTRUCTION [...]; 6.

SPECIAL-HAZARD AREAS, INCLUDING BUT NOT LIMITED TO [...]

WHERE REQUIRED BY THE FIRE CODE OFFICIAL.

SEE CODE PLANS

[F] TABLE 906.3(1) FIRE EXTINGUISHERS FOR CLASS A FIRE HAZARDS:

SEE CODE PLANS. BUILDING HAS EXTINGUISHERS PROVIDED

THROUGHOUT.

912.2.2 [FIRE DEPARTMENT CONNECTIONS] EXISTING BUILDINGS:

BUILDING IS EXISTING. SEE ELEVATIONS FOR FEC LOCATION AND

SIGN.

914.1.2 INTERIOR ACCESS TO SHAFTWAYS:

SEE SIGNAGE SCHEDULE FOR SHAFTWAY IDENTIFICATION SIGNS.

1003.2 [GENERAL MEANS OF EGRESS] CEILING HEIGHT:

ALL MEANS OF EGRESS HAVE CEILING HEIGHTS EXCEEDING 7'-6"

UNLESS OTHERWISE ALLOWED TO BE LOWER BY THIS SECTION.

1003.3.1 [PROTRUDING OBJECTS] HEADROOM:

SOME PROTRUDING OBJECTS EXTEND BELOW MINIMUM CEILING

HEIGHT. THESE DO NOT COMPRISE MORE THAN 50% OF CEILING

AREA AND PROVIDE A HEADROOM OF GREATER THAN 80".

BARRIER PROVIDED AT AREAS WHERE CIRCULATION PATH HAS A

CLEARANCE LESS THAN 80".

1003.3.2 POST-MOUNTED OBJECTS:

POST-MOUNTED OBJECTS MEET THE STANDARD. SEE SIGNAGE

SCHEDULE.

1003.3.3 HORIZONTAL PROJECTIONS:

OBJECTS BETWEEN 27" AND 80" ABOVE FINISHED FLOOR DO NOT

PROJECT GREATER THAN 4" INTO THE CIRCULATION PATH.

1003.3.4 CLEAR WIDTH

PROTRUDING OBJECTS DO NOT REDUCE THE MINIMUM CLEAR

WIDTH OF ACCESSIBLE ROUTES.

1003.4 SLIP-RESISTANT SURFACE:

FLOORS IN CIRCULATION PATHS ARE NON-SLIP AND SECURELY

ATTACHED.

1004.2.1 [CUMULATIVE OCCUPANT LOADS] INTERVENING SPACES OR

ACCESSORY AREAS:

WHERE OCCUPANTS EGRESS FROM ONE OR MORE ROOMS,

AREAS, OR SPACES THROUGH OTHERS, THE DESIGN OCCUPANT

LOAD SHALL BE THE COMBINED OCCUPANT LOAD OF

INTERCONNECTED ACCESSORY OR INTERVENING SPACES.

DESIGN OF EGRESS PATH CAPACITY SHALL BE BASED ON THE

CUMULATIVE PORTION OF OCCUPANT LOADS OF ALL ROOMS,

AREAS, OR SPACES TO THAT POINT ALONG THE PATH OF EGRESS

TRAVEL.

SEE CODE PLANS

1004.5 AREAS WITHOUT FIXED SEATING:

THE NUMBER OF OCCUPANTS SHALL BE COMPUTED AT THE RATE

OF ONE OCCUPANT PER UNIT OF AREA AS PRESCRIBED IN TABLE

1004.5. […]

SEE ROOM OCCUPANT LOAD TABLE

1105.1 [ACCESSIBLE ENTRANCES] PUBLIC ENTRANCES:

BUILDING HAS ONE PUBLIC ENTRANCE. THIS ENTRANCE COMPLIES

WITH STANDARDS FOR ACCESSIBLE ENTRANCES.

1105.1.1 AUTOMATIC DOORS;

BUILDING OCCUPANT LOAD IS LESS THAN 500, THE NUMBER

REQUIRING AUTOMATIC DOOR OPERATION.

1105.1.4 RESTRICTED ENTRANCES:

ONE RESTRICTED ENTRANCE IS ACCESSIBLE.

1106.2 [PARKING AND PASSENGER LOADING FACILITIES] REQUIRED:

SEE SITE PLAN. EACH FACILITY ON-SITE PROVIDES AT LEAST ONE

ACCESSIBLE PARKING SPACE.

1106.6 VAN SPACES:

SEE SITE PLAN. AT LEAST ONE VAN-ACCESSIBLE PARKING SPACE

PROVIDED FOR EACH PARKING FACILITY.

1110.2 TOILET AND BATHING FACILITIES:

ALL TOILET ROOMS ARE ACCESSIBLE.

1110.9 LIFTS:

BUILDING IS EXISTING AND HAS EXISTING PLATFORM LIFT

PROVIDING A COMPONENT OF THE ACCESSIBLE ROUTE.

1209.3 [ACCESS TO UNOCCUPIED SPACES] MECHANICAL APPLIANCES:

ROOFTOP MECHANICAL EQUIPMENT PROVIDED ACCESS PER THE

IMC.

1511.1.1 AREA LIMITATION

PENTHOUSE DOES NOT COVER GREATER THAN ONE-THIRD AREA

OF SUPPORTING ROOF DECK.

1511.2.1 HEIGHT ABOVE ROOF DECK

PENTHOUSE IS LESS THAN 18 FEET IN HEIGHT.

1511.2.2 USE LIMITATIONS

PENTHOUSE SHALL BE USED ONLY FOR SHELTER OF MECHANICAL

AND ELECTRICAL EQUIPMENT.

1511.2.4 TYPE OF CONSTRUCTION

PENTHOUSE WALLS MEET REQUIREMENTS FOR FIRE RATING PER

TABLE 601.

2402.1 [GLAZING REPLACEMENT] GENERAL:

REPLACED GLAZING SHALL MEET REQUIREMENTS FOR NEW

INSTALLATION.

2403.3 GLASS FRAMING:

ALL WINDOWS REPLACED WITH CONTEMPORARY WINDOWS

EVOKING A SIMILAR APPEARANCE TO THE HISTORIC WINDOW WILL

COMPLY WITH THIS PROVISION. ALL DAMAGED HISTORIC

WINDOWS WILL BE REPAIRED IN A MANNER CONSISTENT WITH

THEIR ORIGINAL CONSTRUCTION PER THE IEBC AND MAY NOT

MEET THIS PROVISION.

TABLE 1020.3: MINIMUM CORRIDOR WIDTH (IN)

ANY FACILITY NOT LISTED 44

MECH ACCESS 24

<50 OCC 36

1004.7 OUTDOOR AREAS:

BUILDINGS HAVE COVERED EXTERIOR AREAS ASSOCIATED WITH

THE BUILDING USE. THESE ARE FREE AND OPEN TO A PUBLIC

WAY.

1004.9 POSTING OF OCCUPANT LOAD:

ALL BUILDINGS CONTAIN B OCCUPANCIES WITH SOME ASSEMBLY

SPACES CLASSIFIED AS B. SIGNAGE POSTED WILL PROVIDE

MAXIMUM OCCUPANT LOADS IN ROOMS OF ASSEMBLY USE OR

OCCUPANCY.

1005.3.1 STAIRWAYS:

SEE CODE PLANS. EXISTING EXTERIOR EXIT STAIRWAYS COMPLY

WITH STANDARD BUT ARE NOT MODIFIED WITH PROJECT.

1005.3.2 OTHER EGRESS COMPONENTS:

SEE CODE PLANS. EXISTING COMPONENTS OF EGRESS COMPLY

WITH STANDARD BUT WILL NOT BE MODIFIED WITH PROJECT PER

IEBC. NEW COMPONENTS OF EGRESS WILL COMPLY WITH

STANDARD.

1005.4 CONTINUITY:

COMPONENTS OF EGRESS MEET STANDARDS FOR CAPACITY.

1005.5 DISTRIBUTION OF MINIMUM WIDTH AND REQUIRED CAPACITY:

STORIES OF BUILDING AND SPACES REQUIRE MORE THAN ONE

EXIT. LOSS OF ONE EXIT DOES NOT REDUCE THE AVAILABLE

CAPACITY TO LESS THAN 50% OF THE REQUIRED CAPACITY.

1005.7.1 [ENCROACHMENT] DOORS:

SEE CODE PLANS. DOORS WHEN FULLY OPENED DO NOT REDUCE

REQUIRED WIDTH BY MORE THAN 7".

1005.7.2 OTHER PROJECTIONS:

HANDRAILS PROJECT INTO REQUIRED WIDTH PER SECTION 1014.8.

1006.2.2.1 BOILER, INCINERATOR AND FURNACE ROOMS:

MECHANICAL ROOM DOES NOT HAVE AN AREA GREATER THAN 500

SF.

1009.1 ACCESSIBLE MEANS OF EGRESS REQUIRED:

BUILDINGS ARE EXISTING AND DO NOT REQUIRE ACCESSIBLE

MEANS OF EGRESS PER IEBC. SEE DISCUSSION BELOW.

1010.1.1 SIZE OF DOORS:

ALL NEW DOORS COMPLY WITH STANDARD. EXISTING DOORS NOT

ALTERED IN THIS PROJECT COMPLY WITH STANDARD.

1010.2.2 HARDWARE:

SEE HARDWARE SCHEDULE. SEE HARDWARE SCHEDULE. ALL

DOORS MEET STANDARD.

1010.2.3 HARDWARE HEIGHT:

SEE DOOR SCHEDULE. NEW HARDWARE WILL COMPLY WITH THIS

PROVISION.

1011 STAIRWAYS:

PER IEBC EXISTING MEANS OF EGRESS MAY REMAIN UNALTERED

IF DETERMINED BY CODE OFFICIAL TO NOT POSE DANGER TO LIFE

SAFETY. STAIRWAY MAINTAINS EXISTING LEVEL OF PROTECTION.

1012.2 [RAMPS] SLOPE:

BOTTOM LANDING FOR LIFT IS 2" ABOVE ADJACENT FLOOR. SHORT

RAMP IS NOT PART OF MEANS OF EGRESS AND IS EXCLUSIVELY

USED FOR ACCESSING LIFT. RAMP SLOPE DOES NOT EXCEED 1:8.

1014.2 [HANDRAILS] HEIGHT:

HANDRAIL HEIGHT, MEASURED ABOVE STAIR TREAD NOSINGS, OR

FINISH SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT LESS

THAN 34" AND NOT MORE THAN 38". HANDRAIL HEIGHT OF

ALTERNATING TREAD DEVICES AND SHIP LADDERS, MEASURED

ABOVE TREAD NOSINGS, SHALL BE UNIFORM, NOT LESS THAN 30"

AND NOT MORE THAN 34". SEE STAIR SECTIONS. NEW HANDRAILS

COMPLY WITH STANDARD.

1014.3 HANDRAIL GRASPABILITY:

SEE STAIR SECTIONS. NEW HANDRAILS COMPLY WITH STANDARD.

1014.4 HANDRAIL EXTENSIONS:

SEE STAIR SECTIONS. NEW HANDRAILS COMPLY WITH STANDARD.

1014.7 CLEARANCE:

NEW HANDRAILS COMPLY WITH STANDARD.

1015.3 [GUARDS] HEIGHT:

EXTERIOR STAIR LANDING IS NOT GREATER THAN 30" ABOVE

FINISHED ADJACENT GRADE. NO GUARD REQUIRED.

1016.2 EGRESS THROUGH INTERVENING SPACES:

SEE CODE PLANS. SOME EGRESS PATHS IN BUILDING PASS

THROUGH VESTIBULES OR ADJACENT ROOMS THAT ARE

ACCESSORY TO ONE OR THE OTHER. OFFICE AREAS ON FIRST

FLOOR HAVE A SECOND EXIT THAT PASSES THROUGH ADJACENT

"READY" MUD ROOM WITH CLEAR DISCERNIBLE PATH OF EGRESS.

1017.2 [EXIT ACCESS TRAVEL DISTANCE] LIMITATIONS:

TABLE 1017.2 SPECIFIES 300 FT EXIT ACCESS TRAVEL DISTANCE

MAXIMUM FOR GROUP B IN BUILDING FULLY SPRINKLERED. SEE

CODE PLANS FOR EXIT ACCESS TRAVEL DISTANCE.

1017.3 MEASUREMENT:

SEE CODE PLANS FOR EXIT ACCESS TRAVEL DISTANCE. FIRST

FLOOR OF THE BUILDING IS DIVIDED BETWEEN PUBLIC AND

OFFICE FUNCTIONS. PUBLIC AREAS WILL NOT HAVE FREE EGRESS

THROUGH OFFICE AREA AND OCCUPANT LOAD AND EXIT ACCESS

TRAVEL DISTANCE DOES NOT EXCEED LIMITS FOR HAVING ONLY

ONE EXIT. OFFICE AREAS REQUIRE ONLY ONE EXIT WHICH PASSES

THROUGH "READY" MUD ROOM.

1019.1 [EXIT ACCESS STAIRWAYS] GENERAL:

BUILDING CONTAINS INTERIOR STAIR THAT DOES NOT SERVE AS A

COMPONENT OF EGRESS.

1019.3 OCCUPANCIES OTHER THAN GROUPS I-2 AND I-3:

STAIRWAY CONNECTS ONLY TWO ADJACENT STORIES.

REQUIRED PLUMBING FIXTURES - TABLE 422.1

OCC WC REQ'D U REQ'D LAV REQ'D DF REQ'D

M F SO M M F SO

99 1 3 0 1 1 1 0 1

OTHER: 1 SERVICE SINK

CODE: 2018 UPC

TABLE 422.1 MINIMUM PLUMBING FIXTURES:

BUILDING DOES NOT CHANGE OCCUPANCY BUT PROVIDES

FACILITES PER TABLE 422.1. SEE BELOW. 2 SINGLE OCCUPANT (SO)

TOILET ROOMS PROVIDED ON LEVEL 2. ONE WATERCLOSET

REQUIRED FOR WOMEN PROVIDED IN SO TOILET ROOM SIGNED

FOR USE BY BOTH GENDERS.

601 [TYPES OF CONSTRUCTION] GENERAL:

SEE TABLE 601. BUILDING IS TYPE V-B CONSTRUCTION. SEE

DISCUSSION BELOW.

602.5 TYPE V:

BUILDING IS CONSIDERED TYPE V-B CONSTRUCTION.

TABLE 601: FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING

ELEMENTS (HOURS)

TYPE V-B:

PRIMARY STRUCTURAL FRAME: 0 HRS

BEARING WALLS:

EXTERIOR: 0 HRS

INTERIOR: 0 HRS

NONBEARING WALLS & PARTITIONS:

EXTERIOR: SEE TBL 705.5

INTERIOR: 0 HRS

FLOOR CONSTRUCTION, ETC: 0 HRS

ROOF CONSTRUCTION, ETC: 0 HRS

717.1.2.1 DUCTS THAT PENETRATE NONFIRE-RESISTANCE-RATED

ASSEMBLIES

THE SPACE AROUND THE DUCT PENETRATING A NONFIRE-

RESISTANCE-RATED FLOOR ASSEMBLY SHALL COMPLY WITH

SECTION 717.6.3.

717.6.3 NONFIRE-RESISTANCE-RATED FLOOR ASSEMBLIES

PER METHOD 2, THE DUCTS FROM PENTHOUSE TO LEVEL 1 PASS

THROUGH ONLY 1 STORY. AS PENTHOUSE IS CONSIDERED PART

OF STORY BELOW, THE DUCTS CONNECT NO MORE THAN TWO

STORIES. DUCTS PENETRATE A NONCOMBUSTIBLE FLOOR

ASSEMBLY THAT RESISTS THE FREE PASSAGE OF FLAME AND THE

PRODUCTS OF COMBUSTION AT THE FLOOR LINE OF LEVEL 2.

ANNULAR SPACES AROUND PENETRATING DUCTS PROTECTED

WITH NONCOMBUSTIBLE MATERIAL.

TABLE 705.5: FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR

WALLS BASED ON FIRE SEPARATION DISTANCE

FSD TYPE OF GROUP B, R, S-2

(FT) CONSTRUCTION

10≤X<30 V-B 0 HRS

X≥30 ALL 0 HRS

1020.2 [CORRIDORS] CONSTRUCTION:

BUILDING IS FULLY SPRINKLERED. NEW CORRIDORS PROVIDED

WITH NO FIRE-RESISTANCE RATING PER TABLE.

1020.3 WIDTH AND CAPACITY:

SEE ARCHITECTURAL DRAWINGS. NEW CORRIDORS HAVE WIDTHS

MEETING OR EXCEEDING MINIMUM WIDTH.

1020.5 DEAD ENDS:

SEE ARCHITECTURAL DRAWINGS. LENGTH OF NEW DEAD-END

DOES NOT EXCEED 20'.

1027.3 [EXTERIOR EXIT STAIRWAYS AND RAMPS] OPEN SIDE:

BUILDING HAS EXISTING EXTERIOR EXIT STAIRWAYS AND RAMPS

NOT ALTERED WITH PROJECT. ALL WORK CONDUCTED TO THESE

ELEMENTS CONSTITUTES REPAIRS. ELEMENTS CONSIDERED

CONFORMING WITH CODES ADOPTED AT TIME OF CONSTRUCTION.

EXISTING WIDTHS ACCOMMODATE REQUIRED CAPACITIES.

1028.5 ACCESS TO A PUBLIC WAY:

SEE SITE PLAN. ALL EXITS DISCHARGE TO PUBLIC WAY.

1104.1 SITE ARRIVAL POINTS:

SEE SITE PLAN. ACCESSIBLE ROUTE PROVIDED FROM ACCESSIBLE

PARKING TO ACCESSIBLE BUILDING ENTRANCES. BUILDING IS

EXISTING AND HAS ACCESSIBLE ENTRANCE NOT BEING MODIFIED

IN PROJECT. MODIFIED ENTRANCES ARE MADE ACCESSIBLE TO A

DEGREE TECHNICALLY FEASIBLE WITHOUT ALTERING BUILDING TO

ACCOMMODATE APPROACH CLEARANCES. AUTOMATIC DOOR

OPENERS PROVIDED AT ACCESSIBLE ENTRANCES.

1104.2 WITHIN A SITE:

SEE SITE PLAN. ACCESSIBLE ROUTE PROVIDED ON-SITE TO ALL

ACCESSIBLE FACILITIES, ELEMENTS, AND SPACES.

1104.3 CONNECTED SPACES:

SEE ARCHITECTURAL DRAWINGS. BUILDING HAS AN ACCESSIBLE

ROUTE TO ALL ACCESSIBLE FIRST FLOOR SPACES. SEE

DISCUSSION BELOW.

1104.4 MULTISTORY BUILDINGS AND FACILITIES:

EACH STORY HAS ACCESSIBLE SPACES AND AN ACCESSIBLE

ROUTE IS PROVIDED TO EACH STORY.

1104.5 LOCATION:

ACCESSIBLE ROUTE PROVIDED WITHIN BUILDING WITH EXISTING

WHEELCHAIR LIFT.

UP

DN

DN

DN

DN

CODE LEGEND

EXIT

GROUP B

COMMON PATH OF EGRESS

EXIT ACCESS TRAVEL DISTANCE

BEYOND COMMON PATH

F.E.*255 (545)

68.4"

OCC (REQ'D OCC)

REQ'D CAPACITY 2-A

1 HR RATED ASSEMBLY

A

B C D E F

100'-0"

'-0

20'-0" 20'-0" 20'-0" 20'-0" 20'-0"

'-0

'-0

239 SF

STORAGE S-2

5029 SF

BUSINESS

310 SF

BUSINESS

LOADING

STAIR 1

STORAGE SHED

COVERED ENTRY

482 SF

BUSINESS

11'-3"

'-3

54'-11 1/2"

117'-6 3/4"

6.3"

2.9"

LONGEST COMMON PATH

TO EXIT: 90'-0"

*2-A

*2-A

*2-A

26'-0"

10'-0"

IM

PL

IE

D P

.L.

SEPARATE BUILDING

LONGEST COMMON PATH

TO EXIT: 99'-0"

A

B C D E F

STAIR 1

5343 SF

BUSINESS

21 SF

BUSINESS

19 SF

BUSINESS

100'-0"

'-0

20'-0" 20'-0" 20'-0" 20'-0" 20'-0"

'-0

'-0

60'-0"

'-2

'-0

113'-2 1/4"

38 5.

7"38 5.

7"

*2-A *2-A

*2-A

51'-2"

B C

625 SF

BUSINESS

PENTHOUSE

2 OCC

'-0

20'-0"

'-0

'-5

'-0

'-0

NOTIFICATION OF POTENTIAL HAZARDS

ASBESTOS, LEAD, AND OTHER HAZARDOUS MATERIALS ARE PRESENT IN THE BUILDING

AND MAY IMPACT THE WORK OF ALL TRADES. REGULATED AIR CONTAMINANTS,

INCLUDING ASBESTOS AND LEAD, ARE ALSO PRESENT IN SETTLED AND CONCEALED

DUST IN AND ON ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL

COMPONENTS OR SYSTEMS THROUGHOUT THE BUILDING. ALL TRADES SHALL

COORDINATE WITH OTHER TRADES AND CONDUCT THEIR WORK TO PREVENT WORKER

EXPOSURE OR SITE CONTAMINATION. REFER TO SPECIFICATION DIVISIONS 0, 1, AND 2

FOR SPECIFIC INFORMATION CONCERNING DISTURBING, REMOVING, AND DISPOSING OF

THESE MATERIALS AND THE INSTALLATION OF THE NEW MATERIALS OR COMPONENTS.

THIS NOTIFICATION IS PROVIDED IN ACCORDANCE WITH EPA AND OSHA REQUIREMENTS.

AK

SAL

AFOETATS

T

CETIHCRALANOISSEFOR

PDE

RE

TS

I

GE

R

No. A-140412

JUSTIN M. SCANIO

TH49

06.26.2024

N S

TR

EE

T, S

UI

TE

A N C

HO

RA

G E, A

LA

SK

A

7.

1.

E

CI

/H ye r, In c.

C

HE

C

KE

D

A

UT

HO

R:

PR

O

JE

C T N O

IS

SU

E D A

TE

RE

V

IS

IO

N

FULL SIZE PRINTED ON 22 x 34

G1.03

C O

DE

P

LA

N S

-0 6.

C W R

JM

S

.2 6.

PE

TE

RS

BU

RG

O

FF

IC

E C O N

SO

LI

DA

TIO

N

W O

RK

C

EN

TE

R

RE

PL

A C

EM

EN

T - D

IS

TR

IC

T

O

FF

IC

E

C O N

ST

RU

C

TIO

N D O C

UM

EN

TS

1/16" = 1'-0"1 LEVEL 1 CODE PLAN

1/16" = 1'-0"2 LEVEL 2 CODE PLAN

1/16" = 1'-0"3 LEVEL 3 CODE PLAN

NOTE: CONFERENCE AND HUDDLE ROOMS CONSIDERED

NON-CONCENTRATED ASSEMBLY FOR DETERMINING

NUMBER OF OCCUPANTS

ESTIMATED QUANTITIES TO BE REMOVED (PDO BUILDING)

INCIDENTAL QUANTITIES OF MATERIALS, INCLUDING LEAD-CONTAINING MATERIALS, THAT ARE REQUIRED TO BE REMOVED TO COMPLETE THE WORK, BUT OTHERWISE ARE TO REMAIN, ARE NOT INCLUDED HERE, AS THEY WILL VARY DEPENDING ON THE CONTRACTOR'S CHOICE OF MEANS AND METHODS.

26,850 SQUARE FEET OF GYPSUM WALLBOARD WITH ASBESTOS-CONTAINING JOINT COMPOUND, INCLUDING GYPSUM WALL BOARD SUBSTRATE TO GLUED-ON CEILING TILES

225 SQUARE FEET OF CEMENT ASBESTOS BOARD INSULATED INFILL PANELS, INCLUDING THE SEALANTS AT THE PERIMETER FRAMES.

2,185 SQUARE FEET OF 12" X 24 " ASBESTOS-CONTAINING ASPHALTIC FLOOR TILES AND ASBESTOS-CONTAINING MASTICS TO BE COMPLETELY REMOVED.

4,390 SQUARE FEET OF VARIOUS COLORS OF 9" X 9" VINYL ASBESTOS FLOOR TILES AND ASBESTOS-CONTAINING MASTICS TO BE COMPLETELY REMOVED.

80 SQUARE FEET OF VARIOUS COLORS OF 12" X 12" VINYL COMPOSITE TILE CONTAMINATED BY ASBESTOS-CONTAINING MASTICS TO BE COMPLETELY REMOVED.

1,750 LINEAR FEET OF DUCTWORK WITH ASBESTOS-CONTAINING GRAY-GREEN SEALANTS TO BE COMPLETELY REMOVED.

100* ALLOWANCE FOR REQUIRED REMOVAL OF GLOBS OF INSULATION PIN MASTIC FROM ROUGH CONCRETE SURFACE. THE INSULATION PINS ARE HOLDING RIGID FIBERGLASS PANEL INSULATION TO EXTERIOR WALLS, AND UNDER ENTRY ALCOVES AND ARE ONLY REQUIRED TO BE REMOVED WHERE NECESSARY TO COMPLETE THE WORK. THE VAST MAJORITY OF THE MASTIC OF THE INSULATION PINS ARE TO REMAIN IN PLACE AND HAVE THE PINS CLIPPED OFF OF THE PERFORATED 2" SQUARE METAL PIN PLATES.

2,100 LINEAR FEET OF PIPING, FIBERGLASS INSULATION AND ASBESTOS-CONTAINING "HARD-FITTING" INSULATION AT VALVES, FITTINGS, HANGARS, ETC. TO BE REMOVED.

380 EACH ASBESTOS-CONTAINING "HARD-FITTINGS" AND FIBERGLASS INSULATION TO BE REMOVED FROM ROOF DRAIN PIPING, PIPING TO REMAIN, AND BE RE-INSULATED.

1 LOT ASBESTOS-CONTAINING GASKETS AND VALVE PACKINGS ON PIPING.

3 EACH WOOD FIRE DOORS WITH ASBESTOS-CONTAINING DOOR INSULATION.

1 EACH BOILER WITH ASBESTOS-CONTAINING GASKETS, SEALANTS AND REFRACTORY INSULATION AT BOILER BASE.

40 LINEAR FEET OF SITE ERECTED BOILER STACK WITH ASBESTOS-CONTAINING INSULATION AND METAL JACKET, INCLUDING THROUGH ROOF AND REMOVAL OF THE ENCLOSURE ABOVE THE ROOF IF

NECESSARY FOR COMPLETE REMOVAL OF THE STACK AND INSULATION.

20* SQUARE FOOT ALLOWANCE FOR REMOVAL OF ASSUMED ASBESTOS-CONTAINING TARRY DAMP-PROOFING AT EXTERIOR FOUNDATION WALL.

50* SQUARE FOOT ALLOWANCE FOR REMOVAL OF REMNANTS OF ASSUMED ASBESTOS-CONTAINING BUILT-UP ROOFING OR VAPOR BARRIER ON SURFACE OF ROOF DECK TO BE REMOVED FOR NEW

PENETRATIONS AND EQUIPMENT MOUNTING.

430 MERCURY-CONTAINING FLUORESCENT LAMPS AND COMPACT FLUORESCENT LAMPS

15 SELF ILLUMINATING EXIT RADIOACTIVE SIGNS

15 EMERGENCY LIGHTS OR OTHER EQUIPMENT WITH UNIVERSAL WASTE BATTERIES

1 MERCURY-CONTAINING THERMOSTATS

2,180 LINEAR FEET OF ASBESTOS-CONTAINING SEALANTS AT WINDOWS AND DOORS

GENERAL NOTES

1. THE HAZARDS ABATEMENT PORTION OF THIS PROJECT INCLUDES THE DISTURBANCE AND/OR REMOVAL AND DISPOSAL OF SELECTED ASBESTOS-CONTAINING MATERIALS, POLYCHLORINATED BIPHENYL

(PCB) CONTAINING LIGHT BALLASTS, MERCURY-CONTAINING MATERIALS, LEAD-CONTAINING MATERIALS AND ITEMS CONTAINING RADIOACTIVE COMPOUNDS. THE PURPOSE OF THE HAZARDS ABATEMENT PORTION OF THE WORK IS TO REMOVE THESE MATERIALS FROM THE PDO BUILDING PRIOR TO RENOVATION OR DEMOLITION SO THAT PERSONNEL CAN SAFELY PERFORM THEIR WORK WITHOUT CREATING

HAZARDS TO HEALTH OR THE ENVIRONMENT.

2. THE WORK IN THE PDO BUILDING DOES NOT INCLUDE REMOVAL OF ALL HAZARDOUS MATERIALS IN THE BUILDING. REMOVE HAZARDOUS MATERIALS COORDINATING WITH OTHER TRADES, AS SPECIFIED AND/OR INDICATED ON THE DRAWINGS, OUTLINED IN THE SPECIFICATIONS, AND AS REQUIRED TO COMPLETE THE WORK. "REMOVAL" INCLUDES PROPER HANDLING, PACKAGING AND DISPOSAL OF

MATERIALS REMOVED.

3. POTENTIALLY HAZARDOUS MATERIALS SUCH AS MERCURY-CONTAINING LAMPS AND THERMOSTATS, SELF ILLUMINATING EXIT SIGNS CONTAINING RADIOACTIVE COMPONENTS, METALLIC LEAD ITEMS, REFRIGERANTS, HEATING SYSTEM GLYCOL AND PCB CONTAINING BALLASTS AFFECTED BY THE PROJECT ARE TO BE REMOVED AND DISPOSED OF PROPERLY. REFER TO SPECIFICATIONS AND THE CONTRACTOR'S APPROVED WORK PLAN FOR HAZARDOUS MATERIALS REMOVAL, DISTURBANCE, CLEARANCE, AND DISPOSAL PROCEDURES.

4. LEAD-BASED PAINTS (PAINT CONTAINING EQUAL TO OR GREATER THAN 1.0 mg/cm²) WERE IDENTIFIED DURING THE LIMITED LEAD TESTING SHOWN IN THE HAZMAT SURVEY, AND LEAD-BASED PAINTS MAY BE PRESENT AT OTHER LOCATIONS. LOW LEVELS OF LEAD FOUND BY XRF TESTING DOES NOT MEAN THE PAINTS ARE FREE OF LEAD, THE PAINTS MAY CONTAIN MEASURABLE AMOUNTS OF LEAD.

LEAD-CONTAINING MATERIALS INCLUDE ALL PAINTED SURFACES, CERAMIC TILES, AND METALLIC LEAD, AS WELL AS LEAD-CONTAINING DUSTS. THIS IS NOT A LEAD ABATEMENT PROJECT, AND ALL TRADES WILL LIKELY DISTURB SOME LEAD-CONTAINING MATERIALS. CONTROL WORKER EXPOSURES USING LEAD-SAFE WORK PRACTICES AND CHOICE OF MEANS AND METHODS OF CONDUCTING THE WORK TO

COMPLY WITH 29 CFR 1926.62 AND TO AVOID CONTAMINATION OF THE WORK AREA AND SITE.

5. PERFORM INITIAL AIR MONITORING TESTS ON ALL TASKS THAT DISTURB ASBESTOS OR LEAD-CONTAINING MATERIALS, DUST OR PAINT TO DETERMINE THE APPROPRIATE WORKER AND SITE PROTECTION PROCEDURES REQUIRED. DUE TO THE AGE OF THE BUILDINGS, METALLIC LEAD IS ASSUMED PRESENT IN BELL AND SPIGOT PIPE JOINTS AND IN SOLDER ON COPPER PIPES.

6. SETTLED AND CONCEALED DUST ON ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND MECHANICAL COMPONENTS THROUGHOUT THE PROJECT AREA(S) IS ASSUMED TO CONTAIN REGULATED AIR CONTAMINANTS INCLUDING ASBESTOS AND LEAD. WORK OF ALL TRADES MAY INCLUDE DISTURBANCE OF ASBESTOS AND LEAD AND MAY RESULT IN WORKER EXPOSURE TO ASBESTOS AND LEAD ABOVE THE OSHA ACTION LEVEL OR PERMISSIBLE EXPOSURE LIMITS FOR ASBESTOS OR LEAD IF PROPER WORK PRACTICES AND/OR ENGINEERING CONTROLS ARE NOT USED. IT IS THE CONTRACTOR'S RESPONSIBILITY TO CHOOSE APPROPRIATE WORKER AND SITE PROTECTION PROCEDURES SO THAT THEIR WORKERS ARE NOT EXPOSED ABOVE THOSE LIMITS AND THAT WORK IS PERFORMED IN ACCORDANCE WITH ALL APPLICABLE REGULATIONS. THE PRESENCE OF ASBESTOS OR LEAD IN DUSTS DOES NOT NECESSARILY MAKE THEM A HAZARD TO WORKERS OR A HAZARDOUS WASTE.

7. THE CONTRACTOR'S INDEPENDENT LABORATORY SHALL PROVIDE ALL INSPECTIONS, MONITORING, SAMPLING, ANALYSES AND REPORTING SERVICES AS SPECIFIED. CLEARANCE AIR MONITORING IN THE PDO BUILDING SHALL BE CONDUCTED IN ACCORDANCE WITH 40 CFR 763. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION ON SAMPLING.

8. LOCATIONS OF MATERIALS SHOWN ON THESE DRAWINGS ARE SCHEMATIC AND APPROXIMATE. FIELD VERIFY AND COORDINATE CONSTRUCTION DETAILS, DIMENSIONS, WORK CONDITIONS, AND LOCATIONS WHICH WILL AFFECT THE REMOVAL OR DISTURBANCE OF HAZARDOUS MATERIALS. HAZARDOUS MATERIALS MAY HAVE COME LOOSE AND FALLEN ONTO FLOORS, CEILINGS, CHASES, OR WALL CAVITIES. THE QUANTITIES SHOWN IN THE SHEET SUMMARY ARE APPROXIMATE AND MAY VARY DEPENDING ON THE CONTRACTOR'S MEANS AND METHODS. REQUIRE ALL TRADES TO COORDINATE WITH EACH OTHER AND TO CONDUCT THEIR WORK TO PREVENT WORKER EXPOSURE OR SITE CONTAMINATION, SEE DRAWINGS OF ALL DISCIPLINES FOR ADDITIONAL INFORMATION RELATING TO HAZARDOUS MATERIALS.

IMMEDIATELY COMMUNICATE ALL DISCREPANCIES IN QUANTITIES TO THE OWNER. REFER TO HAZARDOUS MATERIALS ASSESSMENT FOR MORE INFORMATION ABOUT POTENTIALLY HAZARDOUS MATERIALS THAT ARE NOT SCHEDULED FOR DISTURBANCE BY THIS PROJECT. FURNISH ALL WORK AND MATERIALS REQUIRED FOR A FINISHED PROJECT AS DESCRIBED IN THE CONTRACT DOCUMENTS. QUANTITIES LISTED WITH A * MAY VARY DEPENDING ON THE CONTRACTOR'S MEANS AND METHODS. CONTRACTOR'S MEANS AND METHODS RESULTING IN ADDITIONAL MATERIALS REMOVAL SHALL NOT RESULT IN

ADDED CONTRACT COSTS TO THE OWNER.

9. BUILDINGS TO BE RENOVATED OR DEMOLISHED INCLUDE STORED MATERIALS AND CHEMICALS, SUCH AS PAINTS, CLEANING COMPOUNDS, THINNERS, SOLVENTS, ETC. THE OWNER WILL REMOVE AND SALVAGE MATERIALS FOR THEIR CONTINUED USE. THE CONTRACTOR SHALL REMOVE AND PROPERLY DISPOSE OF ALL STORED MATERIALS AND CHEMICALS THAT THE OWNER CHOOSES TO LEAVE IN PLACE

IN THE BUILDINGS.

10. PROVIDE ALL WASTE TESTING, PACKAGING, HANDLING, TRANSPORTATION AND DISPOSAL. ALL COSTS FOR DISPOSAL SHALL BE BORNE BY THE CONTRACTOR. PERFORM TOXICITY CHARACTERISTIC LEACHING PROCEDURE (TCLP) TEST(S) OF WASTE(S) CONTAINING LEAD OR PAINTED WITH LEAD-CONTAINING PAINT TO CHARACTERIZE THE WASTE(S) AS HAZARDOUS OR NON-HAZARDOUS PRIOR TO DISPOSAL. PERFORM TOXICITY CHARACTERISTIC LEACHING PROCEDURE (TCLP) TEST(S) OF HEAT TRANSFER FLUIDS (GLYCOL OR WATER) IN HEATING SYSTEM TO CHARACTERIZE THE WASTE(S) AS HAZARDOUS OR NON-HAZARDOUS PRIOR TO DISPOSAL. COORDINATE REQUIREMENTS OF LANDFILL(S) REGARDING MATERIALS PACKAGING, HANDLING, AND DISPOSAL REQUIREMENTS PRIOR TO SUBMITTING

BID.

H0.1

HA

ZA

RD

S

A

BA

TE

M

EN

T N

O

TE

S A

N D

Q

UA

N

TI

TIE

S

N S

TR

EE

T, S

UI

TE

A N

C

HO

RA

G

E, A

LA

SK

A

7.

1.

E

CI

/H ye r, In c.

C

HE

C

KE

D

A

UT

HO

R:

PR

O

JE

C

T N

O

RA

F

RA

F

IS

SU

E D

A

TE

:0 5.

.2

RE

V

IS

IO

N

EH

S-

A

LA

SK

A

BU

SI

N

ES

S

BO

UL

EV

A

RD

, S

UI

TE

EA

G

LE

R

IV

ER

, A

LA

SK

A

.6

.1

FULL SIZE PRINTED ON 22 x 34

P

R

E

L

I

M

I

N

A

R

Y

N

O

T

F

R

C

O

N

S

T

R

U

C

T

I

O

N

PE

TE

RS

BU

RG

O

FF

IC

E C

O N

SO

LI

DA

TIO

N

W O

RK

C

EN

TE

R

RE

PL

A

C

EM

EN

T

DI

ST

RI

C T

O

FF

IC

E

C O

N

ST

RU

C

TIO

N

D O

C

UM

EN

TS

NOTIFICATION OF POTENTIAL HAZARDS

ASBESTOS, LEAD, AND OTHER HAZARDOUS MATERIALS ARE PRESENT IN THE BUILDING

AND MAY IMPACT THE WORK OF ALL TRADES. REGULATED AIR CONTAMINANTS,

INCLUDING ASBESTOS AND LEAD, ARE ALSO PRESENT IN SETTLED AND CONCEALED

DUST IN AND ON ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL

COMPONENTS OR SYSTEMS THROUGHOUT THE BUILDING. ALL TRADES SHALL

COORDINATE WITH OTHER TRADES AND CONDUCT THEIR WORK TO PREVENT WORKER

EXPOSURE OR SITE CONTAMINATION. REFER TO SPECIFICATION DIVISIONS 0, 1, AND 2

FOR SPECIFIC INFORMATION CONCERNING DISTURBING, REMOVING, AND DISPOSING OF

THESE MATERIALS AND THE INSTALLATION OF THE NEW MATERIALS OR COMPONENTS.

THIS NOTIFICATION IS PROVIDED IN ACCORDANCE WITH EPA AND OSHA REQUIREMENTS.

-0

SHEET NOTES

HAZARDS ABATEMENT DRAWINGS DO NOT SHOW ALL DETAILS OF WORK REQUIRED. ALL TRADES SHALL EXAMINE DRAWINGS OF OTHER TRADES AND COORDINATE WITH EACH OTHER TO DETERMINE EXTENT, TIMING AND LOCATIONS OF MATERIALS AFFECTED BY THE PROJECT.

1 REMOVE GYPSUM WALL BOARD ON WALLS AND CEILINGS WITH ASBESTOS-CONTAINING JOINT COMPOUND. GYPSUM WALL BOARD CEILING AT SECOND FLOOR IS MOSTLY COVERED WITH A GLUED-ON ACOUSTIC CEILING TILES WHICH HAD MASTICS WHICH CONTAINED LESS THAN 1 PERCENT ASBESTOS, BUT ARE CONTAMINATED BY THE ASBESTOS-CONTAINING JOINT COMPOUND. ALL GYPSUM WALL

BOARD IS TO BE REMOVED FROM THE PDO BUILDING.

2 REMOVE CEMENT ASBESTOS BOARD (CAB) "GLASWELD" INSULATED INFILL PANELS, ALUMINUM FRAMES, AND ASSUMED CONCEALED ASBESTOS-CONTAINING SEALANTS FROM CONCRETE WALLS.

3 REMOVE CARPETING, SHEET VINYL, VINYL ASBESTOS TILE AND COMPLETELY REMOVE ASBESTOS-CONTAINING OR CONTAMINATED MASTIC, INCLUDING UNDER WALLS SCHEDULED FOR DEMOLITION.

LOCATIONS OF DIFFERENT TYPES AND MULTIPLE LAYERS OF ACM SHOWN BY LEGEND AND REFER TO SHEET SUMMARY.

4 REMOVE DUCTWORK WITH GRAY-GREEN ASBESTOS-CONTAINING SEALANTS. REFER TO MECHANICAL FOR LOCATIONS. MOSTLY FOUND IN PENTHOUSE FAN ROOM, BUT ASSUMED TO BE LOCATED

THROUGHOUT THE BUILDING.

5 REMOVE ASBESTOS-CONTAINING GREEN MASTIC OF PERFORATED METAL PINS HOLDING FIBERGLASS INSULATION BOARDS TO THE EXTERIOR WALLS, AND UNDERNEATH THE SECOND FLOOR ENTRY

ALCOVES ONLY AS NECESSARY TO COMPLETE THE WORK.

6 REMOVE HEATING AND DOMESTIC WATER PIPING WITH FIBERGLASS INSULATION ON RUNS AND ASBESTOS-CONTAINING INSULATION ON FITTINGS, VALVES, ETC. PIPING IS EXPOSED AND CONCEALED ABOVE CEILINGS AND INSIDE WALLS. REMOVE ASBESTOS-CONTAINING GASKETS AND VALVE PACKINGS, ETC., INCLUDING ON SPRINKLER PIPING.

7 REMOVE ASBESTOS-CONTAINING INSULATION FROM ROOF DRAIN PIPING. PIPING IS EXPOSED AND CONCEALED ABOVE CEILINGS AND INSIDE WALLS. PIPING TO REMAIN AND BE RE-INSULATED.

8 REMOVE FIRE DOORS WITH ASBESTOS-CONTAINING INSULATION.

9 REMOVE BOILER WITH ASBESTOS-CONTAINING GASKETS, SEALANTS, AND ASSUMED ASBESTOS-CONTAINING REFRACTORY AND INSULATION AT THE BOILER BASE.

10 CREATE PENETRATIONS IN FOUNDATION WALLS WITH ASSUMED ASBESTOS-CONTAINING TARRY DAMPPROOFING AS NECESSARY TO COMPLETE PLANNED WORK.

11 CREATE PENETRATIONS AND REMOVE REMNANTS OF ORIGINAL ASBESTOS-CONTAINING BUILT-UP ROOFING WHICH IS ASSUMED TO BE PRESENT UNDER NEWER, NON-ASBESTOS ROOFING MATERIALS (INSTALLED IN 2011) AND REMOVE ASBESTOS-CONTAINING PATCHING TARS WHICH MAY BE PRESENT ON THE NON-ASBESTOS ROOFING MATERIALS, ONLY AS NECESSARY TO COMPLETE THE WORK.

12 REMOVE FLUORESCENT LIGHT FIXTURES WITH PCB-CONTAINING BALLASTS AND MERCURY-CONTAINING LIGHT TUBES. REMOVE THERMOSTATS, SWITCHES AND OTHER ELECTRICAL DEVICES CONTAINING

MERCURY.

13 REMOVE HID LIGHT FIXTURES WITH ASSUMED PCB-CONTAINING BALLASTS AND…