Attachment 09 Drawings 8 of 13 Muskogee 623-21-700.pdf
PDF 20 MB Posted
- Solicitation number
- 36C77624R0046
About this file
These are electrical schedule drawings for the EHRM Infrastructure Upgrades project at the Jack C. Montgomery VA Medical Center in Muskogee, Oklahoma. The documents detail comprehensive electrical distribution panel configurations for Buildings 22, 24, and 52, including panel layouts, circuit breaker specifications, load calculations, and conduit/wire routing schedules. The drawings specify technical details such as voltage ratings (primarily 208/120V, 3-phase, 4-wire), bus amperage ratings, and power distribution for various systems including telecom rooms, condensing units, VAV terminal units, access control systems, and digital power metering.
The electrical schedules include precise technical specifications for multiple distribution panels, with emphasis on load management, circuit assignments, and power demand calculations. Each building's electrical system is documented with specific circuit descriptions, VA load information, connected load factors, and estimated demand loads. Notable technical requirements include integral surge protection devices (SPD), digital power meters, and specific conduit and wire specifications for different electrical systems and equipment feeds. The drawings are part of a comprehensive infrastructure upgrade project for the VA medical facility, prepared by Spees Design Build and Dav Energy Solutions, with an issued bid date of 05/24/2024.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Building No.
Drawing Number
Project Number
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Project Title
ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:
321 4 5 6 7 8 9 10
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE I
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
Floor No.
th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:
05/24/2024100% ISSUED FOR BID
A/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
Department of Veteran Affairs
22EP701
ELECTRICAL SCHEDULES
JACK C MONTGOMERY VAMC
05/24/2024 WNM/SJM RTS/BCL
EHRM INFRASTRUCTURE UPGRADES -
JACK C. MONTGOMERY VA MEDICAL
CENTER
623-21-700
-22
1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
Dwg. 72 of 77
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN ANY
ALL CHANGES: ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL ELECTRICAL SCHEDULES.
3. CONTRACTOR SHALL COORDINATE WITH MANUFACTURER TO PROVIDE
OVERCURRENT PROTECTION AS REQUIRED. ANY DEVIATION FROM BASIS OF DESIGN
EQUIPMENT INCLUDING BUT NOT LIMITED CONDUIT AND WIRE, OVERCURRENT
PROTECTION DEVICE RATING AND QUANTITY SHALL BE PROVIDED AT THE EXPENSIVE
OF THE CONTRACTOR.
1 1
PROVIDE (1) 3/4" CONDUIT WITH (2) 12 AWG AND (1) 12 AWG GND TO PROVIDE POWER
TO DDC CONTROLLER. COORDINATE WITH MECHANICAL FOR EXACT LOCATION OF
DDC CONTROLLER.
VOLTAGE: 208/120V, 3P, 4W MAIN: MCB (200A/LSI)
BUS AMPS: 200A AIC: 22KAIC
OPTIONS: PROVIDE INTEGRAL SPD AND DIGITAL POWER METER
A B C
1 20/3 SPD 100 100 100
2 20/3 DPM 100 100 100 1
3 100/3 PANELBOARD "22-B07A-22A" 4753 4117 4033
4 100/3 PANELBOARD "22-104A-22A" 4117 4033 4753
5 25/2 SPLIT DUCTLESS UNIT "CU-B07A-22-1" - 1409 1409
6 25/2 SPLIT DUCTLESS UNIT "CU-B07A-22-2" 1409 - 1409
7 25/2 SPLIT DUCTLESS UNIT "CU-104A-22-1" 1409 1409 -
8 25/2 SPLIT DUCTLESS UNIT "CU-104A-22-2" - 1409 1409
9 20/3 SPARE - - -
10 20/3 SPARE - - -
11889 12578 13214
99 105 110
CONNECTED LOAD (VA)
DEMAND
FACTOR
ESTIMATED
DEMAND (VA)
TOTALS
2818 125.00% 3523
CONN. POWER
LOAD (VA)
37682
3800 100.00% 3800 CONN. AMP (A) 105
1440 100.00% 1440
EST. POWER
DEMAND (VA)
32428
168 125.00% 210
EST. AMP DEMAND
(A)
9455 100.00% 9455
20000 NOTE 2 14000
NOTE 2: TELECOM RACKS DE-RATED FROM 5000VA TO 3500VA PER WHITE PAPER "POWER CAPACITY PLANNING FOR TRS" (JULY
2021).
TOTAL CONNECTED VA BY PHASE
TOTAL CONNECTED AMPS BY PHASE
LOAD TYPE
LARGEST MOTOR
OTHER
RECEPTACLE
LIGHTING
ALL OTHER MOTOR
TR RACK DATA
LOADING
NOTE 1: PROVIDE CT METERING AS REQUIRED FOR BMS MONITORING. DIGITAL POWER METER (DPM) AND SURGE PROTECTION
DEVICE (SPD) SHALL BE INTEGRAL TO PANEL (FACTORY INSTALLED).
DISTRIBUTION PANEL "22-DP-TRA"
CKT # CB/POLE CKT INFORMATION
VA LOAD
NOTES
Location: BLDG 22, RM B07A-22 Volts: 120/208 Wye A.I.C Rating: 22k
Supply From: 22-DP-TRA Phases: 3 Bus Rating: 100A
Mounting: Surface Wires 4 Main Circuit Breaker: 100A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 30 A 3 3333 720 1 20 A 2
3 "" "" 3333 84 1 20 A 4
5 "" "" 3333 0 1 20 A 6
7 20 A 1 0 0 1 20 A 8
9 20 A 1 0 0 1 20 A 10
11 20 A 1 0 500 1 20 A 12
13 20 A 1 500 0 1 20 A 14
15 20 A 1 0 500 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 12904 VA
Other 1600 100.00% 12925 VA
Receptacle 720 100.00% 36 A
Lighting 84 125.00% 36 A
All other Motor 500 100.00%
10000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
1600 Total Est. Power Demand:
720 Total Conn. Amperage:
105 Total Est. Amperage Demand:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
4753 4117 4033
40 34 34
Branch Panel: 22-B07A-22A
VA PER PHASE
CIRCUIT DESCRIPTION A B C
ACCESS CONTROL "22-ACP-B07A" / DOOR POWER SPARE
SPARE VAV / TERMINAL UNIT "TU-B07A-22"
SPARE SPARE
SPARE SPARE
SPARE DDC CONTROLLER
Telecom Rack 10000
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" LIGHTING - TR ROOM
"" SPARE
SPARE SPARE
SPARE SPD
SPARE ""
SPARE ""
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
Location: BLDG 22, RM 104-22 Volts: 120/208 Wye A.I.C Rating: 22k
Supply From: 22-DP-TRA Phases: 3 Bus Rating: 100A
Mounting: Surface Wires 4 Main Circuit Breaker: 100A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 30 A 3 3333 720 1 20 A 2
3 "" "" 3333 84 1 20 A 4
5 "" "" 3333 0 1 20 A 6
7 20 A 1 0 0 1 20 A 8
9 20 A 1 0 0 1 20 A 10
11 20 A 1 0 500 1 20 A 12
13 -- -- 500 0 1 20 A 14
15 20 A 1 0 500 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 12904 VA
Other 1600 100.00% 12925 VA
Receptacle 720 100.00% 36 A
Lighting 84 125.00% 36 A
All other Motor 500 100.00%
10000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Branch Panel: 22-104A-22A
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPARE SPARE
SPARE SPARE
SPARE DDC CONTROLLER
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" LIGHTING - TR ROOM
"" SPARE
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
ACCESS CONTROL "22-ACP-104A" / DOOR POWER SPARE
SPARE VAV / TERMINAL UNIT "TU-104A-22"
SPARE SPARE
SPARE SPD
SPARE ""
SPARE ""
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
4753 4117 4033
40 34 34
Telecom Rack 10000
1600 Total Est. Power Demand:
720 Total Conn. Amperage:
105 Total Est. Amperage Demand:
VOLTAGE: 208/120V, 3P, 4W MAIN: MCB (200A/LSI)
BUS AMPS: 200A AIC: 22KAIC
OPTIONS: PROVIDE INTEGRAL SPD AND DIGITAL POWER METER
A B C
1 20/3 SPD 100 100 100
2 20/3 DPM 100 100 100 1
3 100/3 PANELBOARD "22-B07A-22B" 4253 3617 3533
4 100/3 PANELBOARD "22-104A-22B" 4253 3575 3533
5 25/2 SPARE - - -
6 25/2 SPARE - - -
7 25/2 SPARE - - -
8 25/2 SPARE - - -
9 20/3 SPARE - - -
10 20/3 SPARE - - -
8707 7393 7267
73 62 61
CONNECTED LOAD (VA)
DEMAND
FACTOR
ESTIMATED
DEMAND (VA)
TOTALS
0 125.00% 0
CONN. POWER
LOAD (VA)
23366
1800 100.00% 1800 CONN. AMP (A) 65
1440 100.00% 1440
EST. POWER
DEMAND (VA)
17398
126 125.00% 158
EST. AMP DEMAND
(A)
0 100.00% 0
20000 NOTE 2 14000
NOTE 2: TELECOM RACKS DE-RATED FROM 5000VA TO 3500VA PER WHITE PAPER "POWER CAPACITY PLANNING FOR TRS"
(JULY 2021).
TOTAL CONNECTED VA BY PHASE
TOTAL CONNECTED AMPS BY PHASE
LOAD TYPE
LARGEST MOTOR
OTHER
RECEPTACLE
LIGHTING
ALL OTHER MOTOR
TR RACK DATA
LOADING
NOTE 1: PROVIDE CT METERING AS REQUIRED FOR BMS MONITORING. DIGITAL POWER METER (DPM) AND SURGE
PROTECTION DEVICE (SPD) SHALL BE INTEGRAL TO PANEL (FACTORY INSTALLED).
DISTRIBUTION PANEL "22-DP-TRB"
CKT # CB/POLE CKT INFORMATION
VA LOAD
NOTES
Location: BLDG 22, RM B07A-22 Volts: 120/208 Wye A.I.C Rating: 22k
Supply From: 22-DP-TRB Phases: 3 Bus Rating: 100A
Mounting: Surface Wires 4 Main Circuit Breaker: 100A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 30 A 3 3333 720 1 20 A 2
3 "" "" 3333 84 1 20 A 4
5 "" "" 3333 0 1 20 A 6
7 20 A 1 0 0 1 20 A 8
9 20 A 1 0 0 1 20 A 10
11 20 A 1 0 0 1 20 A 12
13 20 A 1 0 0 1 20 A 14
15 20 A 1 0 0 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 11404 VA
Other 600 100.00% 11425 VA
Receptacle 720 100.00% 32 A
Lighting 84 125.00% 32 A
All other Motor 0 100.00%
10000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
600 Total Est. Power Demand:
720 Total Conn. Amperage:
105 Total Est. Amperage Demand:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
4253 3617 3533
35 30 29
Branch Panel: 22-B07A-22B
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPARE
Telecom Rack 10000
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" LIGHTING - TR ROOM
"" SPARE
SPARE SPARE
SPARE SPD
SPARE ""
SPARE ""
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
Location: BLDG 22, RM 104 Volts: 120/208 Wye A.I.C Rating: 22k
Supply From: 22-DP-TRB Phases: 3 Bus Rating: 100A
Mounting: Surface Wires 4 Main Circuit Breaker: 100A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 30 A 3 3333 720 1 20 A 2
3 "" "" 3333 42 1 20 A 4
5 "" "" 3333 0 1 20 A 6
7 20 A 1 0 0 1 20 A 8
9 20 A 1 0 0 1 20 A 10
11 20 A 1 0 0 1 20 A 12
13 20 A 1 0 0 1 20 A 14
15 20 A 1 0 0 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 11362 VA
Other 600 100.00% 11373 VA
Receptacle 720 100.00% 32 A
Lighting 42 125.00% 32 A
All other Motor 0 100.00%
10000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
600 Total Est. Power Demand:
720 Total Conn. Amperage:
53 Total Est. Amperage Demand:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
4253 3575 3533
35 30 29
Branch Panel: 22-104A-22B
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPARE
Telecom Rack 10000
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" LIGHTING - TR ROOM
"" SPARE
SPARE SPARE
SPARE SPD
SPARE ""
SPARE ""
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
FROM TO QTY SIZE (QTY) & SIZE
GROUND
SIZE
22-P-01A DISTRIBUTION PANEL "22-DP-TRA" PANELBOARD "ABEQ" JUNCTION BOX "22-JB-01" 1 2" (4) 3/0 AWG 6 AWG - -
22-P-01B DISTRIBUTION PANEL "22-DP-TRA" JUNCTION BOX "22-JB-01" JUNCTION BOX "22-JB-02" 2 2" (4) 1/0 AWG 1 AWG 1.5% -
22-P-01C DISTRIBUTION PANEL "22-DP-TRA" JUNCTION BOX "22-JB-02" DISTRIBUTION PANEL "22-DP-TRA" 1 2" (4) 3/0 AWG 6 AWG - - 22-P-02 PANELBOARD "22-B07A-22A" DISTRIBUTION PANEL "22-DP-TRA" PANELBOARD "22-B07A-22A" 1 1-1/4" (4) 2 AWG 6 AWG 2.0% -
22-P-03 PANELBOARD "22-104A-22A" DISTRIBUTION PANEL "22-DP-TRA" PANELBOARD "22-104A-22A" 1 1-1/4" (4) 3 AWG 8 AWG 1.2% - 22-P-04 DISTRIBUTION PANEL "22-DP-TRB" DISTRIBUTION PANEL "MSB22" DISTRIBUTION PANEL "22-DP-TRB" 1 2" (4) 3/0 AWG 6 AWG 0.3% -
22-P-05 PANELBOARD "22-B07A-22B" DISTRIBUTION PANEL "22-DP-TRB" PANELBOARD "22-B07A-22B" 1 1-1/4" (4) 3 AWG 8 AWG 1.2% - 22-P-06 PANELBOARD "22-104A-22B" DISTRIBUTION PANEL "22-DP-TRB" PANELBOARD "22-104A-22B" 1 1-1/4" (4) 3 AWG 8 AWG 0.4% -
22-P-07 CONDENSING UNIT "CU-B07A-22-1" DISTRIBUTION PANEL "22-DP-TRA" CONDENSING UNIT "CU-B07A-22-1" 1 3/4" (2) 10 AWG 10 AWG 3.8% - 22-P-08 CONDENSING UNIT "CU-B07A-22-2" DISTRIBUTION PANEL "22-DP-TRA" CONDENSING UNIT "CU-B07A-22-2" 1 3/4" (2) 10 AWG 10 AWG 3.8% -
22-P-09 CONDENSING UNIT "CU-104A-22-1" DISTRIBUTION PANEL "22-DP-TRA" CONDENSING UNIT "CU-104A-22-1" 1 3/4" (2) 10 AWG 10 AWG 3.1% - 22-P-10 CONDENSING UNIT "CU-104A-22-2" DISTRIBUTION PANEL "22-DP-TRA" CONDENSING UNIT "CU-104A-22-2" 1 3/4" (2) 10 AWG 10 AWG 3.1% -
P-TR-1A TYPICAL TELECOM ROOM DATA RACK POWER FEED (1-RACK), SIDE A TYPICAL SOURCE A TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE A RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE - P-TR-2A TYPICAL TELECOM ROOM DATA RACK POWER FEED (2-RACK), SIDE A TYPICAL SOURCE A TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE A RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE -
P-TR-1B TYPICAL TELECOM ROOM DATA RACK POWER FEED (1-RACK), SIDE B TYPICAL SOURCE B TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE B RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE -
P-TR-2B TYPICAL TELECOM ROOM DATA RACK POWER FEED (2-RACK), SIDE B TYPICAL SOURCE B TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE B RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE -
NOTES
NOTE(S):
1. NONE.
BLDG 22 - CONDUIT AND WIRE SCHEDULE - VA OK MUSKOGEE EHRM UPGRADES
CONDUIT
TAG
SERVICE
ROUTING CONDUIT CONDUCTORS
VOLTAGE
DROP
Project Number
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Project Title
ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:
321 4 5 6 7 8 9 10
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE I
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
Floor No.
th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:
05/24/2024100% ISSUED FOR BID
A/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
Department of Veteran Affairs
24EP701
ELECTRICAL SCHEDULES
JACK C MONTGOMERY VAMC
05/24/2024 WNM/SJM RTS/BCL
EHRM INFRASTRUCTURE UPGRADES -
JACK C. MONTGOMERY VA MEDICAL
CENTER
623-21-700
-24
1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
Dwg. 73 of 77
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN ANY
ALL CHANGES: ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL ELECTRICAL SCHEDULES.
3. CONTRACTOR SHALL COORDINATE WITH MANUFACTURER TO PROVIDE
OVERCURRENT PROTECTION AS REQUIRED. ANY DEVIATION FROM BASIS OF DESIGN
EQUIPMENT INCLUDING BUT NOT LIMITED CONDUIT AND WIRE, OVERCURRENT
PROTECTION DEVICE RATING AND QUANTITY SHALL BE PROVIDED AT THE EXPENSIVE
OF THE CONTRACTOR.
PROVIDE (1) 3/4" CONDUIT WITH (2) 12 AWG AND (1) 12 AWG GND TO PROVIDE POWER
TO DDC CONTROLLER. COORDINATE WITH MECHANICAL FOR EXACT LOCATION OF
DDC CONTROLLER.
VOLTAGE: 208/120V, 3P, 4W MAIN: MCB (200A/LSI)
BUS AMPS: 200A AIC: 22KAIC
OPTIONS: PROVIDE INTEGRAL SPD AND DIGITAL POWER METER
A B C
1 20/3 SPD 100 100 100
2 20/3 DPM 100 100 100 1
3 100/3 PANELBOARD "24-B4B-24A" 3587 3860 3276
4 100/3 PANELBOARD "24-112-24A" 6022 6352 6163
5 100/3 PANELBOARD "24-205-24A" 6352 6163 6004
6 20/3 SPARE - - -
7 20/3 SPARE - - -
8 20/3 SPARE - - -
9 20/3 SPARE - - -
10 20/3 SPARE - - -
16160 16574 15642
135 138 130
CONNECTED LOAD (VA)
DEMAND
FACTOR
ESTIMATED
DEMAND (VA)
TOTALS
2818 125.00% 3523
CONN. POWER
LOAD (VA)
48377
5400 100.00% 5400 CONN. AMP (A) 134
2160 100.00% 2160
EST. POWER
DEMAND (VA)
41637
225 125.00% 281
EST. AMP DEMAND
(A)
12774 100.00% 12774
25000 NOTE 2 17500
DISTRIBUTION PANEL "24-DP-TRA"
CKT # CB/POLE CKT INFORMATION
VA LOAD
NOTES
NOTE 2: TELECOM RACKS DE-RATED FROM 5000VA TO 3500VA PER WHITE PAPER "POWER CAPACITY PLANNING FOR TRS"
(JULY 2021).
TOTAL CONNECTED VA BY PHASE
TOTAL CONNECTED AMPS BY PHASE
LOAD TYPE
LARGEST MOTOR
OTHER
RECEPTACLE
LIGHTING
ALL OTHER MOTOR
TR RACK DATA
LOADING
NOTE 1: PROVIDE CT METERING AS REQUIRED FOR BMS MONITORING. DIGITAL POWER METER (DPM) AND SURGE
PROTECTION DEVICE (SPD) SHALL BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Location: BLDG 24, RM B4B-24 Volts: 120/208 Wye A.I.C Rating: 22k
Supply From: 24-DP-TRA Phases: 3 Bus Rating: 100A
Mounting: Surface Wires 4 Main Circuit Breaker: 100A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 20 A 3 1667 720 1 20 A 2
3 "" "" 1667 84 1 20 A 4
5 "" "" 1667 0 1 20 A 6
7 20 A 1 0 0 1 20 A 8
9 20 A 1 0 1409 2 25 A 10
11 20 A 1 0 1409 "" "" 12
13 20 A 1 500 500 1 20 A 14
15 20 A 1 0 500 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 2818 125.00% 10722 VA
Other 1600 100.00% 11448 VA
Receptacle 720 100.00% 30 A
Lighting 84 125.00% 32 A
All other Motor 500 100.00%
5000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
1600 Total Est. Power Demand:
720 Total Conn. Amperage:
105 Total Est. Amperage Demand:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
3523 Total Conn. Power Load:
3587 3860 3276
30 32 27
Branch Panel: 24-B4B-24A
VA PER PHASE
CIRCUIT DESCRIPTION A B C
ACCESS CONTROL "24-ACP-B4B" / DOOR POWER DDC CONTROLLER
SPARE VAV / TERMINAL UNIT "TU-B4B-24"
SPARE SPARE
SPARE SPLIT DUCTLESS COOLING UNIT "CU-24-B4B-24-1"
SPARE ""
Telecom Rack 5000
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" LIGHTING - TR ROOM
"" SPARE
SPARE SPARE
SPARE SPD
SPARE ""
SPARE ""
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
Location: BLDG 24, RM 112-24 Volts: 120/208 Wye A.I.C Rating: 22k
Supply From: 24-DP-TRA Phases: 3 Bus Rating: 100A
Mounting: Surface Wires 4 Main Circuit Breaker: 100A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 30 A 3 3333 720 1 20 A 2
3 "" "" 3333 79 1 20 A 4
5 "" "" 3333 1409 2 25 A 6
7 20 A 1 0 1409 "" "" 8
9 20 A 1 0 1409 2 25 A 10
11 20 A 1 0 1409 "" "" 12
13 20 A 1 500 0 1 20 A 14
15 20 A 1 500 500 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 2818 125.00% 18536 VA
Other 1600 100.00% 19261 VA
Receptacle 720 100.00% 51 A
Lighting 79 125.00% 53 A
All other Motor 3318 100.00%
10000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Branch Panel: 24-112-24A
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPARE ""
SPARE SPLIT DUCTLESS COOLING UNIT "CU-24-112-24-2"
SPARE ""
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" LIGHTING - TR ROOM
"" SPLIT DUCTLESS COOLING UNIT "CU-24-112-24-1"
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
ACCESS CONTROL "24-ACP-112" / DOOR POWER SPARE
DDC CONTROLLER VAV / TERMINAL UNIT "TU-112-24"
SPARE SPARE
SPARE SPD
SPARE ""
SPARE ""
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
3523 Total Conn. Power Load:
6163 6022 6352
51 50 53
Telecom Rack 10000
1600 Total Est. Power Demand:
720 Total Conn. Amperage:
99 Total Est. Amperage Demand:
VOLTAGE: 208/120V, 3P, 4W MAIN: MCB (200A/LSI)
BUS AMPS: 200A AIC: 22KAIC
OPTIONS: PROVIDE INTEGRAL SPD AND DIGITAL POWER METER
A B C
1 20/3 SPD 100 100 100
2 20/3 DPM 100 100 100 1
3 100/3 PANELBOARD "24-B4B-24A" 4253 3617 3533
4 100/3 PANELBOARD "24-112-24A" 3613 3533 4253
5 100/3 PANELBOARD "24-205-24A" 3533 4253 3564
6 20/3 SPARE - - -
7 20/3 SPARE - - -
8 20/3 SPARE - - -
9 20/3 SPARE - - -
10 20/3 SPARE - - -
11599 11604 11551
97 97 96
CONNECTED LOAD (VA)
DEMAND
FACTOR
ESTIMATED
DEMAND (VA)
TOTALS
0 125.00% 0
CONN. POWER
LOAD (VA)
29754
2400 100.00% 2400 CONN. AMP (A) 83
2160 100.00% 2160
EST. POWER
DEMAND (VA)
22303
194 125.00% 243
EST. AMP DEMAND
(A)
0 100.00% 0
25000 NOTE 2 17500
DISTRIBUTION PANEL "24-DP-TRB"
CKT # CB/POLE CKT INFORMATION
VA LOAD
NOTES
NOTE 2: TELECOM RACKS DE-RATED FROM 5000VA TO 3500VA PER WHITE PAPER "POWER CAPACITY PLANNING FOR TRS"
(JULY 2021).
TOTAL CONNECTED VA BY PHASE
TOTAL CONNECTED AMPS BY PHASE
LOAD TYPE
LARGEST MOTOR
OTHER
RECEPTACLE
LIGHTING
ALL OTHER MOTOR
TR RACK DATA
LOADING
NOTE 1: PROVIDE CT METERING AS REQUIRED FOR BMS MONITORING. DIGITAL POWER METER (DPM) AND SURGE
PROTECTION DEVICE (SPD) SHALL BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Location: BLDG 24, RM B4B-24 Volts: 120/208 Wye A.I.C Rating: 22k
Supply From: 24-DP-TRB Phases: 3 Bus Rating: 100A
Mounting: Surface Wires 4 Main Circuit Breaker: 100A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 20 A 3 1667 720 1 20 A 2
3 "" "" 1667 84 1 20 A 4
5 "" "" 1667 0 1 20 A 6
7 20 A 1 0 0 1 20 A 8
9 20 A 1 0 0 1 20 A 10
11 20 A 1 0 0 1 20 A 12
13 20 A 1 0 0 1 20 A 14
15 20 A 1 0 0 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 6404 VA
Other 600 100.00% 6425 VA
Receptacle 720 100.00% 18 A
Lighting 84 125.00% 18 A
All other Motor 0 100.00%
5000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
600 Total Est. Power Demand:
720 Total Conn. Amperage:
105 Total Est. Amperage Demand:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
2587 1951 1867
22 16 16
Branch Panel: 24-B4B-24B
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPARE
Telecom Rack 5000
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" LIGHTING - TR ROOM
"" SPARE
SPARE SPARE
SPARE SPD
SPARE ""
SPARE ""
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
Location: BLDG 24, RM 112-24 Volts: 120/208 Wye A.I.C Rating: 22k
Supply From: 24-DP-TRB Phases: 3 Bus Rating: 100A
Mounting: Surface Wires 4 Main Circuit Breaker: 100A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 30 A 3 3333 720 1 20 A 2
3 "" "" 3333 79 1 20 A 4
5 "" "" 3333 0 1 20 A 6
7 20 A 1 0 0 1 20 A 8
9 20 A 1 0 0 1 20 A 10
11 20 A 1 0 0 1 20 A 12
13 20 A 1 0 0 1 20 A 14
15 20 A 1 0 0 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 11399 VA
Other 600 100.00% 11419 VA
Receptacle 720 100.00% 32 A
Lighting 79 125.00% 32 A
All other Motor 0 100.00%
10000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
600 Total Est. Power Demand:
720 Total Conn. Amperage:
99 Total Est. Amperage Demand:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
4253 3613 3533
35 30 29
Branch Panel: 24-112-24B
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPARE
Telecom Rack 10000
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" LIGHTING - TR ROOM
"" SPARE
SPARE SPARE
SPARE SPD
SPARE ""
SPARE ""
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
FROM TO QTY SIZE (QTY) & SIZE
GROUND
SIZE
24-P-01A DISTRIBUTION PANEL "24MDP" JUNCTION BOX "JB-24MDP" DISTRIBUTION PANEL "24MDP" 2 3" (4) 500 kcmil 1/0 AWG 0.67%
24-P-01B DISTRIBUTION PANEL "24-DP-TRB" DISTRIBUTION PANEL "24MDP" DISTRIBUTION PANEL "24-DP-TRB" 1 2" (4) 3/0 AWG 6 AWG 1.0% -
24-P-02 PANELBOARD "24-B4B-24B" DISTRIBUTION PANEL "24-DP-TRB" PANELBOARD "24-B4B-24B" 1 1-1/4" (4) 3 AWG 8 AWG 1.1% -
24-P-03 PANELBOARD "24-112-24B" DISTRIBUTION PANEL "24-DP-TRB" PANELBOARD "24-112-24B" 1 1-1/4" (4) 3 AWG 8 AWG 1.1% -
24-P-04 PANELBOARD "24-206A-24B" DISTRIBUTION PANEL "24-DP-TRB" PANELBOARD "24-206A-24B" 1 1-1/4" (4) 3 AWG 8 AWG 1.8% -
24-P-05A ATS-24, NORMAL FEED MCC-24 ATS-24, NORMAL FEED 2 2" (4) 3/0 AWG 3 AWG 0.2%
24-P-05B ATS-24, EMERGENCY FEED DISTRIBUTION PANEL "G46A" JUNCTION BOX "24-JB-01" 2 2" (4) 3/0 AWG 3 AWG - -
24-P-05C ATS-24, EMERGENCY FEED JUNCTION BOX "24-JB-01" JUNCTION BOX "24-JB-02" 3 4" (4) 600 KCMIL 600 KCMIL 1.2%
24-P-05D ATS-24, EMERGENCY FEED JUNCTION BOX "24-JB-02" ATS-24, EMERGENCY FEED 2 2" (4) 3/0 AWG 3 AWG - -
24-P-05E PANELBOARD "24BE" ATS-24 PANELBOARD "24BE" 2 3" (4) 250 KCMIL 250 KCMIL 1.5% -
24-P-05F DISTRIBUTION PANEL "24-DP-TRA" PANELBOARD "24BE" DISTRIBUTION PANEL "24-DP-TRA" 1 3" (4) 250 KCMIL 250 KCMIL 1.6%
24-P-06 PANELBOARD "24-B4B-24A" DISTRIBUTION PANEL "22-DP-TRA" PANELBOARD "24-B4B-24A" 1 2" (4) 1 AWG 3 AWG 0.4% -
24-P-07 PANELBOARD "24-112-24A" DISTRIBUTION PANEL "22-DP-TRA" PANELBOARD "24-112-24A" 1 2" (4) 1 AWG 3 AWG 2.0% -
24-P-08A PANELBOARD "24-206A-24A" DISTRIBUTION PANEL "22-DP-TRA" JUNCTION BOX "24-JB-03" 1 1-1/4" (4) 3 AWG 8 AWG - -
24-P-08B PANELBOARD "24-206A-24A" JUNCTION BOX "24-JB-03" JUNCTION BOX "24-JB-04" 1 3" (4) 250 KCMIL 250 KCMIL 2.0% -
24-P-08C PANELBOARD "24-206A-24A" JUNCTION BOX "24-JB-04" PANELBOARD "24-206A-24A" 1 1-1/4" (4) 3 AWG 8 AWG - -
24-P-09 CONDENSING UNIT "CU-B4B-24-1" PANELBOARD "24-B4B-24A" CONDENSING UNIT "CU-B4B-24-1" 1 3/4" (2) 10 AWG 10 AWG 1.8% -
24-P-10 CONDENSING UNIT "CU-112-24-1" PANELBOARD "24-112-24A" CONDENSING UNIT "CU-112-24-1" 1 3/4" (2) 10 AWG 10 AWG 4.1% -
24-P-11 CONDENSING UNIT "CU-112-24-2" PANELBOARD "24-112-24A" CONDENSING UNIT "CU-112-24-2" 1 3/4" (2) 10 AWG 10 AWG 4.1% -
24-P-12 CONDENSING UNIT "CU-205-24-1" PANELBOARD "24-206A-24A" CONDENSING UNIT "CU-205-24-1" 1 3/4" (2) 10 AWG 10 AWG 3.0% -
24-P-13 CONDENSING UNIT "CU-205-24-2" PANELBOARD "24-206A-24A" CONDENSING UNIT "CU-205-24-2" 1 3/4" (2) 10 AWG 10 AWG 3.0% -
P-TR-1A TYPICAL TELECOM ROOM DATA RACK POWER FEED (1-RACK), SIDE A TYPICAL SOURCE A TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE A RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE -
P-TR-2A TYPICAL TELECOM ROOM DATA RACK POWER FEED (2-RACK), SIDE A TYPICAL SOURCE A TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE A RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE -
P-TR-1B TYPICAL TELECOM ROOM DATA RACK POWER FEED (1-RACK), SIDE B TYPICAL SOURCE B TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE B RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE -
P-TR-2B TYPICAL TELECOM ROOM DATA RACK POWER FEED (2-RACK), SIDE B TYPICAL SOURCE B TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE B RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE -
NOTES
NOTE(S):
1. NONE
BLDG 24 - CONDUIT AND WIRE SCHEDULE - VA OK MUSKOGEE EHRM UPGRADES
CONDUIT
TAG
SERVICE
ROUTING CONDUIT CONDUCTORS
VOLTAGE
DROP
Project Number
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Project Title
ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:
321 4 5 6 7 8 9 10
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE I
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
Floor No.
th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:
05/24/2024100% ISSUED FOR BID
A/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
Department of Veteran Affairs
24EP702
ELECTRICAL SCHEDULES
JACK C MONTGOMERY VAMC
05/24/2024 WNM/SJM RTS/BCL
EHRM INFRASTRUCTURE UPGRADES -
JACK C. MONTGOMERY VA MEDICAL
CENTER
623-21-700
-24
1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
Dwg. 74 of 77
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN ANY
ALL CHANGES: ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL ELECTRICAL SCHEDULES.
3. CONTRACTOR SHALL COORDINATE WITH MANUFACTURER TO PROVIDE
OVERCURRENT PROTECTION AS REQUIRED. ANY DEVIATION FROM BASIS OF DESIGN
EQUIPMENT INCLUDING BUT NOT LIMITED CONDUIT AND WIRE, OVERCURRENT
PROTECTION DEVICE RATING AND QUANTITY SHALL BE PROVIDED AT THE EXPENSIVE
OF THE CONTRACTOR.
VOLTAGE: 208/120V, 3P, 4W MAIN: MCB (800A/LSGI)
BUS AMPS: 800A AIC: 30KAIC
OPTIONS: PROVIDE INTEGRAL SPD AND DIGITAL POWER METER
A B C
1 20/3 SPD 100 100 100
2 20/3 DPM 100 100 100 1
3 300/3 PANELBOARD "24-AL-AR" - - - 2
4 200/3 PANELBOARD "24-BAC" - - - 2
5 175/3 PANELBOARD "24-BL-BR" - - - 2
6 225/3 PANELBOARD "24-SBA" - - - 2
7 100/3 PANELBOARD "24-BB" - - - 2
8 70/3 SPARE - - - 2
9 70/3 SPARE - - - 2
10 300/3 PANELBOARD "24-K" - - - 2
11 225/3 PANELBOARD "24-1A-1B" - - - 2
12 200/3 SPARE - - - 2
19 175/3 KITCHEN EQUIPMENT - - - 2
20 200/3 ELEVATOR - - - 2
21 100/3 CANTEEN BLOWER - - - 2
22 100/3 SPARE - - - 2
23 200AT/225AF/3 24-DP-TRB 11599 11604 11551
24 100/3 SPARE - - -
25 100/3 SPARE - - -
26 100/3 SPARE - - -
11799 11804 11751
98 98 98
CONNECTED LOAD (VA)
DEMAND
FACTOR
ESTIMATED
DEMAND (VA)
TOTALS
0 125.00% 0
CONN. POWER
LOAD (VA)
30354
3000 100.00% 3000 CONN. AMP (A) 84
2160 100.00% 2160
EST. POWER
DEMAND (VA)
17903
194 125.00% 243
EST. AMP DEMAND
(A)
0 100.00% 0
25000 NOTE 2 12500
NOTE 3: FOR EXISTING LOADING INFORMATION REFERENCE "METERING AND LOAD INFORMATION SCHEDULE" ON SHEET EP702.
NOTE 2: TELECOM RACKS DE-RATED FROM 5000VA TO 2500VA PER WHITE PAPER "POWER CAPACITY PLANNING FOR TRS" (JULY
2021).
TOTAL CONNECTED VA BY PHASE
TOTAL CONNECTED AMPS BY PHASE
LOAD TYPE
LARGEST MOTOR
OTHER
RECEPTACLE
LIGHTING
ALL OTHER MOTOR
TR RACK DATA
LOADING
NOTE 1: PROVIDE CT METERING AS REQUIRED FOR BMS MONITORING. DIGITAL POWER METER (DPM) AND SURGE PROTECTION
DEVICE (SPD) SHALL BE INTEGRAL TO PANEL (FACTORY INSTALLED).
DISTRIBUTION PANEL "24MDP"
CKT # CB/POLE CKT INFORMATION
VA LOAD
NOTES
LSIG
PROVIDE (1) 3/4" CONDUIT WITH (2) 12 AWG AND (1) 12 AWG GND TO PROVIDE POWER
TO DDC CONTROLLER. COORDINATE WITH MECHANICAL FOR EXACT LOCATION OF
DDC CONTROLLER.
Location: BLDG 24, RM 205-24 Volts: 120/208 Wye A.I.C Rating: 22k
Supply From: 24-DP-TRA Phases: 3 Bus Rating: 100A
Mounting: Surface Wires 4 Main Circuit Breaker: 100A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 30 A 3 3333 720 1 20 A 2
3 "" "" 3333 61 1 20 A 4
5 "" "" 3333 1409 2 25 A 6
7 20 A 1 0 1409 "" "" 8
9 20 A 1 0 1409 2 25 A 10
11 20 A 1 0 1409 "" "" 12
13 20 A 1 500 0 1 20 A 14
15 20 A 1 500 500 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 2818 125.00% 18518 VA
Other 1600 100.00% 19238 VA
Receptacle 720 100.00% 51 A
Lighting 61 125.00% 53 A
All other Motor 3318 100.00%
10000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Branch Panel: 24-205-24A
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPARE ""
SPARE SPLIT DUCTLESS COOLING UNIT "CU-24-205-24-2"
SPARE ""
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" LIGHTING - TR ROOM
"" SPLIT DUCTLESS COOLING UNIT "CU-24-205-24-1"
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
ACCESS CONTROL "24-ACP-205" / DOOR POWER SPARE
DDC CONTROLLER VAV / TERMINAL UNIT "TU-205-24"
SPARE SPARE
SPARE SPD
SPARE ""
SPARE ""
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
3523 Total Conn. Power Load:
6163 6004 6352
51 50 53
Telecom Rack 10000
1600 Total Est. Power Demand:
720 Total Conn. Amperage:
77 Total Est. Amperage Demand:
Location: BLDG 24, RM 205-24 Volts: 120/208 Wye A.I.C Rating: 22k
Supply From: 24-DP-TRB Phases: 3 Bus Rating: 100A
Mounting: Surface Wires 4 Main Circuit Breaker: 100A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 30 A 3 3333 720 1 20 A 2
3 "" "" 3333 31 1 20 A 4
5 "" "" 3333 0 1 20 A 6
7 20 A 1 0 0 1 20 A 8
9 20 A 1 0 0 1 20 A 10
11 20 A 1 0 0 1 20 A 12
13 20 A 1 0 0 1 20 A 14
15 20 A 1 0 0 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 11351 VA
Other 600 100.00% 11358 VA
Receptacle 720 100.00% 32 A
Lighting 31 125.00% 32 A
All other Motor 0 100.00%
10000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Branch Panel: 24-205-24B
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPARE SPARE
SPARE SPARE
SPARE SPARE
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" LIGHTING - TR ROOM
"" SPARE
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPD
SPARE ""
SPARE ""
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
4253 3564 3533
35 30 29
Telecom Rack 10000
600 Total Est. Power Demand:
720 Total Conn. Amperage:
38 Total Est. Amperage Demand:
Project Number
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Project Title
ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:
321 4 5 6 7 8 9 10
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE I
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
Floor No.
th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:
05/24/2024100% ISSUED FOR BID
A/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
Department of Veteran Affairs
52EP701
ELECTRICAL SCHEDULES
JACK C MONTGOMERY VAMC
05/24/2024 WNM/SJM RTS/BCL
EHRM INFRASTRUCTURE UPGRADES -
JACK C. MONTGOMERY VA MEDICAL
CENTER
623-21-700
-52
1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
Dwg. 75 of 77
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN ANY
ALL CHANGES: ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL ELECTRICAL SCHEDULES.
3. CONTRACTOR SHALL COORDINATE WITH MANUFACTURER TO PROVIDE
OVERCURRENT PROTECTION AS REQUIRED. ANY DEVIATION FROM BASIS OF DESIGN
EQUIPMENT INCLUDING BUT NOT LIMITED CONDUIT AND WIRE, OVERCURRENT
PROTECTION DEVICE RATING AND QUANTITY SHALL BE PROVIDED AT THE EXPENSIVE
OF THE CONTRACTOR.
PROVIDE (1) 3/4" CONDUIT WITH (2) 12 AWG AND (1) 12 AWG GND TO PROVIDE POWER
TO DDC CONTROLLER. COORDINATE WITH MECHANICAL FOR EXACT LOCATION OF
DDC CONTROLLER.
FROM TO QTY SIZE (QTY) & SIZE
GROUND
SIZE
52-P-01 TRANSFER SWITCH "52-ATS-TRA" EMERGENCY FEED SWITCHBOARD GSHBA TRANSFER SWITCH "52-ATS-TRA" EMERGENCY FEED 1 3" (4) 4/0 AWG 4 AWG 0.7% 1
52-P-02 TRANSFER SWITCH "52-ATS-TRA" NORMAL FEED SUBSTATION 1 TRANSFER SWITCH "52-ATS-TRA" NORMAL FEED 1 2" (4) 3/0 AWG 6 AWG 0.1% -
52-P-03 PANELBOARD "52-201B-522A" TRANSFER SWITCH "52-ATS-TRA" LOAD FEED TRANSFORMER "52-XFMR-TRA" PRIMARY SIDE 1 2" (3) 1 AWG 6 AWG 0.8% -
52-P-04 PANELBOARD "52-201B-522A" TRANSFORMER "52-XFMR-TRA" SECONDARY SIDE PANELBOARD "52-201B-522A" 1 3" (4) 4/0 AWG 4 AWG 0.9% -
52-P-05 TRANSFER SWITCH "ATS-ECB" EMERGENCY FEED SWITCHBOARD EDP TRANSFER SWITCH "ATS-ECB" EMERGENCY FEED 2 4" (4) 350 kcmil 1 AWG 1.7% 1
52-P-06 TRANSFER SWITCH "ATS-ECB" NORMAL FEED SUBSTATION 6 TRANSFER SWITCH "ATS-ECB" NORMAL FEED 2 4" (4) 350 kcmil 1 AWG 1.5% 1
52-P-07 PANELBOARD "ECHCP" TRANSFER SWITCH "ATS-ECB" LOAD FEED PANELBOARD "ECHCP" 2 3" (4) 350 kcmil 1 AWG 1.8% -
52-P-08 PANELBOARD "52-201B-52B" PANELBOARD "ECHCP" TRANSFORMER "52-XFMR-TRB" PRIMARY SIDE 1 1-1/2" (3) 1 AWG 6 AWG 2.0%
52-P-09 PANELBOARD "52-201B-52B" TRANSFORMER "52-XFMR-TRB" PRIMARY SIDE PANELBOARD "52-201B-52B" 1 2-1/2" (4) 4/0 AWG 4 AWG 0.1%
52-P-10 CONDENSING UNIT "CU-201B-52-1" PANELBOARD "52-201B-522A" CONDENSING UNIT "CU-201B-52-1" 1 3/4" (2) 10 AWG 10 AWG 2.6% -
52-P-11 CONDENSING UNIT "CU-201B-52-2" PANELBOARD "52-201B-522A" CONDENSING UNIT "CU-201B-52-2" 1 3/4" (2) 10 AWG 10 AWG 2.6% -
52-P-12 CONDENSING UNIT "CU-201B-52-3" PANELBOARD "52-201B-522A" CONDENSING UNIT "CU-201B-52-3" 1 3/4" (2) 10 AWG 10 AWG 2.6%
52-P-13 CONDENSING UNIT "CU-201B-52-4" PANELBOARD "52-201B-522A" CONDENSING UNIT "CU-201B-52-4" 1 3/4" (2) 10 AWG 10 AWG 2.6% -
52-C-01 TRANSFER SWITCH "52-ATS-TRA" CONTROL / STATUS WIRING TRANSFER SWITCH "52-ATS-TRA" GENERATOR CONTROL ENCLOSURE 1 3/4" (2) 10 AWG 10 AWG - 2
P-TR-1A TYPICAL TELECOM ROOM DATA RACK POWER FEED (1-RACK), SIDE A TYPICAL SOURCE A TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE A RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE -
P-TR-2A TYPICAL TELECOM ROOM DATA RACK POWER FEED (2-RACK), SIDE A TYPICAL SOURCE A TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE A RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE -
P-TR-3A TYPICAL TELECOM ROOM DATA RACK POWER FEED (3-RACK), SIDE A TYPICAL SOURCE A TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE A JUNCTION BOX 1 1" (4) 6 AWG 8 AWG NEGLIGIBLE -
P-TR-1B TYPICAL TELECOM ROOM DATA RACK POWER FEED (1-RACK), SIDE B TYPICAL SOURCE B TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE B RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE -
P-TR-2B TYPICAL TELECOM ROOM DATA RACK POWER FEED (2-RACK), SIDE B TYPICAL SOURCE B TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE B RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE -
P-TR-3B TYPICAL TELECOM ROOM DATA RACK POWER FEED (3-RACK), SIDE B TYPICAL SOURCE B TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE B JUNCTION BOX 1 1" (4) 6 AWG 8 AWG NEGLIGIBLE -
NOTE(S):
2. ROUTE THROUGH EXISTING PULLBOXES AS INDICATED ON SHEET 53EP100S.
BLDG 52 - CONDUIT AND WIRE SCHEDULE - VA OK MUSKOGEE EHRM UPGRADES
CONDUIT
TAG
SERVICE
ROUTING CONDUIT CONDUCTORS
VOLTAGE
DROP
NOTES
1. ROUTE THROUGH ADDED PULLBOXES AS INDICATED ON SHEET 53EP100S.
Location: BLDG 52, RM 201B Volts: 120/208 Wye A.I.C Rating: 42k
Supply From: 52-XFMR-TRA Phases: 3 Bus Rating: 400A
Mounting: Surface Wires 4 Main Circuit Breaker: 225A / 3P / LSI
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 30 A 3 3333 720 1 20 A 2
3 "" "" 3333 275 1 20 A 4
5 "" "" 3333 1409 2 25 A 6
7 60 A 3 0 1409 "" "" 8
9 "" "" 0 1409 2 25 A 10
11 "" "" 0 1409 "" "" 12
13 30 A 3 3333 1409 2 25 A 14
15 "" "" 3333 1409 "" "" 16
17 "" "" 3333 500 1 20 A 18
19 60 A 3 5000 0 1 20 A 20
21 "" "" 5000 1409 2 25 A 22
23 "" "" 5000 1409 "" "" 24
25 20 A 3 1667 500 1 20 A 26
27 "" "" 1667 0 1 20 A 28
29 "" "" 1667 0 1 20 A 30
31 20 A 3 1667 100 3 20 A 32
33 "" "" 1667 100 "" "" 34
35 "" "" 1667 100 "" "" 36
37 20 A 1 500 100 3 30 A 38
39 20 A 1 0 100 "" "" 40
41 20 A 1 0 100 "" "" 42
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 2818 125.00% 59369 VA
Other 1600 100.00% 60142 VA
Receptacle 720 100.00% 165 A
Lighting 275 125.00% 167 A
All other Motor 8955 100.00%
45000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Telecom Rack 45000
1600 Total Est. Power Demand:
720 Total Conn. Amperage:
344 Total Est. Amperage Demand:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
3523 Total Conn. Power Load:
19738 19703 19928
164 164 166
ACCESS CONTROL "52-ACP-201B" / DOOR POWER SPD
SPARE ""
SPARE ""
SERVER RACK RECEPTACLE FOR EXISTING CORE SW DIGITAL POWER METER
MDA SERVER RACK RECEPTACLE VAV / TERMINAL UNIT "TU-201B-52"
"" SPARE
"" SPARE
MDA SERVER RACK RECEPTACLE SPARE
"" SPLIT DUCTLESS COOLING UNIT "CU-201B-52-4"
HORIZONTAL CABLING SERVER RACK RECEPTACLE SPLIT DUCTLESS COOLING UNIT "CU-201B-52-3"
"" DDC CONTROLLER
CIRCUIT DESCRIPTION
ENTRANCE RACKS RECEPTACLE RECEPTACLES - TR ROOM
"" LIGHTING - TR ROOM
"" SPLIT DUCTLESS COOLING UNIT "CU-201B-52-1"
Branch Panel: 52-201B-52A
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPARE ""
"" SPLIT DUCTLESS COOLING UNIT "CU-201B-52-2"
Location: BLDG 52, RM 201B Volts: 120/208 Wye A.I.C Rating: 42k
Supply From: 52-XFMR-TRB Phases: 3 Bus Rating: 400A
Mounting: Surface Wires 4 Main Circuit Breaker: 225A / 3P / LSI
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 30 A 3 3333 720 1 20 A 2
3 "" "" 3333 275 1 20 A 4
5 "" "" 3333 0 1 20 A 6
7 60 A 3 0 0 1 20 A 8
9 "" "" 0 0 1 20 A 10
11 "" "" 0 0 1 20 A 12
13 30 A 3 3333 0 1 20 A 14
15 "" "" 3333 0 1 20 A 16
17 "" "" 3333 0 1 20 A 18
19 60 A 3 5000 0 1 20 A 20
21 "" "" 5000 0 1 20 A 22
23 "" "" 5000 0 1 20 A 24
25 20 A 3 1667 0 1 20 A 26
27 "" "" 1667 0 1 20 A 28
29 "" "" 1667 0 1 20 A 30
31 20 A 3 1667 100 3 20 A 32
33 "" "" 1667 100 "" "" 34
35 "" "" 1667 100 "" "" 36
37 20 A 1 0 100 3 30 A 38
39 20 A 1 0 100 "" "" 40
41 20 A 1 0 100 "" "" 42
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 46595 VA
Other 600 100.00% 46664 VA
Receptacle 720 100.00% 129 A
Lighting 275 125.00% 130 A
All other Motor 0 100.00%
45000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Telecom Rack 45000
600 Total Est. Power Demand:
720 Total Conn. Amperage:
344 Total Est. Amperage Demand:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
15920 15475 15200
133 129 127
SPARE SPD
SPARE ""
SPARE ""
SERVER RACK RECEPTACLE FOR EXISTING CORE SW DIGITAL POWER METER
MDA SERVER RACK RECEPTACLE SPARE
"" SPARE
"" SPARE
MDA SERVER RACK RECEPTACLE SPARE
"" SPARE
"" SPARE
HORIZONTAL CABLING SERVER RACK RECEPTACLE SPARE
"" SPARE
"" SPARE
"" SPARE
CIRCUIT DESCRIPTION
ENTRANCE RACKS RECEPTACLE RECEPTACLES - TR ROOM
"" LIGHTING - TR ROOM
"" SPARE
Branch Panel: 52-201B-52B
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPARE SPARE
"" SPARE
Location: BLDG 52, RM 101F-52 Volts: 480V A.I.C Rating: -
Supply From: ATS-ECB Phases: 3 Bus Rating: 600A
Mounting: Surface Wires 4 Main Circuit Breaker: 600A / 3P / LSI
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 60 A 3 0 15920 3 125 A 2
3 "" "" 0 15475 "" "" 4
5 "" "" 0 15200 "" "" 6
7 20 A 3 0 0 1 20 A 8
9 "" "" 0 0 1 20 A 10
11 "" "" 0 0 1 20 A 12
13 -- -- 0 0 3 100 A 14
15 -- -- 0 0 "" "" 16
17 -- -- 0 0 "" "" 18
19 -- -- 0 0 3 70 A 20
21 -- -- 0 0 "" "" 22
23 -- -- 0 0 "" "" 24
25 20 A 1 0 0 "" "" 26
27 20 A 1 0 0 1 20 A 28
29 20 A 1 0 0 1 20 A 30
31 20 A 1 0 100 3 20 A 32
33 20 A 1 0 100 "" "" 34
35 20 A 1 0 100 "" "" 36
37 125 A 3 0 100 3 30 A 38
39 "" "" 0 100 "" "" 40
41 "" "" 0 100 "" "" 42
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 46595 VA
Other 600 100.00% 33164 VA
Receptacle 720 100.00% 129 A
Lighting 275 125.00% 92 A
All other Motor 0 100.00%
45000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Total Conn. Amperage:
344 Total Est. Amperage Demand:
Panel Totals
0 Total Conn. Power Load:
Telecom Rack 31500
600 Total Est. Power Demand:
134 131 128
Connected Load (VA) Demand Factor Estimated Demand (VA)
16120 15675 15400
SPARE ""
SPARE ""
BOLT ON SUB-FED PANEL "TELCP" SPD
SPARE SPARE
SPARE SPARE
SPARE DIGITAL POWER METER
NOT USABLE ""
NOT USABLE ""
SPARE ""
NOT USABLE ""
NOT USABLE ""
NOT USABLE SPARE
"" SPARE
"" SPARE
NOT USABLE PANEL EWH24 (WAREHOUSE)
PANEL "52-201B-52B" VIA "52-XFMR-TRB"
DOLPHIN-1 SPARE
2. TELECOM RACKS DE-RATED FROM 5000VA TO 3500VA PER VA WHITE PAPER "POWER CAPACITY PLANNING FOR TRS" (JULY 2021).
3. FOR EXISTING LOADING INFORMATION REFERENCE "METERING AND LOAD INFORMATION SCHEDULE" ON SHEET EP702.
Branch Panel: ECHCP (REVISED)
VA PER PHASE
CIRCUIT DESCRIPTION A B C CIRCUIT DESCRIPTION
SEWAGE SUMP PUMP
(REPLACEMENT)
(NOTE 4)
4. EXISTING LOAD TO BE RECIRCUITED TO REPLACEMENT PANEL, TYP.
42k42
42k
File details come from the government source that posted it. Updated .