Attachment 04 Drawings 3 of 13 Muskogee 623-21-700.pdf

PDF 19 MB Posted

Attached to
Y1DA--623-21-700 | Construct EHRM Infrastructure Upgrades | Jack C. Montgomery VAMC - Muskogee, OK | Samantha/Leslie
Solicitation number
36C77624R0046
Issued by

About this file

This document is a set of electrical plan drawings for infrastructure upgrades at the Jack C. Montgomery VA Medical Center in Muskogee, Oklahoma. The comprehensive drawing set includes electrical plans for multiple buildings (Buildings 1, 18, 22, 24, 52, and 53) across various levels, including basement, first floor, second floor, third floor, mezzanine, and roof levels.

The drawings detail electrical infrastructure modifications, including new heat pump installations, condensing units, telecommunications bonding, power distribution equipment replacement, and electrical circuit routing. Key components include transformer locations, panelboard placements, telecommunications rooms, and electrical equipment upgrades across different building zones. The drawings are part of the EHRM (Enterprise Healthcare Resource Management) Infrastructure Upgrades project, with detailed technical specifications for electrical system modifications, conduit routing, and equipment positioning. The drawings are dated 05/24/2024 and prepared by DAV Energy Solutions for the Department of Veterans Affairs.

View the file

Other files

File Type Posted
36C77625R0046 0009.pdf PDF
Attachment 21 - Tech Questions Tracker - FINAL07162025.pdf PDF
Attachment 21 - Tech Questions Tracker - FINAL_07142025.pdf PDF
36C77625R0046 0008.pdf PDF
Attachment to Tech Questions- ASI-001 Mechanical Ductwork Drawings- 20250714.pdf PDF
36C77625R0046 0007.pdf PDF
Attachment 21 - Tech Questions Tracker - 07082025.pdf PDF
Attachment 21 - Tech Questions Tracker - 07022025.pdf PDF
36C77625R0046 0006.pdf PDF
36C77625R0046 0005.pdf PDF
Attachment 16 Muskogee County Wage Rates_06272025.pdf PDF
Attachment 20 - Spec 01 31 00.01 Project Management and Coordination.pdf PDF
36C77625R0046 0004.pdf PDF
Attachment 21 - Tech Questions Tracker - 20250623 Partial.pdf PDF
36C77625R0046 0003.pdf PDF
Attachment 19 Site Visit Sign In Sheet 62323700.pdf PDF
36C77625R0046 0002.pdf PDF
36C77625R0046 0001.pdf PDF
Attachment 05 Drawings 4 of 13 Muskogee 623-21-700.pdf PDF
Attachment 17- Limitations on Subcontracting - Muskogee EHRM.pdf PDF
Attachment 08 Drawings 7 of 13 Muskogee 623-21-700.pdf PDF
Attachment 01 - 623-21-700 - Muskogee - Updated Combined Specifications-20250501.pdf PDF
Attachment 03 Drawings 2 of 13 Muskogee 623-21-700.pdf PDF
36C77625R0046_1.pdf PDF
Attachment 18 Site Map.pdf PDF
Attachment 02 Drawings 1 of 13 Muskogee 623-21-700.pdf PDF
Attachment 16 Muskogee County Wage Rates.pdf PDF
Attachment 07 Drawings 6 of 13 Muskogee 623-21-700.pdf PDF
Attachment 06 Drawings 5 of 13 Muskogee 623-21-700.pdf PDF
Attachment 12 Drawings 11 of 13 Muskogee 623-21-700.pdf PDF
Attachment 14 Drawings 13 of 13 Muskogee 623-21-700.pdf PDF
Attachment 10 Drawings 9 of 13 Muskogee 623-21-700.pdf PDF
Attachment 13 Drawings 12 of 13 Muskogee 623-21-700.pdf PDF
Attachment 11 Drawings 10 of 13 Muskogee 623-21-700.pdf PDF
Attachment 09 Drawings 8 of 13 Muskogee 623-21-700.pdf PDF
Attachment 15- PCRA for EHRM 623-700.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Department of Veteran Affairs

N

M-107A

BUILDING 1 ROOF PLAN

SCALE: 1/8" = 1'-0"

KEY NOTES

SHEET NOTES

NEW HEAT PUMP DAIKIN RK24BXVJU SIZED FOR 2.0

TONS.

HEAT PUMP IS ROUTED TO THE FIFTH FLOOR TO

SERVICE MINI SPLIT IN ROOM 5A04-1.

2 HEAT PUMP IS ROUTED TO THE FOURTH FLOOR TO

SERVICE MINI SPLIT IN ROOM 403-1.

1.A 1.B 1.C 1.D 1.E 1.F 1.G 1.H 1.I 1.J 1.K 1.L 1.M

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.1a

150 SF

STAIRWELL

601C-1

11708 SF

BUILDING 1 ROOF

601-1

121 SF

ELEV LOBBY

600-1

142 SF

STAIRWELL

601B-1

63 SF

P1

52 SF

P2

3'-4"

1 21 3 1 3 1 2

CU-403-1-2

CU-403-1-1

CU-5A04-1-1

CU-5A04-1-2

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building No.

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

STAMP:

AutoCAD SHX Text

EHRM INFRASTRUCTURE UPGRADES - JACK C. MONTGOMERY VA MEDICAL CENTER

AutoCAD SHX Text 623-21-700

AutoCAD SHX Text

AD

AutoCAD SHX Text

AB

AutoCAD SHX Text 05/24/2024

AutoCAD SHX Text Floor No.

AutoCAD SHX Text Dwg. of 24

AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

AutoCAD SHX Text

JACK C MONTGOMERY VAMC 1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

100% ISSUED FOR BID

AutoCAD SHX Text 05/24/2024

AutoCAD SHX Text M-107A

AutoCAD SHX Text

AutoCAD SHX Text

ROOF

AutoCAD SHX Text

BUILDING 1 ROOF PLAN

AutoCAD SHX Text

M-107B

BUILDING 53 ROOF PLAN

SCALE: 1/8" = 1'-0"

N

KEY NOTES

SHEET NOTES

NEW HEAT PUMP DAIKIN RKS30LVJU SIZED FOR 2.5

TONS.

HEAT PUMP IS ROUTED TO THE FIFTH FLOOR TO

SERVICE MINI SPLIT IN ROOM 5A-109.

2 HEAT PUMP IS ROUTED TO THE FOURTH FLOOR TO

SERVICE MINI SPLIT IN ROOM 4A-109.

53.A 53.B 53.C 53.D 53.E 53.F 53.G 53.H 53.I 53.J 53.K 53.L

203 SF

MECH

6A-101

136 SF

STAIR

6A-ST1

2136 SF

MACHINE

PENTHOUSE

6A100-53

CU-4A109-1

CU-4A109-2

CU-5A109-1

CU-5A109-2

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building No.

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

STAMP:

AutoCAD SHX Text

EHRM INFRASTRUCTURE UPGRADES - JACK C. MONTGOMERY VA MEDICAL CENTER

AutoCAD SHX Text 623-21-700

AutoCAD SHX Text

AD

AutoCAD SHX Text

AB

AutoCAD SHX Text 05/24/2024

AutoCAD SHX Text Floor No.

AutoCAD SHX Text Dwg. of 24

AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

AutoCAD SHX Text

JACK C MONTGOMERY VAMC 1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

100% ISSUED FOR BID

AutoCAD SHX Text 05/24/2024

AutoCAD SHX Text M-107B

AutoCAD SHX Text

AutoCAD SHX Text

ROOF

AutoCAD SHX Text

BUILDING 53 ROOF PLAN

Scale: NTS

Veteran Affairs

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text M-401

AutoCAD SHX Text

MECHANICAL SCHEDULES

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building No.

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

STAMP:

AutoCAD SHX Text Floor No.

AutoCAD SHX Text Dwg. of 24

AutoCAD SHX Text

100% ISSUED FOR BID

AutoCAD SHX Text 05/24/2024

AutoCAD SHX Text

EHRM INFRASTRUCTURE UPGRADES - JACK C. MONTGOMERY VA MEDICAL CENTER

AutoCAD SHX Text 623-21-700

AutoCAD SHX Text

AD

AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

JACK C MONTGOMERY VAMC 1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

AutoCAD SHX Text

AB

AutoCAD SHX Text 05/24/2024

AutoCAD SHX Text

DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

Scale: NTS

AC

COND. DRAIN LINE.

SEE PLANS FOR

TERMINATION

SUPPORT ON WALL

RS AND RL

CONTINUATION TO CU

R S

R L

EXIST MASONRY

WALL

CAULK (TYP)

CAULK (TYP)

PIPE SLEEVE

PIPE

INSULATION

PIPE

FIRE RATED CAULKING

FIRE RATED CAULKING

PIPE

INSULATION

PIPE

STAINLESS STEEL BOLTS,

NUTS & WASHERS CONTRACTOR CORE

DRILLED HOLE

EXIST MASONRY

WALL

PIPE SLEEVE

EXTERIOR SIDE OF

CONCRETE WALL

INTERIOR SIDE OF WALL

PIPE CENTERED IN

SLEEVE

PIPE

INSULATION

WITH JACKET

MINERAL WOOL

PIPE

INSULATION

WITH JACKET

OUTSIDE INSIDE

MINERAL WOOL RESILIENT WATERPROOF

CAULKING

MODULAR TYPE WALL

PENETRATION SEAL

LS MODEL (C, L, S-316, O,

OS-316, T)

OUTSIDE INSIDE

CAULK (TYP)

NO SCALE: NO SCALE: NO SCALE: NO SCALE:

FIRE RESISTANT

SEALANT

PIPE RISER

PIPE SLEEVE

1/2"

1/2"

FLOOR OPENING

NO SCALE:

NOTES:

120V TO 24V AREA Tx

TRANSFORMER(S) BY DIV. 15,

EMS CONTRACTOR.

NORMAL MODE CONTROL

ROOM TEMPERATURE SENSOR SHALL MODULATE CAV BOX-REHEAT COIL CONTROL

VALVE TO MAINTAIN THE REQUIRED TEMPERATURE SETPOINT. EMCS SHALL

MONITOR AIRFLOW CFM, VALVE COMMAND POSITION, DISCHARGE AIR

TEMPERATURE, AND ROOM TEMPERATURE.

SEE ELECTRICAL DRAWINGS FOR

120-VOLT CIRCUTS INTENDED TO

SERVE MULTIPLE CAV BOXES. PROVIDE

120V/24V CONTROL TRANSFORMER

DOWNSTREAM OF J-BOX, TYP.

1. DIV. 26 TO MOUNT 120 VOLT J-BOX IN AREA ADJACENT TO BOXES BEING SERVED.

2. REFER TO THE MECHANICAL DRAWINGS FOR EXACT LOCATIONS OF ROOM

TEMPERATURE SENSORS.

3. ROOM SENSOR TO PROVIDE SETPOINT ADJUSTMENT. ROOM TEMPERATURE

SENSOR SHALL BE ABLE TO MAINTAIN SPACE. REFER TO ROOM AIR SCHEDULE

FOR TEMPERATURE SET POINTS.

HOT WATER REQUIREMENTS

FOR HOT WATER HEATING

COIL LISTED ON ATU

SCHEDULE ON DRAWING M-401

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building No.

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

STAMP:

AutoCAD SHX Text

EHRM INFRASTRUCTURE UPGRADES - JACK C. MONTGOMERY VA MEDICAL CENTER

AutoCAD SHX Text 623-21-700

AutoCAD SHX Text

AD

AutoCAD SHX Text

AB

AutoCAD SHX Text 05/24/2024

AutoCAD SHX Text Floor No.

AutoCAD SHX Text Dwg. of 24

AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

AutoCAD SHX Text

JACK C MONTGOMERY VAMC 1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

100% ISSUED FOR BID

AutoCAD SHX Text 05/24/2024

AutoCAD SHX Text M-501

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

MECHANICAL DETAILS

AutoCAD SHX Text

AutoCAD SHX Text

DUCTLESS SPLIT SYSTEM DETAIL

AutoCAD SHX Text

AutoCAD SHX Text

PIPE THROUGH WALL DETAIL

AutoCAD SHX Text

AutoCAD SHX Text

PIPE THROUGH FIRE RATED WALL DETAIL

AutoCAD SHX Text

AutoCAD SHX Text

PIPE PENETRATION THROUGH WALLS BELOW GRADE

AutoCAD SHX Text

AutoCAD SHX Text

PIPE THROUGH FLOOR DETAIL

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

DUCTWORK RADIUS ELBOWS

AutoCAD SHX Text

VANE

AutoCAD SHX Text

VANE

AutoCAD SHX Text

R SHALL EQUAL OR BE GREATER THAN W.

AutoCAD SHX Text

R SHALL EQUAL OR BE GREATER THAN 1/3W.

AutoCAD SHX Text R

AutoCAD SHX Text

R SHALL EQUAL OR BE GREATER THAN 1/6W.

AutoCAD SHX Text

STANDARD RADIUS OR LONG RADIUS ELBOW

AutoCAD SHX Text

SHORT RADIUS ELBOW WITH ONE VANE

AutoCAD SHX Text

SHORT RADIUS ELBOW WITH TWO VANES

AutoCAD SHX Text R

AutoCAD SHX Text NOTE: 1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND. 2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL SHORT ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

DUCTWORK SQUARE VANE ELBOWS

AutoCAD SHX Text NOTE: 1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA. WHEN ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE REGARDLESS OF W 2. DIMENSION. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1 1/2" MAXIMUM DIMENSION. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1 1/2" MAXIMUM SPACE 3. BETWEEN VANES AND A 3/4" TRAILING EDGE. WHEN W EQUALS W2 AND W1 IS GREATER BETWEEN VANES AND A 3/4" TRAILING EDGE. WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" VANES SHALL BE DOUBLE VANE TYPE.

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

EXHAUST OR RETURN BRANCH DUCTWORK

AutoCAD SHX Text

MAIN EXHAUST OR RETURN

AutoCAD SHX Text

%%UPLAN VIEW

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text

PROVIDE VOLUME DAMPER AT EACH BRANCH DUCT

AutoCAD SHX Text 1/4W OR 4" [100mm] MIN.

AutoCAD SHX Text

BRANCH DUCT

AutoCAD SHX Text

VD

AutoCAD SHX Text

NTS

AutoCAD SHX Text

SUPPLY BRANCH DUCTWORK

AutoCAD SHX Text

AutoCAD SHX Text

MAIN SUPPLY

AutoCAD SHX Text

%%UPLAN VIEW

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text

PROVIDE VOLUME DAMPER AT EACH BRANCH DUCT

AutoCAD SHX Text

1/4W OR 4" MIN.

AutoCAD SHX Text

BRANCH DUCT

AutoCAD SHX Text

VD

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

VOLUME DAMPER DETAIL

AutoCAD SHX Text

NOTE: 1. 2.

AutoCAD SHX Text DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.

AutoCAD SHX Text

INSULATION SEE SPECIFICATION

AutoCAD SHX Text

DAMPER BLADE

AutoCAD SHX Text 1/8" [6mm] CLEARANCE ALL AROUND

AutoCAD SHX Text

OUTSIDE END BEARING

AutoCAD SHX Text

INSIDE END BEARING

AutoCAD SHX Text

HANDLE WITH LOCKING QUADRANT

AutoCAD SHX Text

INSULATION STAND-OFF

AutoCAD SHX Text 1/2" [15mm] ROUND ROD PIN

AutoCAD SHX Text

DUCT

AutoCAD SHX Text

STIFFEN BLADE AS REQUIRED

AutoCAD SHX Text

SIDE ELEVATION

AutoCAD SHX Text

SECTION

AutoCAD SHX Text

NTS

AutoCAD SHX Text

DUCT CONNECTIONS - AIR TERMINAL UNITS

AutoCAD SHX Text

AIR TERMINAL UNIT (CV OR VAV)

AutoCAD SHX Text

REHEAT COIL

AutoCAD SHX Text

SOUND ATTENUATOR SEE EQUIPMENT SCHEDULE

AutoCAD SHX Text

HARD AIR DUCT CONNECTOR. SEE DETAIL

AutoCAD SHX Text

DIFFUSER (TYP.)

AutoCAD SHX Text

AutoCAD SHX Text NOTE: 1. RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF INLET RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF INLET 2. PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET. FOR LONGER PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET. FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT OR BELOW 0.2"/100'.

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

ROUND DUCT HANGERS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text ONE 1 x 18 GA STRAP

AutoCAD SHX Text

AutoCAD SHX Text

TWO 1/2%%C RODS

AutoCAD SHX Text

TWO 3/8%%C. RODS

AutoCAD SHX Text ONE 1 x 16 GA STRAP

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text ONE 1 x 22 GA STRAP

AutoCAD SHX Text

QUANTITY/SIZE

AutoCAD SHX Text

MAX. DUCT %%C

AutoCAD SHX Text

AutoCAD SHX Text

HANGER STRAPS OR RODS

AutoCAD SHX Text

MAX. LOAD

AutoCAD SHX Text

LBS.

AutoCAD SHX Text

AutoCAD SHX Text

MAX.

AutoCAD SHX Text

AutoCAD SHX Text

IN.

AutoCAD SHX Text

SPACING

AutoCAD SHX Text

IN.

AutoCAD SHX Text

IN.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text NOTE: TABULATED DATA FROM SMACNA ALLOWS FOR DUCT REINFORCING AND INSULATION, BUT NO EXTERNAL LOAD.

AutoCAD SHX Text

BAND

AutoCAD SHX Text

OVER 50"

AutoCAD SHX Text

HANGER RODS

AutoCAD SHX Text

BAND OF SAME SIZE AS HANGER STRAP

AutoCAD SHX Text

LOAD RATED FASTENERS

AutoCAD SHX Text

50" & UNDER

AutoCAD SHX Text

NTS

AutoCAD SHX Text

TYPICAL CAV BOX CONTROL DIAGRAM

AutoCAD SHX Text

AutoCAD SHX Text

CAV BOX WITH ENCLOSURE

AutoCAD SHX Text 120V

AutoCAD SHX Text

TX

AutoCAD SHX Text

DTS

AutoCAD SHX Text

SA

AutoCAD SHX Text

RTS

AutoCAD SHX Text

DATA BUS

AutoCAD SHX Text

FROM AC UNIT

AutoCAD SHX Text

CF

AutoCAD SHX Text

AI

AutoCAD SHX Text

AI

AutoCAD SHX Text

DI

AutoCAD SHX Text

PWR BY DIV. 26

AutoCAD SHX Text

HW

Scale: NTS

NEW

DUCTLESS SPLIT

MOUNTED HIGH

ON WALL

(COORDINATE MOUNTING

HEIGHT WITH CONDITIONS

OF THE SPACE)

M FLOOR

T1 H T1

RACK PDU'S - SEE PLANS FOR

NUMBER OF RACKS PER TR.

DDC

CONTROLLER

M

H

FLOOR MOISTURE

SPACE HUMIDITY

SPACE TEMP

TIE INTO EXISTING BMS

A.I.

A.I.

A.I.

D.O.

A.I.

A.I.

RACK 1 TEMP/HUM

RACK 1 TEMP/HUM

PDU-1 PDU-2

SEQUENCE OF OPERATION

THE DUCTLESS SPLIT SHALL OPERATE CONTINUOUSLY TO

MAINTAIN A SPACE TEMPERATURE OF 75°(ADJ).

SHOW TEMPERATURE AND HUMIDITY AT THE GRAPHIC

DISPLAY. PROVIDE TEMPERATURE TRENDS.

PROVIDE ALARM FOR TEMPERATURE ABOVE 80F.

PROVIDE ALARM FOR MOISTURE SENSED ON FLOOR.

SHOW RACK TEMPERATURE AND HUMIDITY (SEE PLANS

FOR NUMBER OF RACKS PER TR)

W

AL

L

INSTALL LINE SET PER

MANUFACTURE

RECOMMENDATIONS.

RS AND RL LINES TO

DUCTLESS SPLIT

TOP OF ROOF

FINISH

ROOFER WILL SEAL

AROUND LEGS FOR

COMPLETE WATER

PROOF (TYP)

3/8"Ø GRADE S SCREWS OR THRUBOLT

WITH 1"Ø WASHER TO STRUCTURAL

A36 STEEL MEMBERS (3/16" MIN HOST)

4 ANCHORS PER PLATE .

CONDENSING UNIT

WALL

MINIMUM 12"

BRAIDED

FLEXIBLE

REFRIGERANT

LINE

SUPPORT ON WALL WITH 3/8" Ø POWERS CARBON

STEEL WEDGE BOLT CONCRETE ANCHOR WITH 1" Ø

MIN WASHER, 1-1/2" EMBEDMENT AND 6" MIN EDGE

DISTANCE. SUPPORT PIPING EVERY 6' MINIMUM.

20 GAGE SHEET METAL PAN AROUND

REFRIGERANT LINES FROM BOTTOM

WALL ANCHOR TO EAVE. PAINT PAN

TO MATCH BUILDING COLOR OF OIL

BASE PAINT . FASTEN SECURELY TO

WALL.

4" DIA. HOLE THRU WALL OR SOFFIT

SEAL WEATHER TIGHT

CROSS MEMBER

S L

PROVIDE ISOLATION

VALVES ON EACH SIDE

OF BRAIDED FLEXIBLE

REFRIGERANT LINE

ROOF HOST

STRUCTURE

18"

SECURELY ATTACH CONDENSING

UNIT TO CROSS MEMBER . (4 BOLTS

TOTAL). TWO 1/4"Ø S.S. THRUBOLTS

WITH 5/8" WASHERS AND NUTS

(1) 5/16-18

THRUBOLT TO

INTERLOCK

SQUARE TUBING

USE MIAMI TECH (MTI)

AS14S OR VA APPROVED

SUBSTITUTE.

ROOFING

20 GAGE SHEET METAL PAN AROUND

REFRIGERANT LINES FROM BOTTOM

WALL ANCHOR TO EAVE. PAINT PAN

TO MATCH BUILDING COLOR OF OIL

BASE PAINT . FASTEN SECURELY TO

WALL.

SUPPORT ON WALL WITH 3/8" Ø POWERS CARBON

STEEL WEDGE BOLT CONCRETE ANCHOR WITH 1" Ø

MIN WASHER, 1-1/2" EMBEDMENT AND 6" MIN EDGE

DISTANCE. SUPPORT PIPING EVERY 6' MINIMUM.

4" DIA. HOLE THRU WALL OR SOFFIT

SEAL WEATHER TIGHT

D L S

INSTALL LINE SET PER

MANUFACTURE

RECOMMENDATIONS.

RS AND RL LINES TO

DUCTLESS SPLIT

90° SWEEP

WALL

1" COND. DRAIN LINE.

TERMINATE 4" ABOVE

GRADE.

PROVIDE ISOLATION

VALVES ON EACH SIDE

OF BRAIDED FLEXIBLE

REFRIGERANT LINE

MIN 4" TALL LIFTERS

PREFABRICATED LIGHTWEIGHT

EQUIPMENT PAD

3/8" Ø POWERS CARBON STEEL

WEDGE BOLT CONCRETE

ANCHOR WITH 1" Ø MIN

WASHER, 2-1/2" EMBEDMENT

AND 6" MIN EDGE DISTANCE

ROUND TUBING

MINIMUM 12"

BRAIDED

FLEXIBLE

REFRIGERANT

LINE

CONDENSING UNIT (CU)

NO SCALE:

NO SCALE:

"UNISTRUT" P2000

SERIES PIPE CLAMP

(TYP)

REFRIGERANT PIPING

SEE PLANS

3/8" BOLT (TYP. 4 EACH POST)

"UNISTRUT" P1000

CHANNEL. LENGTH AS

REQUIRED HIGH DESITY/HIGH

IMPACT

POLYPROPYLENE

BASE (TYP)

CONCRETE PAD

INSULATION

ROOF

ROOF DECK

1/4" STEEL PLATE

NO SCALE:

NO SCALE:

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building No.

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

STAMP:

AutoCAD SHX Text

EHRM INFRASTRUCTURE UPGRADES - JACK C. MONTGOMERY VA MEDICAL CENTER

AutoCAD SHX Text 623-21-700

AutoCAD SHX Text

AD

AutoCAD SHX Text

AB

AutoCAD SHX Text 05/24/2024

AutoCAD SHX Text Floor No.

AutoCAD SHX Text Dwg. of 24

AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

AutoCAD SHX Text

JACK C MONTGOMERY VAMC 1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

100% ISSUED FOR BID

AutoCAD SHX Text 05/24/2024

AutoCAD SHX Text M-502

AutoCAD SHX Text

MECHANICAL DETAILS

AutoCAD SHX Text

AutoCAD SHX Text

TELECOMMUNICATION ROOM CONTROL DIAGRAM

AutoCAD SHX Text

AutoCAD SHX Text

CONDENSING UNIT ROOF MOUNT SUPPORT DETAIL

AutoCAD SHX Text

AutoCAD SHX Text

CONDENSING UNIT GROUND MOUNT SUPPORT DETAIL

AutoCAD SHX Text

AutoCAD SHX Text

PIPE ROOF MOUNTING DETAIL

AutoCAD SHX Text

AutoCAD SHX Text

SUPPORT BRACKET DIMENSION

18" 0.25"

1.63"

4" MINIMUM CLEARANCE

FROM WALL

0.81"

CONDENSING UNIT (CU)

WEIGHT: 133 Lbs

WALL

OUTDOOR UNIT SUPPORT

P2233A - 18" BRACKET (SLOT DOWN)(1-5/8" SERIES)

(BRAND: UNISTRUT)

ISOMETRIC VIEW TOP VIEW

4" MINIMUM CLEARANCE

FROM WALL CONDENSING UNIT (CU)

WEIGHT: 133 Lbs

CONDENSING UNIT (CU)

(E)8" CMU

P1000HS - HG"

WALL

OUTDOOR UNIT SUPPORT

P2233A - 18" BRACKET (SLOW DOWN)(1-5/8" SERIES)

(BRAND: UNISTRUT) 18"

GROUTED CELL: 1/2" DIAMETER SIMPSON

WEDGE-ALL STAINLESS STEEL. EMBED 3 1/2"

UNGROUTED CELL: 3/8" DIAMETER STAINLESS

STEEL SIMPSON TITEN HD. EMBED 2 1/2"

16" OUTDOOR UNIT SUPPORT

P2233A (HG) - 18" BRACKET (SLOT DOWN)(1-5/8" SERIES)

(BRAND: UNISTRUT)

FRONT VIEW SIDE VIEW

5.

4'

NO SCALE:

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building No.

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text

STAMP:

AutoCAD SHX Text

EHRM INFRASTRUCTURE UPGRADES - JACK C. MONTGOMERY VA MEDICAL CENTER

AutoCAD SHX Text 623-21-700

AutoCAD SHX Text

AD

AutoCAD SHX Text

AB

AutoCAD SHX Text 05/24/2024

AutoCAD SHX Text Floor No.

AutoCAD SHX Text Dwg. of 24

AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

AutoCAD SHX Text

JACK C MONTGOMERY VAMC 1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM

AutoCAD SHX Text

100% ISSUED FOR BID

AutoCAD SHX Text 05/24/2024

AutoCAD SHX Text M-503

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

MECHANICAL DETAILS

AutoCAD SHX Text

AutoCAD SHX Text

CONDENSING UNIT WALL MOUNT SUPPORT DETAIL

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:

05/24/2024100% ISSUED FOR BID

A/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

Department of Veteran Affairs

EPG001

ABBREVIATIONS, GENERAL NOTES, AND

SHEET INDEX

JACK C MONTGOMERY VAMC

05/24/2024 WNM/SJM RTS/BCL

EHRM INFRASTRUCTURE UPGRADES -

JACK C. MONTGOMERY VA MEDICAL

CENTER

623-21-700

1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

Dwg. 1 of 77

S H E E T I N D E XG E N E R A L N O T E SA B B R E V I A T I O N S

1PH SINGLE-PHASE

1P SINGLE POLE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE-PHASE

4/C FOUR-CONDUCTOR

4W FOUR-WIRE

A/C AIR CONDITIONING UNIT

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR AVAILABLE

FAULT CURRENT

AFCI ARC-FAULT CURRENT INTERRUPTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BAT BATTERY

BD BOARD

BFF BELOW FINISH FLOOR

BLDG BUILDING

BRKR BREAKER

BYP BY PASS

C CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

CD CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/

OWNER INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

C/B CIRCUIT BREAKER

CL CONNECTOR LIGHTING

CLF CURRENT LIMITING FUSE

CLG CEILING

CO CONDUIT ONLY

COAX COAX CABLE

COMM COMMUNICATION

COMPT COMPARTMENT

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CUR CURRENT

DB DECIBEL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DDC DIRECT DIGITAL CONTROLS

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DP DISTRIBUTION PANEL

DMR SW DIMMER SWITCH

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EL ELEVATION OR EXISTING TO BE RELOCATED

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMER/EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

EN EXISTING IN NEW LOCATION

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

EPRF EXPLOSION PROOF

ER EXISTING TO REMAIN

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST(E) EXISTING

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCIO FURNISHED BY CONTRACTOR,

INSTALLED BY OWNER

FOIC FURNISHED BY OWNER,

INSTALLED BY CONTRACTOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLUOR FLUORESCENT

FP FIRE PROTECTION

FT FEET OR FOOT

FU SW FUSED SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G ELECTRICAL GROUND

GEN GENERATOR

GFCI GROUND FAULT

CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTION

GND GROUND

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

IG ISOLATED GROUND

IESNA ILLUMINATION ENGINEERING

SOCIETY OF NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT AMPERE

KVAH KILOVOLT AMPERE PER HOUR

KVAR KILOVOLT AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

KWHM KILOWATT HOUR METER

LCP LIGHTING CONTROL PANEL

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MS MOTOR STARTER

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

NA NOT APPLICABLE

NAC NOTIFICATION APPLIANCE CABINET

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NEUT, N NEUTRAL

NFC NOT FOR CONSTRUCTION

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OL OVERLOAD

OS OCCUPANCY SENSOR

P POLE

PB PULL BOX

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PIV POST INDICATOR VALVE

PF POWER FACTOR

PH PHASE

PNL PANEL

PS POWER SUPPLY

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

R EXISTING TO BE REMOVED

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

RM ROOM

RMC RIGID METAL CONDUIT

RMS ROOT MEAN SQUARE

REQD REQUIRED

SAC SMALL APPLIANCE CIRCUIT

SCC SHORT CIRCUIT CAPACITY

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SM SMART METER

SPD SURGE PROTECTIVE DEVICE

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD OR SB SWITCHBOARD

SWGR OR SG SWITCHGEAR

TEL TELEPHONE

TR TAMPER RESISTANT

TV TELEVISION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER

POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

W WATT/WEATHERPROOF

(WHILE IN USE)

WH WATER HEATER

WP/W WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

EPG001 - ABBREVIATIONS, GENERAL NOTES, AND SHEET INDEX

EPG002 - ELECTRICAL LEGENDS

01EP101 - BLDG 01 - LEVEL 01 - ELECTRICAL PLAN

18EP100B - BLDG 18 - LEVEL 00B - ELECTRICAL PLAN

18&11EP101 - BLDG 18&11 - LEVEL 01 - ELECTRICAL PLAN

22EP100S - BLDG 22 - LEVEL 00S - ELECTRICAL PLAN

22EP100B - BLDG 22 - LEVEL 00B - ELECTRICAL PLAN

22EP101 - BLDG 22 - LEVEL 01 - ELECTRICAL PLAN

24EP100B - BLDG 24 - LEVEL 00B - ELECTRICAL PLAN

24EP101 - BLDG 24 - LEVEL 01 - ELECTRICAL PLAN

52EP102 - BLDG 52 - MEZZANINE - ELECTRICAL PLAN

53EP100S - BLDG 53 - LEVEL 00S - ELECTRICAL PLAN

53EP100B - BLDG 53 - LEVEL 00B - ELECTRICAL PLAN

53EP101 - BLDG 53 - LEVEL 01 - ELECTRICAL PLAN

53EP102 - BLDG 53 - LEVEL 02 - ELECTRICAL PLAN

53EP103 - BLDG 53 - LEVEL 03 - ELECTRICAL PLAN

53EP104 - BLDG 53 - ROOF - ELECTRICAL PLAN

01EP401a - BLDG 01 - LEVEL 01 - ENLARGED ELECTRICAL PLANS 01EP401b - BLDG 01 - LEVEL 01 - ENLARGED ELECTRICAL PLANS 01EP402a - BLDG 01 - LEVEL 02 - ENLARGED ELECTRICAL PLANS 01EP402b - BLDG 01 - LEVEL 02 - ENLARGED ELECTRICAL PLANS

01EP403 - BLDG 01 - LEVEL 03 - ENLARGED ELECTRICAL PLANS

01EP404 - BLDG 01 - LEVEL 04 - ENLARGED ELECTRICAL PLANS

01EP405 - BLDG 01 - LEVEL 05 - ENLARGED ELECTRICAL PLANS

01EP406 - BLDG 01 - ROOF - ENLARGED ELECTRICAL PLAN

18&11EP401 - BLDG 18&11 - LEVEL 01 - ENLARGED ELECTRICAL PLANS

22EP400B - BLDG 22 - LEVEL 00B - ENLARGED ELECTRICAL PLANS

22EP401 - BLDG 22 - LEVEL 01 - ENLARGED ELECTRICAL PLANS

24EP400B - BLDG 24 - LEVEL 00B - ENLARGED ELECTRICAL PLANS

24EP401 - BLDG 24 - LEVEL 01 - ENLARGED ELECTRICAL PLANS

24EP402 - BLDG 24 - LEVEL 02 - ENLARGED ELECTRICAL PLANS

52EP402 - BLDG 52 - MEZZANINE - ENLARGED ELECTRICAL PLANS

53EP400B - BLDG 53 - LEVEL 00B - ENLARGED ELECTRICAL PLANS

53EP401 - BLDG 53 - LEVEL 01 - ENLARGED ELECTRICAL PLANS

53EP403 - BLDG 53 - LEVEL 03 - ENLARGED ELECTRICAL PLANS

53EP404 - BLDG 53 - LEVEL 04 - ENLARGED ELECTRICAL PLANS

53EP405 - BLDG 53 - LEVEL 05 - ENLARGED ELECTRICAL PLANS

EP501 - ELECTRICAL DETAILS

EP502 - ELECTRICAL DETAILS

EP503 - ELECTRICAL DETAILS

EP504 - ELECTRICAL DETAILS

EP505 - ELECTRICAL DETAILS

EP506 - ELECTRICAL DETAILS

EP507 - ELECTRICAL DETAILS

EG601 - TELECOMMUNICATIONS BONDING RISER DIAGRAM

01EP602 - BLDG 01 - PARTIAL ONE-LINE DIAGRAM - DEMOLITION

01EP611 - BLDG 01 - ONE-LINE DIAGRAM - PART 1 OF 4

01EP612 - BLDG 01 - ONE-LINE DIAGRAM - PART 2 OF 4

01EP613 - BLDG 01 - ONE-LINE DIAGRAM - PART 3 OF 4

01EP614 - BLDG 01 - ONE-LINE DIAGRAM - PART 4 OF 4

18&11EP611 - BLDG 18&11 - ONE-LINE DIAGRAM

22EP611 - BLDG 22 - ONE-LINE DIAGRAM

24EP601 - BLDG 24 - ONE-LINE DIAGRAM - DEMOLITION

24EP611 - BLDG 24 - ONE-LINE DIAGRAM

52EP602 - BLDG 52 - PARTIAL ONE-LINE DIAGRAM - DEMOLITION

52EP611 - BLDG 52 - ONE-LINE DIAGRAM - PART 1 OF 2

52EP612 - BLDG 52 - ONE-LINE DIAGRAM - PART 2 OF 2

53EP601 - BLDG 53 - PARTIAL ONE-LINE DIAGRAM - DEMOLITION

53EP602 - BLDG 53 - PARTIAL ONE-LINE DIAGRAM - DEMOLITION

53EP611 - BLDG 53 - ONE-LINE DIAGRAM - PART 1 OF 6

53EP612 - BLDG 53 - ONE-LINE DIAGRAM - PART 2 OF 6

53EP613 - BLDG 53 - ONE-LINE DIAGRAM - PART 3 OF 6

53EP614 - BLDG 53 - ONE-LINE DIAGRAM - PART 4 OF 6

53EP615 - BLDG 53 - ONE-LINE DIAGRAM - PART 5 OF 6

53EP616 - BLDG 53 - ONE-LINE DIAGRAM - PART 6 OF 6

EP701 - ELECTRICAL SCHEDULES

EP702 - ELECTRICAL SCHEDULES

01EP701 - BLDG 01 - ELECTRICAL SCHEDULES

01EP702 - BLDG 01 - ELECTRICAL SCHEDULES

01EP703 - BLDG 01 - ELECTRICAL SCHEDULES

18&11EP701 - BLDG 18&11 - ELECTRICAL SCHEDULES

22EP701 - BLDG 22 - ELECTRICAL SCHEDULES

24EP701 - BLDG 24 - ELECTRICAL SCHEDULES

24EP702 - BLDG 24 - ELECTRICAL SCHEDULES

52EP701 - BLDG 52 - ELECTRICAL SCHEDULES

53EP701 - BLDG 53 - ELECTRICAL SCHEDULES

53EP702 - BLDG 53 - ELECTRICAL SCHEDULES

1. THESE "GENERAL NOTES" SHALL APPLY TO ALL DRAWINGS WITHIN THIS DRAWING SET.

2. IF THE SPECIFICATIONS OR DRAWINGS CONFLICT WITH EACH OTHER THE MORE STRINGENT CRITERIA/SCOPE OF WORK SHALL BE REQUIRED.

3. BLACKENED OR BOLDED EQUIPMENT INDICATES THE EQUIPMENT SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR. ITEMS NOT DIRECTLY FURNISHED BY THE CONTRACTOR SHALL HAVE A DESIGNATION SUCH AS OFCI (OWNER FURNISHED CONTRACTOR INSTALLED), OFOI (OWNER FURNISHED OWNER INSTALLED), OR NIC (NOT IN CONTRACT. GRAY OR GRAY-SCALED EQUIPMENT SHALL BE ASSUMED TO BE EXISTING OR SHOWN FOR EQUIPMENT LOCATION COORDINATION.

4. EXISTING CIRCUITS ASSOCIATED WITH THE PROJECT AREA OF WORK ARE TO BE DE-ENERGIZED DURING CONSTRUCTION.

5. ALL ELECTRICAL WORK SHALL BE COMPLETED WITH ALL PROXIMATE ELECTRICAL CIRCUITS DE-ENERGIZED (i.e. A NEW BREAKER OR CIRCUIT CANNOT BE ADDED TO A PANEL UNLESS THE PANEL IS COMPLETELY DE-ENERGIZED), OR THE CONTRACTOR MUST COMPLY WITH NFPA 70E FOR WORK ON ENERGIZED SERVICE. THE VA WILL DETERMINE IF THE ELECTRICAL SERVICE CAN BE SHUT DOWN OR IT WILL HAVE TO BE WORKED HOT DEPENDING ON THE CRITICALITY OF THE AREA BEING AFFECTED. IF THE WORK MUST BE DONE WITH THE SERVICE LIVE, THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL REQUIRED PROTECTIVE TOOLS, EQUIPMENT, AND CLOTHING, AND MUST FOLLOW THE JOB SPECIFIC WORK PLAN PREPARED BY THE CONTRACTOR AND APPROVED BY THE VA. WORK THAT REQUIRES SHUTTING DOWN ELECTRICAL SERVICE MAY HAVE TO BE ACCOMPLISHED DURING OTHER THAN NORMAL DUTY HOURS.

6. PROVIDE RACEWAYS AND CONDUCTORS/CABLING FROM LUMINAIRES TO THEIR CORRESPONDING CONTROL DEVICES AS INDICATED ON PLANS.

7. LUMINAIRE INSTALLATIONS AND LAYOUTS SHALL BE COORDINATED WITH ALL OBSTACLES, EQUIPMENT AND ARCHITECTURAL FEATURES.

8. WHERE NOT SPECIFICALLY INDICATED ON DRAWINGS, BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG MINIMUM FOR RUNS EQUAL TO OR LESS THAN 65 FEET AND 10 AWG MINIMUM FOR RUNS GREATER THAN 65 FEET. RACEWAYS AND CONDUCTORS SHALL BE SIZED AND QUANTIFIED TO SERVE AND CONTROL APPLICABLE EQUIPMENT WITH VOLTAGE DROP NO GREATER THAN THREE PERCENT. CONDUCTOR SIZE SHALL BE INCREASED TO COMPENSATE FOR DERATING REQUIRED PER NEC 310.15 WHERE MORE THAN THREE CURRENT CARRYING CONDUCTORS WITHIN ONE RACEWAY; CONDUCTOR AMPACITIES SHALL BE TAKEN FROM THE 75°C

COLUMN. INDIVIDUAL CIRCUITS SHALL NOT SHARE NEUTRAL CONDUCTORS.

9. MINIMUM CONDUIT SIZE SHALL BE 1” FOR EXTERIOR AND UNDERGROUND CONDUIT. MINIMUM CONDUIT SIZE SHALL BE 3/4” FOR INTERIOR CONDUIT. ADDITIONAL CONDUCTORS FOR UNSWITCHED HOT CONDUCTOR TO LUMINAIRES WITH EMERGENCY BATTERY POWERED BACKUP UNITS OR TRANSFER DEVICES SHALL BE PROVIDED. ALL CONDUIT SHALL BE CONCEALED. THE ABOVE COMMENTS SHALL BE ADHERED TO UNLESS OTHERWISE NOTED ON THE DRAWINGS.

10. EMERGENCY LIGHTING OR EQUIPMENT CIRCUITS SHALL BE ROUTED INDEPENDENT FROM OTHER CIRCUIT TYPES; ENSURE NEC 700.10 REQUIREMENTS ARE MET.

11. PROVIDE ALL CONDUIT AND WIRE FOR ALL CIRCUITS INDICATED AND/OR NOTED ON THE DRAWINGS AND/OR SPECIFICATIONS. ALL AUXILIARY OR REQUIRED APPURTENANCES FOR PROVIDED EQUIPMENT SHALL BE PROVIDED WITH ALL CONNECTIONS AS REQUIRED.

12. ALL EQUIPMENT AND DEVICES INCLUDING, BUT NOT LIMITED TO, ELECTRICAL DISTRIBUTION EQUIPMENT, RECEPTACLES, DATA OUTLETS, AND SPECIAL SYSTEM DEVICES, SHALL HAVE THEIR EXACT LOCATION COORDINATED WITH ARCHITECTURAL DRAWINGS AND ALL TRADES PRIOR TO COMMENCING WORK.

13. COORDINATE WITH LIGHTING MANUFACTURER FOR ALL LIGHTING CONTROL EQUIPMENT AND APPURTENANCES; PROVIDE ANY ADDITIONAL SENSORS TO PROVIDE FULL COVERAGE OF THE SPACE AS REQUIRED. ALL CONDUIT, WIRE, POWER SUPPLIES, AND APPURTENANCES REQUIRED FOR THE LIGHTING CONTROL SYSTEM

SHALL BE PROVIDED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.

14. ALL EXTERIOR MOUNTED RECEPTACLES AND LUMINAIRE INSTALLATIONS SHALL COORDINATE EXACT LOCATIONS WITH ARCHITECTURAL SHEETS. ADDITIONALLY, WHERE MASONRY IS USED, SMOOTH BLOCK SHALL BE UTILIZED TO PROVIDE A PROPER MOUNTING SURFACE TO ALL EQUIPMENT; RECEPTACLES SHALL BE

INSTALLED FLUSH.

15. ALL CONDUIT/SLEEVE FLOOR AND WALL PENETRATIONS SHALL BE SEALED WITH FIRE RATED ASSEMBLIES, CAULKING, AND APPURTENANCES. ELECTRICAL BOXES

LOCATED IN FIRE RATED WALLS SHALL BE RATED FOR USE IN FIRE RATED WALLS.

16. ALL EQUIPMENT AND INSTALLATION METHODS SHALL BE LISTED AND LABELED PER NEC, UL LISTED, OR REVIEWED EQUAL.

17. FOR ALL EQUIPMENT, COORDINATE WITH ALL TRADES (ARCHITECTURAL, MECHANICAL, PLUMBING, ETC) FOR ELECTRICAL REQUIREMENTS AND INSTALLATION

LOCATIONS PRIOR TO INSTALLATION.

18. ALL LOW-VOLTAGE SYSTEM CABLING NOT RAN IN CONDUIT TO WALL MOUNTED DEVICE SHALL HAVE A MINIMUM 1"C ROUTED FROM DEVICE THROUGH WALL INTO THE ACCESSIBLE CEILING SPACE; CABLING SHALL NOT BE ROUTED IN WALLS OR IN AN INACCESSIBLE LOCATION WITHOUT CONDUIT.

19. GFCI RECEPTACLES SHALL BE PROVIDED WITHIN 6’ OF A SINK/OR WATER SOURCE, WITHIN DAMP ROOMS, OR WHEN MOUNTED OUTDOORS/EXTERIOR TO THE

BUILDING.

20. NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED, OR NOTCHED WITHOUT PRIOR WRITTEN CONSENT FROM THE STRUCTURAL ENGINEER OR ARCHITECT.

21. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.

22. LIGHTING FIXTURES WITH MORE THAN TWO LAMPS SHALL HAVE TWO OUTER LAMPS CONTROLLED WITH ONE SWITCH AND INNER LAMP(S) CONTROLLED BY A

SECOND SWITCH.

23. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC TABLE 250.122. ALL WIRING IS BASED ON Cu COPPER PER NEC TABLE 310.15(B)(16), USING 75°C AMPACITIES

FOR FEEDERS.

24. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN

DEVICES.

25. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES, CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND

REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.

26. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.

27. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

28. ALL PENETRATIONS SHALL BE PERMITTED, LOGGED, AND INSPECTED BY VA MUSKOGEE HCS FIRE DEPARTMENT PRIOR TO FINAL CLOSURE.

29. NO MC CABLE TO BE USED EXCEPT FOR LIGHTING FIXTURES FACTORY WIRED WITH IT.

30. ALL SURGE PROTECTION DEVICES (SPD) AND DIGITAL POWER METERS (DPM) PROVIDED SHALL BE INTEGRAL TO THE EQUIPMENT IT IS PROTECTING /

MONITORING, UNLESS OTHERWISE NOTED.

31. ALL MODIFIED OR PROVIDED RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT "1". REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.

ANY AND ALL FIRE ALARM WORK INCLUDING, BUT NOT LIMITED TO, EQUIPMENT RELOCATION, EXTENDING EXISTING CABLING AND RACEWAYS, AND EQUIPMENT

DEMOLITION SHALL BE PERFORMED BY A LICENSED FIRE ALARM CONTRACTOR.

32.

SECTION

SHEET WHERE SECTION

IS TAKEN FROM

SECTION LETTER

DETAIL NUMBER

SHEET ON WHICH DETAIL APPEARS

DETAIL AREA

XXX CONDUIT & WIRE TAG

(REFER TO CONDUIT AND WIRE SCHEDULE)

XX FAULT CURRENT TAG

(3 PH, SYM AMPS)

KEY NOTE

XXX

FIGURE OR PHOTO

DETAIL NUMBER

IF PHOTO, ARROW DENOTES

DIRECTION TAKEN

SHEET WHERE DETAIL IS TAKEN FROM

DETAIL/PLAN

DETAIL/PLAN NUMBER

XXX

A

XXX

A

XXX

SHEET WHERE SECTION

IS TAKEN FROM

SCALE

SECTION LETTER

1 METERING NOTE

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:

05/24/2024100% ISSUED FOR BID

A/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

Department of Veteran Affairs

EPG002

ELECTRICAL LEGENDS

JACK C MONTGOMERY VAMC

05/24/2024 WNM/SJM RTS/BCL

EHRM INFRASTRUCTURE UPGRADES -

JACK C. MONTGOMERY VA MEDICAL

CENTER

623-21-700

1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

Dwg. 2 of 77

D I V 2 6 - L E G E N D

PE

DS

X

X

X

ALL INTERIOR AREAS TO HAVE MANUAL 0N/AUTO OFF LIGHTING

CONTROL WITH THE USE OF DUAL TECHNOLOGY OCCUPANCY SENSORS.

EXCEPT WHERE A WALL SWITCH OCCUPANCY SENSOR IS NOTED.

PHOTO ELECTRIC SENSOR

DAYLIGHT SENSOR FOR DAYLIGHT HARVESTING

CONTROL. SENSOR SHALL BE CEILING MOUNTED.

RECEPTACLE, SINGLE WITH SWITCH

RECEPTACLE, SPECIAL PURPOSE

Z = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.

Y = 208V, 20A, 3 PHASE, 4 POLE, 5W, NEMA L21-20P

X = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.

W = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.

V = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.

U = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.

T = 208V, 20A, 3 PHASE, 3 POLE, 4W, NEMA L21-20R.

S = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.

R = 208V, 30A, 3 PHASE, 4 POLE, 5W, NEMA L21-30R.

Q = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.

RECEPTACLE, SWITCHED DUPLEX

DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,

GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN FLEXIBLE

CORD (CENTER LINE OF OUTLET: 6'-6" [1981mm] AFF. MINIMUM).

ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm]

CENTERS OR AS DESIGNATED ON DRAWINGS), MTD

3'-6" [1067mm] AFF OR AS INDICATED.

SWITCH

F = FUSED SWITCH K = KEY OPERATED

L = LOCK LM= LOW VOLTAGE MASTER

M = MANUAL MOTOR STARTING MC= MOMENTARY CONTACT

MP= MOTOR SNAP WITH PILOT LIGHT P = WITH PILOT LIGHT

(THERMAL TYPE)

PB= PUSH BUTTON STATION RC= REMOTE CONTROL

WP= WEATHER PROOF X = EXPLOSION PROOF

SWITCH (# SUBSCRIPT AS INDICATED BELOW):

BLANK = SINGLE POLE 2 = DOUBLE POLE

3 = THREE-WAY 4 = FOUR-WAY

D = DIMMER K = KEY OPERATED

LV= LOW VOLTAGE P = WITH PILOT LIGHT

LM= LOW VOLTAGE MASTER RC= REMOTE CONTROL

PB= PUSH BUTTON STATION WP= WEATHER PROOF

T = TIMER OPERATED Mo= OCCUPANCY SENSOR

LIGHTING, ONE HEAD EMERGENCY BATTERY POWER

LIGHTING, TWO HEAD EMERGENCY BATTERY POWER

LIGHTING, THREE HEAD EMERGENCY BATTERY POWER

EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL

ARROWS AND FACES AS SHOWN

EXIT SIGN, CEILING MOUNTED WITH

DIRECTIONAL ARROWS AND FACES AS SHOWN

LIGHT FIXTURE, SURFACE MOUNTED, 2'x2';

LETTER INDICATES TYPE.

LIGHT TRACK WITH HEADS AS SHOWN

LIGHT FIXTURE, BOLLARD

LIGHTING

x = LUMINAIRE SWITCH ZONE (ANY LOWER CASE LETTER APPLIES)

E

S

S

OS

J

G E N E R A L S Y M B O L

EMERGENCY NORMAL

G

SWITCH, MULTIPOSITION

SWITCH, SINGLE BREAK

FUSE

NORMALLY CLOSED RELAY CONTACT

NORMALLY OPEN RELAY CONTACT

SWITCH, FUSED

DRAWOUT AIR CIRCUIT BREAKER

MOTOR

TRANSFORMER (PRIMARY OR SECONDARY WIRING,

DELTA OR WYE AS INDICATED)

EARTH GROUND

JUNCTION BOX

PULL BOX

GENERATOR, POWER

BATTERY

CAPACITOR

RELAY; NUMBER INDICATES RELAY TYPE

50 = INSTANTANEOUS OVER CURRENT OR RATE-OF-RISE

51 = AC-TIME OVER CURRENT

67 = AC-DIRECTIONAL OVER CURRENT

86 = LOCKING OUT

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED

STARTER, COMBINATION WITH DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

METER

AMMETER

VOLTMETER

WATTMETER

WATT-HOUR METER

TRANSFORMER, PLAN

LADDER CABLE TRAY

ELECTRICAL UNDERGROUND BOX, V = VAULT; HH = HANDHOLE.

PANELBOARD, FLUSH MOUNTED

PANELBOARD, SURFACE MOUNTED

RECEPTACLE, DUPLEX

RECEPTACLE, DUPLEX ON EMERGENCY POWER

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER

RECEPTACLE, QUADRUPLEX

RECEPTACLE, SINGLE

POWER

PB

T

V

CONDUIT OR EQUIPMENT TO BE REMOVED

CONDUIT 3/4"C, 3#12 PHASE, 1#12N, & 1#12 GND UNLESS

SHOWN OTHERWISE. ( EXAMPLE SHOWN: TO PANEL P1,

CIRCUIT 1,3,5). LONG TICK FOR NEUTRAL WIRE; ONE SHORT

TICK FOR EACH PHASE WIRE; GROUND SIZED PER NEC. NOTE

THAT A SECOND SHORT TICK FOR LUMINAIRES IS FOR A

TRAVELER WIRE.

CONDUIT HOME RUN - SEE CONDUIT AND WIRE SCHEDULE

CONDUIT CONCEALED IN WALL, CEILING, UNDER FLOOR, IN

FLOOR SLAB, OR ROUTED UNDERGROUND

CONDUIT CONCEALED WHERE POSSIBLE, OTHERWISE EXPOSED

EXTRA-HARD USAGE FLEXIBLE CORD

FLEXIBLE CONDUIT

CONDUIT TURNED UP OR TOWARD

CONDUIT TURNED DOWN OR AWAY

CONDUIT CAPPED

XXXX

J

M

A

V

W

WH

X X

X X

X X

X X

X X

X X

XX

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X = DENOTES LUMINAIRE TAG NAME

RECESSED DOWNLIGHT FIXTURE

LIGHT FIXTURE, RECESSED, 2'x4'

LIGHT FIXTURE, RECESSED, 1'x4'

LIGHT FIXTURE, RECESSED, 1'x8'

LIGHT FIXTURE, RECESSED, 2'x2'

LIGHT FIXTURE, SURFACE MOUNTED, 2'x4'

LIGHT FIXTURE, SURFACE MOUNTED, 1'x4'

LIGHT FIXTURE, SURFACE MOUNTED, 1'x8'

LIGHT FIXTURE, SURFACE MOUNTED, 2'x2'

STRIP LIGHTING, 4' LONG

LIGHT FIXTURE, WALL MOUNTED

STREET LIGHT WITH BRACKET

LIGHT POLE, ONE LUMINAIRE

LIGHT POLE, TWO LUMINAIRES

LIGHT POLE, POST TOP MOUNT LUMINAIRE

LIGHTING WALL PACK, EXTERIOR BUILDING THESE ARE GENERAL LEGENDS. NOT ALL SYMBOLS MAY BE SHOWN.

REFERENCE PLANS FOR ALL UTILIZED SYSMBOLS.

INSULATED TAP

GROUNDING ROD WITH TEST WELL

LIGHTNING AIR TERMINAL

X = DESCRIPTION

E = EMERGENCY POWER OFF (OFF)

X

BUS DUCT - ONE-LINE DIAGRAM

CIRCUIT BREAKER

HH

DIGITAL POWER METER (ASSUME INTEGRAL TO

DEVICE UNLESS OTHERWISE NOTED)

SURGE PROTECTION DEVICE (ASSUME INTEGRAL TO

DEVICE UNLESS OTHERWISE NOTED)

DPM

SPD

CIRCUITING DESIGNATIONS

WHERE A PANEL NAME AND CORRESPONDING CIRCUIT ARE CALLED OUT ADJACENT TO A RECEPTACLE, LUMINAIRE, OR MISC LOAD, THAT LOAD SHALL BE CIRCUITED TO THE CORRESPONDING PANELBOARD CIRCUIT BREAKER. CONDUIT AND WIRE FOR CIRCUIT SHALL BE 3/4" CONDUIT WITH (2) 12 AWG AND (1) 12 AWG GND, UNLESS OTHERWISE NOTED; IF FURTHER THAN 70', PHASE AND GROUND WIRE SHALL BE UPSIZED TO 10 AWG TO ACCOUNT FOR VOLTAGE DROP.

SEE EXAMPLES BELOW:

RECEPTACLE:

PANELBOARD OR POWER SOURCE NAME = "P1"

CIRCUIT NUMBER OF POWER SOURCE = "2"

LUMINAIRE:

PANELBOARD OR POWER SOURCE NAME = "PP3"

CIRCUIT NUMBER OF POWER SOURCE = "4"

TYP LUMINIARE TAG NAME, REFERENCE LUMINAIRE SCHEDULE = "L1"

LIGHTING CONTROL SWITCH LEG = "a"

ALL LUMINAIRES IN SAME ROOM ARE CIRCUITED TO SAME CIRCUIT = PP3-4

MISC LOAD:

PANELBOARD OR POWER SOURCE NAME = "PP"

CIRCUIT NUMBER OF POWER SOURCE = "7"

P1-2 P1-2

HEAT PUMP

PP-7

L1 a

PP3-4

FACP

PP-7

DIV 28 - LEGENDS

MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC

X-REQUEST-FOR-EXIT

M

T

PUSH BUTTON; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BELL PUSH D-DURESS P-PANIC R-DOOR RELEASE

X-REQUEST-FOR-EXIT

M

T

CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

M

SECURITY ACCESS, HORN OR SIREN

S…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .