Attachment 04 Drawings 3 of 13 Muskogee 623-21-700.pdf
PDF 19 MB Posted
- Solicitation number
- 36C77624R0046
About this file
This document is a set of electrical plan drawings for infrastructure upgrades at the Jack C. Montgomery VA Medical Center in Muskogee, Oklahoma. The comprehensive drawing set includes electrical plans for multiple buildings (Buildings 1, 18, 22, 24, 52, and 53) across various levels, including basement, first floor, second floor, third floor, mezzanine, and roof levels.
The drawings detail electrical infrastructure modifications, including new heat pump installations, condensing units, telecommunications bonding, power distribution equipment replacement, and electrical circuit routing. Key components include transformer locations, panelboard placements, telecommunications rooms, and electrical equipment upgrades across different building zones. The drawings are part of the EHRM (Enterprise Healthcare Resource Management) Infrastructure Upgrades project, with detailed technical specifications for electrical system modifications, conduit routing, and equipment positioning. The drawings are dated 05/24/2024 and prepared by DAV Energy Solutions for the Department of Veterans Affairs.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Department of Veteran Affairs
N
M-107A
BUILDING 1 ROOF PLAN
SCALE: 1/8" = 1'-0"
KEY NOTES
SHEET NOTES
NEW HEAT PUMP DAIKIN RK24BXVJU SIZED FOR 2.0
TONS.
HEAT PUMP IS ROUTED TO THE FIFTH FLOOR TO
SERVICE MINI SPLIT IN ROOM 5A04-1.
2 HEAT PUMP IS ROUTED TO THE FOURTH FLOOR TO
SERVICE MINI SPLIT IN ROOM 403-1.
1.A 1.B 1.C 1.D 1.E 1.F 1.G 1.H 1.I 1.J 1.K 1.L 1.M
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.1a
150 SF
STAIRWELL
601C-1
11708 SF
BUILDING 1 ROOF
601-1
121 SF
ELEV LOBBY
600-1
142 SF
STAIRWELL
601B-1
63 SF
P1
52 SF
P2
3'-4"
1 21 3 1 3 1 2
CU-403-1-2
CU-403-1-1
CU-5A04-1-1
CU-5A04-1-2
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building No.
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
STAMP:
AutoCAD SHX Text
EHRM INFRASTRUCTURE UPGRADES - JACK C. MONTGOMERY VA MEDICAL CENTER
AutoCAD SHX Text 623-21-700
AutoCAD SHX Text
AD
AutoCAD SHX Text
AB
AutoCAD SHX Text 05/24/2024
AutoCAD SHX Text Floor No.
AutoCAD SHX Text Dwg. of 24
AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
AutoCAD SHX Text
JACK C MONTGOMERY VAMC 1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
100% ISSUED FOR BID
AutoCAD SHX Text 05/24/2024
AutoCAD SHX Text M-107A
AutoCAD SHX Text
AutoCAD SHX Text
ROOF
AutoCAD SHX Text
BUILDING 1 ROOF PLAN
AutoCAD SHX Text
M-107B
BUILDING 53 ROOF PLAN
SCALE: 1/8" = 1'-0"
N
KEY NOTES
SHEET NOTES
NEW HEAT PUMP DAIKIN RKS30LVJU SIZED FOR 2.5
TONS.
HEAT PUMP IS ROUTED TO THE FIFTH FLOOR TO
SERVICE MINI SPLIT IN ROOM 5A-109.
2 HEAT PUMP IS ROUTED TO THE FOURTH FLOOR TO
SERVICE MINI SPLIT IN ROOM 4A-109.
53.A 53.B 53.C 53.D 53.E 53.F 53.G 53.H 53.I 53.J 53.K 53.L
203 SF
MECH
6A-101
136 SF
STAIR
6A-ST1
2136 SF
MACHINE
PENTHOUSE
6A100-53
CU-4A109-1
CU-4A109-2
CU-5A109-1
CU-5A109-2
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building No.
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
STAMP:
AutoCAD SHX Text
EHRM INFRASTRUCTURE UPGRADES - JACK C. MONTGOMERY VA MEDICAL CENTER
AutoCAD SHX Text 623-21-700
AutoCAD SHX Text
AD
AutoCAD SHX Text
AB
AutoCAD SHX Text 05/24/2024
AutoCAD SHX Text Floor No.
AutoCAD SHX Text Dwg. of 24
AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
AutoCAD SHX Text
JACK C MONTGOMERY VAMC 1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
100% ISSUED FOR BID
AutoCAD SHX Text 05/24/2024
AutoCAD SHX Text M-107B
AutoCAD SHX Text
AutoCAD SHX Text
ROOF
AutoCAD SHX Text
BUILDING 53 ROOF PLAN
Scale: NTS
Veteran Affairs
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text M-401
AutoCAD SHX Text
MECHANICAL SCHEDULES
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building No.
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
STAMP:
AutoCAD SHX Text Floor No.
AutoCAD SHX Text Dwg. of 24
AutoCAD SHX Text
100% ISSUED FOR BID
AutoCAD SHX Text 05/24/2024
AutoCAD SHX Text
EHRM INFRASTRUCTURE UPGRADES - JACK C. MONTGOMERY VA MEDICAL CENTER
AutoCAD SHX Text 623-21-700
AutoCAD SHX Text
AD
AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
JACK C MONTGOMERY VAMC 1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
AutoCAD SHX Text
AB
AutoCAD SHX Text 05/24/2024
AutoCAD SHX Text
DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
Scale: NTS
AC
COND. DRAIN LINE.
SEE PLANS FOR
TERMINATION
SUPPORT ON WALL
RS AND RL
CONTINUATION TO CU
R S
R L
EXIST MASONRY
WALL
CAULK (TYP)
CAULK (TYP)
PIPE SLEEVE
PIPE
INSULATION
PIPE
FIRE RATED CAULKING
FIRE RATED CAULKING
PIPE
INSULATION
PIPE
STAINLESS STEEL BOLTS,
NUTS & WASHERS CONTRACTOR CORE
DRILLED HOLE
EXIST MASONRY
WALL
PIPE SLEEVE
EXTERIOR SIDE OF
CONCRETE WALL
INTERIOR SIDE OF WALL
PIPE CENTERED IN
SLEEVE
PIPE
INSULATION
WITH JACKET
MINERAL WOOL
PIPE
INSULATION
WITH JACKET
OUTSIDE INSIDE
MINERAL WOOL RESILIENT WATERPROOF
CAULKING
MODULAR TYPE WALL
PENETRATION SEAL
LS MODEL (C, L, S-316, O,
OS-316, T)
OUTSIDE INSIDE
CAULK (TYP)
NO SCALE: NO SCALE: NO SCALE: NO SCALE:
FIRE RESISTANT
SEALANT
PIPE RISER
PIPE SLEEVE
1/2"
1/2"
FLOOR OPENING
NO SCALE:
NOTES:
120V TO 24V AREA Tx
TRANSFORMER(S) BY DIV. 15,
EMS CONTRACTOR.
NORMAL MODE CONTROL
ROOM TEMPERATURE SENSOR SHALL MODULATE CAV BOX-REHEAT COIL CONTROL
VALVE TO MAINTAIN THE REQUIRED TEMPERATURE SETPOINT. EMCS SHALL
MONITOR AIRFLOW CFM, VALVE COMMAND POSITION, DISCHARGE AIR
TEMPERATURE, AND ROOM TEMPERATURE.
SEE ELECTRICAL DRAWINGS FOR
120-VOLT CIRCUTS INTENDED TO
SERVE MULTIPLE CAV BOXES. PROVIDE
120V/24V CONTROL TRANSFORMER
DOWNSTREAM OF J-BOX, TYP.
1. DIV. 26 TO MOUNT 120 VOLT J-BOX IN AREA ADJACENT TO BOXES BEING SERVED.
2. REFER TO THE MECHANICAL DRAWINGS FOR EXACT LOCATIONS OF ROOM
TEMPERATURE SENSORS.
3. ROOM SENSOR TO PROVIDE SETPOINT ADJUSTMENT. ROOM TEMPERATURE
SENSOR SHALL BE ABLE TO MAINTAIN SPACE. REFER TO ROOM AIR SCHEDULE
FOR TEMPERATURE SET POINTS.
HOT WATER REQUIREMENTS
FOR HOT WATER HEATING
COIL LISTED ON ATU
SCHEDULE ON DRAWING M-401
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building No.
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
STAMP:
AutoCAD SHX Text
EHRM INFRASTRUCTURE UPGRADES - JACK C. MONTGOMERY VA MEDICAL CENTER
AutoCAD SHX Text 623-21-700
AutoCAD SHX Text
AD
AutoCAD SHX Text
AB
AutoCAD SHX Text 05/24/2024
AutoCAD SHX Text Floor No.
AutoCAD SHX Text Dwg. of 24
AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
AutoCAD SHX Text
JACK C MONTGOMERY VAMC 1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
100% ISSUED FOR BID
AutoCAD SHX Text 05/24/2024
AutoCAD SHX Text M-501
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL DETAILS
AutoCAD SHX Text
AutoCAD SHX Text
DUCTLESS SPLIT SYSTEM DETAIL
AutoCAD SHX Text
AutoCAD SHX Text
PIPE THROUGH WALL DETAIL
AutoCAD SHX Text
AutoCAD SHX Text
PIPE THROUGH FIRE RATED WALL DETAIL
AutoCAD SHX Text
AutoCAD SHX Text
PIPE PENETRATION THROUGH WALLS BELOW GRADE
AutoCAD SHX Text
AutoCAD SHX Text
PIPE THROUGH FLOOR DETAIL
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
DUCTWORK RADIUS ELBOWS
AutoCAD SHX Text
VANE
AutoCAD SHX Text
VANE
AutoCAD SHX Text
R SHALL EQUAL OR BE GREATER THAN W.
AutoCAD SHX Text
R SHALL EQUAL OR BE GREATER THAN 1/3W.
AutoCAD SHX Text R
AutoCAD SHX Text
R SHALL EQUAL OR BE GREATER THAN 1/6W.
AutoCAD SHX Text
STANDARD RADIUS OR LONG RADIUS ELBOW
AutoCAD SHX Text
SHORT RADIUS ELBOW WITH ONE VANE
AutoCAD SHX Text
SHORT RADIUS ELBOW WITH TWO VANES
AutoCAD SHX Text R
AutoCAD SHX Text NOTE: 1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND. 2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL SHORT ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
DUCTWORK SQUARE VANE ELBOWS
AutoCAD SHX Text NOTE: 1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA. WHEN ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE REGARDLESS OF W 2. DIMENSION. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1 1/2" MAXIMUM DIMENSION. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1 1/2" MAXIMUM SPACE 3. BETWEEN VANES AND A 3/4" TRAILING EDGE. WHEN W EQUALS W2 AND W1 IS GREATER BETWEEN VANES AND A 3/4" TRAILING EDGE. WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" VANES SHALL BE DOUBLE VANE TYPE.
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
EXHAUST OR RETURN BRANCH DUCTWORK
AutoCAD SHX Text
MAIN EXHAUST OR RETURN
AutoCAD SHX Text
%%UPLAN VIEW
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text
PROVIDE VOLUME DAMPER AT EACH BRANCH DUCT
AutoCAD SHX Text 1/4W OR 4" [100mm] MIN.
AutoCAD SHX Text
BRANCH DUCT
AutoCAD SHX Text
VD
AutoCAD SHX Text
NTS
AutoCAD SHX Text
SUPPLY BRANCH DUCTWORK
AutoCAD SHX Text
AutoCAD SHX Text
MAIN SUPPLY
AutoCAD SHX Text
%%UPLAN VIEW
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text
AIR FLOW
AutoCAD SHX Text
PROVIDE VOLUME DAMPER AT EACH BRANCH DUCT
AutoCAD SHX Text
1/4W OR 4" MIN.
AutoCAD SHX Text
BRANCH DUCT
AutoCAD SHX Text
VD
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
VOLUME DAMPER DETAIL
AutoCAD SHX Text
NOTE: 1. 2.
AutoCAD SHX Text DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
AutoCAD SHX Text
INSULATION SEE SPECIFICATION
AutoCAD SHX Text
DAMPER BLADE
AutoCAD SHX Text 1/8" [6mm] CLEARANCE ALL AROUND
AutoCAD SHX Text
OUTSIDE END BEARING
AutoCAD SHX Text
INSIDE END BEARING
AutoCAD SHX Text
HANDLE WITH LOCKING QUADRANT
AutoCAD SHX Text
INSULATION STAND-OFF
AutoCAD SHX Text 1/2" [15mm] ROUND ROD PIN
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
STIFFEN BLADE AS REQUIRED
AutoCAD SHX Text
SIDE ELEVATION
AutoCAD SHX Text
SECTION
AutoCAD SHX Text
NTS
AutoCAD SHX Text
DUCT CONNECTIONS - AIR TERMINAL UNITS
AutoCAD SHX Text
AIR TERMINAL UNIT (CV OR VAV)
AutoCAD SHX Text
REHEAT COIL
AutoCAD SHX Text
SOUND ATTENUATOR SEE EQUIPMENT SCHEDULE
AutoCAD SHX Text
HARD AIR DUCT CONNECTOR. SEE DETAIL
AutoCAD SHX Text
DIFFUSER (TYP.)
AutoCAD SHX Text
AutoCAD SHX Text NOTE: 1. RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF INLET RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF INLET 2. PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET. FOR LONGER PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET. FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT OR BELOW 0.2"/100'.
AutoCAD SHX Text
AutoCAD SHX Text
NTS
AutoCAD SHX Text
ROUND DUCT HANGERS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text ONE 1 x 18 GA STRAP
AutoCAD SHX Text
AutoCAD SHX Text
TWO 1/2%%C RODS
AutoCAD SHX Text
TWO 3/8%%C. RODS
AutoCAD SHX Text ONE 1 x 16 GA STRAP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text ONE 1 x 22 GA STRAP
AutoCAD SHX Text
QUANTITY/SIZE
AutoCAD SHX Text
MAX. DUCT %%C
AutoCAD SHX Text
AutoCAD SHX Text
HANGER STRAPS OR RODS
AutoCAD SHX Text
MAX. LOAD
AutoCAD SHX Text
LBS.
AutoCAD SHX Text
AutoCAD SHX Text
MAX.
AutoCAD SHX Text
AutoCAD SHX Text
IN.
AutoCAD SHX Text
SPACING
AutoCAD SHX Text
IN.
AutoCAD SHX Text
IN.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text NOTE: TABULATED DATA FROM SMACNA ALLOWS FOR DUCT REINFORCING AND INSULATION, BUT NO EXTERNAL LOAD.
AutoCAD SHX Text
BAND
AutoCAD SHX Text
OVER 50"
AutoCAD SHX Text
HANGER RODS
AutoCAD SHX Text
BAND OF SAME SIZE AS HANGER STRAP
AutoCAD SHX Text
LOAD RATED FASTENERS
AutoCAD SHX Text
50" & UNDER
AutoCAD SHX Text
NTS
AutoCAD SHX Text
TYPICAL CAV BOX CONTROL DIAGRAM
AutoCAD SHX Text
AutoCAD SHX Text
CAV BOX WITH ENCLOSURE
AutoCAD SHX Text 120V
AutoCAD SHX Text
TX
AutoCAD SHX Text
DTS
AutoCAD SHX Text
SA
AutoCAD SHX Text
RTS
AutoCAD SHX Text
DATA BUS
AutoCAD SHX Text
FROM AC UNIT
AutoCAD SHX Text
CF
AutoCAD SHX Text
AI
AutoCAD SHX Text
AI
AutoCAD SHX Text
DI
AutoCAD SHX Text
PWR BY DIV. 26
AutoCAD SHX Text
HW
Scale: NTS
NEW
DUCTLESS SPLIT
MOUNTED HIGH
ON WALL
(COORDINATE MOUNTING
HEIGHT WITH CONDITIONS
OF THE SPACE)
M FLOOR
T1 H T1
RACK PDU'S - SEE PLANS FOR
NUMBER OF RACKS PER TR.
DDC
CONTROLLER
M
H
FLOOR MOISTURE
SPACE HUMIDITY
SPACE TEMP
TIE INTO EXISTING BMS
A.I.
A.I.
A.I.
D.O.
A.I.
A.I.
RACK 1 TEMP/HUM
RACK 1 TEMP/HUM
PDU-1 PDU-2
SEQUENCE OF OPERATION
THE DUCTLESS SPLIT SHALL OPERATE CONTINUOUSLY TO
MAINTAIN A SPACE TEMPERATURE OF 75°(ADJ).
SHOW TEMPERATURE AND HUMIDITY AT THE GRAPHIC
DISPLAY. PROVIDE TEMPERATURE TRENDS.
PROVIDE ALARM FOR TEMPERATURE ABOVE 80F.
PROVIDE ALARM FOR MOISTURE SENSED ON FLOOR.
SHOW RACK TEMPERATURE AND HUMIDITY (SEE PLANS
FOR NUMBER OF RACKS PER TR)
W
AL
L
INSTALL LINE SET PER
MANUFACTURE
RECOMMENDATIONS.
RS AND RL LINES TO
DUCTLESS SPLIT
TOP OF ROOF
FINISH
ROOFER WILL SEAL
AROUND LEGS FOR
COMPLETE WATER
PROOF (TYP)
3/8"Ø GRADE S SCREWS OR THRUBOLT
WITH 1"Ø WASHER TO STRUCTURAL
A36 STEEL MEMBERS (3/16" MIN HOST)
4 ANCHORS PER PLATE .
CONDENSING UNIT
WALL
MINIMUM 12"
BRAIDED
FLEXIBLE
REFRIGERANT
LINE
SUPPORT ON WALL WITH 3/8" Ø POWERS CARBON
STEEL WEDGE BOLT CONCRETE ANCHOR WITH 1" Ø
MIN WASHER, 1-1/2" EMBEDMENT AND 6" MIN EDGE
DISTANCE. SUPPORT PIPING EVERY 6' MINIMUM.
20 GAGE SHEET METAL PAN AROUND
REFRIGERANT LINES FROM BOTTOM
WALL ANCHOR TO EAVE. PAINT PAN
TO MATCH BUILDING COLOR OF OIL
BASE PAINT . FASTEN SECURELY TO
WALL.
4" DIA. HOLE THRU WALL OR SOFFIT
SEAL WEATHER TIGHT
CROSS MEMBER
S L
PROVIDE ISOLATION
VALVES ON EACH SIDE
OF BRAIDED FLEXIBLE
REFRIGERANT LINE
ROOF HOST
STRUCTURE
18"
SECURELY ATTACH CONDENSING
UNIT TO CROSS MEMBER . (4 BOLTS
TOTAL). TWO 1/4"Ø S.S. THRUBOLTS
WITH 5/8" WASHERS AND NUTS
(1) 5/16-18
THRUBOLT TO
INTERLOCK
SQUARE TUBING
USE MIAMI TECH (MTI)
AS14S OR VA APPROVED
SUBSTITUTE.
ROOFING
20 GAGE SHEET METAL PAN AROUND
REFRIGERANT LINES FROM BOTTOM
WALL ANCHOR TO EAVE. PAINT PAN
TO MATCH BUILDING COLOR OF OIL
BASE PAINT . FASTEN SECURELY TO
WALL.
SUPPORT ON WALL WITH 3/8" Ø POWERS CARBON
STEEL WEDGE BOLT CONCRETE ANCHOR WITH 1" Ø
MIN WASHER, 1-1/2" EMBEDMENT AND 6" MIN EDGE
DISTANCE. SUPPORT PIPING EVERY 6' MINIMUM.
4" DIA. HOLE THRU WALL OR SOFFIT
SEAL WEATHER TIGHT
D L S
INSTALL LINE SET PER
MANUFACTURE
RECOMMENDATIONS.
RS AND RL LINES TO
DUCTLESS SPLIT
90° SWEEP
WALL
1" COND. DRAIN LINE.
TERMINATE 4" ABOVE
GRADE.
PROVIDE ISOLATION
VALVES ON EACH SIDE
OF BRAIDED FLEXIBLE
REFRIGERANT LINE
MIN 4" TALL LIFTERS
PREFABRICATED LIGHTWEIGHT
EQUIPMENT PAD
3/8" Ø POWERS CARBON STEEL
WEDGE BOLT CONCRETE
ANCHOR WITH 1" Ø MIN
WASHER, 2-1/2" EMBEDMENT
AND 6" MIN EDGE DISTANCE
ROUND TUBING
MINIMUM 12"
BRAIDED
FLEXIBLE
REFRIGERANT
LINE
CONDENSING UNIT (CU)
NO SCALE:
NO SCALE:
"UNISTRUT" P2000
SERIES PIPE CLAMP
(TYP)
REFRIGERANT PIPING
SEE PLANS
3/8" BOLT (TYP. 4 EACH POST)
"UNISTRUT" P1000
CHANNEL. LENGTH AS
REQUIRED HIGH DESITY/HIGH
IMPACT
POLYPROPYLENE
BASE (TYP)
CONCRETE PAD
INSULATION
ROOF
ROOF DECK
1/4" STEEL PLATE
NO SCALE:
NO SCALE:
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building No.
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
STAMP:
AutoCAD SHX Text
EHRM INFRASTRUCTURE UPGRADES - JACK C. MONTGOMERY VA MEDICAL CENTER
AutoCAD SHX Text 623-21-700
AutoCAD SHX Text
AD
AutoCAD SHX Text
AB
AutoCAD SHX Text 05/24/2024
AutoCAD SHX Text Floor No.
AutoCAD SHX Text Dwg. of 24
AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
AutoCAD SHX Text
JACK C MONTGOMERY VAMC 1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
100% ISSUED FOR BID
AutoCAD SHX Text 05/24/2024
AutoCAD SHX Text M-502
AutoCAD SHX Text
MECHANICAL DETAILS
AutoCAD SHX Text
AutoCAD SHX Text
TELECOMMUNICATION ROOM CONTROL DIAGRAM
AutoCAD SHX Text
AutoCAD SHX Text
CONDENSING UNIT ROOF MOUNT SUPPORT DETAIL
AutoCAD SHX Text
AutoCAD SHX Text
CONDENSING UNIT GROUND MOUNT SUPPORT DETAIL
AutoCAD SHX Text
AutoCAD SHX Text
PIPE ROOF MOUNTING DETAIL
AutoCAD SHX Text
AutoCAD SHX Text
SUPPORT BRACKET DIMENSION
18" 0.25"
1.63"
4" MINIMUM CLEARANCE
FROM WALL
0.81"
CONDENSING UNIT (CU)
WEIGHT: 133 Lbs
WALL
OUTDOOR UNIT SUPPORT
P2233A - 18" BRACKET (SLOT DOWN)(1-5/8" SERIES)
(BRAND: UNISTRUT)
ISOMETRIC VIEW TOP VIEW
4" MINIMUM CLEARANCE
FROM WALL CONDENSING UNIT (CU)
WEIGHT: 133 Lbs
CONDENSING UNIT (CU)
(E)8" CMU
P1000HS - HG"
WALL
OUTDOOR UNIT SUPPORT
P2233A - 18" BRACKET (SLOW DOWN)(1-5/8" SERIES)
(BRAND: UNISTRUT) 18"
GROUTED CELL: 1/2" DIAMETER SIMPSON
WEDGE-ALL STAINLESS STEEL. EMBED 3 1/2"
UNGROUTED CELL: 3/8" DIAMETER STAINLESS
STEEL SIMPSON TITEN HD. EMBED 2 1/2"
16" OUTDOOR UNIT SUPPORT
P2233A (HG) - 18" BRACKET (SLOT DOWN)(1-5/8" SERIES)
(BRAND: UNISTRUT)
FRONT VIEW SIDE VIEW
5.
4'
NO SCALE:
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Date
AutoCAD SHX Text Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building No.
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text
STAMP:
AutoCAD SHX Text
EHRM INFRASTRUCTURE UPGRADES - JACK C. MONTGOMERY VA MEDICAL CENTER
AutoCAD SHX Text 623-21-700
AutoCAD SHX Text
AD
AutoCAD SHX Text
AB
AutoCAD SHX Text 05/24/2024
AutoCAD SHX Text Floor No.
AutoCAD SHX Text Dwg. of 24
AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
AutoCAD SHX Text
JACK C MONTGOMERY VAMC 1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
AutoCAD SHX Text DAV ENERGY SOLUTIONS 2207 GARNET AVE, SUITE I SAN DIEGO, CA 92109 619-770-8552 WWW.DAVENERGY.COM
AutoCAD SHX Text
100% ISSUED FOR BID
AutoCAD SHX Text 05/24/2024
AutoCAD SHX Text M-503
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL DETAILS
AutoCAD SHX Text
AutoCAD SHX Text
CONDENSING UNIT WALL MOUNT SUPPORT DETAIL
Building No.
Drawing Number
Project Number
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Project Title
ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:
321 4 5 6 7 8 9 10
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE I
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
Floor No.
th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:
05/24/2024100% ISSUED FOR BID
A/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
Department of Veteran Affairs
EPG001
ABBREVIATIONS, GENERAL NOTES, AND
SHEET INDEX
JACK C MONTGOMERY VAMC
05/24/2024 WNM/SJM RTS/BCL
EHRM INFRASTRUCTURE UPGRADES -
JACK C. MONTGOMERY VA MEDICAL
CENTER
623-21-700
1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
Dwg. 1 of 77
S H E E T I N D E XG E N E R A L N O T E SA B B R E V I A T I O N S
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR AVAILABLE
FAULT CURRENT
AFCI ARC-FAULT CURRENT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BD BOARD
BFF BELOW FINISH FLOOR
BLDG BUILDING
BRKR BREAKER
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CD CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/
OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
C/B CIRCUIT BREAKER
CL CONNECTOR LIGHTING
CLF CURRENT LIMITING FUSE
CLG CEILING
CO CONDUIT ONLY
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CUR CURRENT
DB DECIBEL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DDC DIRECT DIGITAL CONTROLS
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DP DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EL ELEVATION OR EXISTING TO BE RELOCATED
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER/EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
EN EXISTING IN NEW LOCATION
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ER EXISTING TO REMAIN
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST(E) EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCIO FURNISHED BY CONTRACTOR,
INSTALLED BY OWNER
FOIC FURNISHED BY OWNER,
INSTALLED BY CONTRACTOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLUOR FLUORESCENT
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G ELECTRICAL GROUND
GEN GENERATOR
GFCI GROUND FAULT
CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTION
GND GROUND
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IG ISOLATED GROUND
IESNA ILLUMINATION ENGINEERING
SOCIETY OF NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
LCP LIGHTING CONTROL PANEL
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MS MOTOR STARTER
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
NA NOT APPLICABLE
NAC NOTIFICATION APPLIANCE CABINET
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NEUT, N NEUTRAL
NFC NOT FOR CONSTRUCTION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
OS OCCUPANCY SENSOR
P POLE
PB PULL BOX
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PIV POST INDICATOR VALVE
PF POWER FACTOR
PH PHASE
PNL PANEL
PS POWER SUPPLY
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
R EXISTING TO BE REMOVED
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
RM ROOM
RMC RIGID METAL CONDUIT
RMS ROOT MEAN SQUARE
REQD REQUIRED
SAC SMALL APPLIANCE CIRCUIT
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SM SMART METER
SPD SURGE PROTECTIVE DEVICE
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD OR SB SWITCHBOARD
SWGR OR SG SWITCHGEAR
TEL TELEPHONE
TR TAMPER RESISTANT
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER
POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT/WEATHERPROOF
(WHILE IN USE)
WH WATER HEATER
WP/W WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
EPG001 - ABBREVIATIONS, GENERAL NOTES, AND SHEET INDEX
EPG002 - ELECTRICAL LEGENDS
01EP101 - BLDG 01 - LEVEL 01 - ELECTRICAL PLAN
18EP100B - BLDG 18 - LEVEL 00B - ELECTRICAL PLAN
18&11EP101 - BLDG 18&11 - LEVEL 01 - ELECTRICAL PLAN
22EP100S - BLDG 22 - LEVEL 00S - ELECTRICAL PLAN
22EP100B - BLDG 22 - LEVEL 00B - ELECTRICAL PLAN
22EP101 - BLDG 22 - LEVEL 01 - ELECTRICAL PLAN
24EP100B - BLDG 24 - LEVEL 00B - ELECTRICAL PLAN
24EP101 - BLDG 24 - LEVEL 01 - ELECTRICAL PLAN
52EP102 - BLDG 52 - MEZZANINE - ELECTRICAL PLAN
53EP100S - BLDG 53 - LEVEL 00S - ELECTRICAL PLAN
53EP100B - BLDG 53 - LEVEL 00B - ELECTRICAL PLAN
53EP101 - BLDG 53 - LEVEL 01 - ELECTRICAL PLAN
53EP102 - BLDG 53 - LEVEL 02 - ELECTRICAL PLAN
53EP103 - BLDG 53 - LEVEL 03 - ELECTRICAL PLAN
53EP104 - BLDG 53 - ROOF - ELECTRICAL PLAN
01EP401a - BLDG 01 - LEVEL 01 - ENLARGED ELECTRICAL PLANS 01EP401b - BLDG 01 - LEVEL 01 - ENLARGED ELECTRICAL PLANS 01EP402a - BLDG 01 - LEVEL 02 - ENLARGED ELECTRICAL PLANS 01EP402b - BLDG 01 - LEVEL 02 - ENLARGED ELECTRICAL PLANS
01EP403 - BLDG 01 - LEVEL 03 - ENLARGED ELECTRICAL PLANS
01EP404 - BLDG 01 - LEVEL 04 - ENLARGED ELECTRICAL PLANS
01EP405 - BLDG 01 - LEVEL 05 - ENLARGED ELECTRICAL PLANS
01EP406 - BLDG 01 - ROOF - ENLARGED ELECTRICAL PLAN
18&11EP401 - BLDG 18&11 - LEVEL 01 - ENLARGED ELECTRICAL PLANS
22EP400B - BLDG 22 - LEVEL 00B - ENLARGED ELECTRICAL PLANS
22EP401 - BLDG 22 - LEVEL 01 - ENLARGED ELECTRICAL PLANS
24EP400B - BLDG 24 - LEVEL 00B - ENLARGED ELECTRICAL PLANS
24EP401 - BLDG 24 - LEVEL 01 - ENLARGED ELECTRICAL PLANS
24EP402 - BLDG 24 - LEVEL 02 - ENLARGED ELECTRICAL PLANS
52EP402 - BLDG 52 - MEZZANINE - ENLARGED ELECTRICAL PLANS
53EP400B - BLDG 53 - LEVEL 00B - ENLARGED ELECTRICAL PLANS
53EP401 - BLDG 53 - LEVEL 01 - ENLARGED ELECTRICAL PLANS
53EP403 - BLDG 53 - LEVEL 03 - ENLARGED ELECTRICAL PLANS
53EP404 - BLDG 53 - LEVEL 04 - ENLARGED ELECTRICAL PLANS
53EP405 - BLDG 53 - LEVEL 05 - ENLARGED ELECTRICAL PLANS
EP501 - ELECTRICAL DETAILS
EP502 - ELECTRICAL DETAILS
EP503 - ELECTRICAL DETAILS
EP504 - ELECTRICAL DETAILS
EP505 - ELECTRICAL DETAILS
EP506 - ELECTRICAL DETAILS
EP507 - ELECTRICAL DETAILS
EG601 - TELECOMMUNICATIONS BONDING RISER DIAGRAM
01EP602 - BLDG 01 - PARTIAL ONE-LINE DIAGRAM - DEMOLITION
01EP611 - BLDG 01 - ONE-LINE DIAGRAM - PART 1 OF 4
01EP612 - BLDG 01 - ONE-LINE DIAGRAM - PART 2 OF 4
01EP613 - BLDG 01 - ONE-LINE DIAGRAM - PART 3 OF 4
01EP614 - BLDG 01 - ONE-LINE DIAGRAM - PART 4 OF 4
18&11EP611 - BLDG 18&11 - ONE-LINE DIAGRAM
22EP611 - BLDG 22 - ONE-LINE DIAGRAM
24EP601 - BLDG 24 - ONE-LINE DIAGRAM - DEMOLITION
24EP611 - BLDG 24 - ONE-LINE DIAGRAM
52EP602 - BLDG 52 - PARTIAL ONE-LINE DIAGRAM - DEMOLITION
52EP611 - BLDG 52 - ONE-LINE DIAGRAM - PART 1 OF 2
52EP612 - BLDG 52 - ONE-LINE DIAGRAM - PART 2 OF 2
53EP601 - BLDG 53 - PARTIAL ONE-LINE DIAGRAM - DEMOLITION
53EP602 - BLDG 53 - PARTIAL ONE-LINE DIAGRAM - DEMOLITION
53EP611 - BLDG 53 - ONE-LINE DIAGRAM - PART 1 OF 6
53EP612 - BLDG 53 - ONE-LINE DIAGRAM - PART 2 OF 6
53EP613 - BLDG 53 - ONE-LINE DIAGRAM - PART 3 OF 6
53EP614 - BLDG 53 - ONE-LINE DIAGRAM - PART 4 OF 6
53EP615 - BLDG 53 - ONE-LINE DIAGRAM - PART 5 OF 6
53EP616 - BLDG 53 - ONE-LINE DIAGRAM - PART 6 OF 6
EP701 - ELECTRICAL SCHEDULES
EP702 - ELECTRICAL SCHEDULES
01EP701 - BLDG 01 - ELECTRICAL SCHEDULES
01EP702 - BLDG 01 - ELECTRICAL SCHEDULES
01EP703 - BLDG 01 - ELECTRICAL SCHEDULES
18&11EP701 - BLDG 18&11 - ELECTRICAL SCHEDULES
22EP701 - BLDG 22 - ELECTRICAL SCHEDULES
24EP701 - BLDG 24 - ELECTRICAL SCHEDULES
24EP702 - BLDG 24 - ELECTRICAL SCHEDULES
52EP701 - BLDG 52 - ELECTRICAL SCHEDULES
53EP701 - BLDG 53 - ELECTRICAL SCHEDULES
53EP702 - BLDG 53 - ELECTRICAL SCHEDULES
1. THESE "GENERAL NOTES" SHALL APPLY TO ALL DRAWINGS WITHIN THIS DRAWING SET.
2. IF THE SPECIFICATIONS OR DRAWINGS CONFLICT WITH EACH OTHER THE MORE STRINGENT CRITERIA/SCOPE OF WORK SHALL BE REQUIRED.
3. BLACKENED OR BOLDED EQUIPMENT INDICATES THE EQUIPMENT SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR. ITEMS NOT DIRECTLY FURNISHED BY THE CONTRACTOR SHALL HAVE A DESIGNATION SUCH AS OFCI (OWNER FURNISHED CONTRACTOR INSTALLED), OFOI (OWNER FURNISHED OWNER INSTALLED), OR NIC (NOT IN CONTRACT. GRAY OR GRAY-SCALED EQUIPMENT SHALL BE ASSUMED TO BE EXISTING OR SHOWN FOR EQUIPMENT LOCATION COORDINATION.
4. EXISTING CIRCUITS ASSOCIATED WITH THE PROJECT AREA OF WORK ARE TO BE DE-ENERGIZED DURING CONSTRUCTION.
5. ALL ELECTRICAL WORK SHALL BE COMPLETED WITH ALL PROXIMATE ELECTRICAL CIRCUITS DE-ENERGIZED (i.e. A NEW BREAKER OR CIRCUIT CANNOT BE ADDED TO A PANEL UNLESS THE PANEL IS COMPLETELY DE-ENERGIZED), OR THE CONTRACTOR MUST COMPLY WITH NFPA 70E FOR WORK ON ENERGIZED SERVICE. THE VA WILL DETERMINE IF THE ELECTRICAL SERVICE CAN BE SHUT DOWN OR IT WILL HAVE TO BE WORKED HOT DEPENDING ON THE CRITICALITY OF THE AREA BEING AFFECTED. IF THE WORK MUST BE DONE WITH THE SERVICE LIVE, THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL REQUIRED PROTECTIVE TOOLS, EQUIPMENT, AND CLOTHING, AND MUST FOLLOW THE JOB SPECIFIC WORK PLAN PREPARED BY THE CONTRACTOR AND APPROVED BY THE VA. WORK THAT REQUIRES SHUTTING DOWN ELECTRICAL SERVICE MAY HAVE TO BE ACCOMPLISHED DURING OTHER THAN NORMAL DUTY HOURS.
6. PROVIDE RACEWAYS AND CONDUCTORS/CABLING FROM LUMINAIRES TO THEIR CORRESPONDING CONTROL DEVICES AS INDICATED ON PLANS.
7. LUMINAIRE INSTALLATIONS AND LAYOUTS SHALL BE COORDINATED WITH ALL OBSTACLES, EQUIPMENT AND ARCHITECTURAL FEATURES.
8. WHERE NOT SPECIFICALLY INDICATED ON DRAWINGS, BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG MINIMUM FOR RUNS EQUAL TO OR LESS THAN 65 FEET AND 10 AWG MINIMUM FOR RUNS GREATER THAN 65 FEET. RACEWAYS AND CONDUCTORS SHALL BE SIZED AND QUANTIFIED TO SERVE AND CONTROL APPLICABLE EQUIPMENT WITH VOLTAGE DROP NO GREATER THAN THREE PERCENT. CONDUCTOR SIZE SHALL BE INCREASED TO COMPENSATE FOR DERATING REQUIRED PER NEC 310.15 WHERE MORE THAN THREE CURRENT CARRYING CONDUCTORS WITHIN ONE RACEWAY; CONDUCTOR AMPACITIES SHALL BE TAKEN FROM THE 75°C
COLUMN. INDIVIDUAL CIRCUITS SHALL NOT SHARE NEUTRAL CONDUCTORS.
9. MINIMUM CONDUIT SIZE SHALL BE 1” FOR EXTERIOR AND UNDERGROUND CONDUIT. MINIMUM CONDUIT SIZE SHALL BE 3/4” FOR INTERIOR CONDUIT. ADDITIONAL CONDUCTORS FOR UNSWITCHED HOT CONDUCTOR TO LUMINAIRES WITH EMERGENCY BATTERY POWERED BACKUP UNITS OR TRANSFER DEVICES SHALL BE PROVIDED. ALL CONDUIT SHALL BE CONCEALED. THE ABOVE COMMENTS SHALL BE ADHERED TO UNLESS OTHERWISE NOTED ON THE DRAWINGS.
10. EMERGENCY LIGHTING OR EQUIPMENT CIRCUITS SHALL BE ROUTED INDEPENDENT FROM OTHER CIRCUIT TYPES; ENSURE NEC 700.10 REQUIREMENTS ARE MET.
11. PROVIDE ALL CONDUIT AND WIRE FOR ALL CIRCUITS INDICATED AND/OR NOTED ON THE DRAWINGS AND/OR SPECIFICATIONS. ALL AUXILIARY OR REQUIRED APPURTENANCES FOR PROVIDED EQUIPMENT SHALL BE PROVIDED WITH ALL CONNECTIONS AS REQUIRED.
12. ALL EQUIPMENT AND DEVICES INCLUDING, BUT NOT LIMITED TO, ELECTRICAL DISTRIBUTION EQUIPMENT, RECEPTACLES, DATA OUTLETS, AND SPECIAL SYSTEM DEVICES, SHALL HAVE THEIR EXACT LOCATION COORDINATED WITH ARCHITECTURAL DRAWINGS AND ALL TRADES PRIOR TO COMMENCING WORK.
13. COORDINATE WITH LIGHTING MANUFACTURER FOR ALL LIGHTING CONTROL EQUIPMENT AND APPURTENANCES; PROVIDE ANY ADDITIONAL SENSORS TO PROVIDE FULL COVERAGE OF THE SPACE AS REQUIRED. ALL CONDUIT, WIRE, POWER SUPPLIES, AND APPURTENANCES REQUIRED FOR THE LIGHTING CONTROL SYSTEM
SHALL BE PROVIDED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
14. ALL EXTERIOR MOUNTED RECEPTACLES AND LUMINAIRE INSTALLATIONS SHALL COORDINATE EXACT LOCATIONS WITH ARCHITECTURAL SHEETS. ADDITIONALLY, WHERE MASONRY IS USED, SMOOTH BLOCK SHALL BE UTILIZED TO PROVIDE A PROPER MOUNTING SURFACE TO ALL EQUIPMENT; RECEPTACLES SHALL BE
INSTALLED FLUSH.
15. ALL CONDUIT/SLEEVE FLOOR AND WALL PENETRATIONS SHALL BE SEALED WITH FIRE RATED ASSEMBLIES, CAULKING, AND APPURTENANCES. ELECTRICAL BOXES
LOCATED IN FIRE RATED WALLS SHALL BE RATED FOR USE IN FIRE RATED WALLS.
16. ALL EQUIPMENT AND INSTALLATION METHODS SHALL BE LISTED AND LABELED PER NEC, UL LISTED, OR REVIEWED EQUAL.
17. FOR ALL EQUIPMENT, COORDINATE WITH ALL TRADES (ARCHITECTURAL, MECHANICAL, PLUMBING, ETC) FOR ELECTRICAL REQUIREMENTS AND INSTALLATION
LOCATIONS PRIOR TO INSTALLATION.
18. ALL LOW-VOLTAGE SYSTEM CABLING NOT RAN IN CONDUIT TO WALL MOUNTED DEVICE SHALL HAVE A MINIMUM 1"C ROUTED FROM DEVICE THROUGH WALL INTO THE ACCESSIBLE CEILING SPACE; CABLING SHALL NOT BE ROUTED IN WALLS OR IN AN INACCESSIBLE LOCATION WITHOUT CONDUIT.
19. GFCI RECEPTACLES SHALL BE PROVIDED WITHIN 6’ OF A SINK/OR WATER SOURCE, WITHIN DAMP ROOMS, OR WHEN MOUNTED OUTDOORS/EXTERIOR TO THE
BUILDING.
20. NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED, OR NOTCHED WITHOUT PRIOR WRITTEN CONSENT FROM THE STRUCTURAL ENGINEER OR ARCHITECT.
21. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.
22. LIGHTING FIXTURES WITH MORE THAN TWO LAMPS SHALL HAVE TWO OUTER LAMPS CONTROLLED WITH ONE SWITCH AND INNER LAMP(S) CONTROLLED BY A
SECOND SWITCH.
23. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC TABLE 250.122. ALL WIRING IS BASED ON Cu COPPER PER NEC TABLE 310.15(B)(16), USING 75°C AMPACITIES
FOR FEEDERS.
24. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN
DEVICES.
25. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES, CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND
REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.
26. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.
27. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.
28. ALL PENETRATIONS SHALL BE PERMITTED, LOGGED, AND INSPECTED BY VA MUSKOGEE HCS FIRE DEPARTMENT PRIOR TO FINAL CLOSURE.
29. NO MC CABLE TO BE USED EXCEPT FOR LIGHTING FIXTURES FACTORY WIRED WITH IT.
30. ALL SURGE PROTECTION DEVICES (SPD) AND DIGITAL POWER METERS (DPM) PROVIDED SHALL BE INTEGRAL TO THE EQUIPMENT IT IS PROTECTING /
MONITORING, UNLESS OTHERWISE NOTED.
31. ALL MODIFIED OR PROVIDED RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT "1". REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
ANY AND ALL FIRE ALARM WORK INCLUDING, BUT NOT LIMITED TO, EQUIPMENT RELOCATION, EXTENDING EXISTING CABLING AND RACEWAYS, AND EQUIPMENT
DEMOLITION SHALL BE PERFORMED BY A LICENSED FIRE ALARM CONTRACTOR.
32.
SECTION
SHEET WHERE SECTION
IS TAKEN FROM
SECTION LETTER
DETAIL NUMBER
SHEET ON WHICH DETAIL APPEARS
DETAIL AREA
XXX CONDUIT & WIRE TAG
(REFER TO CONDUIT AND WIRE SCHEDULE)
XX FAULT CURRENT TAG
(3 PH, SYM AMPS)
KEY NOTE
XXX
FIGURE OR PHOTO
DETAIL NUMBER
IF PHOTO, ARROW DENOTES
DIRECTION TAKEN
SHEET WHERE DETAIL IS TAKEN FROM
DETAIL/PLAN
DETAIL/PLAN NUMBER
XXX
A
XXX
A
XXX
SHEET WHERE SECTION
IS TAKEN FROM
SCALE
SECTION LETTER
1 METERING NOTE
Building No.
Drawing Number
Project Number
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Project Title
ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:
321 4 5 6 7 8 9 10
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE I
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
Floor No.
th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:
05/24/2024100% ISSUED FOR BID
A/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
Department of Veteran Affairs
EPG002
ELECTRICAL LEGENDS
JACK C MONTGOMERY VAMC
05/24/2024 WNM/SJM RTS/BCL
EHRM INFRASTRUCTURE UPGRADES -
JACK C. MONTGOMERY VA MEDICAL
CENTER
623-21-700
1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
Dwg. 2 of 77
D I V 2 6 - L E G E N D
PE
DS
X
X
X
ALL INTERIOR AREAS TO HAVE MANUAL 0N/AUTO OFF LIGHTING
CONTROL WITH THE USE OF DUAL TECHNOLOGY OCCUPANCY SENSORS.
EXCEPT WHERE A WALL SWITCH OCCUPANCY SENSOR IS NOTED.
PHOTO ELECTRIC SENSOR
DAYLIGHT SENSOR FOR DAYLIGHT HARVESTING
CONTROL. SENSOR SHALL BE CEILING MOUNTED.
RECEPTACLE, SINGLE WITH SWITCH
RECEPTACLE, SPECIAL PURPOSE
Z = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.
Y = 208V, 20A, 3 PHASE, 4 POLE, 5W, NEMA L21-20P
X = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.
W = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.
V = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.
U = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.
T = 208V, 20A, 3 PHASE, 3 POLE, 4W, NEMA L21-20R.
S = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.
R = 208V, 30A, 3 PHASE, 4 POLE, 5W, NEMA L21-30R.
Q = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.
RECEPTACLE, SWITCHED DUPLEX
DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,
GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN FLEXIBLE
CORD (CENTER LINE OF OUTLET: 6'-6" [1981mm] AFF. MINIMUM).
ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm]
CENTERS OR AS DESIGNATED ON DRAWINGS), MTD
3'-6" [1067mm] AFF OR AS INDICATED.
SWITCH
F = FUSED SWITCH K = KEY OPERATED
L = LOCK LM= LOW VOLTAGE MASTER
M = MANUAL MOTOR STARTING MC= MOMENTARY CONTACT
MP= MOTOR SNAP WITH PILOT LIGHT P = WITH PILOT LIGHT
(THERMAL TYPE)
PB= PUSH BUTTON STATION RC= REMOTE CONTROL
WP= WEATHER PROOF X = EXPLOSION PROOF
SWITCH (# SUBSCRIPT AS INDICATED BELOW):
BLANK = SINGLE POLE 2 = DOUBLE POLE
3 = THREE-WAY 4 = FOUR-WAY
D = DIMMER K = KEY OPERATED
LV= LOW VOLTAGE P = WITH PILOT LIGHT
LM= LOW VOLTAGE MASTER RC= REMOTE CONTROL
PB= PUSH BUTTON STATION WP= WEATHER PROOF
T = TIMER OPERATED Mo= OCCUPANCY SENSOR
LIGHTING, ONE HEAD EMERGENCY BATTERY POWER
LIGHTING, TWO HEAD EMERGENCY BATTERY POWER
LIGHTING, THREE HEAD EMERGENCY BATTERY POWER
EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL
ARROWS AND FACES AS SHOWN
EXIT SIGN, CEILING MOUNTED WITH
DIRECTIONAL ARROWS AND FACES AS SHOWN
LIGHT FIXTURE, SURFACE MOUNTED, 2'x2';
LETTER INDICATES TYPE.
LIGHT TRACK WITH HEADS AS SHOWN
LIGHT FIXTURE, BOLLARD
LIGHTING
x = LUMINAIRE SWITCH ZONE (ANY LOWER CASE LETTER APPLIES)
E
S
S
OS
J
G E N E R A L S Y M B O L
EMERGENCY NORMAL
G
SWITCH, MULTIPOSITION
SWITCH, SINGLE BREAK
FUSE
NORMALLY CLOSED RELAY CONTACT
NORMALLY OPEN RELAY CONTACT
SWITCH, FUSED
DRAWOUT AIR CIRCUIT BREAKER
MOTOR
TRANSFORMER (PRIMARY OR SECONDARY WIRING,
DELTA OR WYE AS INDICATED)
EARTH GROUND
JUNCTION BOX
PULL BOX
GENERATOR, POWER
BATTERY
CAPACITOR
RELAY; NUMBER INDICATES RELAY TYPE
50 = INSTANTANEOUS OVER CURRENT OR RATE-OF-RISE
51 = AC-TIME OVER CURRENT
67 = AC-DIRECTIONAL OVER CURRENT
86 = LOCKING OUT
DISCONNECT SWITCH, FUSED
DISCONNECT SWITCH, UNFUSED
STARTER, COMBINATION WITH DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
METER
AMMETER
VOLTMETER
WATTMETER
WATT-HOUR METER
TRANSFORMER, PLAN
LADDER CABLE TRAY
ELECTRICAL UNDERGROUND BOX, V = VAULT; HH = HANDHOLE.
PANELBOARD, FLUSH MOUNTED
PANELBOARD, SURFACE MOUNTED
RECEPTACLE, DUPLEX
RECEPTACLE, DUPLEX ON EMERGENCY POWER
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER
RECEPTACLE, QUADRUPLEX
RECEPTACLE, SINGLE
POWER
PB
T
V
CONDUIT OR EQUIPMENT TO BE REMOVED
CONDUIT 3/4"C, 3#12 PHASE, 1#12N, & 1#12 GND UNLESS
SHOWN OTHERWISE. ( EXAMPLE SHOWN: TO PANEL P1,
CIRCUIT 1,3,5). LONG TICK FOR NEUTRAL WIRE; ONE SHORT
TICK FOR EACH PHASE WIRE; GROUND SIZED PER NEC. NOTE
THAT A SECOND SHORT TICK FOR LUMINAIRES IS FOR A
TRAVELER WIRE.
CONDUIT HOME RUN - SEE CONDUIT AND WIRE SCHEDULE
CONDUIT CONCEALED IN WALL, CEILING, UNDER FLOOR, IN
FLOOR SLAB, OR ROUTED UNDERGROUND
CONDUIT CONCEALED WHERE POSSIBLE, OTHERWISE EXPOSED
EXTRA-HARD USAGE FLEXIBLE CORD
FLEXIBLE CONDUIT
CONDUIT TURNED UP OR TOWARD
CONDUIT TURNED DOWN OR AWAY
CONDUIT CAPPED
XXXX
J
M
A
V
W
WH
X X
X X
X X
X X
X X
X X
XX
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X = DENOTES LUMINAIRE TAG NAME
RECESSED DOWNLIGHT FIXTURE
LIGHT FIXTURE, RECESSED, 2'x4'
LIGHT FIXTURE, RECESSED, 1'x4'
LIGHT FIXTURE, RECESSED, 1'x8'
LIGHT FIXTURE, RECESSED, 2'x2'
LIGHT FIXTURE, SURFACE MOUNTED, 2'x4'
LIGHT FIXTURE, SURFACE MOUNTED, 1'x4'
LIGHT FIXTURE, SURFACE MOUNTED, 1'x8'
LIGHT FIXTURE, SURFACE MOUNTED, 2'x2'
STRIP LIGHTING, 4' LONG
LIGHT FIXTURE, WALL MOUNTED
STREET LIGHT WITH BRACKET
LIGHT POLE, ONE LUMINAIRE
LIGHT POLE, TWO LUMINAIRES
LIGHT POLE, POST TOP MOUNT LUMINAIRE
LIGHTING WALL PACK, EXTERIOR BUILDING THESE ARE GENERAL LEGENDS. NOT ALL SYMBOLS MAY BE SHOWN.
REFERENCE PLANS FOR ALL UTILIZED SYSMBOLS.
INSULATED TAP
GROUNDING ROD WITH TEST WELL
LIGHTNING AIR TERMINAL
X = DESCRIPTION
E = EMERGENCY POWER OFF (OFF)
X
BUS DUCT - ONE-LINE DIAGRAM
CIRCUIT BREAKER
HH
DIGITAL POWER METER (ASSUME INTEGRAL TO
DEVICE UNLESS OTHERWISE NOTED)
SURGE PROTECTION DEVICE (ASSUME INTEGRAL TO
DEVICE UNLESS OTHERWISE NOTED)
DPM
SPD
CIRCUITING DESIGNATIONS
WHERE A PANEL NAME AND CORRESPONDING CIRCUIT ARE CALLED OUT ADJACENT TO A RECEPTACLE, LUMINAIRE, OR MISC LOAD, THAT LOAD SHALL BE CIRCUITED TO THE CORRESPONDING PANELBOARD CIRCUIT BREAKER. CONDUIT AND WIRE FOR CIRCUIT SHALL BE 3/4" CONDUIT WITH (2) 12 AWG AND (1) 12 AWG GND, UNLESS OTHERWISE NOTED; IF FURTHER THAN 70', PHASE AND GROUND WIRE SHALL BE UPSIZED TO 10 AWG TO ACCOUNT FOR VOLTAGE DROP.
SEE EXAMPLES BELOW:
RECEPTACLE:
PANELBOARD OR POWER SOURCE NAME = "P1"
CIRCUIT NUMBER OF POWER SOURCE = "2"
LUMINAIRE:
PANELBOARD OR POWER SOURCE NAME = "PP3"
CIRCUIT NUMBER OF POWER SOURCE = "4"
TYP LUMINIARE TAG NAME, REFERENCE LUMINAIRE SCHEDULE = "L1"
LIGHTING CONTROL SWITCH LEG = "a"
ALL LUMINAIRES IN SAME ROOM ARE CIRCUITED TO SAME CIRCUIT = PP3-4
MISC LOAD:
PANELBOARD OR POWER SOURCE NAME = "PP"
CIRCUIT NUMBER OF POWER SOURCE = "7"
P1-2 P1-2
HEAT PUMP
PP-7
L1 a
PP3-4
FACP
PP-7
DIV 28 - LEGENDS
MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC
X-REQUEST-FOR-EXIT
M
T
PUSH BUTTON; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL PUSH D-DURESS P-PANIC R-DOOR RELEASE
X-REQUEST-FOR-EXIT
M
T
CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
M
SECURITY ACCESS, HORN OR SIREN
S…
This is the start of the file's text. The full file is on GovTribe.