These documents are electrical one-line diagram drawings for infrastructure upgrades at the Jack C. Montgomery VA Medical Center in Muskogee, Oklahoma. The drawings detail electrical system modifications for Buildings 01, 18, 22, and 24, including power distribution, panel replacements, circuit breaker modifications, and metering point changes. The technical diagrams show existing electrical infrastructure with proposed upgrades, including transformer connections, main distribution panels, branch circuits, and generator/emergency power systems. The drawings are part of the EHRM (Electrical, HVAC, Roofing, Mechanical) Infrastructure Upgrades project, with detailed specifications for power routing, voltage configurations, and equipment interconnections across multiple campus buildings.

The drawings include comprehensive technical details such as bus amperage ratings, transformer specifications, panel configurations, and circuit breaker assignments. Each building's electrical system is meticulously mapped, showing existing equipment, proposed modifications, and new connection points. The documents emphasize preservation of essential electrical systems during construction, with specific notes about maintaining power to critical equipment and coordinating system shutdowns. The drawings are dated 05/24/2024 and are part of solicitation 36C77624R0046 for the Department of Veterans Affairs, with DAV Energy Solutions and Spees Design Build listed as the consultants and architects/engineers respectively.

View the file

Other files

File Type Posted
36C77625R0046 0009.pdf PDF
Attachment 21 - Tech Questions Tracker - FINAL07162025.pdf PDF
Attachment 21 - Tech Questions Tracker - FINAL_07142025.pdf PDF
36C77625R0046 0008.pdf PDF
Attachment to Tech Questions- ASI-001 Mechanical Ductwork Drawings- 20250714.pdf PDF
36C77625R0046 0007.pdf PDF
Attachment 21 - Tech Questions Tracker - 07082025.pdf PDF
Attachment 21 - Tech Questions Tracker - 07022025.pdf PDF
36C77625R0046 0006.pdf PDF
36C77625R0046 0005.pdf PDF
Attachment 16 Muskogee County Wage Rates_06272025.pdf PDF
Attachment 20 - Spec 01 31 00.01 Project Management and Coordination.pdf PDF
36C77625R0046 0004.pdf PDF
Attachment 21 - Tech Questions Tracker - 20250623 Partial.pdf PDF
36C77625R0046 0003.pdf PDF
Attachment 19 Site Visit Sign In Sheet 62323700.pdf PDF
36C77625R0046 0002.pdf PDF
36C77625R0046 0001.pdf PDF
Attachment 05 Drawings 4 of 13 Muskogee 623-21-700.pdf PDF
Attachment 17- Limitations on Subcontracting - Muskogee EHRM.pdf PDF
Attachment 08 Drawings 7 of 13 Muskogee 623-21-700.pdf PDF
Attachment 01 - 623-21-700 - Muskogee - Updated Combined Specifications-20250501.pdf PDF
Attachment 03 Drawings 2 of 13 Muskogee 623-21-700.pdf PDF
36C77625R0046_1.pdf PDF
Attachment 04 Drawings 3 of 13 Muskogee 623-21-700.pdf PDF
Attachment 18 Site Map.pdf PDF
Attachment 02 Drawings 1 of 13 Muskogee 623-21-700.pdf PDF
Attachment 16 Muskogee County Wage Rates.pdf PDF
Attachment 07 Drawings 6 of 13 Muskogee 623-21-700.pdf PDF
Attachment 12 Drawings 11 of 13 Muskogee 623-21-700.pdf PDF
Attachment 14 Drawings 13 of 13 Muskogee 623-21-700.pdf PDF
Attachment 10 Drawings 9 of 13 Muskogee 623-21-700.pdf PDF
Attachment 13 Drawings 12 of 13 Muskogee 623-21-700.pdf PDF
Attachment 11 Drawings 10 of 13 Muskogee 623-21-700.pdf PDF
Attachment 09 Drawings 8 of 13 Muskogee 623-21-700.pdf PDF
Attachment 15- PCRA for EHRM 623-700.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T

O N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T

O N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

LEG 1 LEG 2 LEG 1 LEG 2 LEG 1 LEG 2

AGROUPA

B

BGROUP AGROUP BGROUP AGROUP BGROUP

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T O

N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T O

N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T O

N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T O

N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

JJ

RACK/ENCLOSURE

RACK-MOUNT

UPS

RACK-MOUNT

UPS

RACKED

EQUIPMENT

RACKED

EQUIPMENT

RACKED

EQUIPMENT

PDU

B

PDU

A

PDU

B

PDU

A

PDU

BPSA PSB PSA PSB PSA PSB

LEG A LEG B

ZONE PDU

SOURCE A

JUNCTION

BOX

SOURCE B

JUNCTION

BOX

60A 3-PHASE ZONE PDU

BASE UNIT - REQUIRES

TWO 60A 3-PHASE (WYE)

CIRCUITS HARD-WIRED

IN JUNCTION BOX

RACKED-MOUNTED 5 KW, 208V

UNINTERRUPTIBLE POWER SUPPLY

(UPS) WITH NEMA 20A L21-20P

INPUT AND L21-20R OUTPUT

RACK-MOUNT

UPS

RACK/ENCLOSURE RACK/ENCLOSURE

SOURCE A

REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT,

TERMINATING IN A HARD-WIRED JUNCTION BOX.

SOURCE B

REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT,

TERMINATING IN A HARD-WIRED JUNCTION BOX.

REFERENCE

TN DRAWINGS

FOR RACK

MOUNTED

NETWORK

EQUIPMENT

REFERENCE

TN DRAWINGS

FOR RACK

MOUNTED

NETWORK

EQUIPMENT

REFERENCE

TN DRAWINGS

FOR RACK

MOUNTED

NETWORK

EQUIPMENT

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T O

N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T O

N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

PDU

A

REFERENCE

TN DRAWINGS

FOR RACK

MOUNTED

NETWORK

EQUIPMENT

L21-20P SIDE B

REQUIRES A 208V, 20A,

THREE-PHASE CIRCUIT,

TERMINATING IN A NEMA

L21-20R LOCKING

RECEPTACLE.

L21-20P SIDE A

REQUIRES A 208V, 20A, THREE-PHASE

CIRCUIT, TERMINATING IN A NEMA

L21-20R LOCKING RECEPTACLE.

RACK/ENCLOSURE

RACK-MOUNT

UPS

RACKED

EQUIPMENT

PSA PSB

PDU

A

PDU

B

SOURCE A 20A

RECEPTACLE

SOURCE B 20A

RECEPTACLE

EP502

TYP.

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T O

N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T O

N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

LEG 1 LEG 2 LEG 1 LEG 2 LEG 1 LEG 2

AGROUPA

B

BGROUP AGROUP BGROUP AGROUP BGROUP

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T O

N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T O

N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T

O N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T

O N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

JJ

RACK/ENCLOSURE

RACK-MOUNT

UPS

RACK-MOUNT

UPS

RACKED

EQUIPMENT

RACKED

EQUIPMENT

RACKED

EQUIPMENT

PDU

B

PDU

A

PDU

B

PDU

A

PDU

BPSA PSB PSA PSB PSA PSB

LEG A LEG B

ZONE PDU

60A 3-PHASE ZONE PDU BASE UNIT -

REQUIRES TWO 60A 3-PHASE (WYE)

CIRCUITS HARD-WIRED IN JUNCTION BOX;

OPTIONALLY, UPSs MAY BE POWERED

DIRECTLY WITH L21-20 OUTLETS

RACKED-MOUNTED 5 KW, 208V

UNINTERRUPTIBLE POWER SUPPLY

(UPS) WITH NEMA 20A L21-20P

INPUT AND L21-20R OUTPUT

RACK/ENCLOSURE RACK/ENCLOSURE

REFERENCE

TN DRAWINGS

FOR RACK

MOUNTED

NETWORK

EQUIPMENT

REFERENCE

TN DRAWINGS

FOR RACK

MOUNTED

NETWORK

EQUIPMENT

REFERENCE

TN DRAWINGS

FOR RACK

MOUNTED

NETWORK

EQUIPMENT

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T O

N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

CB1

CB1

CB2

CB2

CB3

CB3

In lO lO lO

O ut

T em p /H u m id it y

O K

W a rn in g

C ri ti c a l

R e se t

C H

A T

S W

O R

T H

P R

O D

U C

T O

N l

O F

F O

N l

O F

F O

N l

O F

F

CB3

CB3

CB2

CB2

PDU

A

REFERENCE

TN DRAWINGS

FOR RACK

MOUNTED

NETWORK

EQUIPMENT

RACK/ENCLOSURE

RACK-MOUNT

UPS

RACKED

EQUIPMENT

PSA PSB

PDU

A

PDU

B

RACK-MOUNT

UPS

RACK-MOUNT

UPS

RACK-MOUNT

UPS

RACK-MOUNT

UPS

RACK-MOUNT

UPS

SOURCE A

JUNCTION

BOX

SOURCE A

REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT,

TERMINATING IN A HARD-WIRED JUNCTION BOX.

SOURCE B

REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT,

TERMINATING IN A HARD-WIRED JUNCTION BOX.

L21-20P SIDE B

REQUIRES A 208V, 20A,

THREE-PHASE CIRCUIT,

TERMINATING IN A NEMA

L21-20R LOCKING

RECEPTACLE.

L21-20P SIDE A

REQUIRES A 208V, 20A, THREE-PHASE

CIRCUIT, TERMINATING IN A NEMA

L21-20R LOCKING RECEPTACLE.

EP502

TYP.

SOURCE B

JUNCTION

BOX

SOURCE A 20A

RECEPTACLE

SOURCE B 20A

RECEPTACLE

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:

05/24/2024100% ISSUED FOR BID

A/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

Department of Veteran Affairs

EP503

ELECTRICAL DETAILS

JACK C MONTGOMERY VAMC

05/24/2024 WNM/SJM RTS/BCL

EHRM INFRASTRUCTURE UPGRADES -

JACK C. MONTGOMERY VA MEDICAL

CENTER

623-21-700

1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

Dwg. 40 of 77

- NTS

1 POWER ELEVATION AND SCHEMATIC FOR A FOUR RACK TR

EP501

NTS

POWER ELEVATION AND SCHEMATIC FOR A FOUR RACK ENTRANCE ROOM

01EP401a

52EP402

Load

Blue

Occupancy sensor switch

Black Black

White Bare

Ground

GENERAL NOTES:

1. MAINTAIN A MINIMUM CLEARANCE OF 305mm (12") ON ALL SIDES OF ROOF PENETRATION FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER

FLASHING.

2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.

3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.

4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO ENSURE PROPER METHODS & MATERIALS ARE USED TO MAINTAIN ROOF WARRANTY.

9.52mm (3/8")

MIN GALVANIZED

THREADED ROD,

TYP.

CONDUIT CLAMP.

SIZE AS REQUIRED

LOCKING SQUARE

WASHER &

LOCKNUT

STEEL

EXPANSION

ANCHOR

INTEGRAL GALVANIZED

LIPPED STEEL MOUNTING

CHANNEL

PREFABRICATED RUBBER BOOT

CAP WITH GRADUATED STEPS &

WEATHER-PROOF PRESSURE SEAL

TO COLLAR

SEALANT AT PENETRATION

TO MEMBRANE JUNCTURE

BY ROOFING CONTRACTOR

MULTIPLE MEMBRANE STRIPPING PLIES

FEATHERED AT FIELD OF ROOF BY

ROOFING CONTRACTOR. PRIME FLANGE

BEFORE STRIPPING.

PREFABRICATED FORMED 1.52mm

(0.06") THICK ALUMINUM FLASHING

ROUND COLLAR WITH MIN. 76mm (3")

WIDE FLANGE. ATTACH TO ROOF PER

MANUFACTURER'S INSTRUCTIONS

CONDUIT CLAMP.

SIZE AS REQUIRED

BATT INSULATION

ROOF MEMBRANE

WATER CUT-OFF MASTIC

COMPATIBLE WITH ROOF

MEMBRANE

STAINLESS

CLAMP, TYP.

SEAL-OFF

FITTING, TYP.

CONCRETE DECKING

STEEL EXPANSION

ANCHOR

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

CONDUIT,

TYP.

FIELD OF VIEW

FOR DETAIL

FINISHED SURFACE

(OR ROOF)

PROVIDE RMC OR

LTFMC AS

REQUIRED TO

CONNECT TO

LOAD

ALL FASTENING

HARDWARE SHALL

BE STAINLESS

STEEL, TYP.

GENERAL DETAIL NOTES:

1. ALL CHANNEL STRUT, POST BASES AND ACCESSORIES SHALL BE HOT-

DIPPED GALVANIZED, UNLESS SPECIFICALLY NOTED OTHERWISE.

2. THIS IS A GENERAL DETAIL INDICATING GENERAL LAYOUT

REQUIREMENTS. CONTRACTOR SHALL SIZE RACK ACCORDINGLY TO

MOUNT ALL REQUIRED EQUIPMENT AS SHOWN ON PLANS; ADDITIONAL

HORIZONTAL AND/OR VERTICAL STRUCTURAL MEMBERS MAY BE

REQUIRED.

ID PLACARD, PROVIDE PER SPECIFICATIONS.

ALL FASTENING

HARDWARE SHALL

BE STAINLESS

STEEL, TYP.

CHANNEL STRUT, 1-5/8" X 1-5/8", LENGTH AS

REQUIRED, TYP.

MYERS HUB, TYP

48" MIN.

ROOF MOUNTED DISCONNECT

FINISHED GROUND/

EARTH

PROVIDE RMC OR

LTFMC AS

REQUIRED TO

CONNECT TO

LOAD

ANCHOR BOLTS,

1/4"-DIA x 12" L (MIN.), STAINLESS STEEL

ID PLACARD, PROVIDE PER SPECIFICATIONS.

ALL FASTENING

HARDWARE SHALL

BE STAINLESS

STEEL, TYP.

CHANNEL STRUT, 1-5/8" X 1-5/8", LENGTH

AS REQUIRED, TYP.

MYERS HUB, TYP

48" MIN.

GROUND MOUNTED DISCONNECT

CONCRETE FOOTING WITH

CHAMFERED EDGE,

3000-PSI,12"-DIA x 30" L (MIN)

DETAIL NOTES:

PROVIDE CONDUIT AND WIRE FOR A SIDE TR POWER

ALONG EXISTING CONDUIT PATHWAY BETWEEN BUILDING

18 AND BUILDING 50; WEATHERPROOF AND SEAL

PENETRATIONS ON EXTERIOR BUILDING WALLS.

REFERENCE CONDUIT AND WIRE SCHEDULE SHEET

18EP701 FOR ADDITIONAL INFORMATION.

PROVIDE HOT-DIPPED GALVANIZED UNISTRUT CONDUIT

SUPPORT WITH STAINLESS STEEL FASTENING

HARDWARE AS REQUIRED.

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:

05/24/2024100% ISSUED FOR BID

A/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

Department of Veteran Affairs

EP504

ELECTRICAL DETAILS

JACK C MONTGOMERY VAMC

05/24/2024 WNM/SJM RTS/BCL

EHRM INFRASTRUCTURE UPGRADES -

JACK C. MONTGOMERY VA MEDICAL

CENTER

623-21-700

1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

Dwg. 41 of 77

- NTS

1 CONDUIT ROOF PENETRATION DETAIL

- 1 1/2" = 1'-0"

2 TYPICAL UNISTRUT RACK MOUNTED DISCONNECT SWITCH

- NTS

4 NOT USED

NTS

BUILDING 18 AND 50 CONDUIT ROUTE PHOTO DETAIL

18EP100B

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR (TEBC) 6 AWG

IRREVERSIBLE CRIMP

CONNECTOR, TYP.

CABLE TRAY BONDING

CONDUCTOR. TYPICAL AT

EACH SECTION

CONNECTION POINT

TO PRIMARY OR SECONDARY

BONDING BUSBAR

IRREVERSIBBLE

COMPRESSION

CONNECTION

RACK BONDING

CONDUCTOR

(6 AWG)

TEBC

(TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR - 4 AWG)

RACK BONDING CONDUCTOR (6 AWG)

UNIT BONDING CONDUCTOR (6 AWG)

TOP-MOUNTED

RACK BONDING

BUSBAR

IRREVERSIBLE CRIMP

CONNECTOR, TYP.

GROUND TO PRIMARY

BONDING BUSBAR.

COORDINATE WITH VA

FOR EXACT

CONDUCTOR ROUTING

TWO-HOLE COMPRESSION LUGS (RACKS SHALL NOT

BE MODIFIED IF ONLY ONE-HOLE IS PROVIDED; USE

ONE-HOLE COMPRESSION LUGS IN THIS CASE)

TWO-HOLE

COMPRESSION LUGS (RACKS

SHALL NOT BE MODIFIED IF

ONLY ONE-HOLE IS PROVIDED;

USE ONE-HOLE COMPRESSION

LUGS IN THIS CASE)

RACK ISOLATION PADS

CHATSWORTH PRODUCTS

#40158-012, OR APPROVED

EQUAL

MOUNTING BRACKETS

1/4" THICK

L= 12"

D

INSULATOR

TELECOMMUNICATIONS

SECONDARY BONDING BUSBAR

ALL CONNECTIONS TO

BUSBAR SHALL BE (2) BOLT

MECHANICAL LUGS, TYP.

BONDING CONDUCTOR TO

BUILDING STEEL, #3/0 AWG GREEN

INSULATION W/YELLOW TRACER

BONDING CONDUCTOR TO

RACEWAYS, CONDUITS, WIREWAYS,

CABLE TRAYS, #6 AWG GREEN

INSULATION W/ YELLOW TRACER

BONDING CONDUCTOR TO

PANELBOARD(S) AND BUSBAR(S) IN

ROOM PRESENT, #6 AWG GREEN

INSULATION W/ YELLOW TRACER

BONDING CONDUCTOR FROM

TELECOMMUNICATIONS

SECONDARY BONDING BUSBAR

TO TELECOMMUNICATIONS

BONDING BACKBONE (IF NOT

PRESENT, BOND TO PRIMARY

SERVICE ENTRY MAIN

BUSBAR), #3/0 AWG GREEN

INSULATION W/YELLOW

TRACER

TELECOMMUNICATIONS BONDING BACKBONE CONDUCTOR.

PROVIDE WITH GREEN INSULATION AND YELLOW TRACER,

SIZE PER TIA/ANSI STANDARDS AS REQUIRED. WHERE

EXISTING, EXTEND AND REROUTE BACKBONE TO AND

FROM RELOCATED/EXPANDED TELECOMMUNICATIONS

ROOMS. IF NEW, PROVIDE AS REQUIRED.

IRREVERSIBLE

CRIMP CONNECTOR,

UL LISTED

PROVIDE BOND TO ELECTRO-STATIC

DISCHARGE FLOORING. BONDING

CONDUCTOR SHALL BE 12 AWG MIN'

PROVIDE AND INSTALL PER

MANUFACTURER'S INSTRUCTIONS.

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:

05/24/2024100% ISSUED FOR BID

A/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

Department of Veteran Affairs

EP505

ELECTRICAL DETAILS

JACK C MONTGOMERY VAMC

05/24/2024 WNM/SJM RTS/BCL

EHRM INFRASTRUCTURE UPGRADES -

JACK C. MONTGOMERY VA MEDICAL

CENTER

623-21-700

1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

Dwg. 42 of 77

- NTS

2 CABLE TRAY GROUNDING/BONDING REQUIREMENTS

- NTS

1 TELECOMMUNICATION RACK BONDING DETAIL

- NTS

4 NOT USED

- NTS

5 TELECOMMUNICATIONS BONDING BUSBAR

- NTS

3 SECONDARY BONDING BUSBAR BONDING DETAIL

TRANSFORMER

VIBRATION INSULATOR

SUPERSTRUT B1202,

UNISTRUT P1068, OR EQUAL

SUPERSTRUT AB-201-1,

UNISTRUT P1068 OR EQUAL

SIDEFRONT

45° SUPERSTRUT AB-239-3,

UNISTRUT P2458-24

OR EQUAL

M

IN

TRANSFORMER

FLEXIBLE METAL

CONDUIT

RIGID METAL

CONDUIT

TRANSFORMER

3" MIN.

6"

GROUND MOUNTED TRANSFORMER NOT

SHOWN FOR CLARITY OF SUSPENDED

TRANSFORMER MOUNTING

FINISHED

GRADE

CEILING

DETAIL NOTE(S):

1. TYPICAL DETAIL SHALL BE USED FOR CONSTRUCTABILITY

REFERENCE. EXACT DIMENSIONS, MOUNTING SUPPORTS, AND

FASTENING HARDWARE MAY DIFFER FROM FIELD INSTALLATION.

2. ALL CONDUIT NOT SHOWN FOR CLARITY.

JUNCTION BOX, 8" x 8" x 4"

MINIMUM

TO SECURE LOCAL

ACCESS CONTROL

PANEL, 1-1/2" CONDUIT

3/4" CONDUIT

ELECTRIC STRIKE / MORTISE LOCK

PER SYSTEM REQUIREMENTS,

PROVIDE BACKBOX AS REQUIRED

BY MANUFACTURER

DUAL AUTHENTICATION CARD

READER AND KEYPAD, 42" AFF,

HID pivCLASS #RK40 OR

EQUIVALENT, PROVIDE

BACKBOX AS REQUIRED BY

MANUFACTURER

SUSPENDED CEILING

FLOOR

SIREN WIRING, 3/4" CONDUIT

REQUEST-TO-EXIT

WIRING, 3/4" CONDUIT

DOOR POSITION

SWITCH AND MAGNET

REQUEST-TO-EXIT

PIR MOTION SENSOR

REQUEST-TO-EXIT,

PUSH BUTTON

SIREN

DETAILS NOTES:

1. DETAIL IS SHOWN FOR GENERAL

DIAGRAMMATICAL PURPOSES. PROVIDE

ALL REQUIRED EQUIPMENT AND

HARDWARE FOR ALL DOOR TYPES

(SINGLE DOOR, DOUBLE DOOR, ETC.) AS

REQUIRED.

2. CONTRACTOR TO FURNISH AND INSTALL

ALL SECURITY AND PACS HARDWARE AS

REQUIRED PER PHYSICAL SECURITY AND

RESILIENCY DESIGN MANUAL AND

ASSOCIATED APPENDICES. COORDINATE

WITH ARCHITECT AND DOOR

MANUFACTURER TO PROVIDE A

COMPLETE AND FULLY FUNCTIONAL

ELECTRIFIED AND SECURED DOOR.

POWER, 3/4" CONDUIT

42"

WIRING TABLE

PIGTAIL-

WIRE COLOR

TERM STRIP -

CONNECTION

CIRCUIT

FUNCTION

YELLOW

ORANGE

BLACK

RED

DRAIN

BROWN

BLUE

GRAY

PINK

GREEN

WHITE

VIOLET

TAN

RED/GREEN

P1-1

P1-2

P1-3

P1-4

P1-5

P1-6

P1-7

P2-1

P2-2

P2-3

P2-4

P2-5

P2-6

P2-7

NO CONNECT

NO CONNECT

RTN

+VDC

NO CONNECT

NO CONNECT

NO CONNECT

RS485 / TXA

RS485 / TXB

NO CONNECT

NO CONNECT

NO CONNECT

RS485 / RXB

RS485 / RXA

PIV ENABLED TWO-FACTOR AUTHENTICATION KEY PAD

AND CONTACTLESS AUTHENTICATION, HID pivCLASS

#RK40 OR EQUIVALENT

BEEP

GRN

RTN

+VDC

SHLD

RED

HOLD

GP101

GP102

OC/TMPR

DATA1

DATA0

GP103

GP104

CEILING

FLOOR LINE

BONDING BUSBAR

DETAIL NOTES:

1.THESE TYPICAL MOUNTING HEIGHTS

SHALL BE USED UNLESS OTHERWISE

NOTED ON THE PLANS.

ELECTRICAL

DISTRIBUTION

EQUIPMENT

OCCUPANCY SENSOR

KEYPAD/CARD ACCESS

LIGHT SWITCH/WALL STATION

EPO/HVAC SHUTDOWN SWITCH

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:

05/24/2024100% ISSUED FOR BID

A/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

Department of Veteran Affairs

EP506

ELECTRICAL DETAILS

JACK C MONTGOMERY VAMC

05/24/2024 WNM/SJM RTS/BCL

EHRM INFRASTRUCTURE UPGRADES -

JACK C. MONTGOMERY VA MEDICAL

CENTER

623-21-700

1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

Dwg. 43 of 77

- NTS

3 TYPICAL TRANSFORMER STACKING MOUNTING DETAIL

- 3/4" = 1'-0"

2 SECURITY DOOR CARD READER INSTALLATION DETAIL

- NTS

4 TYPICAL CONTACTLESS AUTHENTICATION AND PINPAD DEVICE DETAIL

1 TYPICAL MOUNTING HEIGHT DETAIL

TYPICAL

DATA

RACK

FIN. FLOOR

HORIZONTAL CAT6A

DISTRIBUTION AND

FIBER-OPTIC BACKBONE

CABLE TRAY, TYPICAL.

BOTTOM OF FLOOR OR ROOF ABOVE

LIGHT FIXTURE: REFERENCE TR ROOM

LUMINAIRE MOUNTING SCHEDULE. LIGHT

MOUNTING LOCATION IS DIAGRAMMATIC;

CONTRACTOR SHALL COORDINATE EXACT

MOUNTING HEIGHT AND PLACEMENT WITH ALL

OBSTRUCTIONS INCLUDING CABLE TRAY, RACKS

AND ARCHITECTURAL FEATURES.

84"

6" MIN

F L O

O R

T O

U N

D E

R S

ID

E

S T

R U

C T

U R

E

TERMINATION

PLUG

CAT OS CAT

OCCUPANCY

SENSOR

(QTY AS

NEEDED)

a,b

POWER

PACK

A-SIDE

SWITCHING

(QTY AS

NEEDED)

A-SIDE

LIGHTING

LOAD

(QTY AS

NEEDED)

POWER& 0-10V

CONTROL

CAT 6

POWER

PACK

B-SIDE

SWITCHING

(QTY AS

NEEDED)

B-SIDE

LIGHTING

LOAD

(QTY AS

NEEDED)

POWER& 0-10V

CONTROL

CAT 6

PROGRAMMING

INTERFACE

MODULE

CAT

WALL STATION

(QTY AS

NEEDED)

CAT

TERMINATION

PLUG

DETAIL NOTE(S):

1. REFERENCE PLANS FOR FIELD DEVICE QUANTITIES. PROVIDE CONTROL

CABLING AND WIRING AS REQUIRED.

2. PROVIDE A COMPLETE AND FULLY FUNCTIONAL LIGHTING SYSTEM.

120-277V 120-277V

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:

05/24/2024100% ISSUED FOR BID

A/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

Department of Veteran Affairs

EP507

ELECTRICAL DETAILS

JACK C MONTGOMERY VAMC

05/24/2024 WNM/SJM RTS/BCL

EHRM INFRASTRUCTURE UPGRADES -

JACK C. MONTGOMERY VA MEDICAL

CENTER

623-21-700

1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

Dwg. 44 of 77

BARE

BLACK

BLUE

WHITE WIRE WITH

GREEN SLEEVE

BLUE

BLACKBLACK

BARE

OCCUPANCY

SENSOR SWITCH

LOAD

WHITE

GROUND

HOT/LIVE

120 V~ 50/60 Hz

NEUTRAL

WHEN USING CONTROLS IN

SINGLE LOCATION

INSTALLATIONS, TIGHTEN

THE BLUE TERMINAL OR CAP

BLUE WIRE. DO NOT

CONNECT THE BLUE

TERMINAL/WIRE TO ANY

OTHER WIRE OR TO

GROUND.

- NTS

1 TYPICAL WALL SWITCH OCCUPANCY SENSOR

- 3/4" = 1'-0"

2 TYPICAL TELECOMMUNICATIONS ROOM ELEVATION

NTS

TYPICAL CEILING MOUNTED SENSOR LIGHTING WIRING DIAGRAM

52EP402

- NTS

4 TYPICAL RECESSED LIGHTING INSTALLATION

5 NOT USED

PBB

101-1

TYP.

TYP.

C100M1A-1

2C50B-1 240-1

302-1

403-1

5A04-1

BUILDING 1

106-11

BUILDING 18&11

PBB

B07A-22

BUILDING 22

TYP.

104A-22

PBB

B4B-24

BUILDING 24

112-24

205-24 201B-52

PBB

BB-100C

BUILDING 53

1B-119B

5A-109

BUILDING 52

LEVEL 00B

LEVEL 02

LEVEL 03

LEVEL 04

LEVEL 05

3B-100

4A-109

TYP.

ASG/FSG

TYP.

TYP.

18DPB SUBSTATION #7

LEVEL 01

PBBPBB

RM 1B26-1

RM B07-18

RM SB02-22 24-MDPMSB22 RM B6-24 RM 101F-52 RM 101-53SUBSTATION #1

TYP.

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:

05/24/2024100% ISSUED FOR BID

A/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

Department of Veteran Affairs

EG601

TELECOMMUNICATIONS BONDING RISER

DIAGRAM

JACK C MONTGOMERY VAMC

05/24/2024 WNM/SJM RTS/BCL

EHRM INFRASTRUCTURE UPGRADES -

JACK C. MONTGOMERY VA MEDICAL

CENTER

623-21-700

1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

Dwg. 45 of 77

- NTS

1 TELECOMMUNICATION BONDING RISER DIAGRAM

KEY NOTES (FOR THIS SHEET ONLY)

GENERAL NOTES (FOR THIS SHEET ONLY)

1. ALL BONDING CONDUCTORS, INCLUDING TBB, SHALL FOLLOW SIZING REQUIREMENTS

SPECIFIED IN ANSI/TIA-607-D.

2. CONTRACTOR SHALL PROVIDE ALL REQUIRED BONDING, CONDUCTORS, AND

PATHWAYS AS REQUIRED. PROVIDE ALL PATCHING, REPAIR AND FIREPROOFING FOR

REMOVAL OF ALL EXISTING EQUIPMENT AND CONDUCTORS AS REQUIRED.

3. ALL BONDING CONDUCTORS SHALL BE COPPER AND BE INSULATED UNLESS

OTHERWISE NOTED.

PROVIDE PRIMARY BONDING BUSBAR (PBB). WHERE EXISTING PBB EXISTS,

CONTRACTOR SHALL REPLACE AND RETERMINATE ALL EXISTING CONNECTIONS;

CONTRACTOR TO FIELD VERIFY EXISTING LOCATION. PROVIDE ALL BONDING

CONNECTIONS AS REQUIRED.

PROVIDE TELECOMMUNICATIONS BONDING BACKBONE (TBB) CONDUCTOR AS

INDICATED. CONTRACTOR SHALL ROUTE AND PROVIDE ALL PATHWAYS FOR TBB AS

REQUIRED. EXISTING TBB SHALL BE DEMOLISHED AND REMOVED; PROVIDE ALL

PATCHING, REPAIR AND FIREPROOF SEALING AS REQUIRED.

PROVIDE IRREVERSIBLE CRIMP CONNECTOR, UL LISTED.

TELECOMMUNICATIONS ROOM. REFER TO ENLARGED FLOOR PLANS FOR ADDITIONAL

INFORMATION.

PROVIDE TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR (TEBC) TO

CONNECT TBB TO SBB. MINIMUM SIZE SHALL BE 6 AWG.

PROVIDE SECONDARY BONDING BUSBAR (SBB). PROVIDE TELECOMMUNICATIONS

EQUIPMENT BONDING CONDUCTOR (TEBC) TO BOND SBB TO THE FOLLOWING

EQUIPMENT: DATA RACK, CABLE TRAY, CONDUITS, ELECTRICAL PANEL, ETC.

REFERENCE SHEET EP505 FOR ADDITIONAL BONDING INFORMATION.

PROVIDE TELECOMMUNICATIONS BONDING CONDUCTOR (TBC) TO BOND TO BUILDING

ELECTRICAL SERVICE EQUIPMENT GROUNDING BUSBAR. MINIMUM CONDUCTOR SIZE

SHALL BE 3 AWG.

PROVIDE TELECOM BONDING BACKBONE INTERCONNECTION BONDING CONDUCTOR

TO BOND SECONDARY BONDING BUSBARS (SBBs) TOGETHER AS SHOWN.

TO MEDIUM

VOLTAGE

EQUIPMENT

OUTDOORS

NEAR BLDG. 1

T-A

300KVA

12.5K/208Y /120V

#4 #7

600A

LSI

600A

LSI

200A

LSI

600A

LSI

100%

LSI

LSI

PANEL G1A

208/120V

1000A BUS

1B27-1

ATS-EQ1

600A

4-POLE

IB27-1IB27-1

ATS-C1

600A

4-POLE

100A

PANEL

FC-2

PANEL

FC-1

PANEL

ASG-2

(EYE CLINIC)

201-1

1B27-1 1B2C6B-2

200A200A200A200A200A150A200A

P1 P2

ELEVATORS

1-26

PANEL

26LP

PANEL

46LS1

PANEL

ABPHB

601-1

441-1

PANEL

AB3E

343-1

PANEL

AB2E

EMA

SHORT

STAY

PANEL

ABGE

225 200

337A-11B27-1

S E

C T

IO

N

557-1

PANEL

AB4E

435-1

PANEL

WOMEN'S

CLINIC

201-1

PANEL

AB1E

337A-1

EMA-2

SHORT

STAY

1-26

PANEL

ABGE-1

100A225A225A100A225A225A100A100A225A

600A BUS

PANEL ABEDP 1B27-1

SPARE

2C54-1

PANEL

EC2A2

(LAB)

PANEL

CMLA

(LAB)

3C01-1

PANEL

ECG

1C145-1

PANEL

EC1A

1C155-1

PANEL

E1B

(PHARMACY)

1C155-1

PANEL

E1A

(CLINIC)

1C155-1

PANEL

C1E

2C59A-11

225A125A225A50A225A125A225A125A225A 225A225A200A

SPARESPARESPARE

100150

PANEL

EM

1C56-1

P3

C-WING

ELEVAT

OR

PANEL

C1EN

2CC59A-1

PANEL

E2A

(LAB)

1C155-1

PANEL

E2B

(RADIOLO

GY)

1C155-1

A 2P

PANEL

B1-A-AE

2PC43-1

PANEL

EC2A

(LAB)

2C54-1

601-1

600A 600A BUS

PANEL CEDP 1C10B-1

PANEL ABEQ

208/120V

3PH, 4W

600A BUS

TO ATS-24

1000A

LSI

100%

ASG

208/120V

3PH, 4W

1B27-1

PANEL

ABPHE

40 40

SPARE

SPARE

400A

250A

SPACE

(X14)

SPARE

(FORMERLY

ATS-ELEV)

1200A 300A 1000A

PANEL G46A

G

PORTABLE

GENERATOR OR

LOAD BANK

G G

BUILDING 46

GEN 46A

350kW / 438kVA 208/120V

GEN 46B

340kW / 438kVA 208/120V

SPACE

(X11)

TO FSG

1B27-1

TO T-UPS TO 22E TO CE22 TO EWL24

3P SPACE

(X5)

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:

05/24/2024100% ISSUED FOR BID

A/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

Department of Veteran Affairs

01EP602

BLDG 01 - PARTIAL ONE-LINE DIAGRAM -

DEMOLITION

JACK C MONTGOMERY VAMC

05/24/2024 WNM/SJM RTS/BCL

EHRM INFRASTRUCTURE UPGRADES -

JACK C. MONTGOMERY VA MEDICAL

CENTER

623-21-700

-01

1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

Dwg. 46 of 77

KEY NOTES

GENERAL NOTES

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES

FOUND SHALL BE REPORTED TO THE ENGINEER.

2. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH VA PRIOR TO PERFORMING REQUIRED EQUIPMENT

UPGRADES. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY

POWER PLANS, AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL

PRIOR TO COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30

DAYS PRIOR TO IMPLEMENTATION. POWER TO ALL EXISTING ESSENTIAL EQUIPMENT

CANNOT BE INTERRUPTED AND SHALL REMAIN ACTIVE DURING CONSTRUCTION;

BACKUP POWER AND TIE-IN SHALL CONFORM WITH VA STANDARDS.

3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.

- NTS

1 BLDG 01 - PARTIAL ONE-LINE DIAGRAM - DEMOLITION

(1) EXISTING SPACE TO BE USED TO FEED ADDED LOAD. REFERENCE ONE-LINE

DIAGRAM SHEET 01EP612 FOR ADDITIONAL INFORMATION.

EXISTING CIRCUIT BREAKER, CONDUIT, AND WIRE TO BE DEMOLISHED AND

REPLACED. REFERENCE REVISED ONE-LINE DIAGRAM SHEET 01EP612 FOR

ADDITIONAL INFORMATION.

EQUIPMENT

OUTDOORS

NEAR BLDG. 1

T-F

300KVA

12.5K/208Y /120V

#4 #7

PANEL

CGS

1CS6-1

1000A

LSI 100%

800A

LSI

FSG

208/120V 1000A / 3P

1B27-1

800A

LSI

800A40225225225225225225125225150A

FDP

1827-1

PANEL

AB1A

PANEL

AB1B

50/2

1C10B-1

PANEL

CMDP

S E

C T

IO

N

S E

C T

IO

N

PANEL

CGA-1

1C145-1

PANEL

C1N-B

(NOT IN

USE)

2CC59-1

PANEL

C1C

2CC54A-1

2PC43-1

PANEL

BIA

PANEL

C1SA

2PC43-1

PANEL

C1N-A

2CC59-1

PANEL

C1N-C

2CC59-1

PANEL

C1S

2PC43-1

100 100

2CC45A-1

PANEL

C1

PANEL

NPA

(SHORT STAY)

337A-A

PANEL

ABGB

1B27-1

PANEL

FC4

402-1

PANEL

ABGA

1B27-1

150 150

150 150

PANEL

AB2A

343-1

PANEL

AB2B

343-1

DUPLEX PUMPS

IN C-WING

CRAWL SPACE

OUT OF SERVICE

100 100

PANEL

AB3B

441-1441-1

PANEL

AB3A

SPARE SPARE SPARE SPARE

PANEL

B1

(CHAPEL)

1834-1

J

PANEL

AB4A

557-1

PANEL

AB4B

557-1

3P SPACE

(X9)

01-C100M1A-1B 208/120V

125A/3P, 4W4

01-2C50B-1B 208/120V

125A/3P, 4W

01-240-1B 208/120V

125A/3P, 4W

01-302-1B 208/120V

125A/3P, 4W

01-403-1B 208/120V

125A/3P, 4W

2 2 2 2

400A 3P

LSI

125A 3P

400A/3P

LSI

01-DP-TRB

208/120V 400A/3P, 4W

TO ASG

SHEET 01EP612

NO TIE

125A 3P

125A 3P

125A 3P

125A 3P

125A 3P

40A/3P 20A/3P

01-5A04-1B 208/120V

125A/3P, 4W

01-P-0301-P-02 01-P-06 01-P-0701-P-0501-P-04

01-P-01

DPM

SPD

DPM

SPD

DPM

SPD

DPM

SPD

DPM

SPD

DPM

SPD

DPMSPD

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:

05/24/2024100% ISSUED FOR BID

A/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

Department of Veteran Affairs

01EP611

BLDG 01 - ONE-LINE DIAGRAM - PART 1 OF 4

JACK C MONTGOMERY VAMC

05/24/2024 WNM/SJM RTS/BCL

EHRM INFRASTRUCTURE UPGRADES -

JACK C. MONTGOMERY VA MEDICAL

CENTER

623-21-700

-01

1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

Dwg. 47 of 77

KEY NOTES

GENERAL NOTES

PROVIDE OCPD, CONDUIT AND WIRE AS SHOWN.

REFER TO PANEL SCHEDULES ON 01EP701 AND 01EP702 FOR ADDITIONAL

INFORMATION.

- NTS

1 BLDG 01 - ONE-LINE DIAGRAM - PART 1 OF 4

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES

FOUND SHALL BE REPORTED TO THE ENGINEER.

2. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH VA PRIOR TO PERFORMING REQUIRED EQUIPMENT

UPGRADES. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS. TEMPORARY

POWER PLANS, AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND

APPROVAL PRIOR TO COMMENCING WORK. POWER TO ALL EXISTING ESSENTIAL

EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN ACTIVE DURING

CONSTRUCTION: BACKUP POWER AND TIE-IN SHALL CONFORM WITH VA STANDARDS.

3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.

METERING NOTES

01 METERING POINT: REFERENCE ''METERING AND LOAD INFORMATION SCHEDULE

ON SHEET EP702 FOR ADDITIONAL INFORMATION.

01-C100M1A-1B 208/120V

125A/3P, 4W4

01-2C50B-1B 208/120V

125A/3P, 4W

01-240-1B 208/120V

125A/3P, 4W

01-302-1B 208/120V

125A/3P, 4W

01-403-1B 208/120V

125A/3P, 4W

2 2 2 2

LSI

125A 3P

400A/3P

LSI

01-DP-TRB

208/120V 400A/3P, 4W

TO ASG

SHEET 01EP612

125A 3P

125A 3P

125A 3P

125A 3P

125A 3P

40A/3P 20A/3P

01-5A04-1B 208/120V

125A/3P, 4W

01-P-0301-P-02 01-P-06 01-P-0701-P-0501-P-04

01-P-01

DPM

SPD

DPM

SPD

DPM

SPD

DPM

SPD

DPM

SPD

DPM

SPD

DPMSPD

01-C100M1A-1B 208/120V

125A/3P, 4W4

01-2C50B-1B 208/120V

125A/3P, 4W

01-P-03

DPM

SPD

DPM

SPD

01-JB-05

01-JB-06

01-P-03A

01-P-03B

01-P-03C

01-JB-03

01-JB-04

01-P-02A

01-P-02B

01-P-02C

PROVIDE JUNCTION BOX AND INSULATED TAPS AS REQUIRED FOR CONDUIT

AND WIRE TRANSITION. SIZE JUNCTION BOX PER NEC. CONTRACTOR SHALL

FIELD COORDINATE JUNCTION BOX INSTALLATION LOCATION AS REQUIRED.

TYP.01-JB-01

01-P-01A

01-P-01B

01-P-01C

01-JB-02

EQUIPMENT

TO T-UPS,

SEE

22EP611

TO 22E,

SEE

22EP611

TO CE22,

SEE

22EP611

TO EWL24,

SEE

24EP611

OUTDOORS

NEAR BLDG. 1

T-A

300KVA

12.5K/208Y /120V

#4 #7

600A

LSI

600A

LSI

200A

LSI

200A

LSI

600A

LSI

100%

LSI

LSI

ATS-EQ1

600A

4-POLE

IB27-1IB27-1

ATS-C1

600A

4-POLE

100A

PANEL

FC-2

PANEL

FC-1

PANEL

ASG-2

(EYE CLINIC)

201-1

1B27-1 1B2C6B-2

200A200A200A200A200A150A200A

1-26

PANEL

26LP

PANEL

46LS1

PANEL

ABPHB

601-1

441-1

PANEL

AB3E

343-1

PANEL

AB2E

EMA

SHORT

STAY

PANEL

ABGE

225 200

337A-11B27-1

S E

C T

IO

N

557-1

PANEL

AB4E

435-1

PANEL

WOMEN'S

CLINIC

201-1

PANEL

AB1E

337A-1

EMA-2

SHORT

STAY

1-26

PANEL

ABGE-1

100A225A225A100A225A225A100A100A225A

600A BUS

PANEL ABEDP 1B27-1

SPARE

2C54-1

PANEL

EC2A2

(LAB)

PANEL

CMLA

(LAB)

3C01-1

PANEL

ECG

1C145-1

PANEL

EC1A

1C155-1

PANEL

E1B

(PHARMACY)

1C155-1

PANEL

E1A

(CLINIC)

1C155-1

PANEL

C1E

2C59A-11

225A125A225A50A225A125A225A125A225A 225A225A200A

SPARESPARESPARE

100150

PANEL

EM

1C56-1

P3

C-WING

ELEVAT

OR

PANEL

C1EN

2CC59A-1

PANEL

E2A

(LAB)

1C155-1

PANEL

E2B

(RADIOLO

GY)

1C155-1

A 2P

PANEL

B1-A-AE

2PC43-1

PANEL

EC2A

(LAB)

2C54-1

601-1

600A 600A BUS

PANEL CEDP 1C10B-1

1B27-1

TO ATS-24

(SEE 24EP611)

SPARE

(FORMERLY

ATS-ELEV)

1200A 400A 1000A

PANEL G46A

G

PORTABLE

GENERATOR OR

LOAD BANK

1000A

LSI

100%

1B27-1

PANEL

ABPHE

G G

SPARE

400A

250A

PANEL G1A

208/120V

1000A BUS

1B27-1

BUILDING 46

GEN 46A

350kW / 438kVA 208/120V

GEN 46B

350kW / 438kVA 208/120V

SPACE

(X14)

SPACE

X11

TO FSG,

SHEET 01EP611

ASG

208/120V

3PH, 4W

PANEL ABEQ

208/120V

3PH, 4W

600A BUS

TO 22-DP-TRA,

SEE 22EP611

200A 3P

P1 P2

ELEVATORS

40 40

3P SPACE

(X4)

22-P-01

24-P-05B

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:

05/24/2024100% ISSUED FOR BID

A/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

Department of Veteran Affairs

01EP612

BLDG 01 - ONE-LINE DIAGRAM - PART 2 OF 4

JACK C MONTGOMERY VAMC

05/24/2024 WNM/SJM RTS/BCL

EHRM INFRASTRUCTURE UPGRADES -

JACK C. MONTGOMERY VA MEDICAL

CENTER

623-21-700

-01

1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

Dwg. 48 of 77

KEY NOTES

GENERAL NOTES

- NTS

1 BLDG 01 - ONE-LINE DIAGRAM - PART 2 OF 4

PROVIDE OCPD, CONDUIT AND WIRE AS SHOWN.1

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES

FOUND SHALL BE REPORTED TO THE ENGINEER.

2. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH VA PRIOR TO PERFORMING REQUIRED EQUIPMENT

UPGRADES. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY

POWER PLANS, AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL

PRIOR TO COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30

DAYS PRIOR TO IMPLEMENTATION. POWER TO ALL EXISTING ESSENTIAL EQUIPMENT

CANNOT BE INTERRUPTED AND SHALL REMAIN ACTIVE DURING CONSTRUCTION;

BACKUP POWER AND TIE-IN SHALL CONFORM WITH VA STANDARDS.

3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.

METERING NOTES

01 METERING POINT: REFERENCE ''METERING AND LOAD INFORMATION SCHEDULE ON

SHEET EP702 FOR ADDITIONAL INFORMATION.

METERING POINT: REFERENCE ''METERING AND LOAD INFORMATION SCHEDULE ON

SHEET EP702 FOR ADDITIONAL INFORMATION.

22-P-01A

TO MEDIUM VOLATGE

EQUIPMENT

#7

#5

KVA

"BI"

OUTDOOR NEAR

BUILDING 1

1200AF

1200AT

LSIG

2000AF

2000AT

LSIG

CTB

CTB

1200A RISE

BUS DUCT

1200A

400250

40050/2

9030/2

(X5) 4C01-1

PANEL

4HA

TO

IPU-N1

THRU N5

(SURGERY

ROOMS)

T-H1

15KVA

480/240/ 120V

T-LS4A

30KVA

480/240Y/ 120V

100AS

ATS-LS4

70 A

3-POLE

4C01-1

ATS-EQ4

400 A

3-POLE

4C01-1

ATS-C4

400 A

3-POLE

4C01-1

4C01-1

PANEL

G4HA

TO EDP

SHEET 53EP611

TO SWITCHBOARD "I"

SHEET 01EP614

T-4A

112.5KVA

480/208Y/

120V

100225

225 225

4C01-1

PANEL

4LA

4C01-1

PANEL

4LB

300D-1

PANEL

3LA

300E1G-1

PANEL

3LB

4C02-1

PANEL

MC1

4C01-1

PANEL

H1A

3661-1

PANEL

LS3LA

4C01-1

PANEL

LS3LB

4C01-1

PANEL

LS4LA

4C01A-1

PANEL H1

PANEL

EQ4HA

TEQ4A

30KVA

480/208Y/ 120V

VFD VFD

SAF RAF

AHU-OR

P5 P6 P7

CHILLED WATER

BOOSTER PUMPS

300D-1

PANEL

EQ3LA

300E1G-1

PANEL

EQ3LB

4C01-1

PANEL

EQ4LA

VFD VFD VFD

HWP

-1

HWP

-2

AHU-2A

MICRO

LABS

HOT

WATER

PUMPS

CONTROL

PANEL

WAGD

VACUUM

PUMPS

CONTROL

PANEL

MEDICAL

AIR

COMPRESSOR

CONTROL

PANEL

MEDICAL

VACUUM

PUMPS

MCC-1N

50 35 20

400A BUS

CM4000T

AHU-AB EF-1

30/2250

(X5)4C01-1

PANEL

C4HA TO

IPU-C1

THRU N5

(SURGERY

OR ROOMS)

T-CH4

112.5KVA

480/208Y/ 120V

ST

OR #5

DISCONNECT

"A"

4C01-1

PANEL

C4LA

336D13-1

PANEL

C3LC

300E16-1

PANEL

C3LB

336-1

PANEL

C3LA

TO ATS-EQ1A

SHEET 01EP614

LSI

1E09-1

PANEL

EQ1HA

DW 1

ELEVATOR

CART LIFT

70 100

30 20

3C01-1

PANEL

EAV

CONTROL

PANEL

MEDICAL

VACUUM

CONTROL

PANEL

MEDICAL

AIR

T-ELA

9KVA

480/208Y /120

3C01-1

PANEL

ELA

601B1A-1

PANEL

EQ6HC

A/C

601B1A-1

T-EQ6C

15KVA

480/208Y /120V

601B1A-1

PANEL

EQ6LC

A/C S

A/C N

601B1A-1

P6 S2 S3

ELEVATORS

NORTH

CAT

SCAN

1E-10-1

PANEL

PDPA

XLESP

15KVA

480/208Y /120

1E02A-1

PANEL

HESP

1E02A-1

PANEL

LESP

TO ATS-LS1A

SHEET 01EP614

1E09-1

PANEL

LS1HA

T-LS1A

15KVA

480/208Y/ 120V

1E09-1

PANEL

LS1LA

P6 S2 S3

ELEVATORS

P6, S2, S3

30/1

1C144-1

FIRE

PANEL

LS1LB

60 AS

T-EA

45KVA

480/208Y/ 120V

2C25A-1

PANEL EX

7.5 7.5

5 5

7.5

40 4050

7.5 7.53 3

5553 3

201020

MSG SRG

480/277V

1200A BUS

MSG I

480/277V

2000A BUS

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:

05/24/2024100% ISSUED FOR BID

A/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

Department of Veteran Affairs

01EP613

BLDG 01 - ONE-LINE DIAGRAM - PART 3 OF 4

JACK C MONTGOMERY VAMC

05/24/2024 WNM/SJM RTS/BCL

EHRM INFRASTRUCTURE UPGRADES -

JACK C. MONTGOMERY VA MEDICAL

CENTER

623-21-700

-01

1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

Dwg. 49 of 77

- NTS

1 BLDG 01 - ONE-LINE DIAGRAM - PART 3 OF 4

KEY NOTES

GENERAL NOTES

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES

FOUND SHALL BE REPORTED TO THE ENGINEER.

2. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH VA PRIOR TO PERFORMING REQUIRED EQUIPMENT

UPGRADES. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY

POWER PLANS, AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL

PRIOR TO COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30

DAYS PRIOR TO IMPLEMENTATION. POWER TO ALL EXISTING ESSENTIAL EQUIPMENT

CANNOT BE INTERRUPTED AND SHALL REMAIN ACTIVE DURING CONSTRUCTION;

BACKUP POWER AND TIE-IN SHALL CONFORM WITH VA STANDARDS.

3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.

METERING NOTES

01 METERING POINT: REFERENCE ''METERING AND LOAD INFORMATION SCHEDULE ON

SHEET EP702 FOR ADDITIONAL INFORMATION.

ATS-EQ1A

600A

3-POLE

J J J J

J

SWITCHBOARD "I"

480/277V 2000A/3P

1E-10-1

600AF

600AT

LSIG

600AF

600AT

LSIG

600AF

600AT

LSIG

600AF

600AT

LSIG

800AF

400AT

LSIG

800AF

400AT

LSIG

600AF

400AT

LSIG

400AF

400AT

LSIG

600AF

400AT

LSIG

800AF

400AT

LSIG

800AF

400AT

LSIG

800AF

800AT

LSIG

SPARE SPARE SPARE

PDP 1E-10-1

400A BUS

125 125 12570 50 50 50 50 40 60

TR4

30KVA

480/208Y /120

TR5

30KVA

480/208Y /120

TR8

30KVA

480/208Y /120

TR9

30KVA

480/208Y /120

30KVA

480/208Y /120

TR6

75KVA

480/208Y /120

TR7

75KVA

480/208Y /120

P5

ELEVATOR

1C45-1

PANEL

LP1A

SP1C04A-1

PANEL

LP1B

1E-10-1

PANEL

LP1D

1EC1A-1

PANEL

LP1D

1C04A-1

PANEL

LP1F

125 125 125 125 125 225

SP254-1

PANEL

LP2A

2C54-1

PANEL

LP2A2

L P

A

100100

100100

2C24

PANEL

LP2C

100/2

100 100 100

2C06-1

PANEL

A24

2C04-1

PANEL

A25

2C13-1

PANEL

A27

2C11-12C241

2C09

PANEL

A23

PANEL

LP2C2

PANEL

A26

1E09-1

ATS-LS1A

225A

3-POLE

1E09-1

ATS-S1A

600A

3-POLE

1E09-1

ATS-C1A

400A

3-POLE

1E09-1

125 125 125 125 125 200 125 175

2C04-1

RF

ROOM 1

2C06-1

RF

ROOM 2

2C09-1

RF

ROOM 3

2C13-1

RF

ROOM 5

2C38-1

SOUTH

CT

ROOM DISCONNECTS

PANEL XD 2C24-1

400A

MCC-2 3C01-1

600A BUS

15KVA

EF2

(CLINIC)

AHU-

2B1

(NUC

MED)

1P2

1EF5A

1RF6

1SF61RF3BACKUP

PUMP

1SF3 AHU71RF4

1SF4

1RF2

1SF2

STEAM

PUMO

(OUT OF

SERVICE)

AIR

COMP

IPI

WATER

HEATER

EF-1

EF-3

SPARE SPARE

HRU5

(ROOF)

MC2

J J

TO PANEL EQ1HA,

SHEET 01EP613

TO PANEL LS1HA,

SHEET 01EP613

PANEL

S1HA

1E09-1

1E09-1

PANEL

C1HA

60AS

TR10

30KVA

480/208Y/ 120V

PANEL

EHCSF

1E-10-1

PANEL

E1C

2C22-1

PANEL

C2HA

125 125

PANEL

S2HA

2C22-1

TREC1

5KVA

480/240/

T-EPAC

45KVA

480/208Y/

NOT IN

USE

R&F

ROOM 45KVA

T-S2A

75KVA

480/208Y/ 120V

90125

2C19-1 1E-10-1

PANEL

EPAC

(PACS

SERVER)

PANEL

EC1

(NOT IN

USE)

2C22-1

PANEL

S2LA

125A/3P

01-C100M1A-1A 208/120V 125A/3P, 4W

3 3

01-2C50B-1A 208/120V 125A/3P, 4W

01-403-1A 208/120V 125A/3P, 4W

01-5A04-1A 208/120V 125A/3P, 4W

01-DP-TRA

480/277V

400A, 3 PH, 4W

TO MSG I

SHEET 01EP613

LSI

SPARE

(X6)

SPACE

(X9)

LSI

LSI

1E09-1

TO GSBHA,

SHEET 53EP611

600A/3P/LSI

125A/3P 125A/3P 125A/3P

01-P-1501-P-1401-P-10 01-P-11

01-P-09

01-XMFR-TRA

200KVA

Pri: 480V Sec: 208V/120V

20A/3P 20A/3P

SPARE

01-P-08

DPMSPD

DPM

SPD

DPM

SPD

DPM

SPD

DPM

SPD

400A 3P

LSI

SPARE

PANEL

G1HA

125A/3P 125A/3P

01-240-1A 208/120V 125A/3P, 4W

01-P-12

DPM

SPD

01-302-1A 208/120V 125A/3P, 4W

01-P-13

DPM

SPD

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:

05/24/2024100% ISSUED FOR BID

A/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

Department of Veteran Affairs

01EP614

BLDG 01 - ONE-LINE DIAGRAM - PART 4 OF 4

JACK C MONTGOMERY VAMC

05/24/2024 WNM/SJM RTS/BCL

EHRM INFRASTRUCTURE UPGRADES -

JACK C. MONTGOMERY VA MEDICAL

CENTER

623-21-700

-01

1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

Dwg. 50 of 77

KEY NOTES

GENERAL NOTES

- NTS

1 BLDG 01 - ONE-LINE DIAGRAM - PART 4 OF 4

EXISTING SPARE 400/3P CIRCUIT BREAKER TO BE REPLACED AS INDICATED TO

SERVE ADDED LOAD.

PROVIDE TAP ADJUSTMENTS AS REQUIRED FOR VOLTAGE DROP.

REFER TO PANEL SCHEDULES FOR ADDITIONAL INFORMATION.

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES

FOUND SHALL BE REPORTED TO THE ENGINEER.

2. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH VA PRIOR TO PERFORMING REQUIRED EQUIPMENT

UPGRADES. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS. TEMPORARY

POWER PLANS, AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND

APPROVAL PRIOR TO COMMENCING WORK. POWER TO ALL EXISTING ESSENTIAL

EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN ACTIVE DURING

CONSTRUCTION: BACKUP POWER AND TIE-IN SHALL CONFORM WITH VA STANDARDS.

3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.

METERING NOTES

01 METERING POINT: REFERENCE ''METERING AND LOAD INFORMATION SCHEDULE

ON SHEET EP702 FOR ADDITIONAL INFORMATION.

01-XMFR-TRA

200KVA

Pri: 480V Sec: 208V/120V

DISC-01-XFMR-TRA

400A, 3P

01-P-08

125A/3P

01-C100M1A-1A 208/120V 125A/3P, 4W

3 3

01-2C50B-1A 208/120V 125A/3P, 4W

01-403-1A 208/120V 125A/3P, 4W

01-5A04-1A 208/120V 125A/3P, 4W

01-DP-TRA

480/277V

400A, 3 PH, 4W

600A/3P/LSI

125A/3P 125A/3P 125A/3P

01-P-1501-P-1401-P-10 01-P-11

01-P-09

Pri: 480V Sec: 208V/120V

20A/3P 20A/3P

DPMSPD

DPM

SPD

DPM

SPD

DPM

SPD

DPM

SPD

125A/3P 125A/3P

01-240-1A 208/120V 125A/3P, 4W

01-P-12

DPM

SPD

01-302-1A 208/120V 125A/3P, 4W

01-P-13

DPM

SPD

TYP.

PROVIDE JUNCTION BOX AND INSULATED TAPS AS REQUIRED FOR CONDUIT

AND WIRE TRANSITION. SIZE JUNCTION BOX PER NEC. CONTRACTOR SHALL

FIELD COORDINATE JUNCTION BOX INSTALLATION LOCATION AS REQUIRED.

3 3

DPM

SPD

DPM

SPD

01-C100M1A-1A 208/120V 125A/3P, 4W

3 3

01-2C50B-1A 208/120V 125A/3P, 4W

DPM

SPD

DPM

SPD

01-JB-09

01-JB-10

01-P-10A

01-P-10B

01-P-10C

01-JB-11

01-JB-12

01-P-11A

01-P-11B

01-P-11C

01-JB-07

01-JB-08

01-P-09A

01-P-09B

01-P-09C600A

VFD VFD VFD

TO MEDIUM

VOLTAGE

EQUIPMENT

T-E

300KVA

12.5K/208Y/ 120V

18MDP-SEC.1

208/120V 3P , 4W

18DBP

1200A

800A 125A/ 3P

125A 400A/3P

200A 200A 200A 200A 200A 200A 200A 200A 200A

200 200 200 200 200 200 200 200 200

225 100 100

60A 60A 60A 90A 90A 90A 50A 50A 50A

600A

225A 225A 225A

18EQSB

SEC 1

18EQSB

SEC 1

01-50

B07-18

SB01-18 SB01-18

BOILER

FEED

PUMP #1

BOILER

FEED

PUMP #2

BOILER

FEED

PUMP #3

BOILER

FAN

PUMP #1

BOILER

FAN

PUMP #2

BOILER

FAN

PUMP #3

BOILER

COMPR

#1

BOILER

COMPR

#2

BOILER

COMPR

#3

SB01-18 SB01-18 SB01-18

PANEL

18EQSBB

PANEL

18EQSBC

PANEL

18EQSBD

SB01-18

PANEL

18EQSBA

B07-18

PANEL

18ELSB

SB07-18

PANEL

18ELSSB

B07-18

PANEL

18-1

B08-18

PANEL

18-2

(MACHINE

SHOP)

B04-18

PANEL

18-3

(PLUMBING

SHOP)

B01-18

PANEL

18-4

(CARPENTER

SHOP)

02-18

PANEL

18-5

(ENG

PROJECTS)

08-18

PANEL

18-6

(ENG

C.R.)

12-18

PANEL

18-7

(E-SHOP

STORAGE)

13B1-18

PANEL

18-8

(ELECTRICAL

E-SHOP

CLOSET)

107-11

PANEL

18-9

(M&O

SUPERVISOR

OFFICE)

#4

PANEL 18EGDP

208/120V

1200A BUS

GENERATOR 18

225 kW / 312.5 kVA 208Y/120V

ATS-18LS

225A

3-POLE

01-50

ATS-18EQ

800A

3-POLE

01-50

01-50

PANEL

18N

01-50

PANEL 18ELSDP

208/120V

225A BUS, 3P 4W

400600

PANEL 49-1

01-49

G

10 10 10 10 10 10

SPARE

60A, 3P

800A/ 3P

100A/3P

LSI

SPARE

(X2)

800A 225A

SPARESPARE

125A/ 3P

SPARE

UNKNOWN

SPARE (X2)

SPARE

SPARE

SPARE (X2)

UNKNOWN

11-106-11B 208/120V 100A/3P, 4W

18MDP-SEC. 2

208/120V 3P , 4W

11-P-01

B07-18

PANEL

18EQB

01-50

PANEL 18EQDP

208/120V

3PH, 4W

3P SPACE

(X1)

11-106-11A 208/120V 100A/3P, 4W

11-P-02

100A/3P

SPARE

40A, 3P

DPM

SPD

DPM

SPD

400A/ 3P

SPARE

(X1)

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:

05/24/2024100% ISSUED FOR BID

A/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

Department of Veteran Affairs

18&11EP611

BLDG 18 - ONE-LINE DIAGRAM

JACK C MONTGOMERY VAMC

05/24/2024 WNM/SJM RTS/BCL

EHRM INFRASTRUCTURE UPGRADES -

JACK C. MONTGOMERY VA MEDICAL

CENTER

623-21-700

-18

1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

Dwg. 51 of 77

KEY NOTES

GENERAL NOTES

- NTS

1 BLDG 18 - ONE-LINE DIAGRAM

UTILIZE EXISTING 3P SPACE TO PROVIDE CIRCUIT BREAKER IN EXISTING POWER

DISTRIBUTION EQUIPMENT TO SUPPLY LOAD AS INDICATED.

REFER TO PANEL SCHEDULES ON 18EP701 FOR ADDITIONAL INFORMATION.

CONDUIT ROUTED THROUGH PULLBOX AND JUNCTION BOXES. REFERENCE SHEET

18EP100B FOR ADDITIONAL INFORMATION.

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES

FOUND SHALL BE REPORTED TO THE ENGINEER.

2. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH VA PRIOR TO PERFORMING REQUIRED EQUIPMENT

UPGRADES. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS. TEMPORARY

POWER PLANS, AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND

APPROVAL PRIOR TO COMMENCING WORK. POWER TO ALL EXISTING ESSENTIAL

EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN ACTIVE DURING

CONSTRUCTION: BACKUP POWER AND TIE-IN SHALL CONFORM WITH VA STANDARDS.

3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.

METERING NOTES

01 METERING POINT: REFERENCE ''METERING AND LOAD INFORMATION SCHEDULE ON

SHEET EP702 FOR ADDITIONAL INFORMATION.

PROVIDE JUNCTION BOX AND INSULATED TAPS AS REQUIRED FOR CONDUIT

AND WIRE TRANSITION. SIZE JUNCTION BOX PER NEC. CONTRACTOR SHALL

FIELD COORDINATE JUNCTION BOX INSTALLATION LOCATION AS REQUIRED.

TO ABEQ,

SEE 01EP612

TO ABEQ,

SEE 01EP612

TO ABEQ,

SEE 01EP612

106-22

PANEL

CE-22

LIBERT

PDX UNITS

B15-22

PANEL

22E

ELEVATOR

200AS

150AF

SB01-22PARALLELLING

CABINET

225110

UPS

EXT.

BATT.

SB01-22

BIB

SB02-22

PANEL

P1

SB02-22

PANEL

P2

T-UPS

45KVA

208/208Y/

SB02-22

PANEL

22BW

100A

BC1-22

22CB-1

200A

B09-22

PANEL

22AC-1

225A 150A

B15-22

PANEL

22BE

100A

205C-22

PANEL

P

100A

205C-22

PANEL

L

BC1-22

22CB-2

104-22

PANEL

22LIB

225200 125

100A 100A

MSB22

208/120V 400A

SB02-22

22 AHU-BAHU

AUDITORIUM

RT-CU

600AS

15E

T-C

150KVA

12.5K/208Y/ 120V

TO MEDIUM

VOLTAGE

EQUIPMENT

#4

ADMIN, OIT,

LOGISTICS STAFF

PANEL

T-59

T-59

3P SPACE

(X3)

200A/3P

22-B07A-22A 208/120V 100A/3P, 4W

22-104A-22A 208/120V 100A/3P, 4W

100A/3P 100A/3P

200A/3P

LSI

22-DP-TRA

208/120V 200A/3P, 4W

22-B07A-22B 208/120V 100A/3P, 4W

22-104A-22B 208/120V 100A/3P, 4W

100A/3P 100A/3P

200A/3P

LSI

22-DP-TRB

208/120V 200A/3P, 4W

20A/3P 20A/3P

20A/3P 20A/3P

22-P-05

22-P-06

22-P-04

22-P-02

22-P-03

22-P-01

TO ABEQ,

SEE 01EP612

400A 3P

60A 70A

RT-CU

150A70A

UNKNOWN

LOAD

SPD DPM

SPD

DPM

SPD

DPM

SPD DPM

SPD

DPM

SPD

DPM

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:

05/24/2024100% ISSUED FOR BID

A/E:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

Department of Veteran Affairs

22EP611

BLDG 22 - ONE-LINE DIAGRAM

JACK C MONTGOMERY VAMC

05/24/2024 WNM/SJM RTS/BCL

EHRM INFRASTRUCTURE UPGRADES -

JACK C. MONTGOMERY VA MEDICAL

CENTER

623-21-700

-22

1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401

Dwg. 52 of 77

KEY NOTES

GENERAL NOTES

- NTS

1 BLDG 22 - ONE-LINE DIAGRAM

UTILIZE EXISTING 3P SPACE TO PROVIDE CIRCUIT BREAKER IN EXISTING POWER

DISTRIBUTION EQUIPMENT TO SUPPLY LOAD AS INDICATED.

REFER TO PANEL SCHEDULES ON 22EP701 FOR ADDITIONAL INFORMATION.

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES

FOUND SHALL BE REPORTED TO THE ENGINEER.

2. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM

SHUTDOWNS AND PHASING WITH VA PRIOR TO PERFORMING REQUIRED EQUIPMENT

UPGRADES. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS. TEMPORARY

POWER PLANS, AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND

APPROVAL PRIOR TO COMMENCING WORK. POWER TO ALL EXISTING ESSENTIAL

EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN ACTIVE DURING

CONSTRUCTION: BACKUP POWER AND TIE-IN SHALL CONFORM WITH VA STANDARDS.

3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.

METERING NOTES

01 METERING POINT: REFERENCE ''METERING AND LOAD INFORMATION SCHEDULE

ON SHEET EP702 FOR ADDITIONAL INFORMATION.

TYP.

22-JB-01

22-JB-02

22-P-01A

22-P-01B

22-P-01C

PROVIDE JUNCTION BOX AND INSULATED TAPS AS REQUIRED FOR CONDUIT

AND WIRE TRANSITION. SIZE JUNCTION BOX PER NEC. CONTRACTOR SHALL

FIELD COORDINATE JUNCTION BOX INSTALLATION LOCATION AS REQUIRED.

24MDP, 208/120V

800A BUS, 3PH 4W

Isc 18346A 3P

B06-24

MCC-24

800A BUS

B06-24

300A

2C22-24

PANEL

24-2AR

2C22-24

PANEL

24-2AL

B06-24

PANEL

24-BAC

2C22-24

PANEL

24BL

2C22-24

PANEL

24BR

109-24

PANEL

24-1A

109-24

PANEL

24-1B

100-24

PANEL

24K-1

100-24

PANEL

24K-2

BC09-24

PANEL

24BB

SBC10-24

PANEL

24-SBA

300A 200A 225A 100A175A

ELEVATOR

175A 225A 200A

KITCHEN

EQUIP

800 800

800A

#5 #7

600AS

T-D

500KVA

12.5K/208Y/ 120V

24AHU-1N 24AHU-1S 24RF-1S 24AHU2

RETURN

109-24

PANEL

E24-1C

CONTROL

AIR

COMP

TO G46A

100-24

PANEL

24KE1

2C22-24

PANEL

24-2E

(KITCHEN)

B01-24

PANEL

EWL24

SBC10-24

PANEL

24SBE

SBC10-24

PANEL

24SBE2

B06-24

PANEL 24BE

208/120V

400A BUS

3PH 4W

Isc 14645 A 3P

TO ABEQ

TO MEDIUM

VOLTAGE

EQUIPMENT

200AS

200AF

CANTEEN

24AHU-2

(DIETETICS)

B06-22

ATS-24

400A

3-POLE

SPARE

24P-1 24P-2

PUMPS

SPARE

FOR EWH24 FED

FROM ECHCP

RE: 1/E-2

70A 3P

3P SPACE

(2X)

SPARE

(X2)

100225

SPARES

(2X)

UNKNOWN

400AF

400AT

100A

SPARE

(X2)

100A

24BB

200A

SPARE

(1), (4) 350kcmil

(1), (4) 350kcmil

Building No.

Drawing Number

Project Number

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Project Title

ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:

321 4 5 6 7 8 9 10

DAV ENERGY SOLUTIONS

2207 GARNET AVE, SUITE I

SAN DIEGO, CA 92109

619-770-8552

WWW.DAVENERGY.COM

Floor No.

th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .