Attachment 08 Drawings 7 of 13 Muskogee 623-21-700.pdf
PDF 18 MB Posted
- Solicitation number
- 36C77624R0046
About this file
These electrical schedule drawings detail the electrical infrastructure upgrades for the Jack C. Montgomery VA Medical Center in Muskogee, Oklahoma, as part of the EHRM Infrastructure Upgrades project (Contract No. 623-21-700). The drawings, specifically Drawing Numbers 01EP701, 01EP702, and 01EP703, provide comprehensive electrical panel schedules for multiple buildings (Buildings 1, 11, and 18), including detailed circuit configurations, power distribution, and load calculations for various branch panels.
The electrical schedules include specifications for multiple branch panels across different rooms, such as C100M1A-1, 2C50B-1, 240-1, 302-1, 430-1, and 5A04-1, with voltage ratings of 120/208 Wye and bus ratings ranging from 100A to 125A. Each panel schedule details circuit breaker ratings, VA load per phase, connected load types (including server rack receptacles, cooling units, access control systems, and lighting), and provisions for digital power meters and surge protection devices. The drawings also include a conduit and wire schedule specifying conductor sizes, routing, and voltage drop percentages, emphasizing the comprehensive electrical system design for the VA medical center renovation project.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Building No.
Drawing Number
Project Number
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Project Title
ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:
321 4 5 6 7 8 9 10
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE I
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
Floor No.
th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:
05/24/2024100% ISSUED FOR BID
A/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
Department of Veteran Affairs
01EP701
ELECTRICAL SCHEDULES
JACK C MONTGOMERY VAMC
05/24/2024 WNM/SJM RTS/BCL
EHRM INFRASTRUCTURE UPGRADES -
JACK C. MONTGOMERY VA MEDICAL
CENTER
623-21-700
-01
1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
Dwg. 68 of 77
KEY NOTES
GENERAL NOTES
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN ANY
ALL CHANGES: ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL ELECTRICAL SCHEDULES.
3. CONTRACTOR SHALL COORDINATE WITH MANUFACTURER TO PROVIDE
OVERCURRENT PROTECTION AS REQUIRED. ANY DEVIATION FROM BASIS OF DESIGN
EQUIPMENT INCLUDING BUT NOT LIMITED CONDUIT AND WIRE, OVERCURRENT
PROTECTION DEVICE RATING AND QUANTITY SHALL BE PROVIDED AT THE EXPENSIVE
OF THE CONTRACTOR.
PROVIDE (1) 3/4" CONDUIT WITH (2) 12 AWG AND (1) 12 AWG GND TO PROVIDE POWER
TO DDC CONTROLLER. COORDINATE WITH MECHANICAL FOR EXACT LOCATION OF
DDC CONTROLLER.
Location: BLDG 1, RM C100M1A-1 Volts: 120/208 Wye A.I.C Rating: 30k
Supply From: 01-101-1A Phases: 3 Bus Rating: 125A
Mounting: Surface Wires 4 Main Circuit Breaker: 125A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
7 1 20 A 3 1667 720 1 20 A 2
7 3 "" "" 1667 500 1 20 A 4
7 5 "" "" 1667 0 1 20 A 6
0 7 60 A 3 5000 0 1 20 A 8
0 9 "" "" 5000 79 1 20 A 10
0 11 "" "" 5000 0 1 20 A 12
0 13 20 A 1 500 0 1 20 A 14
9 15 25 A 2 1409 500 1 20 A 16
9 17 "" "" 1409 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
9 23 25 A 2 1409 100 "" "" 24
9 25 "" "" 1409 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 2818 125.00% 28536 VA
Other 1600 100.00% 29261 VA
Receptacle 720 100.00% 79 A
Lighting 79 125.00% 81 A
All other Motor 3318 100.00%
20000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Panelboard: 01-C100M1A-1A
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SERVER RACK RECEPTACLE SPARE
"" LIGHTING - TR ROOM
"" SPARE
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" DDC CONTROLLER
"" SPARE
SPARE DIGITAL POWER METER
SPARE ""
SPLIT DUCTLESS COOLING UNIT "CU-C100M1A-1-2" ""
ACCESS CONTROL "01-ACP-C100M1A-1" / DOOR POWER SPARE
SPLIT DUCTLESS COOLING UNIT "CU-C100M1A-1-1" VAV / TERMINAL UNIT "TU-C100M1A-1"
"" SPARE
"" SPD
SPARE ""
SPARE ""
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
3523 Total Conn. Power Load:
9496 9355 9685
79 78 81
20000Telecom Rack
1600 Total Est. Power Demand:
720 Total Conn. Amperage:
99 Total Est. Amperage Demand:
VOLTAGE: 208/120V, 3P, 4W MAIN: MCB (400A/LSIG)
BUS AMPS: 400A AIC: 42KAIC
OPTIONS: PROVIDE INTEGRAL SPD AND DIGITAL POWER METER
A B C
1 60/3 SPD 100 100 100
2 20/3 DPM 100 100 100 1
3 125/3 PANELBOARD "01-C100M1A-1B" 7587 6946 6867
4 125/3 PANELBOARD "01-2C50B-1B" 6867 7587 6937
5 125/3 PANELBOARD "01-240-1B" 7587 6931 6867
6 125/3 PANELBOARD "01-302-1B" 6867 7587 6931
7 125/3 PANELBOARD "01-403-1B" 5920 5296 5200
8 125/3 PANELBOARD "01-5A03-1B" 5284 5200 5920
9 20/3 SERVER RACK RECEPTACLE 1667 1667 1667
10 60/3 SERVER RACK RECEPTACLE 5000 5000 5000
11 20/1 SPARE - - -
12 20/1 RECEPTACLES - TR ROOM 720 - -
13 20/1 LIGHTING - TR ROOM - - 64
14 20/1 SPARE - - -
15 20/1 SPARE - - -
16 20/1 SPARE - - -
17 100/3 SPARE - - -
18 100/3 SPARE - - -
47697 46413 45652
397 386 380
CONNECTED LOAD (VA)
DEMAND
FACTOR
ESTIMATED
DEMAND (VA)
TOTALS
0 125.00% 0
CONN. POWER
LOAD (VA)
139762
4200 100.00% 4200 CONN. AMP (A) 388
5040 100.00% 5040
EST. POWER
DEMAND (VA)
106892
522 125.00% 652
EST. AMP DEMAND
(A)
0 100.00% 0
130000 NOTE 2 97000
DISTRIBUTION PANEL "01-DP-TRB"
CKT # CB/POLE CKT INFORMATION
VA LOAD
NOTES
TR RACK DATA
LOADING
NOTE 1: PROVIDE CT METERING AS REQUIRED FOR BMS MONITORING. DIGITAL POWER METER (DPM) AND SURGE PROTECTION
DEVICE (SPD) SHALL BE INTEGRAL TO PANEL (FACTORY INSTALLED).
NOTE 2: TELECOM RACKS DE-RATED FROM 5000VA TO 2500VA PER VA WHITE PAPER "POWER CAPACITY PLANNING FOR TRS" (JULY
2021).
TOTAL CONNECTED VA BY PHASE
TOTAL CONNECTED AMPS BY PHASE
LOAD TYPE
LARGEST MOTOR
OTHER
RECEPTACLE
LIGHTING
ALL OTHER MOTOR
Location: BLDG 1, RM C100M1A-1 Volts: 120/208 Wye A.I.C Rating: 30k
Supply From: 01-101-1B Phases: 3 Bus Rating: 125A
Mounting: Surface Wires 4 Main Circuit Breaker: 125A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 20 A 3 1667 720 1 20 A 2
3 "" "" 1667 0 1 20 A 4
5 "" "" 1667 0 1 20 A 6
7 60 A 3 5000 0 1 20 A 8
9 "" "" 5000 79 1 20 A 10
11 "" "" 5000 0 1 20 A 12
13 20 A 1 0 0 1 20 A 14
15 20 A 1 0 0 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 21399 VA
Other 600 100.00% 21419 VA
Receptacle 720 100.00% 59 A
Lighting 79 125.00% 59 A
All other Motor 0 100.00%
20000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Telecom Rack 20000
99 Total Est. Amperage Demand:
600 Total Est. Power Demand:
720 Total Conn. Amperage:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
7587 6946 6867
63 58 57
SPARE SPD
SPARE ""
SPARE ""
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
SPARE SPARE
SPARE SPARE
SPARE SPARE
"" SPARE
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" SPARE
"" SPARE
Branch Panel: 01-C100M1A-1B
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SERVER RACK RECEPTACLE SPARE
"" LIGHTING - TR ROOM
VOLTAGE: 208/120V, 3P, 4W MAIN: MCB (600A/LSI)
BUS AMPS: 600A AIC: 65KAIC
OPTIONS: PROVIDE INTEGRAL SPD AND DIGITAL POWER METER
A B C
1 60/3 SPD 100 100 100
2 20/3 DPM 100 100 100 1
3 225/3 PANELBOARD "01-C100M1A-1A" 9496 9355 9685
4 125/3 PANELBOARD "01-2C50B-1A" 9685 9496 9346
5 125/3 PANELBOARD "01-240-1A" 8087 7431 7367
6 125/3 PANELBOARD "01-302-1A" 7431 7367 8087
7 125/3 PANELBOARD "01-403-1A" 5700 6420 5796
8 125/3 PANELBOARD "01-5A03-1A" 9428 9738 10012
9 20/3 SERVER RACK RECEPTACLE 1667 1667 1667
10 60/3 SERVER RACK RECEPTACLE 5000 5000 5000
11 25/2 SPLIT DUCTLESS COOLING UNIT "CU-01-101-1-1" 1409 1409 -
12 20/1 ACCESS CONTROL "01-ACP-101-1" / DOOR POWER - - 500
13 20/1 RECEPTACLES - TR ROOM 720 - -
14 20/1 LIGHTING - TR ROOM - - 64
15 20/1 DDC CONTROLLER - - 500
16 20/1 VAV / TERMINAL UNIT "TU-101-1" - - 500
17 25/2 SPLIT DUCTLESS COOLING UNIT "CU-101-1-2" - 1409 1409
18 25/2 SPLIT DUCTLESS COOLING UNIT "CU-240-1-1" 1409 - 1409
26 25/2 SPLIT DUCTLESS COOLING UNIT "CU-240-1-2" 1409 1409 -
27 25/2 SPLIT DUCTLESS COOLING UNIT "CU-302-1-1" - 1409 1409
28 25/2 SPLIT DUCTLESS COOLING UNIT "CU-302-1-2" 1409 1409 -
63050 63720 62950
525 531 524
CONNECTED LOAD (VA)
DEMAND
FACTOR
ESTIMATED
DEMAND (VA)
TOTALS
2818 125.00% 3523
CONN. POWER
LOAD (VA)
189719
11200 100.00% 11200 CONN. AMP (A) 527
5040 100.00% 5040
EST. POWER
DEMAND (VA)
157554
522 125.00% 652
EST. AMP DEMAND
(A)
40139 100.00% 40139
130000 NOTE 2 97000
TOTAL CONNECTED VA BY PHASE
TOTAL CONNECTED AMPS BY PHASE
LOAD TYPE
LARGEST MOTOR
SWITCHBOARD "01-DP-TRA"
CKT # CB/POLE CKT INFORMATION
VA LOAD
NOTES
NOTE 2: TELECOM RACKS DE-RATED FROM 5000VA TO 3500VA PER VA WHITE PAPER "POWER CAPACITY PLANNING FOR TRS" (JULY 2021).
OTHER
RECEPTACLE
LIGHTING
ALL OTHER MOTOR
TR RACK DATA
LOADING
NOTE 1: PROVIDE CT METERING AS REQUIRED FOR BMS MONITORING. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD)
SHALL BE INTEGRAL TO PANEL (FACTORY INSTALLED).
30KAIC
FROM TO QTY SIZE (QTY) & SIZE
GROUND
SIZE
01-P-01A DISTRIBUTION PANEL "01-DP-TRB" DISTRIBUTION PANEL "FSG" JUNCTION BOX "01-JB-01" 2 3" (4) 350 kcmil 1 AWG - -
01-P-01B DISTRIBUTION PANEL "01-DP-TRB" JUNCTION BOX "01-JB-01" JUNCTION BOX "01-JB-02" 2 4" (4) 500 kcmil 1/0 AWG 0.5% -
01-P-01C DISTRIBUTION PANEL "01-DP-TRB" JUNCTION BOX "01-JB-02" DISTRIBUTION PANEL "01-DP-TRB" 2 3" (4) 350 kcmil 1 AWG - -
01-P-02A PANELBOARD "01-C100M1A-1B" DISTRIBUTION PANEL "01-DP-TRB" JUNCTION BOX "01-JB-03" 1 2" (4) 1 AWG 6 AWG - -
01-P-02B PANELBOARD "01-C100M1A-1B" JUNCTION BOX "01-JB-03" JUNCTION BOX "01-JB-04" 1 3" (4) 4/0 AWG 1 AWG 1.85% -
01-P-02C PANELBOARD "01-C100M1A-1B" JUNCTION BOX "01-JB-04" PANELBOARD "01-C100M1A-1B" 1 2" (4) 1 AWG 6 AWG - -
01-P-03A PANELBOARD "01-2C50B-1B" DISTRIBUTION PANEL "01-DP-TRB" JUNCTION BOX "01-JB-05" 1 2" (4) 1 AWG 6 AWG - -
01-P-03B PANELBOARD "01-2C50B-1B" JUNCTION BOX "01-JB-05" JUNCTION BOX "01-JB-06" 1 3" (4) 4/0 AWG 1 AWG 2.00% -
01-P-03C PANELBOARD "01-2C50B-1B" JUNCTION BOX "01-JB-06" PANELBOARD "01-2C50B-1B" 1 2" (4) 1 AWG 6 AWG - -
01-P-04 PANELBOARD "01-240-1B" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-240-1B" 1 2" (4) 1 AWG 6 AWG 0.73% -
01-P-05 PANELBOARD "01-302-1B" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-302-1B" 1 2" (4) 1 AWG 6 AWG 0.82% -
01-P-06 PANELBOARD "01-403-1B" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-403-1B" 1 2" (4) 1 AWG 6 AWG 0.81% -
01-P-07 PANELBOARD "01-5A04-1B" DISTRIBUTION PANEL "01-DP-TRB" PANELBOARD "01-5A04-1B" 1 2" (4) 1 AWG 6 AWG 0.88% -
01-P-08 DISTRIBUTION PANEL "01-DP-TRA" PANELBOARD "S1HA" TRANSFORMER "01-XFMR-TRA" 2 2" (4) 3/0 kcmil 3 AWG 0.2% -
01-P-09A DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "01-XFMR-TRA" JUNCTION BOX "01-JB-07" 2 3" (4) 350 kcmil 1 AWG - -
01-P-09 DISTRIBUTION PANEL "01-DP-TRA" TRANSFORMER "01-XFMR-TRA" DISTRIBUTION PANEL "01-DP-TRA" 2 2" (4) 3/0 AWG 3 AWG 0.0% -
01-P-09C DISTRIBUTION PANEL "01-DP-TRA" JUNCTION BOX "01-JB-08" DISTRIBUTION PANEL "01-DP-TRA" 2 3" (4) 350 kcmil 1 AWG - -
01-P-10A PANELBOARD "01-C100M1A-1A" DISTRIBUTION PANEL "01-DP-TRA" JUNCTION BOX "01-JB-09" 1 2" (4) 1 AWG 6 AWG - -
01-P-10B PANELBOARD "01-C100M1A-1A" JUNCTION BOX "01-JB-09" JUNCTION BOX "01-JB-10" 1 3" (4) 4/0 AWG 1 AWG 2.0% -
01-P-10C PANELBOARD "01-C100M1A-1A" JUNCTION BOX "01-JB-10" PANELBOARD "01-C100M1A-1A" 1 2" (4) 1 AWG 6 AWG - -
01-P-11A PANELBOARD "01-2C50B-1A" DISTRIBUTION PANEL "01-DP-TRA" JUNCTION BOX "01-JB-11" 1 2" (4) 1 AWG 6 AWG - -
01-P-11B PANELBOARD "01-2C50B-1A" JUNCTION BOX "01-JB-11" JUNCTION BOX "01-JB-12" 2 2" (4) 1/0 AWG 6 AWG 1.7% -
01-P-11C PANELBOARD "01-2C50B-1A" JUNCTION BOX "01-JB-12" PANELBOARD "01-2C50B-1A" 1 2" (4) 1 AWG 6 AWG - -
01-P-12 PANELBOARD "01-240-1A" DISTRIBUTION PANEL "01-DP-TRA" PANELBOARD "01-240-1A" 1 2" (4) 1 AWG 6 AWG 0.3% -
01-P-13 PANELBOARD "01-302-1A" DISTRIBUTION PANEL "01-DP-TRA" PANELBOARD "01-302-1A" 1 2" (4) 1 AWG 6 AWG 0.4% -
01-P-14 PANELBOARD "01-403-1A" DISTRIBUTION PANEL "01-DP-TRA" PANELBOARD "01-403-1A" 1 2" (4) 1 AWG 6 AWG 0.4% -
01-P-15 PANELBOARD "01-5A04-1A" DISTRIBUTION PANEL "01-DP-TRA" PANELBOARD "01-5A04-1A" 1 2" (4) 1 AWG 6 AWG 0.7% -
01-P-16 CONDENSING UNIT "CU-C100M1A-1-1" PANELBOARD "01-C100M1A-1A" CONDENSING UNIT "CU-C100M1A-1-1" 1 3/4" (2) 10 AWG 10 AWG 1.0% -
01-P-17 CONDENSING UNIT "CU-C100M1A-1-2" PANELBOARD "01-C100M1A-1A" CONDENSING UNIT "CU-C100M1A-1-2" 1 3/4" (2) 10 AWG 10 AWG 1.0% -
01-P-18 CONDENSING UNIT "CU-101-1-1" PANELBOARD "01-101-1A" CONDENSING UNIT "CU-101-1-1" 1 3/4" (2) 10 AWG 10 AWG 1.0% -
01-P-19 CONDENSING UNIT "CU-101-1-2" PANELBOARD "01-101-1A" CONDENSING UNIT "CU-101-1-2" 1 3/4" (2) 10 AWG 10 AWG 1.0% -
01-P-20 CONDENSING UNIT "CU-2C50B-1-1" PANELBOARD "01-2C50B-1A" CONDENSING UNIT "CU-2C50B-1-1" 1 3/4" (2) 10 AWG 10 AWG 1.0% -
01-P-21 CONDENSING UNIT "CU-2C50B-1-2" PANELBOARD "01-2C50B-1A" CONDENSING UNIT "CU-2C50B-1-2" 1 3/4" (2) 10 AWG 10 AWG 1.0% -
01-P-22 CONDENSING UNIT "CU-240-1-1" PANELBOARD "01-101-1A" CONDENSING UNIT "CU-240-1-1" 1 3/4" (2) 10 AWG 10 AWG 1.0% -
01-P-23 CONDENSING UNIT "CU-240-1-2" PANELBOARD "01-101-1A" CONDENSING UNIT "CU-240-1-2" 1 3/4" (2) 10 AWG 10 AWG 1.0% -
01-P-24 CONDENSING UNIT "CU-302-1-1" PANELBOARD "01-101-1A" CONDENSING UNIT "CU-302-1-1" 1 3/4" (2) 10 AWG 10 AWG 1.0% -
01-P-25 CONDENSING UNIT "CU-302-1-2" PANELBOARD "01-101-1A" CONDENSING UNIT "CU-302-1-2" 1 3/4" (2) 10 AWG 10 AWG 1.0% -
01-P-26 CONDENSING UNIT "CU-403-1-1" PANELBOARD "01-5A04-1A" CONDENSING UNIT "CU-403-1-1" 1 3/4" (2) 10 AWG 10 AWG 1.7% -
01-P-27 CONDENSING UNIT "CU-403-1-2" PANELBOARD "01-5A04-1A" CONDENSING UNIT "CU-403-1-2" 1 3/4" (2) 10 AWG 10 AWG 1.7% -
01-P-28 CONDENSING UNIT "CU-5A04-1-1" PANELBOARD "01-5A04-1A" CONDENSING UNIT "CU-5A04-1-1" 1 3/4" (2) 10 AWG 10 AWG 1.7% -
01-P-29 CONDENSING UNIT "CU-5A04-1-2" PANELBOARD "01-5A04-1A" CONDENSING UNIT "CU-5A04-1-2" 1 3/4" (2) 10 AWG 10 AWG 1.7% -
P-TR-1A TYPICAL TELECOM ROOM DATA RACK POWER FEED (1-RACK), SIDE A TYPICAL SOURCE A TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE A RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE -
P-TR-3A TYPICAL TELECOM ROOM DATA RACK POWER FEED (3-RACK), SIDE A TYPICAL SOURCE A TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE A JUNCTION BOX 1 1" (4) 6 AWG 8 AWG NEGLIGIBLE -
P-TR-1B TYPICAL TELECOM ROOM DATA RACK POWER FEED (1-RACK), SIDE B TYPICAL SOURCE B TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE B RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE -
P-TR-3B TYPICAL TELECOM ROOM DATA RACK POWER FEED (3-RACK), SIDE B TYPICAL SOURCE B TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE B JUNCTION BOX 1 1" (4) 6 AWG 8 AWG NEGLIGIBLE -
NOTES
NOTE(S):
BLDG 1 - CONDUIT AND WIRE SCHEDULE - VA OK MUSKOGEE EHRM UPGRADES
CONDUIT
TAG
SERVICE
ROUTING CONDUIT CONDUCTORS
VOLTAGE
DROP
1. ADJUST TAPS ON TRANSFORMER SUCH THAT THE VOLTAGE AT DISTRIBUTION PANEL "01-DP-TRA" IS NO LESS THAN 208V.
Project Number
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Project Title
ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:
321 4 5 6 7 8 9 10
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE I
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
Floor No.
th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:
05/24/2024100% ISSUED FOR BID
A/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
Department of Veteran Affairs
01EP702
ELECTRICAL SCHEDULES
JACK C MONTGOMERY VAMC
05/24/2024 WNM/SJM RTS/BCL
EHRM INFRASTRUCTURE UPGRADES -
JACK C. MONTGOMERY VA MEDICAL
CENTER
623-21-700
-01
1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
Dwg. 69 of 77
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN ANY
ALL CHANGES: ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL ELECTRICAL SCHEDULES.
3. CONTRACTOR SHALL COORDINATE WITH MANUFACTURER TO PROVIDE
OVERCURRENT PROTECTION AS REQUIRED. ANY DEVIATION FROM BASIS OF DESIGN
EQUIPMENT INCLUDING BUT NOT LIMITED CONDUIT AND WIRE, OVERCURRENT
PROTECTION DEVICE RATING AND QUANTITY SHALL BE PROVIDED AT THE EXPENSIVE
OF THE CONTRACTOR.
PROVIDE (1) 3/4" CONDUIT WITH (2) 12 AWG AND (1) 12 AWG GND TO PROVIDE POWER
TO DDC CONTROLLER. COORDINATE WITH MECHANICAL FOR EXACT LOCATION OF
DDC CONTROLLER.
Location: BLDG 1, RM 2C50B-1 Volts: 120/208 Wye A.I.C Rating: 30k
Supply From: 01-101-1A Phases: 3 Bus Rating: 125A
Mounting: Surface Wires 4 Main Circuit Breaker: 125A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
7 1 20 A 3 1667 720 1 20 A 2
7 3 "" "" 1667 500 1 20 A 4
7 5 "" "" 1667 0 1 20 A 6
0 7 60 A 3 5000 0 1 20 A 8
0 9 "" "" 5000 70 1 20 A 10
0 11 "" "" 5000 0 1 20 A 12
0 13 20 A 1 500 0 1 20 A 14
9 15 25 A 2 1409 500 1 20 A 16
9 17 "" "" 1409 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
9 23 25 A 2 1409 100 "" "" 24
9 25 "" "" 1409 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 2818 125.00% 28527 VA
Other 1600 100.00% 29249 VA
Receptacle 720 100.00% 79 A
Lighting 70 125.00% 81 A
All other Motor 3318 100.00%
20000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Branch Panel: 01-2C50B-1A
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SERVER RACK RECEPTACLE SPARE
"" LIGHTING - TR ROOM
"" SPARE
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" DDC CONTROLLER
"" SPARE
SPARE DIGITAL POWER METER
SPARE ""
SPLIT DUCTLESS COOLING UNIT "CU-2C50B-1-2" ""
ACCESS CONTROL "01-ACP-2C50B-1" / DOOR POWER SPARE
SPLIT DUCTLESS COOLING UNIT "CU-2C50B-1-1" VAV / TERMINAL UNIT "TU-2C50B-1"
"" SPARE
"" SPD
SPARE ""
SPARE ""
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
3523 Total Conn. Power Load:
9496 9346 9685
79 78 81
Telecom Rack 20000
88 Total Est. Amperage Demand:
1600 Total Est. Power Demand:
720 Total Conn. Amperage:
Location: BLDG 1, RM 240-1 Volts: 120/208 Wye A.I.C Rating: 30k
Supply From: 01-101-1A Phases: 3 Bus Rating: 125A
Mounting: Surface Wires 4 Main Circuit Breaker: 125A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 20 A 3 1667 720 1 20 A 2
3 "" "" 1667 0 1 20 A 4
5 "" "" 1667 0 1 20 A 6
7 60 A 3 5000 0 1 20 A 8
9 "" "" 5000 64 1 20 A 10
11 "" "" 5000 0 1 20 A 12
13 20 A 1 500 0 1 20 A 14
15 20 A 1 0 500 1 20 A 16
17 20 A 1 0 500 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 22884 VA
Other 1600 100.00% 22900 VA
Receptacle 720 100.00% 64 A
Lighting 64 125.00% 64 A
All other Motor 500 100.00%
20000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Branch Panel: 01-240-1A
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SERVER RACK RECEPTACLE SPARE
"" LIGHTING - TR ROOM
"" SPARE
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" SPARE
"" SPARE
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
ACCESS CONTROL "01-ACP-240-1" / DOOR POWER SPARE
SPARE VAV / TERMINAL UNIT "TU-240-1"
SPARE DDC CONTROLLER
SPARE SPD
SPARE ""
SPARE ""
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
8087 7431 7367
67 62 61
Telecom Rack 20000
80 Total Est. Amperage Demand:
1600 Total Est. Power Demand:
720 Total Conn. Amperage:
Location: BLDG 1, RM 302-1 Volts: 120/208 Wye A.I.C Rating: 30k
Supply From: 01-101-1A Phases: 3 Bus Rating: 125A
Mounting: Surface Wires 4 Main Circuit Breaker: 125A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 20 A 3 1667 720 1 20 A 2
3 "" "" 1667 0 1 20 A 4
5 "" "" 1667 500 1 20 A 6
7 60 A 3 5000 0 1 20 A 8
9 "" "" 5000 64 1 20 A 10
11 "" "" 5000 0 1 20 A 12
13 20 A 1 500 0 1 20 A 14
15 20 A 1 0 500 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 500 125.00% 23384 VA
Other 1600 100.00% 23525 VA
Receptacle 720 100.00% 65 A
Lighting 64 125.00% 65 A
All other Motor 500 100.00%
20000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Branch Panel: 01-302-1A
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SERVER RACK RECEPTACLE SPARE
"" LIGHTING - TR ROOM
"" SPARE
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" SPARE
"" DDC CONTROLLER
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
ACCESS CONTROL "01-ACP-302-1" / DOOR POWER SPARE
SPARE VAV / TERMINAL UNIT "TU-302-1"
SPARE SPARE
SPARE SPD
SPARE ""
SPARE ""
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
625 Total Conn. Power Load:
8087 7431 7367
67 62 61
Telecom Rack 20000
80 Total Est. Amperage Demand:
1600 Total Est. Power Demand:
720 Total Conn. Amperage:
Location: BLDG 1, RM 2C50B-1 Volts: 120/208 Wye A.I.C Rating: 30k
Supply From: 01-101-1B Phases: 3 Bus Rating: 125A
Mounting: Surface Wires 4 Main Circuit Breaker: 125A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 20 A 3 1667 720 1 20 A 2
3 "" "" 1667 0 1 20 A 4
5 "" "" 1667 0 1 20 A 6
7 60 A 3 5000 0 1 20 A 8
9 "" "" 5000 70 1 20 A 10
11 "" "" 5000 0 1 20 A 12
13 20 A 1 0 0 1 20 A 14
15 20 A 1 0 0 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 21390 VA
Other 600 100.00% 21408 VA
Receptacle 720 100.00% 59 A
Lighting 70 125.00% 59 A
All other Motor 0 100.00%
20000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Telecom Rack 20000
88 Total Est. Amperage Demand:
600 Total Est. Power Demand:
720 Total Conn. Amperage:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
7587 6937 6867
63 58 57
SPARE SPD
SPARE ""
SPARE ""
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
SPARE SPARE
SPARE SPARE
SPARE SPARE
"" SPARE
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" SPARE
"" SPARE
Branch Panel: 01-2C50B-1B
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SERVER RACK RECEPTACLE SPARE
"" LIGHTING - TR ROOM
Location: BLDG 1, RM 240-1 Volts: 120/208 Wye A.I.C Rating: 30k
Supply From: 01-101-1B Phases: 3 Bus Rating: 125A
Mounting: Surface Wires 4 Main Circuit Breaker: 125A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 20 A 3 1667 720 1 20 A 2
3 "" "" 1667 0 1 20 A 4
5 "" "" 1667 0 1 20 A 6
7 60 A 3 5000 0 1 20 A 8
9 "" "" 5000 64 1 20 A 10
11 "" "" 5000 0 1 20 A 12
13 20 A 1 0 0 1 20 A 14
15 20 A 1 0 0 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 21384 VA
Other 600 100.00% 21400 VA
Receptacle 720 100.00% 59 A
Lighting 64 125.00% 59 A
All other Motor 0 100.00%
20000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Telecom Rack 20000
80 Total Est. Amperage Demand:
600 Total Est. Power Demand:
720 Total Conn. Amperage:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
7587 6931 6867
63 58 57
SPARE SPD
SPARE ""
SPARE ""
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
SPARE SPARE
SPARE SPARE
SPARE SPARE
"" SPARE
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" SPARE
"" SPARE
Branch Panel: 01-240-1B
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SERVER RACK RECEPTACLE SPARE
"" LIGHTING - TR ROOM
Location: BLDG 1, RM 302-1 Volts: 120/208 Wye A.I.C Rating: 30k
Supply From: 01-101-1B Phases: 3 Bus Rating: 125A
Mounting: Surface Wires 4 Main Circuit Breaker: 125A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 20 A 3 1667 720 1 20 A 2
3 "" "" 1667 0 1 20 A 4
5 "" "" 1667 0 1 20 A 6
7 60 A 3 5000 0 1 20 A 8
9 "" "" 5000 64 1 20 A 10
11 "" "" 5000 0 1 20 A 12
13 20 A 1 0 0 1 20 A 14
15 20 A 1 0 0 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 21384 VA
Other 600 100.00% 21400 VA
Receptacle 720 100.00% 59 A
Lighting 64 125.00% 59 A
All other Motor 0 100.00%
20000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Telecom Rack 20000
80 Total Est. Amperage Demand:
600 Total Est. Power Demand:
720 Total Conn. Amperage:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
7587 6931 6867
63 58 57
SPARE SPD
SPARE ""
SPARE ""
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
SPARE SPARE
SPARE SPARE
SPARE SPARE
"" SPARE
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" SPARE
"" SPARE
Branch Panel: 01-302-1B
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SERVER RACK RECEPTACLE SPARE
"" LIGHTING - TR ROOM
Project Number
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Project Title
ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:
321 4 5 6 7 8 9 10
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE I
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
Floor No.
th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:
05/24/2024100% ISSUED FOR BID
A/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
Department of Veteran Affairs
01EP703
ELECTRICAL SCHEDULES
JACK C MONTGOMERY VAMC
05/24/2024 WNM/SJM RTS/BCL
EHRM INFRASTRUCTURE UPGRADES -
JACK C. MONTGOMERY VA MEDICAL
CENTER
623-21-700
-01
1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
Dwg. 70 of 77
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN ANY
ALL CHANGES: ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL ELECTRICAL SCHEDULES.
3. CONTRACTOR SHALL COORDINATE WITH MANUFACTURER TO PROVIDE
OVERCURRENT PROTECTION AS REQUIRED. ANY DEVIATION FROM BASIS OF DESIGN
EQUIPMENT INCLUDING BUT NOT LIMITED CONDUIT AND WIRE, OVERCURRENT
PROTECTION DEVICE RATING AND QUANTITY SHALL BE PROVIDED AT THE EXPENSIVE
OF THE CONTRACTOR.
PROVIDE (1) 3/4" CONDUIT WITH (2) 12 AWG AND (1) 12 AWG GND TO PROVIDE POWER
TO DDC CONTROLLER. COORDINATE WITH MECHANICAL FOR EXACT LOCATION OF
DDC CONTROLLER.
Location: BLDG 1, RM 430-1 Volts: 120/208 Wye A.I.C Rating: 30k
Supply From: 01-101-1A Phases: 3 Bus Rating: 125A
Mounting: Surface Wires 4 Main Circuit Breaker: 125A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 60 A 3 5000 720 1 20 A 2
3 "" "" 5000 0 1 20 A 4
5 "" "" 5000 500 1 20 A 6
7 20 A 1 0 0 1 20 A 8
9 20 A 1 0 96 1 20 A 10
11 20 A 1 0 0 1 20 A 12
13 20 A 1 500 0 1 20 A 14
15 20 A 1 0 500 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 500 125.00% 18416 VA
Other 1600 100.00% 18565 VA
Receptacle 720 100.00% 51 A
Lighting 96 125.00% 52 A
All other Motor 500 100.00%
15000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Branch Panel: 01-403-1A
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPARE SPARE
SPARE LIGHTING - TR ROOM
SPARE SPARE
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" SPARE
"" DDC CONTROLLER
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
ACCESS CONTROL "01-ACP-403-1" / DOOR POWER SPARE
SPARE VAV / TERMINAL UNIT "TU-403-1"
SPARE SPARE
SPARE SPD
SPARE ""
SPARE ""
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
625 Total Conn. Power Load:
6420 5796 5700
53 48 47
Telecom Rack 15000
120 Total Est. Amperage Demand:
1600 Total Est. Power Demand:
720 Total Conn. Amperage:
Location: BLDG 1, RM 5A04-1 Volts: 120/208 Wye A.I.C Rating: 30k
Supply From: 01-101-1A Phases: 3 Bus Rating: 125A
Mounting: Surface Wires 4 Main Circuit Breaker: 125A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 60 A 3 5000 720 1 20 A 2
3 "" "" 5000 0 1 20 A 4
5 "" "" 5000 0 1 20 A 6
7 20 A 1 0 0 1 20 A 8
9 20 A 1 0 84 1 20 A 10
11 20 A 1 0 0 1 20 A 12
13 20 A 1 500 500 1 20 A 14
15 25 A 2 1409 500 1 20 A 16
17 "" "" 1409 0 1 20 A 18
19 25 A 2 1409 100 3 20 A 20
21 "" "" 1409 100 "" "" 22
23 25 A 2 1409 100 "" "" 24
25 "" "" 1409 100 3 20 A 26
27 25 A 2 1409 100 "" "" 28
29 "" "" 1409 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 2818 125.00% 29178 VA
Other 1600 100.00% 29903 VA
Receptacle 720 100.00% 81 A
Lighting 84 125.00% 83 A
All other Motor 8955 100.00%
15000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Branch Panel: 01-5A04-1A
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPARE SPARE
SPARE LIGHTING - TR ROOM
SPARE SPARE
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" SPARE
"" SPARE
SPLIT DUCTLESS COOLING UNIT "CU-403-1-2" DIGITAL POWER METER
SPLIT DUCTLESS COOLING UNIT "CU-5A04-1-1" ""
ACCESS CONTROL "01-ACP-5A04-1" / DOOR POWER DDC CONTROLLER
SPLIT DUCTLESS COOLING UNIT "CU-403-1-1" VAV / TERMINAL UNIT "TU-5A04-1"
"" SPARE
"" SPD
SPLIT DUCTLESS COOLING UNIT "CU-5A04-1-2" ""
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
3523 Total Conn. Power Load:
9738 10012 9428
81 83 79
Telecom Rack 15000
105 Total Est. Amperage Demand:
1600 Total Est. Power Demand:
720 Total Conn. Amperage:
Location: BLDG 1, RM 430-1 Volts: 120/208 Wye A.I.C Rating: 30k
Supply From: 01-101-1B Phases: 3 Bus Rating: 125A
Mounting: Surface Wires 4 Main Circuit Breaker: 125A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 60 A 3 5000 720 1 20 A 2
3 "" "" 5000 0 1 20 A 4
5 "" "" 5000 0 1 20 A 6
7 20 A 1 0 0 1 20 A 8
9 20 A 1 0 96 1 20 A 10
11 20 A 1 0 0 1 20 A 12
13 20 A 1 0 0 1 20 A 14
15 20 A 1 0 0 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 16416 VA
Other 600 100.00% 16440 VA
Receptacle 720 100.00% 46 A
Lighting 96 125.00% 46 A
All other Motor 0 100.00%
15000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Telecom Rack 15000
120 Total Est. Amperage Demand:
600 Total Est. Power Demand:
720 Total Conn. Amperage:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
5920 5296 5200
49 44 43
SPARE SPD
SPARE ""
SPARE ""
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPARE
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" SPARE
"" SPARE
Branch Panel: 01-403-1B
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPARE SPARE
SPARE LIGHTING - TR ROOM
Location: BLDG 1, RM 5A04-1 Volts: 120/208 Wye A.I.C Rating: 30k
Supply From: 01-101-1B Phases: 3 Bus Rating: 125A
Mounting: Surface Wires 4 Main Circuit Breaker: 125A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 60 A 3 5000 720 1 20 A 2
3 "" "" 5000 0 1 20 A 4
5 "" "" 5000 0 1 20 A 6
7 20 A 1 0 0 1 20 A 8
9 20 A 1 0 84 1 20 A 10
11 20 A 1 0 0 1 20 A 12
13 20 A 1 0 0 1 20 A 14
15 20 A 1 0 0 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 16404 VA
Other 600 100.00% 16425 VA
Receptacle 720 100.00% 46 A
Lighting 84 125.00% 46 A
All other Motor 0 100.00%
15000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
Telecom Rack 15000
105 Total Est. Amperage Demand:
600 Total Est. Power Demand:
720 Total Conn. Amperage:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
5920 5284 5200
49 44 43
SPARE SPD
SPARE ""
SPARE ""
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPARE
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" SPARE
"" SPARE
Branch Panel: 01-5A04-1B
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPARE SPARE
SPARE LIGHTING - TR ROOM
Project Number
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Project Title
ARCHITECT/ENGINEERS:STAMP:CONSULTANTS:
321 4 5 6 7 8 9 10
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE I
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
Floor No.
th re e i n c h e s o n e fo o t o n e i n c h o n e fo o t o n e a n d o n e h a lf i n c h e s o n e fo o t th re e q u a rt e rs i n c h o n e fo o t o n e h a lf i n c h o n e fo o t th re e e ig h th s i n c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th i n c h o n e fo o t DateRevisions:
05/24/2024100% ISSUED FOR BID
A/E:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
Department of Veteran Affairs
18&11EP701
ELECTRICAL SCHEDULES
JACK C MONTGOMERY VAMC
05/24/2024 WNM/SJM RTS/BCL
EHRM INFRASTRUCTURE UPGRADES -
JACK C. MONTGOMERY VA MEDICAL
CENTER
623-21-700
-18
1011 HONOR HEIGHTS DR. MUSKOGEE, OK 74401
Dwg. 71 of 77
KEY NOTES
GENERAL NOTES
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT DIRECTORIES TO INDICATE IN ANY
ALL CHANGES: ALL REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. REFERENCE SHEETS EP701 AND EP702 FOR ALL TYPICAL ELECTRICAL SCHEDULE.
3. CONTRACTOR SHALL COORDINATE WITH MANUFACTURER TO PROVIDE
OVERCURRENT PROTECTION AS REQUIRED. ANY DEVIATION FROM BASIS OF DESIGN
EQUIPMENT INCLUDING BUT NOT LIMITED CONDUIT AND WIRE, OVERCURRENT
PROTECTION DEVICE RATING AND QUANTITY SHALL BE PROVIDED AT THE EXPENSIVE
OF THE CONTRACTOR.
PROVIDE (1) 3/4" CONDUIT WITH (2) 12 AWG AND (1) 12 AWG GND TO PROVIDE POWER
TO DDC CONTROLLER. COORDINATE WITH MECHANICAL FOR EXACT LOCATION OF
DDC CONTROLLER.
Location: BLDG 11, RM 106-11 Volts: 120/208 Wye A.I.C Rating: 30k
Supply From: 18EQDP Phases: 3 Bus Rating: 100A
Mounting: Surface Wires 4 Main Circuit Breaker: 100A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 30 A 3 3333 720 1 20 A 2
3 "" "" 3333 70 1 20 A 4
5 "" "" 3333 1409 2 25 A 6
7 -- -- 0 1409 "" "" 8
9 -- -- 0 1409 2 25 A 10
11 -- -- 0 1409 "" "" 12
13 20 A 1 500 0 1 20 A 14
15 20 A 1 500 500 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 2818 125.00% 18527 VA
Other 1600 100.00% 19249 VA
Receptacle 720 100.00% 51 A
Lighting 70 125.00% 53 A
All other Motor 3318 100.00%
Telecom Rack 10000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
10000
1600 Total Est. Power Demand:
720 Total Conn. Amperage:
88 Total Est. Amperage Demand:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
3523 Total Conn. Power Load:
6163 6013 6352
51 50 53
SPARE SPD
SPARE ""
SPARE ""
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
ACCESS CONTROL "11-ACP-106" / DOOR POWER SPARE
DDC CONTROLLER VAV / TERMINAL UNIT "TU-106-11"
SPARE SPARE
SPACE ""
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" LIGHTING - TR ROOM
"" SPLIT DUCTLESS COOLING UNIT "CU-106-11-1"
Branch Panel: 11-106-11A
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPACE ""
SPACE SPLIT DUCTLESS COOLING UNIT "CU-106-11-2"
Location: BLDG 11, RM 106-11 Volts: 120/208 Wye A.I.C Rating: 42k
Supply From: 18MDP-SEC. 2 Phases: 3 Bus Rating: 100A
Mounting: Surface Wires 4 Main Circuit Breaker: 100A / 3P
Enclosure: Type 1
CKT Trip Poles Poles Trip CKT
1 30 A 3 3333 720 1 20 A 2
3 "" "" 3333 70 1 20 A 4
5 "" "" 3333 0 1 20 A 6
7 20 A 1 0 0 1 20 A 8
9 20 A 1 0 0 1 20 A 10
11 20 A 1 0 0 1 20 A 12
13 20 A 1 0 0 1 20 A 14
15 20 A 1 0 0 1 20 A 16
17 20 A 1 0 0 1 20 A 18
19 20 A 1 0 100 3 20 A 20
21 20 A 1 0 100 "" "" 22
23 20 A 1 0 100 "" "" 24
25 20 A 1 0 100 3 20 A 26
27 20 A 1 0 100 "" "" 28
29 20 A 1 0 100 "" "" 30
Total Load:
Total Amps:
LOAD TYPE
Largest Motor 0 125.00% 11390 VA
Other 600 100.00% 11408 VA
Receptacle 720 100.00% 32 A
Lighting 70 125.00% 32 A
All other Motor 0 100.00%
Telecom Rack 10000 100.00%
Notes:
1. DIGITAL POWER METER (DPM) AND SURGE PROTECTION DEVICE (SPD) TO BE INTEGRAL TO PANEL (FACTORY INSTALLED).
10000
600 Total Est. Power Demand:
720 Total Conn. Amperage:
88 Total Est. Amperage Demand:
Connected Load (VA) Demand Factor Estimated Demand (VA) Panel Totals
0 Total Conn. Power Load:
4253 3603 3533
35 30 29
SPARE SPD
SPARE ""
SPARE ""
SPARE DIGITAL POWER METER
SPARE ""
SPARE ""
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPARE
CIRCUIT DESCRIPTION
SERVER RACK RECEPTACLE RECEPTACLES - TR ROOM
"" LIGHTING - TR ROOM
"" SPARE
Branch Panel: 11-106-11B
VA PER PHASE
CIRCUIT DESCRIPTION A B C
SPARE SPARE
SPARE SPARE
FROM TO QTY SIZE (QTY) & SIZE
GROUND
SIZE
11-P-01 PANELBOARD "11-106-11B" DISTRIBUTION PANEL "18MDP-SEC. 2" PANELBOARD "11-106-11B" 1 1-1/4" (4) 3 AWG 8 AWG 1.2% -
11-P-02 PANELBOARD "11-106-11A" PANELBOARD "18EQDP" PANELBOARD "11-106-11A" 1 2" (4) 1/0 AWG 6 AWG 1.9% -
11-P-03 CONDENSING UNIT "CU-106-1-1" PANELBOARD "11-106-11A" CONDENSING UNIT "CU-106-1-1" 1 3/4" (2) 10 AWG 10 AWG 2.5% -
11-P-04 CONDENSING UNIT "CU-106-1-2" PANELBOARD "11-106-11A" CONDENSING UNIT "CU-106-1-2" 1 3/4" (2) 10 AWG 10 AWG 2.5% -
P-TR-2A TYPICAL TELECOM ROOM DATA RACK POWER FEED (2-RACK), SIDE A TYPICAL SOURCE A TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE A RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE -
P-TR-2B TYPICAL TELECOM ROOM DATA RACK POWER FEED (2-RACK), SIDE B TYPICAL SOURCE B TR PANELBOARD TYPICAL OVERHEAD TR RACK SOURCE B RECEPTACLE 1 3/4" (4) 10 AWG 10 AWG NEGLIGIBLE -
NOTES
NOTE(S):
1. NONE.
BLDG 18&11 - CONDUIT AND WIRE SCHEDULE - VA OK MUSKOGEE EHRM UPGRADES
CONDUIT
TAG
SERVICE
ROUTING CONDUIT CONDUCTORS
VOLTAGE
DROP