This document provides details for a federal solicitation seeking a general contractor to perform infrastructure upgrades at the Tomah Veterans Affairs Medical Center in Tomah, Wisconsin. The solicitation requests bids to expand an existing building by approximately 5,000 square feet to incorporate a new data center and address deficiencies in accessibility, the main computer room, and demarcation room. The selected contractor will be responsible for furnishing all labor, materials, equipment, supervision, and other items necessary to complete the project according to provided specifications and drawings. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. Interested parties should respond with pricing by the specified date to be considered for the award, which is anticipated to occur on a subsequent date following evaluations.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRST FLOOR
100' - 0"
EXTG. FIRST FLOOR
104' - 8"
B.O.S
118' - 0"
SECOND FLOOR
112' - 0"
T.O.M
128' - 0"
CBA 2
M402
B32-AHU-1
B32-PRV-1
B32-CRAC-4
B32-CRAC-2
COMPUTER
RACK, TYP.
1" LPS 36X18 RA
DUCT
2-1/2" GWS/GWR
PIPING
1" HWS/HWR
PIPING
RELIEF
PLENUM
(2) 3/4" LPS
PIPING
20X16 SA
DUCT
3/4" PC
PIPING
2-1/2" HPS
PIPING
30X20 SA
DUCT
20X44 RA
DUCT
14X30 RA DUCT
36X20
OA DUCT
B32-ACCU-1
REFRIGERANT
PIPING FROM
CRAC TO ACCUS
14X70 RA
DUCT, TYP.
20X44 RA
DUCT
RA DUCT DOWN TO CABINET
EXH CONNECTION.
TRANSISTION TO OUTLET SIZE
AS REQUIRED. TYP.
FIRST FLOOR
100' - 0"
EXTG. FIRST FLOOR
104' - 8"
B.O.S
118' - 0"
SECOND FLOOR
112' - 0"
T.O.M
128' - 0"
M402
B32-AHU-1
B32-ACCU-5 B32-ACCU-4 B32-ACCU-3 B32-ACCU-2 B32-ACCU-1
B32-IH-1
COMPUTER
RACK, TYP.
RA DUCT DOWN TO
CABINET EXH
CONNECTION.
TRANSISTION TO
OUTLET SIZE AS
REQUIRED. TYP.
20X30 RA
DUCT
20X30 RA
DUCT
14X30 RA
DUCT
20X36
OA DUCT1-1/2" HWS/HWR
PIPING
B32-VAV-2
1-1/2" RELIEF
VENT
FIRST FLOOR
100' - 0"
EXTG. FIRST FLOOR
104' - 8"
B.O.S
118' - 0"
SECOND FLOOR
112' - 0"
T.O.M
128' - 0"
SA DUCT
VAV BOX,
TYP.
1" HWS/HWR
PIPING TO
VAV BOXES
OFFSET HPS AND
PC PIPING BELOW
BEAM
B32-P-1B
STEAM VENT
PIPING
B32-ET-1
20X36 RA
DUCT
VENT
CHIMNEY,
TYP.
3770 S. PENNSYLVANIA AVENUE, UNIT 8
ST. FRANCIS, WISCONSIN 53235
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked By
Building Number
Project Number
Drawing Number
Drawn By
PROJECT
LEADER:
Department of Veterans Affairs
CONSULTANTS
o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t
VA FORM 08-6231, OCT 1978
500 E VETERANS
TOMAH, WI 54660
MEDICAL CENTER
VETERANS
FULLY
500 E VETERANS
TOMAH, WI 54660
MEDICAL CENTER
VETERANS
FULLY
Office of Facilities
Management
B
A
C
D
E
F
97 8654321
F
E
D
C
B
A
1 2 3 4 5 6 87 9
FULLY FULLY
EHRM INFRASTRUCTURE
UPGRADES TIER 2
VA MEDICAL CENTER TOMAH, WI
FEB. 4, 2022 HFB JMD
M402M402
FINAL BID DOCUMENTS
676-21-701MECHANICAL
SECTIONS
1/4" = 1'-0"1 SECTION 1
1/4" = 1'-0"2 SECTION 2
No. Description Date
STANDING 'S' AND DRIVE SLIP
CONNECTION OR FLANGED DUCT
CONNECTION ALL AROUND
ACCESS DOOR
12" X 12"
PITCH UP TO DUCT SIZE
HOOK DUCT OVER BLADE
SEAL JOINT AND
INSTALL LIP ANGLES
2" RIGID, 3 LB RIGID FIBERGLASS INSULATION
TYPICAL TOP, BOTTOM AND SIDES OF LOUVER
INSULATION SHALL STOP WITHIN 1" FROM
ABOVE BOTTOM FLASHING
LOUVER
BY GC
3 NTS
DUCT CONNECTION TO LOUVER DETAIL
FIELD
2' - 0".
NOTES:
1. SEAL ALL DUCT JOINTS, CORNERS AND SEAMS WATERTIGHT USING
SEALANT AND OR SOLDERING. REFER TO SPECIFICATION SECTION 23 31 00
FOR ACCEPTABLE SEALANTS TO BE UTILIZED IN DUCT SYSTEMS.
BRANCH
ROUND
RECTANGULAR
BRANCH
RADIUS "Y" CONNECTION, INSIDE RADIUS
EQUAL TO WIDTH OF DUCT.
SPIN IN COLLAR CONNECTION.
45° SHOE TAP CONNECTION, MIN. 6" LONG.
DUCT TRANSITION, MAX. 20° OFFSET ANGLE.
MITERED ELBOW WITH TURNING VANES.
PLAN NOTES
RECTANGULAR
BRANCH
VD1 VD 1
1VD
F L O
W
BRANCH
RECTANGULAR
DUCT
MAIN
VD 1
FLOW
CONSTRUCTION OF ALL DUCTWORK
TO CONFORM TO S.M.A.C.N.A. DUCT
CONSTRUCTION STANDARDS.
NTS
EXHAUST OR RETURN AIR
DUCTWORK CONNECTION DETAIL
VOLUME DAMPER (VD):
RECTANGULAR DUCTS - SINGLE BLADE FOR
DUCTS 12" DEEP OR LESS, MULTIPLE BLADE
FOR DUCTS GREATER THAN 12" DEEP.
ROUND DUCTS - SINGLE BLADE.
SECTION "A-A"
"B" "B"
NOTES:
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.
3. SEE SMACNA 2005, FIGURE 9-15
ACCESS PANEL
ACCESS DOOR
CASING
GASKET
HANDLE INSIDE
FLEXIBLE
WASHER
FACTORY
FABRICATED
LATCH
SECTION "B-B"
INSULATION
DUCT
GASKET
INSULATION
INSULATION
"A"
"A"
4 NTS
ACCESS PANEL AND DOOR DETAIL
NOTE:
1.
2.
3.
4.
5.
6.
RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A
MINIMUM OF 3 TIMES THE DIAMETER OF INLET
A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET
TO THIS BOX, BUT ALLOWED TO ACCOMMODATE MINOR OFFSETS.
MAXIMUM LENGTH 3'-0".
DUCT INLET SIZE TO BE MINIMUM ONE SIZE LARGER THAN VAV BOX INLET
SIZE.
FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT
SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT EXCEED 5'-0" [1500mm]. USE
RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER THAN 45°.
COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE
INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT SECTIONS.
USE OF THE FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED ABOVE
GYPSUM BOARD OR ANY HARD CEILING.
AIR TERMINAL UNIT
(CV OR VAV)
REHEAT COIL
FLEXIBLE AIR DUCT
CONNECTOR. SEE DETAIL
DIFFUSER (TYP.)
SEE SPECIFICATIONS FOR
CLAMPS AND SEALANT (TYP.)
VOLUME
DAMPER
6 NTS
VAV BOX DUCTWORK DETAIL
(A=4in min) W3 X D3
(W2 X D2) + (W3 X D3)
W2 X D2 (W2 X D2) + (W3 X D3)
BELLMOUTH ROUND CONNECTION
45° SHOE TAP CONNECTION, MIN. 6in. LONG.
DUCT TRANSITION
RADIUS TRANSITION ELBOW
B =
A =
X W1
X W1
DUCT
MAIN
PLAN NOTES
BRANCH
RECTANGULAR
VD1
VD
VD
F L O
W
VD
ROUND
BRANCH
MAIN
DUCT
W2xD2
FLOW
W xD
AxD1
F L O
W
BxD1
CONSTRUCTION OF ALL DUCTWORK
TO CONFORM TO S.M.A.C.N.A. DUCT
CONSTRUCTION STANDARDS.
VOLUME DAMPER:
RECTANGULAR DUCTS - SINGLE BLADE FOR
DUCTS 12" DEEP OR LESS, MULTIPLE BLADE
FOR DUCTS GREATER THAN 12" DEEP.
ROUND DUCTS - SINGLE BLADE.
NTS
SUPPLY AIR DUCTWORK
CONNECTION DETAIL 5 NTS
FIRE DAMPER INSTALLATION DETAIL
7 NTS
FLEXIBLE DUCT CONNECTION DETAIL 8 NTS
RECTANGULAR DUCT HANGERS DETAIL 9 NTS
ROUND DUCT HANGERS DETAIL 10 NTS
DUCT RISER SUPPORT DETAIL
11 NTS
DUCTWORK TO EQUIPMENT
TRANSITION DETAIL 12 NTS
INLINE EQUIPMENT SUPPORT DETAIL 13 NTS
VOLUME DAMPER DETAIL
ROOFING &
FLASHING
ROOF INSULATION
PREFAB. METAL RAIL WITH
RAISED CANT AND WOOD
NAILER
ROOFING
WOOD NAILER
AND COUNTER-FLASHING
EQUIPMENT LEG
FASTEN RAIL TO ROOF DECK
WITH HILTI 1/2" DIAMETER EPOXY
ANCHOR BOLTS WITH 3-3/4"
EMBEDMENT. PROVIDE 1
ANCHOR BOLT PER CORNER
PER RAIL.
PROVIDE ISOLATION VIBRATION
PER SPECIFICATIONS.
LAG BOLT AND WASHER
SECURED TO WOOD
NAILER.
14 NTS
EQUIPMENT RAIL DETAIL
NOTE:
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND FAN
ROOM FLOORS SHALL BE PROVIDED WITH A 3" [75mm] HIGH CONCRETE CURB AROUND
OPENING FOR DUCT.
SEAL HOLE WITH FIREPROOFING
MATERIAL AFTER DUCT INSTALLATION
2"x2"x1/4" [50x50x6mm] ANGLE
INSTALL ON BOTH LONG
DIMENSION SIDES OF DUCT.
DUCT RISER - SEE FLOOR PLANS
FOR DETAILS
SEAL HOLE WITH FIREPROOFING
MATERIAL AFTER DUCT INSTALLATION
FLOOR
EXTEND ANGLE 3" [75mm]
BEYOND DUCT
DUCT RISER - SEE FLOOR PLANS
FOR SIZES SHEET METAL SCREWS 4" [100mm]
ON CENTER
1 1/2"x1 1/2"x1/8" [40x40x3mm] ANGLE
INSTALL ON BOTH LONG DIMENSION
SIDES OF DUCT. FOR DUCTS OVER 60"
[1500mm] USE 2"x2"x1/8" [50x50x3mm]
ANGLE.
HOLE IN STRUCTURAL FLOOR
DUCT RISER
0.5 INCH WG [125Pa] TO 2 INCHES WG [500Pa] DUCT RISER SUPPORT
ARRANGE RISER SO REINFORCER
TRANSVERSE JOINT IS AT RISER
SUPPORT POINT
FLOOR
2 INCHES WG [500Pa] TO 4 INCHES WG [1000Pa] DUCT RISER SUPPORT
HOLE IN STRUCTURAL FLOOR
DUCT RISER
HANGER STRAPS
60" MAX
[1524mm]
HANGER LOOPS
UNLESS FOOT
OF STRAP IS
PLACED UNDER
A BOTTOM
REINFORCEMENT
STRAP HANGERS
STRAP OR
ANGLE
TRAPEZE HANGERS
ROD
SIZE BOLT(S) FOR LOAD
2500 [1133]
1320 [598]
420 [190]ONE 1 [25] x 18 GA STRAP36 [900]
TWO 1/2 [13]∅ RODS
TWO 3/8 [10]∅. RODS
ONE 1 [25] x 16 GA STRAP
84 [2100]
60 [1500]
50 [1250] 700 [317]
ONE 1 [25] x 22 GA STRAP
QUANTITY/SIZEMAX. DUCT ∅
26 [650]
HANGER STRAPS OR RODS
MAX. LOAD
LBS. [kg]
260 [119]
MAX.
144 [3600]
IN. [mm]
SPACING
IN. [mm] IN. [mm]
144 [3600]
144 [3600]
144 [3600]
144 [3600]
NOTE:
TABULATED DATA FROM SMACNA
ALLOWS FOR DUCT REINFORCING AND
INSULATION, BUT NO EXTERNAL LOAD.
BAND
OVER 50"
[1250mm]∅
HANGER RODS
BAND OF SAME
SIZE AS HANGER
STRAP
LOAD RATED
FASTENERS
50" [1250mm]∅
& UNDER
NOTE:
1.
2.
3.
4.
5.
6.
A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, 1S SIMILAR. FOLLOW
DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR
SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION OR
FLOOR AND NOT OUTSIDE THE PENETRATION.
GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER
FRAME AND TO PERIMETER ANGLES.
PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2" [40x40mm], 14 GAGE, TO
PROVIDE 1" [25mm] MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.
BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.
ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.
PROVIDE 1/4" TO 1/2" [6 TO 15mm] CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE WITH
ROCK WOOL FIRESTOP FIBER.
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND
MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" [75mm] HIGH CONCRETE CURB
AROUND OPENING FOR DUCT.
SLEEVE, NOTE 2
DUCT
CONNECTION
NOTE 4
DAMPER,
NOTE 1
DAMPER COLLAR
EXTENSION INTEGRAL
PART OF SLEEVE
SLEEVE, NOTE 2
NOTE 6FIRE BARRIER
PARTITION OR CHASE
TYPICAL DUCT
INSULATION
PERIMETER ANGLE, NOTE 3 (NOTE
FASTENED TO PARTITION)
ACCESS
PANEL
NOTE 5
[2 m m
NOTE:
1.
2.
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR
MULTI-BLADE DAMPERS & ROUND DAMPERS.
INSULATION SEE
SPECIFICATION
DAMPER BLADE
1/8" [6mm]
CLEARANCE
ALL AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING
QUADRANT
INSULATION
STAND-OFF
1/2" [15mm] ROUND
ROD PIN
DUCT
STIFFEN BLADE
AS REQUIRED
SIDE ELEVATION SECTION
NOTE
ROD HANGER
SPRING ISOLATOR
EACH ROD
PROVIDE ADEQUATE SERVICE ACCESS TO UNIT.
1/4" STEEL CABLE BRACE
TYPICAL OF 2 TRANSVERSE
BRACES AND 2 LONGITUDINAL
BRACES
DUCTWORK FLEXIBLE
CONNECTION (TYP)
PLENUM
STRUCTURE ABOVE.
COUPLER, AS REQUIRED.
0°
15°
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
M
AX.
M A
X
E Q
U
IP
M E
N T
AIR
FLOW
AIR
FLOW
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEWTYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
M
AX.
M A
X
M A
X
M A
X
1/2" 1/2" 1 1/2"
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
FLANGED
CONNECTION ON FAN
SIDE
WASHER 1-1/2" [40mm] MIN. TO 3" [75mm] MAX.
INSTALLED. 6" [150mm] NOMINAL WITH
MATERIAL TAUT
FLEXIBLE
MATERIAL AS
SPECIFIED
1"x1/8" [25x3mm] DRAW BAND
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
5/16" [8mm] FLANGE
DUCT
SHEET METAL SCREWS ON
12" [300mm] CENTERS
RIVET ON 4"
[100mm] CENTERS
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
1" [25mm] FLANGE & HEMALTERNATE
POSITION
OF BOLT 1 1/2" [40mm]
POCKET SLIP
DUCT
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
[15mm] [15mm] [40mm]
1 1/2" [40mm] MIN. TO 3" [75mm] MAX.
INSTALLED. 6" [150mm] NOMINAL WITH
MATERIAL TAUT
FLANGED
CONNECTION
ON FAN SIDE
WASHER
FLEXIBLE MATERIAL
AS SPECIFIED
3770 S. PENNSYLVANIA AVENUE, UNIT 8
ST. FRANCIS, WISCONSIN 53235
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked By
Building Number
Project Number
Drawing Number
Drawn By
PROJECT LEADER:
Department of
Veterans Affairs
CONSULTANTS:
o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t
VA FORM 08-6231, OCT 1978
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
Office of Facilities
Management
B
A
C
D
E
F
97 8654321
F
E
D
C
B
A
1 2 3 4 5 6 87 9
FULLY SPRINKLEREDFULLY SPRINKLERED
EHRM INFRASTRUCTURE
UPGRADES TIER 2
VA MEDICAL CENTER TOMAH, WI
FEB. 4, 2022 HFB JMD
M501M501
FINAL BID DOCUMENTS
676-21-701MECHANICAL
DETAILS AND DIAGRAMS
PIPE HANGERS - PROVIDE DOUBLE
DEFLECTION NEOPRENE (TYPE HN) FOR
FIRST TWO ON EACH SIDE OF PUMP (SEE
NOTE NO. 1)
PRESSURE GAGE
1/2" [15mm]
STRAINERFLEXIBLE
CONNECTION
BALL OR
BUTTERFLY TYP.
NOTES:
1. SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.
BALANCING DEVICE
NOTES:
PROVIDE RESTRAINING CLAMPS 2438mm [8'-0"] O.C.
(8 m m
(4 m m
(1
M
IN
m m
203x203x8.0mm [8"x8"x3/8" STEEL PLATE
WELD PLATE TO PIPESECURE TO ROOF SLAB WITH (4)
8.0mm [ 3/8"] ∅ EXPANSION BOLTS
OR WELD TO STEEL DECK
CONCRETE ROOF SLAB
OR STEEL ROOF DECK
ROOF SYSTEM
INSULATION AND
MEMBRANE
PRE-MOULDED
FLEXIBLE PIPE
COUNTER FLASHING
CLAMPING RING
ROOF SURFACE
WELD PIPE SADDLE
SUPPORT TO PIPE.
PROVIDE WATER
TIGHT CONNECTION
HIGH COMPRESSIVE
STRENGTH INSULATION
INSERT UNDER SHIELD
PIPE AND INSULATION
INSULATION PROTECTION
SHIELD
SEALANT
50mm [2"] STEEL PIPE
65mm [2-1/2"] STEEL PIPE
PROVIDE ALUMINUM
JACKET
PROVIDE VAPOR BARRIER
AS SPECIFIED ON PIPING
CONVEYING FLUID TO
DEGREE C [°F] OR
LOWER
[6 "M
IN
(T Y
P m m
D
D
TEST PLUG
(TYP.)
THERMOMETER (TYP.)
HPS
STEAM
SUPPLY
HEAT
EXCHANGER
(TYP.)
RUN DRAIN LINE FROM RELIEF
VALVE TO NEAREST FLOOR
DRAIN. (TYP.)
TANK O
R TO HPR M
AIN LINE (T
YP.)
15mm [1/2"] CHECK
VALVE VACUUM
BREAKER (TYP.)DDC TEMPERATURE
SENSORS (TYP.)
SEE SCHEDULES FOR RELIEF
VALVE SETTING
THERMOSTATIC AIR
VENT (T
YP.)
IF INSTALLED
LOWER THAN
MAIN HPS LINE,
PROVIDE
ANOTHER
SCALE
POCKET/TRAP
HERE.
IF THE SECOND HEAT
EXCHANGER IS NOT A
REDUNDANT 100% BACK
UP UNIT, THEN PROVIDE
A MOTORIZED ISOLATION
VALVE HERE.
NOTES:
1. THE ABOVE DETAIL SHOWS REQUIRED PIPING FOR TWO HEAT EXCHANGERS IN PARALLEL. INDICATE IF 100% REDUNDANT OR NOT.
2. PROVIDE SADDLE SUPPORTS AND LEGS OR HANGERS FOR HEAT EXCHANGER. MOUNTING HEIGHT SHALL BE ADJUSTED TO
FACILITATE GRAVITY RETURN OF STEAM CONDENSATE.
3. MAKE THE BYPASS THE SAME SIZE AS THE CONNECTIONS TO THE CONTROL VALVES.
4. CONTROL VALVES SHALL BE IN A 1/3 AND 2/3 SIZE ARRANGEMENT.
HWR
HWS
HPR TO FLASH
SCALE POCKET
(TYP.)
TT
PI
PI
SIZE ARRANGEMENT, T
YP.BYPASS
CONTROL VALVES IN
2/3 & 1/3
TT
NC
DDC
PRESSURE
SENSORS
(TYP.)
IF THE SECOND HEAT EXCHANGER IS NOT A
REDUNDANT 100% BACK UP UNIT, THEN PROVIDE
A MOTORIZED ISOLATION VALVE HERE.
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
SADDLE
WELD
SIDE VIEW
TRAPEZE HANGER FOR UP
TO 1000 LB. (453 KG) UNIFORM LOAD
PROVIDE INSULATION SHIELD
AND INSERT FOR ALL PIPING
(8" (200 MM) MIN)
1" (25 MM) MAX
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
HANGER ROD
INSULATION SHIELD
AT HANGER
BAND
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION
(9 PCF MIN DENSITY)
UNDER INSULATION SHIELD
1/2" (15 MM) DIA HANGER
RODS WITH
36" (900 MM) MAX
SPACING ON EACH CHANNEL
1 5/8" (43 MM) 12 GAGE
CHANNEL OR 2"x2"x1/4" (50x50x8 MM) ANGLE
NOTE:
SEE SPECIFER FOR DETAILED HANGER
REQUIREMENTS
DESIGNER'S NOTE:
SHOW ON THE DRAWINGS OTHER
SPECIFIED AND SPECIAL PIPE SUPPORTS
WHERE REQUIRED.
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
MAXIMUM PIPE/TUBING SUPPORT SPACING
TUBING
(5)
NOM SIZE
PIPE
(7)
(6)
(8)
(10)
(9)
(11)
(10)
(12)
(13)
(12)
(14)
(6)
(4)
(5)
(3)
(2)
(2 1/2)
(1 1/2)
(1)
(1 1/4)
MM
(IN)
MM
(FT)
THRU 20
THRU (3/4)
(9)
(7)
(8)
(10)
(12)
(14)
(16)
(18)
(20)
(24)
(7)
(7)
(16)
(17)
(19)
(22)
(23)
(25)
(27)
(27)
(28)
(30)
(32)
MM
(FT)
(8)
(16)
COIL
TEST PLUG (TYP.) REDUCER, IF REQUIRED
WATER RETURN
MANUAL AIR VENT
UNION CONNECTIONS
(TYP.)
WATER SUPPLY
SHUT OFF VALVE
DRAIN WITH HOSE
CONNECTION
MV
MODULATION CONTROL VALVE
STEAM TRAP ASSEMBLY
STEAM LINE DRIP POCKET
FLOW
M
IN
M
IN
[3 m m
[1 m m
DRIP LEG (TYP)
3/4" DRAIN (ALTERNATE LOCATIONS)
(TYPICAL)
STEAM LINE
(TYPICAL)
CAP (TYPICAL)
PIPE T0
STEAM TRAP
(TYPICAL)
FROM DRIP
CONNECTION
DRIP
RETURN
3/8" TEST
CONNECTION
NOTE:
1. ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 12"
MINIMUM HIGH DRIP LEGFROM BOTTOM OF STEAM MAIN TO TRAP INLET.
DRIP LEG SHALL HAVE 6" SCALE POCKET BELOW TRAP INLET.
TO RETURN MAIN
PIPE SIZE SHALL BE SAME SIZE AS TRAP
FLOAT AND THERMOSTATIC TRAP
SEE PLANS AND SCHEDULES
DIELECTRIC FITTING
WHERE RETURN IS COPPER PIPE
SCHEDULE 80
STEEL PIPE
BYPASS-INSTALL IN HORIZONTAL PLANE
LEVEL WITH TRAP OR IN VERTICAL PLANE &
BELOW TRAP PROVIDE BYPASS PIPING
FOR ALL TRAPS 1" AND LARGER.
DRIP LEG OR EQUIPMENT CONNECTION.
MAKE THE SAME SIZE AS THE SUPPLY
MAIN OR EQUIPMENT CONNECTION.
SEE NOTE 1
SCHEDULE 80 STEEL PIPE
SEE DRAWINGS FOR PIPE SIZES
1" GATE
VALVE
INVERTED
BUCKET TRAP
3/4" MIN
3 NTS
FLOAT AND THERMOSTATIC
TRAP ASSEMBLY
M
IN
M
IN
M
IN
M
IN
NOTE:
DRIP POCKET PIPE SIZE SAME AS
STEAM MAIN
UNLESS OTHERWISE NOTED
3/4" MIN
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
3/4" (20 MM) GATE VALVE
ADAPTER TO 20 MM (3/4") HOSE THREAD.
PROVIDE HOSE CAP NUT
ELEVATION
THREADED PIPING
ELEVATION
WELDED PIPING
1/4" (8 MM)
COPPER TUBING
1/2" (15 MM)
GATE VALVE
1/2" (15 MM) x 4" (100 MM)
NIPPLE
REDUCER
CIRCULATING
WATER PIPING
ELEVATION
TYPICAL AIR VENT
TYPICAL DRAIN VALVE
NTS
STEAM HUMIDIFIER PIPING DIAGRAM
NOTES:
1. VENT ALL HIGH POINTS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR
PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
3-WAY CONTROL VALVE
CIRCULATING
PUMP
VALVE, TYP
THERMOMETER, TYP MANUAL AIR VENT, TYP
O U
T D
O O
R A
IR
C
O
IL
DRAIN VALVE, TYP AT EACH COIL, ROUTE
TO VERTICAL STRUCTURE AND THEN
DOWN TO NEAREST FLOOR DRAIN
E X
H A
U S
T
A
IR
C O
IL
SYSTEM DRAIN AND
FILL VALVE, LOCATE
AT LOWEST POINT
OF SYSTEM
UNION, TYP
DUCTED
OUTDOOR
AIR
DUCT TO
AHU INLET
DUCTED
GENERAL
EXHAUST AIR
DUCT TO
EXHAUST
FAN
THERMAL WELL WITH WATER TEMP SENSOR
DISCHARGE SUPPLY AIR
SENSOR IN DUCT
BALANCING VALVE
NOTES:
1. COILS AND PIPING SHALL BE ARRANGED TO BE FULLY DRAINABLE.
2. VERTICAL PIPING SHALL BE OFFSET SUCH THAT COILS CAN BE REMOVED WITHOUT INTERFERENCE.
3. PUMP, VALVES AND PIPING SPECIALTIES SHALL BE LOCATED SUCH THAT THEY ARE FULLY ACCESSIBLE.
D U
C T
H E
IG
H
T
H1 /3
H /3
H /3
H
STEAM CONDENSATE
RETURN
TEMPERATURE SWITCH
SCALE POCKET
HUMIDIFIER CONTROL
VALVE
TO HUMIDISTAT
MANIFOLD PIPE ADAPTERS
STEAM SUPPLY
ON-OFF CONTROL VALVE DUCT CROSS SECTION
M
IN
INVERTED BUCKET
TRAP
ASSEMBLY
SEE MANUFACTURER'S PIPING
RECOMMENDATIONS FOR FINAL
LAYOUT
4 NTS
STEAM LINE DRIP POCKET
STEAM TRAP ASSEMBLY DETAIL
EXP TANK
WALL
PIPE INSULATION
TYPICAL PIPE
AS SPECIFIED
CORE DRILLED. OTHER
TO HAVE SCH. 40 STEEL
WALL CONSTRUCTION
MASONRY WALL TO BE
PIPE SLEEVE.
INSULATION
MINERAL WOOL
PIPE
PIPE WITH INSULATION
PACK OPENING AROUND
ROOFING MEMBRANES
SEALED TO PIPE
C-481 ACCOMADATES (4)
C-412 ACCOMADATES (4)
1" THRU 2" PIPES
3/8" THRU 1" PIPES
ALTERNATE CAPS:
(2) 3/8" THRU 1" PIPES AND 1"
C-212 CAP ACCOMADATES
THRU 2" PIPES
STAINLESS STEEL
SNAP-LOCK CLAMP
7 NTS
PIPE THRU INTERIOR WALL DETAIL6 NTS
PIPE CURB AT ROOF DETAIL
NTS
ENERGY RECOVERY SYSTEM DETAIL
5 NTS
TYPICAL PIPING CONNECTIONS DETAIL
10 NTS
INLINE PUMP DETAIL 11 NTS
TERMINAL UNIT PIPING DETAIL 12 NTS
ROOF PIPE SUPPORT DETAIL 13 NTS
HEATING COIL PIPING DIAGRAM
8 NTS
HEAT EXCHANGER PIPING DIAGRAM
9 NTS
PIPE HANGER DETAIL
14 NTS
PIPE THRU EXTERIOR WALL DETAIL
WATER STOP AND
ANCHOR COLLAR
WALL
WALL
SLEEVE
CARRIER PIPE
HYDRO-STATIC
PIPE WALL
CLOSURE
C
NO
NC
HW HEATING
COIL
WITH BALL VALVE
1/2"∅ CAPPED DRAIN
PT PLUG
STRAINER
UNION
MANUAL AIR VENT
3-WAY CONTROL VALVE
BALANCING VALVE
INSIDE UNIT
EXTENTS OF CRAC UNIT
HWR PIPING
HWS &
3770 S. PENNSYLVANIA AVENUE, UNIT 8
ST. FRANCIS, WISCONSIN 53235
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked By
Building Number
Project Number
Drawing Number
Drawn By
PROJECT LEADER:
Department of
Veterans Affairs
CONSULTANTS:
o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t
VA FORM 08-6231, OCT 1978
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
Office of Facilities
Management
B
A
C
D
E
F
97 8654321
F
E
D
C
B
A
1 2 3 4 5 6 87 9
FULLY SPRINKLEREDFULLY SPRINKLERED
EHRM INFRASTRUCTURE
UPGRADES TIER 2
VA MEDICAL CENTER TOMAH, WI
FEB. 4, 2022 HFB JMD
M502M502
FINAL BID DOCUMENTS
676-21-701MECHANICAL
NTS
CONDENSATE PUMPS - PIPING CONNECTIONS
THERMOMETER
LPR
CONTROL CABINET
RECEIVER WITH
INSULATED JACKET
FLOOR
20mm [3/4"] DRAIN, DISCHARGE INTO NEAREST
FLOOR DRAIN, NC.
THERMOMETER
GRAVITY RETURN
FROM FLASH TANK
IF SHOWN ON
FLOOR PLAN
SCHEDULE 80
PUMP DISCHARGE
TO CONDENSATE
SYSTEM
RELIEF VENT
FLUSHING
CONNECTION
WATER LEVEL
GAUGE
127mm [5"] THICK
CONCRETE
HOUSEKEEPING
PAD
1" CW
STRAINER
HWS
HWS
DRAIN VALVE
WITH THREADED
NIPPLE
AIR SEPARATOR
TANK
1" BYPASS
AUTO FILL
VALVE
DIAPHRAGM
EXPANSION
CONTRACTOR
WORK BY
PLUMBING
CONTRACTOR
WORK BY
HVAC
GLOBE
VALVE
PRESSURE GAGE
WITH SNUBBER
AND PLUG VALVE,
TYP
HPS
PRESSURE
SAFETY
VALVE, TYP
MPS
VENT
TO ATM
2"
BYPASS
2"4"
PRV-10A
PRV-10
4"2"2"
2"
2"
2"
20XDIA
MIN.
10XDIA
MIN.
3/4" DRAIN WITH CAP, SLOPE
1/8" PER FOOT AND SUPPORT
PIPE TO NEAREST FLOOR DRAIN
POT
FEEDER
CHECK
VALVE
DRAIN
VALVE
ISOLATION
VALVE, TYP
PIPE UNION,
TYP
SECURE LEGS TO FLOOR.
NOTE:
SEE DETAILS FOR PIPE HANGER REQUIREMENTS.
V
NOTES:
1. SEE FLOOR PLANS FOR ADDITIONAL PIPE SIZES AND
INFORMATION.
2. SEE EQUIPMENT SCHEDULES FOR VALVE DATA AND PIPE SIZES. INSTALL VALVES AS
RECOMMENDED BY
MANUFACTURER.
3. MAKE BYPASS VALVE DISCHARGE PIPE THE SAME SIZE AS THE LARGEST PRV PIPE
SIZE.
4. PROVIDE UNIONS FOR THE REMOVAL OF PRESSURE REDUCING
VALVES.
5. SLOPE PILOT CONTROL LINE FROM PRESSURE REDUCING VALVE TO DOWN STREAM STEAM
PIPING. MIMIMUM SLOPE SHALL BE
1"/12".
PILOT
CONTROL
LINE, TYP
N.C.
INVERTED
BUCKET TRAP
ASSEMBLY TYP.
NTS
STEAM PRESSURE REDUCING
STATION DOUBLE VALVE (1/3 - 2/3)
NTS
CHEMICAL POT FEEDER DETAIL
NTS
HYDRONIC SYSTEM AIR CONTROL PIPING
UNION
RPZ
HWS
3770 S. PENNSYLVANIA AVENUE, UNIT 8
ST. FRANCIS, WISCONSIN 53235
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked By
Building Number
Project Number
Drawing Number
Drawn By
PROJECT LEADER:
Department of
Veterans Affairs
CONSULTANTS:
o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t
VA FORM 08-6231, OCT 1978
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
Office of Facilities
Management
B
A
C
D
E
F
97 8654321
F
E
D
C
B
A
1 2 3 4 5 6 87 9
FULLY SPRINKLEREDFULLY SPRINKLERED
EHRM INFRASTRUCTURE
UPGRADES TIER 2
VA MEDICAL CENTER TOMAH, WI
FEB. 4, 2022 HFB JMD
M503M503
FINAL BID DOCUMENTS
676-21-701MECHANICAL
TAG AREA SERVICE
FAN SCHEDULE (EF-,RF-)
CAPACITY
CFM HP
MOTOR FAN
TYPERPM
MOTOR
REMARKS
EXHAUST 1800 0.25 208/3/60
NOTES
1. BASIS OF DESIGN: GREENHECK, MODEL BSQ-140 OR APPROVED EQUAL.
BAS.2. PROVIDE ECM MOTOR. COORDINATE INSTALLATION AND CONTROL WIRING.
3. PROVIDE BACKDRAFT DAMPER.
TAG
AIR HANDLING UNIT SCHEDULE (AHU-)
NOTES:
1. BASIS OF DESIGN: JCI MODEL XTI-45x72 OR APPROVED EQUAL.
2. PROVIDE NEW DX COIL, HW HEATING COIL, FINAL FILTER, MIXING BOX, R-410A REFRIGERANT.
3. PROVIDE VFD. EC TO FURNISH AND INSTALL VFDS. MC TO COORDINATE INSTALLATION AND CONTROL WIRING.
SUPPLY AIR
CFM
MIN OA
CFM
ESP
(IN WG)
SENSIBLE
SUPPLY FAN DATA
ROWS
FACE VEL.
(FPM)
TOTAL
MBH
COOLING COIL DATA HEATING COIL DATA
°F DB
FINAL FILTER
REMARKS
TOTAL
MOTOR
HP
FIN
SPACING
EAT
°F
APD
IN WG
DRIVE
DIRECT1725
B32-AHU-1 7000 81291
3/4
(1) (2) (3)2.752100 197 67.6 R410A 6 13.0 500 135 28 180
INLINE (1) (2) (3)
15 25.04500 11
V/PH/HZ
0.88
TAG SERVES
(IN.
W.G.)
LOUVER SCHEDULE (L-)
B32-L-1 RELIEF 0.05
APD
(FPM)
700.0
VEL.
MAX.
MATERIAL
ALUM
COLOR
TBD
FINISH
KYNAR
NOTES:
LOCATION
7,000.0
CFM NOTES
(1) (2)
1. BASIS OF DESIGN IS GREENHECK EDJ-401 OR APPROVED EQUAL. SEE DETAIL 3/M501.
2. PROVIDE BACKDRAFT DAMPER, ALUMINUM INSECT SCREEN, DRAINABLE.
SIZE
(IN X IN)
72X44
MERV
APD
IN WC
0.5
PRE FILTER
STEAM TO WATER HEAT EXCHANGER SCHEDULE (HX-)
SYSTEM
AND/OR
SERVICETAG
B32-HX-1
HW
SHELL/TUBE 2.5
TYPE
WATER CONDITIONS
REMARKS
NOTES:
1. BASIS OF DESIGN: TACO MODEL E06204-S OR APPROVED EQUAL.
SEE DETAIL 8/M502.
MIN SA
CFM °F WB
LATEAT
°F DB °F WB
54.6 53.6
FLUID
TYPE
FLUID
TYPE
NOTE 5
ROWS
MERV
8 0.5
APD
IN WC LBS
LAT
°F
EWT
°F
EWT
°F
FIN
SPACING FLA
208/3/60 17.513.0
FLOW
GPM V/PH/HZ
MERV
APD
IN WC
0.7
ELECTRICAL DATA
B32-EF-1
ESP
(IN WG)
TAG SYSTEM (GPM)
PUMP SCHEDULE (P-)
B32-P-1A 1750
RPM
OPERATING
TEMP. VOLTS
PHASE HERTZ
NOTES:
HW 51
(HEAD (FT)
28 0.75
MOTOR
HP REMARKS
1. BASIS OF DESIGN: BELL & GOSSETT E90 1.5AB OR APPROVED EQUAL.
2.
3. SEE DETAIL 10/M502 FOR FURTHER INFORMATION.
FLUID
32081750180
35 3600 208 3
WATER
WATER
50% GLYCOL
0.75
2.042
25ERC-1
HW
B32-P-1B
B32-P-2
BASIS OF DESIGN: BELL & GOSSETT E90 1.25AAB OR APPROVED EQUAL.
B32-HX-2
HW
SHELL/TUBE
FLOW
(GPM)
EWT
(°F)
LWT
(°F)
WPD
(FT)
2.5
ENT PRESS
(PSIG)
CAPACITY
LBS/HR
RM 203
1.
82.0 B32-ACCU-131
COMPUTER ROOM AIR CONDITIONING UNIT (CRAC-)
LOCATION
CONDENSING UNIT
TAG
B32-CRAC-1
B32-CRAC-2
B32-CRAC-3
B32-CRAC-4
RM 203
RM 203
RM 203
CAPACITY
TONS
BLOWER
(CFM) (HP)
HTG
(MBH)
8,000 7.5 0.5
TOTAL
CLG
(MBH)(ESP)
266.5 80.0
DB
DEG F
ENT AIR
67.0
WB
DEG F
DB
DEG F
LEAV AIR
DB
DEG F
55.0 54.0
HUMIDITY
LB/HR
FILTER
MERV
TAG
FAN
F HP
95 7.5
CONNECTIONS
LIQUID
IN
SUCTION
IN
COND
IN
HUMID
IN REMARKS
(2) 5/8 (2) 1-3/8 0.75 0.25 (1) (2) (3)
(1) (2) (3) (4)
(1) (2) (3)
(1) (2) (3) (4)
NOTES
1. BASIS OF DESIGN: DATA AIRE MODEL DAAD-20/DARC-21 OR APPROVED EQUAL.
2. PROVIDE DOWNFLOW SYSTEM WITH DX COOLING, FLOOR STAND WITH TURNING VANE, TOP RETURN AIR INTAKE, HW REHEAT, STEAM HUMIDIFIER, REMOTE CONDENSER, REFRIGERANT LINE SETS, SMOKE DETECTOR, HOT GAS BYPASS, FOUR STEP CONTROL, AND CONDENSATE PUMP.
3. SEE ELECTRICAL MOTOR SCHEDULES OR PLANS FOR VOLTAGE AND PHASING INFORMATION.
4. REDUNDANT UNIT.
TAG MAX
SYSTEM
AND/OR
SERVICE MIN
CORR 1ST FLR 750 225 160B32-VAV-1
MAX APD
(IN WG)
0.9 180 4
225 160180
VAV TERMINAL UNIT SCHEDULE (VAV-)
AIR FLOW (CFM) LAT
0.4
0.4
°F
EAT
°F
TOTAL MIN
CAPACITY
(MBH)
8.6
8.6
FLOW
(GPM)
0.9
EWT
(°F)
LWT
(°F)
MAX WPD
(FT)
PIPE RUNOUT SIZE
(IN)
3/4
3/4
REMARKS
B32-VAV-2
B32-VAV-3
B32-VAV-4
B32-VAV-5
B32-VAV-6
B32-VAV-7
CORR 2ND FLR
STAIRWAY
STORAGE
TRAMWAY
COMPUTER
MECHANICAL RM
3/4
1800 540
255 0.4
0.4
0.4
0.4
0.4
9.7
12.0
10.3
10.3
20.5 2.1
1.0
1.0
1.0
1.2
3/4
3/4
3/4
3/4
NOTES: 1. SEE DETAILS 11/M502 FOR INSTALLATION INFORMATION
2. PROVIDE VAV BOXES WITH MINIMUM 25% ADDITIONAL CAPACITY ABOVE THE MAX CFM
3. BASIS OF DESIGN: TITUS MODEL DESV OR APPROVED EQUAL.
4. VAV BOXES TO HAVE DDC CONTROLLER.
5. VAV BOXES ARE TO BE FED FROM LOW (CONTROL) VOLTAGE POWER ONLY.
SD-1
NOTES:
1. SEE PLAN FOR AIRFLOW AND NECK SIZE. RUN OUT BE SAME SIZE AS NECK SIZE.
SUPPLY DIFFUSER, 24" x 24", 4 WAY DEFLECTION, LOUVERED, ADJUSTABLE 20 0.05
SD-2
GRILLES, REGISTERS, AND DIFFUSERS SCHEDULE (SD-,RG-)
TAG DESCRIPTION
MAX NOISE
(NC) MATERIAL
SG-3
RG-1
SUPPLY GRILLE, DOUBLE DEFLECTION, 3/4" SPACING, ADJUSTABLE
SUPPLY GRILLE, NOZZLE DIFFUSER, HIGH CAPACITY, APERTURE DAMPER
RETURN EGGCRATE, 1/2" X 1/2" X 1" DEEP CORE, PLENUM BOX
0.05
0.05
MAX NOISE
(IN WG)
ALUMINUM
ALUMINUM
ALUMINUM
20 0.05 ALUMINUM
FINISH MOUNTING NOTES
WHITE LAY-IN
SURFACE
SURFACE
SURFACE
WHITE
WHITE
WHITE
(1) (2)
(1) (2)
(1) (2)
(1) (2)
MECH RM
TAG SERVES
FAN
AIR COOLED CONDENSER SCHEDULE (ACCU-)
B32-ACCU-5 B32-AHU-1 4
COMP
QTY
2.0
ENT AIR
TEMP
(DEG F)
95.0
REFRIG.
CIRCUITS
(NO.)
FLUID
TYPE
R410A
NOTES:
LOCATION REMARKS
(1) (2)
1. BASIS OF DESIGN: JCI J25YC OR APPROVED EQUAL.
2. PROVIDE LOW AMBIENT TEMP CONTROL, CIRCUIT BREAKER/DISCONNECT, BACNECT CONTROLLER, HOT GAS BYPASS, COIL GUARD.
CAPACITY
TON
25.0ROOF 0.75
NO. HP
CONDENSATE PUMP SCHEDULE (CP-)
LOCATIONTAG
B32-CP-1 3
PUMP
208/3
REMARKS
NOTES:
1. BASIS OF DESIGN: BELL & GOSSETT, MODEL 1123 WITH CAST IRON SUMP. SEE DETAIL 1/M503.
CONTROL PANEL TO BE FIELD INSTALLED BY CONTRACTOR. COORDINATED WITH ELECTRICAL FOR POWER CONNECTION.
B32-CP-2
BASEMENT MECH RM
QTY
FLOW
(GPM)
PRESS
(PSIG)
SIZE
(HP)
RECEIVER
CAPACITY
(GALLONS)
VOLTS/
PHASE
3 208/32 160 30 120MECH RM
2.
STEAM PRESSURE REDUCING VALVE SCHEDULE (PRV-)
LOCATIONTAG
B32-PRV-1
REMARKS
NOTES:
1. PROVIDE 1/3 AND 2/3 VALVE ASSEMBLY.
SEE DETAIL 2/M503.
MECH RM
CAPACITY
(LB/HR)
2.
INLET
PRESSURE
(PSIG)
OUTLET
PRESSURE
(PSIG)
(1) (2)
(1) (2)
(1) (2)
B32-PRV-2 MECH RM 150100 15 (1) (2)
STEAM TRAP SCHEDULE (ST-)
TYPETAG
B32-ST-1
REMARKS
NOTES:
1. SEE DETAIL 3 &4/M502.
F&T
CONN SIZE
(IN)
STEAM
PRESSURE
(PSIG)
CONDENSATE
LOAD
(LB/HR)
501 (1)
B32-ST-2 F&T 115 501 (1)
B32-ST-3 INVERTED BUCKET 3/4125 9 (1)
B32-ST-4 F&T 3/415 2 (1)
B32-ST-5 F&T 3/415 2 (1)
B32-ST-6 INVERTED BUCKET 3/4125 9 (1)
SERVICE
LPS HX-1
LPS HX-2
HPS END OF MAIN
LPS END OF MAIN
LPS HUMIDIFIER
HPS INLINE
TAG SERVES
(IN.
W.G.)
INTAKE HOOD SCHEDULE (IH-)
B32-IH-1 INTAKE 0.1
APD
(FPM)
300.0
VEL.
INTAKE
MATERIAL
ALUM
NOTES:
LOCATION
7,000.0
CFM REMARKS
(1) (2)
1. BASIS OF DESIGN IS FABRA HOOD MODEL FGI OR APPROVED EQUAL.
2. PROVIDE ALUMINUM CONSTRUCTION, MOTORIZED DAMPER, ALUMINUM INSECT SCREEN, 18” ROOF CURB, FACTORY APPLIED ½” INSULATION
SIZE
(IN X IN)
30X60MECH RM
TAG (PSI)
HUMIDIFIER SCHEDULE (H-)
B32-H-1 15
ENT PRESS
(LB/HR)
CAPACITY
(F)
NOTES:
LOCATION
DUCT MOUNTED
TYPE REMARKS
(1)
1. BASIS OF DESIGN: ARMSTRONG MODEL HUMIDCLEAN DL SERIES OR APPROVED EQUAL. SEE DETAIL 2/M502.
AIRFLOW
(CFM)
7000MECH RM
(%RH)
EAT DB LAT
TAG
DESIGN
(PSI)
EXPANSION TANK SCHEDULE (ET-)
B32-ET-1 12
OPER PRESS
135 30
NOTES:
LOCATION
HW SYSTEM
TYPE REMARKS
(1) (2)
1. BASIS OF DESIGN: BELL & GOSSET, MODEL B SERIES OR APPROVED EQUAL. SEE DETAIL 4/M503.
2. BLADDER TYPE VERTICAL EXPANSION TANK.
SYSTEM
VOLUME
(GAL)
400MECH RM 180 200
(%RH)
LAT
TANK
VOLUME
(GAL)
MAX
(PSI)
DESIGN
(F)
OPER TEMP
MAX
(F)
2.
FLA
HP
AMB
ELECTRICAL
V/PH/HZ FLA MCA MOP
87 97 125208/3/60
82.0 3120 8,000 7.5 0.5 266.5 80.0 67.0 55.0 54.0 8
82.0 3120 8,000 7.5 0.5 266.5 80.0 67.0 55.0 54.0 8
82.0 3120 8,000 7.5 0.5 266.5 80.0 67.0 55.0 54.0 8
95 7.5 (2) 5/8 (2) 1-3/8 0.75 0.25232 87 97 125208/3/60
95 7.5 (2) 5/8 (2) 1-3/8 0.75 0.25232 87 97 125208/3/60
95 7.5 (2) 5/8 (2) 1-3/8 0.75 0.25232 87 97 125208/3/60
B32-ACCU-2
B32-ACCU-3
B32-ACCU-4
RG-2 RETURN/EXHAUST GRILLE, 45" DEFLECTION, 3/4" SPACING 20 0.05 ALUMINUM SURFACE WHITE (1) (2)
MCA
21.9
MOP
CIRCUIT #1 DATA
FLA MCA
MOP
CIRCUIT #2 DATA
-120/1/60
V/PH/HZMBHMBH
WEIGHTMOTOR
EFF
67%
61%
MOTOR
EFF
61%
45%
EER
10.2
MIN.
COP
2.33
2.33
2.33
2.33
OA
ENERGY RECOVERY COIL SCHEDULE (ERC-)
SYSTEMTAG
B32-ERC-1
B32-ERC-2 EA
AIRFLOW
(CFM)
REMARKS
(1) (2) (3)
(1) (2) (3) (4)
NOTE:
1. BASIS OF DESIGN:GREENHECK OR APPROVED EQUAL.
2. SEE DETAIL 1/M502.
3. CONTROL POINTS TO BE INTEGRATED WITH BAS.
FACE VEL
(FPM)
FLUID TYPE
50% PG
MBH
EAT
F
-20
LAT
F
4.8
CAPACITY - WINTER
AIR PD
(IN WG)
0.2
WATER PD
(FT)
FLOW
GPM
ROWS
HEIGHT
(IN)
WIDTH
(IN)
FPI
MERV
APD
0.50
COIL DATA FILTER DATA
350 50% PG 56 70 57 0.2 15 25 3 24 36 10 8
B32-ST-7 INVERTED BUCKET 3/4125 9 (1)HPS END OF MAIN
B32-ST-8 INVERTED BUCKET 3/4125 9B32-PRV-1
B32-ST-9 INVERTED BUCKET 3/4125 9B32-PRV-1
B32-ST-10 INVERTED BUCKET 3/4125 9B32-PRV-2
B32-ST-11 INVERTED BUCKET 3/4125 9B32-PRV-2
(1) (3)
(1) (3)
(2) (3)
3770 S. PENNSYLVANIA AVENUE, UNIT 8
ST. FRANCIS, WISCONSIN 53235
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked By
Building Number
Project Number
Drawing Number
Drawn By
PROJECT LEADER:
Department of
Veterans Affairs
CONSULTANTS:
o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t
VA FORM 08-6231, OCT 1978
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
Office of Facilities
Management
B
A
C
D
E
F
97 8654321
F
E
D
C
B
A
1 2 3 4 5 6 87 9
FULLY SPRINKLEREDFULLY SPRINKLERED
EHRM INFRASTRUCTURE
UPGRADES TIER 2
VA MEDICAL CENTER TOMAH, WI
FEB. 4, 2022 HFB JMD
M601M601
FINAL BID DOCUMENTS
676-21-701MECHANICAL
SCHEDULES
1 NTS
VARIABLE AIR VOLUME AIR HANDLING UNIT WITH MINIMUM OUTSIDE AIR CONTROL DIAGRAM (B32-AHU-1)
2 NTS
POINTS LIST FOR VAV AIR HANDLING UNIT WITH MINIMUM OUTSIDE AIR
B32-AHU-1 MINIMUM POINTS LIST
T-1
OAT
DP-3
T-3
MAT
PF DX CC
S
S RL
RL
RS
RS
HC
HWS
HWR
SF
DP-4
FF
SA
VFD
OA
B32-ERC-1
B32-ERC-2
Output Input Virtual Local Controller BAS Full BAS IntegrationDigital Analog Digital Analog Digital Analog Visible Adjustable Overridable Visible Adjustable Overridable
SF Command X X X X X
SF Status X
SF Speed Command X X X X X
SF VFD X
SF VFD Fault X X
T-1 (OAT) X X X
T-2 (after ERC-1) X X X
T-3 (MAT) X X X
T-4 (after cooling coil) X X X
T-5 (after heating coil) X X X
T-7 (RAT) X X X
H-2 (discharge air humidity) X X X
H-3 (return air humidity) X X X
DP-1 (ERC-1 filter) X X X
DP-2 (ERC-2 filter) X X X
DP-3 (pre filter) X X X
DS-4 (final filter) X X X
OAD Command X X X X X
OAD Status X X X
EAD Command X X X X
EAD Status X X X
HCV-1 Command (heating coil) X X X X X
HCV-1 Status (heating coil) X X X
CV-1 Command (cooling coil) X X X X X
CV-1 Status (cooling coil) X X X
HV-1 Command (humidifier) X X X X X
HV-1 Status (humidifier) X X X
Temperature Low Limit (TLL) X X X
Smoke Detector (SD Supply) X X X
Smoke Detector (SD Return) X X X
Pressure Switch High (PSL) X X X
Shutdown Switch X X X
BAS Enable/Disable X X X X X
Supply Duct Press P-1 X X X X X X
Return Duct Press P-2 X X X X X X
X
Cooling OA Lockout SP (T-1) X X X X X X
Heating OA Lockout SP (T-1) X X X X X X
MAT SP (T-3)
MAT F/B SP (T-3)
DAT SP (T-9) X X X X X X
DAH SP (H-1) X X X X X X
Zone High Limit Humidity SP (H-2)
Humidifier Lockout SP (H-1) X X X X X X
DA Humid SP X X X X X X
Humidity Switch High (HSL) X X X
SENSOR LOCATED
OUTSIDE UNDER
SHIELD
GENERAL:
1. B32-AHU-1 SHALL BE CONTROLLED BY THE ECC AND PROVIDED WITH A GRAPHICAL LOCAL CONTROL PANEL PROVIDING SYSTEM AND EQUIPMENT STATUS, SETPOINT AND ALARM POINT ADJUST, AND ALARMS. CONTRACTOR SHALL VERIFY EXISTING ECC IS CAPABLE OF THE NEW CONTROLS FOR 451-AHU-1 , 452-EF-1, AND ALL CONTROLS
NOTED ON THE DRAWING SET AND SPECIFICATIONS.
2. 452-AHU-1 SUPPLY FAN IS STARTED AND STOPPED REMOTELY FROM THE ECC. H-O-A SWITCHES SHALL BE KEPT IN THE AUTO POSITION. HAND AND OFF POSITIONS SHALL BE USED ONLY FOR MAINTENANCE. WHEN THE UNIT IS OFF THE OA AND EA DAMPERS SHALL BE FULLY CLOSED, VEFIRIED BY DAMPER END SWITCHES; ALARM IF NOT FULLY CLOSED. WHEN THE UNIT IS ON THE OA AND EA DAMPERS SHALL FULLY OPEN, VERIFIED BY DAMPER END SWITCHES; ALARM IF NOT FULLY OPEN.
3. UPON RECEIPT OF START COMMAND, ECC SHALL ENERGIZE OA AND EA DAMPERS, ONCE OA AND EA DAMPERS ARE PROVEN FULL OPEN VIA THEIR END SWITCHES, THE SUPPLY AND EXHAUST FANS SHALL START AND RAMP TO SPEED, COMING UNDER CONTROL BASED ON DUCT STATIC PRESSURE.
4. SUPPLY FAN OPERATION SHALL BE VERIFIED THROUGH VFD, PROVIDE ALARM AT ECC AND LOCAL CONTROL PANEL SHOULD FAN OPERATION NOT BE VERIFIED WHEN
CONTROL SYSTEM CALLS FOR FAN OPERATION.
5. ENERGY RECOVERY HEAT LOOP SHALL BE VERIFIED OPERATIONAL THROUGH DETERMINING THAT AHU-1 AND EF-1 ARE OPERATING; PROVIDE ALARM AT ECC AND LOCAL CONTROL PANEL SHOULD IT BE DETERMINED AHU-1 IS OFF. NORMAL OPERATION IS WHEN BOTH EXHAUST AND OUTDOOR AIR PASSING THROUGH THE ENERGY RECOVERY
HEAT LOOP.
6. ANY TIME THE AIR HANDLER IS INDEXED OFF, THE SUPPLY FAN SHALL STOP. IN ADDITION, WHENEVER THE AIR HANDLER IS OFF THE FOLLOWING SHALL OCCUR:
• OUTSIDE AND EXHAUST AIR DAMPERS SHALL CLOSE AND BE VERIFIED CLOSED.
• DX COOLING COIL CONTROL VALVES SHALL CLOSE AND BE VERIFIED SHUT.
• AIR COOLED CONDENSING UNIT SHALL SHUT DOWN AND BE VERIFIED SHUT.
• HEATING COIL CONTROL VALVES SHALL REMAIN UNDER DISCHARGE AIR TEMPERATURE CONTROL.
7. AIR HANDLING SYSTEM SHALL OPERATE CONTINUOUSLY WHENEVER THE BUILDING IS SCHEDULED FOR OCCUPANCY BY THE ECC. DURING UNOCCUPIED PERIODS SYSTEM SHALL BE CAPABLE OF OPERATING AT TEMPERATURE SETPOINTS SELECTED TO REDUCE OPERATING COST AND AT REDUCED AIRFLOWS AS LONG AS PRESSURE
RELATIONSHIPS ARE MAINTAINED.
8. DURING SCHEDULED UNOCCUPIED PERIODS THE MOTION SENSOR SHALL START THE AHU AND ASSOCIATED EQUIPMENT FOR 2 HRS, THEN RETURN TO UNOCCUPIED
MODE.
AHU SUPPLY AIR TEMPERATURE / HUMIDITY CONTROL:
1. SETPOINTS AND ALARM POINTS SHALL BE ADJUSTABLE THROUGH AND OUTPUT FROM ECC.
2. PROVIDE CHANGES TO ECC TO HAVE THE ABILITY TO MAKE SETPOINT POINT, ALARM POINT, AND STATUS.
3. AIR HANDLING SYSTEM SHALL OPERATE AT CONSTANT VOLUME AIR FLOW AIR HANDLING UNIT DISCHARGE AIR TEMPERATURE SHALL BE MAINTAINED AT THE HIGHEST TEMPERATURE POSSIBLE TO MINIMIZE HEAT REQUIREMENTS OF ZONE VALVES, ZONE HEAT VALVE SHALL BE MONITORED FOR POSITION WITH THE INTENT OF HAVING AT
LEAST ONE ZONE OPERATING WITHOUT THE NEED FOR ZONE HEAT.
4. SIMULTANEOUSLY, RETURN AIR HUMIDITY SHALL BE MONITORED. SHOULD RETURN AIR RELATIVE HUMIDITY RISE TO EQUIVALENT OF 50% RH AT 75 DEG F (ADJUSTABLE) CONTROL SYSTEM SHALL PROVIDE ADDITIONAL DX COOLING AS REQUIRED TO REDUCE RETURN AIR RH IN SUMMER MODE.
5. ZONE HEAT COILS SHALL PROVIDE HEAT TO SPACE TEMPERATURE SETPOINT. SHOULD ALL ZONES BE CALLING FOR HEAT, AND RETURN AIR HUMIIDITY IS ACCEPTABLE, REDUCE DX COOLING AND INCREASE AIR HANDLING UNIT LEAVING AIR TEMPERATURE USING PREHEAT COIL, UNTIL AT LEAST ONE ZONE COIL IS NOT CALLING FOR HEAT
AND RETURN AIR RH IS WITHIN SPECIFIED RANGE.
6. SUPPLY AIR TEMPERATURE SHALL BE MAINTAINED AT SETPOINT 55 DEG F (ADJUSTABLE) VIA ECC.
7. ALARM AT 5 DEG F (ADJUSTABLE) ABOVE SUMMER AND BELOW WINTER SETPOINTS.
8. SUPPLY AIR RH IN SUPPLY DUCT, SHALL BE THAT REQUIRED TO MAINTAIN REQUIRED RETURN AIR RH BETWEEN MAXIMUM AND MINIMUM VALUES OF 50% RH SUMMER AND 30% RH WINTER (BOTH ADJUSTABLE) VIA ECC BY CONTROLLING THE NUMBER OF STAGES OF DX COOLING OPERATING FOR DEHUMIDIFICATION AND MODULATING THE
STEAM DISPERSION TUBE STEAM CONTROL VALVE TO PROVIDE HUMIDIFICATION.
9. REFER TO STEAM HUMIDIFIER CONTROL SEQUENCE.
10. ALARM AT 5% RH (ADJUSTABLE) ABOVE SUMMER AND BELOW WINTER SETPOINTS AS DETERMINED BY MONITORING OF EXHAUST AIR RH.
FREEZE PROTECTION:
1. SETPOINTS AND ALARM POINTS SHALL BE ADJUSTABLE THROUGH AND OUTPUT FROM ECC.
2. PROVIDE CHANGES TO ECC TO HAVE THE ABILITY TO MAKE SETPOINT POINT, ALARM POINT, AND STATUS.
3. IF THE SUPPLY AIR TEMPERATURE AS SENSED DOWNSTREAM OF THE HEATING COIL FALLS BELOW 40 DEG F (ADJUSTABLE) AN ALARM SIGNAL SHALL BE INITIATED BY THE
ECC.
ENERGY RECOVERY SYSTEM CONTROL:
DURING NORMAL OPERATION:
1. WINTER - START B32-P-2 WITH B32-AHU-1 SUPPLY FAN. PUMP RUNS CONTINUOUSLY. 3-WAY VALVE MODULATES TO MAINTAIN HIGHEST OA TEMP ACROSS B32-ERC-1 WHILE MAINTAINING 50/50 GLYCOL SOLUTION TEMPERATURE TO B32-ERC-1 GREATER THAN OR EQUAL TO 35F.
2. SUMMER - START B32-P-2 WITH B32-AHU-1 SUPPLY FAN. PUMP RUNS CONTINUOUSLY. 3-WAY VALVE MODULATES TO MAINTAIN LOWEST OA TEMP ACROSS B32-ERC-1.
3. OA TEMP - B32-P-2 OPERATES WHEN OAT IS 50F OR LESS AND WHEN OAT IS 68F OR HIGHER.
DURING NIGHT SETBACK:
1. B32-P-2 STOPS WHEN B32-AHU-1 STOP.
SEE CONTROL DIAGRAM DETAIL 3 ON SHEET M702.
ECONOMIZER MODE: BELOW 55°F OA TEMP
1. THE DA TEMP CONTROL LOOP SHALL MODULATE THE ECONOMIZER TO MAINTAIN DA TEMP SETPOINT. A MIXED AIR LO LIMIT LOOP SHALL PREVENT THE MA TEMP FROM DROPPING BELOW THE MA SETPOINT. THE MA SETPOINT SHALL BE THE SAME AS THE DA SETPOINT MINUS 2°F (ADJ.) IF THE UNIT DOES NOT HAVE A PREHEAT COIL THE MIXED AIR LO LIMIT LOOP SHALL BE CAPABLE OF OVERRIDING THE MINIMUM POSITION. THIS IS TO PREVENT THE UNIT FROM TRIPPING OFF ON THE LOW LIMIT SAFETY.
2. THE MINIMUM POSITION SHALL NOT BE OVERRIDDEN BY THE MIXED AIR LO LIMIT LOOP. THE PREHEATING COIL WILL MODULATE TO MAINTAIN THE PH TEMP AT THE PREHEAT SETPOINT. THE PH TEMP SETPOINT SHALL BE THE SAME AS THE MA TEMP SETPOINT MINUS 2°F (ADJ.) THE CONTROL LOOP SHALL BE SEQUENCED SO THAT THE
ECONOMIZER IS AT MINIMUM POSITION BEFORE THE PREHEAT VALVE IS OPENED.
3. COOLING COIL WILL BE LOCKED OUT BELOW 60°F OD TEMP
4. HEATING COIL WILL BE LOCKED OUT. ABOVE 50°F OD TEMP
DX COIL CONTROL:
1. SETPOINTS AND ALARM POINTS SHALL BE ADJUSTABLE THROUGH AND OUTPUT FROM ECC. PROVIDE CHANGES TO ECC TO HAVE THE ABILITY TO MAKE SETPOINT POINT, ALARM POINT, AND STATUS.
2. DX COOLING COIL SHALL OPERATE THROUGH COMPRESSOR STAGING AS REQUIRED TO MAINTAIN LEAVING AIR TEMPERATURE CONTROL.
3. PROVIDE MINIMUM FOUR 25% STEPS (ADJUST BASED ON COMPRESSOR STAGING) OF DX COOLING SHALL BE USED TO MAINTAIN AIR HANDLING UNIT LEAVING AIR
TEMPERATURE CONTROL.
4. CONTROL SYSTEM SHALL VERIFY AIR HANDLING SYSTEM SUPPLY FAN IS OPERATING PRIOR TO ENERGIZING DX SYSTEM COMPRESSORS.
5. DX COOLING SYSTEM SHALL BE PROVIDED WITH FROST STAT TO MONITOR DX COIL TEMPERATURE OR SUCTION LINE TEMPERATURE AND TEMPORARILY (ADJUSTABLE TIME) TURN OFF COMPRESSOR TO ALLOW DX COIL TO WARM SHOULD IT BE DETERMINED THAT OPERATING CONDITIONS ARE SUCH THAT THERE IS POTENTIAL FOR
EVAPORATOR FROSTING.
6. COOLING COIL WILL BE LOCKED OUT BELOW 60°F OD TEMP
HEAT COIL CONTROL:
1. SETPOINTS AND ALARM POINTS SHALL BE ADJUSTABLE THROUGH AND OUTPUT FROM ECC. PROVIDE CHANGES TO ECC TO HAVE THE ABILITY TO MAKE SETPOINT POINT, ALARM POINT, AND STATUS.
2. WHEN THERE IS A CALL FOR HEATING AND WHEN THE OUTDOOR AIR TEMPERATURE IS BELOW 45 DEG F (ADJUSTABLE) HEATING FLUID SHALL CIRCULATE CONSTANTLY
THROUGH THE HEAT COIL.
3. HEATING COIL WILL BE LOCKED OUT ABOVE 50°F OD TEMP.
STEAM HUMIDIFIER CONTROLS:
1. RETURN (OR EXHAUST) AIR HUMIDITY SHALL BE MONITORED.
2. ON A CALL FOR HUMIDIFICATION, HUMIDIFIER VALVE HV-1 SHALL MODULATE TO MAINTAIN THE RETURN AIR HUMIDITY SET POINT TO 30% (ADJUSTABLE). .
3. THE HIGH LIMIT HUMIDITY SENSOR, LOCATED IN THE SUPPLY AIR DUCT SHALL DISABLE THE HUMIDIFIER AND GIVE AN ALARM SIGNAL TO THE ECC, IF THE SUPPLY AIR
HUMIDITY EXCEEDS 60% RH (ADJUSTABLE).
4. THE AIRFLOW SWITCH SHALL PROVE AIRFLOW BEFORE HUMIDITY CONTROLS ARE ACTIVATED.
SEE CONTROL DAIGRAM DETAIL 1 ON SHEET M702.
FILTERS:
1. SETPOINTS AND ALARM POINTS SHALL BE ADJUSTABLE THROUGH AN OUTPUT FROM ECC
2. THE AHU IS PROVIDED WITH TWO PREFILTERS AND AN AFTER FILTER.
3. ALL FILTER SHALL BE PROVIDED WITH DIFFERENTIAL PRESSURE SENSING, PROVIDING INDIVIDUAL FILTER BANK PRESSURE LOSS.
4. ECC SHALL PROVIDE CALL FOR FILTER CHANGE AT FILTER DIFFERENTIAL PRESSURE OF 0.75" WATER GAGE (ADJUSTABLE)
5. DATE OF FILTER CHANGE TO BE INPUT FROM LOCAL CONTROL PANEL. ECC TO MAINTAIN AND PROVIDE DATES OF LAST FOUR FILTER CHANGES WITH INFORMATION
AVAILABLE AT LOCAL CONTROL PANEL.
6. PROVIDE IN-SERVICE SWITCH AT LOCAL CONTROL PANEL FOR FILTER REPLACEMENT OF B32-AHU-1 ERC'S. IN-SERVICE "OFF" B32-AHU-1 OPERATE AS NOTED. IN-SERVICE "ON" B32-AHU-1 STOP. ALL SEQUENCES FOR BOTH UNITS SHUTTING DOWN SHALL OCCUR. THE REVERSE SHALL OCCUR WHEN IN-SERVICE SWITCH IS TURNED TO "OFF"
POSITION.
AHU AIR FLOW CONTROL:
1. SETPOINTS AND ALARM POINTS SHALL BE ADJUSTABLE THROUGH AND OUTPUT FROM ECC.
2. PROVIDE CHANGES TO ECC TO HAVE THE ABILITY TO MAKE SETPOINT POINT, ALARM POINT, AND STATUS.
3. AHU SUPPLY AIR FLOW SHALL BE CONTROLLED BY THE ECC. ECC SHALL MODULATE THE SUPPLY FAN VFD TO MAINTAIN 2.0" OF DUCT STATIC PRESSURE (ADJUSTABLE) AS SENSED BY DUCT STATIC PRESSURE SENSOR. DUCT STATIC PRESSURE SENSOR SETPOINT TO BE DETERMINED DURING T&B WORK FOR MINIMUM DUCT PRESSURE LOSS;
CRITICAL SPACE DUCT DAMPER FULL OPEN.
4. EXHAUST AIR FLOW SHALL BE CONTROLLED BY THE ECC. ECC SHALL MODULATE THE EXHAUST DAMPER TO MAINTAIN 0.75" OF DUCT STATIC PRESSURE (ADJUSTABLE) AS SENSED BY DUCT STATIC PRESSURE SENSOR. DUCT STATIC PRESSURE SETPOINT TO BE DETERMINED DURING T&B WORK FOR MINIMAL DUCT PRESSURE LOSS; CRITICAL
SPACE DUCT DAMPER FULL OPEN.
5. USING HIGH LIMIT DUCT PRESSURE SENSOR LOCATED IN THE SUPPLY AIR DISCHARGE ABOUT 6 FEET DOWNSTREAM FROM AHU, ECC SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 2" OF STATIC PRESSURE (ADJUSTABLE). IF THE STATIC PRESSURE AT HIGH LIMIT DOES EXCEED 2" THE SUPPLY AIR FAN SHALL STOP AND ECC SHALL ALARM, INCLUDING AT LOCAL CONTROL PANEL. HIGH LIMIT SHALL BE HARDWIRED TO THE SUPPLY FAN VFD. FAN SHALL SHUTDOWN IN HAND, AUTO, OR BYPASS
MODE. HIGH LIMIT SHALL REQUIRE MANUAL RESET AT THE DEVICE.
6. USING THE LOW LIMIT DUCT PRESSURE SENSOR LOCATED IN THE EXHAUST AIR DUCT ABOUT 6 FEET UPSTREAM OF EXHAUST DAMPER (BETWEEN ENERGY RECOVERY HEAT EXCHANGER AND EXHAUST FAN) ECC SHALL PREVENT THE EXHAUST FAN FROM DEVELOPING OVER 2.0" OF STATIC (FIELD ADJUSTABLE) IF STATIC PRESSURE AT LOW LIMIT DOES EXCEED -1.0" THE EXHAUST AIR FAN SHALL STOP AND ECC SHALL ALARM, INCLUDING AT LOCAL CONTROL PANEL. HIGH LIMIT SHALL BE HARDWIRED TO THE EXHAUST FAN VFD. FAN SHALL SHUTDOWN IN HAND, AUTO OR BYPASS MODE. HIGH LIMIT SHALL REQUIRE MANUAL RESET AT THE DEVICE.
EMERGENCY CONSTANT SPEED OPERATION:
1. UPON FAILURE OF THE VFD, THE SUPPLY AND EXHAUST FANS SHALL BE STARTED/STOPPED MANUALLY AT THE ECC THROUGH THE VFD BYPASS STARTER. FANS SHALL
THEN BE OPERATED AT CONSTANT SPEED.
SMOKE DETECTION SHUTDOWN/RESTART:
1. WHEN SMOKE IS DETECTED BY SUPPLY OR RETURN AIR SMOKE DETECTORS, THE SUPPLY FAN SHALL SHUT OFF AND AN ALARM SHALL BE TRANSMITTED TO THE FIRE
ALARM SYSTEM.
2. SMOKE DETECTOR SHALL BE HARDWIRED TO THE SUPPLY FAN VFD AND TO SHUTDOWN IN HAND, AUTO, OR BYPASS MODE. SMOKE DETECTORS SHALL REQUIRE MANUAL
RESET AT THE DEVICE.
FIRE ALARM SHUTDOWN/RESTART:
1. UPON FIRE ALARM SYSTEM ALARM, AIR HANDLING UNIT SHALL SHUT DOWN AS DESCRIBED ABOVE IN SMOKE DETECTOR SHUTDOWN.
2. ECC SHALL BE PROVIDED WITH INPUT FROM FIRE ALARM SYSTEM USED TO NOTIFY ECC THAT FIRE ALARM CONDITION EXISTS.
RA
H-2 T-9 P-1
B32-H-1
LPS
H-1T-5T-4
T-8
DP-1
PF
DP-2
PF
M
M
HV-1
OAD
EAD
LOCATE 2/3rd
DOWN DUCT
T-6 (after SF) X X X
T-8 (after ERC-2) X X X
LPR
HCV-1
T-7
B32-P-2
T-2
SD
SD
CV-1
CV-2
CV-2 Command (cooling coil) X X X X X
CV-2 Status (cooling coil) X X X
EA
MMAD
AFMS-2
NO
NC
NC H-3
AFMS-1
ECV-1
T-9 (discharge air temperature) X X X
MAD Command X X X X
MAD Status X X X
X
X
EHV-1 Command (energy recovery) X X X X X
EHV-1 Status (energy recovery) X X X
AFMS-1 Status (SF) X X X
AFMS-2 Status (OA) X X X
P-2
T-6 HSH PSH
H-1 (inlet air humidity) X X X
3770 S. PENNSYLVANIA AVENUE, UNIT 8
ST. FRANCIS, WISCONSIN 53235
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked By
Building Number
Project Number
Drawing Number
Drawn By
PROJECT LEADER:
Department of
Veterans Affairs
CONSULTANTS:
o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t
VA FORM 08-6231, OCT 1978
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
Office of Facilities
Management
B
A
C
D
E
F
97 8654321
F
E
D
C
B
A
1 2 3 4 5 6 87 9
FULLY SPRINKLEREDFULLY SPRINKLERED
EHRM INFRASTRUCTURE
UPGRADES TIER 2
VA MEDICAL CENTER TOMAH, WI
FEB. 4, 2022 HFB JMD
M701M701
FINAL BID DOCUMENTS
676-21-701MECHANICAL
CONTROL DIAGRAMS
1 NTS
STEAM HUMIDIFIER CONTROL
DIAGRAM (B32-H-1)
2 NTS
VAV REHEAT CONTROL DIAGRAM
CONTROLLER/ACTUATOR
VAV DAMPER
CONTROL POINT
DESCRIPTION
VELOCITY SENSOR
SPACE THERMOSTAT
CONTROL
POINT
SEQUENCE OF OPERATION:
DURING NORMAL OPERATION:
THE SPACE THERMOSTAT CONTROLS THE MODULATING HOT WATER CONTROL VALVE AND
THE VOLUME DAMPER TO MAINTAIN THE SPACE TEMPERATURE SETPOINT OF 68 DEG. F.
DURING NIGHT SETBACK:
OPERATION THE SPACE THERMOSTAT CONTROLS THE MODULATING HOT WATER CONTROL
VALVE AND THE VOLUME DAMPER TO MAINTAIN THE SPACE TEMPERATURE SETPOINT OF 55
DEG. F.
HWR
HWS
OUTLET
HW
COIL
INLET
3 2
2-WAY CONTROL VALVE
SUPPLY AIR
STEAM SUPPLY
RETURN OR
EXHAUST AIR
PC
SEQUENCE OF OPERATIONS:
• RETURN (OR EXHAUST) AIR HUMIDITY SHALL BE MONITORED.
• ON A CALL FOR HUMIDIFICATION, HUMIDIFIER VALVE V-1 SHALL MODULATE TO MAINTAIN THE RETURN (OR EXHAUST) AIR HUMIDITY SET POINT TO 30% (ADJUSTABLE). PRIOR TO ACTIVATION OF
V-1, THE ON/OFF CONTROL VALVE V-2 SHALL BE ENABLED THROUGH ECC AND JACKET
TEMPERATURE SENSED BY TSH SHALL BE WARM ENOUGH TO PREVENT CONDENSATION.
• THE HIGH LIMIT HUMIDITY SENSOR, LOCATED IN THE SUPPLY AIR DUCT 10 FEET AWAY FROM THE HUMIDIFIER SHALL DISABLE THE HUMIDIFIER AND GIVE AN ALARM SIGNAL TO THE ECC, IF THE
SUPPLY AIR HUMIDITY EXCEEDS 90% RH (ADJUSTABLE).
• THE AIRFLOW SWITCH SHALL PROVE AIRFLOW BEFORE HUMIDITY CONTROLS ARE ACTIVATED.
TSH
MODULATING
CONTROL VALVE
RAH
ZC
AFS HHL
V-1
STEAM JACKET
AIRFLOW
SWITCH
HIGH HUMIDITY
LIMIT SWITCH
RETURN AIR
HUMIDITY
ZONE
CONTROL
PROGRAMMABLE
CONTROLLER
STEAM
CONDENSATE
TEMPERATURE
SENSOR
CONTROL VALVE
AND STEAM
SEPARATOR
3 NTS
ENERGY RECOVERY SYSTEM
CONTROL DIAGRAM
TEMPERATURE TRANSMITTER
DIFFERENTIAL PRESSURE TRANSMITTER
CONTROL POINT
DESCRIPTION
TEMPERATURE TRANSMITTER
PUMP START/STOP
CONTROL
POINT
SEQUENCE OF OPERATION:
DURING NORMAL OPERATION:
• WINTER - START B32-P-2 WITH B32-AHU-1 SUPPLY FAN. PUMP RUNS CONTINUOUSLY. 3-WAY VALVE MODULATES TO
MAINTAIN HIGHEST OA TEMP ACROSS B32-ERC-1 WHILE MAINTAINING 50/50 GLYCOL SOLUTION TEMPERATURE TO B32-
ERC-1 GREATER THAN OR EQUAL TO 35F.
• SUMMER - START B32-P-2 WITH B32-AHU-1 SUPPLY FAN. PUMP RUNS CONTINUOUSLY. 3-WAY VALVE MODULATES TO
MAINTAIN LOWEST OA TEMP ACROSS B32-ERC-1.
• OA TEMP - B32-P-2 OPERATES WHEN OAT IS 50F OR LESS AND WHEN OAT IS 68F OR HIGHER.
DURING NIGHT SETBACK:
• B32-P-2 STOPS WHEN B32-AHU-1 STOP.
DIFFERENTIAL PRESSURE TRANSMITTER
B32-P-2
B32-ERC-1
COIL
B32-ERC-2
COIL
DP-X
TT
DP-X
T
3-WAY
MODULATING
VALVE
TT
EXHAUST
SUPPLY
SEQUENCE OF OPERATION
OA VENTILATION DAMPERS SHALL OPEN, AND EXHAUST FAN RUNS
CONTINUOUSLY WHEN SPACE IS ABOVE 80°F. OA VENTILATION
DAMPERS CLOSE AND FAN SHUTS OFF WHEN ATTIC SPACE IS 80°F OR
BELOW.
EXH.EXH.
BACKDRAFT DAMPER3
CURRENT SENSOR
FAN START/STOP
POINT
CONTRO
DESCRIPTION
EXHAUST
FAN
4 EXHAUST AIR DAMPER
EAD
4 NTS
COMPUTER ROOM AIR CONDITIONING (CRAC) CONTROL DIAGRAM
6 NTS
VENTILATION FAN CONTROL DIAGRAM
LPR
T
STEAM TRAP T
STEAM TO WATER
HEAT EXCHANGER
L P
R
LPS
O.A.
140°F (60°C)
(MIN.)
HX-1 2/3 STEAM CONTROL VALVE
HX-1 1/3 STEAM CONTROL VALVE
HWR TEMPERATURE SENSOR7
AUTOMATIC ISOLATION VALVE
AUTOMATIC ISOLATION VALVE
DESCRIPTION
CONTROL POINT
PUMP P-1B START/STOP
PUMP P-1A START/STOP
HWS TEMPERATURE SENSOR
PUMP DIFFERENTIAL PRESSURE SENSOR
OUTDOOR AIR TEMPERATURE SENSOR
PUMP VFD CONTROLLER
6B
6A
CONTROL
POINT
DP4
HWS
HWR
HWS
REFER TO FLOOR PLANS FOR
LOCATION OF DIFFERENTIAL
PRESSURE SENSOR
AI
AI
AI
AO
AI
A0
AI
A0
INPUT/OUTPUT
TYPE
DO/DI
DO/DI
AI
TT
TT
AIR SEPARATOR
6B
6A
180°F (82°C)
(MAX.)
TYP OSA RESET SCHEDULE
B32-P-1B
B32-P-1A
B32-HX-1
SEQUENCES OF OPERATIONS:
1. THE 1/3 CAPACITY STEAM CONTROL VALVE (HV-1) SHALL BE MODULATED OPEN TO MAINTAIN TEMPERATURE SETPOINT; THE 2/3 CAPACITY CONTROL VALVE (HV-2) SHALL BE CLOSED. IF THE TEMPERATURE RISES ABOVE THE SETPOINT, HV-1 SHALL MODULATE CLOSED TO MAINTAIN THE
SETPOINT TEMPERATURE.
2. IF HV-1 IS FULL OPEN AND CANNOT MAINTAIN THE TEMPERATURE SETPOINT THEN THE 2/3 CAPACITY CONTROL VALVE (HV-2) SHALL BE OPENED AND HV-1 SHALL MODULATE CLOSED. IF THE HW SUPPLY TEMPERATURE RISES ABOVE THE SETPOINT, HV-2 SHALL MODULATE CLOSED TO
MAINTAIN THE SETPOINT TEMPERATURE.
3. IF HV-2 IS FULL OPEN AND CANNOT MAINTAIN THE TEMPERATURE SETPOINT THEN HV-1 SHALL MODULATE OPEN. IF THE TEMPERATURE RISES ABOVE THE SETPOINT, HV-1 SHALL MODULATE CLOSED TO MAINTAIN THE SETPOINT TEMPERATURE.
4. OPEN AND CLOSE VALVES SLOWLY.
5. THE LEAVING HOT WATER TEMPERATURE SHALL BE RESET INVERSELY WITH THE OUTDOOR TEMPERATURE AS SCHEDULED.
6. PRIMARY PUMP SHALL RUN TO MAINTAIN TEMPERATURE SETPOINT. IN THE EVENT THE PUMP FAILS TO START WITHIN 30 SECONDS, AN ALARM
SHALL BE INITIATED AND SECONDARY PUMP SHALL BE INITIATED.
7. SPEED CONTROL: INSTALL A DIFFERENTIAL PRESSURE SENSOR ACROSS THE SUPPLY AND RETURN PIPING AT THE POINT IN THE SYSTEM WITH THE HIGHEST PRESSURE DROP. THE DDC SYSTEM SHALL CONTROL THE OPERATING PUMP VFD TO MODULATED TO MAINTAIN A CONSTANT SETPOINT OF 10 PSIG (ADJ.) AT THE DIFFERENTIAL PRESSURE SENSOR. FINAL SETPOINT SHALL BE OPTIMIZED BY THE BALANCING CONTRACTOR.
5 NTS
STEAM TO HOT WATER SYSTEM CONTROL POINT DIAGRAM
STEAM TO WATER
HEAT EXCHANGER
B32-HX-2
T
LPS
6D
6C
DP-1
T-1
RAT
PF DX CC
S
S RL
RL
RS
RS
HC
HWS
HWR
SF SA
H-2 T-5 P-1
HUMIDIFIER
LPS
H-1T-4T-2
T-3
HV-1
LPR
HCV-1
SD
CV-1
CV-2
RA
B32-CRAC-# MINIMUM POINTS LIST
Output Input Virtual Local Controller BAS Full BAS
IntegrationDigital Analog Digital Analog Digital Analog Visible Adjustable Overridable Visible Adjustable Overridable
SF Command…