Updated Drawings - ELECTRICAL_ADD1.pdf

PDF 565 KB Posted

Attached to
Y1EZ--EHRM Infrastructure Upgrades Tier 2 Construction - Tomah VAMC 676-21-701
Solicitation number
36C77622B0025
Issued by

About this file

This document package includes construction drawings and specifications for an electrical infrastructure project, as well as details of a related federal contract opportunity.

The construction drawings show demolition, power, and telecommunications plans for the first floor of Building 32 at the Tomah VA Medical Center. The project will expand the existing IT space by constructing a new 5,000 square foot addition between Building 32 and the tramway. This will incorporate a new data center and correct deficiencies related to accessibility, the main computer room, and demarcation room. The solicitation is seeking a general contractor to furnish all required labor, materials, and equipment in accordance with the specifications and drawings. The Department of Veterans Affairs Technology Acquisition Center Austin is the contracting agency. The response due date and award date are not provided.

View the file

Other files

File Type Posted
36C77622B0025 0006.pdf PDF
C102 - Contractor Markup for Question 35.pdf PDF
P001 - COR Markup for Response 35.pdf PDF
36C77622B0025 0005.pdf PDF
Reference Pictures for Question 29.pdf PDF
Tech Questions - Tomah T2 - 5-12-22.pdf PDF
EP100.pdf PDF
36C77622B0025 0004.pdf PDF
Att 9 - DBA Wage Rates - Monroe County - 04-29-22.pdf PDF
36C77622B0025 0003.pdf PDF
Updated Drawings - CIVIL ADD1.pdf PDF
Tech Questions - Tomah T2 - 5-5-22.pdf PDF
Updated Specs - 055000 Metal Fabrications.pdf PDF
36C77622B0025 0002.pdf PDF
Tech Questions - Tomah T2 - 4-28-22.pdf PDF
36C77622B0025 0001.pdf PDF
Site Visit Sign-in Sheet - Tomah Tier 2.pdf PDF
Tech Questions from Site Visit - Tomah T2 - 4-20-22.pdf PDF
Tomah Tier 2 IFB 36C77622B0025 - 4-6-22.pdf PDF
Att 9 - DBA Wage Rates - Monroe County - 03-18-22.pdf PDF
Att 3 - Final Drawings 1 of 4.pdf PDF
Att 7 - VHA Supp Contract Reqs COVID-19 - 12-14-21.pdf PDF
Att 8 - Limitations on Subcontracting - Construction.docx DOCX document
Att 6 - Final Drawings 4 of 4.pdf PDF
Att 11 - Tomah VAMC - EHRM Tier 2 - Site Visit Map.pdf PDF
Att 10 - Contractor Safety - Enviro Record Eval Form.docx DOCX document
Att 5 - Final Drawings 3 of 4.pdf PDF
Att 1 - Final Specifications Vol 1.pdf PDF
Att 4 - Final Drawings 2 of 4.pdf PDF
Att 2 - Final Specifications Vol 2.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S

S

1. REFER TO SHEET E001 FOR GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.

2. REFER TO SHEET EP101 FOR NEW POWER PLAN.

3. ALL ELECTRICALLY POWERED EQUIPMENT, CONDUIT AND WIRE WITHIN THE

SMOKE SHACK TO BE DISCONNECTED AND REMOVED, UNLESS NOTED

OTHERWISE. THIS INCLUDES AND IS NOT LIMITED TO RECEPTACLES, POWER

PANELS, DISCONNECTS, SWITCHES, TELEPHONE, CARD READERS, AND POWERED

MECHANICAL EQUIPMENT TO BE REMOVED AS PART OF THE PROJECT SCOPE.

4. COORDINATE DEMOLITION WITH GENERAL, CIVIL, AND MECHANICAL

CONTRACTORS.

GENERAL NOTES

EXISTING MECHANICAL EQUIPMENT AND ASSOCIATED ELECTRICAL IN EAST GATE

OUTSIDE IS TO BE DISCONNECTED, CONDUIT AND WIRING REMOVED BACK TO

SOURCE. SALVAGE EXISTING CIRCUIT FOR REUSE AND RELOCATION OF

MECHANICAL EQUIPMENT. SEE MECHANICAL PLANS FOR ADDITIONAL

INFORMATION. EC TO EXTEND EXISTING CIRCUITS TO NEW LOCATION AND

PROVIDE NEW CONDUIT AND WIRE AS REQUIRED. FIRE PROOF ALL

PENETRATIONS.

REMOVE EXISTING LIGHT FIXTURE IN TRAMWAY. DEMOLISH ALL ELECTRICAL

CONDUIT, RECEPTACLES, AND DISCONNECT ANY EXISTING MECHANICAL

EQUIPMENT IN PORTION OF TRAMWAY TO BE DEMOLISHED. EC TO EXTEND

EXISTING LIGHTING CIRCUITS TO APPROXIMATE SAME LOCATION IN NEW

TRAMWAY. (TYP.)

REMOVE ALL ELECTRICAL AT DEMOLISHED WALLS. RELOCATE JUNCTION

BOXES/CONDUIT FOR EQUIPMENT TO REMAIN. FIELD VERIFY NEED FOR

REROUTING OR CONDUIT AND WIRE TO BE REMOVED BACK TO SOURCE.

REMOVE EXISTING POWER CONDUIT TO EXISTING UNDERGROUND ENTRANCE.

PROTECT FOR REINSTALLATION. REWORK/REROUTE EXISTING CONDUIT FOR

POWER RUNNING ALONG WALL AND RELOCATE UNDER NEW TRAMWAY SLAB

BACK TO CUTOFF POINT AND ROUTE BACK UP TO BUILDING 23.

REMOVE EXISTING TELEPHONE CONDUIT TO EXISTING UNDERGROUND

ENTRANCE. COIL CABLE AND PROTECT FOR REINSTALLATION. REWORK/REROUTE

EXISTING CONDUIT FOR TELECOM CABLING RUNNING ALONG CEILING AND

RELOCATE UNDER NEW TRAMWAY SLAB BACK TO CUTOFF POINT AND ROUTE

BACK UP TO BUILDING 23.

KEYED NOTES

CU

CU CU

1 1

UH

UH

SMOKE SHACK

ETR

EX 1" C.

EX 1/2" TEL

CONDUIT

EX 3" FO

CONDUIT

DEMO

EX

EXIST

3770 S. PENNSYLVANIA AVENUE, UNIT 8

ST. FRANCIS, WISCONSIN 53235

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked By

Building Number

Project Number

Drawing Number

Drawn By

PROJECT LEADER:

Department of

Veterans Affairs

CONSULTANTS:

o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231, OCT 1978

500 E VETERANS ST

TOMAH, WI 54660

MEDICAL CENTER

VETERANS AFFAIRS

FULLY SPRINKLERED

500 E VETERANS ST

TOMAH, WI 54660

MEDICAL CENTER

VETERANS AFFAIRS

FULLY SPRINKLERED

Office of Facilities

Management

B

A

C

D

E

F

97 8654321

F

E

D

C

B

A

1 2 3 4 5 6 87 9

FULLY SPRINKLEREDFULLY SPRINKLERED

KEY PLAN N

BLDG 32

T R

A M

W A

Y

BLDG 401

BLDG 32

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

VA TOMAH

FEB. 2, 2022 HFB SJS

ED101ED101

FINAL BID DOCUMENTS

676-21-701ELECTRICAL

DEMOLITION PLAN - FIRST FLOOR

1/4" = 1'-0"1 DEMOLITION PLAN - FIRST FLOOR

No. Description Date

1 ADDENDUM NO. 1 4/28/2022

C

B

A

AHU-1

B32-MDP-IT

MECHANICAL

ROOM

13215

CORRIDOR

13211 CORRIDOR

13212

CORRIDOR

13210

STAIR

S1

ELEV.

E1

B32-MP

ATS-EM

B32-E1

ATS-LR

B32-DP-LR

GFCI

GFI/WP

ELEV-1

ELECTRICAL

ROOM

13215A

P1-A

P1-B

NP-1

EF-1

P-2B

CP-2

BUSBAR

NP-1

NP-1

NP-1

NP-1

NP-1

NP-1

NP-1

NP-1

NP-1

NP-1

NP-1

NP-1

NP-1

NP-1

NP-1

NP-1

R RR

E

LE

V A

T O

R R

E C

A

LL

A

LT

E R

N A

T E

F

LO

O R

R E

LA

Y

F

IR

E M

A N

H A

T R

E

LA

Y

AHU-1-VFD

HVAC

CONTROL

PANELS

NP-1

NP-1

SP-1

SP-2

CONDUIT

ROUTE UNDER

EXIST FIRST

FLOOR

DO

DO

J

CONDUIT DROP

UNDER NEW

FLOOR. TO BE

TERMINATED AT

ATS-LR. SEE ARCH

DETAIL ON A501

FOR FIRE RATED

ASSEMBLY DETAIL.

DO

DO

J

J

B32-E1

B32-E1

B32-E1

DO

DO

SP-3

SP-4

CP-1

TELECOM

CONDUIT

AREA

TELECOM

CONDUIT

AREA

TELECOM

CONDUIT

AREA

SP-5

SUMP PUMP LOCATED

APPROXIMATELY 50' AWAY

FROM BUILDING SEE SHEET C102 FOR

ADDITIONAL INFORMATION.

SUMP

CONTROL

PANEL

(SCP)

~150 FT FROM GEN TO ATS

SCP

NP-1

NP-1

SP-6

SP-7

SP-8

EXIST 1" C.

NEW 1"

GRC

UNDGND

11 J

J

1. REFER TO SHEET E001 FOR GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.

2. REFER TO EQUIPMENT CONNECTION SCHEDULE, SHEET E602 FOR ADDITIONAL

INFORMATION.

3. REFER TO GC SHEETS FOR PHASING PLANS. ALL WORK TO BE DONE IN

ACCORDANCE WITH THE PHASES IDENTIFIED.

4. CONTRACTOR SHALL NOTIFY AND RECEIVE WRITTEN APPROVAL FROM OWNER

PRIOR TO SCHEDULED INTERRUPTION OF ANY SERVICE.

5. SEE STRUCTURAL DRAWINGS FOR GROUNDING ROD LOCATIONS.

GENERAL NOTES

KEYED NOTESKEYED NOTES

1 RELOCATED CONDENSING UNIT. EXTEND EXISTING BRANCH CIRCUIT TO NEW

LOCATION. SEE MECHANICAL PLANS FOR ADDITIONAL INFORMATION.

VERIFY ELECTRICAL REQUIREMENTS FROM SHOP DRAWINGS. SEE E701 FOR

ADDITIONAL INFORMATION.

PROVIDE PULL BOX MINIMUM 24"WX 36"H X 10"D TO TRANSITION UNDERGROUND

CONDUITS FROM BUILDING 32 TO NEW PANELBOARD MDP-IT.

PROVIDE A NEW 20A/2P BREAKER IN EXISTING PANEL B32-P-1 LOCATED ON SOUTH

WEST WALL APPROX 50 FT AWAY WITH 2-#12, 1-#12 GND IN 3/4" C. TO PUMP.

PROVIDE LOCAL DISCONNECT AS REQUIRED FOR PUMP.

PROVIDE 120V POWER FROM NEAREST AVAILABLE CIRCUIT TO SUMP PUMP

CONTROL PANEL. VERIFY LOCATION WITH MC.

PROVIDE A NEW 40A/2P BREAKER IN EXISTING PANEL B32-P-1 LOCATED ON SOUTH

WALL APPROX 50 FT AWAY WITH 2-#12, 1-#12 GND IN 3/4" C. TO PUMP. PROVIDE

LOCAL DISCONNECT AS REQUIRED FOR PUMP.

ROUGH-IN SUMP PUMP CONDUIT FROM EXISTING TELECOM MANHOLE PRIOR TO

POURING OF NEW FLOOR SLAB.

(2) 4" CONDUIT FROM EXISTING TELECOM ROOM IN BASEMENT TO NEW TELECOM

AREA IN ELECTRICAL ROOM. RUN CONDUITS NEXT TO CONDUITS IN NEW

DUCTBANK. SEE EP100 FOR CONTINUATION IN EXISTING BUILDING. PROVIDE

SUPPORTS EVERY 5 FT IN STAIR FOR EXPOSED CONDUITS ABOVE FLOOR. TO BE

ENCLOSED IN STAIR. SEE ARCHITECTURAL PLANS FOR ADDITIONAL INFORMATION.

PROVIDE (20) EMPTY 4" CONDUITS FOR FUTURE CABLES VIA DUCTBANK. STUB AND

CAP (8) AND CONTINUE (12) UP TO 2ND FLOOR.

PROVIDE (20) EMPTY 4" CONDUITS FOR FUTURE CABLES VIA DUCTBANK. STUB AND

CAP (12) AND CONTINUE (8) UP TO 2ND FLOOR.

PROVIDE 1" UNDERGROUND CONDUIT FOR POWER. PROVIDE JUNCTION BOX AT

ENTRY AND EXITING OF NEW UNDERGROUND CONDUIT. RECONNECT EXISTING

POWER.

3770 S. PENNSYLVANIA AVENUE, UNIT 8

ST. FRANCIS, WISCONSIN 53235

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked By

Building Number

Project Number

Drawing Number

Drawn By

PROJECT LEADER:

Department of

Veterans Affairs

CONSULTANTS:

o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231, OCT 1978

500 E VETERANS ST

TOMAH, WI 54660

MEDICAL CENTER

VETERANS AFFAIRS

FULLY SPRINKLERED

500 E VETERANS ST

TOMAH, WI 54660

MEDICAL CENTER

VETERANS AFFAIRS

FULLY SPRINKLERED

Office of Facilities

Management

B

A

C

D

E

F

97 8654321

F

E

D

C

B

A

1 2 3 4 5 6 87 9

FULLY SPRINKLEREDFULLY SPRINKLERED

KEY PLAN N

BLDG 32

T R

A M

W A

Y

BLDG 401

BLDG 32

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

VA TOMAH

FEB. 2, 2022 HFB SJS

EP101EP101

FINAL BID DOCUMENTS

676-21-701ELECTRICAL

POWER PLAN - FIRST FLOOR

1/4" = 1'-0"1 POWER PLAN - FIRST FLOOR

No. Description Date

1 ADDENDUM NO. 1 4/28/2022

C

B

A

CORRIDOR

13211

CORRIDOR

13212

CORRIDOR

13210

ELECTRICAL

ROOM

13215A

ELEV.

E1

STAIR

S1

TELECOM

AREA

TELECOM

AREA

W

W

W

13215A

13215

13211

13212B

13212A13210

S1.0

W

W

TELECOM

AREA

S1.1A

MECH

3 J

J

3" F.O.

1/2"

TEL.

KEYED NOTES

TRAVELING CABLES ROUTED BACK TO ELEVATOR EQUIPMENT FOR TELEPHONE.

COORDINATE WITH INSTALLATION OF ELEVATOR.

SEE CIVIL SHEETS FOR FUTURE CABLES VIA DUCTBANKS.

PROVIDE 4" UNDERGROUND CONDUIT FOR TELEPHONE AND FIBER CABLES.

PROVIDE TELECOM JUNCTION BOX AT ENTRY AND EXITING OF NEW

UNDERGROUND CONDUIT. RETERMINATE EXISTING TELEPHONE AND FIBER

CABLES.

GENERAL NOTES:

1. REFER TO SHEET E001 FOR GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.

2. REFER TO EQUIPMENT CONNECTION SCHEDULE, SHEET E601 FOR ADDITIONAL

INFORMATION.

3. TERMINATE ALL CABLES TO COMPUTER ROOM UNLESS OTHERWISE NOTED.

4. TERMINATE ALL DOOR ACCESS CONTROL TO COMPUTER ROOM UNLESS OTHERWISE NOTED.

5. REFER TO GC SHEETS FOR PHASING PLANS. ALL WORK TO BE DONE IN ACCORDANCE WITH THE PHASES

IDENTIFIED.

6. CONTRACTOR SHALL NOTIFY AND RECEIVE WRITTEN APPROVAL FROM OWNER PRIOR TO SCHEDULED

INTERRUPTION OF ANY SERVICE.

7. COORDINATE WITH THE TOMAH IT DEPT. THE DISCONNECTION AND RECONNECTION OF TELEPHONE AND

FIBER CABLES. PROVIDE TESTING OF CABLES AS REQUIRED.

8. PROVIDE TESTING OF CABLES AS REQUIRED PER SPECIFICATION 271500 -- COMMUNICATIONS STRUCTURED

CABLING.

3770 S. PENNSYLVANIA AVENUE, UNIT 8

ST. FRANCIS, WISCONSIN 53235

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked By

Building Number

Project Number

Drawing Number

Drawn By

PROJECT LEADER:

Department of

Veterans Affairs

CONSULTANTS:

o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t

VA FORM 08-6231, OCT 1978

500 E VETERANS ST

TOMAH, WI 54660

MEDICAL CENTER

VETERANS AFFAIRS

FULLY SPRINKLERED

500 E VETERANS ST

TOMAH, WI 54660

MEDICAL CENTER

VETERANS AFFAIRS

FULLY SPRINKLERED

Office of Facilities

Management

B

A

C

D

E

F

97 8654321

F

E

D

C

B

A

1 2 3 4 5 6 87 9

FULLY SPRINKLEREDFULLY SPRINKLERED

KEY PLAN N

BLDG 32

T R

A M

W A

Y

BLDG 401

BLDG 32

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

VA TOMAH

FEB. 2, 2022 HFB SJS

ET101ET101

FINAL BID DOCUMENTS

676-21-701ELECTRICAL

TELECOM PLAN - FIRST FLOOR

1/4" = 1'-0"1 TELECOM PLAN - FIRST FLOOR

No. Description Date

1 ADDENDUM NO. 1 4/28/2022

Sheets
ED101 - DEMOLITION PLAN - FIRST FLOOR
EP101 - POWER PLAN - FIRST FLOOR
ET101 - TELECOM PLAN - FIRST FLOOR

File details come from the government source that posted it. Updated .