Updated Drawings - ELECTRICAL_ADD1.pdf
PDF 565 KB Posted
- Solicitation number
- 36C77622B0025
About this file
This document package includes construction drawings and specifications for an electrical infrastructure project, as well as details of a related federal contract opportunity.
The construction drawings show demolition, power, and telecommunications plans for the first floor of Building 32 at the Tomah VA Medical Center. The project will expand the existing IT space by constructing a new 5,000 square foot addition between Building 32 and the tramway. This will incorporate a new data center and correct deficiencies related to accessibility, the main computer room, and demarcation room. The solicitation is seeking a general contractor to furnish all required labor, materials, and equipment in accordance with the specifications and drawings. The Department of Veterans Affairs Technology Acquisition Center Austin is the contracting agency. The response due date and award date are not provided.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S
S
1. REFER TO SHEET E001 FOR GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.
2. REFER TO SHEET EP101 FOR NEW POWER PLAN.
3. ALL ELECTRICALLY POWERED EQUIPMENT, CONDUIT AND WIRE WITHIN THE
SMOKE SHACK TO BE DISCONNECTED AND REMOVED, UNLESS NOTED
OTHERWISE. THIS INCLUDES AND IS NOT LIMITED TO RECEPTACLES, POWER
PANELS, DISCONNECTS, SWITCHES, TELEPHONE, CARD READERS, AND POWERED
MECHANICAL EQUIPMENT TO BE REMOVED AS PART OF THE PROJECT SCOPE.
4. COORDINATE DEMOLITION WITH GENERAL, CIVIL, AND MECHANICAL
CONTRACTORS.
GENERAL NOTES
EXISTING MECHANICAL EQUIPMENT AND ASSOCIATED ELECTRICAL IN EAST GATE
OUTSIDE IS TO BE DISCONNECTED, CONDUIT AND WIRING REMOVED BACK TO
SOURCE. SALVAGE EXISTING CIRCUIT FOR REUSE AND RELOCATION OF
MECHANICAL EQUIPMENT. SEE MECHANICAL PLANS FOR ADDITIONAL
INFORMATION. EC TO EXTEND EXISTING CIRCUITS TO NEW LOCATION AND
PROVIDE NEW CONDUIT AND WIRE AS REQUIRED. FIRE PROOF ALL
PENETRATIONS.
REMOVE EXISTING LIGHT FIXTURE IN TRAMWAY. DEMOLISH ALL ELECTRICAL
CONDUIT, RECEPTACLES, AND DISCONNECT ANY EXISTING MECHANICAL
EQUIPMENT IN PORTION OF TRAMWAY TO BE DEMOLISHED. EC TO EXTEND
EXISTING LIGHTING CIRCUITS TO APPROXIMATE SAME LOCATION IN NEW
TRAMWAY. (TYP.)
REMOVE ALL ELECTRICAL AT DEMOLISHED WALLS. RELOCATE JUNCTION
BOXES/CONDUIT FOR EQUIPMENT TO REMAIN. FIELD VERIFY NEED FOR
REROUTING OR CONDUIT AND WIRE TO BE REMOVED BACK TO SOURCE.
REMOVE EXISTING POWER CONDUIT TO EXISTING UNDERGROUND ENTRANCE.
PROTECT FOR REINSTALLATION. REWORK/REROUTE EXISTING CONDUIT FOR
POWER RUNNING ALONG WALL AND RELOCATE UNDER NEW TRAMWAY SLAB
BACK TO CUTOFF POINT AND ROUTE BACK UP TO BUILDING 23.
REMOVE EXISTING TELEPHONE CONDUIT TO EXISTING UNDERGROUND
ENTRANCE. COIL CABLE AND PROTECT FOR REINSTALLATION. REWORK/REROUTE
EXISTING CONDUIT FOR TELECOM CABLING RUNNING ALONG CEILING AND
RELOCATE UNDER NEW TRAMWAY SLAB BACK TO CUTOFF POINT AND ROUTE
BACK UP TO BUILDING 23.
KEYED NOTES
CU
CU CU
1 1
UH
UH
SMOKE SHACK
ETR
EX 1" C.
EX 1/2" TEL
CONDUIT
EX 3" FO
CONDUIT
DEMO
EX
EXIST
3770 S. PENNSYLVANIA AVENUE, UNIT 8
ST. FRANCIS, WISCONSIN 53235
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked By
Building Number
Project Number
Drawing Number
Drawn By
PROJECT LEADER:
Department of
Veterans Affairs
CONSULTANTS:
o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t
VA FORM 08-6231, OCT 1978
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
Office of Facilities
Management
B
A
C
D
E
F
97 8654321
F
E
D
C
B
A
1 2 3 4 5 6 87 9
FULLY SPRINKLEREDFULLY SPRINKLERED
KEY PLAN N
BLDG 32
T R
A M
W A
Y
BLDG 401
BLDG 32
EHRM INFRASTRUCTURE
UPGRADES - TIER 2
VA TOMAH
FEB. 2, 2022 HFB SJS
ED101ED101
FINAL BID DOCUMENTS
676-21-701ELECTRICAL
DEMOLITION PLAN - FIRST FLOOR
1/4" = 1'-0"1 DEMOLITION PLAN - FIRST FLOOR
No. Description Date
1 ADDENDUM NO. 1 4/28/2022
C
B
A
AHU-1
B32-MDP-IT
MECHANICAL
ROOM
13215
CORRIDOR
13211 CORRIDOR
13212
CORRIDOR
13210
STAIR
S1
ELEV.
E1
B32-MP
ATS-EM
B32-E1
ATS-LR
B32-DP-LR
GFCI
GFI/WP
ELEV-1
ELECTRICAL
ROOM
13215A
P1-A
P1-B
NP-1
EF-1
P-2B
CP-2
BUSBAR
NP-1
NP-1
NP-1
NP-1
NP-1
NP-1
NP-1
NP-1
NP-1
NP-1
NP-1
NP-1
NP-1
NP-1
NP-1
NP-1
R RR
E
LE
V A
T O
R R
E C
A
LL
A
LT
E R
N A
T E
F
LO
O R
R E
LA
Y
F
IR
E M
A N
H A
T R
E
LA
Y
AHU-1-VFD
HVAC
CONTROL
PANELS
NP-1
NP-1
SP-1
SP-2
CONDUIT
ROUTE UNDER
EXIST FIRST
FLOOR
DO
DO
J
CONDUIT DROP
UNDER NEW
FLOOR. TO BE
TERMINATED AT
ATS-LR. SEE ARCH
DETAIL ON A501
FOR FIRE RATED
ASSEMBLY DETAIL.
DO
DO
J
J
B32-E1
B32-E1
B32-E1
DO
DO
SP-3
SP-4
CP-1
TELECOM
CONDUIT
AREA
TELECOM
CONDUIT
AREA
TELECOM
CONDUIT
AREA
SP-5
SUMP PUMP LOCATED
APPROXIMATELY 50' AWAY
FROM BUILDING SEE SHEET C102 FOR
ADDITIONAL INFORMATION.
SUMP
CONTROL
PANEL
(SCP)
~150 FT FROM GEN TO ATS
SCP
NP-1
NP-1
SP-6
SP-7
SP-8
EXIST 1" C.
NEW 1"
GRC
UNDGND
11 J
J
1. REFER TO SHEET E001 FOR GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.
2. REFER TO EQUIPMENT CONNECTION SCHEDULE, SHEET E602 FOR ADDITIONAL
INFORMATION.
3. REFER TO GC SHEETS FOR PHASING PLANS. ALL WORK TO BE DONE IN
ACCORDANCE WITH THE PHASES IDENTIFIED.
4. CONTRACTOR SHALL NOTIFY AND RECEIVE WRITTEN APPROVAL FROM OWNER
PRIOR TO SCHEDULED INTERRUPTION OF ANY SERVICE.
5. SEE STRUCTURAL DRAWINGS FOR GROUNDING ROD LOCATIONS.
GENERAL NOTES
KEYED NOTESKEYED NOTES
1 RELOCATED CONDENSING UNIT. EXTEND EXISTING BRANCH CIRCUIT TO NEW
LOCATION. SEE MECHANICAL PLANS FOR ADDITIONAL INFORMATION.
VERIFY ELECTRICAL REQUIREMENTS FROM SHOP DRAWINGS. SEE E701 FOR
ADDITIONAL INFORMATION.
PROVIDE PULL BOX MINIMUM 24"WX 36"H X 10"D TO TRANSITION UNDERGROUND
CONDUITS FROM BUILDING 32 TO NEW PANELBOARD MDP-IT.
PROVIDE A NEW 20A/2P BREAKER IN EXISTING PANEL B32-P-1 LOCATED ON SOUTH
WEST WALL APPROX 50 FT AWAY WITH 2-#12, 1-#12 GND IN 3/4" C. TO PUMP.
PROVIDE LOCAL DISCONNECT AS REQUIRED FOR PUMP.
PROVIDE 120V POWER FROM NEAREST AVAILABLE CIRCUIT TO SUMP PUMP
CONTROL PANEL. VERIFY LOCATION WITH MC.
PROVIDE A NEW 40A/2P BREAKER IN EXISTING PANEL B32-P-1 LOCATED ON SOUTH
WALL APPROX 50 FT AWAY WITH 2-#12, 1-#12 GND IN 3/4" C. TO PUMP. PROVIDE
LOCAL DISCONNECT AS REQUIRED FOR PUMP.
ROUGH-IN SUMP PUMP CONDUIT FROM EXISTING TELECOM MANHOLE PRIOR TO
POURING OF NEW FLOOR SLAB.
(2) 4" CONDUIT FROM EXISTING TELECOM ROOM IN BASEMENT TO NEW TELECOM
AREA IN ELECTRICAL ROOM. RUN CONDUITS NEXT TO CONDUITS IN NEW
DUCTBANK. SEE EP100 FOR CONTINUATION IN EXISTING BUILDING. PROVIDE
SUPPORTS EVERY 5 FT IN STAIR FOR EXPOSED CONDUITS ABOVE FLOOR. TO BE
ENCLOSED IN STAIR. SEE ARCHITECTURAL PLANS FOR ADDITIONAL INFORMATION.
PROVIDE (20) EMPTY 4" CONDUITS FOR FUTURE CABLES VIA DUCTBANK. STUB AND
CAP (8) AND CONTINUE (12) UP TO 2ND FLOOR.
PROVIDE (20) EMPTY 4" CONDUITS FOR FUTURE CABLES VIA DUCTBANK. STUB AND
CAP (12) AND CONTINUE (8) UP TO 2ND FLOOR.
PROVIDE 1" UNDERGROUND CONDUIT FOR POWER. PROVIDE JUNCTION BOX AT
ENTRY AND EXITING OF NEW UNDERGROUND CONDUIT. RECONNECT EXISTING
POWER.
3770 S. PENNSYLVANIA AVENUE, UNIT 8
ST. FRANCIS, WISCONSIN 53235
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked By
Building Number
Project Number
Drawing Number
Drawn By
PROJECT LEADER:
Department of
Veterans Affairs
CONSULTANTS:
o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t
VA FORM 08-6231, OCT 1978
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
Office of Facilities
Management
B
A
C
D
E
F
97 8654321
F
E
D
C
B
A
1 2 3 4 5 6 87 9
FULLY SPRINKLEREDFULLY SPRINKLERED
KEY PLAN N
BLDG 32
T R
A M
W A
Y
BLDG 401
BLDG 32
EHRM INFRASTRUCTURE
UPGRADES - TIER 2
VA TOMAH
FEB. 2, 2022 HFB SJS
EP101EP101
FINAL BID DOCUMENTS
676-21-701ELECTRICAL
POWER PLAN - FIRST FLOOR
1/4" = 1'-0"1 POWER PLAN - FIRST FLOOR
No. Description Date
1 ADDENDUM NO. 1 4/28/2022
C
B
A
CORRIDOR
13211
CORRIDOR
13212
CORRIDOR
13210
ELECTRICAL
ROOM
13215A
ELEV.
E1
STAIR
S1
TELECOM
AREA
TELECOM
AREA
W
W
W
13215A
13215
13211
13212B
13212A13210
S1.0
W
W
TELECOM
AREA
S1.1A
MECH
3 J
J
3" F.O.
1/2"
TEL.
KEYED NOTES
TRAVELING CABLES ROUTED BACK TO ELEVATOR EQUIPMENT FOR TELEPHONE.
COORDINATE WITH INSTALLATION OF ELEVATOR.
SEE CIVIL SHEETS FOR FUTURE CABLES VIA DUCTBANKS.
PROVIDE 4" UNDERGROUND CONDUIT FOR TELEPHONE AND FIBER CABLES.
PROVIDE TELECOM JUNCTION BOX AT ENTRY AND EXITING OF NEW
UNDERGROUND CONDUIT. RETERMINATE EXISTING TELEPHONE AND FIBER
CABLES.
GENERAL NOTES:
1. REFER TO SHEET E001 FOR GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.
2. REFER TO EQUIPMENT CONNECTION SCHEDULE, SHEET E601 FOR ADDITIONAL
INFORMATION.
3. TERMINATE ALL CABLES TO COMPUTER ROOM UNLESS OTHERWISE NOTED.
4. TERMINATE ALL DOOR ACCESS CONTROL TO COMPUTER ROOM UNLESS OTHERWISE NOTED.
5. REFER TO GC SHEETS FOR PHASING PLANS. ALL WORK TO BE DONE IN ACCORDANCE WITH THE PHASES
IDENTIFIED.
6. CONTRACTOR SHALL NOTIFY AND RECEIVE WRITTEN APPROVAL FROM OWNER PRIOR TO SCHEDULED
INTERRUPTION OF ANY SERVICE.
7. COORDINATE WITH THE TOMAH IT DEPT. THE DISCONNECTION AND RECONNECTION OF TELEPHONE AND
FIBER CABLES. PROVIDE TESTING OF CABLES AS REQUIRED.
8. PROVIDE TESTING OF CABLES AS REQUIRED PER SPECIFICATION 271500 -- COMMUNICATIONS STRUCTURED
CABLING.
3770 S. PENNSYLVANIA AVENUE, UNIT 8
ST. FRANCIS, WISCONSIN 53235
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked By
Building Number
Project Number
Drawing Number
Drawn By
PROJECT LEADER:
Department of
Veterans Affairs
CONSULTANTS:
o n e e ig h th in ch o n e f o o t th re e in ch e s o n e f o o t o n e a n d o n e h a lf in ch e s o n e f o o t o n e in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t
VA FORM 08-6231, OCT 1978
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
500 E VETERANS ST
TOMAH, WI 54660
MEDICAL CENTER
VETERANS AFFAIRS
FULLY SPRINKLERED
Office of Facilities
Management
B
A
C
D
E
F
97 8654321
F
E
D
C
B
A
1 2 3 4 5 6 87 9
FULLY SPRINKLEREDFULLY SPRINKLERED
KEY PLAN N
BLDG 32
T R
A M
W A
Y
BLDG 401
BLDG 32
EHRM INFRASTRUCTURE
UPGRADES - TIER 2
VA TOMAH
FEB. 2, 2022 HFB SJS
ET101ET101
FINAL BID DOCUMENTS
676-21-701ELECTRICAL
TELECOM PLAN - FIRST FLOOR
1/4" = 1'-0"1 TELECOM PLAN - FIRST FLOOR
No. Description Date
1 ADDENDUM NO. 1 4/28/2022
| Sheets |
| ED101 - DEMOLITION PLAN - FIRST FLOOR |
| EP101 - POWER PLAN - FIRST FLOOR |
| ET101 - TELECOM PLAN - FIRST FLOOR |
File details come from the government source that posted it. Updated .