Atch 8 - CIVIL 2 of 2 - DRAWINGS.pdf

PDF 10 MB Posted

Attached to
Y1AZ--EHRM Infrastructure Upgrades Construction - Marion Federal contract opportunity
Solicitation number
36C77622B0040
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document provides details for a federal solicitation for infrastructure upgrades and renovations at a Department of Veterans Affairs facility. The solicitation seeks to upgrade electrical, HVAC, communication, physical security, and fiber infrastructure across campus and between buildings at the Marion VA facility. It also involves reconfiguring and renovating existing spaces impacted by infrastructure improvements. Data center WAN updates and hazardous material abatement are required. Response and award dates, pricing terms, and set-asides are not included, though the soliciting agency is the Department of Veterans Affairs Technology Acquisition Center located in Austin.

View the file

Other files for this federal contract opportunity

Other files attached to Y1AZ--EHRM Infrastructure Upgrades Construction - Marion, newest first.
File Type Posted
36C77622B0040 0005.pdf PDF
Clarifications - Marion.pdf PDF
Atch 27 - Construction Wage Rates - Grant 8-19-22.pdf PDF
36C77622B0040 0004.pdf PDF
Atch 27 - Construction Wage Rates - Grant 8-12-22.pdf PDF
Technical Questions - FINAL - Marion 8-11-22.pdf PDF
03 30 00 - Cast-In-Place Concrete.pdf PDF
36C77622B0040 0003.pdf PDF
Atch 27 - Construction Wage Rates - Grant 7-15-22.pdf PDF
36C77622B0040 0002.pdf PDF
Atch 27 - Construction Wage Rates - Grant 7-8-22.pdf PDF
Site Visit Sign-in Sheet - Marion 7-11-22.pdf PDF
36C77622B0040 0001.pdf PDF
Atch 7 - CIVIL 1 of 2 - DRAWINGS.pdf PDF
Atch 11 - ELEC 3 of 3 - DRAWINGS.pdf PDF
Atch 13 - HAZARDOUS ASBESTOS - DRAWINGS.pdf PDF
Atch 14 - HAZARDOUS LEAD BASED PAINT - DRAWINGS.pdf PDF
Atch 22 - STRUCTURAL - DRAWINGS.pdf PDF
Atch 24 - TELECOM 2 of 2 - DRAWINGS.pdf PDF
Atch 25 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Atch 15 - MECH 1 of 7 - DRAWINGS.pdf PDF
Atch 1 - SPECIFICATIONS.pdf PDF
Atch 4 - ARCH 2 of 4 - DRAWINGS.pdf PDF
Atch 5 - ARCH 3 of 4 - DRAWINGS.pdf PDF
Atch 9 - ELEC 1 of 3 - DRAWINGS.pdf PDF
Atch 10 - ELEC 2 of 3 - DRAWINGS.pdf PDF
Atch 12 - GENERAL - DRAWINGS.pdf PDF
Atch 16 - MECH 2 of 7 - DRAWINGS.pdf PDF
Atch 20 - MECH 6 of 7 - DRAWINGS.pdf PDF
Atch 23 - TELECOM 1 of 2 - DRAWINGS.pdf PDF
Atch 27 - Construction Wage Rates - Grant 6-10-22.pdf PDF
36C77622B0040 - 6-27-22.pdf PDF
Atch 3 - ARCH 1of 4 - DRAWINGS.pdf PDF
Atch 26 - Limitations on Subcontracting - Construction.docx DOCX document
Atch 21 - MECH 7 of 7 - DRAWINGS.pdf PDF
Atch 2 - DRAWINGS SHEET INDEX.pdf PDF
Atch 6 - ARCH 4 of 4 - DRAWINGS.pdf PDF
Atch 17 - MECH 3 of 7 - DRAWINGS.pdf PDF
Atch 18 - MECH 4 of 7 - DRAWINGS.pdf PDF
Atch 19 - MECH 5 of 7 - DRAWINGS.pdf PDF
Atch 28 - Contractor Safety - Environmental Form.docx DOCX document
Atch 29 - Site Visit Instructions.pdf PDF
Show all 42

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C

C

6" VCP

S S

S

S S S S S S S S S S S S S

S S

S S

SSSSSSSS

C C

C C

C C

C

C

GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS

GAS GAS

C C

C

C

C

C

C

C

C

C

C

C

C

NELSON AVENUE844

SAN

SAN

SAN

ST

WAT

WAT

WAT

FO/

COMM

FO/

COMM

0+

0+

400+00

400+43

240+0024 1+00

2+

243+00

244+00

245+00

6+

247+00

8+

SAN

ST

FO/

COMM

ELEC

ELEC

ELEC

ELEC

ELEC

ELEC

ELEC

ELEC

ELEC

STEAM

STEAM

ELEC

GEOTH

45° BEND

STA = 241+00

PULL BOX - 411

STA = 411+87

PULL BOX - 237

STA = 245+99

PULL BOX - 238

STA = 246+22

EXISTING BEND

STA = 381+49

CONSTRUCT NEW

PULL BOX OVER EXISTING

FIBER OPTIC CONDUIT

PULL BOX - 235

STA = 244+34

PULL BOX - 234

STA = 243+24

45° BEND

STA = 243+46

PULL BOX - 401

STA = 400+43

PULL BOX - 420

STA = 420+18

90° BEND

STA = 247+27

MATCHLINE: SHEET CU-211

MATCHLINE: SHEET CU-206

M

AT

C H

LI

N

E:

S

H

EE

T C

U -2

M

AT

C H

LI

N

E:

S

H

EE

T C

U -2

M

ATC

H

LIN

E: SH

EET C

U

-209

M

ATC

H

LIN

E: SH

EET C

U -212

PULL BOX - 239

STA = 248+10

CONNECT TO EXISTING

FIBER OPTIC CONDUIT

PULL BOX - 236

STA = 245+57

WATER STREET

PULL BOX - 233

STA = 241+71

SAN

WAT

PULL BOX - 232

STA = 240+83

45° BEND

STA = 246+16

45° BEND

STA = 246+06

11.25° BEND

STA = 245+62

0 20' 40'

N

LEGENDLEGENDLEGEND

PROPERTY LIMITS

EXISTING PAVEMENT EDGE

EXISTING CONCRETE CURB

EXISTING WATERMAIN

EXISTING SANITARY SEWER

EXISTING STORM SEWER

EXISTING HYDRANT AND GATE VALVE

EXISTING SANITARY MANHOLE

EXISTING STORM SEWER INLETS

EXISTING STEAM MANHOLE

EXISTING UNDERGROUND ELECTRIC

EXISTING OVERHEAD ELECTRIC

EXISTING GEOTHERMAL

EXISTING FIBER OPTIC

EXISTING STEAM / CHILLED WATER

EXISTING GAS MAIN

EXISTING UNIDENTIFIED UNDERGROUND UTILITY

LIMITS OF TOPOGRAPHIC SURVEY

LIMITS OF CONSTRUCTION

EXISTING FIBER OPTIC WITH NEW CABLE

PROPOSED PRIMARY EXTERIOR FIBER OPTIC DUCT LINE

PROPOSED SECONDARY FIBER OPTIC DUCT LINE

PROPOSED EXTERIOR PULL BOX

EXISTING UTILITY CROSSING

EXISTING BUILDING NUMBER

XX

XX

GENERAL NOTESGENERAL NOTES

THE FOLLOWING 26 BUILDINGS ARE INCLUDED IN THE PROJECT SCOPE AND SHALL BE SERVED

BY THE PROPOSED FIBER OPTIC INFRASTRUCTURE.

2 5 6 9 15 17 41

49 51 52 53 55 65 76

79 114 124 127 138 170 172

173 174 185

BUILDINGS SERVED

1. ALL PVC CONDUITS TO BE 4-INCH DIAMETER, SCHEDULE 40 PVC.

2. IN LIEU OF USING PRE-FABRICATED BENDS, HORIZONTAL AND

VERTICAL PVC PIPE BENDS MAY BE ACCOMPLISHED BY APPLYING

HEAT AND BENDING PIPE IF DONE IN FULL ACCORDANCE WITH

MANUFACTURER'S REQUIREMENTS AND IF PROCESS IS

PRE-APPROVED BY THE CONTRACTING OFFICER'S REPRESENTATIVE

(COR).

3. SURVEY LIMITS SHOW EXTENT OF TOPOGRAPHIC SURVEY

PERFORMED FROM 5/11/2021 TO 5/19/2021 AND EXPANDED SURVEY

PERFORMED FROM 11/22/2021 TO 11/28/2021. EXISTING BUILDINGS,

PAVEMENTS, AND UTILITIES SHOWN BEYOND THIS LINE WERE

OBTAINED BY THE VA MARION RECORD DRAWINGS. CONTRACTOR TO

FIELD VERIFY ALL LOCATIONS AND ELEVATIONS AS NEEDED.

4. REFER TO SPECIFICATIONS FOR TRENCHING, BACKFILLING, AND

COMPACTION REQUIREMENTS.

5. REFER TO ELECTRICAL PLANS FOR INSTALLATION OF ALL CONDUIT

WITHIN 5.0-FT OF BUILDINGS AND IN OTHER LOCATIONS NOTED ON

CIVIL PLANS.

6. TOPS OF CONCRETE ENCASED DUCTS SHALL BE 24” MIN. UNDER TURF

AREAS OR 30” MIN. BELOW PAVED SURFACES, AND NOT LESS THAN

THE DEPTHS SHOWN ON CIVIL PLANS.

7. ALL CONCRETE-ENCASED CONDUIT IS EXPECTED TO BE INSTALLED BY

OPEN TRENCH. DIRECTIONAL BORING OR JACKING OF CONDUIT IS NOT

ANTICIPATED FOR THIS PROJECT. IF CONTRACTOR WISHES TO

INSTALL BY BORING OR JACKING, PLANS TO DO SO MUST BE

APPROVED BY THE COR PRIOR TO CONSTRUCTION.

8. BEFORE PERFORMING TRENCHING WORK, CONTRACTOR SHALL

PERFORM A GROUND PENETRATING RADAR SURVEY TO REVEAL ALL

EXISTING UNDERGROUND DUCTS, CONDUITS, CABLES, AND OTHER

UTILITY SYSTEMS.

9. ALL MULTIPLE CONDUIT RUNS SHALL HAVE CONDUIT SPACERS

SECURELY SUPPORTING AND MAINTAINING UNIFORM SPACING OF THE

DUCT ASSEMBLY AND SHALL BE INSTALLED IN ACCORDANCE

SPECIFICATIONS AND DUCT BANK DETAILS.

10. PITCH CONDUIT TRENCHES TOWARD MANHOLES/PULLBOXES, OR

BOTH WAYS FROM HIGH POINTS BETWEEN STRUCTURES WITH A

MINIMUM SLOPE OF 0.40% TO ACHIEVE REQUIRED DUCT LINE

DRAINAGE.

11. AVOID SLOPING CONDUIT DUCTS TOWARD BUILDINGS.

12. AFTER CONCRETE-ENCASED DUCTS HAVE SUFFICIENTLY CURED,

CONTRACTOR SHALL BACKFILL TRENCH IN GRADE WITH EARTH, AND

INSTALL THE APPROPRIATE WARNING TAPE APPROXIMATELY 12”

ABOVE THE DUCTS.

13. MAINTAIN 12” MINIMUM VERTICAL SEPARATION BETWEEN EXTERIOR

OF CONCRETE EXCASEMENT OF DUCT LINES AND OTHER UTILITY

SYSTEMS INCLUDING SANITARY SEWER, WATER MAIN, STORM SEWER,

AND CHILLED WATER AT ALL CROSSINGS.

14. KEEP DUCTS CLEAN OF EARTH, SAND, OR GRAVEL, AND SEAL WITH

TAPERED PLUCS UPON COMPLETION OF EACH PORTION OF WORK.

APPROXIMATE LIMITS

OF TOPOGRAPHIC

SURVEY PERFORMED

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL BID

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

Project Director

04/04/2022 LRK JPRRevisions: Date:

Fi le

P at h:

y

:\1

\1 s es

- e hr m v am c

- m ar io n\

_0 ci vi l\_ c ad fi le s\ _0 sh ee ts

\1

_p la n vi ew

.d w g ed it:

jri ch ne r s av ed

:4 /1

5/

:3

AM

p lo t:4

/1 5/

1:

A

M

16181

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT:

20459

Sheet of 45

No. 10910393

STATEOF

INDIANA

DI

REGSTERERO

GER A AN. DERSON

PRO

FESS IONAL ENGIN

EE

R

04/04/2022

CU-212

PLANNED CONSTRUCTION - PLAN

APPROXIMATE LOCATION

OF GEOTHERMAL WELLS

AND PIPING

LIMITS OF

CONSTRUCTION (TYP.)

41 97

153 156

EXISTING FIBER OPTIC

CONDUIT WITH NEW CABLE

PROPOSED EXTERNAL FIBER OPTIC

(6) 4" CONDUIT

SEE DETAIL 1/C-501

SEE SHEET CU-303 FOR PROFILE

PROPOSED EXTERNAL FIBER OPTIC

(6) 4" CONDUIT

SEE DETAIL 1/C-501

SEE SHEET CU-303 FOR PROFILE

SEE MECHANICAL FOR 5' OUTSIDE OF BUILDING TO

INSIDE OF BUILDING (TYP.)

CONSTRUCT PULL BOX5.0' FROM FACE OF BLDG. (TYP.)

PROPOSED EXTERNAL FIBER OPTIC

(1) 4" CONDUIT

SEE DETAIL 1/C-501

SEE SHEET CU-306 FOR PROFILE

NW Main Alignment: 99+50 to 106+00

100+00 101+00 102+00 103+00 104+00 105+00 106+00

South Main Alignment: 199+90 to 207+10

Bldg 114 Alignment: 109+50 to 113+60

200+00 201+00 202+00 203+00 204+00 205+00 206+00 207+00

5 LF (4) 4 IN. @ 0.49%

5 LF (4) 4 IN. @ 0.91%

53 LF (4) 4 IN. @ -1.38%

PU

LL

B O

X

- 1

BO

D

: 8

.9

SU

M

P:

.9

" x

8"

ST

A:

+2

R

IM

: 8

.4

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

2+

BO

D

: 8

.4

PU

LL

B O

X

- 1

BO

D

: 8

.3

" x

8"

ST

A:

+3

R

IM

: 8

.3

PU

LL

B O

X

- 1

BO

D

: 8

.8

" x

8"

ST

A:

+5

R

IM

: 8

.2

PU

LL

B O

X

- 2

BO

D

: 8

.1

" X

8"

ST

A:

+1

R

IM

: 8

.5

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

3+

BO

D

: 8

.9

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

4+

BO

D : 8

.8

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

2+

BO

D : 8

.7

H O

R

IZ

O N

TA

L

.2

5° B

EN

D

ST

A:

6+

BO

D : 8

.1

5 LF (9) 4 IN. @ 3.86%

132 LF (9) 4 IN. @ -0.89%133 LF (9) 4 IN. @ 0.45%

CROSSING X-3

EX. STORM

21 IN RCP

STA: 105+19

INV 836.84

PU

LL

B O

X

- 1

BO

D

: 8

.9

SU

M

P:

.9

" x

8"

ST

A:

+2

R

IM

: 8

.4

23 LF (4) 4 IN. @ 18.70%

14 LF (4) 4 IN. @ -25.60%

22 LF (4) 4 IN. @ -0.40%

EL

GAS

WAT

FO

GAS

EL

FO

EL

WAT

125 LF (9) 4 IN. @ -2.11%

54 LF (9) 4 IN. @ 2.08%

56 LF (9) 4 IN. @ 0.75%

50 LF (9) 4 IN. @ 2.08%

19 LF (9) 4 IN. @ -3.81%

110+00 111+00 112+00 113+00 113+60

ST

WAT

PU

LL

B O

X

- 1

BO

D

: 8

.9

SU

M

P:

.9

" x

8"

ST

A:

+0

R

IM

: 8

.4

8 LF (1) 4 IN. @ 1.50%

PU

LL

B O

X

- 1

BO

D

: 8

.3

SU

M

P:

.3

" x

8"

ST

A:

+9

R

IM

: 8

.2

109 LF (1) 4 IN. @ 1.75%

PU

LL

B O

X

- 1

BO

D

: 8

.2

" x

0"

ST

A:

+0

R

IM

: 8

.7

VE

R

TI

C

AL

1.

° B

EN

D

ST

A:

4+

BO

D

:8

.6

VE

R

TI

C

AL

1.

° B

EN

D

ST

A:

5+

BO

D

:8

.9

101 LF (1) 4 IN. @ 0.52%

FO

WAT

5 LF (9) 4 IN. @ 50.50%

25 LF (9) 4 IN. @ 0.50%

PU

LL

B O

X

- 2

BO

D

: 8

.9

SU

M

P:

.9

" x

8"

ST

A:

+6

R

IM

: 8

.8

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

1+

BO

D

:8

.0

5 VE

R

TI

C

AL

2.

5° B

EN

D

ST

A:

1+

BO

D :8

.5

H O

R

IZ

O N

TA

L

.2

5° B

EN

D

ST

A:

1+

BO

D : 8

.2

12 LF (9) 4 IN. @ -2.40%

PU

LL

B O

X

- 2

BO

D

: 8

.7

" x

8"

ST

A:

+0

R

IM

: 8

.7

PU

LL

B O

X

- 1

BO

D

: 8

.1

SU

M

P:

.1

" x

8"

ST

A:

+1

R

IM

: 8

.6

PU

LL

B O

X

- 1

BO

D

: 8

.2

" x

0"

ST

A:

+0

R

IM

: 8

.7

13 LF (1) 4 IN. @ -8.31%

PU

LL

B O

X

- 2

BO

D

: 8

.8

" x

8"

ST

A:

+0

R

IM

: 8

.6

WAT

ST ST

WAT

EL

WAT

EL

EL

EL

EL

EL EL

EL

WAT

EL

WAT

178 LF (1) 4 IN. @ -2.25%

5 LF (4) 4 IN. @ 50.89%

7 LF (1) 4 IN. @ -49.48%

84 LF (4) 4 IN. @ 0.91%

6 LF (1) 4 IN. @ 49.50%

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

1+

BO

D

:8

.6

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

1+

BO

D

:8

.1

2 VE

R

TI

C

AL

2.

5° B

EN

D

ST

A:

1+

BO

D :8

.6

EX. STORM

12 IN RCP

STA: 101+53

INV 836.10

EX. STORM

24 IN RCP

STA: 112+62

TOP 826.73

EX. STORM

12 IN RCP

STA: 112+86

TOP 829.70

CROSSING X-4

EX. STORM

12 IN RCP

STA: 110+06

INV 835.88

CROSSING X-5

EX. STORM

12 IN RCP

STA: 201+56

INV 839.26

EX. STORM

12 IN RCP

STA: 201+77

INV 838.93

CROSSING X-6

EX. STORM

15 IN RCP

STA: 201+87

INV 836.38

EX. STORM

12 IN RCP

STA: 100+51

TOP 830.88

CROSSING X-1

EX. STORM

12 IN RCP

STA: 101+53

INV 836.10

CROSSING X-2

EX. SANITARY

8 IN PVC Pipe

STA: 104+03

TOP 838.83

CROSSING X-7

EX. SANITARY

8 IN PVC Pipe

STA: 203+66

INV 838.22

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP). 24" MIN. COVER

UNPAVED AREAS (TYP).

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

0+

BO

D

:8

.3

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

0+

BO

D

:8

.3

EX. ELEC

STA: 102+30

EX. ELEC

STA: 103+36

EX. WATER

STA: 103+08

EX. ELEC

STA: 104+80

EX. ELEC

STA: 104+85

EX. ELEC

STA: 104+90

EX. ELEC

STA: 105+42EX. ELEC

STA: 104+08

EX. WATER

STA: 101+05

EX. WATER

STA: 100+05

EX. STEAM

STA: 100+85

EX. STEAM

STA: 100+27

EX. STEAM

STA: 110+15

EX. WATER

STA: 110+95

EX. COMM

STA: 111+63

EX. WATER

STA: 112+73

EX. ELEC

STA: 200+37

EX. ELEC

STA: 202+00

EX. ELEC

STA: 202+31

EX. ELEC

STA: 202+61

EX. COMM

STA: 203+21

EX. GAS

STA: 205+03

EX. ELEC

STA: 206+34

EX. COMM

STA: 206+42

EX. ELEC

STA: 206+59

EX. WATER

STA: 206+98

EX. WATER

STA: 203+11

EX. WATER

STA: 202+86

EX. WATER

STA: 202+29

M

AT

C H

LI

N

E

ST

A.

+0

(S

EE

S

H

EE

T C

U -3

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

24" MIN. COVER

UNPAVED AREAS (TYP).

4 LF (9) 4 IN. @ -2.40%

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

1+

BO

D

:8

.3

7 LF (9) 4 IN. @ -49.50%

10 LF (9) 4 IN. @ -0.40%

5 LF (9) 4 IN. @ 49.50%

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

3+

BO

D

:8

.1

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

3+

BO

D

:8

.8

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

3+

BO

D

:8

.1

6 LF (4) 4 IN. @ 0.50%

5 LF (4) 4 IN. @ 50.35%

28 LF (4) 4 IN. @ 1.32%

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

4+

BO

D

:8

.5

0 VE

R

TI

C

AL

2.

5° B

EN

D

ST

A:

4+

BO

D :8

.0

PU

LL

B O

X

- 1

BO

D

: 8

.5

(N

BO

D

: 8

.4

(S

SU

M

P:

.4

" x

8"

ST

A:

+9

R

IM

: 8

.4

BU

ILD

IN

G

BU

ILD

IN

G

BU

ILD

IN

G

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

5+

BO

D

: 8

.1

4 LF (4) 4 IN. @ 18.70%

5 LF (9) 4 IN. @ 3.86%

PU

LL

B O

X

- 2

BO

D

: 8

.5

(W

BO

D

: 8

.7

(N

S E)

SU

M

P:

.7

" x

8"

ST

A:

+7

R

IM

: 8

.6

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

3+

BO

D

:8

.6

50 LF (9) 4 IN. @ 0.45%

PU

LL

B O

X

- 2

BO

D

: 8

.4

" x

8"

ST

A:

+7

R

IM

: 8

.1

32 LF (9) 4 IN. @ 0.89%

PU

LL

B O

X

- 1

BO

D

: 8

.4

" x

8"

ST

A:

+5

R

IM

: 8

.1

24" MIN. COVER

UNPAVED AREAS (TYP).

148 LF (4) 4 IN. @ 1.39%

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

1+

BO

D

:8

.2

5 LF (1) 4 IN. @ -4.62%

8 LF (9) 4 IN. @ -52.40%

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

1+

BO

D

:8

.5

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL BID

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

Project Director

04/04/2022 LRK JPRRevisions: Date:

Fi le

P at h:

y

:\1

\1 s es

- e hr m v am c

- m ar io n\

_0 ci vi l\_ c ad fi le s\ _0 sh ee ts

\1

_p ro fil es .d w m m ille r s av ed

:4 /1

5/

1:

A M lo t:4 /1

5/

1:

A M

16181

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT:

20459

Sheet of 45

No. 10910393

STATEOF

INDIANA

DI

REGSTERERO

GER A AN. DERSON

PRO

FESS IONAL ENGIN

EE

R

04/04/2022

CU-301

PLANNED CONSTRUCTION -

PROFILE 1

NOTES:

1. ALL PVC CONDUITS TO BE 4-INCH DIAMETER, SCHEDULE 40 PVC.

2. IN LIEW OF USING PRE-FABRICATED BENDS, HORIZONTAL AND VERTICAL

PVC PIPE BENDS MAY BE ACCOMPLISHED BY APPLYING HEAT AND

BENDING PIPE IN DONE IN FULL ACCORDANCE WITH MANUFACTURER'S

REQUIREMENTS AND IF PROCESS IS PRE-APPROVED BY THE

CONTRACTING OFFICERS REPRESENTATIVE (COR).

3. DEPTH OF ELECTRICAL, COMMUNICATIONS, NATURAL GAS, WATER,

STEAM, AND GEOTHERMAL UTILITIES ARE APPROXIMATE. CONTRACTOR

SHALL FIELD VERIFY AND NOTIFY COR OF ANY CONFLICTS WITH

PROPOSED DUCT BANK.

4. CONTRACTOR TO RAISE OR LOWER EXISTING ELECTRIC, COMM, AND

GAS LINES IN-PLACE AT EACH CROSSING TO PROVIDE THE REQUIRED 12"

MIN. VERTICAL CLEARANCE. THIS WORK SHALL BE INCIDENTAL TO

CONCRETE ENCASED FIBER OPTIC CONSTRUCTION.

5. WHEN SLACK DOES NOT ALLOW RAISING OR LOWERING IN-PLACE OF

EXISTING ELECTRICAL, COMMUNICATIONS, AND NATURAL GAS

CONTRACTOR MAY LOWER PROPOSED FIBER OPTIC DUCT BANK

ALIGNMENT. HOWEVER, IF THE LOWERING INTRODUCES A LOW-POINT IN

THE VERTICAL ALIGNMENT, CONTRACTOR MUST INSTALL A PULL BOX

WITH 2.0' SUMP AT EACH LOW-POINT. CONTRACTOR MUST RECEIVE

PRE-APPROVAL FROM COR FOR ANY ADDITIONAL PULL BOXES.

6. WHEN SLACK DOES NOT ALLOW RAISING OR LOWERING IN PLACE OF

EXISTING IRRIGATION LINES, CONTRACTOR SPLICE IRRIGATION LINE TO

PROVIDE ADEQUATE SLACK TO MEET MIN. CLEARANCE REQUIREMENTS.

7. MINIMUM SLOPE IN EACH CONDUIT SHALL BE NO LESS THAN 0.4% TO

PROMOTE DRAINAGE WITHIN CONDUITS.

100+00 to 105+51

110+00 to 113+01

200+00 to 207+00

NOTE: OVERALL OBJECTIVE IS TO INSTALL PROPOSED EHRM

FIBER DUCT BANKS AS SHALLOW AS POSSIBLE WITHIN VA

DESIGN REQUIREMENTS. DEPTH OF EXISTING UTILITIES

ARE UNCONFIRMED. CONTRACTOR TO FIELD VERIFY. IF

CONFIRMED DEPTH ALLOWS FOR ALTERNATE SHALLOW

CROSSING ABOVE THE EXISTING UTILITY USING DETAIL

10/C-501, CONTRACTOR SHALL CONTACT COR FOR

APPROVAL OF DESIGN CHANGE.

South Main Alignment: 213+90 to 221+10

South Main Alignment: 220+90 to 228+10

South Main Alignment: 206+90 to 214+10

ST

WAT

EL

WAT

FO

GAS

WAT

GAS

GEO

EL

EL EL

EL

WAT

GAS

GAS

EL

207+00 208+00 209+00 210+00 211+00 212+00 213+00 214+00

214+00 215+00 216+00 217+00 218+00 219+00 220+00 221+00

GAS

221+00 222+00 223+00 224+00 225+00 226+00 227+00 228+00

FOEL

5 LF (6) 4 IN. @ -1.60%

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

5+

BO

D : 8

.5

60 LF (6) 4 IN. @ 0.73%

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

3+

BO

D : 8

.1

93 LF (6) 4 IN. @ 0.73%

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

3+

BO

D

: 8

.4

45 LF (6) 4 IN. @ 0.87%

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

2+

BO

D

: 8

.8

33 LF (6) 4 IN. @ 0.87%

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

1+

BO

D : 8

.5

13 LF (6) 4 IN. @ -0.50%

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

1+

BO

D : 8

.2

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

7+

BO

D

: 8

.1

PU

LL

B O

X

- 2

BO

D

: 8

.6

" x

8"

ST

A:

+5

R

IM

: 8

.1

62 LF (6) 4 IN. @ 1.60%

5 LF (6) 4 IN. @ -0.72%

PU

LL

B O

X

- 2

BO

D

: 8

.6

(W

E

BO

D

: 8

.0

(N

SU

M

P:

.0

" x

8"

ST

A:

+8

R

IM

: 8

.3

86 LF (6) 4 IN. @ -0.72%

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

9+

BO

D : 8

.2

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

7+

BO

D : 8

.2

162 LF (6) 4 IN. @ -0.40%

223 LF (6) 4 IN. @ -1.20%

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

8+

BO

D : 8

.6

15 LF (9) 4 IN. @ 0.50%

132 LF (9) 4 IN. @ -0.89%

67 LF (9) 4 IN. @ -0.57%

PU

LL

B O

X

- 2

BO

D

: 8

.0

" x

8"

ST

A:

+0

R

IM

: 8

.8

82 LF (6) 4 IN. @ -0.49%

118 LF (9) 4 IN. @ 0.64%

PU

LL

B O

X

- 2

BO

D

: 8

.6

" x

8"

ST

A:

+9

R

IM

: 8

.0

PU

LL

B O

X

- 2

BO

D

: 8

.5

(W

BO

D

: 8

.6

(E

SU

M

P:

.6

" x

8"

ST

A:

+0

R

IM

: 8

.3

PU

LL

B O

X

- 2

BO

D

: 8

.0

(N E)

BO

D

: 8

.3

(N W

S

E)

" x

8"

ST

A:

+1

R

IM

: 8

.5

PU

LL

B O

X

- 2

BO

D

: 8

.9

" x

8"

ST

A:

+9

R

IM

: 8

.9

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

0+

BO

D

:8

.6

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

0+

BO

D

:8

.1

PU

LL

B O

X

- 2

BO

D

: 8

.0

(W

BO

D

: 8

.6

(E

SU

M

P:

.0

" x

8"

ST

A:

+5

R

IM

: 8

.4

5 LF (6) 4 IN. @ -49.50% 24 LF (6) 4 IN. @ -0.50%

86 LF (6) 4 IN. @ -0.49%

86 LF (6) 4 IN. @ -0.49%

PU

LL

B O

X

- 2

BO

D

: 8

.2

" x

8"

ST

A:

+6

R

IM

: 8

.9

36 LF (6) 4 IN. @ 0.73%

WAT

EL

FO

WAT

EL

GAS

ST

EX. STORM

12 IN RCP

STA: 224+50

TOP 830.71

EX. STORM

12 IN RCP

STA: 224+74

TOP 830.62

EX. STORM

12 IN RCP

STA: 225+53

TOP 830.25

EX. STORM

12 IN RCP

STA: 225+40

TOP 837.83

EX. STORM

8 IN RCP

STA: 209+10

TOP 834.63

CROSSING X-9

EX. STORM

12 IN RCP

STA: 210+10

TOP 834.97

CROSSING X-10

EX. STORM

8 IN RCP

STA: 220+34

INV 836.95

EX. STORM

12 IN RCP

STA: 221+37

TOP 833.82

CROSSING X-8

EX. SANITARY

8 IN PVC Pipe

STA: 208+55

INV 835.07

EX. SANITARY

8 IN PVC Pipe

STA: 211+74

INV 836.70EX. STEAM

STA: 207+20

EX. WATER

STA: 208+18

EX. WATER

STA: 208+84

EX. WATER

STA: 209+25

EX. WATER

STA: 210+57

EX. WATER

STA: 212+46 EX. WATER

STA: 213+81

EX. STEAM

STA: 213+20

EX. ELEC

STA: 213+97

EX. ELEC

STA: 213+72

EX. ELEC

STA: 213+51

EX. GAS

STA: 213+25

EX. ELEC

STA: 212+49

EX. ELEC

STA: 212+15

EX. COMM

STA: 212+03

EX. ELEC

STA: 211+29

EX. ELEC

STA: 208+29

EX. GAS

STA: 210+42

EX. GAS

STA: 209+18

EX. GAS

STA: 214+25

EX. GAS

STA: 215+87 EX. ELEC

STA: 216+74 EX. GAS

STA: 219+94

EX. COMM

STA: 222+13

EX. ELEC

STA: 222+14

EX. GEOTHERMAL

STA: 211+17

FIELD VERIFY GEOTHERMAL DEPTH.

PROTECT GEOTHERMAL UTILITY.

NOTIFY COR IF GEOTHERMAL INTERFERS

WITH INSTALLATION OF DUCT BANK.

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

M

AT

C H

LI

N

E

ST

A.

+0

(S

EE

S

H

EE

T C

U -3

M

AT

C H

LI

N

E

ST

A.

+0

(S

EE

S

H

EE

T C

U -3

M

AT

C H

LI

N

E

ST

A.

+0

(S

EE

S

H

EE

T C

U -3

M

AT

C H

LI

N

E

ST

A.

+0

(S

EE

S

H

EE

T C

U -3

M

AT

C H

LI

N

E

ST

A.

+0

(S

EE

S

H

EE

T C

U -3

M

AT

C H

LI

N

E

ST

A.

+0

(S

EE

S

H

EE

T C

U -3

(RAISE OR LOWER ELEC /

COMM / GAS TO PROVIDE 12"

MIN CLEARANCE, TYP.)

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

24" MIN. COVER

UNPAVED AREAS (TYP).

24" MIN. COVER

UNPAVED AREAS (TYP).

24" MIN. COVER

UNPAVED AREAS (TYP).

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).PU

LL

B

O X

- 2

BO

D

: 8

.2

SU

M

P:

.2

" x

8"

ST

A:

+4

R

IM

: 8

.6

8 LF (9) 4 IN. @ 50.50%

41 LF (9) 4 IN. @ 0.41%

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

8+

BO

D

:8

.6

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

8+

BO

D

:8

.7

12 LF (9) 4 IN. @ 0.40%

EX. COMM

STA: 209+00

5 LF (9) 4 IN. @ 0.83%

33 LF (9) 4 IN. @ -0.40%

PU

LL

B O

X

- 2

BO

D

: 8

.4

(N

BO

D

: 8

.6

(W

E

" x

8"

ST

A:

+7

R

IM

: 8

.4

PU

LL

B O

X

- 2

BO

D

: 8

.0

" x

8"

ST

A:

+3

R

IM

: 8

.3

98 LF (9) 4 IN. @ -0.40%

PU

LL

B O

X

- 2

BO

D

: 8

.6

(W

BO

D

: 8

.6

(E

SU

M

P:

.6

" x

8"

ST

A:

+3

R

IM

: 8

.6

8 LF (9) 4 IN. @ 67.13%

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

0+

BO

D

:8

.6

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

0+

BO

D

:8

.0

74 LF (9) 4 IN. @ 4.00%

PU

LL

B O

X

- 2

BO

D

: 8

.9

" x

8"

ST

A:

+9

R

IM

: 8

.5

190 LF (9) 4 IN. @ 0.83%

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

1+

BO

D

: 8

.0

PU

LL

B O

X

- 2

BO

D

: 8

.2

" x

8"

ST

A:

+1

R

IM

: 8

.8

10 LF (6) 4 IN. @ -0.40%

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

8+

BO

D

: 8

.5

42 LF (6) 4 IN. @ -0.72%

39 LF (6) 4 IN. @ 0.87%

PU

LL

B O

X

- 2

BO

D

: 8

.6

" x

8"

ST

A:

+2

R

IM

: 8

.7

200 LF (6) 4 IN. @ -0.66%

PU

LL

B O

X

- 2

BO

D

: 8

.3

" x

8"

ST

A:

+2

R

IM

: 8

.7

48 LF (6) 4 IN. @ -0.49%

91 LF (6) 4 IN. @ -0.49%

5 LF (9) 4 IN. @ 0.50%

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL BID

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

Project Director

04/04/2022 LRK JPRRevisions: Date:

Fi le

P at h:

y

:\1

\1 s es

- e hr m v am c

- m ar io n\

_0 ci vi l\_ c ad fi le s\ _0 sh ee ts

\1

_p ro fil es .d w m m ille r s av ed

:4 /1

5/

1:

lo t:4 /1

5/

1:

A M

16181

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT:

20459

Sheet of 45

No. 10910393

STATEOF

INDIANA

DI

REGSTERERO

GER A AN. DERSON

PRO

FESS IONAL ENGIN

EE

R

04/04/2022

CU-302

PLANNED CONSTRUCTION -

PROFILE 2

207+00 to 214+00

214+00 to 221+00

221+00 to 228+00

NOTES:

1. ALL PVC CONDUITS TO BE 4-INCH DIAMETER, SCHEDULE 40 PVC.

2. IN LIEW OF USING PRE-FABRICATED BENDS, HORIZONTAL AND VERTICAL PVC PIPE

BENDS MAY BE ACCOMPLISHED BY APPLYING HEAT AND BENDING PIPE IN DONE IN

FULL ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS AND IF PROCESS IS

PRE-APPROVED BY THE CONTRACTING OFFICERS REPRESENTATIVE (COR).

3. DEPTH OF ELECTRICAL, COMMUNICATIONS, NATURAL GAS, WATER, STEAM, AND

GEOTHERMAL UTILITIES ARE APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY

AND NOTIFY COR OF ANY CONFLICTS WITH PROPOSED DUCT BANK.

4. CONTRACTOR TO RAISE OR LOWER EXISTING ELECTRIC, COMM, AND GAS LINES

IN-PLACE AT EACH CROSSING TO PROVIDE THE REQUIRED 12" MIN. VERTICAL

CLEARANCE. THIS WORK SHALL BE INCIDENTAL TO CONCRETE ENCASED FIBER

OPTIC CONSTRUCTION.

5. WHEN SLACK DOES NOT ALLOW RAISING OR LOWERING IN-PLACE OF EXISTING

ELECTRICAL, COMMUNICATIONS, AND NATURAL GAS CONTRACTOR MAY LOWER

PROPOSED FIBER OPTIC DUCT BANK ALIGNMENT. HOWEVER, IF THE LOWERING

INTRODUCES A LOW-POINT IN THE VERTICAL ALIGNMENT, CONTRACTOR MUST

INSTALL A PULL BOX WITH 2.0' SUMP AT EACH LOW-POINT. CONTRACTOR MUST

RECEIVE PRE-APPROVAL FROM COR FOR ANY ADDITIONAL PULL BOXES.

6. WHEN SLACK DOES NOT ALLOW RAISING OR LOWERING IN PLACE OF EXISTING

IRRIGATION LINES, CONTRACTOR SPLICE IRRIGATION LINE TO PROVIDE ADEQUATE

SLACK TO MEET MIN. CLEARANCE REQUIREMENTS.

7. MINIMUM SLOPE IN EACH CONDUIT SHALL BE NO LESS THAN 0.4% TO PROMOTE

DRAINAGE WITHIN CONDUITS.

NOTE: OVERALL OBJECTIVE IS TO INSTALL PROPOSED EHRM

FIBER DUCT BANKS AS SHALLOW AS POSSIBLE WITHIN VA

DESIGN REQUIREMENTS. DEPTH OF EXISTING UTILITIES

ARE UNCONFIRMED. CONTRACTOR TO FIELD VERIFY. IF

CONFIRMED DEPTH ALLOWS FOR ALTERNATE SHALLOW

CROSSING ABOVE THE EXISTING UTILITY USING DETAIL

10/C-501, CONTRACTOR SHALL CONTACT COR FOR

South Main Alignment: 234+90 to 242+20

South Main Alignment: 241+90 to 249+20

South Main Alignment: 227+90 to 235+20

EL

GAS

WAT

EL GAS EL

228+00 229+00 230+00 231+00 232+00 233+00 234+00 235+00

64 LF (6) 4 IN. @ -0.49%

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

8+

BO

D

: 8

.6

PU

LL

B O

X

- 2

BO

D

: 8

.7

" x

8"

ST

A:

+0

R

IM

: 8

.2

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

9+

BO

D : 8

.3

H O

R

IZ

O N

TA

L

.5

° B

EN

D H

O R

IZ

O

N

TA

L

.2 5°

B

EN

D

ST

A:

1+

BO

D

: 8

.2

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

2+

BO

D

: 8

.6

112 LF (6) 4 IN. @ -0.60%

91 LF (6) 4 IN. @ -0.49%

146 LF (6) 4 IN. @ -2.03%

132 LF (6) 4 IN. @ 1.50%

235+00 236+00 237+00 238+00 239+00 240+00 241+00 242+00

FO

WAT

EL FO

EL

WAT

WAT

ST

EL

H O

R

IZ

O N

TA

L

° B

EN

D

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

6+

BO

D

: 8

.5

85 LF (6) 4 IN. @ 0.83%

10 LF (6) 4 IN. @ 0.83%

17 LF (6) 4 IN. @ -0.40%

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

1+

BO

D : 8

.0

PU

LL

B O

X

- 2

BO

D

: 8

.2

(S

BO

D

: 8

.8

(N

SU

M

P:

.8

" x

8"

ST

A:

+8

R

IM

: 8

.5

101 LF (6) 4 IN. @ 2.00%

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

5+

BO

D

: 8

.6

20 LF (6) 4 IN. @ 0.40%

83 LF (6) 4 IN. @ 0.67%

PU

LL

B O

X

- 2

BO

D

: 8

.5

" x

8"

ST

A:

+1

R

IM

: 8

.8

PU

LL

B O

X

- 2

BO

D

: 8

.3

SU

M

P:

.3

" x

8"

ST

A:

+3

R

IM

: 8

.7

5 LF (6) 4 IN. @ 50.50%

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

3+

BO

D : 8

.7

84 LF (6) 4 IN. @ -0.50%

6 LF (6) 4 IN. @ -0.54%

PU

LL

B O

X

- 2

BO

D

: 8

.4

SU

M

P:

.4

" x

8"

ST

A:

+2

R

IM

: 8

.0

105 LF (6) 4 IN. @ 0.67%

PU

LL

B O

X

- 2

BO

D

: 8

.8

" x

8"

ST

A:

+5

R

IM

: 8

.0

89 LF EX. FIBER CONDUIT

EX

IS

TI

N

G B

EN

D

ST

A:

1+

BO

D : 8

.8

34 LF EX. FIBER CONDUIT

PU

LL

B O

X

- 2

" x

8"

ST

A:

+9

R

IM

: 8

.9

37 LF (6) 4 IN. @ -0.54%

GAS

EL

PU

LL

B O

X

- 2

BO

D

: 8

.9

" x

8"

ST

A:

+8

R

IM

: 8

.8

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

7+

BO

D : 8

.1

EX. STORM

6 IN RCP

STA: 237+94

INV 841.84

21 LF (6) 4 IN. @ 0.50%

PU

LL

B O

X

- 2

BO

D

: 8

.7

(N E)

BO

D

: 8

.8

(S W

SU

M P:

.8

" X

8"

ST

A:

+2

R

IM

: 8

.0

139 LF (6) 4 IN. @ -0.50%

CROSSING X-13

EX. STORM

6 IN RCP

STA: 248+39

INV 840.73

EX. SANITARY

8 IN PVC Pipe

STA: 231+68

INV 836.72

CROSSING X-11

EX. SANITARY

8 IN PVC Pipe

STA: 241+77

INV 840.32

EX. SANITARY

8 IN PVC Pipe

STA: 237+88

TOP 830.92

EX. SANITARY

8 IN PVC Pipe

STA: 248+44

TOP 837.05

EX. WATER

STA: 237+42

EX. WATER

STA: 239+96

EX. COMM

STA: 239+86

EX. ELEC

STA: 241+57

EX. COMM

STA: 241+29

EX. ELEC

STA: 241+21

EX. ELEC

STA: 241+13

EX. GAS

STA: 239+00

EX. ELEC

STA: 238+67

EX. GAS

STA: 238+71

EX. ELEC

STA: 238+72

EX. ELEC

STA: 237+13

EX. GAS

STA: 237+19

EX. WATER

STA: 242+56 EX. WATER

STA: 247+88

EX. STEAM

STA: 248+36

EX. ELEC

STA: 248+54

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

M

AT

C H

LI

N

E

ST

A.

+0

(S

EE

S

H

EE

T C

U -3

M

AT

C H

LI

N

E

ST

A.

+0

(S

EE

S

H

EE

T C

U -3

M

AT

C H

LI

N

E

ST

A.

+0

(S

EE

S

H

EE

T C

U -3

M

AT

C H

LI

N

E

ST

A.

+0

(S

EE

S

H

EE

T C

U -3

M

AT

C H

LI

N

E

ST

A.

+0

(S

EE

S

H

EE

T C

U -3

CROSSING X-12

EX. STORM

12 IN RCP

STA: 243+42

INV 839.18

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

139 LF (6) 4 IN. @ -0.50%

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

24" MIN. COVER

UNPAVED AREAS (TYP).

24" MIN. COVER

UNPAVED AREAS (TYP).

24" MIN. COVER

UNPAVED AREAS (TYP).

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

6 LF (6) 4 IN. @ 0.50%

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

1+

BO

D

:8

.8

7 LF (6) 4 IN. @ 49.50%

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

1+

BO

D

:8

.4

PU

LL

B O

X

- 2

BO

D

: 8

.7

(N E)

BO

D

: 8

.7

(S W

SU

M P:

.7

" x

8"

ST

A:

+7

R

IM

: 8

.0

72 LF (6) 4 IN. @ -0.40%

8 LF (6) 4 IN. @ 49.86%

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

8+

BO

D

:8

.2

7VE

R

TI

C

AL

2.

5° B

EN

D

ST

A:

8+

BO

D :8

.2

PU

LL

B O

X

- 2

BO

D

: 8

.7

(S

BO

D

: 8

.0

(W

SU

M

P:

.0

" x

8"

ST

A:

+1

R

IM

: 8

.7

26 LF (6) 4 IN. @ 0.51%

BU

ILD

IN

G

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

3+

BO

D

:8

.9

EX. SANITARY

8 IN PVC Pipe

STA: 235+20

TOP 833.27

10 LF (6) 4 IN. @ 0.69%

242+00 243+00 244+00 245+00 246+00 247+00 248+00 249+00 249+20

PU

LL

B O

X

- 2

BO

D

: 8

.3

" x

8"

ST

A:

+2

R

IM

: 8

.3

48 LF (6) 4 IN. @ -2.03%

PU

LL

B O

X

- 2

BO

D

: 8

.4

" x

8"

ST

A:

+2

R

IM

: 8

.0

32 LF (6) 4 IN. @ -0.60%

5 LF (6) 4 IN. @ 1.50%

PU

LL

B O

X

- 2

BO

D

: 8

.5

SU

M

P:

.5

" x

8"

ST

A:

+6

R

IM

: 8

.4

H O

R

IZ

O N

TA

L

° B

EN

D

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

4+

BO

D

: 8

.8

149 LF (6) 4 IN. @ 2.47%

5 LF (6) 4 IN. @ 2.47%

149 LF (6) 4 IN. @ 2.47%

121 LF (6) 4 IN. @ 0.69%

PU

LL

B O

X

- 2

BO

D

: 8

.5

" x

8"

ST

A:

+5

R

IM

: 8

.0

PU

LL

B O

X

- 2

BO

D

: 8

.4

" x

8"

ST

A:

+8

R

IM

: 8

.5

200 LF (6) 4 IN. @ -0.50%

PU

LL

B O

X

- 2

BO

D

: 8

.0

" x

8"

ST

A:

+8

R

IM

: 8

.8

10 LF (6) 4 IN. @ -0.54%

6 LF (6) 4 IN. @ -0.54%

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

6+

BO

D : 8

.5

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

6+

BO

D : 8

.4

H O

R

IZ

O N

TA

L

.2

5° B

EN

D

ST

A:

5+

BO

D : 8

.7

5 LF (6) 4 IN. @ -0.54%

50 LF (6) 4 IN. @ 0.40%

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

8+

BO

D : 8

.4

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL BID

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

Project Director

04/04/2022 LRK JPRRevisions: Date:

Fi le

P at h:

y

:\1

\1 s es

- e hr m v am c

- m ar io n\

_0 ci vi l\_ c ad fi le s\ _0 sh ee ts

\1

_p ro fil es .d w m m ille r s av ed

:4 /1

5/

1:

lo t:4 /1

5/

1:

A M

16181

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT:

20459

Sheet of 45

No. 10910393

STATEOF

INDIANA

DI

REGSTERERO

GER A AN. DERSON

PRO

FESS IONAL ENGIN

EE

R

04/04/2022

CU-303

PLANNED CONSTRUCTION -

PROFILE 3

228+00 to 235+00

235+00 to 242+00

242+00 to 249+00

NOTES:

1. ALL PVC CONDUITS TO BE 4-INCH DIAMETER, SCHEDULE 40 PVC.

2. IN LIEW OF USING PRE-FABRICATED BENDS, HORIZONTAL AND VERTICAL PVC PIPE BENDS

MAY BE ACCOMPLISHED BY APPLYING HEAT AND BENDING PIPE IN DONE IN FULL

ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS AND IF PROCESS IS PRE-APPROVED

BY THE CONTRACTING OFFICERS REPRESENTATIVE (COR).

3. DEPTH OF ELECTRICAL, COMMUNICATIONS, NATURAL GAS, WATER, STEAM, AND

GEOTHERMAL UTILITIES ARE APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY AND

NOTIFY COR OF ANY CONFLICTS WITH PROPOSED DUCT BANK.

4. CONTRACTOR TO RAISE OR LOWER EXISTING ELECTRIC, COMM, AND GAS LINES IN-PLACE

AT EACH CROSSING TO PROVIDE THE REQUIRED 12" MIN. VERTICAL CLEARANCE. THIS

WORK SHALL BE INCIDENTAL TO CONCRETE ENCASED FIBER OPTIC CONSTRUCTION.

5. WHEN SLACK DOES NOT ALLOW RAISING OR LOWERING IN-PLACE OF EXISTING ELECTRICAL, COMMUNICATIONS, AND NATURAL GAS CONTRACTOR MAY LOWER PROPOSED FIBER OPTIC

DUCT BANK ALIGNMENT. HOWEVER, IF THE LOWERING INTRODUCES A LOW-POINT IN THE

VERTICAL ALIGNMENT, CONTRACTOR MUST INSTALL A PULL BOX WITH 2.0' SUMP AT EACH

LOW-POINT. CONTRACTOR MUST RECEIVE PRE-APPROVAL FROM COR FOR ANY ADDITIONAL

PULL BOXES.

6. WHEN SLACK DOES NOT ALLOW RAISING OR LOWERING IN PLACE OF EXISTING IRRIGATION

LINES, CONTRACTOR SPLICE IRRIGATION LINE TO PROVIDE ADEQUATE SLACK TO MEET MIN.

CLEARANCE REQUIREMENTS.

7. MINIMUM SLOPE IN EACH CONDUIT SHALL BE NO LESS THAN 0.4% TO PROMOTE DRAINAGE

WITHIN CONDUITS.

NOTE: OVERALL OBJECTIVE IS TO INSTALL PROPOSED EHRM FIBER DUCT

BANKS AS SHALLOW AS POSSIBLE WITHIN VA DESIGN REQUIREMENTS.

DEPTH OF EXISTING UTILITIES ARE UNCONFIRMED. CONTRACTOR TO

FIELD VERIFY. IF CONFIRMED DEPTH ALLOWS FOR ALTERNATE

SHALLOW CROSSING ABOVE THE EXISTING UTILITY USING DETAIL

10/C-501, CONTRACTOR SHALL CONTACT COR FOR APPROVAL OF

DESIGN CHANGE.

Secondary Loop Alignment: 349+75 to 351+60

Bldg 170 Alignment: 299+50 to 301+00

Bldg 173 Alignment: 339+75 to 344+25

Bldg 170 E Alignment: 309+50 to 310+50

300+00 301+00

350+00 351+00 351+60

PU

LL

B O

X

- 2

BO

D

: 8

.9

" x

8"

ST

A:

+9

R

IM

:8

.6

150 LF (1) 4 IN. @ -1.02%

PU

LL

B O

X

- 3

BO

D

: 8

.9

" x

0"

ST

A:

+5

R

IM

:8

.4

175 LF (4) 4 IN. @ -2.31%

ST

WAT

Bldg 3 W Alignment: 319+90 to 321+50

BU

ILD

IN

G

PU

LL

B O

X

- 2

BO

D

: 8

.2

(W

BO

D

: 8

.7

(N

S

" x

8"

ST

A:

+0

R

IM

:8

.7

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

0+

BO

D : 8

.8

PU

LL

B O

X

- 3

BO

D

: 8

.4

SU

M

P:

.4

" x

8"

ST

A:

+0

R

IM

: 8

.3

105 LF (1) 4 IN. @ 3.62%

310+00 310+50

PU

LL

B O

X

- 3

BO

D

: 8

.1

" x

0"

ST

A:

+7

R

IM

:8

.0

PU

LL

B O

X

- 2

BO

D

: 8

.5

(W

BO

D

: 8

.7

(N

S E)

" x

8"

ST

A:

+7

R

IM

:8

.6

Bldgs 2-6 Main Alignment: 329+90 to 333+00

FO

WAT

EL

ELGAS

EL

EL

EL

ST

GAS EL

EX. STORM

6 IN PVC Pipe

STA: 300+09

INV 840.5

PU

LL

B O

X

- 3

BO

D

: 8

.2

" x

0"

ST

A:

+1

R

IM

:8

.2

PU

LL

B O

X

- 2

BO

D

: 8

.3

(N W

S

E)

BO

D : 8

.0

(N

E)

" x

8"

ST

A:

+1

R

IM

:8

.5

8 LF (1) 4 IN. @ 3.59%

70 LF (1) 4 IN. @ 3.59%

EX. COMM

STA: 300+38

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

EX. WATER

STA: 300+74

12 LF (1) 4 IN. @ 3.54%

PU

LL

B O

X

- 3

BO

D

: 8

.9

" x

0"

ST

A:

+1

R

IM

:8

.2

EX. ELEC

STA: 340+18

EX. GAS

STA: 340+24

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

EX. ELEC

STA: 340+24

EX. ELEC

STA: 340+37

EX. STEAM

STA: 340+91

EX. WATER

STA: 343+92

23 LF (1) 4 IN. @ 0.66%

EX. ELEC

STA: 350+56

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.) EX. GAS

STA: 350+86

EX. STEAM

STA: 350+84

EX. ELEC

STA: 350+82

EX. ELEC

STA: 351+24

24" MIN. COVER

UNPAVED AREAS (TYP).

24" MIN. COVER

UNPAVED AREAS (TYP).

24" MIN. COVER

UNPAVED AREAS (TYP).

24" MIN. COVER

UNPAVED AREAS (TYP).

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

M

AT

C H

LI

N

E

ST

A.

+5

(S

EE

S

H

EE

T C

U -3

330+00 331+00 332+00 333+00

FO

WAT WAT

FO

EL

WAT

WAT

EL EL EL EL

EL

ST

WAT

GAS

EX. STORM

12 IN Concrete Pipe

STA: 330+42

TOP 831.02

PU

LL

B O

X

- 3

BO

D

: 8

.5

" x

8"

ST

A:

+0

R

IM

:8

.8

57 LF (4) 4 IN. @ -4.27%

PU

LL

B O

X

- 3

BO

D

: 8

.1

SU

M

P:

.1

" x

8"

ST

A:

+5

R

IM

: 8

.3

8 LF (4) 4 IN. @ -48.22%

26 LF (4) 4 IN. @ 2.00%

20 LF (4) 4 IN. @ 0.41%

PU

LL

B O

X

- 3

BO

D

: 8

.8

SU

M

P:

.8

" x

8"

ST

A:

+2

R

IM

: 8

.7

8 PU

LL

B

O X

- 3

BO

D

: 8

.8

" x

8"

ST

A:

+7

R

IM

:8

.5

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

2+

BO

D

:8

.2

EX. SANITARY

8 IN PVC Pipe

STA: 330+29

INV: 837.54

EX. STORM

12 IN PVC Pipe

STA: 331+37

TOP 831.36

EX. STORM

6 IN PVC Pipe

STA: 332+12

TOP 835.83

EX. STORM

6 IN PVC Pipe

STA: 332+15

TOP 835.92

EX. SANITARY

8 IN PVC Pipe

STA: 332+45

INV: 836.71

WAT

EX. WATER

STA: 330+17

EX. WATER

STA: 330+36

EX. WATER

STA: 331+71

EX. WATER

STA: 331+54

EX. WATER

STA: 332+66

EX. WATER

STA: 332+48

EX. COMM

STA: 331+10

EX. ELEC

STA: 331+18

EX. ELEC

STA: 331+88

EX. ELEC

STA: 331+82

EX. ELEC

STA: 331+81

EX. ELEC

STA: 331+80

EX. ELEC

STA: 332+53

EX. STEAM

STA: 332+53

CROSSING X-14

EX. STORM

8 IN PVC Pipe

STA: 332+39

INV 835.2

9 LF (4) 4 IN. @ 50.41%

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

2+

BO

D

:8

.8

VE

R

TI

C

AL

2.

5°

B

EN

D

ST

A:

2+

BO

D

:8

.9

158 LF (4) 4 IN. @ 1.78%

PU

LL

B O

X

- 3

BO

D

: 8

.8

" x

0"

ST

A:

+0

R

IM

:8

.3

25 LF (4) 4 IN. @ -0.40%

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

BU

ILD

IN

G

BU

ILD

IN

G

BU

ILD

IN

G

BU

ILD

IN

G

EX. WATER

STA: 330+04

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

BU

ILD

IN

G

EX. COMM

STA: 332+23

22 LF (4) 4 IN. @ 4.28%

PU

LL

B O

X

- 3

" x

8"

ST

A:

+7

R

IM

: 8

.4

BO

D : 8

.0

SU

M P:

.0

PU

LL

B O

X

- 2

BO

D

: 8

.4

(N

BO

D

: 8

.6

(W

N

" x

8"

ST

A:

+0

R

IM

:8

.4

WAT

GAS

WAT

EX. WATER

STA: 320+16

EX. WATER

STA: 320+92

EX. GAS

STA: 320+27

320+00 321+00

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

1+

BO

D : 8

.8

132 LF (1) 4 IN. @ 0.66%

54 LF (4) 4 IN. @ -0.40%

H O

R

IZ

O N

TA

L

.2

5° B

EN

D

ST

A:

0+

BO

D : 8

.3

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL BID

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

Project Director

04/04/2022 LRK JPRRevisions: Date:

Fi le

P at h:

y

:\1

\1 s es

- e hr m v am c

- m ar io n\

_0 ci vi l\_ c ad fi le s\ _0 sh ee ts

\1

_p ro fil es -2

.d w sb et ke r s av ed :4

/1 5/

1:

lo t:4

/1 5/

1:

A

M

16181

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT:

20459

Sheet of 45

No. 10910393

STATEOF

INDIANA

DI

REGSTERERO

GER A AN. DERSON

PRO

FESS IONAL ENGIN

EE

R

04/04/2022

CU-304

PLANNED CONSTRUCTION -

PROFILE 4

300+00 to 300+78 310+00 to 310+12 320+00 to 320+00

330+00 to 333+00

340+00 to 344+08 350+00 to 351+50

NOTES:

1. ALL PVC CONDUITS TO BE 4-INCH DIAMETER, SCHEDULE 40 PVC.

2. IN LIEW OF USING PRE-FABRICATED BENDS, HORIZONTAL AND

VERTICAL PVC PIPE BENDS MAY BE ACCOMPLISHED BY APPLYING HEAT

AND BENDING PIPE IN DONE IN FULL ACCORDANCE WITH

MANUFACTURER'S REQUIREMENTS AND IF PROCESS IS PRE-APPROVED

BY THE CONTRACTING OFFICERS REPRESENTATIVE (COR).

3. DEPTH OF ELECTRICAL, COMMUNICATIONS, NATURAL GAS, WATER,

STEAM, AND GEOTHERMAL UTILITIES ARE APPROXIMATE. CONTRACTOR

SHALL FIELD VERIFY AND NOTIFY COR OF ANY CONFLICTS WITH

PROPOSED DUCT BANK.

4. CONTRACTOR TO RAISE OR LOWER EXISTING ELECTRIC, COMM, AND

GAS LINES IN-PLACE AT EACH CROSSING TO PROVIDE THE REQUIRED

12" MIN. VERTICAL CLEARANCE. THIS WORK SHALL BE INCIDENTAL TO

CONCRETE ENCASED FIBER OPTIC CONSTRUCTION.

5. WHEN SLACK DOES NOT ALLOW RAISING OR LOWERING IN-PLACE OF

EXISTING ELECTRICAL, COMMUNICATIONS, AND NATURAL GAS

CONTRACTOR MAY LOWER PROPOSED FIBER OPTIC DUCT BANK

ALIGNMENT. HOWEVER, IF THE LOWERING INTRODUCES A LOW-POINT IN

THE VERTICAL ALIGNMENT, CONTRACTOR MUST INSTALL A PULL BOX

WITH 2.0' SUMP AT EACH LOW-POINT. CONTRACTOR MUST RECEIVE

PRE-APPROVAL FROM COR FOR ANY ADDITIONAL PULL BOXES.

6. WHEN SLACK DOES NOT ALLOW RAISING OR LOWERING IN PLACE OF

EXISTING IRRIGATION LINES, CONTRACTOR SPLICE IRRIGATION LINE TO

PROVIDE ADEQUATE SLACK TO MEET MIN. CLEARANCE REQUIREMENTS.

7. MINIMUM SLOPE IN EACH CONDUIT SHALL BE NO LESS THAN 0.4% TO

PROMOTE DRAINAGE WITHIN CONDUITS.

NOTE:

OVERALL OBJECTIVE IS TO INSTALL PROPOSED EHRM FIBER DUCT

BANKS AS SHALLOW AS POSSIBLE WITHIN VA DESIGN REQUIREMENTS.

DEPTH OF EXISTING UTILITIES ARE UNCONFIRMED. CONTRACTOR TO

FIELD VERIFY. IF CONFIRMED DEPTH ALLOWS FOR ALTERNATE

SHALLOW CROSSING ABOVE THE EXISTING UTILITY USING DETAIL

10/C-501, CONTRACTOR SHALL CONTACT COR FOR APPROVAL OF

DESIGN CHANGE.

Bldg 9 Alignment: 389+75 to 392+75

Bldg 55 Alignment: 379+75 to 383+50

Secondary Loop Alignment: 351+40 to 358+70

Bldgs 53 and 76 Alignment: 369+90 to 374+60

370+00 371+00 372+00 373+00 374+00 374+60

Bldg 173 Secondary Alignment: 359+90 to 361+70

8 LF (1) 4 IN. @ -0.40%

PU

LL

B O

X

- 3

BO

D

: 8

.6

" x

8"

ST

A:

+3

R

IM

:8

.3

5 LF (1) 4 IN. @ 0.94%

PU

LL

B O

X

- 3

BO

D

: 8

.7

" x

0"

ST

A:

+5

R

IM

:8

.7

80 LF (1) 4 IN. @ 4.26%

PU

LL

B O

X

- 2

BO

D

: 8

.7

" x

8"

ST

A:

+0

R

IM

:8

.2

WAT

ST

GAS

WAT

WAT

352+00 353+00 354+00 355+00 356+00 357+00 358+00 358+70

WAT

WAT

EL

WAT

GAS

WAT

ST

GAS

EL

EL

EL

EL GAS

359+90 360+00 361+00 361+70

GAS

GAS

WAT

EL GAS

390+00 391+00 392+00 392+75

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

2+

BO

D : 8

.4

71 LF (4) 4 IN. @ -0.49%

PU

LL

B O

X

- 3

BO

D

: 8

.2

(N

E

BO

D

: 8

.1

(W

SU

M

P:

.0

" x

8"

ST

A:

+5

R

IM

: 8

.7

18 LF (4) 4 IN. @ 2.16%

7 LF (4) 4 IN. @ 2.16%

H O

R

IZ

O N

TA

L

.2

5° B

EN

D

ST

A:

5+

BO

D : 8

.0

88 LF (4) 4 IN. @ -1.60%

PU

LL

B O

X

- 2

BO

D

: 8

.6

(W

E

BO

D

: 8

.0

(N

SU

M

P:

.0

" x

8"

ST

A:

+3

R

IM

: 8

.3

104 LF (4) 4 IN. @ -0.40%

PU

LL

B O

X

- 3

BO

D

: 8

.8

" x

8"

ST

A:

+7

R

IM

:8

.4

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

3+

BO

D : 8

.8

PU

LL

B O

X

- 2

BO

D

: 8

.6

" x

8"

ST

A:

+5

R

IM

:8

.1

20 LF (1) 4 IN. @ 1.09%

167 LF (1) 4 IN. @ 1.09%

5 LF (1) 4 IN. @ 1.41%

81 LF (1) 4 IN. @ 0.40%

34 LF (1) 4 IN. @ 1.00%

230 LF (1) 4 IN. @ 0.42%

GAS

WAT

EL

WAT

GAS

EX. STORM

12 IN PVC Pipe

STA: 355+16

TOP 834.69

PU

LL

B O

X

- 3

BO

D

: 8

.6

" x

8"

ST

A:

+8

R

IM

:8

.1

157 LF (4) 4 IN. @ -0.40%

EX. STORM

8 IN PVC Pipe

STA: 373+66

TOP 837.05

PU

LL

B O

X

- 2

BO

D

: 8

.9

" x

8"

ST

A:

+9

R

IM

:8

.9

PU

LL

B O

X

- 3

BO

D

: 8

.9

" x

8"

ST

A:

+7

R

IM

:8

.0

PU

LL

B O

X

- 3

BO

D

: 8

.2

" x

0"

ST

A:

+5

R

IM

:8

.7

135 LF (1) 4 IN. @ 1.09%

PU

LL

B O

X

- 3

BO

D

: 8

.0

" x

8"

ST

A:

+3

R

IM

:8

.9

PU

LL

B O

X

- 3

BO

D

: 8

.1

" x

0"

ST

A:

+2

R

IM

:8

.6

PU

LL

B O

X

- 3

BO

D

: 8

.1

" x

0"

ST

A:

+3

R

IM

:8

.9

PU

LL

B O

X

- 2

BO

D

: 8

.9

" x

8"

ST

A:

+8

R

IM

:8

.8

EX. STORM

12 IN PVC Pipe

STA: 390+77

TOP 833.62

PU

LL

B O

X

- 3

BO

D

: 8

.8

" x

8"

ST

A:

+3

R

IM

:8

.6

PU

LL

B O

X

- 3

BO

D

: 8

.2

" x

0"

ST

A:

+6

R

IM

:8

.2

78 LF (1) 4 IN. @ -0.96%

PU

LL

B O

X

- 3

BO

D

: 8

.7

" X

0"

ST

A:

+4

R

IM

:8

.8

EX. GAS

STA: 352+50

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

EX. WATER

STA: 352+69

EX. ELEC

STA: 352+78

EX. WATER

STA: 353+01

EX. WATER

STA: 353+67

EX. WATER

STA: 353+92

EX. WATER

STA: 355+39

EX. GAS

STA: 354+19

EX. GAS

STA: 355+73

EX. GAS

STA: 357+88

EX. ELEC

STA: 353+76 EX. ELEC

STA: 356+01

EX. ELEC

STA: 356+17

EX. ELEC

STA: 356+97

EX. ELEC

STA: 357+23

EX. STEAM

STA: 355+77

EX. GAS

STA: 360+23

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

EX. WATER

STA: 361+31

EX. ELEC

STA: 372+51

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

EX. GAS

STA: 372+61

EX. WATER

STA: 382+63

EX. WATER

STA: 390+73

EX. WATER

STA: 391+13

EX. GAS

STA: 391+02

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

EX. STEAM

STA: 390+89

EX. WATER

STA: 353+24

FO

EX. COMM

STA: 374+32

24" MIN. COVER

UNPAVED AREAS (TYP).

24" MIN. COVER

UNPAVED AREAS (TYP).

24" MIN. COVER

UNPAVED AREAS (TYP).

24" MIN. COVER

UNPAVED AREAS (TYP).

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

M

AT

C H

LI

N

E

ST

A.

+5

(S

EE

S

H

EE

T C

U -3

EX. GAS

STA: 355+83

BU

ILD

IN

G

BU

ILD

IN

G

BU

ILD

IN

G

49 LF (1) 4 IN. @ 0.89%

PU

LL

B O

X

- 3

BO

D

: 8

.3

SU

M

P:

.3

" x

8"

ST

A:

+0

R

IM

: 8

.3

175 LF (4) 4 IN. @ -2.31%

EX. GAS

STA: 361+24

PU

LL

B O

X

- 3

BO

D

: 8

.0

" x

8"

ST

A:

+8

R

IM

:8

.7

163 LF (1) 4 IN. @ 0.96%

5 LF (1) 4 IN. @ 0.96%

27 LF (1) 4 IN. @ -0.40%

128 LF (4) 4 IN. @ 2.16%

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

3+

BO

D

: 8

.5

PU

LL

B O

X

- 3

BO

D

: 8

.5

" x

8"

ST

A:

+0

R

IM

:8

.6

90 LF (4) 4 IN. @ -1.60%

66 LF (1) 4 IN. @ 1.41%

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

0+

BO

D : 8

.8

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

0+

BO

D

: 8

.7

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

0+

BO

D : 8

.6

H

O R

IZ

O

N

TA

L

° B

EN

D

ST

A:

0+

BO

D

: 8

.7

24" MIN. COVER

UNPAVED AREAS (TYP).

6 LF (1) 4 IN. @ 0.94%

40 LF (1) 4 IN. @ 0.94%

BU

ILD

IN

G

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

0+

BO

D : 8

.1

H O

R

IZ

O N

TA

L

.5

° B

EN

D

ST

A:

4+

BO

D

: 8

.3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL BID

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

Project Director

04/04/2022 LRK JPRRevisions: Date:

Fi le

P at h:

y

:\1

\1 s es

- e hr m v am c

- m ar io n\

_0 ci vi l\_ c ad fi le s\ _0 sh ee ts

\1

_p ro fil es -2

.d w sb et ke r s av ed :4

/1 5/

1:

lo t:4

/1 5/

1:

A

M

16181

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT:

20459

Sheet of 45

No. 10910393

STATEOF

INDIANA

DI

REGSTERERO

GER A AN. DERSON

PRO

FESS IONAL ENGIN

EE

R

04/04/2022

CU-305

PLANNED CONSTRUCTION -

PROFILE 5

351+50 to 358+57

360+00 to 361+52 370+00 to 374+49

380+00 to 383+13 390+00 to 392+64

NOTES:

1. ALL PVC CONDUITS TO BE 4-INCH DIAMETER, SCHEDULE 40 PVC.

2. IN LIEW OF USING PRE-FABRICATED BENDS, HORIZONTAL AND VERTICAL PVC PIPE BENDS MAY

BE ACCOMPLISHED BY APPLYING HEAT AND BENDING PIPE IN DONE IN FULL ACCORDANCE WITH

MANUFACTURER'S REQUIREMENTS AND IF PROCESS IS PRE-APPROVED BY THE CONTRACTING

OFFICERS REPRESENTATIVE (COR).

3. DEPTH OF ELECTRICAL, COMMUNICATIONS, NATURAL GAS, WATER, STEAM, AND GEOTHERMAL

UTILITIES ARE APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY AND NOTIFY COR OF ANY

CONFLICTS WITH PROPOSED DUCT BANK.

4. CONTRACTOR TO RAISE OR LOWER EXISTING ELECTRIC, COMM, AND GAS LINES IN-PLACE AT EACH CROSSING TO PROVIDE THE REQUIRED 12" MIN. VERTICAL CLEARANCE. THIS WORK SHALL

BE INCIDENTAL TO CONCRETE ENCASED FIBER OPTIC CONSTRUCTION.

5. WHEN SLACK DOES NOT ALLOW RAISING OR LOWERING IN-PLACE OF EXISTING ELECTRICAL, COMMUNICATIONS, AND NATURAL GAS CONTRACTOR MAY LOWER PROPOSED FIBER OPTIC

DUCT BANK ALIGNMENT. HOWEVER, IF THE LOWERING INTRODUCES A LOW-POINT IN THE

VERTICAL ALIGNMENT, CONTRACTOR MUST INSTALL A PULL BOX WITH 2.0' SUMP AT EACH

LOW-POINT. CONTRACTOR MUST RECEIVE PRE-APPROVAL FROM COR FOR ANY ADDITIONAL

PULL BOXES.

6. WHEN SLACK DOES NOT ALLOW RAISING OR LOWERING IN PLACE OF EXISTING IRRIGATION

LINES, CONTRACTOR SPLICE IRRIGATION LINE TO PROVIDE ADEQUATE SLACK TO MEET MIN.

CLEARANCE REQUIREMENTS.

7. MINIMUM SLOPE IN EACH CONDUIT SHALL BE NO LESS THAN 0.4% TO PROMOTE DRAINAGE

WITHIN CONDUITS.

NOTE:

OVERALL OBJECTIVE IS TO INSTALL PROPOSED EHRM FIBER DUCT BANKS AS

SHALLOW AS POSSIBLE WITHIN VA DESIGN REQUIREMENTS. DEPTH OF EXISTING

UTILITIES ARE UNCONFIRMED. CONTRACTOR TO FIELD VERIFY. IF CONFIRMED

DEPTH ALLOWS FOR ALTERNATE SHALLOW CROSSING ABOVE THE EXISTING

UTILITY USING DETAIL 10/C-501, CONTRACTOR SHALL CONTACT COR FOR

Bldg 76 Alignment: 509+85 to 511+10

Bldg 5 Alignment: 439+75 to 440+60

510+00 511+00 511+10440+00 440+60

PU

LL

B O

X

- 4

BO

D

: 8

.0

" x

0"

ST

A:

+4

R

IM

:8

.3

Bldg 79 Main Alignment: 499+75 to 501+30

Bldg 2 Alignment: 429+75 to 430+75

430+00 430+75

49 LF (1) 4 IN. @ 1.84%

PU

LL

B O

X

- 4

BO

D

: 8

.8

" x

0"

ST

A:

+4

R

IM

:8

.8

Bldg 41 Alignment: 419+75 to 420+50

420+00 420+50

Bldg 49 Alignment: 409+85 to 412+05

GAS

GEO

GEO

GAS

Bldg 52 Alignment: 399+75 to 400+60

400+00 400+60 410+00 411+00 412+00 412+05

EL

EL EL EL

ST

FO EL EL

WAT

EL

ST

PU

LL

B O

X

- 2

BO

D

: 8

.3

SU

M

P:

.3

" x

8"

ST

A:

+3

R

IM

: 8

.7

43 LF (4) 4 IN. @ 7.58%

(RUN THROUGH EXISTING FIBER CONDUIT)

187 LF (1) 4 IN. @ 0.83%

PU

LL

B O

X

- 2

BO

D

: 8

.5

" x

8"

ST

A:

+0

R

IM

:8

.9

PU

LL

B O

X

- 4

BO

D

: 8

.1

" x

0"

ST

A:

+8

R

IM

:8

.6

10 LF (1) 4 IN. @ 0.90%

18 LF (1) 4 IN. @ 8.60%

PU

LL

B O

X

- 4

BO

D

: 8

.0

" x

0"

ST

A:

+1

R

IM

:8

.0

500+00 501+00 501+30

EL

PU

LL

B O

X

- 4

BO

D

: 8

.6

" x

ST

A:

+4

R

IM

:8

.6

PU

LL

B O

X

- 4

BO

D

: 8

.9

" x

8"

ST

A:

+0

R

IM

:8

.9

PU

LL

B O

X

- 4

BO

D

: 8

.3

SU

M

P:

.3

" x

8"

ST

A:

+0

R

IM

: 8

.5

CROSSING X-15

EX. STORM

12 IN PVC Pipe

STA: 440+05

INV 838.6

EX. STORM

12 IN PVC

STA: 510+33

TOP 834.87

PU

LL

B O

X

- 5

BO

D

: 8

.3

" x

8"

ST

A:

+9

R

IM

:8

.5

105 LF (1) 4 IN. @ 3.80%

PU

LL

B O

X

- 5

BO

D

: 8

.7

" x

0"

ST

A:

+1

R

IM

:8

.8

PU

LL

B O

X

- 3

BO

D

: 8

.2

(N

E

BO

D

: 8

.0

(W

SU

M

P:

.0

" x

8"

ST

A:

+0

R

IM

: 8

.7

18 LF (1) 4 IN. @ 24.71%

EX. GAS

STA: 440+33

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

EX. ELEC

STA: 510+16

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

EX. STEAM

STA: 510+46EX. ELEC

STA: 500+52

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

EX. ELEC

STA: 410+29

EX. ELEC

STA: 410+36

EX. ELEC

STA: 410+49

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

EX. ELEC

STA: 410+56 EX. ELEC

STA: 410+93

EX. ELEC

STA: 410+98

EX. COMM

STA: 410+77

EX. WATER

STA: 411+14

EX. GAS

STA: 430+38

(RAISE OR LOWER

ELEC / COMM / GAS

TO PROVIDE 12" MIN

CLEARANCE, TYP.)

EX. SANITARY

8 IN PVC Pipe

STA: 410+87

TOP: 833.55

EX. SANITARY

8 IN PVC Pipe

STA: 411+35

TOP: 837.33

EX. SANITARY

8 IN PVC Pipe

STA: 411+63

TOP: 837.52

EX. SANITARY

8 IN PVC Pipe

STA: 430+11

TOP: 835.11

CROSSING X-16

EX. SANITARY

8 IN PVC Pipe

STA: 440+06

INV 837.2

24" MIN. COVER

UNPAVED AREAS (TYP).

24" MIN. COVER

UNPAVED AREAS (TYP).

24" MIN. COVER

UNPAVED AREAS (TYP).24" MIN. COVER

UNPAVED AREAS (TYP).

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

30" MIN. COVER PAVED

(DRIVING) AREAS (TYP).

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

MAINTAIN 12" MIN. VERTICAL

CLEARANCE AT ALL

EX. UTILITY CROSSINGS

EX. STEAM

STA: 410+76

EX. GEO

STA: 430+21

EX. GEO

STA: 440+17

VE

R

TI

C

AL

1.

° B

EN

D

ST

A:

0+

BO

D

:8

.4

BU

ILD

IN

G

BU

ILD

IN

G

BU

ILD

IN

G

BU

ILD

IN

G

BU

ILD

IN

G

BU

ILD

IN

G

BU

ILD

IN

G

25 LF (1) 4 IN. @ 0.40%

EX. GEO

STA: 400+13

H O

R

IZ

O N

TA

L

° B

EN

D

ST

A:

1+

BO

D : 8

.1

12 LF (1) 4 IN. @ 4.45%

PU

LL

B O

X

- 2

BO

D

: 8

.4

SU

M

P:

7.

" x

8"

ST

A:

+2

R

IM

:8

.0

PU

LL

B O

X

- 3

BO

D

: 8

.5

" x

8"

ST

A:

+0

R

IM

:8

.6

H O

R

IZ

O N

TA

L

.2

5° B

EN

D

ST

A:

0+

BO

D : 8

.6

81 LF (1) 4 IN. @ 0.93%

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL BID

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

Project Director

04/04/2022 LRK JPRRevisions: Date:

Fi le

P at h:

y

:\1

\1 s es

- e hr m v am c

- m ar io n\

_0 ci vi l\_ c ad fi le s\ _0 sh ee ts

\1

_p ro fil es -2

.d w sb et ke r s av ed :4

/1 5/

1:

lo t:4

/1 5/

1:

A

M

16181

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT:

20459

Sheet of 45

No. 10910393

STATEOF

INDIANA

DI

REGSTERERO

GER A AN. DERSON

PRO

FESS IONAL ENGIN

EE

R

04/04/2022

CU-306

PLANNED CONSTRUCTION -

PROFILE 6

410+00 to 411+82 420+00 to 420+13 430+00 to 430+49400+00 to 400+43

500+00 to 500+90 510+00 to 510+93

NOTES:

1. ALL PVC CONDUITS TO BE 4-INCH DIAMETER, SCHEDULE 40 PVC.

2. IN LIEW OF USING PRE-FABRICATED BENDS, HORIZONTAL AND VERTICAL

PVC PIPE BENDS MAY BE ACCOMPLISHED BY APPLYING HEAT AND

BENDING PIPE IN DONE IN FULL ACCORDANCE WITH MANUFACTURER'S

REQUIREMENTS AND IF PROCESS IS PRE-APPROVED BY THE

CONTRACTING OFFICERS REPRESENTATIVE (COR).

3. DEPTH OF ELECTRICAL, COMMUNICATIONS, NATURAL GAS, WATER,

STEAM, AND GEOTHERMAL UTILITIES ARE APPROXIMATE. CONTRACTOR

SHALL FIELD VERIFY AND NOTIFY COR OF ANY CONFLICTS WITH

PROPOSED DUCT BANK.

4. CONTRACTOR TO RAISE OR LOWER EXISTING ELECTRIC, COMM, AND

GAS LINES IN-PLACE AT EACH CROSSING TO PROVIDE THE REQUIRED 12"

MIN. VERTICAL CLEARANCE. THIS WORK SHALL BE INCIDENTAL TO

CONCRETE ENCASED FIBER OPTIC CONSTRUCTION.

5. WHEN SLACK DOES NOT ALLOW RAISING OR LOWERING IN-PLACE OF

EXISTING ELECTRICAL, COMMUNICATIONS, AND NATURAL GAS

CONTRACTOR MAY LOWER PROPOSED FIBER OPTIC DUCT BANK

ALIGNMENT. HOWEVER, IF THE LOWERING INTRODUCES A LOW-POINT IN

THE VERTICAL ALIGNMENT, CONTRACTOR MUST INSTALL A PULL BOX

WITH 2.0' SUMP AT EACH LOW-POINT. CONTRACTOR MUST RECEIVE

PRE-APPROVAL FROM COR FOR ANY ADDITIONAL PULL BOXES.

6. WHEN SLACK DOES NOT ALLOW RAISING OR LOWERING IN PLACE OF

EXISTING IRRIGATION LINES, CONTRACTOR SPLICE IRRIGATION LINE TO

PROVIDE ADEQUATE SLACK TO MEET MIN. CLEARANCE REQUIREMENTS.

7. MINIMUM SLOPE IN EACH CONDUIT SHALL BE NO LESS THAN 0.4% TO

PROMOTE DRAINAGE WITHIN CONDUITS.

NOTE:

OVERALL OBJECTIVE IS TO INSTALL PROPOSED EHRM FIBER DUCT BANKS AS

SHALLOW AS POSSIBLE WITHIN VA DESIGN REQUIREMENTS. DEPTH OF EXISTING

UTILITIES ARE UNCONFIRMED. CONTRACTOR TO FIELD VERIFY. IF CONFIRMED

DEPTH ALLOWS FOR ALTERNATE SHALLOW CROSSING ABOVE THE EXISTING

UTILITY USING DETAIL 10/C-501, CONTRACTOR SHALL CONTACT COR FOR

3" 3"

VARIES BASED ON

NUMBER OF CONDUITS

12" MIN.

CLEARANCE

43" MIN.

DEPTH FOR

OPTION A

24" MIN. CLEARANCE

TO TOP OF CONDUIT

4" PVC

CONDUITS

CONCRETE

ENCASEMENT

EXISTING UTILITY

3"

12" MIN.

CLEARANCE

4" PVC

CONDUITS

CONCRETE

ENCASEMENT

EXISTING UTILITY

OPTION A OPTION B

6" TO TOP OF CONDUIT

#4 REBAR (12" O.C.)

NOTES:

1. USE OF OPTION B REQUIRES PRIOR DOCUMENTED APPROVAL OF

COR FOR ALL CASES.

2. ALL CONDUITS TO BE REALIGNED TO STACKED ALIGNMENTS ON

EITHER SIDE OF CROSSING PRIOR TO CONNECTING TO PULL BOXES.

3"

VARIES BASED ON

NUMBER OF CONDUITS

6" COMPACTED

SUBGRADE

6" COMPACTED

SUBGRADE

3"

25" MIN.

DEPTH FOR

OPTION B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL BID

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

Project Director

04/04/2022 LRK JPRRevisions: Date:

Fi le

P at h:

y

:\1

\1 s es

- e hr m v am c

- m ar io n\

_0 ci vi l\_ c ad fi le s\ _0 sh ee ts

\1

_d et ai ls .d w sb et ke r s av ed

:4 /1

5/

1:

lo t:4 /1

5/

1:

A M

16181

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT:

20459

Sheet of 45

No. 10910393

STATEOF

INDIANA

DI

REGSTERERO

GER A AN. DERSON

PRO

FESS IONAL ENGIN

EE

R

04/04/2022 C-501

CIVIL DETAILS - PLAN 1

SEALANT-JOINT 14" MIN. WIDE BY 38"

DEEP (TYP.)

CAST IN PLACE EXTERIOR CONCRETE DUCT

BANK PER DETAIL 2.

ESCUTCHEON (TYP.)

(4) 4"- PVC CONDUIT PENETRATIONS

4" PVC STUBBED OUT 4". CAP

UNUSED CONDUITS.

PLYWOOD BACKER FOR

JUNCTION BOARD.

TERMINATE PVC CONDUIT

WITHIN MAINTENANCE HOLE

SCALE:2 PULL BOX PENETRATION DETAIL

NOT TO SCALE

TRACER WIRE ACCESS BOX SHALL BE INSTALLED

DIRECTLY ADJACENT TO MAINTENANCE HOLE. INSTALL

TRACER WIRE BOX NOT TO BE INSTALLED IN AREAS WITH

VEHICULAR TRAFFIC.

INSTALL TRACER WIRE PER SPECIFICATION

SECTION 27 05 33 2.1.G. CENTERED ON DUCT

BANK

SCALE:5 TRACER WIRE ACCESS BOX

NOT TO SCALE

INSTALL TRACER WIRE OUTSIDE OF

MAINTENANCE HOLE. TRACER WIRE NOT TO

ENTER MAINTENANCE HOLE.

EXISTING WATERMAIN OR SERVICE PIPE

4" STYROFOAM INSULATION,

OFFSET SEAMS BETWEEN LAYERS

4'

12"

SCALE:6 TRACER WIRE FOR CONCRETE DUCT BANK

NOT TO SCALE SCALE:7 WATERMAIN INSULATION

NOT TO SCALE

SCALE:3 EXTERIOR PULL BOX (30"X48")

NOT TO SCALE

SCALE:11 WARNING TAPE DETAIL

NOT TO SCALE

4" PVC SCH 35 CONDUIT

(TYP.)

REINFORCED CONCRETE

DUCT BANK. PROVIDE 3" OF

COVER MIN. ALL SIDES.

18"

3"

3"

4"

4"

VA

RI

ES

"-3 6"

NOTE

PVC CONNECTIONS SHALL BE WATER

TIGHT

4" MNDOT 3149 SELECT GRANULAR

BORROW (MIN)

PROVIDE WARNING TAPE PER

SPECIFICATION SECTION 27 05 11 2.3.A

6" COMPACTED GRANULAR

MATERIAL

24" - 36" (TYP)

18"

PROPOSED FIBER DUCT BANK

8" COMPACTED GRANULAR

MATERIAL

CONCRETE KNOCKOUT

VARIES BY DUCT SIZE

9" SUMP

CAST IN

FRAME ASSEMBLY

GALVANIZED DROP IN LOCKING

COVER ASSEMBLIES

COVER MARKED

"TELEPHONE"

18 HOLE CABLE RACK

2 PER SIDE WALL

4 TOTAL

18"x18"

KNOCKOUT

1 EACH

END WALL

GALVANIZED

PULLING IRONS 2

TOTAL

6"

VARIES

2'-10' MIN

30" 48"

4'-8" 3'-2"

SCALE:4 EXTERIOR PULL BOX (30"X30")

NOT TO SCALE

CONCRETE KNOCKOUT

VARIES BY DUCT SIZE

CAST IN

FRAME ASSEMBLY

GALVANIZED DROP IN LOCKING

COVER ASSEMBLIESCOVER MARKED

"TELEPHONE"

18 HOLE CABLE RACK

2 PER SIDE WALL

4 TOTAL

18"x18"

KNOCKOUT

1 EACH

END WALL

6"

VARIES

2'-10'

MIN

30"

30"

3'-2" 3'-2"

GALVANIZED

PULLING IRONS 2

TOTAL

SCALE:9 EXTRA DEPTH CROSSING DETAIL

NOT TO SCALE

NOTE: SEE PLANNED CONSTRUCTION PROFILE SHEETS FOR INDIVIDUAL

STRUCTURE DEPTHS AND KNOCKOUT INVERTS AND LOCATIONS

NOTE: SEE PLANNED CONSTRUCTION PROFILE SHEETS FOR INDIVIDUAL

STRUCTURE DEPTHS AND KNOCKOUT INVERTS AND LOCATIONS

PLASTIC

SPACER

INNERDUCT,

SEE NOTE

4" DUCT

(3

3" m m m m m m

3"

76mm (3")

76mm

(3")

(3") 76mm

152mm

TIE

WIRE

(6")(SEE NOTE 4)

(3")

6-WAY DUCT LINE

4-WAY DUCT LINE2-WAY DUCT LINE

GENERAL NOTES:

1.

2.

3.

4.

5.

CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.

PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS WHEN CROSSING OR PLACED IN ROADWAYS.

MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24") OR AS OTHERWISE SPECIFIED IN SECTION 26 05 41.

PROVIDE MINIMUM 152mm (6") SPACE BETWEEN POWER AND TELECOMMUNICATION DUCTS. INCREASE SIZE AS

REQUIRED.

INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS.

(3") 76mm

(3 m m

(3 ") 76 m m

76mm

(3") 76mm

3" m m

3" m m

(3 m m (3")

(3") 76mm

(3") 76mm76mm

1 VA STANDARD DETAIL - SD260541-02

NTS

(T

YP

DUCT BANK DETAILS

(3") 76mm

(3") 76mm

TIE WIRE

INNERDUCT, SEE NOTE 4

PLASTIC SPACER

4" DUCT

(3") 76mm

1-WAY DUCT LINE

(3") 76mm

(3 m m

(3 ") 76 m m (3")

76mm (T

YP

12-WAY DUCT LINE

(3") 76mm

(3 m m (3 m m

(3 m m (3 m m

" M

IN

ST

AT

IO

N

A

ST

AT

IO

N

B

SE

E

PR

O

FI

LE

8.5' ± TO BOTTOM

SEE PROFILE 5.0'

MIN SEE PROFILE

MAX

VERTICAL

BEND (TYP.)

EX. GROUND

SURFACE

EX. UTILITY

PULL BOX

5.0'

MIN

MIN 1%

SLOPE

24" (MIN.)

30" (MIN. UNDER

PAVED AREAS)

3'-2"

CONTRACTOR TO DETERMINE

CONCRETE WALL THICKNESS

BASED ON DEPTH OF STRUCTURE

CONTRACTOR TO DETERMINE

CONCRETE WALL THICKNESS

BASED ON DEPTH OF STRUCTURE

PROVIDE INTERLOCKING

EDGE AROUND PERIMETER (TYP.)

PROVIDE INTERLOCKING

EDGE AROUND PERIMETER (TYP.)

SCALE:10 ALTERNATE SHALLOW CROSSING DETAIL

NOT TO SCALE

SCALE:8 EXTERIOR PULL BOX (48"X48")

NOT TO SCALE

NOTE: SEE PLANNED CONSTRUCTION PROFILE SHEETS FOR INDIVIDUAL

STRUCTURE DEPTHS AND KNOCKOUT INVERTS AND LOCATIONS

CONCRETE KNOCKOUT

VARIES BY DUCT SIZE

9" SUMP

CA…