Atch 19 - MECH 5 of 7 - DRAWINGS.pdf

PDF 19 MB Posted

Attached to
Y1AZ--EHRM Infrastructure Upgrades Construction - Marion Federal contract opportunity
Solicitation number
36C77622B0040
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This federal contract opportunity solicitation involves infrastructure upgrades and renovations to existing spaces at the Marion VA facility. The solicitation seeks contractors to perform electrical, HVAC, communication, physical security, and fiber infrastructure upgrades campus wide within and between buildings. Additional requirements include modifying impacted roads, walks, grading and drainage, updating other existing utilities and the WAN, as well as hazardous material abatement. The soliciting agency is the Department of Veterans Affairs Technology Acquisition Center located in Austin.

View the file

Other files for this federal contract opportunity

Other files attached to Y1AZ--EHRM Infrastructure Upgrades Construction - Marion, newest first.
File Type Posted
36C77622B0040 0005.pdf PDF
Clarifications - Marion.pdf PDF
Atch 27 - Construction Wage Rates - Grant 8-19-22.pdf PDF
36C77622B0040 0004.pdf PDF
Atch 27 - Construction Wage Rates - Grant 8-12-22.pdf PDF
03 30 00 - Cast-In-Place Concrete.pdf PDF
Technical Questions - FINAL - Marion 8-11-22.pdf PDF
36C77622B0040 0003.pdf PDF
Atch 27 - Construction Wage Rates - Grant 7-15-22.pdf PDF
36C77622B0040 0002.pdf PDF
Atch 27 - Construction Wage Rates - Grant 7-8-22.pdf PDF
Site Visit Sign-in Sheet - Marion 7-11-22.pdf PDF
36C77622B0040 0001.pdf PDF
Atch 7 - CIVIL 1 of 2 - DRAWINGS.pdf PDF
Atch 11 - ELEC 3 of 3 - DRAWINGS.pdf PDF
Atch 13 - HAZARDOUS ASBESTOS - DRAWINGS.pdf PDF
Atch 14 - HAZARDOUS LEAD BASED PAINT - DRAWINGS.pdf PDF
Atch 22 - STRUCTURAL - DRAWINGS.pdf PDF
Atch 24 - TELECOM 2 of 2 - DRAWINGS.pdf PDF
Atch 25 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Atch 15 - MECH 1 of 7 - DRAWINGS.pdf PDF
Atch 2 - DRAWINGS SHEET INDEX.pdf PDF
Atch 6 - ARCH 4 of 4 - DRAWINGS.pdf PDF
Atch 17 - MECH 3 of 7 - DRAWINGS.pdf PDF
Atch 18 - MECH 4 of 7 - DRAWINGS.pdf PDF
Atch 28 - Contractor Safety - Environmental Form.docx DOCX document
Atch 29 - Site Visit Instructions.pdf PDF
36C77622B0040 - 6-27-22.pdf PDF
Atch 3 - ARCH 1of 4 - DRAWINGS.pdf PDF
Atch 8 - CIVIL 2 of 2 - DRAWINGS.pdf PDF
Atch 26 - Limitations on Subcontracting - Construction.docx DOCX document
Atch 21 - MECH 7 of 7 - DRAWINGS.pdf PDF
Atch 1 - SPECIFICATIONS.pdf PDF
Atch 4 - ARCH 2 of 4 - DRAWINGS.pdf PDF
Atch 5 - ARCH 3 of 4 - DRAWINGS.pdf PDF
Atch 9 - ELEC 1 of 3 - DRAWINGS.pdf PDF
Atch 10 - ELEC 2 of 3 - DRAWINGS.pdf PDF
Atch 12 - GENERAL - DRAWINGS.pdf PDF
Atch 16 - MECH 2 of 7 - DRAWINGS.pdf PDF
Atch 20 - MECH 6 of 7 - DRAWINGS.pdf PDF
Atch 23 - TELECOM 1 of 2 - DRAWINGS.pdf PDF
Atch 27 - Construction Wage Rates - Grant 6-10-22.pdf PDF
Show all 42

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REMARKS:

1. PERFORMANCE BASED ON CONDITIONS INDICATED IN THIS SCHEDULE.

2. PROVIDE THE FOLLOWING ACCESSORIES: MANUFACTURER'S DISCONNECT AND LINESET.

3. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT

BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR

PRIOR TO ORDERING EQUIPMENT.

REMARKS:

1. PERFORMANCE BASED ON CONDITIONS INDICATED IN THIS SCHEDULE.

2. PROVIDE CONCRETE PAD AND ANCHOR EXTERIOR UNIT TO PAD.

3. PROVIDE CURB RAILS AND ROOF SUPPORTS FOR OUTDOOR UNIT.

4. PROVIDE THE FOLLOWING ACCESSORIES: SINGLE POINT POWER CONNECTION, DISCONNECT, HAIL GUARDS, LOW AMBIENT KIT, WIND BAFFLES.

5. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT

BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR

PRIOR TO ORDERING EQUIPMENT.

REMARKS:

1. PROVIDE WITH WINDOW INSTALLATION KIT.

REMARKS:

1. PROVIDE DISCONNECT.

2. PROVIDE VIBRATION ISOLATION.

3. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS.

EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR PRIOR TO ORDERING EQUIPMENT.

REMARKS:

1. PROVIDE MAGNAHELIC GAUGE ACROSS HOUSING FILTER.

2. PROVIDE FILTER BANK HOLDING FRAME. SUPPORT FRAME FROM STRUCTURE.

REMARKS:

1. PROVIDE WITH INTEGRAL CONDENSATE COOLER, BLOWER PACK.

REMARKS:

1. COORDINATE EXACT MODEL AND FRAME WITH CEILING / WALL TYPE.

REMARKS:

1. PERFORMANCE BASED ON FLUID AND CONDITIONS INDICATED IN THIS SCHEDULE.

2. PROVIDE WITH HIGH WATER LEVEL (OVERFLOW DETECTION) SWITCH WITH TERMINAL FOR CONNECTION TO DDC

EXTERNAL ALARM.

3. PROVIDE WITH BRASS CHECK VALVES.

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459

NON-SPRINKLERED

Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:0

:2

P

M

B124-M600

MECHANICAL SCHEDULES EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B124

04/15/2022 JMM GTS

16181

80 176

SPLIT SYSTEM AIR CONDITIONER - INDOOR SCHEDULE

MARK

ROOM SERVED

NOMINAL

CAPACITY

[TONS]

TOTAL COOLING

CAPACITY

[MBH]

CONDENSATE DRAIN

SIZE

INDOOR UNIT ELECTRICAL DATA

MANUFACTURER REMARKSNAME NUMBER

DIMENSIONS [IN] EAT

(DB / WB)

[°F] MODEL FLA VOLTAGE PHASE MCA DISCONNECT BY SCCRLENGTH WIDTH HEIGHT

SSIU-124-136A TR 136 2.5 30 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0301KA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)

SSIU-124-136B TR 136 3.0 30 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0301KA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)

SSIU-124-217A TR 217 3.0 30 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0301KA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)

SSIU-124-217B TR 217 3.0 30 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0301KA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)

SSIU-124-314A TR 314 3.0 30 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0301KA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)

SSIU-124-314B TR 314 3.0 30 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0301KA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)

SPLIT SYSTEM AIR CONDITIONER - OUTDOOR SCHEDULE

MARK

ROOM SERVED

NOMINAL

CAPACITY

[TONS]

TOTAL COOLING

CAPACITY

[MBH]

OUTDOOR UNIT ELECTRICAL DATA

MANUFACTURER REMARKSNAME NUMBER

DIMENSIONS [IN] SUMMER AMBIENT

AIR

[°F]

WINTER AMBIENT

AIR

[°F]

OPERATING

WEIGHT

[LBS] MODEL FLA VOLTAGE PHASE MCA MOCP DISCONNECT BY SCCRLENGTH WIDTH HEIGHT

SSOU-124-136A TR 136 2.5 30 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0301KA70NA 7.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)

SSOU-124-136B TR 136 2.5 30 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0301KA70NA 7.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)

SSOU-124-217A TR 217 2.5 30 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0301KA70NA 7.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)

SSOU-124-217B TR 217 2.5 30 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0301KA70NA 7.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)

SSOU-124-314A TR 314 2.5 30 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0301KA70NA 7.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)

SSOU-124-314B TR 314 2.5 30 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0301KA70NA 7.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)

WINDOW AIR CONDITIONER SCHEDULE

MARK SERVES NOMINAL TONS

DIMENSIONS [IN] AMBIENT TEMPERATURE

(SUMMER )

[°F]

TOTAL COOLING

CAPACITY

[MBH]

ELECTRICAL DATA

MODEL MANUFACTURER REMARKSLENGTH WIDTH HEIGHT VOLTAGE PHASE

AC-1 BREAK ROOM 341 1.25 29" 26" 18" 90 15 115 V 1 LW1521ERSM LG (1)

DIFFUSER, REGISTER, AND GRILLE SCHEDULE

MARK IMAGE DESCRIPTION MAX S.P. MATERIAL FINISH

FACE SIZE

NECK SIZE AIRFLOW MANUFACTURER MODEL REMARKSLENGTH WIDTH

G1 PERFORATED RETURN

GRILLE

0.10 in-wg STEEL PAINT, WHITE 24" 24" 6"x6" 8"x8"

10"x10" 12"x12" 14"x14"

0-125 126-180 181-210 211-300 301-410

TITUS

KRUEGER

PRICE

PAR

PDDR

(1)

G6 SINGLE DEFLECTION

RETURN GRILLE

0.10 in-wg STEEL PAINT, WHITE 6" 6" SEE PLAN SEE PLAN TITUS 350RL/SL (1)

FAN SCHEDULE

MARK TYPE

MAX WEIGHT

[LBS]

AIRFLOW

[CFM]

TOTAL S.P.

[IN W.C.] MAX FAN RPM MAX FAN BHP

ELECTRICAL DATA

MANUFACTURER MODEL REMARKSFLA VOLTAGE PHASE DISCONNECT BY

F-1 IN-LINE 24 100 0.54 1288 0.03 1.5 115 V 1 MECHANICAL GREENHECK CSP-A390-VG (1)(2)

F-2 IN-LINE 24 100 0.54 1288 0.03 1.5 115 V 1 MECHANICAL GREENHECK CSP-A390-VG (1)(2)

F-3 IN-LINE 24 100 0.54 1288 0.03 1.5 115 V 1 MECHANICAL GREENHECK CSP-A390-VG (1)(2)

FILTER SCHEDULE

MARK ASSOCIATED EQUIPMENT TYPE

DEPTH

[IN] MERV RATING REMARKS

PF-1 F-1 12"x12" 2" 11 (1)(2)

PF-2 F-2 12"x12" 2" 11 (1)(2)

PF-3 F-3 12"x12" 2" 11 (1)(2)

ELECTRODE STEAM HUMIDIFIER SCHEDULE

MARK SERVICE

MAKE UP WATER

CONNECTION SIZE

WATER PIPING ELECTRICAL DATA

MANUFACTURER MODEL REMARKS

CAPACITY

[LB / HR]

DRAIN PIPE CONNECTION

SIZE KW VOLTAGE PHASE

H-1 TR 314 1/2" 5.6 3/4" 1.9 120 V 1 DRISTEEM XRT (1)

H-2 TR 314 1/2" 5.6 3/4" 1.9 120 V 1 DRISTEEM XRT (1)

H-3 TR 314 1/2" 5.6 3/4" 1.9 120 V 1 DRISTEEM XRT (1)

PUMP SCHEDULE

MARK

FLOW

[GPH]

TOTAL HEAD

[FT]

SHUT-OFF HEAD

[FT]

SUCTION /

DISCHARGE SIZE

[IN]

ELECTRICAL DATA

MANUFACTURER MODEL REMARKSHP FLA VOLTAGE

CP-1 200 20 32 3/8" 0.125 1.4 115 V LITTLE GIANT HT-VCL-30-P (1)(2)(3)

Revisions: Date:

UPS ROOM

100A

CLOSET

101B

PHONE ROOM

ELEC/UPS

ENTRANCE

FACILITY

2" F

1/

4" F

1"

1"

1"

KEY PLAN

MAIN

ENTRY

BUILDING 127

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:0

:5

P

M

B127-F201

FIRST LEVEL FLOOR PLAN - FIRE

PROTECTION

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B127

04/15/2022 JLK SSK

16181

81 176

1/4" = 1'-0" F4

FIRST LEVEL FLOOR PLAN - FIRE PROTECTION

0 2' 4'1'

SHEET NOTES:

1. 2" FIRE PROTECTION PIPING FROM BUILDING 15. SEE SHEET B15-F201 FOR CONTINUATION.

2. PROVIDE CLEAN AGENT FIRE PROTECTION SYSTEM TO SERVE ENTRANCE FACILITY. ENTRANCE FACILITY IS

275 SQ FT. PROVIDE ONE CYLINDER, CONTROL PANEL, AND ASSOCIATED PIPING TO FEED ENTRANCE

FACILITY.

GENERAL NOTES:

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.

KEY PLAN

MAIN

ENTRY

BUILDING 127

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:0

:5

P

M

B127-M101

FIRST LEVEL FLOOR PLAN -

MECHANICAL DEMO

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B127

04/15/2022 JMM GTS

16181

82 176

1/4" = 1'-0" F4

FIRST LEVEL FLOOR PLAN - MECHANICAL - DEMO

0 2' 4'1'

SHEET NOTES:

1. DEMOLISH ABOVE CEILING FAN COIL UNIT, ASSOCIATED DUCTWORK, ROOF MOUNTED CONDENSING UNIT

AND PIPING SERVING EXISTING COMM ROOM 102. PATCH ALL PENETRATIONS TO MATCH EXISTING

CONSTRUCTION AND ROOF WARRANTIES.

2. DEMOLISH ALL PLUMBING SUPPLY, VENT AND WASTE PIPING BACK TO CONNECTION TO MAINS.

3. DEMOLISH ALL ABOVE CEILING DUCTWORK BACK TO CONNECTIONS TO MAINS OUTSIDE OF ROOM.

4. DEMOLISH EXISTING ROOM SPRINKLER HEADS.

5. DEMOLISH THE EXISTING COOLING UNITS, ASSOCIATED DUCTWORK, EXTERIOR CONDENSING AND PIPING

SERVING THE EXISTING OFFICE SPACE AND HALLWAY. REPAIR ROOFING WHERE EXISTING ROOFTOP UNITS

AND PIPE PENETRATIONS ARE REMOVED.

GENERAL NOTES:

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.

CR AC

UPS ROOM

100A

CLOSET

101B

PHONE ROOM

ELEC/UPS

ENTRANCE

FACILITY

SSIU-127-102B SSIU-127-102C

1 1

SSIU-127-101C

SSIU-127-101B

SSIU-127-101A

SSIU-127-102A

G1

14"x14"

D2

8"x8"

D2

6"x6"

D2

6"x6"

D2

6"x6"

D2

6"x6"

D2

6"x6"

8"x8"

GE7

EF-1 ON

ROOF ABOVE

8x8 EA

12x12 RA 12x12 SA

10x8 SA

200 CFM SIDEWALL

SUPPLY. REFER TO

BUILDING 15.SF-1

FSFS

FSFS

PF-1

H-2

H-1

CP-1

CP-2

3/4" PC

3/4" CD

3/4" CD

121212

3/4" PC

13 13

1" PC

8x8 SA

6x6 SA

3/4" CD

3/4" CD

1" CD

M501

D1

M501

D1

1/2"

1" CD

KEY PLAN

MAIN

ENTRY

BUILDING 127

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:0

:0

P

M

B127-M201

FIRST LEVEL FLOOR PLAN -

MECHANICAL

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B127

04/15/2022 JMM GTS

16181

83 176

1/4" = 1'-0" F4

FIRST LEVEL FLOOR PLAN - MECHANICAL

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.

SHEET NOTES:

1. REFRIGERANT LINES UP TO CONDENSING UNITS ON ROOF.

2. ROUTE CONDENSATE FROM UNIT TO COMMON CONDENSATE DRAIN LINE AS SHOWN.

3. LOCATE NEW SPRINKLERS IN SPACE TO ACCOMMODATE NEW ROOM LAYOUT.

4. LOCATE CONDENSERS FOR ROOM COOLING UNITS ON ROOF ABOVE. SEE PHOTO FOR LOCATION

COORDINATION. MOUNT ON ROOF PER DETAIL B1 ON SHEET M500.

5. PROVIDE UPDATED SPRINKLER LAYOUT COORDINATED WITH NEW EQUIPMENT AND WALL REVISIONS.

6. ROUTE PUMPED CONDENSATE TO FLOOR DRAIN APPROXIMATELY IN THIS LOCATION. DO NOT ROUTE DRAIN

OVER EXISTING ELECTRICAL EQUIPMENT.

7. MOUNT FROM CEILING WITH UNISTRUT.

8. CONDENSING UNITS MAY BE LOCATED IN SPACES VACATED BY EXISTING EQUIPMENT TO BE DEMOLISHED.

PROVIDE MANUFACTURERS RECOMMENDED CLEARANCES FROM ADJACENT WALLS AND OTHER PIECES OF

EQUIPMENT.

9. PROVIDE WATER BUG AT FLOOR TO ALARM TO DDC WHEN ACTIVATED.

10. PROVIDE FILTER RACK UPSTREAM OF SUPPLY FAN SF-1. PROVIDE TRANSITION DUCT FROM PRE-FILTER TO

FAN INLET.

11. EXTEND NEW DOMESTIC COLD WATER LINE FROM EXISTING WATER LINE AT DEMOLISHED SINK TO SERVE

BACKFLOW PREVENTER FOR HUMIDIFIER MAKE-UP WATER.

12. BOTTOM OF COOLING UNIT SHALL BE A MINIMUM OF 7-0” A.F.F. ADJUST MOUNTING HEIGHT TO AVOID

CONFLICTS WITH CABLE TRAY. MAINTAIN MANUFACTURERS SERVICE CLEARANCE RECOMMENDATIONS.

13. ROUTE 3/8" REFRIGERANT LIQUID LINE AND 5/8" REFRIGERANT HOT GAS LINE FROM CONDENSING UNIT TO

CORRESPONDING DUCT-FREE SYSTEM. PIPE SIZES ARE FOR COST ESTIMATING PURPOSES, AND BASED ON

BASIS OF DESIGN MANUFACTURE AS LISTED IN THE SCHEDULE. SIZE LINES ACCORDING TO

MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL ACCESSORIES REQUIRED FOR A COMPLETE AND

OPERABLE SYSTEM.

14. DISCHARGE 3/4" PUMPED CONDENSATE INTO TOP OF 1" PUMPED CONDENSATE LINE.

15. PUMPED CONDENSATE SHALL SLOPE TOWARDS DISCHARGE.

16. CONDENSATE PUMP LOCATED ON FLOOR BELOW HUMIDIFIER. DISCHARGE ALL ENTRANCE FACILITY 102

COOLING CONDENSATE DRAINS INTO A COMMON GRAVITY HEADER AND COMBINE WITH HUMIDIFIER-1 & 2 DRAIN AND ASSOCIATED RO DRAINS AND ROUTE TO CONDENSATE PUMP. PROVIDE DRAIN PAN UNDER

CONDENSATE PIPING WITHIN ROOM 102 WITH WATER BUG ALARM TO DDC.

17. CONDENSATE PUMP LOCATED ON FLOOR BELOW COOLING UNIT AND COLLECTS GRAVITY CONDENSATE

FROM SSIU-127-101A, SSIU-127-101B, AND SSIU-127-101C.

18. PROVIDE 1/2" NON-POTABLE WATER TO HUMIDIFIER AND RO SYSTEM. PROVIDE DRAIN PAN UNDER PIPING

WITHIN ENTRANCE FACILITY 102 WITH WATER BUG ALARM TO DDC.

19. PROVIDE 1/2" NON-POTABLE WATER TO HUMIDIFIER AND RO SYSTEM FROM BACKFLOW PREVENTER.

20. PROVIDE REDUCED PRESSURE ZONE BACKFLOW PREVENTER ON WALL AND ROUTE 1/2" DOMESTIC COLD

WATER TO BACKFLOW PREVENTER.

21. ROUTE BACKFLOW PREVENTER DRAIN LINE TO FLOOR DRAIN APPROXIMATELY IN THIS LOCATION. DO NOT

ROUTE DRAIN OVER EXISTING ELECTRICAL EQUIPMENT.

22. MAINTAIN HUMIDIFIER MANUFACTURERS REQUIRED “NON-WETTING” CLEARANCES FROM

HUMIDIFIER. COORDINATE WITH OTHER TRADES TO ENSURE NO SOLID SURFACES OR OBJECTS ARE

LOCATED WITHIN THE MANUFACTURES “NON-WETTING” DISTANCES.

GENERAL NOTES:

0 2' 4'1'

CLOUDED AREAS ARE

ACCEPTABLE LOCATIONS

FOR CONDENSING UNITS.

PHOTO 01

REMARKS:

1. PERFORMANCE BASED ON CONDITIONS INDICATED IN THIS SCHEDULE.

2. PROVIDE THE FOLLOWING ACCESSORIES: MANUFACTURER'S DISCONNECT AND LINESET.

3. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT

BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR

PRIOR TO ORDERING EQUIPMENT.

REMARKS:

1. PERFORMANCE BASED ON CONDITIONS INDICATED IN THIS SCHEDULE.

2. PROVIDE CONCRETE PAD AND ANCHOR EXTERIOR UNIT TO PAD.

3. PROVIDE CURB RAILS AND ROOF SUPPORTS FOR OUTDOOR UNIT.

4. PROVIDE THE FOLLOWING ACCESSORIES: SINGLE POINT POWER CONNECTION, DISCONNECT, HAIL GUARDS, LOW AMBIENT KIT, WIND BAFFLES.

5. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT

BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR

PRIOR TO ORDERING EQUIPMENT.

REMARKS:

1. PROVIDE DISCONNECT.

2. PROVIDE VIBRATION ISOLATION.

3. PROVIDE WITH 18" ROOF CURB.

4. PROVIDE AUTOMATIC BACKDRAFT DAMPER INTERLOCKED WITH MOTOR.

REMARKS:

1. PROVIDE FILTER BANK HOLDING FRAME. SUPPORT FRAME FROM STRUCTURE.

2. PROVIDE 24" x 12" FILTER.

REMARKS:

1. PROVIDE WITH INTEGRAL CONDENSATE COOLER, BLOWER PACK.

REMARKS:

1. PERFORMANCE BASED ON FLUID AND CONDITIONS INDICATED IN THIS SCHEDULE.

2. PROVIDE WITH HIGH WATER LEVEL (OVERFLOW DETECTION) SWITCH WITH TERMINAL FOR CONNECTION TO DDC

EXTERNAL ALARM.

3. PROVIDE WITH 6’, 3-CONDUCTOR CABLE WITH GROUNDED 3-PRONGE PLUG.

4. MAXIMUM 5’ OF 3/8” VINYL DISCHARGE TUBING FOR TRANSITION CONNECTION TO COPPER PUMPED CONDENSATE

PIPING.

5. PROVIDE WITH BRASS CHECK VALVE.

REMARKS:

1. COORDINATE EXACT MODEL AND FRAME WITH CEILING / WALL TYPE.

2. WHEN INSTALLED IN A WALL, THE BLADES FOR THESE GRILLES SHALL BE SUCH THAT THE FRONT BLADES ARE HORIZONTAL (PARALLEL TO THE

FLOOR). WHEN INSTALLED IN A CEILING, THE BLADES FOR THESE GRILLES SHALL BE SUCH THAT THE FRONT BLADES ARE PARALLEL TO THE LONG

DIMENSION OF THE GRILLE.

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:0

:0

P

M

B127-M600

MECHANICAL SCHEDULES EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B127

04/15/2022 JMM GTS

16181

84 176

SPLIT SYSTEM AIR CONDITIONER - INDOOR SCHEDULE

MARK

ROOM SERVED

NOMINAL

CAPACITY

[TONS]

TOTAL COOLING

CAPACITY

[MBH]

CONDENSATE DRAIN

SIZE

INDOOR UNIT ELECTRICAL DATA

MANUFACTURER REMARKSNAME NUMBER

DIMENSIONS [IN] EAT

(DB / WB)

[°F] MODEL FLA VOLTAGE PHASE MCA DISCONNECT BY SCCRLENGTH WIDTH HEIGHT

SSIU-127-101A ELEC/UPS 101 2.5 30 3/4" 46 1/16" 11 5/8" 14 3/8" 90/72 PKA-A30KA7 0.36 208 V 1 1 MANUFACTURER 5 MITSUBISHI ELECTRIC (1)(2)(3)

SSIU-127-101B ELEC/UPS 101 2.5 30 3/4" 46 1/16" 11 5/8" 14 3/8" 90/72 PKA-A30KA7 0.36 208 V 1 1 MANUFACTURER 5 MITSUBISHI ELECTRIC (1)(2)(3)

SSIU-127-101C ELEC/UPS 101 2.5 30 3/4" 46 1/16" 11 5/8" 14 3/8" 90/72 PKA-A30KA7 0.36 208 V 1 1 MANUFACTURER 5 MITSUBISHI ELECTRIC (1)(2)(3)

SSIU-127-102A ENTRANCE FACILITY 102 2.0 24 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0241KA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)

SSIU-127-102B ENTRANCE FACILITY 102 2.0 24 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0241KA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)

SSIU-127-102C ENTRANCE FACILITY 102 2.0 24 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0241KA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)

SPLIT SYSTEM AIR CONDITIONER - OUTDOOR SCHEDULE

MARK

ROOM SERVED

NOMINAL

CAPACITY

[TONS]

TOTAL COOLING

CAPACITY

[MBH]

OUTDOOR UNIT ELECTRICAL DATA

MANUFACTURER REMARKSNAME NUMBER

DIMENSIONS [IN] SUMMER AMBIENT

AIR

[°F]

WINTER AMBIENT

AIR

[°F]

OPERATING

WEIGHT

[LBS] MODEL FLA VOLTAGE PHASE MCA MOCP DISCONNECT BY SCCRLENGTH WIDTH HEIGHT

SSOU-127-101A ELEC/UPS 101 2.5 30 37 7/16" 13 3/16" 37 1/8" 115 -40 151 PUY-A30NHA7 0.4 208 V 1 19 26 ELEC 5 MITSUBISHI ELECTRIC (1)(2)(3)(4)(5)

SSOU-127-101B ELEC/UPS 101 2.5 30 37 7/16" 13 3/16" 37 1/8" 115 -40 151 PUY-A30NHA7 0.4 208 V 1 19 26 ELEC 5 MITSUBISHI ELECTRIC (1)(2)(3)(4)(5)

SSOU-127-101C ELEC/UPS 101 2.5 30 37 7/16" 13 3/16" 37 1/8" 115 -40 151 PUY-A30NHA7 0.4 208 V 1 19 26 ELEC 5 MITSUBISHI ELECTRIC (1)(2)(3)(4)(5)

SSOU-127-102-A ENTRANCE FACILITY 102 2.0 24 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0241HA70NA 11.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)

SSOU-127-102-B ENTRANCE FACILITY 102 2.0 24 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0241HA70NA 11.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)

SSOU-127-102-C ENTRANCE FACILITY 102 2.0 24 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0241HA70NA 11.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)

FAN SCHEDULE

MARK TYPE

AIRFLOW

[CFM]

DUCT CONNECTION SIZE

[IN]

TOTAL S.P.

[IN W.C.] MAX FAN RPM MAX FAN BHP

ELECTRICAL DATA

MANUFACTURER MODEL REMARKSHP VOLTAGE PHASE

SF-1 INLINE 700 18 x 18 0.75 1,393 0.19 0.5 115 V 1 GREENHECK SQ-130HP-VG (1)(2)

EF-1 DOWNBLAST 200 8 x 8 0.38 1,589 0.03 0.1 115 V 1 GREENHECK G-070-VG (3)(4)

FILTER SCHEDULE

MARK ASSOCIATED EQUIPMENT FUNCTION TYPE

DEPTH

[IN] MERV RATING REMARKS

PF-1 SF-1 PREFILTER PLEATED 2 8 (1)(2)

ELECTRODE STEAM HUMIDIFIER SCHEDULE

MARK SERVICE

MAKE UP WATER

CONNECTION SIZE

WATER PIPING ELECTRICAL DATA

MANUFACTURER MODEL REMARKS

CAPACITY

[GAL / HR]

DRAIN PIPE CONNECTION

SIZE KW VOLTAGE PHASE

H-1 ENTRANCE FACILITY 102 1/2" 5.6 3/4" 1.9 120 V 1 DRISTEEM XTR (1)

H-2 ELEC/UPS 101 1/2" 5.6 3/4" 1.9 120 V 1 DRISTEEM XTR (1)

PUMP SCHEDULE

MARK

FLOW

[GPH]

TOTAL HEAD

[FT]

SHUT-OFF HEAD

[FT]

SUCTION /

DISCHARGE SIZE

[IN]

ELECTRICAL DATA

MANUFACTURER MODEL REMARKSHP FLA VOLTAGE

CP-1 200 20 32 3/8" 0.125 1.4 115 V LITTLE GIANT HT-VCL-30-P (1)(2)(5)

CP-2 10 20 21 3/8" 0.033 1.5 115 V LITTLE GIANT VCMX-20ULS (1)(2)(3)(4)

DIFFUSER, REGISTER, AND GRILLE SCHEDULE add remarks

MARK IMAGE DESCRIPTION MAX S.P. MATERIAL FINISH

FACE SIZE

NECK SIZE AIRFLOW MANUFACTURER MODEL REMARKSLENGTH WIDTH

D2 DOUBLE DEFLECTION

SUPPLY GRILLE

0.10 in-wg STEEL PAINT, WHITE SEE PLAN SEE PLAN SEE PLAN SEE PLAN TITUS

KRUEGER

PRICE

300RL/SL

(1)(2)

G1 SINGLE DEFLECTION

RETURN GRILLE

0.10 in-wg STEEL PAINT, WHITE SEE PLAN SEE PLAN SEE PLAN SEE PLAN TITUS

KRUEGER

PRICE

350RL/SL

S80

(1)

GE7 SINGLE DEFLECTION

RETURN GRILLE

0.10 in-wg STEEL PAINT, WHITE SEE PLAN SEE PLAN SEE PLAN SEE PLAN TITUS

KRUEGER

PRICE

350RL/SL

S80

(1)

A R

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

A R

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

TU R 27 28 29

23m

24s

25s 25 2626s

22 23s

191817161515s

13 14

14s13s

10KL

MNOPQS

5s 6 6s 7m

7s

J

Jw

Cm

2 3

4 4s

Im

Iw

Hm

A

B

C

D

E

F

G

H

Am

Bw

I

KEY PLAN

MAIN

ENTRY

BUILDING 138

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:3

:0

P

M

B138-M100

BASEMENT LEVEL FLOOR PLAN -

OVERALL - MECHANICAL - DEMO

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

04/15/2022 JMM GTS

16181

85 176

3/32" = 1'-0" F2

BASEMENT LEVEL FLOOR PLAN - MECHANICAL - DEMO - OVERALL*

0 8' 16'4'

E A

A

A R

E A

B

A R

E A

A

A R

E A

B

TU R

10KL

MNOPQS

5s 6 6s 7m

7s

J

Jw

Cm

2 3

4 4s

Im

Iw

Hm

A

B

C

D

E

F

G

H

Am

Bw

I

4" SAN 4" SAN

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:3

:0

P

M

B138-M100-A

BASEMENT LEVEL FLOOR PLAN -

AREA A - MECHANICAL - DEMO

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

04/15/2022 JMM GTS

16181

86 176

1/8" = 1'-0" F3

BASEMENT LEVEL FLOOR PLAN - AREA A - MECHANICAL - DEMO

0 8' 16'4'

SHEET NOTES:

1. REMOVE SECTION OF EXISTING 22X7 DUCT AND RELOCATE EAST. REFER TO NEW WORK PLAN FOR

RELOCATION.

GENERAL NOTES:

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE

ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

A R

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

191817161515s

13 14

14s13s

J

Jw

Cm

Im

Iw

Hm

A

B

C

D

E

F

G

H

Am

Bw

I

DCW

DHW

DHWC

18x16 20x12

14x12 8ø

HPS

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:3

:0

P

M

B138-M100-B

BASEMENT LEVEL FLOOR PLAN -

AREA B - MECHANICAL - DEMO

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

04/15/2022 JMM GTS

16181

87 176

1/8" = 1'-0" F3

BASEMENT LEVEL FLOOR PLAN - AREA B - MECHANICAL - DEMO

0 8' 16'4'

SHEET NOTES:

1. WATER CLOSET AND TRIM TO BE REPLACED WITH NEW. REFER TO NEW WORK PLAN.

2. LAVATORY TO BE SALVAGED FOR RELOCATION. DEMOLISH EXISTING LAVATORY FAUCET AND TRIM. REFER

TO NEW WORK PLAN FOR ADDITIONAL INFORMATION. EXISTING BRANCH WATER LINES AND ISOLATION

VALVES TO BE REUSED.

3. EXISTING WATER AND STEAM LINES IN SPACE TO REMAIN. REFER TO NEW WORK PLANS FOR DRAIN PAN

AND SENSOR REQUIREMENTS.

4. DEMOLISH EXISTING EXHAUST DUCTWORK SERVING BATHROOM.

5. DEMOLISH EXISTING SPRINKLER HEADS.

6. DEMOLISH ONE EXISTING SUPPLY DUCT AND ONE EXISTING RETURN DUCT AND ASSOCIATED DIFFUSERS

AND GRILLES THAT SERVE THE ROOM TO A POINT TWO FEET OUTSIDE THE PERIMETER OF THE ROOM.

ESTIMATED DUCT SIZES ARE NINE INCH.

GENERAL NOTES:

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE

E A

B

A R

E A

C

A R

E A

B

A R

E A

C

27 28 29

23m

24s

25s 25 2626s

22 23s

J

Jw

Cm

Im

Iw

Hm

A

B

C

D

E

F

G

H

Am

Bw

I

DCW

DHW

DHWC

18x16 20x12

14x12

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:3

:1

P

M

B138-M100-C

BASEMENT LEVEL FLOOR PLAN -

AREA C - MECHANICAL - DEMO

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

04/15/2022 JMM GTS

16181

88 176

1/8" = 1'-0" F3

BASEMENT LEVEL FLOOR PLAN - AREA C - MECHANICAL - DEMO

0 8' 16'4'

SHEET NOTES:

1. PRETEST SUPPLY AND EXHAUST OUTLETS IN MORGUE UNDER ALL OPERATING CONDITIONS AND RECORD

AND SUBMIT RESULTS TO THE COR. RECORD ROOM PRESSURIZATION LEVELS AS PART OF THE TEST AND

BALANCE.

GENERAL NOTES:

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

A R

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

TU R 27 28 29

23m

24s

25s 25 2626s

22 23s

191817161515s

13 14

14s13s

10KL

MNOPQS

5s 6 6s 7m

7s

J

Jw

Cm

2 3

4 4s

Im

Iw

Hm

A

B

C

D

E

F

G

H

Am

Bw

I

KEY PLAN

MAIN

ENTRY

BUILDING 138

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:3

:1

P

M

B138-M101

FIRST LEVEL FLOOR PLAN -

OVERALL - MECHANICAL - DEMO

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

04/15/2022 JMM GTS

16181

89 176

3/32" = 1'-0"F2

FIRST LEVEL FLOOR PLAN - MECHANICAL - DEMO - OVERALL*

E A

A

A R

E A

B

A R

E A

A

A R

E A

B

TU R

10KL

MNOPQS

5s 6 6s 7m

7s

J

Jw

Cm

2 3

4 4s

Im

Iw

Hm

A

B

C

D

E

F

G

H

Am

Bw

I

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:3

:1

P

M

B138-M101-A

FIRST LEVEL FLOOR PLAN - AREA

A - MECHANICAL - DEMO

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

04/15/2022 JMM GTS

16181

90 176

1/8" = 1'-0" F3

FIRST LEVEL FLOOR PLAN - AREA A - MECHANICAL - DEMO

0 8' 16'4'

SHEET NOTES:

1. DEMOLISH EXISTING ROOM SPRINKLER HEADS. DEMOLISH EXISTING SPRINKLER PIPING AS NECESSARY TO

ACCOMMODATE NEW WORK PLAN.

2. DEMOLISH HEATING HOT WATER LINES ROUTING TO EXISTING CABINET HEATER IN STAIRWELL. SEE NEW

WORK PLAN FOR NEW LINES TO SERVE CABINET UNIT HEATER.

3. EXISTING TERMINAL BOX TO BE SAVED FOR RELOCATION. REFER TO NEW PLAN FOR NEW LOCATION.

CONFIRM EXISTING BALANCE AIRFLOW BEFORE REMOVED.

4. DEMOLISH HEATING HOT WATER LINE SERVING TERMINAL AIR BOX AND UNIT HEATER. REFER TO NEW WORK

PLAN FOR NEW HEATING HOT WATER LINES.

5. UNIDENTIFIED BLACK COATED PIPE IN CEILING. DEMOLISH EXTENTS OF PIPE WITHIN BOUNDARIES OF NEW

TR ROOM.

6. EXISTING STEAM LINES TO REMAIN. PROVIDE DRAIN PAN WITH WATERBUG ALARM. ALARM TO BUILDING

MANAGEMENT SYSTEM.

GENERAL NOTES:

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

A R

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

191817161515s

13 14

14s13s

J

Jw

Cm

Im

Iw

Hm

A

B

C

D

E

F

G

H

Am

Bw

I

EXPECTED AREA OF

DEMOLITION AND REWORK

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:3

:1

P

M

B138-M101-B

FIRST LEVEL FLOOR PLAN - AREA

B - MECHANICAL - DEMO

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

04/15/2022 JMM GTS

16181

91 176

1/8" = 1'-0" F3

FIRST LEVEL FLOOR PLAN - AREA B - MECHANICAL - DEMO

0 8' 16'4'

SHEET NOTES:

1. DEMOLISH SUPPLY DUCTWORK AS SHOWN AND CAP END OF EXISTING DUCT. TEST UPSTREAM TERMINAL

BOX AND DOWNSTREAM OUTLETS BEFORE DEMOLITION AND RECORD RESULTS. REBALANCE EXISTING DIFFUSERS TO REMAIN TO PRE-BALANCE READINGS AND REDUCE TERMINAL AIR BOX SETTING TO NEW

VALUES.

2. DEMOLISH HEATING HOT WATER MAINS ROUTING THROUGH PROPOSED TR SPACE AS SHOWN. REFER TO

NEW WORK PLAN FOR REROUTING.

3. DEMOLISH HEATING HOT WATER LINES ROUTING TO EXISTING HEATING UNIT IN STAIRWELL. REFER TO NEW

WORK PLAN FOR REROUTING.

4. EXISTING STEAM LINES SERVING HEATER IN STAIRWELL TO REMAIN. PROVIDE DRAIN PAN UNDER PIPING

WITH WATERBUG ALARM TO DDC.

5. EXISTING ISOLATION EXHAUST DUCT TO REMAIN.

GENERAL NOTES:

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE

E A

B

A R

E A

C

A R

E A

B

A R

E A

C

27 28 29

23m

24s

25s 25 2626s

22 23s

J

Jw

Cm

Im

Iw

Hm

A

B

C

D

E

F

G

H

Am

Bw

I

EXPECTED AREA

OF DEMOLITION

AND REWORK

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:3

:2

P

M

B138-M101-C

FIRST LEVEL FLOOR PLAN - AREA

C - MECHANICAL - DEMO

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

04/15/2022 JMM GTS

16181

92 176

1/8" = 1'-0" F3

FIRST LEVEL FLOOR PLAN - AREA C - MECHANICAL - DEMO

0 8' 16'4'

GENERAL NOTES:

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

A R

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

TU R 27 28 29

23m

24s

25s 25 2626s

22 23s

191817161515s

13 14

14s13s

10KL

MNOPQS

5s 6 6s 7m

7s

J

Jw

Cm

2 3

4 4s

Im

Iw

Hm

A

B

C

D

E

F

G

H

Am

Bw

I

KEY PLAN

MAIN

ENTRY

BUILDING 138

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:3

:2

P

M

B138-M102

SECOND LEVEL FLOOR PLAN -

OVERALL - MECHANICAL - DEMO

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

04/15/2022 JMM GTS

16181

93 176

3/32" = 1'-0" F2

SECOND LEVEL FLOOR PLAN - MECHANICAL - DEMO - OVERALL*

E A

A

A R

E A

B

A R

E A

A

A R

E A

B

TU R

10KL

MNOPQS

5s 6 6s 7m

7s

J

Jw

Cm

2 3

4 4s

Im

Iw

Hm

A

B

C

D

E

F

G

H

Am

Bw

I

1 2

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:3

:3

P

M

B138-M102-A

SECOND LEVEL FLOOR PLAN -

AREA A - MECHANICAL - DEMO

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

04/15/2022 JMM GTS

16181

94 176

1/8" = 1'-0" F3

SECOND LEVEL FLOOR PLAN - AREA A - MECHANICAL - DEMO

0 8' 16'4'

SHEET NOTES:

1. DEMOLISH SUPPLY DIFFUSER AND ASSOCIATED SUPPLY DUCT SERVING OFFICE 226. REFER TO NEW WORK

PLAN FOR SUPPLY AIR REVISIONS TO THIS SPACE. EXISTING SUPPLY DUCT THROUGH SPACE TO REMAIN.

2. DEMOLISH EXISTING RETURN DUCT AND RETURN DIFFUSER IN OFFICE 226 BACK TO CONNECTION TO MAIN.

3. DEMOLISH EXISTING ROOM SPRINKLER HEADS. DEMOLISH EXISTING SPRINKLER PIPING AS NECESSARY TO

ACCOMMODATE NEW WORK PLAN.

4. REMOVE SECTION OF DUCT AT PENETRATION OF WALL AND REPLACE WITH MINIMUM 22 GAUGE SHEET

METAL AND THROUGH PENETRATION FIRE STOPPING TO MEET WALL RATINGS TO AVOID INSTALLATION OF

FIRE DAMPER.

5. CONFIRM AIR BALANCE OF SUPPLY DIFFUERS DOWNSTREAM OF EXISTING OFFICE 226. AFTER COMPLETION

OF NEW WORK, RETURN DIFFUSERS TO PREVIOUS AIR BALANCE VALUES.

6. EXISTING STEAM RISERS AND LATERAL PIPING IN SPACE TO REMAIN. PROVIDE DRAIN PAN WITH WATER BUG

SENSOR ALARM IN DRAIN PAN. WATER BUG TO ALARM TO BUILDING MANAGEMENT SYSTEM.

GENERAL NOTES:

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

A R

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

191817161515s

13 14

14s13s

J

Jw

Cm

Im

Iw

Hm

A

B

C

D

E

F

G

H

Am

Bw

I

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:3

:3

P

M

B138-M102-B

SECOND LEVEL FLOOR PLAN -

AREA B - MECHANICAL - DEMO

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

04/15/2022 JMM GTS

16181

95 176

1/8" = 1'-0" F3

SECOND LEVEL FLOOR PLAN - AREA B - MECHANICAL - DEMO

0 8' 16'4'

SHEET NOTES:

1. REMOVE SUPPLY DUCTWORK TO OUTSIDE THE ROOM.

2. REMOVE ALL DOMESTIC AND SANITARY PIPING SERVING SINK. BACK TO THEIR CONNECTIONS TO MAINS AND

CAP. REMOVE PIPING AND VALVES ABOVE THE CEILING BACK TO MAIN CONNECTIONS AND CAP.

3. CAP EXISTING EXHAUST DUCT SERVING PHYSIATRY HOOD ABOVE CEILING.

4. DEMOLISH EXISTING ROOM SPRINKLER HEADS. DEMOLISH EXISTING SPRINKLER PIPING AS NECESSARY TO

ACCOMMODATE NEW WORK PLAN.

5. DEMOLISH WALL HUNG LAVATORY. PREPARE PLUMBING CONNECTIONS FOR CONNECTION TO NEW SINK.

GENERAL NOTES:

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

A R

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

TU R 27 28 29

23m

24s

25s 25 2626s

22 23s

191817161515s

13 14

14s13s

10KL

MNOPQS

5s 6 6s 7m

7s

J

Jw

Cm

2 3

4 4s

Im

Iw

Hm

A

B

C

D

E

F

G

H

Am

Bw

I

KEY PLAN

MAIN

ENTRY

BUILDING 138

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:3

:3

P

M

B138-M103

THIRD LEVEL FLOOR PLAN -

OVERALL - MECHANICAL - DEMO

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

04/15/2022 JMM GTS

16181

96 176

3/32" = 1'-0" F2

THIRD LEVEL FLOOR PLAN - MECHANICAL - DEMO - OVERALL*

E A

A

A R

E A

B

A R

E A

A

A R

E A

B

TU R

10KL

MNOPQS

5s 6 6s 7m

7s

J

Jw

Cm

2 3

4 4s

Im

Iw

Hm

A

B

C

D

E

F

G

H

Am

Bw

I

STAIRS

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:3

:3

P

M

B138-M103-A

THIRD LEVEL FLOOR PLAN - AREA

A - MECHANICAL - DEMO

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

04/15/2022 JMM GTS

16181

97 176

1/8" = 1'-0"F3

THIRD LEVEL FLOOR PLAN - AREA A - MECHANICAL - DEMO

0 8' 16'4'

SHEET NOTES:

1. REMOVE MEDICAL GAS PIPING IN CEILING BACK TO CONNECTION TO MAIN AND CAP.

2. REMOVE ALL DOMESTIC AND SANITARY PIPING SERVING SINK BACK TO THEIR CONNECTIONS TO MAINS AND

CAP. REMOVE PIPING AND VALVES ABOVE THE CEILING BACK TO MAIN CONNECTIONS AND CAP.

3. STEAM PIPING RISER SERVING THIRD FLOOR TO REMAIN. PROVIDE WATER BUG ALARM SENSOR AT FLOOR

LEVEL. WATER BUG TO ALARM TO BUILDING MANAGEMENT SYSTEM.

4. DEMOLISH EXISTING ROOM SPRINKLER HEADS.

GENERAL NOTES:

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

A R

E A

A

A R

E A

B

A R

E A

B

A R

E A

C

191817161515s

13 14

14s13s

J

Jw

Cm

Im

Iw

Hm

A

B

C

D

E

F

G

H

Am

Bw

I

STAIRS

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.T

R

.r v t

/1

/2

:3

:4

P

M

B138-M103-B

THIRD LEVEL FLOOR PLAN - AREA

B - MECHANICAL - DEMO

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

04/15/2022 JMM GTS

16181

98 176

1/8" = 1'-0" F3

THIRD LEVEL FLOOR PLAN - AREA B - MECHANICAL - DEMO

0 8' 16'4'

SHEET NOTES:

1. REMOVE AND SALVAGE EXISTING WINDOW AIR CONDITIONERS FOR RE-USE.

2. DEMOLISH EXISTING ROOM SPRINKLER HEADS.

3. DEMOLISH TWO PERIMETER CABINET UNIT HEATERS AND PIPING BACK TO CONNECTION TO MAIN.

GENERAL NOTES:

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR

DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER

PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL

PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO

PERFORM THIS WORK.

5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE

E A

B

A R

E A

C

A R

E A

B

A R

E A

C

27 28 29

23m

24s

25s 25 2626s

22 23s

J

Jw

Cm

Im

Iw

Hm

A

B

C

D

E

F

G

H

Am

Bw

I

STAIRS

BATH

340A

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459 Sheet of

04/15/2022