Atch 11 - ELEC 3 of 3 - DRAWINGS.pdf

PDF 16 MB Posted

Attached to
Y1AZ--EHRM Infrastructure Upgrades Construction - Marion Federal contract opportunity
Solicitation number
36C77622B0040
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This federal contract opportunity solicitation involves infrastructure upgrades and renovations at the Department of Veterans Affairs facility in Marion, Illinois. The project scope includes electrical, bonding, UPS, building management system, HVAC, communication, physical security, and fiber infrastructure upgrades across multiple buildings on campus as well as modification to impacted roads, walks, grading, drainage, and other existing utilities. The solicitation also requires Data Center WAN updates and hazardous material abatement. Offerors are invited to respond to solicitation number 36C77622B0040 by the specified deadline to provide the products and services outlined for the Y1AZ--EHRM Infrastructure Upgrades Construction project located at the Marion VA facility.

View the file

Other files for this federal contract opportunity

Other files attached to Y1AZ--EHRM Infrastructure Upgrades Construction - Marion, newest first.
File Type Posted
Clarifications - Marion.pdf PDF
Atch 27 - Construction Wage Rates - Grant 8-19-22.pdf PDF
36C77622B0040 0005.pdf PDF
Technical Questions - FINAL - Marion 8-11-22.pdf PDF
36C77622B0040 0004.pdf PDF
Atch 27 - Construction Wage Rates - Grant 8-12-22.pdf PDF
03 30 00 - Cast-In-Place Concrete.pdf PDF
Atch 27 - Construction Wage Rates - Grant 7-15-22.pdf PDF
36C77622B0040 0003.pdf PDF
36C77622B0040 0002.pdf PDF
Atch 27 - Construction Wage Rates - Grant 7-8-22.pdf PDF
Site Visit Sign-in Sheet - Marion 7-11-22.pdf PDF
36C77622B0040 0001.pdf PDF
Atch 1 - SPECIFICATIONS.pdf PDF
Atch 4 - ARCH 2 of 4 - DRAWINGS.pdf PDF
Atch 5 - ARCH 3 of 4 - DRAWINGS.pdf PDF
Atch 9 - ELEC 1 of 3 - DRAWINGS.pdf PDF
Atch 10 - ELEC 2 of 3 - DRAWINGS.pdf PDF
Atch 12 - GENERAL - DRAWINGS.pdf PDF
Atch 16 - MECH 2 of 7 - DRAWINGS.pdf PDF
Atch 20 - MECH 6 of 7 - DRAWINGS.pdf PDF
Atch 23 - TELECOM 1 of 2 - DRAWINGS.pdf PDF
Atch 27 - Construction Wage Rates - Grant 6-10-22.pdf PDF
36C77622B0040 - 6-27-22.pdf PDF
Atch 3 - ARCH 1of 4 - DRAWINGS.pdf PDF
Atch 8 - CIVIL 2 of 2 - DRAWINGS.pdf PDF
Atch 26 - Limitations on Subcontracting - Construction.docx DOCX document
Atch 21 - MECH 7 of 7 - DRAWINGS.pdf PDF
Atch 7 - CIVIL 1 of 2 - DRAWINGS.pdf PDF
Atch 13 - HAZARDOUS ASBESTOS - DRAWINGS.pdf PDF
Atch 14 - HAZARDOUS LEAD BASED PAINT - DRAWINGS.pdf PDF
Atch 22 - STRUCTURAL - DRAWINGS.pdf PDF
Atch 24 - TELECOM 2 of 2 - DRAWINGS.pdf PDF
Atch 25 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Atch 15 - MECH 1 of 7 - DRAWINGS.pdf PDF
Atch 2 - DRAWINGS SHEET INDEX.pdf PDF
Atch 6 - ARCH 4 of 4 - DRAWINGS.pdf PDF
Atch 17 - MECH 3 of 7 - DRAWINGS.pdf PDF
Atch 18 - MECH 4 of 7 - DRAWINGS.pdf PDF
Atch 19 - MECH 5 of 7 - DRAWINGS.pdf PDF
Atch 28 - Contractor Safety - Environmental Form.docx DOCX document
Atch 29 - Site Visit Instructions.pdf PDF
Show all 42

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J

E

E

E

{LS1}

A

E

J J

E

E

{LS1}

A

138-U-TR-11

138-N-TR-11

1,3,5

7,9,11

13,15,17

1,3,5

7,9,11

13,15,17

MX-1

INDOOR SPLIT

MX-1

INDOOR SPLIT

TEMP. CONTROL PANEL/12

SECURITY PANEL/16

138-N-TR-11-4

VAV

F1

F1

F1

F1E

NL

O

138-U-TR-12

138-N-TR-12

1,3,5

7,9,11

13,15,17

1,3,5

7,9,11

13,15,17

SECURITY PANEL/2

MX-1

MX-1

INDOOR SPLIT

INDOOR SPLIT

TEMP. CONTROL PANEL/12

SECURITY PANEL/2

F1

F1

F1

F1E

NL

O

KEY PLAN

MAIN

ENTRY

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459

04/15/2022 Sheet of

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.E

R

.r v t

/1

/2

:5

:2

P

M

B138-E103

FIRST LEVEL PLAN - ENLARGED

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

ZWC PD

16181

81 127

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 21001283.00

1/4" = 1'-0"

FIRST LEVEL PLAN -

ELECTRICAL POWER - TR 104C

1/4" = 1'-0"

FIRST LEVEL PLAN - ELECTRICAL

LIGHTING & FIRE ALARM - TR 104C

1/4" = 1'-0"

FIRST LEVEL PLAN -

ELECTRICAL POWER - TR 163

1/4" = 1'-0"

FIRST LEVEL PLAN - ELECTRICAL

LIGHTING & FIRE ALARM - TR 163

KEY NOTES:

1. EXTEND EXISTING FIRE ALARM SYSTEM

NOTIFICATION CIRCUIT VIA 3/4"C AND WIRING AS

DIRECTED BY MANUFACTURER'S WIRING DIAGRAMS

AND CONNECT NEW NOTIFICATION APPLIANCE

COMPLETE.

2. INDOOR UNIT IS POWERED FROM OUTDOOR UNIT.

PROVIDE 3/4" CONDUIT AND WIRING BETWEEN

INDOOR UNIT AND OUTDOOR UNIT PER

MANUFACTURER.

3. PROVIDE CIRCUIT INDICATED FOR NEW VAV.

CONNECT CIRCUIT COMPLETE TO VAV LOW-

VOLTAGE TRANSFORMER AND CONNECT VAV

COMPLETE PER MANUFACTURER'S WIRING

DIAGRAMS.

GENERAL NOTES:

1. CONTRACTOR SHALL REFER TO SHEET ES-E000, ES-

E300, AND ES-E500 FOR LEGENDS, SCHEDULES,

NOTES AND OTHER GENERAL INFORMATION.

2. CONTRACTOR IS PERMITTED TO ADJUST LAYOUT AS

NECESSARY TO ACCOMMODATE OTHER SYSTEMS

AND COORDINATE WITH EXISTING DUCT WORK.

GENERAL LOCATION SHALL BE MAINTAINED. DO NOT

MOUNT LUMINAIRES TO THE DUCT WORK. MOUNT

LUMINAIRE SUCH THAT SHADOWS ARE NOT CAST.

3. RECEPTACLES, LIGHTING AND EQUIPMENT ON THIS

SHEET SHALL BE CONNECTED TO PANELBOARDS

WITHIN THE IT ROOM UNLESS OTHERWISE

INDICATED. SHADING INDICATES CONNECTION TO

EMERGENCY/UPS PANEL.

Revisions: Date:

04/15/2022 16181

B138-E105

3B138-E105

PHLEMB

LAB

PHLEMB

LAB

OFFICE

TR

S2

STAIRS

H.A.C.

CHECK IN

C204

CORRIDOR

CHECK IN

OFFICE

DENTAL

STORAGE

AUDIOLOGY

EXAM

OFFICE

OFFICE

CORRIDOR

C205

CORRIDOR

EXAM

AUDIO

EXAM

TESTER

OFFICE

AUDIO

TESTING

BOOTH

SUPPLY

STAFF

LOUNGE

TOILET

224A

BATH

TOILET

C203

CORRIDOR

EXAM

EXAM

SOILED

UTILITY

DENTAL

WAITING

CORRIDOR

C202

CORRIDOR

DENTAL

TREATMENT

210A

STORAGE

210B

FMS

OPERATORY

OPERATORY

CORRIDOR

ORAL

SURGERY

CLEAN

UTILITY

C O

R R

ID

O

R

ELEVATOR

ELEVATOR

H.A.C.

278A

PHYSIATRY

OFFICE

OFFICE

DENTAL LAB

OPERATORY

OPERATORY

OPERATORY

OPERATORY

C200

CORRIDOR

S1

STAIRS

TOILET

C201

CORRIDOR

WAITING

ELEC33

ELEVATOR

STORAGE

LOUNGE

OFFICE

LOCKER

C209

LOCKER

240A

CHECK IN

STORAGE

241A

EYE EXAM

272B

TR

VEST

272A

EXAM

CORRIDOR

OFFICE

OFFICE

TOILET

FMS

EXAM

OFFICE

OFFICE

ULTRASOUND

CLEAN

SUPPLY

NEUROLOGY

OFFICE

PROCEDURE

PROCEDURE

TOILET

SOILED

LINEN

STORAGE

SUPPLY

C206

CORRIDOR

STAIRS

247A

CT

CONTROL

CT SCAN

OFFICE

SUB-WAIT 250

CHECK IN

C207

CORRIDOR

OFFICE

X-RAY

X-RAY254

WORKROOM

X-RAY

ELEC

ELEC

STORAGE

253A

BATH

252A

BATH

151412

7s77m6s65s5

4s4

321 13

Jw

Im

Iw

He

H

F

E

D

Bw

Am

C

B

A

22 23s 23 24s 24 25 26s 2726 28

25s

I

J

23m

14s

Hm

Cm

G

KLM

N

OPQ

R

STU V

W

Y

13s

206A

FMS

233B

OFFICE

233A

STORAGE

P A

S S

A G

E W

A Y

B138-E105

B138-E105

B138-E105

B138-E105

B138-E105

B138-E105

138-L2B

138-P2B 138-L2A

138-P2A

138-P2C138-E2C

138-L2C

KEY PLAN

MAIN

ENTRY

BUILDING 138

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459

04/15/2022 Sheet of

FULLY SPRINKLERED

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.E

R

.r v t

/1

/2

:5

:2

P

M

B138-E104

SECOND LEVEL PLAN -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

ZWC PD

16181

82 127

3/32" = 1'-0"

SECOND LEVEL PLAN - ELECTRICAL POWER

GENERAL NOTES:

1. CONTRACTOR SHALL REFER TO SHEET ES-

E000, ES-E300, AND ES-E500 FOR LEGENDS,

SCHEDULES, NOTES AND OTHER GENERAL

INFORMATION.

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 21001283.00

Revisions: Date:

E

E

{LS1} A

J

J E

E

{LS1}

A

A1

{LS1}

{LD1}

A1

OC

A1

TOILET

233B

OFFICE

233A

STORAGE

P A

S S

A G

E W

A Y

138-L2B 40

138-L2B 40 138-L2B 40

138-L2B 40

138-L2B 40138-L2B 40

138-L2B 40 138-L2B 40

138-N-TR-21

138-U-TR-21

TR

INDOOR SPLIT

MX-1

INDOOR SPLIT

1,3,5

7,9,11

13,15,17

1,3,5

7,9,11

13,15,17

MX-1

SECURITY PANEL/4

TEMP. CONTROL PANEL/6

138-P2B

138-L2B

F1

F1

F1

F1E

NL

TR

O

138-U-TR-22

138-N-TR-22

S1

STAIRS

272B

TR

VESTMX-1

INDOOR SPLIT

INDOOR SPLIT

,3

,5

,3

,5

,9

,1

,9

,1

,1

,1

,1

,1

SECURITY PANEL/2

MX-1

4 4

TEMP. CONTROL PANEL/6

F1E

NL

F1

F1/8

F1/8

S1

STAIRS

272B

TR

VEST

O

TOILET

233B

OFFICE

233A

STORAGE

P A

S S

A G

E W

A Y

F3 138-L2B

F3 138-L2B

F3 138-L2B

O

F2 138-L2B

F2 138-L2B

ELEVATOR

ELEVATOR

H.A.C.

278A

PHYSIATRY

OFFICE

OFFICE

D

C

14s

Cm 138-P2B 33

138-P2B 33

138-P2B 33

138-P2B 33

138-P2B 33

EXAM

H

F

G

PYXIS

138-E2C-29

A 138-P2C-31

A 138-P2C-31

12" BELOW

FINISHED CEILING

6" BELOW

FINISHED CEILING

138-E2C 14

ELEVATOR

ELEVATOR

H.A.C.

278A

PHYSIATRY

OFFICE

OFFICE

D

C

14s

Cm

EXAM

H

F

G

KEY PLAN

MAIN

ENTRY

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459

04/15/2022 Sheet of

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.E

R

.r v t

/1

/2

:5

:4

P

M

B138-E105

SECOND LEVEL PLAN - ENLARGED

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

ZWC PD

16181

83 127

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 21001283.00

1/4" = 1'-0"

SECOND LEVEL PLAN -

ENLARGED ELECTRICAL

POWER - OFFICE 233A & 233B

1/4" = 1'-0"

SECOND LEVEL PLAN -

ELECTRICAL POWER - TR 226

1/4" = 1'-0"

SECOND LEVEL PLAN -

ELECTRICAL LIGHTING & FIRE

ALARM - TR 226

1/4" = 1'-0"

SECOND LEVEL PLAN -

ELECTRICAL POWER - TR 272B

1/4" = 1'-0"

SECOND LEVEL PLAN -

ELECTRICAL LIGHTING & FIRE

ALARM - TR 272B

KEY NOTES:

1. EXTEND EXISTING FIRE ALARM SYSTEM

NOTIFICATION CIRCUIT VIA 3/4"C AND WIRING AS

DIRECTED BY MANUFACTURER'S WIRING DIAGRAMS

AND CONNECT NEW NOTIFICATION APPLIANCE

COMPLETE.

2. INDOOR UNIT IS POWERED FROM OUTDOOR UNIT.

PROVIDE 3/4" CONDUIT AND WIRING BETWEEN

INDOOR UNIT AND OUTDOOR UNIT PER

MANUFACTURER.

GENERAL NOTES:

1. CONTRACTOR SHALL REFER TO SHEET ES-E000, ES-

E300, AND ES-E500 FOR LEGENDS, SCHEDULES,

NOTES AND OTHER GENERAL INFORMATION.

2. CONTRACTOR IS PERMITTED TO ADJUST LAYOUT AS

NECESSARY TO ACCOMMODATE OTHER SYSTEMS

AND COORDINATE WITH EXISTING DUCT WORK.

GENERAL LOCATION SHALL BE MAINTAINED. DO NOT

MOUNT LUMINAIRES TO THE DUCT WORK. MOUNT

LUMINAIRE SUCH THAT SHADOWS ARE NOT CAST.

3. RECEPTACLES, LIGHTING AND EQUIPMENT ON THIS

SHEET SHALL BE CONNECTED TO PANELBOARDS

WITHIN THE IT ROOM UNLESS OTHERWISE

INDICATED. SHADING INDICATES CONNECTION TO

EMERGENCY/UPS PANEL.

1/4" = 1'-0"

SECOND LEVEL PLAN -

ENLARGED ELECTRICAL

POWER - OFFICE 233A & 233B

3/16" = 1'-0"

SECOND LEVEL PLAN - ENLARGED

ELECTRICAL POWER - PHYSIATRY

OFFICE 278A

3/16" = 1'-0"

SECOND LEVEL PLAN - ENLARGED

ELECTRICAL POWER - EXAM 242

3/16" = 1'-0"

SECOND LEVEL PLAN - ENLARGED

ELECTRICAL LIGHTING & FIRE

ALARM - PHYSIATRY OFFICE 278A

3/16" = 1'-0"

SECOND LEVEL PLAN - ENLARGED

ELECTRICAL LIGHTING - EXAM 242

Revisions: Date:

EXISTING PANEL

138-L3B1

EXISTING STACKED

ELECTRICAL ROOM WITH

PANELS PANEL RCU-1

PANEL RCU

PANEL 138-L3C1

L3C/1 AND

DISCONNECT

B138-E107

B138-E107

317C

STORAGE

317D

EXAM

319A

BATH

VESTIBULE

MULTI-PURPOSE

MENS

TOILET

CLEAN

LINEN

STORAGE

OFFICE

TELEHEALTH

OFFICE

CHECK-IN

C306

CORRIDOR

317B

OFFICE

317A

OFFICE

EXAM ROOM

CORRIDOR

C305

CORRIDOR

TR

ELECT

SUPPLY

H A C

TOILET

WOMEN

STAIRS

C303

CORRIDOR

STORAGE 304

STAFF

LOUNGE

OFFICE

OFFICE/EXAM

C304

CORRIDOR

OFFICE

308A

OFFICE

OFFICE/EXAM

OFFICE/EXAM

327A

WORK

ROOM

OFFICE

C302

CORRIDOR

OFFICE

OFFICE

MECH302A

SHOWER

BATH

H A C

2B

S T

O R

A G

E

CARDIO

PULMINARY

372A

PULMINARY

LAB

C308

CORRIDOR

ELEC

PS-5

ELEVATOR

PS-6

ELEVATOR

372C

LOUNGE

372E

STORAGE 7

STAIRS

TOILET

ICE

MACHINE

TOILET

C307

WAITING

331A

STORAGE

EKG

ELEVATOR

333B

HOLTER

ROOM 333C

STORAGE

333A E K G

335A

STORAGE

334A

VEST

H.A.C.

CONFERENCE

CLINIC

ORTHO LAB

C311

CORRIDOR

9A

B A

T H

340A

BATH

STORAGE

STORAGE

STORAGE

TOILET

338A

STORAGE

337A

WAITING

ROOM

VESTIBULE

EXAM

336A

VESTIBULE

366B

BATH

337B

BATH

C300

CORRIDOR

C309

CORRIDOR

C310

CORRIDOR

OFFICE

STORAGE

TOILET 8

STAIRS

H A C

STORAGE 352

TOILET

OFFICE

OFFICE

CONSULT

BREAKROOM

CLINIC

CONSULT

CONSULT

359A

OFFICE

CLINIC

CLINIC

MECH

CHASE

OFFICE

346A

OFFICE

OFFICE/STORAGE

2120191817161515s141211109

7s

7m6s65s

4s

321 13

Jw

Im

Iw

He

H

F

E

D

Bw

Am

C

B

A

22 23s 23 24s 24 25 26s 2726 28

25s

I

J

23m

14s

Hm

Cm

G

KLM

N

OPQR STU V

W

Y

13s

FMS

FMS

365C

FMS

367A

TR

367B

OFFICE

OFFICE

138-P3A

138-L3A

KEY PLAN

MAIN

ENTRY

BUILDING 138

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459

04/15/2022 Sheet of

FULLY SPRINKLERED

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.E

R

.r v t

/1

/2

:5

:2

P

M

B138-E106

THIRD LEVEL PLAN - ELECTRICAL EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

ZWC PD

16181

84 127

3/32" = 1'-0"

THIRD LEVEL PLAN - ELECTRICAL POWER

GENERAL NOTES:

1. CONTRACTOR SHALL REFER TO SHEET ES-

E000, ES-E300, AND ES-E500 FOR LEGENDS,

SCHEDULES, NOTES AND OTHER GENERAL

INFORMATION.

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 21001283.00

Revisions: Date:

JE

E

E

{LS1}

A

J

E

J

E

E

{LS1}

A

138-U-TR-31138-N-TR-31

TR

STAIRS

MX-1

INDOOR SPLIT

INDOOR SPLIT

MX-1

1,3,5

1,3,5

7,9,11

7,9,11

13,15,17

13,15,17

TEMP. CONTROL PANEL/8

SECURITY PANEL/6

FAN/4

F1

F1

F1E

NL

F1

TR 1

O

138-U-TR-32

138-N-TR-32

STAIRS

TOILET

367A

TR

367B

OFFICE

OFFICE

MX-1

INDOOR SPLIT

1,3,5

1,3,5

7,9,11

7,9,11

13,15,17

13,15,17

SECURITY PANEL/2

MX-1

INDOOR SPLIT

2 4

TEMP. CONTROL PANEL/8

138-P3A 32

FAN/4

F1/6

F1

F1/6

F1

F1E

NL

F1

STAIRS

TOILET

367A

TR

O

KEY PLAN

MAIN

ENTRY

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459

04/15/2022 Sheet of

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.E

R

.r v t

/1

/2

:5

:0

P

M

B138-E107

THIRD LEVEL PLAN - ENLARGED

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

ZWC PD

16181

85 127

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 21001283.00

1/4" = 1'-0"

THIRD LEVEL PLAN - ELECTRICAL

POWER - TR 314

1/4" = 1'-0"

THIRD LEVEL PLAN - ELECTRICAL

LIGHTING & FIRE ALARM - TR 314

1/4" = 1'-0"

THIRD LEVEL PLAN - ELECTRICAL

POWER - TR 367

1/4" = 1'-0"

THIRD LEVEL PLAN - ELECTRICAL

LIGHTING & FIRE ALARM - TR 367

KEY NOTES:

1. EXTEND EXISTING FIRE ALARM SYSTEM

NOTIFICATION CIRCUIT VIA 3/4"C AND WIRING AS

DIRECTED BY MANUFACTURER'S WIRING DIAGRAMS

AND CONNECT NEW NOTIFICATION APPLIANCE

COMPLETE.

2. INDOOR UNIT IS POWERED FROM OUTDOOR UNIT.

PROVIDE 3/4" CONDUIT AND WIRING BETWEEN

INDOOR UNIT AND OUTDOOR UNIT PER

MANUFACTURER.

3. PROVIDE NEW RECEPTACLE FOR NEW WINDOW-

MOUNTED AIR CONDITIONING UNIT. COORDINATE

EXACT LOCATION IN FIELD. CONNECT COMPLETE TO

CIRCUIT INDICATED VIA 2#12 AND 1#12 GND IN 3/4"C.

GENERAL NOTES:

1. CONTRACTOR SHALL REFER TO SHEET ES-E000, ES-

E300, AND ES-E500 FOR LEGENDS,

SCHEDULES, NOTES AND OTHER GENERAL

INFORMATION.

2. CONTRACTOR IS PERMITTED TO ADJUST LAYOUT AS

NECESSARY TO ACCOMMODATE OTHER SYSTEMS

AND COORDINATE WITH EXISTING DUCT WORK.

GENERAL LOCATION SHALL BE MAINTAINED. DO NOT

MOUNT LUMINAIRES TO THE DUCT WORK. MOUNT

LUMINAIRE SUCH THAT SHADOWS ARE NOT CAST.

3. RECEPTACLES, LIGHTING AND EQUIPMENT ON THIS

SHEET SHALL BE CONNECTED TO PANELBOARDS

WITHIN THE IT ROOM UNLESS OTHERWISE

INDICATED. SHADING INDICATES CONNECTION TO

EMERGENCY/UPS PANEL.

Revisions: Date:

B138-E109

B138-E109

21191817161515s1412111097s7m6s65s1 13

Jw

Im

Iw

He

H

F

E

D

Bw

Am

C

B

A

22 23s 23 24s 24 25 26s 2726 28

25s

I

J

23m14s

Hm

Cm

G

KMNPQR ST

W

US/OPT.

COH.

STORAGE405

SOILED

ULTILITY

PHOTO

CLEAN

SUPPLY

407B

CLERICAL

TLT, STAFF

410A

EYE PROV.

OFC, OPT.

CHIEF

OFC, OPTH.

CHIEF

EQ

ELEC.

TR

EXAM

EXAM

EXAM

EXAM TECH

423B

AUDIO

EXAM 424B

AUDIO

EXAM

CERUMEN

MGMT.

TLT. PAT.

STORAGE

OFC, AUD.

CHIEF

LOUNGE

HEARING

AID FAB.

INST. CAL.

WAITING

OFFICE

OFFICE

STORAGE

STERILE

INSTRUMENTS

400C

CORRIDOR

475C

SUB-WAITING

SOIL

UTILITY

456A

WORK,

STAFF

DENTIST

OFFICE

DENTAL

CHIEF

459A

LAB,

GENERAL

460A

DENTAL

TECH

LOCKER

ROOM

WOMEN

MECHANICAL

EQUIPMENT

H A C

H A C

SUB-WAIT

400EA

Room

DTR,

SPECIAL

DTR

DTR

DTR

RECEPTION475A

WAITING

TR

400I

CORRIDOR

STAIRS

400H

CORRIDOR

RECEPTION

ELEVATOR

ELEVATOR

STAIRS

446B

CT, CONE

BEAM

400B

CORRIDOR

400E

CORRIDOR

STAIRS

400G

CORRIDOR

VISUAL

FIELDS

422B

AUDIO

EXAM

422A

AUDIO

CONTROL

423A

AUDIO

CONTROL 424A

AUDIO

CONTROL

REC.

407A

CLERICAL

LOUNGE

410B

EYE PROV.

410C

EYE PROV.

OFC,

OPTH./OPT.

CHIEF

425B

CHASE

DTR

DTR

DTR

SUB

WAITING

LOCKER

ROOM MEN

LOUNGE

460B

DENTAL

TECH

460C

DENTAL

TECH

459D

LAB, SHIP /

REC

459C

LAB, ACR.

FINISH

459B

LAB, ARC.

PROC

TOILET

STAFF

STORAGE,

DENTAL

SUPPLY 456B

WORK,

STAFF

DENTIST

456C

WORK,

STAFF

DENTIST

400D

CORRIDOR

475B

TOILET

PATIENT

SCRUB

ORAL

SURGERY

ORAL

SURGERY

CLEAN

446A

CT

CONTROL

ELEC

FITTING

PATIENT

EDUCATION

W.C.

ALCOVE

PRETEST

PRETEST

400X

ALCOVE

CRASH

CART

SUPPLY

EQUIPMENT

EXAM, OPT

EXAM, OPT

EXAM, OPTH

EXAM, OPT

STORAGE

EQUIPMENT

PRETEST

DIL. WAIT

RECEPTION

H. A. C.

400F

CORRIDOR

CHECK-IN

KIOSK

EYE WAIT

W.C.

ALCOVE

TOILET

TOILET

SHELL

CONFERENCE

400A

CORRIDOR

WATING

Room

KEY PLAN

MAIN

ENTRY

BUILDING 138

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459

04/15/2022 Sheet of

FULLY SPRINKLERED

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.E

R

.r v t

/1

/2

:5

:3

P

M

B138-E108

FOURTH LEVEL PLAN -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

ZWC PD

16181

86 127

3/32" = 1'-0"

FOURTH LEVEL PLAN - ELECTRICAL POWER

GENERAL NOTES:

1. CONTRACTOR SHALL REFER TO SHEET ES-

E000, ES-E300, AND ES-E500 FOR LEGENDS,

SCHEDULES, NOTES AND OTHER GENERAL

INFORMATION.

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 21001283.00

Revisions: Date:

E

E

{LS1}

A

J J

E E

E

{LS1}

A

138-U-TR-41

138-N-TR-41

TR

EXAM

INDOOR SPLIT

MX-1

1,3,5

1,3,5

13,15,17

13,15,17

7,9,11

7,9,11

INDOOR SPLIT

MX-1

2 2

TEMP. CONTROL PANEL/6

SECURITY PANEL/4

F1E

NL

F1

F1/8

F1

F1

F1/8

TR

EXAM

O

138-N-TR-42

138-U-TR-42

TR

STAIRS

ELEC

INDOOR SPLIT

MX-1

1,3,5

1,3,5

2,4,6

13,15,17

7,9,11

7,9,11

INDOOR SPLIT

MX-1 2

13 2

TEMP. CONTROL PANEL/14

SECURITY PANEL/24

MX-1

CP-5

138-U-TR-42-17

F1/15

F1

F1/15

F1

F1E

NL

F1

TR

STAIRS

ELEC

O

KEY PLAN

MAIN

ENTRY

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459

04/15/2022 Sheet of

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.E

R

.r v t

/1

/2

:5

:1

P

M

B138-E109

FOURTH LEVEL PLAN - ENLARGED

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

ZWC PD

16181

87 127

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 21001283.00

1/4" = 1'-0"

FOURTH LEVEL PLAN -

ELECTRICAL POWER - TR 416

1/4" = 1'-0"

FOURTH LEVEL PLAN -

ELECTRICAL LIGHTING & FIRE

ALARM - TR 416

1/4" = 1'-0"

FOURTH LEVEL PLAN -

ELECTRICAL POWER - TR 476

1/4" = 1'-0"

FOURTH LEVEL PLAN -

ELECTRICAL LIGHTING & FIRE

ALARM - TR 476

KEY NOTES:

1. EXTEND EXISTING FIRE ALARM SYSTEM

NOTIFICATION CIRCUIT VIA 3/4"C AND WIRING AS

DIRECTED BY MANUFACTURER'S WIRING DIAGRAMS

AND CONNECT NEW NOTIFICATION APPLIANCE

COMPLETE.

2. INDOOR UNIT IS POWERED FROM OUTDOOR UNIT.

PROVIDE 3/4" CONDUIT AND WIRING BETWEEN

INDOOR UNIT AND OUTDOOR UNIT PER

MANUFACTURER.

GENERAL NOTES:

1. CONTRACTOR SHALL REFER TO SHEET ES-E000, ES-

E300, AND ES-E500 FOR LEGENDS, SCHEDULES,

NOTES AND OTHER GENERAL INFORMATION.

2. CONTRACTOR IS PERMITTED TO ADJUST LAYOUT AS

NECESSARY TO ACCOMMODATE OTHER SYSTEMS

AND COORDINATE WITH EXISTING DUCT WORK.

GENERAL LOCATION SHALL BE MAINTAINED. DO NOT

MOUNT LUMINAIRES TO THE DUCT WORK. MOUNT

LUMINAIRE SUCH THAT SHADOWS ARE NOT CAST.

3. RECEPTACLES, LIGHTING AND EQUIPMENT ON THIS

SHEET SHALL BE CONNECTED TO PANELBOARDS

WITHIN THE IT ROOM UNLESS OTHERWISE

INDICATED. SHADING INDICATES CONNECTION TO

EMERGENCY/UPS PANEL.

Revisions: Date:

E

E

E

E

E

E

E

EE

EE

E

15s

7s

7m6s65s

4s432

1 13

Jw

Im

Iw

He

H

F

E

D

Bw

Am

C

B

A

22 23s 23

24s

26s

26 28 2925s

I

J

23m

14s

Hm

Cm

G

KLM

N

OPQ

R

STU V

W

Y

13s

OUTDOOR SPLIT

138-U-TR-22-10,12

OUTDOOR SPLIT

138-U-TR-22-14,16

OUTDOOR SPLIT

138-U-TR-42-16,18

OUTDOOR SPLIT

138-U-TR-32-10,12

OUTDOOR SPLIT

138-U-TR-32-14,16

OUTDOOR SPLIT

138-U-TR-42-20,22

OUTDOOR SPLIT

138-U-TR-41-14,16

OUTDOOR SPLIT

138-U-TR-31-14,16

OUTDOOR SPLIT

138-U-TR-21-14,16

OUTDOOR SPLIT

138-U-TR-41-10,12

OUTDOOR SPLIT

138-U-TR-31-10,12

OUTDOOR SPLIT

138-U-TR-21-10,12

FDS-30R

FDS-30R

FDS-30R

FDS-30R

FDS-30R

FDS-30R

138-N-TR-42-4

W

1 FDS-30R

1 FDS-30R

1FDS-30R

1 FDS-30R

1 FDS-30R

1FDS-30R

138-N-TR-41-4

W

KEY PLAN

MAIN

ENTRY

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459

04/15/2022 Sheet of

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.E

R

.r v t

/1

/2

:5

:4

P

M

B138-E110

ROOF PLAN - ELECTRICAL POWER EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

ZWC PD

16181

88 127

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 21001283.00

3/32" = 1'-0"

ROOF PLAN - ELECTRICAL POWER

GENERAL NOTES:

1. CONTRACTOR SHALL REFER TO SHEET ES-E000, ES-

E300, AND ES-E500 FOR LEGENDS, SCHEDULES,

NOTES AND OTHER GENERAL INFORMATION.

2. ROUTE ELECTRIC FEEDERS FOR MECHANICAL

EQUIPMENT ADJACENT TO MECHANICAL PIPING.

PROVIDE ADDITIONAL ROOF SUPPORTS WHERE

NECESSARY.

KEYNOTES:

1. MOUNT DISCONNECTING MEANS ON OUTDOOR-

RATED STRUT SUPPORT SYSTEM ADJACENT TO UNIT.

FIELD COORDINATE MOUNTING LOCATION TO AVOID

RESTRICTING ACCESSIBILITY TO UNIT'S ACCESS

PANELS.

Revisions: Date:

N

L

E

N E

U T

R A

L

A

M P

B U

S

GROUND

480/277V, 3ø, 4W

22,000 SCCR

6 (1) 100A/3P

SPACE

DP-138-E-B1

11,660 ISC

N E

U T

R A

L

A

M P

B U

S

GROUND

208/120V, 3ø, 4W

35,000 SCCR

800A

(6) 100A/3P

SPACES (MIN)

DP-138-U-B1

22,329 ISC

PANEL 138-U-TR-B1

100 A

80A/3P

PANEL 138-U-TR-B2

100 A

4-#3 & 1#8 GND

IN 1.5" C.

PANEL 138-U-TR-11

100 A

PANEL 138-U-TR-12

100 A

PANEL 138-U-TR-21

100 A

PANEL 138-U-TR-22

100 A

N E

U T

R A

L

A

M P

B U

S

GROUND

208/120V, 3ø, 4W

35,000 SCCR

800A

(6) 100A/3P

SPACES (MIN)

DP-138-U-B2

21,916 ISC

PANEL 138-U-TR-31

100 A

80A/3P

PANEL 138-U-TR-32

100 A

PANEL 138-U-TR-41

100 A PANEL 138-U-TR-42

100 A

PANEL 185-U-TR-11

100 A

NEW WORK

ATS-DP-138-E-B1

600 A

(SEE BUILDING 175

FOR LOCATION)

PANEL 185-U-TR-21

100 A

(1) 100A/3P

SPACE

(1) 225A/3P

SPACE

(1) 225A/3P

SPACE

N E

U T R

A L

A

M P

B U

S

GROUND

480/277V, 3ø, 4W

###A/3P

EXISTING EHDS1

(SEE BUILDING 175

FOR LOCATION)

1600A/3P

800A/3P

250A/3P

800A/3P

400A/3P

250A/3P

600A/3P - LSI

E FEED, ATS-1

E FEED, ATS-5

E FEED, ATS-3

E FEED, ATS-9

E FEED, ATS-7

GEN 1

750KW

1200A/3P

N E

U T

R A

L

A

M P

B U

S

GROUND

480/277V, 3ø, 4W

35,000 SCCR

6 (1) 225A/3P

SPACE

SB-175-N-11

NEMA 1

17,289 ISC

1600A/3P

LSIG - AER

(1) 225A/3P

SPACE

(1) 400A/3P

SPACE

(1) 400A/3P

SPACE

600A/3P - LSIG

600A/3P - LSIG

EXISTING 2 SETS OF 4#350KCMIL

N E

U T R

A L

A M

P B

U S

GROUND

480/277V, 3ø, 4W

###A/3P

EXISTING MDP-2

600A/3P

200A/3P

200A/3P

400A/3P

RAD. RM 261

RAD. RM 262

TO 138-ATS-9

TO SWBD MAIN

GEAR 120/208V

3 PH 4W

TO PNL-EMDP-1

700A UPS

OUTPUT

BREAKER

700A UPS

OUTPUT

BREAKER

400A/3P - LSI

400A/3P - LSI

(2) SETS OF 4#350KCMIL & 1#1 GND

EACH IN 3"C (UNDERGROUND - DUCT BANK)

(2) SETS OF 4#350KCMIL & 1#1 GND

EACH IN 3"C

4 SETS OF 4#750KCMIL & 1#4/0 GND

EACH IN 4"C (UNDERGROUND - DUCT BANK)

(2) SETS OF 4#350KCMIL & 1#1 GND

EACH IN 4"C

3#500KCMIL & 1#3 GND

IN 3.5"C

3#500KCMIL & 1#3 GND

IN 3.5"C

(2) SETS OF 4#500KCMIL & 1#1/0 GND

EACH IN 4"C

(2) SETS OF 4#500KCMIL & 1#1/0 GND

EACH IN (2) 4"C

(2) SETS OF 4#350KCMIL & 1#1 GND

EACH IN 3"C (UNDERGROUND - DUCT BANK)

80A/3P

80A/3P

80A/3P

80A/3P

80A/3P

80A/3P

80A/3P

80A/3P

80A/3P

80A/3P

UPS-138-B1

480:208/120V 200kW FRAME,

(3) 50kW MODULES UPS-138-B2

480:208/120V 200kW FRAME,

(3) 50kW MODULES

SWITCH 'J'

12470V

600A, 3 PHASE

PROVIDE (3) NEW 125 A

MEDIUM VOLTAGE FUSES

3-#2 (MV-105 15kV SHIELDED) & 1#6 GND

IN 4"C

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

DPM

DPM

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459

04/15/2022 Sheet of

FULLY SPRINKLERED

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.E

R

.r v t

/1

/2

:5

:5

P

M

B138-E400

ONE LINE DIAGRAMS EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

ZWC PD

16181

89 127

NO SCALE

UPS 138 & 185 ONE-LINE DIAGRAM

1000 KVA

12,470V PRI

277/480V SEC

3PH, 4W

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 21001283.00

ELECTRICAL INSTALLATION SEQUENCE:

1. PROVIDE NEW ELECTRICAL EQUIPMENT AT

LOCATIONS AS INDICATED ON PLANS.

A. EXTERIOR SITE TRANSFORMER ON NEW

PRE-FABRICATED CONCRETE VAULT.

B. EXTERIOR SWITCHBOARD 'DP-138' ON NEW

CONCRETE PAD.

C. INTERIOR AUTOMATIC TRANSFER SWITCH

'ATS-DP-139-UHB1'.

2. PROVIDE NEW DUCT BANKS AS INDICATED ON

SITE PLAN FROM EACH SOURCE TO LOAD.

A. MEDIUM-VOLTAGE PRIMARY FEEDER

UNDER-GROUND FROM SWITCH J TO NEW

SITE TRANSFORMER.

B. NORMAL FEEDER TO 'ATS-DP-138-UHB1'

C. LOAD FEEDER FROM 'ATS-DP-138-UHB1'

D. BACKFEED TO EXISTING 'MDP-2'

3. SHUTDOWN:

A. DURING A SINGLE OFF-HOURS SHUTDOWN,

CONTRACTOR SHALL:

a. DE-ENGERGIZE EXISTING MEDIUM-

VOLTAGE FEED TO SWITCH J.

b. REPLACE EXISTING FUSES IN SWITCH J

AS INDICATED TO FEED NEW SITE

TRANSFORMER.

c. DISCONNECT EXISTING TRANSFORMER

PRIMARY CONDUCTORS.

d. CONNECT NEW TRANSFORMER

PRIMARY AND SECONDARY

CONDUCTORS.

e. VERIFY ROTATION ON NEW

CONNECTIONS.

f. RE-ENERGIZE SWITCH J AND TEST NEW

TRANSFORMER.

4. PROVIDE REMAINING INDOOR ELECTRICAL

EQUIPMENT

A. AUTOMATIC TRANSFER SWITCH

ATS-DP-138-UHB1

B. DISTRIBUTION PANELS DP-138-UHB1,

DP-138-UBL1 AND DP-138-UBL2.

C. UPS EQUIPMENT 138-UPS-1 AND 138-UPS-2

D. TELECOMMUNICATION ROOM ELECTRICAL

PANELS.

KEY NOTES:

1. PROVIDE 2"C FROM NEW AUTOMATIC

TRANSFER SWITCH TO GENERATOR

CONTROLLER FOR CONTROL WIRING. PROVIDE

(2) #12AWG CONDUCTORS PER CONTROL

CIRCUIT (ENGINE START, BLOCK TRANSFER,

REMOTE TEST, AND LOAD SHED) PLUS (4)

ADDITIONAL #12 AWG FOR FUTURE

ACCESSORIES. COORDINATE CONTROLS WITH

GENERATOR AND TRANSFER SWITCH

VENDORS AND INCLUDE WIRING DIAGRAMS

WITH SUBMITTALS TO INDICATE CONDUCTORS

TO SPECIFIC TERMINAL BLOCKS.

2. ADDITIONAL 2P AND 1P LOADS NOT SHOWN ON

ONE-LINE DIAGRAM. REFER TO PANELBOARD

SCHEDULES FOR ADDITIONAL INFORMATION

Revisions: Date:

N E

U T R

A L

GROUND

208/120V, 3ø, 4W

EXISTING DP2

(SQUARE D - I-LINE SWITCHBOARD)

EXISTING

138 LBA

138 L1A

138 L2A

138 L3A

138 L4A

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

138 PSA

138 P2A

138 P3A

138 P4A

EXISTING

EXISTING

UNLABELED

AC UNIT 3RD FLOOR

80A/3P

PANEL 138-N-TR-B1

100 A

PANEL 138-N-TR-B2

100 A

PANEL 138-N-TR-11

100 A

PANEL 138-N-TR-12

100 A

PANEL 138-N-TR-21

100 A

PANEL 138-N-TR-22

100 A

PANEL 138-N-TR-31

100 A

PANEL 138-N-TR-32

100 A

80A/3P

80A/3P

PANEL 138-N-TR-41

100 A

PANEL 138-N-TR-42

100 A

EXISTING (8) 4-500 KCMIL

N E

U T R

A L

GROUND

208/120V, 3ø, 4W

###A/3P

SWBD. MAIN

GEAR

3000A/3P

1200A/3P

800A/3P

600A/3P

CHILLER

EEDP-A

EMDP

SWITCH 'J'

12470V

600A, 3 PHASE

PROVIDE (3) NEW 125 A

MEDIUM VOLTAGE FUSES

TO PNL-EMDP-1

800A/3P

1600A/3P

800A/3P

DP1

DP3

300A/3P

AC

REFER TO B138-E400

80A/3P

80A/3P

80A/3P

80A/3P

80A/3P

80A/3P

80A/3P 4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

4-#3 & 1#8 GND

IN 1.5" C.

NEW WORK

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459

04/15/2022 Sheet of

FULLY SPRINKLERED

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.E

R

.r v t

/1

/2

:5

:0

P

M

B138-E401

ONE LINE DIAGRAMS EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

ZWC PD

16181

90 127

NO SCALE

NORMAL POWER 138 ONE-LINE DIAGRAM

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 21001283.00

Revisions: Date:

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459

04/15/2022 Sheet of

FULLY SPRINKLERED

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.E

R

.r v t

/1

/2

:5

:0

P

M

B138-E500

ELECTRICAL SCHEDULES EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

ZWC PD

16181

91 127

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 16.1 A

TOTAL CONNECTED AMPS: 22.32 A

TOTAL ESTIMATED DEMAND LOAD: 5.79 kVA

ITE 7.5 kVA 70.00% 5.25 kVA TOTAL CONNECTED LOAD: 8.04 kVA

Receptacles 0.54 kVA 100.00% 0.54 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 25.33 20.83 20.83

Total Load: 3.04 kVA 2.50 kVA 2.50 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 -- -- -- -- -- -- 0.83 0 -- -- -- 1 20 A SPARE 18 --

-- 15 -- -- -- -- -- -- 0.83 0 -- -- -- 1 20 A SPARE 16 --

13 RCPT L21-20R RACK 20 A 3 12 12 12 0.83 0 -- -- -- 1 20 A SPARE 14 --

-- 11 -- -- -- -- -- -- 0.83 0 -- -- -- 1 20 A SPARE 12 --

-- 9 -- -- -- -- -- -- 0.83 0 -- -- -- 1 20 A SPARE 10 --

7 RCPT L21-20R RACK 20 A 3 12 12 12 0.83 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 0.83 0 -- -- -- 1 20 A SPARE 6 --

-- 3 -- -- -- -- -- -- 0.83 0 -- -- -- 1 20 A SPARE 4 --

1 RCPT L21-20R RACK 20 A 3 12 12 12 0.83 0.54 12 12 12 1 20 A RCPT - 005B 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

ISC: 3.21 kA

SCCR: 22,000

LOCATION: TR 005B WIRE: 4

FED FROM: EXISTING PANEL DP2 PHASE: 3

ENCLOSURE: BOLT-ON SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MLO

PANEL 138-N-TR-B1

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

ITE 7.5 kVA 70.00% 5.25 kVA

Redundant 3.16 kVA 0.01% 0 kVA TOTAL ESTIMATED DEMAND AMPS: 26.4 A

Receptacles 0.54 kVA 100.00% 0.54 kVA TOTAL CONNECTED AMPS: 40.99 A

Power 0.7 kVA 100.00% 0.7 kVA TOTAL ESTIMATED DEMAND LOAD: 9.497 kVA

Lighting 0.089 kVA 100.00% 0.089 kVA TOTAL CONNECTED LOAD: 14.77 kVA

HVAC Cooling Only 3.16 kVA 100.00% 3.16 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 39.03 46.92 37.53

Total Load: 4.66 kVA 5.61 kVA 4.50 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 -- -- -- -- -- -- 0.83 0 -- -- -- 1 20 A SPARE 18 --

-- 15 -- -- -- -- -- -- 0.83 0.09 12 12 12 1 20 A LTG - 005B 16

13 RCPT L21-20R RACK 20 A 3 12 12 12 0.83 0.2 12 12 12 1 20 A TEMP. CONTROL PANEL 14

-- 11 -- -- -- -- -- -- 0.83 0.54 12 12 12 1 20 A RCPT - 005B 12

-- 9 -- -- -- -- -- -- 0.83 1.58 -- -- -- -- -- -- 10 --

7 RCPT L21-20R RACK 20 A 3 12 12 12 0.83 1.58 10 10 10 2 25 A OUTDOOR SPLIT SYSTEM 8

-- 5 -- -- -- -- -- -- 0.83 1.58 -- -- -- -- -- -- 6 --

-- 3 -- -- -- -- -- -- 0.83 1.58 10 10 10 2 25 A OUTDOOR SPLIT SYSTEM 4

1 RCPT L21-20R RACK 20 A 3 12 12 12 0.83 0.5 12 12 12 1 20 A SECURITY PANEL 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

ISC: 4.96 kA

SCCR: 10,000

LOCATION: TR 005B WIRE: 4

FED FROM: DP-138-U-B1 PHASE: 3

ENCLOSURE: BOLT-ON SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MLO

PANEL 138-U-TR-B1

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 16.1 A

TOTAL CONNECTED AMPS: 22.32 A

TOTAL ESTIMATED DEMAND LOAD: 5.79 kVA

ITE 7.5 kVA 70.00% 5.25 kVA TOTAL CONNECTED LOAD: 8.04 kVA

Receptacles 0.54 kVA 100.00% 0.54 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 25.33 20.83 20.83

Total Load: 3.04 kVA 2.50 kVA 2.50 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 -- -- -- -- -- -- 0.83 0 -- -- -- 1 20 A SPARE 18 --

-- 15 -- -- -- -- -- -- 0.83 0 -- -- -- 1 20 A SPARE 16 --

13 RCPT L21-20R RACK 20 A 3 12 12 12 0.83 0 -- -- -- 1 20 A SPARE 14 --

-- 11 -- -- -- -- -- -- 0.83 0 -- -- -- 1 20 A SPARE 12 --

-- 9 -- -- -- -- -- -- 0.83 0 -- -- -- 1 20 A SPARE 10 --

7 RCPT L21-20R RACK 20 A 3 12 12 12 0.83 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 0.83 0 -- -- -- 1 20 A SPARE 6 --

-- 3 -- -- -- -- -- -- 0.83 0 -- -- -- 1 20 A SPARE 4 --

1 RCPT L21-20R RACK 20 A 3 12 12 12 0.83 0.54 12 12 12 1 20 A RCPT - 025D 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

ISC: 14.14 kA

SCCR: 22,000

LOCATION: TR 025D WIRE: 4

FED FROM: EXISTING PANEL DP2 PHASE: 3

ENCLOSURE: BOLT-ON SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MLO

PANEL 138-N-TR-B2

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

ITE 7.5 kVA 70.00% 5.25 kVA

Redundant 3.16 kVA 0.01% 0 kVA TOTAL ESTIMATED DEMAND AMPS: 27.7 A

Receptacles 0.54 kVA 100.00% 0.54 kVA TOTAL CONNECTED AMPS: 42.37 A

Power 1.21 kVA 100.00% 1.21 kVA TOTAL ESTIMATED DEMAND LOAD: 9.992 kVA

Lighting 0.089 kVA 100.00% 0.089 kVA TOTAL CONNECTED LOAD: 15.26 kVA

HVAC Cooling Only 3.16 kVA 100.00% 3.16 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 38.83 47.16 42.11

Total Load: 4.66 kVA 5.61 kVA 5.00 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 -- -- -- -- -- -- 0.83 0.51 12 12 12 1 20 A CP-1 CONDENSATE PUMP 18

-- 15 -- -- -- -- -- -- 0.83 0.09 12 12 12 1 20 A LTG - 025D 16

13 RCPT L21-20R RACK 20 A 3 12 12 12 0.83 0.2 12 12 12 1 20 A TEMP. CONTROL PANEL 14

-- 11 -- -- -- -- -- -- 0.83 0.54 12 12 12 1 20 A RCPT - 025D 12

-- 9 -- -- -- -- -- -- 0.83 1.58 -- -- -- -- -- -- 10 --

7 RCPT L21-20R RACK 20 A 3 12 12 12 0.83 1.58 10 10 10 2 25 A OUTDOOR SPLIT SYSTEM 8

-- 5 -- -- -- -- -- -- 0.83 1.58 -- -- -- -- -- -- 6 --

-- 3 -- -- -- -- -- -- 0.83 1.58 10 10 10 2 25 A OUTDOOR SPLIT SYSTEM 4

1 RCPT L21-20R RACK 20 A 3 12 12 12 0.83 0.5 12 12 12 1 20 A SECURITY PANEL 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

ISC: 4.62 kA

SCCR: 10,000

LOCATION: TR 025D WIRE: 4

FED FROM: DP-138-U-B2 PHASE: 3

ENCLOSURE: BOLT-ON SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MLO

PANEL 138-U-TR-B2

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 21001283.00

CIRCUIT NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

ITE 42.127 kVA 70.00% 29.489 kVA

Redundant 19.752 kVA 0.01% 0.002 kVA TOTAL ESTIMATED DEMAND AMPS: 167.6 A

Receptacles 4.14 kVA 100.00% 4.14 kVA TOTAL CONNECTED AMPS: 256.01 A

Power 4.2 kVA 100.00% 4.2 kVA TOTAL ESTIMATED DEMAND LOAD: 60.393 kVA

Lighting 0.707 kVA 100.00% 0.707 kVA TOTAL CONNECTED LOAD: 92.23 kVA

HVAC Cooling Only 22.912 kVA 100.00% 22.912 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY (INCLUDES ALL TUBS IN THIS PANEL)

16 LIGHTING 0.13 kVA 1 20 A 20 A 2#12AWG AND 1#12AWG GND IN 3/4"C

15 RCPT - 010 0.36 kVA 1 20 A 20 A 2#12AWG AND 1#12AWG GND IN 3/4"C

14 SPARE 0 kVA 2 25 A 25 A -- -- --

13 SSOU-138-010B 3.16 kVA 2 25 A 25 A 3#10AWG AND 1#10AWG GND IN 3/4"C

12 PROVISION -- 3 -- -- -- -- -- --

11 PROVISION -- 3 -- -- -- -- -- --

10 PROVISION -- 3 -- -- -- -- -- --

9 PROVISION -- 3 -- -- -- -- -- --

8 PROVISION -- 3 -- -- -- -- -- --

7 PROVISION -- 3 -- -- -- -- -- --

6 185-U-TR-11 16.91 kVA 3 100 A 80 A LSI SEE ONE-LINE

5 138-U-TR-41 14.99 kVA 3 100 A 80 A LSI SEE ONE-LINE

4 138-U-TR-31 14.77 kVA 3 100 A 80 A LSI SEE ONE-LINE

3 138-U-TR-21 14.77 kVA 3 100 A 80 A LSI SEE ONE-LINE

2 138-U-TR-11 12.76 kVA 3 100 A 80 A LSI SEE ONE-LINE

1 138-U-TR-B1 14.77 kVA 3 100 A 80 A LSI SEE ONE-LINE

CKT LOAD DESCRIPTION Load POLES FRAME TRIP TYPE ACC. WIRE AND RACEWAY

CIRCUIT

NOTES

NOTES:

ISC: 22,329 A

SCCR: 35,000

LOCATION: UPS 010 WIRE: 4

FED FROM: UPS-138-B1 PHASE: 3

ENCLOSURE: BOLT-ON SOLID NEUTRAL VOLTS: 120/208 Wye

MAIN: 800 A MLO

DP-138-U-B1

CIRCUIT NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

ITE 42.127 kVA 70.00% 29.489 kVA

Redundant 19.752 kVA 0.01% 0.002 kVA TOTAL ESTIMATED DEMAND AMPS: 172.5 A

Receptacles 4.5 kVA 100.00% 4.5 kVA TOTAL CONNECTED AMPS: 260.91 A

Power 5.72 kVA 100.00% 5.72 kVA TOTAL ESTIMATED DEMAND LOAD: 62.154 kVA

Lighting 0.619 kVA 100.00% 0.619 kVA TOTAL CONNECTED LOAD: 94.00 kVA

HVAC Cooling Only 22.912 kVA 100.00% 22.912 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY (INCLUDES ALL TUBS IN THIS PANEL)

16 SPARE 0 kVA 1 20 A 20 A -- -- --

15 RECEPTACLES - UPS ROOM 0.36 kVA 1 20 A 20 A 2#12AWG AND 1#12AWG GND IN 3/4"C

14 SPARE 0 kVA 2 25 A 25 A -- -- --

13 SSOU-138-010A 3.16 kVA 2 25 A 25 A 3#10AWG AND 1#10AWG GND IN 3/4"C

12 PROVISION -- 3 -- -- -- -- -- --

11 PROVISION -- 3 -- -- -- -- -- --

10 PROVISION -- 3 -- -- -- -- -- --

9 PROVISION -- 3 -- -- -- -- -- --

8 PROVISION -- 3 -- -- -- -- -- --

7 PROVISION -- 3 -- -- -- -- -- --

6 185-U-TR-21 16.91 kVA 3 100 A 80 A LSI SEE ONE-LINE

5 138-U-TR-42 15.02 kVA 3 100 A 80 A LSI SEE ONE-LINE

4 138-U-TR-32 15.28 kVA 3 100 A 80 A LSI SEE ONE-LINE

3 138-U-TR-22 14.94 kVA 3 100 A 80 A LSI SEE ONE-LINE

2 138-U-TR-12 13.43 kVA 3 100 A 80 A LSI SEE ONE-LINE

1 138-U-TR-B2 15.26 kVA 3 100 A 80 A LSI SEE ONE-LINE

CKT LOAD DESCRIPTION Load POLES FRAME TRIP TYPE ACC. WIRE AND RACEWAY

CIRCUIT

NOTES

NOTES:

ISC: 21,916 A

SCCR: 35,000

LOCATION: UPS 010 WIRE: 4

FED FROM: UPS-138-B2 PHASE: 3

ENCLOSURE: BOLT-ON SOLID NEUTRAL VOLTS: 120/208 Wye

MAIN: 800 A MLO

DP-138-U-B2

Revisions: Date:

Phone: 402.991.5520 www.specializedeng.com

SES PROJECT #

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% FINAL STAMPED

BID DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

20459

04/15/2022 Sheet of

FULLY SPRINKLERED

B

IM

/2

V

A M a ri o n E

H R

M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6

-7

.B

.E

R

.r v t

/1

/2

:5

:4

P

M

B138-E501

ELECTRICAL SCHEDULES EHRM INFRASTRUCTURE

UPGRADES, MARION, IN

MARION, IN

610-21-701

B138

ZWC PD

16181

92 127

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 12 A

TOTAL CONNECTED AMPS: 16.35 A

ITE 5.25 kVA 70.00% 3.675 kVA TOTAL ESTIMATED DEMAND LOAD: 4.315 kVA

Receptacles 0.54 kVA 100.00% 0.54 kVA TOTAL CONNECTED LOAD: 5.89 kVA

HVAC 0.1 kVA 100.00% 0.1 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 19.21 15.54 14.58

Total Load: 2.29 kVA 1.85 kVA 1.75 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 -- -- -- -- -- -- 0.58 0 -- -- -- 1 20 A SPARE 18 --

-- 15 -- -- -- -- -- -- 0.58 0 -- -- -- 1 20 A SPARE 16 --

13 RCPT L21-20R RACK 20 A 3 12 12 12 0.58 0 -- -- -- 1 20 A SPARE 14 --

-- 11 -- -- -- -- -- -- 0.58 0 -- -- -- 1 20 A SPARE 12 --

-- 9 -- -- -- -- -- -- 0.58 0 -- -- -- 1 20 A SPARE 10 --

7 RCPT L21-20R RACK 20 A 3 12 12 12 0.58 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 0.58 0 -- -- -- 1 20 A SPARE 6 --

-- 3 -- -- -- -- -- -- 0.58 0.1 12 12 12 1 20 A VAV 4

1 RCPT L21-20R RACK 20 A 3 12 12 12 0.58 0.54 12 12 12 1 20 A RCPT - 104C 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

ISC: 3.01 kA

SCCR: 22,000

LOCATION: TR 104C WIRE: 4

FED FROM: EXISTING PANEL DP2 PHASE: 3

ENCLOSURE: BOLT-ON SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MLO

PANEL 138-N-TR-11

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

ITE 5.25 kVA 70.00% 3.675 kVA

Redundant 3.16 kVA 0.01% 0 kVA TOTAL ESTIMATED DEMAND AMPS: 22.6 A

Receptacles 0.72 kVA 100.00% 0.72 kVA TOTAL CONNECTED AMPS: 35.42 A

Power 0.7 kVA 100.00% 0.7 kVA TOTAL ESTIMATED DEMAND LOAD: 8.137 kVA

Lighting 0.089 kVA 100.00% 0.089 kVA TOTAL CONNECTED LOAD: 12.76 kVA

HVAC Cooling Only 3.16 kVA 100.00% 3.16 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 41.53 36.36 30.14

Total Load: 4.88 kVA 4.26 kVA 3.62 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 -- -- -- -- -- -- 0.58 0.18 12 12 12 1 20 A RCPT - OUTDOOR SERVICE 18

-- 15 -- -- -- -- -- -- 0.58 0.5 12 12 12 1 20 A SECURITY PANEL 16

13 RCPT L21-20R RACK 20 A 3 12 12 12 0.58 0.09 12 12 12 1 20 A LTG - 104C 14

-- 11 -- -- -- -- -- -- 0.58 0.2 12 12 12 1 20 A TEMP. CONTROL PANEL 12

-- 9 -- -- -- -- -- -- 0.58 0.54 12 12 12 1 20 A RCPT - 104C 10

7 RCPT L21-20R RACK 20 A 3 12 12 12 0.58 1.58 -- -- -- -- -- -- 8 --

-- 5 -- -- -- -- -- -- 0.58 1.58 10 10 10 2 25 A OUTDOOR SPLIT SYSTEM 6

-- 3 -- -- -- -- -- -- 0.58 1.58 -- -- -- -- -- -- 4 --

1 RCPT L21-20R RACK 20 A 3 12 12 12 0.58 1.58 10 10 10 2 25 A OUTDOOR SPLIT SYSTEM 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

ISC: 4.96 kA

SCCR: 10,000

LOCATION: TR 104C WIRE: 4

FED FROM: DP-138-U-B1 PHASE: 3

ENCLOSURE: BOLT-ON SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MLO

PANEL 138-U-TR-11

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 12.2 A

TOTAL CONNECTED AMPS: 16.57 A

TOTAL ESTIMATED DEMAND LOAD: 4.395 kVA

ITE 5.25 kVA 70.00% 3.675 kVA TOTAL CONNECTED LOAD: 5.97 kVA

Receptacles 0.72 kVA 100.00% 0.72 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 20.58 14.58 14.58

Total Load: 2.47 kVA 1.75 kVA 1.75 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 -- -- -- -- -- -- 0.58 0 -- -- -- 1 20 A SPARE 18 --

-- 15 -- -- -- -- -- -- 0.58 0 -- -- -- 1 20 A SPARE 16 --

13 RCPT L21-20R RACK 20 A 3 12 12 12 0.58 0 -- -- -- 1 20 A SPARE 14 --

-- 11 -- -- -- -- -- -- 0.58 0 -- -- -- 1 20 A SPARE 12 --

-- 9 -- -- -- -- -- -- 0.58 0 -- -- -- 1 20 A SPARE 10 --

7 RCPT L21-20R RACK 20 A 3 12 12 12 0.58 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 0.58 0 -- -- -- 1 20 A SPARE 6 --

-- 3 -- -- -- -- -- -- 0.58 0 -- -- -- 1 20 A SPARE 4 --

1 RCPT L21-20R RACK 20 A 3 12 12 12 0.58 0.72 12 12 12 1 20 A RCPT - 163 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

ISC: 10.10 kA

SCCR: 22,000

LOCATION: TR 163 WIRE: 4

FED FROM: EXISTING PANEL DP2 PHASE: 3

ENCLOSURE: BOLT-ON SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MLO

PANEL 138-N-TR-12

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

ITE 5.25 kVA 70.00% 3.675 kVA

Redundant 3.16 kVA 0.01% 0 kVA TOTAL ESTIMATED DEMAND AMPS: 24.4 A

Receptacles 0.9 kVA 100.00% 0.9 kVA TOTAL CONNECTED AMPS: 37.28 A

Power 1.2 kVA 100.00% 1.2 kVA TOTAL ESTIMATED DEMAND LOAD: 8.804 kVA

Lighting 0.089 kVA 100.00% 0.089 kVA TOTAL CONNECTED LOAD: 13.43 kVA

HVAC Cooling Only 3.16 kVA 100.00% 3.16 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 40.87 41.93 31.60

Total Load: 4.76 kVA 4.88 kVA 3.79 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 -- -- -- -- -- -- 0.58 0.36 12 12 12 1 20 A RCPT - OUTDOOR SERVICE 18

-- 15 -- -- -- -- -- -- 0.58 0.09 12 12 12 1 20 A LTG - 163 16

13 RCPT L21-20R RACK 20 A 3 12 12 12 0.58 0.54 12 12 12 1 20 A RCPT - 163 14

-- 11 -- -- -- -- -- -- 0.58 0.2 12 12 12 1 20 A TEMP. CONTROL PANEL 12

-- 9 -- -- -- -- -- -- 0.58 1.58 -- -- -- -- -- -- 10 --

7 RCPT L21-20R RACK 20 A 3 12 12 12 0.58 1.58 10 10 10 2 25 A OUTDOOR SPLIT SYSTEM 8

-- 5 -- -- -- -- -- -- 0.58 1.58 -- -- -- -- -- -- 6 --

-- 3 -- -- -- -- -- -- 0.58 1.58 10 10 10 2 25 A OUTDOOR SPLIT SYSTEM 4

1 RCPT L21-20R RACK 20 A 3 12 12 12 0.58 1 12 12 12 1 20 A SECURITY PANEL 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

ISC: 4.09 kA

SCCR: 10,000

LOCATION: TR 025D WIRE: 4

FED FROM: DP-138-U-B2 PHASE: 3

ENCLOSURE: BOLT-ON SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MLO

PANEL 138-U-TR-12

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 21001283.00

CIRCUIT KEY NOTES: *E= NEW LOAD ON EXISTING BREAKER, *N= NEW BREAKER

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 3.3 A

TOTAL CONNECTED AMPS: 3.28 A

TOTAL ESTIMATED DEMAND LOAD: 1.18 kVA

TOTAL CONNECTED LOAD: 1.18 kVA

Receptacles 1.18 kVA 100.00% 1.18 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 1.73 0.00 8.56

Total Load: 0.18 kVA 0.00 kVA 1.00 kVA

-- 41 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 42 --

-- 39 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- -- -- -- 40 --

-- 37 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 2 20 A EXISTING LOAD 38 --

-- 35 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- -- -- -- 36 --

-- 33 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 2 20 A EXISTING LOAD 34 --

-- 31 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 30 A EXISTING LOAD 32 --

*E 29 PYXIS EXAM RM 242 20 A 1 12 12 12 1 0 -- -- -- -- -- -- 30 --

-- 27 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- -- -- -- 28 --

-- 25 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 3 20 A EXISTING LOAD 26 --

-- 23 -- -- -- -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 24 --

-- 21 -- -- -- -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 22 --

-- 19 SPARE 30 A 3 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 20 --

-- 17 -- -- -- -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 18 --

-- 15 -- -- -- -- -- -- 0 0 -- -- -- 1 20 A SPARE, *N 16 --

-- 13 EXISTING LOAD 30 A 3 -- -- -- 0 0.18 12 12 12 1 20 A RCPTS EXAM RM 242 14 *N

-- 11 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 12 --

-- 9 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 10 --

-- 7 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- -- -- -- 8 --

-- 5 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 2 30 A SPARE 6 --

-- 3 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 4 --

-- 1 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 2 --

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

ISC UNKNOWN

SCCR: 22,000

LOCATION: ELEC 147A WIRE: 4

FED FROM: PHASE: 3

ENCLOSURE: BOLT-ON SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A

138-E2C

CIRCUIT KEY NOTES: *N= REPLACE EXISTING 20A/2P BREAKER WITH NEW 20A/1P BREAKER.

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 4.5 A

TOTAL CONNECTED AMPS: 4.50 A

TOTAL ESTIMATED DEMAND LOAD: 1.62 kVA

Receptacles 1.62 kVA 100.00% 1.62 kVA TOTAL CONNECTED LOAD: 1.62 kVA

Lighting 0 kVA 0.00% 0 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 0.00 13.50 0.00

Total Load: 0.00 kVA 1.62 kVA 0.00 kVA

-- 41 EXISTING LOAD 20 A 1 -- -- -- 0 0 12 12 12 1 20 A LIGHTING RM 233, 233A,223B 42 *N

-- 39 EXISTING LOAD 20 A 1 -- -- -- 0 1.62 12 12 12 1 20 A RCPTS RM 233, 233A,223B 40 *N

-- 37 EXISTING LOAD 30 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 38 --

-- 35 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 36 --

-- 33 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 34 --

-- 31 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 32 --

-- 29 -- -- -- -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 30 --

-- 27 -- -- -- -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 28 --

-- 25 EXISTING LOAD 60 A 3 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 26 --

-- 23 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 24 --

-- 21 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 22 --

-- 19 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 20 --

-- 17 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 18 --

-- 15 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 16 --

-- 13 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 14 --

-- 11 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 12 --

-- 9 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 10 --

-- 7 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 8 --

-- 5 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A EXISTING LOAD 6 --

-- 3 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- -- -- -- 4 --

-- 1 EXISTING LOAD 20 A 1 -- -- -- 0 0 -- -- -- 2 20 A EXISTING LOAD 2 --

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

ISC UNKNOWN

SCCR: 10,000

LOCATION: TR 104C WIRE: 4

FED FROM: PHASE: 3

ENCLOSURE: BOLT-ON SOLID NEUTRAL VOLTS:…