Atch 16 - MECH 2 of 7 - DRAWINGS.pdf
PDF 16 MB Posted
- Attached to
- Y1AZ--EHRM Infrastructure Upgrades Construction - Marion Federal contract opportunity
- Solicitation number
- 36C77622B0040
About this file
This federal contract opportunity solicitation involves infrastructure upgrades and renovations to buildings on a Department of Veterans Affairs campus. The project scope includes electrical, bonding, UPS, building management system interfaces, HVAC, communication, physical security upgrades, and fiber infrastructure backbone campus wide within and between buildings. The work also includes modification to impacted roads, walks, grading and drainage, and other existing utilities. Data Center WAN updates and hazardous material abatement are required. Offerors must respond by the date listed in solicitation number 36C77622B0040 to be considered for this contract with the Technology Acquisition Center Austin.
View the file
Other files for this federal contract opportunity
Show all 42
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 3 4 5 6 7 8 9 10 11 12
C
D
KEY PLAN
MAIN
ENTRY
BUILDING 16
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459
NON-SPRINKLERED
Sheet of
04/04/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:2
:5
P
M
B16-M101
FIRST LEVEL FLOOR PLAN -
MECHANICAL - DEMO
EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B16
04/15/2022 JMM GTS
Project Number
31 176
1/8" = 1'-0" F2
FIRST LEVEL FLOOR PLAN - MECHANICAL - DEMO
0 8' 16'4'
SHEET NOTES:
1. DISCONNECT EXISTING UNIT HEATER AND PIPING ACCESSORIES AND MOVE TO NEW LOCATION INDICATED
ON NEW WORK PLAN.
2. PLUG EXISTING FLOOR DRAIN. REFER TO ARCHITECTURAL PLANS FOR MORE INFORMATION.
PHOTO 01
INDICATES POINT OF VIEW OF REFERENCE PHOTO ON SHEET WITH CORRESPONDING NUMBER.##
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED
AND/OR DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL
OTHER PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS
OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES
REQUIRED TO PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE
DDC.
GENERAL NOTES:
Revisions: Date:
T
C
D
OFFICE
Room
TOILET
WORKROOM
ANTE
OFFICE
COPY
104A
DATA
WOMENS TOILET
TOILET
STAIR
S101
DATA
100B
H.A.C.
ELEC
Room
100A
Room
CORRIDOR
C103
CORRIDOR
C102
STORAGE
ELEVATOR LOBBY
ELEV
Room
ELEV
CORRIDOR
C100
OFFICE
OFFICE
CORRIDOR
C101
OFFICE
OFFICE
TRAINING ROOM
MENS TOILET
OFFICE
Room
OFFICE
STORAGE
CORRIDOR
BIO-HAZARD
OXYGEN
STORAGE
CORRIDOR
C104
STORAGE
117A
BATH
115A
BATH
114A
OFFICE
ELEVATOR LOBBY
12x8 12x8
EF-1
FSFS
DDC
3" F
KEY PLAN
MAIN
ENTRY
BUILDING 16
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459
NON-SPRINKLERED
Sheet of
04/04/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:2
:5
P
M
B16-M201
FIRST LEVEL FLOOR PLAN -
MECHANICAL
EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B16
04/15/2022 JMM GTS
Project Number
32 176
1/8" = 1'-0" F2
FIRST LEVEL FLOOR PLAN - MECHANICAL
0 8' 16'4'
SHEET NOTES:
1. RELOCATE EXISTING CABINET UNIT HEATER AND EXTEND EXISTING PIPING TO NEW LOCATION.
2. THERMOSTAT USED FOR MONITORING. REPORT TO BUILDING ECC.
3. BOTTOM OF DUCT AT 6'-6" ABOVE FINISHED FLOOR.
4. DISCHARGE EXHAUST AIR UP THROUGH ROOF. TERMINATE 18 INCHES ABOVE ROOF WITH GOOSENECK
DISCHARGE.
5. CONNECT NEW FIRE PROTECTION PIPING TO EXISTING WET PIPE SPRINKLER RISER. PROVIDE NEW TEST
CONNECTION AT TIE-IN LOCATION TO EXISTING RISER.
6. EXTEND NEW FIRE PROTECTION PIPING TO SERVE SERVER ROOM AND ADACENT ENTRANCE AND UPS
ROOMS. SEE SHEET B15-F201 FOR CONTINUATION.
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED
AND/OR DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL
OTHER PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS
OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES
REQUIRED TO PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE
DDC.
REMARKS:
1. COORDINATE EXACT MODEL AND FRAME WITH CEILING / WALL TYPE.
2. PROVIDE REMOTE DAMPER ACTUATION IN HARD CEILINGS.
3. PROVIDE BLACKOUT PANELS ON TRANSFER GRILLES.
4. COORDINATE LOCATION OF GRILLES WITH ARCHITECTURAL CEILING PLANS AND ELEVATIONS.
5. DIFFUSER / GRILLE CONSTRUCTION SHALL BE ALUMINUM CONSTRUCTION IN ALL RESTROOMS, TOILETS, RECEIVING AREAS, AND VESTIBULES.
6. DIFFUSER / GRILLE CONSTRUCTION SHALL BE 100% ALUMINUM AND RATED FOR USE IN MRI APPLICATIONS
BY THE MANUFACTURER.
7. WHEN INSTALLED IN A WALL, THE BLADES FOR THESE GRILLES SHALL BE SUCH THAT THE FRONT BLADES
ARE HORIZONTAL (PARALLEL TO THE FLOOR). WHEN INSTALLED IN A CEILING, THE BLADES FOR THESE GRILLES SHALL BE SUCH THAT THE FRONT BLADES ARE PARALLEL TO THE LONG DIMENSION OF THE
GRILLE.
REMARKS:
1. PROVIDE DISCONNECT.
2. PROVIDE VIBRATION ISOLATION.
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459
NON-SPRINKLERED
Sheet of
04/04/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:2
:5
P
M
B16-M600
MECHANICAL SCHEDULES EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B16
04/15/2022 JMM GTS
Project Number
33 176
DIFFUSER, REGISTER, AND GRILLE SCHEDULE add remarks
MARK IMAGE DESCRIPTION MAX S.P. MATERIAL FINISH
FACE SIZE
NECK SIZE AIRFLOW MANUFACTURER MODEL REMARKSLENGTH WIDTH
D7 DOUBLE DEFLECTION
SUPPLY GRILLE
0.10 in-wg STEEL PAINT, WHITE SEE PLAN SEE PLAN SEE PLAN SEE PLAN TITUS
KRUEGER
PRICE
300RL/SL
G7 SINGLE DEFLECTION
RETURN GRILLE
0.10 in-wg STEEL PAINT, WHITE SEE PLAN SEE PLAN SEE PLAN SEE PLAN TITUS
KRUEGER
PRICE
350RL/SL
S80
FAN SCHEDULE
MARK TYPE
MAX WEIGHT
[LBS]
AIRFLOW
[CFM]
TOTAL S.P.
[IN W.C.] MAX FAN RPM MAX FAN BHP
ELECTRICAL DATA
MANUFACTURER MODEL REMARKSFLA VOLTAGE PHASE
F-1 CABINET 40 400 0.5 1,260 0.14 2.45 115 V 1 GREENHECK CSP-A510-VG (1)(2)
2 1
KEY PLAN
MAIN
ENTRY
BUILDING 17
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459
NON-SPRINKLERED
Sheet of
04/15/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:3
:0
P
M
B17-M101
FIRST LEVEL FLOOR PLAN -
MECHANICAL - DEMO
EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B17
04/15/2022 JMM GTS
Project Number
34 176
1/8" = 1'-0" F2
FIRST LEVEL FLOOR PLAN - MECHANICAL - DEMO
0 8' 16'4'
SHEET NOTES:
1. DEMOLISH PERIMETER HEATERS AND ASSOCIATED STEAM CONNECTIONS BACK TO MAIN IN CRAWL SPACE
BELOW. FINISH WITH NEW INSULATION.
2. DEMOLISH PERIMETER HEATER PIPING IN CEILINGS SERVING LEVEL 2 CABINET UNIT HEATER ABOVE. REFER
TO B17-M102 PLAN FOR MORE INFORMATION.
GENERAL NOTES:
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE
ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
PHOTO 01
INDICATES POINT OF VIEW OF REFERENCE PHOTO ON SHEET WITH CORRESPONDING NUMBER.##
1 1
KEY PLAN
MAIN
ENTRY
BUILDING 17
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459
NON-SPRINKLERED
Sheet of
04/15/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:3
:0
P
M
B17-M102
SECOND LEVEL FLOOR PLAN -
MECHANICAL - DEMO
EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B17
04/15/2022 JMM GTS
Project Number
35 176
1/8" = 1'-0"F2
SECOND LEVEL FLOOR PLAN - MECHANICAL - DEMO
0 8' 16'4'
SHEET NOTES:
1. DEMOLISH PERIMETER HEATERS AND ASSOCIATED STEAM CONNECTIONS BACK TO MAIN IN CRAWL SPACE
BELOW. REFER TO B17-M101 PLAN FOR MORE INFORMATION.
GENERAL NOTES:
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE
ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
T H
STORAGE
118A
STORAGE
117A
CLASSROOM
CORRIDOR
EDUCATIONAL
DEPARTMENT
CORRIDOR
STORAGE
119A
STORAGE
121A
STORAGE
119B
V.E.R.C.
CORRIDOR
CORRIDOR
EDUC. DEPT.
OFFICE
RELATIONSHIP
BASED CARE
EDUC. DEPT.
OFFICE
CONFERENCE
ROOM
WORKROOM
STAFF LOUNGE
MECH CHASE
103B
STAIRWELL
S100
H.A.C.
Room
103A
INSTRUCTOR
STAIRWELL
S101
STORAGE
SIMULATION
ROOM
CLINIC
INSTRUCTOR
CLINIC
INSTRUCTOR
LIBRARY
MANAGER
EDUCATION
COORDINATOR
V.E.R.C.
DAYROOM
SECRETARY
EDUC. DEPT,
OFFICE
OFFICE
COORDINATOR
TR
VETERANS
EDUCATION
RESOURCES
CENTER
WOMENS TOILET
COORDINATOR
OFFICE
1 2 3 4 5 6 7 8 9 10 11 12
B17-M400
F6
SSOU-17-223B
SSOU-17-126A
SSOU-17-126B
SSOU-17223A
M500
B7
G3
1/2" DCW
1/2" NPW
C6/F6
KEY PLAN
MAIN
ENTRY
BUILDING 17
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459
NON-SPRINKLERED
Sheet of
04/15/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:3
:1
P
M
B17-M201
FIRST LEVEL FLOOR PLAN -
MECHANICAL
EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B17
04/15/2022 JMM GTS
Project Number
36 176
1/8" = 1'-0" F2
FIRST LEVEL FLOOR PLAN - MECHANICAL
0 8' 16'4'
SHEET NOTES:
1. ROUTE NEW REFRIGERANT LINES OUT OF SIDEWALL OF BUILDING TO ASSOCIATED AIR COOLED
CONDENSER.
2. ROUTE 3/4" PUMPED CONDENSATE TO MOP SINK IN H.A.C. 101
3. CONNECT NEW 1/2" DOMESTIC COLD WATER INTO EXISTING DOMESTIC COLD WATER LINE IN CEILING.
PROVIDE REDUCED PRESSURE ZONE BACKFLOW PREVENTER ON WALL OF H.A.C. AND ROUTE DRAIN LINE TO MOP SINK. PROVIDE 1/2' NON-POTABLE COLD WATER LINE TO SERVE HUMIDIFIER H-1 AND
ASSOCIATED RO SYSTEM.
GENERAL NOTES:
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE
ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
BUILDING 17
LOCATE TWO OF THE BUILDING 17
CONDENSING UNITS IN THIS AREA.
MAINTAIN SERVICE CLEARANCES FOR
BUILDING ENTRANCES AND EQUIPMENT.
BUILDING 17
LOCATE TWO BUILDING 17 AIR
COOLED CONDENSERS IN THIS AREA.
PROVIDE TWO FOOT CLEARANCE
BETWEEN THE BUILDING.
INDICATES POINT OF VIEW OF REFERENCE PHOTO ON SHEET WITH CORRESPONDING NUMBER.##
PHOTO 01
PHOTO 02
HT
TR
223 OFFICE
OFFICE
CORRIDOR
C200
STAFF LOUNGE
OFFICE
OFFICE
CONFERENCE
ROOM
OFFICE
SUPPLY ROOM
WORKROOM
MECH CHASE
203B
MENS TOILET
203A
CORRIDOR
C201
STORAGE
216A
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
OFFICE
OFFICE
WOMEN TOILET
OFFICE
OFFICES
1 2 3 4 5 6 7 8 9 10 11 12
B17-M400
F1
G1
12x12 RA
3/4" PC
1/2" NPW
KEY PLAN
MAIN
ENTRY
BUILDING 17
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459
NON-SPRINKLERED
Sheet of
04/15/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:3
:1
P
M
B17-M202
SECOND LEVEL FLOOR PLAN -
MECHANICAL
EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B17
04/15/2022 JMM GTS
Project Number
37 176
1/8" = 1'-0" F2
SECOND LEVEL FLOOR PLAN - MECHANICAL
0 8' 16'4'
SHEET NOTES:
1. ROUTE 3/4" PUMPED CONDENSATE TO MOP SINK IN H.A.C. 201.
2. CONNECT NEW 1/2" DOMESTIC COLD WATER INTO EXISTING DOMESTIC COLD WATER LINE IN CEILING.
PROVIDE REDUCED PRESSURE ZONE BACKFLOW PREVENTER ON WALL AND ROUTE BACKFLOW REPVENTER DRAIN LINE TO MOP SINK. PROVIDE 1/2" NON-POTABLE WATER FROM BACKFLOW PREVENTER TO SERVE
HUMIDIFIER H-1 AND ASSOCIATED RO SYSTEM.
3. CONNECT 1/2" NON-POTABLE WATER LINE TO HUMIDIFER AND ASSOCIATED RO SYSTEM.
GENERAL NOTES:
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE
ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
C1/F1
TR
S S
IU
-1
7-
6A
S S
IU
-1
7-
6B5
FDFD
F-1
PF-16"x6"
G6
12x12
H-1
CP-1
M501
D1
TR
SSIU-17-223A1
SSIU-17-223B
FDFD
6"x6"
G6
PF-2
F-2
12x12
CP-2
H-2
M501
D1
TR
H-2
CP-2
3/4" PC
1" CD
SSIU-17-223A
SSIU-17-223B
1/2" NPW
M501
D1
TR
CP-1
H-1
3/4" CD
1/2" NPW
SSIU-17-126A
SSIU-17-126B
3/4" CD
1" CD
M501
D1
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459
NON-SPRINKLERED
Sheet of
04/15/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:3
:1
P
M
B17-M400
MECHANICAL - ENLARGED PLANS EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B17
04/15/2022 JMM GTS
Project Number
38 176
1/2" = 1'-0" F6
ENLARGED MECHANICAL PLAN - ROOM 126
1/2" = 1'-0"
F1
ENLARGED MECHANICAL PLAN - ROOM 223
0 2' 4'1' 0 2' 4'1'
SHEET NOTES:
1. BOTTOM OF COOLING UNIT SHALL BE A MINIMUM OF 7-0” A.F.F. ADJUST MOUNTING HEIGHT TO AVOID
CONFLICTS WITH CABLE TRAY. MAINTAIN MANUFACTURERS SERVICE CLEARANCE RECOMMENDATIONS.
2. ROUTE 3/8" REFRIGERANT LIQUID LINE AND 5/8" REFRIGERANT HOT GAS LINE FROM CONDENSING UNIT TO
CORRESPONDING DUCT-FREE SYSTEM. PIPE SIZES ARE FOR COST ESTIMATING PURPOSES, AND BASED ON
BASIS OF DESIGN MANUFACTURE AS LISTED IN THE SCHEDULE. SIZE LINES ACCORDING TO
MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL ACCESSORIES REQUIRED FOR A COMPLETE AND
OPERABLE SYSTEM.
3. ROUTE 3/4” GRAVITY CONDENSATE DRAIN LINE FROM SSIU-17-126B NORTH. COMBINE WITH SSIU-17-126A CONDENSATE DRAIN LINE. CONTINUE DRAIN LINE AS SHOWN ON PLANS, COMBINE WITH HUMIDIFIER DRAIN
AND RO DRAIN LINE AND CONTINUE AS 1" LINE TO CP-1.
4. REFRIGERANT LINES UP TO LEVEL 2.
5. PROVIDE WATER BUG AT FLOOR TO ALARM TO DDC WHEN ACTIVATED.
6. CONNECT NEW 1/2" NON-POTABLE WATER TO NEW HUMIDIFIER H-1 AND RO SYSTEM IN TR ROOM. PROVIDE
DRAIN PAN UNDER WATER LINES WITHIN TR ROOMS WITH WATER BUG ALARM TO BMS.
7. CONNECT 1/2" NON-POTABLE WATER TO HUMIDIFIER AND RO SYSTEM.
8. ROUTE NEW REFRIGERANT LINES DOWN THROUGH FLOOR AND OUT SIDEWALL OF BUILDING TO
ASSOCIATED AIR COOLED CONDENSER MOUNTED AT GRADE.
9. MAINTAIN HUMIDIFIER MANUFACTURERS REQUIRED “NON-WETTING” CLEARANCES FROM
HUMIDIFIER. COORDINATE WITH OTHER TRADES TO ENSURE NO SOLID SURFACES OR OBJECTS ARE
LOCATED WITHIN THE MANUFACTURES “NON-WETTING” DISTANCES.
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
GENERAL NOTES:
1/2" = 1'-0" C1
ENLARGED PLUMBING PLAN - ROOM 223
0 2' 4'1'
1/2" = 1'-0" C6
ENLARGED PLUMBING PLAN - ROOM 126
0 2' 4'1'
1. PERFORMANCE BASED ON CONDITIONS INDICATED IN THIS SCHEDULE.
2. PROVIDE THE FOLLOWING ACCESSORIES: MANUFACTURER'S DISCONNECT AND LINESET.
3. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT
BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR
PRIOR TO ORDERING EQUIPMENT.
REMARKS:
1. PERFORMANCE BASED ON CONDITIONS INDICATED IN THIS SCHEDULE.
2. PROVIDE CONCRETE PAD AND ANCHOR EXTERIOR UNIT TO PAD.
3. PROVIDE CURB RAILS AND ROOF SUPPORTS FOR OUTDOOR UNIT.
4. PROVIDE THE FOLLOWING ACCESSORIES: SINGLE POINT POWER CONNECTION, DISCONNECT, HAIL GUARDS, LOW AMBIENT KIT, WIND BAFFLES.
5. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT
BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR
PRIOR TO ORDERING EQUIPMENT.
REMARKS:
1. COORDINATE EXACT MODEL AND FRAME WITH CEILING / WALL TYPE.
2. WHEN INSTALLED IN A WALL, THE BLADES FOR THESE GRILLES SHALL BE SUCH THAT THE FRONT BLADES
ARE HORIZONTAL (PARALLEL TO THE FLOOR). WHEN INSTALLED IN A CEILING, THE BLADES FOR THESE GRILLES SHALL BE SUCH THAT THE FRONT BLADES ARE PARALLEL TO THE LONG DIMENSION OF THE
GRILLE.
REMARKS:
1. PROVIDE MAGNAHELIC GAUGE ACROSS HOUSING FILTER.
2. PROVIDE FILTER BANK HOLDING FRAME. SUPPORT FRAME FROM STRUCTURE.
REMARKS:
1. PROVIDE DISCONNECT.
2. PROVIDE VIBRATION ISOLATION.
3. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT
BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION.
EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL
CONTRACTOR PRIOR TO ORDERING EQUIPMENT.
REMARKS:
1. PROVIDE WITH THE FOLLOWING ACCESSORIES: BLOWER PACK, BLOWER PACK FILTER SET, INLET AIR FILTER, CLEANING KIT, AND MANUFACTURER RO SYSTEM TO SERVE HUMIDIFIER.
2. PROVIDE DRAIN PIPING CONNECTION TO UNIT AND CONNECT INDIRECTLY TO SANITARY DRAINAGE SYSTEM.
REMARKS:
1. PERFORMANCE BASED ON FLUID AND CONDITIONS INDICATED IN THIS SCHEDULE.
2. PROVIDE WITH HIGH WATER LEVEL (OVERFLOW DETECTION) SWITCH WITH TERMINAL FOR CONNECTION TO DDC EXTERNAL ALARM.
3. PROVIDE WITH 6’, 3-CONDUCTOR CABLE WITH GROUNDED 3-PRONGE PLUG.
4. MAXIMUM 5’ OF 3/8” VINYL DISCHARGE TUBING FOR TRANSITION CONNECTION TO COPPER PUMPED CONDENSATE PIPING.
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459
NON-SPRINKLERED
Sheet of
04/15/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:3
:1
P
M
B17-M600
MECHANICAL SCHEDULES EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B17
04/15/2022 JMM GTS
Project Number
39 176
SPLIT SYSTEM AIR CONDITIONER - INDOOR SCHEDULE
MARK
ROOM SERVED
NOMINAL
CAPACITY
[TONS]
TOTAL COOLING
CAPACITY
[MBH]
CONDENSATE DRAIN
SIZE
INDOOR UNIT ELECTRICAL DATA
MANUFACTURER REMARKSNAME NUMBER
DIMENSIONS [IN] EAT
(DB / WB)
[°F] MODEL FLA VOLTAGE PHASE MCA DISCONNECT BY SCCRLENGTH WIDTH HEIGHT
SSIU-17-126A TR 126 2.0 24 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0241KA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)
SSIU-17-126B TR 126 2.0 24 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0241KA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)
SSIU-17-223A TR 223 2.0 24 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0241KA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)
SSIU-17-223B TR 223 2.0 24 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0241KA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)
SPLIT SYSTEM AIR CONDITIONER - OUTDOOR SCHEDULE
MARK
ROOM SERVED
NOMINAL
CAPACITY
[TONS]
TOTAL COOLING
CAPACITY
[MBH]
OUTDOOR UNIT ELECTRICAL DATA
MANUFACTURER REMARKSNAME NUMBER
DIMENSIONS [IN] SUMMER AMBIENT
AIR
[°F]
WINTER AMBIENT
AIR
[°F]
OPERATING
WEIGHT
[LBS] MODEL FLA VOLTAGE PHASE MCA MOCP DISCONNECT BY SCCRLENGTH WIDTH HEIGHT
SSOU-17-126A TR 126 2.0 24 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0241KA70NA 7.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)
SSOU-17-126B TR 126 2.0 24 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0241KA70NA 7.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)
SSOU-17-223B TR 223 2.0 24 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0241KA70NA 7.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)
SSOU-17223A TR 223 2.0 24 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0241KA70NA 7.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)
DIFFUSER, REGISTER, AND GRILLE SCHEDULE
MARK IMAGE DESCRIPTION MAX S.P. MATERIAL FINISH
FACE SIZE
NECK SIZE AIRFLOW MANUFACTURER MODEL REMARKSLENGTH WIDTH
G1 PERFORATED RETURN
GRILLE
0.10 in-wg STEEL PAINT, WHITE 24" 24" 6"x6" 8"x8"
10"x10" 12"x12" 14"x14"
0-125 126-180 181-210 211-300 301-410
TITUS
KRUEGER
PRICE
PAR
PDDR
(1)
G6 SINGLE DEFLECTION
RETURN GRILLE
0.10 in-wg STEEL PAINT, WHITE 6" 6" SEE PLAN SEE PLAN TITUS 350RL/SL (1)(2)
FAN SCHEDULE
MARK TYPE
MAX WEIGHT
[LBS]
AIRFLOW
[CFM]
TOTAL S.P.
[IN W.C.] MAX FAN RPM MAX FAN BHP
ELECTRICAL DATA
MANUFACTURER MODEL REMARKSFLA VOLTAGE PHASE DISCONNECT BY
F-2 IN-LINE 24 100 0.54 1288 0.03 1.5 115 V 1 MECHANICAL GREENHECK CSP-A390-VG (1)(2)(3)
F-1 IN-LINE 24 100 0.54 1288 0.03 1.5 115 V 1 MECHANICAL GREENHECK CSP-A390-VG (1)(2)(3)
FILTER SCHEDULE
MARK ASSOCIATED EQUIPMENT TYPE
DEPTH
[IN] MERV RATING REMARKS
PF-1 F-1 12"x12" 2" 11 (1)(2)
PF-2 F-2 12"x12" 2" 11 (1)(2)
ULTRASONIC HUMIDIFIER SCHEDULE
MARK SERVICE
MAKE UP WATER
CONNECTION SIZE
WATER PIPING ELECTRICAL DATA
MANUFACTURER MODEL REMARKS
CAPACITY
[LB / HR]
DRAIN PIPE CONNECTION
SIZE KW VOLTAGE PHASE
H-1 TR 126 1/2" 6.6 1" 0.25 120 V 1 CONDAIR US-7 (1)(2)
H-2 TR 223 1/2" 6.6 1" 0.25 120 V 1 CONDAIR US-7 (1)(2)
PUMP SCHEDULE
MARK
FLOW
[GPM]
TOTAL HEAD
[FT]
SHUT-OFF HEAD
[FT]
SUCTION /
DISCHARGE SIZE
[IN]
ELECTRICAL DATA
MANUFACTURER MODEL REMARKSHP FLA VOLTAGE
CP-1 10 20 21 3/8 0.0333 1.5 115 V LITTLE GIANT VCMX-20ULS (1)(2)(3)(4)
CP-2 10 20 21 3/8 0.0333 1.5 115 V LITTLE GIANT VCMX-20ULS (1)(2)(3)(4)
KITCHEN
GARAGE
BATH
STAIR
103A
LOUNGE
B41-M400
F5
REFS
REFL
SSOU-41-104
3/4" PC
KEY PLAN
MAIN
ENTRY
BUILDING 41
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459
NON-SPRINKLERED
Sheet of
04/15/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:1
:0
P
M
B41-M201
FIRST LEVEL FLOOR PLAN -
MECHANICAL
EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B41
04/15/2022 JMM GTS
Project Number
40 176
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
SHEET NOTES:
1. ROUTE 3/4" PUMPED CONDENSATE DOWN WALL TO BELOW LAVATORY. PROVIDE NEW 1-1/4" HUB DRAIN
CONNECTION WITH TRAP INTO EXISTING SANITARY. PROVIDE INDIRECT DISCHARGE CONNECTION INTO HUB
DRAIN.
GENERAL NOTES:
1/4" = 1'-0" F4
FIRST LEVEL FLOOR PLAN - MECHANICAL
0 4' 8'2'
LOUNGE
SSIU-41-104
3/4" PC
3 2
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459
NON-SPRINKLERED
Sheet of
04/15/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:1
:0
P
M
B41-M400
MECHANICAL - ENLARGED PLANS EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B41
04/15/2022 JMM GTS
Project Number
41 176
1/2" = 1'-0" F5
ENLARGED MECHANICAL AND PLUMBING PLAN - ROOM 104
0 2' 4'1'
SHEET NOTES:
1. BOTTOM OF NEW EQUIPMENT SHALL BE 7'-6" ABOVE FINISHED FLOOR.
2. ROUTE 3/8" REFRIGERANT LIQUID LINE AND 5/8" REFRIGERANT HOT GAS LINE FROM CONDENSING UNIT TO
CORRESPONDING DUCT-FREE SYSTEM. PIPE SIZES ARE FOR COST ESTIMATING PURPOSES, AND BASED ON
BASIS OF DESIGN MANUFACTURE AS LISTED IN THE SCHEDULE. SIZE LINES ACCORDING TO
MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL ACCESSORIES REQUIRED FOR A COMPLETE AND
OPERABLE SYSTEM.
3. CONNECT COOLING UNIT PUMPED CONDENSATE LINE INTO 3/4" COPPER DRAIN LINE.
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
2. PROVIDE THE FOLLOWING ACCESSORIES: MANUFACTURER'S DISCONNECT AND LINESET.
3. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT
BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR
PRIOR TO ORDERING EQUIPMENT.
REMARKS:
1. PERFORMANCE BASED ON CONDITIONS INDICATED IN THIS SCHEDULE.
2. PROVIDE CONCRETE PAD AND ANCHOR EXTERIOR UNIT TO PAD.
3. PROVIDE CURB RAILS AND ROOF SUPPORTS FOR OUTDOOR UNIT.
4. PROVIDE THE FOLLOWING ACCESSORIES: SINGLE POINT POWER CONNECTION, DISCONNECT, HAIL GUARDS, LOW AMBIENT KIT, WIND BAFFLES.
5. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT
BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR
PRIOR TO ORDERING EQUIPMENT.
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459
NON-SPRINKLERED
Sheet of
04/15/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:1
:0
P
M
B41-M600
MECHANICAL SCHEDULES EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B41
04/15/2022 JMM GTS
Project Number
42 176
SPLIT SYSTEM AIR CONDITIONER - INDOOR SCHEDULE
MARK
ROOM SERVED
NOMINAL
CAPACITY
[TONS]
TOTAL COOLING
CAPACITY
[MBH]
CONDENSATE DRAIN
SIZE
INDOOR UNIT ELECTRICAL DATA
MANUFACTURER REMARKSNAME NUMBER
DIMENSIONS [IN] EAT
(DB / WB)
[°F] MODEL FLA VOLTAGE PHASE MCA DISCONNECT BY SCCRLENGTH WIDTH HEIGHT
SSIU-41-104 LOUNGE 104 2.0 24 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0241HA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)
SPLIT SYSTEM AIR CONDITIONER - OUTDOOR SCHEDULE
MARK
ROOM SERVED
NOMINAL
CAPACITY
[TONS]
TOTAL COOLING
CAPACITY
[MBH]
OUTDOOR UNIT ELECTRICAL DATA
MANUFACTURER REMARKSNAME NUMBER
DIMENSIONS [IN] SUMMER AMBIENT
AIR
[°F]
WINTER AMBIENT
AIR
[°F]
OPERATING
WEIGHT
[LBS] MODEL FLA VOLTAGE PHASE MCA MOCP DISCONNECT BY SCCRLENGTH WIDTH HEIGHT
SSOU-41-104 LOUNGE 104 2.0 24 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0241HA10NA 7.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)
121314
KEY PLAN
MAIN
ENTRY
BUILDING 49
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459 Sheet of
04/15/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:2
:1
P
M
B49-M100
BASEMENT LEVEL FLOOR PLAN -
MECHANICAL DEMO
EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B49
04/15/2022 JMM GTS
Project Number
43 176
1/4" = 1'-0" F3
BASEMENT LEVEL FLOOR PLAN - MECHANICAL - DEMO
0 4' 8'2'
SHEET NOTES:
1. DEMOLISH EXISTING ROOM SPRINKLER HEADS. DEMOLISH EXISTING SPRINKLER PIPING WITHIN AREA OF
NEW CONSTRUCTION AND REROUTE PIPING AROUND ROOM.
2. DEMOLISH EXISTING ROOM COOLING UNIT, PIPING, AND EXTERIOR CONDENSING UNIT. COORDINATE WITH
NEW WORK.
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
121314
SPRINKLER
STORAGE
H. A. C.
MECHANICAL
TOILET
MECHANICAL
002 STAIRS
S001
ELEV EQUIP
VESTIBULE
C001
LOWER LEVEL
TR
B49-M400
B1
3/4" PC
1/2" NPW
KEY PLAN
MAIN
ENTRY
BUILDING 49
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459 Sheet of
04/15/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:2
:1
P
M
B49-M200
BASEMENT LEVEL FLOOR PLAN -
MECHANICAL
EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B49
04/15/2022 JMM GTS
Project Number
44 176
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
SHEET NOTES:
1. ROUTE REFRIGERANT PIPING THROUGH SIDE WALL OUT TO GRADE MOUNTED CONDENSING UNIT.
2. ROUTE 3/4" PUMPED CONDENSATE TO WITHIN TWO INCHES OF MOP SINK IN H.A.C. 008 AND DISCHARGE WITH
ONE INCH AIR GAP. SLOPE PUMPED CONDENSATE DRAIN TOWARD MOP SINK.
3. CONNECT 1/2" DOMESTIC COLD WATER TO EXISTING DOMESTIC COLD WATER LINE IN CEILING ABOVE MOP
SINK. PROVIDE REDUCED PRESSURE ZONE BACKFLOW PREVENTER ON WALL, ROUTE DRAIN LINE TO MOP
SINK.
4. ROUTE 1/2" NON-POTABLE WATER FROM BACKFLOW PREVENTER TO HUMIDIFIER AND RO SYSTEM.
GENERAL NOTES:
1/4" = 1'-0" F3
BASEMENT LEVEL FLOOR PLAN - MECHANICAL
0 4' 8'2'
121314
WORK ROOM
STORAGE
ELEV
TOILET
VESTIBULE
STAIR
MEDICAL LIBRARY
CIRCULATION
STORAGE
105A
SSOU-49-105B
SSOU-49-105A
M500
B7
KEY PLAN
MAIN
ENTRY
BUILDING 49
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459 Sheet of
04/15/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:2
:1
P
M
B49-M201
FIRST LEVEL FLOOR PLAN -
MECHANICAL
EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B49
04/15/2022 JMM GTS
Project Number
45 176
1/4" = 1'-0" F3
FIRST LEVEL FLOOR PLAN - MECHANICAL
0 4' 8'2'
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
R
T H
TR
SSIU-49-105A 1 1
2 2
PF-1
F-1
FDFD
SSIU-49-105B
CP-1
H-1
3/4" PC
6"x6"
G6
12x12
12"x12"
G6
1" CD
M501
D1
CP-2
3/4" PC
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459 Sheet of
04/15/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:2
:1
P
M
B49-M400
MECHANICAL - ENLARGED PLANS EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B49
04/15/2022 JMM GTS
Project Number
46 176
1/2" = 1'-0" B1
ENLARGED MECHANICAL & PLUMBING PLAN - BASEMENT
0 2' 4'1'
SHEET NOTES:
1. BOTTOM OF COOLING UNIT SHALL BE A MINIMUM OF 7-0” A.F.F. ADJUST MOUNTING HEIGHT TO AVOID
CONFLICTS WITH CABLE TRAY. MAINTAIN MANUFACTURERS SERVICE CLEARANCE RECOMMENDATIONS.
2. ROUTE 3/8" REFRIGERANT LIQUID LINE AND 5/8" REFRIGERANT HOT GAS LINE FROM CONDENSING UNIT TO
CORRESPONDING DUCT-FREE SYSTEM. PIPE SIZES ARE FOR COST ESTIMATING PURPOSES, AND BASED ON
BASIS OF DESIGN MANUFACTURE AS LISTED IN THE SCHEDULE. SIZE LINES ACCORDING TO
MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL ACCESSORIES REQUIRED FOR A COMPLETE AND
OPERABLE SYSTEM.
3. ROUTE 3/4" GRAVITY CONDENSATE DRAIN LINE FROM SSIU-49-105A. COMBINE WITH SSIU-49-105B DRAIN LINE
AND CONTINUE AS SHOWN ON PLANS TO CP-1.
4. PROVIDE WATER BUG AT FLOOR TO ALARM TO DDC WHEN ACTIVATED.
5. LOCATE NEW SPRINKLERS IN NEW TR AND ADJOINING CORRIDOR PER CODE AND TO ACCOMODATE NEW
ROOM LAYOUT. PROVIDE SPRINKLER GUARDS ON ALL SPRINKLERS IN TR ROOM.
6. CONNECT 1/2" NON-POTABLE WATER TO HUMIDIFER AND RO SYSTEM.
7. MAINTAIN HUMIDIFIER MANUFACTURERS REQUIRED “NON-WETTING” CLEARANCES FROM
HUMIDIFIER. COORDINATE WITH OTHER TRADES TO ENSURE NO SOLID SURFACES OR OBJECTS ARE
LOCATED WITHIN THE MANUFACTURES “NON-WETTING” DISTANCES.
8. ROUTE 3/4" CONDENSATE DRAIN FROM HUMIDIFIER TO CP-2.
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
5. WHETHER INDICATED BY OTHER PLAN NOTES OR NOT, PROVIDE A DRAIN PAN UNDER ALL EXISTING OR NEW HORIZONTAL PLUMBING OR MECHANICAL PIPING LOCATED IN TR ROOMS, SERVER ROOMS OR ENTRANCE ROOMS. DRAIN PANS TO BE PROVIDED WITH WATER BUG SENSORS WITH ALARM TO THE DDC.
2. PROVIDE THE FOLLOWING ACCESSORIES: MANUFACTURER'S DISCONNECT AND LINESET.
3. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT
BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR
PRIOR TO ORDERING EQUIPMENT.
REMARKS:
1. PERFORMANCE BASED ON CONDITIONS INDICATED IN THIS SCHEDULE.
2. PROVIDE CONCRETE PAD AND ANCHOR EXTERIOR UNIT TO PAD.
3. PROVIDE CURB RAILS AND ROOF SUPPORTS FOR OUTDOOR UNIT.
4. PROVIDE THE FOLLOWING ACCESSORIES: SINGLE POINT POWER CONNECTION, DISCONNECT, HAIL GUARDS, LOW AMBIENT KIT, WIND BAFFLES.
5. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT
BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR
PRIOR TO ORDERING EQUIPMENT.
REMARKS:
1. COORDINATE EXACT MODEL AND FRAME WITH CEILING / WALL TYPE.
2. WHEN INSTALLED IN A WALL, THE BLADES FOR THESE GRILLES SHALL BE SUCH THAT THE FRONT BLADES ARE HORIZONTAL (PARALLEL TO THE FLOOR). WHEN INSTALLED IN A CEILING, THE BLADES FOR THESE GRILLES SHALL BE SUCH THAT THE
FRONT BLADES ARE PARALLEL TO THE LONG DIMENSION OF THE GRILLE.
REMARKS:
1. PROVIDE DISCONNECT.
2. PROVIDE VIBRATION ISOLATION.
3. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING
SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR PRIOR TO ORDERING EQUIPMENT.
REMARKS:
1. PROVIDE MAGNAHELIC GAUGE ACROSS HOUSING FILTER.
2. PROVIDE FILTER BANK HOLDING FRAME. SUPPORT FRAME FROM STRUCTURE.
REMARKS:
1. PROVIDE WITH INTEGRAL CONDENSATE COOLER, BLOWER PACK.
REMARKS:
1. PERFORMANCE BASED ON FLUID AND CONDITIONS INDICATED IN THIS SCHEDULE.
2. PROVIDE WITH HIGH WATER LEVEL (OVERFLOW DETECTION) SWITCH WITH TERMINAL FOR CONNECTION TO DDC EXTERNAL ALARM.
3. PROVIDE WITH 6’, 3-CONDUCTOR CABLE WITH GROUNDED 3-PRONGE PLUG.
4. MAXIMUM 5’ OF 3/8” VINYL DISCHARGE TUBING FOR TRANSITION CONNECTION TO COPPER PUMPED CONDENSATE PIPING.
5. PROVIDE WITH BRASS CHECK VALVE.
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459 Sheet of
04/15/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
.T
R
.r v t
/1
/2
:2
:1
P
M
B49-M600
MECHANICAL SCHEDULES EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B49
04/15/2022 JMM GTS
Project Number
47 176
SPLIT SYSTEM AIR CONDITIONER - INDOOR SCHEDULE
MARK
ROOM SERVED
NOMINAL
CAPACITY
[TONS]
TOTAL COOLING
CAPACITY
[MBH]
CONDENSATE DRAIN
SIZE
INDOOR UNIT ELECTRICAL DATA
MANUFACTURER REMARKSNAME NUMBER
DIMENSIONS [IN] EAT
(DB / WB)
[°F] MODEL FLA VOLTAGE PHASE MCA DISCONNECT BY SCCRLENGTH WIDTH HEIGHT
SSIU-49-105A TR 009 2.0 24 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0241KA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)
SSIU-49-105B TR 009 2.0 24 3/4" 46 1/16" 11 5/8" 14 3/8" 80/67 TPKA0A0241KA70A 0.36 208 V 1 1 MANUFACTURER 5 TRANE (1)(2)(3)
SPLIT SYSTEM AIR CONDITIONER - OUTDOOR SCHEDULE
MARK
ROOM SERVED
NOMINAL
CAPACITY
[TONS]
TOTAL COOLING
CAPACITY
[MBH]
OUTDOOR UNIT ELECTRICAL DATA
MANUFACTURER REMARKSNAME NUMBER
DIMENSIONS [IN] SUMMER AMBIENT
AIR
[°F]
WINTER AMBIENT
AIR
[°F]
OPERATING
WEIGHT
[LBS] MODEL FLA VOLTAGE PHASE MCA MOCP DISCONNECT BY SCCRLENGTH WIDTH HEIGHT
SSOU-49-105A TR 105 2.0 24 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0241KA70NA 7.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)
SSOU-49-105B TR 105 2.0 24 38" 13 3/8" 38" 95 / 75 -10 151 TRUYA0241KA70NA 7.4 208 V 1 19 26 ELEC 5 TRANE (1)(2)(3)(4)(5)
DIFFUSER, REGISTER, AND GRILLE SCHEDULE
MARK IMAGE DESCRIPTION MAX S.P. MATERIAL FINISH
FACE SIZE
NECK SIZE AIRFLOW MANUFACTURER MODEL REMARKSLENGTH WIDTH
G6 SINGLE DEFLECTION
RETURN GRILLE
0.10 in-wg STEEL PAINT, WHITE 6" 6" SEE PLAN SEE PLAN TITUS 350RL/SL (1)(2)
FAN SCHEDULE
MARK TYPE
MAX WEIGHT
[LBS]
AIRFLOW
[CFM]
TOTAL S.P.
[IN W.C.] MAX FAN RPM MAX FAN BHP
ELECTRICAL DATA
MANUFACTURER MODEL REMARKSFLA VOLTAGE PHASE DISCONNECT BY
F-1 IN-LINE 24 100 0.54 1288 0.03 1.5 115 V 1 MECHANICAL GREENHECK CSP-A390-VG (1)(2)(3)
FILTER SCHEDULE
MARK ASSOCIATED EQUIPMENT TYPE
DEPTH
[IN] MERV RATING REMARKS
PF-1 F-1 12"x12" 2" 11 (1)(2)
ELECTRODE STEAM HUMIDIFIER SCHEDULE
MARK SERVICE
MAKE UP WATER
CONNECTION SIZE
STEAM TO STEAM ELECTRIC ELECTRICAL DATA HUMIDIFIER MANIFOLD
REMARKS
CAPACITY
[LB / HR]
DRAIN PIPE CONNECTION
SIZE KW VOLTAGE PHASE MANUFACTURER MODEL
H-1 TR 009 1/2" 5.6 3/4" 1.9 120 V 1 DRISTEEM XTR (1)
PUMP SCHEDULE
MARK
FLOW
[GPM]
TOTAL HEAD
[FT]
SHUT-OFF HEAD
[FT]
SUCTION /
DISCHARGE SIZE
[IN]
ELECTRICAL DATA
MANUFACTURER MODEL REMARKSHP FLA VOLTAGE
CP-1 10 20 21 3/8" 0.0333 1.5 115 V LITTLE GIANT VCMX-20ULS (1)(2)(3)(4)
CP-2 200 20 32 3/8" 0.125 1.4 115 V LITTLE GIANT HT-VCL-30-P (1)(2)(5)
B
A
D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
B
C
A
D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
10x6
KEY PLAN
MAIN
ENTRY
BUILDING 51-52
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES PROJECT #
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% FINAL STAMPED
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
20459 Sheet of
04/15/2022
B
IM
/2
V
A M a ri o n E
H R
M I n fr a s tr u c tu re U p g ra d e s D e s ig n /6
-7
.B
-5
.T
R
.r v t
/1
/2
:2
:2
P
M
B51-52-M100
BASEMENT LEVEL FLOOR PLAN -
MECHANICAL - DEMO
EHRM INFRASTRUCTURE
UPGRADES, MARION, IN
MARION, IN
610-21-701
B51-52
04/15/2022 JMM GTS
16181
48 176
1/8" = 1'-0" E1
BASEMENT LEVEL FLOOR PLAN - MECHANICAL - DEMO
0 8' 16'4'
SHEET NOTES:
1. REMOVE PORTION OF EXISTING GLYCOL HEAT PUMP LINES AND REROUTE TO AVOID NEW TR ROOM.
ASSUMED SIZE FOR BIDDING PURPOSES IS 3". CONFIRM PIPE SIZE IN FIELD.
2. REMOVE PORTION OF EXISTING 10X6 DUCTWORK TO AVOID NEW TR ROOM. SALVAGE SUPPLY GRILLE AND
MOVE TO NEW LOCATION. REFER TO NEW WORK PLAN.
3. DEMOLISH 1/2" DOMESTIC COLD WATER LINE AND SALVAGE EXTERIOR HOSE BIBB FOR REUSE. REFER TO
NEW WORK PLAN.
1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR
DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS…