This document is a technical riser diagram for a Video Surveillance Security (SSTV) System improvement project at the Alvin C. York Campus in Murfreesboro, Tennessee, prepared by Apogee Consulting Group, P.A. for the U.S. Department of Veterans Affairs (VA Project 22-215, Drawing T-601).
The project specifies installation of video surveillance infrastructure across multiple buildings, including two 44-unit server cabinets equipped with Avigilon NVR5-PRM-288TB-S19-NA network video recorders with 10G Ethernet connections, an SMT3000C UPS for power continuity, 24-port PoE switches with 2-10 GigE uplinks (to be provided by VA), fiber optic and copper patch panels, and wire management systems. Additional requirements include three 55-inch VSS monitors with HDMI inputs for the Police Dispatch room (wall-mounted), one monitor with desk stand (HDMI inputs), a slide-out 17-inch laptop workstation, and new telecommunications outlets in the dispatch area. The contractor must coordinate exact fiber routing, conduit penetrations with fire-caulking for rated walls/floors, and all stub-up locations with the Contracting Officer's Representative (COR) prior to rough-in. Cabling specifications mandate Cat 6A UTP for runs under 295 feet (minimum 1-1/4" conduit) and fiber for longer runs (minimum 3/4" electrical conduit). The project is marked "Fully Sprinklered" and dated June 13, 2024, with coordination required among VA, COR, Police, and OIT representatives.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
24 PORT PoE
SWITCH(ES)
WIRE MANAGEMENT
WIRE MANAGMENT
FIBER OPTIC
PATCH PANEL
WIRE MANAGMENT
COPPER
PATCH PANEL
WIRE MANAGEMENT
SPACE
NVR
NVR
NVR
BUILDING 5
(IRM SERVER ROOM 115)
4UPS
55" VSS
MONITOR
PC
DISPATCH ROOM
55" VSS
MONITOR
55" VSS
MONITOR
6 6 6
8 8
BUILDING 112
(IRM SERVER ROOM 115)
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:2
:0
P
M C
U s e rs
\l s ta rn e s \D o c u m e n ts
\E -2
-2
Y
-V A
Y o rk
-V id e o S e c I m p ro v -T
N ls ta rn e s C
B U
M B
.r v t
T-601
TECHNOLOGY RISERS
26 26LAS
VIDEO SURVEILLANCE
SECURITY YORK
ALVIN C. YORK CAMPUS
3400 LEBANON ROAD
MURFREESBORO, TN 37129 JUNE 13, 2024
BID DOCUMENTS
626A4-22-10422-215
JVE
1 INCOMING MMF FIBER FROM TELECOM
ROOMS ROUTED TO FIBER OPTIC PATCH
PANEL IN SERVER RACK.
2 CCTV CABINET SHALL BE 44 Us - 23"W x 30"D -
FRONT GLASS DOOR, QUIET FAN WITH
FILTER, POWER STRIP SURGE PROTECTION
WITH FILTER, VERTICAL GROUND BUS BAR,
AND SHELVES.
13.CCTV CABINET, IN BUILDING 74, SHALL BE
44 Us - 23"W x 30"D - FRONT GLASS DOOR, QUIET FAN WITH FILTER, POWER STRIP
SURGE PROTECTION WITH FILTER, VERTICAL
GROUND BUS BAR, AND SHELVES.
3 AVIGILON (BASIS OF DESIGN) MODEL
#NVR5-PRM-288TB--S19-NA INSTALLED IN
NEW CCTV CABINET. INCLUDE 10G
ETHERNET CONNECTION.
4 NEW SMT3000C UPS TO PROVIDE
CONTINUITY OF POWER FOR RACK
EQUIPMENT.
5 RUN CAT 6A CABLING FROM SPARE PORTS IN
EXISTING SWITCH OR PATCH PANEL TO NEW
TELECOMMUNICATIONS OUTLET.
6 VSS MONITORS SHALL HAVE HDMI INPUTS.
VSS MONITORS SHALL BE WALL MOUNTED IN
POLICE DISPATCH. COORDINATE VSS
MONITOR CONNECTIONS WITH COR AND
POLICE.
7 VSS MONITOR SHALL HAVE HDMI INPUTS.
PROVIDE DESK STAND FOR VSS MONITOR.
COORDINATE VSS MONITOR CONNECTIONS
WITH COR AND OIT REPRESENTATIVE.
8 PROVIDE NEW TELECOMMUNICATIONS
OUTLET IN POLICE DISPATCH TO SERVE NEW
MONITOR WORKSTATION - PC, KEYBOARD,
MOUSE INCLUDED. COORDINATE WITH COR
AND POLICE FOR PC LOCATION.
9 PROVIDE SLIDE OUT LAPTOP. LAPTOP SHALL
HAVE 17" SCREEN.
10 COORDINATE LOCATION OF TELECOM
CLOSET WITH OIT AND COR.
Scale: No Scale
SSTV SYSTEM RISER DIAGRAM
A. FIBER ROUTING SHOWN IS DIAGRAMMATIC TO
INDICATE PROPOSED ROUTING. CONTRACTOR
TO COORDINATE EXACT ROUTING IN FIELD
WITH THE COR PRIOR TO ROUGH-IN.
B. CONTRACTOR SHALL FIELD COORDINATE ALL
STUB UP LOCATIONS WITH COR AND FIELD
CONDITIONS PRIOR TO ROUGH-IN.
C. PROVIDE FIRE-CAULK FOR ALL CONDUIT/CABLE
PENETRATIONS THROUGH RATED WALLS
AND/OR FLOORS.
D. SEE PROPOSED PHASING SCHEME, SHEET
T-001, FOR ADDITIONAL INFORMATION.
E. VA TO PROVIDE PoE DATA SWITCH WITH 2-10
GIG UPLINK FOR ALL CCTV EQUIPMENT SHALL.
F. USE 4 PR UTP FOR CABLE RUNS OF LESS THAN
295 FEET.
G. USE FIBER FOR CABLE RUNS GREATER THAN
295 FEET.
H. ALL ELECTRICAL CONDUIT SHALL BE MINIMUM
3/4" CONDUIT. ALL 4 PAIR BALANCED TWISTED
PAIR CONDUIT SHALL BE MINIMUM 1-1/4"
CONDUIT.
Scale: No Scale
SSTV SYSTEM RISER DIAGRAM
Docusign Envelope ID: B9B77CD2-F0C1-4BAA-8538-6B315B443E44
7/24/2024
| 22-215YELEC |
| Sheets |
| T-601 - TECHNOLOGY RISERS |