Atch 14 22-215Y BD Dwgs _Part4.pdf

PDF 2 MB Posted

Attached to
Z1DA--Project 626A4-22-104_Video Surveillance Security TVHS VAMC - Alvin C. York Campus
Solicitation number
36C24926R0064
Issued by

About this file

These are architectural bid documents for a Video Surveillance Security York project at the Alvin C. York Campus (3400 Lebanon Road, Murfreesboro, TN 37129) for the U.S. Department of Veterans Affairs. The project number is 22-215 with ACG project number 626A4-22-104. The documents consist of security plan drawings for Buildings 5, 6, and 7, prepared by Apogee Consulting Group, P.A., dated June 13, 2024, and marked as fully sprinklered.

The work involves camera installation, removal, and cabling infrastructure across multiple building floors. Key requirements include: (1) removing existing cameras and cabling in Buildings 6 and 7 and repairing affected surfaces to match existing conditions; (2) installing new cameras with new 4-pair UTP cabling routed to telecom rooms; (3) proposing a new Cisco 9300 switch and patch panel location in Building 5's IRM Server Room 115, verified with the Contracting Officer's Representative (COR) and OIT representative; (4) routing multimode fiber (MMF) from telecom rooms to Building 5 server room racks; (5) installing a new CCTV head-end equipment cabinet; (6) providing 1P, 20A circuit breaker in existing 120/208V UPS distribution panel with under-floor receptacle and circuit; (7) running CCTV cabling on J-hooks at 2-foot on-center spacing above ceiling in corridors; and (8) using 3/4-inch minimum conduit per NEC standards. Where camera-to-rack equipment distances exceed 295 feet (90 meters), fiber optic cable must be used. All work requires COR coordination prior to rough-in, ICRA containment measures, and contractor replacement of damaged ceiling tiles and grid at no additional cost to the government.

View the file

Other files

File Type Posted
S06 AMEND_7 36C24926R0064 0007-York Campus.pdf PDF
S02 AMEND-6_36C24926R0064 0006 MUR.pdf PDF
S02 36C24926R0064 0005 VIDEO -YORK.pdf PDF
Atch 24 JA Brand Name Avigilon VIDEO 626A4-22-104 MUR_Redacted.pdf PDF
S02 AMEND_4 36C24926R0064 0004.pdf PDF
S02 AMEND 36C24926R0064 0003 Protest.pdf PDF
Atch 1 Video camera design changes- York.pdf PDF
S02 AMEND 36C24926R0064 0002 VIDEO-York.pdf PDF
Atch 1 Video camera design changes.pdf PDF
S02 AMEND 36C24926R0064 0002 VIDEO-York.pdf PDF
Atch 1 Site Visit Sign In Sheet 626A4-22-104 _York.pdf PDF
S02 AMEND_1 36C24926R0064 0001 VIDEO York.pdf PDF
S02 36C24926R0064_1 VIDEO 626A4-22-104 YORK.pdf PDF
Atch 18 22-215Y BD Dwgs _Part8.pdf PDF
Atch 13 22-215Y BD Dwgs _Part3.pdf PDF
Atch 11 22-215Y BD Dwgs _Part1.pdf PDF
Atch 9 Price Breakout Schedule.xlsx XLSX spreadsheet
Atch 2 WD SCA 2015-4647 REV31 _05.13.2026 Rutherford-Davidson.docx DOCX document
36C24926R0064_1.docx DOCX document
Atch 22 JA Brand Name JCI VIDEO 626A4-22-104 MUR_1_Redacted.pdf PDF
Atch 17 22-215Y BD Dwgs _Part7.pdf PDF
Atch 12 22-215Y BD Dwgs _Part2.pdf PDF
Atch 10 22-215Y BD Specs.pdf PDF
Atch 8 General Conditions Breakout.xlsx XLSX spreadsheet
Atch 5 RFI Form.docx DOCX document
Atch 21 JA Brand Name Avigilon VIDEO 626A4-22-104 MUR_2_Redacted.pdf PDF
Atch 20 Fire-Smoke Barrier Permit.doc DOC document
Atch 15 22-215Y BD Dwgs _Part5.pdf PDF
Atch 3 Past Performance Questionnaire York.docx DOCX document
Atch 1 WD DBA-TN20260187 BUILDING MOD-0 01.02.2026 - MUR.docx DOCX document
Atch 23 SF1442 36C24926R0064_2.pdf PDF
Atch 19 HotWorkPermit.pdf PDF
Atch 16 22-215Y BD Dwgs _Part6.pdf PDF
Atch 7 Contractor EMR Certification Form.docx DOCX document
Atch 6 Calc. of Self Performed Work.xlsx XLSX spreadsheet
Atch 4 UEI _ TAX ID.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SERVER ROOM 115

5.T-101

1 2

PANEL 'A2'

PANEL 'A1'

PANEL 'B1'

PANEL 'B2'

PANEL 'A2'

PANEL 'A1'

PANEL 'B1'

PANEL 'B2'

PANEL 'A1'

PANEL 'B1'

PANEL 'A1'

PANEL 'B1'

PANEL 'A1'

PANEL 'C'

Engineers Architects

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/2

/2

:2

:0

P

M C

U s e rs

\l s ta rn e s \D o c u m e n ts

\E -2

-2

Y

-V A

Y o rk

-V id e o S e c I m p ro v -T

N ls ta rn e s C

B U

M B

.r v t

5.T-101

BUILDING 5 FIRST FLOOR SECURITY

PLAN

10 26LAS

VIDEO SURVEILLANCE

SECURITY YORK

ALVIN C. YORK CAMPUS

3400 LEBANON ROAD

MURFREESBORO, TN 37129 JUNE 13, 2024

BID DOCUMENTS

626A4-22-10422-215

JVE

Scale: 3/32" = 1'-0"

BUILDING 5 FIRST FLOOR SECURITY PLAN

1 PROPOSED LOCATION OF NEW CISCO 9300

SWITCH AND PATCH PANEL. VERIFY

LOCATION WITH COR AND OIT

REPRESENTATIVE.

2 INSTALL NEW CAMERAS. PROVIDE NEW 4 PR

UTP CABLING FROM CAMERA TO NEW POE

SWITCH IN TELECOM ROOM. REPAIR/

REPLACE SURFACES AFFECTED BY CAMERA

EQUIPMENT INSTALLATION TO MATCH

SIMILAR/EXISTING CONDITIONS.

CONTRACTOR TO REPLACE DAMAGED

CEILING TILE AND GRID ASSOCIATED WITH

WORK AT NO ADDITIONAL COST TO

GOVERNMENT.

3 EXISTING UPS WITH 120/208V POWER

DISTRIBUTION PANEL.

4 NEW CCTV HEAD END EQUPMENT TO BE

MOUNTED IN NEW CABINET. COORDINATE

LOCATION WITH COR.

5 PROVIDE 1P, 20A CIRCUIT BREAKER IN THE

EXISTING 120/208V UPS DISTRIBUTION

PANEL. RECEPTACLE AND CIRCUIT TO

LOCATED UNDER RAISED FLOOR.

Scale: 3/8" = 1'-0"

BUILDING 5 FIRST FLOOR IRM SERVER ROOM ENLARGED PLAN

N O

R T

H

0 84 16

N O

R T

H

0 21 4

A. REFERENCE SHEET TS101 AND TS102 FOR

EXTERIOR CAMERA LOCATIONS.

B. ALL EXISTING CONDITIONS ARE BASED ON THE

BEST AVAILABLE INFORMATION AT THE TIME

OF SURVEY.

C. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'

OC ABOVE CEILING IN CORRIDORS.

D. ALL CONDUIT SHALL BE 3/4" MINIMUM.

ELECTRICAL CONTRACTOR TO SIZE CONDUIT.

PER THE MOST CURRENT EDITION OF THE NEC.

E. WHERE LENGTH FROM CAMERA TO RACK

EQUIPMENT EXCEEDS 295' (90M) CONTRACTOR

SHALL USE FIBER OPTIC CABLE.

F. COORDINATE AND CONFIRM ALL ROUTING

WITH COR PRIOR TO ROUGH-IN.

G. SEE SHEET G-100 FOR ICRA MEASURES.

H. USE MOBILE CONTAINMENT CART (6/G-100)

ALONG CORRIDORS.

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Docusign Envelope ID: B9B77CD2-F0C1-4BAA-8538-6B315B443E44

7/24/2024

TR ROOM G25:

1 2 3 4

H6 N #101

H6 N #102

H6 N #103

H6 N #104

H6 N #105

N #98

N #99

N #100

H6 N #106

RM 'G25'

RM 'G25'

RM 'G25'

RM 'G25'

RM 'G25'

RM 'G25'

RM 'G25'

RM 'G25'

RM 'G25'

Engineers Architects

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/2

/2

:2

:0

P

M C

U s e rs

\l s ta rn e s \D o c u m e n ts

\E -2

-2

Y

-V A

Y o rk

-V id e o S e c I m p ro v -T

N ls ta rn e s C

B U

M B

.r v t

6.T-101

BULDING 6 GROUND FLOOR SECURITY

PLAN

11 26LAS

VIDEO SURVEILLANCE

SECURITY YORK

ALVIN C. YORK CAMPUS

3400 LEBANON ROAD

MURFREESBORO, TN 37129 JUNE 13, 2024

BID DOCUMENTS

626A4-22-10422-215

JVE

Scale: 1/8" = 1'-0"

BUILDING 6 GROUND FLOOR SECURITY PLAN

1 REMOVE EXISTING CAMERAS AND CABLING

BACK TO SOURCE. REPAIR/REPLACE

EXISTING SURFACES AFFECTED BY

REMOVAL OF CAMERA EQUIPMENT TO

MATCH SIMILAR EXISTING CONDITIONS.

2 INSTALL NEW CAMERAS. PROVIDE NEW 4 PR

UTP CABLING FROM CAMERA TO NEW POE

SWITCH IN TELECOM ROOM. REPAIR/

REPLACE SURFACES AFFECTED BY CAMERA

EQUIPMENT INSTALLATION TO MATCH

SIMILAR/EXISTING CONDITIONS.

CONTRACTOR TO REPLACE DAMAGED

CEILING TILE AND GRID ASSOCIATED WITH

WORK AT NO ADDITIONAL COST TO

GOVERNMENT.

3 PROPOSED LOCATION OF NEW CISCO 9300

SWITCH AND PATCH PANEL. VERIFY

LOCATION WITH COR AND OIT

REPRESENTATIVE.

4 ROUTE MMF FROM TELECOM ROOM TO

RACKS IN BUILDING 5 SERVER ROOM.

NORTH0 4 8 16

A. REFERENCE SHEET TS101 AND TS102 FOR

EXTERIOR CAMERA LOCATIONS.

B. ALL EXISTING CONDITIONS ARE BASED ON THE

BEST AVAILABLE INFORMATION AT THE TIME

OF SURVEY.

C. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'

OC ABOVE CEILING IN CORRIDORS.

D. ALL CONDUIT SHALL BE 3/4" MINIMUM.

ELECTRICAL CONTRACTOR TO SIZE CONDUIT.

PER THE MOST CURRENT EDITION OF THE NEC.

E. WHERE LENGTH FROM CAMERA TO RACK

EQUIPMENT EXCEEDS 295' (90M) CONTRACTOR

SHALL USE FIBER OPTIC CABLE.

F. COORDINATE AND CONFIRM ALL ROUTING

WITH COR PRIOR TO ROUGH-IN.

G. SEE SHEET G-100 FOR ICRA MEASURES.

H. USE MOBILE CONTAINMENT CART (6/G-100)

ALONG CORRIDORS.

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

N #116

H5A DH

N #113

N #115

H6 N #117

H6 N #118

H6 N #119

H6 N #120

H6 N #121

H6 N #122

H6 N #123

H6SL

N

#124H5A FE

RP

#114

FIXED

RV

RM 'G05'

RM '102'

RM '102'

RM '102'

RM '102'

RM '102'

RM '102'

RM '102'

RM '102'

RM '102'

RM '102'

RM '102'

Engineers Architects

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/2

/2

:2

:0

P

M C

U s e rs

\l s ta rn e s \D o c u m e n ts

\E -2

-2

Y

-V A

Y o rk

-V id e o S e c I m p ro v -T

N ls ta rn e s C

B U

M B

.r v t

7.T-101

BULDING 7 GROUND FLOOR SECURITY

PLAN

12 26LAS

VIDEO SURVEILLANCE

SECURITY YORK

ALVIN C. YORK CAMPUS

3400 LEBANON ROAD

MURFREESBORO, TN 37129 JUNE 13, 2024

BID DOCUMENTS

626A4-22-10422-215

JVE

Scale: 1/8" = 1'-0"

BUILDING 7 GROUND FLOOR SECURITY PLAN

1 REMOVE EXISTING CAMERAS AND CABLING

BACK TO SOURCE. REPAIR/REPLACE

EXISTING SURFACES AFFECTED BY

REMOVAL OF CAMERA EQUIPMENT TO

MATCH SIMILAR EXISTING CONDITIONS.

2 INSTALL NEW CAMERAS. PROVIDE NEW 4 PR

UTP CABLING FROM CAMERA TO NEW POE

SWITCH IN TELECOM ROOM. REPAIR/

REPLACE SURFACES AFFECTED BY CAMERA

EQUIPMENT INSTALLATION TO MATCH

SIMILAR/EXISTING CONDITIONS.

CONTRACTOR TO REPLACE DAMAGED

CEILING TILE AND GRID ASSOCIATED WITH

WORK AT NO ADDITIONAL COST TO

GOVERNMENT.

3 ROUTE UTP CABLING UP TO TELECOM ROOM

ABOVE.

N O

R T

H

0 84 16

A. REFERENCE SHEET TS101 AND TS102 FOR

EXTERIOR CAMERA LOCATIONS.

B. ALL EXISTING CONDITIONS ARE BASED ON THE

BEST AVAILABLE INFORMATION AT THE TIME

OF SURVEY.

C. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'

OC ABOVE CEILING IN CORRIDORS.

D. ALL CONDUIT SHALL BE 3/4" MINIMUM.

ELECTRICAL CONTRACTOR TO SIZE CONDUIT.

PER THE MOST CURRENT EDITION OF THE NEC.

E. WHERE LENGTH FROM CAMERA TO RACK

EQUIPMENT EXCEEDS 295' (90M) CONTRACTOR

SHALL USE FIBER OPTIC CABLE.

F. COORDINATE AND CONFIRM ALL ROUTING

WITH COR PRIOR TO ROUGH-IN.

G. SEE SHEET G-100 FOR ICRA MEASURES.

H. USE MOBILE CONTAINMENT CART (6/G-100)

ALONG CORRIDORS.

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

TR ROOM 102:

7 PR SPARE MMF

FIXED

RV

H5A DH

N #125

RM '102'

RM '102'

N #126

FIXED

RV

FIXED

RV

Engineers Architects

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/2

/2

:2

:1

P

M C

U s e rs

\l s ta rn e s \D o c u m e n ts

\E -2

-2

Y

-V A

Y o rk

-V id e o S e c I m p ro v -T

N ls ta rn e s C

B U

M B

.r v t

7.T-102

BULDING 7 FIRST FLOOR SECURITY

PLAN

13 26LAS

VIDEO SURVEILLANCE

SECURITY YORK

ALVIN C. YORK CAMPUS

3400 LEBANON ROAD

MURFREESBORO, TN 37129 JUNE 13, 2024

BID DOCUMENTS

626A4-22-10422-215

JVE

Scale: 1/8" = 1'-0"

BUILDING 7 FIRST FLOOR SECURITY PLAN

1 REMOVE EXISTING CAMERAS AND CABLING

BACK TO SOURCE. REPAIR/REPLACE

EXISTING SURFACES AFFECTED BY

REMOVAL OF CAMERA EQUIPMENT TO

MATCH SIMILAR EXISTING CONDITIONS.

2 INSTALL NEW CAMERAS. PROVIDE NEW 4 PR

UTP CABLING FROM CAMERA TO NEW POE

SWITCH IN TELECOM ROOM. REPAIR/

REPLACE SURFACES AFFECTED BY CAMERA

EQUIPMENT INSTALLATION TO MATCH

SIMILAR/EXISTING CONDITIONS.

CONTRACTOR TO REPLACE DAMAGED

CEILING TILE AND GRID ASSOCIATED WITH

WORK AT NO ADDITIONAL COST TO

GOVERNMENT.

3 PROPOSED LOCATION OF NEW CISCO 9300

SWITCH AND PATCH PANEL. VERIFY

LOCATION WITH COR AND OIT

REPRESENTATIVE.

4 ROUTE MMF FROM TELECOM ROOM TO

RACKS IN BUILDING 5 SERVER ROOM.

N O

R T

H

0 4 8 16

A. REFERENCE SHEET TS101 AND TS102 FOR

EXTERIOR CAMERA LOCATIONS.

B. ALL EXISTING CONDITIONS ARE BASED ON THE

BEST AVAILABLE INFORMATION AT THE TIME

OF SURVEY.

C. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'

OC ABOVE CEILING IN CORRIDORS.

D. ALL CONDUIT SHALL BE 3/4" MINIMUM.

ELECTRICAL CONTRACTOR TO SIZE CONDUIT.

PER THE MOST CURRENT EDITION OF THE NEC.

E. WHERE LENGTH FROM CAMERA TO RACK

EQUIPMENT EXCEEDS 295' (90M) CONTRACTOR

SHALL USE FIBER OPTIC CABLE.

F. COORDINATE AND CONFIRM ALL ROUTING

WITH COR PRIOR TO ROUGH-IN.

G. SEE SHEET G-100 FOR ICRA MEASURES.

H. USE MOBILE CONTAINMENT CART (6/G-100)

ALONG CORRIDORS.

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

22-215YELEC
Sheets
5.T-101 - BUILDING 5 FIRST FLOOR SECURITY PLAN
6.T-101 - BULDING 6 GROUND FLOOR SECURITY PLAN
7.T-101 - BULDING 7 GROUND FLOOR SECURITY PLAN
7.T-102 - BULDING 7 FIRST FLOOR SECURITY PLAN