Atch 17 22-215Y BD Dwgs _Part7.pdf
PDF 2 MB Posted
- Solicitation number
- 36C24926R0064
About this file
This is a set of bid documents for a Video Surveillance Security project at the Alvin C. York Campus in Murfreesboro, Tennessee. The project, identified as VA Project Number 22-215 and ACG Project Number 626A4-22-104, is under the U.S. Department of Veterans Affairs.
The documents contain detailed architectural and engineering plans for Building 117 First Floor Security and Building 120 Security implementations. Work includes installation of new CCTV cameras with associated 4-pair unshielded twisted pair (UTP) cabling routed to new Power over Ethernet (POE) switches in telecom rooms, removal of existing cameras and cabling, and repair or replacement of surfaces damaged during installation. Key technical specifications require 3/4-inch minimum conduit sized per the National Electrical Code, J-hooks spaced maximum 2 feet on center for ceiling-mounted cabling, and fiber optic cable substitution where camera-to-rack distances exceed 295 feet. The contract includes installation of new Cisco 9300 switches and patch panels, multimode fiber (MMF) routing between buildings, and telecommunications outlet installation. Camera models specified include H5A MH, H6A, and H6SL dome cameras with various mounting options. All work must be coordinated with the Contracting Officer's Representative and VA Information Technology department. The documents are fully sprinklered facility specifications dated June 13, 2024, prepared by Apogee Consulting Group, P.A.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N #227
N #228
H6 N #231
N #229
H6SL
N #232
H6SL
N #233
H6SL
N #234
BUILDING 3
BUILDING 117
BUILDING 117
BUILDING 120
BUILDING 2
BUILDING 3 BUILDING 5
BUILDING 117
BUILDING 5
BUILDING 117
B U
IL
D
IN
G
N #230
RM 'G63'
RM 'G63'
RM 'G63'
RM 'G63'
RM 'G63'
RM 'G63'
RM 'G63'
RM 'G63'
RM 'G63'
SW
N #235
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:2
:5
P
M C
U s e rs
\l s ta rn e s \D o c u m e n ts
\E -2
-2
Y
-V A
Y o rk
-V id e o S e c I m p ro v -T
N ls ta rn e s C
B U
M B
.r v t
117.T-102
BUILDING 117 FIRST FLOOR SECURITY
PLAN
22 26LAS
VIDEO SURVEILLANCE
SECURITY YORK
ALVIN C. YORK CAMPUS
3400 LEBANON ROAD
MURFREESBORO, TN 37129 JUNE 13, 2024
BID DOCUMENTS
626A4-22-10422-215
JVE
Scale: 1/8" = 1'-0"
BUILDING 117 FIRST FLOOR SECURITY PLAN
1 ROUTE UTP CABLING DOWN TO TELECOM
ROOM.
2 INSTALL NEW CAMERAS. PROVIDE NEW 4 PR
UTP CABLING FROM CAMERA TO NEW POE
SWITCH IN TELECOM ROOM. REPAIR/
REPLACE SURFACES AFFECTED BY CAMERA
EQUIPMENT INSTALLATION TO MATCH
SIMILAR/EXISTING CONDITIONS.
CONTRACTOR TO REPLACE DAMAGED
CEILING TILE AND GRID ASSOCIATED WITH
WORK AT NO ADDITIONAL COST TO
GOVERNMENT.
A. REFERENCE SHEET TS101 AND TS102 FOR
EXTERIOR CAMERA LOCATIONS.
B. ALL EXISTING CONDITIONS ARE BASED ON THE
BEST AVAILABLE INFORMATION AT THE TIME
OF SURVEY.
C. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'
OC ABOVE CEILING IN CORRIDORS.
D. ALL CONDUIT SHALL BE 3/4" MINIMUM.
ELECTRICAL CONTRACTOR TO SIZE CONDUIT.
PER THE MOST CURRENT EDITION OF THE NEC.
E. WHERE LENGTH FROM CAMERA TO RACK
EQUIPMENT EXCEEDS 295' (90M) CONTRACTOR
SHALL USE FIBER OPTIC CABLE.
F. COORDINATE AND CONFIRM ALL ROUTING
WITH COR PRIOR TO ROUGH-IN.
G. SEE SHEET G-100 FOR ICRA MEASURES.
H. USE MOBILE CONTAINMENT CART (6/G-100)
ALONG CORRIDORS.
N O
R T
H
0 84 16
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Docusign Envelope ID: B9B77CD2-F0C1-4BAA-8538-6B315B443E44
7/24/2024
ROOM G02:
4 PR SPARE MMF
1 2 3
BUILDING 117
BUILDING 120
B U
IL
D
IN
G
B U
IL
D
IN
G
BUILDING 1
H6 N
#238RM 'G02'
H6 N #239
N #237
RM 'G02'RM 'G02'
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:2
:0
P
M C
U s e rs
\l s ta rn e s \D o c u m e n ts
\E -2
-2
Y
-V A
Y o rk
-V id e o S e c I m p ro v -T
N ls ta rn e s C
B U
M B
.r v t
120.T-101
BUILDING 120 SECURITY PLANS
23 26LAS
VIDEO SURVEILLANCE
SECURITY YORK
ALVIN C. YORK CAMPUS
3400 LEBANON ROAD
MURFREESBORO, TN 37129 JUNE 13, 2024
BID DOCUMENTS
626A4-22-10422-215
JVE
Scale: 1/8" = 1'-0"
BUILDING 120 GROUND FLOOR SECURITY PLAN
1 REMOVE EXISTING CAMERAS AND CABLING
BACK TO SOURCE.
2 INSTALL NEW CAMERAS. PROVIDE NEW 4 PR
UTP CABLING FROM CAMERA TO NEW POE
SWITCH IN TELECOM ROOM.
3 PROPOSED LOCATION OF NEW CISCO 9300
SWITCH AND PATCH PANEL. VERIFY
LOCATION WITH COR AND OIT
REPRESENTATIVE.
4 ROUTE MMF FROM TELECOM ROOM TO
RACKS IN BUILDING 5 SERVER ROOM.
N O
R T
H
0 4 8 16
A. REFERENCE SHEET TS101 AND TS102 FOR
EXTERIOR CAMERA LOCATIONS.
B. ALL EXISTING CONDITIONS ARE BASED ON THE
BEST AVAILABLE INFORMATION AT THE TIME
OF SURVEY.
C. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'
OC ABOVE CEILING IN CORRIDORS.
D. ALL CONDUIT SHALL BE 3/4" MINIMUM.
ELECTRICAL CONTRACTOR TO SIZE CONDUIT.
PER THE MOST CURRENT EDITION OF THE NEC.
E. WHERE LENGTH FROM CAMERA TO RACK
EQUIPMENT EXCEEDS 295' (90M) CONTRACTOR
SHALL USE FIBER OPTIC CABLE.
F. COORDINATE AND CONFIRM ALL ROUTING
WITH COR PRIOR TO ROUGH-IN.
G. SEE SHEET G-100 FOR ICRA MEASURES.
H. USE MOBILE CONTAINMENT CART (6/G-100)
ALONG CORRIDORS.
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX
DIAM OF CIRCULAR THROUGH OPENING IS 32-1/2 IN. (826 MM).
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
1A. STEEL SLEEVE (OPTIONAL, NOT SHOWN) - NOM 12 IN. (305 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL PIPE SLEEVE CAST INTO CONCRETE FLOOR OR WALL. SLEEVE TO BE FLUSH WITH OR PROJECT MAX 2 IN.
(51MM) FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL.
2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN. (0 MM)(POINT CONTACT) TO MAX 1-3/8 IN. (35 MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF
METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
A1. IRON PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
B. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) RIGID STEEL CONDUIT.
C. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING.
3. PACKING MATERIAL - POLYETHYLENE BACKER ROD OR NOM 1 IN. (25 MM) THICKNESS OF TIGHTLY-PACKED CERAMIC (ALUMINA SILICA) FIBER BLANKET, MINERAL WOOL BATT OR GLASS FIBER INSULATION MATERIAL USED AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF SOLID CONCRETE OR CONCRETE BLOCK WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF CAULK FILL MATERIAL (ITEM 4). AS AN ALTERNATE WHEN MAX PIPE SIZE IS 10 IN. (254 MM) DIAM AND WHEN MAX ANNULAR SPACE IS 1 IN. (25 MM), A MIN 1 IN. (25 MM) THICKNESS OF TIGHTLY-PACKED CERAMIC FIBER BLANKET OR MINERAL WOOL BATT PACKING MATERIAL MAY BE RECESSED MIN 1/2 IN. (13 MM) FROM BOTTOM SURFACE OF FLOOR
OR FROM EITHER SIDE OF SOLID CONCRETE WALL.
4. FILL,VOID OR CAVITY MATERIALS* - CAULK OR SEALANT - APPLIED TO FILL THE ANNULAR SPACE TO THE MIN
THICKNESS SHOWN IN THE FOLLOWING TABLE:
(A) BR = POLYETHYLENE BACKER ROD.
CF = CERAMIC FIBER BLANKET.
GF = GLASS FIBER INSULATION.
MW = MINERAL-WOOL BATT.
(B) CAULK INSTALLED FLUSH WITH TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL.
(C) CAULK INSTALLED FLUSH WITH BOTTOM SURFACE OF FLOOR OR ONE SURFACE OF SOLID (NON- CONCRETE
BLOCK) WALL.
3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT.
(NOTE: W RATING APPLIES ONLY WHEN FB-3000 WT SEALANT IS USED.)
*BEARING THE UL CLASSIFICATION MARKING
MAX PIPE DIAM
IN. (MM)
10 (254)
10 (254)
30 (762)
MAX ANNULAR
SPACE IN. (MM)
1 (25)
1 (25)
2-1/2 (64)
PACKING MATL
TYPE (a)
BR, CF, GF OR MW
CF OR MW
BR, CF, GF OR MW
MIN. CAULK THKNS
IN. (MM)
1/2 (13) (b)
1/2 (13) (c)
1 (25) (b)
System No. C-AJ-1001 June 15, 2005 F Rating - 3 Hr T Rating - 0 Hr
W Rating - Class I (See Item 4)
SECTION A-A
4 4 1
A
A
1. FLOOR OR WALL ASSEMBLY - LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE. EXCEPT AS NOTED IN TABLE UNDER ITEM 4, MIN THICKNESS OF SOLID CONCRETE FLOOR OR WALL ASSEMBLY IS 4-1/2 IN. (114 MM). FLOOR MAY ALSO BE CONSTRUCTED OF ANY MIN 6 IN. (152 MM) THICK UL CLASSIFIED HOLLOW CORE PRECAST CONCRETE UNITS*. WHEN FLOOR IS CONSTRUCTED OF HOLLOW CORE PRECAST CONCRETE UNITS, PACKING MATERIAL (ITEM 3) AND CAULK FILL MATERIAL (ITEM 4) TO BE INSTALLED SYMMETRICALLY ON BOTH SIDES OF FLOOR, FLUSH WITH FLOOR SURFACE. WALL ASSEMBLY MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS IN SOLID LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE. FLOOR IS 32 IN. (813 MM).
MAX DIAM OF OPENING IN FLOOR CONSTRUCTED OF HOLLOW-CORE PRECAST CONCRETE UNITS IS 7 IN. (178 MM).
SEE CONCRETE BLOCKS (CAZT) AND PRECAST CONCRETE UNITS (CFTV) CATEGORIES IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF
MANUFACTURERS.
1A. STEEL SLEEVE (OPTIONAL, NOT SHOWN) - MAX 15 IN. (381 MM) ID (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY. SLEEVE MAY EXTEND A MAX OF 2 IN. (51 MM) ABOVE TOP OF FLOOR OR BEYOND EITHER SURFACE OF WALL. MAX 16 IN. (406 MM) ID (OR SMALLER) MIN 0.028 (0.71 MM) WALL THICKNESS (OR HEAVIER) GALVANIZED STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY. SLEEVE MAY EXTEND A MAX OF 1/2 IN. (13 MM) BEYOND EITHER SURFACE OF FLOOR OR
WALL.
2. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. MAX ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND EDGE OF THROUGH OPENING OR SLEEVE IS DEPENDENT ON THE PARAMETERS SHOWN IN ITEM 4. MIN ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH OPENING IS 0 IN. (0 MM) (POINT CONTACT). PIPE CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE
FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE - NOM 30 IN. (762 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) RIGID STEEL CONDUIT.
D. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING.
E. COPPER - TUBING NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBE.
F. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
3. PACKING MATERIAL - POLYETHYLENE BACKER ROD OR NOM 1 IN. (25 MM) THICKNESS OF TIGHTLY-PACKED MINERAL WOOL BATT OR GLASS FIBER INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF CAULK FILL MATERIAL (ITEM 4).
4. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - APPLIED TO FILL THE ANNULAR SPACE FLUSH WITH TOP SURFACE OF FLOOR. IN WALL ASSEMBLIES, REQUIRED CAULK THICKNESS TO BE INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL, FLUSH WITH WALL SURFACE.
AT POINT CONTACT LOCATION BETWEEN PENETRANT AND SLEEVE OR BETWEEN PENETRANT AND CONCRETE, A MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK SHALL BE APPLIED AT TOP SURFACE OF FLOOR AND AT BOTH SURFACES OF WALL. THE HOURLY F RATINGS AND THE MIN REQUIRED CAULK THICKNESSES ARE DEPENDENT UPON A NUMBER OF PARAMETERS, AS SHOWN IN THE FOLLOWING TABLE:
(A)MIN 2 IN. (51 MM) THICKNESS OF MINERAL WOOL BATT INSULATION REQUIRED IN ANNULAR SPACE.
(B)MIN 1 IN. (25 MM) THICKNESS OF MINERAL WOOL BATT INSULATION REQUIRED IN ANNULAR SPACE ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. MIN 1 IN. (25 MM) THICKNESS OF CAULK TO BE INSTALLED FLUSH WITH EACH SURFACE OF FLOOR OR WALL ASSEMBLY.
3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT. (NOTE: W RATING APPLIES ONLY WHEN FB-3000 WT SEALANT IS USED.)
*BEARING THE UL CLASSIFICATION MARKING
MIN FLOOR OR
WALL THKNS IN.
(MM)
2-1/2 (64)
2-1/2 (64)
4-1/2 (114)
NOM PIPE TUBE OR
CONDUIT DIAM IN.
(MM)
1/2-12 (13-305)
1/2-12 (13-305)
1/2-6 (13-152)
MAX
ANNULAR
SPACE IN.
(MM)
1-3/8 (35)
3-1/4 (83)
MIN. CAULK
THKNS IN.
(MM)
1/2 (13)
1 (25)
1/4 (6) (a)
System No. C-AJ-1044 June 15, 2005
F Ratings - 2, 3, and 4 Hr (See Items 2A and 4) T Rating - 0 Hr
L Rating At Ambient - 2 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft
W Rating - Class I (See Item 4)
SECTION A-A
A
A
F
RATING
HR
1-3/8 (35)
1/2 (13)
1 (25)
1 (25)
1 (25)
2 (51)
1 (25) (b)1-3/8 (35)
3-1/4 (83)
2 (51)
2 (51)
2 (51)
1-1/4 (32)1/2-12 (13-305)
1/2-12 (13-305)
22-30 (558-762)
1/2-20 (13-508)
1/2-6 (13-152)
1/2-20 (13-508)
4-1/2 (114)
4-1/2 (114)
4-1/2 (114)
4-1/2 (114)
4-1/2 (114)
5-1/2 (140)
1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC WITH NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM)
WIDE BY 1-3/8 IN. (35 MM) DEEP CHANNELS SPACED MAX 24 IN. (610 MM) OC.
B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF
OPENING IS 26 IN. (660 MM).
2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN. (0 MM) (POINT CONTACT) TO MAX 2 IN. (51 MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN.
(305 MM) DIAM (OR SMALLER) OR CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE.
C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL
ELECTRICAL METALLIC TUBING
D. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING
E. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
F. THROUGH PENETRATING PRODUCT* - FLEXIBLE METAL PIPING - THE FOLLOWING TYPES OF STEEL FLEXIBLE METAL GAS
PIPING MAY BE USED:
1. NOM 2 IN. (51 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
OMEGA FLEX INC
2. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
TITEFLEX CORP
A BUNDY CO
3. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
WARD MFG INC
3. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. 1-1/4,1-7/8 AND 2-1/2 IN. (16, 32, 48 AND 64 MM) THICKNESS OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES, RESPECTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT CONTACT
LOCATION ON BOTH SIDES OF WALL.
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN
WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE.
THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW:
+WHEN COPPER PIPE IS USED, T RATING IS 0 HR.
3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT,
*BEARING THE UL CLASSIFICATION MARKING
SYSTEM NO.W-L-1001
JUNE 15, 2005
F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3)
T RATINGS - 0, 1, 2, 3, AND 4 HR (SEE ITEM 3)
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT
MAX PIPE OR
CONDUIT DIAM
IN. (mm)
1 (25)
1 (25)
4 (102)
6 (152)
12 (305)
F RATING
HR
1 OR 2
3 OR 4
1 OR 2
3 OR 4
1 OR 2
T RATING
HR
0+, 1 OR 2
3 OR 4
SECTION A-A
1B
1A
3A
A
NOTES:
1. J-HOOKS TO BE LOCATED MAX 5' APART.
2. 1' MAX.
FINISHED FLOOR
MOUNT AT HEIGHT
EQUIVALENT TO ADJACENT
POWER, NOMINALLY 18" AFF
4-11/16" SQ. BY 2-1/2"
DEEP BOX WITH SINGLE
GANG 5/8" TILE RING.
1-1/4" CONDUIT WITH
COMMUNICATIONS WIRING
WALL
CORRIDORROOM
6" MIN NYLON BUSHING
COORDINATE WITH DUCTWORK
EXTEND CONDUIT TO ABOVE
FINISHED ACCESSABLE
CEILING IN CORRIDOR TO
CABLE TRAY UNLESS NOTED
OTHERWISE.
SUSPENDED LAY-IN CEILING
CABLE TRAY
GROUND CONDUIT TO
CABLE TRAY
DETAIL NOTES:
A. ALL EQUIPMENT AND INSTALLATION SHALL BE APPROVED BY VAMC
IT DEPARTMENT.
(1) 4 PR UTP
DATA
CABLE/JACK
(1) 4 PR UTP
TELEPHONE
CABLE/JACK
1/2" HIGH BLACK LETTERS
ON CLEAR BACKGROUND,
PANDUIT OR EQUAL ON
PERMANENT LABEL,
TYPICAL.
XXX
XXX
B B
T T
BLANK
SINGLE GANG COVER
PLATE WITH 6 OUTLETS
(TYPICAL). LOCATIONS
AS SHOWN ON PLANS
TELE/DATA (TYP.) ( 4)
(1) 4 PR UTP
TELEPHONE
CABLE/JACK
C C
(1) 4 PR UTP
DATA CABLE/JACK
BLANK
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:2
:0
P
M C
U s e rs
\l s ta rn e s \D o c u m e n ts
\E -2
-2
Y
-V A
Y o rk
-V id e o S e c I m p ro v -T
N ls ta rn e s C
B U
M B
.r v t
T-501
TECHNOLOGY DETAILS
24 26LAS
VIDEO SURVEILLANCE
SECURITY YORK
ALVIN C. YORK CAMPUS
3400 LEBANON ROAD
MURFREESBORO, TN 37129 JUNE 13, 2024
BID DOCUMENTS
626A4-22-10422-215
JVE
Scale: No Scale
UL PENETRATION DETAIL C-AJ-1001
Scale: No Scale
UL PENETRATION DETAIL C-AJ-1044
Scale: No Scale
UL PENETRATION DETAIL W-L-1001
Scale: No Scale
J-HOOK DETAIL
Scale: No Scale
TELECOMMUNICATIONS OUTLET INSTALLATION DETAIL
Scale: No Scale
TELECOMMUNICATIONS FACEPLATES
/8
/8
4 1/2"
/4
1 3/4"
/8
/4
3 3/8"
1 3/4"
/8
2 1/2"
/4
/8
/2
2 3/8" 5 3/4"
SURFACE MOUNT
IN CEILING
PENDANT MOUNT
D=7 1/8"
5 1/8"
P13 DOME - OUTDOOR SURFACE MOUNT ADAPTER
D=6 1/8"
4 1/2" 2 1/2"
/2
H6SL DOME - SURFACE MOUNT ADPATER
SURFACE MOUNT
IN CEILING
PENDANT MOUNT
10 1/4"
/8
/2
/8
/4
7 3/4"
/4
/8
/4
7 7/8"
PENDANT ARM
1'-3 1/4"
/2
/8
/4
3 7/8"
D=11 3/4"
8 7/8"
/2
/8
7 7/8"
/4
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:2
:0
P
M C
U s e rs
\l s ta rn e s \D o c u m e n ts
\E -2
-2
Y
-V A
Y o rk
-V id e o S e c I m p ro v -T
N ls ta rn e s C
B U
M B
.r v t
T-502
TECHNOLOGY DETAILS
25 26LAS
VIDEO SURVEILLANCE
SECURITY YORK
ALVIN C. YORK CAMPUS
3400 LEBANON ROAD
MURFREESBORO, TN 37129 JUNE 13, 2024
BID DOCUMENTS
626A4-22-10422-215
JVE
Scale: N.T.S.
CAMERA H5A MH - DIMENSIONS - BASIS OF DESIGN
Scale: N.T.S.
CAMERA H6A - DIMENSIONS - BASIS OF DESIGN
Scale: N.T.S.
CAMERA H6SL - DIMENSIONS - BASIS OF DESIGN
Scale: N.T.S.
CAMERA H5A MH - ISOMETRIC - BASIS OF DESIGN
Scale: N.T.S.
CAMERA H5A MH - DIMENSIONS - BASIS OF DESIGN
| 22-215YELEC |
| Sheets |
| 117.T-102 - BUILDING 117 FIRST FLOOR SECURITY PLAN |
| 120.T-101 - BUILDING 120 SECURITY PLANS |
| T-501 - TECHNOLOGY DETAILS |
| T-502 - TECHNOLOGY DETAILS |
File details come from the government source that posted it. Updated .