332110_Water_Supply_Wells.pdf

PDF 25 KB Posted

Attached to
RECOVERY - Lost Lake Campground - Grand Mesa, Uncompahgre and Gunnison NFs
Solicitation number
AG-82B1-S-09-0057
Issued by

About this file

docs

View the file

Other files

File Type Posted
331111-Water_Supply_Design_Construction.pdf PDF
311000_Clearing_Grubbing_REV Amd 2.doc DOC document
WS Demo - Aframe tank 1.JPG JPG image
033000_Cast-in-place_concrete.pdf PDF
U9_WELL-DETAILS.pdf PDF
Optional Bid Item 12 Amend 2.doc DOC document
WS Demo - culvert.JPG JPG image
U1-UTIL-PLAN.pdf PDF
U4_UTILITY-DETAILS.pdf PDF
Revised Schedule of Items Amend 2.xls XLS spreadsheet
312316_Struct_Excavation_Backfill.pdf PDF
LOST_LAKE_CG_WS_SPEC_INDEX.pdf PDF
U6_TREATMENT-BLDG-PLAN.pdf PDF
017700_closeout_procedures.pdf PDF
WS Demo - Aframe tank 2.JPG JPG image
013300_submittal_procedures.pdf PDF
331219-Water-hydrant.pdf PDF
011100_summary_of_work.pdf PDF
016400_government_furnished_mats.pdf PDF
T1_TITLE_SHEET.pdf PDF
011100_summary_of_work_REV09_03_09.pdf PDF
311100_Clearing_Grubbing.pdf PDF
T1_TITLE_SHEET-SIGNATURES.pdf PDF
WS Demo - Spring and piping.JPG JPG image
U8_TYP_SPUR_UTIL_DET.pdf PDF
011419_use_of_site.pdf PDF
331116-Water-distribution.pdf PDF
U7_TREATMENT-BLDG-PLUMBING.pdf PDF
U5-HYDRANT-DETAILS.pdf PDF
U2-UTIL-PLAN-PROFILE.pdf PDF
SF 30 AMEND 2.PDF PDF
017419_constr_waste_management_disposal.pdf PDF
312317_Trenching_Utilities.pdf PDF
012200_definition_bid_items_REV09_03_09.pdf PDF
100perc_FINAL_Lost_Lake_CG_Spec_Index_REV09_03_09.pdf PDF
012200_definition_bid_items.pdf PDF
wage determination.txt TXT text file
024113_selective_site_demolition.pdf PDF
U3-UTIL-PLAN-PROFILE.pdf PDF
Amendment 001 to Solicitation AG.doc DOC document
Amendment 001 —
AG-82B1-S-09-0057.pdf PDF
sf 1442.pdf PDF
lost-lake-dwgs.pdf PDF
sf24_f.pdf PDF
lost-lake-specs.pdf PDF
wage determination.txt TXT text file
Show all 47

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LOST LAKE CAMPGROUND 332110 - 1

WATER SYSTEM WATER SUPPLY WELLS

SECTION 332110

WATER SUPPLY WELLS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplemen-tary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Related Sections include the following:

1. Division 33 Section "Water Distribution" for water-service.

1.3 DEFINITIONS

A. The following are industry abbreviations for plastic materials:

1. ABS: Acrylonitrile-butadiene-styrene plastic.

2. PA: Polyamide (nylon) plastic.

3. PE: Polyethylene plastic.

4. PP: Polypropylene plastic.

5. PVC: Polyvinyl chloride plastic.

1.4 SUBMITTALS

A. Product Data: Submit certified performance curves and rated capacities of selected well pumps and furnished specialties for each type and size of well pump indicated.

B. Shop Drawings: Show layout and connections for well pumps.

1. Wiring Diagrams: Power, signal, and control wiring.

a. Setting Drawings: Include templates and directions for installing founda-tion

C. Operation and Maintenance Data: For each well pump to include in emergency, op-eration, and maintenance manuals.

1.5 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: UL Listed and labeled.

B. AWWA Compliance: Comply with AWWA A100 for water supply wells.

LOST LAKE CAMPGROUND 332110 - 2

PART 2 - PRODUCTS

2.1 WELL CASING FITTINGS

A. Pitless Adapter: Fitting, of shape required to fit onto casing, with waterproof seals.

B. Pitless Unit: Factory-assembled equipment that includes pitless adapter.

C. Well Seals: Casing cap, with screened vent and holes for piping and cables, that fits into top of casing and is lockable, removable, waterproof, and vermin proof.

2.2 DISINFECTANT

A. Chlorine or chlorine compounds shall be used. The disinfectant shall be delivered to the jobsite in original closed containers bearing the original label indicating the per-centage of available chlorine.

B. Dry disinfectants used in the preparation of solutions shall not be outdated, shall be full strength, and shall be prepared to the required concentration in accordance with the manufacturer’s directions for mixing.

2.3 GROUT

A. Cement: ASTM C 150, Type II.

B. Aggregates: ASTM C 33, fine and coarse grades.

C. Water: Potable.

PART 3 - EXECUTION

3.1 CONNECTIONS

A. Drawings indicate general arrangement of piping, fittings, and specialties.

1. Install pitless adapter.

2. Connect piping between well pump and water piping.

3. Connect water distribution system in trench to well pipe at pitless adapter.

4. Connect building water distribution to well pipe inside well house.

B. Ground equipment according to Division 26 Section "Grounding and Bonding."

3.2 WELL DISINFECTION

A. Before disinfecting the well, all components of the well shall be cleaned of all foreign substances such as cement, oil, grease, joint dope, and scum. The well must have al-ready been developed. The system must have operated long enough to flush out all turbid water.

LOST LAKE CAMPGROUND 332110 - 3

B. Disinfection shall comply with National Ground Water Association’s “Manual of Wa-ter Well Construction Practices” using the EPA requirement for minimum concentra-tion of 100 ppm available chlorine.

C. A chlorine solution of the appropriate concentration to disinfect the well shall be pre-pared on the surface in containers having an aggregate volume equal to or at least twice the volume of water capable of being held in the well casing and well screen.

The solution shall then be rapidly discharged into the well so as to thoroughly flush that portion of the casing that is above the static water level. The disinfecting agent shall be left in the well a minimum of 24 hrs.

D. The quantity of chlorine compounds used for disinfection shall be sufficient to pro-duce a minimum of 100 ppm (parts per million) available chlorine in solution when mixed with the total volume of water in the well. A 100 ppm solution should result from utilizing quantities of chlorine compounds, proportion to the depth of water, as listed in the table below.

TABLE 2.3 CHLORINE COMPOUND REQUIRED TO DOSE 100 FEET

OF WATER-FILLED WELL AT 100 PPM

Casing Di-ameter

(Inches

Measure)

Volume

100 Feet

(Gallons)

70% HTH

Perchloron, ect

(Dry Weight)*

Per 100 Feet

Chlorine Compounds

25% Chloride of Lime

(Dry Weight)*

Per 100 Feet

5.25% Purex Chlo-rox

(Liquid)

Per 100 Feet

2 16.3 1/2 ounce 1 ounce 4 ounce

4 65.3 2 ounce 4 ounce 18 ounce

6 146.9 4 ounce 8 ounce 40 ounce

8 261.1 6 ounce 14 ounce 4-1/4pints

10 408.0 8 ounce 22 ounce 7 pints

12 587.5 12 ounce 2 pounds 10 pints

14 1,044.5 20 ounce 3 1/2 pounds 2 gallons

16 1,632.0 2 pounds 6 pounds 3-1/2 gallons

20 2,350.1 3 pounds 8 pounds 4-2/3 gallons

Note: Liquid sodium hypochlorite in a 12 percent solution is often sold for water and wastewater treatment plant use, as commercial bleach, or for use with swimming pools. Utilizing a solution of this nature would call for a liquid measure equal to one-half the volumes presented in Column

5.

* - Where a dry chemical is used, it should be mixed with water to form a chlorine solution prior to placing it into the well. This applies to all wells except flowing artesian wells.

E. Follow water supply well disinfection procedures required by authorities having juris-diction before testing well pumps.

LOST LAKE CAMPGROUND 332110 - 4

F. Clean tested and developed water supply wells of foreign substances. Swab casings using alkalis, if necessary, to remove foreign substances.

3.3 PROTECTION

1. Water Quality Protection: Prevent well contamination, including undesirable physical and chemical characteristics.

3.4 FIELD QUALITY CONTROL

A. Water Analysis Testing: Engage a qualified testing agency to perform bacteriological analyses of water from each finished well and report the results. Make analyses ac-cording to requirements of authorities having jurisdiction.

B. Start well pump, fill storage tank and adjust controls and pressure setting. Replace damaged and malfunctioning controls and equipment.

END OF SECTION 332110