6. M0.01 - Mechanical Schedules & Details - 12.24.24.pdf

PDF 234 KB Posted

Attached to
ITB-2425-111 Rex Putnam High School Chiller Replacement Project
Solicitation number
S-P03012-00012402
Issued by
Clackamas County, Oregon

About this file

This mechanical drawing sheet from Rex Putnam High School in North Clackamas School District details specifications for a chiller replacement project, including mechanical schedules, pump details, and control diagrams. The document includes detailed specifications for a new Trane Ascent Air Cooled Chiller (Model ACR) with 298.5 tons capacity, three pumps (CHWP-1, HWP-1, and HWP-2), and associated mechanical systems. The drawings show mechanical legends, symbols, pump details, and control diagrams for chilled water and heating water systems.

The specifications call for specific equipment including a Bell & Gossett base-mounted centrifugal pump for the chilled water system (CHWP-1) rated at 700 GPM and 85 ft head pressure, and two heating water pumps (HWP-1 and HWP-2) rated at 680 GPM and 340 GPM respectively. All equipment must meet the 2021 Oregon Energy Efficiency Specialty Code requirements. The chiller specifications include single-point power connection, factory-powered GFCI convenience outlet, and detailed electrical requirements (460V/3PH, 496.0 MCA, 600.0 MOCP). The document includes specific installation requirements such as 4-inch housekeeping pads for certain pumps and detailed control diagrams for system operation.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2" ROUND PIPE DIAMETER, INCHES

REMOVE EXISTING

RELOCATE EXISTING

CAP OR PLUG

LOCATE IN JOIST SPACE

EXISTING TO REMAIN

CONNECT TO EXISTING

ABANDON

SYMBOLS

ABBREVIATIONS

I/O - INPUT OR OUTPUT

A/D - ANALOG OR DIGITAL

D

I

CONTROL DIAGRAM SYMBOLS

R RELAY

A

C

E

J

P

R

X

CHILLED WATER PUMP CONTROL DIAGRAM

CHWR

CHWS

Ct

VFD

CHWP-1

CAP OR PLUG

DV

HOSE END DRAIN VALVE

CHECK VALVE

BALL VALVE

BALANCING FITTING (CIRCUIT SETTER)

PRESSURE REDUCING VALVE

THERMOMETER

PRV

UNION

BAL

P

PRESSURE GAUGE W/ VALVE

X PIPE ANCHOR

EXPANSION JOINT

HWR

HWS

HEATING WATER RETURN

HEATING WATER SUPPLY

CHWR

CHWS

CHILLED WATER RETURN

CHILLED WATER SUPPLY

PRESSURE / TEMPERATURE TAP

TRIPLE DUTY VALVE (SPRING CHECK, SHUT-OFF, BALANCE)TDV

M

M0.1

FROM CHILLER

TO CHILLER

TO CHW / HHW SYSTEM

POINT

DI

DO

CONTROL FUNCTION

CHWP-1 PUMP ON/OFF

CHWP-1 STATUS

MOTOR STARTER

VARIABLE FREQUENCY DRIVE

CURRENT TRANSFORMER

DAMPER ACTUATOR MOTOR

CONTROL VALVE

DIAGRAMMATIC

AIR COOLED CHILLER CONTROL DIAGRAM4

M0.1

DIAGRAMMATIC

MECHANICAL LEGEND

GATE VALVE

FLEXIBLE CONNECTION

CHECK VALVE

B&G CIRCUIT SETTER

(FLOW INDICATING VALE)

ISOLATION VALVE

M0.1

SUCTION DIFFUSER

PETE'S PLUG

(TYP.)

SHUT OFF COCK

SPRING HANGER(TYP.)

PRESSURE

GAUGE

SUCTION DIFFUSER

BASE MOUNTED PUMP DETAIL

3-WAY CONTROL VALVE

INLINE MOUNTED PUMP DETAIL

PRESSURE

GAUGE

ISOLATION

VALVE

PETE'S

PLUG

VOLUTE CASING

PRESSURE

GAUGE

ISOLATION

VALVE

SUCTION DISCHARGE

MOTOR

PETE'S

PLUG

HEATING WATER SUPPLY (DEMO)

HEATING WATER RETURN (DEMO)

CHILLED WATER SUPPLY (DEMO)

CHILLED WATER RETURN (DEMO)

M0.1

FS FLOW SENSOR

MOTORIZED DAMPER OR VALVE ACTUATOR

POINT OF CONNECTION

PUMP SCHEDULE

EQUIPMENT

TAG

EQUIPMENT SERVED

BASIS OF DESIGN

ELECTRICAL

REVOLUTIONS /

MINUTE

FLOWRATE

HEAD

PRESSURE

PHYSICAL

NOTES

VOLTAGE

POWER (EA.) FLA (EA.)

MCA

CONNECTION SIZE

LENGTH WIDTH HEIGHT WEIGHT

MAKE MODEL RPM GPM FT

SUCTION DISCHARGE

V HP A A INCH INCH INCH INCH INCH LBS

CHWP-1

CHILLED WATER SYSTEM (P-13)

BELL & GOSSETT

BG-E1510

460/3PH 20 23.20 30.0 1731 700 85 5 4 48.38 20.62 23.75 602

1—3, 5

HWP-1 HEATING HOT WATER SYSTEM (P-12)

BELL & GOSSETT

BG-E1510

460/3PH 10 11.34 15.0 1754 680 45 5 4 39.25 19.18 20.75 418

1—3, 5

HWP-2 HEATING HOT WATER SYSTEM (SMALL PUMP)

BELL & GOSSETT

BGE80S

460/3PH 7.5 9.55 15.0 1682 340 45 4 4 25 14.45 36.38 480

1, 2, 4

NOTES:

1) ENERGY EFFICIENCY REQUIREMENTS MUST MEET MINIMUM EFFICIENCY REQUIREMENTS; 2021 OREGON ENERGY EFFICIENCY SPECIALTY CODE.

2) PUMP MOTOR TO HAVE VARIABLE FREQUENCY DRIVE

3) BASE MOUNTED CENTRIFUGAL PUMP

4) INLINE CENTRIFUGAL PUMP

5) PROVIDE ON 4" HOUSEKEEPING PAD

NEW 4"

HOUSEKEEPING

PAD OR INERTIA

BASE

FROM CHW / HHW SYSTEM

FS

HEATING WATER PUMP CONTROL DIAGRAM

HWS

Ct

VFD

HWP-2

M0.1

FROM BOILER

DIAGRAMMATIC

CHW FLOW AI

POINT

DI

DO

CONTROL FUNCTION

HWP-1 ON/OFF

HWP-1 STATUS

DI

HWP-1

FROM BOILER

TO HHW SYSTEM

FS

HWS

Ct

VFD

DO

AI

HWP-2 ON/OFF

HWP-2 STATUS

HHW FLOW

CHILLER SCHEDULE

EQUIPMENT

TAG

AREA SERVED

BASIS OF DESIGN COOLING DATA ELECTRICAL

PRESSURE

DROP

PHYSICAL

NOTES

MAKE MODEL

CAPACITY

@ OAT

DESIGN

FLOWRATE

IPLV EER

COMPRESSOR DATA OVERALL DATA

FT H2O

LENGTH WIDTH HEIGHT WEIGHT

REFRIGERANT

QTY. CKT. A CKT. B VOLT MCA MOCP

TONS °F GPM # LBS LBS V A A INCH INCH INCH LBS

CH-1

CHILLED WATER

SYSTEM

TRANE

ASCENT AIR COOLED CHILLER

MODEL ACR

298.5 95 713 21.6 11.6 R-134A 2 325 325 460/3PH 496.0 600.0 13.8 440.0 87.8 98.4

18,800 1,2,3

NOTES:

1) SINGLE-POINT POWER CONNECTION.

2) FACTORY-POWERED GFCI CONVENIENCE OUTLET. OUTLET SHALL BE POWERED PRIOR TO UNIT ELECTRICAL DISCONNECT. OUTLET SHALL BE FACTORY WIRED AND CONNECTED TO MAIN FEED WITH INTEGRAL TRANSFORMER.

3) MUST MEET ENERGY EFFICIENCY REQUIREMENTS OF 2021 OREGON ENERGY EFFICIENCY SPECIALTY CODE.

M0.1

JF

MECHANICAL

SCHEDULES &

DETAILS

REVISIONS:

ISSUE DATE:

SDC JOB #:

DESIGNED BY:

CHECKED BY:

DRAWN BY:

SET TYPE:

R

EX

P U

TN

A

M H

IG

H

S C

H O

O L

C H

IL

LE

R R

EP

LA

C

EM

EN

T

N O

R

TH

C

LA

C K

A M

A S

SC

H

O O

L D

IS

T.

S E

R O

ET

H

E R

D M

IL

W

A U

K

IE

, O R

EG

O

N

SYSTEM DESIGN CONSULTANTS INC.

333 SE SECOND AVE

SUITE 100

PORTLAND OR

97214

503-248-0227

NCS2401

12/24/2024

59898

OREGON

EXPIRES: 12/31/25

PROFESS I ONAL

DERETSIGER

NEERIGNE

9, 2 0 0 2

YLUJ

D. F A R L E Y

NHOJ

NB

NB

AutoCAD SHX Text D

AutoCAD SHX Text O

AutoCAD SHX Text D

AutoCAD SHX Text I

AutoCAD SHX Text M

AutoCAD SHX Text Ct

AutoCAD SHX Text

VFD

AutoCAD SHX Text Ms

AutoCAD SHX Text

POINT

AutoCAD SHX Text

CONTROL FUNCTION

AutoCAD SHX Text

CHILLER ALARM

AutoCAD SHX Text

DI

AutoCAD SHX Text

CHILLER STATUS

AutoCAD SHX Text

DI

AutoCAD SHX Text

CHILLER START / STOP

AutoCAD SHX Text

DO

AutoCAD SHX Text D

AutoCAD SHX Text O

AutoCAD SHX Text D

AutoCAD SHX Text I

AutoCAD SHX Text

CHILLER CONTROL PANEL

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text

OUTSIDE AIR TEMP SENSOR

AutoCAD SHX Text T

AutoCAD SHX Text

OUTSIDE AIR TEMP

AutoCAD SHX Text

AI

AutoCAD SHX Text D

AutoCAD SHX Text I

AutoCAD SHX Text

DIAGRAMMATIC

AutoCAD SHX Text

DIAGRAMMATIC

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text D

AutoCAD SHX Text O

AutoCAD SHX Text D

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text D

AutoCAD SHX Text O

AutoCAD SHX Text D

AutoCAD SHX Text I

AutoCAD SHX Text

%%UCH-1

File details come from the government source that posted it. Updated .