6. M0.01 - Mechanical Schedules & Details - 12.24.24.pdf
PDF 234 KB Posted
- Solicitation number
- S-P03012-00012402
- Issued by
- Clackamas County, Oregon
About this file
This mechanical drawing sheet from Rex Putnam High School in North Clackamas School District details specifications for a chiller replacement project, including mechanical schedules, pump details, and control diagrams. The document includes detailed specifications for a new Trane Ascent Air Cooled Chiller (Model ACR) with 298.5 tons capacity, three pumps (CHWP-1, HWP-1, and HWP-2), and associated mechanical systems. The drawings show mechanical legends, symbols, pump details, and control diagrams for chilled water and heating water systems.
The specifications call for specific equipment including a Bell & Gossett base-mounted centrifugal pump for the chilled water system (CHWP-1) rated at 700 GPM and 85 ft head pressure, and two heating water pumps (HWP-1 and HWP-2) rated at 680 GPM and 340 GPM respectively. All equipment must meet the 2021 Oregon Energy Efficiency Specialty Code requirements. The chiller specifications include single-point power connection, factory-powered GFCI convenience outlet, and detailed electrical requirements (460V/3PH, 496.0 MCA, 600.0 MOCP). The document includes specific installation requirements such as 4-inch housekeeping pads for certain pumps and detailed control diagrams for system operation.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2" ROUND PIPE DIAMETER, INCHES
REMOVE EXISTING
RELOCATE EXISTING
CAP OR PLUG
LOCATE IN JOIST SPACE
EXISTING TO REMAIN
CONNECT TO EXISTING
ABANDON
SYMBOLS
ABBREVIATIONS
I/O - INPUT OR OUTPUT
A/D - ANALOG OR DIGITAL
D
I
CONTROL DIAGRAM SYMBOLS
R RELAY
A
C
E
J
P
R
X
CHILLED WATER PUMP CONTROL DIAGRAM
CHWR
CHWS
Ct
VFD
CHWP-1
CAP OR PLUG
DV
HOSE END DRAIN VALVE
CHECK VALVE
BALL VALVE
BALANCING FITTING (CIRCUIT SETTER)
PRESSURE REDUCING VALVE
THERMOMETER
PRV
UNION
BAL
P
PRESSURE GAUGE W/ VALVE
X PIPE ANCHOR
EXPANSION JOINT
HWR
HWS
HEATING WATER RETURN
HEATING WATER SUPPLY
CHWR
CHWS
CHILLED WATER RETURN
CHILLED WATER SUPPLY
PRESSURE / TEMPERATURE TAP
TRIPLE DUTY VALVE (SPRING CHECK, SHUT-OFF, BALANCE)TDV
M
M0.1
FROM CHILLER
TO CHILLER
TO CHW / HHW SYSTEM
POINT
DI
DO
CONTROL FUNCTION
CHWP-1 PUMP ON/OFF
CHWP-1 STATUS
MOTOR STARTER
VARIABLE FREQUENCY DRIVE
CURRENT TRANSFORMER
DAMPER ACTUATOR MOTOR
CONTROL VALVE
DIAGRAMMATIC
AIR COOLED CHILLER CONTROL DIAGRAM4
M0.1
DIAGRAMMATIC
MECHANICAL LEGEND
GATE VALVE
FLEXIBLE CONNECTION
CHECK VALVE
B&G CIRCUIT SETTER
(FLOW INDICATING VALE)
ISOLATION VALVE
M0.1
SUCTION DIFFUSER
PETE'S PLUG
(TYP.)
SHUT OFF COCK
SPRING HANGER(TYP.)
PRESSURE
GAUGE
SUCTION DIFFUSER
BASE MOUNTED PUMP DETAIL
3-WAY CONTROL VALVE
INLINE MOUNTED PUMP DETAIL
PRESSURE
GAUGE
ISOLATION
VALVE
PETE'S
PLUG
VOLUTE CASING
PRESSURE
GAUGE
ISOLATION
VALVE
SUCTION DISCHARGE
MOTOR
PETE'S
PLUG
HEATING WATER SUPPLY (DEMO)
HEATING WATER RETURN (DEMO)
CHILLED WATER SUPPLY (DEMO)
CHILLED WATER RETURN (DEMO)
M0.1
FS FLOW SENSOR
MOTORIZED DAMPER OR VALVE ACTUATOR
POINT OF CONNECTION
PUMP SCHEDULE
EQUIPMENT
TAG
EQUIPMENT SERVED
BASIS OF DESIGN
ELECTRICAL
REVOLUTIONS /
MINUTE
FLOWRATE
HEAD
PRESSURE
PHYSICAL
NOTES
VOLTAGE
POWER (EA.) FLA (EA.)
MCA
CONNECTION SIZE
LENGTH WIDTH HEIGHT WEIGHT
MAKE MODEL RPM GPM FT
SUCTION DISCHARGE
V HP A A INCH INCH INCH INCH INCH LBS
CHWP-1
CHILLED WATER SYSTEM (P-13)
BELL & GOSSETT
BG-E1510
460/3PH 20 23.20 30.0 1731 700 85 5 4 48.38 20.62 23.75 602
1—3, 5
HWP-1 HEATING HOT WATER SYSTEM (P-12)
BELL & GOSSETT
BG-E1510
460/3PH 10 11.34 15.0 1754 680 45 5 4 39.25 19.18 20.75 418
1—3, 5
HWP-2 HEATING HOT WATER SYSTEM (SMALL PUMP)
BELL & GOSSETT
BGE80S
460/3PH 7.5 9.55 15.0 1682 340 45 4 4 25 14.45 36.38 480
1, 2, 4
NOTES:
1) ENERGY EFFICIENCY REQUIREMENTS MUST MEET MINIMUM EFFICIENCY REQUIREMENTS; 2021 OREGON ENERGY EFFICIENCY SPECIALTY CODE.
2) PUMP MOTOR TO HAVE VARIABLE FREQUENCY DRIVE
3) BASE MOUNTED CENTRIFUGAL PUMP
4) INLINE CENTRIFUGAL PUMP
5) PROVIDE ON 4" HOUSEKEEPING PAD
NEW 4"
HOUSEKEEPING
PAD OR INERTIA
BASE
FROM CHW / HHW SYSTEM
FS
HEATING WATER PUMP CONTROL DIAGRAM
HWS
Ct
VFD
HWP-2
M0.1
FROM BOILER
DIAGRAMMATIC
CHW FLOW AI
POINT
DI
DO
CONTROL FUNCTION
HWP-1 ON/OFF
HWP-1 STATUS
DI
HWP-1
FROM BOILER
TO HHW SYSTEM
FS
HWS
Ct
VFD
DO
AI
HWP-2 ON/OFF
HWP-2 STATUS
HHW FLOW
CHILLER SCHEDULE
EQUIPMENT
TAG
AREA SERVED
BASIS OF DESIGN COOLING DATA ELECTRICAL
PRESSURE
DROP
PHYSICAL
NOTES
MAKE MODEL
CAPACITY
@ OAT
DESIGN
FLOWRATE
IPLV EER
COMPRESSOR DATA OVERALL DATA
FT H2O
LENGTH WIDTH HEIGHT WEIGHT
REFRIGERANT
QTY. CKT. A CKT. B VOLT MCA MOCP
TONS °F GPM # LBS LBS V A A INCH INCH INCH LBS
CH-1
CHILLED WATER
SYSTEM
TRANE
ASCENT AIR COOLED CHILLER
MODEL ACR
298.5 95 713 21.6 11.6 R-134A 2 325 325 460/3PH 496.0 600.0 13.8 440.0 87.8 98.4
18,800 1,2,3
NOTES:
1) SINGLE-POINT POWER CONNECTION.
2) FACTORY-POWERED GFCI CONVENIENCE OUTLET. OUTLET SHALL BE POWERED PRIOR TO UNIT ELECTRICAL DISCONNECT. OUTLET SHALL BE FACTORY WIRED AND CONNECTED TO MAIN FEED WITH INTEGRAL TRANSFORMER.
3) MUST MEET ENERGY EFFICIENCY REQUIREMENTS OF 2021 OREGON ENERGY EFFICIENCY SPECIALTY CODE.
M0.1
JF
MECHANICAL
SCHEDULES &
DETAILS
REVISIONS:
ISSUE DATE:
SDC JOB #:
DESIGNED BY:
CHECKED BY:
DRAWN BY:
SET TYPE:
R
EX
P U
TN
A
M H
IG
H
S C
H O
O L
C H
IL
LE
R R
EP
LA
C
EM
EN
T
N O
R
TH
C
LA
C K
A M
A S
SC
H
O O
L D
IS
T.
S E
R O
ET
H
E R
D M
IL
W
A U
K
IE
, O R
EG
O
N
SYSTEM DESIGN CONSULTANTS INC.
333 SE SECOND AVE
SUITE 100
PORTLAND OR
97214
503-248-0227
NCS2401
12/24/2024
59898
OREGON
EXPIRES: 12/31/25
PROFESS I ONAL
DERETSIGER
NEERIGNE
9, 2 0 0 2
YLUJ
D. F A R L E Y
NHOJ
NB
NB
AutoCAD SHX Text D
AutoCAD SHX Text O
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text M
AutoCAD SHX Text Ct
AutoCAD SHX Text
VFD
AutoCAD SHX Text Ms
AutoCAD SHX Text
POINT
AutoCAD SHX Text
CONTROL FUNCTION
AutoCAD SHX Text
CHILLER ALARM
AutoCAD SHX Text
DI
AutoCAD SHX Text
CHILLER STATUS
AutoCAD SHX Text
DI
AutoCAD SHX Text
CHILLER START / STOP
AutoCAD SHX Text
DO
AutoCAD SHX Text D
AutoCAD SHX Text O
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text
CHILLER CONTROL PANEL
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text
OUTSIDE AIR TEMP SENSOR
AutoCAD SHX Text T
AutoCAD SHX Text
OUTSIDE AIR TEMP
AutoCAD SHX Text
AI
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text
DIAGRAMMATIC
AutoCAD SHX Text
DIAGRAMMATIC
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text D
AutoCAD SHX Text O
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text D
AutoCAD SHX Text O
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text
%%UCH-1