Part 5 of 5 - 962-003_Mare Island_ADD 005_2026-06-04.pdf
PDF 3 MB Posted
- Solicitation number
- 36C78626R0059_1
About this file
This document is a set of Bid Documents (structural drawings and general construction notes) for repair work at Mare Island Naval Cemetery in Vallejo, California, issued by the U.S. Department of Veterans Affairs, Office of Design and Construction Services.
The project (Number 962-003, issued May 4, 2026) involves repair details for marker C-17-008 (Wall, William H.), including removal of old ferrous screws and straps, crack repair with pin installation, and patch repairs to marble surfaces. The work also includes a flag pole foundation and comprehensive footing and foundation systems throughout the cemetery grounds. The structural drawings specify concrete construction with compressive strengths of 4000 psi for footings, exterior foundation walls, and piers. Reinforcing steel must be Grade 60 epoxy-coated deformed bars (ASTM A615) or Grade 60 low-carbon welded reinforcing (ASTM A706), with specific clear cover requirements ranging from 3/4 inches to 3 inches depending on application. The project requires compliance with the 2024 International Building Code as approved by the State of California and City of Vallejo, with seismic design category E and wind exposure category C (110 mph ultimate wind speed). Special inspections are mandated per IBC Sections 1704 and 1705 for concrete construction, soils, and structural observation, with daily testing and inspection reports required. The contractor must verify all site conditions prior to work commencement and is responsible for temporary bracing, shoring, and protection of the structure during all phases of demolition and construction. Addendum 005 providing bidding RFI responses was issued June 5, 2026.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C-17-008 WALL, WILLIAM H.
GENERAL NOTES:
1. REMOVE OLD FERROUS SCREWS AND STRAPS AND PATCH. CRACK REPAIR;
REPAIR PIN INSTALLATION ALONG CRACK; PATCH REPAIRS.
2. SEE GENERAL NOTES ON ARMATURES AND PINS ON CS410.
FRONT - MARKER C-17-008
NOT TO SCALE
DETAIL C-17-008.DWG
REMOVE CONCRETE COLLAR. IF IT
CANNOT BE REMOVED, SMOOTH CUT
SIDES NEAR-FLUSH WITH MARBLE,
WITHOUT DAMAGING MARBLE.
REAR - MARKER C-17-008
NOT TO SCALE
DETAIL C-17-008.DWG
ARMATURE & PINS DETAILS - MARKER C-17-008
SCALE: 3" = 1'-0"
DETAIL C-17-008_04.DWG
1'- 0"
M
IN
A. FRONT (EAST) ELEVATION
2" 5"
2"
1/
2" V
IF
7"
1/
2" V
IF
2" 1'-
1"1'- 2"
B. SIDE (NORTH) ELEV
1"
C. SIDE (SOUTH) ELEV
1"
D. REAR (WEST) ELEVATION
3/
4"
/4
2'-
0"
1'- 6"
1'- 6"
4"
2" SS PINS, TYP
6"
1/4" THICK SS
SIDE STRIP, TYP
1/4" DIA x 2" LONG
SMOOTH
(UNTHREADED)
SS DOWEL WELDED
TO FRONT FACE
OF SIDE STRIP, TYP
REPAIR CRACK
1" WIDE x 1/4" THICK
SS BACKER STRIP, TYP
COUNTER-SUNK
SPANNER SCREW, TYP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 18181Date:
Office of Design and Construction
Services
MARE ISLAND NAVAL CEMETERY
962-003
MAY 04, 2026
IMHOFF ROAD, VALLEJO, CA, 94592
BID DOCUMENTS
BID DOCUMENTS
2026.05.04
REPAIR DETAILS
JP SS
CS415
5 2
ADDENDUM 005 - BIDDING RFI RESPONSES 06/05/2026
GENERAL CONSTRUCTION NOTES:
1. ALL WORK SHALL COMPLY WITH THE 2024 INTERNATIONAL BUILDING CODE, AS
APPROVED BY THE STATE OF CALIFORNIA / CITY OF VALLEJO.
2. REFERENCE STANDARDS: UNLESS OTHERWISE NOTED (U.O.N.), ALL
STANDARDS SHALL BE CURRENT EDITION, WITH LATEST ADDENDA, IF
APPLICABLE.
3. THE CONTRACTOR SHALL VERIFY ALL CONTRACT DOCUMENTS, SITE
ELEVATIONS, DIMENSIONS AND CONDITIONS PRIOR TO STARTING WORK AND
SHALL NOTIFY THE ARCHITECT/ ENGINEER OF ANY DISCREPANCIES OR
INCONSISTENCIES.
4. SPECIFIC NOTES AND DETAILS SHALL TAKE PRECEDENCE OVER GENERAL
NOTES.
5. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT
THE FINISHED STRUCTURE. UNLESS OTHERWISE INDICATED, THEY DO NOT
INDICATE THE MEANS OR METHOD OF CONSTRUCTION. TEMPORARY BRACING
AND SHORING AGAINST WIND AND ERECTION CONDITIONS DURING
CONSTRUCTION OF THE BUILDING, SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE
PROTECTION OF THE STRUCTURE DURING ALL PHASES OF DEMOLITION,
CONSTRUCTION, AND INSTALLATION.
6. NO AREA OF THE STRUCTURE SHALL BE LOADED WITH CONSTRUCTION
MATERIALS OR EQUIPMENT THAT EXCEEDS FINAL DESIGN CRITERIA.
7. VERIFY LOCATION OF BOX OUTS AND OPENINGS WITH MECHANICAL
CONTRACTORS. OPENING SIZES AND LOCATIONS SHOWN FOR PIPES, DUCTS
ETC. ARE FOR GENERAL INFORMATION ONLY AND SHALL BE VERIFIED WITH THE
MECHANICAL CONTRACTOR BEFORE COMMENCING THE WORK.
8. IF MECHANICAL AND ELECTRICAL EQUIPMENT SIZES, WEIGHTS, OR LOCATIONS
DO NOT COINCIDE WITH EQUIPMENT SHOWN ON PLANS, COORDINATE
ADJUSTMENTS WITH THE STRUCTURAL ENGINEER.
9. HOLES, PIPES, SLEEVES, ETC. NOT SHOWN ON THE DRAWINGS MUST BE
APPROVED BY THE STRUCTURAL ENGINEER BEFORE PLACEMENT THROUGH
STRUCTURAL MEMBERS.
10. CONTRACTOR SHALL PROVIDE A CAST-IN SLEEVE FOR ALL HORIZONTAL
ELEMENTS THAT EXTEND THROUGH FOOTING. IE: DRAIN TILE, ELECTRICAL
CONDUIT, MECHANICAL PIPING, ETC. ALL SLEEVES SHALL BE COORDINATED
WITH ARCHITECT/ENGINEER.
11. SHOP DRAWINGS PREPARED BY SUPPLIERS, SUBCONTRACTORS, ETC., SHALL
BE DIMENSIONED, REVIEWED, COORDINATED, AND SIGNED/ STAMPED BY THE
GENERAL CONTRACTOR PRIOR TO SUBMITTING TO THE STRUCTURAL
ENGINEER.
12. FABRICATOR SHALL CLEARLY NOTE CHANGES MADE IN THE SHOP DRAWINGS
WHICH DO NOT COMPLY WITH THE CONTRACT DOCUMENTS. REVIEWED
APPROVAL SHOP DRAWINGS SHOWING ENGINEERS COMMENTS ACCOMPANIED
WITH RECORD SET SHOP SHOP DRAWINGS, SHALL BE AVAILABLE FOR
REFERENCE AT THE CONSTRUCTION SITE.
13. CONCRETE ANCHORS SHALL BE SIMPSON 'TITEN HD" SCREW ANCHORS OR
EQUIVALENT (U.O.N.). INSTALL ANCHORS USING THE MANUFACTURER'S
RECOMMENDATIONS.
FOUNDATION NOTES:
1. FOOTING ELEVATIONS ARE TO TOP OF FOOTING (T.O. FTG.), UNLESS OTHERWISE
NOTED.
2. FOOTINGS ARE DESIGNED FOR A MINIMUM NET ALLOWABLE SOIL BEARING
PRESSURE OF1500 psf FOR CONTINUOUS AND 1500 psf FOR PAD FOOTINGS.
FOUNDATION DESIGN COMPLIES W/ GEOTECHNICAL REPORT DATED: MAY 12, 2025
BY TERRACON
3. FOOTINGS SHALL BEAR ON NATURAL UNDISTURBED SOIL OR ENGINEERED FILL.
SOILS SHALL BE OBSERVED AND APPROVED BY A GEOTECHNICAL ENGINEER
PRIOR TO PLACEMENT OF FOOTING CONCRETE. IF NATURAL UNDISTURBED SOILS
ARE NOT ENCOUNTERED AND/OR INADEQUATE SOILS ARE NOTED AT FOOTING
BEARING LEVEL, ARCHITECT/ENGINEER SHALL BE NOTIFIED PRIOR TO
PROCEEDING WITH FURTHER WORK AT THOSE FOOTING LOCATIONS.
4. PROTECT FOOTINGS FROM THE ACTION OF WATER OR FREEZING.
5. FOOTINGS ARE CENTERED UNDER WALLS ABOVE - UNLESS OTHERWISE NOTED.
6. PRIOR TO PLACEMENT OF FOOTING CONCRETE, CLEAN FOOTING EXCAVATIONS
OF SNOW, WATER AND DEBRIS.
7. FOOTINGS MAY NOT BE EARTH FORMED.
EXCAVATION & BACKFILL NOTES:
1. EXCAVATION AND BACKFILL SHALL BE EXECUTED IN ACCORDANCE WITH THE
PROJECT SPECIFICATIONS.
2. BACKFILL, & COMPACTION SHALL BE INSPECTED AND CERTIFIED BY A LICENSED
GEOTECHNICAL ENGINEER. REPORTS ARE TO BE SUBMITTED TO THE
ARCHITECT/ ENGINEER.
3. FOOTING EXCAVATIONS SHALL BE EXCAVATED TO PROPER LINE AND LEVEL TO
ENSURE MINIMUM CONCRETE COVER OF FOOTING REINFORCEMENT FOR
FOOTING DEPTH.
4. BACKFILL SHALL BE COMPACTED BY MECHANICAL MEANS. FLOODING OR
WATER INUNDATION SHALL NOT BE PERMITTED.
5. BACKFILL SHALL BE PLACED IN ALTERNATING LIFTS ON EACH SIDE OF THE
FOUNDATION WALLS TO MAINTAIN STABILITY OF THE FOUNDATION WALLS.
6. BACKFILL SHALL NOT BE PLACED AGAINST BASEMENT FOUNDATION WALLS
UNLESS WALLS ARE ADEQUATELY BRACED TOP AND BOTTOM. FINAL WALL
BRACING IS BASEMENT SLAB OR ENGINEERED BACKFILL AND 1ST FLOOR
STRUCTURE. IF THESE ELEMENTS ARE NOT IN PLACE AT TIME OF BACKFILL,
CONTRACTOR SHALL PROVIDE AN ENGINEERED, TEMPORARY BRACING
SYSTEM. THE TEMPORARY BRACING SYSTEM PROPOSED SHALL BE SUBMITTED
TO THE ARCHITECT/ ENGINEER FOR REVIEW PRIOR TO BACKFILLING.
CONCRETE NOTES:
1. CONCRETE CONSTRUCTION SHALL CONFORM TO AMERICAN CONCRETE
INSTITUTE (ACI) CODES AND SPECIFICATIONS, LATEST EDITION. ACI 301
"SPECIFICATIONS FOR STRUCTURAL CONCRETE" ACI 315 "DETAILS &
DETAILING OF CONCRETE REINFORCEMENT" ACI 318 "BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE".
2. CONCRETE MIX DESIGN SHALL BE BY AN INDEPENDENT TESTING
LABORATORY.
3. CAST-IN-PLACE CONCRETE SHALL BE SUBJECT TO TESTING BY AN
INDEPENDENT TESTING LABORATORY. SEE PROJECT SPECIFICATIONS
FOR REQUIREMENTS.
4. NON WELDED REINFORCING STEEL SHALL BE GRADE 60 DEFORMED,
BILLET-STEEL, ASTM A615, U.O.N. ALL WELDED WIRE FABRIC (WWF)
SHALL BE PLAIN, ASTM A185.
5. WELDED REINFORCING STEEL SHALL BE GRADE 60, LOW CARBON, ASTM
A706.
6. PROVIDE EXTRA REINFORCEMENT AROUND ALL OPENINGS GREATER
THAN 12" SQUARE OR 12" IN DIAMETER, INCLUDING DOOR OPENINGS, IN
CONCRETE WALLS & SLABS. PROVIDE 2 - #5 BARS @ 3" O.C., ON EACH
SIDE OF THE OPENING EXTENDING 24" BEYOND THE CORNER OF THE
OPENING & 2 - #5 BARS AT 3" O.C. BY 3'-0" LONG DIAGONAL BARS AT EACH
CORNER. PLACE DIAGONAL BARS CENTERED ON CORNER @ 2" CLEAR
OF CORNER. ADDITIONAL REINFORCEMENT SHALL BE PROVIDED AT EACH
LAYER OF REINFORCING.
7. REINFORCING STEEL SHALL BE BENT, SPLICED, AND PLACED IN
ACCORDANCE WITH THE ACI 301 (LATEST EDITION).
8. PROVIDE ADEQUATE SUPPORT BARS AND ACCESSORIES TO HOLD
REINFORCING BARS FIRMLY IN PLACE TO SPECIFIED COVERAGES.
9. CAST DOWELS, WITH STD 90 DEGREE HOOK, IN FOOTINGS FOR
CONCRETE PIERS AND WALLS ABOVE. DOWELS SHALL BE THE SAME SIZE
AND NUMBER AS THE VERTICAL REINFORCING. (U.O.N.)
10. CONCRETE MIX DESIGNS REQUIREMENTS: - AGGREGATES SHALL
CONFORM TO ASTM C33. - CONCRETE EXPOSED TO FREEZE THAW SHALL
HAVE 4.5%-7.5% AIR. - WATER/CEMENT RATIO 0.55 MAX. FOR FOOTINGS
AND WALLS, 0.5 MAX. FOR SLABS - NO FLY ASH IN EXPOSED SLABS, 0.25
MAX. FLY ASH/CEMENT RATIO IN ALL OTHER APPLICATIONS - WATER
PROOFING ADMIXTURE ADD FOR EXTERIOR EXPOSED CONCRETE.
11. INJECTION ADHESIVE ANCHORS SHALL BE SIMPSON "SET-3G" USING
STANDARD 36 KSI THREADED RODS (U.O.N.). SEE SPECIFICATIONS FOR
USAGE. INSTALL ANCHORS IN STRUCTURAL CONFORMANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
12. ALL REINFORCING STEEL SHALL BE EPOXY COATED.
CAST-IN-PLACE CONCRETE COMPRESSIVE STREGNTHS
FOOTINGS 4000 psi.
EXTERIOR FOUNDATION WALLS 4000 psi.
PIERS 4000 psi.
REINFORCING CLEAR CONCRETE COVER
CONCRETE ON SOIL 3"
SLABS ON GRADE MIDHEIGHT
FORMED WALLS & STRUCTURAL SLABS EXPOSED TO EARTH OR
WEATHER: #6 THRU #18
2"
FORMED WALLS & STRUCTURAL SLABS EXPOSED TO EARTH OR
WEATHER: #5 OR SMALLER
1 1/2"
FORMED WALLS & STRUCTURAL SLABS NOT EXPOSED TO EARTH OR
WEATHER: #11 AND SMALLER
3/4"
BEAMS AND COLUMNS (COVER TO STIRRUPS OR TIES) 1 1/2"
CONC. REINFORCING BAR LAP SPLICE
SCHEDULE
BAR SIZE
f'c = 3000 psi.
f'c = 4000 psi.
f'c = 5000 psi.
CLASS
"B"
CLASS
"B"
CLASS
"B"
#3 22" 20" 18"
#4 30" 26" 22"
#5 36" 32" 28"
#6 44" 38" 34"
#7 64" 54" 50"
#8 72" 62" 56"
#9 82" 70" 64"
#10 92" 80" 70"
#11 102" 88" 78"
BAR LAP SCHEDULE NOTES:
A. REINFORCING BAR LAP SPLICE SCHEDULE APPLIES TO UNCOATED, GRADE 60
REINFORCING BAR NORMAL WEIGHT CONCRETE.
B. PROVIDE CLASS "B" LAP UNLESS OTHERWISE NOTED.
C. FOR EPOXY COATED BAR, MULTIPLY THE NOTED LENGTHS BY 1.5.
D. FOR LIGHT WEIGHT CONCRETE, MULTIPLY THE NOTED LENGTHS BY 1.3.
E. MAXIMUM SPACING OF BARS BEING LAPPED IS ONE FIFTH THE LAP SPLICE
LENGTH, NOT TO EXCEED 6".
F. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 12" OF FRESH CONCRETE
PLACED BELOW HORIZONTAL REINFORCEMENT.FOR TOP BARS, MULTIPLY THE
NOTED LENGTHS BY 1.3.
ABBREVIATIONS & SYMBOLS:
+/- PLUS OR MINUS
@ AT
A.B. ANCHOR BOLT
A.P.A. AMERICAN PLYWOOD
ASSOCIATION
A.S.T.M. AMERICAN SOCIETY OF TESTING
MATERIALS
ARCH. ARCHITECTURAL
B.B. BOND BEAM
B.O. BOTTOM OF
BLK. BLOCK
BM. BEAM
BOT. BOTTOM
BRG. BEARING
C CHANNEL
C.M.U. CONCRETE MASONRY UNIT
CCJ CONSTRUCTION CONTROL JOINT
CJ CONTROL JOINT
CL. CENTER LINE
CLR. CLEAR
COL. COLUMN
CONC. CONCRETE
CONN. CONNECTION
CONT. CONTINUOUS
D.L. DEAD LOAD
D.T. DOUBLE TEE / DRAIN TILE
DBL. DOUBLE
DIA. DIAMETER
DIM. DIMENSION
DWL. DOWEL
E.F. EACH FACE
E.J. EXPANSION JOINT
E.W. EACH WAY
EA. EACH
EL. ELEVATION
ELEV. ELEVATOR
EQ. EQUAL
EX. EXISTING
EXC. EXCAVATION
EXP. EXPANSION
F.D. FLOOR DRAIN
FDN. FOUNDATION
FT. FEET
FTG. FOOTING
G.C. GENERAL CONTRACTOR
G.T. GIRDER TRUSS
GA. GAUGE
GALV. GALVANIZE
HC. HOLLOWCORE
HORIZ. HORIZONTAL
HSS HOLLOW STRUCTURAL SECTION
I.F. INSIDE FACE
INT. INTERIOR
JST. JOIST
KLF. KIPS PER LINEAR FOOT
KSI. KIPS PER SQUARE INCH
L ANGLE
LB LEDGER BEAM
LL LIVE LOAD / DOUBLE ANGLE
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG. LONGITUDINAL
LWC LIGHT WEIGHT CONCRETE
M.C. MECHANICAL CONTRACTOR
MAS. MASONRY
MAX. MAXIMUM
MECH. MECHANICAL
MFG. MANUFACTURER
MIN. MINIMUM
MISC. MISCELLANEOUS
MTL. METAL
N. NORTH
N.T.S. NOT TO SCALE
NS. NON-SHRINK
O.C. ON CENTER
O.D. OUTSIDE DIAMETER
O.F. OUTSIDE FACE
O.H. OVERHEAD
OPNG. OPENING
ORIG. ORIGINAL
P.A.F. POWDER ACTUATED FASTENER
P.C. PRECAST CONCRETE
PART. PARTITION
PL. PLATE
PLF POUNDS PER LINEAR FOOT
PNL. PANEL
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PW PLYWOOD
R. OR
RAD.
RADIUS
R.D. ROOF DRAIN
REINF. REINFORCING
REQD. REQUIRED
S.A. STUD ANCHOR
S.B. SOIL BORING
S.D. SEE DETAIL
S.D.L. SUPERIMPOSED DEAD LOAD
S.E.R. STRUCTURAL ENGINEER OF
RECORD
S.L. SNOW LOAD
S.L.L. SUPERIMPOSED LIVE LOAD
S.S. STAINLESS STEEL
SCHED. SCHEDULE
SHT. SHEET
SIM. SIMILAR
SPA. SPACING / SPACES
SPECS. SPECIFICATIONS
SQ. SQUARE
STD. STANDARD
STL. STEEL
T & B TOP & BOTTOM
T & G TONGUE & GROOVE
T.O. TOP OF
T.O.B. TOP OF BEAM
T.O.J. TOP OF JOIST
T.O.S. TOP OF STEEL
T.O.W. TOP OF WALL
T.S.E. TOP OF STEEL ELEVATION
TEMP. TEMPORARY
THK. THICK / THICKENED
TRANS. TRANSVERSE
TYP. TYPICAL
U.O.N. UNLESS OTHERWISE NOTED
V. / VER. VERIFY
VERT. VERTICAL
W.L. WIND LOAD
W/ WITH
W/O WITH OUT
WD. WOOD
WTS. WEIGHTS
WWF WELDED WIRE FABRIC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Design and Construction
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
18181
GEOTECHNICAL/HAZMAT/
ENVIRONMENTAL:
TERRACON
1900 GARDEN ROAD SUITE 210
MONTEREY, CA 93940
831-574-7013
POINT OF CONTACT
JESS SUTTON
COST ESTIMATING:
OCMI
8851 RESEARCH DRIVE
IRVINE, CA 92618
702-339-9870
POINT OF CONTACT
ALLICIA WARNER
IRRIGATION:
EC DESIGN
400 5TH STREET
WEST DES MOINES, IA 50265
515-225-6365
POINT OF CONTACT
LISA ESSY
Project Director
2026.05.04
BID DOCUMENTS
CONSERVATOR:
ARCHITECTURAL RESOURCES GROUP
PIER 9, THE EMBARCADERO SUITE 107
SAN FRANSISCO, CA 94111
415-421-1680
POINT OF CONTACT
JENNIFER PONT
C U s e rs \J
B u e rm a n n \D o c u m e n ts \1
M
A R
E I S
L A
N D
R
V T jb u e rm a n n S
R X
R
.r v t
/1
/2
:0
:5
P
M
NOTE SHEET
MAY 04, 2025 FY JB
S001
IMHOFF ROAD, VALLEJO, CA 94592
MARE ISLAND NAVAL CEMETERY
962-003
RESPONSE MODIFICATION FACTOR R = 1.5
SEISMIC DESIGN CATEGORY E
SITE CLASS D (DEFAULT)
DESIGN SPECTRAL RESPONSE Sd1 = 1.21 DESIGN SPECTRAL RESPONSE Sds = 1.61
MAPPED SPECTRAL RESPONSE S1 = 0.9
MAPPED SPECTRAL RESPONSE Ss = 2.33 SEISMIC IMPORTANT FACTOR le = 1
SEISMIC LOADS
IMPORTANCE FACTOR Iw = 1.0
POLE DIAMETER 12" TAPERED TO 4.4"
WIND EXPOSURE "C"
RISK CATEGORY II
ULTIMATE WIND SPEE (3 SECOND GUST) 110 MPH.
LATERAL LOADS
ASSUMED FLAG POLE WP 500 LB
DEAD LOADS:
14. DESIGN LOADS:
SPECIAL INSPECTION SHALL BE PROVIDED PER THE REQUIREMENTS OF IBC SECTION 1704 AND 1705 AND AS NOTED HEREIN.
STATEMENT OF SPECIAL INSPECTIONS - CONCRETE CONSTRUCTION
STRUCTURAL SYSTEM # VERIFICATION AND INSPECTION CONTINUOUS PERIODIC COMMENTS REFERENCES
1705.3 CONCRETE
CONSTRUCTION
1. INSPECTION OF REINFORCING STEEL INCLUDING
PLACEMENT
-- X ACI 318 CH. 20, 25.2, 25.3,
26.5.1-26.5.3 & IBC 1905
IBC 1705.3
2. REINFORCING BAR WELDING IBC TABLE 1705.3
2a. VERIFY WELDABILITY OF REINFORCING BARS OTHER
THAN ASTM A 706
-- X IBC 1905, AWS D1.4, ACI
318: 26.5.4
IBC TABLE 1705.3
3. INSPECTION OF ANCHORS CAST IN CONCRETE -- X IBC 1905, ACI 318: 17.8.2 IBC TABLE 1705.3
4. INSPECTION OF ANCHORS POST-INSTALLED IN
HARDENED CONCRETE MEMBERS
4a. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR
UPWARDLY INCLINED
X -- ACI 318: 17.8.2.4 IBC TABLE 1705.3
4b. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN 4a
-- X ACI 318: 17.8.2 IBC TABLE 1705.3
5. VERIFYING USE OF REQUIRED DESIGN MIX -- X ACI 318: CH.19, 26.4.3,
26.4.4
IBC 1904.1, 1904.2,
1908.2, 1908.3, TABLE 1705.3
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE
SPECIMENS FOR STRENGTH TESTS, PERFORM SLUMP
AND AIR CONTENT TESTS, AND DETERMINE THE AIR
TEMPERATURE OF THE CONCRETE
X -- ASTM C172, ASTM C31, ACI
318: 26.4.5, 26.12
IBC 1908.10 &
TABLE 1705.3
7. INSPECTION OF CONCRETE AND SHOTCRETE
PLACEMENT FOR PROPER APPLICATION TECHNIQUES
X -- ACI 318: 26.4.5 IBC 1908.6, 1908.7,
1908.8, TABLE
1705.3
8. VERIFY MAINTENANCE OF SPECIFIED CURING
TEMPERATURE AND TECHNIQUES
-- X ACI 318: 26.4.7 – 26.4.9 IBC 1908.9 & TABLE
1705.3
9. INSPECT FORMWORK FOR SHAPE, LOCATION AND
DIMENSIONS OF THE CONCRETE MEMBER BEING
FORMED
-- X ACI 318: 26.10.1(b) IBC TABLE 1705.3
SPECIAL INSPECTION SHALL BE PROVIDED PER THE REQUIREMENTS OF IBC SECTION 1704 AND 1705 AND AS NOTED HEREIN.
STATEMENT OF SPECIAL INSPECTIONS - STRUCTURAL OBSERVATION
STRUCTURAL SYSTEM # VERIFICATION AND INSPECTION CONTINUOUS PERIODIC COMMENTS REFERENCES
1704.6 STRUCTURAL
OBSERVATION
REPORT THE OWNER SHALL EMPLOY A REGISTERED DESIGN
PROFESSIONAL TO PERFORM STRUCTURAL
OBSERVATION, THE STRUCTURAL OBSERVER SHALL
SUBMIT TO THE BUILDING OFFICIAL A WRITTEN
STATEMENT IDENTIFYING FREQUENCY AND EXTENT OF
STRUCTURAL OBSERVATIONS.
-- X SEISMIC DESIGN
CATEGORY D, E, OR F
ONLY
IBC 1704.6
SPECIAL INSPECTION SHALL BE PROVIDED PER THE REQUIREMENTS OF IBC SECTION 1704 AND 1705 AND AS NOTED HEREIN.
STATEMENT OF SPECIAL INSPECTIONS - SOILS
STRUCTURAL SYSTEM # VERIFICATION AND INSPECTION CONTINUOUS PERIODIC COMMENTS REFERENCES
1705.6 SOILS
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS
ARE ADEQUATE TO ACHIEVE THE DESIGN BEARING
CAPACITY
-- X IBC TABLE 1705.6
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER
DEPTH AND HAVE REACHED PROPER MATERIAL
-- X IBC TABLE 1705.6
3. PERFORM CLASSIFICATION AND TESTING OF
COMPACTED FILL MATERIALS
-- X IBC TABLE 1705.6
4. VERIFY USE OF PROPER MATERIALS, DENSITIES AND
LIFT THICKNESSES DURING PLACEMENT AND
COMPACTION OF COMPACTED FILL
X -- IBC TABLE 1705.6
5. PRIOR TO PLACEMENT OF COMPACTED FILL, OBSERVE
SUB-GRADE AND VERIFY THAT SITE HAS BEEN
PREPARED PROPERLY
-- X IBC TABLE 1705.6
NOTES:
TESTING AND SPECIAL INSPECTION REPORTS SHALL BE PREPARED FOR EACH INSPECTION
ITEM ON A DAILY BASIS WHENEVER WORK IS PERFORMED ON THAT ITEM. REPORTS SHALL
BE DISTRIBUTED TO OWNER, CONTRACTOR, BUILDING OFFICIAL, ARCHITECT AND
STRUCTURAL ENGINEER OF RECORD.
STRUCTURAL OBSERVATIONS SHALL BE PERFORMED BY THE STRUCTURAL ENGINEER OF
RECORD OR DESIGNATED REPRESENTATIVE IN ACCORDANCE WITH IBC 1704.6.
STRUCTURAL OBSERVATION SHALL BE PERFORMED AS FOLLOWS:
• PERIODIC VISUAL OBSERVATION OF STRUCTURAL SYSTEMS FOR GENERAL
CONFORMANCE TO CONSTRUCTION DOCUMENTS AT SIGNIFICANT CONSTRUCTION
STAGES.
• REVIEW OF TESTING AND INSPECTION REPORTS.
• REPORTS SHALL BE PREPARED FOR EACH SITE VISIT AND SHALL BE DISTRIBUTED TO
ARCHITECT.
GENERAL CONTRACTOR SHALL SUBMIT A WRITTEN CONTRACTOR'S STATEMENT OF
RESPONSIBILITY TO THE BUILDING OFFICIAL AND OWNER PRIOR TO COMMENCEMENT OF
WORK. THE CONTRACTOR'S STATEMENT OF RESPONSIBILITY SHALL INCLUDE
ACKNOWLEDGMENT OF AWARENESS OF THE SPECIAL INSPECTION REQUIREMENTS
CONTAINED IN THE STATEMENT OF SPECIAL INSPECTION.
Revisions: Date:
ADDENDUM 005 - BIDDING RFI RESPONSES 2026.06.05
T.O. PIER
EL. = SEE ARCH.
3.91°
/8
A
B 112' - 2 1/8"
C
33.63°
6' - 2"
7' - 8 5/8"
7' - 7 3/4"
20' - 11"
18' - 11"
37' - 11 3/8"
26' - 5 3/4"
29' - 6 1/4"
FC6
FC6
FC6
FC6
FC6
FC6
FC6
10"
10"
10"10"
4' - 1"
4' - 1 1"
26' - 11"
S301
S301
S
S
14' - 0"
43' - 0"
T.O. FTG.
EL. = 38' - 0"
T.O. FTG.
EL. = 36' - 0"
T.O. FTG.
EL. = 34' - 0"
24' - 0" S
T.O. FTG.
EL. = 32' - 6"
T.O. FTG.
EL. = 31' - 0"
CONCRETE APRON
SEE CIVIL
FLAG POLE BY
OTHERS
3 - #4 TIES
@ 3" O.C.
3' - 0"
A
S101
NOTE: COORDINATE WITH CIVIL FOR FINAL LOCATION OF FLAG POLE
CONC. PIER
SECTION "A"
12 - #6 VERTS. W/
#4 TIES @ 1'-0" O.C.
U.O.N.
GRID
GRID
" L
A P
1 1/2" CLR.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Design and Construction
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
18181
GEOTECHNICAL/HAZMAT/
ENVIRONMENTAL:
TERRACON
1900 GARDEN ROAD SUITE 210
MONTEREY, CA 93940
831-574-7013
POINT OF CONTACT
JESS SUTTON
COST ESTIMATING:
OCMI
8851 RESEARCH DRIVE
IRVINE, CA 92618
702-339-9870
POINT OF CONTACT
ALLICIA WARNER
IRRIGATION:
EC DESIGN
400 5TH STREET
WEST DES MOINES, IA 50265
515-225-6365
POINT OF CONTACT
LISA ESSY
Project Director
2026.05.04
BID DOCUMENTS
CONSERVATOR:
ARCHITECTURAL RESOURCES GROUP
PIER 9, THE EMBARCADERO SUITE 107
SAN FRANSISCO, CA 94111
415-421-1680
POINT OF CONTACT
JENNIFER PONT
C U s e rs \J
B u e rm a n n \D o c u m e n ts \1
M
A R
E I S
L A
N D
R
V T jb u e rm a n n S
R X
R
.r v t
/1
/2
:0
:5
P
M
FOOTING & FOUNDATION PLAN
MAY 04, 2025 FY JB
S101
IMHOFF ROAD, VALLEJO, CA 94592
MARE ISLAND NAVAL CEMETERY
962-003
1. VERIFY ALL DIMENSIONS WITH CIVIL DRAWINGS.
2. SEE SHEET S001 FOR GENERAL STRUCTURAL NOTES.
3. FC/S/T# = FOOTING MARK - SEE FOOTING SCHEDULE ON THIS SHEET.
4. = STEPPED FOOTING LOCATION - S.D. 1/S301.
5. ALL REINFORCING STEEL SHALL BE EPOXY COATED.
SHEET NOTES:
S
1/16" = 1'-0"
FOOTING & FOUNDATION PLAN
T.O. EXT. FOOTING EL. = 31' (CIVIL GRADING REF) @ GRID 1
Schedule - Footings
MARK WIDTH DEPTH
REINFORCING
COMMENTS
TRANSVERSE LONGITUDINAL
FC6 6'-0" CONT. 1'-4" #6 @ 1'-0" O.C. #5 @ 1'-0" O.C. T&B
FOOTING SCHEDULE NOTES:
1. T&B DESIGNATES REINFORCING STEEL TO BE AT TOP & BOTTOM OF FOOTING.
2. ALL REINFORCING STEEL SHALL BE EPOXY COATED.
0 16' 32'8'
1/2" = 1'-0"
FLAG POLE FOUNDATION
T.O. FTG. EL. = 34' (CIVIL GRADING REF) @ GRID 2
Revisions: Date:
T.O. WALL
(VARIES)
EL. = SEE CIVIL
T.O. GRADE
EL. = SEE CIVIL
T.O. GRADE
EL. = SEE CIVIL
T.O. WALL
(VARIES)
EL. = SEE CIVIL
3" CLR. - TYP.
SIZE & REINF.
SEE PLAN FOR
NOTE:
EXTEND ALL REINFORCING THRU CORNER - LAP & TIE.
NOTE:
IF WALL SURFACE IS SOIL LOADED EXTEND HORIZONTAL BARS TO OPPOSITE FACE & PROVIDE STANDARD HOOK.
SIZE & REINF.
SEE PLAN FOR
3 - #4 VERT. W/ DWL.
TO MATCH @ FOOTING.
CORNER BARS TO
MATCH SIZE &
SPACING OF HORIZ.
WALL REINF.
S E
E S
C H
E D
LA
P
S P
LI
C
E D
1 1/2" CLR. - TYP.
SIZE & REINF.
SEE PLAN FOR
CORNER BARS
TO MATCH SIZE
& SPACING OF
HORIZ. WALL
REINF.
1 1/2" CLR. - U.O.N.
SIZE & REINF.
SEE PLAN FOR
VERT. W/ DWL. TO
MATCH @ FOOTING.
CORNER BARS TO
MATCH SIZE &
SPACING OF HORIZ.
WALL REINF.
1 1/2" CLR. - U.O.N.
S E
E S
C H
E D
LA
P
S P
LI
C
E
S E
E S
C H
E D
LA
P
S P
LI
C
E
NOTE:
CONST. JOINT SHOWN MAY BE OMITTED @ CONTRACTOR'S OPTION.
SIZE & REINF.
SEE PLAN FOR
2" x 4" x 6" LONG.
VERT. KEYWAY
EVENLY SPACED
BETWEEN HORIZ.
REINF. SPACING
DWL. W/ STANDARD
HOOK TO MATCH
SIZE & SPACING OF
HORIZ. REINFORCING
2" CLR. - TYP.
S E
E S
C H
E D
LA
P
S P
LI
C
E
2" x 6" x 6" LONG.
VERT. KEYWAY
EVENLY SPACED
BETWEEN HORIZ.
REINF. SPACING
DWL. W/ STANDARD
HOOK TO MATCH
SIZE & SPACING OF
HORIZ. REINFORCING
SIZE & REINF.
SEE PLAN FOR
2" CLR. - TYP.
S E
E S
C H
E D
LA
P
S P
LI
C
E
NOTE:
JOINT MAXIMUM SPACING 40'-0". SPACING MAY BE INCREASED TO 80'-0"
IF WALL IS BACKFILLED INTERIOR SIDE FOR FULL HEIGHT OR 120'-0" IF
WALL IS BACKFILLED ON BOTH SIDES FOR FULL HEIGHT.
1"
1/2"
S
IZ
E
R E
IN
F
S E
E P
LA
N
F O
R
1 1/2"
6" 6"
SEE SCHED.
LAP SPLICE3" CLR.VERT. CAULK JOIST @
EACH FACE
2" x 6" x 6" LONG. VERT. KEYWAY (2" x 4" x 6" @ 8" WALL) EVENLY
SPACED BETWEEN HORIZ. REINF.
SPACING. KEYWAY CONT. WHERE
WATERSTOP IS REQUIRED
VERT. CAULK
VERT. ROD STOCK
WATERSTOP
WHERE
REQUIRED
#6 @ 12" O.C. VERT.
EACH FACE
#5 @ 1'-0" O.C. HORIZ.
EACH FACE
SEE PLAN FOR
FOOTING SIZE,
REINF. & ELEV.
DWL. TO MATCH
EACH VERT.
3" CLR. - TYP.
2' - 0" 10" 3' - 2"
1 1/2" CLR.
2" CLR.
#6 @ 12" O.C. TOP &
BOT.
NOTE:
PROVIDE 12" GRAVEL LAYER BEHIND WALLS PER GEOTECHNICAL REPORT
DRAIN TILE
#6 @ 12" O.C. VERT.
#6 @ 12" O.C. VERT.
SEE PLAN FOR
FOOTING SIZE,
REINF. & ELEV.
DWL. TO MATCH
EACH VERT.
3" CLR. - TYP.
2' - 8" 10" 2' - 6"
1 1/2" CLR.
2" CLR.
#6 @ 12" O.C. TOP &
BOT.
EX. GRADE
#5 @ 12" O.C. HORIZ.
EACH FACE
#5 @ 12" O.C. CONT.
TOP & BOT.
NOTE:
PROVIDE 12" GRAVEL LAYER BEHIND WALLS PER GEOTECHNICAL REPORT
DRAIN TILE
2a U.O.N.
a
SEE PLAN
3" CLR. - TYP.
DEPTH 1'-0" MIN.
EQUAL TO FTG.
2a U.O.N.
NOTES:
1. SEE PLAN FOR FOOTING SIZE AND REINFORCING.
2. SLOPED OR STEPPED FOOTINGS SHALL BE CAST AS A UNIT.
3. STEPPED FOOTING LINES SHOWN ON PLAN ARE @ BOTTOM OF FOOTING.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Design and Construction
Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
18181
GEOTECHNICAL/HAZMAT/
ENVIRONMENTAL:
TERRACON
1900 GARDEN ROAD SUITE 210
MONTEREY, CA 93940
831-574-7013
POINT OF CONTACT
JESS SUTTON
COST ESTIMATING:
OCMI
8851 RESEARCH DRIVE
IRVINE, CA 92618
702-339-9870
POINT OF CONTACT
ALLICIA WARNER
IRRIGATION:
EC DESIGN
400 5TH STREET
WEST DES MOINES, IA 50265
515-225-6365
POINT OF CONTACT
LISA ESSY
Project Director
2026.05.04
BID DOCUMENTS
CONSERVATOR:
ARCHITECTURAL RESOURCES GROUP
PIER 9, THE EMBARCADERO SUITE 107
SAN FRANSISCO, CA 94111
415-421-1680
POINT OF CONTACT
JENNIFER PONT
C U s e rs \J
B u e rm a n n \D o c u m e n ts \1
M
A R
E I S
L A
N D
R
V T jb u e rm a n n S
R X
R
.r v t
/1
/2
:0
:5
P
M
FOOTING & FOUNDATION DETAILS
MAY 04, 2025 FY JB
S301
IMHOFF ROAD, VALLEJO, CA 94592
MARE ISLAND NAVAL CEMETERY
962-003
1/2" = 1'-0"S301
1 FOOTING CORNER REINF. DETAIL
1/2" = 1'-0"S301
2 WALL CORNER REINF. DETAIL
1/2" = 1'-0"S301
3 WALL INTERSECTION DETAIL
1/2" = 1'-0"S301
4 WALL CONSTRUCTION JOINT DETAIL
1/2" = 1'-0"S301
5 RETAINING WALL DETAIL
1/2" = 1'-0"S301
6 RETAINING WALL DETAIL
1/2" = 1'-0"S301
7 STEPPED FOOTING DETAIL
Revisions: Date:
| Add 005_06-10-2026 15 |
| Add 005_06-10-2026 16 |
| Add 005_06-10-2026 17 |
| Add 005_06-10-2026 18 |