This document package includes construction drawings and specifications for fire alarm and fire suppression system upgrades at the Kansas City VA Medical Center. The drawings show the design and locations for new and replacement fire alarm notification devices, initiating devices, control panels, circuits and equipment. Fire alarm audibility plans illustrate expected sound pressure levels throughout occupied areas. Fire suppression drawings include hazard classifications by area, sprinkler piping schematics, riser diagrams and details for new control valves. Specifications provide performance requirements and reference applicable codes. This work supports the solicitation for EHRM infrastructure upgrades at the medical center to modernize life safety systems. The solicitation is issued by the VA Technology Acquisition Center with an opportunity number of 36C77623B0020. Construction is to take place at the Kansas City VAMC facility located at 4801 Linwood Blvd.
View the file
Other files for this federal contract opportunity
Show all 36
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE ALARM GENERAL NOTES
GENERAL:
1. THE CONTRACTOR SHALL CAREFULLY REVIEW ALL APPLICABLE
DESIGN CRITERIA, THESE DRAWINGS, AND THE PROJECT
SPECIFICATIONS FOR IMPORTANT QUALIFICATION, DEFINITION,
SUBMITTAL, PRODUCT, INSTALLATION, AND TESTING REQUIREMENTS.
2. ALL SUBMITTALS, INSTALLATION, AND TESTING SHALL BE COMPLETED
IN A NEAT, WORKMAN-LIKE MANNER.
3. PRODUCT, DESIGN, INSTALLATION, AND TESTING ALTERNATE
APPROACHES AND/OR SUBSTITUTIONS WILL BE CONSIDERED BY THE
ENGINEER IF THE CONTRACTOR PROVIDES WRITTEN, WELL-
DOCUMENTED, ENGINEERING-BASED SUBSTANTIATION FOR
PROPOSED ALTERNATIVE.
APPLICABLE CODES AND STANDARDS:
1. VA FIRE PROTECTION DESIGN MANUAL EIGHTH EDITION - JUNE 2021
2. NFPA 70 NATIONAL ELECTRIC CODE (2020)
3. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE (2019)
4. NFPA 101 (2021)
5. INTERNATIONAL BUILDING CODE (2021)
AUDIBILITY AND INTELLIGIBILITY DESIGN:
1. BECAUSE OF UNPREDICTABLE BACKGROUND NOISES AND PROJECT
CONDITIONS, THE AUDIBILITY DESIGN GOALS SHALL BE CONFIRMED
BY MEASUREMENT WITH CALIBRATED TEST EQUIPMENT. IF RESULTS
INDICATE THAT ADDITIONAL NOTIFICATION APPLIANCES ARE
REQUIRED, THE CONTRACTOR SHALL ADD THEM AT NO ADDITIONAL
COST.
2. SPEAKERS MAY BE FIELD-LOCATED WITHIN 6 FT OF THE LOCATION
INDICATED ON THE APPROVED DESIGN WITHOUT CONSULTING THE
ENGINEER.
3. INTELLIGIBILITY OF THE OCCUPANT NOTIFICATION SHALL BE TESTED
IN ACCORDANCE WITH NFPA 72 AND THE VA FIRE PROTECTION
DESIGN MANUAL. QUALITATIVE TESTING IS ALLOWED. ALL SCOPE OF
WORK AREAS ARE REQUIRED TO HAVE A CIS SCORE OF 0.65.
VISUAL NOTIFICATION DESIGN:
1. CLEAR STROBES SHALL BE PROVIDED WHERE INDICATED ON THE
APPROVED DESIGN.
2. STROBES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE LOCATION
INDICATED ON THE APPROVED DESIGN WITHOUT CONSULTING THE
ENGINEER. CONSULT WITH ENGINEER PRIOR TO RELOCATING
STROBES MORE THAN 3 FT.
INITIATING DEVICES:
1. INITIATING DEVICES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE
LOCATION INDICATED ON THE APPROVED DESIGN WITHOUT
CONSULTING THE ENGINEER. CONSULT WITH ENGINEER PRIOR TO
RELOCATING INITIATING DEVICES MORE THAN 3 FT.
CIRCUITS AND CONDUIT:
1. ALL CIRCUITS SHALL BE PROVIDED IN CONDUIT IN ACCORDANCE WITH
NFPA 70 AND THE CONDUIT LISTING.
2. NEW SIGNALING LINE CIRCUITS AND NOTIFICATION APPLIANCE
CIRCUITS SHALL BE ARRANGED SO THAT A SINGLE FAULT DOES NOT
CAUSE THE LOSS OF ADDRESSABLE DEVICES ON MORE THAN ONE
SMOKE COMPARTMENT.
3. WIRING SHALL BE INSTALLED IN METAL RACEWAY. PER VA DESIGN
MANUAL THIS IN COMBINATION WITH BUILDINGS PROTECTED
THROUGHOUT BY SPRINKLERS SHALL BE CONSIDERED TO MEET THE
REQUIREMENTS FOR PATHWAY SURVIVABILITY LEVEL 2 IN
ACCORDANCE WITH NFPA 72 AND VA AUTHORITY HAVING
JURISDICTION.
4. SPEAKERS AND STROBES SHALL BE ARRANGED TO OPERATE ON
SEPARATE CIRCUITS.
INSTALLATION:
1. ALL EQUIPMENT SHALL BE INSTALLED TIGHT TO THE BUILDING
STRUCTURE AND SHALL BE INSTALLED PARALLEL OR
PERPENDICULAR TO THE BUILDING STRUCTURE UNLESS NOTED
OTHERWISE.
2. THE CONTRACTOR SHALL NOT APPRECIABLY DEVIATE FROM THE
APPROVED DESIGN WITHOUT WRITTEN APPROVAL FROM THE
ENGINEER.
TESTING:
1. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL
PERFORM ALL ACCEPTANCE TESTING IN ACCORDANCE WITH THE
APPLICABLE DESIGN CRITERIA AND THE EQUIPMENT
MANUFACTURER'S INSTRUCTIONS.
2. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL
PERFORM TESTING AND PROVIDE DOCUMENTATION PRIOR TO
REQUESTING ENGINEER'S PRESENCE TO WITNESS TESTING.
FACU
SPD
FIRST FLOOR
NOTES:
1. TO DEDICATED 120VAC BRANCH CIRCUIT
2. EXISTING FIRE ALARM CONTROL UNIT, LOCATED IN MECHANICAL B01.
3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM DESIGN INTENT, PANEL
CONNECTIONS, AND GENERAL CIRCUIT ROUTING REQUIREMENTS. EXACT QUANTITIES AND
TYPES OF DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT INDICATED.
THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE GENERAL SYSTEM CONFIGURATION
AFTER SUCCESSFUL COMPLETION OF THE PROJECT.
2 3
SECOND FLOOR
BASEMENT
S
S S
SS
F
F
S E
FS
E
VS
AIM
WF
AIM
VS
AIM
VS
AIM
H E
F
WF
AIM
WF
AIM
18 ANY OTHER SYSTEM TROUBLE X X X 18
10 SHUNT TRIP POWER MONITOR X X X 10
11 CONTROL VALVE SUPERVISORY SWITCH X X X 11
7 WATERFLOW/PRESSURE SWITCH X X X X X X 7
8 WATERFLOW SWITCH - ELEVATOR MACHINE ROOM X X X X X X X 8
9 HEAT DETECTOR - ELEVATOR MACHINE ROOM - OTHER THAN DESIGNATED RECALL LEVEL X X X X X X X 9
SUPERVISORY CONDITIONS A B C D E F G H I J K L M N O
A B C D E F G H I J K L M N O
X PERFORM OPERATION/REPORT DEVICE STATUS
NOTES:
1. THIS INPUT/OUTPUT MATRIX IS REPRESENTATIVE OF THE SCOPE OF WORK OF THIS PROJECT. NOT ALL EXISTING INPUTS AND OUTPUTS ARE REPRESENTED ON THIS MATRIX. PLEASE REFER
TO THE EXISTING FIRE ALARM PANEL FOR ALL OF THE INPUTS AND OUTPUTS.
TROUBLE CONDITIONS A B C D E F G H I J K L M N O
12 AC POWER FAILURE X X X 12
13 LOW BATTERY X X X 13
14 OPEN CIRCUIT X X X 14
15 GROUND FAULT X X X 15
16 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 16
17 REMOTE POWER SUPPLY COMMON TROUBLE X X X 17
SYSTEM OUTPUTS
SYSTEM INPUTS
F A
C U
A N
N U
N C
IA
T
IO
N
A C
T
IV
A T
E C
O M
M O
N A
L A
R M
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
A L A
R M
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N S
U P
E R
V
IS
O R
Y S
IG
N
A L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
S U
P E
R V
IS
O
R Y
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N T
R O
U B
L E
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
T R
O U
B L E
S
IG
N A
L
A C
T
IV
A T
E S
E P
A R
A T
E A
N D
D
IS
T
IN
C T
IV
E
V
IS
IB
L E
A N
N U
C
IA
T
IO
N
D
IS
P L A
Y /P
R
IN
T C
H A
N G
E O
F S
T A
T U
S
N O
T
IF
IC
A
T
IO
N
A C
T
IV
A T
E T
E M
P O
R A
L
A L E
R T
T O
N E
A N
D P
R E
-R E
C O
R D
E D
F
IR
E
E V
A C
U A
T
IO
N M
E S
S A
G E
T H
R O
U G
H O
U T
B U
IL
D
IN
G
A C
T
IV
A T
E S
T R
O B
E S
T H
R O
U G
H O
U T
B U
IL
D
IN
G
N O
T
IF
Y F
IR
E
D E
P A
R T
M E
N T
A U
X
IL
IA
R
Y F
U N
C T
IO
N
S
R E
C A
L L E
L E
V A
T O
R T
O D
E S
IG
N
A T
E D
L E
V E
L
R E
C A
L L E
L E
V A
T O
R T
O A
L T
E R
N A
T E
L E
V E
L
A C
T
IV
A T
E E
L E
V A
T O
R H
A T
L
IG
H T
F
L A
S H
IN
G
S H
U N
T T
R
IP
P O
W E
R T
O E
L E
V A
T O
R
ALARM CONDITIONS A B C D E F G H I J K L M N O
1 MANUAL ALARM PULL STATION X X X X X X 1
2 SMOKE DETECTOR - SPOT TYPE X X X X X X 2
3 SMOKE DETECTOR - ELEVATOR LOBBY - DESIGNATED RECALL LEVEL X X X X X X X 3
4 SMOKE DETECTOR - ELEVATOR LOBBY - OTHER THAN DESIGNATED RECALL LEVEL X X X X X X X 4
5 SMOKE DETECTOR - ELEVATOR MACHINE ROOM - DESIGNATED LEVEL X X X X X X X X 5
6 SMOKE DETECTOR - ELEVATOR MACHINE ROOM - OTHER THAN DESIGNATED RECALL LEVEL X X X X X X X X 6
FIRE ALARM LEGEND
F NEW FIRE ALARM PULL STATION
SPD EXISTING SURGE PROTECTIVE DEVICE
FACU EXISTING FIRE ALARM CONTROL UNIT
NEW SPEAKER STROBE
S NEW SPEAKER
SYMBOL MODIFIERS
ncd CANDELA RATING
C nW
CEILING MOUNTED
WATT TAP
WF NEW WATERFLOW SWITCH
VS NEW VALVE SUPERVISORY SWITCH
S NEW SMOKE DETECTOR - SPOT TYPE
E ELEVATOR RECALL
F NEW WATERFLOW BELL
FCV FLOOR CONTROL VALVE
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2009021688 EXP. 12/31/2023
ENGR REG. NO. PE 20190403952 EXP. 12/31/2023
ENGR REG. NO. PE 2018038407 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGIENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:2 :4
A
M
FIRE ALARM GENERAL NOTES, LEGEND,
AND DIAGRAMS
SAB 31 72BLS
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
06/28/2022
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
FA001
SPUR #: 1794.13
SCALE: NONE
FIRE ALARM RISER DIAGRAM2
SCALE: NONE
FACU INPUT/OUTPUT MATRIX1
No. REVISION DESCRIPTION DATE
CS4
CRAWLSPACE
CS4 B07
MECHANICAL
B07
B01
MECHANICAL
B01
STAIR 1
CS2
CRAWLSPACE
CS2
CS3
CRAWLSPACE
CS3 B02
MECHANICAL
B02 CS1
CRAWLSPACE
CS1
CS5
CRAWLSPACE
CS5
B07A
MECH
B07A
3-101
BREAKROOM
3-101
STAIR 2
ELEV
EX ELEV
ELEV3-100
EX ELEV
MECH
3-1003-102
CONFERENCE
ROOM
3-1023-104
WOMENS
RR
3-1043-106
MENS RR
3-1063-108
TELECOM
3-1083-110
ADMIN
3-110
3-111
ADMIN
3-111
3-112
CLASSROOM
/ IV
TESTING
3-112
3-112B
EX STOR
3-112B 3-112A
EX STOR
3-112A
3-107
ADMIN
3-107
3-105
EX ENTRY
3-105 B07B
STAIR1
B07B
C1-3-1
CORRIDOR
C1-3-1
3-103
ADMIN
3-103
3-109B
CORRIDOR
3-109B
3-211
CLASSROOM
/ IV
TESTING
3-211
3-210
CLASSROOM
/ IV
TESTING
3-210 3-200
CLASSROOM
/ IV
TESTING
3-200 3-206
WOMENS
RR
3-2063-208
MENS RR
3-208
3-203
WAITING
ROOM
3-203 3-201
BREAKROOM
3-201
ELEV
EX ELEV
ELEV
STAIR 2
B07B
STAIR1
B07B3-209
HAC
3-209
3-208A
CORRIDOR
3-208AC2-3-2
CORRIDOR
C2-3-2
REQUIRED AUDIBILITY LEGEND
54dB AMBIENT SPL 69dB EXPECTED SPL (BUSINESS OCCUPANCIES)
60dB AMBIENT SPL 75dB EXPECTED SPL (ASSEMBLY OCCUPANCIES)
30dB AMBIENT SPL 45dB EXPECTED SPL (STORAGE OCCUPANCIES)
91dB AMBIENT SPL 106dB EXPECTED SPL (MECHANICAL OCCUPANCIES)
FIRE - 1 HOUR (NEW/EXISTING)
PARTITION LEGEND
SMOKE (NEW/EXISTING)
EXISTING NON-RATED
WALL TO REMAIN
NEW WALL
NOTE: WALL RATINGS ARE REFRENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2009021688 EXP. 12/31/2023
ENGR REG. NO. PE 20190403952 EXP. 12/31/2023
ENGR REG. NO. PE 2018038407 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGIENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:2 :4
A
M
FIRE ALARM AUDIBILITY PLANS
SAB 32 72BLS
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
06/28/2022
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
FA101
SPUR #: 1794.13
N
1/8" = 1'-0"
FIRE ALARM AUDIBILITY PLAN - BASEMENT1
N
1/8" = 1'-0"
FIRE ALARM AUDIBILITY PLAN - FIRST FLOOR2
N
1/8" = 1'-0"
FIRE ALARM AUDIBILITY PLAN - SECOND FLOOR3
F
2W
30cd
2W
30cd
0.5W
30cd15cd15cd
0.25W
15cd
0.25W
15cd
0.25W
15cd
0.25W
30cd
F
F
F
F
F
0.5W
30cd
.5
W c d
.5
W c d
.2
W c d
0.25W
15cd
0.25W
15cd
0.25W
15cd
F
0.5W
30cd
0.5W
75cd
0.25W
30cd
15cd 15cd
0.25W
15cd
0.25W
15cd
.2
W c d
F
F 0.25W
15cd
0.25W
75cd
CS4
CRAWLSPACE
CS4
B07
MECHANICAL
B07
B01
MECHANICAL
B01
STAIR 1
CS2
CRAWLSPACE
CS2
CS3
CRAWLSPACE
CS3
B02
MECHANICAL
B02
CS1
CRAWLSPACE
CS1
CS5
CRAWLSPACE
CS5
F A
C U
F C
P S
S
B07A
MECH
B07A VS FCV
WFFCV
3-101
BREAKROOM
3-101
STAIR 2
ELEV
EX ELEV
ELEV
3-100
EX ELEV
MECH
3-100
3-102
CONFERENCE
ROOM
3-1023-104
WOMENS
RR
3-1043-106
MENS RR
3-106 3-108
TELECOM
3-1083-110
ADMIN
3-110
3-111
ADMIN
3-111
3-112
CLASSROOM
/ IV
TESTING
3-112
3-112B
EX STOR
3-112B 3-112A
EX STOR
3-112A
3-107
ADMIN
3-107
3-105
EX ENTRY
3-105
B07B
STAIR1
B07B
C1-3-1
CORRIDOR
C1-3-1
3-103
ADMIN
3-103
S E
WF
VS
3-109B
CORRIDOR
3-109B
WFFCV
VS FCV
H E
S E
WF
VS
3-211
CLASSROOM
/ IV
TESTING
3-211
3-210
CLASSROOM
/ IV
TESTING
3-210 3-200
CLASSROOM
/ IV
TESTING
3-200
3-206
WOMENS
RR
3-2063-208
MENS RR
3-208
3-203
WAITING
ROOM
3-203
3-201
BREAKROOM
3-201
ELEV
EX ELEV
ELEV
STAIR 2
3-209
HAC
3-209
3-208A
CORRIDOR
3-208A
B07B
STAIR1
B07B
S E
C2-3-2
CORRIDOR
C2-3-2
VS FCV
WFFCV
FIRE ALARM LEGEND
F NEW FIRE ALARM PULL STATION
SPD EXISTING SURGE PROTECTIVE DEVICE
FACU EXISTING FIRE ALARM CONTROL UNIT
NEW SPEAKER STROBE
S NEW SPEAKER
SYMBOL MODIFIERS
ncd CANDELA RATING
C nW
CEILING MOUNTED
WATT TAP
WF NEW WATERFLOW SWITCH
VS NEW VALVE SUPERVISORY SWITCH
S NEW SMOKE DETECTOR - SPOT TYPE
E ELEVATOR RECALL
F NEW WATERFLOW BELL
FCV FLOOR CONTROL VALVE
FIRE - 1 HOUR (NEW/EXISTING)
PARTITION LEGEND
SMOKE (NEW/EXISTING)
EXISTING NON-RATED
WALL TO REMAIN
NEW WALL
NOTE: WALL RATINGS ARE REFRENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2009021688 EXP. 12/31/2023
ENGR REG. NO. PE 20190403952 EXP. 12/31/2023
ENGR REG. NO. PE 2018038407 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGIENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:2 :4
A
M
FIRE ALARM FLOOR PLANS
SAB 33 72BLS
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
06/28/2022
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
FA102
SPUR #: 1794.13
N
1/8" = 1'-0"
FIRE ALARM PLAN - BASEMENT1
N
1/8" = 1'-0" 1/ FX001
FIRE ALARM PLAN - FIRST FLOOR2
N
1/8" = 1'-0" 1/ FX001
FIRE ALARM PLAN - SECOND FLOOR3
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL AND WILL THEREFORE
NOT REQUIRE SMOKE DETECTION IN ACCORDANCE WITH
VA FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C.
FIRE SUPPRESSION GENERAL NOTES:
1. THE DESIGN AND INSTALLATION OF THE FIRE PROTECTION, FIRE
SUPPRESSION SYSTEM MUST BE IN ACCORDANCE WITH U.S.
DEPARTMENT OF VETERANS AFFAIRS FIRE PROTECTION DESIGN
MANUAL, EIGHTH EDITION, JUNE 2021; NFPA 13: STANDARD FOR
THE INSTALLATION OF SPRINKLER SYSTEMS, 2022 EDITION.
2. THIS INFORMATION HAS BEEN PREPARED TO PROVIDE GUIDANCE
FOR BIDDING. THE FIRE PROTECTION CONTRACTOR SHALL BE
FULLY RESPONSIBLE FOR PROVIDING A COMPLETE AND FULLY
OPERABLE SYSTEM WHICH SHALL BE IN STRICT ACCORDANCE
WITH PROJECT SPECIFICATIONS AND APPLICABLE CODES AND
STANDARDS. THE WORK THAT IS INDICATED IN THIS DOCUMENT IS
AN OVERVIEW OF THE PROJECT, INTENDED TO ESTABLISH THE
MINIMUM SCOPE REQUIREMENTS FOR THE PROJECT AS WELL AS
THE CONTRACTOR’S RESPONSIBILITIES. THE CONTRACTOR SHALL
SUBMIT A COMPLETE SET OF WORKING DRAWINGS, EQUIPMENT,
AND CALCULATIONS TO THE OWNER’S REPRESENTATIVE AND AHJ
FOR REVIEW AND APPROVAL PRIOR TO FABRICATION AND
INSTALLATION WITH THEIR ENGINEERS SEAL. UNLESS
SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL
PERFORM ALL ACCEPTANCE TESTING IN ACCORDANCE WITH THE
APPLICABLE DESIGN CRITERIA AND THE EQUIPMENT
MANUFACTURER'S INSTRUCTIONS.
3. SPRINKLER CONTRACTOR SHALL COORDINATE LOCATIONS OF
FIRE PROTECTION COMPONENTS INCLUDING PIPING, ALARMS,
DRAINS, SPRINKLERS, TEST POINTS, ETC., WITH ALL
ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL
COMPONENTS. OBSTRUCTIONS TO SPRINKLER DISCHARGE SHALL
BE CONSIDERED DURING INSTALLATION. DO NOT INSTALL
SPRINKLER PIPING BELOW EQUIPMENT OR WITHIN CLEARANCE
SPACES FOR MECHANICAL AND ELECTRICAL EQUIPMENT.
SPRINKLERS SHALL BE INSTALLED UNDER OBSTRUCTIONS IN
ACCORDANCE WITH NFPA 13.
4. MATERIALS AND ACCESSORIES NECESSARY MUST BE INSTALLED
IN ACCORDANCE WITH THE APPLICABLE NFPA CODES AND
STANDARDS, PROJECT SPECIFICATIONS, AND BE UL LISTED OR FM
APPROVED FOR FIRE PROTECTION USE, UNLESS OTHERWISE
NOTED.
5. ALL VALVES INSIDE TO BE PROVIDED WITH ELECTRONIC TAMPER
SWITCHES WIRED TO THE FACU. VALVES IN NORMAL CLOSED
POSITION SHALL BE PROVIDED WITH TAMPER TO ACTIVATE IN
THREE TURNS OR LESS. ALL VALVES OUTSIDE TO BE
ELECTRONICALLY MONITORED BY FIRE ALARM.
6. ALL HANGERS MUST BE PROVIDED AND INSTALLED IN
ACCORDANCE WITH NFPA 13 AND PROJECT SPECIFICATIONS.
7. LOCATION AND INSTALLATION OF PIPE SUPPORTS (HANGERS,
VERTICAL RESTRAINTS, AND GUIDES) SHALL MEET THE
REQUIREMENTS OF NFPA 13 AND THE SPECIAL LISTING
REQUIREMENTS (IF APPLICABLE) OF THE PIPE AND SUPPORTS. THE
SEISMIC DESIGN CATEGORY FOR THIS PROJECT IS D, PLEASE
REFER TO THE STRUCTURAL DESIGN SHEETS FOR MORE
INFORMATION.
8. THE INSPECTOR'S TEST VALVES MUST BE LOCATED NO MORE
THAN 7 FEET AFF.
9. APPLICABLE UL CONSTRUCTION DETAILS AND SYSTEMS SHALL BE
USED WHERE FIRE RATED BARRIERS ARE PENETRATED BY
SPRINKLER PIPING.
10. ALL VALVES (DRAINS, INSPECTOR'S TEST, CONTROL) MUST BE
IDENTIFIED AS REQUIRED BY NFPA 13.
11. PIPING MUST BE ARRANGED FOR FLUSHING. READILY REMOVABLE
FITTINGS MUST BE PROVIDED AT THE END OF ALL CROSS MAINS.
12. ALL PENDENT SPRINKLERS MUST BE INSTALLED IN THE CENTER
OF THE CEILING TILES.
13. DRAINS MUST BE LOCATED TO PROVIDE DRAINAGE IN
ACCORDANCE WITH NFPA 13. ALL DRAINS AND TEST
CONNECTIONS MUST DISCHARGE TO THE EXTERIOR OF THE
BUILDING ON TO A SPLASH BLOCK OR PAVEMENT, AND SHALL NOT
DISCHARGE ACROSS PATHS OF EGRESS.
14. ALL SPRINKLER SYSTEM ALARM INITIATING AND SUPERVISORY
DEVICES MUST BE CONNECTED TO THE FIRE ALARM SYSTEM.
15. ADDITIONAL SPRINKLERS MAY BE REQUIRED UNDER DUCT WORK
TO PROVIDE ADEQUATE COVERAGE PER NFPA 13.
16. A LISTED RELIEF VALVE MUST BE PROVIDED IN ACCORDANCE
WITH NFPA 13, SECTION 8.1.2 FOR THE SPRINKLER SYSTEM.
17. AN AIR VENT MUST BE PROVIDED IN ACCORDANCE WITH NFPA 13,
SECTION 8.1.5 AND SECTION 16.7 FOR THE SPRINKLER SYSTEM.
18. THIS BUILDING WILL HAVE A WET PIPE AUTOMATIC SPRINKLER
SYSTEM WHICH WILL REQUIRE ALL AREAS OF THE BUILDING TO BE
MAINTAINED ABOVE 40 DEGREES F.
19. PROVIDE SPRINKLER PROTECTION WITHIN ALL COMBUSTIBLE
CONCEALED SPACES.
20. DATA FROM FIRE HYDRANT FLOW TEST PERFORMED BY POOLE
FIRE PROTECTION OCTOBER 5, 2021.
A. STATIC PRESSURE: 53 PSI
B. RESIDUAL PRESSURE: 31 PSI
C. TEST FLOW: 669 GPM
D. FLOW @ 20 PSI: 833 GPM
UNDERGROUND LEAD-IN
FIRE DEPARTMENT
CONNECTION
WATERFLOW SWITCH
TEST/DRAIN PRESSURE
RELIEF VALVE
MAINLINE TO
SPRINKLER SYSTEM
MAIN DRAIN DISCHARGE
RISER CHECK
VALVE ASSEMBLY
CHECK VALVE
NORMALLY CLOSED
BUTTERFLY VALVE
AUTOMATIC BALL DRIP
LEVEL 1
0' - 0"
LEVEL 2
9' - 4"
FX001
"4
LEVEL 1
0' - 0"
LEVEL 2
9' - 4"
FX001
FEED MAIN SUPPLY TO
SPRINKLER SYSTEM
PRESSURE GAUGE
WATERFLOW SWITCH
CHECK VALVE
INDICATING-TYPE FLOOR CONTROL
VALVE WITH SUPERVISORY SWITCH
UNION WITH CORROSION-
RESISTANT ORIFICE GIVING FLOW
EQUIVALENT TO THE SMALLEST
SPRINKLER ORIFICE IN THE
SYSTEM
SIGHT GLASS
TEST VALVE WITH PRESSURE
RELIEF VALVE
SECTIONAL DRAIN VALVE
2" DRAIN RISER
TO DISCHARGE
AT A SAFE POINT
OUTSIDE THE
BUILDING SPRINKLER RISER
FX001
FX001
39"
CONTRACTOR TO MAINTAIN 36"
CLEARANCE AT AND BELOW
HANDRAIL HEIGHT IN
ACCORDANCE WITH NFPA 101
SECTION 7.2.2 REQUIREMENTS.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2009021688 EXP. 12/31/2023
ENGR REG. NO. PE 20190403952 EXP. 12/31/2023
ENGR REG. NO. PE 2018038407 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGIENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:2 :5
A
M
FIRE SUPPRESSION GENERAL NOTES
AND RISER DIAGRAM
SAB 34 72BLS
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
06/28/2022
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
FX001
SPUR #: 1794.13
SCALE: NONE
SUPPRESSION RISER DIAGRAM3 1" = 1'-0" 2/ FX001
FIRE SUPPRESSION RISER SECTION 111" = 1'-0" 1/ FX001
FIRE SUPPRESSION RISER SECTION 22
SCALE: NONE
FLOOR CONTROL VALVE DETAIL4
1/2" = 1'-0"
RISER PLAN VIEW AT HANDRAIL HEIGHT5
CS4
CRAWLSPACE
CS4 B07
MECHANICAL
B07
B01
MECHANICAL
B01
STAIR 1
CS2
CRAWLSPACE
CS2
CS3
CRAWLSPACE
CS3 B02
MECHANICAL
B02 CS1
CRAWLSPACE
CS1
CS5
CRAWLSPACE
CS5
B07A
MECH
B07A F/Z
NEW 6" FIRE
PROTECTION
LEAD-IN
REFER TO CIVIL
DRAWINGS FOR
PIPING CONTINUATION
CONTRACTOR TO PIPE
INSPECTORS TEST CONNECTION
TO FLOOR DRAIN LOCATED IN B07.
REFER TO PLUMBING DRAWINGS
FOR LOCATION OF DRAIN.
3-101
BREAKROOM
3-101
STAIR 2
ELEV
EX ELEV
ELEV3-100
EX ELEV
MECH
3-1003-102
CONFERENCE
ROOM
3-1023-104
WOMENS
RR
3-1043-106
MENS RR
3-1063-108
TELECOM
3-1083-110
ADMIN
3-110
3-111
ADMIN
3-111
3-112
CLASSROOM
/ IV
TESTING
3-112
3-112B
EX STOR
3-112B 3-112A
EX STOR
3-112A
3-107
ADMIN
3-107
3-105
EX ENTRY
3-105
B07B
STAIR1
B07B
C1-3-1
CORRIDOR
C1-3-1
3-103
ADMIN
3-103
3-109B
CORRIDOR
3-109B
3-211
CLASSROOM
/ IV
TESTING
3-211
3-210
CLASSROOM
/ IV
TESTING
3-210 3-200
CLASSROOM
/ IV
TESTING
3-200 3-206
WOMENS
RR
3-2063-208
MENS RR
3-208
3-203
WAITING
ROOM
3-203 3-201
BREAKROOM
3-201
ELEV
EX ELEV
ELEV
STAIR 2
B07B
STAIR1
B07B3-209
HAC
3-209
3-208A
CORRIDOR
3-208AC2-3-2
CORRIDOR
C2-3-2
F/Z
HAZARD CLASSIFICATION LEGEND
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
ORDINARY HAZARD 2
(0.20 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
FIRE SUPPRESSION LEGEND
FLOOR CONTROL VALVE
F/Z
FIRE - 1 HOUR (NEW/EXISTING)
PARTITION LEGEND
SMOKE (NEW/EXISTING)
EXISTING NON-RATED
WALL TO REMAIN
NEW WALL
NOTE: WALL RATINGS ARE REFRENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2009021688 EXP. 12/31/2023
ENGR REG. NO. PE 20190403952 EXP. 12/31/2023
ENGR REG. NO. PE 2018038407 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGIENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:2 :5
A
M
FIRE SUPPRESSION HAZARD
CLASSIFICATION PLANS
SAB 35 72BLS
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
06/28/2022
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
FX101
SPUR #: 1794.13
N
1/8" = 1'-0"
FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN - BASEMENT1
N
1/8" = 1'-0" 1/ FX001
FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN - FIRST FLOOR2
N
1/8" = 1'-0" 1/ FX001
FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN - SECOND FLOOR3
| Sheets |
| FA001 - FIRE ALARM GENERAL NOTES, LEGEND, AND DIAGRAMS |
| FA101 - FIRE ALARM AUDIBILITY PLANS |
| FA102 - FIRE ALARM FLOOR PLANS |
| FX001 - FIRE SUPPRESSION GENERAL NOTES AND RISER DIAGRAM |
| FX101 - FIRE SUPPRESSION HAZARD CLASSIFICATION PLANS |