Attachment 11 - Electrical - Drawings.pdf
PDF 2 MB Posted
- Attached to
- Y1DA--EHRM Training and Admin Space Support Construction - Kansas City VAMC Federal contract opportunity
- Solicitation number
- 36C77623B0020
About this file
This package includes construction drawings and specifications for electrical, security, and technology upgrades at the Kansas City VA Medical Center. The project involves renovating space to support EHRM training and administration. Drawings show lighting, power, equipment, panel schedules, details and security plans for the renovated areas on various levels of the building. Specifications include lighting, panelboard, and security device schedules with manufacturer and model numbers. The project appears aimed at upgrading critical building systems to support the new facility functions.
View the file
Other files for this federal contract opportunity
Show all 36
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UE
OE
M/G 400A/3P
M/G 400A/3P
C
PC
R
TS
T
100/3
100/3/70
100/3/70/1
100/3/CB
PP
J
GF
OR
OR
OR
EPO
AM
VM
DM
ST
KK
GFR
M
SPD
R
LP1
A1
LIGHT FIXTURE, CEILING MOUNTED
a
LIGHTING TRACK WITH TRACK LIGHT FIXTURES
LIGHT FIXTURE, POLE MOUNTED
LIGHT FIXTURE, WALL MOUNTED
EMERGENCY BATTERY PACK LIGHT FIXTURE,
WALL MOUNTED
EMERGENCY BATTERY PACK LIGHT FIXTURE,
CEILING MOUNTED
EXIT SIGN, WALL MOUNTED, FACE/ARROWS AS INDICATED
EXIT SIGN, CEILING MOUNTED, FACE/ARROWS AS INDICATED
EMERGENCY LIGHT FIXTURE, CEILING MOUNTED
A1E a
A1 a
A1
A1
X1E
X1E
Y1E
Y1E
HOMERUN TO PANELBOARD, ARROWS INDICATE
NUMBER OF CIRCUITS, TICK MARKS INDICATE
NUMBER OF CONDUCTORS. DESIGNATIONS ARE
PANELBOARD AND CIRCUIT NUMBERS.
UNSWITCHED HOT CONDUCTORS SHOWN LEADING
NEUTRAL CONDUCTOR
NEUTRAL CONDUCTOR
SWITCHED HOT CONDUCTORS SHOWN TRAILING
GROUND CONDUCTOR
EQUIPMENT GROUNDING CONDUCTOR IN RACEWAY
ISOLATED GROUNDING CONDUCTOR IN RACEWAY
CONCEALED RACEWAY
EXPOSED RACEWAY
RACEWAY TURNING DOWN
RACEWAY TURNING UP
EQUIPMENT TERMINATION
LOW VOLTAGE CABLE (NOT ROUTED IN CONDUIT)
LIGHT FIXTURE, BOLLARDA1
RECEPTACLE, SIMPLEX, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, DOUBLE-DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, CEILING MOUNTED, NEMA 5-20R, UNO
RECEPTACLE, SPECIAL PURPOSE
RECEPTACLE, TWIST-LOCK
RECEPTACLE, DUPLEX, FLOOR MOUNTED, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, DROP CORD, NEMA 5-20R, UNO
RECEPTACLE, MOUNTED 6" ABOVE COUNTER,
TYPE AS INDICATED ABOVE
RECEPTACLE DESIGNATIONS AS FOLLOWS:
SWITCH, SINGLE POLE
SWITCH DESIGNATIONS AS FOLLOWS:
OCCUPANCY SENSOR, CEILING MOUNTED
POWER PACK FOR LIGHTING CONTROL
JUNCTION BOX
RECEPTACLE ON EMERGENCY POWER
RECEPTACLE, ISOLATED GROUND TYPE
MULTI-OUTLET, SURFACE RACEWAY, 24" ON CENTER,
NEMA 5-20R, UNO
SWITCHBOARD, MOTOR CONTROL CENTER OR DISTRIBUTION
PANELBOARD ON HOUSEKEEPING PAD
PANELBOARD, RECESS MOUNTED
PANELBOARD, SURFACE MOUNTED
TRANSFORMER
DISCONNECT SWITCH, NON-FUSED, 100/3 INDICATES
AMPERES/POLES, CB = CIRCUIT BREAKER TYPE
DISCONNECT SWITCH, FUSED, 100/3/70 INDICATES
AMPERES/POLES/FUSE, CB = CIRCUIT BREAKER TYPE
COMBINATION DISCONNECT SWITCH WITH MOTOR STARTER
100/3/70/1 INDICATES AMPERES/POLES/FUSE/ NEMA STARTER
SIZE, NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE
MAGNETIC MOTOR STARTER, NEMA SIZE AS NOTED,
3-POLE, UNO
CONTACTOR
PHOTOCELL
RELAY
TIME SWITCH
LOW-VOLTAGE TRANSFORMER
PUSH BUTTON, TYPE AS NOTED
VARIABLE FREQUENCY DRIVE WITH DISCONNECT SWITCH
100/3/70 INDICATES AMPERES/POLES/FUSE SIZE,
NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE
UNDERGROUND ELECTRIC LINE
MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
CABINET, RECESS MOUNTED
CABINET, SURFACE MOUNTED
RECEPTACLE, DUPLEX, GROUND-FAULT CIRCUIT
INTERRUPTER, NEMA 5-20R, UNO
MULTI-SERVICE POWER POLE WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
OVERHEAD ELECTRIC LINE
MUSHROOM TYPE PUSH BUTTON, TYPE AS NOTED
TRANSFER SWITCH, RATINGS AS INDICATED
ATS = AUTOMATIC TRANSFER SWITCH
TX#
600AF
3P
500AT
400AS
3P
225AF
275KW STANDBY
480Y/277V, 3PH, 4W
GENERATOR, SEPARATELY DERIVED
SOURCE, TYPE AND RATINGS AS INDICATED
275KW STANDBY
480Y/277V, 3PH, 4W
GENERATOR, NON-SEPARATELY DERIVED
SOURCE, TYPE AND RATINGS AS INDICATED
DRAWOUT CIRCUIT
BREAKER, RATINGS
AS INDICATED
600AF
3P
500AT
CIRCUIT BREAKER,
RATINGS AS
INDICATED
LPS-R
FUSED DISCONNECT
SWITCH, RATINGS
AS INDICATED
400AS
3P
225AF
LPS-R
COMBINATION FUSED
SWITCH AND STARTER,
RATINGS AS
PANELBOARD,
SINGLE-SECTION,
RATINGS PER
SCHEDULES
PANELBOARD,
MULTI-SECTION,
RATINGS PER
SCHEDULES
NEMA 1
AMMETER
VOLTMETER
COMBINATION DIGITAL
SHUNT-TRIP RELAY
KIRK-KEY INTERLOCK
GROUND-FAULT RELAY
UTILITY METER
RELAY
SURGE PROTECTION
AMMETER/VOLTMETER
DEVICE
AUTOMATIC TRANSFER SWITCH WITH BYPASS
TYPE AND RATINGS AS INDICATED
VARIABLE FREQUENCY
DRIVE WITH
DISCONNECT, RATINGS
GROUND CONNECTION
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
GROUND CONNECTION
WITH TEST WELL
CONTACT, OPEN
CONTACT, CLOSED
MOTOR
FEEDER TAGCAPACITOR
SURGE ARRESTER
HEATER
225A 3P
NEMA 1
INDICATED
COMBINATION CIRCUIT
BREAKER AND
STARTER, RATINGS AS
INDICATED AS INDICATED
225A 3P
200A 3P
ATS#
200A 3P
ATS#
TRANSFORMER
TX#
TRANSFORMER,
SHIELDED
200A DEAD-FRONT ELBOW
600A DEAD-FRONT ELBOW
DEAD-FRONT SPLITTER
FAULT INDICATOR
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION CABLE CONNECTION
LIGHTNING PROTECTION GROUND ROD
LIGHTNING PROTECTION CONDUCTOR
MTS = MANUAL TRANSFER SWITCH
LIGHTNING PROTECTION SYMBOLS
ELECTRICAL ONE-LINE DIAGRAM SYMBOLS
OS# = CEILING MOUNTED OCCUPANCY SENSOR, REFER
TO OCCUPANCY SENSOR AND SWITCH SCHEDULE
2 = TWO-POLE WALL SWITCH
3 = THREE-WAY WALL SWITCH
4 = FOUR-WAY WALL SWITCH
D = DIMMER SWITCH
OS# = OCCUPANCY SENSOR WALL SWITCH, REFER
TO OCCUPANCY SENSOR AND SWITCH SCHEDULE
P = SINGLE-POLE, SINGLE-THROW PILOT LIGHT
WALL SWITCH
K = KEYED WALL SWITCH
M = MOTOR RATED SWITCH
WP = WEATHER PROOF SWITCH AND COVER
C = CLOCK HANGER
E = EMERGENCY POWER
GF = GROUND FAULT CIRCUIT INTERRUPTER
IG = ISOLATED GROUND
S = SWITCHED
TR = TAMPER RESISTANT
WP = WEATHER PROOF COVER
WR = WEATHER RESISTANT
XP = EXPLOSION PROOF
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT
FIXTURE SCHEDULE
Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT
FIXTURE SCHEDULE
X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT
FIXTURE SCHEDULE
X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT
FIXTURE SCHEDULE
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
NL = NIGHT LIGHT
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
NL = NIGHT LIGHT
= ARROW INDICATES AIMING DIRECTION
LIGHTING SYMBOLS
POWER EQUIPMENT SYMBOLS
WIRING DEVICE SYMBOLS
CIRCUITING SYMBOLS
ES EMERGENCY SHUNT RELAY
CU
MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT
PLUMBING PLAN NOTE CALL OUT
ELECTRICAL, TECHNOLOGY OR FIRE ALARM
PLUMBING EQUIPMENT DESIGNATION
EQUIPMENT DESIGNATION TAG
OWNER FURNISHED, CONTRACTOR INSTALLED
EQUIPMENT DESIGNATION
NEW WORK TO EXISTING WORK CONNECTION POINT
DETAIL REFERENCE
SECTION CUT DESIGNATION
ELECTRICAL: (AFF, AFG UNLESS NOTED OTHERWISE)
PLAN NOTE CALL OUT
EP-101
EP-101
M (CONT'D)
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
AUDIBLE APPLIANCES (CENTERLINE) 84"
ALARMS (TOP) 48"
ANNUNCIATOR PANELS (TOP) 48"
CLOCK OUTLETS (CENTERLINE) 84"
CONTROLS (TOP) 48"
EXIT SIGNS (WALL-MOUNTED, BOTTOM) 80"
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY) 60"
FIRE ALARM BELL (EXTERIOR) 120"
FIRE ALARM CONTROL PANEL/UNIT (DISPLAY) 60"
INTERCOM (AFEA ONLY) 36"
INTERCOMS (TOP) 48"
PANELS & PANELBOARDS (TOP) 72"
PULL STATIONS (TOP) 48"
PHOTOCELLS 144"
RECEPTACLES (BOTTOM) 18"
RECEPTACLES, EXTERIOR (BOTTOM) 24"
RECEPTACLES, GARAGES (BOTTOM) 26"
RECEPTACLES IN EQUIPMENT ROOMS (TOP) 48"
RECEPTACLES ABOVE COUNTERTOPS (TOP) 44"
REMOTE INDICATING LIGHT, EQUIPMENT ROOMS (TOP) 48"
REMOTE INDICATING LIGHT, FINISHED AREAS (TOP) CEILING
SAFETY SWITCHES & STARTERS 48"
SWITCHES (TOP) 48"
TELEPHONE/DATA/TV OUTLETS (BOTTOM) 18"
VISIBLE APPLIANCES (CENTERLINE) 84"
X
W
V
U
T
S
R
ANNOTATION STANDARD MOUNTING HEIGHTS
P
O
N
M
L
K
J
I
H
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLUOR FLUORESCENT
FO FIBER-OPTIC
FP FIRE PROTECTION
FT FEET OR FOOT
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G
F
E
D
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMER. MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
ETD EXISTING TO BE DEMOLISHED
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
C CONDUIT
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/
OWNER
CFE CONTRACTOR FURNISHED
EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
C
B
A
ABBREVIATIONS
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VCM VERTICAL CABLE MANAGER
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
TC TIME CLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REC RECESSED
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RU RACK UNIT
N NEUTRAL
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
JB OR J-BOX JUNCTION BOX
XFER TRANSFER
XFMR TRANSFORMER
XP EXPLOSION PROOF
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
IESNA ILLUMINATION ENGINEERING
SOCIETY OF NORTH AMERICA
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
G OR GND GROUND OR GENERATOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR
PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
POE POWER OVER ETHERNET
PP PATCH PANEL
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
1P SINGLE POLE
1PH SINGLE-PHASE
3P THREE POLE
3PH THREE-PHASE
3W THREE WIRE
4W FOUR WIRE
A/C AIR CONDITIONING
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR
ARMORED
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER,
AUTOMATIC FREQUENCY
CONTROL, OR AVAILABLE FAULT
CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
HCM HORIZONTAL CABLE MANAGER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BLK BLOCK
BPIP BOILER PLANT INSTRUMENTATION
PANEL
BRKR BREAKER
BYP BY PASS
IC INSULATION CONTACT
GENERAL NOTES
APPLICABLE CODES AND STANDARDS
1. ELECTRICAL PLANS AND SECTIONS ARE INTENDED TO
ACCURATELY ILLUSTRATE THE SCOPE OF WORK, BUT ARE STILL
DIAGRAMMATIC IN NATURE.
2. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO
BE INSTALLED. THE CONTRACTOR IS RESPONSIBLE FOR
ENSURING THAT ALL SYSTEMS ARE FULLY FUNCTIONAL AND
COMPLIANT WITH APPLICABLE CODES.
3. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS
WITH BUILDING DISCIPLINES. HOWEVER, COORDINATION WITH
OTHER TRADES IS REQUIRED.
4. COORDINATE WITH SCHEDULE WITH THE CONTRACTING
OFFICER'S REPRESENTATIVE BEFORE THE START OF WORK.
5. PANELBOARD'S AND OTHER ELECTRICAL EQUIPMENT REQUIRE
SHUTDOWN. COORDINATE SERVICE SHUT-DOWN FOR ALL
EQUIPMENT WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE.
6. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND
TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES
SHALL HAVE DIVIDERS BETWEEN DEVICES.
7. UPDATE ALL PANELBOARD SCHEDULES AFFECTED AT THE
COMPLETION OF THE PROJECT.
A. AMERICANS WITH DISABILITIES ACT
B. ASHRAE STANDARD 90.1-2010 – ENERGY STANDARD FOR
BUILDINGS
C. ILLUMINATING ENGINEERING SOCIETY (IES) HANDBOOK, 10TH
EDITION
D. IBC 2021 – INTERNATIONAL BUILDING CODE
E. IEBC 2021 – INTERNATIONAL EXISTING BUILDING CODE
F. IECC 2021 – INTERNATIONAL ENERGY CONSERVATION CODE
G. JCAHO EC 7.40 – EMERGENCY ELECTRICAL POWER SYSTEM
INSPECTION, MAINTENANCE, AND TESTING
H. NFPA 70-2020 - NATIONAL ELECTRICAL CODE (NEC)
I. NFPA 99-2021 – HEALTHCARE FACILITIES CODE
J. NFPA 101-2021 – LIFE SAFETY CODE
K. NFPA 110-2022 – STANDARD FOR EMERGENCY AND STANDBY
POWER SYSTEMS
L. NFPA 111-2022 – STANDARDS FOR STORED ENERGY POWER
SYSTEMS
M. VA PG-18-10 ELECTRICAL DESIGN MANUAL, DECEMBER 2019
N. VA PG-18-10 LIGHTING DESIGN MANUAL, DECEMBER 2015
CCTV
CR
DB
DB
DM
EL
EO
GB
KP
MD
PB
RE
EC
KT
GO
C
CLOSED CIRCUIT TELEVISION LINE, MIN. 1" RACEWAY
CARD READER, PROXIMITY TYPE
DOOR BELL PUSHBUTTON
DOOR BELL CHIME
DOOR POSITION MONITOR
ELECTRIFIED LOCKING DEVICE, REQUEST TO EXIT SENSOR,
LATCH BOLT MONITOR, AND DOOR POSITION SWITCH
ELECTRIFIED LOCKING DEVICE
GLASS BREAK DETECTOR
INTRUSION DETECTION KEYPAD
INTRUSION DETECTION MOTION DETECTOR
DURESS PUSHBUTTON
REQUEST TO EXIT BUTTON
SINGLE VIEW SECURITY CAMERA
EMERGENCY CALL STATION
RFID KEY TAG READER
GATE OPENER
DUAL VIEW SECURITY CAMERA
180-DEGREE PANORAMIC VIEW SECURITY CAMERA
270-DEGREE PANORAMIC/MULTI-IMAGE VIEW
360-DEGREE PANORAMIC/MULTI-IMAGE VIEW
SECURITY CAMERA
SECURITY CAMERA
SECURITY SYMBOLS
MA MOTION-ACTIVATED
DC DOOR CONTROLLER
IC MASTER INTERCOM STATION
IC INTERCOM STATION
M th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGIENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:3
:3
ELECTRICAL LEGEND AND NOTES
MIJ 55 72BEN
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
E-000
SPUR #: 1794.13
No. REVISION DESCRIPTION DATE
06/28/2022
COMM
T
T T
E E
E E
E E
E E
E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E E
E E
E E
E E
E E
E
CRIC
GO
T
T
T
T T
T T
T
T
GO
J
T
T
T
T
T
T
HANDHOLE - TURF AREAS
NO SCALE
TELECOMMUNICATIONS UNDERGROUND
DUCT BANK DETAIL
NO SCALE
ELECTRICAL
ROOM MB-575
SWBD T9 (ETR)
BLDG 1
NEW TRAFFIC H-20 RATED
HANDHOLE SIMILAR TO
FIBERCRETE FHR-24-36-36.
EXISTING
UTILITY
TUNNEL
ES101
ES101
(1) 1" CONDUIT
WITH 12 STRAND
FIBER (6 SINGLE
AND 6 MULTIMODE)
ELECTRICAL
ROOM MB-304
SWBD CDP-1
(ETR)
TRANSITION FROM BASEMENT
TO EXTERIOR CONCRETE
ENCASED DUCT BANK.
1.5" CONDUIT FOR DATA
CABLING TO GATE ADDESS
CONTROLS AND POE
COMERAS. ROUT THROUGH
BASEMENT TIGHT TO
STRUCTURE ABOVE.
1.5" CONCRETE
ENCASED CONDUIT FOR
DATA CABLING TO GATE
ACCESS CONTROLS
AND POE CAMERAS.
USE RED CONCRETE
DYE.
ES101
BLDG 56
BLDG 1
BLDG
E-500
1.25"
CONCRETE-
ENCASED
CONDUIT FOR
DATA CABLING
TO HANDHOLE
12"x22"
(NOMINAL I.D.)
HANDHOLE
12"x22"
(NOMINAL I.D.)
HANDHOLE
CONTINUATION
ON DETAIL 1,
SHEET ES101.
CONTINUATION
ON DETAIL 3,
SHEET ES101.
1.25" CONCRETE-
ENCASED
CONDUIT FOR
DATA CABLING
TO EXIT GATE
STUB UP CONDIUT
IN HOLLOW POLE
1.5" CONCRETE ENCASED CONDUIT
FOR DATA CABLING FROM BUILDING 3
1" CONCRETE ENCASED CONDUIT FOR
DATA CABLING TO GATE CAMERAS
1" CONCRETE-
ENCASED CONDUIT
FOR DATA CABLING
TO GATE ACCESS
CONTROL DEVICES
ES101
ES101
BP
CONTINUATION
ON DETAIL 2,
SHEET ES101.
12"x22" (NOMINAL
I.D.) HANDHOLE
1.25" CONCRETE-
ENCASED CONDUIT
FOR DATA CABLING
FROM ENTRANCE
GATE TO EXIT GATE
1" CONCRETE-ENCASED
CONDUIT FOR DATA
CABLING TO GATE ACCESS
CONTROL DEVICES
ES101
BP
PROVIDE TIER 22 LOCKABLE COVER
WITH "TELECOMMUNICATIONS"
IMPRINTED IN LID.
HANDHOLE (SEE SPECIFICATIONS)
LINE SIDES OF
EXCAVATION WITH
13.6 KG (30 LBS.)
FELT PAPER
GRADE, FEATHER & TAMP
BACKFILL TO CREATE FLUSH
INSTALLATION AND POSITIVE
DRAINAGE AWAY FROM BOX
CLEAN 19mm (3/4")
CRUSHED ROCK
(2
M
IN
m m
1. CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.
2. PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS WHEN
CROSSING OR PLACED IN ROADWAYS.
3. MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24") OR AS
OTHERWISE SPECIFIED IN SECTION 26 05 41.
4. PROVIDE MINIMUM 152mm (6") SPACE BETWEEN POWER AND
TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.
5. INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS.
76mm
3"
76mm
3"
76mm
3" m m m m
(1) 3" CONDUIT WITH (3) 1" INNER DUCTS
FOR TELECOMM. WITHIN THE INNER
DUCTS, PROVIDE (2) SETS OF 12-STRAND
ARMORED FIBER (6-STRAND MULTIMODE
OM4, AND 6-STRAND SINGLE MODE OS2)
(1) SPARE 3" CONDUIT FOR
POWER FOR GATE
OPERATOR
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGIENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:3
:3
ELECTRICAL AND SECURITY SITE PLAN
MIJ 56 72BEN
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
ES101
SPUR #: 1794.13
N
1" = 30'-0"
ELECTRICAL SITE PLAN1
ELECTRICAL KEYNOTES
4 STUB UP 1.5" CONDUIT TO TELECOM ROOM ABOAVE, REFER TO DETAIL 4/EP101 FOR
CONTINUATION.
5 STUB UP EMERGENCY POWER ELECTRICAL FEED TO PANEL 3-CR-OIT ABOVE (REFER TO SHEET
EP101 FOR CONTINUATION).
13 PROVIDE (4) 3" CONDUITS FROM SWITCHBOARD T9 TO NEW HANDHOLE BEHIND BUILDING 3.
14 PROVIDE NEW 24" X 24" X 10" (MIN.) PULL BOX.
16 TRANSITION CONDUIT PATHWAYS FROM THE EXISTING CORRIDOR TO THE EXISTING UTILITY
TUNNEL CONNECTING TO BUILDING 3.
17 ROUTE CONDUIT FROM SWITCHBOARD T9 LOCATED IN ELECTRICAL ROOM MB-575 TO ABOVE
DEILING IN CORRIDOR CB-54.
19 FASTEN THE NEW CONDUITS ABOVE EXISTING HYDRONIC PIPING TO EXISITNG STRUCTURE OR
PROVIDE NEW FASTENERS ON THE OPPOSITE WALL TO THE PIPING AT LEAST 24" ABOVE
FINSHED FLOOR. PROVIDE PULLBOX ALONG CONDUIT PATH AT A MINIMUM OF EVERY 150 FT.
20 ROUTE CONDUIT FROM FINISHED SPACE INTO CRAWL SPACE.
21 CONCRETE ENCASED DUCT BANK WITH FROM BASEMENT TO HANDHOLE. DUCT BANK SHALL BE
DYED WITH RED CONCRETE DYE.
24 PROVIDE AND INSTALL GATE ARM OPERATOR WITH GATE POSITION MONITOR TO INDICATE THE
POSITION OF THE GATE ARM. PROVIDE INTEGRATIONS TO ALLOW THE ACCESS CONTROL
SYSTEM TO CONDUCT POSITION MONITORING, REMOTE OPENING, OPEN SCHEDULE, ABILITY
TO MAINTAIN OPEN STATE FOR SCHEDULED PERIOD OF TIME, AND TO OPEN ON AUTHORIZED
TRIPLE AUTHENTICATION. TYPICAL.
26 PROVIDE VEHICLE DETECTION LOOP. COORDINATE CONNECTION INTO GATE OPERATING
SYSTEM CONTROLS. TYPICAL.
28 PROVIDE CONDUIT AND CONDUCTORS FROM SWITCHBOARD CDP-1 TO NEW PANELBOARD
3-CR-OIT IN BUILDING 3. REFER TO ONE-LINE FOR MORE INFORMATION.
35 PROVIDE NEW 24" X 24" X 10" (MIN.) PULL BOX FOR EACH CONDUIT SET JUST AFTER ENTERING
THE TUNNEL. WALL OR CEILING MOUNT IN THE LEAST OBSTRUCTIVE LOCATION. COORDINATE
EXACT LOCATION WITH VA COR AND ELECTRICAL SHOP SUPERVISOP.
36 PROVIDE NEW 24" X 24" X 10" (MIN.) PULL BOX FOR EACH CONDUIT SET MID WAY THROUGH THE
TUNNEL. WALL OR CEILING MOUNT IN THE LEAST OBSTRUCTIVE LOCATION. COORDINATE
EXACT LOCATION WITH VA COR AND ELECTRICAL SHOP SUPERVISOP.
N
3/16" = 1'-0"
ELECTRICAL SITE PLAN - ENTRY GATE2
N
3/16" = 1'-0"
ELECTRICAL SITE PLAN - EXIT GATE3
A (ETR)
MDP-3 (ETR)
BP (ETD)
B3-1 (ETR)
STAIR 1
STAIR 2
ETR
ETR
ETR
ETR ETR
ETR
ETR
ETR
ETR
STAIR 1
EXISTING
3-103
EXISTING
3-101
EXISTING
3-102
EXISTING
3-104
EX BREAK ROOM
3-108
EX MENS RESTROOM
3-106
EX WOMENS RESTROOM
3-105
EXISTING
3-111
EXISTING
3-110
EXISTING
3-107
EXISTING AUDITORIUM
3-112
EXISTING
3-109
EX HAC CLOSET
3-111A
EX CORRIDOR
3-120
EX ELEV MECH
3-100
EX ELEV
ELEV
EXISTING
3-101A
EXISTING
3-112A
EXISTING
3-112B
EXISTING
3-204
EXISTING
3-200
EXISTING
3-201
EXISTING
3-202
EXISTING
3-203EXISTING
3-205
EXISTING SPECIMEN COLLECTION
3-206
EXISTING
3-207
EXISTING CORRIDOR
3-208
EXISTING
3-209
EXISTING
3-210
EXISTING
3-211
EXISTING
3-212
EXISTING
3-201A
EX ELEV
ELEV
STAIR
MECHANICAL
B07
MECHANICAL
B02 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGIENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:3
:3
ELECTRICAL LIGHTING DEMOLITION
PLANS
MIJ 57 72BEN
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
ED101
SPUR #: 1794.13
N
1/8" = 1'-0"
ELECTRICAL LIGHTING DEMOLITION PLAN - BASEMENT1
N
1/8" = 1'-0"
ELECTRICAL LIGHTING DEMOLITION PLAN - LEVEL 12
N
1/8" = 1'-0"
ELECTRICAL LIGHTING DEMOLITION PLAN - LEVEL 23
ELECTRICAL GENERAL NOTES:
A. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S REPRESENTATIVE
BEFORE THE START OF WORK.
B. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY ALL EXISTING
CONDITIONS BEFORE START OF WORK.
C. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE SHUTDOWN. COORDINATE
SERVICE SHUTDOWN FOR ALL EQUIPMENT WITH CONTRACTING OFFICER'S
REPRESENTATIVE.
D. THE DEMOLITION DRAWINGS ARE SCHEMATIC, BASED ON AVAILABLE INFORMATION AND
MAY NOT REPRESENT ALL DEVICES/EQUIPMENT REQUIRED FOR DEMOLITION. FIELD VERIFY
ALL EXISTING WORK PRIOR TO BID.
E. REMOVE ALL LIGHTING AND LIGHTING CONTROLS IN THE AREA OF WORK. DEMOLISH
EXISTING POWER CIRCUIT BACK TO NEAREST JUNCTION BOX FOR REUSE. MAINTAIN
CONTINUITY OF LIGHTING AREAS THAT ARE NOT IN THE AREA OF WORK.
No. REVISION DESCRIPTION DATE
ELECTRICAL KEYNOTES
32 SALVAGE EXISTING LIGHT AND PROTECT FOR RE-INSTALLATION. COORDINATE STORAGE WITH
VA COR.
J J
J
J
J
J
J
MDP-3 (ETR)
A (ETR)
FCU-1
(ETD)
CP-1
CP-2
BP (ETD)
B3-1 (ETR)
ACCU-1
(ETD)
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETDETDETDETD
ETD
ETD
ETD
ETD
ETD ETD
ETD ETD ETD
ETD
ETD
ETD
22 2
2 2
ACU-1
(ETD)
AHU-1
AHU-2
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD
ETD(ETD)
ETD
ETD
L-2
L-1
(ETD)
EXISTING
3-204
EXISTING
3-200
EXISTING
3-201
EXISTING
3-202
EXISTING
3-203EXISTING
3-205
EXISTING SPECIMEN COLLECTION
3-206
EXISTING
3-207
EXISTING CORRIDOR
3-208
EXISTING
3-209
EXISTING
3-210
EXISTING
3-211
EXISTING
3-212
EXISTING
3-201A
EX ELEV
ELEV
EXISTING
3-103
EXISTING
3-101
EXISTING
3-102
EXISTING
3-104
EX BREAK ROOM
3-108
EX MENS RESTROOM
3-106 EX WOMENS RESTROOM
3-105
EXISTING
3-110
EXISTING
3-107EXISTING
3-109
EX CORRIDOR
3-120
EXISTING
3-111
EXISTING AUDITORIUM
3-112
EX HAC CLOSET
3-111A
EXISTING
3-112A
EXISTING
3-112B
EXISTING
3-101A
EX ELEV
ELEV
MECHANICAL
B07
ELEC
B07A
MECHANICAL
B02
MECHANICAL
B01
EF-1
(ETD)
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGIENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:3
:3
ELECTRICAL POWER DEMOLITION
PLANS
MIJ 58 72BEN
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
ED201
SPUR #: 1794.13
N
1/8" = 1'-0"
ELECTRICAL POWER DEMOLITION PLAN - BASEMENT1
N
1/8" = 1'-0"
ELECTRICAL POWER DEMOLITION PLAN - LEVEL 12
N
1/8" = 1'-0"
ELECTRICAL POWER DEMOLITION PLAN - LEVEL 23
ELECTRICAL GENERAL NOTES:
A. COORDINATE WORK SCHEDULE WITH THE CONTRACTING OFFICER'S REPRESENTATIVE
BEFORE THE START OF WORK.
B. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES. VERIFY ALL EXISTING
CONDITIONS BEFORE START OF WORK.
C. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE SHUTDOWN. COORDINATE
SERVICE SHUTDOWN FOR ALL EQUIPMENT WITH CONTRACTING OFFICER'S
REPRESENTATIVE.
D. THE DEMOLITION DRAWINGS ARE SCHEMATIC, BASED ON AVAILABLE INFORMATION AND
MAY NOT REPRESENT ALL DEVICES/EQUIPMENT REQUIRED FOR DEMOLITION. FIELD VERIFY
ALL EXISTING WORK PRIOR TO BID.
ELECTRICAL KEYNOTES
1 REMOVE CONDUIT AND CONDUCTORS FEEDING MECHANICAL UNIT SHOWN BACK TO
UPSTREAM PANELBOARD/ SWITCHBOARD. REMOVE ASSOCIATED DISCONNECT. COORDINATE
DEMOLITION WITH MECHANICAL CONTRACTOR.
2 DEMOLISH ALL RECEPTACLES AND JUNCTION BOXES IN THIS ROOM BACK TO UPSTREAM
PANELBOARD.
18 REMOVE CONDUIT AND CONDUCTORS FEEDING PUMP SHOWN BACK TO UPSTREAM
PANELBOARD. REMOVE ASSOCIATED DISCONNECT. COORDINATE DEMOLITION WITH
MECHANICAL CONTRACTOR.
29 REPLACE EXISTING 42 POLE PANEL WITH 72 POLE PANEL. RELOCATE ALL EXISTING TO REMAIN
CIRCUITS. SEE PANEL SCHEDULE FOR MORE INFORMATION.
N
1/8" = 1'-0"
ELECTRICAL POWER DEMOLITION PLAN - ROOF4
PP
PP
PP
PP
PP
PP
PP
PP
PP
PP
PP
PP
PP
ADMIN
3-111
CLASSROOM / IV TESTING
3-112
EX HAC CLOSET
3-111A
EX STOR
3-112A
BREAKROOM
3-101
EX ENTRY
3-105
CONFERENCE ROOM
3-102
TELECOM
3-108
ADMIN
3-110
ADMIN
3-103
ADMIN
3-107
MENS RR
3-106
WOMENS RR
3-104
CORRIDOR
C1-3-1
LV1
OS2
LV1
LV1
LV1
LV1
LV1
LV1
LV1
LV1
LV1LV1
LV1
OS2
OS2OS2
OS2 OS2
OS2 OS2
OS2OS2
OS2
OS2
OS2
OS1 OS1
LV1
B3-1 (ETR)
OS2
A
B
AA
A
AA
AA
A A A
AAA
A
A
A
A
A
B B
A A
B B
A
B
A
B
A
B
A
B
A
A A
A A
ETR
X
X
X
X
RC1
RC1
OS1
RC1
S1E
S1E
X
AG AG
S1E
S1E S1E
AB
A A
PS
PS
PS
PS 1
A
B3-1
EX ELEV MECH
3-100
PS
PS
PS
PS
Y1E
Y1E
Y1E
V1
X
ETR ETR
X
STAIR 1
STAIR 2
EX STOR
3-112B
A A
B
B
A
BB BBB
X
XX
X
Y1E
ETR
ETR
B
BREAKROOM
3-201
CLASSROOM / IV TESTING
3-200
CLASSROOM / IV TESTING
3-210
HAC
3-209
WAITING ROOM
3-203
CLASSROOM / IV TESTING
3-211
MENS RR
3-208
WOMENS RR
3-206
CORRIDOR
C2-3-2
A A A
A A
A A A A
A
B B B
A
B
A A
AB
A A
A
A
A
OS2OS2
OS2 OS2
OS2
OS2OS2
OS2
OS2 OS2
OS2
LV1
LV1
OS1
LV1
LV1
LV1
OS1 OS1
X
X
RC1
RC1
RC1
RC1
RC1
AG AG
AA A A
PS
PS
PS
A
PSPS PS
V1
B
BB
B B
A
B
A
A A
STAIR 2
STAIR 1
X
ETR
ETR
ETR
ETR
MDP-3 (ETR)
A (ETR)
BP (NEW)
MECHANICAL
B07
MECHANICAL
B02
MECHANICAL
B01 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGIENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:3
:3
ELECTRICAL LIGHTING PLANS
MIJ 59 72BEN
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
EL101
SPUR #: 1794.13
N
1/8" = 1'-0"
ELECTRICAL LIGHTING PLANS - LEVEL 12
N
1/8" = 1'-0"
ELECTRICAL LIGHTING PLANS - LEVEL 23
N
1/8" = 1'-0"
ELECTRICAL LIGHTING PLANS - BASEMENT1
No. REVISION DESCRIPTION DATE
ELECTRICAL KEYNOTES
33 LIGHT SHOWN IS EXISTING TO BE REINSTALLED. CONNECT TO EXISTING POWER CIRCUIT AND
LIGHTING CONTROLS.
ADMIN
3-111
EX ELEV MECH
3-100
EX ELEV
ELEV
STAIR 1
CLASSROOM / IV TESTING
3-112
EX HAC CLOSET
3-111A
EX STOR
3-112A
EX STOR
3-112B
BREAKROOM
3-101
EX ENTRY
3-105
CONFERENCE ROOM
3-102
TELECOM
3-108
ADMIN
3-110
ADMIN
3-103
ADMIN
3-107
MENS RR
3-106
WOMENS RR
3-104
CORRIDOR
C1-3-1
B3-1 (ETR)
+72"
+72"
EP101
ETR
A
A
A
BP
A
A
A
A
A
B3-1
B3-1
B3-1
B3-1
A
8,10,12
MDP-3
BP
BP
A
B3-1
B3-1
B3-1
B3-1
A
A
A
DC
STAIR 2
A +66"
WP
BP
BREAKROOM
3-201
CLASSROOM / IV TESTING
3-200
CLASSROOM / IV TESTING
3-210
HAC
3-209
WAITING ROOM
3-203
CLASSROOM / IV TESTING
3-211
MENS RR
3-208
WOMENS RR
3-206
CORRIDOR
C2-3-2
+72"
+72"
+72"
BP
A
BP
BP
BP
BP
BP
BP
BP
A
A
A
A
BP
A
USB USB
USB
A
BP
STAIR 2
MDP-3 (ETR)
A (ETR)
BP (NEW)
MECHANICAL
B02
MECHANICAL
B07
MECHANICAL
B01
M
FCU-1
TELECOM
3-108
GROUND BAR (NEW)
3-CR-OIT
3-CR-OIT
3-CR-OIT
3-CR-OIT 8,10
3-CR-OIT
3-CR-OIT
(NEW)
26,28,30
BP
1,3,5
3-CR-OIT
SECURITY PANEL
EF-1
HRU-1 HRU-2 DOAU-2DOAU-1
111111
(TYPICAL)
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGIENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:3
:3
ELECTRICAL POWER PLANS
MIJ 60 72BEN
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
EP101
SPUR #: 1794.13
N
1/8" = 1'-0"
ELECTRICAL POWER PLAN - LEVEL 12
N
1/8" = 1'-0"
ELECTRICAL POWER PLAN - LEVEL 23
N
1/8" = 1'-0"
ELECTRICAL POWER PLAN - BASEMENT1N
1/4" = 1'-0"
TELECOM ROOM 3-108 ENLARGED PLAN4
N
1/8" = 1'-0"
ELECTRICAL LIGHTNING PROTECTION PLAN - ROOF5
ELECTRICAL KEYNOTES
11 TIE INTO EXISTING LIGHTNING PROTECTION SYSTEM.
30 RELOCATE EXISTING LIGHTNING PROTECTION AIR TERMINALS TO THE TOP OF THE METAL
RAILING. TIE METAL RAILING INTO EXISITNG LIGHTING PROTECTION SYSTEM. BOND BOTH
RAILINGS TO EACH OTHER.
31 PROVIDE DOOR CONTROLLER PUSH PLATE. CONNECT TO EXISTING DOOR OPENER AND
EXISTING DOOR CIRCUIT.
B3-1 (ETR)
30/2/NF/3R30/2/NF/3R
8,10
3-CR-OIT
16,18
B3-1
8,10
3-CR-OIT
16,18
B3-1
B3-1
BP
M
M
M
M
M
M
M
M
M
M
M
FCU-2
VRF-2-6
VRF-1-6
VRF-1-5
FCU-1
VRF-1-8
VRF-1-4
SB-1
VRF-1-3
VRF-1-2
VRF-1-1-2
VRF-1-1-1
CU-2
CU-1
UH-2
46,48,50
BP
30/3/30/NEMA-1
SOLO-1
SOLO-2
SOLO-4
SOLO-3
SOLO-6
SOLO-5
SOLO-7
A
(PART)
M
M
BP
SP-1
M
M
M
M
M
M
VRF-2-5
VRF-2-4
VRF-2-3VRF-2-1
VRF-2-2
SB-2
VRF-2-7
VRF-1-7
SOLO-9
SOLO-8
SOLO-10
SOLO-11
SOLO-12
A
(PART)
EF-2
M
M
M
BP
DOAU-2
EF-1
HRU-1 HRU-2DOAU-1
200/3/125/3R
200/3/125/3R 100/3/80/3R 100/3/80/3R
M
BP
15,17,19
MDP-3
27,29,31
MDP-3
21,23,25
MDP-3
14,16,18
MDP-3
BP
WP/WR WP/WR
EF-3
BP
M
UH-1
HX-1
HWP-2
HWP-1
PGP-1
MECHANICAL
B07
MECHANICAL
B01
MECHANICAL
B02
STAIR 1
MDP-3 (ETR)
A (ETR)
BP (NEW)
34,36,38
BP
35,37,39
BP
40,42,44
BP
BP
43,45,47
BP
30/3/30/NEMA-1
30/3/30/1
30/3/30/1
30/3/30/1
PS-1
WH-1
61,63,65
BP
BP
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGIENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:3
:3
ELECTRICAL EQUIPMENT POWER PLANS
MIJ 61 72BEN
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
EP111
SPUR #: 1794.13
N
1/8" = 1'-0"
ELECTRICAL EQUIPMENT POWER PLAN - LEVEL 12
N
1/8" = 1'-0"
ELECTRICAL EQUIPMENT POWER PLAN - LEVEL 23
N
1/8" = 1'-0"
ELECTRICAL POWER PLAN - ROOF4 N
1/8" = 1'-0"
ELECTRICAL EQUIPMENT POWER PLAN - BASEMENT1
ELECTRICAL KEYNOTES
12 POWER CIRCUIT IS PENETRATING THE ROOF AT THE EQUIPMENT. COORDINATE ROOF SEALING
AND WARRANTY REQUIREMENTS WITH ROOFING CONTRACTOR PRIOR TO ROUGH-IN. TYPICAL.
34 RELOCATE EXISTING WATER HEATER DISCONNECT. RELOCATE POWER FOR WATER HEATER
FROM OLD LOCATION TO NEW LOCATION. PROVIDE EXTRA LENGTH OF WIRE AS REQUIRED TO
MAKE NEW CONNECTION.
CONTROL PEDESTAL BASE DETAIL
NO SCALE
EMPLOYEE GATE ACCESS
LIGHTNING PROTECTION
CONDUCTOR
UNIVERSAL PARALLEL
CABLE SPLICER
BUTT END STRAIGHT
CABLE SPLICER
PARALLEL CABLE
SPLICER
LIGHTNING PROTECTION
BONDING CONDUCTOR
TO BONDS
m m
(1
M
A X m m
(1
M
A X
SECTION "A-A"
ELEVATION
RIGID STEEL CONDUIT
FOR SUPPORT PER N.E.C.
ART. 314
ROOF PENETRATION AND
CONDUIT SUPPORT PER
SD260533-05
RIGID STEEL CONDUIT
FOR WIRING
A
A
CAST METAL
"WHILE-IN-USE"
WP COVER(S) &
RECEPTACLE(S).
CAST METAL, 2-GANG, NEMA
3R JUNCTION BOX WITH
THREADED HUBS.
ADHESIVE STYLE CABLE
FASTENER MOUNTED TO
ROOF
LIGHTNING PROTECTION
CONDUCTOR
CABLE FASTENER WITH
STAINLESS STEEL
HARDWARE, CAULK
PENETRATIONS
BONDING PLATE MOUNTED
WITH STAINLESS STEEL
FASTENERS, CAULK
PENETRATIONS
GENERAL NOTE:
1. ALL HARDWARE SHOWN SHALL BE STAINLESS STEEL.
2. PROVIDE 1 MOUNTING POINT PER 12" OF BAR LENGTH.
3. HOLES MAY BE ADDED IF REQUIRED.
1"
STEEL EXPANSION
ANCHOR
SECTION
1/4" DIA. HOLE
TYP OF (8)
2'-0" MIN
1/4" THICK
CU BUSS
1/2" FENDER WASHERS (EACH SIDE)
1/2" STANDARD WASHER
1/2" LOCK WASHER
1/2" NUT
1/2"DIA. x2"L. BOLT
TYP. OF (2)
3/8" DIA. HOLE
TYP. OF (6)
3" DEEP FIBERGLASS
CHANNEL SAME
LENGTH AS CU BUSS
1/4" DIA.
MOUNTING HOLES
TYP. OF (4)
[51mm]
MIN
2"
[1 m m
/8
1 1/2" TYP
2" 1" 1"
"CONDUIT CLAMP. SIZE
AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
REFER TO PLANS FOR
QUANTITY & SIZE OF
CONDUITS
GENERAL NOTES:
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL
LONGER THAN 915mm (36") SHALL BE INSTALLED WITH A
CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED
METHOD PER SPECIFICATION 26 05 33, RACEWAY AND BOXES
FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO
SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT
REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
LENGTH AS REQUIRED
LOCKING SQUARE
WASHER & LOCKNUT
9.52mm (3/8") MIN
GALVANIZED THREADED
ROD, TYP.
WASHER &
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
LOCKING
SQUARE
WASHER &
LOCKNUT
CONDUIT CLAMP.
SIZE AS
REQUIRED
CONDUIT,
TYP.
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
STEEL
EXPANSION
ANCHOR
ROOF
SEAL-OFF
FITTING,
TYP.
9.52mm (3/8") MIN
GALVANIZED
THREADED ROD,
TYP.
STAINLESS CLAMP, TYP.
WATER CUT-OFF MASTIC
COMPATIBLE WITH ROOF
MEMBRANE
ROOF MEMBRANE
BATT INSULATION
CONDUIT CLAMP. SIZE AS
REQUIRED
PREFABRICATED FORMED 1.52mm
(0.06") THICK ALUMINUM FLASHING
ROUND COLLAR WITH MIN. 76mm (3")
WIDE FLANGE. ATTACH TO ROOF
PER MANUFACTURER'S
INSTRUCTIONS
MULTIPLE MEMBRANE STRIPPING PLIES
FEATHERED AT FIELD OF ROOF BY
ROOFING CONTRACTOR. PRIME
FLANGE BEFORE STRIPPING.
SEALANT AT PENETRATION TO
MEMBRANE JUNCTURE BY
ROOFING CONTRACTOR
PREFABRICATED RUBBER BOOT
CAP WITH GRADUATED STEPS &
WEATHER-PROOF PRESSURE
SEAL TO COLLAR
GENERAL NOTES:
1. MAINTAIN A MINIMUM CLEARANCE OF 305mm (12") ON ALL SIDES OF ROOF PENETRATION
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.
2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.
3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.
4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO ENSURE
PROPER METHODS & MATERIALS ARE USED TO MAINTAIN ROOF WARRANTY.
STACKED JUNCTION BOXES
SIDE-BY-SIDE JUNCTION BOXES
HIGH VOLTAGE WIRING
JUNCTION BOX
COVER PLATE
EXTENSION BOX
POWER PACK LOW VOLTAGE WIRING
JUNCTION BOXES
LOW VOLTAGE WIRING
HIGH VOLTAGE WIRING
NOTE: DO NOT MOUNT
POWER PACKS CLOSER
THAN 6" TO 12" FROM
ANY SENSOR
TYPICAL MOUNTING
ARCHITECTURAL
CEILING GRID
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS
AND USING THE RECOMMENDED MOUNTING HARDWARE.
LUMINAIRE.
REFER TO
SCHEDULE
ACOUSTICAL CEILING
TILE (TYP)
LUMINAIRE.
REFER TO
SCHEDULE
FIXTURE WHIP FROM
JUNCTION BOX
(1829mm (6') LONG
MAX.)
LUMINAIRE SUSPENSION
WIRES REFER TO
SPECIFICATION
SECTION 26 51 00
3 TWIST MINIMUM
(TYP)
LUMINAIRE MANUFACTURER'S
MOUNTING HARDWARE
REFER TO SPECIFICATION SECTION
26 51 00
WIRE TIE OR SCREW
BAR HANGER TO CROSS
BEAM TYP.
CEILING MAIN
BEAM
CEILING
CROSS BEAM
FIXTURE WHIP FROM
JUNCTION BOX (1829mm (6')
LONG MAX)
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS
AND USING THE RECOMMENDED MOUNTING HARDWARE.
RECESSED CAN
LUMINAIRE
CEILING BEAM
RECESSED CAN
LUMINAIRE
REFER TO
SCHEDULE.
GYPSUM
BOARD (TYP)
LUMINAIRE
BAR HANGERS
CEILING HANGER
WIRE, TYP.
LUMINAIRE SUSPENSION WIRES
REFER TO SPECIFICATION SECTION 26 51 00
ARCHITECTURAL
CEILING GRID
HANGER WIRE AND MOUNTING
CHANNEL ATTACHED TO STRUCTURE
REFER TO SPECIFICATION SECTION
26 51 00
ARCHITECTURAL
CEILING GRID
ACOUSTICAL
CEILING
TILE (TYP)
ARCHITECTURAL
CEILING GRID
WIRE TIE THROUGH
MOUNTING CHANNEL &
CROSS BEAM, TYP.
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS
AND USING THE RECOMMENDED MOUNTING HARDWARE.
LOCKING SQUARE
WASHER & NUT
6.35mm (1/4") SCREW
JUNCTION BOX
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
FIXTURE WHIP FROM JUNCTION BOX
(1829mm (6') LONG MAX)
CEILING HANGER WIRE
DOOR POSITION
SWITCH
ACCESSIBLE CEILING
PROVIDE DOUBLE-GANG
BACKBOX WITH SINGLE-GANG
PLASTER RING FOR DOOR
MOTION DETECTOR.
LOCATION PER PLANS.
3/4" CONDUIT
(TYPICAL, UNO)
ELECTRIFIED
LOCKSET/STRIKE
DOOR
PROVIDE 6"X6"X4" DEEP
JUNCTION BOX WITH
HINGED COVER.
LOCATE ON SECURE
SIDE OF DOOR.
PROVIDE 1" CONDUIT
BACK TO ACCESS
CONTROL PANEL.
PROVIDE DOUBLE-GANG
BACKBOX WITH
SINGLE-GANG PLASTER
RING FOR CARD READER.
LOCATION PER PLANS.
FLOOR
MAX. 48" AFF
OR MATCH
LIGHT SWITCH
MOUNTING HEIGHT
PER SCHEDULE OR AS
NOTED ON DRAWINGS
CABLING PER RISER
DIAGRAM
EXPANSION ANCHORS
WITH STAINLESS STEEL
SECURITY FASTENERS
FLUSH MOUNTED OUTLET
BOX. COORDINATE
LOCATION TO MATCH
CAMERA WIRING LOCATION
ACCESS.
1" CONDUIT TO
NEAREST CABLE TRAY
WALL
CAMERA PER
SCHEDULE
GENERAL NOTES:
1. BACKFILL, CONCRETE, REINFORCING STEEL, AND ANCHOR BOLTS ARE
SHOWN FOR REFERENCE ONLY. POLE BASE STRUCTURAL REQUIREMENTS
SHALL BE DESIGNED AND SEALED BY A PROFESSIONAL ENGINEER
LICENSED IN THE PROJECT STATE AND SUBMITTED AS PART OF THE
SUBMITTAL PROCESS.
m m M
IN
(2
M
IN
PVC CONDUIT
PVC CONDUIT ADAPTER
COUPLING
RIGID STEEL CONDUIT
PROVIDE 36"Lx36"Wx4"D
CONCRETE MOW PAD AT
GRADE.
BASE COVER PLATE
FINISHED GRADE
PEDESTAL, WEATHER HOODS,
AND DEVICES PER SCHEDULES.
GALVANIZED ANCHOR BOLTS &
HEX NUTS. PROVIDE LEVELING
SHIMS OR HEX NUTS.
UNDISTURBED SOIL OR SELECT,
COMPACTED BACKFILL. SEE
NOTE BELOW.
CONCRETE BASE &
REINFORCING STEEL. SEE
NOTE BELOW.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGIENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:3
:3
ELECTRICAL AND SECURITY DETAILS
MIJ 62 72BEN
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
E-500
SPUR #: 1794.13
SPLICERS-CONDUCTORS DTL1RECEPTACLE ROOF MTG DTL2MECHANICAL UNIT BONDING TERMINAL3
GROUNDING BAR DETAIL5CONDUIT TRAPEZE MNTG DTL6COND ROOF PNTRTN DTL7OCCUPANCY SENSOR POWER PACK MOUNTING DETAILS8
LUMINAIRE MOUNTING - LAY - IN CEILING9DOWNLIGHT MOUNTING - GYPBOARD CEILING10EXIT SIGN MOUNTING - LAY - IN CEILING11SECURITY DOOR CR12
EXT WALL - MT VIDEO CAMERA13
CONTROLLED UNCLASSIFIED INFORMATION
CONTROLLED UNCLASSIFIED INFORMATION
125AF
125AT
3P
175AF
175AT
3P
30AF
30AT
3P
P N
L B
D B
P
(E T
R
C H
IL
L E
R
C O
N D
E N
S E
R
P N
L B
D A
(E T
R
4000AF
4000AT
3P
4000 AMPS 120Y/208V, 3PH, 4W
BLDG 1 ELECTRICAL RM MB575
SWBD T8 (ETR)
4000AF
4000AT
3P
4000 AMPS 120Y/208V, 3PH, 4W
BLDG 1 ELECTRICAL RM MB575
SWBD T9 (ETR)
400AF
400AT
3P
200AF
200AT
3P
E L E
V A
T O
R
600AF
600AT
3P
400AF
400AT
3P
1200AF
1200AT
3P
800AF
800AT
3P
800AF
800AT
3P
200AF
200AT
3P
200AF
200AT
3P
1200AF
1200AT
3P
400AF
400AT
3P
1200AF
1200AT
3P
200AF
200AT
3P
200AF
200AT
3P
200AF
200AT
3P
400AF
400AT
3P
600AF
600AT
3P
1200AF
1200AT
3P
400AF
400AT
3P
600AF
600AT
3P
600AF
600AT
3P
1200AF
1200AT
3P
600AF
600AT
3P
600AF
600AT
3P
400AF
400AT
3P
1200AF
1200AT
3P
A T
S -4
A T
S -2
A T
S -9
A T
S -3
A T
S -6
B D
A
D P
P K
P K
A C
C -1
B D
B
M -B
W
-M C
C
A T
S -1
A T
S -1
D P
-4
B D
A
A T
S -1
B D
B
400AF
400AT
3P
400 AMPS 120Y/208V, 3PH, 4W
MECHANICAL ROOM B07
MDP-3 (ETR)
SPD 125AF
125AT
3P
20AF
20AT
3P
20AF
20AT
3P
E L E
V A
T O
R
M E
T E
R C
O M
M
125AF
125AT
3P
3P
200AS
125AF
3R
D O
A U
-1
125AF
125AT
3P
3P
200AS
125AF
3R
D O
A U
-2
100AF
80AT
3P
3P
100AS
80AF
3R
H R
U -1
100AF
80AT
3P
3P
100AS
80AF
3R
H R
U -2
3P
200AS
125AF
3R
1200AF
1200AT
3P
H A
N D
H O
L E
F O
R T
R A
IL
E
R S
O U
T S
ID
E
B U
IL
D
IN
G
600 AMPS 120Y/208V, 3PH, 4W
BASEMENT BUILDING 1
DP-1 (ETR)
300AF
300AT
3P
125AF
125AT
3P
250AF
250AT
3P
P N
L B
D A
(E T
R
P N
L B
D A
(E T
R
400 AMPS 120Y/208V, 3PH, 4W
MB-304
CDP-1 (ETR)
100AF
100AT
3P
200AF
200AT
3P
400 AMPS 120Y/208V, 3PH, 4W
MB-304
CDP-3 (ETR)
225AF
225AT
3P
225AF
225AT
3P
100AF
100AT
3P
P N
L B
D B
-1
(E T
R
ATS-5
1000A 3P
400AF
400AT
3P
225AF
225AT
3P
400AF
400AT
3P
P N
L B
D C
D P
-2
(E T
R
200AF
200AT
3P
D T
-D
T
E C
A
-E C
A
E -L
S
E C
A
-E C
A
D T
B -D
T
30AF
30AT
3P
225AF
225AT
3P
225AF
225AT
3P
20AF
20AT
1P
E C
B
-E C
B
E C
B
-E C
B
100AF
100AT
3P
P N
L B
D
-C R
-O
IT
(N E
W
E T
D
E T
D
E T
R
E T
R
E
T R
E T
R
E T
D
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
D
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
ETR
ETR
ETR
E T
R
E T
R
E T
R
NOT TO SCALENOT TO SCALE
T e m p
/H u m id ity O u t
C B
O
F F
O
O N I
C B
O
F F
O
O N I
C B
R e s e t
O F
F
O
O N I
C H
A T
S W
O R
T H
P R
O D
U C
T W a rn in g
O K
C ri ti c a l
/1
In I O
IO
IO
CB3
CB2
CB1
CB3
CB2
CB1
CB1
CB2
CB3
CB1
CB2
CB3
T e m p
/H u m id ity O u t
C B
O
F F
O
O N I
C B
O
F F
O
O N I
C B
R e s e t
O F
F
O
O N I
C H
A T
S W
O R
T H
P R
O D
U C
T W a rn in g
O K
C ri ti c a l
/1
In I O
IO
IO
CB3
CB2
CB1
CB3
CB2
CB1
CB1
CB2
CB3
CB1
CB2
CB3
T e m p
/H u m id ity O u t
C B
O
F F
O
O N I
C B
O
F F
O
O N I
C B
R e s e t
O F
F
O
O N I
C H
A T
S W
O R
T H
P R
O D
U C
T W a rn in g
O K
C ri ti c a l
/1
In I O
IO
IO
CB3
CB2
CB1
CB3
CB2
CB1
CB1
CB2
CB3
CB1
CB2
CB3
T e m p
/H u m id ity O u t
C B
O
F F
O
O N I
C B
O
F F
O
O N I
C B
R e s e t
O F
F
O
O N I
C H
A T
S W
O R
T H
P R
O D
U C
T W a rn in g
O K
C ri ti c a l
/1
In I O
IO
IO
CB3
CB2
CB1
CB3
CB2
CB1
CB1
CB2
CB3
CB1
CB2
CB3
L21-30P SIDE A
REQUIRES A 208V, 30A, THREE-PHASE
CIRCUIT, TERMINATING IN A NEMA L21-
30R LOCKING RECEPTACLE.
ZONE PDU
30A 3-PHASE ZONE PDU BASE
UNIT – REQUIRES TWO 30A 3-
PHASE (WYE) CIRCUITS WITH L21-
30R RECEPTACLES
UNINTERRUPTIBLE POWER SUPPLY
(UPS) WITH NEMA 20A L21-20P INPUT
AND L21-20R OUTPUT
RACK-MOUNTED 5 KW, 208V
L21-30P SIDE B
REQUIRES A 208V, 30A, THREE-PHASE
CIRCUIT, TERMINATING IN A NEMA L21-
30R LOCKING RECEPTACLE.
ZONE PDU
LEG1 LEG2
RACK-MOUNT
UPS
RACK-MOUNT
UPS
PDU
A
RACKED
EQUIPMENT
PS2PS1
PDU
B
PDU
A
RACKED
EQUIPMENT
PS2PS1
PDU
B
RACK/ENCLOSURE RACK/ENCLOSURE
BUS A BUS B
PH ASE Z
A GROUP
OX
A
OY
GROUP B
OZ OX
GR OUP
OY
A
OZ
GROUP B
OX OY
GRP A
GRP B
LEG 2
LEG 1
GRP A
GRP B LEG 1
LEG 2 GRP A
GRP B LEG 1
LEG 2
OZ
B
LEG 1 LEG 2 LEG 1 LEG 2
OY OX OZ
P HASE Y PHAS E X
REQUIRES ONE (1)
L21-20R
CHATSWORTH ECONNECT PDU; VERTICAL; MONITORED; L21-20 PLUG;
THREE PHASE; 120/208V INPUT; 20A; (30) C13 (6) C19 OUTLETS; 208V
OUTPUT; 3 X 2P 20A HYDRAULIC MAGNETIC BREAKERS; LCD;
ETHERNET, USB, AND ENVIRONMENTAL SENSOR PORTS; IP AND
SERIAL MONITORING; IP CONSOLIDATION (PDU LINKING); TOOL-LESS
MOUNTING; 70.5"H (1791 MM) X 2.2"W (56 X 2.2"D (56 MM)
T e m p
/H u m id ity O u t
C B
O
F F
O
O
NI
C B
O
F F
O
O
NI
C B
R e se t
O F
F
O
O
NI
C H
A T S
W O
R T
H
P R
O D
U C
T W a rn in g
O K
C ritic a l
/1
In
/ IO
IO
IO
CB3
CB2
CB1
CB3
CB2
CB1
CB1
CB2
CB3
CB1
CB2
CB3
20A 0 /208V
Y
208V RACK PDU FOR TRs
POWER ELEVATION AND SCHEMATIC FOR A TWO RACK TR
(E T
D
(E T
D
FROM TRANSFORMER T8 FROM TRANSFORMER T9
(E T
D
SPARE
C H
IL
L E
D W
A T
E R
P
U M
P W
E S
B B
A S
E M
E N
T (E
T R
C H
IL
L E
D W
A T
M
P E
A
B B
A S
E M
E N
T (E
T R
N
G
SPACE
C H
IL
L E
D W
A T
M
P (E
T R
(N E
W
(E T
R
(N E
W
(N E
W
(N E
W
N
G
N
G
N
G
N
G
N
G
FROM
SWBD-28
SPACE
(TYPICAL
OF 4)
SPARE
(TYPICAL
OF 5)
SPARE
(TYPICAL
OF 3)
SPARE
8,10,12 14,16,18 15,17,19 20,22,24 26,28,3021,23,25 27,29,31
(N E
W th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRIN…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .