Attachment 6 - Structural - Drawings.pdf
PDF 1 MB Posted
- Attached to
- Y1DA--EHRM Training and Admin Space Support Construction - Kansas City VAMC Federal contract opportunity
- Solicitation number
- 36C77623B0020
About this file
This document outlines special inspection requirements for steel construction. It requires verification and inspection of high-strength bolts, nuts, and washers used in bearing-type bolt connections and pre-tensioned or slip-critical connections. Structural steel must be verified for identification markings conforming to ASTM standards specified in approved construction documents. Weld filler materials must also be verified for identification markings and be accompanied by a manufacturer's certificate of compliance. Inspection of welding is mandated for complete and partial penetration groove welds, multi-pass fillet welds, and single-pass fillet welds greater than or equal to 5/16 inches.
The related federal contract opportunity is a solicitation from the Department of Veterans Affairs Technology Acquisition Center Austin for construction services to support EHRM infrastructure upgrades at the Kansas City VAMC. The solicitation number is 36C77623B0020 and is for the Y1DA EHRM Training and Admin Space Support Construction project.
View the file
Other files for this federal contract opportunity
Show all 36
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPECIAL INSPECTION OF STEEL CONSTRUCTION
REQ'D VERIFICATION & INSPECTION CONTINUOUS PERIODIC
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
1. MATERIAL VERIFICATION OF HIGH-STRENGTH
BOLTS, NUTS & WASHERS:
A. IDENTIFICATION MARKINGS TO CONFORM TO
ASTM STANDARDS SPECIFIED IN THE APPROVED
CONSTRUCTION DOCUMENTS.
B. MANUFACTURES CERTIFICATE OF
COMPLIANCE REQUIRED.
2. INSPECTION OF HIGH-STRENGTH BOLTING:
A. BEARING-TYPE BOLT CONNECTIONS
B. PRE-TENSIONED & SLIP-CRITICAL
CONNECTIONS
3. MATERIAL VERIFICATION OF STRUCTURAL
STEEL:
A. IDENTIFICATION MARKINGS TO CONFORM TO
ASTM STANDARDS SPECIFIED IN THE APPROVED
CONSTRUCTION DOCUMENTS.
4. MATERIAL VERIFICATION OF WELD FILLER
MATERIALS:
A. IDENTIFICATION MARKINGS TO CONFORM TO
ASTM STANDARDS SPECIFIED IN THE APPROVED
CONSTRUCTION DOCUMENTS.
B. MANUFACTURES CERTIFICATE OF
COMPLIANCE REQUIRED.
5. INSPECTION OF WELDING:
A. STRUCTURAL STEEL:
1) COMPLETE & PARTIAL PENETRATION GROOVE
WELDS
2) MULTI-PASS FILLET WELDS
3) SINGLE-PASS FILLED WELD >5/16"
4) SINGLE-PASS FILLET WELDS <=5/16"
5) FLOOR AND DECK WELDS
B. REINFORCING STEEL:
1) VERIFICATION OF WELDABILITY OF
REINFORCING STEEL OTHER THAN ASTM A706
2) WELDING OF REINFORCING STEEL RESISTING
FLEXURAL & AXIAL FORCES IN INTERMEDIATE &
SPECIAL MOMENT FRAMES, & BOUNDARY
ELEMENTS OF SPECIAL REINFORCED
CONCRETE SHEAR WALLS & SHEAR
REINFORCEMENT.
3) WELDING OF SHEAR REINFORCEMENT
4) WELDING OF OTHER REINFORCING STEEL
6. INSPECTION OF STEEL FRAME JOINT DETAILS
FOR COMPLIANCE WITH APPROVED
CONSTRUCTION DOCUMENTS:
A. DETAILS SUCH AS BRACING & STIFFENING
B. MEMBER LOCATIONS
C. GROUTING OF SHEAR LUGS AND
BASEPLATES
D. APPLICATION OF PROPER JOINT DETAILS AT
EACH CONNECTION
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
SPUR #: 1794.13
/2
/2
:1
:4
A
M
STRUCTURAL GENERAL NOTES
TJSCGB
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
06/28/2022
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
S001
03_Abbreviation Schedule
Abbreviation Abbreviation Name
+/- PLUS OR MINUS
ADDNL ADDITIONAL
ADJ ADJACENT
AESS ARCHITECTURALLY EXPOSED
STRUCTURAL STEEL
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
AR ANCHOR ROD
ARCH ARCHITECT OR ARCHITECTURAL
B/ BOTTOM OF
B/W BETWEEN
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BRG BEARING
BWP BRACED WALL PANEL
CFS COLD FORMED STEEL
CHKD CHECKED
CIP CAST IN PLACE
CJ CONTROL JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
CTR CENTER
db DIA OF REINF BAR, DIA OF BOLT
DBA DEFORMED BAR ANCHOR
DIA or Ø DIAMETER
DIAG DIAGONAL
DIR DIRECTION
DWL DOWEL
EA EACH
EE EXTENDED END
EJ EXPANSION JOINT
ELEV ELEVATION
ENGR ENGINEER
EOD EDGE OF DECK
EOS EDGE OF SLAB
EQ EQUAL
EW EACH WAY
EXIST EXISTING
EXT EXTERIOR
FDN FOUNDATION
FLG FLANGE
FLR FLOOR
FS FAR SIDE
FTG FOOTING
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GC GENERAL CONTRACTOR
HORIZ HORIZONTAL
HSA HEADED STUD ANCHOR
HSS HOLLOW STRUCTURAL SECTION
IF INSIDE FACE
INT INTERIOR
JST JOIST
K KIPS (1000 LBS)
LCE COMPRESSION EMBEDMENT LENGTH
LCS COMPRESSION LAP SPLICE LENGTH
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LTE TENSION EMBEDMENT LENGTH
LTS TENSION LAP SLICE LENGTH
LW LIGHTWEIGHT
MFCR MANUFACTURER
MTL METAL
NIC NOT IN CONTRACT
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OF OUTSIDE FACE
OPP OPPOSITE
OVS OVERSIZED
P/C PRECAST
PAF POWDER ACTUATED FASTENER
PAR PARALLEL
PEMB PRE-ENGINEERED METAL BUILDING
PEN PENETRATION
PERP PERPENDICULAR
PL PLATE
PLF POUNDS PER LINEAR FOOT
PREFAB PREFABRICATED
PRELIM PRELIMINARY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
RC REINFORCED CONCRETE
RE: REFER TO
REINF REINFORCING
REQD REQUIRED
RF RIGID FRAME
SC SLIP CRITICAL
SDS SELF DRILLING SCREW
SIM SIMILAR
SLV SHORT LEG VERTICAL
SOG SLAB ON GRADE
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STIR STIRRUPS
STL STEEL
SW SHEAR WALL
SYM SYMMETRIC
T&B TOP AND BOTTOM
T/ TOP OF
TRANS TRANSVERSE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
W/ WITH
W/O WITHOUT
WF WIDE FLANGE
WP WORK POINT
WWR WELDED WIRE REINFORCEMENT
STRUCTURAL DESIGN CRITERIA (2021 IBC AND ASCE 7-16):
1. BUILDING OCCUPANCY RISK CATEGORY II.
2. LIVE LOADS [UNIFORM (PSF) / POINT LOADS (KIPS)]:
-- ROOF:………………………………………...............20 PSF / 300#
-- OFFICES:………………….…..…............................50 PSF + 15 PSF
PARTITIONS / 2.0 K
-- UPPER LEVEL CORRIDORS................................80 PSF / 2.0 K
-- GROUND LEVEL CORRIDORS ...............……….100 PSF / 2.0 K
3. ROOF SNOW LOAD:
-- GROUND SNOW LOAD (Pg):……………………....20 PSF -- FLAT ROOF SNOW LOAD (Pf): ............................14 PSF W/O DRIFT
-- PARAPET DRIFT ..................................................18.9 PSF
-- MIN UNIFORM ROOF SNOW LOAD (Pm):…...…..20 PSF (NO DRIFT OR RAIN) -- RAIN ON SNOW SURCHARGE (Prs) ..................5.0 PSF -- SNOW EXPOSURE FACTOR (Ce):………………..1.0, EXPOSURE B & C -- SNOW LOAD IMPORTANCE FACTOR (Is):….......1.0 -- THERMAL FACTOR (Ct):……………………….......1.0
4. WIND DESIGN DATA:
-- BASIC WIND SPEED (3 SEC GUST):……………..115 MPH
-- WIND EXPOSURE:…………………………………..B
-- DIRECTIONALITY FACTOR (Kd) .........................0.85
-- ROOFTOP EQUIPMENT (GCr).............................1.9 -- WIND PRESSURE ON EQUIPMENT…………….. 30 psf
STRUCTURAL GENERAL NOTES:
1. DESIGN AND CONSTRUCTION SHALL CONFORM TO THE "INTERNATIONAL
BUILDING CODE, 2021 EDITION". REFER TO THE SPECIAL STRUCTURAL INSPECTION
NOTES FOR ADDITIONAL REQUIREMENTS.
2. CONTRACTOR TO VERIFY ALL DIMENSIONS, ELEVATIONS AND EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE ARCHITECT PRIOR TO
COMMENCING WORK.
3. IF DISCREPANCIES EXIST BETWEEN STRUCTURAL PLANS, ARCHITECTURAL
PLANS, OTHER PLANS, OR SPECIFICATIONS, THE CONTRACTOR OR
SUBCONTRACTOR SHALL PROVIDE A WRITTEN REQUEST FOR CLARIFICATION FROM
THE ARCHITECT AND/OR ENGINEER PRIOR TO PROCEEDING WITH THE WORK.
4. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER
THE BUILDING IS FULLY COMPLETED. IT IS SOLELY THE CONTRACTOR'S
RESPONSIBILITY TO EXECUTE AND DETERMINE FINAL ERECTION PROCEDURES,
SEQUENCING AND TO ENSURE THE SAFETY OF THE BUILDING AND ITS COMPONENT
PARTS DURING ERECTION. THIS INCLUDES WHATEVER SHORING, SHEETING,
TEMPORARY BRACING, GUYING OR TIE DOWNS WHICH MIGHT BE NECESSARY.
5. THE STRUCTURE AND FOUNDATIONS ARE NOT DESIGNED FOR FUTURE
EXPANSION.
6. FABRICATORS AND SUPPLIERS SHALL CLEARLY NOTE AND HIGHLIGHT CHANGES
MADE IN SHOP DRAWINGS, WHICH DO NOT COMPLY WITH THE CONTRACT
DOCUMENTS.
7. COLUMNS, BEAMS, JOISTS, OR TRUSSES SHALL NOT BE FIELD CUT OR TRIMMED
FOR ANY REASON WITHOUT THE WRITTEN APPROVAL OF THE
ARCHITECT/ENGINEER.
8. HOLES, PIPES, SLEEVES, ETC. NOT SHOWN ON THE DRAWINGS MUST BE
REVIEWED BY THE ARCHITECT/ENGINEER BEFORE PLACEMENT THROUGH
STRUCTURAL MEMBERS.
9. IF MECHANICAL AND ELECTRICAL EQUIPMENT SIZES, WEIGHTS, OR LOCATIONS
DO NOT COINCIDE WITH EQUIPMENT SHOWN ON THE PLANS, COORDINATE
ADJUSTMENTS WITH THE ARCHITECT.
10. NO AREA OF THE STRUCTURE SHALL BE LOADED WITH CONSTRUCTION
MATERIALS OR EQUIPMENT THAT EXCEEDS FINAL DESIGN CRITERIA.
11. BEAMS, COLUMNS, WALLS AND FOOTING CENTERS SHALL BE CENTERED UNDER
SUPPORTING MEMBERS (TYPICAL UNLESS NOTED OTHERWISE).
12. TYPICAL DETAILS ARE SHOWN ON SHEETS DESIGNATED S050. THE INCLUDED
TYPICAL DETAILS MAY OR MAY NOT BE CUT / REFERENCED ON PLANS OR
SECTIONS, BUT ARE TO BE USED AS APPLICABLE.
14. DELEGATED DESIGN - DEFERRED SUBMITTALS SHALL BE SIGNED/ SEALED
PRIOR TO
SUBMITTAL FOR REVIEW. THESE INCLUDE:
A. PRE-ENGINEERED CANOPIES
B. COLD FORM FRAMING
SUBMIT THESE SHOP DRAWINGS AND CALCULATIONS SEALED BY A STRUCTURAL
ENGINEER LICENSED TO PRACTICE IN THE JURISDICTION OF THE PROJECT SHALL
BE FURNISHED TO THE ENGINEER OF RECORD FOR REVIEW. CONTRACTOR SHALL
SUBMIT COPIES OF DEFERRED SUBMITTALS TO CONTRACTING OFFICERS
REPRESENTATIVE AFTER ARCH/ENG REVIEW.
EARTHWORK AND FOUNDATIONS:
1. ALL FOOTINGS SHALL BEAR A MINIMUM DEPTH BELOW GRADE OF 3'-0" ON FIRM
NATIVE MATERIALS, COMPACTED OR ENGINEERED FILL CAPABLE OF SUPPORTING A
PRESUMPTIVE ALLOWABLE BEARING PRESSURE OF 2,000 PSF PER KCMO. DEEPEN
FOOTINGS, AND REMOVE AND REPLACE UNACCEPTABLE SOILS WITH ENGINEERED
FILL AS REQUIRED TO PROVIDE THIS MINIMUM DEPTH AND SUITABLE BEARING.
2. UNDERCUT THE PAD TO A DEPTH OF 18-INCHES BELOW BOTTOM OF FLOOR SLAB
ELEVATION AND REPLACE WITH LOW-VOLUME-CHANGE MATERIALS PER THE
GEOTECHNICAL REPORT.
3. FILL PLACEMENT, COMPACTION, AND SOIL BEARING TESTS SHALL BE
PERFORMED BY A GEOTECHNICAL ENGINEER PRIOR TO INSTALLING FOOTINGS TO
ENSURE DESIGN ALLOWABLE BEARING VALUES AND SLAB SUBGRADE
REQUIREMENTS ARE SATISFIED. IF ACTUAL SITE CONDITIONS DO NOT SATISFY
THESE REQUIREMENTS, COORDINATE ADJUSTMENTS WITH ARCHITECT/ENGINEER/
GEOTECHNICAL ENGINEER
4. SURFACE WATER SHALL NOT BE ALLOWED TO STAND ADJACENT TO OR DRAIN
TOWARDS THE FOUNDATION AND SLAB SUBGRADES UNDER ANY CIRCUMSTANCES.
PAVEMENTS OR GRADED SOILS AT THE PERIMETER OF THE BUILDING, EXCEPT AS
REQUIRED AT EXITS OR AS NOTED, SHALL BE SLOPED AWAY AT 5% OR 6” MIN FOR
THE FIRST TEN FEET AND AS REQUIRED TO PROVIDE POSITIVE DRAINAGE.
5. FOOTINGS MAY BE POURED TO NEAT LINES OF EXCAVATIONS PROVIDING
VERTICAL LINES OF EXCAVATIONS CAN BE MAINTAINED DURING CONCRETE
PLACEMENT.
6. FOUNDATION WALL BACKFILL SHALL NOT BE UNBALANCED BY MORE THAN TWO
FEET ON EITHER SIDE AT ANY TIME. BASEMENT WALL AND RESTRAINED RETAINING
WALL BACKFILL SHALL NOT BE PLACED, UNLESS THE WALL IS ADEQUATELY
BRACED. RETAINING WALL AND BASEMENT WALL BACKFILL SHALL BE FREE
DRAINING GRANULAR BACKFILL ACCEPTABLE TO THE GEOTECHNICAL ENGINEER.
OPEN WEB STEEL BAR JOISTS:
1. REINFORCE WEBS OF JOISTS WITH ADDITIONAL ANGLES FIELD-WELDED PER THE
TYPICAL DETAILS AT ALL LOCATIONS WHERE POINT LOADS OCCUR BETWEEN
PANEL POINTS, INCLUDING AT EDGES AND CORNERS OF CURBS & FRAMES
SUPPORTING ROOF TOP EQUIPMENT.
STRUCTURAL STEEL:
1. SUBMIT SHOP DRAWINGS FOR STEEL.
STRUCTURAL STEEL SHAPES AND PLATE MATERIAL REQUIREMENTS (TYPICAL
UNLESS NOTED OTHERWISE):
a. WIDE FLANGE SHAPES - ASTM A992 (FY = 50 KSI MIN.)
b. CHANNELS, ANGLES, AND PLATES: - ASTM A36 (FY = 36 KSI MIN)
c. ROUND HSS - ASTM A500, GR B (FY = 42 KSI)
d. RECTANGULAR HSS - ASTM A500, GR B (FY = 46 KSI)
e. PIPE - ASTM A53, GR B (FY = 35 KSI)
f. ANCHOR RODS - ASTM F1554 (FY = 36 KSI MIN.),
g. ADHESIVE ANCHORS - SIMPSON SET-3G, HILTI HIT-HY 200, OR
EQUIVALENT
2. STRUCTURAL STEEL SHALL BE NEW AND MEET THE 15TH EDITION A.I.S.C.
“SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS AND BRIDGES”, AND THE
“CODE OF STANDARD PRACTICES FOR STEEL BUILDINGS AND BRIDGES”,
EXCLUDING SECTION 4.4.1.B.
3. THE STRUCTURAL STEEL FABRICATOR SHALL BE AN AISC QUALITY CERTIFIED
COMPANY FOR THE CATEGORY OF WORK IN THIS PROJECT OR PROVIDE A QUALITY
ASSURANCE PLAN AND SPECIAL INSPECTIONS AS DEFINED IN THE CODE.
4. USE STANDARD AISC FRAMING CONNECTIONS WITH A325-N BOLTS, F436
WASHERS, AND A563 HEAVY-HEX NUTS AS REQUIRED, UNLESS NOTED OTHERWISE.
5. BOLTS IN MOMENT AND BRACED FRAME CONNECTIONS SHALL BE PRE-
TENSIONED. ALL A490 BOLTS SHALL BE PRE-TENSIONED. OTHER BOLTED
CONNECTIONS USING A325 BOLTS MAY BE SNUG-TIGHTENED, UNLESS NOTED
OTHERWISE.
6. STEEL BEAMS SHALL BE FABRICATED WITH MILL CAMBER UP.
7. WELDING SHALL CONFORM TO THE CURRENT AND APPLICABLE AWS STANDARDS
AND BE COMPLETED BY AN AWS CERTIFIED WELDER. ALL WELDS SHALL UTILIZE
E70xx ELECTRODES. SHOP DRAWINGS SHALL SHOW FIELD WELDS, AS
APPROPRIATE.
a. AWS D1.1 - STRUCTURAL WELDING CODE - STEEL
b. AWS D1.3 - STRUCTURAL WELDING CODE - SHEET STEEL
c. AWS D1.6 - STRUCTURAL WELDING CODE - STAINLESS STEEL
8. WELD SIZES SHALL BE INCREASED TO MEET THE REQUIRED EFFECTIVE THROAT
WIDTH IF GAPS EXIST AT THE FAYING SURFACE.
9. NO COLUMN OR BEAM SPLICES, UNLESS CLEARLY INDICATED ON THE
STRUCTURAL DRAWINGS, WILL BE ALLOWED WITHOUT WRITTEN APPROVAL OF THE
STRUCTURAL ENGINEER.
10. SEE ARCHITECTURAL PLANS FOR FIREPROOFING & FINISHING REQUIREMENTS,
AND COORDINATE STEEL PRIMING & COATINGS ACCORDINGLY.
11. GROUT WHERE INDICATED ON PLANS AT BASE PLATES SHALL BE NON-METALLIC
NON-SHRINK WITH A MINIMUM COMPRESSIVE STRENGTH OF 6000 PSI AT 28 DAYS
CONFORMING TO ASTM C1107
12. ALL POST-INSTALLED ANCHORS WHERE NOTED SHALL BE MANUFACTURED BY
SIMPSON STRONG-TIE OR HILTI, INC. AND INSTALLED PER MANUFACTURER'S
SPECIFICATIONS. SUBSTITUTIONS SHALL BE SUBMITTED FOR REVIEW AND
APPROVAL WITH APPROPRIATE IC-ES EVALUATION REPORTS.
13. ALL STEEL AND ASSOCIATED FASTENERS NOT PROTECTED FROM WEATHER OR
WHOLLY WITHIN A CONDITIONED SPACE (INCLUDING ALL MASONRY LINTELS) SHALL
BE HOT DIPPED GALVANIZED PER ASTM A123.
CAST IN PLACE CONCRETE:
1. SUBMIT PROPOSED MIXED DESIGNS OF EACH TYPE FOR REVIEW.
REQUIRED MINIMUM CONCRETE COMPRESSIVE STRENGTHS AT 28 DAYS:
a. FOOTING AND GRADE BEAM CONCRETE…………..…...4000 PSI
b. SLAB ON GRADE AND STRUC SLAB ABOVE GRADE…..4000 PSI
2. ALL CONCRETE MIX DESIGNS SHALL HAVE WATER TO CEMENT RATIOS LESS
THAN 0.52 (0.45 FOR MOISTURE SENSITIVE FLOORING), WITH A MAXIMUM 60/40 FINE
TO COARSE AGGREGATE RATIO. CONCRETE MIX DESIGNS THAT DO NOT CONFORM
TO THE ABOVE STANDARD AND/OR CONTAIN WATER REDUCING ADMIXTURES SHALL
BE SUBMITTED WITH APPROPRIATE TEST DATA PER A.C.I.. ALL CONCRETE SHALL BE
IN CONFORMANCE WITH THE A.C.I. 301 STANDARD THAT IS REFERENCED IN THE
BUILDING CODE AT THE TIME OF PERMITTING THE PROJECT..
3. EXTERIOR CONCRETE (FLOOR SLABS, WALLS, ETC) SHALL HAVE 6.5%
(PLUS/MINUS 1.5%) ENTRAINED AIR.
4. CHAMFER ALL EXPOSED CONCRETE EDGES 3/4” (VERIFY WITH ARCHITECT).
5. NO ALUMINUM SHALL BE EMBEDDED IN ANY CONCRETE.
6. NO CALCIUM CHLORIDE SHALL BE USED IN CONCRETE
7. THE DESIGN, CONSTRUCTION, AND SAFETY OF ALL FORMWORK IS THE
RESPONSIBILITY OF THE CONTRACTOR
8. ALL CONCRETE IS REINFORCED UNLESS SPECIFICALLY NOTED AS
UNREINFORCED. REINFORCE ALL CONCRETE NOT OTHERWISE SHOWN WITH THE
SAME REINFORCING AS SIMILAR SECTIONS OR AREAS.
9. WHERE FRESH CONCRETE IS DEPOSITED AGAINST HARDENED CONCRETE
(GREATER THAN 8 HRS OLD), CLEAN EXISTING SURFACE OF LAITANCE AND
FOREIGN MATERIAL AND DAMPEN THE EXISTING SURFACE. IF REQUIRED,
ROUGHEN EXISTING CONCRETE TO ¼” AMPLITUDE.
10. SLABS ON GRADE SHALL BE 4” THICK MINIMUM ON 4” OF GRANULAR FILL. REINF
SLAB WITH 6 X 6-W2.1xW2.1 WWR OR #3 BARS @ 18" OC EA WAY. PLACE REINF IN
UPPER 1/3 OF SLAB THICKNESS. AT INTERIOR SLABS, A 10 MIL VAPOR BARRIER
SHALL BE PLACED BETWEEN THE CONCRETE AND GRANULAR BASE AND CARE
SHOULD BE TAKEN DURING CURING TO PREVENT SLAB CURLING. THIS NOTE SHALL
BE TYPICAL UNLESS NOTED OTHERWISE
11. SAW CUT JOINTS OR KEYED CONSTRUCTION JOINTS IN SLABS ON GRADE SHALL
BE SPACED TO DIVIDE THE SLAB INTO PANELS NOT TO EXCEED 225 SQUARE FEET.
THE LONGER DIMENSION OF EACH PANEL SHALL NOT EXCEED THE SHORTER
DIMENSIONS BY MORE THAN 40%. JOINTS SHALL BE LOCATED AT COLUMN
CENTERLINES WHERE POSSIBLE. SPACING BETWEEN JOINTS SHALL NOT EXCEED 15
FEET. CONTRACTOR SHALL SUBMIT JOINT LAYOUT TO ARCHITECT FOR APPROVAL.
REFER TO TYPICAL DETAILS.
12. REINFORCEMENT SHALL BE CONTINUOUS AND LAPPED 53 BAR DIAMETERS
(2’ -6” MIN.) EXCEPT AS NOTED AND PROVIDE CORNER BARS OF SAME SIZE AND
SPACING.
13. MINIMUM REINFORCING AROUND CONCRETE WALL OPENINGS 2’-0” OR GREATER
(TYPICAL UNLESS NOTED): 2 - #5, EXTEND REINF 2’-0” PAST OPENINGS. PROVIDE
2-#5 x 4’-0” DIAGONAL BARS AT CORNERS
14. CONTRACTOR SHALL COORDINATE ALL CURING COMPOUNDS WITH FLOOR
FINISH REQUIREMENTS TO ENSURE COMPATIBILITY.
15. FOUNDATION CONTRACTOR TO ENSURE PROPER ANCHOR ROD PROJECTION
AND THAT ANCHOR RODS ARE HELD SECURELY IN POSITION PRIOR TO CONCRETE
PLACEMENT. INSTALL ANCHOR RODS TO THE STRICT DIMENSIONAL TOLERANCES
PER AISC REQUIREMENTS. STRUCTURAL STEEL COLUMN ANCHOR RODS SHALL BE
SET WITH A RIGID TEMPLATE.
16. AGGREGATES AND/OR CONCRETE MIXES SHALL BE CERTIFIED TO BE FREE OF
AND ELIMINATE DAMAGE OF CONCRETE DUE TO ALKALI-SILICA REACTION OR
ALKALI-AGGREGATE REACTIONS WHEN EXPOSED TO SOILS AND/OR AN EXTERIOR
ENVIRONMENT.
17. ALL CONCRETE MIX DESIGNS EXPOSED TO AN EXTERIOR ENVIRONMENT SHALL
MEET THE REQUIREMENTS OF THE KANSAS CITY METRO MATERIALS BOARD
(KCMMB) OR THE JOHNSON COUNTY CONCRETE BOARD (JCCB).
SPECIAL INSPECTIONS:
1. PROVIDE SPECIAL STRUCTURAL INSPECTIONS AND VERIFICATIONS BY A THIRD
PARTY MEETING THE REQUIREMENTS OF CHAPTER 17 OF THE BUILDING CODE AND
THE BUILDING OFFICIAL. RE: SPEC SECTION 01 45 00
2. SPECIAL INSPECTORS SHALL BE QUALIFIED AND FURNISH THEIR REPORTS IN A
TIMELY MANNER TO THE CONTRACTOR, BUILDING OFFICIALS, ARCHITECT, AND/OR
ENGINEER
3. SHOULD INSPECTOR IDENTIFY ANY DISCREPANCY, THEY SHALL NOTIFY
CONTRACTOR FIRST, AND THEN ARCHT/ ENGINEER IMMEDIATELY THEREAFTER IF
CORRECTIVE ACTION IS NEEDED.
4. SPECIAL INSPECTIONS AS REQUIRED BY CODE:
A. STEEL: SECTION 1705.2, AND AISC 360. PERIODIC OBSERVATIONS OF
FIELD WELDING. VISUALLY INSPECT FIELD WELDS ACCORDING TO AWS D1.1/D1.1M
NOTE: SPECIAL INSPECTIONS TO BE PAID FOR BY CONTRACTOR
COLD FORMED STEEL FRAMING NOTES:
1. SUBMIT SHOP DRAWINGS AND CALCULATIONS PER THE DEFERRED SUBMITTAL
REQUIREMENTS. SHOP DRAWINGS SHALL INCLUDE PLAN AND SECTION DETAILS TO
SHOW LAYOUT, SPACINGS, SIZES, THICKNESSES, AND TYPES OF COLD-FORMED
STEEL FRAMING. IN ADDITION, SHOP DRAWINGS SHALL INCLUDE ALL FASTENING,
ANCHOR DETAILS, SUPPLEMENTAL FRAMING, STRAPPING, BRACING, BRIDGING,
CONNECTION DETAILS, AND ATTACHMENTS TO ADJOINING WORK
CFS DESIGN CRITERIA:
-- INTERIOR WALLS: 5 PSF HORIZONTAL PRESSURE;H/600 FOR WALLS BRACING
MASONRY; H/360 FOR WALLS SUPPORTING TILE OR METAL PANEL; H/240 FOR ALL
OTHER WALLS.
LIGHT GAUGE FRAMING MEMBERS SHALL HAVE THE FOLLOWING MINIMUM
MATERIAL PROPERTIES: FY = 33 KSI FOR 18 GA AND LIGHTER MEMBERS, FY = 50 KSI
FOR ALL DIAGONAL STRAP BRACING AND FOR 16 GA AND HEAVIER MEMBERS. ALL
MATERIALS, CONNECTORS, FASTENERS SHALL BE GALVANIZED
CFS SUPPLIER SHALL INCLUDE AN ALLOWANCE (2% OF CFS BID PACKAGE) FOR
MISC CLIPS, CONNECTORS, AND ANGLES TO ADDRESS ANY ADDITIONAL CFS ITEMS
NEEDED DURING THE SHOP DRAWING REVIEW AND CONSTRUCTION PROCESS.
2. ALL DESIGN, FABRICATION, AND ERECTION SHALL BE IN CONFORMANCE WITH
AISI “SPECIFICATIONS FOR THE DESIGN OF COLD FORMED STEEL STRUCTURAL
MEMBERS.”
3. MINIMUM GAUGE OF STRUCTURAL STUDS SHALL BE 43 mils (18 GAUGE), UNLESS
NOTED OTHERWISE.
4. TRACKS SHALL BE SECURELY ANCHORED TO THE SUPPORTING STRUCTURE TO
PROPERLY TRANSFER IMPOSED LOADS. MINIMUM GAUGE OF TRACKS SHALL BE 43
mils (18 GAUGE). DEFLECTION TRACKS AT EXTERIOR WALL SHALL BE 16 GA
MINIMUM.
5. PROVIDE WALL STUD BRIDGING FOR EACH STUD AS RECOMMENDED BY THE
MANUFACTURER. MAXIMUM SPACING SHALL BE 4’-0” CENTERS.
6. ALL FRAMING COMPONENTS SHALL BE CUT SQUARELY FOR ATTACHMENTS TO
PERPENDICULAR MEMBER. MEMBERS SHALL BE HELD POSITIVELY IN PLACE UNTIL
PROPERLY FASTENED.
7. NOTCHES OR SPLICES IN ANY STRUCTURAL STUDS WILL NOT BE PERMITTED.
8. ALL WELDING SHALL BE PERFORMED BY WELDERS EXPERIENCED IN LIGHT
GAUGE STEEL FRAMING WORK. TOUCH UP ALL WELDS WITH GALVANIZE COATING.
9. SCREWS IN LIGHT GAUGE FRAMING SHALL BE INSTALLED WITH MINIMUM EDGE
DISTANCES OF 1/2" AND MINIMUM SPACING BETWEEN SCREWS OF 3/4".
10. WHERE BACK-TO-BACK STUD COLUMNS ARE USED, ATTACH WITH #10 SCREWS
@ 12" OC MAX, UNO.
11. LATERAL BRACING MUST BE IN PLACE IN EACH DIRECTION BEFORE ANY LOAD IS
APPLIED TO THE WALLS & LEFT IN PLACE UNTIL THE WORK IS PERMANENTLY
STABILIZED.
No. REVISION DESCRIPTION DATE cblauwiekel_stand-se PWS MO Seal cblauwiekel_stand-se Typewritten Text 6/28/2022
90.00°
90.00°
4" M
IN (TYP)
NOTES:
A. PROVIDE SONOTUBE BLOCKOUT
WHEN CONTROL/ CONSTRUCTION
JOINTS DO NOT EXTEND FROM ALL
CORNERS OF BLOCKOUT
INTERIOR COL
EXTERIOR COL
CORNER COL
DETAIL NOTES:
EDGE OF SLAB OR
FACE OF WALL
EDGE OF BLOCKOUT
CONTROL OR
CONSTRUCTION JOINT
1/4" PREFORMED
JOINT FILLER AROUND
COLUMN AND AT EDGE
OF BLOCKOUT. FILL
JOINT WITH SEALANT
(TYP)
2" MAX
P
DETAIL NOTES:
POINT LOAD FROM
MECHANICAL EQUIPMENT
CURB OR BASE PERIMETER
(2)L 1 1/2x1 1/2x3/16 EA SIDE
OF CHORD
NOTES:
REINFORCEMENT
REQUIRED FOR ALL LOADS
NOT LOCATED AT A JOIST
PANEL POINT
TOP CHORD LOAD
3/16 2
3/16 2
TYP
A
3/16
TYP @ ALL
WEB REINF
3/16
TYP @ ALL WEB
REINF
2TYP
VARIES
DETAIL NOTES:
EXIST JST ROD WEB
(2) L2X2X3/16 WEB REINF TYP FOR ALL WEB MEMBERS
ALONG ENTIRE LENGTH OF JOIST
STITCH WELD ALONG LENGTH B/W ANGLE & ROD
SECTION A
SECTION A
SECTION B
1/8 1
1/8 1
TYP
2 1/4"
1" MAX
DETAIL NOTES:
CUT DECK AS REQD AT OPENING. FASTEN
DECK TO ANGLES SIMILAR TO TYPICAL
SUPPORT FASTENING (WELDS OR SCREWS)
4x4x1/4" TAG PL
MATCH T/JST ELEV
3/16
TYP
3/16
TYP
'-0
M
A X
DETAIL NOTES:
4x4x1/4" TAG PL (4 PLCS). SEE SECTION A
L6x4x5/16 (LLV)
EXISTING OPEN WEB JOISTS, RE: PLAN
L6x4x5/16" (LLV) TYP 4 PLCS
EXISTING OPEN WEB JOISTS, RE: PLAN
PROFILE OF RTU CURB. STEEL DECK MAY BE REMOVED INSIDE OF STEEL
FRAME OR PROVIDE ISOLATED HOLES IN THE DECK AT DUCT DROP
LOCATIONS. ISOLATED HOLES SHOWN IN THIS DETAIL
POINT LOAD REINF RE:
ANGLE FRAME NOTES:
1. WELD DECK TO ANGLE SUPPORTS SIMILAR TO MAIN FRAMING PATTERN
2. SEE TYPICAL DETAIL FOR JOIST PANEL POINT REINFORCEMENT
3. SEE TYPICAL DETAIL FOR RTU CURB SUPPORT ON METAL DECK
S050
S050 B
A
/3 S0507
7 7
DETAIL NOTES:
4x4x1/4" TAG PL (4 PLCS). SEE
L6x4x1/4 (LLV)
EXISTING OPEN WEB JOISTS, RE: PLAN
L6x4x5/16" (LLV)
ANGLE FRAME NOTES:
1. WELD DECK TO ANGLE SUPPORTS SIMILAR TO MAIN FRAMING PATTERN
/5 S050
DETAIL NOTES:
PRE-FABRICATED INSULATED ROOF CURB RE: MECH. COORDINATE ACTUAL
WIDTH & ATTACHMENT REQUIREMENTS W/ SUPPLIER
METAL LATHE
STEEL SUPPORT ANGLE, RE: ROOF OPENING SUPPORT FRAME DETAILS
FASTEN CURB TO SUPPORT ANGLE WITH 1/2" THROUGH BOLTS @ 36" OC
MAX
5/8" PUDDLE WELDS @ 18" OC FROM DECK TO SUPPORT ANGLES, OR #10
SCREWS @ 12" OC
TREATED WOOD BLOCKING, WIDTH TO MATCH RTU CURB
WOOD NAILER BY CURB SUPPLIER
WATERPROOFING RE: ARCH AND MECH
FAN/RTU. FASTEN TO CURB PER MANUFACTURER
2 3
5/8 5
FAN/RTU
DETAIL NOTES:
EXISTING STRUCTURAL BEARING WALL
EXISTING 10" JOISTS. REINFORCE WEBS PER
EXISTING 2 1/2" CONCRETE SLAB ON METAL LATH AND 2"
LIGHTWEIGHT CONCRETE
WHERE DOAS BEARS ON WALL, PROVIDE HSS2 1/2X2 1/2X1/4
X 9" LONG DIRECTLY BELOW UNIT CURB. HSS TO BE SNUG
BETWEEN TOP OF WALL AND UNDERSIDE OF
CONCRETE/WIRE MESH. ALTERNATE: GROUT SOLID
BETWEEN TOP OF WALL AND UNDERSIDE OF CONRETE.
ROOFTOP EQUIPEMENT CURB RE: 6/S050
ROOFTOP EQUIPEMENT RE: PLAN.
WHERE HRU BEARS ON WALL, PROVIDE HSS2 1/2X2 1/2X1/4
CONTINUOUSLY BELOW THE UNIT CURB, PROVIDING BREAKS
AT JOIST SEATS. HSS TO BE SNUG BETWEEN TOP OF WALL
AND UNDERSIDE OF CONCRETE/WIRE MESH. ALTERNATE:
GROUT SOLID BETWEEN TOP OF WALL AND UNDERSIDE OF
CONRETE.
HRU
DOAS
3@12 3/16
3@12 3/16
3@12 3/16
1 DETAIL NOTES:
EXIST DOUBLE ANGLE TOP CHORD
1/2" ROUND BAR TOP CHORD REINF.
EXISTING BOTTOM CHORD
EXIST ROUND BAR WEB DIAGONALS
3"x1/4" CONT PLATE
NOTE:
WEB REINF NOT SHOWN FOR CLARITY
D th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
SPUR #: 1794.13
/2
/2
:1
:4
A
M
TYPICAL DETAILS - STEEL
TJSCGB
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
06/28/2022
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
S050
3/4" = 1'-0"
SLAB ON GRADE JOINTS @ COLUMNS1
3/4" = 1'-0"
JOIST REINF @ POINT LOAD3
1" = 1'-0"
JOIST WEB REINFORCEMENT2
1 1/2" = 1'-0"
TYP OPENING DETAIL - EXISTING ROOF5
3/8" = 1'-0"
TYPICAL RTU SUPPORT- EXISTING ROOF43/8" = 1'-0"
ROOF OR FLOOR PENETRATION7
1 1/2" = 1'-0"
RTU SUPPORT - METAL DECK REINF6
3/4" = 1'-0"
SECTION AT BEARING WALL BELOW RTU8
1" = 1'-0"
JOIST CHORD REINFORCEMENT9
No. REVISION DESCRIPTION DATE cblauwiekel_stand-se PWS MO Seal cblauwiekel_stand-se
W8X24
S101
11 1
EXIST 10C@15.3
E X
IS
T
W F
F2.5
F2.5
EXIST W6x9
E X
IS
T
W 6X
W8X24
4444 5
S100
Sim
VERIFY RE: ARCH
6' - 1"
V E
R
IF
Y R
E : A
R C
H
5'
0"
F2.0
S101
PLAN NOTES:
EXISTING 10" DEEP SJ-102 AND 10" DEEP SJ-103 BAR JOISTS SPACED AS INDICATED.
LOCATIONS DIMENSIONED ONLY IN AREAS OF PENTRATIONS FOR CLARITY.
SPACINGS AND LOCATIONS SHALL BE FIELD VERIFIED
CANOPY FRAMING PER CANOPY SUPPLIER
EXIST 1 1/2" X 20 GA. STEEL FLOOR DECK WITH 4" (1 1/2" +2 1/2") LW CONC
INFILL BELOW EXISTING HEADER RE: ARCH. THICKNESS TO MATCH EXISTING WALL
3 1/2" DIA STD ADJUSTABLE PIPE COL (SCH 40). FRAME OUT WALL AROUND COLUMN
RE: ARCH
EXISTING METAL LATH WITH 2 1/2" CONC SLAB
REINFORCE FLOOR AT PENETRATION RE: 7/S050
NEW DUCT PENETRATION. RE: MECHANICAL PLAN FOR COORDINATION. PROVIDE
LINTEL RE: 4/S100
PLAN NOTES:
EXISTING 10" DEEP SJ-102 AND 10" DEEP SJ-103 BAR JOISTS SPACED AS
INDICATED. LOCATIONS DIMENSIONED ONLY IN AREAS OF PENTRATIONS
FOR CLARITY. SPACINGS AND LOCATIONS SHALL BE FIELD VERIFIED.
EXTERIOR CONC RE: CIVIL
EXIST 1 1/2" X 20 GA. STEEL FLOOR DECK WITH 4" (1 1/2" +2 1/2") LW CONC
INFILL BELOW EXISTING HEADER RE: ARCH. THICKNESS TO MATCH
EXISTING WALL
3 1/2" DIA STD ADJUSTABLE PIPE COL (SCH 40). FRAME OUT WALL AROUND
COLUMN RE: ARCH
EXISTING METAL LATH WITH 2 1/2" CONC SLAB
NEW DUCT PENETRATION. RE: MECHANICAL PLAN FOR COORDINATION.
PROVIDE LINTEL RE: 4/S100
W 8X
SHEET NOTES:
A. REFERENCE SHEET S001 FOR STRUCTRURAL GENERAL NOTES. REVIEW NOTES & DETAILS
FOR APPLICABILITY.
B. SEE ARCHITECTURAL DRAWING FOR DETAILS & DIMENSIONS NOT SHOWN.
C. REFER TO S050 FOR TYPICAL DETAILS.
D. SPREAD FOOTINGS DENOTED ON PLAN BY "Fx.x". REFER TO SCHEDULE ON THIS SHEET FOR
SIZE AND REINFORCING.
E. PROVIDE BLOCKOUTS IN SLAB FOR COLUMNS PER TYPICAL DETAIL
H. STEEL COLUMNS ARE DENOTED ON PLAN AS "Cx.x". REFER TO SCHEDULE ON THIS SHEET FOR
COLUMN SIZE, BASEPLATE TYPE, AND BASEPLATE DIMENSIONS.W8X24W8X24
11 1 1
EXIST 10C@15.3
E X
IS
T
W F
E X
IS
T
W F
EXIST W6x9
E X
IS
T
W 6X
W
8X
4 4 4 4 45 55 5
6 5
S050
Sim
S100
Sim
4" +/-
1' - 9 1/2" +/-
29' - 7 1/2" +/- 2' - 0" +/-
4" +/- 1' - 7" +/- 1' - 6 1/2" +/- 4" +/-
15' - 7" +/-1' - 10" +/-
7 7
2' - 0 1/2" +/- 8' - 2" +/-
1' - 9 1/2" +/-4" +/-
S101
S101
PLAN NOTES:
LOAD BEARING WALL
EXIST FIRE - 1HR WALL
DETAIL NOTES:
STANDARD PIPE COL (SCH 40), RE: TO PLAN FOR DIA
HEADER BEAM RE: PLAN
FRAME OUT WALL RE: ARCH
EXISTING STRUCTURAL BEARING WALL BEYOND
EXISTING 10" JOISTS
EXISTING 2 1/2" CONCRETE SLAB ON METAL LATH
EXISTING CONC. BEARING WALL
PROVIDE ATTACHMENT FROM STEEL POST TO STEEL BEAM.
USE (4) #12 SELF-DRILLING SCREWS
IF COLUMN ABOVE BEARS BETWEEN JOISTS SEATS, PROVIDE
HSS2 1/2X2 1/2X1/4 X 9" LONG DIRECTLY BELOW COLUMN.
HSS TO BE SNUG BETWEEN TOP OF WALL AND UNDERSIDE
OF CONCRETE/WIRE MESH. ALTERNATE: GROUT SOLID
BETWEEN TOP OF WALL AND UNDERSIDE OF CONRETE.
8 8
LEVEL 2
9' - 4"
T.O.S.
18' - 3 1/2"
T.O.S.
8' - 11"
LEVEL 1
0' - 0"
NOTES:
1. HEIGHT OF MASONRY ABOVE LINTEL MUST
BE MINIMUM OF 1/2 THE OPENING WIDTH
2. LINTELS SPECIFICALLY CALLED OUT ON
DRAWINGS SHALL GOVERN OVER THIS
SCHEDULE
4. ALL STEEL ANGLES SHALL HAVE SHORT LEG
HORIZONTAL (SLH) AND SHALL BE PRIME
PAINTED.
5. DRY PACK GROUT AROUND NEW ANGLES TO
ELIMINATE ANY GAPS BETWEEN LINTEL AND
CMU. USE N.S. 5000 PSI GROUT MIN.
L1 L2, L3, L4
L1
L2
L3
L4
UP TO 1'-8"
1'-9" TO 3'-0"
3'-1" TO 5'-0"
5'-1" TO 7'-0"
MARK OPENING SIZE LINTEL SIZE MIN BRG LENGTH
LINTEL SCHEDULE @ WALL OPENINGS
5/16" PL x WALL WIDTH - 1/2"
L3 1/2" x 3 1/2" x1/4"
L3 1/2" x 3 1/2" x5/16"
L5" x 3 1/2" x3/8"
3"
4"
4"
4"
DETAIL NOTES:
EXISTING BRICK
EXISTING CMU WALL
1/2" DIA GALVANIZED THREADED ROD. DRILL AND EPOXY INTO EXISTING CMU WALL. EMBED MIN 4"
INTO CMU. PROVIDE SCREENING TUBE
3/4" Ø STL PIPE TO PREVENT BRICK CRUSHING
WATER PROOFING RE: ARCH
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
SPUR #: 1794.13
/2
/2
:1
:4
A
M
FOUNDATION, 1ST AND 2ND FLOOR
PLAN
TJSCGB
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
06/28/2022
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
S100
N 1/8" = 1'-0"
1ST FLOOR FRAMING PLAN2
N 1/8" = 1'-0"
BASEMENT1
N 1/8" = 1'-0"
SECOND FLOOR FRAMING PLAN3
SCHEDULE - SPREAD FOOTING
TYPE MARK LENGTH WIDTH THICKNESS REINF
F2.5 2' - 6" 2' - 6" 2' - 6" (4) #4 EA WAY,
BOT
F2.0 2' - 0" 2' - 0" 3' - 6" (3) #4 EA WAY,
TOP & BOT
3/4" = 1'-0"
SECTION AT HEADER5
No. REVISION DESCRIPTION DATE
1" = 1'-0"
CMU STEEL LINTEL - EXISTING WALL4
1 1/2" = 1'-0"
LADDER ANCHORAGE6
cblauwiekel_stand-se PWS MO Seal cblauwiekel_stand-se
PLAN NOTES:
EXISTING 10" DEEP SJ-102 @ 2' - 5 3/4" OC
EXISTING 10" DEEP SJ-S102 @ 2' - 4" OC
EXISTING 10" DEEP SJ-S103 @ 1' - 7" OC
EXISTING 1 1/2" DEEP x 20 GA ROOF DECK WITH 4" THICK (1 1/2" + 2 1/2") LIGHT
WT. CONC. FILL
EXISTING 8" CMU BEARING WALL
EXISTING BEARING WALL
EXISTING METAL LATH WITH 2 1/2" CONC SLAB AND 2" LIGHT WEIGHT CONC
TOPPING WITH #10 - 6"X6" MESH
AT RTU BEARING POINTS ALONG BEARING WALL PROVIDE 2 1/2 X 2 1/2 X 1/4 HSS
SNUG BETWEEN TOP OF WALL AND UNDERSIDE OF CONCRETE/WIRE MESH.
PROVIDE BREAK IN HSS AT JOIST SEATS. ALTERNATE: GROUT SOLID BETWEEN
TOP OF WALL AND DECK.
REINFORCE ALL JOIST WEBS PER AND REINFORCE TOP AND BOTTOM
CHORD PER . SHORE JOIST TO TO REMOVE LOAD PRIOR TO
REINFORCING
HRU SHALL NOT BEAR WEST OF LOAD BEARING WALL. CENTER OVER THREE
JOISTS. FIELD VERIFY LOCATION OF JOISTS IN RELATION TO HRU. IF OFF
CENTER ALSO REINFORCE JOISTS THAT ARE DIRECTLY ADJACENT TO THE UNIT.
PROVIDE JOIST REINFORCEMENT RE: DIRECTLY BELOW THE
PERIMETER OF THE DOAU AND HRU UNITS AT EACH JOIST
NON-PENETRATING, FALL PROTECTION SYSTEM RE: ARCH
NEW COLUMN FOR HOIST WHEEL SUPPORT RE: 4/S101
NEW OSHA COMPLIANT LADDER AND LADDER CAGE, ANCHOR TO EXISTING WALL
RE: 6/S100
REINFORCE ROOF AT PENETRATION RE:7/S050
/2 S0509
/3 S05011
/9 S050
SHEET NOTES:
A. REFERENCE SHEET S001 FOR STRUCTRURAL GENERAL NOTES. REVIEW NOTES & DETAILS
FOR APPLICABILITY.
B. SEE ARCHITECTURAL DRAWING FOR DETAILS & DIMENSIONS NOT SHOWN.
C. REFER TO S050 FOR TYPICAL FRAMING DETAILS.
D. JOIST LOCATIONS ARE BASED ON EXISTING DRAWINGS. FIELD VERIFY JOIST SPACING AND
NOTIFY ENGINEER IF SPACING DIFFERS FROM PLAN AT MECHANICAL EQUIPMENT
LOCATIONS.
E. AT ALL WELDING LOCATIONS RE: GENERAL NOTES AND SPECIFICATIONS FOR
REQUIREMENTS.
22 3
1' - 4 1/2" 1' - 4 1/2"
E X
IS
T
W 6X
S
T L
B M
ELEVATOR
SHAFT
OPEN
E X
IS
T
W 6X
S
T L
B M
DOAU - 1
8' - 4" X 4' - 6"
3316 LBS (W/ CURB)
HRU - 1
2' - 9" X 5' - 8"
1067 lbs
1'
M A
X
1'
M A
X
DOAU - 2
8' - 4" X 4' - 6"
3316 LBS (W/ CURB)
HRU - 2
2' - 9" X 5' - 8"
1067 lbs
2'
M A
X
2'
9" M
A X
10 10
2' -9
M
A X
2' -9
M
A X
11 1111 11
S050
Sim
11 11
11 11 11
9 9 9 9
9 9 9
9 9 9 9
9 99
7 3/4" 2' - 5 3/4" 2' - 5 3/4" 2' - 5 3/4" 2' - 5 3/4" 7 3/4"14' - 10 1/2" 2' - 5 3/4"
2' - 4"
1' - 7"
2' - 4"
28' - 0" 4' - 6 1/2"
6 1/2"
6 1/2"
S101
S101
Sim
6' - 1"
WORK
POINT
DETAIL NOTES
CANOPY COLUMNS RE: CANOPY SUPPLIER
PROVIDE EITHER HEADED ANCHOR RODS, OR
ALTERNATIVELY PROVIDE 3" SQ x 1/4" PL WASHER
WITH HEAVY HEX NUT. TACK WELD WASHER AND
NUT TO ANCHOR ROD
BASE PLATE AND ANCHOR RODS, PER CANOPY
SUPPLIER
1 1/2" MIN NON-SHRINK NON-METALLIC GROUT
CONCRETE FOOTING RE: PLAN
BOND BREAK
PROVIDE BLOCKOUT IN SLAB FOR STEEL POST
PROVIDE OVERSIZED HOLES IN BASE PLATE AND
1/4" PL WASHER WITH HEAVY HEX NUTS ON
ANCHOR RODS. WELD WASHERS TO BASE PLATE
1" MIN ALL 4 SIDES
RODS TO EXTEND 1/2" MIN THRU NUTS TOP AND
BOT
NOTES:
A. ACCOUNT FOR GROUT THICKNESS WHEN
DETERMINING BOTTOM OF BASE PLATE ELEVATION
B. ANCHOR RODS SHALL BE F1554 GR. 36 UNO
C. PROVIDE SIMILAR DETAIL AT VERTICAL CANOPY
COLUMN
D. FOOTING AND ANCHORAGE ARE NOT DESIGNED
FOR BASE FIXITY
M
IN
U N
O
10.00° 20.00°
DETAIL NOTES:
EXISTING BRICK
EXISTING CMU WALL
NEW COLUMN RE: PLAN
1/2" DIA GALVANIZED THREADED ROD.
DRILL AND EPOXY INTO EXISTING CMU
WALL. EMBED MIN 4" INTO CMU.
PROVIDE SCREENING TUBE
L3X2X3/16 ANGLE. 3" LEG VERTICAL.
COPE ENDS AND BEND 45 DEGREES
(2) 1/2" GALVANIZED NUTS AND (3)
WASHERS
WATER PROOFING RE: ARCH
3 1/2" x 3 1/2" x 1/4" SHEAR TAB. WELDED
TO COLUMN WITH 3/16" DOUBLE FILLET
3/4" Ø STL PIPE TO PREVENT BRICK
CRUSHING
4 4
1'
8" +/-
45.00°
.0
0°
0_FOUNDATION PLAN
100' - 0"
1_FRAMING PLAN
109' - 4"
DETAIL NOTES:
HSS5X5X1/4 COLUMN. PROVIDE 1/4" CAP PLATE
WELDED TO TOP.
HOIST ARM BY HOIST ARM SUPPLIER. HOIST ARM TO
SUPPORT 250 LBS MAX. BOLT, WELD, OR CLAMP TO
PIPE PER MANUFACTURER SPECIFICATIONS.
HOIST WHEEL TO BE SUPPLIED. MAX LIFTED LOAD OF
125 LBS. WHEEL TO SUPPORT 250 LBS.
FASTEN TO WALL RE: 5/S101
11" x 11" x 3/8" BASE PLATE ON 2" GROUT. (4) 3/4" ANCHOR RODS IN 8"x8" PATTERN, EMBED 8" MIN. WELD
HSS TO BASE PLATE WITH 3/16" FILLET ALL AROUND.
(2) #4 DOWELS x 2' - 0". DRILL AND EPOXY 5" MIN INTO
EXISTING FDN WALL. CLEAN AND ROUGHEN THE
SURFACE OF EXISTING FOOTING, AND APPLY A
BONDING AGENT PRIOR TO POURING NEW FOOTING
AGAINST IT.
FTG AND REINF RE: 2/S100
NOTE: ALL STEEL SHALL BE PRIMED AND PAINTED
4' - 0" MAX
125 LB
MAX
LB
T
E N
S
IO
N M
A X
3'
M
IN
7'
6" M
A X
D E
T E
R M
IN
E
D
IN
F
IE
LD
D
IM
T O
G R
A D
E
6"
1_FRAMING PLAN
109' - 4"
DETAIL NOTES:
CANOPY, RE: CANOPY SUPPLIER
WATERPROOFING, RE: ARCH
L4X4X1/4 ANGLE ALONG LENGTH OF CANOPY.
1/2" DIA GALVANIZED THREADED ROD @ 12" OC. DRILL AND EPOXY INTO EXISTING CMU WALL.
EMBED MIN 4" INTO CMU. PROVIDE SCREENING TUBE.
3/4" Ø STL PIPE TO PREVENT BRICK CRUSHING.
PROVIDE SLOTTED SLIP CONNECTION TO CANOPY. COORDINATE WITH CANOPY SUPPLIER
NOTE: LEDGER WAS DESIGNED FOR 170 PLF VERTICAL LOAD. LEDGER IS NOT DESIGNED FOR
TENSION.
4 6 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
SPUR #: 1794.13
/2
/2
:1
:4
A
M
ROOF FRAMING PLAN
TJSCGB
FINAL BID DOCUMENTS
EHRM TRAINING & ADMIN
SUPPORT
06/28/2022
589-21-702
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
S101
N 1/4" = 1'-0"
ROOF1
1/2" = 1'-0"
CANOPY SECTION21 1/2" = 1'-0"
HSS BRACE - 4 BOLT BASE PLATE3
No. REVISION DESCRIPTION DATE
1 1/2" = 1'-0"
PIPE COLUMN CONN TO WALL5
3/4" = 1'-0"
HOIST COLUMN4
3/4" = 1'-0"
CANOPY CONNECTION AT WALL6
cblauwiekel_stand-se PWS MO Seal cblauwiekel_stand-se
| Sheets |
| S001 - STRUCTURAL GENERAL NOTES |
| S050 - TYPICAL DETAILS - STEEL |
| S100 - FOUNDATION, 1ST AND 2ND FLOOR PLAN |
| S101 - ROOF FRAMING PLAN |
File details come from the government source that posted it. Updated .