This solicitation is for an EHRM Training and Admin Space Support Construction project at the Kansas City VA Medical Center. The solicitation seeks to upgrade EHRM infrastructure through the construction of new training and administration spaces. The Department of Veterans Affairs Technology Acquisition Center Austin is the contracting agency. The project involves construction services including building new training classrooms and administration offices, upgrading mechanical, electrical and technology systems, and demolishing existing network equipment and cabling. The response due date is not provided in this document.
View the file
Other files for this federal contract opportunity
Show all 36
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABBREVIATIONS
STANDARD MOUNTING HEIGHTSANNOTATION
ELECTRICAL:
AUDIBLE APPLIANCES (CENTERLINE) 84"
ALARMS 48"
ANNUNCIATOR PANELS 48"
CLOCK OUTLETS (CENTERLINE) 84"
CONTROLS (TOP) 48"
EXIT SIGNS (WALL-MOUNTED, BOTTOM) 80"
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY) 60"
FIRE ALARM BELL (EXTERIOR) 120"
FIRE ALARM CONTROL PANEL/UNIT (DISPLAY) 60"
INTERCOM (AFEA ONLY) 36"
INTERCOMS (TOP) 48"
PANELS & PANELBOARDS (TOP) 72"
PULL STATIONS (HANDLE) 48"
PHOTOCELLS 144"
RECEPTACLES (BOTTOM) 18"
RECEPTACLES (EXTERIOR) 24"
RECEPTACLES (GARAGES) 26"
RECEPTACLES IN EQUIPMENT ROOMS (TOP) 48"
REMOTE INDICATING LIGHT (EQUIPMENT ROOMS) 48"
REMOTE INDICATING LIGHT (FINISHED AREAS) CEILING
SAFETY SWITCHES & STARTERS 48"
SWITCHES (TOP) 48"
TELEPHONE/DATA/TV OUTLETS (BOTTOM) 18"
VISIBLE APPLIANCES (CENTERLINE) 84"
(AFF, AFG UNLESS NOTED OTHERWISE)
CU
MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT
PLUMBING PLAN NOTE CALL OUT
ELECTRICAL, TECHNOLOGY OR FIRE ALARM PLAN NOTE
CALL OUT
PLUMBING EQUIPMENT DESIGNATION
EQUIPMENT DESIGNATION TAG
OWNER FURNISHED, CONTRACTOR INSTALLED
EQUIPMENT DESIGNATION
NEW WORK TO EXISTING WORK CONNECTION POINT
IC
CATV
FO
T
D
S
IC
S
WAP
#/#TV
M
S
V
COMMUNICATIONS OUTLET, TYPE AS NOTED
COMMUNICATIONS OUTLET, FLOOR BOX, TYPE AS NOTED
WIRELESS ACCESS POINT, CEILING MOUNTED
COMMUNICATIONS OUTLET, CEILING MTD, TYPE AS NOTED
SPEAKER, WALL MOUNTED
SPEAKER, CEILING MOUNTED
SERVER RACK, TWO-POST, FLOOR MOUNTED
3/4"x4'x8', FIRE-RATED PLYWOOD BACKBOARD
GROUND BAR, TYPE AS NOTED
SERVER RACK, WALL MOUNTED
CABLE TRAY, TYPE AS NOTED
CABLE TELEVISION LINE
FIBEROPTIC LINE
TELEPHONE LINE
FIBER OPTIC BACKBONE PATHWAY "A"
DATA LINE
SPEAKER LINE
INTERCOM LINE
INTERCOM, "M" DENOTES MASTER STATION
VOLUME CONTROL, WALL MOUNTED
MULTI-SERVICE POWER POLE WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
SERVER RACK, FOUR-POST, FLOOR MOUNTED
SERVER CABINET, FLOOR MOUNTED
# = DATA, # = QUANTITY OF CABLES
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
# = DATA, # = QUANTITY OF CABLES
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#V = VOICE, # = QUANTITY OF CABLES
# = DATA, # = QUANTITY OF CABLES
#E = ELEVATOR, # = QUANTITY OF CABLES
#FMS = FACILITY MONITORING SYSTEM,
# = QUANTITY OF CABLES
TELECOMMUNICATIONS SYMBOLS
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#V = VOICE, # = QUANTITY OF CABLES
M (CONT'D)
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
X
W
V
U
T
S
R
P
O
N
M
L
K
J
I
H
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLUOR FLUORESCENT
FO FIBER-OPTIC
FP FIRE PROTECTION
FT FEET OR FOOT
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G
F
E
D
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMER. MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
ETD EXISTING TO BE DEMOLISHED
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
C CONDUIT
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER
INSTALLED
CFE CONTRACTOR FURNISHED
EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
C
B
A
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VCM VERTICAL CABLE MANAGER
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
TC TIME CLOCK
TEL TELEPHONE
TO TELECOMMUNICATIONS OUTLET
TR TELECOMMUNICATIONS ROOM
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REC RECESSED
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RU RACK UNIT
N NEUTRAL
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
JB JUNCTION BOX
J-BOX JUNCTION BOX
XFER TRANSFER
XFMR TRANSFORMER
XP EXPLOSION PROOF
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
W WATT
WAO WORK AREA OUTLET
WP WEATHERPROOF
IESNA ILLUMINATION ENGINEERING SOCIETY
OF NORTH AMERICA
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
G OR GND GROUND OR GENERATOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR
PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
POE POWER OVER ETHERNET
PP PATCH PANEL
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
1P SINGLE POLE
1PH SINGLE-PHASE
3P THREE POLE
3PH THREE-PHASE
3W THREE WIRE
4W FOUR WIRE
A/C AIR CONDITIONING
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR
AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
HCM HORIZONTAL CABLE MANAGER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BLK BLOCK
BPIP BOILER PLANT
INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY PASS
DETAIL REFERENCE
SECTION CUT DESIGNATION
EP-101
EP-101
PATH-A
PATH-B FIBER OPTIC BACKBONE PATHWAY "B"
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
No. REVISION DESCRIPTION DATE
FINAL BID DOCUMENTS
589-21-702TECHNOLOGY SYMBOLS & ABBREVIATIONS
T-000
EHRM TRAINING &
SUPPORT
SPUR #: 1794.13
06/28/2022 SR NR 72
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
N/A
6/
/2
4:
:3
PM
CRAWLSPACE
CS1
CRAWLSPACE
CS2
CRAWLSPACE
CS4
CRAWLSPACE
CS3
CRAWLSPACE
CS5
MECHANICAL
B07
MECHANICAL
B02
MECHANICAL
B01
MECH
B07A STAIR 1
1 1 T-300
DN
DN
UP
UP
3-
3-
3-111B
3-
3-
3-
S2-1A
3-
2B
3-
2A
3-111E
3-111D
3-
2C 3-
2D
S1 -1
B
S2-1B
S1-1A
3-
3-
1C
3-
1A
3-
3-
3-111
ADMIN
56 SF
EX ELEV MECH
3-100
EX ELEV
STAIR 2
STAIR 1
799 SF
CLASSROOM /
IV TESTING
3-112
20 SF
EX HAC
CLOSET
3-111A
34 SF
EX STOR
3-112A
34 SF
EX STOR
3-112B
131 SF
BREAKROOM
3-10177 SF
EX ENTRY
3-105
192 SF
CONFERENCE
ROOM
3-102
100 SF
TELECOM
3-108
210 SF
ADMIN
3-110
283 SF
ADMIN
3-103
316 SF
ADMIN
3-107
59 SF
MENS RR
3-106
59 SF
WOMENS RR
3-104
CORRIDOR
C1-3-1
WAP
WAP WAP
4 4
4 4 4
666666
T-300
WAP
DN
DN
3-
S1 -2
3-207B
3-
S2-2
3-
3-
3-
7A
3-
3-
C2-3-2
CORRIDOR
131 SF
BREAKROOM
3-201
EX ELEV
STAIR 2
STAIR1
245 SF
CLASSROOM /
IV TESTING
3-200
306 SF
CLASSROOM /
IV TESTING
3-210
98 SF
HAC
3-209
237 SF
WAITING
ROOM
3-203
372 SF
CLASSROOM /
IV TESTING
3-211
59 SF
MENS RR
3-208
59 SF
WOMENS RR
3-206
WAP
4 4
44 4
44 4 4
TECHNOLOGY KEYNOTES
INSTALL BASKET TRAY (12" W, 6" H) ABOVE DROP CEILING ALONG HALLWAY. INSTALL J-HOOKS IN
AREAS WHERE BASKET TRAY IS INAPPROPRIATE.
INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON BOTH ENDS. INBOUND REDUNDANT FIBER BACKBONE 'B' INSTALLED IN DIFFERENT CONDUIT IN
THIS PATHWAY.
INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE CONNECTORS
ON BOTH ENDS.
4" VERTICAL CONDUIT SLEEVES FOR FIBER OPTIC BACKBONE CABLING.
4" VERTICAL CONDUITS FOR CATEGORY CABLING.
CONDUIT BANK FOR FUTURE MODULAR BUILDINGS.
GENERAL PLAN NOTES
1. CONTRACTOR SHALL COORDINATE WITH CUSTOMER FOR WORK AREA OUTLET (WAO) LOCATIONS.
2. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND
DURING INSTALLATION.
3. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
4. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL
CUT-OVER TO THE NEW CABLING.
5. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO, FOUR, OR SIX CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN
IT'S DESIGNATED TR.
6. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED
UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
7. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL
AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)
8. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS
ALONG THE CABLE PATHWAYS.
9. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
10. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING
BUSBAR.TRAY SYSTEM, TO THE TELECOMMUNICATIONS
11. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE
WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR
SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER
ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE
RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING
WAS REMOVED.
12. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE
SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE
THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.
13. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND
CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
14. DEMO NETWORK RACK AND ALL NETWORK AND TELEPHONE CABLING, THROUGHOUT THE BUILDING, FROM THE BASEMENT TR B07A.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
No. REVISION DESCRIPTION DATE
FINAL BID DOCUMENTS
589-21-702TECHNOLOGY FLOOR PLAN
T-100
EHRM TRAINING &
SUPPORT
SPUR #: 1794.13
06/28/2022 SR NR 72
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
6/
/2
4:
:3
PM
N N
N
1 1/8" = 1'-0"
BASEMENT
2 1/8" = 1'-0"
LEVEL 1
3 1/8" = 1'-0"
LEVEL 2
BLDG 3
BLDG 56
EXISTING UTILITY TUNNEL.
NEW CONDUIT BANK, FUTURE FIBER OPTIC BACK BONE CONNECTION TO MODULAR BUILDINGS.
INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON BOTH ENDS. INBOUND REDUNDANT FIBER BACKBONE 'B' INSTALLED IN DIFFERENT CONDUIT IN
THIS PATHWAY.
INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE CONNECTORS
ON BOTH ENDS.
IN-GROUND HAND HOLE FOR ACCESS TO PULL POINTS ALONG NEW CONDUIT BANK.
TECHNOLOGY KEYNOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
No. REVISION DESCRIPTION DATE
FINAL BID DOCUMENTS
589-21-702TECHNOLOGY SITE PLAN
T-200
EHRM TRAINING &
SUPPORT
SPUR #: 1794.13
06/28/2022 SR NR 72
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
6/
/2
4:
:3
PM
1 1/16" = 1'-0"
INTER-BUILDING FIBER OPTIC BACKBONE PATHWAYSN
AutoCAD SHX Text
COMM
INSTALL BASKET TRAY (12"W, 4"H) ABOVE RACK IN TR 3-108 AS SHOWN ON PLANS
INSTALL (2) QUAD POST RACKS (7'H, 19"W, 29"D), WITH (3) VERTICAL CABLE MANAGERS IN TR 3-108.
INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON BOTH ENDS. INBOUND REDUNDANT FIBER BACKBONE 'B' INSTALLED IN DIFFERENT CONDUIT IN
THIS PATHWAY.
INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24
STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE
CONNECTORS ON BOTH ENDS.
DEMO DATA AND TELEPHONE CABLING AFTER CUT-OVER.
DEMO NETWORK RACK AFTER CUT-OVER
DEMO DATA AND TELEPHONE CABLING FROM WAOs ALL THE WAY BACK TO OLD TR 3-B07A.
4" VERTICAL CONDUIT SLEEVES FOR FIBER OPTIC CABLE FROM BASEMENT
TECHNOLOGY KEYNOTES
MECH
B07A
100 SF
TELECOM
3-108
3-
GENERAL PLAN NOTES
1. CONTRACTOR SHALL COORDINATE WITH CUSTOMER FOR WORK AREA OUTLET (WAO) LOCATIONS.
2. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND
DURING INSTALLATION.
3. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
4. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL
CUT-OVER TO THE NEW CABLING.
5. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO, FOUR, OR SIX CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN
IT'S DESIGNATED TR.
6. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED
UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
7. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL
AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)
8. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS
ALONG THE CABLE PATHWAYS.
9. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
10. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING
BUSBAR.TRAY SYSTEM, TO THE TELECOMMUNICATIONS
11. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE
WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR
SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER
ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE
RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING
WAS REMOVED.
12. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE
SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE
THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.
13. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND
CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
14. DEMO NETWORK RACK AND ALL NETWORK AND TELEPHONE CABLING, THROUGHOUT THE BUILDING, FROM THE BASEMENT TR B07A.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
No. REVISION DESCRIPTION DATE
FINAL BID DOCUMENTS
589-21-702TECHNOLOGY ENLARGED PLAN
T-300
EHRM TRAINING &
SUPPORT
SPUR #: 1794.13
06/28/2022 SR NR 72
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
6/
/2
4:
:3
PM
1 3/4" = 1'-0"
TECHNOLOGY DEMO PLANS - BASEMENT2 3/4" = 1'-0"
TECHNOLOGY PLANS - LEVEL 1 -TR 3-108
TELECOMMUNICATIONS EQUIPMENT RACK, 7'H x 19"W x 29"D, 4-POST, OPEN FRAME TYPE.
VERTICAL CABLE MANAGER, 6"Wx 6"D, W/DOOR
WIRE-MESH (WIRE BASKET) CABLE TRAY - 12"W x 4"H (TYPICAL). RADIUS DROPS REQUIRED WHERE
CABLES EXIT.
PLYWOOD BACKBOARD, 4'W x 8'H x 3/4"T, AC GRADE, FIRE-RETARDANT, PAINTED W/FIRE
RETARDANT PAINT (TYPICAL ON 3 WALLS)
INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON BOTH ENDS. INBOUND REDUNDANT FIBER BACKBONE 'B' INSTALLED IN DIFFERENT CONDUIT IN
THIS PATHWAY.
INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE CONNECTORS
ON BOTH ENDS.
144 PORT FIBER OPTIC PATCH PANEL, LOADED WITH (2) 24 PORT OS2 ADAPTER PLATES TO
ACCOMMODATE BOTH 'A' & 'B' REDUNDANT FIBER OPTIC CABLES. FIBER OPTIC CABLES TO BE
FIELD TERMINATED IN THIS PATCH PANEL WITH LC TYPE CONNECTORS.
CATEGORY 6A UNSHIELDED TWISTED PAIR (UTP) HORIZONTAL (STATION) CABLES INBOUND FROM
THE VARIOUS WORK AREA OUTLETS (WAO) DESIGNATED TO THIS TR.
1RU 48 PORT, ANGLED, EMPTY PATCH PANEL, POPULATED WITH (48) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS (TYPICAL). CATEGORY 6A STATION CABLES TO BE TERMINATED ONTO JACKS PER
THE ANSI/TIA/EIA T568B TERMINATION SCHEME.
1RU RACK-MOUNTED HORIZONTAL CABLE MANAGEMENT PANEL (TYPICAL) MOUNTED BETWEEN
GOVERNMENT FURNISHED/GOVERNMENT INSTALLED (GFGI) DATA SWITCHES.
WALL ANGLE BRACKET TO SUPPORT WIRE MESH (WIRE BASKET) CABLE RUNWAYS ON ALL (4)
WALLS.
TECHNOLOGY KEYNOTES
SPECIFIED BY DIVISION 26
CFCI RACK-MOUNT UPS
SPECIFIED BY DIVISION 26
CFCI RACK-MOUNT UPS
GFGI DATA EQUIPMENT
GFGI DATA SWITCHES
GFGI DATA SWITCHES
THIS AREA
GFGI DATA SWITCHES
GFGI DATA SWITCHES
A B
C D
F E
BUILDING 3
TR 3-108
(1) 2RU FIBER OPTIC LIU
(2) 24 STRAND OS2
BUILDING 1
SR/DC/MCR
(1) 2RU FIBER OPTIC LIU
(2) 24 STRAND OS2
FIBER OPTIC PATHWAY 'B'
FIBER OPTIC PATHWAY 'A'
GENERAL PLAN NOTES
1. CONTRACTOR SHALL COORDINATE WITH CUSTOMER FOR WORK AREA OUTLET (WAO) LOCATIONS.
2. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND
DURING INSTALLATION.
3. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
4. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL
CUT-OVER TO THE NEW CABLING.
5. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO, FOUR, OR SIX CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN
IT'S DESIGNATED TR.
6. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED
UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
7. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL
AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)
8. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS
ALONG THE CABLE PATHWAYS.
9. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
10. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING
BUSBAR.TRAY SYSTEM, TO THE TELECOMMUNICATIONS
11. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE
WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR
SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER
ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE
RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING
WAS REMOVED.
12. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE
SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE
THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.
13. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND
CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
14. DEMO NETWORK RACK AND ALL NETWORK AND TELEPHONE CABLING, THROUGHOUT THE BUILDING, FROM THE BASEMENT TR B07A.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
No. REVISION DESCRIPTION DATE
FINAL BID DOCUMENTS
589-21-702TECHNOLOGY RACK ELEVATIONS & RISER
DIAGRAM PLAN
T-400
EHRM TRAINING &
SUPPORT
SPUR #: 1794.13
06/28/2022 SR NR 72
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
6/
/2
4:
:3
PM
1 1" = 1'-0"
RACK ELEVATION - LEVEL1 - TR 3-108 (LOOKING NORTH)2 NONE
FIBER OPTIC BACKBONE RISER DIAGRAM
J-HOOK CAPACITY FOR CAT6A CABLE
J-HOOK SIZE
1" 1-5/16"
2" 3" 4"
CAPACITY
BASED ON 70% FILL
TYPICAL J-HOOK, CABLE LOOP IN
CEILING ABOVE STATION JACK. J-HOOK, SIZES AS
NEEDED
1/4" OR 3/8" THREADED ROD OR #12 TO #8
HANGER WIRE ATTACHED TO STRUCTURE
ABOVE. (DO NOT USE EXISTING CEILING
HANGER WIRES. MUST HAVE ITS OWN
HANGER WIRE.)
PARALLEL MOUNTING PERPENDICULAR MOUNTING
MOUNTING PLATE FOR CABLE TRAY TO EQUIPMENT
RACKS. KIT INCLUDES ALL MOUNTING HARDWARE.
CHATSWORTH PRODUCTS, INC.: PN 10595-712 (12")
CHATSWORTH PRODUCTS, INC.: PN 10595-718 (18")
CHATSWORTH PRODUCTS, INC.: PN 11312-712
CHATSWORTH PRODUCTS, INC. PN 11421-712
WALL ANGLE BRACKET FOR 12" CABLE TRAY WITH
J-BOLT KIT INCLUDES HEX NUTS AND LOCK WASHERS.
SUPPORT ATTACHES TO PLYWOOD BACKBOARD AS
SPECIFIED.
TRIANGULAR SUPPORT BRACKET FOR CABLE TRAY
TO RACK ATTACHMENT.
3/4" FIRE-RETARDANT TREATED PLYWOOD
SPANNING AT LEAST TWO BUILDING
STUDS, OR IF THAT IS NOT POSSIBLE,
ANCHORED INTO AT LEAST ONE STUD
AND TOGGLED INTO THE DRYWALL WITH
5/16" OR LARGER TOGGLE BOLT WITH
FENDER WASHERS.
NUT, 5/16-18 HEX,
STEEL 2 PLACES
WASHER, SLIT LOCK, FOR
5/16, SCR STEEL, 2 PLACES
5/16" LAG BOLTS, FOR PLYWOOD
BACKER BOARDS OR 5/16" HEX
CAPBOLTS AND APPROPRIATE WALL
ANCHORS FOR CONCRETE WALLS
FLAT WASHER,
FOR 5/16" BOLTS
J-BOLT, 5/16-18 THD'D
X 2.25" LONG, 2 PLACES
A1-A035WRAPAROUND CABLE
LABEL WITHIN 6" OF EACH
END OF THE CABLE
ALL LABELING SHALL BE ANSI/TIA/EIA/606C COMPLIANT. BLACK LETTERING
ON WHITE FIELD. MACHINE PRINTED. FURTHER GUIDANCE ON
ADMINISTRATION MAY BE SPECIFIED IN OTHER SECTIONS OF THIS DESIGN
PACKAGE.
RADIUS DROP
RADIUS DROP ATTACHES TO THE TOP OF THE CABINET AND
PROVIDES
A SMOOTH CURVED SUPPORT WHERE CABLES EXIT OR ENTER THE
CABLE MANAGEMENT SPACE ALONG THE SIDES OF THE CABINET.
· ATTACHES TO THE TOP OF THE CABINET TO SUPPORT CABLES
AS THEY EXIT/ENTER THE CABINET
· RADIUS DROP IS 11"L (279 MM) WITH A 1.3" (33MM) DIAMETER
RADIUS
· INCLUDES: RADIUS DROP, INSTALLATION HARDWARE
· MATERIAL: ALUMINUM; SELECT PART NUMBER TO MATCH THE
COLOR OF THE CABINET
.90
.65 eXtreme 10G QuickPort Connector, Channel-Rated, 8-Conductor
6110G-RX6
LEVITON
TYPICAL FACEPLATE WILL BE INSTALLED WITH TWO RJ45s. HIGH DENSITY FACEPLATES WILL BE ISNTALLED WITH FOUR RJ45s.
TYPICAL WORK AREA OUTLET FACEPLATE WILL BE INSTALLED WITH CATEGORY
6A COMPONENT-COMPLIANT 8P8C MEDIA INTERFACE CONNECTORS (RJ45).
EACH CONNECTOR WILL BE TERMINATED TO HIGH QUALITY CATEGORY 6A
HORIZONTAL CABLING WHICH WILL TERMINATE IN THE TELECOMMUNICATIONS
ROOM AS SPECIFIED ELSEWHERE IN THIS DESIGN PACKAGE. ALL HORIZONTAL
UTP SHALL BE CATEGORY 6A AND TERMINATED TO T568B.
RECOMMENDED UTP PATCH PANEL:
LEVITON e2XHD-BLK HIGH-DENSITY ANGLED
48 POSITION
ONE (1) RACK UNIT PER PANEL
TYPICAL WALL-MOUNT (VOIP) OUTLET TYPICAL FLOOR -MOUNT OUTLET
TYPICAL HIGH DENSITY WALL MOUNTED WORK AREA STANDARD DENSITY WALL MOUNTED WORK AREA
OUTLET CONFIGURATION OUTLET CONFIGURATION
FOUR POSITION FACEPLATE
MOUNTED ON SINGLE GANG
WORKBOX. FACEPLATE COLOR
SPECIFIED BY OTHERS.
TWO CATEGORY 6A
8P8C OUTLETS ACTIVE
FOR TELEPHONY/DATA
FOUR POSITION FACEPLATE
MOUNTED ON SINGLE GANG
WORKBOX. FACEPLATE COLOR
SPECIFIED BY OTHERS.
FOUR CATEGORY 6A 8P8C
OUTLETS ACTIVE FOR
TELEPHONY/DATA
SINGLE GANG WORKBOX
WITH TWO CONNECTOR
CHASSIS.
SINGLE GANG
WORKBOX WITH ONE
CONNECTOR
CHASSIS.
MINIMUM OF FOUR
CATEGORY 6A 8P8C
OUTLETS FOR DATA OR
TELEPHONY
ONE CATEGORY 6A
8P8C OUTLET
ACTIVE FOR
TELEPHONY
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
No. REVISION DESCRIPTION DATE
FINAL BID DOCUMENTS
589-21-702TECHNOLOGY DETAILS
T-500
EHRM TRAINING &
SUPPORT
SPUR #: 1794.13
06/28/2022 SR NR 72
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
N/A
6/
/2
4:
:3
PM
1 CABLE SUPPORTS (J-HOOK) DETAIL2 CABLE TRAY TO RACK SUPPORT DETAIL3 CABLE TRAY WALL SUPPORT DETAIL 1
4 CABLE TRAY WALL SUPPORT DETAIL 2
6 CABLE LABELING DETAIL
5 TYPICAL RADIUS DROP DETAIL
7 CATEGORY 6A UTP JACK (RJ-45 TYPE) DETAIL8 UNSHIELDED TWISTED PAIR (UTP) PATCH PANEL DETAIL
9 TELECOMMUNICATIONS OUTLET DETAIL
RECOMMENDED CASSETTE: LEVITON HDX ENTERPRISE MTP
FIBER TYPE: OM4/OS1
FIBER COUNT: 12-FIBER
CONNECTOR (FRONT): LC CONNECTOR
(REAR): MPO POLARITY: TYPE A
RECOMMENDED FIBER DISTRIBUTION CABINET:
LEVITON ANGLED OPT-X UHDX
144 FIBER
ONE (1) RACK UNIT
TO PBB/SBB
IRREVERSIBLE CRIMP CONNECTOR
EXAMPLE “A” EXAMPLE “B”
UNIT BONDING CONDUCTOR (6AWG)
TOP-MOUNTED RBB RACK BONDING CONDUCTOR (6AWG)
TO PBB/SBB
TELECOMMUNICATIONS
EQUIPMENT BONDING
CONDUCTOR (TEBC) – 6AWG IRREVERSIBLE
CRIMP CONNECTOR
CABLE TRAY BONDING
CONDUCTOR. TYPICAL AT EACH
SECTION CONNECTION POINT
RACK
ISOLATION
PADS (IF
APPLICABLE)
RACK BONDING CONDUCTOR
EXTENDED TO BOTTOM OF RACK
TO ACCOMMODATE FUTURE
GROWTH
INDIVIDUAL EQUIPMENT BONDING
CONDUCTORS FROM EACH PIECE
OF EQUIPMENT AND RACK TO THE
RACK BONDING CONDUCTOR
RACK BONDING
CONDUCTORS – ALL
CONDUCTORS
ROUTED TO PBB/ SBB
TWO-HOLE COMPRESSION
LUGS (RACKS SHALL NOT BE
MODIFIED IF ONLY ONE-HOLE IS
PROVIDED; USE ONE-HOLE
COMPRESSION LUGS IN THIS
CASE)
RACK BONDING
CONDUCTOR (6AWG)
TEBC
(TELECOMMUNICATIONS
EQUIPMENT BONDING
CONDUCTOR – 6AWG)
IRREVERSIBLE
COMPRESSION
CONNECTION
CHATSWORTH PRODUCTS, INC.: PN 10622-020
WALL MOUNTED BUS BAR KIT INCLUDES 4"W x 12"L x 1/4"T
COPPER GROUND BAR, INSULATORS, AND STAND-OFF
BRACKETS. MOUNTING HEIGHT @ 18" AFF. UON
12"
4"
ALL EQUIPMENT SHALL BE GROUNDED PER MANUFACTURER’S INSTRUCTIONS.
ANSI/EIA/TIA COMPLIANT BUSBAR
CHATSWORTH P/N: 40158-012
ALL GROUNDING SHALL BE DONE IN ACCORDANCE WITH J-STD-607 “COMMERCIAL BUILDING GROUNDING (EARTHING) AND BONDING REQUIREMENTS FOR TELECOMMUNICATIONS”, NFPA 70, AND IN COMPLIANCE
WITH LOCAL CODES.
OPTICAL FIBER CABLE
RADIUS ELBOW
3 PROVIDE GROUNDING JUMPER BETWEEN EACH SECTION OF TRAY (MOUNTED ON
OVER CABLE TRAY FROM ANY OBSTRUCTION
MECHANICAL DUCT SYSTEMS STRIVE TO MAINTAIN MINIMUM 12" OF CLEARANCE
PER ANSI/TIA/EIA STANDARDS CABLE TRAY SHALL NOT IMPEDE ANY
INSTALLATION GUIDE AS WELL AS THE MINIMUM CABLE BEND RADIUS ALLOWED
CUTTING AND BENDING RECOMMENDATIONS FROM THE MANUFACTURER'S
THAT INTERFERE WITH THE DECLARED PATH CONTRACTOR SHALL FOLLOW
2 CABLE TRAY SHALL BE ROUTED AROUND, OVER OR UNDER ANY OBSTACLES
APPROVED MANUFACTURER HAS TO OFFER
1 CABLE TRAY MAY BE SUPPORTED WITH OTHER SUPPORT MECHANISMS THAT THE
GENERAL NOTES:
SIDE) AND FROM TRAY TO EACH HORIZONTAL DISTRIBUTION CONDUIT
COMPLETE WORKING INSTALLATION INCLUDING MISCELLANEOUS APPURTENANCES
4 NOT ALL PARTS ARE SHOWN THE CONTRACTOR IS RESPONSIBLE FOR A
NOTE:
SIDE VIEW
EZ-PATH FIRESTOP DEVICE
EZ-PATH FIRESTOP DEVICE
FRONT VIEW
CABLE LADDER RETAINING POST
RUNWAY DROPS
WASHER
CLAMP
LOCKING NUT
WASHER
NOTE:
FROM TYPICAL LOCATION
#6 AWG
SUPPORT RUNWAY AT 1 8 METER
INTERVALS CABLE LADDER FOR
USE IN COMMUNICATIONS ROOMS
ONLY
AFFIX CABLE TRAY TO
WALL THAT SHALL BE
NO MORE THAN 2" FROM
BOTTOM OF SLEEVE
STEEL WALL PLATE
AND GASKET (TYPICAL)
STI NO: EZDP33FW F
RATINGS-1 AND 2 HOUR T
RATINGS-3/4 AND 1 HOUR
GYPSUM BOARD OPENING SHALL
BE 3-1/4"Wx3-1/4"H MAXIMUM
GYPSUM BOARD OPENING SHALL
BE 3-1/4"Wx3-1/4"H MAXIMUM
TELECOMMUNICATIONS
COPPER AND OPTICAL
FIBER CABLES
TELECOMMUNICATIONS
COPPER AND OPTICAL
FIBER CABLES
STEEL WALL PLATE
AND GASKET
INTUMESCENT
MATERIAL
150mm - 300mm WIDE
HOT DIPPED
GALVANIZED STEEL
CABLE RUNWAY
WITH 225mm RUNG
SPACING
GALVANIZED
THREADED ROD
WITH PVC SLEEVES
PROVIDE RETAINING POST
EVERY 150mm ON BOTH
SIDES OF THE CABLE LADDER
LADDER TYPE CABLE TRAY
TEE INTERSECTION
LADDER TYPE CABLE TRAY
90° RETURN
UNIVERSAL SUPPORT BRACKET SUPPORT
TRAY AT 5 FOOT INTERVALS, STARTING
AT 1 FOOT OFF THE FIRST AND LAST
SEGMENTS OF CABLE TRAY
CLAMP CORNERS WIIH
SPLICE WASHER ASSEMBLY
12" CABLE TRAY, SEE
PLANS FOR LOCATION
PROVIDE WATERFALLS AT
CABLE EXIT LOCATIONS
TELECOMMUNICATIONS ROOM
CABLE TRAY SYSTEM
TRAPEZE HANGING CLIPS WITH THREADED ROD AT 5
FOOT INTERVALS, STARTING AT 1 FOOT OFF THE
FIRST AND LAST SEGMENTS OF CABLE TRAY
TYPICAL RADIUS CORNER INTERIOR
RADIUS SHALL BE 5" MINIMUM, OUTSIDE
SIZE WILL VARY WITH TRAY WIDTH
MAINTAIN 12" MIN CLEARANCE ABOVE
TRAY TO OBSTRUCTIONS OR CEILING
PROVIDE TWO UL LISTED FAST
SPLICE FOR CABLE TRAY COUPLING
OR BOND SECTIONS TOGETHER
GROUND BUSHING WITH
#6 3AWG TO CABLE TRAY
PROPOSED CABLE TRAY:
CABLOFIL CF150/300
6" DEEP X 12" WIDE MINIMUM (4"X16" OR 4"X18" ACCEPTABLE)
WHITE POWERCOAT
TRAY INSERT
MAX. CAPACITY:
MAXIMUM PLANNED UTP CABLE FILL:
288 CABLES AT .35 OD CMP
MAXIMUM LOAD:
15.68 LBS PER FOOT
MAXIMUM ANTICIPATED LOAD:
~13.41 LBS PER FOOT
LOAD IN LBS FT PER SPAN:
5: 175.9 6: 155* 7: 113.9 8: 98.3
* RECOMMENDED MAX UNSUPPORTED SPAN
357 CATEGORY 6A UTP (0.35 OD)
486 CATEGORY 6A UTP (0.30 OD)
SCREWS (M4)
NETWORK EQUIPMENT MUST BE GROUNDED. NEVER DEFEAT THE GROUND CONDUCTOR
OR OPERATE THE EQUIPMENT IN THE ABSENCE OF A SUITABLY INSTALLED GROUND
CONDUCTOR. THESE DEVICES WILL BE BONDED TO THE RBB IN THE SAME RACK. EACH
DEVICE WILL HAVE A DEDICATED UNIT BONDING CONDUCTOR (UBC). THE UBC WILL NOT
BE SHARED.
DIRECTLY BONDED TO
RBB
TWO-HOLE
COMPRESSION LUG
SYSTEM GROUND
LOCATION
GROUNDING PAD
UBC
UNIVERSAL EARTHQUAKE BRACING KIT
RACK TO WALL
TO WALL
FRAMING TO CEILING
TO CEILING
RACK TO FRAMING
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR 2012034754 EXP. 12/31/2023
ENGR REG. NO. PE 2014031351 EXP. 12/31/2023
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY-SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
HEALTHCARE PLANNER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
No. REVISION DESCRIPTION DATE
FINAL BID DOCUMENTS
589-21-702TECHNOLOGY DETAILS
T-501
EHRM TRAINING &
SUPPORT
SPUR #: 1794.13
06/28/2022 SR NR 72
VA MEDICAL CENTER
4801 LINWOOD BLVD
KANSAS CITY, MO 64128
N/A
6/
/2
4:
:3
PM
1 FIBER CASSETTE DETAIL
2 FIBER DISTROBUTION ENCLOSURE DETAIL4 PATHWAY - RACK - BONDING CONDUCTOR CONNECTION REQUIREMENTS
5 TELECOMMUNICATIONS PRIMARY BONDING BUSBAR (PBB)
6 TELECOMMUNICATIONS SECONDARY BONDING BUSBAR (SBB) DETAIL
8 BASKET TRAY 2 DETAIL
9 EARTHING EXAMPLE (CISCO 6509) Ref. CISCO PRODUCT INSTALLATION GUIDE
7 BASKET TRAY 1 DETAIL
3 UNIVERSAL SEISMIC BRACING DETAIL