Attachment 4 - Hazardous - Drawings.pdf

PDF 600 KB Posted

Attached to
Y1DA--EHRM Training and Admin Space Support Construction - Kansas City VAMC Federal contract opportunity
Solicitation number
36C77623B0020
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document contains drawings and specifications for hazardous material abatement work at the Kansas City VA Medical Center. The drawings identify locations of asbestos, lead-based paint and other hazardous materials throughout the basement, first, second floors and roof of Building 3 that require abatement. Key abatement work includes removal of asbestos floor tiles, mastics and caulks; asbestos roofing materials; lead-containing ceramic tiles; and asbestos tar. The abatement will be conducted using negative pressure enclosures, wet methods and HEPA vacuuming. The related federal contract opportunity is for the EHRM Infrastructure Upgrades project at the Kansas City VAMC, solicited by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--EHRM Training and Admin Space Support Construction - Kansas City VAMC, newest first.
File Type Posted
Addendum 01 Drawings and Specifications.pdf PDF
36C77623B0020 0003.docx DOCX document
Sign in Sheet - 36C77623B0020 EHRM Training and Admin Space - KC.pdf PDF
36C77623B0020 0002.docx DOCX document
71-02-C17 Pipe Trench.pdf PDF
Technical Questions - Responses.pdf PDF
Data Center Location.pdf PDF
Wage Rates 4-28-23.pdf PDF
Attachment 17 - Site Map.pdf PDF
Attachment 7 - Architectural - Drawings.pdf PDF
Attachment 3 - General - Drawings.pdf PDF
Attachment 16 - Site Visit Instructions.pdf PDF
Attachment 15 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 10 - Mechanical - Drawings.pdf PDF
Attachment 9 - Plumbing - Drawings.pdf PDF
Attachment 5 - Civil - Drawings.pdf PDF
Attachment 14 - Wage Rates - 3-3-23.pdf PDF
Attachment 13 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 12 - Technology - Drawings.pdf PDF
Attachment 8 - Fire Protection - Drawings.pdf PDF
Attachment 6 - Structural - Drawings.pdf PDF
Attachment 2 - Specifications - Volume II - EHRM Training Support KC.pdf PDF
Attachment 1 - Specifications - Volume I - EHRM Training Support KC.pdf PDF
Attachment 11 - Electrical - Drawings.pdf PDF
36C77623B0020 0001.docx DOCX document
Attachment 10 - Site Map.pdf PDF
Attachment 8 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 7 - Wage Rates - 3-3-23.pdf PDF
Attachment 4 - Drawings - EHRM Training and Support KC - 31-53.pdf PDF
Attachment 2 - Specifications - Volume II - EHRM Training Support KC - Final.pdf PDF
Attachment 5 - Drawings - EHRM Training and Support KC - 54 - 72.pdf PDF
36C77623B0020_1.docx DOCX document
Attachment 3 - Drawings - EHRM Training and Support KC - 1-30.pdf PDF
Attachment 9 - Site Visit Instructions.pdf PDF
Attachment 6 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 1 - Specifications - Volume I - EHRM Training Support KC - Final.pdf PDF
Show all 36

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t

A

B

C

D

E

F

Veterans

Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY-SPRINKLERED

INDUSTRIAL HYGIENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

ARCH REG. NO. AR 2009021688 EXP. 12/31/2023

ENGR REG. NO. PE 20190403952 EXP. 12/31/2023

ENGR REG. NO. PE 2018038407 EXP. 12/31/2023

A

M

BASEMENT - ENVIRONMENTAL HAZARDS

CD

04 72

JR

EHRM TRAINING & ADMIN

SUPPORT

06/28/2022

589-21-702

VA MEDICAL CENTER

4801 LINWOOD BLVD

KANSAS CITY, MO 64128

HA300

SPUR #: 1794.13

No. REVISION DESCRIPTION DATE

KEY NOTES

KEYNOTED AREAS OF ASBESTOS CONTAMINATED

CRAWLSPACE SOIL ARE TO BE FULLY ENCLOSED.

IN THE AREAS OF NEW ENCLOSURES AND UNDER

NEGATIVE PRESSURE, REMOVE VISIBLE DEBRIS

WHERE PRESENT. INSTALL A 60 MILLIMETER

THICK EPDM MEMBRANE OVER EXPOSED SOIL

SURFACE, WITH MEMBRANE SHEETS

CHEMICALLY WELDED AT SEAMS (WITH 12"

OVERLAP AT ALL SEAMS), AND PHYSICALLY

SEALED ALONG PERIMETER EDGES (I.E. FURRING

STRIPS AND TAP-CONS WITH MEMBRANE FOLDED

OVER) TO CONCRETE WALLS AND/OR COLUMNS,

AS NEEDED TO ENSURE AN AIR-TIGHT LAYER IS

ACHIEVED AND MAINTAINED BETWEEN SOILS AND

CRAWL SPACE. INSTALL AIR TIGHT EDPM COVER

SYSTEMS WITH EDGE SEALS. PERFORM ALL

WORK WITHIN NEGATIVE PRESSURE ENCLOSURE.

RIGOROUS PRE-CLEANING BY HEPA VACUUM AND

MANUAL WIPING OF ALL SURFACES WILL BE

NECESSARY TO ACHIEVE CLEARANCE, 2,250 SF

OF EDPM COVER SYSTEMS, 4 NEGATIVE

PRESSURE ENCLOSURES AND 1 MOBILIZATION.

REMOVE ASBESTOS BLACK TAR ON CONCRETE

WALL USING MANUAL MEANS AND CHEMICAL

METHODS WITHIN A NEGATIVE PRESSURE

ENCLOSURE, 6 SF (2 SF AT 3 LOCATIONS).

COORDINATE PENETRATION LOCATIONS AND

EXTENTS WITH THE GENERAL CONTRACTOR.

YELLOW ASBESTOS PENETRATION CAULK,

PROTECT AS NECESSARY.

ABANDONED ASBESTOS BRAIDED WIRE STUBS

(PACM), PROTECT AS NECESSARY.

ASBESTOS FIRE DOOR AND FRAME ASSEMBLY

(PACM), PROTECT AS NECESSARY.

ASBESTOS CONTAMINATED SOIL, PROTECT AS

NECESSARY.

ASBESTOS BLACK TAR ON WALL, PROTECT AS

NECESSARY.

REMOVE ASBESTOS BLACK TAR ON CONCRETE

WALL USING MANUAL MEANS AND CHEMICAL

METHODS WITHIN A NEGATIVE PRESSURE

ENCLOSURE, 2 SF AT 1 LOCATION. COORDINATE

PENETRATION LOCATION AND EXTENTS WITH THE

GENERAL CONTRACTOR.

ORANGE LBP PRESENT ON I-BEAM SUPPORT,

PROTECT AS NECESSARY.

LBP PRESENT ON STAIR SYSTEM COMPONENTS,

PROTECT AS NECESSARY.

A1

A2

A3

A4

A5

A6

A7

A8

L1

L2

VISUAL KEY

NEGATIVE PRESSURE ENCLOSURE

2000 CFM AIR MACHINES WITH 3 STAGE

FILTRATION

3-STAGE WET DECONTAMINATION

ASBESTOS BLACK TAR ON EXTERIOR WALL

GENERAL NOTES

ABATEMENT WORK WILL REQUIRE SEVERAL MOBILIZATIONS TO FACILITATE PROJECT SCHEDULE.

CONTRACTOR IS TO BE LICENSED TO ENGAGE IN ASBESTOS AND LEAD RELATED PROJECT WORK AND USE LICENSED/TRAINED PERSONNEL.

WITHIN AN NEGATIVE PRESSURE ENCLOSURE (NPE), HVAC AIR FLOW SHALL BE SHUTDOWN AND DUCT OPENINGS COVERED WITH CRITICAL BARRIERS THROUGHOUT ABATEMENT. SCHEDULE SHUTDOWNS WITH

THE VACOR TO ACCOMMODATE FACILITY AND CONSTRUCTION REQUIREMENTS.

ALL AUTHORIZED PERSONNEL WITHIN AN NPE SHALL DON, AT MINIMUM, HALF FACE AIR PURIFYING RESPIRATORS WITH P100 FILTERS, DISPOSABLE DUST SUITS (WITH BOOT AND HEAD COVERS) AND GLOVES.

RESPIRATORY PROTECTION MAY REQUIRE USE OF POWERED AIR PURIFYING RESPIRATORS.

REGULATED AREA NEGATIVE PRESSURE ENCLOSURES SHALL BE PREPARED IN ACCORDANCE WITH THE FOLLOWING:A) ALL FLOORS, CEILINGS AND WALLS SHALL BE ISOLATED USING APPROPRIATE LAYERS OF

6-MIL & 4-MIL POLY SHEETING; B) OSHA ASBESTOS SIGNAGE AT ENTRANCE TO REGULATED AREAS; (SEE SPEC 02 82 11, SECTION 2.1 ITEM 13). C)SINGLE-POINT OF ENTRY WITH 3-STAGE WET DECONTAMINATION

STATION TO ALLOW WORKERS TO REMOVE PPE, WASH AND VACUUM THEMSELVES OFF PRIOR TO EXITING THE REGULATED WORK AREA; D) MAINTAINED UNDER NEGATIVE PRESSURE (-0.02 IN WG OR BETTER)

USING HEPA FILTERED AIR MACHINES WITH EXHAUST ROUTED TO OUTDOORS; E) MINIMUM OF 4 AIR CHANGES PER HOUR; F) CLEAN/CHANGE ROOM SUFFICIENT FOR WORKERS TO CHANGE INTO STREET

CLOTHES (OPAQUE POLY REQUIRED AS NEEDED FOR PRIVACY); G) RENEWABLE ADHESIVE MATS IMMEDIATELY OUTSIDE OF REGULATED WORK AREA TO ENSURE FOOT TRAFFIC DOES NOT SPREAD DUST/DEBRIS

TO OTHER AREAS OF FACILITY.

PERFORM ABATEMENT USING THE FOLLOWING CONTROLS: A) HEPA FILTERED VACUUM FOR CONTINUOUS AND FINAL CLEANUP; B) ONLY MANUAL REMOVAL MEANS/TOOLS ARE ALLOWED TO DISTURB ACM

(MECHANICAL TOOLS PROHIBITED FOR ACM REMOVAL).

CLEANING OF REGULATED WORK AREAS IS TO INCLUDE HEPA VACUUMING & WET WIPING METHODS. REGULATED AREAS ARE TO PASS A SUCCESSFUL VISUAL INSPECTION BY THE VA PROFESSION INDUSTRIAL

HYGIENIST (VPIH) PRIOR TO COLLECTION OF CLEARANCE SAMPLES.

VPIH WILL PERFORM PERIMETER AIR MONITORING, VISUAL INSPECTIONS AND FINAL AIR CLEARANCE SAMPLING.

CONTRACTOR TO PERFORM OSHA EMPLOYEE EXPOSURE MONITORING.

WASTE PRODUCED DURING REMEDIATION SHALL BE COLLECTED, CONTAINERIZED, LABELED, CHARACTERIZED AND DISPOSED IN ACCORDANCE WITH ASBESTOS AND LEAD SPECIFICATIONS 02.82.11 AND

02833313.

WASTE CONTAINERS, TOOLS, EQUIPMENT, ETC. SHALL BE WET WIPED PRIOR TO LEAVING REGULATED WORK AREA.

WHERE THE COMBINED AREA OF THE NPE INCLUDING , DECONTAMINATION, LOADOUT, AND WORK CHAMBERS DOES NOT FIT WITHIN A ROOM, THE DECON/LOADOUT CONFIGURATION MAY EXTEND INTO 1/2

WIDTH OF THE HALLWAY AS REQUIRED TO ALLOW PASSAGE IN CORRIDOR

NIGHT WORK IS TO BE PERFORMED DURING OFF HOURS FROM 5:00 PM - 7:00 AM MONDAY THROUGH FRIDAY AND WEEKEND WORK FRIDAY 6 PM THROUGH SUNDAY. WORK IS PROHIBITED ON FEDERAL HOLIDAYS.

N

NOT TO SCALE

BLDG 3 - BASEMENT PLAN

A7

A1

A7

A2

A3

A1

A5

A5

A5

A5

A5

A5

A7

A1

A1

A2

A2

A1

A7

A4

A6

A6 A6

A6

A8

FINAL BID DOCUMENTS

AutoCAD SHX Text B07

AutoCAD SHX Text B07A

AutoCAD SHX Text

AutoCAD SHX Text

CS5

AutoCAD SHX Text

CS4

AutoCAD SHX Text

CS2

AutoCAD SHX Text

CS3

AutoCAD SHX Text

CS1

r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t

A

B

C

D

E

F

Veterans

Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY-SPRINKLERED

INDUSTRIAL HYGIENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

ARCH REG. NO. AR 2009021688 EXP. 12/31/2023

ENGR REG. NO. PE 20190403952 EXP. 12/31/2023

ENGR REG. NO. PE 2018038407 EXP. 12/31/2023

A

M

LEVEL 1 - ENVIRONMENTAL HAZARDS

CD

05 72

JR

EHRM TRAINING & ADMIN

SUPPORT

06/28/2022

589-21-702

VA MEDICAL CENTER

4801 LINWOOD BLVD

KANSAS CITY, MO 64128

HA301

SPUR #: 1794.13

No. REVISION DESCRIPTION DATE

KEY NOTES

REMOVE CARPET AND UNDERLYING ASBESTOS

BLACK MASTIC REMNANTS USING MANUAL

MEANS AND CHEMICAL METHODS WITHIN A

NEGATIVE PRESSURE ENCLOSURE, 300 SF AND 2

NEGATIVE PRESSURE ENCLOSURES.

REMOVE WINDOW ASSEMBLIES WITH HIDDEN

ASBESTOS CAULK USING MANUAL MEANS WITHIN

A NEGATIVE PRESSURE ENCLOSURE, 6 WINDOW

ASSEMBLY GROUPS AND 2 NEGATIVE PRESSURE

ENCLOSURE, 5 OF THE WINDOW ASSEMBLIES

ARE IN STAIRWELL 1 EXTENDING FROM GROUND

LEVEL TO LEVEL 2.

REMOVE ASBESTOS BLACK TAR ON EXTERIOR

WALL USING MANUAL MEANS AND CHEMICAL

METHODS WITHIN A NEGATIVE PRESSURE

ENCLOSURE, 3 SF ASBESTOS BLACK TAR AND 1

NEGATIVE PRESSURE ENCLOSURE. COORDINATE

PENETRATION AND EXTENT WITH THE GENERAL

CONTRACTOR. REMOVE NON-ASBESTOS

DRYWALL TO ACCESS TAR AS NECESSARY

ASBESTOS FIRE DOOR AND FRAME ASSEMBLY

(PACM), PROTECT AS NECESSARY.

ASBESTOS BLACK TAR IN EXTERIOR WALL VOIDS,

PROTECT AS NECESSARY.

WINDOW ASSEMBLIES WITH HIDDEN ASBESTOS

CAULK, PROTECT AS NECESSARY.

ASBESTOS BLACK TAR ON WALL PRESENT, USE

EXISTING PENETRATION FOR NEW DUCTWORK,

PROTECT AS NECESSARY.

LBP PRESENT ON STAIR SYSTEM COMPONENTS,

PROTECT AS NECESSARY.

REMOVE WINDOW ASSEMBLIES WITH LBP

COMPONENTS USING MANUAL MEANS WITHIN A

NEGATIVE PRESSURE ENCLOSURE, 5 WINDOW

ASSEMBLIES AND 1 ENCLOSURE.

A1

A2

A3

A4

A5

A6

A7

L1

L2

VISUAL KEY

NEGATIVE PRESSURE ENCLOSURE

2000 CFM AIR MACHINES WITH 3 STAGE

FILTRATION

3-STAGE WET DECONTAMINATION

ASBESTOS BLACK TAR ON EXTERIOR WALL

FIRE RATED WALL - 1 HOUR (NEW/EXISTING)

3-101A

3-101

3-102

3-100

3-104

3-105

3-106

3-107

3-109

3-110

3-112 3-111

3-103

N

NOT TO SCALE

BLDG 3 - LEVEL 1 PLAN

A6A6A2 A6A6

A5

A6

A3

A4

A6 A6

A5

A4

A4

L1

A6 A6 A6

A4

A4

A1

A1

A5

A6

A5

A5

A5 A5

A2

L2

FINAL BID DOCUMENTS

AutoCAD SHX Text A110

AutoCAD SHX Text A109

AutoCAD SHX Text A108

AutoCAD SHX Text A106

AutoCAD SHX Text A105

AutoCAD SHX Text A104

AutoCAD SHX Text A102

AutoCAD SHX Text A100

AutoCAD SHX Text

AutoCAD SHX Text A101

AutoCAD SHX Text A103 r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t

A

B

C

D

E

F

Veterans

Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY-SPRINKLERED

INDUSTRIAL HYGIENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

ARCH REG. NO. AR 2009021688 EXP. 12/31/2023

ENGR REG. NO. PE 20190403952 EXP. 12/31/2023

ENGR REG. NO. PE 2018038407 EXP. 12/31/2023

A

M

LEVEL 2 - ENVIRONMENTAL HAZARDS

CD

06 72

JR

EHRM TRAINING & ADMIN

SUPPORT

06/28/2022

589-21-702

VA MEDICAL CENTER

4801 LINWOOD BLVD

KANSAS CITY, MO 64128

HA302

SPUR #: 1794.13

No. REVISION DESCRIPTION DATE

KEY NOTES

REMOVE CARPET AND UNDERLYING ASBESTOS

BLACK MASTIC USING MANUAL MEANS AND

CHEMICAL METHODS WITHIN A NEGATIVE

PRESSURE ENCLOSURE, 875 SF AND 3 NEGATIVE

PRESSURE ENCLOSURES.

REMOVE WINDOW ASSEMBLIES WITH HIDDEN

ASBESTOS CAULK USING MANUAL MEANS WITHIN

A NEGATIVE PRESSURE ENCLOSURE, 2 WINDOW

ASSEMBLY GROUPS AND 2 NEGATIVE PRESSURE

ENCLOSURES.

REMOVE HVAC LOUVER ASSEMBLY WITH HIDDEN

ASBESTOS CAULK USING MANUAL MEANS WITHIN

A NEGATIVE PRESSURE ENCLOSURE, 2 LOUVERS

AND 2 NEGATIVE PRESSURE ENCLOSURES.

ASBESTOS FIRE DOOR AND FRAME ASSEMBLY

(PACM), PROTECT AS NECESSARY.

ASBESTOS BLACK TAR IN EXTERIOR WALL VOIDS,

PROTECT AS NECESSARY.

WINDOW ASSEMBLIES WITH HIDDEN ASBESTOS

CAULK, PROTECT AS NECESSARY.

ASBESTOS BLACK TAR ON WALL PRESENT, USE

EXISTING PENETRATION FOR NEW DUCTWORK,

PROTECT AS NECESSARY.

LBP PRESENT ON STAIR SYSTEM COMPONENTS,

PROTECT AS NECESSARY.

REMOVE WINDOW ASSEMBLIES WITH LBP

COMPONENTS USING MANUAL MEANS WITHIN A

NEGATIVE PRESSURE ENCLOSURE, (5 WINDOW

ASSEMBLIES TOTAL EXTENDING FROM LEVEL 1

TO LEVEL 2.

REMOVE 6" LEAD CONTAINING CERAMIC COVE

BASE AND ASSOCIATED NON LEAD CONTAINING

TILES WHERE NECESSARY USING MANUAL

MEANS WITHIN A NEGATIVE PRESSURE

ENCLOSURE, 20LF AND 1 ENCLOSURE

A1

A2

A3

A4

A5

A6

A7

L1

L2

L3

VISUAL KEY

NEGATIVE PRESSURE ENCLOSURE

2000 CFM AIR MACHINES WITH 3 STAGE

FILTRATION

3-STAGE WET DECONTAMINATION

ASBESTOS BLACK TAR ON EXTERIOR WALL

FIRE RATED WALL - 1 HOUR (NEW/EXISTING)

3-211

3-209

3-212

3-210

3-208

3-206 3-204

3-202

3-205 3-203

3-201A

3-200

3-207

3-211

3-209

3-212

3-210

3-208

3-206 3-204

3-202

3-205 3-203

3-201A

3-200

3-207

N

NOT TO SCALE

BLDG 3 - LEVEL 2 PLAN

A4

A4

A6A6A2A6 A6

A6

A6

A6 A6 A6

A6 A3 A2

A2

A1

A1

A5 A1

A1

A1 A1

A4

A4

L1

3-2013-201

A7

A3

A3

A4

L3

A2

L2

FINAL BID DOCUMENTS

AutoCAD SHX Text A212

AutoCAD SHX Text A210

AutoCAD SHX Text A211

AutoCAD SHX Text A209

AutoCAD SHX Text A208

AutoCAD SHX Text A206

AutoCAD SHX Text A207

AutoCAD SHX Text

AutoCAD SHX Text A205

AutoCAD SHX Text A203

AutoCAD SHX Text

AutoCAD SHX Text A200

AutoCAD SHX Text A202

AutoCAD SHX Text A204

A201 r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t

A

B

C

D

E

F

Veterans

Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY-SPRINKLERED

INDUSTRIAL HYGIENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

ARCH REG. NO. AR 2009021688 EXP. 12/31/2023

ENGR REG. NO. PE 20190403952 EXP. 12/31/2023

ENGR REG. NO. PE 2018038407 EXP. 12/31/2023

A

M

ROOF - ENVIRONMENTAL HAZARDS

CD

07 72

JR

EHRM TRAINING & ADMIN

SUPPORT

06/28/2022

589-21-702

VA MEDICAL CENTER

4801 LINWOOD BLVD

KANSAS CITY, MO 64128

HA303

SPUR #: 1794.13

No. REVISION DESCRIPTION DATE

N

NOT TO SCALE

BLDG 3 - ROOF PLAN

KEY NOTES

REMOVE ASBESTOS ROOF AND UNDERLYING

MASTICS OR TARS USING MANUAL MEANS AND

CHEMICAL METHODS IN A REGULATED AREA.

COORDINATE SPOT AREAS OF REMOVAL AND

EXACT SIZES OF ROOF PENETRATIONS WITH THE

GENERAL CONTRACTOR, 10 ROOF AREAS AND 140

SF TOTAL AND 1 MOBILIZATION. USE CLEAR

BRIDGING ENCAPSULANT ON EXPOSED

SURFACES.

REMOVE ASBESTOS ROOF AND UNDERLYING

MASTICS OR TARS USING MANUAL MEANS AND

CHEMICAL METHODS IN A REGULATED AREA.

COORDINATE SPOT AREAS OF REMOVAL AND

EXACT SIZES OF ROOF PENETRATIONS WITH THE

GENERAL CONTRACTOR, 13 ROOF AREAS FOR

PIPE AND DUCT SUPPORTS AND 50 SF TOTAL AND

2 MOBILIZATIONS. USE CLEAR BRIDGING

ENCAPSULANT ON EXPOSED SURFACES.

REMOVE ASBESTOS ROOF AND UNDERLYING

MASTICS OR TARS USING MANUAL MEANS AND

CHEMICAL METHODS IN A REGULATED AREA.

COORDINATE SPOT AREAS OF REMOVAL AND

EXACT SIZES OF ROOF PENETRATIONS WITH THE

GENERAL CONTRACTOR, 5 ROOF AREAS FOR

CRANE AND FALL RAILING SYSTEM, 7 SF TOTAL

AND 1 MOBILIZATION. USE CLEAR BRIDGING

ENCAPSULANT ON EXPOSED SURFACES.

ASBESTOS BUILT UP ROOF (PACM), PROTECT AS

NECESSARY.

WET HYGIENE STATION

A1

A1

A2

A1

A2 A2

A2

A2

A1

A3

A2

A2 A2

A1

A2

A2

A1

A3

A4

A3

A3

A1 A1 A1

A1

A1

D

A2

A3

A4

D

FINAL BID DOCUMENTS

HA300
Sheets and Views
Model
HA301
Sheets and Views
Model
HA302
Sheets and Views
Model
HA303
Sheets and Views
Model