Attachment 3 - General - Drawings.pdf

PDF 4 MB Posted

Attached to
Y1DA--EHRM Training and Admin Space Support Construction - Kansas City VAMC Federal contract opportunity
Solicitation number
36C77623B0020
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document package includes construction drawings and specifications for upgrades to an EHRM training and administrative support facility at the Kansas City VA Medical Center. The project involves renovations and systems work across approximately 6,856 square feet of existing space spread across two levels. Drawings depict demolition plans, new partitions, life safety plans, mechanical and plumbing systems, electrical plans, telecommunications, and other construction details. Specification sections address requirements for general contracting, hazardous materials abatement, civil work, structural elements, architectural finishes, fire protection, plumbing, HVAC, electrical, technology systems, and elevator modernization. The related federal contract opportunity is solicitation number 36C77623B0020 for the EHRM Infrastructure Upgrades project at Fort Meade. The soliciting agency is the Department of Veterans Affairs Technology Acquisition Center in Austin.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--EHRM Training and Admin Space Support Construction - Kansas City VAMC, newest first.
File Type Posted
Addendum 01 Drawings and Specifications.pdf PDF
36C77623B0020 0003.docx DOCX document
71-02-C17 Pipe Trench.pdf PDF
Technical Questions - Responses.pdf PDF
Data Center Location.pdf PDF
Wage Rates 4-28-23.pdf PDF
Sign in Sheet - 36C77623B0020 EHRM Training and Admin Space - KC.pdf PDF
36C77623B0020 0002.docx DOCX document
Attachment 16 - Site Visit Instructions.pdf PDF
Attachment 15 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 10 - Mechanical - Drawings.pdf PDF
Attachment 9 - Plumbing - Drawings.pdf PDF
Attachment 5 - Civil - Drawings.pdf PDF
Attachment 11 - Electrical - Drawings.pdf PDF
36C77623B0020 0001.docx DOCX document
Attachment 17 - Site Map.pdf PDF
Attachment 7 - Architectural - Drawings.pdf PDF
Attachment 14 - Wage Rates - 3-3-23.pdf PDF
Attachment 13 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 12 - Technology - Drawings.pdf PDF
Attachment 8 - Fire Protection - Drawings.pdf PDF
Attachment 6 - Structural - Drawings.pdf PDF
Attachment 4 - Hazardous - Drawings.pdf PDF
Attachment 2 - Specifications - Volume II - EHRM Training Support KC.pdf PDF
Attachment 1 - Specifications - Volume I - EHRM Training Support KC.pdf PDF
Attachment 4 - Drawings - EHRM Training and Support KC - 31-53.pdf PDF
Attachment 2 - Specifications - Volume II - EHRM Training Support KC - Final.pdf PDF
Attachment 9 - Site Visit Instructions.pdf PDF
Attachment 6 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 1 - Specifications - Volume I - EHRM Training Support KC - Final.pdf PDF
Attachment 10 - Site Map.pdf PDF
Attachment 8 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 7 - Wage Rates - 3-3-23.pdf PDF
Attachment 5 - Drawings - EHRM Training and Support KC - 54 - 72.pdf PDF
36C77623B0020_1.docx DOCX document
Attachment 3 - Drawings - EHRM Training and Support KC - 1-30.pdf PDF
Show all 36

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AREA

PLAN

LOCATION

PLAN

PROJECT LOCATION

BUILDING 3

N N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

U.S. DEPARTMENT OF VETERANS AFFAIRS

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. AR 2009021688 EXP. 12/31/2023

ENGR REG. NO. PE 20190403952 EXP. 12/31/2023

ENGR REG. NO. PE 2018038407 EXP. 12/31/2023

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY-SPRINKLERED

INDUSTRIAL HYGIENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/2

/2

:4 :5

A

M

COVER SHEET

NRL 01 72BKM

FINAL BID DOCUMENTS

EHRM TRAINING & ADMIN SUPPORT

VA PROJECT NUMBER: 589-21-702

EHRM TRAINING & ADMIN

SUPPORT

06/28/2022

589-21-702

VA MEDICAL CENTER

4801 LINWOOD BLVD

KANSAS CITY, MO 64128

KANSAS CITY VA MEDICAL CENTER

4801 LINWOOD BLVD

KANSAS CITY, MO 64128

FINAL BID DOCUMENTS

GI000

SPUR #: 1794.13

SHEET INDEX

SEQUENCE NUMBER SHEET NAME

[07] PLUMBING

36 P-000 PLUMBING LEGEND, ABBREVIATIONS AND GENERAL NOTES

37 PD101 PLUMBING WASTE AND VENT DEMOLITION PLANS

38 PD102 PLUMBING DOMESTIC WATER DEMOLITION PLANS

39 P-101 PLUMBING WASTE AND VENT PLANS

40 P-102 PLUMBING DOMESTIC WATER PLANS

41 P-301 PLUMBING WASTE AND VENT RISER DIAGRAM

42 P-302 PLUMBING DOMESTIC WATER RISER DIAGRAM

43 P-501 PLUMBING DETAILS

44 P-601 PLUMBING SCHEDULES

[08] MECHANICAL

45 M-000 MECHANICAL LEGEND, ABBREVIATIONS AND GENERAL NOTES

46 MD101 MECHANICAL DUCT DEMOLITION PLANS

47 MD102 MECHANICAL PIPING DEMOLITION PLANS

48 M-101 MECHANICAL DUCT PLANS

49 M-102 MECHANICAL PIPING PLANS

50 M-201 HVAC SECTION VIEWS

51 M-501 MECHANICAL DETAILS

52 M-601 MECHANICAL SCHEDULES

53 M-701 MECHANICAL CONTROLS - 1

54 M-702 MECHANICAL CONTROLS - 2

[09] ELECTRICAL

55 E-000 ELECTRICAL LEGEND AND NOTES

56 ES101 ELECTRICAL AND SECURITY SITE PLAN

57 ED101 ELECTRICAL LIGHTING DEMOLITION PLANS

58 ED201 ELECTRICAL POWER DEMOLITION PLANS

59 EL101 ELECTRICAL LIGHTING PLANS

60 EP101 ELECTRICAL POWER PLANS

61 EP111 ELECTRICAL EQUIPMENT POWER PLANS

62 E-500 ELECTRICAL AND SECURITY DETAILS

63 E-600 ELECTRICAL ONE-LINE DIAGRAM AND RACK ELEVATIONS

64 E-601 ELECTRICAL PANELBOARD SCHEDULES

65 TY101 SECURITY PLAN

[10] TELECOM

66 T-000 TECHNOLOGY SYMBOLS & ABBREVIATIONS

67 T-100 TECHNOLOGY FLOOR PLAN

68 T-200 TECHNOLOGY SITE PLAN

69 T-300 TECHNOLOGY ENLARGED PLAN

70 T-400 TECHNOLOGY RACK ELEVATION & RISER DIAGRAM PLAN

71 T-500 TECHNOLOGY DETAILS

72 T-501 TECHNOLOGY DETAILS

TOTAL SHEETS: 72

SHEET INDEX

SEQUENCE NUMBER SHEET NAME

[01] GENERAL

01 GI000 COVER SHEET

02 GI001 GENERAL INFORMATION

03 GI011 LIFE SAFETY PLANS

[02] HAZARDOUS

04 HA300 BASEMENT - ENVIRONMENTAL HAZARDS

05 HA301 LEVEL 1 - ENVIRONMENTAL HAZARDS

06 HA302 LEVEL 2 - ENVIRONMENTAL HAZARDS

07 HA303 ROOF - ENVIRONMENT HAZARDS

[03] CIVIL

08 GS001 GENERAL LAYOUT PLAN

09 GS002 DIMENSION AND UTILITY PLAN

10 GS003 EROSION CONTROL PLAN

11 GS004 EROSION CONTROL DETAILS

12 GS005 DETAILS

13 GS006 DETAILS

[04] STRUCTURAL

14 S-001 STRUCTURAL GENERAL NOTES

15 S-050 TYPICAL DETAILS - STEEL

16 S-100 FOUNDATION, 1ST AND 2ND FLOOR PLAN

17 S-101 ROOF FRAMING PLAN

[05] ARCHITECTURAL

18 AS001 ARCHITECTURAL SITE PLAN

19 AD011 DEMOLITION PLANS

20 AD131 REFLECTED CEILING DEMOLITION PLANS

21 AE021 PARTITION TYPES

22 AE101 REFERENCE PLANS

23 AE111 DIMENSION PLANS

24 AE121 ROOF PLAN

25 AE131 REFLECTED CEILING PLANS

26 AE201 BUILDING ELEVATIONS

27 AE401 ENLARGED PLANS AND INTERIOR ELEVATIONS

28 AE601 DOOR & WINDOW SCHEDULES & DETAILS

29 AF701 FINISH FLOOR PLANS

30 AF711 FINISH SCHEDULE

[06] FIRE PROTECTION

31 FA001 FIRE ALARM GENERAL NOTES, LEGEND, AND DIAGRAMS

32 FA101 FIRE ALARM AUDIBILITY PLANS

33 FA102 FIRE ALARM FLOOR PLANS

34 FX001 FIRE SUPPRESSION GENERAL NOTES AND RISER DIAGRAM

35 FX101 FIRE SUPPRESSION HAZARD CLASSIFICATION PLANS

No. REVISION DESCRIPTION DATE brenden.bond Image

ABBREVIATIONS CODES STANDARDS AND EXECUTIVE ORDERS

4' -0

M

A X

4' -0

M

A X

2' -1

0" M

A X

2' -3

M

IN

1'-6" MIN

1. GENERAL CONTRACTOR TO PROVIDE FIRE RATED WOOD

SUPPORT BLOCKING FOR ALL WALL MOUNTED

ACCESSORIES, FIXTURES, AND EQUIPMENT.

2. PROVIDE ADA SUPPORT BRACKETS PLACED AT ALL OPEN

COUNTERTOPS @ 36"-48" MAX ON CENTER.

3. SPECIFIED MAXIMUMS ARE MEASURED FROM AFTER

FINISHED FLOOR TO THE OPERABLE PART OF THE FIXTURE.

4. FIXTURES SHOWN ARE REPRESENTATIONAL ONLY. NOT ALL

FIXTURES MAY BE USED. REFER TO SPECIFICATIONS FOR

FIXTURE TYPES USED IN THIS PROJECT.

5. FIXTURES MAY OVERLAP WAINSCOT. WHERE APPLICABLE,

BACKING TO BE PROVIDED AS SHIM FOR FLUSH

APPLICATION. SHIM TO MATCH SCHEDULED WALL FINISH.

6" MAX

9" M

IN

SHOWER

VA TOILET ROOM

TURNING RADIUS

DRINKING

FOUNTAIN

PAPER TOWEL

DISPENSER

SANITARY

NAPKIN

DISPENSER

4' -0

"M A

X

WASTE

RECEPTACLE

LAVATORY

WITH MIRROR

ON CENTER

WALL

4' -0

M

A X

SOAP

DISPENSER

2' -1

0" M

A X

T O

B .O

. R E

F

LE

C T

IV

E

S U

R F

A C

E

3' -4

"M A

X

17 MIN

2' -3

M

IN

3' -0

M

A X

1'-6" MIN

WALL

2' -9

" 4' -0

M

IN

2'-0" MIN

8" MIN

WALL

LAVATORY

WITH APRON

1' -5

M

A X

1'-6" MIN

URINAL

WALL

1'-5" - 1'-7" (AMBULATORY)

1'-4" - 1'-6" (WHEELCHAIR)

CLEAR FLOOR

5'-6"

CLEAR FLOOR

6'-0"

3'-0" MIN

2' -9

3' -0

1'-0" MIN

3'-6" MIN 1'-0"MAX

4'-6" MIN

1' -5

'-7

1' -6

M

IN

A N

S I I

C C

A

7.

1)

1' -3

M

IN

A D

A /A

B A

2' -9

'-0

WALL

WALL

4' -0

M

A X

WALL HOOK

7' -0

CLOCK

WALL

FINISHED FLOOR

FIRE EXTINGUISHER

CABINET

WEIGHT > 40LBS

FIRE EXTINGUISHER

CABINET

WEIGHT < 40LBS

3' -1

1/

6" M

A X

4' -0

M

A X

TOILET SEAT

COVER

DISPENSER

BABY

CHANGING

STATION

CLEAR FLOOR SPACE

@ WATER CLOSET

5'-6"

2'-6"

4' -0

2'-6"

4' -0

HANDRAILS AND

BUMPERGUARDS

FIXTURE MOUNTING HEIGHTS AND CLEARANCES

18" MIN

M

IN

FRONT APPROACH,

PULL SIDE

36" MIN

M

IN

HINGE APPROACH,

PULL SIDE

HINGE APPROACH,

PULL SIDE

*12" MIN48

M

IN

FRONT APPROACH,

PUSH SIDE

M

IN

HINGE APPROACH,

PUSH SIDE

22" MIN 24" MIN

*4 8"

M

IN

LATCH APPROACH,

PULL SIDE

24" MIN*4

2"

M

IN

LATCH APPROACH,

PUSH SIDE

*IF BOTH CLOSER

AND LATCH ARE

PROVIDED

*54" MIN IF CLOSER

IS PROVIDED

*48" IF CLOSER IS

PROVIDED

FRONT APPROACH,

PUSH SIDE

M

IN

42" MIN

DOOR AND FIXTURE CLEARANCES

MATERIALS LEGEND

PURPOSE: THE PUBLIC BUILDINGS AMENDMENT ACT OF 1988, PUBLIC LAW (PUB. L.) 100-678 REQUIRES FEDERAL AGENCIES TO FOLLOW NATIONAL RECOGNIZED "MODEL" BUILDING CODES. THE FEDERAL PARTICIPATION IN THE DEVELOPMENT AND USE OF VOLUNTARY STANDARDS, OFFICE OF MANAGEMENT AND BUDGET (OMB) CIRCULAR A-119, REQUIRES ALL EXECUTIVE AGENCIES TO RELY ON VOLUNTARY STANDARDS, BOTH DOMESTIC AND INTERNATIONAL, WHENEVER FEASIBLE, AND TO PARTICIPATE IN

VOLUNTARY STANDARD BODIES.

GENERAL: VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS

SPECIFY OTHER CODES AND STANDARDS THAT VA FOLLOWS ON ITS PROJECTS:

• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL

INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).

• 2021 INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES BELOW)

• 2021 INTERNATIONAL EXISTING BUILDING CODE (IEBC) (IF APPLICABLE)

• 2021 NFPA 101 LIFE SAFETY CODE (SEE NOTES BELOW)

• 2021 NATIONAL FIRE CODES (NFPA)

• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.

• 2020 VA SEISMIC DESIGN REQUIREMENTS, H-18-8

• 2021 INTERNATIONAL MECHANICAL CODE

• 2020 NATIONAL ELECTRICAL CODE (NEC), NFPA 70

• 2021 INTERNATIONAL PLUMBING CODE (IPC)

• 2016 SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) A 17.1.

• 2015 ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS INCLUDING VA SUPPLEMENT, VA BARRIER FREE DESIGN STANDARD (PG-18-13)

• 2017 ANSI ICC A117.1 ACCESIBLE AND USABLE BUILDINGS AND FACILITIES

• 2019 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY, AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318-19)

• 2017 STEEL CONSTRUCTION MANUAL (15TH EDITION), AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)

• ENERGY POLICY ACT OF 2005 (EPACT)

• 2007 DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND

NEW LOW-RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435.

• 2006 FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING (MOU)

• 2018 EXECUTIVE ORDER 13834: EFFICIENT FEDERAL OPERATIONS

• 2021 THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 010000 OF THE VA MASTER CONSTRUCTION

SPECIFICATION.

• 2019 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1

• 2019 SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15

LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES. HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN OPPORTUNITY TO REVIEW DRAWINGS PROVIDED THAT VA DOES NOT PAY FOR REVIEW OR INSPECTION FEES.

NOTES:

1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT

NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN.

DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES

EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).

2. CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.

ASHRAE 90.1 - 2019 EDITION

BUILDING LOCATION: KANSAS CITY, MO

CLIMATE ZONE (TABLE ANNEX 1-1): ZONE 4A

INTERIOR DESIGN CONDITIONS:

THE INTERIOR DESIGN TEMPERATURES FOR HEATING AND COOLING AS DEPICTED IN THE PROJECT DESIGN CONDITIONS SCHEDULE IN THE MECHANICAL CONTROL DRAWINGS SHALL BE THE MAXIMUM

AND MINIMUM VALUES FOR THE ASSOCIATED TEMPERATURE CONTROL ZONES.

BUILDING ENVELOPE REQUIREMENTS (5.5 )

BUILDING ENVELOPE REQUIREMENTS FOR CLIMATE ZONE 4 (A,B,C)

ROOFS REQUIRED DESIGNED

INSULATION: R-30 c.i. EXISTING METAL BUILDINGS: R-19 + R-11 Ls or R-25 + R-8 Ls N/A

ATTIC AND OTHER: R-49 N/A

WALLS, ABOVE GRADE

MASS: R-9.5 c.i. EXISTING METAL BUILDING: R-0 + R-15.8 c.i. N/A STEEL-FRAMED: R-13 + R-7.5 c.i. EXISTING WOOD-FRAMED AND OTHER: R-13 + R-3.8 c.i. or R-20 N/A

WALL, BELOW GRADE

BELOW-GRADE WALL: R-7.5 c.i. EXISTING

FLOORS

MASS: R-14.6 c.i. EXISTING

STEEL-FRAMED: R-30 EXISTING

WOOD-FRAMED AND OTHER: R-30 N/A

SLAB-ON-GRADE FLOORS

UNHEATED SLABS: R-15 for 24 in. EXISTING HEATED SLABS: R-20 for 24 in. EXISTING

OPAQUE DOORS

SWINGING: U-0.370 EXISTING

NONSWINGING: U-0.310 N/A

FENESTRATION (TABLE 5.5-4):

VERTICAL FENESTRATION, U-FACTOR

FIXED: U-0.36 EXISTING

OPERABLE: U-0.45 EXISTING

ENTRANCE DOOR: U-0.63 EXISTING

DEFINITIONS

c.i = CONTINUOUS INSULATION Ls = LINEAR SYSTEM

NR = NO (INSULATION) REQUIREMENT

ENERGY REQUIREMENTS

N

1. DRAWINGS ARE PART OF A COMPLETE DOCUMENTS SET. CONTRACTOR SHALL CONFIRM ALL

ITEMS REQUIRED BASED UPON THE OVERALL DESIGN INTENT OF THE ENTIRE DOCUMENT

SET.

2. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, PRIOR TO BEGINNING ANY WORK,

TO CONFIRM THE ACCURACY OF THE DRAWINGS AND REPORT ANY DISCREPANCIES TO THE

ARCHITECT. DO NOT SCALE THE DRAWINGS. FIELD VERIFY ALL DIMENSIONS AND EXISTING

STRUCTURAL CONDITIONS.

3. ALL AREAS NOT INVOLVED IN THE SCOPE OF WORK FOR THIS PROJECT SHALL BE KEPT

CLEAN AND FREE OF OBSTRUCTIONS AT ALL TIMES.

4. ERECT BARRICADES AND WARNING SIGNS TO DIVERT AND WARN PASSERS-BY OF THE

CONSTRUCTION WORK. PROVIDE DUST PROOFING ENCLOSURES TO SEPARATE WORK

AREAS FROM THE EXISTING FACILITIES.

5. ALL TRASH AND DEBRIS TO BE REMOVED ON A DAILY BASIS.

6. PROVIDE PROTECTION FOR ALL EXISTING SURFACES AND CONDITIONS TO REMAIN IN PLACE

DURING THE SCOPE OF WORK. SHOULD ANY DAMAGE OCCUR, PATCH AND REPAIR ANY

DAMAGE TO ADJACENT FINISHES TO MATCH EXISTING.

7. ANY DAMAGE CAUSED TO THE BUILDING OR OWNER EQUIPMENT SHALL BE REPAIRED OR

REPLACED BACK TO ITS ORIGINAL CONDITIONS AT NO ADDITIONAL COST TO THE OWNER.

8. COVER ALL RETURN AIR GRILLES WITHIN THE AREA OF CONSTRUCTION TO PREVENT

PARTICULATE MATERIAL FROM EXHAUSTING INTO SURROUNDING SPACES.

9. APPROPRIATE LIGHT FIXTURES SHALL BE TEMPORARILY SUSPENDED TO PROVIDE

ADEQUATE LIGHTING LEVELS FOR CONSTRUCTION.

10. CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO COORDINATE WITH OTHER

DISCIPLINES TO INSTALL COMPLETE AND OPERATIONAL SYSTEMS. DRAWINGS, AS A WHOLE,

REPRESENT A COMPLETE SET AND DEPICT REQUIREMENTS FOR COMPLETE AND

OPERATIONAL SYSTEMS. INDIVIDUAL DRAWINGS MAY NOT DEPICT COMPLETE AND

ACCURATE INFORMATION TO COORDINATE COMPLETE AND OPERATIONAL SYSTEMS, BUT

DO SO AS AN ENTIRE DOCUMENT TO BE REFERENCED WITH OTHER INDIVIDUAL DRAWINGS.

CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO REFERENCE OTHER SHEETS AND

SPECIFICATIONS AS AN ENTIRE SET OF CONSTRUCTION DOCUMENTS THAT REFLECT WORK

REQUIRED TO ACHIEVE A COMPLETE AND OPERATIONAL GOAL. LACK OF COORDINATION

AND REVIEW OF DRAWINGS AND SPECIFICATIONS AS AN ENTIRE DOCUMENT TO INSTALL

COMPLETE AND OPERATIONAL SYSTEMS, BEING OBVIOUS AND TYPICAL INDUSTRY

STANDARD, IDENTIFIED IN THE DRAWINGS AND SPECIFICATIONS, SHALL NOT BE IN ANY WAY

AN ADDITIONAL COST TO THE GOVERNMENT.

11. CONTRACTOR SHALL SUBMIT A REQUEST, IN WRITING, TO INTERRUPT ANY SUCH SERVICES

TO COR (CONTRACTING OFFICER’S REPRESENTATIVE) 48 HOURS IN ADVANCE OF PROPOSED

INTERRUPTION. REQUEST SHALL STATE REASON, DATE, EXACT TIME OF, AND APPROXIMATE

DURATION OF SUCH INTERRUPTION. MAJOR INTERRUPTIONS OF ANY SYSTEM MUST BE

REQUESTED, IN WRITING, AT LEAST 60 CALENDAR DAYS PRIOR TO THE DESIRED TIME AND

SHALL BE PERFORMED AS DIRECTED BY THE COR. MAJOR INTERRUPTIONS SHALL BE

COORDINATED WITH OTHER MAJOR INTERRUPTIONS AND MAY NOT BE SCHEDULED FOR ONE

DISCIPLINE MORE THAN TWICE THROUGHOUT THE OVERALL CONSTRUCTION SCHEDULE

UNLESS REQUESTED IN WRITING AND APPROVED BY THE COR. CONTRACTOR WILL BE

ADVISED, IN WRITING, OF APPROVAL OF REQUEST, OR OF WHICH OTHER DATE AND/OR TIME

SUCH INTERRUPTION WILL CAUSE THE LEAST INCONVENIENCE TO OPERATIONS OF THE

MEDICAL CENTER. INTERRUPTION TIME APPROVED BY THE MEDICAL CENTER MAY OCCUR AT

TIMES OTHER THAN CONTRACTOR'S NORMAL WORKING HOURS. SCHEDULE INTERRUPTION

MAY BE ON WEEKENDS OR LATE HOURS AND MAY NOT BE AN ADDITIONAL COST TO THE

GOVERNMENT. COORDINATE ALL INTERRUPTIONS THAT MAY AFFECT THE NORMAL

OPERATION OF THE FACILITY WITH THE COR WHEN SUBMITTING THE CONSTRUCTION

SCHEDULE OR UPDATES TO THE CONSTRUCTION SCHEDULE.

12. NO ASBESTOS CONTAINING MATERIALS ARE TO BE USED ON THIS PROJECT. SPUR DESIGN, THE A/E OF RECORD, CAN CERTIFY THAT NO ASBESTOS CONTAINING BUILDING MATERIALS

(ACBM) OR LEAD BASED PAINT (LBP) PRODUCTS WERE DESIGNED/SPECIFIED AS BUILDING

MATERIAL IN ANY OF THE CONSTRUCTION DOCUMENTS.

13. ELEVATOR: CONTRACTOR TO PROVIDE COMPLETE MODERNIZATION OF ELEVATOR BASED

ON SCOPE OF WORK DETAILED IN SPECIFICATION SECTION 142410. GENERAL SCOPE OF

WORK TO INCLUDE NEW CONTROLLER WITH LEVELLING SYSTEM AND BATTERY LOWERING,

POWER UNIT, FIREFIGHTERS SERVICE, HYDRAULIC JACK ASSEMBLY, CAR BUFFERS, CAR

AND HALL FIXTURES, CAR ENCLOSURE FINISHES, DOOR OPERATOR AND RELATED

HOISTWAY DOOR EQUIPMENT. RELATED BUILDING WORK ITEMS TO INCLUDE DISCONNECTS,

SUMP PUMP, MACHINE ROOM CLIMATE CONTROL, MACHINE ROOM AND HOISTWAY LIGHTING,

GFCI OUTLETS IN MACHINE ROOM AND PIT, SEALING OF PENETRATIONS IN MACHINE ROOM

AND HOISTWAY. CONTRACTOR IS RESPONSIBLE FOR FIELD SURVEY AND VERIFICATION OF

ALL DIMENSIONS, EQUIPMENT APPLICATIONS, APPLICABLE CODES AND COORDINATION OF

TRADES.

GENERAL NOTES

AREA NAME

150 SF

A101

A101

SIM

A

00.0

A101

1 1

A101

LEVEL NAME

00'-00"

00'-00" 4B

3A

FIBERGLASS BATT

INSULATION

RIGID INSULATION

CONCRETE / PRECAST

CONCRETE

EARTH / SOIL

SAND, EIFS FINISH, OR

PLASTER FINISH

GYPSUM BOARD FINISH

BRICK

CONCRETE MASONRY

UNIT

STONE / CAST STONE

GYPSUM BOARD SECTION

EXTERIOR SHEATHING

BOARD SECTION

PLYWOOD SECTION

CLEAN UTILITY

000A

150 SF

/1 A101

X0000

6"

3' -0

M

A X

ROOM TAG

AREA TAG

SPECIALTY EQUIPMENT TAG

DOOR TAG

KEYED NOTE TAG

WALL TAG

WINDOW TAG

REF: 12/AE601

A101

SIM

A101

SIM

A

ACB ACOUSTIC CEILING BAFFLE

ACP ACOUSTIC CEILING PANEL

ACST ACOUSTIC

ADA AMERICANS WITH DISABILITIES ACT

ACT ACOUSTICAL CEILING TILE

ADDL ADDITIONAL

ADDN ADDITION

ADJ ADJACENT, ADJOINING, OR

ADJUSTABLE

ADMIN ADMINISTRATION

AE ARCHITECT/ENGINEER

AF ACCESS FLOORING

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AIA AMERICAN INSTITUTE OF

ARCHITECTS

ALT ALTERNATE

ALT NO ALTERNATE NUMBER

ALUM ALUMINIUM (TRIM)

AMT AMOUNT

APPROX APPROXIMATE

ARCH ARCHITECT

ASC ABOVE SUSPENDED CEILING

AT ACOUSTIC CEILING TILE

AVG AVERAGE

B

BD BOARD

BLDG BUILDING

BLKG BLOCKING

BLT IN BUILT-IN

BOS BOTTOM OF STEEL

BOT BOTTOM

BRKT BRACKET

BTWN BETWEEN

C

CAB CABINET

CAV CAVITY

CBB CONCRETE BACKER BOARD

CD CONSTRUCTION DOCUMENTS

CFM CUBIC FEET PER MINUTE

CFS CUBIC FEET PER SECOND

CG CORNER GUARD

CH BD CHALK BOARD

CIP CAST-IN-PLACE

CJ CONTROL JOINT

CL CENTER LINE

CLG CEILING

CLG HT CEILING HEIGHT

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CO CONTRACTING OFFICER

COL COLUMN

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUOUS

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CP CONTRACTOR PROVIDED

CP/CI CONTRACTOR PROVIDED /

CONTRACTOR INSTALLED

CPT CAROET/CARPET TILE

CS CONCRETE SEALED

CSWK CASEWORK

CT CERAMIC TILE

CTB CERAMIC TILE BASE

CTR CENTER

CU FT CUBIC FEET

D

DBL DOUBLE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DIA DIAMETER

DIR DIRECTION

DIST DISTANCE

DOC DOCUMENT

DR DOOR

DS DOWNSPOUT

DWG DRAWING

DWP DIMENSIONAL WALL PANEL

E

EA EACH

EJ EXPANSION JOINT

EL ELEVATION

ELEV ELEVATOR

ENTR ENTRANCE

EPY EPXOY FLOORING

EQ EQUAL

ETR EXISTING TO REMAIN

EX EXISTING

EXP EXPOSED

EXT EXTERIOR

F

FAB FABRIC

FED FEDERAL

FF FINISH FACE

FF EL FINISH FLOOR ELEVATION

FIN FINISH

FIN BS FINISH BOTH SIDES

FIN FLR FINISH FLOOR

FIN GR FINISH GRADE

FIXT FIXTURE

FLDG FOLDING

FLEX FLEXIBLE

FLG FLOORING

FLMT FLUSH MOUNT

FLR FLOOR

FOC FACE OF CONCRETE

FOM FACE OF MASONRY

FP FIRE PROTECTION

FR FIRE RESISTANT

FT FEET

FTG FOOTING

FV FIELD VERIFY

FWC FABRIC WALL COVERING

G

GDR GUARDRAIL

GL GLASS/GLAZING

GRAN GRANITE

GR FL GROUND FLOOR

GT GROUT

GSM GALVANIZED SHEET METAL

GYP BD GYPSUM BOARD

H

HDW HARDWARE

HEPA HIGH EFFICIENCY

PARTICULATE AIR (FILTER)

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HANDRAIL

HT HEIGHT

I

IBC INTERNATIONAL BUILDING CODE

INSUL INSULATION

INT INTERIOR

ILO IN LIEU OF

J

J-BOX JUNCTION BOX

L

LAV LAVATORY

LBS POUND

LDG LANDING

LF LINEAR FEET (FOOT)

LIN LINEAR

LN LINOLEUM

LOC LOCATION

LT LIGHT

LVR LOUVER

LVT LUXURY VINYL TILE

M

MAT CARPET MAT / WALK-OFF MAT

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MEMB MEMBRANE

MFR MANUFACTURER

MID MIDDLE

MIL STD MILITARY STANDARD

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MOD MODIFY

MTG MOUNTING

MTL METAL

MVBL MOVABLE

N

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

O

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OPNG OPENING

OPP OPPOSITE

OPR OPERABLE

ORD OVERFLOW ROOF DRAIN

ORIG ORIGINAL

P

P PAINT

PA PUBLIC ADDRESS

PBD PARTICLE BOARD

PCF POUNDS PER CUBIC FOOT

PCT PERCENT

PERF PERFORATED

PERIM PERIMETER

PERP PERPENDICULAR

PL PROPERTY LINE

PLAM PLASTIC LAMINATE

PLBG PLUMBING

PNL PANEL

PR PAIR

PRB PROFILE BASE

PRKG PARKING

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PORCELAIN TILE

PWR POWER

Q

QA QUALITY ASSURANCE

QC QUALITY CONTROL

QTY QUANTITY

REFERENCE SYMBOLS IDENTIFICATION TAGS

NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.

GRID HEAD AND

LINE

LEVEL INDICATOR

MATCH LINE AND

VIEW REFERENCE

NORTH ARROW W/

PROJECT NORTH

SPOT ELEVATION

DETAIL

SECTION

**48" MIN IF BOTH CLOSER

AND LATCH PROVIDED

WALL

SECTION

BUILDING

SECTION

DETAIL

ELEVATION

INTERIOR

ELEVATION

BUILDING

ELEVATION

1 1

6'- 0"

5'- 6"

BARIATRIC TOILET ROOM

TURNING RADIUS

CLEAR FLOOR SPACE

@ ADA LAVATORY

CLEAR FLOOR SPACE @ ADA

DRINKING FOUNTAIN

4"

6"

3"

6" 1'

-6

6" MAX

7" - 9" 11" MIN

17" - 25"

M

IN

6' -0

(ANSI ICC A117.1)

39"- 41"

(A N

S I I

C C

A

7.

1)

M

IN

(A N

S I I

C C

A

7.

1)

1"

3' -5

/2

M

A X

4' -1

1/

6" M

A X

R

RAF RESILIENT ATHETIC FLOORING

RB RUBBER BASE/RESILIENT BASE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REC RECESSED

REF REFERENCE

REM REMOVABLE

REP REPAIR

REPL REPLACE

REQ REQUIRE

REQD REQUIRED

RES RESINOUS FLOORING

RES-W RESINOUS / EPOXY WALL / CEILING

RF RUBBER FLOORING

RFG ROOFING

RM ROOM

RO ROUGH OPENING

RP RESIN PANEL

RSF RESILIENT SHEET FLOORING

RV ROOF VENT

RWC RIGID VINYL WALLCOVERING

S

SC SPECIALTY COATING

SD STATIC DISSIPATIVE FLOORING/TILE

SCHED SCHEDULE

SECT SECTION

SF SQUARE FOOT (FEET)

SGL SINGLE

SIM SIMILAR

SJ SCORED JOINT

SLNT SEALANT

SM SHEET METAL

SPEC SPECIFICATION

SQ SQUARE

SQ IN SQUARE INCH

SQ YD SQUARE YARD

SS SOLID SURFACE

ST STONE

STD STANDARD

STOR STORAGE

SV SHEET VINYL (ROLLED OR TILE)

T

TEL TELEPHONE

TEMP TEMPORARY

TER TERRAZO

TOF TOP OF FOOTING/ FOUNDATION

TOM TOP OF MASONRY

TOS TOP OF SLAB/ STEEL

U

UNO UNLESS NOTED OTHERWISE

UTIL UTILITY

V

VAR VARIES

VC VA PROVIDED / CONTRACTOR

INSTALLED

VCT VINYL COMPOSITION TILE

VFAT VINYL FACED ACOUSTICLAL TILE

VP VENEERED PLASTER

VT VINYL TILE

VV VA PROVIDED / VA INSTALLED

VWC VINYL WALLCOVERING

VWF VINYL WALL FABRIC

W

W/ WITH

W/O WITHOUT

W/C WATER CLOSET

WC WHEELCHAIR

WD WOOD

WFAB WALL FABRIC

WPM WATERPROOF MEMBRANE

WSF WELDED SHEET FLOOR

X

X BRACE CROSS BRACE

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. AR 2009021688 EXP. 12/31/2023

ENGR REG. NO. PE 20190403952 EXP. 12/31/2023

ENGR REG. NO. PE 2018038407 EXP. 12/31/2023

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY-SPRINKLERED

INDUSTRIAL HYGIENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/2

/2

:4 :5

A

M

GENERAL INFORMATION

NRL 02 72BKM

FINAL BID DOCUMENTS

EHRM TRAINING & ADMIN

SUPPORT

06/28/2022

589-21-702

VA MEDICAL CENTER

4801 LINWOOD BLVD

KANSAS CITY, MO 64128

GI001

SPUR #: 1794.13

No. REVISION DESCRIPTION DATE

NFPA 101-2021 EDITION

BUILDING HEIGHT:

2 STORIES, 23'-3" HEIGHT

BUILDING AREA:

AREA LIMITATION: 37,500 SF PER FLOOR (2021 IBC TABLE 503)

FIRST FLOOR 4,168 SF

SECOND FLOOR 2,688 SF

TOTAL 6,856 SF

BUILDING IS EQUIPPED WITH A FULLY AUTOMATIC FIRE SPRINKLER SYSTEM THROUGHOUT

CONSTRUCTION TYPE: (TABLE A.8.2.1.2): TYPE II (000)

FIRE RESISTANCE RATINGS (TABLE A.8.2.1.2):

• COLUMNS: 0 HR

• BEAM, GIRDERS, TRUSSES: 0 HR

• FLOOR/CEILING ASSEMBLIES: 0 HR

• ROOF/CEILING ASSEMBLIES: 0 HR

• EXTERIOR NON-BEARING WALLS: 0 HR

• INTERIOR NON-BEARING WALLS: 0 HR

FIRE-RESISTIVE REQUIREMENTS:

• NON COMBUSTIBLE MATERIALS FOR STRUCTURAL FRAME, FLOORS, ROOF DECK, EXTERIOR

NON-BEARING WALLS, INTERIOR NON-BEARING WALLS (U.N.O. AT EXTERIOR)

OCCUPANT LOAD FACTOR (TABLE 7.3.1.2):

• BUSINESS USE: 150 SF/PERSON

• CONCENTRATED BUSINESS USE: 50 SF/PERSON

• ASSEMBLY USE, CONCENTRATED USE, WITHOUT FIXED SEATING: 7 SF/PERSON

• ACCESSORY STORAGE / MECHANICAL EQUIPMENT ROOM: 500 SF/PERSON

SHAFTS MINIMUM 1-HOUR RATING (8.6.5)

CHAPTER 39: EXISTING BUSINESS OCCUPANCY

• DEAD END CORRIDOR MAXIMUM DISTANCE (NFPA 101-2021 CH 39 - 39.2.5.3): 50'

• MAXIMUM COMMON PATH OF TRAVEL (NFPA 101-2021 CH 39 - 39.2.5.2.2): 100'

• MAXIMUM TRAVEL DISTANCE (NFPA 101-2021 CH 39 - 39.2.6.3): 300'

• CORRIDOR MINIMUM FIRE RATING (NFPA 101-2021 CH 39 - 39.3.6): 0 HR

ALL EXIT DOORS PROVIDED ARE 36" LEAF MINIMUM YIELDING 34" CLEAR EXIT WIDTH.

• 32" MINIMUM DOOR LEAF WIDTH (NFPA 101-2021 7.2.1.2)

• 0.2"/PERSON (NFPA 101-2021 TABLE 7.3.3.1) ALLOWS 170 OCCUPANT LOAD.

STAIR WIDTH CAPACITY:

• .3"/PERSON (NFPA 101-2021 TABLE 7.3.3.1)

• PROVIDED 36 1/2" AT STAIR 1 (BASEMENT TO FIRST FLOOR) ALLOWS 121 MAX OCC LOAD

• PROVIDED 44" AT STAIR 1 (SECOND FLOOR TO FIRST FLOOR) ALLOWS 146 MAX OCC LOAD

• PROVIDED 42" AT STAIR 2 ALLOWS 140 MAX OCC LOAD

PROTECTED AREAS:

• STORAGE ROOMS/CLEAN/SOILED - REQUIRED VA FIRE PROTECTION DESIGN MANUAL 3.1.A AND

PER NFPA 101: 39.3.2.1 AND 8.7 SMOKE PARTITIONS WITH SPRINKLER PROTECTION, PROVIDED.

SMOKE COMPARTMENTALIZATION:

• NOT REQUIRED FOR BUSINESS OCCUPANCIES, NOT PROVIDED.

FIRE ALARM SYSTEM:

• REQUIRED/PROVIDED AUTOMATIC SYSTEM.

STANDPIPES:

• NOT REQUIRED / NOT PROVIDED.

LIFE SAFETY CODE ANALYSIS

LIFE SAFETY LEGEND

FIRE EXTINGUISHER CABINET

EXIT LIGHT / SIGN

ASSEMBLY

BUILDING EXIT

EGRESS PATH

EGRESS START

BUSINESS

BUSINESS CONCENTRATED

STORAGE

NOT IN SCOPE

FEC

AREA OCCUPANCY TAG

X

00 SF

OCCUPANCY USE ABBREVIATION

AREA

OCCUPANT LOAD FACTOR

OCCUPANT LOAD

OCCUPANCY USE

FIRE EXTINGUISHER CABINET FITTED

WITH CLEAN AGENT FIRE EXTINGUISHER

FEC2

FIRE - 1 HOUR (NEW/EXISTING)

PARTITION LEGEND

SMOKE (NEW/EXISTING)

EXISTING NON-RATED

WALL TO REMAIN

NEW WALL

2065 SF

BUSINESS

B 150

223 SF

BUSINESS

CONCENTRATED

BC 50

5 107 SF

STORAGE

S 500

1 202 SF

ASSEMBLY, LESS

CONCENTRATED

A 15

15 62 SF

STORAGE

S 500

175 SF

STORAGE

S 500

24 SF

STORAGE

S 500

TRAVEL DISTANCE: 62'

TRAVEL DISTANCE: 54'

TRAVEL DISTANCE: 47'

FEC

F E

C

EX ELEV MECH

3-100

CLASSROOM /

IV TESTING

3-112

EX HAC

CLOSET

3-111A

EX STOR

3-112A

EX STOR

3-112B

BREAKROOM

3-101

EX ENTRY

3-105

CONFERENCE

ROOM

3-102

TELECOM

3-108

ADMIN

3-110

ADMIN

3-103ADMIN

3-107

MENS RR

3-106

WOMENS RR

3-104

EX ELEV

STAIR 2

STAIR1

F E

C

ADMIN

3-111

809 SF

BUSINESS

CONCENTRATED

BC 50

821 SF

BUSINESS

CONCENTRATED

BC 50

17 284 SF

ASSEMBLY, LESS

CONCENTRATED

A 15

298 SF

BUSINESS

CONCENTRATED

BC 50

1096 SF

BUSINESS

B 150

5125 SF

STORAGE

S 500

TRAVEL DISTANCE: 45'

TRAVEL DISTANCE: 40'

FEC

BREAKROOM

3-201

EX ELEV STAIR 2

STAIR 1

CLASSROOM /

IV TESTING

3-200

CLASSROOM /

IV TESTING

3-210

HAC

3-209

WAITING

ROOM

3-203

CLASSROOM /

IV TESTING

3-211

MENS RR

3-208

WOMENS RR

3-206

CORRIDOR

C2-3-2

618 SF

STORAGE

S 500

FEC

MECHANICAL

B07

MECHANICAL

B02

MECHANICAL

B01

MECH

B07A

STAIR 1

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. AR 2009021688 EXP. 12/31/2023

ENGR REG. NO. PE 20190403952 EXP. 12/31/2023

ENGR REG. NO. PE 2018038407 EXP. 12/31/2023

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY-SPRINKLERED

INDUSTRIAL HYGIENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

HEALTHCARE PLANNER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/2

/2

:4 :5

A

M

LIFE SAFETY PLANS

NRL 03 72BKM

FINAL BID DOCUMENTS

EHRM TRAINING & ADMIN

SUPPORT

06/28/2022

589-21-702

VA MEDICAL CENTER

4801 LINWOOD BLVD

KANSAS CITY, MO 64128

GI011

SPUR #: 1794.13

N

1/8" = 1'-0"

LEVEL 1 - LIFE SAFETY PLAN2

N

1/8" = 1'-0"

LEVEL 2 - LIFE SAFETY PLAN3

OCCUPANT LOAD

OCCUPANCY USE ABBREVIATION

OCCUPIED

AREA

OCCUPANT

LOAD FACTOR

OCCUPANT

LOAD

BASEMENT

STORAGE S 618 SF 500 2

618 SF 2

LEVEL 1

ASSEMBLY, LESS

CONCENTRATED

A 202 SF 15 15

BUSINESS B 2065 SF 150 14

BUSINESS

CONCENTRATED

BC 223 SF 50 5

BUSINESS

CONCENTRATED

BC 809 SF 50 16

STORAGE S 107 SF 500 1

STORAGE S 62 SF 500 1

STORAGE S 75 SF 500 1

STORAGE S 24 SF 500 1

3568 SF 54

LEVEL 2

ASSEMBLY, LESS

CONCENTRATED

A 284 SF 15 20

BUSINESS B 1096 SF 150 5

BUSINESS

CONCENTRATED

BC 821 SF 50 17

BUSINESS

CONCENTRATED

BC 298 SF 50 7

STORAGE S 125 SF 500 1

2626 SF 50

TOTAL 6811 SF 106

N

1/8" = 1'-0"

BASEMENT - LIFE SAFETY PLAN1

No. REVISION DESCRIPTION DATE

Sheets
GI000 - COVER SHEET
GI001 - GENERAL INFORMATION
GI011 - LIFE SAFETY PLANS

File details come from the government source that posted it. Updated .