This document is an Addendum (#1) dated July 23, 2025, for the Upgrade Cath Lab #4 project at the VA Minneapolis Health Care System, Project Number 618-CSI-230. The addendum modifies multiple architectural drawings and specifications, including revisions to the Cover Sheet, Third Level Demolition Reflected Ceiling Plan, Third Level Floor Plan, Third Level Reflected Ceiling Plan, Interior Elevations, Partition Types, and Finish Plan.
Key changes include adding Section 07 81 00 (Applied Fireproofing), removing and replacing Section 09 67 23.20 with Section 09 67 23.30 (Resinous Flooring), and updating Section 00 55 00 (Metal Fabrications) to include new details about frames, particularly for lead-lined doors. The addendum affects various drawing sheets across architectural, general, structural, electrical, mechanical, and plumbing disciplines, with specific modifications to ceiling plans, floor plans, and interior elevations. The changes are part of a comprehensive renovation of Cath Lab #4 in Building 70 at the VA Minneapolis facility.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
13605 1st Avenue North Suite 100, Plymouth, MN 55441 P 763.412.4000 F 763.412.4090 ae-mn.com
INSTRUCTIONS TO BIDDERS
ADDENDUM #1
July 23, 2025
Upgrade Cath Lab #4
VAMC Minneapolis
Minneapolis, MN
Project #618-CSI-230
The Contents of this Addendum alter and amend the original drawings and specifications and take precedence over the related items therein.
Drawings:
1. Drawing GI000 – COVER SHEET
a. Revised Sheet Index.
2. Drawing AD132 – THIRD LEVEL REFLECTED CEILING DEMOLIITION PLAN
a. Revised demolition reflected ceiling plan as indicated.
b. Added Keynote DC9.
3. Drawing AE131 – THIRD LEVEL FLOOR PLAN
a. Revised keynote as indicated in Equipment 3J-140A.
4. Drawing AE132 – THIRD LEVEL REFLECTED CEILING PLAN
a. Revised Z E reflected ceiling plan as indicated.
b. Added Keynote RC7.
5. Drawing AE211 – INTERIOR ELEVATIONS
a. Elevation 7: Revised note as indicated.
b. Detail 11: Revised note as indicated.
6. Drawing AE601 – PARTITION TYPES, DOOR SCHEDULE AND DETAILS
a. Detail 2: Revised notes as indicated.
b. Detail 3: Added detail.
7. Drawing AF101 – FINISH PLAN, SCHEDULE, & DETAILS, & MOUNTING HEIGHTS
a. Finish Plan: Revised finish note as indicated.
b. Material Schedule: Revised materials as indicated.
Specifications:
1. Specification 00 01 10 – Table of Contents
a. Added Section 07 81 00 – Applied Fireproofing.
b. Remove Section 09 67 23.20 – Resinous Flooring.
c. Added Section 09 67 23.30 – Resinous Flooring.
2. Specification 00 55 00 – Metal Fabrications
a. Added Section 1.1, Item B.2. Frames.
b. Added Section 2.6 Frames.
c. Added Section 3.4 Frames for Lead Lined Doors.
13605 1st Avenue North Suite 100, Plymouth, MN 55441 P 763.412.4000 F 763.412.4090 ae-mn.com
3. Specification 07 81 00 – Applied Fireproofing
a. Added specification.
4. Specification 09 67 23.30 – Resinous (Epoxy Base) High Performance Decorative Mortar Flooring
a. Added specification.
ATTACHMENTS:
DRAWINGS: G000, AD132, AE131, AE132, AE211, AE601 & AF101
SPECIFICATIONS: 01 01 10, 00 55 00, 07 81 00 & 09 67 23.30
The inclusion of this Addendum shall be acknowledged upon submission of the Contractor’s Bid. By submission of a Bid, Bidder agrees to full acceptance of the provisions herein. All other provisions of these Specifications, Drawings, and Contract Documents shall remain unchanged and in full effect.
This Addendum shall be attached to and become part of the Specifications for the above Contract.
ISSUED BY ANDERSON: TO, JU, AW
END OF ADDENDUM #1
VAMC Minneapolis VA Project# 618-CSI-230
Upgrade Cath Lab #4 01-31-2025; Revised 07-23-2025
1 Veterans Drive CONSTRUCTION DOCUMENTS
Minneapolis, MN 55417
00 01 10-1
DEPARTMENT OF VETERANS AFFAIRS
VHA MASTER SPECIFICATIONS
TABLE OF CONTENTS
Section 00 01 10
SECTION NO DIVISION AND SECTION TITLES DATE
DIVISION 00 - SPECIAL SECTIONS
00 01 15 List of Drawing Sheets 05-20
DIVISION 01 - GENERAL REQUIREMENTS
01 00 00 General Requirements 11-21
01 32 16.15 Project Schedules (Small Projects – Design/Bid/Build 11-21
01 33 23 Shop Drawings, Product Data, and Samples 02-23
01 33 23.01 Submittal Register
01 33 24 Electronic Submittal Procedures
01 35 26 Safety Requirements 10-22
01 42 19 Reference Standards 11-20
01 45 00 Quality Control 02-21
01 58 16 Temporary Interior Signage 07-15
01 74 19 Construction Waste Management 04-22
01 81 13 Sustainable Construction Requirements
DIVISION 02 – EXISTING CONDITIONS
02 41 00 Selective Demolition 08-17
DIVISION 03 – CONCRETE
DIVISION 04 – MASONRY (NOT USED)
DIVISION 05 – METALS
05 50 00 Metal Fabrications 08-18
DIVISION 06 – WOOD, PLASTICS AND COMPOSITES
06 10 00 Rough Carpentry 10-17
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 81 00 Applied Fireproofing 07-23
07 84 00 Firestopping 01-21
07 92 00 Joint Sealants 04-22
00 01 10-2
DIVISION 08 - OPENINGS
08 11 13 Hollow Metal Doors and Frames
08 71 00 Door Hardware
08 71 13 Automatic Door Operators 01-21
DIVISION 09 – FINISHES
09 05 16 Subsurface Preparation for Floor Finishes 01-21
09 22 16 Non-Structural Metal Framing 06-18
09 29 00 Gypsum Board 04-20
09 51 00 Acoustical Ceilings 12-18
09 65 13 Resilient Base and Accessories
09 67 23.30 Resinous Flooring 07-23
09 91 00 Painting 01-21
DIVISION 10 – SPECIALTIES
10 26 00 Wall and Door Protection 01-21
DIVISION 11 – EQUIPMENT
DIVISION 12 – FURNISHINGS
12 31 00 Manufactured Metal Casework
12 36 00 Countertops 12-18
DIVISION 13 - SPECIAL CONSTRUCTION
13 49 00 Radiation Protection 01-21
DIVISION 21- FIRE SUPPRESSION
21 13 13 Wet-Pipe Sprinkler Systems 06-15
DIVISION 22 – PLUMBING
22 05 11 Common Work Results for Plumbing 01-23
22 05 23 General-Duty Valves for Plumbing Piping 09-20
22 07 11 Plumbing Insulation 09-19
22 11 00 Facility Water Distribution 05-21
22 13 00 Facility Sanitary and Vent Piping 09-20
22 40 00 Plumbing Fixtures 12-22
22 62 00 Vacuum Systems for Laboratory and Healthcare Facilities
22 63 00 Gas Systems for Laboratory and Healthcare Facilities
00 01 10-3
DIVISION 23 – HEATING, VENTILATING, AND AIR
CONDITIONING (HVAC)
23 05 11 Common Work Results for HVAC 03-23
23 05 93 Testing, Adjusting, and Balancing for HVAC 03-23
23 07 11 HVAC and Boiler Plant Insulation 02-20
23 08 00 Commissioning of HVAC Systems 03-23
23 09 23 Direct-Digital Control System for HVAC 03-23
23 21 13 Hydronic Piping 03-23
23 31 00 HVAC Ducts and Casings 03-23
23 36 00 Air Terminal Units 03-23
23 37 00 Air Outlets and Inlets 03-23
DIVISION 26 – ELECTRICAL
26 05 11 Requirements for Electrical Installations 11-22
26 05 19 Low-Voltage Electrical Power Conductors and Cables 11-22
26 05 26 Grounding and Bonding for Electrical Systems 11-22
26 05 33 Raceway and Boxes for Electrical Systems 11-22
26 05 36 Wireways for Radiology Equipment 11-22
26 05 53 Identification for Electrical Systems
26 05 73 Overcurrent Protective Device Coordination Study 11-22
26 08 00 Commissioning of Electrical Systems 11-22
26 09 23 Lighting Controls 11-22
26 24 16 Panelboards 11-22
26 27 26 Wiring Devices 11-22
26 29 21 Enclosed Switches and Circuit Breakers 11-22
26 51 00 Interior Lighting 11-22
DIVISION 27 – COMMUNICATIONS
27 05 11 Requirements for Communications Installations 09-19
27 05 26 Grounding and Bonding for Communications Systems 06-15
27 05 33 Raceways and Boxes for Communications Systems 10-18
27 10 00 Control, Communication and Signal Wiring 06-15
27 15 00 Communications Structured Cabling 01-16
27 52 23 Nurse Call and Code Blue Systems 10-18
DIVISION 28 – ELECTRONIC SAFETY AND SECURITY
28 05 00 Common Work Results for Electronic Safety and Security 04-18
28 05 13 Conductors and Cables for Electronic Safety and
Security
10-18
28 05 26 Grounding and Bonding for Electronic Safety and
Security
09-11
28 05 28.33 Conduits and Backboxes for Electronic Safety and
Security
09-11
1 Veterans Drive CONSTRUCTION DOCUMENTS
Minneapolis, MN 55417
05 50 00- 1
METAL FABRICATIONS
SECTION 05 50 00
METAL FABRICATIONS
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies items and assemblies fabricated from structural steel shapes and other materials as shown and specified.
B. Items specified.
1. Support for Wall and Ceiling Mounted Items: (SD055000-01, SD055000-02, SD102113-01, SD102600-01, SD123100-01 &
SD123100-02)
2. Frames
1.2 RELATED WORK
A. Prime and finish painting: Section 09 91 00, PAINTING.
1.3 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Shop Drawings:
1. Each item specified, showing complete detail, location in the project, material and size of components, method of joining various components and assemblies, finish, and location, size and type of anchors.
2. Mark items requiring field assembly for erection identification and furnish erection drawings and instructions.
3. Provide templates and rough-in measurements as required.
C. Manufacturer's Certificates:
1. Live load designs as specified.
D. Design Calculations for specified live loads including dead loads.
1.4 QUALITY ASSURANCE
A. Each manufactured product shall meet, as a minimum, the requirements specified, and shall be a standard commercial product of a manufacturer regularly presently manufacturing items of type specified.
B. Each product type shall be the same and be made by the same manufacturer.
C. Assembled product to the greatest extent possible before delivery to the site.
1 Veterans Drive CONSTRUCTION DOCUMENTS
Minneapolis, MN 55417
05 50 00- 2
METAL FABRICATIONS
D. Include additional features, which are not specifically prohibited by this specification, but which are a part of the manufacturer's standard commercial product.
1.5 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B. American Society of Mechanical Engineers (ASME):
B18.6.1-97..............Wood Screws
B18.2.2-87(R2010).......Square and Hex Nuts
C. American Society for Testing and Materials (ASTM):
A36/A36M-14.............Structural Steel
A47-99(R2014)...........Malleable Iron Castings
A48-03(R2012)...........Gray Iron Castings
A53-12..................Pipe, Steel, Black and Hot-Dipped, Zinc-Coated
Welded and Seamless
A123-15.................Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel Products
A240/A240M-15...........Standard Specification for Chromium and
Chromium-Nickel Stainless Steel Plate, Sheet and Strip for Pressure Vessels and for General
Applications.
A269-15.................Seamless and Welded Austenitic Stainless Steel
Tubing for General Service
A307-14.................Carbon Steel Bolts and Studs, 60,000 PSI
Tensile Strength
A391/A391M-07(R2015)....Grade 80 Alloy Steel Chain
A786/A786M-15...........Rolled Steel Floor Plate
B221-14.................Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes
B456-11.................Electrodeposited Coatings of Copper Plus Nickel
Plus Chromium and Nickel Plus Chromium
B632-08.................Aluminum-Alloy Rolled Tread Plate
C1107-13................Packaged Dry, Hydraulic-Cement Grout
(Nonshrink)
D3656-13................Insect Screening and Louver Cloth Woven from
Vinyl-Coated Glass Yarns
1 Veterans Drive CONSTRUCTION DOCUMENTS
Minneapolis, MN 55417
05 50 00- 3
METAL FABRICATIONS
F436-16.................Hardened Steel Washers
F468-06(R2015)..........Nonferrous Bolts, Hex Cap Screws, Socket Head
Cap Screws and Studs for General Use
F593-13.................Stainless Steel Bolts, Hex Cap Screws, and
Studs
F1667-15................Driven Fasteners: Nails, Spikes and Staples
D. American Welding Society (AWS):
D1.1-15.................Structural Welding Code Steel
D1.2-14.................Structural Welding Code Aluminum
D1.3-18.................Structural Welding Code Sheet Steel
E. National Association of Architectural Metal Manufacturers (NAAMM)
AMP 521-01(R2012).......Pipe Railing Manual
AMP 500-06..............Metal Finishes Manual
MBG 531-09(R2017).......Metal Bar Grating Manual
MBG 532-09..............Heavy Duty Metal Bar Grating Manual
F. Structural Steel Painting Council (SSPC)/Society of Protective
Coatings:
SP 1-15.................No. 1, Solvent Cleaning
SP 2-04.................No. 2, Hand Tool Cleaning
SP 3-04.................No. 3, Power Tool Cleaning
G. Federal Specifications (Fed. Spec):
RR-T-650E...............Treads, Metallic and Nonmetallic, Nonskid
PART 2 - PRODUCTS
2.1 DESIGN CRITERIA
A. Design fabrications to support the dead loads unless otherwise specified.
2.2 MATERIALS
A. Structural Steel: .
1. Plates and Bars: ASTM A36/A36M
2. Hollow Structural Sections: ASTM A500/A500M Gr. C
3. Bolts, Nuts and Washers: Galvanized for galvanized framing and plain finish for other framing.
a. High-strength bolts, including nuts and washers: ASTM F3125.
b. Bolts and nuts, other than high-strength: ASTM A307, Grade A.
c. Plain washers, other than those in contact with high-strength bolt heads and nuts: ASME B18.22.1.
4. Welding Materials: AWS D1.1, type to suit application.
1 Veterans Drive CONSTRUCTION DOCUMENTS
Minneapolis, MN 55417
05 50 00- 4
METAL FABRICATIONS
B. Stainless Steel: ASTM A240, Type 302 or 304.
C. Primer Paint: As specified in Section 09 91 00, PAINTING.
D. Modular Channel Units:
1. Factory fabricated, channel shaped, cold formed sheet steel shapes, complete with fittings bolts and nuts required for assembly.
2. Form channel within turned pyramid shaped clamping ridges on each side.
3. Provide case hardened steel nuts with serrated grooves in the top edges designed to be inserted in the channel at any point and be given a quarter turn so as to engage the channel clamping ridges.
Provide each nut with a spring designed to hold the nut in place.
4. Factory finish channels and parts with oven baked primer when exposed to view. Channels fabricated of ASTM A525, G90 galvanized steel may have primer omitted in concealed locations. Finish screws and nuts with zinc coating.
5. Fabricate snap-in closure plates to fit and close exposed channel openings of not more than 0.3 mm (0.0125 inch) thick stainless steel.
2.3 HARDWARE
A. Rough Hardware:
1. Furnish rough hardware with a standard plating, applied after punching, forming and assembly of parts; galvanized, cadmium plated, or zinc-coated by electro-galvanizing process. Galvanized G-90 where specified.
2. Use G90 galvanized coating on ferrous metal for exterior work unless non-ferrous metal or stainless is used.
B. Fasteners:
1. Bolts with Nuts:
a. ASME B18.2.2.
b. ASTM A307 for 415 MPa (60,000 psi) tensile strength bolts.
c. ASTM F468 for nonferrous bolts.
d. ASTM F593 for stainless steel.
2. Screws: ASME B18.6.1.
3. Washers: ASTM F436, type to suit material and anchorage.
4. Nails: ASTM F1667, Type I, style 6 or 14 for finish work.
2.4 FABRICATION GENERAL
A. Material
1 Veterans Drive CONSTRUCTION DOCUMENTS
Minneapolis, MN 55417
05 50 00- 5
METAL FABRICATIONS
1. Use material as specified. Use material of commercial quality and suitable for intended purpose for material that is not named or its standard of quality not specified.
2. Use material free of defects which could affect the appearance or service ability of the finished product.
B. Size:
1. Size and thickness of members as shown.
2. When size and thickness is not specified or shown for an individual part, use size and thickness not less than that used for the same component on similar standard commercial items or in accordance with established shop methods.
C. Connections
1. Except as otherwise specified, connections may be made by welding, riveting or bolting.
2. Field riveting will not be approved.
3. Design size, number and placement of fasteners, to develop a joint strength of not less than the design value.
4. Holes, for rivets and bolts: Accurately punched or drilled and burrs removed.
5. Size and shape welds to develop the full design strength of the parts connected by welds and to transmit imposed stresses without permanent deformation or failure when subject to service loadings.
6. Use Rivets and bolts of material selected to prevent corrosion
(electrolysis) at bimetallic contacts. Plated or coated material will not be approved.
7. Use stainless steel connectors for removable members machine screws or bolts.
D. Fasteners and Anchors
1. Use methods for fastening or anchoring metal fabrications to building construction as shown or specified.
2. Where fasteners and anchors are not shown, design the type, size, location and spacing to resist the loads imposed without deformation of the members or causing failure of the anchor or fastener, and suit the sequence of installation.
3. Use material and finish of the fasteners compatible with the kinds of materials which are fastened together and their location in the finished work.
1 Veterans Drive CONSTRUCTION DOCUMENTS
Minneapolis, MN 55417
05 50 00- 6
METAL FABRICATIONS
4. Fasteners for securing metal fabrications to new construction only, may be by use of threaded or wedge type inserts or by anchors for welding to the metal fabrication for installation before the concrete is placed or as masonry is laid.
5. Fasteners for securing metal fabrication to existing construction or new construction may be expansion bolts, toggle bolts, power actuated drive pins, welding, self-drilling and tapping screws or bolts.
E. Workmanship
1. General:
a. Fabricate items to design shown.
b. Furnish members in longest lengths commercially available within the limits shown and specified.
c. Fabricate straight, true, free from warp and twist, and where applicable square and in same plane.
d. Provide holes, sinkages and reinforcement shown and required for fasteners and anchorage items.
e. Provide openings, cut-outs, and tapped holes for attachment and clearances required for work of other trades.
f. Prepare members for the installation and fitting of hardware.
g. Cut openings in gratings and floor plates for the passage of ducts, sumps, pipes, conduits and similar items. Provide reinforcement to support cut edges.
h. Fabricate surfaces and edges free from sharp edges, burrs and projections which may cause injury.
2. Welding:
a. Weld in accordance with AWS.
b. Welds shall show good fusion, be free from cracks and porosity and accomplish secure and rigid joints in proper alignment.
c. Where exposed in the finished work, continuous weld for the full length of the members joined and have depressed areas filled and protruding welds finished smooth and flush with adjacent surfaces.
d. Finish welded joints to match finish of adjacent surface.
3. Joining:
a. Miter or butt members at corners.
1 Veterans Drive CONSTRUCTION DOCUMENTS
Minneapolis, MN 55417
05 50 00- 7
METAL FABRICATIONS
b. Where frames members are butted at corners, cut leg of frame member perpendicular to surface, as required for clearance.
4. Anchors:
a. Where metal fabrications are shown to be preset in concrete, weld
32 x 3 mm (1-1/4 by 1/8 inch) steel strap anchors, 150 mm (6 inches) long with 25 mm (one inch) hooked end, to back of member at 600 mm (2 feet) on center, unless otherwise shown.
b. Where metal fabrications are shown to be built into masonry use
32 x 3 mm (1-1/4 by 1/8 inch) steel strap anchors, 250 mm (10 inches) long with 50 mm (2 inch) hooked end, welded to back of member at 600 mm (2 feet) on center, unless otherwise shown.
5. Cutting and Fitting:
a. Accurately cut, machine and fit joints, corners, copes, and miters.
b. Fit removable members to be easily removed.
c. Design and construct field connections in the most practical place for appearance and ease of installation.
d. Fit pieces together as required.
e. Fabricate connections for ease of assembly and disassembly without use of special tools.
f. Joints firm when assembled.
g. Conceal joining, fitting and welding on exposed work as far as practical.
h. Do not show rivets and screws prominently on the exposed face.
i. The fit of components and the alignment of holes shall eliminate the need to modify component or to use exceptional force in the assembly of item and eliminate the need to use other than common tools.
F. Finish:
1. Finish exposed surfaces in accordance with NAAMM AMP 500 Metal
Finishes Manual.
3. Steel and Iron: NAAMM AMP 504.
a. Zinc coated (Galvanized): ASTM A123, G90 unless noted otherwise.
b. Surfaces exposed in the finished work:
1) Finish smooth rough surfaces and remove projections.
2) Fill holes, dents and similar voids and depressions with epoxy type patching compound.
1 Veterans Drive CONSTRUCTION DOCUMENTS
Minneapolis, MN 55417
05 50 00- 8
METAL FABRICATIONS
c. Shop Prime Painting:
1) Surfaces of Ferrous metal:
a) Items not specified to have other coatings.
b) Galvanized surfaces specified to have prime paint.
c) Remove all loose mill scale, rust, and paint, by hand or power tool cleaning as defined in SSPC-SP2 and SP3.
d) Clean of oil, grease, soil and other detrimental matter by use of solvents or cleaning compounds as defined in SSPC-
SP1.
e) After cleaning and finishing apply one coat of primer as specified in Section 09 91 00, PAINTING.
1. Spot prime all abraded and damaged areas of zinc coating which expose the bare metal, using zinc rich paint on hot-dip zinc coat items and zinc dust primer on all other zinc coated items.
2.5 SUPPORTS
A. General:
1. Fabricate ASTM A36 structural steel shapes as shown.
2. Use clip angles or make provisions for welding hangers and braces to overhead construction.
3. Field connections may be welded or bolted.
C. For Wall Mounted Items:
1. For items supported by metal stud partitions.
2. Steel strip or hat channel minimum of 1.5 mm (0.0598 inch) thick.
3. Steel strip minimum of 150 mm (6 inches) wide, length extending one stud space beyond end of item supported.
4. Steel hat channels where shown. Flange cut and flatted for anchorage to stud.
5. Structural steel tube or channel for grab bar at water closets floor to structure above with clip angles or end plates formed for anchors.
6. Use steel angles for thru wall counters. Drill angle for fasteners at ends and not over 100 mm (4 inches) on center between ends.
F. Supports at Ceiling for Radiographic (x-ray) Equipment:
1. Fabricate hangers braces, and track of modular channel units assembly as shown.
2. Fabricate steel plates for anchor to structure above.
3. Drill bent plates for bolting at mid height at concrete beams.
1 Veterans Drive CONSTRUCTION DOCUMENTS
Minneapolis, MN 55417
05 50 00- 9
METAL FABRICATIONS
G. For Operating Room Light:
1. Fabricate as shown to suit equipment furnished.
2. Drill leveling plate for light fixture bolts.
2.6 FRAMES
A. Frames for Lead Lined Doors:
1. Obtain accurate dimensions and templates from suppliers of lead lined doors, finish hardware, and hollow steel door frames.
2. Fabricate as shown for use in connection with lead lined doors.
3. Deliver assembled frames with removable shipping spreaders at top and bottom.
4. Extend angles at jambs from floor to structural slab above. At floors of interstitial spaces, terminate jamb sections and provide anchors as shown.
5. Continuously weld plates and reinforcements to frame members and head members of angle frames between jambs.
6. Weld strap anchors, not over 600 mm (24 inches) on centers, to the back of angles for embedment in masonry or concrete unless shown otherwise.
7. Type 15 Door Frames:
a. Structural steel angle frames with plate or bar full height to heads. Extend reinforcing at hinge cutouts two inches beyond cutout.
b. Fabricate top anchorage to beam side at mid height.
c. Weld clip angles to both legs of angle at top and bottom.
d. Drill clips and plates, at top and bottom for anchoring jamb angles with two 9 mm (3/8 inch) expansion bolts at each location.
e. Cut rabbet for pivot hinges and lock strike.
2.7 GUARDS (NOT USED)
2.8 COVERS AND FRAMES FOR PITS AND TRENCHES (NOT USED)
2.9 GRATINGS (NOT USED)
2.10 LOOSE LINTELS (NOT USED)
2.11 SHELF ANGLES (NOT USED)
2.12 PLATE DOOR SILL (NOT USED)
2.13 SAFETY NOSINGS (NOT USED)
2.14 LADDERS (NOT USED)
2.15 RAILINGS (NOT USED)
1 Veterans Drive CONSTRUCTION DOCUMENTS
Minneapolis, MN 55417
05 50 00- 10
METAL FABRICATIONS
2.16 CATWALKS (NOT USED)
2.17 TRAP DOOR AND FRAMES WITH CEILING HATCH (NOT USED)
2.18 SIDEWALK DOOR (NOT USED)
2.19 SCREENED ACCESS DOORS AND FRAMES (NOT USED)
2.20 STEEL COUNTER OR BENCH TOP FRAME AND LEGS (NOT USED)
2.21 STEEL PIPE BOLLARD (NOT USED)
PART 3 - EXECUTION
3.1 INSTALLATION, GENERAL
A. Set work accurately, in alignment and where shown, plumb, level, free of rack and twist, and set parallel or perpendicular as required to line and plane of surface.
B. Items set into concrete or masonry.
1. Provide temporary bracing for such items until concrete or masonry is set.
2. Place in accordance with setting drawings and instructions.
3. Build strap anchors, into masonry as work progresses.
C. Set frames of gratings, covers, corner guards, trap doors and similar items flush with finish floor or wall surface and, where applicable, flush with side of opening.
D. Field weld in accordance with AWS.
1. Design and finish as specified for shop welding.
2. Use continuous weld unless specified otherwise.
E. Install anchoring devices and fasteners as shown and as necessary for securing metal fabrications to building construction as specified.
Power actuated drive pins may be used except for removable items and where members would be deformed or substrate damaged by their use.
F. Spot prime all abraded and damaged areas of zinc coating as specified and all abraded and damaged areas of shop prime coat with same kind of paint used for shop priming.
G. Isolate aluminum from dissimilar metals and from contact with concrete and masonry materials as required to prevent electrolysis and corrosion.
H. Secure escutcheon plate with set screw.
3.2 INSTALLATION OF SUPPORTS
A. Anchorage to structure.
1. Secure angles or channels and clips to overhead structural steel by continuous welding unless bolting is shown.
1 Veterans Drive CONSTRUCTION DOCUMENTS
Minneapolis, MN 55417
05 50 00- 11
METAL FABRICATIONS
2. Secure supports to concrete inserts by bolting or continuous welding as shown.
3. Secure supports to mid height of concrete beams when inserts do not exist with expansion bolts and to slabs, with expansion bolts.
unless shown otherwise.
4. Secure steel plate or hat channels to studs as detailed.
D. Support at Ceiling for X-ray Tube Stand and Radiographic Equipment:
1. Bolt modular steel channel frames to hangers as shown, anchored to structure above.
2. Fasten frames with modular channel manufacturers fittings, bolts, and nuts. Space modular channel supports and hangers as shown and as required to suit equipment furnished.
3. Install closure plates in channels at ceiling where channel opening is visible. Coordinate and cut plates to fit tight against equipment anchors after equipment anchors are installed.
E. Ceiling Support for Operating Light:
1. Anchor support to structure above as shown.
2. Set leveling plate as shown level with ceiling.
3. Secure operating light to leveling plate in accordance with light manufacturer's requirements.
3.3 COVERS AND FRAMES FOR PITS AND TRENCHES (NOT USED)
3.4 FRAMES FOR LEAD LINED DOORS
A. Secure jamb angle clips and plates, at top and bottom with two, 9 mm
(3/8 inch) expansion bolts to concrete.
B. Secure 150 x 90 x 13 mm (6 x 3-1/2 x 1/2 inch) angle to steel framing for anchorage when expansion bolts to concrete is not possible.
C. Secure clips by welding to steel.
D. At interstitial spaces, anchor jamb angles as shown.
3.5 DOOR FRAMES (NOT USED)
3.6 OTHER FRAMES
A. Set frame flush with surface unless shown otherwise.
B. Anchor frames at ends and not over 450 mm (18 inches) on centers unless shown otherwise.
C. Set in formwork before concrete is placed.
3.7 GUARDS (NOT USED)
3.8 GRATINGS (NOT USED)
3.9 STEEL LINTELS (NOT USED)
1 Veterans Drive CONSTRUCTION DOCUMENTS
Minneapolis, MN 55417
05 50 00- 12
METAL FABRICATIONS
3.10 SHELF ANGLES (NOT USED)
3.11 PLATE DOOR SILL (NOT USED)
3.12 SAFETY NOSINGS (NOT USED)
3.13 LADDERS (NOT USED)
3.14 RAILINGS (NOT USED)
3.15 CATWALK AND PLATFORMS (NOT USED)
3.16 SIDEWALK DOOR, TRAP DOORS, AND FRAMES (NOT USED)
3.17 SCREENED ACCESS DOOR (NOT USED)
3.18 STEEL COMPONENTS FOR MILLWORK ITEMS (NOT USED)
3.19 INSTALLATION OF STEEL PIPE BOLLARD (NOT USED)
3.20 CLEAN AND ADJUSTING
A. Adjust movable parts including hardware to operate as designed without binding or deformation of the members centered in the opening or frame and, where applicable, contact surfaces fit tight and even without forcing or warping the components.
B. Clean after installation exposed prefinished and plated items and items fabricated from stainless steel, aluminum and copper alloys, as recommended by the metal manufacture and protected from damage until completion of the project.
- - - E N D - - -
Upgrade Cath Lab #4 07-23-2025
1 Veterans Drive ADDENDUM #1
Minneapolis, MN 55417
07 81 00 - 1
SECTION 07 81 00
APPLIED FIREPROOFING
PART 1 - GENERAL
1.1 DESCRIPTION:
A. This section specifies spray-applied cementitious coverings to provide fire resistance to interior structural steel members shown. Sprayed-applied mineral fiber fireproofing is not permitted.
1.2 RELATED WORK:
A. Sustainable Design Requirements: Section 01 81 13, SUSTAINABLE
CONSTRUCTION REQUIREMENTS.
1.3 SUBMITTALS:
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Sustainable Design Submittals, as described below:
1. Volatile organic compounds per volume as specified in PART
2 - PRODUCTS.
C. Installer qualifications.
D. Testing laboratory accreditations.
E. Manufacturer's Literature and Data:
1. Manufacturer's complete and detailed application instructions and specifications.
2. Manufacturer's repair and patching instructions.
F. Certificates:
1. Certificate from testing laboratory attesting fireproofing material and application method meet the specified fire ratings.
a. List thickness and density of material required to meet fire ratings.
b. Accompanied by complete test report and test record.
2. Manufacturer's certificate indicating sprayed-on fireproofing material supplied under the Contract is same within manufacturing tolerance as fireproofing material tested.
G. Miscellaneous:
1. Manufacturer's written approval of surfaces to receive sprayed-on fireproofing.
2. Manufacturer's written approval of completed installation.
3. Manufacturer's written approval of the applicators of fireproofing material.
1 Veterans Drive ADDENDUM #1
Minneapolis, MN 55417
07 81 00 - 2
1.3 PRODUCT DELIVERY, STORAGE AND HANDLING:
A. Deliver to job-site in sealed containers marked and labeled to show manufacturer's name and brand and UL certification markings of compliance with the specified requirements.
B. Remove damaged or opened containers from the site.
C. Store the materials off the ground, under cover, away from damp surfaces.
D. Keep dry until ready for use.
E. Remove materials that have been exposed to water before installation from the site.
1.4 FIELD CONDITIONS:
A. Temperature: Do not apply fireproofing when substrate or ambient temperature is below 4 degrees C (40 degrees F) unless temporary protection and heat are provided to maintain temperature at or above stated value during application and for 24 hours before and after application.
B. Humidity: Maintain relative humidity levels within limits recommended by fireproofing manufacturer.
C. Ventilation: Provide ventilation to properly dry the fireproofing after application. Provide a minimum of four (4) air exchanges per hour by forced air circulation. When permitted by Contracting Officer
Representative (COR), ventilate by natural circulation.
1.5 QUALITY ASSURANCE:
A. Installer Qualifications: A firm or individual certified, licensed, or otherwise qualified by fireproofing manufacturer as experienced and with sufficient trained staff to install manufacturer’s products according to specified requirements. Submit manufacturer’s certification that each installer is trained and qualified to install the specified fireproofing. Submit evidence that each installer has a minimum of three (3) years’ experience and a minimum of four (4) installations using the specified fireproofing.
B. Testing Laboratory Accreditation Requirements: Construction materials testing laboratories must be accredited by a laboratory accreditation authority. Submit a copy of the Certificate of Accreditation and Scope of Accreditation.
C. Test for fire endurance in accordance with ASTM E119, for fire rating specified, in a nationally recognized laboratory.
1 Veterans Drive ADDENDUM #1
Minneapolis, MN 55417
07 81 00 - 3
D. Manufacturer's inspection and approval of surfaces to receive fireproofing.
E. Manufacturer's approval of fireproofing applications.
F. Manufacturer's approval of completed installation.
G. Manufacturer's representative is to observe and advise at the commencement of application, and is required to visit the site as required thereafter for the purpose of ascertaining proper application.
H. Pre-Application Test Area.
1. Apply a test area consisting of a typical overhead fireproofing installation, including not less than 4.5 m (15 feet) of beam and deck.
a. Apply to one (1) column.
b. Apply for the hourly ratings required in the construction documents.
2. Install in location selected by the COR, for approval by the representative of the fireproofing material manufacturer and the
COR.
3. Perform Bond test for cohesive and adhesive strength in accordance with ASTM E736 for each applied fireproofing design used.
4. Perform density test in accordance with ASTM E736 for each applied fireproofing design used.
5. Do not proceed in other areas until installation of test area has been completed and approved.
6. Keep approved installation area open for observation as criteria for sprayed-on fireproofing.
1.6 APPLICABLE PUBLICATIONS
A. Publications listed below form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only.
B. ASTM International (ASTM):
C841-03(R2013)..........Installation of Interior Lathing and Furring
C847-14.................Metal Lath
E84-14..................Surface Burning Characteristics of Building
Materials
E119-12a................Fire Tests of Building Construction and
Materials
1 Veterans Drive ADDENDUM #1
Minneapolis, MN 55417
07 81 00 - 4
E605-93(R2011)..........Thickness and Density of Sprayed Fire-Resistive
Materials Applied to Structural Members
E736-00(R2011)..........Cohesion/Adhesion of Sprayed Fire-Resistive
Materials Applied to Structural Members
E759-92(R2011)..........The Effect of Deflection on Sprayed Fire-
Resistive Material Applied to Structural
Members
E760-92(R2011)..........Impact on Bonding of Sprayed Fire-Resistive
Material Applied to Structural Members
E761-92(R2011)..........Compressive Strength of Fire-Resistive Material
Applied to Structural Members
E859-93(R2011)..........Air Erosion of Sprayed Fire-Resistive Materials
Applied to Structural Members
E937-93(R2011)..........Corrosion of Steel by Sprayed Fire-Resistive
Material Applied to Structural Members
E1042-02(R2014).........Acoustically, Absorptive Materials Applied by
Trowel or Spray.
G21-13..................Determining Resistance of Synthetic Polymeric
Materials to Fungi
C. Underwriters Laboratories, Inc. (UL):
Fire Resistance Directory...Latest Edition including Supplements
D. Warnock Hersey (WH):
Certification Listings..Latest Edition
E. Factory Mutual System (FM):
Approval Guide..........Latest Edition including Supplements
F. Environmental Protection Agency (EPA):
40 CFR 59(2014).........National Volatile Organic Compound Emission
Standards for Consumer and Commercial Products
PART 2 - PRODUCTS
2.1 SPRAYED-ON FIREPROOFING:
A. ASTM E1042, Class (a), Category A.
1. Factory mixed cementitious materials with approved aggregate.
B. Materials containing asbestos are not permitted.
C. Fireproofing characteristics when applied in the thickness and density required to achieve the fire-rating specified.
1 Veterans Drive ADDENDUM #1
Minneapolis, MN 55417
07 81 00 - 5
Characteristic Test Results
1. Deflection ASTM E759 No cracking, spalling, or delamination when backing to which it is applied has a deflection up to 1/120 in 3 m
(10 ft.)
2. Corrosion-Resistance ASTM E937 No promotion of corrosion of steel.
3. Bond Impact ASTM E760 No cracking, spalling, or delamination.
4. Cohesion/Adhesion
(Bond Strength)
ASTM E736 Minimum cohesive/adhesive strength of 9.57 kPa (200 lbf per
sq. ft.) for protected areas.
19.15 kPa (400 lbf per sq. ft.)
for exposed areas.
5. Air Erosion ASTM E859 Maximum gain weight of the collecting filter
0.27 gm per sq. meter
(0.025 gm per sq. ft.).
6. Compressive Strength ASTM E761 Minimum compressive strength
48 kPa (1000 psf).
7. Surface Burning
Characteristics with adhesive and sealer to be used
ASTM E84 Flame spread 25 or less smoke developed 50 or less
8. Fungi Resistance ASTM G21 Resistance to mold growth when inoculated with aspergillus niger
(28 days for general application)
2.2 ADHESIVE:
A. Adhesive may be an integral part of the material or applied separately to surface receiving fireproofing material.
2.3 SEALER:
A. Surface burning characteristics as specified for fireproofing material.
B. Fungus resistant.
C. Sealer may be an integral part of the material or applied separately to the exposed surface. When applied separately use contrasting color pigmented sealer, white preferred.
D. VOC content: Product to comply with VOC content limits of authorities having jurisdiction and the following VOC limits when calculated according to 40 CFR 59, (EPA Method 24):
1. Flat Paints and Coatings: 50 g/L.
2. Nonflat Paints and Coatings: 150 g/L.
1 Veterans Drive ADDENDUM #1
Minneapolis, MN 55417
07 81 00 - 6
3. Primers, Sealers, and Undercoaters: 200 g/L.
2.4 WATER:
A. Clean, fresh, and free from organic and mineral impurities.
B. pH of 6.9 to 7.1.
2.5 MECHANICAL BOND MATERIAL:
A. Expanded Metal Lath: ASTM C847, minimum weight of 0.92 kg per square meter (1.7 pounds per square yard) or as required, according to fire-resistance designs indicated and fire proofing manufacturer’s written instructions.
B. Fasteners: ASTM C841.
C. Reinforcing Fabric: Glass- or carbon-fiber fabric of type, weight, and form required to comply with fire-resistance designs indicated;
approved and provided by fireproofing manufacturer.
D. Reinforcing Mesh: Metallic mesh reinforcement of type, weight, and form required to comply with fire-resistance design indicated; approved and provided by fireproofing manufacturer. Include pins and attachments.
PART 3 - EXECUTION
3.1 EXAMINATION:
A. Verify surfaces to receive fireproofing are clean and free of dust, soot, oil, grease, water soluble materials or any foreign substance which would prevent adhesion of the fireproofing material.
B. Verify hangers, inserts and clips are installed before the application of fireproofing material.
C. Verify ductwork, piping, and other obstructing material and equipment is not installed that will interfere with fireproofing installation.
D. Conduct tests according to fireproofing manufacturer’s written instructions to verify that substrates are free of substances capable of interfering with bond. Submit test report.
3.2 APPLICATION:
A. Do not start application until written approval has been obtained from manufacturer of fireproofing materials that surfaces have been inspected by the manufacturer or his representative, and are suitable to receive sprayed-on fireproofing.
B. Coordinate application of fireproofing material with other trades.
C. Cover other work and exterior openings subject to damage from fallout or overspray of fireproofing materials during application.
D. Application of Metal Lath:
1 Veterans Drive ADDENDUM #1
Minneapolis, MN 55417
07 81 00 - 7
1. Apply to beam and columns having painted surfaces which fail
ASTM E736 Bond Test requirements in pre-application test area.
2. Apply to beam flanges 305 mm (12-inches) or more in width.
3. Apply to column flanges 406 mm (16-inches) or more in width.
4. Apply to beam or column web 406 mm (16-inches) or more in depth.
5. Tack weld or mechanically fasten on maximum of 305 mm (12-inch) center.
6. Lap and tie lath member in accordance with ASTM C841.
E. Mix and apply in accordance with manufacturer's instructions.
1. Mechanically control material and water ratios.
2. Apply adhesive and sealer, when not an integral part of the materials, in accordance with the manufacturer's instructions.
3. Apply to density and thickness indicated in UL Fire Resistance
Directory, FM Approval Guide, or WH Certification Listings unless specified otherwise. Test in accordance with ASTM E119.
4. Minimum ASTM E605 applied dry density per cubic meter (cubic foot) for the underside of the walk on deck (interstitial) hung purlin or beam and steel deck, columns in interstitial spaces and mechanical equipment rooms to be as follows:
a. Factory mixed cemitious material - 350 kg per cubic meter (22 lb.
per cubic ft.).
F. Complete application is to be completed in one area. Inspection and approval by COR is required before removal of application equipment and proceeding with further work.
3.3 FIELD TESTS:
A. The applied fireproofing to be tested by a COR approved independent testing laboratory and paid for by the Contractor. Submit test reports documenting results of tests on the applied material in the project.
B. COR will select area to be tested in specific bays on each floor using a geometric grid pattern. Apply test sample every 929 square meters
(10,000 square feet) of floor area or two (2) for each floor, whichever produces the greatest number of test areas.
C. Test for thickness and density in accordance with ASTM E605. Areas showing thickness less than that required as a result of fire endurance test are not acceptable.
D. Areas showing less than required fireproofing characteristics are not suitable for the following field tests.
1 Veterans Drive ADDENDUM #1
Minneapolis, MN 55417
07 81 00 - 8
1. Test for cohesion/adhesion: ASTM E736.
2. Test for bond impact strength: ASTM E760.
3.4 PATCHING AND REPAIRING:
A. Inspect after mechanical, electrical and other trades have completed work in contact with fireproofing material, but before sprayed material is covered by subsequent construction.
B. Perform corrective measures in accordance with fireproofing material manufacturer's recommendations.
1. Respray areas requiring additional fireproofing material to provide the required thickness, and replace dislodged or removed material.
2. Spray material for patching by machine directly on point to be patched, or into a container and then hand apply.
3. Do not hand mix material.
C. Repair:
1. Respray test and rejected areas.
2. Patch fireproofing material which is removed or disturbed after approval.
D. Perform final inspection of sprayed areas after patching and repair.
3.6 SCHEDULE:
A. Apply fireproofing material in interior structural steel members // and on underside of interior steel floor and roof decks //, except on following surfaces:
1. Structural steel and underside of steel decks in elevator or dumbwaiter machine rooms.
2. Steel members in elevator hoist ways.
3. Areas used as air handling plenums.
4. Steel to be encased in concrete or designated to receive other type of fireproofing.
1 Veterans Drive ADDENDUM #1
Minneapolis, MN 55417
09 67 23.30 - 1
SECTION 09 67 23.30
RESINOUS (EPOXY BASE) HIGH PERFORMANCE DECORATIVE MORTAR FLOORING
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies a seamless resinous (epoxy resin composition) and aliphatic poly urethane sealer, flooring systems with integral cove base.
1.2 RELATED WORK
A. Concrete and Moisture Vapor Barrier: Section 03 30 00, CAST-IN-PLACE
CONCRETE.
B. Substrate Preparation for Floor Finishes: Section 09 05 16.
C. Color and location of each type of resinous (epoxy resin composition) flooring: See Material and Room Finish Schedule in Drawings.
D. Floor Drains: Division 22, PLUMBING.
1.3 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Manufacturer's Literature and Data:
1. Description of each product to be provided.
2. Application and installation instructions.
3. Maintenance Instructions: Submit manufacturer’s written instructions for recommended maintenance practices.
C. Qualification Data: For Installer.
D. Sustainable Submittal:
1. Product data for products having recycled content, submit documentation indicating percentages by weight of postconsumer and pre consumer recycled content.
a. Include statements indicating costs for each product having recycled content, and low emitting materials.
2. Product data for Environmental Quality Credit EQ 4.2 low emitting materials, include printed statement of VOC content indicating compliance with environmental requirements.
3. Product data for Material Resource Credit MR 4.1, 12%-35% post-consumer recycled glass content.
E. Samples:
1. Each color and texture specified in the Material Schedule in
Drawings.
1 Veterans Drive ADDENDUM #1
Minneapolis, MN 55417
09 67 23.30 - 2
2. Samples for verification prior to installation: For each (color and texture) resinous flooring system required, 18 inches (152 mm) square, applied to a smooth rigid backing by installer for this project.
3. Sample showing construction from substrate to finish surface in thickness specified and color and texture of finished surfaces.
Finished flooring must match the approved samples in color and texture.
F. Shop Drawings: Include plans, sections, component details, and attachment to other trades. Indicate layout of the following:
1. Edge configurations.
G. Certifications and Approvals:
1. Manufacturer's certification of material and substrate compliance with specification.
2. Manufacturer's approval of installer.
3. Contractor's certificate of compliance with Quality Assurance requirements.
H. Warranty: As specified in this section.
1.4 QUALITY ASSURANCE
A. Manufacture Certificate: Manufacture shall certify that a particular resinous flooring system has been in use for a minimum of (5) five years.
B. Installer Qualifications: Engage an installer (applicator) who is experienced in applying resinous flooring systems similar in material, design, and extent to those indicated for this project for a minimum period of (5) five years, whose work has resulted in applications with a record of successful in-service performance, and who is acceptable to resinous flooring manufacturer.
1. Engage an installer who is certified in writing by resinous flooring manufacturer as qualified to apply resinous flooring systems indicated.
2. Contractor shall have completed at least (5) five projects of similar size and complexity. Include list of at least (5) five projects. List must include owner (purchaser); address of installation, contact information at installation project site; and date of installation.
1 Veterans Drive ADDENDUM #1
Minneapolis, MN 55417
09 67 23.30 - 3
3. Installer's Personnel: Employ persons trained for application of specified product.
C. Source Limitations:
1. Obtain primary resinous flooring materials including primers, resins, hardening agents, grouting coats and finish or sealing coats from a single manufacturer.
2. Provide secondary materials, including patching and fill material, joint sealant, and repair material of type and from source recommended by manufacturer of primary materials.
D. Pre-Installation Conference:
1. Convene a meeting not less than thirty days prior to starting work.
2. Attendance:
a. Contractor
b. VA COR
c. Manufacturer and Installer's Representative
3. Review the following:
a. Environmental requirements
1) Air and surface temperature
2) Relative humidity
3) Ventilation
4) Dust and contaminates
b. Protection of surfaces not scheduled to be coated
c. Inspect and discus condition of substrate and other preparatory work performed
d. Review and verify availability of material; installer’s personnel, equipment needed
e. Design and edge conditions.
f. Performance of the coating with chemicals anticipated in the area receiving the resinous (epoxy resin composition) flooring system
g. Application and repair
h. Field quality control
i. Cleaning
j. Protection of coating systems
k. One-year inspection and maintenance
l. Coordination with other work
m. Installation instruction in accordance with Manufacturer’s requirements.
1 Veterans Drive ADDENDUM #1
Minneapolis, MN 55417
09 67 23.30 - 4
E. Manufacturer’s Field Services: Manufacturer’s representative shall provide technical assistance and guidance for surface preparation and application of resinous flooring systems.
F. Contractor Job Site Log: Contractor shall document daily; the work accomplished environmental conditions and any other condition event significant to the long-term performance of the resinous flooring systems installation. The Contractor shall maintain these records for one year after Substantial Completion.
1.5 MATERIAL PACKAGING DELIVERY AND STORAGE
A. Deliver materials to the site in original sealed packages or containers, clearly marked with the manufacturer's name or brand, type and color, production run number and date of manufacture.
B. Protect materials from damage and contamination in storage or delivery, including moisture, heat, cold, direct sunlight, etc.
C. Maintain temperature of storage area between 60- and 80-degrees F (15 and 26 degrees C).
D. Keep containers sealed until ready for use.
E. Do not use materials beyond manufacturer’s shelf-life limits.
F. Package materials in factory pre-weighed and in single, easy to manage batches sized for ease of handling and mixing proportions from entire package or packages. No On site weighing or volumetric measurements are allowed.
1.6 PROJECT CONDITIONS
A. Environmental Limitations: Comply with resinous flooring manufacturer's written instructions for substrate temperature, ambient temperature, moisture, ventilation, and other conditions affecting resinous flooring application.
1. Maintain material and substrate temperature between 65- and 85-degrees Fahrenheit (18 and 30 degrees C) during resinous flooring application and for not less than 24 hours after application.
2. Concrete substrate shall be properly cured per referenced section 03
30 00, CAST-IN-PLACE CONCRETE. Standard cure time a minimum of 30 days. A vapor barrier must be present for concrete subfloors on or below grade.
a. Resinous flooring applications where moisture testing resulting in readings exceeding limits as defined in this specification under part 3, section 3.4, paragraph B, shall employ a multiple
1 Veterans Drive ADDENDUM #1
Minneapolis, MN 55417
09 67 23.30 - 5 component 15 mil thick system designed to suppress excess moisture in concrete.
b. Application at a minimum thickness of 15 mils, over properly prepared concrete substrate as defined in section 3.4.
c. Moisture suppression system must meet the design standards as follows:
Property Test Value
Tensile Strength ASTM D638 4,400 psi
Volatile Organic
Compound Limits
(V.O.C.)
EPA & LEED 25 grams per liter
Permeance ASTM E96 @ 16mils/
0.4mm on concrete
0.1 perms
Tensile Modulus ASTM D638 1.9X105 psi
Percent Elongation ASTM D638 12%
Cure Rate Per manufacturer’s
Data
4 hours Tack free with 24hr recoat window
Bond Strength ASTM D7234 100% bond to concrete failure
B. Lighting: Provide permanent lighting or, if permanent lighting is not in place, simulate permanent lighting conditions during resinous flooring application.
C. Close spaces to traffic during resinous flooring application and for not less than 24 hours after application unless manufacturer recommends a longer period.
1.7 WARRANTY
A. Work subject to the terms of the Article “Warranty of Construction”
FAR clause 52.246-21.
B. Warranty: Manufacture shall furnish a single, written warranty covering the full assembly for both material and workmanship for…