Atch 26 - Electrical WW R2 20260818.pdf

PDF 8 MB Posted

Attached to
Z2DA--687-24-101 Demolish Regrade Connecting Corridor
Solicitation number
36C26026R0080
Issued by

About this file

This is a set of electrical bid documents and design drawings for the Jonathan M. Wainwright Memorial VA Medical Center in Walla Walla, Washington, specifically for the demolition and regrading of a connecting corridor project (Project Number 687-24-101). The documents include detailed electrical demolition plans, installation plans, conduit schedules, and surveillance system specifications.

The scope encompasses comprehensive electrical demolition of an existing elevated corridor structure, including removal of all conduits, conductors, junction boxes, and associated electrical equipment from Buildings 74, 68, 80, 69, 75, 77, T1, T2, and T-2. Critical work includes identifying and converting energized conduits to underground routing, removing two 120V electric vehicle charging stations, addressing hazardous materials (mercury in fluorescent tubes and PCBs in ballasts), and maintaining emergency power systems to Buildings 68, 69, 74, and 75 supplied by a motor generator set in Building 80. The contractor must coordinate with maintenance staff 48 hours prior to accessing restricted areas and field-verify all electrical connections before disconnection. Installation work involves routing new electrical systems underground using Schedule 40 conduits, installing new lighting fixtures with 1.5-inch Schedule 80 conduit containing #8 AWG bare copper conductors, establishing surveillance camera infrastructure with fiber optic and ethernet systems, and installing junction boxes with proper grounding and bonding per National Electrical Safety Code requirements. Conductor specifications include copper minimum #12 THW/THWN for branch circuits with separate green insulated grounding conductors, and the work must comply with the National Electrical Code, NFPA, and OSHA standards.

View the file

Other files

File Type Posted
Amendment 0005.pdf PDF
20260821 Walla Walla_EP106.pdf PDF
20260821 Walla Walla_E-504.pdf PDF
36C26026R0080 0004.pdf PDF
Amendment 0003.pdf PDF
Atch 24 - Civil_GC101 Staging Area.pdf PDF
Atch 20 - 01 45 00 - QUALITY CONTROL rev1.pdf PDF
Amendment 0002.pdf PDF
Atch 21 - 02 82 11.1 Hazmat Survey Report 06-12-25.pdf PDF
Atch 23 - 28 23 00 Video Surveillance rev1.pdf PDF
Atch 28 - GeoTech Report 2.pdf PDF
Atch 18 - QUESTIONS and ANSWERS - 36C26026R0080.pdf PDF
Atch 19 - 00 01 10 TOC.pdf PDF
Atch 22 - 02 83 33.13.1 Lead Based Paint Survey 07-2006.pdf PDF
Atch 25 - Civil_C-401 and C-404 Safety Railing.pdf PDF
Atch 27 - GeoTech Report 1.pdf PDF
Amendment 0001.pdf PDF
Atch 17 - Wage Determination 05.18.2026.pdf PDF
Atch 16 - Site Visit Sign In Sheet.pdf PDF
Atch 2 - Drawings_Connect Corridor 687-24-101.pdf PDF
Atch 3 - Specs_Connect Corridor 687-24-101.pdf PDF
Atch 4 - Bldgs 68 and 69 Phase 3 PCRA_Connect Corridor 687-24-101.pdf PDF
Atch 8 - Bldg 75 Phase 2 PCRA_Connect Corridor 687-24-101.pdf PDF
Atch 12 - Limitations on Subcontracting_Connect Corridor 687-24-101.pdf PDF
Atch 13 - Contractor Rules of Behavior_Connect Corridor 687-24-101.pdf PDF
Atch 5 - Bldg 68 Sprinkler Demo Install PCRA_Connect Corridor 687-24-101.pdf PDF
Atch 10 - Bldg 80 Phase 3 PCRA_Connect Corridor 687-24-101.pdf PDF
Atch 14 - Past Performance Questionnaire_Connect Corridor 687-24-101.docx DOCX document
Atch 15 - Wage Determination 01.23.2026, Connect Corridor, 687-24-101.pdf PDF
Atch 6 - Bldg 74 Phase 4 PCRA_Connect Corridor 687-24-101.pdf PDF
Atch 9 - Bldg 78 Phase 1 PCRA_Connect Corridor 687-24-101.pdf PDF
Solicitation 36C26026R0080_Connect Corridor 687-24-101.pdf PDF
Atch 1 - SOW_Connect Corridor 687-24-101.docx DOCX document
Atch 7 - Bldg 74 Sprinkler Demo PCRA_Connect Corridor 687-24-101.pdf PDF
Atch 11 - Divisional Price Breakout_Connect Corridor 687-24-101.xlsx XLSX spreadsheet
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BUILDING 80

E

H

H

H

H

H

H

H

H

H

H

H

H

H

H H

H H

AGC

AGC

AGC BGC

AGC

AG

C

AGC

AGC

AGC

AGC

FOC

FO

C

AG

C

AGC

FOC

AGC

FOC

FOC

AGCAGC

FOC

BGC

BGC

AGC

FOC

BGC

FOC

Project Number

Building Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

N/A

U. S. Department of Veterans Affairs

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

56 Louis Prima Drive, Suite B, Covington, LA 70433 504.684.4408; Sean Fitzpatrick

JONATHAN M.WAINWRIGHT

MEMORIAL VA MC - DEMOLISH AND

REGRADE CONNECTING CORRIDOR

Walla Walla, Washington

687-24-101

N/A Project Manager

04/28/2026Revisions: Date:

Connor Henderson General Engineer Facilities Management Service (FMS) Phone: (509) 759-2923 Email: Connor.Henderson@va.gov

ZTNT

JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980

Sheet Number

ELECTRICAL DEMOLITION PLAN

(OVERVIEW)

ED103

KEYED NOTES

1. ASSUMED EMERGENCY POWER TO BUILDING 77 AND BUILDING T-2 IS

UNDERGROUND, CONTRACTOR TO CONFIRM.

2. BUILDING 80 ENCLOSES EXISTING MOTOR GENERATOR SET THAT PROVIDES

EMERGENCY POWER TO BUILDING 68, 69, 74, AND 75.

3. MAIN EMERGENCY POWER LEAVES BUILDING 80 AND ATTACHES TO THE

UNDERSIDE OF CORRIDOR, ROUTES TO OTHER BUILDINGS FROM THIS LOCATION.

4. LARGE NUMBER OF CONDUITS ARE ATTACHED TO THE UNDERSIDE OF THE

ELEVATED CORRIDOR. MAJORITY OF CONDUITS ARE ABANDONED. CONTRACTOR

TO REMOVE ALL CONDUITS, FITTINGS, JUNCTION BOXES, CONDUCTORS, HANGERS,

ETC, FROM ALL SOURCES TO LOAD AND DISPOSE.

5. CARE MUST BE TAKEN BY CONTRACTOR TO CONFIRM ALL ENERGIZED AND IN USE

CONDUITS ARE IDENTIFIED, SOURCE TO LOAD AND CONVERTED TO

UNDERGROUND.

6. RESTRICTED ACCESS ROOM. IF ACCESS IS REQUIRED, CONTRACTOR TO

COORDINATE WITH MAINTENANCE STAFF 48 HOURS PRIOR TO NEEDING ACCESS

FOR PROPER CONTROL REQUIREMENTS.

7. REMOVE TWO (2) 120V ELECTRIC VEHICLE CHARGING STATIONS, INCLUDING ALL

ASSOCIATED CONDUITS, CONDUCTORS AND WIRING BACK TO THE POWER

SOURCE.

8. REFER TO SHEET ED109, DETAIL C1. REFER TO ED101 KEYED NOTES FOR SPECIFIC

REQUIREMENTS.

GENERAL NOTES

GENERAL NOTES- DEMOLITION

N

SCALE: 1'' = 40'-0''

PLAN OVERVIEWF4

1. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRUITS.

EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED

EQUIPMENT GROUNDING CONDUCTOR.

2. MULTI-GANG BACK BOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY

AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

3. REMOVE PA SYSTEM IN CORRIDOR AND REMOVE BACK TO ELECTRICAL SOURCE.

ATS E69DB1

69DB1

FIBER CONDUIT

JBOX 80-3

JBOX 80-2

JBOX 80-1

T-69/78-12KV-208V

DISC. B75

DISC. B69

JBOX 69

ATS-E75P11 E78PS1

E78DS1

78DS1

JBOX 80

E80DB1

HVAC

BLDG 68

EXTERNAL

JBOX 68

DISCONNECT

ATS-E68PB1

PULLBOX 74

T-74-12KV-208V

JBOX 74

JBOX 74-1

JBOX 74-2

JBOX 74-3

74D14

T1P11

T2P11

77P11

77P11-1

ATS-E74P19

JBOX

PANEL E74D11

JBOX

DISCONNECT

ATS-E74P19

1. FOR EXISTING EQUIPMENT, SUCH AS LIGHTNING FIXTURES, WIRING DEVICES,

CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP

CONDUITS AT THE AREA OF WORK, DISCONNECTING WIRING AT THE

OVERCURRENT PROTECTIVE DEVICE AND REMOVE WIRING COMPLETELY FROM

THE ABANDONED CONDUITS.

2. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT

PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.

3. MAINTAIN AND RESTORE IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS

PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

4. ALL CONDUITS, ELECTRICAL CIRCUITS AND TELECOMMUNICATIONS CIRCUITS ARE

TO BE REMOVED FROM THE CORRIDOR WETHER IN USE OR NOT.

5. THE IDENTIFIED CONDUITS AND CIRCUITS ATTACHED TO OR UNDER THE

CORRIDOR ARE SHOWN ON PLANS FOR REPLACEMENT TO UNDERGROUND

CONDUITS AND CIRCUITS. THERE COULD BE ADDITIONAL CIRCUITS NOT IDENTIFIED

WITHIN THE PLANS. CONTRACTOR SHALL MAKE A COMPLETE DETERMINATION OF

CIRCUITS THAT ARE IN USE AND SHALL BE REQUIRE TO CONVERT TO BELOW

GRADE, SHALL

6. MERCURY IS COMMONLY FOUND IN FLUORESCENT LIGHT TUBES AS WELL AS IN

ORDER WALL MOUNTED THERMOSTATS. NO SAMPLING WAS CONDUCTED FOR

MERCURY DURING THIS INVESTIGATION; HOWEVER, THESE MATERIALS SHOULD BE

ASSUMED TO CONTAIN MERCURY AND TREATED AS SUCH DURING THE

DEMOLITION.RENOVATION ACTIVITIES.

7. POLYCHLORINATED BIPHENYL (PCBs) ARE COMMONLY FOUND IN FLUORESCENT

LIGHT BALLASTS AS WELL AS CAULKING AND GLAZING'S IN CONSTRUCTION. NO

SAMPLING WAS CONDUCTED FOR PCBs DURING THIS INVESTIGATION; HOWEVER, THESE MATERIALS SHOULD BE ASSUMED TO CONTAIN PCBs AND TREATED AS

SUCH DURING THE DEMOLITION ACTIVITIES. ALL LIGHT BALLASTS OBSERVED BY

TRC DURING THIS SURVEY WERE NEWER AND HAD A ''NO-PCB'' LABEL AND THUS

WOULD NOT NEED TO BE DISPOSED OF AS PCB CONTAINING WASTE. HOWEVER,

ANY LIGHT BALLASTS THAT DO NOT HAVE THE ''NO-PCB'' LABEL THAT ARE

ENCOUNTERED DURING THE DEMOLITION ACTIVITIES SHOULD BE ASSUMED TO

CONTAIN PCBs.

E74D11

ATS-E74D11

JBOX 75

GENERATOR 74

GENERATOR 74

PULLBOX

DISCONNECT

AutoCAD SHX Text

BUILDING 74

AutoCAD SHX Text

BUILDING 68

AutoCAD SHX Text

BUILDING 69

AutoCAD SHX Text

BUILDING 75

AutoCAD SHX Text

BUILDING 78

AutoCAD SHX Text

BUILDING 77

AutoCAD SHX Text

BUILDING T2

AutoCAD SHX Text

BUILDING T1

AutoCAD SHX Text

ROSE BUSH BEDS

AutoCAD SHX Text

L.S.AREA

scott Image scott Pen

TN

scott Pen scott Pen scott Pen scott Pen

E

H

H

H

H

H

H

H

H

H

H

H

AGC

FOC

FOC

AGCAGC

FOC

BGC

BGC

BGC

AGC

FOC

Project Number

Building Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

N/A

U. S. Department of Veterans Affairs

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

56 Louis Prima Drive, Suite B, Covington, LA 70433 504.684.4408; Sean Fitzpatrick

JONATHAN M.WAINWRIGHT

MEMORIAL VA MC - DEMOLISH AND

REGRADE CONNECTING CORRIDOR

Walla Walla, Washington

687-24-101

N/A Project Manager

04/28/2026Revisions: Date:

Connor Henderson General Engineer Facilities Management Service (FMS) Phone: (509) 759-2923 Email: Connor.Henderson@va.gov

ZTNT

JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980

Sheet Number

ELECTRICAL DEMOLITION PLAN

(BLDG 74,68,80)

ED104

KEYED NOTES

1. ALL ELECTRICAL OUTLETS, SWITCHES, LIGHTS, WIRING WITHIN THE CORRIDOR ARE

TO BE COMPLETELY DEMOLISHED BACK TO SOURCE ELECTRICAL PANEL.

2. PANEL 74D14 TO PULLBOX 74 CONNECTED TO CORRIDOR, TO BE DEMOLISHED AND

CONVERTED TO UNDERGROUND CONDUIT, EXISTING PANEL ATTACHED TO

CORRIDOR TO BE SUPPORTED PRIOR TO DEMOLISHING CORRIDOR.

3. HEAT PUMP CONDUIT TO BE REMOVED AND INSTALLED UNDERGROUND.

4. REMOVE TWO (2) 120V ELECTRIC VEHICLE CHARGING STATIONS, INCLUDING ALL

ASSOCIATED CONDUITS, CONDUCTORS AND WIRING BACK TO THE POWER

SOURCE.

GENERAL NOTES

GENERAL NOTES- DEMOLITION

1. FOR EXISTING EQUIPMENT, SUCH AS LIGHTNING FIXTURES, WIRING DEVICES,

CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP

CONDUITS AT THE AREA OF WORK, DISCONNECTING WIRING AT THE

OVERCURRENT PROTECTIVE DEVICE AND REMOVE WIRING COMPLETELY FROM

THE ABANDONED CONDUITS. CONTRACTOR TO FIELD VERIFY THESE ARE NOT HOT

CONDUCTORS OR ID'ING SOURCE/LOAD BEFORE DISCONNECTING.

2. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT

PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.

N

SCALE: 1'' = 20'-0''

PLAN VIEW BLDG 74,68F4

1. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRUITS.

EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED

EQUIPMENT GROUNDING CONDUCTOR.

2. MULTI-GANG BACK BOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY

AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

3. REMOVE PA SYSTEM IN CORRIDOR AND REMOVE BACK TO ELECTRICAL SOURCE.

CONDUIT SCHEDULE

CONDUIT

RUN SOURCE LOAD DETAILS

JBOX 80 JBOX 74 ED107, C1

JBOX 74 ATS-E74D11 ED109, F1

JBOX 74-1 JBOX 74-3 ED109, C1

JBOX 74-1 JBOX 74-3 ED109, C1

JBOX 74-2 DISCONNECT ATS-74P19 ED109, C1

JBOX 74-2 JBOX 74-2 ED109, C5

JBOX 74-2 E74D15 ED109, C1

JBOX 74-2 UNKNOWN ED109, C1

JBOX 74-2 ED7415 ED109, C1

JBOX 74-2 E74D15 ED109, C1

BUILDING 68 JBOX 80-3 ED109, C6

JBOX 74-3 BUILDING 68 ED108, F1

JBOX 74-3 BUILDING 80 ED108, F1

JBOX 80-3 BUILDING 68 ED110, C4

BUILDING 68 CONDUIT

ENTRANCE

TRANSITION POINT TO

BUILDING 68 ED107, F5

JBOX 80-1 ATS-E68PB1 ED110, C1

T-74-12KV-208 PULLBOX 74 ED110, F1

PULLBOX 74 E74D14 ED110, F1

C4

ED110

F5

ED107

C7

ED110

C4

ED110

C1

ED109

F1

ED108

F1

ED109

C1

ED109

A

E

H

I

J

K

L

M

X

CC

DD

FF

GG

DD

X

X

CC

FF

GG

U

V

A

E

I

H W

J

K

QP

M

L

JBOX 74-2

JBOX 74-1

T-74-12KV-208

PULLBOX 74

74D14

JBOX 68

BLDG 68

EXTERNAL

HVAC

ATS-E74P19

JBOX

PANEL E74D11

JBOX 74-3

DISCONNECT

ATS-E74P19

E74D11

ATS-E74D11

JBOX 74

68PB1

68PB2

68PB3

ATS-E68PB1

68DB1

DISCONNECT

ATS-E68PB1

E68PB1

T

Q

P

V

U

A

V

V

DD

U

X

U

DD

GENERATOR 74

GENERATOR 74

PULLBOX

DISCONNECT

AutoCAD SHX Text

BUILDING 74

AutoCAD SHX Text

BUILDING 68

scott Image scott Pen

TN

scott Pen scott Pen scott Pen scott

H

H

H

H

H H

H H

AGC

AGC

AGC BGC

AGC

AG

C

AGC

AGC

AGC

FOC

FO

C

AGC

FO

CFO

C

Project Number

Building Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

N/A

U. S. Department of Veterans Affairs

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

56 Louis Prima Drive, Suite B, Covington, LA 70433 504.684.4408; Sean Fitzpatrick

JONATHAN M.WAINWRIGHT

MEMORIAL VA MC - DEMOLISH AND

REGRADE CONNECTING CORRIDOR

Walla Walla, Washington

687-24-101

N/A Project Manager

04/28/2026Revisions: Date:

Connor Henderson General Engineer Facilities Management Service (FMS) Phone: (509) 759-2923 Email: Connor.Henderson@va.gov

ZTNT

JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980

Sheet Number

ELECTRICAL DEMOLITION PLAN

(BLDG 80,69,75)

ED105

KEYED NOTES

1. ALL ELECTRICAL OUTLETS, SWITCHES, LIGHTS, WIRING WITHIN THE CORRIDOR ARE

TO BE COMPLETELY DEMOLISHED BACK TO THE SOURCE ELECTRICAL PANEL

2. DEMOLISH EXISTING EXTERIOR DISCONNECT, RETAIN CONDUITS AND

CONDUCTORS CONNECTED TO THIS DEVICE.

GENERAL NOTES

GENERAL NOTES- DEMOLITION

1. FOR EXISTING EQUIPMENT, SUCH AS LIGHTNING FIXTURES, WIRING DEVICES,

CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP

CONDUITS AT THE AREA OF WORK, DISCONNECTING WIRING AT THE

OVERCURRENT PROTECTIVE DEVICE AND REMOVE WIRING COMPLETELY FROM

THE ABANDONED CONDUITS CONTRACTOR TO FIELD VERIFY THESE ARE NOT HOT

CONDUCTORS OR ID'ING SOURCE/LOAD BEFORE DISCONNECTING.

2. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT

PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.

3. MAINTAIN AND RESTORE IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS

PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

4. ALL CONDUITS, ELECTRICAL CIRCUITS AND TELECOMMUNICATIONS CIRCUITS ARE

TO BE REMOVED FROM THE CORRIDOR WETHER IN USE OR NOT.

5. THE IDENTIFIED CONDUITS AND CIRCUITS ATTACHED TO OR UNDER THE

CORRIDOR ARE SHOWN ON PLANS FOR REPLACEMENT TO UNDERGROUND

CONDUITS AND CIRCUITS. THERE COULD BE ADDITIONAL CIRCUITS NOT IDENTIFIED

WITHIN THE PLANS. CONTRACTOR SHALL MAKE A COMPLETE DETERMINATION OF

CIRCUITS THAT ARE IN USE AND WILL BE REQUIRE TO CONVERT TO BELOW GRADE.

N

SCALE: 1'' = 20'-0''

PLAN VIEW BLDG 80,69,75F4

1. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRUITS.

EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED

EQUIPMENT GROUNDING CONDUCTOR.

2. MULTI-GANG BACK BOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY

AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

3. REMOVE PA SYSTEM IN CORRIDOR AND REMOVE BACK TO ELECTRICAL SOURCE.

4. DEMOLISH SECURITY CAMERA, CONDUIT, AND ALL WIRING BACK TO SOURCE. VA

TO RETAIN OWNERSHIP OF CAMERA.

5. EXTERNAL CONDUIT NEEDS TO BE TRACED BACK TO SOURCE AND CONTRACTOR

TO DETERMINE IF CIRCUIT NEEDS TO BE RELOCATED OR DEMOLISHED.

CONDUIT SCHEDULE

CONDUIT

RUN SOURCE LOAD DETAILS

PANEL E80DB1 JBOX 74 ED107, C1

PANEL E80DB1 JBOX 80-1 ED107, C6

PANEL E80DB1 JBOX 80-2 ED107, C1

JBOX 80-2 ATS-E69DB1 ED107, C6

PANEL E80DB1 JBOX 80-2 ED107, C6

DISCONNECT 69 JBOX 69 ED108, D5, D8

JBOX 69 PANEL 69DB1 ED108, D1

JBOX 80-2 JBOX 75 ED109, C8

BUILDING 80 JBOX 80-3 ED107, C6

JBOX 75 ATS-E75-P11 ED109, C8

BUILDING 68 JBOX 80-3 ED107, C6

JBOX 80-1 DISCONNECT

ATS-68PB1 ED107, C6

C

D

E

F

G

P

T

C8

ED109

D8

ED108

D5

ED108

F1

ED108

D1

ED108

C1

ED107

C6

ED107

D

P

C

E80DB1

JBOX 80-1

100 FUSE

JBOX 80-2

JBOX 80-3

FIBER CONDUIT

69DB1

ATS-E69DB1

T

G

F

JBOX 69

ATS-E75P11

B

JBOX 80

D

DISCONNECT

BUILDING 69

G

V X

A

DD

DD

A

A

B

K

R

JBOX 75

K

K

K

R

ADDENDMENT 001 08/12/20261

AutoCAD SHX Text

BUILDING 69

AutoCAD SHX Text

BUILDING 80

AutoCAD SHX Text

BUILDING 75

scott Image scott Pen

TN

scott Pen scott Pen scott Pen scott

Project Number

Building Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

N/A

U. S. Department of Veterans Affairs

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

56 Louis Prima Drive, Suite B, Covington, LA 70433 504.684.4408; Sean Fitzpatrick

JONATHAN M.WAINWRIGHT

MEMORIAL VA MC - DEMOLISH AND

REGRADE CONNECTING CORRIDOR

Walla Walla, Washington

687-24-101

N/A Project Manager

04/28/2026Revisions: Date:

Connor Henderson General Engineer Facilities Management Service (FMS) Phone: (509) 759-2923 Email: Connor.Henderson@va.gov

ZTNT

JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980

Sheet Number

ELECTRICAL DEMOLITION PLAN

(BLDG 80,69,75)

ED106

KEYED NOTES

1. ALL ELECTRICAL OUTLETS, SWITCHES, LIGHTS, WIRING WITHIN THE CORRIDOR ARE

TO BE COMPLETELY DEMOLISHED BACK TO THE SOURCE ELECTRICAL PANEL.

2. THE ROUTING OF ALL CONDUITS BENEATH THE CORRIDOR IS PRESUMED, AS

THERE WAS NO FEASIBLE METHOD TO VERIFY THE EXACT PATHS WITHOUT

DEMOLITION. DUE TO LIMITED ACCESS AND LACK VISIBLE INDICATORS, THE

CONDUIT RUNS COULD NOT BE CONFIRMED THROUGH NON-INVASIVE MEANS,

CONTRACTOR TO CONFIRM.

3. RETAIN UNDERGROUND CONDUITS FROM BUILDING 78 TO EXISTING JUNCTION BOX

UNDER THE CORRIDOR.

4. DEMOLISH EXISTING JUNCTION BOX AND CONDUITS ATTACHED TO THE CORRIDOR.

DEMOLISH ALL CONDUCTORS FROM SOURCE BUILDING 78 TO ALL LOAD SIDE

PANELS. RETAIN ALL CONDUITS THAT ARE INTERIOR OF THE BUILDINGS FOR

REUSE.

GENERAL NOTES

1. LIGHTING FIXTURES WITH MORE THAN TWO LAMPS SHALL HAVE OUTER LAMPS

CONTROLLED WITH ONE SWITCH AND INNER LAMP(S) CONTROLLED BY A SECOND

SWITCH.

2. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRUITS.

EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED

EQUIPMENT GROUNDING CONDUCTOR.

3. MULTI-GANG BACK BOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY

AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

4. REMOVE PA SYSTEM IN CORRIDOR AND REMOVE BACK TO ELECTRICAL SOURCE.

GENERAL NOTES- DEMOLITION

1. FOR EXISTING EQUIPMENT, SUCH AS LIGHTNING FIXTURES, WIRING DEVICES,

CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP

CONDUITS AT THE AREA OF WORK, DISCONNECTING WIRING AT THE

OVERCURRENT PROTECTIVE DEVICE AND REMOVE WIRING COMPLETELY FROM

THE ABANDONED CONDUITS CONTRACTOR TO FIELD VERIFY THESE ARE NOT HOT

CONDUCTORS OR ID'ING SOURCE/LOAD BEFORE DISCONNECTING.

2. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT

PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.

3. MAINTAIN AND RESTORE IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS

PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

4. ALL CONDUITS, ELECTRICAL CIRCUITS AND TELECOMMUNICATIONS CIRCUITS ARE

TO BE REMOVED FROM THE CORRIDOR WETHER IN USE OR NOT.

5. THE IDENTIFIED CONDUITS AND CIRCUITS ATTACHED TO OR UNDER THE

CORRIDOR ARE SHOWN ON PLANS FOR REPLACEMENT TO UNDERGROUND

CONDUITS AND CIRCUITS. THERE COULD BE ADDITIONAL CIRCUITS NOT IDENTIFIED

WITHIN THE PLANS. CONTRACTOR SHALL MAKE A COMPLETE DETERMINATION OF

CIRCUITS THAT ARE IN USE AND WILL BE REQUIRE TO CONVERT TO BELOW GRADE.

N

SCALE: 1'' = 20'-0''

PLAN VIEW BLDG 75,T2,T1,77F4

77P11-2

77P11-1 T1P11

T2P11

78DS1

E78DS1

E78PS1

ADDENDMENT 001 08/12/20261

AutoCAD SHX Text

BUILDING 75

AutoCAD SHX Text

BUILDING 78

AutoCAD SHX Text

BUILDING 77

AutoCAD SHX Text

BUILDING T2

AutoCAD SHX Text

BUILDING T1

AutoCAD SHX Text

ROSE BUSH BEDS

scott Image scott Pen

TN

scott Pen scott Pen scott Pen scott

H

H H

H

Project Number

Building Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

N/A

U. S. Department of Veterans Affairs

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

56 Louis Prima Drive, Suite B, Covington, LA 70433 504.684.4408; Sean Fitzpatrick

JONATHAN M.WAINWRIGHT

MEMORIAL VA MC - DEMOLISH AND

REGRADE CONNECTING CORRIDOR

Walla Walla, Washington

687-24-101

N/A Project Manager

04/28/2026Revisions: Date:

Connor Henderson General Engineer Facilities Management Service (FMS) Phone: (509) 759-2923 Email: Connor.Henderson@va.gov

ZTNT

JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980

Sheet Number

LIGHTING INSTALLATION PLAN

BUILDING 75,78,77,T2,T1

EL102

N

KEYED NOTES

1. THE LIGHTING CONDUIT SYSTEM UTILIZES 1 1/2" SCHEDULE 80 CONDUIT,

CONTAINING #8 AWG BARE COPPER CONDUCTORS. ADDITIONALLY, 20A CIRCUIT

BREAKERS ARE INSTALLED TO ENSURE PROPER ELECTRICAL PROTECTION AND

SYSTEM FUNCTIONALITY.

2. EACH CONDUIT INSTALLATION MUST INCLUDE AN ADDITIONAL SPARE CONDUIT.

THIS ENSURES THE AVAILABILITY OF EXTRA CAPACITY FOR FUTURE NEEDS.

3. THE CONTRACTOR SHALL INSTALL LIGHTING DIRECTED TOWARD THE SIDEWALK

TO IMPROVE ILLUMINATION LEVELS, ENHANCING PEDESTRIAN VISIBILITY AND

SAFETY.

4. BRING CONDUCTORS AND CONDUIT INTO EXITING LIGHTING PULL BOX AND

TERMINATED CONDUCTORS INTO EXISTING LIGHTING CIRCUITRY, RAN IN SERIES.

5. SECURELY AFFIX CONDUIT TO A NEWLY INSTALLED LIGHT POLE ATTACHING TO

LIGHTING MOUNTING EQUIPMENT WHEN INSTALLED.

6. INSTALL LIGHT ONTO POLE WITH SURVEILLANCE CAMERAS.

SCALE: 1'' = 20'-0''

PLAN VIEW BLDG 75,78,77,T2,T1F4

LIGHTING DETAILS

MANUFACTURER CATALOG NUMBER DESCIRPTION

COOPER RSXF3 PE-DBLXD WALL MOUNTED, .56AMPS, 95 WATTS

SCALE: NTS

YOKE (YK) MOUNTING DETAILF5

GENERAL NOTES

1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH

THE LATEST EDITION OF THE NEC, NFPA, AND OSHA. THE CONTRACTOR SHALL

PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL EQUIPMENT AND

CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM TO OTHER

DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A COMPLETE,

FUNCTIONAL ELECTRICAL SYSTEM.

2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN SCH

80. CONDUITS FOR ABOVEGROUND AND SCH 40. FOR UNDERGROUND RUNS.

PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM SCH 40. TO SCH 80. CONDUIT

(RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE GROUND

SURFACE.

3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)

GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR

SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.

4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,

ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED

ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY

MATERIALS NEEDED TO FULFILL THE PROJECT REQUIREMENTS SHALL BE

PROVIDED AT NO ADDITIONAL COST.

5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES

COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,

EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO

INSTALLATION.

6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE

APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE

INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,

MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO

ADDITIONAL COST.

7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING

JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL

ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING

CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.

8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS

INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN

DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS

EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS

PRIOR TO THE START OF THE AFFECTED WORK.

9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED

AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS.

10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.

11. ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE DRAWINGS, BUT ARE

SHOWN OR DESCRIBED IN THE OTHER TRADES, AND ALL ITEMS NECESSARY TO

MAKE THE ELECTRICAL SYSTEM COMPLETE AND OPERATIONAL, SHALL FORM A

PART OF THE WORK.

12. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS.

EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED

EQUIPMENT GROUNDING CONDUCTOR.

13. UNDERGROUND FACILITIES AND CABLE LOCATIONS ARE ESTIMATED.

UNDERGROUND LOCATES OF EXISTING UNDERGROUND FACILITIES IS REQUIRED

TO CONFIRM ROUTE.

ADDENDMENT 001 08/12/20261

AutoCAD SHX Text T

AutoCAD SHX Text

BUILDING 69

AutoCAD SHX Text

BUILDING 80

AutoCAD SHX Text

BUILDING 75

AutoCAD SHX Text

BUILDING 76

AutoCAD SHX Text

GRAVEL

AutoCAD SHX Text

ROSE BUSH BEDS

AutoCAD SHX Text

L.S.AREA

AutoCAD SHX Text

L.S.AREA

AutoCAD SHX Text

L.S.AREA

AutoCAD SHX Text e scott Image scott Pen

TN

scott Pen scott Pen scott Pen scott

H

H

H

H

H

H

H

H

H

H

H

H

H H

H H

Project Number

Building Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

N/A

U. S. Department of Veterans Affairs

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

56 Louis Prima Drive, Suite B, Covington, LA 70433 504.684.4408; Sean Fitzpatrick

JONATHAN M.WAINWRIGHT

MEMORIAL VA MC - DEMOLISH AND

REGRADE CONNECTING CORRIDOR

Walla Walla, Washington

687-24-101

N/A Project Manager

04/28/2026Revisions: Date:

Connor Henderson General Engineer Facilities Management Service (FMS) Phone: (509) 759-2923 Email: Connor.Henderson@va.gov

ZTNT

JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980

Sheet Number

ELECTRICAL INSTALLATION PLAN

BUILDING 74,68

EP102

KEYED NOTES

1. RESTRICTED ACCESS ROOM. IF ACCESS IS REQUIRED, CONTRACTOR TO

COORDINATE WITH MAINTENANCE STAFF 48 HOURS PRIOR TO NEEDING ACCESS

FOR PROPER CONTROL REQUIREMENTS.

2. CARE SHALL BE TAKEN WHEN DIGGING. THEY SHALL BE HAND DUG WITHIN 18" OF

ANY KNOW BURIED UTILITIES.

3. PANEL 74D11 IS CURRENTLY ATTACHED TO THE ELEVATED WALKWAY. INSTALL

PHYSICAL SUPPORTS TO MOUNT THE EXISTING PANEL SUCH THAT THE

PANELBOARD CAN BE SUPPORTED WHEN THE CORRIDOR IS REMOVED. ALL

EXISTING LOAD CIRCUITS FROM THIS PANEL CAN REMAIN. SOURCE CONDUCTOR

TO BE REMOVED AS SHOWN AND NEW CONDUIT AND CONDUCTOR INSTALLED.

4. UNABLE TO IDENTIFY THE ORIGINATING SOURCE OF THE EXISTING HEAT PUMP

DISCONNET. SOURCE THE NEW HEATER PUMP FROM THE SAME LOCATION AS THE

EXISTING.

5. THE IRRIGATION CONTROLLER IS CONNECTED TO THE DISCONNECT, WHICH IS FED

BY CONDUIT RUN NO. 26 SUPPLIED FROM PANEL 68PB4.

6. INSTALL NEMA 3R CABINET 36'' X 36'' X 12'' LABELED ''GEN 74-JUNCTION-E74'' FOR

TERMINATION CABINET OF EMERGENCY SOURCE CONDUCTORS FROM

GENERATOR 74. INSULATED AND CABINET MOUNTED TERMINATION LUGGED

BUSBAR TO BE INSTALLED FOR EACH PHASE, NEUTRAL AND GROUND

CONDUCTORS. INTERCONNECT ALL GROUNDING CONDUCTORS AND BONDING

ONTO APPROPRIATELY RATED BONDING BUSBAR MEETING NATIONAL ELECTRICAL

SAFETY CODE REQUIREMENTS. AS SHOWN ON SHEET EP101.

7. CAREFULLY EXPOSE THE EXISTING (2) SETS OF 2 1/2'' CONDUITS NEAR

INSTALLATION LOCATION OF JUNCTION ''GEN 74 - JUNCTION 74'' FOR INSTALLATION.

INSTALL NEW ELBOW AND CONDUIT BRINGING EXISTING (2) 2 1/2'' CONDUIT AND (2)

SET OF (4) 3/0 AWG AND (1) #3 AWG GROUND INTO NEW JUNCTION. TERMINATE

SOURCE CONDUCTORS FROM GENERATOR AS PER KEYED NOTE 6. INSTALL

INDIVIDUAL SETS OF 500 MCM COPPER TO ATS - E74P19 AND ATS - E74D11. REFER

TO EP101 FOR DETAILS.

8. CONTRACTOR TO INSTALL NEW PANEL 74D14 MATCHING THE EXISTING PANEL

74D14 SIZE AND CAPACITY. CONTRACTOR TO RELOCATE ALL EXISTING CIRCUITS

WITHIN EXISTING PANEL INTO NEW PANEL. NO SPLICING OF EXISTING

CONDUCTORS IS TO BE ALLOWED. IF EXISTING CONDUCTORS DO NOT REACH NEW

PANEL LOCATION, NEW CONDUCTOR SHALL BE RUN FROM NEW PANEL LOCATION

TO THE EXISTING LOAD.

GENERAL NOTES

1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH

THE LATEST EDITION OF THE NEC, NFPA, AND OSHA. THE CONTRACTOR SHALL

PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL EQUIPMENT AND

CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM TO OTHER

DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A COMPLETE,

FUNCTIONAL ELECTRICAL SYSTEM.

2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN SCH

80. CONDUITS FOR ABOVEGROUND AND SCH 40. FOR UNDERGROUND RUNS.

PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM SCH 40. TO SCH 80. CONDUIT

(RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE GROUND

SURFACE.

3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)

GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR

SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.

4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,

ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED

ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY

MATERIALS NEEDED TO FULFILL THE PROJECT REQUIREMENTS SHALL BE

PROVIDED AT NO ADDITIONAL COST.

5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES

COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,

EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO

INSTALLATION.

6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE

APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE

INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,

MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO

ADDITIONAL COST.

7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING

JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL

ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING

CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.

8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS

INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN

DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS

EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS

PRIOR TO THE START OF THE AFFECTED WORK.

9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED

AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS.

10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.

11. ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE DRAWINGS, BUT ARE

SHOWN OR DESCRIBED IN THE OTHER TRADES, AND ALL ITEMS NECESSARY TO

MAKE THE ELECTRICAL SYSTEM COMPLETE AND OPERATIONAL, SHALL FORM A

PART OF THE WORK.

12. UNDERGROUND FACILITIES AND CABLE LOCATIONS ARE ESTIMATED.

UNDERGROUND LOCATES OF EXISTING UNDERGROUND FACILITIES IS REQUIRED

TO CONFIRM ROUTE.

13. ALL HEXAGON KEYED NOTES WITH LETTERS ARE REFERENCED FROM SCHEDULES

IN SHEET EP106.

14. CONTRACTOR SHALL INSTALL EMERGENCY LIGHTING WITH BATTERY BACKUP IN

BUILDING 68 PROVIDE APPROXIMATELY 40 LIGHTS PER FLOOR.

15. CONTRACTOR SHALL INSTALL EMERGENCY BATTERY BACKUP LOWERING SYSTEM

FOR THE ELEVATOR IN BUILDING 68.

N

SCALE: 1'' = 20'-0''

PLAN VIEW BLDG 74,68,80F4

D

D

T

GENERATOR 74

T-74-12KV-208

74D14

ATS-E74P19

JBOX, EXISTING

PANEL E74D11

JBOX 74-3, EXISTING

DISCONNECT

ATS-E74P19

E74D11

ATS-E74D11

GENERATOR 74

PULLBOX, EXISTING

DISCONNECT

N

JBOX 74-GEN

AutoCAD SHX Text

BUILDING 74

AutoCAD SHX Text

BUILDING 68

AutoCAD SHX Text

BUILDING 69

AutoCAD SHX Text

AutoCAD SHX Text scott Image scott Pen

TN

scott Pen scott Pen scott Pen scott

Project Number

Building Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

N/A

U. S. Department of Veterans Affairs

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

56 Louis Prima Drive, Suite B, Covington, LA 70433 504.684.4408; Sean Fitzpatrick

JONATHAN M.WAINWRIGHT

MEMORIAL VA MC - DEMOLISH AND

REGRADE CONNECTING CORRIDOR

Walla Walla, Washington

687-24-101

N/A Project Manager

04/28/2026Revisions: Date:

Connor Henderson General Engineer Facilities Management Service (FMS) Phone: (509) 759-2923 Email: Connor.Henderson@va.gov

ZTNT

JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980

Sheet Number

ELECTRICAL INSTALLATION PLAN

BUILDING 80,69,75

EP103

GENERAL NOTES

1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH

THE LATEST EDITION OF THE NEC, NFPA, AND OSHA. THE CONTRACTOR SHALL

PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL EQUIPMENT AND

CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM TO OTHER

DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A COMPLETE,

FUNCTIONAL ELECTRICAL SYSTEM.

2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN SCH

80. CONDUITS FOR ABOVEGROUND AND SCH 40. FOR UNDERGROUND RUNS.

PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM SCH 40. TO SCH 80. CONDUIT

(RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE GROUND

SURFACE.

3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)

GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR

SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.

4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,

ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED

ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY

MATERIALS NEEDED TO FULFILL THE PROJECT REQUIREMENTS SHALL BE

PROVIDED AT NO ADDITIONAL COST.

5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES

COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,

EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO

INSTALLATION.

6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE

APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE

INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,

MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO

ADDITIONAL COST.

7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING

JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL

ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING

CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.

8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS

INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN

DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS

EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS

PRIOR TO THE START OF THE AFFECTED WORK.

9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED

AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS.

10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.

11. ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE DRAWINGS, BUT ARE

SHOWN OR DESCRIBED IN THE OTHER TRADES, AND ALL ITEMS NECESSARY TO

MAKE THE ELECTRICAL SYSTEM COMPLETE AND OPERATIONAL, SHALL FORM A

PART OF THE WORK.

12. UNDERGROUND FACILITIES AND CABLE LOCATIONS ARE ESTIMATED.

UNDERGROUND LOCATES OF EXISTING UNDERGROUND FACILITIES IS REQUIRED

TO CONFIRM ROUTE.

13. ALL HEXAGON KEYED NOTES WITH LETTERS ARE REFERENCED FROM SCHEDULES

IN SHEET EP106.

14. CONTRACTOR SHALL INSTALL EMERGENCY LIGHTING WITH BATTERY BACKUP IN

BUILDING 69 PROVIDE APPROXIMATELY 40 LIGHTS PER FLOOR.

15. CONTRACTOR SHALL INSTALL EMERGENCY BATTERY BACKUP LOWERING SYSTEM

FOR THE ELEVATOR IN BUILDING 69.

N

KEYED NOTES

1. PULLBOX TO CONTAIN NORMAL SOURCE CIRCUIT TO BUILDING 69. CONTRACTOR

TO LABEL ALL CABLES AND PROVIDE ADEQUATE CIRCUIT SEPARATION AND

PHYSICAL SUPPORT WITHIN PULLBOX.

2. CARE SHALL BE TAKEN WHEN DIGGING. THEY SHALL BE HAND DUG WITHIN 18" OF

ANY KNOW BURIED UTILITIES.

3. PREFERRED CONDUIT ROUTE FOR CONSTRUCTION PARALLEL TO THE CORRIDOR

AND NOT UNDERNEATH. TRANSITION FROM 6" CONDUIT TO 4'' CONDUIT USING A

WALL MOUNTED 36'x36' CABINET, SEE DETAIL D2 ON SHEET EP602. INSTALL

GROUNDING CONDUCTORS AND GROUND RODS AS PER NEC.

4. EXISTING DISCONNECT TO BE REPLACED WITH SUITABLE RATED NEMA 3R PANEL.

REUSE EXISTING CONDUCTORS AND CONDUITS. INSTALL GROUNDING

CONDUCTORS AND GROUND RODS PER NEC.

SCALE: 1'' = 10'-0''

PLAN VIEW BLDG 80,69,75F4

B

A

69DB1

ATS-E69DB1

PULLBOX 69

DISC. B75

DISC. B69

T-69/75-12KV-208

PULLBOX 69-2

EXISTING 4" CONDUIT

ADDENDMENT 001 08/12/20261

1FIBER SWITCH

AutoCAD SHX Text

BUILDING 69

scott Image scott Pen

TN

scott Pen scott Pen scott Pen scott

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

N/A

U. S. Department of Veterans Affairs

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

56 Louis Prima Drive, Suite B, Covington, LA 70433 504.684.4408; Sean Fitzpatrick

JONATHAN M.WAINWRIGHT

MEMORIAL VA MC - DEMOLISH AND

REGRADE CONNECTING CORRIDOR

Walla Walla, Washington

687-24-101

N/A Project Manager

04/28/2026Revisions: Date:

Connor Henderson General Engineer Facilities Management Service (FMS) Phone: (509) 759-2923 Email: Connor.Henderson@va.gov

ZTNT

JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980

Sheet Number

ELECTRICAL INSTALLATION PLAN

(BLDG 80,69,75)

EP104

KEYED NOTES

1. INSTALL PULLBOX 78 AT THE END OF EXISTING CONDUITS FROM BUILDING 78.

2. INSTALL NEW CONDUIT FROM PULLBOX 78 TO EXISTING INTERIOR CONDUITS

WITHIN BUILDING 77. TRANSITION BETWEEN NEW CONDUITS AND EXISTING

CONDUITS WITH PROPER SIZED LB FITTINGS.

3. INSTALL NEW CONDUCTOR FROM SOURCE PANELS IN BUILDING 78 TO LOAD

PANELS IN BUILDING 77.

4. INSTALL NEW CONDUIT FROM PULLBOX 78 TO PANEL T2P11.

5. INSTALL NEW CONDUCTOR FROM SOURCE PANELS IN BUILDING 78 TO PANEL

T2P11.

6. INSTALL NEW CONDUCTOR AND CONDUIT BETWEEN T2P11 AND T1P11.

7. CONTRACTOR TO TIE EXISTING CONDUCTORS USING EXTERIOR J-BOX. B77 HAS

HAZARDOUS MOLD CONDITIONS ON THE INTERIOR.

GENERAL NOTES

1. LIGHTING FIXTURES WITH MORE THAN TWO LAMPS SHALL HAVE OUTER LAMPS

CONTROLLED WITH ONE SWITCH AND INNER LAMP(S) CONTROLLED BY A SECOND

SWITCH.

2. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRUITS.

EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED

EQUIPMENT GROUNDING CONDUCTOR.

3. MULTI-GANG BACK BOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY

AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

4. REMOVE PA SYSTEM IN CORRIDOR AND REMOVE BACK TO ELECTRICAL SOURCE.

5. REFER TO CONDUIT SCHEDULE FOR CONDUIT AND CONDUCTOR SIZE.

N

SCALE: 1'' = 20'-0''

PLAN VIEW BLDG 75,T2,T1,77F4

77P11-2

77P11-1 T1P11

T2P11

78DS1

E78DS1

E78PS1

1 PB78

ADDENDMENT 001 08/12/2026

2 3

J

E

H

AutoCAD SHX Text

BUILDING 75

AutoCAD SHX Text

BUILDING 78

AutoCAD SHX Text

BUILDING 77

AutoCAD SHX Text

BUILDING T2

AutoCAD SHX Text

BUILDING T1

AutoCAD SHX Text

ROSE BUSH BEDS

scott Image scott Pen

TN

scott Pen scott Pen scott Pen scott

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

N/A

U. S. Department of Veterans Affairs

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

56 Louis Prima Drive, Suite B, Covington, LA 70433 504.684.4408; Sean Fitzpatrick

JONATHAN M.WAINWRIGHT

MEMORIAL VA MC - DEMOLISH AND

REGRADE CONNECTING CORRIDOR

Walla Walla, Washington

687-24-101

N/A Project Manager

04/28/2026Revisions: Date:

Connor Henderson General Engineer Facilities Management Service (FMS) Phone: (509) 759-2923 Email: Connor.Henderson@va.gov

ZTNT

JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980

Sheet Number

CONDUIT SCHEDULE

EP105

GENERAL NOTES

1. EVERY INSTALLED CONDUIT SHOULD HAVE A SPARE CONDUITS.

2. CONDUITS ARE TO BE BROUGHT INTO PULL BOX AND SEALED AROUND PULLBOX,

EACH SPARE CONDUIT SHALL BE CAPPED WITH PULL STRING INSTALLED FROM

EACH END.

3. ALL CONDUITS SHALL BE TESTED AND CLEANED DURING THE CONSTRUCTION AND

INSPECTION PROCESS AS PER VA STANDARDS

ELECTRICAL CONDUCTOR CONDUIT & WIRING SCHEDULE (COPPER CONDUCTORS)

CONDUIT RUN SOURCE LOAD HOMERUN CONDUIT SIZE CONDUCTOR SIZE

(QTY) NEUTRAL SIZE GROUND SIZE

A DISC. B69 PB69 (2) 6'' (2) 500 MCM/PHASE 500 MCM (1)

B PB69 PB69-2 (2) 6'' (2) 500 MCM/PHASE 500 MCM (1)

D GEN 74-JUNCTION E-74 ATS E74D11 (1) 5'' (1) 500 MCM/PHASE (1) #2 AWG

E PB78 77P11-1 BUILDING 78 MATCH EXISTING INTERIOR CONDUIT SIZE (3) #4/0 AWG #4/0 AWG (1) #4/0 AWG

H PB78 T2P11 (1) 2'' (3) #3/0 AWG #3/0 AWG (1) #3/0 AWG

J T2P11 T1P11 (1) 1 1/2'' (2) #2 AWG #2 AWG (1) #2 AWG

N GEN 74-JUNCTION E-74 ATS-E74-P19 (1) 5'' (1) 500 MCM/PHASE (1) #2 AWG

T T-74-12KV-208 74D14 (1) 6'' (3) #3/0 AWG/PHASE #3/0 AWG (1)

FIBER OPTIC CONDUIT SCHEDULE

CONDUIT RUN TO FROM HOMERUN CONDUIT RUN

G BUILDING 74 BUILDING 68 1"

I PB74 BUILDING 68 1"

M PB74 E74D11 1"

AA CAMERA B68 CAMERA B69A 1''

BB CAMERA B69A CAMERA B69B 1''

CC CAMERA B69B CAMERA B75 1''

DD CAMERA B75 BUILDING 78 1''

SURVEILLANCE CONDUIT SCHEDULE

CONDUIT RUN SOURCE HOMERUN CONDUIT SIZE CONDUCTOR SIZE

S 78DS1 1'' 1''

U BUILDING 78 MEDIA CONTROL ROOM 1'' 1''

ADDENDMENT 001 08/12/20261

scott Image scott Pen

TN

scott Pen scott Pen scott Pen scott

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

N/A

U. S. Department of Veterans Affairs

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

56 Louis Prima Drive, Suite B, Covington, LA 70433 504.684.4408; Sean Fitzpatrick

JONATHAN M.WAINWRIGHT

MEMORIAL VA MC - DEMOLISH AND

REGRADE CONNECTING CORRIDOR

Walla Walla, Washington

687-24-101

N/A Project Manager

04/28/2026Revisions: Date:

Connor Henderson General Engineer Facilities Management Service (FMS) Phone: (509) 759-2923 Email: Connor.Henderson@va.gov

ZTNT

JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980

Sheet Number

EP602

JUNCTION BOX DETAILS

SCALE: NTS

JUNCTION BOX TERMINALD5

1. BURNDY FULLY INSULATED DISTRIBUTION BLOCK CATALOG NUMBER BIBD7506HD

SHOWN FOR EXAMPLE ONLY. CONTRACTOR CAN USE SUITABLE REPLACEMENT.

2. NEW 6" CONDUIT TO BE INSTALLED PARALLEL TO THE EXISTING CORRIDOR BUT

NOT UNDERNEATH, WHERE PRACTICAL, TO EASE IN CONSTRUCTION.

3. POSITION NEW JBOX INTO EXISTING 4'' CONDUIT WHERE CONDUIT PENETRATES

EXTERIOR WALL OF BUILDING 69. GROUND JBOX WITH GROUNDING CONDCUTOR

AND DRIVEN GROUND RODS AS PER SPECIFICATION.

GENERAL NOTES

1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH

THE LATEST EDITION OF THE NEC, NFPA, AND OSHA. THE CONTRACTOR SHALL

PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL EQUIPMENT AND

CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM TO OTHER

DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A COMPLETE,

FUNCTIONAL ELECTRICAL SYSTEM.

2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN SCH

80. CONDUITS FOR ABOVEGROUND AND SCH 40. FOR UNDERGROUND RUNS.

PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM SCH 40. TO SCH 80. CONDUIT

(RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE GROUND

SURFACE.

3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)

GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR

SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.

4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,

ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED

ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY

MATERIALS NEEDED TO FULFILL THE PROJECT REQUIREMENTS SHALL BE

PROVIDED AT NO ADDITIONAL COST.

5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES

COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,

EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO

INSTALLATION.

6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE

APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE

INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,

MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO

ADDITIONAL COST.

7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING

JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL

ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING

CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.

8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS

INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN

DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS

EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS

PRIOR TO THE START OF THE AFFECTED WORK.

9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED

AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS.

10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.

11. ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE DRAWINGS, BUT ARE

SHOWN OR DESCRIBED IN THE OTHER TRADES, AND ALL ITEMS NECESSARY TO

MAKE THE ELECTRICAL SYSTEM COMPLETE AND OPERATIONAL, SHALL FORM A

PART OF THE WORK.

12. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS.

EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED

EQUIPMENT GROUNDING CONDUCTOR.

13. UNDERGROUND FACILITIES AND CABLE LOCATIONS ARE ESTIMATED.

UNDERGROUND LOCATES OF EXISTING UNDERGROUND FACILITIES IS REQUIRED

TO CONFIRM ROUTE.

KEYED NOTES

SCALE: NTS

BUILDING 69 JUNCTION BOXD2

GRADE

36"x36"x12"

NEMA 3R CABINET

ADDENDMENT 001 08/12/20261

scott Image scott Pen

TN

scott Pen scott Pen scott Pen scott

H

H

H

H

H H

H H

EDUMEDIA

CONTROL ROOM

151 SF

Project Number

Building Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

N/A

U. S. Department of Veterans Affairs

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

56 Louis Prima Drive, Suite B, Covington, LA 70433 504.684.4408; Sean Fitzpatrick

JONATHAN M.WAINWRIGHT

MEMORIAL VA MC - DEMOLISH AND

REGRADE CONNECTING CORRIDOR

Walla Walla, Washington

687-24-101

N/A Project Manager

04/28/2026Revisions: Date:

Connor Henderson General Engineer Facilities Management Service (FMS) Phone: (509) 759-2923 Email: Connor.Henderson@va.gov

ZTNT

JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980

Sheet Number

CORRIDOR SURVEILLANCE

INSTALLATION PLAN

E-503

GENERAL NOTES

1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH

THE LATEST EDITION OF THE NEC, NFPA, AND OSHA. THE CONTRACTOR SHALL

PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL EQUIPMENT AND

CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM TO OTHER

DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A COMPLETE,

FUNCTIONAL ELECTRICAL SYSTEM.

2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN SCH

80. CONDUITS FOR ABOVEGROUND AND SCH 40. FOR UNDERGROUND RUNS.

PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM SCH 40. TO SCH 80. CONDUIT

(RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE GROUND

SURFACE.

3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)

GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR

SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.

4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,

ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED

ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY

MATERIALS NEEDED TO FULFILL THE PROJECT REQUIREMENTS SHALL BE

PROVIDED AT NO ADDITIONAL COST.

5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES

COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,

EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO

INSTALLATION.

6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE

APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE

INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,

MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO

ADDITIONAL COST.

7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING

JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL

ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING

CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.

8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS

INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN

DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS

EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS

PRIOR TO THE START OF THE AFFECTED WORK.

9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED

AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS.

10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.

11. ITEMS OMITTED FROM EITHER THE SPECIFICATIONS OR THE DRAWINGS, BUT ARE

SHOWN OR DESCRIBED IN THE OTHER TRADES, AND ALL ITEMS NECESSARY TO

MAKE THE ELECTRICAL SYSTEM COMPLETE AND OPERATIONAL, SHALL FORM A

PART OF THE WORK.

12. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS.

EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED

EQUIPMENT GROUNDING CONDUCTOR.

13. UNDERGROUND FACILITIES AND CABLE LOCATIONS ARE ESTIMATED.

UNDERGROUND LOCATES OF EXISTING UNDERGROUND FACILITIES IS REQUIRED

TO CONFIRM ROUTE.

N

SCALE: 1'' = 20'-0''

PLAN VIEW BLDG 69,75,78F4

KEYED NOTES

1. INSTALL 1'' CONDUIT FOR FIBER OPTIC WITH 1'' SPARE, AND SEPARATE 1'' CONDUIT

FOR ELECTRICAL WITH 1'' SPARE FOR FUTURE USE . REFER TO SHEET EP107

DETAIL 3 FOR TRENCH DETAIL.

2. POWER TO SURVEILLANCE CAMERAS COME FROM PANEL 78DS1. CONTRACTOR TO

INVESTIGATE ALTERNATIVE CIRCUIT LOCATIONS AND PROVIDE A SUBMITTAL FOR

THE ELECTRICAL CIRCUIT PLACEMENT IF BREAKER SPACE IS UNAVAILABLE IN THE

SHOWN PANELS.

3. INSTALL A MINIMUM 270 DEGREE MULTI SENSOR, NIGHT VISION CAMERA ON THE

NORTHEAST EXTERIOR CORNER OF BUILDING 68 AT THE ROOF'S EDGE. PROGRAM

THIS DEVICE WITH ANALYTICS TO DETECT RUNNING, FIGHTING AND GUNSHOTS.

4. INSTALL A 360 DEGREE MULTI SENSOR, NIGHT VISION CAMERA ON A NEW POLE AT

THE TOP OF THE STAIRS. INSTALL A PTZ CAMERA TO SUPPORT OBSERVATION OF

PARKING AREAS. PROGRAM THESE DEVICE WITH ANALYTICS TO DETECT RUNNING,

FIGHTING AND GUNSHOTS. REFER TO SHEET E-504 DETAIL 1,2,3,4 FOR

INSTALLATION DETAILS.

5. THE POLE SHALL HAVE (2) PROPERLY SIZED PULLBOXES. (1) ELECTRICAL AND (1)

FIBER OPTIC PULLBOX THAT SHALL HAVE THE APPROPRIATE CONDUITS WITHIN

EACH PULLBOX.

6. CONNECT SURVEILLANCE COMMUNICATION CABLING INTO EXISTING

SURVEILLANCE INFRASTRUCTURE.

CAMERA B69A

CAMERA B69B

CAMERA B75

CC

S

BB

1 3

DD

U

78DS1

E78PB1

ROOM

B102

E

D

C

F

ADDENDMENT 001 08/12/2026

G

AutoCAD SHX Text

BUILDING 69

AutoCAD SHX Text

BUILDING 75

AutoCAD SHX Text

BUILDING 78

AutoCAD SHX Text

BUILDING T2

AutoCAD SHX Text

BUILDING T1

AutoCAD SHX Text

ROSE BUSH BEDS

AutoCAD SHX Text e

AutoCAD SHX Text R scott Image scott Pen

TN

scott Pen scott Pen scott Pen scott

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

N/A

U. S. Department of Veterans Affairs

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

56 Louis Prima Drive, Suite B, Covington, LA 70433 504.684.4408; Sean Fitzpatrick

JONATHAN M.WAINWRIGHT

MEMORIAL VA MC - DEMOLISH AND

REGRADE CONNECTING CORRIDOR

Walla Walla, Washington

687-24-101

N/A Project Manager

04/28/2026Revisions: Date:

Connor Henderson General Engineer Facilities Management Service (FMS) Phone: (509) 759-2923 Email: Connor.Henderson@va.gov

ZTNT

JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980

Sheet Number

E-505

SURVEILLANCE SINGLE LINE

AND MATERIAL LIST

SURVEILLANCE CAMERA MATERIAL LIST

MANUFACTURER CATALOG NUMBER DESCRIPTION

AXIS COMMUNICATIONS AXIS P3738-PLE PANORAMIC CAMERA 4X4K MULTIDIRECTIONAL CAMERA, 360 IR

AXIS COMMUNICATIONS AXIS Q1805-LE BULLET BULLET CAMERA WITH 2mp LENS

AXIS COMMUNICATIONS AXIS POE MIDSPAN 8 PORT ETHERNET SWITCH WITH POE CAPABILITIES

LED LIGHTING SUPPLY MLLG-WL-POLE-25-4RD-DB-BZ-TN 25FT ABOVE GRADE ROUND STEEL POLE

CONTRACTOR SPECIFIED CONTRACTOR SPECIFIED FIBER OPTIC CABLE

CONTRACTOR SPECIFIED CONTRACTOR SPECIFIED FIBER OPTIC CABLE, ETHERNET TERMINATION

GENERAL NOTES

1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH

THE LATEST EDITION OF THE NEC, NFPA, AND OSHA. THE CONTRACTOR SHALL

PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL EQUIPMENT AND

CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM TO OTHER

DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A COMPLETE,

FUNCTIONAL ELECTRICAL SYSTEM.

2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN SCH

80. CONDUITS FOR ABOVEGROUND AND SCH 40. FOR UNDERGROUND RUNS.

PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM SCH 40. TO SCH 80. CONDUIT

(RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE GROUND

SURFACE.

3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)

GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR

SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.

4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,

ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED

ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY

MATERIALS NEEDED TO FULFILE THE PROJECT REQUIREMENTS SHALL BE

PROVIDED AT NO ADDITIONAL COST.

5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES.

COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,

EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO

INSTALLATION.

6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE

APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE

INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,

MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO

ADDITIONAL COST.

7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING

JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL

ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING

CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.

8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS

INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN

DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS

EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS

PRIOR TO THE START OF THE AFFECTED WORK.

9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED

AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATIONS.

10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.

SCALE: NTS

SURVEILLANCE CAMERA SINGLE LINE DIAGRAME1 SCALE: NTS

BUILDING 78 ROOM B102 MEDIA CONTROL ROOME5

KEYED NOTES

1. INSTALL ETHERNET SWITCH #1 IN BUILDING 78 ROOM B102 MEDIA CONTROL ROOM.

2. INSTALL CAT6 CABLE FROM ETHERNET SWITCH #1 INTO EXISTING SURVEILLANCE

CAMERA SYSTEM.

3. EACH CABINET REQUIRES A SEPARATELY DERIVED GROUNDING SYSTEM

COMPRISED OF (2) DRIVEN 8 FT COPPER CLAD 1/2'' GROUND RODS, 8 FT

HORIZONTALLY SPACED. INTERCONNECTED AND ATTACHED TO THE CABINET WITH

#6 CU SOLID CONDUCTOR.

This is the start of the file's text. The full file is on GovTribe.