20260821 Walla Walla_E-504.pdf
PDF 640 KB Posted
- Solicitation number
- 36C26026R0080
About this file
This is a bid document containing electrical design and construction specifications for a site lighting and surveillance system project at Jonathan M. Wainwright Memorial VA Medical Center in Walla Walla, Washington. The project involves demolishing and regrading a connecting corridor, with associated electrical infrastructure for surveillance cameras and site lighting.
The document specifies all electrical work must comply with the latest editions of the National Electrical Code (NEC), NFPA standards, and OSHA requirements. Conductors must be copper minimum #12 THW or THWN installed in Schedule 80 conduit for aboveground applications and Schedule 40 for underground runs. All branch circuits must include insulated green grounding conductors sized per NEC specifications. The project requires installation of surveillance poles (25-foot height), wall-mounted surveillance equipment, junction boxes (24" x 24" x 6" NEMA 3R), ethernet switches, duplex receptacles, and conduit systems for both fiber optic and power conductors. The contractor must coordinate work with civil contract documents to ensure routing paths and mounting arrangements avoid interference with other equipment and maintain required working clearances. All materials and equipment must be heavy-duty and UL-approved, installed per manufacturer specifications. The project manager is Connor Henderson (Facilities Management Service) at the VA Medical Center, with the design firm being JD Engineering, PC, located in Hamilton, Montana. The issue date for these bid documents is April 28, 2026.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FT
FT
Project Number
Building Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
N/A
U. S. Department of Veterans Affairs
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
56 Louis Prima Drive, Suite B, Covington, LA 70433 504.684.4408; Sean Fitzpatrick
JONATHAN M.WAINWRIGHT
MEMORIAL VA MC - DEMOLISH AND
REGRADE CONNECTING CORRIDOR
Walla Walla, Washington
687-24-101
N/A Project Manager
04/28/2026Revisions: Date:
Connor Henderson General Engineer Facilities Management Service (FMS) Phone: (509) 759-2923 Email: Connor.Henderson@va.gov
ZTNT
JD Engineering, PC 371 Zimmerman Lane Hamilton, MT 59840 Phone: (406) 218 - 9980
Sheet Number
E-504
SITE LIGHTING CAMERA'S
KEYED NOTES
GENERAL NOTES
1. ALL ELECTRICAL WORK IS NEW, AND SHALL BE INSTALLED IN ACCORDANCE WITH
THE LATEST EDITION OF THE NEC, NFPA, AND OSHA. THE CONTRACTOR SHALL
PROVIDE AND INSTALL ALL NECESSARY ELECTRICAL EQUIPMENT AND
CONNECTIONS INCLUDING CONTROL WIRING IN CONDUIT SYSTEM TO OTHER
DISCIPLINES' EQUIPMENT AS INDICATED/AS REQUIRED FOR A COMPLETE,
FUNCTIONAL ELECTRICAL SYSTEM.
2. CONDUCTORS SHALL BE COPPER MINIMUM #12 THW OR THWN, INSTALLED IN SCH
80. CONDUITS FOR ABOVEGROUND AND SCH 40. FOR UNDERGROUND RUNS.
PROVIDE 90° ELBOW AND CONDUIT TRANSITION FROM SCH 40. TO SCH 80. CONDUIT
(RGS) FOR UNDERGROUND ROUTING BEFORE TURNING UP TO ABOVE GROUND
SURFACE.
3. ALL BRANCH CIRCUITS SHALL CONTAIN WIRING INCLUDING AN INSULATED (GREEN)
GROUNDING CONDUCTOR IN A CONDUIT, EACH SIZED PER NEC. ALL CONDUCTOR
SIZES ARE BASED ON THE USE OF "THW/THWN" INSULATION.
4. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,
ELBOWS, JB'S, WIRE TROUGHS, PULL BOXES, HANDHOLES OR OTHER REQUIRED
ELEMENTS FOR PROPER INSTALLATION OF THE WORK. ALL NECESSARY
MATERIALS NEEDED TO FULFILE THE PROJECT REQUIREMENTS SHALL BE
PROVIDED AT NO ADDITIONAL COST.
5. WORK SHALL BE CARRIED OUT IN COORDINATION WITH OTHER DISCIPLINES.
COORDINATE WITH CIVIL CONTRACT DOCUMENTS IN TERMS OF ROUTING PATHS,
EQUIPMENT COMPATIBILITY AND MOUNTING ARRANGEMENT PRIOR TO
INSTALLATION.
6. THE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND CONDUIT ROUTING ARE
APPROXIMATE. COORDINATE AND INSTALL THESE ITEMS SO AS TO ELIMINATE
INTERFERENCE WITH PIPING AND ALL OTHER EQUIPMENT. ADJUST THE LOCATION,
MHT's AND PROVIDE APPROPRIATE MOUNTING HARDWARE AS REQUIRED AT NO
ADDITIONAL COST.
7. COMPLY WITH NFPAs, UFAS, OTHER APPLICABLE CODES, AND AUTHORITY HAVING
JURISDICTION OR AS SHOWN ON DRAWINGS FOR MOUNTING HEIGHTS OF ALL
ELECTRICAL EQUIPMENT AND DEVICES. MAINTAIN MINIMUM WORKING
CLEARANCES REQUIRED BY NEC AND LOCAL UTILITY COMPANY.
8. FOLLOW MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATIONS, UNLESS
INDICATED OR SPECIFIED OTHERWISE. INFORM VA AND OBTAIN WRITTEN
DIRECTION FROM THE CONTRACTING OFFICER REPRESENTATIVE IF CONFLICTS
EXIST BETWEEN MANUFACTURERS REQUIREMENTS AND CONTRACT DOCUMENTS
PRIOR TO THE START OF THE AFFECTED WORK.
9. ALL MATERIALS AND EQUIPMENT SHALL BE HEAVY DUTY, UL APPROVED/LISTED
AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
10. PROVIDE ALL GROUNDING AS PER SPECIFICATION 260526.
1. PROVIDE ONE 1" CONDUIT WITH 1" SPARE FOR FIBER, AND A SEPARATE 1" CONDUIT
WITH 1" SPARE FOR FUTURE ELECTRICAL USE. REFER TO SHEET EP107 DETAIL 3
FOR TRENCH DETAIL.
2. CONDUIT WITH FIBER OPTIC CONDUCTORS BETWEEN JUNCTION BOX AND
PULLBOX.
3. CONDUIT WITH POWER CONDUCTORS BETWEEN JUNCTION BOX AND PULLBOX.
SCALE: NTS
SURVEILLANCE POLE PLAN VIEWC2 SCALE: NTS
SURVEILLANCE POLE ELEVATION VIEWD5
NEMA 3R POLE
MOUNTED
JUNCTION BOX
CAMERA #1
PANORAMIC CAMERA
ELECTRICAL
PULLBOX
25FT POLE
SURVEILLANCE POLE
ETHERNET SWITCH
DUPLEX
RECEPTACLE
24'' X 24'' X 6''
NEMA 3R
JUNCTION BOX
GRADE
SCALE: NTS
SURVEILLANCE WALL MOUNTED PLAN VIEWF1 SCALE: NTS
SURVEILLANCE WALL MOUNTED ELEVATION VIEWF5
NEMA 3R POLE
MOUNTED
JUNCTION BOX
ELECTRICAL
PULLBOX
24'' X 24'' X 6''
NEMA 3R
JUNCTION BOX
GRADE
scott Text Box
ADDEDMENT 001
scott Text Box 08/12/2026 scott Polygon scott Text Box scott Image scott Pen
TN
scott Pen scott Pen scott Pen scott Pen scott Cloud scott Cloud scott Polygon scott Text Box scott Polygon scott Text Box scott Polygon scott Text Box scott Cloud
| Sheets and Views |
| E-504 |
File details come from the government source that posted it. Updated .