3b Short Circuit LV Monentary Report Interpretation.pdf

PDF 468 KB Posted

Attached to
H130--Amendment to Answer Questions for the Electrical Power Distribution System
Solicitation number
36C25925Q0292
Issued by

About this file

The document is a Low Voltage Momentary Report Interpretation guide that provides detailed explanations of technical parameters and table headers for electrical fault analysis. The guide breaks down key sections including the Section Header, which identifies software details and page information, and Table Headers that explain complex electrical engineering metrics such as Faulted Bus, Fault Duties, Asymmetrical Current, and Fault Contributions. Specific technical definitions are provided for terms like Thevenin Equivalent fault current, voltage per unit, power factor phase angle, and sequence resistance/reactance, which are used to analyze electrical system fault characteristics and impedance at specific locations.

View the file

Other files

File Type Posted
36C25925Q0292 0009.docx DOCX document
P09 - Final SOW 9 Sep 25.docx DOCX document
36C25925Q0292 0009_1.docx DOCX document
36C25925Q0292 0008_1.docx DOCX document
36C25925Q0292 0008.docx DOCX document
36C25925Q0292 0007.docx DOCX document
S02 36C25925Q0292 0007_1.docx DOCX document
36C25925Q0292 0005.docx DOCX document
36C25925Q0292 0005_1.docx DOCX document
36C25925Q0292 0004.docx DOCX document
36C25925Q0292 0003_1.docx DOCX document
P09 Final SOW.docx DOCX document
S02 36C25925Q0292 0003.docx DOCX document
36C25925Q0292 0002.docx DOCX document
36C25925Q0292 0002_1.docx DOCX document
2022 GJ VA Combined Triennial Electrical Report.pdf PDF
4a Coordination Study Opening Section.pdf PDF
2022 GJ VA Triennial Electrical Vol2.pdf PDF
20220911 Electrical One Line Diagram Final.pdf PDF
6b Disclaimer.pdf PDF
4c TCC Finding and Observations.pdf PDF
4b Coordination Study Reports Interpretation.pdf PDF
3d Equipment Duty Reports Findings.pdf PDF
3a Short Circuit Study Opening Section.pdf PDF
2 Executive Summary.pdf PDF
36C25925Q0292 0001.docx DOCX document
7 Building Division Index.pdf PDF
6a Glossary of Terms.pdf PDF
5b Arc Flash Concepts.pdf PDF
3c Short Circuit Equipment Duty Interpretation.pdf PDF
0 Grand Junction VA Table of Contents Vol 1.pdf PDF
5c Arc Flash Study Reports Interpretation.pdf PDF
5a Arc Flash Study Opening Section.pdf PDF
1 Introduction.pdf PDF
36C25925Q0292 0001_1_01.docx DOCX document
S02_ 36C25925Q0292_1.docx DOCX document
36C25925Q0292.docx DOCX document
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Low Voltage Momentary Report

Low Voltage Momentary Report Page 1

The following is provides to aid in interpreting and understanding the information provided in the Low Voltage Momentary Report.

SECTION HEADER

1st Line – Identifies Easy Power Software and Version #, Date of last entry or Creation date, and Path and electronic file name.

The right side of the page includes the current page number and the total number of pages included in this schedule.

2nd Line – Software Creator ESA, Inc 3rd Line – Comments Specific to this Report

TABLE HEADERS

FAULTED BUS – Includes Bus name, Base kV, 3 Phase and Voltage per unit value Bus name: uses the same naming convention as the one-line and short circuit analysis report which identifies faulted bus location within the system.

Base kV: lists the bus and associate operating voltage.

3 Phase: identifies the fault type as being a 3 phase bolted fault.

Vpu:-voltage per unit expresses the system voltage as fractions of the base unit.

This simplifies calculations where different voltages are present in a system.

FAULT DUTIES – Includes entries for E/Z (kA), MVA, Degree, X/R, R1 (pu), X1 (pu), R0 (pu), and X0 (pu).

E/Z (kA): The Thevenin Equivalent (symmetrical) fault current in kilo amps at this location.

MVA: The Thevenin Equivalent MVA fault value at this location.

Degree: The voltage to current phase angle. This is used to determining the power factor (P.F.).

X/R: The ratio of reactance and effective resistance of the effective system fault impedance at this location.

R1 (pu): Positive sequence resistance from the point of the fault.

X1 (pu): Positive sequence inductive reactance from the point of the fault.

R0 (pu): Zero sequence resistance from the point of the fault.

X0 (pu): Zero sequence inductive reactance from the point of the fault.

ASYM CURRENT – Includes entries for kA (1.6*Isym) and kA (based on X/R).

Low Voltage Momentary Report Page 2 kA (1.6*Isym): Maximum asymmetrical current based on a factor of 1.6 times the symmetrical fault current.

kA (based on X/R): Asymmetrical fault current based on the fault impedance X/R ratio.

CONTRIBUTIONS in kA – Includes entries for the “from bus”, “to bus”, kA, Deg, device and Branch.

From Bus: list the adjoining buses directly contributing to the faulted bus.

To Bus: list the faulted buses.

kA: Fault current in kilo Amps contributed by “from bus”.

Deg: The power factor phase angle for contributed fault current.

Device: Indicates the type of contributing source.

Branch: Indicates the name of the adjoining equipment feeder (conductors, cables, busways, etc.)

Definitions:

BWY designates busway in this report.