2022 GJ VA Triennial Electrical Vol2.pdf

PDF 10 MB Posted

Attached to
H130--Amendment to Answer Questions for the Electrical Power Distribution System
Solicitation number
36C25925Q0292
Issued by

About this file

This document is a comprehensive Project Report - Volume 2 for an Arc Flash Hazard Analyses Project conducted at the Veterans Affairs Medical Center in Grand Junction, Colorado, covering the period from January to May 2022. The report details an extensive electrical system data validation process for multiple buildings, including Building 1 North, Building 1 South, Building 5, Building 8, Building 9, Building 13, Building 20, Building 35, Building 36, Building 39, and Building 45.

The data validation methodology involved multiple critical steps: reviewing electrical drawings (some not updated since 2009), performing field verifications to confirm circuit relationships, and capturing detailed dataplate and circuit characteristics for various electrical equipment types such as medium voltage substations, transformers, switches, protective relays, circuit breakers, generators, solar inverters, and motor control centers. The report includes comprehensive spreadsheets documenting equipment data by building and location, and supplemented the data gathering with thermographic and visual inspections of electrical system components. The project was performed under Contract No. 36C25922P006 in cooperation with Slocum & Associates, with the primary objective of ensuring accurate electrical system modeling for proper arc flash incident energy calculations and personnel safety assessment.

View the file

Other files

File Type Posted
P09 - Final SOW 9 Sep 25.docx DOCX document
36C25925Q0292 0009_1.docx DOCX document
36C25925Q0292 0009.docx DOCX document
36C25925Q0292 0008_1.docx DOCX document
36C25925Q0292 0008.docx DOCX document
S02 36C25925Q0292 0007_1.docx DOCX document
36C25925Q0292 0007.docx DOCX document
36C25925Q0292 0005.docx DOCX document
36C25925Q0292 0005_1.docx DOCX document
36C25925Q0292 0004.docx DOCX document
P09 Final SOW.docx DOCX document
S02 36C25925Q0292 0003.docx DOCX document
36C25925Q0292 0003_1.docx DOCX document
36C25925Q0292 0002_1.docx DOCX document
36C25925Q0292 0002.docx DOCX document
20220911 Electrical One Line Diagram Final.pdf PDF
6b Disclaimer.pdf PDF
4c TCC Finding and Observations.pdf PDF
4b Coordination Study Reports Interpretation.pdf PDF
3d Equipment Duty Reports Findings.pdf PDF
3b Short Circuit LV Monentary Report Interpretation.pdf PDF
3a Short Circuit Study Opening Section.pdf PDF
2 Executive Summary.pdf PDF
36C25925Q0292 0001.docx DOCX document
7 Building Division Index.pdf PDF
6a Glossary of Terms.pdf PDF
5b Arc Flash Concepts.pdf PDF
3c Short Circuit Equipment Duty Interpretation.pdf PDF
0 Grand Junction VA Table of Contents Vol 1.pdf PDF
2022 GJ VA Combined Triennial Electrical Report.pdf PDF
4a Coordination Study Opening Section.pdf PDF
5c Arc Flash Study Reports Interpretation.pdf PDF
5a Arc Flash Study Opening Section.pdf PDF
1 Introduction.pdf PDF
36C25925Q0292 0001_1_01.docx DOCX document
S02_ 36C25925Q0292_1.docx DOCX document
36C25925Q0292.docx DOCX document
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Report - Volume 2

January – May 2022

Arc Flash Hazard Analyses ProjectArc Flash Hazard Analyses Project

CoverCover

Veterans Affairs Medical Center Grand Junction, Colorado

CoverCover in cooperation with

Slocum & Associates

337 Sundance Trail

Liberty Hill, Texas 78642

P - (512)484-5594

845 Long Branch Circle

Sugar Hill, Georgia 30518

P - (678)546-9393, F – (678)828-5903

Arc Flash Hazard Analyses – Volume 2 Contract No. 36C25922P006

Veterans Affairs Medical Center

Grand Junction, Colorado January – May 2022

Section 1 Data Validation Overview

Section 2 Tabulated Datasheets (by location)

Table of Contents

1 | P a g e

Volume 2 Overview – Data Validation

Arc Flash Hazard Analyses Project, Contract No. 36C25922P006

Process

Data validation is a critical aspect of any arc flash study. Obtaining complete and accurate information is the only way to ensure the electrical system is properly modeled for performing necessary calculations and achieving the best results – proper arc flash incident energy calculations and their impact on personnel safety.

This segment provides the raw data incorporated obtained in modeling the electrical system for the coordination and arc flash phases at the Leavenworth VA Medical Center. The process to capture and verify electrical system data includes the following elements:

Electrical Drawings – a set of the most recent electrical drawings were provided by the VA. It should be noted the drawings had not been updated since 2009 or earlier. System upgrades or changes were documented as a part of this process.

Field Verification – was performed to verify accuracy of drawings and depicted circuit relationships.

Data Spreadsheets – were used to capture dataplate and other pertinent circuit characteristics for the following equipment items:

Medium Voltage Substations

Medium Voltage Transformers

Medium Voltage Sectionalizing Switches

Protective Relays

Circuit Breakers

Protective Relays

Switchboards/Panelboards

Generators

Solar Inverters

Disconnect Switches

Automatic Transfer Switches

Motor Control Centers/VFDs/Motors

Conductors and Lengths

Documentation

Contained in this volume are the above-referenced spreadsheets used to tabulate the data of the various equipment items by building or major location.

Slocum & Associates in cooperation with

2 | P a g e

Supplemental Action

Due to the invasive nature of the data gathering/validation phase, it is an ideal time to perform a thermographic (infrared) and visual inspection of the various electrical system components. This inspection was performed by Slocum personnel. A listing of the equipment inspected and documentation of noted thermal anomalies or issues has been provided in the test report for the electrical testing phase of this project.

Arc Flash Hazard Analyses Project, Contract No. 36C25922P006 Veterans Affairs Medical Center – Grand Junction, Colorado

Equipment Data Records

Enclosed are the various data records for each piece of equipment evaluated under this contract.

Equipment items have been grouped by location. Each major group is separated by a red divider page to distinguish the groups.

The groups are categorized as follows:

Building 1 North

Building 1 South

Building 5

Building 8

Building 9

Building 13

Building 20

Building 35

Building 36

Building 39

Building 45

Medium Voltage Equipment:

▪ MV Substation

▪ MV S&C Switches

▪ MV Oil Transformers

Location: Building 1N

Source Load Phases Neutral Ground Phases Neutral Ground

OPA Building Substation US2 MSA Switchboard 500 MCM 500 MCM 1/0 AWG 6 6 6 75'

OPA Building MSA PVOPA2 Disc Disconnect Switch 600 kCMIL 600 kCMIL 3/0 AWG 2 2 2 50'

OPA Building PVOPA2 Disc PVOPA2 Panelboard 600 kCMIL 600 kCMIL 3/0 AWG 2 2 2 20'

OPA Building PVOPA2 PVEL1 Panelboard 600 kCMIL 600 kCMIL 3/0 AWG 2 2 2 10'

OPA Building PVEL1 (Line Side) Inverter E1 Inverter 3/0 AWG 3/0 AWG 3/0 AWG 1 1 1 50'

OPA Building PVEL1 Inverter E1.3 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 25'

OPA Building PVEL1 Inverter E1.4 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 30'

OPA Building PVEL1 Inverter E4-1 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 35'

OPA Building PVEL1 Inverter E4-6 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 40'

OPA Building PVEL1 Inverter E4.2 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 15'

OPA Building PVEL1 PVEL2 Panelboard #6 AWG #6 AWG #8 AWG 1 1 1 15'

OPA Building PVEL1 PVEL1.1 Panelboard 1/0 AWG 1/0 AWG #6 AWG 1 1 1 10'

OPA Building PVEL1.1 Inverter 4-7 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 45'

OPA Building PVEL1.1 Inverter 4-8 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 50'

OPA Building PVEL1.1 Inverter 4-5 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 50'

OPA Building PVEL1.1 Inverter 4-4 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 45'

OPA Building PVEL1.1 Inverter 4-3 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 40'

OPA Building PVEL1.1 Inverter 4-7 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 35'

OPA Building PVEL1.1 Inverter 4-7 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 25'

OPA Building PVEL1.1 Inverter 4-7 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 20'

OPA Building PVEL1.1 Inverter 4-7 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 20'

3rd Floor Roof MSA (PV AC Breaker) PVOPA1 Panelboard 2/0 AWG 2/0 AWG #2 AWG 1 1 1 60'

3rd Floor Roof PVOPA1 OPA-1 Inverter #8 AWG #8 AWG #8 AWG 1 1 1 5'

3rd Floor Roof PVOPA1 OPA-2 Inverter #8 AWG #8 AWG #8 AWG 1 1 1 10'

3rd Floor Roof PVOPA1 OPA-3 Inverter #8 AWG #8 AWG #8 AWG 1 1 1 15'

3rd Floor Roof PVOPA1 OPA-4 Inverter #8 AWG #8 AWG #8 AWG 1 1 1 20'

3rd Floor Roof PVOPA1 OPA-5 Inverter #8 AWG #8 AWG #8 AWG 1 1 1 25'

3rd Floor Roof PVOPA1 OPA-6 Inverter #8 AWG #8 AWG #8 AWG 1 1 1 30'

3rd Floor Roof PVOPA1 OPA-7 Inverter #8 AWG #8 AWG #8 AWG 1 1 1 35'

3rd Floor Roof MSA NP3 (MSA) Distribution Panel 4/0 AWG 4/0 AWG #2 AWG 1 1 1 20'

- NP3 (MSA) ANP3 (NIS) Panelboard #4 AWG #4 AWG #8 AWG 1 1 1 -

3628 MSA DNP3 Panelboard 500 kCMIL 500 kCMIL #1 AWG 1 1 1 40'

1635 MSA ATS #6 Panelboard 500 kCMIL 500 kCMIL #1 AWG 1 1 1 25'

1634 MSA ATS #1 Automatic Transfer Sw 4/0 AWG 4/0 AWG #2 AWG 1 1 1 30'

Cable Schedule

Power Qty Location Equipment Type

Size Type Distance

Building 1 North - Cables

1635 MSA ATS #4 Automatic Transfer Sw 500 kCMIL 500 kCMIL #1 AWG 1 1 1 15'

1634 MSA ATS #3 Automatic Transfer Sw 500 kCMIL 500 kCMIL #1 AWG 1 1 1 25'

1635 MSA ATS #7 Automatic Transfer Sw 500 kCMIL 500 kCMIL #1 AWG 1 1 1 25'

1634 MSA ATS #2 Automatic Transfer Sw 350 kCMIL 350 kCMIL #1 AWG 2 2 2 25'

Outside MSA PPCV1 Panelboard 350 kCMIL 350 kCMIL #1 AWG 2 2 2 125'

Outside PPCV1 Temp Chiller Chiller 350 kCMIL 350 kCMIL #1 AWG 2 2 2 25'

Outside PPCV1 TPP1 LV Dry-Type Transformer #10 AWG #10 AWG #10 AWG 1 1 1 5'

Outside TPP1 PP1 Panelboard #2 AWG #2 AWG #8 AWG 1 1 1 5'

1635 MSA TVSS TVSS #6 AWG #6 AWG #6 AWG 1 1 1 10'

3015 MP3 (NP3 om Dwg) ANP3 (NIS) Panelboard Not in Service -

3608 DNP3 NP3 (DNP3) Panelboard #6 AWG #6 AWG #10 AWG 1 1 1 175'

3667 DNP3 DN3 Panelboard #1 AWG #1 AWG #8 AWG 1 1 1 180'

3628 DNP3 T4 LV Dry-Type Transformer 2/0 AWG 2/0 AWG #6 AWG 1 1 1 55'

3628 T4 DNL3 Panelboard 500 kCMIL 500 kCMIL #1 AWG 1 1 1 65'

3628 DNL3 NL3A Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 20'

3666 DNL3 NL3B Section 1 Panelboard #1 AWG #1 AWG #6 AWG 1 1 1 175'

3666 NL3B Section 1 NL3B Section 2 Panelboard #1 AWG #1 AWG #6 AWG 1 1 1 5'

3608 DNL3 NL3C Section 1 Panelboard #1 AWG #1 AWG #6 AWG 1 1 1 100'

3608 NL3C Section 1 NL3C Section 2 Panelboard #1 AWG #1 AWG #6 AWG 1 1 1 105'

3628 DNP3 T2 LV Dry-Type Transformer #1 AWG #1 AWG #6 AWG 1 1 1 50'

3628 T2 DNL3A Panelboard 350 MCM 350 MCM #1 AWG 1 1 1 55'

3640 DNL3A OR1 Panelboard #6 AWG #6 AWG #8 AWG 1 1 1 90'

3641 DNL3A OR2 Panelboard #6 AWG #6 AWG #8 AWG 1 1 1 70'

3642 DNL3A OR3 Panelboard #6 AWG #6 AWG #8 AWG 1 1 1 120'

3643 DNL3A OR4 Panelboard #6 AWG #6 AWG #8 AWG 1 1 1 110'

1635 ATS #2 DPQ Distribution Panel #8 AWG #8 AWG #10 AWG 1 1 1 40'

3014 DPQ AEQP3 Panelboard #4 AWG #4 AWG #8 AWG 1 1 1 75'

0022 DPQ DQPB Panelboard 350 MCM 350 MCM #4 AWG 1 1 1 25'

B34-3 DPQ 34H1A Panelboard #4 AWG #4 AWG #8 AWG 1 1 1 50'

B34-3 DPQ 34T1 Disc Disconnect Switch #4 AWG #4 AWG #8 AWG 1 1 - 180'

B34-3 34T1 Disc 34T1 LV Dry-Type Transformer #2 AWG #2 AWG - 1 1 - 15'

B34-3 34T1 34L1A Section 1 Panelboard 3/0 AWG 3/0 AWG #6 AWG 2 2 2 25'

B34-3 34L1A Section 1 34L1A Section 2 Panelboard 3/0 AWG 3/0 AWG #6 AWG 2 2 2 5'

B34-3 34L1A Section 2 ATS-UPS (Normal) Automatic Transfer Sw 3/0 AWG 3/0 AWG #6 AWG 1 1 1 10'

B34-3 EDP1 (Bldg 1S) ATS-UPS (Emergency) Automatic Transfer Sw 3/0 AWG 3/0 AWG #6 AWG 1 1 1 15'

IT Room ATS-UPS (Normal) UPS UPS 3/0 AWG 3/0 AWG #6 AWG 1 1 1 75'

0022 DQPB DQTB LV Dry-Type Transformer #8 AWG #8 AWG #10 AWG 1 1 1 10'

0022 DQPB DQLB Panelboard #2 AWG #2 AWG #6 AWG 1 1 1 5'

0022 DQPB Elevator S5 Disc Disconnect Switch #4 AWG #4 AWG #6 AWG 1 1 1 30'

0022 Elevator S5 Disc Elevator S5 Disc Controller #4 AWG #4 AWG #6 AWG 1 1 1 10'

0022 DQPB Elevator P3 Disc Disconnect Switch #4 AWG #4 AWG #6 AWG 1 1 1 20'

0022 Elevator P3 Disc Elevator P3 Disc Controller #4 AWG #4 AWG #6 AWG 1 1 1 10'

0022 DQPB EUH-1 Heater #12 AWG #12 AWG #12 AWG 1 1 1 30'

1633 DPQ DQP1 Panelboard #4 AWG #4 AWG #8 AWG 1 1 1 50'

1633 DPQ TVSS TVSS #8 AWG #8 AWG #8 AWG 1 1 1 5'

2639 DQP1 DQP2 Panelboard #4 AWG #4 AWG #8 AWG 1 1 1 40'

1633 DQP1 DQT1 LV Dry-Type Transformer #12 AWG #12 AWG #12 AWG 1 1 1 15'

1633 DQT1 DQL1 Panelboard #10 AWG #10 AWG #8 AWG 1 1 1 15'

Roof Mech Rm, 2600 DPQ BQP2 Panelboard #4 AWG #4 AWG #8 AWG 1 1 1 100'

1689 DPQ AQP1 Panelboard 2/0 AWG 2/0 AWG #6 AWG 1 1 1 200'

1634 DPQ PSEG Panelboard #4 AWG #4 AWG #8 AWG 1 1 1 25'

1634 PSEG TSEG Panelboard #8 AWG #8 AWG #10 AWG 1 1 1 5'

1634 TSEG LSEG Panelboard #2 AWG #2 AWG #8 AWG 1 1 1 5'

3627 DPQ DQP3A Panelboard 350 kCMIL 350 kCMIL 1/0 AWG 1 1 1 65'

3627 DQP3A Chiller 1-CH-3 Motor/VFD 2/0 AWG 2/0 AWG #6 AWG 1 1 1 60'

3627 DQP3A CWP 1-P1 Motor/VFD #12 AWG #12 AWG #12 AWG 1 1 1 40'

3627 DQP3A CWP 1-P2 Motor/VFD #12 AWG #12 AWG #12 AWG 1 1 1 40'

3627 DQP3A Chiller Cond 1-CU-1 Motor/VFD #8 AWG #8 AWG #10 AWG 1 1 1 40'

3627 ATS #6 DPQ3 Panelboard 500 kCMIL 500 kCMIL #1 AWG 1 1 1 30'

3627 DPQ3 DQP3B Panelboard 1/0 AWG 1/0 AWG #6 AWG 1 1 1 180'

3627 DPQ3 TVSS TVSS #8 AWG #8 AWG #10 AWG 1 1 1 10'

3666 DPQ3B T3 Disc Disconnect Switch #1 AWG #1 AWG #6 AWG 1 1 1 35'

3666 T3 Disc T3 LV Dry-Type Transformer #1 AWG #1 AWG #6 AWG 1 1 1 5'

3666 T3 QL3B Panelboard 3/0 AWG 3/0 AWG #4 AWG 1 1 1 10'

3628 QL3B QL3A Panelboard #6 AWG #6 AWG #10 AWG 1 1 1 170'

1635 ATS #4 DNP1 Disc CB Disconnect Switch 300 MCM 300 MCM #2 AWG 1 1 1 10'

1632 DNP1 Disc DNP1 Panelboard 500 MCM 500 MCM #2 AWG 1 1 1 60'

2638 DNP1 Disc DNP2 Panelboard 500 MCM 500 MCM #2 AWG 1 1 1 30'

1632 DNP1 DNT1 LV Dry-Type Transformer #2 AWG #2 AWG #6 AWG 1 1 1 15'

1632 DNT1 DNL1 Section 1 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 20'

1632 DNL1 Section 1 DNL1 Section 2 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 5'

2638 DNL1 Section 2 DNL2 Section 1 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 30'

2638 DNL2 Section 1 DNL2 Section 2 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 5'

1635 ATS #4 ANP1 CB Disconnect Switch 300 MCM 300 MCM #2 AWG 1 1 1 190'

1690 ANP1 ANP1 Panelboard 500 MCM 500 MCM #1 AWG 2 2 2 10'

2664 ANP1 ANP2 Panelboard 500 MCM 500 MCM #2 AWG 2 2 2 35'

1690 ANP1 ANT1 LV Dry-Type Transformer #2 AWG #2 AWG #8 AWG 1 1 1 15'

1690 ANT1 ANL1 Section 1 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 15'

1690 ANL1 Section 1 ANL1 Section 2 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 5'

2664 ANT1 ANL2 Section 1 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 35'

2664 ANL2 Section 1 ANL2 Section 2 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 5'

1635 ATS #1 DPLS Distribution Panel 3/0 AWG 3/0 AWG #6 AWG 1 1 1 30'

1632 DPLS DLP1 Panelboard #6 AWG #6 AWG #10 AWG 1 1 1 65'

1632 DLP1 DLT2 Disc Disconnect Switch #12 AWG #12 AWG #12 AWG 1 1 1 35'

1632 DLT2 Disc DLT2 LV Dry-Type Transformer #10 AWG #10 AWG #10 AWG 1 1 1 5'

2638 DLT2 DLL2 Panelboard #10 AWG #10 AWG #6 AWG 1 1 1 20'

1600 DPLS CLP1 Panelboard #6 AWG #6 AWG #10 AWG 1 1 1 130'

1600 CLP1 CLT1 LV Dry-Type Transformer #12 AWG #12 AWG #12 AWG 1 1 1 20'

1600 CLT1 CLL1 Panelboard #10 AWG #10 AWG #6 AWG 1 1 1 15'

2604 CLL1 CLL2 Panelboard #8 AWG #8 AWG #10 AWG 1 1 1 30'

1690 DPLS ALP1 Panelboard #6 AWG #6 AWG #10 AWG 1 1 1 200'

1690 ALP1 ALT2 Disc Disconnect Switch #8 AWG #8 AWG #10 AWG 1 1 1 30'

2664 ALT2 Disc ALT2 Disc LV Dry-Type Transformer #8 AWG #8 AWG #10 AWG 1 1 1 5'

2664 ALT2 ALL2 Panelboard #10 AWG #10 AWG #6 AWG 1 1 1 20'

3628 DPLS LP3 Panelboard #6 AWG #6 AWG #10 AWG 1 1 1 55'

3666 LP3 T1 Disc. Disconnect Switch #10 AWG #10 AWG #10 AWG 1 1 1 195'

3666 T1 Disc. T1 LV Dry-Type Transformer #10 AWG #10 AWG #10 AWG 1 1 1 5'

3666 T1 LL3 Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 20'

1635 DPLS TVSS TVSS #6 AWG #6 AWG #10 AWG 1 1 1 5'

1635 ATS #3 DPC Distribution Panel 500 MCM 500 MCM #4 AWG 1 1 1 40'

2638 DPC DCP2 Panelboard #2 AWG #2 AWG #6 AWG 1 1 1 80'

2638 DCP2 DCT2 LV Dry-Type Transformer 1/0 AWG 1/0 AWG #6 AWG 1 1 1 20'

2638 DCT2 DCL2 Panelboard 1/0 AWG 1/0 AWG #6 AWG 1 1 1 20'

1632 DCT2 DCL1 Panelboard 1/0 AWG 1/0 AWG #6 AWG 1 1 1 30'

1600 DPC CCP1 Panelboard #1 AWG #1 AWG #6 AWG 1 1 1 125'

1600 CCP1 CCT1 LV Dry-Type Transformer #6 AWG #6 AWG #10 AWG 1 1 1 20'

1600 CCT1 CCL1 Panelboard 1/0 AWG 1/0 AWG #6 AWG 1 1 1 20'

1004 CCT1 BCL1 Panelboard 2/0 AWG 2/0 AWG #6 AWG 1 1 1 30'

2604 DPC CCP2 Panelboard #2 AWG #2 AWG #6 AWG 1 1 1 135'

2604 CCP2 CCT2 LV Dry-Type Transformer #8 AWG #8 AWG #10 AWG 1 1 1 20'

2604 CCT2 Splice Splice #2 AWG #2 AWG #8 AWG 1 1 1 5'

2604 Splice CCL2 Panelboard #2 AWG #2 AWG #8 AWG 1 1 1 30'

2602 Splice BCL2 Panelboard #2 AWG #2 AWG #8 AWG 1 1 1 15'

2664 DPC ACP2 Panelboard #2 AWG #2 AWG #6 AWG 1 1 1 205'

2664 ACP2 ACT2 LV Dry-Type Transformer #6 AWG #6 AWG #10 AWG 1 1 1 20'

2664 ACT2 ACL2 Panelboard 1/0 AWG 1/0 AWG #6 AWG 1 1 1 15'

1690 ACT2 ACL1 Panelboard 1/0 AWG 1/0 AWG - 1 1 - 35'

2664 DPC TVSS TVSS #8 AWG #8 AWG #8 AWG 1 1 1 10'

3608 DPC DCP3 Panelboard 350 MCM 350 MCM #2 AWG 1 1 1 135'

3608 DCP3 CP3 Panelboard #6 AWG #6 AWG #10 AWG 1 1 1 15'

3627 DCP3 T6 LV Dry-Type Transformer 2/0 AWG 2/0 AWG #6 AWG 1 1 1 105'

3608 DCP3 T5 LV Dry-Type Transformer #2 AWG #2 AWG #6 AWG 1 1 1 20'

3627 T6 DCL3 Panelboard 500 kCMIL 500 kCMIL #3 AWG 1 1 1 20'

3643 DCL3 OR4A Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 50'

3642 DCL3 OR3A Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 50'

3641 DCL3 OR2A Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 50'

3640 DCL3 OR1A Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 50'

3608 T5 DCL3A Panelboard 350 kCMIL 350 kCMIL #4 AWG 1 1 1 15'

3628 DCL3A CL3A Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 95'

3666 DCL3A CL3B Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 120'

3608 DCL3A CL3C Section 1 Panelboard #3 AWG #3 AWG #6 AWG 1 1 1 25'

3608 CL3C Section 1 CL3C Section 2 Panelboard #3 AWG #3 AWG #6 AWG 1 1 1 5'

1635 ATS #7 CNP1 Disc CB Disconnect Switch 500 MCM 500 MCM #2 AWG 1 1 1 115'

1600 CNP1 Disc CNP1 Panelboard 500 MCM 500 MCM #2 AWG 1 1 1 10'

1600 CNP1 CNT1 LV Dry-Type Transformer #2 AWG #2 AWG #8 AWG 1 1 1 15'

1600 CNT1 CNL1 Panelboard 4/0 AWG 4/0 AWG #2 AWG 1 1 1 20'

1004 CNT1 BNL1 Section 1 Panelboard 4/0 AWG 4/0 AWG #6 AWG 1 1 1 25'

1004 BNL1 Section 1 BNL1 Section 2 Panelboard 4/0 AWG 4/0 AWG #6 AWG 1 1 1 5'

2604 ATS #7 CNP2 Disc CB Disconnect Switch 500 MCM 500 MCM #2 AWG 1 1 1 130'

1635 CNP2 Disc CNP2 Panelboard 500 MCM 500 MCM #2 AWG 1 1 1 10'

2604 CNP2 CNT2 LV Dry-Type Transformer #2 AWG #2 AWG #8 AWG 1 1 1 5'

2604 CNT2 CNL2 Panelboard 4/0 AWG 4/0 AWG #2 AWG 1 1 1 25'

2602 CNL2 BNL2 Section 1 Panelboard 4/0 AWG 4/0 AWG #2 AWG 1 1 1 25'

2602 BNL2 Section 1 BNL2 Section 2 Panelboard 4/0 AWG 4/0 AWG #2 AWG 1 1 1 5'

Generator Room Generator EDP2 Switchboard 500 MCM 500 MCM #4 AWG 5 5 5 150'

1635 EDP2 ATS #5 (NRAD) Automatic Transfer Sw 500 kCMIL 500 kCMIL 1/0 AWG 1 1 1 30'

1635 EDP2 ATS #6 Automatic Transfer Sw 500 kCMIL 500 kCMIL #1 AWG 1 1 1 30'

1635 EDP2 ATS #7 Automatic Transfer Sw 500 kCMIL 500 kCMIL #1 AWG 1 1 1 30'

1635 EDP2 ATS #4 Automatic Transfer Sw 500 kCMIL 500 kCMIL #1 AWG 1 1 1 30'

1634 EDP2 ATS #2 Automatic Transfer Sw 350 kCMIL 350 kCMIL #1 AWG 2 2 2 30'

1634 EDP2 ATS #1 Automatic Transfer Sw 4/0 AWG 4/0 AWG #2 AWG 1 1 1 30'

1634 EDP2 ATS #3 Automatic Transfer Sw 500 kCMIL 500 kCMIL #1 AWG 1 1 1 30'

1635 ATS #5 (NRAD) NRAD Distribution Panel 3/0 AWG 3/0 AWG #4 AWG 2 2 2 35'

Outside Temp Generator EDP2 Switchboard 600 kCMIL 600 kCMIL 1/0 AWG 4 4 4 75'

Outside NRAD MRI Trailer Disc Disconnect Switch 2/0 AWG 2/0 AWG 2/0 AWG 1 1 1 50'

2610 NRAD CAT Scan T-DAT2 CB Disconnect Switch 250 MCM 250 MCM 1/0 AWG 1 1 1 115'

2613-15 NRAD GE Fluoroscopy Panelboard 1/0 AWG 1/0 AWG #2 AWG 1 1 1 135'

2420 NRAD Phillips Xray CB Disconnect Switch 3/0 AWG 3/0 AWG 3/0 AWG 1 1 1 165'

2415 NRAD Toshiba Xray CB Disconnect Switch 3/0 AWG 3/0 AWG 3/0 AWG 1 1 1 145'

2415 NRAD Xray CB Disconnect Switch #4 AWG #4 AWG #4 AWG 1 1 1 145'

2405 NRAD Fluoroscopy CB Disconnect Switch 1/0 AWG 1/0 AWG 1/0 AWG 1 1 1 145'

Outside T6 ATS #5 (NRAD) Disc Disconnect Switch 500 kCMIL 500 kCMIL 1/0 AWG 1 1 1 75'

Outside ATS #5 (NRAD) Disc ATS #5 (NRAD) Automatic Transfer Sw 500 kCMIL 500 kCMIL 1/0 AWG 1 1 1 10'

2613 GE Fluoroscopy PD1 PDU #2 AWG #2 AWG #4 AWG 1 1 1 10'

2613 GE Fluoroscopy PDU UPS #12 AWG #12 AWG #10 AWG 1 1 1 15'

Location: Building 1 North

Load ID Substation US2

Trip Device Type MicroLogic 6.0P

Breaker ID Main

Frame Size 16--A

Breaker Type

ICB

Rating 1600A

Inst

Manufacturer Square D

Poles 1600A

Current Time Delay Current Time Delay Current Current Time Delay

Model

RK1600

IAC Rating 65 kIAC .4-1X .5-24s 1.5-10X .1-.4s 2-15X - -

Serial No CT Ratio 1X .5s 1.5X .1s On 2X A .1s On

Load ID Main

Trip Device Type MicroLogic 3-3S

Breaker ID

DNP3

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

LJ400

IAC Rating 65 kAIC 125-400A 1.5-10s - - 1.5-12X - -

Serial No CT Ratio 400A 1s - - 1.5X - -

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Feeder Breaker #1

Range

Settings

Equipment ID MSA

General Switchboard Data

Power Source Substation US2/PVOPA2 Floor OPA Building

Manufacturer Square D Room 1635

Model QED Voltage 480V

Long Time

IAC Rating Unknown Buss

(Copper or Aluminum)

160A

Switchboard Breaker Data

Short Time Ground Fault

Range

Settings

Switchboard Schedule

Main Breaker #1

Trip Device Settings (as found)

Building 1 North - LV Swbds

Main

Trip Device Type MicroLogic 3-3S

Breaker ID

ATS-6

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

LJ400

IAC Rating 65 kAIC 125-400A 1.5-10s - - 1.5-12X - -

Serial No CT Ratio 400A 1s - - 1.5X - -

Load ID Main

Trip Device Type MicroLogic 3-3S

Breaker ID

PPCV1

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

LJ400

IAC Rating 65 kAIC 125-400A 1.5-10s - - 1.5-12X - -

Serial No CT Ratio 400A 1s - - 1.5X - -

Load ID Main

Trip Device Type MicroLogic 3-3S

Breaker ID

ATS-7

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

LJ400

IAC Rating 65 kAIC 125-400A 1.5-10s - - 1.5-12X - -

Serial No CT Ratio 300A 1s - - 1.5X - -

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Feeder Breaker #3

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Feeder Breaker #2

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Feeder Breaker No. 4

Trip Device Settings (as found)

Miscellaneous Information Electrical or Manual Operation? (E or M)

Trip Device Type MicroLogic 3-3S

Breaker ID

ATS-4

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

LJ400

IAC Rating 65 kAIC 125-400A 1.5-10s - - 1.5-12X - -

Serial No CT Ratio 400A 1s - - 1.5X - -

Load ID Main

Trip Device Type MicroLogic 5.0

Breaker ID

ATS-2

Frame Size 800A

Breaker Type

MCB

Rating 800A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

PK800

IAC Rating 50 kAIC .4-1X .5-24s 1.5-10X .1-.4s 2-15X - -

Serial No CT Ratio .7s .5s 1.5s .1s On 2X - -

Load ID Main

Trip Device Type MicroLogic 3-3S

Breaker ID

ATS-3

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

LJ400

IAC Rating 65 kAIC 125-400A 1.5-10s - - 1.5-12X - -

Serial No CT Ratio 400A 6s - - 10X - -

Feeder Breaker No. 7

Trip Device Settings (as found)

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Feeder Breaker No. 5

Trip Device Settings (as found)

Feeder Breaker No. 6

Trip Device Settings (as found)

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Trip Device Type MicroLogic 3-2S

Breaker ID

TVSS

Frame Size 150A

Breaker Type

MCB

Rating 150A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

HJ150

IAC Rating 65 kAIC 35-100A 1.5-10s - - 1.5-12X - -

Serial No CT Ratio 60A 1s - - 1.5X - -

Load ID Main

Trip Device Type MicroLogic 3-2S

Breaker ID Spare

Frame Size 250A

Breaker Type

MCB

Rating 250A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

JJ250

IAC Rating 65 kAIC 70-250A 1.5-10s - - 1.5-12X - -

Serial No CT Ratio 250A 1s - - 1.5X - -

Load ID Main

Trip Device Type T-M

Breaker ID

ATS-1

Frame Size 150A

Breaker Type

MCB

Rating 150A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

HJ150

IAC Rating 65 kAIC - - - - Fixed - -

Serial No CT Ratio

- - - - 1300A - -

Feeder Breaker No. 8

Trip Device Settings (as found)

Feeder Breaker No. 9

Trip Device Settings (as found)

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Feeder Breaker No. 10

Trip Device Settings (as found)

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Trip Device Type MicroLogic 3-3S

Breaker ID

NP3 (MSA)

Frame Size 250A

Breaker Type

MCB

Rating 250A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

JJ250

IAC Rating 65 kAIC 70-250A 1.5-10s - - 1.5-12X - -

Serial No CT Ratio 250A 1s - - 1.5X - -

Load ID Main

Trip Device Type MicroLogic 3-3S

Breaker ID

PV AC

Frame Size 250A

Breaker Type

MCB

Rating 250A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

JJ250

IAC Rating 65 kAIC 70-250A 1.5-10s - - 1.5-12X - -

Serial No CT Ratio 200A 1s - - 1.5X - -

Feeder Breaker No. 11

Trip Device Settings (as found)

Feeder Breaker No. 12

Trip Device Settings (as found)

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Location: Building 1 North

Generator

Trip Device Type

ETU 545

Breaker ID Main

Frame Size 1600A

Breaker Type

MCB

Rating 1600A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

NPX3U160

IAC Rating 35 kAIC 700-1600A - - - 1.5-8X - -

Serial No CT Ratio 1600A - - - 6X @ .2s Off - -

Load ID Main

Trip Device Type

ETU 545

Breaker ID

ATS #1

Frame Size 250A

Breaker Type

MCB

Rating 250A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

NFX3U250

IAC Rating 35 kAIC 70-250A - - - 2-10X - -

Serial No CT Ratio 150A - - - 10X @ .5s Off - -

Manufacturer Siemens Room Generator Room

Model SB3 Voltage 480V

Switchboard Schedule

Equipment ID EDP2

General Switchboard Data

Power Source Generator Floor 1st Floor

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

IAC Rating Unknown Buss

(Copper or Aluminum)

1600A

Switchboard Breaker Data

Main Breaker #1

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Feeder Breaker #1

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Trip Device Type

ETU 545

Breaker ID

ATS #3

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

NJX3U400

IAC Rating 35 kAIC 150-400A - - 2-10X - -

Serial No CT Ratio 400A - - 10X @ .1s Off - -

Load ID Main

Trip Device Type

ETU 545

Breaker ID

ATS #7

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

NJX3U400

IAC Rating 35 kAIC 150-400A - - 2-10X - -

Serial No CT Ratio 400A - - 10X @ .1s Off - -

Load ID Main

Trip Device Type

ETU 545

Breaker ID

ATS #5

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

NJX3U400

IAC Rating 35 kAIC 150-400A - - 2-10X - -

Serial No CT Ratio 400A - - 10X @ .1s Off - -

Feeder Breaker #2

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Feeder Breaker #3

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Feeder Breaker No. 4

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Trip Device Type

ETU 545

Breaker ID

ATS #6

Frame Size 600A

Breaker Type

MCB

Rating 600A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

HLK3U600

IAC Rating 35 kAIC 200-600A - - 2-10X - -

Serial No CT Ratio 600A - - 8X @ .1s Off - -

Load ID Main

Trip Device Type

ETU 545

Breaker ID

ATS #2

Frame Size 600A

Breaker Type

MCB

Rating 600A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

HLK3U600

IAC Rating 35 kAIC 200-600A - - 2-10X - -

Serial No CT Ratio 600A - - 8X @ .1s Off - -

Load ID Main

Trip Device Type

ETU 555

Breaker ID Quick Disconnect

Frame Size 1200A

Breaker Type

MCB

Rating 1200A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

NNX3V120

IAC Rating 35 kAIC 700-1200A - - - 2-10X - -

Serial No CT Ratio 700A 10s - - 10X @ 0s Off - -

Feeder Breaker No. 5

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Feeder Breaker No. 6

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Feeder Breaker No. 7

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

ATS #2

Trip Device Type MicroLogic 3.3

Breaker ID Main

Frame Size 600A

Breaker Type

MCB

Rating 600A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

LG600

IAC Rating 35 kAIC 200-600A 1.5-10s - - 1.5-11X - -

Serial No CT Ratio 600A 2.5s - - 1.5X - -

34T1 Square D BG100 3 1

BQP2 Square D BG100 3 1

34H1A Square D BG100 3 1

DQP1 Square D BG100 3 1

AQP1 Square D JG250 3 1

PSEG Square D BG70 3 1

DQPB Square D LA300A 3 1

1000A

MCB 300A 300A 30 kAIC 1500-3000A 1500A

MCB 70A 70A 35 kAIC

875-1250A 875A

MCB 100A 100A 35 kAIC 1250A

MCB 250A 175A 35 kAIC

35 kAIC 1250A

MCB 100A 100A 35 kAIC

Manufacturer Square D Room 1635

Circuit ID

MCB 100A 100A 35 kAIC 1250A

1250A

MCB 100A 100A

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

600A

Breaker Data

Main Breaker

Distribution Panel Schedule

Panel ID

DPQ

General Panel Data

Power Source ATS #2 Floor 1st Floor

Branch Breaker Data

Trip Device Settings (as found)

Model HCP Voltage 480V

Long Time Short Time Ground Fault

Range

Settings

IAC Rating 200 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

Building 1 North - Distribution Panels

1EQP3 Square D BG100 3 1

TVSS Square D BG60 3 1

1250A

MCB 60A 60A 35 kAIC

MCB 100A 100A 35 kAIC

ATS #1

Trip Device Type T-M

Breaker ID Main

Frame Size 250A

Breaker Type

NCB

Rating 250A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

JG250

IAC Rating 35 kAIC 1125-2250A

Serial No

CT Ratio 1125A

DLP1 Square D EDB34050 3 1

ALP1 Square D EDB34060 3 1

TVSS Square D EDB34060 3 1

LP3 Square D EDB34060 3 1

CLP1 Square D EDB34060 3 1

Distribution Panel Schedule

Panel ID

DPLS

General Panel Data

Power Source ATS #1 Floor 1st Floor

Main Breaker

Manufacturer Square D Room 1635

Model NF Voltage 480V

IAC Rating 200 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

MCB 50A 50A 18 kAIC

Qty Range Setting

MCB 60A 60A 18 kAIC

60A 18 kAIC

MCB 60A 60A 18 kAIC

MCB 60A 60A 18 kAIC

MCB 60A

ATS #3

Trip Device Type

ET1.0

Breaker ID Main

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

MG400

IAC Rating 35 kAIC 2-10X

Serial No CT Ratio 2X

CCP2 Square D BG100 3 1

DCP2 Square D BG100 3 1

DCP3 Square D JG250 3 1

CCP1 Square D BG125 3 1

ACP2 Square D BG100 3 1

TVSS Square D BG60 3 1

Distribution Panel Schedule

Panel ID

DPC

General Panel Data

Power Source ATS #3 Floor 1st Floor

Main Breaker

Manufacturer Square D Room 1634

Model HCP Voltage 480V

IAC Rating 299 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

400A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

MCB 250A

Branch Breaker Data

Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

MCB 125A 125A 35 kAIC

MCB 100A 100A 35 kAIC

1250A

Qty Range Setting

1250A

1250A

MCB 100A 100A 35 kAIC

250A 35 kAIC 1250-2500A 1250A

MCB 60A 60A 35 kAIC 800A

MCB 100A 100A 35 kAIC 1250A

DPQ

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

1-EF-15 Square D EGB34015 3 1

EF-10 Square D EGB34020 3 1

1-A-13R Square D EGB34020 3 1

1-A-13S Square D EGB34060 3 1

1-EF-14 Square D EGB34015 3 1

Panel Schedule

Panel ID

AEQP3

General Panel Data

Power Source DPQ Floor 3rd Floor

Main Breaker

Manufacturer Square D Room 3014

Model NF Voltage 480V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

125A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB 15A 15A 35 kAIC

MCB 20A 20A 35 kAIC

MCB 20A 20A 35 kAIC

MCB 60A 60A 35 kAIC

MCB 15A 15A 35 kAIC

Building 1 North- Panels

DPQ

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

DQTB General Electric TEYD3040B 3 1

Elevator S5 General Electric TED34150 3 1

Elevator P3 General Electric TED34150 3 1

EUH-1 General Electric TEYD3015B 3 1

Panel Schedule

Panel ID

DQPB

General Panel Data

Power Source DPQ Floor Basement

Main Breaker

Manufacturer General Electric Room 0022

Model AEF3304MBX Voltage 480V

IAC Rating 18 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

40)A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB 40A 40A 25 kAIC

MCB 150A 150A 18 kAIC

MCB 150A 150A 18 kAIC

MCB 15A 15A 18 kAIC

DPQ

Trip Device Type T-M

Breaker ID Main

Frame Size 90A

Breaker Type

MCB

Rating 90A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

THQB

IAC Rating 22 kAIC

Serial No CT Ratio

General Electric THQB 1 1

Panel Schedule

Panel ID

DQLB

General Panel Data

Power Source DPQ Floor Basement

Main Breaker

Manufacturer General Electric Room 0022

Model Unknown Voltage 208V

IAC Rating Unknown Buss

(Copper, Aluminum, Bolt On, etc)

Unknown

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MBC 20A 20A 22 kAIC

DPQ

Trip Device Type T-M

Breaker ID Main

Frame Size 100A

Breaker Type

MCB

Rating 100A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

TEY

IAC Rating 14 kAIC

Serial No CT Ratio

Misc General Electric TEY 1 1

DQT1 General Electric TEY 1 1

Panel Schedule

Panel ID

DQP1

General Panel Data

Power Source DPQ Floor 1st Floor

Main Breaker

Manufacturer General Electric Room 1633

Model Unknown Voltage 480V

IAC Rating 100 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

Unknown

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB 20A 20A 14 kAIC

MCB 15A 15A 14 kAIC

DQP1

Trip Device Type T-M

Breaker ID Main

Frame Size 50A

Breaker Type

MCB

Rating 50A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

TEY

IAC Rating 14 kAIC

Serial No CT Ratio

1-P3 General Electric TEY 3 1

1-P5 General Electric TEY 3 1

1-P4 General Electric TEY 3 1

1-P6 General Electric TEY 3 1

Panel Schedule

Panel ID

DQP2

General Panel Data

Power Source DQP1 Floor 2nd Floor

Main Breaker

Manufacturer General Electric Room 2639

Model AEF3301BBX Voltage 480V

IAC Rating 100 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

125A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB 20A 20A 14 kAIC

MCB 15A 15A 14 kAIC

MCB 20A 20A 14 kAIC

MCB 15A 15A 14 kAIC

DQT1

Trip Device Type T-M

Breaker ID Main

Frame Size 30A

Breaker Type

MCB

Rating 30A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

THQB

IAC Rating 22 kAIC

Serial No CT Ratio

General Electric THQB 1 1

Panel Schedule

Panel ID

DQL1

General Panel Data

Power Source DQT1 Floor 1st Floor

Main Breaker

Manufacturer General Electric Room 1633

Model AWF3181CBX Voltage 208V

IAC Rating 200 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

125A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 20A 20A 22 kAIC

DPQ

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

1-MV-1 General Electric TEY 3 1

Dental Air General Electric TEY 3 1

Panel Schedule

Panel ID

AQP1

General Panel Data

Power Source DPQ Floor 1st Floor

Main Breaker

Manufacturer General Electric Room 1689

Model Unknown Voltage 480V

IAC Rating 100 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

Unknown

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB 20A 20A 14 kAIC

MCB 100A 100A 14 kAIC

DPQ

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

TSEG General Electric TEY 3 1

Panel Schedule

Panel ID

PSEG

General Panel Data

Power Source DPC Floor 1st Floor

Main Breaker

Manufacturer General Electric Room 1634

Model AEF3241MTX Voltage 480V

IAC Rating 100 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

125A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB 40A 40A 14 kAIC

DPQ

Trip Device Type T-M

Breaker ID Main

Frame Size 90A

Breaker Type

MCB

Rating 90A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

THQB

IAC Rating 22 kAIC

Serial No CT Ratio

General Electric THQB 2 1

Panel Schedule

Panel ID

LSEG

General Panel Data

Power Source DPQ Floor 1st Floor

Main Breaker

Manufacturer General Electric Room 1634

Model Unknown Voltage 208V

IAC Rating 200 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

125A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 50A 50A 10 kAIC

DPQ

Trip Device Type T-M

Breaker ID Main

Frame Size 150A

Breaker Type

MCB

Rating 100A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

HD150

IAC Rating 18 kAIC Fixed

Serial No CT Ratio 1300A

CRAC-5 Square D EDB34015 3 1

CRAC-6 Square D EDB34015 3 1

CRAC-7 Square D EDB34015 3 1

Condenser-5 Square D EDB34020 3 1

Condenser-6 Square D EDB34020 3 1

Condenser-7 Square D EDB34020 3 1

Panel Schedule

Panel ID 34H1A

General Panel Data

Power Source DPQ Floor First Floor

Main Breaker

Manufacturer Square D Room B34-3

Model NF Voltage 480V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

125A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB 15A 15A 18 kAIC

MCB 15A 15A 18 kAIC

MCB 15A 15A 18 kAIC

MCB 20A 20A 18 kAIC

MCB 20A 20A 18 kAIC

MCB 20A 20A 18 kAIC

DPQ via 34T1

Trip Device Type T-M

Breaker ID Main

Frame Size 400A

Breaker Type

MCB

Rating 250A

Inst

Manufacturer Eaton

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

HKD3400F

IAC Rating 100 kAIC 5-10X

Serial No CT Ratio 10X

Eaton BA 1

Panel Schedule

Panel ID 34L1A Section 1

General Panel Data

Power Source DPQ via 34T1 Floor First Floor

Main Breaker

Manufacturer Eaton Room B34-3

Model PRL1A Voltage 208V

IAC Rating 10 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

400A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 20A 20A 10 kAIC

DPQ via 34T1

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

ATS-2 (Normal) Eaton ED3175 3 1

Eaton BA 1 1

Panel Schedule

Panel ID 34L1A Section 2

General Panel Data

Power Source DPQ via 34T1 Floor First Floor

Main Breaker

Manufacturer Eaton Room B34-3

Model PRL1A Voltage 208V

IAC Rating 10 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

400A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB 175A 175A 65 kAIC

NCB 20A 20A 10 kAIC

ATS #6

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

DQP3B General Electric TED134150 3 1

Air Handler General Electric TEY 3 1

Med Air Comp General Electric TEY 3 1

Condensate Pump General Electric TEY 3 1

Ex Fan 7 General Electric TEY 3 1

Ex Fan 6 General Electric TEY 3 1

Med Vac Pump General Electric TEY 3 1MCB 60A 60A 14 kAIC

MCB 15A 15A 14 kAIC

15A 14 kAIC

MCB 30A 30A 14 kAIC

Panel Schedule

Panel ID

DQP3

General Panel Data

Power Source ATS #6 Floor 3rd Floor

Main Breaker

Manufacturer General Electric Room 3627

Model Spectra Voltage 480

IAC Rating 42 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

400A

Breaker Data

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Circuit ID Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

MCB 15A

60A 60A

Breaker Type

14 kAIC

Range Setting

MCB 150A 150A 14 kAIC

MCB 90A 90A 14 kAIC

MCB

Return Air Fan General Electric TEY 3 1

TVSS General Electric TEY 3 1

HW Pump 3 General Electric TEY 3 1

HW Pump 4 General Electric TEY 3 1

MCB 15A 15A 14 kAIC

MCB 60A 60A 14 kAIC

MCB 40A 40A 14 kAIC

15A 14 kAICMCB 15A

DPQ

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Chiller 1-CH-3 General Electric SFHA36AT0250 3 1

Spare General Electric TEY 3 1

CWP 1 General Electric TEY 3 1

Chiller Condenser General Electric TEY 3 1

CWP2 General Electric TEY 3 1MCB 20A 20A 14 kAIC

MCB 20A 20A 14 kAIC

MCB 30A 30A 14 kAIC

Range Setting

MCB 250A 175A 25 kAIC 515-1750A 1750A

MCB 100A 100A 14 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer General Electric Room 3627

Model Spectra Voltage 480V

IAC Rating 42 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

400A

Breaker Data

Panel Schedule

Panel ID

DQP3A

General Panel Data

Power Source DPQ Floor 3rd Floor

DQP3

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

EF-2 General Electric TEY 3 1

EF-5 General Electric TEY 3 1

EF-9 General Electric TEY 3 1

1-EF-24A General Electric TEY 3 1

AHU-23 General Electric TEY 3 1

T3 General Electric TEYD3125B 3 1

Temp Pwr Skid General Electric TEYD3125B 3 1

MCB 125A 125A 14 kAIC

MCB 30A 30A 14 kAIC

MCB 20A 20A 14 kAIC

MCB 15A 15A 14 kAIC

15A 14 kAIC

MCB 15A 15A 14 kAIC

Panel Schedule

Panel ID

DQP3B

General Panel Data

Power Source DQP3 Floor 3rd Floor

Main Breaker

Manufacturer General Electric Room 3667

Model AEF3422MT Voltage 480V

IAC Rating 14 kAIC

MCB 15A

Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB 125A 125A 14 kAIC

Booster Pump General Electric TEY 3 1

Return Air Fan General Electric TEY 3 1

RO System Skid General Electric TEY 3 1

AC1 General Electric TEY 3 1

AHU-24 General Electric TEY 3 1

1-EF-24A General Electric TEYD3020B 3 1

Culligan Sys Skid General Electric TEYD3015B 3 1

MCB 40A 40A 14 kAIC

MCB 20A 20A 14 kAIC

MCB 15A 15A 14 kAIC

MCB 15A 15A 14 kAIC

MCB 20A 20A 14 kAIC

MCB

MCB 15A 15A 14 kAIC

15A 15A 14 kAIC

DQP3B

Trip Device Type T-M

Breaker ID Main

Frame Size 200A

Breaker Type

MCB

Rating 200A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

TQD32200

IAC Rating 10 kAIC

Serial No CT Ratio

EF-4 General Electric THQB 3 1

QL3A General Electric THQB 3 1

Panel Schedule

Panel ID

QL3B

General Panel Data

Power Source DQP3B Floor 3rd Floor

Main Breaker

Manufacturer General Electric Room 3666

Model AQF3602ABX Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB 20A 20A 10 kAIC

MCB 60A 60A 10 kAIC

QL3B

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

General Electric THHQB 1 1

Panel Schedule

Panel ID

QL3A

General Panel Data

Power Source QL3B Floor 3rd Floor

Main Breaker

Manufacturer General Electric Room 3628

Model AQF3241MTX Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

125A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 20A 20A 22 kAIC

ATS #4 via CB Disc

Trip Device Type T-M

Breaker ID Main

Frame Size 400A

Breaker Type

MCB

Rating 300A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

TJJ436400

IAC Rating 30 kAIC 900-3000A

Serial No CT Ratio 3000A

1-SF-1 General Electric THED136020 3 1

1-EF-1 General Electric THED136015 3 1

1-PEF-1 General Electric THED136015 3 1

1-PEF-2 General Electric THED136015 3 1

1-P1 General Electric THED136040 3 1

1-EF General Electric THED136015 3 1

1-EF-13 General Electric THED136015 3 1

Panel Schedule

Panel ID

DNP1

General Panel Data

Power Source ATS #4 via CB Disc Floor 1st Floor

Main Breaker

Manufacturer General Electric Room 1632

Model Unknown Voltage 480V

IAC Rating Unknown Buss

(Copper, Aluminum, Bolt On, etc)

400A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB 20A 20A 25 kAIC

MCB 15A 15A 25 kAIC

MCB 15A 15A 25 kAIC

MCB 15A 15A 25 kAIC

MCB 40A 40A 25 kAIC

MCB 15A 15A 25 kAIC

MCB 15A 15A 25 kAIC

1-P2 General Electric THED136040 3 1

DNT1 General Electric THED136100 3 1MCB 100A 100A 25 kAIC

MCB 40A 40A 25 kAIC

DNP1

Trip Device Type T-M

Breaker ID Main

Frame Size 225A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

TFJ236225

IAC Rating 22 kAIC 1000-2250A

Serial No CT Ratio 2250A

1-SF4 General Electric THED136050 3 1

1-PEF7 General Electric THED136015 3 1

RF5 General Electric THED136015 3 1

1-DF5 General Electric THED136020 3 1

1-RF4 General Electric THED136015 3 1

1-PEF8 General Electric THED136015 3 1

SF5 General Electric THED136050 3 1

Panel Schedule

Panel ID

DNP2

General Panel Data

Power Source DNP1 Floor 2nd Floor

Main Breaker

Manufacturer General Electric Room 2638

Model NHB Voltage 480V

IAC Rating Unknown Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID

MCB 15A 15A 25 kAIC

MCB 50A 50A 25 kAIC

25 kAIC

Range Setting

25 kAIC

MCB 15A 15A 25 kAIC

MCB 20A 20A 25 kAIC

MCB 15A 15A 25 kAIC

MCB 50A 50A

MCB 15A 15A

DNT1

Trip Device Type T-M

Breaker ID Main

Frame Size 225A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

THQD32225

IAC Rating 22 kAIC

Serial No CT Ratio

General Electric THQB 1 1

Panel Schedule

Panel ID DNL1 Section 1

General Panel Data

Power Source DNT1 Floor 1st Floor

Main Breaker

Manufacturer General Electric Room 1632

Model Unknown Voltage 208V

IAC Rating 200 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 20A 20A 22 kAIC

DNL1 Section 1

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

General Electric THQB 1 1

Panel Schedule

Panel ID DNL1 Section 2

General Panel Data

Power Source DNL1 Section 1 Floor 1st Floor

Main Breaker

Manufacturer Unknown Room 1632

Model Unknown Voltage 208V

IAC Rating 10 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 20A 20A 10 kAIC

DNL1 Section 1

Trip Device Type T-M

Breaker ID Main

Frame Size 225A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

THQD32225

IAC Rating 22 kAIC

Serial No CT Ratio

General Electric THQB 1 1

Panel Schedule

Panel ID DNL2 Section 1

General Panel Data

Power Source DNL1 Section 1 Floor 2nd Floor

Main Breaker

Manufacturer General Electric Room 2638

Model AQF3422MBX Voltage 208V

IAC Rating 200 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 20A 20A 10 kAIC

DNL2 Section 1

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

General Electric TQHB 1 1

Panel Schedule

Panel ID DNL2 Section 2

General Panel Data

Power Source DNL2 Section 1 Floor 2nd Floor

Main Breaker

Manufacturer General Electric Room 2638

Model AQF3422MBX Voltage 208V

IAC Rating 200 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 20A 20A 22 kAIC

ATS #4

Trip Device Type T-M

Breaker ID Main

Frame Size 300A

Breaker Type

MCB

Rating 300A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

TJJ436300

IAC Rating 30 kAIC 900-3000A

Serial No CT Ratio 3000A

1-A2-SF General Electric TEY 3 1

1-A2-RF General Electric TEY 3 1

1-EF-2 General Electric TEY 3 1

1-PEF-3 General Electric TEY 3 1

1-PEF-4 General Electric TEY 3 1

1-PEF-17 General Electric TEY 3 1

1-PEF-18 General Electric TEY 3 1

Panel Schedule

Panel ID

ANP1

General Panel Data

Power Source ATS #4 Floor 1st Floor

Main Breaker

Manufacturer General Electric Room 1690

Model Unknown Voltage 480V

IAC Rating 100 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

Unknown

Br…