2022 GJ VA Triennial Electrical Vol2.pdf
PDF 10 MB Posted
- Solicitation number
- 36C25925Q0292
About this file
This document is a comprehensive Project Report - Volume 2 for an Arc Flash Hazard Analyses Project conducted at the Veterans Affairs Medical Center in Grand Junction, Colorado, covering the period from January to May 2022. The report details an extensive electrical system data validation process for multiple buildings, including Building 1 North, Building 1 South, Building 5, Building 8, Building 9, Building 13, Building 20, Building 35, Building 36, Building 39, and Building 45.
The data validation methodology involved multiple critical steps: reviewing electrical drawings (some not updated since 2009), performing field verifications to confirm circuit relationships, and capturing detailed dataplate and circuit characteristics for various electrical equipment types such as medium voltage substations, transformers, switches, protective relays, circuit breakers, generators, solar inverters, and motor control centers. The report includes comprehensive spreadsheets documenting equipment data by building and location, and supplemented the data gathering with thermographic and visual inspections of electrical system components. The project was performed under Contract No. 36C25922P006 in cooperation with Slocum & Associates, with the primary objective of ensuring accurate electrical system modeling for proper arc flash incident energy calculations and personnel safety assessment.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Report - Volume 2
January – May 2022
Arc Flash Hazard Analyses ProjectArc Flash Hazard Analyses Project
CoverCover
Veterans Affairs Medical Center Grand Junction, Colorado
CoverCover in cooperation with
Slocum & Associates
337 Sundance Trail
Liberty Hill, Texas 78642
P - (512)484-5594
845 Long Branch Circle
Sugar Hill, Georgia 30518
P - (678)546-9393, F – (678)828-5903
Arc Flash Hazard Analyses – Volume 2 Contract No. 36C25922P006
Veterans Affairs Medical Center
Grand Junction, Colorado January – May 2022
Section 1 Data Validation Overview
Section 2 Tabulated Datasheets (by location)
Table of Contents
1 | P a g e
Volume 2 Overview – Data Validation
Arc Flash Hazard Analyses Project, Contract No. 36C25922P006
Process
Data validation is a critical aspect of any arc flash study. Obtaining complete and accurate information is the only way to ensure the electrical system is properly modeled for performing necessary calculations and achieving the best results – proper arc flash incident energy calculations and their impact on personnel safety.
This segment provides the raw data incorporated obtained in modeling the electrical system for the coordination and arc flash phases at the Leavenworth VA Medical Center. The process to capture and verify electrical system data includes the following elements:
Electrical Drawings – a set of the most recent electrical drawings were provided by the VA. It should be noted the drawings had not been updated since 2009 or earlier. System upgrades or changes were documented as a part of this process.
Field Verification – was performed to verify accuracy of drawings and depicted circuit relationships.
Data Spreadsheets – were used to capture dataplate and other pertinent circuit characteristics for the following equipment items:
Medium Voltage Substations
Medium Voltage Transformers
Medium Voltage Sectionalizing Switches
Protective Relays
Circuit Breakers
Protective Relays
Switchboards/Panelboards
Generators
Solar Inverters
Disconnect Switches
Automatic Transfer Switches
Motor Control Centers/VFDs/Motors
Conductors and Lengths
Documentation
Contained in this volume are the above-referenced spreadsheets used to tabulate the data of the various equipment items by building or major location.
Slocum & Associates in cooperation with
2 | P a g e
Supplemental Action
Due to the invasive nature of the data gathering/validation phase, it is an ideal time to perform a thermographic (infrared) and visual inspection of the various electrical system components. This inspection was performed by Slocum personnel. A listing of the equipment inspected and documentation of noted thermal anomalies or issues has been provided in the test report for the electrical testing phase of this project.
Arc Flash Hazard Analyses Project, Contract No. 36C25922P006 Veterans Affairs Medical Center – Grand Junction, Colorado
Equipment Data Records
Enclosed are the various data records for each piece of equipment evaluated under this contract.
Equipment items have been grouped by location. Each major group is separated by a red divider page to distinguish the groups.
The groups are categorized as follows:
Building 1 North
Building 1 South
Building 5
Building 8
Building 9
Building 13
Building 20
Building 35
Building 36
Building 39
Building 45
Medium Voltage Equipment:
▪ MV Substation
▪ MV S&C Switches
▪ MV Oil Transformers
Location: Building 1N
Source Load Phases Neutral Ground Phases Neutral Ground
OPA Building Substation US2 MSA Switchboard 500 MCM 500 MCM 1/0 AWG 6 6 6 75'
OPA Building MSA PVOPA2 Disc Disconnect Switch 600 kCMIL 600 kCMIL 3/0 AWG 2 2 2 50'
OPA Building PVOPA2 Disc PVOPA2 Panelboard 600 kCMIL 600 kCMIL 3/0 AWG 2 2 2 20'
OPA Building PVOPA2 PVEL1 Panelboard 600 kCMIL 600 kCMIL 3/0 AWG 2 2 2 10'
OPA Building PVEL1 (Line Side) Inverter E1 Inverter 3/0 AWG 3/0 AWG 3/0 AWG 1 1 1 50'
OPA Building PVEL1 Inverter E1.3 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 25'
OPA Building PVEL1 Inverter E1.4 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 30'
OPA Building PVEL1 Inverter E4-1 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 35'
OPA Building PVEL1 Inverter E4-6 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 40'
OPA Building PVEL1 Inverter E4.2 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 15'
OPA Building PVEL1 PVEL2 Panelboard #6 AWG #6 AWG #8 AWG 1 1 1 15'
OPA Building PVEL1 PVEL1.1 Panelboard 1/0 AWG 1/0 AWG #6 AWG 1 1 1 10'
OPA Building PVEL1.1 Inverter 4-7 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 45'
OPA Building PVEL1.1 Inverter 4-8 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 50'
OPA Building PVEL1.1 Inverter 4-5 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 50'
OPA Building PVEL1.1 Inverter 4-4 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 45'
OPA Building PVEL1.1 Inverter 4-3 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 40'
OPA Building PVEL1.1 Inverter 4-7 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 35'
OPA Building PVEL1.1 Inverter 4-7 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 25'
OPA Building PVEL1.1 Inverter 4-7 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 20'
OPA Building PVEL1.1 Inverter 4-7 Inverter #6 AWG #6 AWG #8 AWG 1 1 1 20'
3rd Floor Roof MSA (PV AC Breaker) PVOPA1 Panelboard 2/0 AWG 2/0 AWG #2 AWG 1 1 1 60'
3rd Floor Roof PVOPA1 OPA-1 Inverter #8 AWG #8 AWG #8 AWG 1 1 1 5'
3rd Floor Roof PVOPA1 OPA-2 Inverter #8 AWG #8 AWG #8 AWG 1 1 1 10'
3rd Floor Roof PVOPA1 OPA-3 Inverter #8 AWG #8 AWG #8 AWG 1 1 1 15'
3rd Floor Roof PVOPA1 OPA-4 Inverter #8 AWG #8 AWG #8 AWG 1 1 1 20'
3rd Floor Roof PVOPA1 OPA-5 Inverter #8 AWG #8 AWG #8 AWG 1 1 1 25'
3rd Floor Roof PVOPA1 OPA-6 Inverter #8 AWG #8 AWG #8 AWG 1 1 1 30'
3rd Floor Roof PVOPA1 OPA-7 Inverter #8 AWG #8 AWG #8 AWG 1 1 1 35'
3rd Floor Roof MSA NP3 (MSA) Distribution Panel 4/0 AWG 4/0 AWG #2 AWG 1 1 1 20'
- NP3 (MSA) ANP3 (NIS) Panelboard #4 AWG #4 AWG #8 AWG 1 1 1 -
3628 MSA DNP3 Panelboard 500 kCMIL 500 kCMIL #1 AWG 1 1 1 40'
1635 MSA ATS #6 Panelboard 500 kCMIL 500 kCMIL #1 AWG 1 1 1 25'
1634 MSA ATS #1 Automatic Transfer Sw 4/0 AWG 4/0 AWG #2 AWG 1 1 1 30'
Cable Schedule
Power Qty Location Equipment Type
Size Type Distance
Building 1 North - Cables
1635 MSA ATS #4 Automatic Transfer Sw 500 kCMIL 500 kCMIL #1 AWG 1 1 1 15'
1634 MSA ATS #3 Automatic Transfer Sw 500 kCMIL 500 kCMIL #1 AWG 1 1 1 25'
1635 MSA ATS #7 Automatic Transfer Sw 500 kCMIL 500 kCMIL #1 AWG 1 1 1 25'
1634 MSA ATS #2 Automatic Transfer Sw 350 kCMIL 350 kCMIL #1 AWG 2 2 2 25'
Outside MSA PPCV1 Panelboard 350 kCMIL 350 kCMIL #1 AWG 2 2 2 125'
Outside PPCV1 Temp Chiller Chiller 350 kCMIL 350 kCMIL #1 AWG 2 2 2 25'
Outside PPCV1 TPP1 LV Dry-Type Transformer #10 AWG #10 AWG #10 AWG 1 1 1 5'
Outside TPP1 PP1 Panelboard #2 AWG #2 AWG #8 AWG 1 1 1 5'
1635 MSA TVSS TVSS #6 AWG #6 AWG #6 AWG 1 1 1 10'
3015 MP3 (NP3 om Dwg) ANP3 (NIS) Panelboard Not in Service -
3608 DNP3 NP3 (DNP3) Panelboard #6 AWG #6 AWG #10 AWG 1 1 1 175'
3667 DNP3 DN3 Panelboard #1 AWG #1 AWG #8 AWG 1 1 1 180'
3628 DNP3 T4 LV Dry-Type Transformer 2/0 AWG 2/0 AWG #6 AWG 1 1 1 55'
3628 T4 DNL3 Panelboard 500 kCMIL 500 kCMIL #1 AWG 1 1 1 65'
3628 DNL3 NL3A Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 20'
3666 DNL3 NL3B Section 1 Panelboard #1 AWG #1 AWG #6 AWG 1 1 1 175'
3666 NL3B Section 1 NL3B Section 2 Panelboard #1 AWG #1 AWG #6 AWG 1 1 1 5'
3608 DNL3 NL3C Section 1 Panelboard #1 AWG #1 AWG #6 AWG 1 1 1 100'
3608 NL3C Section 1 NL3C Section 2 Panelboard #1 AWG #1 AWG #6 AWG 1 1 1 105'
3628 DNP3 T2 LV Dry-Type Transformer #1 AWG #1 AWG #6 AWG 1 1 1 50'
3628 T2 DNL3A Panelboard 350 MCM 350 MCM #1 AWG 1 1 1 55'
3640 DNL3A OR1 Panelboard #6 AWG #6 AWG #8 AWG 1 1 1 90'
3641 DNL3A OR2 Panelboard #6 AWG #6 AWG #8 AWG 1 1 1 70'
3642 DNL3A OR3 Panelboard #6 AWG #6 AWG #8 AWG 1 1 1 120'
3643 DNL3A OR4 Panelboard #6 AWG #6 AWG #8 AWG 1 1 1 110'
1635 ATS #2 DPQ Distribution Panel #8 AWG #8 AWG #10 AWG 1 1 1 40'
3014 DPQ AEQP3 Panelboard #4 AWG #4 AWG #8 AWG 1 1 1 75'
0022 DPQ DQPB Panelboard 350 MCM 350 MCM #4 AWG 1 1 1 25'
B34-3 DPQ 34H1A Panelboard #4 AWG #4 AWG #8 AWG 1 1 1 50'
B34-3 DPQ 34T1 Disc Disconnect Switch #4 AWG #4 AWG #8 AWG 1 1 - 180'
B34-3 34T1 Disc 34T1 LV Dry-Type Transformer #2 AWG #2 AWG - 1 1 - 15'
B34-3 34T1 34L1A Section 1 Panelboard 3/0 AWG 3/0 AWG #6 AWG 2 2 2 25'
B34-3 34L1A Section 1 34L1A Section 2 Panelboard 3/0 AWG 3/0 AWG #6 AWG 2 2 2 5'
B34-3 34L1A Section 2 ATS-UPS (Normal) Automatic Transfer Sw 3/0 AWG 3/0 AWG #6 AWG 1 1 1 10'
B34-3 EDP1 (Bldg 1S) ATS-UPS (Emergency) Automatic Transfer Sw 3/0 AWG 3/0 AWG #6 AWG 1 1 1 15'
IT Room ATS-UPS (Normal) UPS UPS 3/0 AWG 3/0 AWG #6 AWG 1 1 1 75'
0022 DQPB DQTB LV Dry-Type Transformer #8 AWG #8 AWG #10 AWG 1 1 1 10'
0022 DQPB DQLB Panelboard #2 AWG #2 AWG #6 AWG 1 1 1 5'
0022 DQPB Elevator S5 Disc Disconnect Switch #4 AWG #4 AWG #6 AWG 1 1 1 30'
0022 Elevator S5 Disc Elevator S5 Disc Controller #4 AWG #4 AWG #6 AWG 1 1 1 10'
0022 DQPB Elevator P3 Disc Disconnect Switch #4 AWG #4 AWG #6 AWG 1 1 1 20'
0022 Elevator P3 Disc Elevator P3 Disc Controller #4 AWG #4 AWG #6 AWG 1 1 1 10'
0022 DQPB EUH-1 Heater #12 AWG #12 AWG #12 AWG 1 1 1 30'
1633 DPQ DQP1 Panelboard #4 AWG #4 AWG #8 AWG 1 1 1 50'
1633 DPQ TVSS TVSS #8 AWG #8 AWG #8 AWG 1 1 1 5'
2639 DQP1 DQP2 Panelboard #4 AWG #4 AWG #8 AWG 1 1 1 40'
1633 DQP1 DQT1 LV Dry-Type Transformer #12 AWG #12 AWG #12 AWG 1 1 1 15'
1633 DQT1 DQL1 Panelboard #10 AWG #10 AWG #8 AWG 1 1 1 15'
Roof Mech Rm, 2600 DPQ BQP2 Panelboard #4 AWG #4 AWG #8 AWG 1 1 1 100'
1689 DPQ AQP1 Panelboard 2/0 AWG 2/0 AWG #6 AWG 1 1 1 200'
1634 DPQ PSEG Panelboard #4 AWG #4 AWG #8 AWG 1 1 1 25'
1634 PSEG TSEG Panelboard #8 AWG #8 AWG #10 AWG 1 1 1 5'
1634 TSEG LSEG Panelboard #2 AWG #2 AWG #8 AWG 1 1 1 5'
3627 DPQ DQP3A Panelboard 350 kCMIL 350 kCMIL 1/0 AWG 1 1 1 65'
3627 DQP3A Chiller 1-CH-3 Motor/VFD 2/0 AWG 2/0 AWG #6 AWG 1 1 1 60'
3627 DQP3A CWP 1-P1 Motor/VFD #12 AWG #12 AWG #12 AWG 1 1 1 40'
3627 DQP3A CWP 1-P2 Motor/VFD #12 AWG #12 AWG #12 AWG 1 1 1 40'
3627 DQP3A Chiller Cond 1-CU-1 Motor/VFD #8 AWG #8 AWG #10 AWG 1 1 1 40'
3627 ATS #6 DPQ3 Panelboard 500 kCMIL 500 kCMIL #1 AWG 1 1 1 30'
3627 DPQ3 DQP3B Panelboard 1/0 AWG 1/0 AWG #6 AWG 1 1 1 180'
3627 DPQ3 TVSS TVSS #8 AWG #8 AWG #10 AWG 1 1 1 10'
3666 DPQ3B T3 Disc Disconnect Switch #1 AWG #1 AWG #6 AWG 1 1 1 35'
3666 T3 Disc T3 LV Dry-Type Transformer #1 AWG #1 AWG #6 AWG 1 1 1 5'
3666 T3 QL3B Panelboard 3/0 AWG 3/0 AWG #4 AWG 1 1 1 10'
3628 QL3B QL3A Panelboard #6 AWG #6 AWG #10 AWG 1 1 1 170'
1635 ATS #4 DNP1 Disc CB Disconnect Switch 300 MCM 300 MCM #2 AWG 1 1 1 10'
1632 DNP1 Disc DNP1 Panelboard 500 MCM 500 MCM #2 AWG 1 1 1 60'
2638 DNP1 Disc DNP2 Panelboard 500 MCM 500 MCM #2 AWG 1 1 1 30'
1632 DNP1 DNT1 LV Dry-Type Transformer #2 AWG #2 AWG #6 AWG 1 1 1 15'
1632 DNT1 DNL1 Section 1 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 20'
1632 DNL1 Section 1 DNL1 Section 2 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 5'
2638 DNL1 Section 2 DNL2 Section 1 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 30'
2638 DNL2 Section 1 DNL2 Section 2 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 5'
1635 ATS #4 ANP1 CB Disconnect Switch 300 MCM 300 MCM #2 AWG 1 1 1 190'
1690 ANP1 ANP1 Panelboard 500 MCM 500 MCM #1 AWG 2 2 2 10'
2664 ANP1 ANP2 Panelboard 500 MCM 500 MCM #2 AWG 2 2 2 35'
1690 ANP1 ANT1 LV Dry-Type Transformer #2 AWG #2 AWG #8 AWG 1 1 1 15'
1690 ANT1 ANL1 Section 1 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 15'
1690 ANL1 Section 1 ANL1 Section 2 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 5'
2664 ANT1 ANL2 Section 1 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 35'
2664 ANL2 Section 1 ANL2 Section 2 Panelboard 4/0 AWG 4/0 AWG #3 AWG 1 1 1 5'
1635 ATS #1 DPLS Distribution Panel 3/0 AWG 3/0 AWG #6 AWG 1 1 1 30'
1632 DPLS DLP1 Panelboard #6 AWG #6 AWG #10 AWG 1 1 1 65'
1632 DLP1 DLT2 Disc Disconnect Switch #12 AWG #12 AWG #12 AWG 1 1 1 35'
1632 DLT2 Disc DLT2 LV Dry-Type Transformer #10 AWG #10 AWG #10 AWG 1 1 1 5'
2638 DLT2 DLL2 Panelboard #10 AWG #10 AWG #6 AWG 1 1 1 20'
1600 DPLS CLP1 Panelboard #6 AWG #6 AWG #10 AWG 1 1 1 130'
1600 CLP1 CLT1 LV Dry-Type Transformer #12 AWG #12 AWG #12 AWG 1 1 1 20'
1600 CLT1 CLL1 Panelboard #10 AWG #10 AWG #6 AWG 1 1 1 15'
2604 CLL1 CLL2 Panelboard #8 AWG #8 AWG #10 AWG 1 1 1 30'
1690 DPLS ALP1 Panelboard #6 AWG #6 AWG #10 AWG 1 1 1 200'
1690 ALP1 ALT2 Disc Disconnect Switch #8 AWG #8 AWG #10 AWG 1 1 1 30'
2664 ALT2 Disc ALT2 Disc LV Dry-Type Transformer #8 AWG #8 AWG #10 AWG 1 1 1 5'
2664 ALT2 ALL2 Panelboard #10 AWG #10 AWG #6 AWG 1 1 1 20'
3628 DPLS LP3 Panelboard #6 AWG #6 AWG #10 AWG 1 1 1 55'
3666 LP3 T1 Disc. Disconnect Switch #10 AWG #10 AWG #10 AWG 1 1 1 195'
3666 T1 Disc. T1 LV Dry-Type Transformer #10 AWG #10 AWG #10 AWG 1 1 1 5'
3666 T1 LL3 Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 20'
1635 DPLS TVSS TVSS #6 AWG #6 AWG #10 AWG 1 1 1 5'
1635 ATS #3 DPC Distribution Panel 500 MCM 500 MCM #4 AWG 1 1 1 40'
2638 DPC DCP2 Panelboard #2 AWG #2 AWG #6 AWG 1 1 1 80'
2638 DCP2 DCT2 LV Dry-Type Transformer 1/0 AWG 1/0 AWG #6 AWG 1 1 1 20'
2638 DCT2 DCL2 Panelboard 1/0 AWG 1/0 AWG #6 AWG 1 1 1 20'
1632 DCT2 DCL1 Panelboard 1/0 AWG 1/0 AWG #6 AWG 1 1 1 30'
1600 DPC CCP1 Panelboard #1 AWG #1 AWG #6 AWG 1 1 1 125'
1600 CCP1 CCT1 LV Dry-Type Transformer #6 AWG #6 AWG #10 AWG 1 1 1 20'
1600 CCT1 CCL1 Panelboard 1/0 AWG 1/0 AWG #6 AWG 1 1 1 20'
1004 CCT1 BCL1 Panelboard 2/0 AWG 2/0 AWG #6 AWG 1 1 1 30'
2604 DPC CCP2 Panelboard #2 AWG #2 AWG #6 AWG 1 1 1 135'
2604 CCP2 CCT2 LV Dry-Type Transformer #8 AWG #8 AWG #10 AWG 1 1 1 20'
2604 CCT2 Splice Splice #2 AWG #2 AWG #8 AWG 1 1 1 5'
2604 Splice CCL2 Panelboard #2 AWG #2 AWG #8 AWG 1 1 1 30'
2602 Splice BCL2 Panelboard #2 AWG #2 AWG #8 AWG 1 1 1 15'
2664 DPC ACP2 Panelboard #2 AWG #2 AWG #6 AWG 1 1 1 205'
2664 ACP2 ACT2 LV Dry-Type Transformer #6 AWG #6 AWG #10 AWG 1 1 1 20'
2664 ACT2 ACL2 Panelboard 1/0 AWG 1/0 AWG #6 AWG 1 1 1 15'
1690 ACT2 ACL1 Panelboard 1/0 AWG 1/0 AWG - 1 1 - 35'
2664 DPC TVSS TVSS #8 AWG #8 AWG #8 AWG 1 1 1 10'
3608 DPC DCP3 Panelboard 350 MCM 350 MCM #2 AWG 1 1 1 135'
3608 DCP3 CP3 Panelboard #6 AWG #6 AWG #10 AWG 1 1 1 15'
3627 DCP3 T6 LV Dry-Type Transformer 2/0 AWG 2/0 AWG #6 AWG 1 1 1 105'
3608 DCP3 T5 LV Dry-Type Transformer #2 AWG #2 AWG #6 AWG 1 1 1 20'
3627 T6 DCL3 Panelboard 500 kCMIL 500 kCMIL #3 AWG 1 1 1 20'
3643 DCL3 OR4A Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 50'
3642 DCL3 OR3A Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 50'
3641 DCL3 OR2A Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 50'
3640 DCL3 OR1A Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 50'
3608 T5 DCL3A Panelboard 350 kCMIL 350 kCMIL #4 AWG 1 1 1 15'
3628 DCL3A CL3A Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 95'
3666 DCL3A CL3B Panelboard #3 AWG #3 AWG #8 AWG 1 1 1 120'
3608 DCL3A CL3C Section 1 Panelboard #3 AWG #3 AWG #6 AWG 1 1 1 25'
3608 CL3C Section 1 CL3C Section 2 Panelboard #3 AWG #3 AWG #6 AWG 1 1 1 5'
1635 ATS #7 CNP1 Disc CB Disconnect Switch 500 MCM 500 MCM #2 AWG 1 1 1 115'
1600 CNP1 Disc CNP1 Panelboard 500 MCM 500 MCM #2 AWG 1 1 1 10'
1600 CNP1 CNT1 LV Dry-Type Transformer #2 AWG #2 AWG #8 AWG 1 1 1 15'
1600 CNT1 CNL1 Panelboard 4/0 AWG 4/0 AWG #2 AWG 1 1 1 20'
1004 CNT1 BNL1 Section 1 Panelboard 4/0 AWG 4/0 AWG #6 AWG 1 1 1 25'
1004 BNL1 Section 1 BNL1 Section 2 Panelboard 4/0 AWG 4/0 AWG #6 AWG 1 1 1 5'
2604 ATS #7 CNP2 Disc CB Disconnect Switch 500 MCM 500 MCM #2 AWG 1 1 1 130'
1635 CNP2 Disc CNP2 Panelboard 500 MCM 500 MCM #2 AWG 1 1 1 10'
2604 CNP2 CNT2 LV Dry-Type Transformer #2 AWG #2 AWG #8 AWG 1 1 1 5'
2604 CNT2 CNL2 Panelboard 4/0 AWG 4/0 AWG #2 AWG 1 1 1 25'
2602 CNL2 BNL2 Section 1 Panelboard 4/0 AWG 4/0 AWG #2 AWG 1 1 1 25'
2602 BNL2 Section 1 BNL2 Section 2 Panelboard 4/0 AWG 4/0 AWG #2 AWG 1 1 1 5'
Generator Room Generator EDP2 Switchboard 500 MCM 500 MCM #4 AWG 5 5 5 150'
1635 EDP2 ATS #5 (NRAD) Automatic Transfer Sw 500 kCMIL 500 kCMIL 1/0 AWG 1 1 1 30'
1635 EDP2 ATS #6 Automatic Transfer Sw 500 kCMIL 500 kCMIL #1 AWG 1 1 1 30'
1635 EDP2 ATS #7 Automatic Transfer Sw 500 kCMIL 500 kCMIL #1 AWG 1 1 1 30'
1635 EDP2 ATS #4 Automatic Transfer Sw 500 kCMIL 500 kCMIL #1 AWG 1 1 1 30'
1634 EDP2 ATS #2 Automatic Transfer Sw 350 kCMIL 350 kCMIL #1 AWG 2 2 2 30'
1634 EDP2 ATS #1 Automatic Transfer Sw 4/0 AWG 4/0 AWG #2 AWG 1 1 1 30'
1634 EDP2 ATS #3 Automatic Transfer Sw 500 kCMIL 500 kCMIL #1 AWG 1 1 1 30'
1635 ATS #5 (NRAD) NRAD Distribution Panel 3/0 AWG 3/0 AWG #4 AWG 2 2 2 35'
Outside Temp Generator EDP2 Switchboard 600 kCMIL 600 kCMIL 1/0 AWG 4 4 4 75'
Outside NRAD MRI Trailer Disc Disconnect Switch 2/0 AWG 2/0 AWG 2/0 AWG 1 1 1 50'
2610 NRAD CAT Scan T-DAT2 CB Disconnect Switch 250 MCM 250 MCM 1/0 AWG 1 1 1 115'
2613-15 NRAD GE Fluoroscopy Panelboard 1/0 AWG 1/0 AWG #2 AWG 1 1 1 135'
2420 NRAD Phillips Xray CB Disconnect Switch 3/0 AWG 3/0 AWG 3/0 AWG 1 1 1 165'
2415 NRAD Toshiba Xray CB Disconnect Switch 3/0 AWG 3/0 AWG 3/0 AWG 1 1 1 145'
2415 NRAD Xray CB Disconnect Switch #4 AWG #4 AWG #4 AWG 1 1 1 145'
2405 NRAD Fluoroscopy CB Disconnect Switch 1/0 AWG 1/0 AWG 1/0 AWG 1 1 1 145'
Outside T6 ATS #5 (NRAD) Disc Disconnect Switch 500 kCMIL 500 kCMIL 1/0 AWG 1 1 1 75'
Outside ATS #5 (NRAD) Disc ATS #5 (NRAD) Automatic Transfer Sw 500 kCMIL 500 kCMIL 1/0 AWG 1 1 1 10'
2613 GE Fluoroscopy PD1 PDU #2 AWG #2 AWG #4 AWG 1 1 1 10'
2613 GE Fluoroscopy PDU UPS #12 AWG #12 AWG #10 AWG 1 1 1 15'
Location: Building 1 North
Load ID Substation US2
Trip Device Type MicroLogic 6.0P
Breaker ID Main
Frame Size 16--A
Breaker Type
ICB
Rating 1600A
Inst
Manufacturer Square D
Poles 1600A
Current Time Delay Current Time Delay Current Current Time Delay
Model
RK1600
IAC Rating 65 kIAC .4-1X .5-24s 1.5-10X .1-.4s 2-15X - -
Serial No CT Ratio 1X .5s 1.5X .1s On 2X A .1s On
Load ID Main
Trip Device Type MicroLogic 3-3S
Breaker ID
DNP3
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
LJ400
IAC Rating 65 kAIC 125-400A 1.5-10s - - 1.5-12X - -
Serial No CT Ratio 400A 1s - - 1.5X - -
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Feeder Breaker #1
Range
Settings
Equipment ID MSA
General Switchboard Data
Power Source Substation US2/PVOPA2 Floor OPA Building
Manufacturer Square D Room 1635
Model QED Voltage 480V
Long Time
IAC Rating Unknown Buss
(Copper or Aluminum)
160A
Switchboard Breaker Data
Short Time Ground Fault
Range
Settings
Switchboard Schedule
Main Breaker #1
Trip Device Settings (as found)
Building 1 North - LV Swbds
Main
Trip Device Type MicroLogic 3-3S
Breaker ID
ATS-6
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
LJ400
IAC Rating 65 kAIC 125-400A 1.5-10s - - 1.5-12X - -
Serial No CT Ratio 400A 1s - - 1.5X - -
Load ID Main
Trip Device Type MicroLogic 3-3S
Breaker ID
PPCV1
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
LJ400
IAC Rating 65 kAIC 125-400A 1.5-10s - - 1.5-12X - -
Serial No CT Ratio 400A 1s - - 1.5X - -
Load ID Main
Trip Device Type MicroLogic 3-3S
Breaker ID
ATS-7
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
LJ400
IAC Rating 65 kAIC 125-400A 1.5-10s - - 1.5-12X - -
Serial No CT Ratio 300A 1s - - 1.5X - -
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Feeder Breaker #3
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Feeder Breaker #2
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Feeder Breaker No. 4
Trip Device Settings (as found)
Miscellaneous Information Electrical or Manual Operation? (E or M)
Trip Device Type MicroLogic 3-3S
Breaker ID
ATS-4
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
LJ400
IAC Rating 65 kAIC 125-400A 1.5-10s - - 1.5-12X - -
Serial No CT Ratio 400A 1s - - 1.5X - -
Load ID Main
Trip Device Type MicroLogic 5.0
Breaker ID
ATS-2
Frame Size 800A
Breaker Type
MCB
Rating 800A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
PK800
IAC Rating 50 kAIC .4-1X .5-24s 1.5-10X .1-.4s 2-15X - -
Serial No CT Ratio .7s .5s 1.5s .1s On 2X - -
Load ID Main
Trip Device Type MicroLogic 3-3S
Breaker ID
ATS-3
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
LJ400
IAC Rating 65 kAIC 125-400A 1.5-10s - - 1.5-12X - -
Serial No CT Ratio 400A 6s - - 10X - -
Feeder Breaker No. 7
Trip Device Settings (as found)
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Feeder Breaker No. 5
Trip Device Settings (as found)
Feeder Breaker No. 6
Trip Device Settings (as found)
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Trip Device Type MicroLogic 3-2S
Breaker ID
TVSS
Frame Size 150A
Breaker Type
MCB
Rating 150A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
HJ150
IAC Rating 65 kAIC 35-100A 1.5-10s - - 1.5-12X - -
Serial No CT Ratio 60A 1s - - 1.5X - -
Load ID Main
Trip Device Type MicroLogic 3-2S
Breaker ID Spare
Frame Size 250A
Breaker Type
MCB
Rating 250A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
JJ250
IAC Rating 65 kAIC 70-250A 1.5-10s - - 1.5-12X - -
Serial No CT Ratio 250A 1s - - 1.5X - -
Load ID Main
Trip Device Type T-M
Breaker ID
ATS-1
Frame Size 150A
Breaker Type
MCB
Rating 150A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
HJ150
IAC Rating 65 kAIC - - - - Fixed - -
Serial No CT Ratio
- - - - 1300A - -
Feeder Breaker No. 8
Trip Device Settings (as found)
Feeder Breaker No. 9
Trip Device Settings (as found)
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Feeder Breaker No. 10
Trip Device Settings (as found)
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Trip Device Type MicroLogic 3-3S
Breaker ID
NP3 (MSA)
Frame Size 250A
Breaker Type
MCB
Rating 250A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
JJ250
IAC Rating 65 kAIC 70-250A 1.5-10s - - 1.5-12X - -
Serial No CT Ratio 250A 1s - - 1.5X - -
Load ID Main
Trip Device Type MicroLogic 3-3S
Breaker ID
PV AC
Frame Size 250A
Breaker Type
MCB
Rating 250A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
JJ250
IAC Rating 65 kAIC 70-250A 1.5-10s - - 1.5-12X - -
Serial No CT Ratio 200A 1s - - 1.5X - -
Feeder Breaker No. 11
Trip Device Settings (as found)
Feeder Breaker No. 12
Trip Device Settings (as found)
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Location: Building 1 North
Generator
Trip Device Type
ETU 545
Breaker ID Main
Frame Size 1600A
Breaker Type
MCB
Rating 1600A
Inst
Manufacturer Siemens
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
NPX3U160
IAC Rating 35 kAIC 700-1600A - - - 1.5-8X - -
Serial No CT Ratio 1600A - - - 6X @ .2s Off - -
Load ID Main
Trip Device Type
ETU 545
Breaker ID
ATS #1
Frame Size 250A
Breaker Type
MCB
Rating 250A
Inst
Manufacturer Siemens
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
NFX3U250
IAC Rating 35 kAIC 70-250A - - - 2-10X - -
Serial No CT Ratio 150A - - - 10X @ .5s Off - -
Manufacturer Siemens Room Generator Room
Model SB3 Voltage 480V
Switchboard Schedule
Equipment ID EDP2
General Switchboard Data
Power Source Generator Floor 1st Floor
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
IAC Rating Unknown Buss
(Copper or Aluminum)
1600A
Switchboard Breaker Data
Main Breaker #1
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Feeder Breaker #1
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Trip Device Type
ETU 545
Breaker ID
ATS #3
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer Siemens
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
NJX3U400
IAC Rating 35 kAIC 150-400A - - 2-10X - -
Serial No CT Ratio 400A - - 10X @ .1s Off - -
Load ID Main
Trip Device Type
ETU 545
Breaker ID
ATS #7
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer Siemens
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
NJX3U400
IAC Rating 35 kAIC 150-400A - - 2-10X - -
Serial No CT Ratio 400A - - 10X @ .1s Off - -
Load ID Main
Trip Device Type
ETU 545
Breaker ID
ATS #5
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer Siemens
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
NJX3U400
IAC Rating 35 kAIC 150-400A - - 2-10X - -
Serial No CT Ratio 400A - - 10X @ .1s Off - -
Feeder Breaker #2
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Feeder Breaker #3
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Feeder Breaker No. 4
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Trip Device Type
ETU 545
Breaker ID
ATS #6
Frame Size 600A
Breaker Type
MCB
Rating 600A
Inst
Manufacturer Siemens
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
HLK3U600
IAC Rating 35 kAIC 200-600A - - 2-10X - -
Serial No CT Ratio 600A - - 8X @ .1s Off - -
Load ID Main
Trip Device Type
ETU 545
Breaker ID
ATS #2
Frame Size 600A
Breaker Type
MCB
Rating 600A
Inst
Manufacturer Siemens
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
HLK3U600
IAC Rating 35 kAIC 200-600A - - 2-10X - -
Serial No CT Ratio 600A - - 8X @ .1s Off - -
Load ID Main
Trip Device Type
ETU 555
Breaker ID Quick Disconnect
Frame Size 1200A
Breaker Type
MCB
Rating 1200A
Inst
Manufacturer Siemens
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
NNX3V120
IAC Rating 35 kAIC 700-1200A - - - 2-10X - -
Serial No CT Ratio 700A 10s - - 10X @ 0s Off - -
Feeder Breaker No. 5
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Feeder Breaker No. 6
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Feeder Breaker No. 7
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
ATS #2
Trip Device Type MicroLogic 3.3
Breaker ID Main
Frame Size 600A
Breaker Type
MCB
Rating 600A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
LG600
IAC Rating 35 kAIC 200-600A 1.5-10s - - 1.5-11X - -
Serial No CT Ratio 600A 2.5s - - 1.5X - -
34T1 Square D BG100 3 1
BQP2 Square D BG100 3 1
34H1A Square D BG100 3 1
DQP1 Square D BG100 3 1
AQP1 Square D JG250 3 1
PSEG Square D BG70 3 1
DQPB Square D LA300A 3 1
1000A
MCB 300A 300A 30 kAIC 1500-3000A 1500A
MCB 70A 70A 35 kAIC
875-1250A 875A
MCB 100A 100A 35 kAIC 1250A
MCB 250A 175A 35 kAIC
35 kAIC 1250A
MCB 100A 100A 35 kAIC
Manufacturer Square D Room 1635
Circuit ID
MCB 100A 100A 35 kAIC 1250A
1250A
MCB 100A 100A
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty Range Setting
600A
Breaker Data
Main Breaker
Distribution Panel Schedule
Panel ID
DPQ
General Panel Data
Power Source ATS #2 Floor 1st Floor
Branch Breaker Data
Trip Device Settings (as found)
Model HCP Voltage 480V
Long Time Short Time Ground Fault
Range
Settings
IAC Rating 200 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
Building 1 North - Distribution Panels
1EQP3 Square D BG100 3 1
TVSS Square D BG60 3 1
1250A
MCB 60A 60A 35 kAIC
MCB 100A 100A 35 kAIC
ATS #1
Trip Device Type T-M
Breaker ID Main
Frame Size 250A
Breaker Type
NCB
Rating 250A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
JG250
IAC Rating 35 kAIC 1125-2250A
Serial No
CT Ratio 1125A
DLP1 Square D EDB34050 3 1
ALP1 Square D EDB34060 3 1
TVSS Square D EDB34060 3 1
LP3 Square D EDB34060 3 1
CLP1 Square D EDB34060 3 1
Distribution Panel Schedule
Panel ID
DPLS
General Panel Data
Power Source ATS #1 Floor 1st Floor
Main Breaker
Manufacturer Square D Room 1635
Model NF Voltage 480V
IAC Rating 200 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
MCB 50A 50A 18 kAIC
Qty Range Setting
MCB 60A 60A 18 kAIC
60A 18 kAIC
MCB 60A 60A 18 kAIC
MCB 60A 60A 18 kAIC
MCB 60A
ATS #3
Trip Device Type
ET1.0
Breaker ID Main
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
MG400
IAC Rating 35 kAIC 2-10X
Serial No CT Ratio 2X
CCP2 Square D BG100 3 1
DCP2 Square D BG100 3 1
DCP3 Square D JG250 3 1
CCP1 Square D BG125 3 1
ACP2 Square D BG100 3 1
TVSS Square D BG60 3 1
Distribution Panel Schedule
Panel ID
DPC
General Panel Data
Power Source ATS #3 Floor 1st Floor
Main Breaker
Manufacturer Square D Room 1634
Model HCP Voltage 480V
IAC Rating 299 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
400A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
MCB 250A
Branch Breaker Data
Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
MCB 125A 125A 35 kAIC
MCB 100A 100A 35 kAIC
1250A
Qty Range Setting
1250A
1250A
MCB 100A 100A 35 kAIC
250A 35 kAIC 1250-2500A 1250A
MCB 60A 60A 35 kAIC 800A
MCB 100A 100A 35 kAIC 1250A
DPQ
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
1-EF-15 Square D EGB34015 3 1
EF-10 Square D EGB34020 3 1
1-A-13R Square D EGB34020 3 1
1-A-13S Square D EGB34060 3 1
1-EF-14 Square D EGB34015 3 1
Panel Schedule
Panel ID
AEQP3
General Panel Data
Power Source DPQ Floor 3rd Floor
Main Breaker
Manufacturer Square D Room 3014
Model NF Voltage 480V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
125A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID Range Setting
MCB 15A 15A 35 kAIC
MCB 20A 20A 35 kAIC
MCB 20A 20A 35 kAIC
MCB 60A 60A 35 kAIC
MCB 15A 15A 35 kAIC
Building 1 North- Panels
DPQ
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
DQTB General Electric TEYD3040B 3 1
Elevator S5 General Electric TED34150 3 1
Elevator P3 General Electric TED34150 3 1
EUH-1 General Electric TEYD3015B 3 1
Panel Schedule
Panel ID
DQPB
General Panel Data
Power Source DPQ Floor Basement
Main Breaker
Manufacturer General Electric Room 0022
Model AEF3304MBX Voltage 480V
IAC Rating 18 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
40)A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID Range Setting
MCB 40A 40A 25 kAIC
MCB 150A 150A 18 kAIC
MCB 150A 150A 18 kAIC
MCB 15A 15A 18 kAIC
DPQ
Trip Device Type T-M
Breaker ID Main
Frame Size 90A
Breaker Type
MCB
Rating 90A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
THQB
IAC Rating 22 kAIC
Serial No CT Ratio
General Electric THQB 1 1
Panel Schedule
Panel ID
DQLB
General Panel Data
Power Source DPQ Floor Basement
Main Breaker
Manufacturer General Electric Room 0022
Model Unknown Voltage 208V
IAC Rating Unknown Buss
(Copper, Aluminum, Bolt On, etc)
Unknown
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty Range Setting
MBC 20A 20A 22 kAIC
DPQ
Trip Device Type T-M
Breaker ID Main
Frame Size 100A
Breaker Type
MCB
Rating 100A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
TEY
IAC Rating 14 kAIC
Serial No CT Ratio
Misc General Electric TEY 1 1
DQT1 General Electric TEY 1 1
Panel Schedule
Panel ID
DQP1
General Panel Data
Power Source DPQ Floor 1st Floor
Main Breaker
Manufacturer General Electric Room 1633
Model Unknown Voltage 480V
IAC Rating 100 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
Unknown
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID Range Setting
MCB 20A 20A 14 kAIC
MCB 15A 15A 14 kAIC
DQP1
Trip Device Type T-M
Breaker ID Main
Frame Size 50A
Breaker Type
MCB
Rating 50A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
TEY
IAC Rating 14 kAIC
Serial No CT Ratio
1-P3 General Electric TEY 3 1
1-P5 General Electric TEY 3 1
1-P4 General Electric TEY 3 1
1-P6 General Electric TEY 3 1
Panel Schedule
Panel ID
DQP2
General Panel Data
Power Source DQP1 Floor 2nd Floor
Main Breaker
Manufacturer General Electric Room 2639
Model AEF3301BBX Voltage 480V
IAC Rating 100 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
125A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID Range Setting
MCB 20A 20A 14 kAIC
MCB 15A 15A 14 kAIC
MCB 20A 20A 14 kAIC
MCB 15A 15A 14 kAIC
DQT1
Trip Device Type T-M
Breaker ID Main
Frame Size 30A
Breaker Type
MCB
Rating 30A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
THQB
IAC Rating 22 kAIC
Serial No CT Ratio
General Electric THQB 1 1
Panel Schedule
Panel ID
DQL1
General Panel Data
Power Source DQT1 Floor 1st Floor
Main Breaker
Manufacturer General Electric Room 1633
Model AWF3181CBX Voltage 208V
IAC Rating 200 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
125A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty Range Setting
MCB 20A 20A 22 kAIC
DPQ
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
1-MV-1 General Electric TEY 3 1
Dental Air General Electric TEY 3 1
Panel Schedule
Panel ID
AQP1
General Panel Data
Power Source DPQ Floor 1st Floor
Main Breaker
Manufacturer General Electric Room 1689
Model Unknown Voltage 480V
IAC Rating 100 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
Unknown
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID Range Setting
MCB 20A 20A 14 kAIC
MCB 100A 100A 14 kAIC
DPQ
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
TSEG General Electric TEY 3 1
Panel Schedule
Panel ID
PSEG
General Panel Data
Power Source DPC Floor 1st Floor
Main Breaker
Manufacturer General Electric Room 1634
Model AEF3241MTX Voltage 480V
IAC Rating 100 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
125A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID Range Setting
MCB 40A 40A 14 kAIC
DPQ
Trip Device Type T-M
Breaker ID Main
Frame Size 90A
Breaker Type
MCB
Rating 90A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
THQB
IAC Rating 22 kAIC
Serial No CT Ratio
General Electric THQB 2 1
Panel Schedule
Panel ID
LSEG
General Panel Data
Power Source DPQ Floor 1st Floor
Main Breaker
Manufacturer General Electric Room 1634
Model Unknown Voltage 208V
IAC Rating 200 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
125A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty Range Setting
MCB 50A 50A 10 kAIC
DPQ
Trip Device Type T-M
Breaker ID Main
Frame Size 150A
Breaker Type
MCB
Rating 100A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
HD150
IAC Rating 18 kAIC Fixed
Serial No CT Ratio 1300A
CRAC-5 Square D EDB34015 3 1
CRAC-6 Square D EDB34015 3 1
CRAC-7 Square D EDB34015 3 1
Condenser-5 Square D EDB34020 3 1
Condenser-6 Square D EDB34020 3 1
Condenser-7 Square D EDB34020 3 1
Panel Schedule
Panel ID 34H1A
General Panel Data
Power Source DPQ Floor First Floor
Main Breaker
Manufacturer Square D Room B34-3
Model NF Voltage 480V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
125A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID Range Setting
MCB 15A 15A 18 kAIC
MCB 15A 15A 18 kAIC
MCB 15A 15A 18 kAIC
MCB 20A 20A 18 kAIC
MCB 20A 20A 18 kAIC
MCB 20A 20A 18 kAIC
DPQ via 34T1
Trip Device Type T-M
Breaker ID Main
Frame Size 400A
Breaker Type
MCB
Rating 250A
Inst
Manufacturer Eaton
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
HKD3400F
IAC Rating 100 kAIC 5-10X
Serial No CT Ratio 10X
Eaton BA 1
Panel Schedule
Panel ID 34L1A Section 1
General Panel Data
Power Source DPQ via 34T1 Floor First Floor
Main Breaker
Manufacturer Eaton Room B34-3
Model PRL1A Voltage 208V
IAC Rating 10 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
400A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty Range Setting
MCB 20A 20A 10 kAIC
DPQ via 34T1
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
ATS-2 (Normal) Eaton ED3175 3 1
Eaton BA 1 1
Panel Schedule
Panel ID 34L1A Section 2
General Panel Data
Power Source DPQ via 34T1 Floor First Floor
Main Breaker
Manufacturer Eaton Room B34-3
Model PRL1A Voltage 208V
IAC Rating 10 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
400A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID Range Setting
MCB 175A 175A 65 kAIC
NCB 20A 20A 10 kAIC
ATS #6
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
DQP3B General Electric TED134150 3 1
Air Handler General Electric TEY 3 1
Med Air Comp General Electric TEY 3 1
Condensate Pump General Electric TEY 3 1
Ex Fan 7 General Electric TEY 3 1
Ex Fan 6 General Electric TEY 3 1
Med Vac Pump General Electric TEY 3 1MCB 60A 60A 14 kAIC
MCB 15A 15A 14 kAIC
15A 14 kAIC
MCB 30A 30A 14 kAIC
Panel Schedule
Panel ID
DQP3
General Panel Data
Power Source ATS #6 Floor 3rd Floor
Main Breaker
Manufacturer General Electric Room 3627
Model Spectra Voltage 480
IAC Rating 42 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
400A
Breaker Data
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Circuit ID Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
MCB 15A
60A 60A
Breaker Type
14 kAIC
Range Setting
MCB 150A 150A 14 kAIC
MCB 90A 90A 14 kAIC
MCB
Return Air Fan General Electric TEY 3 1
TVSS General Electric TEY 3 1
HW Pump 3 General Electric TEY 3 1
HW Pump 4 General Electric TEY 3 1
MCB 15A 15A 14 kAIC
MCB 60A 60A 14 kAIC
MCB 40A 40A 14 kAIC
15A 14 kAICMCB 15A
DPQ
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
Chiller 1-CH-3 General Electric SFHA36AT0250 3 1
Spare General Electric TEY 3 1
CWP 1 General Electric TEY 3 1
Chiller Condenser General Electric TEY 3 1
CWP2 General Electric TEY 3 1MCB 20A 20A 14 kAIC
MCB 20A 20A 14 kAIC
MCB 30A 30A 14 kAIC
Range Setting
MCB 250A 175A 25 kAIC 515-1750A 1750A
MCB 100A 100A 14 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer General Electric Room 3627
Model Spectra Voltage 480V
IAC Rating 42 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
400A
Breaker Data
Panel Schedule
Panel ID
DQP3A
General Panel Data
Power Source DPQ Floor 3rd Floor
DQP3
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
EF-2 General Electric TEY 3 1
EF-5 General Electric TEY 3 1
EF-9 General Electric TEY 3 1
1-EF-24A General Electric TEY 3 1
AHU-23 General Electric TEY 3 1
T3 General Electric TEYD3125B 3 1
Temp Pwr Skid General Electric TEYD3125B 3 1
MCB 125A 125A 14 kAIC
MCB 30A 30A 14 kAIC
MCB 20A 20A 14 kAIC
MCB 15A 15A 14 kAIC
15A 14 kAIC
MCB 15A 15A 14 kAIC
Panel Schedule
Panel ID
DQP3B
General Panel Data
Power Source DQP3 Floor 3rd Floor
Main Breaker
Manufacturer General Electric Room 3667
Model AEF3422MT Voltage 480V
IAC Rating 14 kAIC
MCB 15A
Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID Range Setting
MCB 125A 125A 14 kAIC
Booster Pump General Electric TEY 3 1
Return Air Fan General Electric TEY 3 1
RO System Skid General Electric TEY 3 1
AC1 General Electric TEY 3 1
AHU-24 General Electric TEY 3 1
1-EF-24A General Electric TEYD3020B 3 1
Culligan Sys Skid General Electric TEYD3015B 3 1
MCB 40A 40A 14 kAIC
MCB 20A 20A 14 kAIC
MCB 15A 15A 14 kAIC
MCB 15A 15A 14 kAIC
MCB 20A 20A 14 kAIC
MCB
MCB 15A 15A 14 kAIC
15A 15A 14 kAIC
DQP3B
Trip Device Type T-M
Breaker ID Main
Frame Size 200A
Breaker Type
MCB
Rating 200A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
TQD32200
IAC Rating 10 kAIC
Serial No CT Ratio
EF-4 General Electric THQB 3 1
QL3A General Electric THQB 3 1
Panel Schedule
Panel ID
QL3B
General Panel Data
Power Source DQP3B Floor 3rd Floor
Main Breaker
Manufacturer General Electric Room 3666
Model AQF3602ABX Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID Range Setting
MCB 20A 20A 10 kAIC
MCB 60A 60A 10 kAIC
QL3B
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
General Electric THHQB 1 1
Panel Schedule
Panel ID
QL3A
General Panel Data
Power Source QL3B Floor 3rd Floor
Main Breaker
Manufacturer General Electric Room 3628
Model AQF3241MTX Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
125A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty Range Setting
MCB 20A 20A 22 kAIC
ATS #4 via CB Disc
Trip Device Type T-M
Breaker ID Main
Frame Size 400A
Breaker Type
MCB
Rating 300A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
TJJ436400
IAC Rating 30 kAIC 900-3000A
Serial No CT Ratio 3000A
1-SF-1 General Electric THED136020 3 1
1-EF-1 General Electric THED136015 3 1
1-PEF-1 General Electric THED136015 3 1
1-PEF-2 General Electric THED136015 3 1
1-P1 General Electric THED136040 3 1
1-EF General Electric THED136015 3 1
1-EF-13 General Electric THED136015 3 1
Panel Schedule
Panel ID
DNP1
General Panel Data
Power Source ATS #4 via CB Disc Floor 1st Floor
Main Breaker
Manufacturer General Electric Room 1632
Model Unknown Voltage 480V
IAC Rating Unknown Buss
(Copper, Aluminum, Bolt On, etc)
400A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID Range Setting
MCB 20A 20A 25 kAIC
MCB 15A 15A 25 kAIC
MCB 15A 15A 25 kAIC
MCB 15A 15A 25 kAIC
MCB 40A 40A 25 kAIC
MCB 15A 15A 25 kAIC
MCB 15A 15A 25 kAIC
1-P2 General Electric THED136040 3 1
DNT1 General Electric THED136100 3 1MCB 100A 100A 25 kAIC
MCB 40A 40A 25 kAIC
DNP1
Trip Device Type T-M
Breaker ID Main
Frame Size 225A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
TFJ236225
IAC Rating 22 kAIC 1000-2250A
Serial No CT Ratio 2250A
1-SF4 General Electric THED136050 3 1
1-PEF7 General Electric THED136015 3 1
RF5 General Electric THED136015 3 1
1-DF5 General Electric THED136020 3 1
1-RF4 General Electric THED136015 3 1
1-PEF8 General Electric THED136015 3 1
SF5 General Electric THED136050 3 1
Panel Schedule
Panel ID
DNP2
General Panel Data
Power Source DNP1 Floor 2nd Floor
Main Breaker
Manufacturer General Electric Room 2638
Model NHB Voltage 480V
IAC Rating Unknown Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID
MCB 15A 15A 25 kAIC
MCB 50A 50A 25 kAIC
25 kAIC
Range Setting
25 kAIC
MCB 15A 15A 25 kAIC
MCB 20A 20A 25 kAIC
MCB 15A 15A 25 kAIC
MCB 50A 50A
MCB 15A 15A
DNT1
Trip Device Type T-M
Breaker ID Main
Frame Size 225A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
THQD32225
IAC Rating 22 kAIC
Serial No CT Ratio
General Electric THQB 1 1
Panel Schedule
Panel ID DNL1 Section 1
General Panel Data
Power Source DNT1 Floor 1st Floor
Main Breaker
Manufacturer General Electric Room 1632
Model Unknown Voltage 208V
IAC Rating 200 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty Range Setting
MCB 20A 20A 22 kAIC
DNL1 Section 1
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
General Electric THQB 1 1
Panel Schedule
Panel ID DNL1 Section 2
General Panel Data
Power Source DNL1 Section 1 Floor 1st Floor
Main Breaker
Manufacturer Unknown Room 1632
Model Unknown Voltage 208V
IAC Rating 10 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty Range Setting
MCB 20A 20A 10 kAIC
DNL1 Section 1
Trip Device Type T-M
Breaker ID Main
Frame Size 225A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
THQD32225
IAC Rating 22 kAIC
Serial No CT Ratio
General Electric THQB 1 1
Panel Schedule
Panel ID DNL2 Section 1
General Panel Data
Power Source DNL1 Section 1 Floor 2nd Floor
Main Breaker
Manufacturer General Electric Room 2638
Model AQF3422MBX Voltage 208V
IAC Rating 200 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty Range Setting
MCB 20A 20A 10 kAIC
DNL2 Section 1
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
General Electric TQHB 1 1
Panel Schedule
Panel ID DNL2 Section 2
General Panel Data
Power Source DNL2 Section 1 Floor 2nd Floor
Main Breaker
Manufacturer General Electric Room 2638
Model AQF3422MBX Voltage 208V
IAC Rating 200 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty Range Setting
MCB 20A 20A 22 kAIC
ATS #4
Trip Device Type T-M
Breaker ID Main
Frame Size 300A
Breaker Type
MCB
Rating 300A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
TJJ436300
IAC Rating 30 kAIC 900-3000A
Serial No CT Ratio 3000A
1-A2-SF General Electric TEY 3 1
1-A2-RF General Electric TEY 3 1
1-EF-2 General Electric TEY 3 1
1-PEF-3 General Electric TEY 3 1
1-PEF-4 General Electric TEY 3 1
1-PEF-17 General Electric TEY 3 1
1-PEF-18 General Electric TEY 3 1
Panel Schedule
Panel ID
ANP1
General Panel Data
Power Source ATS #4 Floor 1st Floor
Main Breaker
Manufacturer General Electric Room 1690
Model Unknown Voltage 480V
IAC Rating 100 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
Unknown
Br…