These security system documents detail comprehensive security infrastructure design for Buildings 04 and 05 of the New Orleans Veterans Healthcare System Medical Center replacement project. The documents include detailed technical drawings and specifications for integrated security systems covering multiple building levels, encompassing closed-circuit television (CCTV) surveillance, access control, fiber optic networking, door hardware interfaces, and security device placement. Key components include fixed and pan-tilt-zoom cameras on each floor, card readers, door position sensors, electromagnetic locks, emergency telephones, intercom stations, and centralized monitoring equipment.

The technical specifications mandate rigorous installation standards, including conduit routing, cable management, power supply requirements, fire-stopping protocols, and system interconnectivity. Specific requirements include using dedicated security conduits, maintaining minimum cable separation distances, implementing tamper-resistant device enclosures, connecting systems to emergency power circuits, and ensuring compatibility with fire alarm systems. The designs specify security equipment placement on floors 1-7 of parking structures, with careful consideration of architectural constraints, seismic requirements, and Department of Veterans Affairs security protocols.

View the file

Other files

File Type Posted
0211-4AS102-K.pdf PDF
NOVA VOLUME 2-Low Voltage_2013_0930.pdf PDF
NOVA VOLUME 2-Fire Protection_2013_0930.pdf PDF
629-25-100 Phase 1 RFI Register 05212025.docx DOCX document
0238-5AS102-L.pdf PDF
0216-4AS107-K.pdf PDF
0240-5AS104-L.pdf PDF
NOVA VOLUME 2-Plumbing Tanks_2013_0930.pdf PDF
NOVA VOLUME 2-Plumbing_2013_0930.pdf PDF
NOVA VOLUME 2-Mechanical_2013_0930.pdf PDF
0243-5AS107-L.pdf PDF
0210-4AS101-K.pdf PDF
NOVA VOLUME 1_2013_0930.pdf PDF
NOVA VOLUME 2-Electrical_2013_0930.pdf PDF
0237-5AS101-L.pdf PDF
36C25625R0084 0001.docx DOCX document
0213-4AS104-K.pdf PDF
36C25625R0084 VA Patient Garage Report .pdf PDF
36C25625R0084 EXHIBIT F.docx DOCX document
36C25625R0084 01 00 00 General Requirements 03272025 .docx DOCX document
36C25625R0084 EXHIBIT C.docx DOCX document
36C25625R0084 RFP.docx DOCX document
36C25625R0084 EXHIBIT B.docx DOCX document
36C25625R0084 EXHIBIT A.docx DOCX document
36C25625R0084 01 35 26 Safety Requirements 03262025 .docx DOCX document
36C25625R0084 EXHIBIT E.docx DOCX document
36C25625R0084 EXHIBIT D.docx DOCX document
36C25625R0084 VA Staff Garage Report .pdf PDF
36C25625R0084.docx DOCX document
36C25625R0084 629-25-100 SOW 03262025 .docx DOCX document
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ET

ET

VBS

GO

PTZ

EL

PACS

MCPS

IDS

120VAC

120VAC-E

UPS

SMS

JB

KEYBOARD

ELECTRONIC SAFETY AND SECURITY SYMBOLS

ELECTRONIC SAFETY AND SECURITY ABBREVIATIONS

GENERAL NOTES:

360°

40°

X

M PTZ

M

T

M

T

M

F

T

M

T

T

M

M

M

M

T

T

M

T

M

T

M

T

M

T

M

M

T

M

T

M

T

M

T

CP

AP

TS

PROVIDE ALL COMPONENTS, INTERCONNECTION CONDUIT, CABLE/WIRE,

APPURTENANCES, AND MATERIALS AS REQUIRED TO FORM A COMPLETE COORDINATED

SYSTEM READY FOR OPERATION.

PROVIDE ALL PLAN CHECKS, PERMITS, AND LICENSES NECESSARY FOR THE

EXECUTION OF WORK AS APPLICABLE FOR THE PROJECT. ALL FEES, CHANGES AND

OTHER ASSOCIATED COSTS INCURRED BY THE FOREGOING SHALL BE BORNE BY THE

CONTRACTOR.

THE CONTRACTOR SHALL PROVIDE A QUALIFIED AND COMPETENT FACTORY

TRAINED AND STATE LICENSED FIELD SUPERVISOR ON-SITE TO ENSURE THE PROPER

INSTALLATION OF ALL SYSTEMS SPECIFIED AND IN ACCORDANCE WITH THE CONTRACT

DOCUMENTS. THE CONTRACTOR SHALL COORDINATE CONSTRUCTION ACTIVITIES WITH

OTHER CONTRACTORS, TRADES, AND DEPARTMENT OF VETERANS AFFAIRS AND SECURITY

OR THEIR AUTHORIZED REPRESENTATIVE.

THE CONTRACTOR SHALL PROVIDE FACTORY TRAINED AND STATE LICENSED

TECHNICIANS FOR THE INSTALLATION AND SHALL PROVIDE PROOF OF SUCH SYSTEMS

AUTHORIZED TRAINING.

PROVIDE ALL WIRING FROM EQUIPMENT HARDWARE MANUFACTURERS TERMINAL

STRIPS TO FINAL CONNECTION POINTS OF EQUIPMENT.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING ALL EXISTING

CONDITIONS AND ANY CRITICAL DIMENSIONS ASSOCIATED WITH THE SCOPE OF WORK

PRIOR TO SUBMITTING THE CONSTRUCTION BID. THE CONTRACTOR SHALL CONFIRM

THAT ALL WORK OUTLINED WITHIN THE CONTRACT DOCUMENTS CAN BE

ACCOMPLISHED AS SHOWN, AND SHALL NOTIFY IN WRITING VA OR THEIR AUTHORIZED

REPRESENTATIVE OF ANY CONDITIONS ENCOUNTERED WHICH MAY AFFECT BUILDING

CODE COMPLIANCE.

VERIFY PARTITION LOCATIONS, AND AVOID CONFLICTS WITH LIGHTS, DIFFUSERS,

GRILLS, AND OTHER LIKE OBSTRUCTIONS. LOCATIONS OF ALL VISIBLE DEVICES AND

EQUIPMENT SHALL BE COORDINATED WITH THE ARCHITECT FOR REVIEW AND APPROVAL

PRIOR TO INITIATION OF WORK.

COORDINATE A FINAL SECURITY SYSTEM EQUIPMENT LAYOUT AND ROUTING OF THE

CONDUIT WITH THE CONTRACT DOCUMENTS. ANY CONFLICTS DISCOVERED SHALL

IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE OWNER FOR REVIEW AND

APPROVAL PRIOR TO INITIATION OF WORK.

EQUIPMENT AND COMPONENTS SHOWN ON THESE PLANS ARE DIAGRAMMATIC IN

NATURE AND ARE NOT TO BE SCALED FOR EXACT DEVICE LOCATIONS. CONTRACTOR

SHALL LOCATE DEVICES BASED ON APPLICABLE CODE, KEY NOTES AND AS DESIGNED

BY THE ARCHITECT.

INSTALL ALL MATERIALS AND EQUIPMENT IN STRICT ACCORDANCE WITH THE

MANUFACTURERS DIRECTION, TESTING AND OPERATIONAL PROCEDURES.

ALL MATERIALS, DEVICES AND EQUIPMENT SHALL BE UNUSED, OF CURRENT

MANUFACTURE, AND MEET OR EXCEED THE LATEST PUBLISHED SPECIFICATIONS OF THE

MANUFACTURER. DEVICES AND EQUIPMENT SHALL BE THE LATEST MODEL OF THE

MANUFACTURER UNLESS OTHERWISE INDICATED, OR UNLESS SUCH MODEL FAILS TO

MEET THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.

ALL ELECTRONICS COMPONENTS SHALL BE STANDARD, UNMODIFIED PRODUCTION

MODELS EXCEPT AS NOTED WITH THE LATEST FIRMWARE/BIOS OFFERED BY THE

MANUFACTURER AT THE TIME OF THE FINAL TEST.

PROTECT ALL EXISTING WORK, AND THE WORK OF OTHER ASSOCIATED TRADES

FROM DAMAGE. ALL EQUIPMENT PROVIDED SHALL BE KEPT INTERNALLY CLEAN AND

PROTECTED AGAINST BLOWING DUST, WIND, STORMS, SUN, FLOOD, RAIN, SNOW, HEAT,

RAIN, MOISTURE, AND ANY OTHER DAMAGING FACTORS. ALL INSTALLATION WORK

SHALL BE COVERED AND PROTECTED AGAINST DAMAGE.

EQUIPMENT AND MATERIALS SHALL BE PROPERLY STORED, ADEQUATELY

PROTECTED AND CAREFULLY HANDLED TO PREVENT DAMAGE BEFORE AND DURING

INSTALLATION.

EQUIPMENT STORED ON THE PREMISES IS AT THE CONTRACTORS OWN RISK. THE

OWNER IS NOT THE CARETAKER OF UNINSTALLED OR STAGING OF HARDWARE ON-SITE

UNLESS PREVIOUSLY AUTHORIZED IN WRITING BY DEPARTMENT OF VETERANS AFFAIRS

OR ITS AUTHORIZED REPRESENTATIVE TO ACCEPT CUSTODIANSHIP OF THE HARDWARE.

ELECTRICAL CONTRACTOR SHALL PROVIDE PRIMARY, DEDICATED ELECTRICAL POWER

(120/220 VAC).

ELECTRICAL CONTRACTOR SHALL SUPPLY AND PROVIDE DEDICATED 20 AMP, 120

VAC POWER AT SECURITY LOCATIONS FOR CONNECTION BY THE SECURITY

CONTRACTOR. ALL PRIMARY CONTROL PANELS SHALL BE CONNECTED TO GENERATOR

BACKUP CIRCUITS.

ALL PRIMARY CONTROL PANELS, COMMUNICATION TRANSPORTATION DEVICES,

POWER SUPPLIES, AND NETWORK VIDEO RECORDERS SHALL BE CONNECTED TO UPS

BACKUP CIRCUITS, BATTERY BACKUP, AND GENERATOR POWER BACKUP SYSTEM.

PROVIDE ALL THE INTERCONNECTIONS BETWEEN POWERED JUNCTION BOXES AND

THE SECURITY EQUIPMENT.

ADHERE TO ALL SYSTEM AND COMPONENT GROUNDING REQUIREMENTS AS

SPECIFIED BY THE EQUIPMENT MANUFACTURERS.

PROVIDE SURGE SUPPRESSION, GROUNDING AND BONDING THAT WILL EFFECTIVELY

PROTECT, WITHIN TESTED LIMITS, THE SYSTEMS HARDWARE AND EQUIPMENT AGAINST

LIGHTNING TRANSIENTS, INTERNAL AND EXTERNAL SWITCHING TRANSIENTS, AND OTHER

SURGE TRANSIENTS THROUGHOUT THE USEFUL LIFE OF THE SYSTEM.

ALL WIRING SHALL BE PROPERLY SUPPORTED AND INSTALLED IN CONDUIT AND CABLE

TRAY, ON CENTER AS REQUIRED IN CONTRACT DOCUMENTS.

ALL CONDUIT FILL SHALL NOT EXCEED 40 PERCENT (40%) OF INTERIOR CROSS

SECTIONAL AREA WHERE THREE OR MORE CABLES ARE CONTAINED WITHIN A SINGLE

CONDUIT.

CABLES, RACEWAYS AND CONDUIT SHALL NOT BE SUPPORTED FROM DUCTWORK,

PIPING, PLUMBING SYSTEMS, CEILING TILE AND LIGHTING FIXTURE SUSPENSION WIRES

OR BUILDING STRUCTURE.

CABLES SHALL BE ROUTED IN CONDUIT OR OTHER SUITABLE RACEWAY SUBJECT TO

ACCEPTANCE BY THE ARCHITECT.

AT LOCATIONS WHERE CABLES PASS THROUGH METAL STUDS OR DOOR FRAMES, THE

CONTRACTOR SHALL INSTALL A BUSHING OR GROMMET TO PREVENT DAMAGE TO THE

CABLES.

ALL CABLES MUST BE FREE OF TENSION AT BOTH ENDS AND OVER THE ENTIRE

LENGTH OF THE RUN.

CABLE TIES AND SUPPORTS SHALL NOT PINCH, BIND, CRIMP, OR IN ANY WAY

CAUSE PHYSICAL OR ELECTRICAL CHARACTERISTIC DAMAGE TO THE CABLING. THE

CONTRACTOR SHALL ASSURE THAT DURING AND UPON COMPLETION OF THE

INSTALLATION, ALL CABLES ARE FREE OF KINKS, SHARP BENDS, TWISTS, GOUGES,

CUTS OR ANY OTHER PHYSICAL DAMAGE.

ALL CABLING SHALL BE PLENUM RATED IN ACCORDANCE WITH THE NEC.

PLENUM RATED CABLE TIES AND CABLE SUPPORTS SHALL BE UTILIZED IN ALL

PLENUM RATED SPACES.

ALL CABLE RUNS SHALL BE CONTINUOUS BETWEEN DEVICES WITHOUT SPLICES.

CONNECTIONS SHALL BE MADE USING TERMINAL BLOCKS. WIRES CONNECTED TOGETHER

SHALL HAVE THE SAME COLOR INSULATION. ALL CONNECTIONS SHALL BE ACCESSIBLE

FOR INSPECTION AND SERVICES AND SHALL BE CLEARLY IDENTIFIED ON THE

CONTRACTOR'S AS-BUILT DRAWINGS. ALL DEVICE BACK BOXES, JUNCTION BOXES AND

PULL BOXES SHALL BE LABELED AND ACCESSIBLE FOR INSPECTION AND MAINTENANCE.

WIRING COLOR CODE SHALL BE MAINTAINED THROUGHOUT THE INSTALLATION AS

REQUIRED BY THE SPECIFICATIONS AND DEPARTMENT OF VETERANS AFFAIRS.

TERMINALS, CONNECTORS, DEVICES, CIRCUITS, CABLES, AND CABLE TERMINATIONS

SHALL BE CLEARLY, LOGICALLY AND PERMANENTLY MARKED DURING INSTALLATION.

ALL EQUIPMENT AND CONDUITS SHALL BE IDENTIFIED.

ALL WIRING AND ELECTRICAL CIRCUITS SHALL BE NUMERICALLY IDENTIFIED AT

BOTH ENDS AS REQUIRED BY THE CONTRACT DOCUMENTS. EACH SYSTEM CONDUIT

JUNCTION BOX, PULL BOX, OR ELECTRICAL ENCLOSURE (FROM TERMINATION TO

TERMINATION) CONTAINING SYSTEM CONDUCTORS, INCLUDING INITIATING DEVICE,

NOTIFICATION APPLIANCE, AND AUXILIARY FUNCTION CIRCUITS.

AC POWER CONDUCTORS OR GROUNDING CONDUCTORS SHALL BE UNIQUELY

AND PERMANENTLY LABELED WITH A NUMBERED TAG, LABEL OR STENCIL. LABEL

SYSTEM PROPOSED BY THE CONTRACTOR SHALL BE TYPEWRITTEN AND APPROVED BY

DEPARTMENT OF VETERANS AFFAIRS OR THEIR AUTHORIZED REPRESENTATIVE.

ENCLOSURES, CABINETS, HOUSINGS, CONSOLES, POWER SUPPLY ENCLOSURES,

CONTROL AND TERMINAL CABINETS, CONTROL UNITS, WIRING GUTTERS AND OTHER

COMPONENT HOUSINGS, BOXES AND FITTINGS OR EVERY PRODUCT DESCRIPTION,

COLLECTIVELY REFERRED TO AS ENCLOSURES, SHALL BE SO FORMED AND ASSEMBLED

AS TO BE STURDY AND RIGID.

ENCLOSURES, CABINETS, HOUSINGS, BOXES AND FITTINGS OR EVERY PRODUCT

DESCRIPTION HAVING HINGED DOORS OR REMOVABLE COVERS AND WHICH CONTAIN

CIRCUITS, OR THE INTEGRATED SECURITY SYSTEMS AND IT'S POWER SUPPLIES SHALL

BE PROVIDED WITH COVER OPERATED, CORROSION-RESISTANT TAMPER SWITCHES.

ALL EQUIPMENT SHALL BE PROPERLY ATTACHED AND HELD FIRMLY IN PLACE.

FASTENINGS AND SUPPORTS SHALL BE ADEQUATE TO SUPPORT LOADS WITH MINIMUM

SAFETY FACTOR OF THREE (3). ALL MEANS OF EQUIPMENT AND CONDUIT SUPPORT

SHALL BE APPROVED.

ALL WIRING SHALL BE RUN PERPENDICULAR OR PARALLEL TO

THE FLOOR PLANE, WITH ALL BENDS MADE AT NEAT RIGHT ANGLES.

ALL WIRING WITHIN THE CABINET SHALL BE PERMANENTLY ATTACHED USING

SPIRAL WRAP TUBING AND NYLON WIRE TIES WITH MECHANICAL (I.E.: SCREWS, RIVETS)

FASTENERS. THE USE OF SELF-ADHESIVE FASTENERS INSIDE THE CABINET(S) IS

SPECIFICALLY PROHIBITED.

ALL ENCLOSURE PENETRATIONS SHALL BE FROM THE BOTTOM UNLESS THE

SYSTEM DESIGN REQUIRES PENETRATIONS FROM OTHER DIRECTIONS. PENETRATIONS

OF INTERIOR ENCLOSURES INVOLVING TRANSITIONS OF CONDUIT FROM INTERIOR TO

EXTERIOR, AND ALL PENETRATIONS ON EXTERIOR ENCLOSURES SHALL BE SEALED WITH

RUBBER SILICONE SEALANT TO PRECLUDE THE ENTRY OF WATER. THE TERMINATOR

SHALL BE FILLED WITH AN APPROVED SEALANT AS RECOMMENDED BY THE CABLE

MANUFACTURER AND IN SUCH A MANNER THAT THE CABLE IS NOT DAMAGED.

ALL WIRING WITHIN THE CABINET SHALL BE NEATLY ROUTED IN HORIZONTAL AND

VERTICAL CHANNELS PARALLEL TO THE CABINET'S SIDES AND THE INTERIOR TERMINAL

STRIPS. WIRING SHALL NOT BE ROUTED OVER CIRCUIT BOARDS, TRANSFORMERS, AND

TERMINAL STRIPS. AS GENERAL PRACTICE, RUN ALL POWER CABLES, CONTROL

CABLES, AND HIGH-LEVEL CABLES ON ONE SIDE OF AN EQUIPMENT CABINET. RUN

ALL OTHER CABLES ON THE OPPOSITE SIDE OF AN EQUIPMENT CABINET. THE

CONTRACTOR SHALL MAINTAIN A MINIMUM OF A TWELVE (12) INCH DISTANCE BETWEEN ALL

PARALLEL RUNS OF AC ELECTRICAL POWER AND LOW VOLTAGE CONDUIT OR LOW

VOLTAGE WIRING.

NO CONDUIT SHALL BE LESS THAN 1" IN DIAMETER UNLESS DESIGNATED BY

THESE SPECIFICATIONS AND/OR PLANS. A PULL STRING SHALL BE INCLUDED IN EACH

INDIVIDUAL CONDUIT RUN.

PROVIDE TESTING AND VERIFY THAT ALL SYSTEM CABLING AND FIELD WIRING IS

FREE OF SHORTS, GROUNDS, OPENS, HIGH RESISTANCE AND OTHER FAULTS PRIOR TO

TERMINATION TO DEVICES AND EQUIPMENT. THE CONTRACTOR SHALL PROVIDE A

DETAILED REPORT OF THE TEST TO THE DEPARTMENT OF VETERANS AFFAIRS AND ITS

ALL CONDUITS SHALL BE IN INSTALLED IN ACCORDANCE WITH NFPA 70, THE

NATIONAL ELECTRICAL CODE (NEC), AMERICAN DISABILITY ACT (ADA) AND

THE CONTRACT DOCUMENTS.

ALL CONDUIT ROUTES SHALL BE SO DESIGNED TO ENSURE THAT ALL LOW VOLTAGE

WIRE AND CONDUIT MAINTAIN THE REQUIRED MINIMUM OF TWELVE-INCH (12") DISTANCE

SEPARATION FROM ANY OPEN CONDUCTORS OF POWER, OR CLASS 1 CIRCUIT AND

SHALL NOT BE PLACED IN ANY CONDUIT, JUNCTION BOX OR RACEWAY CONTAINING

THESE CONDUCTORS, AS PER NFPA 70, THE NATIONAL ELECTRICAL CODE (NEC).

THE ELECTRICAL CONTRACTOR SHALL AVOID CONDUIT RUNS PARALLEL TO ALL AC

ELECTRICAL POWER. ANY LOW VOLTAGE CONDUIT OR LOW VOLTAGE WIRING THAT

CROSSES OVER AC ELECTRICAL POWER SHALL BE AT A 90-DEGREE ANGLE.

ALL CONDUITS, RACEWAYS, AND OTHER ASSOCIATED ITEMS RELATED TO THE

SYSTEM INSTALLED, SHALL NOT OBSTRUCT ANY PORTION OF A WINDOW, DOORWAY,

STAIRWELL, OR PASSAGEWAY AND SHALL NOT INTERFERE WITH THE OPERATION OF ANY

EXISTING MECHANICAL OR ELECTRICAL EQUIPMENT.

ALL BACK BOXES PROVIDED FOR RECESSED CEILING INSTALLATION SHALL INCLUDE

ADEQUATE ACCESS AND SHALL BE RATED FOR USE IN CEILINGS AND SHALL MEET OR

EXCEED ALL APPLICABLE NATIONAL AND LOCAL ELECTRICAL CODES.

ALL JUNCTION BOXES DEFINED BY THE RECORD SPECIFICATION MAYBE CONCEALED

BUT MUST REMAIN ACCESSIBLE FOR SERVICE AND TESTING. SECURITY JUNCTIONS

BOXES MAY BE RECESSED INTO WALL OR CEILING.

ALL JUNCTION BOXES AND SMALL DEVICE ENCLOSURES BELOW THE CEILING AND

EASILY ACCESSIBLE TO EMPLOYEES OR THE PUBLIC SHALL BE TAMPER PROOF, MONITORED,

AND COVERED WITH SUITABLE COVER PLATE. ALL JUNCTION BOXES ABOVE CEILING LEVEL

IN OCCUPIED AREAS OF THE BUILDING SHALL NOT BE CONSIDERED TO BE EASILY ACCESSIBLE.

ALL LOCATIONS CONTAINING SECURITY SYSTEM COMPONENTS UNDER THESE CONDITIONS

SHALL INCORPORATE SECURE TAMPERPROOF SCREWS OR SIMILAR APPROVED DEVICES.

ALL SYSTEM CABLING PROVIDED, AS PART OF THIS SYSTEM SHALL BE INSTALLED

IN DEDICATED CONDUIT RACEWAYS, WHICH ARE NOT USED FOR ANY OTHER PURPOSE,

FUNCTION OR SYSTEM.

CONDUIT SHALL BE CONCEALED IN ALL FINISHED AREAS. EXPOSED CONDUIT IS

PERMITTED IN ELECTRICAL, MECHANICAL AND UNFINISHED AREAS ONLY AS DETERMINED

BY THE ARCHITECT PRIOR TO INSTALLATION.

ANY RUN OF EXPOSED CONDUIT SHALL BE PARALLEL OR AT RIGHT ANGLE TO THE

BUILDING LINES.

THE SECURITY CONTRACTOR SHALL COORDINATE WITH ELECTRICAL CONTRACTOR TO

PROVIDE CONSTANT 120VAC TO ALL SECURITY EQUIPMENT ROOMS.

ALL DEVICES GENERATING RADIO FREQUENCIES SHALL BE CERTIFIED TO COMPLY

WITH THE REQUIREMENTS OF FCC PART 15 AND LABELED AS SET FORTH IN FCC PART

15.

CONTRACTOR SHALL TAKE ALL OTHER PRECAUTIONS IN ACCORDANCE WITH

MANUFACTURE'S RECOMMENDATIONS TO PREVENT ELECTROMAGNETIC INTERFERENCE WITH

DATA TRANSMISSIONS.

NON-SECURITY SYSTEM WIRING SHALL NOT SHARE SECURITY CONDUIT.

THE SECURITY SYSTEM NETWORK SHALL COMMUNICATE WITH THE SYSTEM CONTROL

WORKSTATIONS THROUGH INDUSTRY STANDARD NETWORK SWITCHES AND ROUTERS AND

SHALL NOT BE REQUIRED TO RESIDE ON THE SAME SUBNET, AS THE INFORMATION

TECHNOLOGY NETWORK.

THE SECURITY CONTRACTOR SHALL COORDINATE WITH THE CONTRACTOR OF

DIVISION 08 700-DOOR HARDWARE.

ALL ELECTRIFIED DOORS SHALL BE OPERATIONAL FROM THE INSIDE WITHOUT USE

OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT PER NFPA 101.

THE SECURITY CONTRACTOR SHALL COORDINATE WITH THE DOOR HARDWARE

CONTRACTOR AS TO INTERCONNECTION OF ALL INPUT TRIGGERS FOR RELEASE OF

ELECTRICAL LOCKING HARDWARE AND CONTACT OUTPUTS REQUIRED TO MONITOR

DOOR RELATED ALARM POINTS.

ALL CAMERA CABLING SHALL BE CONCEALED AND PROTECTED IN A RIGID

ENCASEMENT, CONDUIT, ARMORED FLEX, OR SIMILAR APPROVED PASSAGES. CAMERA

PLACEMENTS IN THE FIELD ARE FORBIDDEN TO HAVE UNPROTECTED AND EXPOSED

CONNECTORS, POWER CABLE, AND VIDEO FEEDS. INTEGRATED ARMATURES THAT PASS

THE CABLING FROM THE CAMERA TO THE WALL / JUNCTION BOX WITHOUT EXPOSING

THE CABLING AT ANY POINT SHALL BE DEEMED ACCEPTABLE.

THE FINAL FIELD PLACEMENT AND FIELD OF VIEW FOR EACH CAMERA LOCATION

SHALL BE DETERMINED BY ON SITE CONDITIONS. PRIOR TO THE PURCHASE OF ANY

(CCTV) HARDWARE THE CONTRACTOR SHALL OBTAIN WRITTEN ACCEPTANCE OF

PROPOSED PLACEMENTS AND ASSOCIATED FOCAL LENGTHS FROM THE DEPARTMENT

OF VETERANS AFFAIRS OR ITS AUTHORIZED REPRESENTATIVE.

ALL PENETRATIONS THROUGH FIRE RATED BUILDING STRUCTURES, WALLS AND

FLOORS SHALL BE SEALED WITH AN APPROPRIATE FIRE STOP SYSTEM. THIS

REQUIREMENT APPLIES TO THROUGH PENETRATIONS (COMPLETE PENETRATION) AND

MEMBRANE PENETRATIONS (THROUGH ONE SIDE OF A HOLLOW FIRE RATED STRUCTURE).

ANY PENETRATING ITEMS I.E., RISER SLOTS AND SLEEVES, CABLES, CONDUIT, CABLE

TRAY, AND RACEWAYS, ETC. SHALL BE PROPERLY FIRE STOPPED. THE CONTRACTOR

SHALL ENSURE THAT ANY FIRE STOP SYSTEMS SHALL BE UL CLASSIFIED TO ASTM E8

14 (UL 1479).

THE CONTRACTOR SHALL ENSURE THAT ALL FIRE STOP SYSTEMS SHALL BE

INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND SHALL

BE COMPLETELY INSTALLED AND AVAILABLE FOR INSPECTION BY THE LOCAL INSPECTION

AUTHORITIES PRIOR TO CABLE SYSTEM ACCEPTANCE.

UPON SUCCESSFUL COMPLETION OF THE INSTALLATION, THE CONTRACTOR SHALL

CONDUCT FULL SYSTEM TESTING TO ASSURE THAT THE SYSTEMS ARE CORRECTLY

INSTALLED AND FULLY OPERATIONAL. CONFIRM IN WRITING TO THE ARCHITECT THAT

ALL ASPECTS OF THE SYSTEM HAVE BEEN TESTED BY THE CONTRACTOR AND FOUND

TO BE FULLY OPERATIONAL AND READY FOR FINAL ACCEPTANCE TESTING.

AT THE CONCLUSION OF TESTING PROVIDE (2) COPIES OF ALL TEST REPORT

DOCUMENTATION OF THE TESTS THAT SHALL REFLECT THE DATE, TIME AND SYSTEM

TESTING RESULTS. ADJUST, BALANCE AND TUNE ALL EQUIPMENT AS REQUIRED FOR

OPTIMUM QUALITY TO MEET MANUFACTURER'S PUBLISHED PERFORMANCE

SPECIFICATIONS AND DEPARTMENT OF VETERANS AFFAIRS REQUIREMENTS.

PR

POTS

POIINTEGRATED SERVICES DIGITAL NETWORK

INTERNATIONAL STANDARDS ORGANIZATION

INSIDE WIRING (CABLE)

KILOHERTZ

POINT OF INTERFACE

PAIR

PLAIN OLD TELEPHONE SERVICE

KHz

IW

ISO

ISDN

DC

DB

DAF

D/A DIGITAL TO ANALOG CONVERSION

DEDICATED ACCESS FACILITY

DECIBELA/D

AC

8P8C 8-POSITION, 8-CONDUCTOR

ALTERNATING CURRENT

ANALOG TO DIGITAL CONVERSION

TB

SYS

SWB

SW

STP

STA

SPG

SPD

SPC

SP

SNA

SMPS

SI

PVC

SE

SL

SER

KEY TELEPHONE SYSTEM

LOCAL AREA NETWORK

LIGHT AMPLIFICATION BY STIMULATED EMISSION OF RADIATION

LOCAL ACCESS TRANSPORT AREA.

LINE BUILDOUT

LOCAL EXCHANGE CARRIER

LIGHT EMITTING DIODE

LOW CAPACITANCE

MANUFACTURING AUTOMATION/PROTOCOL

MAXIMUM

MAIN CROSS-CONNECT

MAIN DISTRIBUTION FRAME

MOTOR/GENERATOR SET

MAINTENANCE HOLE

MICROMETER

MINIMUM

MISCELLANEOUS

POLYVINYL CHLORIDE

SERVICE ENTRANCE

SATELITE EQUIPMENT ROOM

SYSTEM INTERNATIONAL

SLEEVE

SERVICE PROVIDER

STORED PROGRAM CONTROL

SURGE PROTECTION DEVICE

SINGLE-POINT GROUND

STATION

SHIELDED TWISTED PAIR

STATION WIRE

SWITCHBOARD

SYSTEM

TERMINAL BLOCK

SWITCHED MODE POWER SUPPLY

SYSTEMS NETWORK ARCHITECTURE

TSB

TPPMD

TPDDI

TO

TMGB

TM

TIA

THD

TGB

TERM

TELCO

TEL

TEBC

TDM

TC

TBC

TR

MINIMUM POINT OF PRESENCE

MAIN TELEPHONE TERMINAL

NEWTON

NATIONAL ELECTRIC CODE

NATIONAL ELECTRIC SAFETY CODE

NETWORK INTERFACE

NOT IN CONTRACT

NETWORK INTERFACE DEVICE

NETWORK INTERFACE UNIT

NATIONALLY RECOGNIZED TESTING LABORATORY

NOT TO SCALE

ON CENTER

OUTSIDE DIAMETER

OPTICAL FIBER NON-CONDUCTIVE PLENUM

OPTICAL FIBER NON-CONDUCTIVE RISER

OVERCURRENT PROTECTION DEVICE

OUTSIDE PLANT ENGINEER

TIME DIVISION MULTIPLEXING

TELEPHONE

TELEPHONE COMPANY

TERMINAL

THIRD HARMONIC DISTORTION

TELECOMMUNICATIONS ROOM

TELECOMMUNICATIONS BONDING CONDUCTOR

TELECOMMUNICATIONS CLOSET

TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR

TELECOMMUNICATIONS GROUNDING BUSBAR

TELECOMMUNICATIONS INDUSTRY ASSOCIATION

TRANSFORMER MAINTENANCE HOLE

TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

TELECOMMUNICATIONS OUTLET

TWISTED PAIR DISTRIBUTED DATA INTERFACE

TWISTED PAIR PHYSICAL MEDIA DEPENDENT

TELECOMMUNICATIONS SYSTEM BULLETIN

TBBCMODULATOR/DEMODULATOR TELECOMMUNICATIONS BACKBONE BONDING CONDUCTOR

MIN

MAX

MISC

MICRON

MH

M/G

MDF

MC

MAP

LOCAP

LED

LEC

LBO

LATA

LASER

LAN

KTS

ELEC

DWG

EC

EMT

EMR

EMI

EMC

EIA

EF

DW

DTE

DGM

DEMARC

DD

DCO

DCE

EBC

DATA CIRCUIT-TERMINATION EQUIPMENT

DIGITAL CENTRAL OFFICE

DISTRIBUTION DESIGNER

DEMARCATION POINT

DATA GRADE MEDIUM

DATA TERMINAL EQUIPMENT

DISTRIBUTION WIRE

DRAWING(S)

EQUIPMENT BONDING CONDUCTOR

ELECTRICAL CONTRACTOR

ENTRANCE FACILITY

ELECTRONICS INDUSTRY ASSOCIATION

ELECTRICAL

ELECTROMAGNETIC COMPATIBILITY

ELECTROMAGNETIC INTERFERENCE

ELECTROMAGNETIC RADIATION

ELECTRIC METALLIC TUBINGBEF

BDF

BD

BBISDN

B

AWG

ATM

ASCII

ARMM

ANSI

AM

AIA

AFF

AER

ADO

ADA

BC

AMERICANS WITH DISABILITIES ACT

AUXILIARY DISCONNECT OUTLET

ABOVE FINISHED FLOOR

AMERICAN INSTITUTE OF ARCHITECTS

AMPLITUDE MODULATION

AMERICAN NATIONAL STANDARDS INSTITUTE

ASYNCHRONOUS TRANSFER MODE

AMERICAN WIRE GAUGE

BONDING CONDUCTOR

BROAD BAND INTEGRATED SERVICES DIGITAL NETWORK

BUILDING DISTRIBUTOR

BUILDING DISTRIBUTION FRAME

BUILDING ENTRANCE FACILITY

PIC RISER, EXPANDED POLYETHYLENE PVC, 24 AWG, ALVYN

AMERICAN STANDARD CODE FOR INFORMATION INTERCHANGE

OC

OD

FDDI

OPE

OPD

NTS

NRTL

NIU

NID

NIC

NI

NESC

NEC

N

MTT

MPOP

GND

GHz

GEC

GA

FTP

FREQ

FOTP

FDR

FDM

FD

FCC

EXT

EXCH

ESS

E/W

OFNP

OFNR

FO

EQUIPPED WITH

ELECTRONIC SWITCHING SYSTEM

EXCHANGE

EXTENSION

FEDERAL COMMUNICATIONS COMMISSION

FLOOR DISTRIBUTION

FIBER DISTRIBUTED DATA INTERFACE

FREQUENCY DIVISION MULTIPLEXING

FEEDER

FIBER OPTIC

FIBER OPTIC TRANSMISSION SYSTEM

FREQUENCY

FOIL TWISTED PAIR

GAUGE

GROUNDING ELECTRIC CONDUCTOR

GIGAHERTZ

GROUND

CC

CLO

CFC

CIRC

CDO

CDF

CDDI

CD

CCITT

CBC

CATV

CA

BTU

BRISDN

BICSI

BIC

CER

BUILDING INDUSTRY CONSULTANT

BUILDING INDUSTRY CONSULTING SERVICES

BASIC RATE INTEGRATED SERVICES DIGITAL NETWORK

BRITISH THERMAL UNIT

CABLE TELEVISION

COUPLED BONDING CONDUCTOR

COMMUNICATIONS CONTRACTOR

COPPER DISTRIBUTED DATA INTERFACE

COPPER DISTRIBUTION FRAME

COMMUNITY DIAL OFFICE

COMPUTER EQUIPMENT ROOM

COMMUNICATIONS FLAT CABLE

THE INTERNATIONAL TELEGRAPH AND TELEPHONE CONSULTATIVE COMMITTEE

MODEMETWBER BIT ERROR RATE EDUCATIONAL TELEVISION

PTSSACO ANALOG CENTRAL OFFICE DIRECTED CURRENT PASSIVE TRANSMISSION SUBSYSTEM

UTP

UPS

UL

UG

TYP

TVSS

TTY

TTB

OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION

OUTSIDE PLANT

PULSE AMPLITUDE MODULATE

PULL BOX

PRIVATE BRANCH EXCHANGE

PULSE CODE MODULATION

POLYETHYLENE INSULATED CONDUCTOR

PRIVATE LINES

PLANT

PHASE MODULATION

TELEPHONE TERMINAL BOARD

TEXT TELEPHONES

TYPICAL

UNDERGROUND

UNSHIELDED TWISTED PAIR

TRANSCEND VOLTAGE SURGE SUPPRESSOR

UNDERWRITERS LABORATORIES

UNINTERRUPTIBLE POWER SUPPLY

OSP

OSHA

IEEE

IDC

ICEA

IC

Hz

HVAC

HH

HF

PM

PLT

PL

PIC

PCM

PBX

PAM

PB

IDF

HIGH FREQUENCY

HANDHOLE

HEATING, VENTILATION AND AIR CONDITIONING

INTERMEDIATE CROSS CONNECTED

INSULATED CABLE ENGINEERS ASSOCIATION

INSULATION DISPLACEMENT CONNECTION

INTERMEDIATE DISTRIBUTION FRAME

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS

HERTZ

CSMA/CD

CSMA/CA

CSA

CPU

CPE

CPC

COT

COE

CODEC CODER/DECODER

CENTRAL OFFICE EQUIPMENT

CENTRAL OFFICE TERMINAL

CUSTOMER PREMISES COMMUNICATIONS

CUSTOMER PREMISES EQUIPMENT

CENTRAL PROCESSING UNIT

CANADIAN STANDARDS ASSOCIATION

CARRIER SENSE MULTIPLE ACCESS/COLLISION AVOIDANCE

CARRIER SENSE MULTIPLE ACCESS/COLLISION DETECTION

HC TTCO CENTRAL OFFICE HORIZONTAL CROSS-CONNECT TELEPHONE TERMINAL

T

T

AUTHORIZED REPRESENTATIVE.

PUSH BUTTON; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BELL PUSH D-DURESS G-GATE OPERATOR ACTIVATOR P-PANIC

R-DOOR RELEASE X-REQUEST-FOR-EXIT

MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC

X-REQUEST-FOR-EXIT

MONITOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DATA G-GRAPHIC M-MULTISCREEN V-VIDEO

KEYPAD DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

INTERCOM; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

M-MASTER S-SUBSTATION

GLASS BREAKAGE SENSOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

A-AUDIO S-SHOCK

FIELD PANEL; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

A-ALARM C-CARD READER

FIBER OPTIC MODULE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

R-RECEIVER T-TRANSCEIVER TX-TRANSMITTER

EXIT DEVICE; LETTER INDICATES AS FOLLOWS:

T=TECHNOLOGY/TYPE

D-DELAYED EGRESS E-ELECTRIFIED M-MECHANICAL X-HIGH SECURITY

ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:

M=MOUNT

D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DEADBOLT H-HYBRID L-LATCH SET M-MAGNETIC S-STRIKE

CONTROL PANEL; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BURGLAR D-DOOR F-FIRE P-PERIMETER

CENTRAL PROCESSING UNIT

CARD READER WITH TIME AND ATTENDANCE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR HALL CALL

M-MAG STRIP P-PROXIMITY S-SMART CARD

T-TOKEN

BIOMETRICS ACCESS CONTROL DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

F-FINGER PRINT H-HAND GEOMETRY I-EYE IRIS

R-EYE RETINA V-VOICE

BI-STATIC BEAM SENSOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

I-INFRARED M-MICROWAVE

F=FUNCTION

RX-RECEIVE TX-TRANSMIT

AUDIO DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BELL C-CHIME H-HORN K-KLAXON

L-LISTEN-IN M-MICROPHONE S-SOUNDER S-SPEAKER Z-BUZZER

ALARM, VOICE COMMUNICATION PANEL

ALARM, TAMPER SWITCH

SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW

SECURITY ACCESS, TELEPHONE HANDSET

SECURITY ACCESS, SWITCH, BALANCED MAGNETIC CONTROL

SECURITY ACCESS, SENSOR, BURIED VEHICULAR

SECURITY ACCESS, PANNING CAMERA TRAVERSE ANGLE

VIDEO MOTION DETECTOR

VIDEO CONTROL KEYBOARD

SECURITY WINDOW SCREEN; LETTER INDICATES AS FOLLOWS:

T=TECHNOLOGY/TYPE

B-BLIND

SECURITY SCREEN WITH ALARM; LETTER INDICATES AS FOLLOWS:

T=TECHNOLOGY/TYPE

B-BLIND S-SHADE

SECURITY ACCESS, VOLUMETRIC SENSOR

SECURITY ACCESS, VIDEO CAMERA WITH LENS

M = MOTION DETECTOR

PZ = MOTION DETECTOR WITH PAN AND ZOOM

PTZ= MOTION DETECTOR WITH PAN, TILT, AND ZOOM

SECURITY ACCESS, PANIC ALARM

SECURITY ACCESS, OUTDOOR MICROWAVE TRANSMISSION UNIT

SECURITY ACCESS, HORN OR SIREN

SECURITY ACCESS, GENERIC "X" INDICATES THE TYPE

SECURITY ACCESS, CONTROL UNIT WITH CLOSED CIRCUIT TELEVISION CAMERA

SECURITY ACCESS, BUZZER. MTD 1'-6" AFF UNLESS OTHERWISE NOTED

SECURITY ACCESS, ANNUNCIATOR PANEL

RECORDER; LETTER INDICATES AS FOLLOWS:

M=MOUNT

D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

A-AUDIO D-DIGITAL V-VIDEO

EMERGENCY TELEPHONE CALL STATION

EMERGENCY TELEPHONE CALL STATION WITH INTEGRATED CAMERA

VISITOR BADGING STATION

VEHICLE ACCESS GATE OPERATOR. PROVIDED BY OTHERS.

WIRED FOR PHYSICAL ACCESS CONTROL BY SECURITY CONTRACTOR

PAN, TILT, ZOOM DOME POWER SUPPLY

ELECTRONIC LOCK POWER SUPPLY

ACCESS CONTROL PANEL POWER SUPPLY

MULTIPLE CAMERA POWER SUPPLY

INTRUSION DETECTION SYSTEM POWER SUPPLY

DUPLEX POWER OUTLET-120VAC

QUAD POWER OUTLET-120VAC

JUNCTION BOX WITH 120VAC CONNECTION

JUNCTION BOX WITH 120VAC EMERGENCY CIRCUIT CONNECTION

UNINTERRUPTIBLE POWER SUPPLY

SECURITY MANAGEMENT SYSTEM WORK STATION

JUNCTION BOX

AERIAL

BURIED

CABLE

CONDUIT

CIRCUIT

CLOSET

PROVIDE 4-11/16" X 4-11/16" X 2-1/2"D DEVICE BOX AND ASSOCIATED CONDUIT,

17.

18.

19.

20.

21.

22.

23.

24.

25.

26.

27.

28.

29.

30.

31.

32.

33.

34.

35.

36.

37.

38.

39.

40.

41.

42.

43.

44.

45.

46.

47.

48.

49.

50.

51.

52.

53.

54.

55.

56.

57.

58.

59.

60.

62.

63.

64.

65.

66.

61.

67.

68.

69.

70.

71.

72.

73.

74.

75.

76.

77.

78.

79.

80.

81.

82.

83.

1. THE SECURITY MANAGEMENT SYSTEM (SMS) SHALL INTEGRATE THE DIGITAL VIDEO SURVEILLANCE SYSTEM (DVS), CLIENT WORKSTATIONS, FIELD DATA GATHERING PANELS (FIELD PANELS), CARD READERS AND EACH SUPPORT DEVICE AS INDICATED HEREIN AND SPECIFIED IN THE CONTRACT

SPECIFICATIONS.

2. ALL WIRING AND CABLE BETWEEN DEVICES SHALL BE IN ACCORDANCE WITH THE OPERATING

REQUIREMENTS OF THE SMS SYSTEM AND SHALL SUPPORT COMMUNICATIONS FOR POINT

IDENTIFICATION AND ACCESS CONTROL TRANSACTIONS TO/FROM EACH DEVICE.

3. THE CONTROL WIRING BETWEEN FIELD DEVICES, REMOTE ACCESS CONTROL EQUIPMENT AND

FIELD PANELS/DATA GATHERING PANELS SHALL BE A MINIMUM OF No. 18 AWG AND SHALL BE

COLOR-CODED.

4. PROVIDE WIRING FROM THE SMS FIELD PANEL TO THE INSTALLED FIRE ALARM SYSTEM SUCH

THAT IN THE EVENT OF A FIRE ALARM OR WHEN THE FIRE ALARM SYSTEM IS ACTIVATED,

ALL DOORS FITTED WITH ELECTROMAGNETIC LOCKS SHALL REVERT TO FAIL SAFE MODE OF

OPERATION IN ACCORDANCE WITH THE LOCAL AUTHORITY HAVING JURISDICTION AND DEPARTMENT

OF VETERANS AFFAIRS.

5. ALL NON STAIRWELL DOORS FITTED WITH ELECTRIC MORTISE LOCKS SHALL REVERT TO A FAIL SECURE MODE OF OPERATION IN ACCORDANCE WITH THE LOCAL AUTHORITY HAVING JURISDICTION

AND DEPARTMENT OF VETERANS AFFAIRS.

6. ALL STAIRWELL DOORS FITTED WITH ELECTRIC MORTISE LOCKS SHALL BE FAIL SAFE.

7. PROVIDE A HARD WIRED CONNECTION TO A 120 VAC, 20AMP NON-EMERGENCY CIRCUIT THAT IS DEDICATED TO SECURITY FOR EACH SECURITY EQUIPMENT POWER SUPPLY LOCATION AS INDICATED

ON THE DRAWINGS. THE CIRCUIT CONNECTION SHALL BE PROVIDED WITHIN A 4-11/16" X

4-11/16" X 2-1/2" BOX, SURFACE MOUNTED AT 18" A.F.F. UNLESS OTHERWISE NOTED.

TERMINATE WIRE ENDS WITH INSULATED WIRE NUTS.

8. PROVIDE A HARD WIRED CONNECTION TO A 120 VAC, 20AMP EMERGENCY CIRCUIT THAT IS

DEDICATED TO SECURITY FOR EACH SECURITY EQUIPMENT POWER SUPPLY LOCATION AS INDICATED

ON THE DRAWINGS. THE CIRCUIT CONNECTION SHALL BE PROVIDED WITHIN A 4-11/16" X

4-11/16" X 2-1/2" BOX, SURFACE MOUNTED AT 18" A.F.F. UNLESS OTHERWISE NOTED.

TERMINATE WIRE ENDS WITH INSULATED WIRE NUTS.

9. PROVIDE AN UNSWITCHED DUPLEX OUTLET CONNECTED TO A 120 VAC, 20AMP EMERGENCY

CIRCUIT DEDICATED TO SECURITY IN THE SECURITY CONTROL CENTER AND EQUIPMENT

ROOMS AS INDICATED ON THE DRAWINGS. THE DUPLEX OUTLET SHALL BE FLUSH MOUNTED

WITHIN THE FLOOR BELOW THE CONSOLE AND/OR EQUIPMENT RACKS. EXACT LOCATION SHALL

BE AS DIRECTED BY THE ARCHITECT.

10. PROVIDE A HARD WIRED CONNECTION TO A 120 VAC, 20 AMP NON-EMERGENCY CIRCUIT

DEDICATED TO SECURITY FOR DOORS UTILIZING EXIT DEVICES AS INDICATED ON THE DRAWINGS.

THE CIRCUIT CONNECTION SHALL BE PROVIDED WITHIN A 4-11/16" X 4-11/16" X 2-1/2" BOX, MOUNTED ABOVE THE CEILING, WITHIN AN ACCESSIBLE LOCATION ADJACENT TO THE DOOR.

TERMINATE WIRE ENDS WITH INSULATED WIRE NUTS.

11. PROVIDE AN UNSWITCHED DUPLEX OUTLET CONNECTED TO A 120 VAC, 20AMP NON-EMERGENCY CIRCUIT DEDICATED TO SECURITY FOR EACH SECURITY CONVENIENCE DEVICE AS INDICATED ON THE

DRAWINGS. THE OUTLET SHALL BE FLUSH MOUNTED TO THE WALL AT 18" A.F.F UNLESS

OTHERWISE NOTED.

12. REVIEW ALL CONTRACT DRAWINGS AND SURVEY EXISTING SITE CONDITIONS PRIOR TO ORDERING

EQUIPMENT OR PROCEEDING WITH WORK.

13. DRAWINGS SHALL BE USED BY THE CONTRACTOR AS A REFERENCE FOR THE REQUIREMENT AND LOCATION OF THE SYSTEM COMPONENTS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ACQUAINT THEMSELVES WITH ALL OF THE CONTRACT DRAWINGS, AND CONFIRM THE REQUIRED

QUANTITIES OF DEVICES AND SPECIFIC OPTIONS ON LOCATION.

14. PERFORM ALL WORK, PROVIDE PRODUCTS, SYSTEM INTEGRATION, COORDINATION, ENGINEERING, AND DESIGN WORK REQUIRED FOR THE PROJECT IN ORDER TO ENSURE THE PROPER INSTALLATION OF THE COMPLETE AND FULLY OPERATIONAL SYSTEMS PURSUANT TO THE CONTRACT DOCUMENTS AND

DEPARTMENT OF VETERANS AFFAIRS.

15. ALL SYSTEMS PROVIDED SHALL BE IN ACCORDANCE WITH THE MOST CURRENT REVISION OF THE FEDERAL, STATE, AND LOCAL CODES AND STANDARDS. THE AUTHORITY HAVING JURISDICTION SHALL PROVIDE FINAL CLARIFICATION OF CODE REQUIREMENTS. CONFLICT OF ANY CODE REQUIREMENT WILL REQUIRE THE ADAPTATION OF THE MORE STRINGENT REQUIREMENT FOR THE APPLICATION

UNLESS A VARIANCE IS AUTHORIZED BY THE LOCAL AUTHORITY HAVING JURISDICTION.

16.

LOCKNUTS, COUPLINGS, THREADED BUSHINGS AND PULL ROPE FOR ALL DEVICES AS

INDICATED ON DRAWINGS AND AS SPECIFIED

ALL CONDUIT AND CONDUIT FITTINGS, COUPLINGS, SUPPORTS, FASTERNERS

SHALL BE RGS, GALVANIZED.

84.

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

NEW ORLEANS, LOUISIANA

4TY001

BUILDING 04 SECURITY SYMBOLS AND

LEGENDS

JLE JJPJUNE 30, 2011

CONSTRUCTION DOCUMENTS 1

629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, LOW VOLTAGE

ARCHITECTURAL ENGINEERING / PLUMBING

SCALES ASSOCIATES / FIRE PROTECTION

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

EWP_04

CR

EL

ACCESS/ENTRY SIDE

INTERIOR SIDE

DOOR FRAME

DOOR

FINISHED FLOOR

CARD READER

3 3

JB

1-1/4" C

TO LVSR

JUNCTION BOX ABOVE

ACCESSIBLE CEILING

ON SECURE SIDE

DOOR POSITION SWITCHES

OPERATIONAL DESCRIPTION:

DOUBLE DOOR, AUTO OPERATION, 24 HOURS SECURED,

REMOTE RELEASE. DOORS ARE NORMALLY CLOSED &

LOCKED IN ALARM MODE. DOOR POSITION STATUS FOR

EACH DOOR IS MONITORED BY ELECTRONIC DOOR

POSITION SWITCH CONTACTS (DC). IN THE EVENT OF

BUILDING POWER LOSS, THE DOORS SHALL REMAIN

LOCKED (FAIL SECURE). ACCESS IS ACHIEVED VIA

AUTHORIZED CARD CREDENTIAL OR REMOTE RELEASE.

CARD OR REMOTE RELEASE MOMENTARILY SHUNTS

SIGNAL FROM DC, MOMENTARILY UNLOCKS THE

ELECTRIFIED EXIT DEVICE & SENDS SIGNAL TO LOW

ENERGY POWER ASSIST OPERATOR WHICH OPENS

DOOR. ALTERNATIVELY, A PERSON CAN MANUALLY

PULL THE DOOR OPEN USING THE EXIT DEVICE PULL.

CAMERA RECORDS FOR (DURATION TO BE

DETERMINED BY VA) SECONDS DURING ACCESS AND

EGRESS OF AUTHORIZED EVENTS. CAMERAS RECORD

CONTINUOUSLY UPON AN ALARM EVENT AT THIS DOOR

LOCATION UNTIL ALARM CONDITION HAS BEEN RESET.

FREE EGRESS IS PROVIDED AT ALL TIMES BY MANUAL

OPERATION OF EXIT DEVICE OR BY PRESSING WALL

MOUNTED INTERIOR DOOR ACTIVATION SWITCH

POWER

TRANSFER

DEVICE

POWER

TRANSFER

DEVICE

ELDC DC

ELECTROMECHANIC VERTICAL ROD LOCKS

WITH INTEGRAL REQUEST TO EXIT.

ROLL-UP DOOR OPERATOR

AND ASSOCIATED

EQUIPMENT BY GENERAL

CONTRACTOR

LOADING DOCK FLOOR

ROLL-UP DOOR

DOOR FRAME

MAGNETIC DOOR

CONTACT SWITCH AT

INTERIOR SIDE

FLUSH

MOUNT

4-CONDUCTOR, #18AWG

WITHIN 1" CONDUIT TO

NEAREST LVSR

JUNCTION BOX LOCATED

AT SECURED SIDE.

FINISHED FLOOR

OPERATIONAL DESCRIPTION:

TYPICAL SINGLE INTERIOR DOOR WITH ACCESS / ENTRY

CONTROL VIA CARD READER, 24 HOUR SECURED. DOORS IN

ALARM MODE. DOOR POSITION STATUS FOR EACH DOOR IS

MONITORED BY ELECTRONIC DOOR POSITION SWITCH

CONTACTS (DC). DOOR IS NORMALLY CLOSED AND LOCKED.

ELECTROMECHANICAL LOCK SHALL REMAIN IN SECURE MODE

DURING LOSS OF BUILDING POWER (FAIL SECURE). SIGNAL

FROM CARD CREDENTIAL MOMENTARILY SHUNTS SIGNAL

FROM DC & UNLOCKS ELECTROMECHANICAL LOCK. ACCESS

IS THEN ACHIEVED BY MANUAL OPERATION OF LEVER. FREE

EGRESS IS PERMITTED AT ALL TIMES BY MANUAL OPERATION

OF LEVER LOCK.

DOOR

DOOR FRAME

CARD READER

EL

CR ACCESS/ENTRY SIDE

INTERIOR SIDE

JB

ACCESSIBLE CEILING

JUNCTION BOX ABOVE ACCESSIBLE

CEILING ON SECURE SIDE

1-1/4" C

TO LVSR

CONCEALED

DOOR CONTACTS

ELECTROMECHANICAL MORTISE LOCK WITH INTEGRAL

REQUEST TO EXIT

DC

POWER TRANSFER DEVICE

OPERATIONAL DESCRIPTION:

SINGLE EXTERIOR, MONITORED

DOOR. DOOR IS NORMALLY

CLOSED AND MECHANICALLY

LOCKED. IN ALARM MODE, THE

DOOR POSITION STATUS (OPEN

OR CLOSED) IS MONITORED BY

DOOR CONTACTS. FREE EGRESS

IS PROVIDED AT ALL TIMES.

FINISHED

FLOOR

JB

ACCESSIBLE CEILING

JUNCTION BOX ABOVE ACCESSIBLE

CEILING ON INTERIOR SIDE

1-1/4" C

TO LVSR

DC

EXTERIOR SIDE

INTERIOR SIDE

CONCEALED

DOOR CONTACT

DC

DOOR

DOOR FRAME

SIMILAR FOR DOUBLE DOORS.

FINISHED FLOOR

OPERATIONAL DESCRIPTION:

TYPICAL SINGLE INTERIOR DOOR WITH ACCESS / ENTRY

CONTROL VIA CARD READER, 24 HOUR SECURED. DOORS IN

ALARM MODE. DOOR POSITION STATUS FOR EACH DOOR IS

MONITORED BY ELECTRONIC DOOR POSITION SWITCH

CONTACTS (DC). DOOR IS NORMALLY CLOSED AND LOCKED.

ELECTROMECHANICAL LOCK SHALL REMAIN IN SECURE MODE

DURING LOSS OF BUILDING POWER (FAIL SECURE). SIGNAL

FROM CARD CREDENTIAL MOMENTARILY SHUNTS SIGNAL

FROM DC & UNLOCKS ELECTROMECHANICAL LOCK. ACCESS

IS THEN ACHIEVED BY MANUAL OPERATION OF LEVER. FREE

EGRESS IS PERMITTED AT ALL TIMES BY MANUAL OPERATION

OF LEVER LOCK.

DOOR

DOOR FRAME

EL

CR ACCESS/ENTRY SIDE

INTERIOR SIDE

JB

JUNCTION BOX ABOVE ACCESSIBLE

CEILING ON SECURE SIDE

1-1/4" C

TO LVSR

CONCEALED

DOOR CONTACTS

ELECTROMECHANICAL MORTISE LOCK WITH INTERGRAL

REQUEST TO EXIT

DC

EMERGENCY REX

CONNECT IN SERIES

BETWEEN REX AND

EM LOCK

TO LVSR

24 VAC AUDIBLE ALARM

CARD READER

POWER TRANSFER DEVICE

FINISHED FLOOR

OPERATIONAL DESCRIPTION:

TYPICAL SINGLE INTERIOR DOOR WITH ACCESS / ENTRY

CONTROL VIA CARD READER, 24 HOUR SECURED. DOORS IN

ALARM MODE. DOOR POSITION STATUS FOR EACH DOOR IS

MONITORED BY ELECTRONIC DOOR POSITION SWITCH

CONTACTS (DC). DOOR IS NORMALLY CLOSED AND LOCKED.

ELECTROMECHANICAL LOCK SHALL REMAIN IN SECURE MODE

DURING LOSS OF BUILDING POWER (FAIL SECURE). SIGNAL

FROM CARD CREDENTIAL MOMENTARILY SHUNTS SIGNAL

FROM DC & UNLOCKS ELECTROMECHANICAL LOCK. ACCESS

IS THEN ACHIEVED BY MANUAL OPERATION OF LEVER. FREE

EGRESS IS PERMITTED AT ALL TIMES BY MANUAL OPERATION

OF LEVER LOCK.

DOOR

DOOR FRAME

CARD

READER

EL

CR ACCESS/ENTRY SIDE

INTERIOR SIDE

JB

ACCESSIBLE CEILING

JUNCTION BOX ABOVE ACCESSIBLE

CEILING ON SECURE SIDE

1-1/4" C

TO LVSR

CONCEALED

DOOR CONTACTS

ELECTROMECHANICAL MORTISE LOCK WITH INTEGRAL

REQUEST TO EXIT

DC

POWER TRANSFER DEVICE

CR

CARD

READER

EGRESS

SIDE

ACCESS

SIDE

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

NEW ORLEANS, LOUISIANA

4TY002

BUILDING 04 SECURITY DOOR DETAILS

JLE JJPJUNE 30, 2011

CONSTRUCTION DOCUMENTS 1

629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, LOW VOLTAGE

ARCHITECTURAL ENGINEERING / PLUMBING

SCALES ASSOCIATES / FIRE PROTECTION

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

EWP_04

1/2" = 1'-0"

SINGLE DOOR ELEVATION-TYP DOOR

WITH CR & DC

1/2" = 1'-0"

SINGLE DOOR ELEVATION-TYP DOOR

WITH DC

1/2" = 1'-0"

DOUBLE DOOR ELEVATION

1/2" = 1'-0"

DOUBLE DOOR ELEVATION.

1/2" = 1'-0"

OVERHEAD DOOR ELEVATION

1/2" = 1'-0"

SINGLE DOOR ELEVATION-TYP DOOR

WITH DUAL CR & DC

5 ADDENDUM #6- POST BID 01/27/12

10 BULLETIN 011D 05/31/13

FINISHED FLOOR

OPERATIONAL DESCRIPTION:

SINGLE INTERIOR FRAMED GLASS DOOR. CARD

READER SYSTEM SHALL BE PROGRAMMED FOR

UNLOCKED OPERATION DURING THE DAY & LOCKED

OPERATION AT NIGHT. DOORS ARE IN ALARM MODE AT

NIGHT. AT NIGHT, DOOR POSITION STATUS FOR EACH

DOOR IS MONITORED BY ELECTRONIC DOOR POSITION

SWITCH CONTACTS (DC). DURING THE DAY, DOOR IS

NORMALLY CLOSED AND UNLOCKED. ACCESS BY

MANUAL OPERATION OF LEVER. AT NIGHT, DOOR IS

NORMALLY CLOSED AND LOCKED.

ELECTROMACHANICAL LOCK SHALL REMAIN IN

SECURE MODE DURING LOSS OF POWER (FAIL

SECURE). SIGNAL FROM CARD CREDENTIAL

MOMENTARILY SHUNTS SIGNAL FROM DC AND

UNLOCKS ELECTROMACHANICAL LOCK. ACCESS IS

THE ACHIEVED BY MANUAL OPERATION OF LEVER.

FREE EGRESS PERMITTED AT ALL TIMES BY MANUAL

OPERATION OF LEVER.

ALUMINUM &

GLASS DOOR

ALUMINUM DOOR

FRAME PREWIRED FOR

ELECTROMAGNETIC

LOCK & POWER

TRANSFER HINGE

PROXIMITY

CARD READER

23/4" C

EL

CR ACCESS/ENTRY SIDE

INTERIOR SIDE

JB

ACCESSIBLE CEILING - SEE RCP

JUNCTION BOX ABOVE ACCESSIBLE

CEILING ON INTERIOR SIDE

1-1/4" C

TO NEAREST

LVSR

CONCEALED DOOR CONTACTS (TYPICAL)

ELECTRIC STRIKE

DC

POWER TRANSFER DEVICE

TO FIRE ALARM

CONTROL MODULE

REQUEST TO

EXIT (REX)

INTERIOR SIDE

EXTERIOR SIDE

ACCESSIBLE CEILING - SEE RCP

2 2

JB

1-1/4" C

TO NEAREST

LVSR

JUNCTION BOX

ABOVE ACCESSIBLE

CEILING ON

INTERIOR SIDE

CONCEALED DOOR

CONTACTS (TYPICAL)

POWER

TRANSFER

DEVICE

POWER

TRANSFER

DEVICE

120V BY DIV 26PS

EL EL

LOW ENERGY, POWER

ASSIST OPERATOR

DC DC

AUTO-DOOR

ACTIVATION SWITCH ON

EXTERIOR COLUMN BY

AUTO-DOOR SUPPLIER

AS

AUTO-DOOR

ACTIVATION

SWITCH ON

INTERIOR WALL

BY AUTO-DOOR

SUPPLIER

FRAME

DOOR

FIN. FLR.

AS

AS

AS

AUTO-DOOR ACTIVATION

SWITCH BY AUTO-DOOR

SUPPLIER

AUTO-DOOR ACTIVATION

SWITCH BY AUTO-DOOR

SUPPLIER

LOCAL POWER SUPPLY

GENERAL NOTES:

1. ALARM MODE FOR DAY / NIGHT OPERATION SHALL REFER TO THAT PERIOD OF TIME

BETWEEN HOURS OF 6:00 PM AND 7:00 AM EVERY DAY, WHERE THE SECURITY

MANAGEMENT SYSTEM SHALL BE ACTIVATED. DOORS WITH 24 HOUR OPERATION SHALL BE

IN ALARM 24 HOURS PER DAY.

2. COORDINATE ALL SECURITY DEVICES WITH THE FINAL DOOR HARDWARE SCHEDULE

AND SPECIFICATION SECTION 088710.

DOOR WIRING LEGEND

(1)#18AWG, 2-CONDUCTOR, UNSHIELDED TWISTED PAIR CABLE WITHIN 3/4" CONCEALED CONDUIT

(1)#18AWG, 4-CONDUCTOR, UNSHIELDED TWISTED PAIR CABLE WITHIN 3/4" CONCEALED CONDUIT

(1)#18AWG, 6-CONDUCTOR, UNSHIELDED TWISTED PAIR CABLE WITHIN 3/4" CONCEALED CONDUIT

(1)#18AWG, 8-CONDUCTOR, SHIELDED TWISTED PAIR CABLE WITHIN 3/4" CONCEALED CONDUIT

(1)#22AWG, 2-CONDUCTOR, UNSHIELDED TWISTED PAIR CABLE WITHIN 3/4" CONCEALED CONDUIT

(1)#18AWG, 4-CONDUCTOR, SHIELDED TWISTED PAIR CABLE WITHIN 3/4" CONCEALED CONDUIT

CARD READER

INTERCOM

STANTION BY GARAGE

CONTROLS VENDOR/GC

ISLAND

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

NEW ORLEANS, LOUISIANA

4TY003

BUILDING 04 SECURITY DOOR DETAILS

JLE JJPJUNE 30, 2011

CONSTRUCTION DOCUMENTS 1

629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, LOW VOLTAGE

ARCHITECTURAL ENGINEERING / PLUMBING

SCALES ASSOCIATES / FIRE PROTECTION

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

EWP_04

1/2" = 1'-0"

SINGLE DOOR ELEVATION

1/2" = 1'-0"

DOUBLE DOOR ELEVATION .

1 1/2" = 1'-0"

GARAGE CONTROL STANTION

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

NEW ORLEANS, LOUISIANA

4TY004

BUILDING 04 SECURITY CAMERA DETAILS

JLE JJPJUNE 30, 2011

CONSTRUCTION DOCUMENTS 1

629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, LOW VOLTAGE

ARCHITECTURAL ENGINEERING / PLUMBING

SCALES ASSOCIATES / FIRE PROTECTION

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

EWP_04

HH

CEILING MOUNTED FIXED MINI DOME CAMERA

SCALE: NTS

SCALE: NTS

EXTERIOR WALL MOUNTED CAMERA

SCALE: NTS

EXTERIOR CORNER MOUNTED CAMERA

LIGHT POLE BASE AND HANDHOLE REFERENCE DETAIL

SCALE: NTS

SCALE: NTS

POLE MOUNT CAMERA

INTERIOR WALL MOUNTED FIXED DOME CAMERA

SCALE: NTS

INTERIOR PENDANT SUSPENDED DOME CAMERA

SCALE: NTS5

7 8

NOTE:

1. COORDINATE COLORS AND FINISHES, OF

CAMERA DOME HOUSING, MOUNTING

BRACKET AND POLE / LIGHT POLE. SUBMIT

COLORS FOR APPROVAL BY ARCHITECT.

TINTED DOME

SUN SHIELD

SECURE WITH 3/8" STAINLESS

STEEL FASTENERS

ENVIRONMENTAL DOME WITH

HEATER & BLOWER

CAMERA MOUNTING BRACKET

MOUNT

TINTED DOME

SUN SHIELD

SECURE WITH STAINLESS STEEL MOUNTING

FASTENERS OF APPROPRIATE LENGTH

MOUNTING CLEAT

ADJUSTMENT PLATE

CORNER MOUNT WITH ACCESS PANEL

USE 3/8" STAINLESS STEEL BOLTS OF

APPROPRIATE LENGTH.

ENVIRONMENTAL DOME WITH

HEATER & BLOWER

ROOF LEVEL

M

IN

NOTES:

HAND HOLE WITH SOLID BOTTOM

13"W X 24"L X 11"D (CLEAR INSIDE)

WITH THE WORD "SECURITY" LOGO

ON COVER.

TYPICAL

CONDUITS 36"

BELOW FINISHED

GRADE.

BY EC. SEE

9ESS1 FOR

DETAILS

CAST-IN-PLACE ARCHITECTURAL

CONCRETE BASE BY OTHERS

(COORDINATE CONDUIT

INSTALLATION WITH CM),

COORDINATE WITH HARDSCAPE

AND CIVIL DRAWINGS

POLE INSTALLATION IS BY

OTHERS.

REFER TO ELECTRICAL

DRAWINGS

FOR REQUIREMENTS.

CONTRACTOR TO VERIFY

OPENING

SIZE IN POLE BASE PLATE

PRIOR

TO SETTING CONDUIT

SLEEVES.

1.

2.

POLE REFER TO

LANDSCAPE

AND ARCHITECTURAL

DRAWINGS

FOR ADDITIONAL

INFORMATION

BUSHED

CONDUIT END

WITH DUCT SEAL

LOW VOLTAGE

CONDUIT TO LVSR.

BY EC. SEE 9ESS1

FOR DETAILS

SECURITY CABLE

EXTERIOR POLE

MOUNTED

CAMERA

(REFER TO DETAIL

#3)

4"x4" BACK BOX

POLE MOUNTED ADAPTER

TINITED DOME

SUN SHROUD

SPLIT WASHERS AND NUTS

ENVIRONMENTAL DOME WITH

HEATER & BLOWER

MOUNT

POLE BASE COVER

FIN. GRADE

POLE HANDHOLE

COORDINATE

INSTALLATION WITH

ARCHITECT PRIOR TO

COMMENCING

WITH WORK

3.

3" (MINIMUM) POLE

BACKBOX 6"X6"X2"

CONDUIT TO LVSR

WALL

MOUNT

TINTED DOME

DOME

MOUNTING CLEAT PROVIDED WITH MOUNT

ADJUSTMENT PLATE PROVIDED WITH MOUNT

SECURE WITH MOUNTING FASTENERS OF

APPROPRIATE

LENGTH AND SIZE, SUITED FOR

ENVIRONMENT

TINTED DOME

DOME

1" CONDUIT TO LVSR

THREADED COUPLING

RIGID CONDUIT

JUNCTION BOX

TYPICAL CONDUIT TO

LVSR

LIGHT POLE SHALL HAVE

SEPARATE

1-1/2" RACEWAY

DEDICATED TO

LOW VOLTAGE CABLING.

4.

M

IN

PROVIDE INTEGRAL POLE MOUNT

BRACKET - NO STRAPS

3/4" CONDUIT TO LVSR

CEILING

CAMERA HOUSING

TINTED MINI DOMED INTERIOR

ANTI TAMPER FASTENERS

CUT AWAY SIDE VIEW

MOUNT/SECURE TO

STRUCTURE PER

SEISMIC REQUIREMENTS

WITH 12 GA. MINIMUM

HANGER WIRE - TYPICAL

CAMERA BACKBOX

6"X6"X2"BACKBOX

1" CONDUIT TO LVSR

WALL

ANTI-TAMPER FASTENERS

TINTED MINI DOME

INTERIOR WALL MOUNTED FIXED MINI DOME CAMERA

SCALE: NTS

MOUNT PER ADA

STANDARDS -

COORDINATE WITH

ARCHITECTURAL

DRAWINGS

INTERCOM SUB

STATION W/

STAINLESS STEEL

FACEPLATE - SEE

SPEC

CONDUIT

PARTITION

SURFACE MOUNTED

INTERCOM SUB STATION

- SEE PLANS FOR

LOCATIONS & QUANTITY

EMERGENCY TELEPHONE TOWER -

SEE SPEC

FINISHED GRADE

M

IN

M A X A B O V E F

IN

G R A D E O R T O P O F C O N C R E T E S

ID

E W

A L K

PROVIDE EMERGENCY TELEPHONE CABLING

PER SPECIFICATIONS - CONNECT TO

EMERGENCY TELEPHONE TOWER PER

MANUFACTURERS INSTALLATION

REQUIREMENTS

PROVIDE DEDICATED 1-1/2" WIDE

RACEWAY WITHIN TOWER FOR LVSR

CABLING ONLY

PROVIDE 1" CONDUIT FROM FIRST

FLOOR LVSR STUBBED TO TOWER

LOCATION - COORDINATE WITH PLAN

SEPARATE RACEWAY AND CONDUITS

FOR ELECTRICAL POWER

NOTE:

REFER TO ELECTRICAL

DRAWINGS FOR ALL

POWER & GROUNDING

INFORMATION - ALL

WORK TO BE DONE PER

MANUFACTURES

INSTALLATION

REQUIREMENTS.

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

NEW ORLEANS, LOUISIANA

4TY005

BUILDING 04 SECURITY DETAILS

JLE JJPJUNE 30, 2011

CONSTRUCTION DOCUMENTS 1

629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, LOW VOLTAGE

ARCHITECTURAL ENGINEERING / PLUMBING

SCALES ASSOCIATES / FIRE PROTECTION

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

EWP_04

6" = 1'-0"

INTERCOM DETAIL

1" = 1'-0"

EMERGENCY TELEPHONE TOWER

4 CABLES

8 CABLES

11 CABLES

19 CABLES

33 CABLES

50 CABLES

83 CABLES

1-INCH

2-INCH

3-INCH

1-1/4-INCH

1-1/2-INCH

2-1/2-INCH

4-INCH

EMT TRADE

SIZE

ALLOWABLE NO. OF

CAT 6A CABLES

** CABLE COUNT BASED ON NEC ALLOWABLE FILL RATIO

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

NEW ORLEANS, LOUISIANA

4TY006

BUILDING 04 SECURITY DETAILS

JLE JJPJUNE 30, 2011

CONSTRUCTION DOCUMENTS 1

629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, LOW VOLTAGE

ARCHITECTURAL ENGINEERING / PLUMBING

SCALES ASSOCIATES / FIRE PROTECTION

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

EWP_04

BOX SUPPORT OFFSET

WOOD OR

METAL

WALL STUD

TYPICAL SECURITY DEVICE BOX DETAILWALL SECTION AT ACCESS READER

SCALE: NTS SCALE: NTS

PANIC SWITCH INSTALLATION DETAIL

SCALE: NTS

1 2

6"X6" STEEL DEVICE COVER

PLATE (SINGLE GANG)

CONTRACTOR TO SIZE DEPTH

OF DEVICE COVER PLATE TO

INCLUDE BOX SUPPORT

OFFSET, THICKNESS OF

DRYWALL AND WALL COVERING

(IF USED).

ELECTRICAL CONTRACTOR TO

SIZE DEPTH OF

PLASTER RING TO INCLUDE BOX

SUPPORT

OFFSET, THICKNESS OF DRYWALL

AND WALL

COVERING (IF USED).

6"X6" STEEL DEVICE

COVER

PLATE (SINGLEGANG

DEVICE)

6"X6"X2" METAL

BOX WITH PLASTER

RING

BOX SUPPORT OFFSET

WOOD OR

METAL

WALL STUD

1" CONDUIT WITH APPROVED

LOCKOUT AND BUSHING TO

INTERFACE JUNCTION BOX

ABOVE ASSOCIATED DOOR

LOCATION

JUNCTION BOX

(6"X6"X2")

SINGLE GANG DEVICE COVER

PLATE (ELECTRICAL

CONTRACTOR TO SIZE DEPTH

OF PLASTER RING TO INCLUDE

BOX SUPPORT OFFSET,

THICKNESS OF DRYWALL AND

WALL COVERING (IF USED).

BOX SUPPORT OFFSET

JUNCTION BOX

(6"X6"X 2" D)

FRONT VIEW

TOP VIEW (PARTITION)

WALL BOARD / FINISH

ISOMETRIC VIEW

TYPICAL SECURITY DEVICE

TYPICAL SECURITY DEVICE

1" CONDUIT WITH APPROVED LOCKNUT

AND BUSHING TO INTERFACE JUNCTION

BOX ABOVE ASSOCIATED DOOR LOCATION

1" CONDUIT WITH APPROVED

LOCK NUT AND BUSHING TO

INTERFACE JUNCTION BOX

ABOVE ASSOCIATED DOOR

LOCATION

R E F E R T O A R C H

IT

E C T U R A L D R A W

IN

G S

SURFACE MOUNTED PROXIMITY READER

SINGLE-GANG OR 2-GANG

BACKBOX OFFSET IN

WALL

(HORIZ)

BACKBOXES ARE

STAGGERED.

DO NOT MOUNT

BACKBOXES

BACK TO BACK.

NOTE:

EXTENSION RING

CONDUIT

WALL

COUPLING

LVSR

CONDUIT SLEEVES DEDICATED TO SECURITY

TYPICAL PARTITION

TYPICAL DESK TOP

PANIC SWITCH MOUNTED

UNDER

COUNTER TOP. INSTALL SWITCH

PER UL 305 UL STANDARD

6"x6" BACK BOX FOR CABLE FEED

METALLIC FLEX CONNECTOR

TO PANIC SWITCH BACK BOX

PANIC SWITCH BACK BOX

SECURITY PANEL

1" C

22/2 AWG SECUIRTY CABLE

FINISHED FLOOR

CEILING

WALL MOUNTED

SIDE ELEVATION

EMT CONDUIT FILL TABLE

SCALE: 12" = 1'-0"

04-L1 100' - 0" 05-L1 100' - 0"

OPERATIONAL REQUIREMENTS

DOOR IS NORMALLY CLOSED AND LOCKED. ACCESS/

ENTRY TO INTERIOR IS PERMITTED VIA AUTHORIZED

CARD CREDENTIAL OR KEY. OUTSIDE LEVER IS ALWAYS

FIXED. AUTHORIZED CARD CREDENTIAL RELEASES THE

ELECTRIC STRIKE OR KEY AT OUTSIDE LEVER RETRACTS

LATCHBOLT. IN ALARM MODE, DOOR POSITION (OPEN OR CLOSED)

IS MONITORED VIA CONCEALED MAGNETIC SWITCH CONTACT.

INTERIOR LEVER RETRACTS LATCHBOLT AT ALL TIMES (FREE

EGRESS). CAMERA RECORDS FOR 5 SECONDS UPON AUTHORIZED

CARD CREDENTIAL. CAMERA RECORDS CONTINUOUSLY UPON

ALARM EVENT UNTIL RESET BY AUTHORIZED PERSONNEL.