Drawing P201 Plumbing Enlarged Basement Floor Plan Rooms-Remodel.pdf

PDF 4 MB Posted

Attached to
Z2DA--Correct Reusable Medical Equipment Storage PN: 589A4-24-101
Solicitation number
36C25525R0114
Issued by

About this file

These are plumbing engineering design drawings for a VA Medical Center project located at 800 Hospital Drive in Columbia, Missouri. The project involves remodeling and upgrading plumbing systems across multiple floors, including the basement, third floor, elevator machine rooms, and penthouse areas. The drawings, prepared by Alesia Architecture P.C. and dated 07/25/2025, detail specific plumbing modifications such as installing new water softener equipment, providing condensate drain connections, extending water supply piping, and adding make-up water lines to various mechanical systems. The documents are marked as 100% Final Bid Documents and include two amendments (dated 07/29/2025 and 08/05/2025), indicating the project is in its final stages of design and preparation for construction bidding.

The plumbing design drawings comprehensively cover existing and proposed piping configurations, with detailed keynotes specifying exact installation requirements. Key technical specifications include provisions for softened water connections, condensate drains with specific slope requirements, backflow preventer installations, and precise piping routing instructions. The drawings specify that all piping installed above head should be placed as close to the structure as possible, but no less than 8 feet above the finished floor. The project is fully sprinklered and involves upgrades to the Correct Reusable Medical Equipment Storage and ACA HVAC systems, with the engineering work certified by a registered professional engineer from California.

View the file

Other files

Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WORK

ROOM

F002

MECH

ROOM

E003

ELEC ROOM

E003A

COLD ROOM

B037A

(E)ACA-AHU-6

ACA-AHU-3 BY

MECHANICAL

ACA-AHU-2 BY

MECHANICAL

ACA-AHU-1 BY

MECHANICAL

ACA-AHU-4 BY

MECHANICAL

ACA-USG-1 BY

MECHANICAL

(E)USG

(E)FD

(E)FD (E)FD

(E)FD

(E)FD

(E)FD

(E)FD

(E)HB

(E)FD

(E)FD

(E)3/4"

(E )3

/4

(E)2 1/2" CW UP

(E)3/4"

(E)2 1/2"

(E )4

(E

)3

(E)4"

(E)4" CW DN

(E)FD

(E)FD

(E)FD

3/4" SW

(E)HB

(E)SW

ACA-AS-1 BY

MECHANICAL

3/4" D

RPBP-2

2" MU

PRV-1

WS-1

2 3 1 4 5 5.6

B

C

D.1

D

A

1" D

(E)CW

P401

(TYP)

1" CD

3/4" D

3/4" D

1" CD

3/4" D

3/4" D

1" CD

3/4" D

3/4" D

3/4" D

3/4" D

1" CD

3/4" CW DN

3/4"CW

113/4" CW DN

3/4" CW DN113/4" CW DN 11

N

3/16" = 1'-0"1

PLUMBING - ENLARGED BASEMENT FLOOR PLAN - MECH. RM E003 - REMODEL

RE

G

IS

TE

RE

DPROFESSIONALENG

IN

EERER

IC

M.DeSPLINTER

M

ECHANICA

L

S

TATE OF CALIFORNIA

38688 Exp. 12-31-25

SIGNED: 06/23/25

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CORRECT REUSABLE

MEDICAL EQUIP STORAGE

589A4-24-101

800 HOSPITAL DR, COLUMBIA, MO

Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015

Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383

Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086

(412) 212-7515

STAMP

07/25/2025

BASEMENT KEYPLAN

NORTH

E & F

SHIPPING

WAREHOUSE

OR ADDITION B A

ACA BUILDING

AREAS

AREA AREA

G

AREA

C & D

AREAS

BUILDING 1

100% FINAL BID

DOCUMENTS

A u to d e s k D o c s /1

A

-2

-1

C o rr e c t R e u s a b le

M e d ic a l E q u ip m e n t S to ra g e /2

M

E P

T

.0

C o lu m b ia

M

O V

A M

C R

M E

S to ra g e

A C

A H

V A

C U p g ra d e s .r v t

-0 -2

:0

:2

P

M

P201

RSS PSK

PLUMBING - ENLARGED BASEMENT FLOOR

PLAN ROOMS - REMODEL

KEYNOTES - P201

NUMBER TEXT

EXTEND NEW WALL-MOUNTED 3/4" SW FROM EXISTING SYSTEM TO ACA-USG-1

COMPLETE WITH LINE SIZE ISOLATION VALVE.

RECONNECT CW AND SW PIPING FROM ISOLATION VALVES TO THE NEW WATER

SOFTENER EQUIPMENT.

PROTECT IN PLACE EXISTING DRAIN MOUNTED TO WALL FROM THE BACKFLOW

PREVENTER TO THE FLOOR SINK.

4 PROTECT IN PLACE EXISTING WALL MOUNTED BACKFLOW PREVENTER ASSEMBLY.

PROVIDE CONDENSATE DRAIN FROM EQUIPMENT TO FLOOR SINK. SPILL 1"

ABOVE FLOOD LEVEL RIM MINIMUM. SEE DETAIL 1/P401 FOR ADDITIONAL

INFORMATION.

PROVIDE INDIRECT DRAIN FROM BACK FLOW PREVENTER TO FLOOR SINK. SPILL

1" ABOVE FLOOD LEVEL RIM MINIMUM.

PROTECT IN PLACE EXISTING WALL-MOUNTED SW PIPING ABOVE AND CW PIPING

BELOW.

PROVIDE NEW BACKFLOW PREVENTER ASSEMBLY AND PIPING ABOVE HEAD AS

SHOWN TO THE EQUIPMENT ACA-AS-1.

DEDUCT 1: DO NOT PROVIDE CONDENSATE PIPING FROM ACA-AHU-4

EQUIPMENT.

DEDUCT 2: DO NOT PROVIDE CONDENSATE PIPING FROM ACA-AHU-3, AND

ACA-AHU-4 EQUIPMENT.

11 PROVIDE 3/4"CW PIPING TO DRAIN COOLER AS SHOWN.

3/4" INDIRECT DRAIN FROM HUMIDIFIER ABOVE AND 3/4" DRAIN FROM DRAIN

COOLER BELOW. SEE DETAIL 9/MP401 FOR MORE INFORMATION.

WHERE PIPING IS CALLED OUT TO BE INSTALLED ABOVE HEAD, PIPING SHALL BE

PLACED AS CLOSE TO THE STRUCTURE AS POSSIBLE, BUT NO LESS THAN 8' ABOVE

FINISHED FLOOR.

NUMBER TEXT

GENERAL NOTES - P201

Mark Revisions: Date:

1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES 07/29/2025

2 AMENDMENT #2 08/05/2025

CLEAN

RECEIVING

BREAKOUT

G048

BULK

STORE

ROOM

G047

ETO

STERILIZER

ACCESS

G045

STERILIZER

ACCESS

G043A

MECH

ROOM

G001

USG-2 BY

MECHANICAL

(E)AHU-8

(E)USG-1

(E)HX-4

(E)HX-3

(E)HX-2

(E)HX-1

(E)CP-1

(E)AHU-9

(E)AHU-7A

(E)AHU-7B

(E)WATER

SOFTENING

SYSTEM

3/4" SW

1" D

(E)FD

(E)FD(E)FD

8.2

9.1

Z V

8.3

8.9

9.8

BB AA Y X W

(E)AC-S13

(E)AHU-14

WORK SHOWN EAST OF THIS

LINE IS IN PIPE BASEMENT.

(E)FD

D 1" D

USG-3 BY

MECHANICAL

WS-1

3/4" SW ABOVE HEAD

3/4" CW ABOVE HEAD

(E )4

C

W (E

)4

C W

3/4" D

(E)FD

RPBP-1

T S R Q P Na N

8.2

9.1

10.4

11.5

8.3

8.9

9.8

10.2

H-3 BY

MECHANICAL

H-2 BY

MECHANICAL

1" D

1" D

MP401

MP401

1" D

3/4" CW

3/4" CW

3/4" CW

3/4" CW 8

8 3/4" CW

RE

G

IS

TE

RE

DPROFESSIONALENG

IN

EERER

IC

M.DeSPLINTER

M

ECHANICA

L

S

TATE OF CALIFORNIA

38688 Exp. 12-31-25

SIGNED: 06/23/25

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CORRECT REUSABLE

MEDICAL EQUIP STORAGE

589A4-24-101

800 HOSPITAL DR, COLUMBIA, MO

Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015

Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383

Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086

(412) 212-7515

STAMP

07/25/2025

BASEMENT KEYPLAN

NORTH

E & F

SHIPPING

WAREHOUSE

OR ADDITION B A

ACA BUILDING

AREAS

AREA AREA

G

AREA

C & D

AREAS

BUILDING 1

100% FINAL BID

DOCUMENTS

A u to d e s k D o c s /1

A

-2

-1

C o rr e c t R e u s a b le

M e d ic a l E q u ip m e n t S to ra g e /2

M

E P

T

.0

C o lu m b ia

M

O V

A M

C R

M E

S to ra g e

A C

A H

V A

C U p g ra d e s .r v t

-0 -2

:0

:2

P

M

P202

RSS PSK

PLUMBING - ENLARGED BASEMENT FLOOR

PLAN ROOMS - REMODEL

N

3/16" = 1'-0"2

PLUMBING - ENLARGED BASEMENT FLOOR PLAN - RM G001 - REMODEL

N

1/8" = 1'-0"1

PLUMBING - ENLARGED PIPE BASEMENT FLOOR PLAN - RM C012 - REMODEL

KEYNOTES - P202

NUMBER TEXT

PROVIDE SOFTENED WATER TO USG-3 ABOVE HEAD FROM WATER SOFTENER AS

SHOWN.

PROVIDE SOFTENED WATER TO USG-2 ABOVE HEAD FROM EXISTING WATER

SOFTENER AS SHOWN.

PROVIDE CONDENSATE DRAIN FROM FIXTURE TO FLOOR SINK. SPILL 1" ABOVE

FLOOD LEVEL RIM MINIMUM.

PROVIDE INDIRECT DRAIN FROM BACKFLOW PREVENTER TO FLOOR SINK. SPILL 1"

ABOVE FLOOD LEVEL RIM MINIMUM.

PROVIDE A NEW FLOOR-MOUNTED WATER SOFTENER. EXTEND 3/4" COLD

WATER TO THE NEW EQUIPMENT FROM THE EXISTING MAIN ABOVE HEAD

COMPLETE WITH NEW BACKFLOW PREVENTER ASSEMBLY.

PROVIDE CONDENSATE DRAIN FROM H-3 ABOVE HEAD TO THE FLOOR SINK AS

SHOWN. SPILL 1" ABOVE FLOOD LEVEL RIM MINIMUM.

7 PROVIDE 1" DRAIN AT FLOOR LEVEL TO (E)FD. SPILL 1" ABOVE FLOOD LEVEL RIM.

8 PROVIDE 3/4"CW PIPING TO DRAIN COOLER AS SHOWN.

WHERE PIPING IS CALLED OUT TO BE INSTALLED ABOVE HEAD, PIPING SHALL BE

PLACED AS CLOSE TO THE STRUCTURE AS POSSIBLE, BUT NO LESS THAN 8' ABOVE

FINISHED FLOOR.

NUMBER TEXT

GENERAL NOTES - P202

Mark Revisions: Date:

1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES 07/29/2025

2 AMENDMENT #2 08/05/2025

H-1 BY

MECHANICAL

P401

ABOVE HEAD

/4

D

(E)TU-AHU7-002

FIRE SEAL, SEE

3/4" D

MP401

(E)MS

(E)S

3/4" CW 2

RE

G

IS

TE

RE

DPROFESSIONALENG

IN

EERER

IC

M.DeSPLINTER

M

ECHANICA

L

S

TATE OF CALIFORNIA

38688 Exp. 12-31-25

SIGNED: 06/23/25

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CORRECT REUSABLE

MEDICAL EQUIP STORAGE

589A4-24-101

800 HOSPITAL DR, COLUMBIA, MO

Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015

Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383

Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086

(412) 212-7515

STAMP

07/25/2025

THIRD FLOOR KEYPLAN

NORTH

E & F

SHIPPING

WAREHOUSE

OR ADDITION B A

ACA BUILDING

AREAS

AREA AREA

G

AREA

C & D

AREAS

BUILDING 1

100% FINAL BID

DOCUMENTS

A u to d e s k D o c s /1

A

-2

-1

C o rr e c t R e u s a b le

M e d ic a l E q u ip m e n t S to ra g e /2

M

E P

T

.0

C o lu m b ia

M

O V

A M

C R

M E

S to ra g e

A C

A H

V A

C U p g ra d e s .r v t

-0 -2

:0

:3

P

M

P203

RSS PSK

PLUMBING - ENLARGED THIRD FLOOR PLAN

ROOMS - REMODEL

KEYNOTES - P203

NUMBER TEXT

1 3/4"D DOWN IN WALL TO MOP SINK. SPILL 1" ABOVE FLOOD LEVEL RIM.

2 PROVIDE 3/4"CW PIPING TO DRAIN COOLER AS SHOWN.

PROVIDE 3/4" CW FROM FROM EXISING WATER SUPPLY TO SINK. CONTRACTOR

TO FIELD VERIFY EXACT LOCATION.

N

1/4" = 1'-0"1

PLUMBING - ENLARGED THIRD FLOOR PLAN - RM E320 - REMODEL

WHERE PIPING IS CALLED OUT TO BE INSTALLED ABOVE HEAD, PIPING SHALL BE

PLACED AS CLOSE TO THE STRUCTURE AS POSSIBLE, BUT NO LESS THAN 8' ABOVE

FINISHED FLOOR.

NUMBER TEXT

GENERAL NOTES - P203

Mark Revisions: Date:

1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES 07/29/2025

2 AMENDMENT #2 08/05/2025

(E)AC-S4

(E)FD

(E)FD

1" D

USG-4 BY

MECHANICAL

(E)CW DN TO

BELOW FLOOR

(E)HB

(E)PUMP

(E)BACK FLOW

PREVENTER

3/4" MU

WS-1

3/4" SW

/4

S

W

3/4" D

3/4" D

FD-S-Z-HP-Y-2

PIPING ABOVE

HEAD

PIPING ABOVE

HEAD

L K Jb J Hb H

5.4

5.5

6.2

6.3

6.7

7.2

8.2

7.6

P401

3/4" MU

3/4" MU UP

(E)FD

3/4"D FROM ABOVE

(E)FD

3/4"D FROM

DRAIN COOLER

(E)AC-S3

L K Jb J Hb H

5.4

5.5

6.2

6.3

6.7

7.2

8.2

7.6

/4

M

U

3/4" MU

/4

M

U

3/4"SW FROM

BELOW

RE

G

IS

TE

RE

DPROFESSIONALENG

IN

EERER

IC

M.DeSPLINTER

M

ECHANICA

L

S

TATE OF CALIFORNIA

38688 Exp. 12-31-25

SIGNED: 06/23/25

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CORRECT REUSABLE

MEDICAL EQUIP STORAGE

589A4-24-101

800 HOSPITAL DR, COLUMBIA, MO

Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015

Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383

Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086

(412) 212-7515

STAMP

07/25/2025

100% FINAL BID

DOCUMENTS

NORTH

E & F

OR ADDITION B A

C & D

ACA BUILDING

AREAS

AREA AREA

AREAS

G

AREA BUILDING 1

PENTHOUSE FLOOR KEYPLAN

A u to d e s k D o c s /1

A

-2

-1

C o rr e c t R e u s a b le

M e d ic a l E q u ip m e n t S to ra g e /2

M

E P

T

.0

C o lu m b ia

M

O V

A M

C R

M E

S to ra g e

A C

A H

V A

C U p g ra d e s .r v t

-0 -2

:0

:3

P

M

P204

RSS PSK

PLUMBING - PENTHOUSE FLOOR PLAN

N

3/16" = 1'-0"1

PLUMBING - ELEVATOR MACHINE ROOM - LOWER LEVEL - REMODEL

KEYNOTES - P204

NUMBER TEXT

1 NEATLY SAWCUT THE FLOOR TO PROVIDE FLOOR SINK.

PROVIDE CONDENSATE DRAIN FROM FIXTURE TO FLOOR SINK. SPILL 1" ABOVE

FLOOD LEVEL RIM MINIMUM.

3 PROVIDE 3/4"MAKE UP WATER PIPING TO DRAIN COOLER AS SHOWN.

WHERE PIPING IS CALLED OUT TO BE INSTALLED ABOVE HEAD, PIPING SHALL BE

PLACED AS CLOSE TO THE STRUCTURE AS POSSIBLE, BUT NO LESS THAN 8' ABOVE

FINISHED FLOOR.

NUMBER TEXT

GENERAL NOTES - P204

Mark Revisions: Date:

2 AMENDMENT #2 08/05/2025

N

3/16" = 1'-0"2

PLUMBING - ELEVATOR MACHINE ROOM - UPPER LEVEL - REMODEL

3/4"D FROM

DRAIN COOLER

DN TO BELOW

NUT (TOP & BOTTOM)

ALL THREADED ROD

WASHER (TOP & BOTTOM)

PROVIDE PLASTIC COATED

HANGER WHEN HANGING

DISSIMILAR METAL PIPING.

ALL THREADED ROD

PROVIDE PLASTIC COATED

HANGER WHEN HANGING

DISSIMILAR METAL PIPING.

KNURLED HANGER

ROD NUT

DETAIL NOTES:

1. PROVIDE MINIMUM 1/2" SPACING BETWEEN FINISHED COVERING AND

ADJACENT WORK.

UNINSULATED PIPE

UNINSULATED/INSULATED

PIPE

SWIVEL RING HANGER CLEVIS HANGER

CONDENSATE DRAIN CONNECTION NTS 1

SUSPENDED PIPE SUPPORT NTS 2

FIRE SEAL OF 2 HR RATED FLOOR - FLOOR SINK NTS 4FIRE SEAL OF 1 HR RATED WALL - INSULATED PIPE NTS 5 HUMIDIFIER CONDENSATE PIPE CONNECTION TO DRAIN NTS 3

3/4"CONDENSATE PIPING

FROM HUMIDIFIER AND

DRAIN COOLER

1" DRAIN PIPING FROM

COOLING COIL(PLUMBING)

OPEN VENT

1"DRAIN TO

PLUMBING RECEPTOR

2% SLOPE

2% SLOPE

RE

G

IS

TE

RE

DPROFESSIONALENG

IN

EERER

IC

M.DeSPLINTER

M

ECHANICA

L

S

TATE OF CALIFORNIA

38688 Exp. 12-31-25

SIGNED: 06/23/25

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CORRECT REUSABLE

MEDICAL EQUIP STORAGE

589A4-24-101

800 HOSPITAL DR, COLUMBIA, MO

Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015

Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383

Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086

(412) 212-7515

STAMP

07/25/2025

100% FINAL BID

DOCUMENTS

A u to d e s k D o c s /1

A

-2

-1

C o rr e c t R e u s a b le

M e d ic a l E q u ip m e n t S to ra g e /2

M

E P

T

.0

C o lu m b ia

M

O V

A M

C R

M E

S to ra g e

A C

A H

V A

C U p g ra d e s .r v t

-0 -2

:0

:3

P

M

P401

RSS PSK

PLUMBING - DETAILS

Mark Revisions: Date:

1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES 07/29/2025

2 AMENDMENT #2 08/05/2025

P201 - PLUMBING -ENLARGED BASEMENT FLOOR PLAN ROOMS -REMODEL
P202 - PLUMBING -ENLARGED BASEMENT FLOOR PLAN ROOMS -REMODEL
P203 - PLUMBING -ENLARGED THIRD FLOOR PLAN ROOMS -REMODEL
P204 - PLUMBING -PENTHOUSE FLOOR PLAN
P401 - PLUMBING -DETAILS

File details come from the government source that posted it. Updated .