The document is a plumbing design set for the VA Medical Center project in Columbia, Missouri, specifically for correcting reusable medical equipment storage and HVAC upgrades. The plumbing sheets cover multiple floors (basement, first, third, and sixth) and include detailed renovation plans, demolition plans, enlarged floor plans, and technical details for plumbing systems. Key plumbing components include reduced pressure backflow preventers (RPBP-1 and RPBP-2), a water softener (WS-1), pressure reducing valves (PRV-1), and condensate drain connections. The design follows multiple building codes including the 2021 International Building Code, 2024 NFPA Life Safety Code, and 2022 NFPA National Fire Codes, with specific emphasis on professional installation, coordination between contractors, and compliance with VA project phasing requirements. The project involves multiple construction phases with work to be performed during unoccupied hours and careful coordination with VA staff to minimize disruption to hospital operations.

View the file

Other files

Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PLUMBING SHEET INDEX:

AFF ABOVE FINISHED FLOOR

AHU AIR-HANDLING UNIT

BFP BACKFLOW PREVENTOR

BHP BRAKE HORSEPOWER

BTU BRITISH THERMAL UNIT

CFM CUBIC FEET PER MINUTE

CU FT CUBIC FEET

DIA, Ø DIAMETER

DN DOWN

DTR DOWN THRU ROOF

EL ELEVATION

ECM ELECTRONICALLY COMMUTATED MOTOR

FPS FEET PER SECOND

FT, ' FOOT OR FEET

FT LB FOOT-POUND

FD FLOOR DRAIN

GA GAGE OR GAUGE

GAL GALLONS

HD HEAD (PRESSURE)

HT HEIGHT

ID DIAMETER, INSIDE

IE INVERT ELEVATION BELOW FINISHED FLOOR

IN., " INCH OR INCHES

LF LINEAR FOOT OR FEET

MAX MAXIMUM

MIN MINIMUM

N/A NOT APPLICABLE

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NO., # NUMBER

NTS NOT TO SCALE

OA OUTSIDE AIR

OD DIAMETER, OUTSIDE

PDI PLUMBING & DRAINAGE INSTITUTE

PML PLUMBING MATERIAL LIST

PPM PARTS PER MILLION

PSI POUNDS PER SQUARE INCH

RPM REVOLUTIONS PER MINUTE

RTU ROOFTOP UNIT

SCFM CFM, STANDARD CONDITIONS

SPEC SPECIFICATION

T TON

UTR UP THRU ROOF

VTR VENT THRU ROOF

PLUMBING ABBREVIATIONS:

ABBREVIATION DESCRIPTION

CW POTABLE COLD WATER

NOTES:

1. NOT ALL ABBREVIATIONS MAY APPLY.

2. PLUMBING MATERIAL LIST/PLUMBING SCHEDULES CONTAIN EQUIPMENT TAG

ABBREVIATIONS THAT ARE HEREBY INCORPORATED INTO THE ABBREVIATION LIST.

3. SEE OTHER DISCIPLINE DRAWINGS WITHIN THE CONSTRUCTION DOCUMENTS FOR

ABBREVIATIONS NOT DEFINED ABOVE OR IN PLUMBING MATERIAL LIST/PLUMBING

SCHEDULES.

1. INSTALLATION SHALL COMPLY WITH ALL APPLICABLE CODES, STANDARDS, AND

MANUFACTURER'S INSTALLATION REQUIREMENTS.

2. REVIEW ALL PROJECT DOCUMENTS INCLUDING SPECS AND DRAWINGS PERTAINING TO ALL

DISCIPLINES PRIOR TO SUBMITTING A BID. SUBMIT PRE-BID REQUEST FOR INFORMATION FOR

ITEMS IN QUESTION AND/OR CONFLICTS FOUND.

3. DRAWINGS SHOW THE DESIGN INTENT DIAGRAMMATICALLY. THEY DO NOT SHOW THE EXACT

UTILITY ROUTING NOR EVERY ELBOW, OFFSET, ETC. WHERE REQUIRED, THE CONTRACTOR

SHALL MAKE ADJUSTMENTS TO THEIR SYSTEMS TO AVOID CONFLICT WITH THE STRUCTURE

AND OTHER DISCIPLINES. THE COST FOR SUCH ADJUSTMENTS SHALL BE INCLUDED IN THE BID.

4. OBTAIN AND PAY FOR ALL PERMITS REQUIRED FOR WORK PERFORMED.

5. THE G.C. OR C.M. TEAM SHALL LEAD THE SUBCONTRACTORS IN PROVIDING A COORDINATED

SET OF SHOP DRAWINGS. SEE GENERAL REQUIREMENTS SPEC FOR ADDITIONAL

INFORMATION.

6. PROVIDE FIRESTOPPING FOR ALL UTILITY PENETRATIONS THRU FIRE-RATED ASSEMBLIES.

7. COORDINATE FRAMING REQUIREMENTS FOR ACCESS PANELS AND EQUIPMENT/PANEL

SUPPORTS WITH G.C. OR C.M. PRIOR TO SUBMITTING BID.

8. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE CORRECTION OF CONSTRUCTION

DEFICIENCIES LISTED ON THE JOB SITE OBSERVATION REPORT. RETURN THE JOB SITE

OBSERVATION REPORT TO A/E WITH DEFICIENCIES SIGNED OFF. PROVIDE PHOTOGRAPHIC

AND/OR VIDEO EVIDENCE OF CORRECTED DEFICIENCIES IF REQUESTED BY THE ENGINEER.

9. PROVIDE CLOSEOUT DOCUMENTATION UPON COMPLETION OF PROJECT. SEE GENERAL

REQUIREMENTS SPEC FOR ADDITIONAL INFORMATION.

GENERAL NOTES:

1. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID SUBMISSION TO VERIFY ALL FIELD

CONDITIONS INCLUDING BUT NOT LIMITED TO THE FOLLOWING:

A. LOCATIONS OF EXISTING PLUMBING SYSTEMS.

B. LOCATIONS OF ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL,

TECHNOLOGY, FIRE PROTECTION, AND FIRE ALARM SYSTEMS.

C. EXISTING SURFACES WHICH REQUIRE ALTERING.

D. INVERTS OF EXISTING DRAINAGE PIPING VIA CLEANOUT DEPTHS.

2. SCAN/X-RAY POST TENSION SLABS PRIOR TO ALTERATION. SHOP DRAWINGS SHALL REFLECT

REBAR AND TENSION CABLE LOCATIONS. OPENINGS SHALL BE COORDINATED WITH THE

STRUCTURAL ENGINEER PRIOR TO PERFORMING ANY WORK.

3. NOTIFY OWNER OF REQUIRED SYSTEM SHUTDOWNS AT LEAST TWO WEEKS PRIOR TO

SHUTDOWN. EXACT SHUTDOWN TIME AND PROCEDURE SHALL BE COORDINATED WITH

OWNER AT LEAST 96 HOURS PRIOR TO SHUTDOWN.

4. WHEN PIPING, EQUIPMENT, OR FIXTURES ARE NOTATED TO BE PERMANENTLY REMOVED

THEIR ASSOCIATED COMPONENTS SHALL ALSO BE REMOVED INCLUDING HANGERS,

SUPPORTS, AND ACCESSORIES.

5. COORDINATE THE DISCONNECTION AND REMOVAL OF POWERED SYSTEMS WITH THE E.C.

WHEN REMOVING POWERED PLUMBING EQUIPMENT.

6. REPAIR EXISTING FLOORS, WALLS, AND CEILINGS IN ALTERED AREAS TO MATCH EXISTING.

SEE ARCHITECTURAL PLANS FOR FINISH DETAILS IN REMODEL AREAS.

RENOVATION NOTES:

ISOLATION VALVE, NORMALLY OPEN

UNION

PIPE DOWN

PIPE UP

BRANCH-TOP CONNECTION

BRANCH-BOTTOM CONNECTION

PIPE CAP

CLEANOUT PLUGCO

CO

FLOOR CLEANOUTFCO

WALL CLEANOUT

WCO

FLOOR DRAIN

FLOOR SINK

1/8"/1'-0" PITCH DOWN - IN DIRECTION OF ARROW

PLUMBING SYMBOLS:

LINETYPE/SYMBOL DESCRIPTION

NOTES:

1. NOT ALL SYMBOLS MAY APPLY.

2. SEE SPECS AND DRAWINGS FOR SPECIFIC COMPONENT REQUIREMENTS.

PIPE REDUCER

DIRECTION OF WATER/GAS FLOW

ACCESS PANEL OR ROOF HATCH

ISOLATION VALVE IN VERTICAL PIPE, NO

FD FD

2021 INTERNATIONAL BUILDING CODE (IBC)

2024 NFPA 101 LIFE SAFETY CODE

2022 NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900

2023 NATIONAL ELECTRICAL CODE (NEC) (NFPA 70)

2021 INTERNATIONAL MECHANICAL CODE (IMC)

2021 INTERNATIONAL PLUMBING CODE (IPC)

2015 ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)

ENERGY POLICY ACT OF 2005 (EPACT)

DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL,

COMMERCIAL AND MULTI-FAMILY HIGH-RISERESIDENTIAL BUILDINGS AND NEW LOW-RISE

RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435.

VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1- 2022.

SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15 – 2022.

UNLESS OTHERWISE SPECIFIED, SPECIFIC REFERENCES TO CODES, REGULATIONS, STANDARDS, MANUFACTURERS' INSTRUCTIONS, OR REQUIREMENTS OF REGULATORY AGENCIES, SHALL MEAN

THE LATEST EDITION OF EACH IN EFFECT AT THE DATE OF PROJECT SUBMISSION (U.N.O.)

EDITION REFERENCE CODE/STANDARD

CODES AND STANDARDS:

POINT OF CONNECTION OR DISCONNECTION

KEYNOTE SYMBOL#

DETAIL CALL-OUT SYMBOL

###-# EQUIPMENT TAG

GENERAL LEGEND:

SYMBOL DESCRIPTION

SECTION CUT CALL-OUT SYMBOL

ENLARGED PLAN CALL-OUT SYMBOL

EXISTING TO REMAIN

EXISTING TO BE REMOVED

NEW CONSTRUCTION

(E) EXISTING TO REMAIN

LINETYPE DESCRIPTION

(X) EXISTING TO BE REMOVED

1. PLUMBING WORK SHALL BE CONSTRUCTED IN A PROFESSIONAL MANNER. ENSURE

FIXTURES, EQUIPMENT, AND ASSOCIATED COMPONENTS ARE INSTALLED LEVEL AND PLUMB.

SEALANT BETWEEN FIXTURES AND SURFACES SHALL BE EVEN AND NEAT. COMPONENTS

SHALL BE CLEANED PRIOR TO OWNER TURNOVER.

2. IF A CONTRACTOR PROVIDES EQUIPMENT OTHER THAN THE BASIS OF DESIGN, THAT

CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COSTS INCURRED AS A RESULT. THAT

INCLUDES, BUT IS NOT LIMITED TO, STRUCTURAL MODIFICATIONS FOR INCREASED WEIGHT,

AND ELECTRICAL EQUIPMENT, WIRING CONDUIT, AND BREAKER CHANGES FOR DIFFERENT

ELECTRICAL REQUIREMENTS.

3. COORDINATE POWER REQUIREMENTS WITH THE E.C. PRIOR TO PROVIDING SUBMITTALS TO

THE ENGINEER.

4. SEE SPEC SECTIONS 22 11 00 AND 22 13 00, FOR PIPE SYSTEM INSTALLATION, TESTING, CLEANING, AND DISINFECTION REQUIREMENTS.

5. PROVIDE IDENTIFICATION FOR PIPING, VALVES, AND EQUIPMENT PER SPEC SECTION

22 05 23.

6. PIPING SHALL NOT PASS THRU NOR UNDER ELECTRICAL ROOMS, DATA ROOMS, ELEVATOR

MACHINE ROOMS, ELEVATOR HOISTWAYS, SKYLIGHTS, AND ROOF ACCESS HATCHES.

7. INSULATION SHALL BE PROVIDED CONTINUOUS THROUGHOUT THE PIPING SYSTEM

INCLUDING AT HANGERS/SUPPORTS, PIPE FITTINGS, VALVES, AND ACCESSORIES. OPENINGS

SHALL BE PROVIDED TO ALLOW FOR VALVE HANDLE OPERATION AND ACCESS. INSULATION

THICKNESS SHALL MEET THE LISTED ENERGY CODE MINIMUM REQUIREMENTS. SEE SPEC

SECTION 22 07 11 FOR SYSTEMS REQUIRING INSULATION AND ADDITIONAL INSTALLATION

REQUIREMENTS.

8. VALVES SHALL BE ACCESSIBLE. PROVIDE KEYED ACCESS PANELS WHERE VALVES HAVE BEEN

LOCATED IN CONCEALED AREAS. ACCESS PANEL SIZE SHALL BE LARGE ENOUGH TO ACCESS

EACH VALVE AND FOR FULL VALVE OPERATION.

9. CLEANOUTS SHALL BE PROVIDED PER PLUMBING CODE REQUIREMENTS. IN ADDITION,

PROVIDE CLEANOUTS AT LAVATORIES, SINKS, AND URINALS. CLEANOUTS SHALL BE

INSTALLED IN ACCESSIBLE LOCATIONS.

10. INSTALL - TO PLACE IN POSITION AND CONNECT COMPLETE READY FOR USE.

FURNISH - TO PURCHASE/SUPPLY.

PROVIDE - TO FURNISH AND INSTALL.

PLUMBING NOTES:

CONTRACTOR ABBREVIATIONS:

ABBREVIATION DESCRIPTION

C.M. CONSTRUCTION MANAGER

E.C. ELECTRICAL CONTRACTOR

F.A.C. FIRE ALARM CONTRACTOR

F.P.C. FIRE PROTECTION CONTRACTOR

G.C. GENERAL CONTRACTOR

M.C. MECHANICAL CONTRACTOR

P.C. PLUMBING CONTRACTOR

T.C. TECHNOLOGY CONTRACTOR

T.C.C. TEMPERATURE CONTROL CONTRACTOR

INDIRECT DRAIND

POTABLE COLD WATER

SOFTENED WATERSW

PUMP DISCHARGE LINEPD

PLUMBING SYSTEMS:

LINETYPE/SYMBOL DESCRIPTION

NOTES:

1. NOT ALL SYMBOLS MAY APPLY.

2. SEE SPECS AND DRAWINGS FOR SPECIFIC COMPONENT REQUIREMENTS.

CD CONDENSATE DRAIN

DEIONIZED WATERDI

1. THE PROJECT WILL BE CONSTRUCTED IN MULTIPLE PHASES. SEE ARCHITECTURAL &

PHASING DOCUMENTS FOR PHASING REQUIREMENTS.

2. CONTRACTOR SHALL CONFIRM WORK BEING PERFORMED IN ACTIVE PHASE DOES NOT

ADVERSELY AFFECT NORMAL OPERATIONS IN OTHER OCCUPIED SPACES.

3. PROVIDE TEMPORARY CONNECTIONS AS REQUIRED TO MAINTAIN SERVICE TO OCCUPIED

SPACES.

4. DESIGN DRAWINGS DO NOT INDICATE EVERY REQUIRED STEP TO ACHIEVE PHASED

CONSTRUCTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DEVELOP A CONSTRUCTION

PLAN TO INSTALL THE DESIGN WITHIN THE PHASING CONSTRAINTS.

5. CONSTRUCTION ACTIVITIES IN OCCUPIED SPACES SHALL BE PERFORMED DURING

UNOCCUPIED HOURS (NIGHTS, WEEKENDS, AND/OR HOLIDAYS). RESTORE SPACES TO

ORIGINAL CONDITIONS BEFORE HOSPITAL STAFF AND/OR PATIENTS ARRIVE.

6. CONSTRUCTION ACTIVITIES IN UNOCCUPIED SPACES THAT HAVE ADVERSE EFFECTS

(EXCESSIVE NOISE, EXCESSIVE VIBRATION, ETC.) SHALL BE PERFORMED DURING

UNOCCUPIED HOURS (NIGHTS, WEEKENDS, AND/OR HOLIDAYS).

7. COORDINATE SCHEDULE WITH THE VA TO DETERMINE EXACT ALLOWABLE TIMES OF

CONSTRUCTION ACTIVITIES IN EACH PROJECT AREA.

PHASING NOTES:

MAKEUP WATERMU

LINE TYPE /SYMBOL DESCRIPTION

1-HOUR FIRE BARRIER

2-HOUR FIRE BARRIER

1-HOUR SMOKE BARRIER

1-HOUR HAZARDOUS AREA FIRE BARRIER

FIRE-RATED ASSEMBLY LEGEND:

S S S S

HZ HZ HZ HZ

RE

G

IS

TE

RE

DPROFESSIONALENG

IN

EERER

IC

M.DeSPLINTER

M

ECHANICA

L

S

TATE OF CALIFORNIA

38688 Exp. 12-31-25

SIGNED: 06/23/25

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CORRECT REUSABLE

MEDICAL EQUIP STORAGE

589A4-24-101

800 HOSPITAL DR, COLUMBIA, MO

Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015

Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383

Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086

(412) 212-7515

STAMP

07/25/2025

100% FINAL BID

DOCUMENTS

A u to d e s k D o c s /1

A

-2

-1

C o rr e c t R e u s a b le

M e d ic a l E q u ip m e n t S to ra g e /2

M

E P

T

.0

C o lu m b ia

M

O V

A M

C R

M E

S to ra g e

A C

A H

V A

C U p g ra d e s .r v t

-0 -2

:4

:4

P

M

P001

RSS PSK

PLUMBING COVER SHEET

Sheet

Number Sheet Name

P001 PLUMBING COVER SHEET

P100 PLUMBING - BASEMENT FLOOR PLAN

P101 PLUMBING - FIRST FLOOR PLAN

P102 PLUMBING - THIRD FLOOR PLAN

P103 PLUMBING - SIXTH FLOOR PLAN

PD201 PLUMBING - ENLARGED BASEMENT FLOOR PLAN ROOMS - DEMOLITION

PD202 PLUMBING - ENALARGED BASEMENT FLOOR PLAN ROOMS - DEMOLITION

PD203 PLUMBING - ENLARGED FIRST FLOOR PLAN - PATHOLOGY - DEMOLITION

P201 PLUMBING - ENLARGED BASEMENT FLOOR PLAN ROOMS - REMODEL

P202 PLUMBING - ENLARGED BASEMENT FLOOR PLAN ROOMS - REMODEL

P203 PLUMBING - ENLARGED THIRD FLOOR PLAN ROOMS - REMODEL

P204 PLUMBING - PENTHOUSE FLOOR PLAN

P401 PLUMBING - DETAILS

PLUMBING MATERIAL LIST

SYMBOL DESCRIPTION MANUFACTURER AND MODEL

RPBP-1 REDUCED PRESSURE BACKFLOW PREVENTER:

3/4" SIZE, LOW LEAD BRONZE MAIN BODY AND ACCESS COVERS (ASTM B 584), INTERNAL

POLYMER SEAT RING AND SILICONE SEAT DISC ELASTOMERS. COMPLETE WITH AIR GAP ADAPTER

AND INDIRECT DRAIN TO THE LOCAL FLOOR SINK. THE ASSEMBLY SHALL BE CONFIGURABLE TO

INCLUDE A SENSOR TO MONITOR EXCESSIVE WATER DISCHARGE FROM THE RELIEF VALVE FOR

FLOOD DETECTION. THE ASSEMBLY SHALL MEET THE REQUIREMENTS OF: USC; ASSE STD. 1013;

AWWA STD. C511; CSA B64.4. SHALL BE A ZURN WILKINS.

SEE SPECIFICATION SECTION 22 05 23 FOR PRODUCT REQUIREMENTS.

ZURN 975XL2 OR EQUAL.

RPBP-2 REDUCED PRESSURE BACKFLOW PREVENTER:

2" SIZE, LOW LEAD BRONZE MAIN BODY AND ACCESS COVERS (ASTM B 584), INTERNAL

POLYMER SEAT RING AND SILICONE SEAT DISC ELASTOMERS. COMPLETE WITH AIR GAP ADAPTER

AND INDIRECT DRAIN TO THE LOCAL FLOOR SINK. THE ASSEMBLY SHALL BE CONFIGURABLE TO

INCLUDE A SENSOR TO MONITOR EXCESSIVE WATER DISCHARGE FROM THE RELIEF VALVE FOR

FLOOD DETECTION. THE ASSEMBLY SHALL MEET THE REQUIREMENTS OF: USC; ASSE STD. 1013;

AWWA STD. C511; CSA B64.4. SHALL BE A ZURN WILKINS.

SEE SPECIFICATION SECTION 22 05 23 FOR PRODUCT REQUIREMENTS.

ZURN 975XL2 OR EQUAL.

FD-S-Z-HP-Y-2 FLOOR SINK:

SEE SPECIFICATION SECTION 22 13 00 FOR PRODUCT REQUIREMENTS.

ZURN G1750 OR EQUAL.

WS-1 WATER SOFTENER:

FLOOR-MOUNTED AUTOMATIC WATER SOFTENER SYSTEM. FRP RESIN TANK WITH HDPE BRINE

TANK CONSTRUCTION. 200 LBS/HR CAPACITY, 7 GPM CONTINUOUS FLOW RATE, 280 LBS SALT

STORAGE, 0.5 LBS/CU. FT. RESIN CAPACITY, 1 CU. FT. RESIN VOLUME, 94 HOURS BETWEEN

REGENERATION, 30-100 OPERATING PRESSURE RANGE, 1.2 GPM BACKWASH RATE.

SEE SPECIFICATION SECTION 22 31 11 FOR PRODUCT REQUIREMENTS.

ELECTRICAL REQUIREMENTS:

120V-1PH-60HZ, 5A

DIMENSIONS:

SOFTENER TANK 44"H X 7"ø

BRINE TANK 33"H X 18"ø

500 LBS TOTAL OPERATING WEIGHT.

MARLO MGT-15-3/4, OR EQUAL

PRV-1 PRESSURE REDUCING VALVE:

2" SIZE LOW LEAD CAST BRONZE ASTB 584 MAIN VALVE BODY, STAINLESS STEEL FASTENERS, ASSE LISTED 1003, IAPMO LISTED, CSA CERTIFIED, MEETS THE REQUIREMENTS OF NSF/ANSI 61. 25

PSI TO 75 PSI REDUCED PRESSURE RANGE. 50 PSI FACTORY PRESET. SET AT 30PSI.

SEE SPECIFICATION SECTION 22 05 23 FOR PRODUCT REQUIREMENTS.

ZURN 500XLHTSTSC, OR EQUAL

WET VENT SIZING:

BASED ON IPC, TABLE 912.3.

DRAINGE FIXTURE

UNIT LOAD

WET VENT PIPE SIZE

11-1/2"

42"

62-1/2"

123"

SANITARY DRAINAGE / VENT PIPE SIZING:

TABLE BASED ON IPC, CHAPTER 7, TABLE 710.1(1).

3 FT/SEC VELOCITY.

PIPE SIZE 4"3"2"1 1/2"

TOTAL FOR HORIZONTAL BRANCH 1602063

Mark Revisions: Date:

1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES 07/29/2025

DN

DN

WORK

ROOM

F002

MECH

ROOM

E003

ELEC ROOM

E003A

COLD ROOM

B037A

(E)ACA-AHU-6

ACA-AHU-3 BY

MECHANICAL

ACA-AHU-2 BY

MECHANICAL

ACA-AHU-1 BY

MECHANICAL

ACA-AHU-4 BY

MECHANICAL

ACA-USG-1 BY

MECHANICAL

(E)USG

(E)FD

(E)FD (E)FD

(E)FD

(E)FD

(E)FD

(E)FD

(E)HB

(E)FD

(E)FD

(E)3/4"

(E )3

/4

(E)2 1/2" CW UP

(E)3/4"

(E)2 1/2"

(E )4

(E

)3

(E)4"

(E)4" CW DN

(E)FD

(E)FD

(E)FD

3/4" SW

(E)HB

(E)SW

ACA-AS-1 BY

MECHANICAL

3/4" D

RPBP-2

2" MU

PRV-1

WS-1

2 3 1 4 5 5.6

B

C

D.1

D

A

1" D

(E)CW

P401

(TYP)

1" CD

3/4" D

3/4" D

1" CD

3/4" D

3/4" D

1" CD

3/4" D

3/4" D

3/4" D

3/4" D

1" CD

N

3/16" = 1'-0"1

PLUMBING - ENLARGED BASEMENT FLOOR PLAN - MECH. RM E003 - REMODEL

RE

G

IS

TE

RE

DPROFESSIONALENG

IN

EERER

IC

M.DeSPLINTER

M

ECHANICA

L

S

TATE OF CALIFORNIA

38688 Exp. 12-31-25

SIGNED: 06/23/25

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CORRECT REUSABLE

MEDICAL EQUIP STORAGE

589A4-24-101

800 HOSPITAL DR, COLUMBIA, MO

Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015

Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383

Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086

(412) 212-7515

STAMP

07/25/2025

BASEMENT KEYPLAN

NORTH

E & F

SHIPPING

WAREHOUSE

OR ADDITION B A

ACA BUILDING

AREAS

AREA AREA

G

AREA

C & D

AREAS

BUILDING 1

100% FINAL BID

DOCUMENTS

A u to d e s k D o c s /1

A

-2

-1

C o rr e c t R e u s a b le

M e d ic a l E q u ip m e n t S to ra g e /2

M

E P

T

.0

C o lu m b ia

M

O V

A M

C R

M E

S to ra g e

A C

A H

V A

C U p g ra d e s .r v t

-0 -2

:4

:0

P

M

P201

RSS PSK

PLUMBING - ENLARGED BASEMENT FLOOR

PLAN ROOMS - REMODEL

KEYNOTES - P201

NUMBER TEXT

EXTEND NEW WALL-MOUNTED 3/4" SW FROM EXISTING SYSTEM TO ACA-USG-1

COMPLETE WITH LINE SIZE ISOLATION VALVE.

RECONNECT CW AND SW PIPING FROM ISOLATION VALVES TO THE NEW WATER

SOFTENER EQUIPMENT.

PROTECT IN PLACE EXISTING DRAIN MOUNTED TO WALL FROM THE BACKFLOW

PREVENTER TO THE FLOOR SINK.

4 PROTECT IN PLACE EXISTING WALL MOUNTED BACKFLOW PREVENTER ASSEMBLY.

PROVIDE CONDENSATE DRAIN FROM EQUIPMENT TO FLOOR SINK. SPILL 1"

ABOVE FLOOD LEVEL RIM MINIMUM. SEE DETAIL 1/P401 FOR ADDITIONAL

INFORMATION.

PROVIDE INDIRECT DRAIN FROM BACK FLOW PREVENTER TO FLOOR SINK. SPILL

1" ABOVE FLOOD LEVEL RIM MINIMUM.

PROTECT IN PLACE EXISTING WALL-MOUNTED SW PIPING ABOVE AND CW PIPING

BELOW.

PROVIDE NEW BACKFLOW PREVENTER ASSEMBLY AND PIPING ABOVE HEAD AS

SHOWN TO THE EQUIPMENT ACA-AS-1.

DEDUCT 1: DO NOT PROVIDE CONDENSATE PIPING FROM ACA-AHU-4

EQUIPMENT.

DEDUCT 2: DO NOT PROVIDE CONDENSATE PIPING FROM ACA-AHU-3, AND

ACA-AHU-4 EQUIPMENT.

WHERE PIPING IS CALLED OUT TO BE INSTALLED ABOVE HEAD, PIPING SHALL BE

PLACED AS CLOSE TO THE STRUCTURE AS POSSIBLE, BUT NO LESS THAN 8' ABOVE

FINISHED FLOOR.

NUMBER TEXT

GENERAL NOTES - P201

Mark Revisions: Date:

1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES 07/29/2025

CLEAN

RECEIVING

BREAKOUT

G048

BULK

STORE

ROOM

G047

ETO

STERILIZER

ACCESS

G045

STERILIZER

ACCESS

G043A

MECH

ROOM

G001

USG-2 BY

MECHANICAL

(E)AHU-8

(E)USG-1

(E)HX-4

(E)HX-3

(E)HX-2

(E)HX-1

(E)CP-1

(E)AHU-9

(E)AHU-7A

(E)AHU-7B

(E)WATER

SOFTENING

SYSTEM

3/4" SW

1" D

(E)FD

(E)FD(E)FD

8.2

9.1

Z V

8.3

8.9

9.8

BB AA Y X W

(E)AC-S13

(E)AHU-14

WORK SHOWN EAST OF THIS

LINE IS IN PIPE BASEMENT.

(E)FD

D 1" D

USG-3 BY

MECHANICAL

WS-1

3/4" SW ABOVE HEAD

3/4" CW ABOVE HEAD

(E )4

C

W (E

)4

C W

3/4" D

(E)FD

RPBP-1

T S R Q P Na N

8.2

9.1

10.4

11.5

8.3

8.9

9.8

10.2

H-3 BY

MECHANICAL

H-2 BY

MECHANICAL

D

1" D

MP401

MP401

1" D

RE

G

IS

TE

RE

DPROFESSIONALENG

IN

EERER

IC

M.DeSPLINTER

M

ECHANICA

L

S

TATE OF CALIFORNIA

38688 Exp. 12-31-25

SIGNED: 06/23/25

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CORRECT REUSABLE

MEDICAL EQUIP STORAGE

589A4-24-101

800 HOSPITAL DR, COLUMBIA, MO

Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015

Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383

Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086

(412) 212-7515

STAMP

07/25/2025

BASEMENT KEYPLAN

NORTH

E & F

SHIPPING

WAREHOUSE

OR ADDITION B A

ACA BUILDING

AREAS

AREA AREA

G

AREA

C & D

AREAS

BUILDING 1

100% FINAL BID

DOCUMENTS

A u to d e s k D o c s /1

A

-2

-1

C o rr e c t R e u s a b le

M e d ic a l E q u ip m e n t S to ra g e /2

M

E P

T

.0

C o lu m b ia

M

O V

A M

C R

M E

S to ra g e

A C

A H

V A

C U p g ra d e s .r v t

-0 -2

:4

:0

P

M

P202

RSS PSK

PLUMBING - ENLARGED BASEMENT FLOOR

PLAN ROOMS - REMODEL

N

3/16" = 1'-0"2

PLUMBING - ENLARGED BASEMENT FLOOR PLAN - RM G001 - REMODEL

N

1/8" = 1'-0"1

PLUMBING - ENLARGED PIPE BASEMENT FLOOR PLAN - RM C012 - REMODEL

KEYNOTES - P202

NUMBER TEXT

PROVIDE SOFTENED WATER TO USG-3 ABOVE HEAD FROM WATER SOFTENER AS

SHOWN.

PROVIDE SOFTENED WATER TO USG-2 ABOVE HEAD FROM EXISTING WATER

SOFTENER AS SHOWN.

PROVIDE CONDENSATE DRAIN FROM FIXTURE TO FLOOR SINK. SPILL 1" ABOVE

FLOOD LEVEL RIM MINIMUM.

PROVIDE INDIRECT DRAIN FROM BACKFLOW PREVENTER TO FLOOR SINK. SPILL 1"

ABOVE FLOOD LEVEL RIM MINIMUM.

PROVIDE A NEW FLOOR-MOUNTED WATER SOFTENER. EXTEND 3/4" COLD

WATER TO THE NEW EQUIPMENT FROM THE EXISTING MAIN ABOVE HEAD

COMPLETE WITH NEW BACKFLOW PREVENTER ASSEMBLY.

PROVIDE CONDENSATE DRAIN FROM H-3 ABOVE HEAD TO THE FLOOR SINK AS

SHOWN. SPILL 1" ABOVE FLOOD LEVEL RIM MINIMUM.

7 PROVIDE 1" DRAIN AT FLOOR LEVEL TO (E)FD. SPILL 1" ABOVE FLOOD LEVEL RIM.

WHERE PIPING IS CALLED OUT TO BE INSTALLED ABOVE HEAD, PIPING SHALL BE

PLACED AS CLOSE TO THE STRUCTURE AS POSSIBLE, BUT NO LESS THAN 8' ABOVE

FINISHED FLOOR.

NUMBER TEXT

GENERAL NOTES - P202

Mark Revisions: Date:

CLEAN

UTILITY

ROOM

E320

OPERATORY

DENTAL

CHIEF

OFFICE

E319

HSKING

F308

STAFF

TOILET

F309

H-1 BY

MECHANICAL

P401

ABOVE HEAD

/4

D

(E)TU-AHU7-002

FIRE SEAL, SEE

3/4" D

MP401

RE

G

IS

TE

RE

DPROFESSIONALENG

IN

EERER

IC

M.DeSPLINTER

M

ECHANICA

L

S

TATE OF CALIFORNIA

38688 Exp. 12-31-25

SIGNED: 06/23/25

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CORRECT REUSABLE

MEDICAL EQUIP STORAGE

589A4-24-101

800 HOSPITAL DR, COLUMBIA, MO

Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015

Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383

Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086

(412) 212-7515

STAMP

07/25/2025

THIRD FLOOR KEYPLAN

NORTH

E & F

SHIPPING

WAREHOUSE

OR ADDITION B A

ACA BUILDING

AREAS

AREA AREA

G

AREA

C & D

AREAS

BUILDING 1

100% FINAL BID

DOCUMENTS

A u to d e s k D o c s /1

A

-2

-1

C o rr e c t R e u s a b le

M e d ic a l E q u ip m e n t S to ra g e /2

M

E P

T

.0

C o lu m b ia

M

O V

A M

C R

M E

S to ra g e

A C

A H

V A

C U p g ra d e s .r v t

-0 -2

:4

:0

P

M

P203

RSS PSK

PLUMBING - ENLARGED THIRD FLOOR PLAN

ROOMS - REMODEL

KEYNOTES - P203

NUMBER TEXT

1 3/4"D DOWN IN WALL TO MOP SINK. SPILL 1" ABOVE FLOOD LEVEL RIM.

N

1/4" = 1'-0"1

PLUMBING - ENLARGED THIRD FLOOR PLAN - RM E320 - REMODEL

WHERE PIPING IS CALLED OUT TO BE INSTALLED ABOVE HEAD, PIPING SHALL BE

PLACED AS CLOSE TO THE STRUCTURE AS POSSIBLE, BUT NO LESS THAN 8' ABOVE

FINISHED FLOOR.

NUMBER TEXT

GENERAL NOTES - P203

Mark Revisions: Date:

DRAW THRU

BLOW THRU

2" [50mm]

PLUS X

1" [25mm]

MINIMUM

X

2X

UNIT TYPE A B

WHERE X = STATIC PRESSURE IN PAN

DRAIN LINE SHALL BE AT LEAST THE SAME SIZE

AS THE NIPPLE ON THE DRAIN PAN

PIPING SHALL BE RIGID COPPER TYPE L OR

TYPE M UNLESS NOTE BELOW IS MET

PITCH DOWN

TOWARD DRAIN

CLEAN OUT

FLOOR SINK

DRAIN

PAN

NOTE: 1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND

IS INDOORS AND DOES NOT PASS THROUGH RATED BARRIERS.

2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE

TO BE CONNECTED.

[2 m m

DIELECTRIC

FITTING

A B

NUT (TOP & BOTTOM)

ALL THREADED ROD

WASHER (TOP & BOTTOM)

PROVIDE PLASTIC COATED

HANGER WHEN HANGING

DISSIMILAR METAL PIPING.

ALL THREADED ROD

PROVIDE PLASTIC COATED

HANGER WHEN HANGING

DISSIMILAR METAL PIPING.

KNURLED HANGER

ROD NUT

DETAIL NOTES:

1. PROVIDE MINIMUM 1/2" SPACING BETWEEN FINISHED COVERING AND

ADJACENT WORK.

UNINSULATED PIPE

UNINSULATED/INSULATED

PIPE

SWIVEL RING HANGER CLEVIS HANGER

CONDENSATE DRAIN CONNECTION NTS 1

SUSPENDED PIPE SUPPORT NTS 2

FIRE SEAL OF 2 HR RATED FLOOR - FLOOR SINK NTS 4FIRE SEAL OF 1 HR RATED WALL - INSULATED PIPE NTS 5 HUMIDIFIER CONDENSATE PIPE CONNECTION TO DRAIN NTS 3

3/4"CONDENSATE PIPING

FROM HUMIDIFIER

1" DRAIN PIPING FROM

COOLING COIL(PLUMBING)

OPEN VENT

1"DRAIN TO

PLUMBING RECEPTOR

2% SLOPE

2% SLOPE

RE

G

IS

TE

RE

DPROFESSIONALENG

IN

EERER

IC

M.DeSPLINTER

M

ECHANICA

L

S

TATE OF CALIFORNIA

38688 Exp. 12-31-25

SIGNED: 06/23/25

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CORRECT REUSABLE

MEDICAL EQUIP STORAGE

589A4-24-101

800 HOSPITAL DR, COLUMBIA, MO

Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015

Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383

Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086

(412) 212-7515

STAMP

07/25/2025

100% FINAL BID

DOCUMENTS

A u to d e s k D o c s /1

A

-2

-1

C o rr e c t R e u s a b le

M e d ic a l E q u ip m e n t S to ra g e /2

M

E P

T

.0

C o lu m b ia

M

O V

A M

C R

M E

S to ra g e

A C

A H

V A

C U p g ra d e s .r v t

-0 -2

:4

:1

P

M

P401

RSS PSK

PLUMBING - DETAILS

Mark Revisions: Date:

P001 - PLUMBING COVER SHEET
P201 - PLUMBING -ENLARGED BASEMENT FLOOR PLAN ROOMS -REMODEL
P202 - PLUMBING -ENLARGED BASEMENT FLOOR PLAN ROOMS -REMODEL
P203 - PLUMBING -ENLARGED THIRD FLOOR PLAN ROOMS -REMODEL
P401 - PLUMBING -DETAILS