This document is a set of mechanical piping design and flow diagrams for the Columbia, MO VA Medical Center's Reusable Medical Equipment Storage and ACA HVAC Upgrades project. The drawings detail complex mechanical piping systems, including demolition and remodel plans for heating water, chilled water, and steam piping across multiple building floors and mechanical rooms. Key technical specifications include:
The documents outline comprehensive mechanical system modifications involving heat exchangers, pumps, steam generators, and air handling units. The project involves replacing existing piping infrastructure, installing new equipment like ACA-HX-1 and ACA-HX-2 heat exchangers, ACA-HWP-1 and ACA-HWP-2 heating water pumps, and ACA-USG-1 steam generators. The design includes redundant systems, future extension provisions, and compliance with multiple building codes including 2021 International Building Code, 2024 NFPA Life Safety Code, and ASHRAE standards. The diagrams show detailed piping routes, equipment locations, and system flow configurations across basement, first, second, third, and penthouse floors of the facility.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL SHEET INDEX:
1. INSTALLATION SHALL COMPLY WITH ALL APPLICABLE CODES, STANDARDS, AND
MANUFACTURER'S INSTALLATION REQUIREMENTS.
2. REVIEW ALL PROJECT DOCUMENTS INCLUDING SPECS AND DRAWINGS PERTAINING TO ALL
DISCIPLINES PRIOR TO SUBMITTING A BID. SUBMIT PRE-BID REQUEST FOR INFORMATION FOR
ITEMS IN QUESTION AND/OR CONFLICTS FOUND.
3. DRAWINGS SHOW THE DESIGN INTENT DIAGRAMMATICALLY. THEY DO NOT SHOW THE EXACT
UTILITY ROUTING NOR EVERY ELBOW, OFFSET, ETC. WHERE REQUIRED, THE CONTRACTOR
SHALL MAKE ADJUSTMENTS TO THEIR SYSTEMS TO AVOID CONFLICT WITH THE STRUCTURE
AND OTHER DISCIPLINES. THE COST FOR SUCH ADJUSTMENTS SHALL BE INCLUDED IN THE BID.
4. OBTAIN AND PAY FOR ALL PERMITS REQUIRED FOR WORK PERFORMED.
5. OBTAIN UTILITY PURVEYOR REQUIREMENTS PRIOR TO PURCHASING EQUIPMENT OR
PERFORMING WORK.
6. THE G.C. OR C.M. TEAM SHALL LEAD THE SUBCONTRACTORS IN PROVIDING A COORDINATED
SET OF SHOP DRAWINGS. SEE GENERAL REQUIREMENTS SPEC FOR ADDITIONAL
INFORMATION.
7. PROVIDE FIRESTOPPING FOR ALL UTILITY PENETRATIONS THRU FIRE-RATED ASSEMBLIES.
8. COORDINATE FRAMING REQUIREMENTS FOR ACCESS PANELS AND EQUIPMENT/PANEL
SUPPORTS WITH G.C. OR C.M. PRIOR TO SUBMITTING BID.
9. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE CORRECTION OF CONSTRUCTION
DEFICIENCIES LISTED ON THE JOB SITE OBSERVATION REPORT. RETURN THE JOB SITE
OBSERVATION REPORT TO A/E WITH DEFICIENCIES SIGNED OFF. PROVIDE PHOTOGRAPHIC
AND/OR VIDEO EVIDENCE OF CORRECTED DEFICIENCIES IF REQUESTED BY THE ENGINEER.
10. PROVIDE CLOSEOUT DOCUMENTATION UPON COMPLETION OF PROJECT. SEE GENERAL
REQUIREMENTS SPEC FOR ADDITIONAL INFORMATION.
11. COORDINATE AND SCHEDULE WORK TO MINIMIZE DISRUPTION, ENSURING ACCEPTABLE
DOWNTIMES ARE AGREED UPON WITH THE OWNER PRIOR TO COMMENCING WORK.
RESTORE ALL SPACES TO FULLY FUNCTIONAL CONDITIONS UPON COMPLETION OF WORK.
PROVIDE TEMPORARY FACILITIES AND CONTROLS AS REQUIRED TO MAINTAIN SAFE AND
OPERATIONAL CONDITIONS DURING CONSTRUCTION.
GENERAL NOTES:MECHANICAL ABBREVIATIONS:
ABBREVIATION DESCRIPTION
EA EXHAUST AIR OR RELIEF AIR
MA MAKEUP AIR
OA OUTSIDE AIR
RA RETURN AIR
SA SUPPLY AIR
TA TRANSFER AIR
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AFMS AIRFLOW MEASURING STATION
AHU AIR-HANDLING UNIT
AMB AMBIENT TEMPERATURE
BD BACKDRAFT DAMPER
DB DRY-BULB TEMPERATURE
DCV DEMAND CONTROL VENTILATION
DIA, Ø DIAMETER
DN DOWN
DPT DEW-POINT TEMPERATURE
DTR DOWN THRU ROOF
EAT ENTERING AIR TEMPERATURE
ECM ELECTRONICALLY COMMUTATED MOTOR
EGE EXISTING EXHAUST AIR GRILLE
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
FD FIRE DAMPER
FSD FIRE SMOKE DAMPER
FT, ' FOOT OR FEET
GA GAGE OR GAUGE
GR GRAINS
HD HEAD (PRESSURE)
ID DIAMETER, INSIDE
IN., " INCH OR INCHES
LAT LEAVING AIR TEMPERATURE
LF LINEAR FOOT OR LINEAR FEET
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MIN MINIMUM
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO. , # NUMBER
NTS NOT TO SCALE
OD DIAMETER, OUTSIDE
PD PRESSURE DROP
PPM PARTS PER MILLION
RGE EXISTING RETURN AIR GRILLE
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
SD SMOKE DAMPER
SDE EXISTING SUPPLY AIR DIFFUSER
SP STATIC PRESSURE
SPEC SPECIFICATION
TAB TESTING, ADJUSTING, AND BALANCING
TG TRANSFER GRILLE
TSP TOTAL STATIC PRESSURE
TU TERMINAL UNIT
TYP TYPICAL
UTR UP THRU ROOF
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
WB WET-BULB TEMPERATURE
NOTES:
1. NOT ALL ABBREVIATIONS MAY APPLY.
2. MECHANICAL SCHEDULES CONTAIN EQUIPMENT TAG ABBREVIATIONS THAT ARE HEREBY
INCORPORATED INTO THE ABBREVIATION LIST.
3. SEE OTHER DISCIPLINE DRAWINGS WITHIN THE CONSTRUCTION DOCUMENTS FOR
ABBREVIATIONS NOT DEFINED ABOVE OR IN MECHANICAL SCHEDULES.
MECHANICAL SYMBOLS:
CHECK VALVE
SAFETY OR RELIEF VALVE
SOLENOID VALVE
S
AIR VENT, AUTOMATIC
AV
AV
S
AIR VENT, MANUAL
AIR SEPARATOR
FLOWMETER, VENTURI
FLOWMETER, ORIFICE PLATE WITH FLANGES
VMF-1
FLOW SWITCH
FS
PRESSURE GAUGE WITH GAUGE COCK
PRESSURE SWITCH
PS
PUMP
PUMP SUCTION DIFFUSERPSD
STRAINER
STRAINER, BLOW OFF
STRAINER, DUPLEX
THERMOMETER IN PIPE WELL
LINETYPE/SYMBOL DESCRIPTION
PIPE DOWN
PIPE UP
BRANCH - TOP CONNECTION
BRANCH - BOTTOM CONNECTION
PIPE CAP
NOTES:
1. NOT ALL SYMBOLS MAY APPLY.
2. SEE SPECS AND DRAWINGS FOR SPECIFIC COMPONENT REQUIREMENTS.
DIRECTION OF WATER FLOW
PITCH DOWN OR UP-IN DIRECTION OF ARROW
PIPE REDUCER
ISOLATION VALVE, NORMALLY OPEN
ISOLATION VALVE, NORMALLY CLOSED
TWO WAY CONTROL VALVE
M
M
THREE WAY CONTROL VALVE
UNION
TEMPERATURE SENSOR IN PIPE WELL
T
M METER
FLEXIBLE CONNECTOR
REDUCED ZONE BACKFLOW PREVENTER
1/8"/1'-0"
BALANCING VALVE (##.# INDICATES GPM)
DOUBLE-CHECK BACKFLOW PREVENTER
ISOLATION VALVE IN VERTICAL PIPE, NO
ISOLATION VALVE IN VERTICAL PIPE, NC
2021 INTERNATIONAL BUILDING CODE (IBC)
2024 NFPA 101 LIFE SAFETY CODE
2022 NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900
2023 NATIONAL ELECTRICAL CODE (NEC) (NFPA 70)
2021 INTERNATIONAL MECHANICAL CODE (IMC)
2021 INTERNATIONAL PLUMBING CODE (IPC)
2015 ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)
ENERGY POLICY ACT OF 2005 (EPACT)
DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL,
COMMERCIAL AND MULTI-FAMILY HIGH-RISERESIDENTIAL BUILDINGS AND NEW LOW-RISE
RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435.
VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1- 2022.
SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15 – 2022.
UNLESS OTHERWISE SPECIFIED, SPECIFIC REFERENCES TO CODES, REGULATIONS, STANDARDS, MANUFACTURERS' INSTRUCTIONS, OR REQUIREMENTS OF REGULATORY AGENCIES, SHALL MEAN
THE LATEST EDITION OF EACH IN EFFECT AT THE DATE OF PROJECT SUBMISSION (U.N.O.)
CODES AND STANDARDS:
POINT OF CONNECTION OR DISCONNECTION
KEYNOTE SYMBOL#
DETAIL CALL-OUT SYMBOL
###-# EQUIPMENT TAG
GENERAL LEGEND:
SYMBOL DESCRIPTION
SECTION CUT CALL-OUT SYMBOL
ENLARGED PLAN CALL-OUT SYMBOL
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NEW CONSTRUCTION
(E) EXISTING TO REMAIN
LINETYPE DESCRIPTION
(X) EXISTING TO BE REMOVED
1. MECHANICAL WORK SHALL BE CONSTRUCTED IN A PROFESSIONAL MANNER. COMPONENTS
SHALL BE CLEANED PRIOR TO OWNER TURNOVER.
2. IF A CONTRACTOR PROVIDES EQUIPMENT OTHER THAN THE BASIS OF DESIGN, THAT
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COSTS INCURRED AS A RESULT. THAT
INCLUDES, BUT IS NOT LIMITED TO, STRUCTURAL MODIFICATIONS FOR INCREASED WEIGHT,
AND ELECTRICAL EQUIPMENT, WIRING, CONDUIT, AND BREAKER CHANGES FOR DIFFERENT
ELECTRICAL REQUIREMENTS.
3. COORDINATE POWER REQUIREMENTS WITH THE E.C. PRIOR TO PROVIDING SUBMITTALS TO
THE ENGINEER.
4. PROVIDE CONCRETE EQUIPMENT PADS FOR FLOOR-MOUNTED EQUIPMENT, UNLESS
OTHERWISE NOTED. SEE PLANS AND DETAILS FOR ADDITIONAL INFORMATION.
5. SEE SPEC SECTIONS 23 2113 AND 23 2213 FOR PIPE SYSTEM INSTALLATION, TESTING, AND
CLEANING REQUIREMENTS.
6. PROVIDE PIPE EXPANSION JOINT THAT ACCOMMODATES THE BUILDING MOVEMENT WHERE
DUCTWORK OR PIPING CROSSES BUILDING EXPANSION JOINT.
7. PROVIDE IDENTIFICATION FOR PIPING, VALVES, AND EQUIPMENT PER SPEC SECTION
23 0553.
8. PIPING SHALL NOT PASS THRU NOR UNDER ELECTRICAL ROOMS, DATA ROOMS, ELEVATOR
MACHINE ROOMS, ELEVATOR HOISTWAYS, SKYLIGHTS, AND ROOF ACCESS HATCHES.
9. INSULATION SHALL BE PROVIDED CONTINUOUS THROUGHOUT THE PIPING SYSTEM
INCLUDING AT HANGERS/SUPPORTS, FITTINGS, VALVES, AND ACCESSORIES. OPENINGS
SHALL BE PROVIDED TO ALLOW FOR VALVE HANDLE OPERATION AND ACCESS. INSULATION
THICKNESS SHALL MEET THE LISTED ENERGY CODE MINIMUM REQUIREMENTS. SEE SPEC
SECTIONS 23 0711 FOR SYSTEMS REQUIRING INSULATION AND ADDITIONAL INSTALLATION
REQUIREMENTS.
10. VALVES SHALL BE ACCESSIBLE. PROVIDE KEYED ACCESS PANELS WHERE VALVES HAVE BEEN
LOCATED IN CONCEALED AREAS. ACCESS PANEL SIZE SHALL BE LARGE ENOUGH TO ACCESS
EACH VALVE AND FOR FULL VALVE OPERATION.
11. ALL FINAL BRANCH PIPING TO TERMINAL UNITS SHALL BE 3/4" UNLESS NOTED OTHERWISE.
12. PIPING SHALL BE AT LEAST 8’ AFF UNLESS OTHERWISE NOTED OR FOR THE EXPLICIT
PURPOSE OF CONNECTING TO EQUIPMENT BELOW 8’ AFF.
13. INSTALL - TO PLACE IN POSITION AND CONNECT COMPLETE READY FOR USE.
FURNISH - TO PURCHASE/SUPPLY.
PROVIDE - TO FURNISH AND INSTALL.
MECHANICAL NOTES:
1. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID SUBMISSION TO VERIFY ALL FIELD
CONDITIONS INCLUDING BUT NOT LIMITED TO THE FOLLOWING:
A. LOCATIONS OF EXISTING MECHANICAL SYSTEMS.
B. LOCATIONS OF ARCHITECTURAL, STRUCTURAL, ELECTRICAL, PLUMBING,
TECHNOLOGY, FIRE PROTECTION, AND FIRE ALARM SYSTEMS.
C. EXISTING SURFACES WHICH REQUIRE ALTERING.
2. SCAN/X-RAY POST TENSION SLABS PRIOR TO ALTERATION. SHOP DRAWINGS SHALL REFLECT
REBAR AND TENSION CABLE LOCATIONS. OPENINGS SHALL BE COORDINATED WITH THE
STRUCTURAL ENGINEER PRIOR TO PERFORMING ANY WORK.
3. NOTIFY OWNER OF REQUIRED SYSTEM SHUTDOWNS AT LEAST TWO WEEKS PRIOR TO
SHUTDOWN. EXACT SHUTDOWN TIME AND PROCEDURE SHALL BE COORDINATED WITH
OWNER AT LEAST 96 HOURS PRIOR TO SHUTDOWN.
4. WHEN PIPING, CONTROLS, OR EQUIPMENT ARE NOTATED TO BE PERMANENTLY REMOVED
THEIR ASSOCIATED COMPONENTS SHALL ALSO BE REMOVED INCLUDING HANGERS,
SUPPORTS, AND ACCESSORIES.
5. COORDINATE THE DISCONNECTION AND REMOVAL OF POWERED SYSTEMS WITH THE E.C.
WHEN REMOVING POWERED MECHANICAL EQUIPMENT.
6. REPAIR EXISTING FLOORS, WALLS, AND CEILINGS IN ALTERED AREAS TO MATCH EXISTING.
SEE ARCHITECTURAL PLANS FOR FINISH DETAILS IN REMODEL AREAS.
RENOVATION NOTES:
CHILLED WATER RETURN CHWR
CHILLED WATER SUPPLYCHWS
DRAIND
HEATING WATER RETURN HWR
MAKEUP WATERMU
HEATING WATER SUPPLYHWS
CLEAN STEAM CONDENSATE (# DENOTES PRESSURE
IN PSI)
SC(#)
CLEAN STEAM (# DENOTES PRESSURE IN PSI)S(#)
MECHANICAL PIPING SYSTEMS:
LINETYPE/SYMBOL DESCRIPTION
1. THE PROJECT WILL BE CONSTRUCTED IN MULTIPLE PHASES. SEE ARCHITECTURAL &
PHASING DOCUMENTS FOR PHASING REQUIREMENTS.
2. CONTRACTOR SHALL CONFIRM WORK BEING PERFORMED IN ACTIVE PHASE DOES NOT
ADVERSELY AFFECT NORMAL OPERATIONS IN OTHER OCCUPIED SPACES.
3. PROVIDE TEMPORARY CONNECTIONS AS REQUIRED TO MAINTAIN SERVICE TO OCCUPIED
SPACES.
4. DESIGN DRAWINGS DO NOT INDICATE EVERY REQUIRED STEP TO ACHIEVE PHASED
CONSTRUCTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DEVELOP A CONSTRUCTION
PLAN TO INSTALL THE DESIGN WITHIN THE PHASING CONSTRAINTS.
5. HVAC SYSTEMS (EXCEPT ACA-AHU-1,-2,-3,-4) IMPACTED BY THE PROJECT SCOPE SHALL NOT
BE OFFLINE FOR LONGER THAN A 6-HOUR SPAN. PROVIDE TEMPORARY PORTABLE
HEATERS/COOLERS FOR SPACES IMPACTED BY HVAC SYSTEM OUTAGES TO MAINTAIN
ADEQUATE OCCUPIED SPACE CONDITIONS DURING CONSTRUCTION.
6. CONSTRUCTION ACTIVITIES IN OCCUPIED SPACES SHALL BE PERFORMED DURING
UNOCCUPIED HOURS (NIGHTS, WEEKENDS, AND/OR HOLIDAYS). RESTORE SPACES TO
ORIGINAL CONDITIONS BEFORE HOSPITAL STAFF AND/OR PATIENTS ARRIVE.
7. CONSTRUCTION ACTIVITIES IN UNOCCUPIED SPACES THAT HAVE ADVERSE EFFECTS
(EXCESSIVE NOISE, EXCESSIVE VIBRATION, ETC.) SHALL BE PERFORMED DURING
UNOCCUPIED HOURS (NIGHTS, WEEKENDS, AND/OR HOLIDAYS).
8. COORDINATE SCHEDULE WITH THE VA TO DETERMINE EXACT ALLOWABLE TIMES OF
CONSTRUCTION ACTIVITIES IN EACH PROJECT AREA.
PHASING NOTES:
CONTRACTOR ABBREVIATIONS:
ABBREVIATION DESCRIPTION
C.M. CONSTRUCTION MANAGER
E.C. ELECTRICAL CONTRACTOR
F.A.C. FIRE ALARM CONTRACTOR
F.P.C. FIRE PROTECTION CONTRACTOR
G.C. GENERAL CONTRACTOR
M.C. MECHANICAL CONTRACTOR
P.C. PLUMBING CONTRACTOR
T.C. TECHNOLOGY CONTRACTOR
T.C.C. TEMPERATURE CONTROL CONTRACTOR
LOW PRESSURE STEAM CONDENSATE (# DENOTES
PRESSURE IN PSI)
LOW PRESSURE STEAM SUPPLY
(# DENOTES PRESSURE IN PSI)
LPC(#)
LPS(#)
MPS(#) MEDIUM PRESSURE STEAM (# DENOTES PRESSURE
IN PSI)
MEDIUM PRESSURE STEAM CONDENSATE (#
DENOTES PRESSURE IN PSI)
MPC(#)
LOW PRESSURE STEAM RETURN
(# DENOTES PRESSURE IN PSI)
LPR(#)
NOT IN SCOPE
CPD PUMPED STEAM CONDENSATE
TEST PLUG
STEAM TRAP
RELIEF VENT
LINE TYPE /SYMBOL DESCRIPTION
1-HOUR FIRE BARRIER
2-HOUR FIRE BARRIER
1-HOUR SMOKE BARRIER
1-HOUR HAZARDOUS AREA FIRE BARRIER
FIRE-RATED ASSEMBLY LEGEND:
S S S S
HZ HZ HZ HZ
RE
G
IS
TE
RE
DPROFESSIONALENG
IN
EERER
IC
M.DeSPLINTER
M
ECHANICA
L
S
TATE OF CALIFORNIA
38688 Exp. 12-31-25
SIGNED: 06/23/25
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
CORRECT REUSABLE
MEDICAL EQUIP STORAGE
589A4-24-101
800 HOSPITAL DR, COLUMBIA, MO
Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015
Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383
Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086
(412) 212-7515
STAMP
07/25/2025
100% FINAL BID
DOCUMENTS
A u to d e s k D o c s /1
A
-2
-1
C o rr e c t R e u s a b le
M e d ic a l E q u ip m e n t S to ra g e /2
M
E P
T
.0
C o lu m b ia
M
O V
A M
C R
M E
S to ra g e
A C
A H
V A
C U p g ra d e s .r v t
-0 -2
:4
:3
P
M
MP001
EMD BST
PIPING COVER SHEET
Sheet
Number Sheet Name
MP001 PIPING COVER SHEET
MP100 PIPING - BASEMENT FLOOR PLAN
MP101 PIPING - FIRST FLOOR PLAN
MP102 PIPING - SECOND FLOOR PLAN
MP103 PIPING - THIRD FLOOR PLAN
MP104 PIPING - SIXTH FLOOR PLAN
MPD201 PIPING - ENLARGED BASEMENT FLOOR PLAN - AREA E & F - DEMOLITION
MPD202 PIPING - ENLARGED FIRST FLOOR PLAN - AREA E & F - DEMOLITION
MPD203 PIPING - ENLARGED BASEMENT FLOOR PLAN ROOMS - DEMOLITION
MPD204 PIPING - ENLARGED BASEMENT FLOOR PLAN ROOMS - DEMOLITION - DEDUCT #1
MPD205 PIPING - ENLARGED BASEMENT FLOOR PLAN ROOMS - DEMOLITION - DEDUCT #2
MPD206 PIPING - ENLARGED BASEMENT FLOOR PLAN ROOMS - DEMOLITION
MPD207 PIPING - ENLARGED FIRST FLOOR PLAN - PATHOLOGY - DEMOLITION
MPD208 PIPING - ENLARGED FIRST FLOOR PLAN ROOMS - DEMOLITION
MPD209 PIPING - ENLARGED THIRD FLOOR PLAN ROOMS - DEMOLITION
MP201 PIPING - ENLARGED BASEMENT FLOOR PLAN - AREA E & F - REMODEL
MP202 PIPING - ENLARGED FIRST FLOOR PLAN - AREA E & F - REMODEL
MP203 PIPING - ENLARGED SECOND FLOOR PLAN - AREA E & F - REMODEL
MP204 PIPING - ENLARGED BASEMENT FLOOR PLAN ROOMS - REMODEL
MP205 PIPING - ENLARGED BASEMENT FLOOR PLAN ROOMS - REMODEL - DEDUCT #1
MP206 PIPING - ENLARGED BASEMENT FLOOR PLAN ROOMS - REMODEL - DEDUCT #2
MP207 PIPING - ENLARGED BASEMENT FLOOR PLAN ROOMS - REMODEL
MP208 PIPING - ENLARGED BASEMENT FLOOR PLAN ROOMS - REMODEL
MP209 PIPING - ENLARGED FIRST FLOOR PLAN ROOMS - REMODEL
MP210 PIPING - ENLARGED THIRD FLOOR PLAN ROOMS - REMODEL
MP211 PIPING - PENTHOUSE FLOOR PLAN - REMODEL
MP301 PIPING - SECTION VIEWS
MP401 PIPING DETAILS
MP402 PIPING DETAILS
MP403 PIPING DETAILS
MP501 PIPING SCHEDULES
MP601 PIPING FLOW DIAGRAMS - HYDRONIC
MP602 PIPING FLOW DIAGRAMS - HYDRONIC - DEDUCT #1
MP603 PIPING FLOW DIAGRAMS - HYDRONIC - DEDUCT #2
MP604 PIPING FLOW DIAGRAMS - STEAM
MP605 PIPING FLOW DIAGRAMS - STEAM - DEDUCT #1
MP606 PIPING FLOW DIAGRAMS - STEAM - DEDUCT #2
Mark Revisions: Date:
1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES 07/29/2025
T T
T T
T T T
T
T
T
T
T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T T
T
T
T
T
T
EXAM RM.5
F110
EXAM
F111
PSY.
F112 EXAM
F113
GYN.
F114
TLT.
F114A
TLT.
F138A
GYN. EXAM
F138
EXAM
F139
EXAM
F140
EXAM
F141
PROCS.
F142
EXAM /
OFFICE
F155
EXAM /
OFFICE
F156
OFFICE
F157
OFFICE
F158
OFFICE
F159
OFFICE
F160
OFFICE
F161
STORAGE
F179
ELEC
F180
PHARMACY
WORK
F177
VAULT
F178
DISPENSING
F177A
F179B
UNKNOWN
F174
CONSULT 3
F174C
CONSULT 2
F174B
CONSULT 1
F174A
SWAMP
F176
OFFICE
F175
STAIR #11
F173F.M.S. ENG.
F170
PHARMACY
E141
ENTR. VEST.
E-1100
STORAGE
C1E34
STORAGE
C1E32
EXAM
F109
EXAM
F108
EXAM
F107
EXAM
F106
EXAM
F105
OFFICE
F103B
OFFICE
F103A
SOILED
UTIL.
F120
TLT.
F119
CLEAN
UTILITY
F118
EXAM
F116
EXAM
F115
GYN. EXAM
F137
TLT.
F137A
CONSULT
RM.
F136
CONSULT
RM.
F117
M.P.R.
CONF.
CLASS
F132
SOILED
UTILITY
F133
TOILET
F134
CLEAN
UTILITY
F135
EXAM
F142
EXAM /
OFFICE
F154
EXAM
F144
CLEAN
UTILITY
F153
EXAM
F145
EXAM /
OFFICE
F152
EXAM
F146
EXAM
F149
EXAM
F147
DIETITIAN
F148
SPEC.
F150 TLT.
F171A
EXAM
F171
PHARMACY
F163
BLDG. MGT.
LKR. / LNGE.
/ TLT.
F168
BLDG. MGT.
LKR. / LNGE.
/ TLT.
F167
ENVIRO.
MGT.
F169
HOME
TELEHEALTH
N.
F166
OFFICE
F165
OFFICE
F164
OFFICE
F162
ST. LNGE.
F151
TLT.
F151A
TLT.
F151B
DECONTAMINATION
C1E21
F.M.S. ENG.
F101
ELEC. TELE.
MECH.
F102
STAIR #10
F102A
EXAM
E125A
EXAM
E125B
EXAM
E125C
ISO.
E125D
PT. TLT.
E15E E.N.T. EXAM
E125F
H. NURSE /
NOD
E109
ST. LNGE. /
LKR. / CONF.
E110
SOILED UTIL
E112
PT. TLT
E111
CLEAN
STORAGE
E129
B.H. EXAM
E127
TOILET
E127A
VETR RM. 1
E132
VERT RM. 2
E131
VERT RM. 3
E130
TREAT. 1
E124
TREAT. 2
E123
RESUS /
BARIATRIC
E122
TREAT. 4
E120
PT. TLT/SHR
E117
MED.
E133
N. STN./
PHYS. WK.
E126
CORRIDOR
C1E29
TRIAGE
E114
TRIAGE
E116
RECEPTION
E115
TREAT. 3
E121
CORRIDOR
C1E24
CONSULT
RM.
F128
CONSULT
F123
CONSULT
RM.
F124
CONSULT
RM.
F127
BLDG. MGT.
LKR. / LNGE.
/ TLT.
F125
BLDG. MGT.
LKR. / LNGE.
/ TLT.
F126
ST. TLT.
F122
ST. TLT.
F129
TRAVEL
E140
TELEHEALTH
IMAGING
E143
TRANSCRIPTION
OFFICE
E144
R.O.I E145
R.O.I E146
OFFICE
E148
EYE
SCREENING
E147INFO. MGT.
SVC
E139
F.M.S ENG.
E138
EQ. STG.
E144
F.M.S ENG.
E137
HBA
E102F
ROI LEGAL
E102E
HBA
E102D
HBA
E102C
HBA
E102B
PRE-REG
E102A
CORRIDOR
C1F22CORRIDOR
C1E8
ELEVATOR
LOBBY
C1E9
ELEVATOR
LOBBY
C1E10
WAITING
AREA
C1E12
WAITING
C1E35
CORRIDOR
C1E12A
CORRIDOR
C1E15
CORRIDOR
F1F23
CORRIDOR
C1F18
CORRIDOR
C1F17
CORRIDOR
C1F16
CORRIDOR
C1F19
CORRIDOR
C1F12
CORRIDOR
C1F10
UNKNOWN
C1F13
ALCOVE
C1F11
CORRIDOR
C1F14
N. STN.
F131
M.A.S.
F130
CORRIDOR
C1F15
PROVIDER
WK. RM.
F121
ALCOVE
C1F6 ALCOVE
C1F8
CORRIDOR
C1F7
CORRIDOR
C1F5
CORRIDOR
C1F9
CORRIDOR
C1F7
N. STN.
CORRIDOR
C1F2
WAITING
C1F20
WAITING
F103
CORRIDOR
C1F1
CORRIDOR
C1F21
LOBBY
F406
PHARM.
ENTRY
E100
CORRIDOR
F104
M.A.S.
F105A
ALCOVE
C1F7
KIOSK
E101
OFFICE
F163B
CORRIDOR
C1E18
CORRIDOR
C1E12
CORRIDOR
C1E13
ELEV.
#11
ELEV.
#10
ELEV.
#9
E129B
E129A
(E)1"
(E )H
W S
(E )H
W R
(E)1"
(E)3/4"
(E )H
W S
(E )H
W R
(E)1"(E)1"
(E)1"
(E)1"(E)1"
(E)1 1/2"(E)1 1/2"
(E )H
W S
(E )H
W R
(E)1 1/2"(E)1 1/2"
(E)HWR
(E)HWS
(E)1 1/2"
(E)1"
(E)1"
(E)1"(E)1"
(E)1 1/2"(E)1 1/2"
(E)1 1/2"
(E)1 1/2"
(E)1"(E)1"
(E)2"(E)2"
(E)2"(E)2"
(E)1"(E)1"
(X)2 1/2"
(X)2" HWS
(X)2" HWR
(E)3/4"
(E)HWR
(E)HWS
(X )3
/4
H W
R (X
)3 /4
H
W S
(E )H
W R
(E )H
W S
(E)HWR
(E)HWS
(E )H
W R
(E )H
W S
(E)1"(E)1"
(E)1"
(E)1"
(E)1 1/2"
(E)1"
(E)1"
(E)1"
(E)1 1/4"
(E)1 1/4"
(E)1"(E)1" (E)1 1/4" (E)1"
(E)1"
(E)RB 1-4
(E)RB 1-3
(X)VAV 1-8
(X)VAV 1-7
(X)VAV 1-9
(X)VAV 1-11
(X)VAV 1-10
(X)VAV 1-14 (X)VAV 1-13
(X)VAV 1-12
(X)VAV 1-15
(X)VAV 1-1
(X)VAV 1-3
(X)VAV 1-2
(X)VAV 1-6
(X)VAV 1-4
(X)VAV 1-5
(E)VAV E-6
(E)VAV E-4 (E)VAV E-5
(E)RB 1-13
(E)RB 1-14
(X)VAV 1-22
(X)VAV 1-21
(E)1-T2.17
(E)1-T2.18 (E)1-T2.16
(E)FTU 1-1
(E)RB 1-12
(E)RB 1-11
(E)RB 1-10
(E)RB 1-9
(E)RB 1-8
(E)RB 1-7
(E)RB 1-6
(E)RB 1-5
(E)1-T1.14
(E)1-T1.13
(E)1-T1.12
(E)1-T1.11
(E)1-T1.15
(E)1-T1.16
(E)1-T1.17
(E)1-T1.18
(E)RB 1-15
(E)RB 1-16
(E)VAV E-9
(E)VAV E-8
(E)VAV E-11
(E)VAV E-10
(E)VAV E-12
(E)VAV E-13
(E)VAV E-14
(E)VAV E-3
(E)VAV E-1
(E)VAV E-7
(E)FTU 1-2
(E)VAV E-2
(E)RB 1-1
(E)RB 1-2
(X)VAV 1-20
(E)5" HWR &
HWS UP &
DOWN
(E)HWR &
HWS DN
(E)RB
1-4(E)RB
1-3
(E)RB 1-5
(E)RB 1-6 (E)RB 1-7
(E)RB 1-8
(E)VAV 1-11
(E)VAV 1-7
(E)VAV 1-8
(E)VAV 1-9
(E)VAV 1-4
(E)VAV 1-6
(E)VAV 1-3
(E)VAV 1-1
(E)VAV 1-14
(E)VAV 1-13
(E)VAV 1-12
(E)VAV 1-10
(E)TU 1-15
(E)VAV 1-20
(E)RB 1-9
(E)RB 1-10
(E)RB 1-2
(E)RB 1-1
(E)RB 1-15 (E)RB 1-12
2 3 1 4 5 5.6 6 6.3 7 8 9 10 10.6 11 11.5
H
G
F
B
C
D.1
D
E.1
E
(E)FTU
1-2 (E)VAV E-1
(E)VAV E-2
(E)VAV E-4
(E)VAV E-3
(E)VAV E-6
(E)VAV E-7
(E)VAV E-8
(E)VAV E-9
(E)VAV E-10
(E)VAV E-11
(E)VAV E-13
(E)VAV E-14
(X)VAV 1-16
(X)3/4"
(E)VAV 1-2
(E)VAV 1-16
(E)VAV 1-21
(E)VAV 1-22
(E)HWR &
HWS UP
(E)CUH-2
(E)CUH-1
RE
G
IS
TE
RE
DPROFESSIONALENG
IN
EERER
IC
M.DeSPLINTER
M
ECHANICA
L
S
TATE OF CALIFORNIA
38688 Exp. 12-31-25
SIGNED: 06/23/25
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
CORRECT REUSABLE
MEDICAL EQUIP STORAGE
589A4-24-101
800 HOSPITAL DR, COLUMBIA, MO
Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015
Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383
Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086
(412) 212-7515
STAMP
07/25/2025
FIRST FLOOR KEYPLAN
E & F
SHIPPING
WAREHOUSE
OR ADDITION
NORTH
B A
ACA BUILDING
AREAS
AREA AREA
G
AREA
C & D
AREAS
BUILDING 1
100% FINAL BID
DOCUMENTS
A u to d e s k D o c s /1
A
-2
-1
C o rr e c t R e u s a b le
M e d ic a l E q u ip m e n t S to ra g e /2
M
E P
T
.0
C o lu m b ia
M
O V
A M
C R
M E
S to ra g e
A C
A H
V A
C U p g ra d e s .r v t
-0 -2
:4
:5
P
M
MPD202
EMD BST
PIPING - ENLARGED FIRST FLOOR PLAN - AREA
E & F - DEMOLITION
N
1/8" = 1'-0"1
PIPING - ENLARGED FIRST FLOOR PLAN - AREA E & F - DEMOLITION
KEYNOTES - MPD202
NUMBER TEXT
1 REMOVE EXISTING PIPING AS SHOWN AND PREPARE FOR NEW CONNECTION.
Mark Revisions: Date:
1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES 07/29/2025
DN
MECH
ROOM
E003
ELEC ROOM
E003A
(E)LPC DN
(X)ACA-HX-1
(BELOW)
(E)HX-4
(E)HX-5
(BELOW)
(E)ACA-AHU-6
(E)STEAM
GENERATOR
(E )H
W R
(E)HWR
(E )H
W R
(E )M
P S
(E)4" HWR
(E)4" HWS
(X)ACA-AHU-3 (X)ACA-AHU-2 (X)ACA-AHU-1
(E)4" CHWS
(E)4" CHWR
(E)2" MPS
(E)4" LPS
(E)2" LPC
(X)ACA-AHU-4
(E)5" HWS
(E)5" HWR
(X)2 1/2" CHWS
(X)2 1/2" CHWR
(X)4" CHWR
(X)4" CHWS
(X)4" CHWS
(X)4" CHWR
(X)4" CHWS
(X)5" CHWR
(E)4" LPC
(E)1" LPC
(E)2" LPC
(E)2" LPC
(E)5" CHWS
(E)2" LPC
(E)5" CHWR
(E)5" CHWS
(E)5" CHWR
(E)6" CHWR
(E)6" CHWS
(X)HWP-2
(X)HWP-1
(X)HWP-3
(X)ACA-HX-2
(X)5" HWS
(E)3" HWR
(E)3" HWS
(E)5" HWS
(E)5" HWR(E)5" LPS
(E )M
P S
(E)MPS
(X)4" HWR
(X)ACA-HX-3 1
(X)5" HWR
(E)4" LPS
(X)4" LPS
(X)4" LPS
(E)4" PC
(E)2 1/2" CHWR
(E)2 1/2" CHWS
(X)4" LPS
(E)4" LPS
(E)MPS
(X)AS
(E)4" LPS
(X)ET
(X)5" HWS
(E)UH
(X)4" HWR
(E)4" HWR
(E)4" HWS
(E)STEAM CONDENSATE TANK
AND CONDENSATE PUMP
(X)POT FEEDER
(X)LPS
(X)LPC
(X)LPC
(X)HC-4
(X)LPS
2 3 1 4 5 5.6
B
C
D.1
D
A
(E)HWR
(E)HWS 3
(X)LPS TO HC-2(X)LPS TO HC-3
(X)LPS TO HC-1
(E)4" LPC
7 7
(E)12" MPS
(E)4" SC
(E)4" LPC
(E)5" LPS
(E)5" LPS
(X)HC-3 (X)HC-2 (X)HC-1
(X)4" HWS
TO (E)AHU
TO DUCT
MOUNTED
HUMIDIFIER
(E)5" HWS
(E)5" HWR
(E)6" CHWS
(E)6" CHWR
(E)HWS TO UNIT
HEATER
(E)HWR TO UNIT
HEATER
RE
G
IS
TE
RE
DPROFESSIONALENG
IN
EERER
IC
M.DeSPLINTER
M
ECHANICA
L
S
TATE OF CALIFORNIA
38688 Exp. 12-31-25
SIGNED: 06/23/25
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
CORRECT REUSABLE
MEDICAL EQUIP STORAGE
589A4-24-101
800 HOSPITAL DR, COLUMBIA, MO
Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015
Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383
Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086
(412) 212-7515
STAMP
07/25/2025
BASEMENT KEYPLAN
NORTH
E & F
SHIPPING
WAREHOUSE
OR ADDITION B A
ACA BUILDING
AREAS
AREA AREA
G
AREA
C & D
AREAS
BUILDING 1
100% FINAL BID
DOCUMENTS
A u to d e s k D o c s /1
A
-2
-1
C o rr e c t R e u s a b le
M e d ic a l E q u ip m e n t S to ra g e /2
M
E P
T
.0
C o lu m b ia
M
O V
A M
C R
M E
S to ra g e
A C
A H
V A
C U p g ra d e s .r v t
-0 -2
:4
:5
P
M
MPD203
EMD BST
PIPING - ENLARGED BASEMENT FLOOR PLAN
ROOMS - DEMOLITION
N
1/4" = 1'-0"1
PIPING - ENLARGED BASEMENT FLOOR PLAN - MECHANICAL RM E003 - DEMOLITION
KEYNOTES - MPD203
NUMBER TEXT
REMOVE EXISTING HEAT EXCHANGER AND ASSOCIATED PIPING, AS SHOWN.
REMOVE ASSOCIATED ACCESSORIES, SUPPORTS, CONTROLS, ETC.
REMOVE EXISTING PUMP AND ASSOCIATED PIPING, AS SHOWN. REMOVE
ASSOCIATED ACCESSORIES, SUPPORTS, CONTROLS, ETC.
REMOVE CHILLED WATER PIPING, AS NEEDED, TO ALLOW FOR NEW AHU
INSTALLATION AND PREPARE FOR NEW CONNECTION.
REMOVE EXISTING AIR SEPARATOR AND ASSOCIATED PIPING AS SHOWN.
REMOVE ASSOCIATED ACCESSORIES, SUPPORTS, CONTROLS, ETC.
REMOVE EXISTING EXPANSION TANK AND ASSOCIATED PIPING AS SHOWN.
REMOVE ASSOCIATED ACCESSORIES, SUPPORTS, CONTROLS, ETC.
6 REMOVE EXISTING PIPING AS SHOWN AND PREPARE FOR NEW CONNECTION.
REMOVE EXISTING PIPING AS SHOWN AND CAP. REMOVE ASSOCIATED
ACCESSORIES, SUPPORTS, CONTROLS, ETC. INSULATE AND JACKET TO MATCH
EXISTING.
REMOVE EXISTING POT FEEDER AND ASSOCIATED PIPING AS SHOWN. REMOVE
ASSOCIATED ACCESSORIES, SUPPORTS, CONTROLS, ETC.
Mark Revisions: Date:
WORK
ROOM
F002
MECH
ROOM
E003
ELEC ROOM
E003A
2 3 1 4 5 5.6
B
C
D.1
D
A
(E)LPC DN
(X)ACA-HX-1
(BELOW)
(E)HX-4
(E)HX-5
(BELOW)
(E)ACA-AHU-6
(E)STEAM
GENERATOR
(E )H
W R
(E)HWR
(E )H
W R
(E)6" CHWS DN
(E)6" CHWR DN
(E )M
P S
(E)4" HWR
(E)4" HWS
(X)ACA-AHU-3 (X)ACA-AHU-2 (X)ACA-AHU-1
(E)4" CHWS
(E)4" CHWR
(E)2" MPS
(E)4" LPS
(E)2" LPC
(E)5" HWS
(E)5" HWR
(X)4" CHWR
(X)4" CHWS(X)4" CHWS
(X)4" CHWR
3 3
(X)4" CHWS
(X)5" CHWR
(E)4" LPC
(E)1" LPC
(E)2" LPC
(E)2" LPC
(E)5" CHWS
(E)2" LPC
(E)5" CHWR
(E)5" CHWS
(E)5" CHWR
(E)6" CHWR
(E)6" CHWS
(X)HWP-2
(X)HWP-1
(X)HWP-3
(X)ACA-HX-2
(X)5" HWS
(E)3" HWR
(E)3" HWS
(E)5" HWS
(E)5" HWR(E)5" LPS
(E )M
P S
(E)MPS
(X)4" HWR
(X)ACA-HX-3 1
(X)5" HWR
(E)4" LPS
(X)4" LPS
(X)4" LPS
(E)4" PC
(E)2 1/2" CHWR
(E)2 1/2" CHWS
(X)4" LPS
(E)4" LPS
(E)MPS
(X)AS
(E)4" LPS
(X)ET
(X)5" HWS
(E)UH
(X)4" HWR
(E)4" HWR
(E)4" HWS
(E)STEAM CONDENSATE TANK
AND CONDENSATE PUMP
(X)POT FEEDER
(E)LPS
(E)LPC
(E)LPC
(E)HC-4
(E)LPS
(E)ACA-AHU-4
(E )M
P S
(E )L
P S
(E )L
P C
(E )S
C
(E )L
P S
(X)HC-3 (X)HC-2 (X)HC-1
(X)4" HWS
TO (E)AHU
TO (E)AHU
TO DUCT
MOUNTED
HUMIDIFIER
(E)1" HWS TO UNIT
HEATER
(E)1" HWR TO UNIT
HEATER
RE
G
IS
TE
RE
DPROFESSIONALENG
IN
EERER
IC
M.DeSPLINTER
M
ECHANICA
L
S
TATE OF CALIFORNIA
38688 Exp. 12-31-25
SIGNED: 06/23/25
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
CORRECT REUSABLE
MEDICAL EQUIP STORAGE
589A4-24-101
800 HOSPITAL DR, COLUMBIA, MO
Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015
Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383
Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086
(412) 212-7515
STAMP
07/25/2025
BASEMENT KEYPLAN
NORTH
E & F
SHIPPING
WAREHOUSE
OR ADDITION B A
ACA BUILDING
AREAS
AREA AREA
G
AREA
C & D
AREAS
BUILDING 1
100% FINAL BID
DOCUMENTS
A u to d e s k D o c s /1
A
-2
-1
C o rr e c t R e u s a b le
M e d ic a l E q u ip m e n t S to ra g e /2
M
E P
T
.0
C o lu m b ia
M
O V
A M
C R
M E
S to ra g e
A C
A H
V A
C U p g ra d e s .r v t
-0 -2
:4
:5
P
M
MPD204
EMD BST
PIPING - ENLARGED BASEMENT FLOOR PLAN
ROOMS - DEMOLITION - DEDUCT #1
N
1/4" = 1'-0"1 PIPING - ENLARGED BASEMENT FLOOR PLAN - MECHANICAL RM E003 - DEMOLITION DEDUCT #1
KEYNOTES - MPD204
NUMBER TEXT
REMOVE EXISTING HEAT EXCHANGER AND ASSOCIATED PIPING AS SHOWN.
REMOVE ASSOCIATED ACCESSORIES, SUPPORTS, CONTROLS, ETC.
REMOVE EXISTING PUMP AND ASSOCIATED PIPING AS SHOWN. REMOVE
ASSOCIATED ACCESSORIES, SUPPORTS, CONTROLS, ETC.
REMOVE CHILLED WATER PIPING, AS NEEDED, TO ALLOW FOR NEW AHU
INSTALLATION AND PREPARE FOR NEW CONNECTION.
REMOVE EXISTING AIR SEPARATOR AND ASSOCIATED PIPING AS SHOWN.
REMOVE ASSOCIATED ACCESSORIES, SUPPORTS, CONTROLS, ETC.
REMOVE EXISTING EXPANSION TANK AND ASSOCIATED PIPING AS SHOWN.
REMOVE ASSOCIATED ACCESSORIES, SUPPORTS, CONTROLS, ETC.
6 REMOVE EXISTING PIPING AS SHOWN AND PREPARE FOR NEW CONNECTION.
REMOVE EXISTING PIPING AS SHOWN AND CAP. REMOVE ASSOCIATED
ACCESSORIES, SUPPORTS, CONTROLS, ETC. INSULATE AND JACKET TO MATCH
EXISTING.
REMOVE EXISTING POT FEEDER AND ASSOCIATED PIPING AS SHOWN. REMOVE
ASSOCIATED ACCESSORIES, SUPPORTS, CONTROLS, ETC.
Mark Revisions: Date:
1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES 07/29/2025
WORK
ROOM
F002
MECH
ROOM
E003
ELEC ROOM
E003A
2 3 1 4 5 5.6
B
C
D.1
D
A
(E)LPC DN
(X)ACA-HX-1
(BELOW)
(E)HX-4
(E)HX-5
(BELOW)
(E)ACA-AHU-6
(E)STEAM
GENERATOR
(E )H
W R
(E)HWR
(E )H
W R
(E)6" CHWS DN
(E)6" CHWR DN
(E )M
P S
(E)4" HWR
(E)4" HWS
(X)ACA-AHU-2 (X)ACA-AHU-1
(E)4" CHWS
(E)4" CHWR
(E)2" MPS
(E)4" LPS
(E)2" LPC
(E)5" HWS
(E)5" HWR
(X)4" CHWR
(X)4" CHWS
(X)4" CHWS
(X)4" CHWR
(E)4" LPC
(E)1" LPC
(E)2" LPC
(E)2" LPC
(E)5" CHWS
(E)2" LPC
(E)5" CHWR
(E)5" CHWS
(E)5" CHWR
(E)6" CHWR
(E)6" CHWS
(X)HWP-2
(X)HWP-1
(X)HWP-3
(X)ACA-HX-2
(X)5" HWS
(E)3" HWR
(E)3" HWS
(E)5" HWS
(E)5" HWR
(E)5" LPS
(E )M
P S
(E)MPS
(X)4" HWR
(X)ACA-HX-3 1
(X)5" HWR
(E)4" LPS
(X)4" LPS
(X)4" LPS
(E)4" PC
(E)2 1/2" CHWR
(E)2 1/2" CHWS
(X)4" LPS
(E)4" LPS
(E)MPS
(X)AS
(E)4" LPS
(X)ET
(X)5" HWS
(E)UH
(X)4" HWR
(E)4" HWR
(E)4" HWS
(E)STEAM CONDENSATE TANK
AND CONDENSATE PUMP
(X)POT FEEDER
(E)LPS
(E)LPC
(E)LPC
(E)HC-4
(E)LPS
(E)ACA-AHU-4
(E)ACA-AHU-3
(E )M
P S
(E )L
P S
(E )L
P S
(E )L
P C
(E )S
C
(X)HC-1(X)HC-2
(X)4" LPS
(X)4" HWS
TO (E)AHU
(E)HC-3
(E)1" HWS TO UNIT
HEATER
(E)1" HWR TO UNIT
HEATER
TO DUCT
MOUNTED
HUMIDIFIER
RE
G
IS
TE
RE
DPROFESSIONALENG
IN
EERER
IC
M.DeSPLINTER
M
ECHANICA
L
S
TATE OF CALIFORNIA
38688 Exp. 12-31-25
SIGNED: 06/23/25
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
CORRECT REUSABLE
MEDICAL EQUIP STORAGE
589A4-24-101
800 HOSPITAL DR, COLUMBIA, MO
Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015
Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383
Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086
(412) 212-7515
STAMP
07/25/2025
BASEMENT KEYPLAN
NORTH
E & F
SHIPPING
WAREHOUSE
OR ADDITION B A
ACA BUILDING
AREAS
AREA AREA
G
AREA
C & D
AREAS
BUILDING 1
100% FINAL BID
DOCUMENTS
A u to d e s k D o c s /1
A
-2
-1
C o rr e c t R e u s a b le
M e d ic a l E q u ip m e n t S to ra g e /2
M
E P
T
.0
C o lu m b ia
M
O V
A M
C R
M E
S to ra g e
A C
A H
V A
C U p g ra d e s .r v t
-0 -2
:4
:0
P
M
MPD205
EMD BST
PIPING - ENLARGED BASEMENT FLOOR PLAN
ROOMS - DEMOLITION - DEDUCT #2
KEYNOTES - MPD205
NUMBER TEXT
REMOVE EXISTING HEAT EXCHANGER AND ASSOCIATED PIPING AS SHOWN.
REMOVE ASSOCIATED ACCESSORIES, SUPPORTS, CONTROLS, ETC.
REMOVE EXISTING PUMP AND ASSOCIATED PIPING AS SHOWN. REMOVE
ASSOCIATED ACCESSORIES, SUPPORTS, CONTROLS, ETC.
REMOVE CHILLED WATER PIPING, AS NEEDED, TO ALLOW FOR NEW AHU
INSTALLATION AND PREPARE FOR NEW CONNECTION.
REMOVE EXISTING AIR SEPARATOR AND ASSOCIATED PIPING AS SHOWN.
REMOVE ASSOCIATED ACCESSORIES, SUPPORTS, CONTROLS, ETC.
REMOVE EXISTING EXPANSION TANK AND ASSOCIATED PIPING AS SHOWN.
REMOVE ASSOCIATED ACCESSORIES, SUPPORTS, CONTROLS, ETC.
6 REMOVE EXISTING PIPING AS SHOWN AND PREPARE FOR NEW CONNECTION.
REMOVE EXISTING PIPING AS SHOWN AND CAP. REMOVE ASSOCIATED
ACCESSORIES, SUPPORTS, CONTROLS, ETC. INSULATE AND JACKET TO MATCH
EXISTING.
REMOVE EXISTING POT FEEDER AND ASSOCIATED PIPING AS SHOWN. REMOVE
ASSOCIATED ACCESSORIES, SUPPORTS, CONTROLS, ETC.
N
1/4" = 1'-0"1 PIPING - ENLARGED BASEMENT FLOOR PLAN - MECHANICAL RM E003 - DEMOLITION DEDUCT #2
Mark Revisions: Date:
1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES 07/29/2025
FIRE
SPRINKLER
PUMP ROOM
D017
PIPE &
MECHANICS
SHOP
D016
(X)USG
(X)2 1/2" MPS
E D
10.4
(X)S
(X)2 1/2" MPS DN TO MAIN
(X)1 1/2" MPC DN
(E)LPR
RE
G
IS
TE
RE
DPROFESSIONALENG
IN
EERER
IC
M.DeSPLINTER
M
ECHANICA
L
S
TATE OF CALIFORNIA
38688 Exp. 12-31-25
SIGNED: 06/23/25
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
CORRECT REUSABLE
MEDICAL EQUIP STORAGE
589A4-24-101
800 HOSPITAL DR, COLUMBIA, MO
Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015
Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383
Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086
(412) 212-7515
STAMP
07/25/2025
BASEMENT KEYPLAN
NORTH
E & F
SHIPPING
WAREHOUSE
OR ADDITION B A
ACA BUILDING
AREAS
AREA AREA
G
AREA
C & D
AREAS
BUILDING 1
100% FINAL BID
DOCUMENTS
A u to d e s k D o c s /1
A
-2
-1
C o rr e c t R e u s a b le
M e d ic a l E q u ip m e n t S to ra g e /2
M
E P
T
.0
C o lu m b ia
M
O V
A M
C R
M E
S to ra g e
A C
A H
V A
C U p g ra d e s .r v t
-0 -2
:4
:0
P
M
MPD206
EMD BST
PIPING - ENLARGED BASEMENT FLOOR PLAN
ROOMS - DEMOLITION
N
3/16" = 1'-0"1
PIPING - ENLARGED BASEMENT FLOOR PLAN - RM D017- DEMOLITION
KEYNOTES - MPD206
NUMBER TEXT
REMOVE AND SALVAGE EXISTING STEAM GENERATOR IN WORKING CONDITION.
REMOVE ASSOCIATED PIPING AS SHOWN. RETURN STEAM GENERATOR TO
OWNER.
REMOVE EXISTING STEAM CONDENSATE PIPING BACK TO FLOOR PENETRATION
AND CAP. INSULATE TO MATCH EXISTING.
REMOVE CLEAN STEAM PIPING BACK TO FLOOR PENETRATION AND CAP. TAG AS
ABANDONED.
REMOVE EXISTING STEAM PIPING BACK TO MAINS AND CAP. INSULATE TO
MATCH EXISTING. (E)ISOLATION VALVE IS IN BASEMENT MECH ROOM, BEHIND
SOFTENER HOLDING TANK.
Mark Revisions: Date:
T
STERILE
STORAGE
C347
CORRIDOR
C3C6
La L K
10.4
(E)3/4" HWS
(E)3/4" HWR
(X)1-TU06.13 (E)1-TU06.13
CLEAN
UTILITY
ROOM
E320
DENTAL
OPERATOR
E341
DENTAL
OPERATORY
E321
DENTAL
OPERATORY
E324
CORRIDOR
C3E2
DENTAL
OPERATORY
E317
DENTAL
OPERATORY
E318
DENTAL
CHIEF
OFFICE
E319
DENTAL
OPERATORY
E322
DENTAL
OPERATORY
E323
CORRIDOR
C3F1
CONFERENCE
ROOM
F307
HSKING
F308
STAFF
TOILET
F309
STAFF
TOILET
F310
EXAM ROOM
F328
EXAM ROOM
F327
STAFF
TOILET
F319
CLEAN
DISPATCH
F318
SOLID
HOLDING
F314
CORRIDOR
C3E3
CLO.
F306A
F
C
D.1
D
E.1
E
(E)TU-AHU7-002
(X)VAV-132
(E )1
H
W S
(E )1
H
W R
(E)VAV-132
(E)TU-AHU7-002
RE
G
IS
TE
RE
DPROFESSIONALENG
IN
EERER
IC
M.DeSPLINTER
M
ECHANICA
L
S
TATE OF CALIFORNIA
38688 Exp. 12-31-25
SIGNED: 06/23/25
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
CORRECT REUSABLE
MEDICAL EQUIP STORAGE
589A4-24-101
800 HOSPITAL DR, COLUMBIA, MO
Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015
Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383
Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086
(412) 212-7515
STAMP
07/25/2025
THIRD FLOOR KEYPLAN
NORTH
E & F
SHIPPING
WAREHOUSE
OR ADDITION B A
ACA BUILDING
AREAS
AREA AREA
G
AREA
C & D
AREAS
BUILDING 1
100% FINAL BID
DOCUMENTS
A u to d e s k D o c s /1
A
-2
-1
C o rr e c t R e u s a b le
M e d ic a l E q u ip m e n t S to ra g e /2
M
E P
T
.0
C o lu m b ia
M
O V
A M
C R
M E
S to ra g e
A C
A H
V A
C U p g ra d e s .r v t
-0 -2
:4
:0
P
M
MPD209
EMD BST
PIPING - ENLARGED THIRD FLOOR PLAN
ROOMS - DEMOLITION
N
1/4" = 1'-0"1 PIPING - THIRD FLOOR PLAN - RM C347 - DEMOLITION
N
1/4" = 1'-0"2
PIPING - THIRD FLOOR PLAN - RM E320, F318 - DEMOLITION
KEYNOTES - MPD209
NUMBER TEXT
1 DISCONNECT TERMINAL UNIT PIPING . PREPARE FOR NEW INSTALLATION.
Mark Revisions: Date:
T T
T
T T T
T
T
T
T
T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T T
T
T
T
T
T
EXAM RM.5
F110
EXAM
F111
PSY.
F112 EXAM
F113
GYN.
F114
TLT.
F114A
TLT.
F138A
GYN. EXAM
F138
EXAM
F139
EXAM
F140
EXAM
F141
PROCS.
F142
EXAM /
OFFICE
F155
EXAM /
OFFICE
F156
OFFICE
F157
OFFICE
F158
OFFICE
F159
OFFICE
F160
OFFICE
F161
STORAGE
F179
ELEC
F180
PHARMACY
WORK
F177
VAULT
F178
DISPENSING
F177A
F179B
UNKNOWN
F174
CONSULT 3
F174C
CONSULT 2
F174B
CONSULT 1
F174A
SWAMP
F176
OFFICE
F175
STAIR #11
F173F.M.S. ENG.
F170
PHARMACY
E141
ENTR. VEST.
E-1100
STORAGE
C1E34
STORAGE
C1E32
EXAM
F109
EXAM
F108
EXAM
F107
EXAM
F106
EXAM
F105
OFFICE
F103B
OFFICE
F103A
SOILED
UTIL.
F120
TLT.
F119
CLEAN
UTILITY
F118
EXAM
F116
EXAM
F115
GYN. EXAM
F137
TLT.
F137A
CONSULT
RM.
F136
CONSULT
RM.
F117
M.P.R.
CONF.
CLASS
F132
SOILED
UTILITY
F133
TOILET
F134
CLEAN
UTILITY
F135
EXAM
F142
EXAM /
OFFICE
F154
EXAM
F144
CLEAN
UTILITY
F153
EXAM
F145
EXAM /
OFFICE
F152
EXAM
F146
EXAM
F149
EXAM
F147
DIETITIAN
F148
SPEC.
F150 TLT.
F171A
EXAM
F171
PHARMACY
F163
BLDG. MGT.
LKR. / LNGE.
/ TLT.
F168
BLDG. MGT.
LKR. / LNGE.
/ TLT.
F167
ENVIRO.
MGT.
F169
HOME
TELEHEALTH
N.
F166
OFFICE
F165
OFFICE
F164
OFFICE
F162
ST. LNGE.
F151
TLT.
F151A
TLT.
F151B
DECONTAMINATION
C1E21
F.M.S. ENG.
F101
ELEC. TELE.
MECH.
F102
STAIR #10
F102A
EXAM
E125A
EXAM
E125B
EXAM
E125C
ISO.
E125D
PT. TLT.
E15E E.N.T. EXAM
E125F
H. NURSE /
NOD
E109
ST. LNGE. /
LKR. / CONF.
E110
SOILED UTIL
E112
PT. TLT
E111
CLEAN
STORAGE
E129
B.H. EXAM
E127
TOILET
E127A
VETR RM. 1
E132
VERT RM. 2
E131
VERT RM. 3
E130
TREAT. 1
E124
TREAT. 2
E123
RESUS /
BARIATRIC
E122
TREAT. 4
E120
PT. TLT/SHR
E117
MED.
E133
N. STN./
PHYS. WK.
E126
CORRIDOR
C1E29
TRIAGE
E114
TRIAGE
E116
RECEPTION
E115
TREAT. 3
E121
CORRIDOR
C1E24
CONSULT
RM.
F128
CONSULT
F123
CONSULT
RM.
F124
CONSULT
RM.
F127
BLDG. MGT.
LKR. / LNGE.
/ TLT.
F125
BLDG. MGT.
LKR. / LNGE.
/ TLT.
F126
ST. TLT.
F122
ST. TLT.
F129
TRAVEL
E140
TELEHEALTH
IMAGING
E143
TRANSCRIPTION
OFFICE
E144
R.O.I E145
R.O.I E146
OFFICE
E148
EYE
SCREENING
E147INFO. MGT.
SVC
E139
F.M.S ENG.
E138
EQ. STG.
E144
F.M.S ENG.
E137
HBA
E102F
ROI LEGAL
E102E
HBA
E102D
HBA
E102C
HBA
E102B
PRE-REG
E102A
CORRIDOR
C1F22CORRIDOR
C1E8
ELEVATOR
LOBBY
C1E9
ELEVATOR
LOBBY
C1E10
CORRIDOR
C1E33
WAITING
AREA
C1E12
WAITING
C1E35
CORRIDOR
C1E12A
CORRIDOR
C1E15
CORRIDOR
F1F23
CORRIDOR
C1F18
CORRIDOR
C1F17
CORRIDOR
C1F16
CORRIDOR
C1F19
CORRIDOR
C1F12
CORRIDOR
C1F10
UNKNOWN
C1F13
ALCOVE
C1F11
CORRIDOR
C1F14
N. STN.
F131
M.A.S.
F130
CORRIDOR
C1F15
PROVIDER
WK. RM.
F121
ALCOVE
C1F6 ALCOVE
C1F8
CORRIDOR
C1F7
CORRIDOR
C1F5
CORRIDOR
C1F9
CORRIDOR
C1F7
N. STN.
CORRIDOR
C1F2
WAITING
C1F20
WAITING
F103
CORRIDOR
C1F1
CORRIDOR
C1F21
LOBBY
F406
PHARM.
ENTRY
E100
CORRIDOR
F104
M.A.S.
F105A
ALCOVE
C1F7
KIOSK
E101
OFFICE
F163B
CORRIDOR
C1E18
CORRIDOR
C1E12
CORRIDOR
C1E13
ELEV.
#11
ELEV.
#10
ELEV.
#9
E129B
E129A
(E)1" HWS
(E)1" HWR
(E)1 1/2" HWR
(E)1 1/2" HWS
(E)2" HWR
(E)2" HWS
(E)1" HWR
(E)1" HWS
(E)1" HWR
(E)1" HWS
1-TU-ACAAHU1,2,3-8
1-TU-ACAAHU1,2,3-10
1-TU-ACAAHU1,2,3-14
1-TU-ACAAHU1,2,3-11
1-TU-ACAAHU1,2,3-7
1-TU-ACAAHU1,2,3-6
1-TU-ACAAHU1,2,3-12
1-TU-ACAAHU1,2,3-4
1-TU-ACAAHU1,2,3-13
1-TU-ACAAHU1,2,3-2
1-TU-ACAAHU1,2,3-16
1-TU-ACAAHU1,2,3-17
1-TU-ACAAHU1,2,3-21
1-TU-ACAAHU1,2,3-1
1-TU-ACAAHU1,2,3-22
(E)RB 1-4
(E)RB 1-3
(E)VAV E-6
(E)VAV E-4
(E)VAV E-5
(E)RB 1-13
(E)RB 1-14
(E)1-T2.17
(E)1-T2.18
(E)1-T2.16
(E)FTU 1-1
(E)RB 1-12
(E)RB 1-11
(E)RB 1-10
(E)RB 1-9
(E)RB 1-8
(E)RB 1-7
(E)RB 1-6
(E)RB 1-5
(E)1-T1.14
(E)1-T1.13
(E)1-T1.12
(E)1-T1.11
(E)1-T1.15
(E)1-T1.16
(E)1-T1.17
(E)1-T1.18
(E)RB 1-15
(E)RB 1-16
(E)VAV E-9
(E)VAV E-8
(E)VAV E-11(E)VAV E-10
(E)VAV E-13
(E)VAV E-14
(E)VAV E-3
(E)VAV E-1
(E)VAV E-7
(E)FTU 1-2
(E)VAV E-2
(E)RB 1-1
(E)RB 1-2
(E)1 1/2"
(E)1 1/2" HWR
(E)1 1/2" HWS
(E)1"
(E)2"(E)2"
(E)2" HWR
(E)2" HWS
(E)1"(E)1"
(E)3/4"
(E)1"
(E)1"
(E)1"
(E)1 1/4"
(E)1 1/4" (E)1"(E)1"
(E)1 1/4"
(E)3/4"
(E)1"
(E)1"
1-TU-ACAAHU1,2,3-18
1-TU-ACAAHU1,2,3-20
1-TU-ACAAHU1,2,3-31-TU-ACAAHU1,2,3-5
1" HWR
1" HWS
1-TU-ACAAHU1,2,3-9
1-TU-ACAAHU1,2,3-15
(E)5" HWS &
HWR UP & DN
(E)1" HWS
(E)1" HWR
(E)1" HWS
(E)1" HWR
(E)1 1/2" HWS
(E)1 1/2" HWR
1" HWS
1" HWR
1" HWS
1" HWR
(E)1" HWS
(E)1" HWR
1 1/4" HWR
1 1/4" HWS
2 1/2" HWR
2 1/2" HWS
2 1/2" HWS
2 1/2" HWR
2" HWS
2" HWR
1" HWS
1" HWR
1 1/4" HWR
1 1/4" HWS
1 1/4" HWR
1 1/4" HWS
1" HWR
1" HWS
1" HWR
1" HWS
1"
3/4"
(E)RB 1-1
(E)RB
1-3
(E)RB
1-4
(E)RB 1-2
(E)RB 1-15
1-TU-ACAAHU1,2,3-20
1-TU-ACAAHU1,2,3-8
1-TU-ACAAHU1,2,3-10 1-TU-ACAAHU1,2,3-14
1-TU-ACAAHU1,2,3-11
1-TU-ACAAHU1,2,3-6
1-TU-ACAAHU1,2,3-12
1-TU-ACAAHU1,2,3-4
1-TU-ACAAHU1,2,3-16
1-TU-ACAAHU1,2,3-17
1-TU-ACAAHU1,2,3-21
1-TU-ACAAHU1,2,3-18
(E)RB 1-6
(E)RB 1-5
(E)RB 1-7
(E)RB 1-8
1-TU-ACAAHU1,2,3-11-TU-ACAAHU1,2,3-2
(E)RB 1-10
(E)RB 1-9
2 3 4 5 5.6 6 6.3 7 8 9 10 10.6 11 11.5
H
G
F
B
C
D.1
D
E.1
E
1-TU-ACAAHU1,2,3-9
1-TU-ACAAHU1,2,3-15
1-TU-ACAAHU1,2,3-19
1-TU-ACAAHU1,2,3-19
(E)FTU
1-2
(E)RB 1-12
(E)VAV E-1
(E)VAV E-2
(E)VAV E-4
(E)VAV E-3
(E)VAV E-6
(E)VAV E-7
(E)VAV E-8
(E)VAV E-9
(E)VAV E-10
(E)VAV E-11
(E)VAV E-13
(E)VAV E-14
1-TU-ACAAHU4-1
1-TU-ACAAHU1,2,3-13
1-TU-ACAAHU1,2,3-22
1-TU-ACAAHU1,2,3-5
1-TU-ACAAHU1,2,3-3
1-TU-ACAAHU4-1
3"
1"
(E)CUH-2
(E)CUH-1
(E)HWS &
HWR UP
RE
G
IS
TE
RE
DPROFESSIONALENG
IN
EERER
IC
M.DeSPLINTER
M
ECHANICA
L
S
TATE OF CALIFORNIA
38688 Exp. 12-31-25
SIGNED: 06/23/25
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
CORRECT REUSABLE
MEDICAL EQUIP STORAGE
589A4-24-101
800 HOSPITAL DR, COLUMBIA, MO
Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015
Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383
Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086
(412) 212-7515
STAMP
07/25/2025
FIRST FLOOR KEYPLAN
E & F
SHIPPING
WAREHOUSE
OR ADDITION
NORTH
B A
ACA BUILDING
AREAS
AREA AREA
G
AREA
C & D
AREAS
BUILDING 1
100% FINAL BID
DOCUMENTS
A u to d e s k D o c s /1
A
-2
-1
C o rr e c t R e u s a b le
M e d ic a l E q u ip m e n t S to ra g e /2
M
E P
T
.0
C o lu m b ia
M
O V
A M
C R
M E
S to ra g e
A C
A H
V A
C U p g ra d e s .r v t
-0 -2
:4
:0
P
M
MP202
EMD BST
PIPING - ENLARGED FIRST FLOOR PLAN - AREA
E & F - REMODEL
N
1/8" = 1'-0"1
PIPING - ENLARGED FIRST FLOOR PLAN - AREA E & F - REMODEL
KEYNOTES - MP202
NUMBER TEXT
EXTEND NEW HWS/R PIPING TO NEW TERMINAL UNITS AS SHOWN. PROVIDE
ISOLATION VALVES ON NEW PIPES AT MAIN TAPS
2 RECONNECT HWS/R PIPING TO NEW TERMINAL UNIT AS SHOWN.
1 1
Mark Revisions: Date:
1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES 07/29/2025
T
T T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T T
T
T
T
T
T
TT
T
T
T
T
TT
T
T
T
T T
T
T
T
T
T
T
T T
T
T
T
T T
T
T
T
T
T
T
T
PROCEDURE
ROOM
F210
PROCEDURE
ROOM
F211
TLT.
F211A
PROCEDURE
ROOM
F212
SECTION
CHIEF
F214
OFFICE
PHYSICIAN
F215
OFFICE
PHYSICIAN
F216 OFFICE PFT
F217
EXAM 5
F235
CLEAN
STORAGE
F236
EXAM
F237
EXAM
F239
EXAM
F240
EXAM 15
F267
EXAM 16
F266
EXAM 17
F265
STAIR #10
F200
TLT.
F210A
PROCEDURE
ROOM
F208
BLOOD GAS
ANALYSIS
F206B
SURG.
SUPPLIES
F206A
PULMONARY
FUNCTION
LAB
F206
OFFICE
F206C
OFFICE
F206D
CONSULT
RM.
F205
JAN.
F203
RECEPT.
F204
PAT.
RECOVERY
F213
CHANGING
F213B
CLEAN
SCOPE
STORAGE
F209A
SCOPE
DECONTAMINATION
ROOM
F209
TLT.
F213A
STORAGE
SUPPLIES
F207
VASCULAR
LAB
F222
ST. WK.
F221
CONSULT /
VIEW RM.
F220
EXAM
F226
TLT.
F222A
EXAM
F225
CAST
F227
MICROSCOPE
ROOM
F232
PROCEDURE
& EXAM 1
F231
EXAM 5
F234
CHEMO.
F219
SOILED
UTIL.
F233
TLT.
F238
EXAM
F242
CLEAN
DISPATCH
F257
EXAM 18
F256
PHYS.
OFFICE
F230
EXAM 16
F245
EXAM 15
F246
EXAM 13
F247
EXAM 12
F244
EXAM 11
F243
EXAM 10
F241
EXAM 10
F273
EXAM 11
F272
EXAM 12
F271
EXAM 13
F270
EXAM 14
F269
WAITING
F268
NURSE
F264
WAITING
F263
EXAM 18
F262
EXAM 19
F261
EXAM 20
F260
EXAM 21
F259
EXAM 22
F258
ELEC.
CLOSET
F252 INTENR /
RES.
SWAMP
E215
WAITING
DILATION
F257
E.N.T. RES.
E235
E.N.T. EXAM
E234
E.N.T. EXAM
E233
E.N.T. EXAM
E232
E.N.T. EXAM
E230
TLT.
E229
TLT.
E227
EYE EXAM
E248 VISUAL
FIELDS
E250
EYE EXAM
E245
LASER
E244
TLT.
E236
TLT.
E237
E.N.T.
OFFICE
E239
OFFICE
E240
OFFICE
E241
EYE EXAM
E242
EYE EXAM
E243
EYE EXAM
E249
EYE EXAM
E251
DISPENSING
& FITTING
E252
ELEC.
CLOSET
E201
ELECTRICAL
E202
TELE / DATA
E203
OFFICE
E204A
EXAM /
OFFICE
E221EXAM
E222
EXAM
E223
ATTENDING
OFFICE /
EXAM
E225
EXAM
E226
JAN.
E205
EXAM
E214
CLEAN UTIL.
E212
VISUAL
FIELDS
E211
EXAM
E218
EXAM
E217
ROOM
F256
ROOM
E216WK. RM.
E255
CLEAN
STORAGE
E254
DIRTY
E253
REFRAC.
E210
TLT.
F253
OFFICE
F255
EXAM 14
F248
EXAM 17
F249OFFICE
F251
ST. TLT.
F250
N. STN.
F229
ELEV.
LOBBY
C3E10
FAM.
COUNSELING
E209
TLT.
E208
TLT.
E207
CORRIDOR
C2E3
EQUIP.
E205A
ADMIT / WK.
RM.
E224A
CORRIDOR
C2E1
CORRIDOR
C2F24
CORRIDOR
C2F23
CORRIDOR
C2F22
CORRIDOR
C2F21
CORRIDOR
C2F20
CORRIDOR
C2F1
CORRIDOR
C2E16
CORRIDOR
C2E18
TLT.
F223
TLT.
F224 CORRIDOR
C2F19
RECEPT.
F228
CORRIDOR
C2F18
CORRIDOR
C2F16
ALCOVE
C2F17
CORRIDOR
C2F13
CORRIDOR
C2F14
CORRIDOR
C2F15
CORRIDOR
C2F12
RECEPT.
F218
CORRIDOR
C2F11
CORRIDOR
C2F5
ALCOVE
C2F3
CORRIDOR
C2F2B
CORRIDOR
C2F2
WAITING
AREA
C2F6
WAITING
AREA
C2F8
ELEC.
CLOSET
F202
SIGNAL
F201
CORRIDOR
C2E7
STAIR #11
F274
ALCOVE
C2E13
PROCS.
EXAM
E213 EXAM
E219
CORRIDOR
C2E2CORRIDOR
C2E17
CLEAN
DISPATCH
E238
PROC. RM.
E246
CASTING
ROOM
E247
E.N.T. EXAM
E231
RECEP.
E228
STORAGE
E203A
OFFICE
E204
HALL
C2E4
EXAM
E220
WAITING
C2E9
CORRIDOR
C2E12
WAITING
C2E11
CORRIDOR
C2E15
CORRIDOR
C2E6
(E)1 1/4" HWS
(E)1 1/4" HWR
(E)1 1/2" HWR
(E)1 1/2" HWS
(E )2
H
W S
(E )2
H
W R
(E)2" HWR
(E)3/4" HWS
(E)3/4" HWR
(E)2" HWS
(E)2" HWR
(E)HWS
(E)HWR
(E)1/2" HWS
(E )H
W S
(E )H
W R
(E)1 1/4" HWS
(E)1 1/4" HWR
(E)5" HWS & HWR
UP & DN
(E)1/2" HWR
(E)1" HWR
(E)1" HWS
(E)2 1/2" HWS
(E)3" HWS
(E)3" HWR
(E)3" HWS
(E)1 1/2" HWR
(E)1 1/2" HWS
2-TU-ACAAHU1,2,3-22
2-TU-ACAAHU1,2,3-26
2-TU-ACAAHU1,2,3-24
2-TU-ACAAHU1,2,3-25
2-TU-ACAAHU1,2,3-4
2-TU-ACAAHU1,2,3-20
2-TU-ACAAHU1,2,3-21
2-TU-ACAAHU1,2,3-17
2-TU-ACAAHU1,2,3-18
2-TU-ACAAHU1,2,3-5
2-TU-ACAAHU1,2,3-11
2-TU-ACAAHU1,2,3-16
2-TU-ACAAHU1,2,3-15
2-TU-ACAAHU1,2,3-13
2-TU-ACAAHU1,2,3-12
2-TU-ACAAHU1,2,3-2
2-TU-ACAAHU1,2,3-3
2-TU-ACAAHU1,2,3-1
2-TU-ACAAHU1,2,3-29
2-TU-ACAAHU1,2,3-23
2-TU-ACAAHU1,2,3-28
2-TU-ACAAHU1,2,3-32 2-TU-ACAAHU1,2,3-31
2-TU-ACAAHU1,2,3-30
2-TU-ACAAHU1,2,3-27
2-TU-ACAAHU1,2,3-6
2-TU-ACAAHU1,2,3-8 2-TU-ACAAHU1,2,3-7
(E)1-T2.01
2-TU-ACAAHU1,2,3-10
2-TU-ACAAHU1,2,3-9
(E)1-T1.05
(E)1-T1.09
(E)1-T1.08
(E)1-T1.10
(E)1-T1.06
(E)1-T1.07
(E)1-T2.02 (E)1-T2.03
(E)1-T2.04
(E)1-T2.05
(E)1-T2.10
(E)1-T2.11
(E)1-T2.09
(E)1-T2.08
(E)1-T2.07
(E)1-T2.06
(E)1-T2.13 (E)1-T2.12
(E)1-T2.14
(E)RB 2-1(E)FTU 2-9
(E)RB 2-10
(E)RB 2-11(E)RB 2-12(E)RB 2-13(E)RB 2-14
(E)RB 2-15
(E)RB 2-9
(E)RB 2-8
(E)RB 2-16
(E)RB 2-17
(E)RB 2-18
(E)FTU 2-1
(E)RB 2-19
(E)FTU 2-2
(E)FTU 2-5
(E)FTU 2-6
(E)FTU 2-7
(E)RB 2-22
(E)RB 2-2
(E)RB 2-26(E)RB 2-25
(E)RB-2-25A
(E)RB 2-24 (E)RB 2-23
(E)RB 2-21
(E)FTU 2-4
(E)RB 2-20
(E)FTU 2-3
1" HWS
1" HWR
2-TU-ACAAHU1,2,3-19
(E)1 1/4"(E)1 1/4"
(E)1 1/2"
(E)1 1/2"
(E)1"
(E)1 1/4"
(E)1 1/2"
(E)2 1/2" HWR
(E)2 1/2" HWS
(E)2 1/2"
(E)3"
(E)1"
(E)1 1/4"(E)1 1/4" (E)1 1/4" HWS
(E)1 1/4" HWR
(E)1 1/4"
(E)1"
(E)2"
(E)1 1/2" (E)1"
(E)1"
(E)1"
(E)1 1/4"
(E)1 1/4"
(E)2 1/2"
(E)2"
(E)1"
(E)1/2" UP
(E)1/2" UP
(E)3/4" UP
(E)1/2" UP
(E)2" HWS
(E)1-T1.03
(E)1-T1.04
(E)1-T1.01
(E)1-T1.02
2-TU-ACAAHU1,2,3-14
(E)2" HWR
(E)2" HWS
(E)1 1/2" HWR
(E)1 1/2" HWS
(E)3" HWR
(E)3" HWS
(E)1 1/2" HWR
(E)1 1/2" HWS
(E)2" HWR
(E)2" HWS
(E)2" HWR
(E)2" HWS
(E)1" HWR
(E)1" HWS
(E)1 1/4" HWR
(E)1 1/4" HWS
(E)1 1/2" HWS
(E)1 1/2" HWR
1" HWR
(E)3" HWR
(E)3" HWS
1 1/4" HWR
1 1/4" HWS
2 1/2" HWS
2 1/2" HWR
2" HWR
2" HWS
1" HWS
2" HWR
2" HWS
1 1/4" HWS
1 1/4" HWR
(E)1 1/2"
(E)1 1/4"
(E)1" HWS
(E)1" HWR
1" HWS
1" HWR
1"
1" HWR
1" HWS
(E)RB 2-19
(E)FTU 2-2
(E)FTU 2-1
(E)FTU 2-3
(E)FTU 2-4
(E) RB 2-18
(E)RB 2-17
(E)RB 2-13
(E)RB 2-14
(E)RB 2-15
(E)RB 2-8
(E)RB 2-9
(E)RB 2-12
(E)RB 2-11
(E)RB 2-20
(E)RB 2-26
(E)RB 2-2
(E)RB 2-23(E)RB 2-24
(E)RB 2-25
(E)RB
2-16
(E)RB 2-10
(E)FTU 2-6
(E)FTU 2-5
(E)RB 2-22
(E)RB 2-1
(E)RB 2-21
2-TU-ACAAHU1,2,3-19
2-TU-ACAAHU1,2,3-20
2-TU-ACAAHU1,2,3-21
2-TU-ACAAHU1,2,3-17
2-TU-ACAAHU1,2,3-13
2-TU-ACAAHU1,2,3-12
2-TU-ACAAHU1,2,3-3
2-TU-ACAAHU1,2,3-14
2-TU-ACAAHU1,2,3-15
2-TU-ACAAHU1,2,3-16
2-TU-ACAAHU1,2,3-2
2-TU-ACAAHU1,2,3-5
2-TU-ACAAHU1,2,3-25
2-TU-ACAAHU1,2,3-26
2-TU-ACAAHU1,2,3-23
2-TU-ACAAHU1,2,3-24
2-TU-ACAAHU1,2,3-22
2-TU-ACAAHU1,2,3-29
2-TU-ACAAHU1,2,3-28
2-TU-ACAAHU1,2,3-30
2-TU-ACAAHU1,2,3-31
2-TU-ACAAHU1,2,3-8
2-TU-ACAAHU1,2,3-27
2-TU-ACAAHU1,2,3-10
2 3 4 5 5.6 6 6.3 7 8 9 10 10.6 11 11.5
H
G
F
B
C
D.1
D
E.1
E
(E)1 1/2"
2-TU-ACAAHU1,2,3-18
2-TU-ACAAHU1,2,3-32
2-TU-ACAAHU1,2,3-9
2-TU-ACAAHU1,2,3-11
2-TU-ACAAHU1,2,3-6
2-TU-ACAAHU1,2,3-28
(E)FTU 2-9
3/4" HWR
3/4" HWS
2-TU-ACAAHU1,2,3-4
1"
(E)HWS DN
(E)HWR DN
RE
G
IS
TE
RE
DPROFESSIONALENG
IN
EERER
IC
M.DeSPLINTER
M
ECHANICA
L
S
TATE OF CALIFORNIA
38688 Exp. 12-31-25
SIGNED: 06/23/25
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
CORRECT REUSABLE
MEDICAL EQUIP STORAGE
589A4-24-101
800 HOSPITAL DR, COLUMBIA, MO
Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015
Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383
Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086
(412) 212-7515
STAMP
07/25/2025
SECOND FLOOR KEYPLAN
NORTH
E & F
SHIPPING
WAREHOUSE
OR ADDITION B A
ACA BUILDING
A…