Columbia MO VAMC RME Storage and ACA HVAC Upgrades_Electrical.pdf

PDF 900 KB Posted

Attached to
Z2DA--Correct Reusable Medical Equipment Storage PN: 589A4-24-101
Solicitation number
36C25525R0114
Issued by

About this file

These electrical design documents are for the VA Medical Center in Columbia, Missouri, detailing electrical system upgrades for the Reusable Medical Equipment Storage and ACA HVAC systems. The project involves modifications to existing electrical infrastructure, including new electrical connections for air handling units (ACA-AHU-1 through ACA-AHU-4), heating water pumps (ACA-HWP-1 and ACA-HWP-2), and associated control systems. Key electrical work includes installing new breakers in motor control centers (MCC-B3-480VN and MCC-D8-480VQ), extending conduit and conductors, and updating electrical panels and variable frequency drives (VFDs). The design documents specify electrical schedules, single-line diagrams, and detailed connection requirements for new and existing equipment, with careful consideration of phasing and minimal disruption to hospital operations.

View the file

Other files

Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2021 INTERNATIONAL BUILDING CODE (IBC)

2024 NFPA 101 LIFE SAFETY CODE

2022 NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900

2023 NATIONAL ELECTRICAL CODE (NEC) (NFPA 70)

2021 INTERNATIONAL MECHANICAL CODE (IMC)

2021 INTERNATIONAL PLUMBING CODE (IPC)

2015 ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)

ENERGY POLICY ACT OF 2005 (EPACT)

DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL,

COMMERCIAL AND MULTI-FAMILY HIGH-RISERESIDENTIAL BUILDINGS AND NEW LOW-RISE

RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435.

VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1- 2022.

SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15 – 2022.

UNLESS OTHERWISE SPECIFIED, SPECIFIC REFERENCES TO CODES, REGULATIONS, STANDARDS, MANUFACTURERS' INSTRUCTIONS, OR REQUIREMENTS OF REGULATORY AGENCIES, SHALL MEAN

THE LATEST EDITION OF EACH IN EFFECT AT THE DATE OF PROJECT SUBMISSION (U.N.O.)

CODES AND STANDARDS:

ELECTRICAL SHEET INDEX:

1. INSTALLATION SHALL COMPLY WITH ALL APPLICABLE CODES, STANDARDS, AND

MANUFACTURER'S INSTALLATION REQUIREMENTS.

2. REVIEW ALL PROJECT DOCUMENTS INCLUDING SPECS AND DRAWINGS PERTAINING TO ALL

DISCIPLINES PRIOR TO SUBMITTING A BID. SUBMIT PRE-BID REQUEST FOR INFORMATION FOR

ITEMS IN QUESTION AND/OR CONFLICTS FOUND.

3. DRAWINGS SHOW THE DESIGN INTENT DIAGRAMMATICALLY. THEY DO NOT SHOW THE EXACT

UTILITY ROUTING NOR EVERY ELBOW, OFFSET, ETC. WHERE REQUIRED, THE CONTRACTOR

SHALL MAKE ADJUSTMENTS TO THEIR SYSTEMS TO AVOID CONFLICT WITH THE STRUCTURE

AND OTHER DISCIPLINES. THE COST FOR SUCH ADJUSTMENTS SHALL BE INCLUDED IN THE BID.

4. OBTAIN AND PAY FOR ALL PERMITS REQUIRED FOR WORK PERFORMED.

5. OBTAIN UTILITY PURVEYOR REQUIREMENTS PRIOR TO PURCHASING EQUIPMENT OR

PERFORMING WORK.

6. THE G.C. OR C.M. TEAM SHALL LEAD THE SUBCONTRACTORS IN PROVIDING A COORDINATED

SET OF SHOP DRAWINGS. SEE GENERAL REQUIREMENTS SPEC FOR ADDITIONAL

INFORMATION.

7. PROVIDE FIRESTOPPING FOR ALL UTILITY PENETRATIONS THRU FIRE-RATED ASSEMBLIES.

8. COORDINATE FRAMING REQUIREMENTS FOR ACCESS PANELS AND EQUIPMENT/PANEL

SUPPORTS WITH G.C. OR C.M. PRIOR TO SUBMITTING BID.

9. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE CORRECTION OF CONSTRUCTION

DEFICIENCIES LISTED ON THE JOB SITE OBSERVATION REPORT. RETURN THE JOB SITE

OBSERVATION REPORT TO A/E WITH DEFICIENCIES SIGNED OFF. PROVIDE PHOTOGRAPHIC

AND/OR VIDEO EVIDENCE OF CORRECTED DEFICIENCIES IF REQUESTED BY THE ENGINEER.

10. PROVIDE CLOSEOUT DOCUMENTATION UPON COMPLETION OF PROJECT. SEE GENERAL

REQUIREMENTS SPEC FOR ADDITIONAL INFORMATION.

GENERAL NOTES:

ELECTRICAL SYMBOLS:

LINETYPE/SYMBOL DESCRIPTION

ELECTRICAL SYMBOLS:

CONDUIT CONCEALED IN FINISHED AREAS OR

EXPOSED IN UNFINISHED AREAS

JUNCTION BOX - FLUSH CEILING MOUNT/IN CEILING

SPACE

J

ELECTRICAL MOTOR CONTROL CENTER

ELECTRICAL SURFACE MOUNT BRANCH CIRCUIT

PANELBOARD

xxA DISCONNECT SWITCH - UNFUSED TYPE - SEE

DRAWINGS FOR SIZE - (xxA) INDICATES AMPERAGE

VARIABLE FREQUENCY DRIVE (VFD) WITH INTEGRAL

DISCONNECT SWITCH - SEE DRAWINGS FOR VFD SIZE

AND RATINGS

LINETYPE/SYMBOL DESCRIPTION

POINT OF CONNECTION OR DISCONNECTION

KEYNOTE SYMBOL#

DETAIL CALL-OUT SYMBOL

###-# EQUIPMENT TAG

GENERAL LEGEND:

SYMBOL DESCRIPTION

SECTION CUT CALL-OUT SYMBOL

ENLARGED PLAN CALL-OUT SYMBOL

EXISTING TO REMAIN

EXISTING TO BE REMOVED

NEW CONSTRUCTION

(E) EXISTING TO REMAIN

LINETYPE DESCRIPTION

(X) EXISTING TO BE REMOVED

1. ELECTRICAL WORK SHALL BE CONSTRUCTED IN A PROFESSIONAL MANNER. COMPONENTS

SHALL BE CLEANED PRIOR TO OWNER TURNOVER.

2. THE SCHEDULED EQUIPMENT SHALL BE USED AS THE BASIS OF DESIGN. MODEL NUMBERS

ARE PROVIDED FOR REFERENCE ONLY. EQUIPMENT SHALL MEET SPECIFIED PERFORMANCE.

THE CONTRACTOR SHALL IDENTIFY ALL SELECTED OPTIONS IN THE SUBMITTAL.

3. IF A CONTRACTOR PROVIDES EQUIPMENT OTHER THAN THE BASIS OF DESIGN, THAT

CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COSTS INCURRED AS A RESULT. THAT

INCLUDES, BUT IS NOT LIMITED TO, STRUCTURAL MODIFICATIONS FOR INCREASED WEIGHT

AND, ELECTRICAL EQUIPMENT, WIRING, CONDUIT, AND BREAKER CHANGES FOR DIFFERENT

ELECTRICAL REQUIREMENTS.

4. SEE SPEC SECTIONS 26 05 33 AND FOR CONDUIT/RACEWAY SYSTEM INSTALLATION AND

CLEANING REQUIREMENTS.

5. PROVIDE CONDUIT OR RACEWAY EXPANSION JOINT THAT ACCOMMODATES THE BUILDING

MOVEMENT WHERE CONDUIT OR RACEWAY CROSSES BUILDING EXPANSION JOINT.

6. PAINT INTERIOR EXPOSED CONDUIT/RACEWAYS, PULL BOXES, AND ASSOCIATED

HANGERS/SUPPORTS LOCATED IN OCCUPIED SPACES TO MATCH THE SURROUNDING

ARCHITECTURAL COLOR SCHEME. PAINT EXTERIOR CONDUIT/RACEWAYS, PULL BOXES, AND

ASSOCIATED HANGERS/SUPPORTS ADJACENT TO EXTERIOR WALL TO MATCH WALL COLOR.

FINAL COLORS SHALL BE APPROVED BY THE ARCHITECT AND ENGINEER. SEE SPEC SECTION

26 0500 FOR ADDITIONAL REQUIREMENTS.

7. PROVIDE IDENTIFICATION FOR CONDUIT/RACEWAYS, PULL BOXES, AND EQUIPMENT PER

SPEC SECTION 26 0553.

8. CONDUIT/RACEWAY SHALL NOT PASS THRU NOR UNDER DATA ROOMS, ELEVATOR

MACHINE ROOMS, ELEVATOR HOISTWAYS, SKYLIGHTS, AND ROOF ACCESS HATCHES.

9. PULL BOXES SHALL BE ACCESSIBLE. PROVIDE KEYED ACCESS PANELS WHERE PULL BOXES

HAVE BEEN LOCATED IN CONCEALED AREAS. ACCESS PANEL SIZE SHALL BE LARGE ENOUGH

TO ACCESS EACH PULL BOX.

10. ELECTRICAL CONTRACTOR SHALL COORDINATE LOCATION OF LIGHTING FIXTURES AND

LIGHTING DEVICES WITH MECHANICAL AND FIRE PROTECTION, AND FIRE ALARM DEVICES.

11. E.C. SHALL VERIFY U.L. LISTING AND PROCEED WITH FINAL CONNECTION.

12. ELECTRICAL OUTLETS INSTALLED ON OPPOSITE SIDES OF FIRE-RATED ASSEMBLIES SHALL BE

SEPARATED BY 24". OPENINGS SHALL BE FIRESTOPPED WITH THE SPECIFIED MATERIAL.

13. WHERE NEW CIRCUIT BREAKERS ARE TO BE ADDED TO EXISTING ELECTRICAL EQUIPMENT,

THEY SHALL BE OF THE SAME MANUFACTURER AND DESIGN AS THE EXISTING BREAKERS

AND SHALL BE OF THE SIZES INDICATED.

14. INSTALL - TO PLACE IN POSITION AND CONNECT COMPLETE READY FOR USE.

FURNISH - TO PURCHASE/SUPPLY.

PROVIDE - TO FURNISH AND INSTALL.

ELECTRICAL NOTES:

1. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID SUBMISSION TO VERIFY ALL FIELD

CONDITIONS INCLUDING BUT NOT LIMITED TO THE FOLLOWING:

A. LOCATIONS OF EXISTING ELECTRICAL SYSTEMS.

B. LOCATIONS OF ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING,

TECHNOLOGY, FIRE PROTECTION, AND FIRE ALARM SYSTEMS.

C. EXISTING SURFACES WHICH REQUIRE ALTERING.

D. EXISTING MAIN SWITCHGEAR CONDITIONS.

2. NOTIFY OWNER OF REQUIRED SYSTEM SHUTDOWNS AT LEAST TWO WEEKS PRIOR TO

SHUTDOWN. EXACT SHUTDOWN TIME AND PROCEDURE SHALL BE COORDINATED WITH

OWNER AT LEAST 96 HOURS PRIOR TO SHUTDOWN.

3. WHEN ELECTRICAL CONDUIT OR EQUIPMENT ARE NOTATED TO BE PERMANENTLY REMOVED

THEIR ASSOCIATED COMPONENTS SHALL ALSO BE REMOVED INCLUDING HANGERS,

SUPPORTS, AND ACCESSORIES.

4. COORDINATE THE DISCONNECTION AND REMOVAL OF THE POWERED SYSTEMS WITH THE

M.C., P.C., T.C., F.A.C., AND F.P.C. WHEN REMOVING POWERED EQUIPMENT.

5. REPAIR EXISTING FLOORS, WALLS, AND CEILINGS IN ALTERED AREAS TO MATCH EXISTING.

SEE ARCHITECTURAL PLANS FOR FINISH DETAILS IN REMODEL AREAS.

6. E.C. SHALL CONFIRM THAT ONCE POWER IS RESTORED, (E) ELECTRICAL DEVICES

DOWNSTREAM OF REPLACED DEVICES ARE OPERATIONAL WITH ADEQUATE ELECTRICAL

CONTINUITY.

RENOVATION NOTES:

CONTRACTOR ABBREVIATIONS:

ABBREVIATION DESCRIPTION

C.M. CONSTRUCTION MANAGER

E.C. ELECTRICAL CONTRACTOR

F.A.C. FIRE ALARM CONTRACTOR

F.P.C. FIRE PROTECTION CONTRACTOR

G.C. GENERAL CONTRACTOR

M.C. MECHANICAL CONTRACTOR

P.C. PLUMBING CONTRACTOR

T.C. TECHNOLOGY CONTRACTOR

T.C.C. TEMPERATURE CONTROL CONTRACTOR

AFG ABOVE FINISHED GRADE

CM COUNTER MOUNTED

FBO FURNISHED BY OTHERS

FF FINISHED FLOOR

IG ISOLATED GROUND

PED PEDESTAL MOUNTED

UNO UNLESS NOTED OTHERWISE

+XX DIMENSIONED HEIGHT ABOVE FINISHED FLOOR

-XX DIMENSIONED HEIGHT BELOW FINISHED FLOOR

1P ONE POLE

1W ONE WIRE

2P TWO POLE

2W TWO WIRE

3P THREE POLE

3W THREE WIRE

AC ALTERNATING CURRENT

ADJ ADJUSTABLE

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT

AFCI AVAILABLE FAULT CURRENT INTERRUPTER

AHU AIR-HANDLING UNIT

AIC AMPERES INTERRUPTING CAPACITY

AT AMP TRIP

C.O. CONDUIT ONLY

CB CIRCUIT BREAKER

CKT CIRCUIT

D DEDICATED DEVICE ON INDIVIDUAL BRANCH CIRCUIT. CIRCUIT CAN

BE COMBINED WITH OTHER CIRCUITS FOR HOMERUNNING TO

PANEL.

DISC DISCONNECT

DN DOWN

EM EQUIPMENT POWERED WITH EMERGENCY SOURCE-INTERNAL OR

EXTERNAL, UNLESS NOTED OTHERWISE

FD FIRE DAMPER

FLA FULL LOAD AMPS

FSD FIRE SMOKE DAMPER

FT, ' FOOT OR FEET

GFCI GROUND FAULT CIRCUIT INTERRUPTER

IN., " INCH OR INCHES

INV EMERGENCY INVERTER

J-BOX JUNCTION BOX

KCMIL THOUSAND CIRCULAR MILLS

KVA KILOVOLT AMPERE

KW KILOWATT

LTG LIGHTING

MAX MAXIMUM

MCB MAIN CIRCUIT BREAKER

MIN MINIMUM

MLO MAIN LUGS ONLY

N/A NOT APPLICABLE

NIC NOT IN CONTRACT

NO., # NUMBER

NTS NOT TO SCALE

RTU ROOFTOP UNIT

SD SMOKE DAMPER

SPEC SPECIFICATION

TYP TYPICAL

U.C. UNDERGROUND CONDUIT

UTR UP THRU ROOF

WP WEATHERPROOF

ELECTRICAL ABBREVIATIONS:

ABBREVIATION DESCRIPTION

NOTES:

1. NOT ALL ABBREVIATIONS MAY APPLY.

2. ELECTRICAL SCHEDULES CONTAIN EQUIPMENT TAG ABBREVIATIONS THAT ARE HEREBY

INCORPORATED INTO THE ABBREVIATION LIST.

3. SEE OTHER DISCIPLINE DRAWINGS WITHIN THE CONSTRUCTION DOCUMENTS FOR

ABBREVIATIONS NOT DEFINED ABOVE OR IN ELECTRICAL SCHEDULES.

1. THE PROJECT WILL BE CONSTRUCTED IN MULTIPLE PHASES. SEE ARCHITECTURAL &

PHASING DOCUMENTS FOR PHASING REQUIREMENTS.

2. CONTRACTOR SHALL CONFIRM WORK BEING PERFORMED IN ACTIVE PHASE DOES NOT

ADVERSELY AFFECT NORMAL OPERATIONS IN OTHER OCCUPIED SPACES.

3. PROVIDE TEMPORARY CONNECTIONS AS REQUIRED TO MAINTAIN SERVICE TO OCCUPIED

SPACES.

4. DESIGN DRAWINGS DO NOT INDICATE EVERY REQUIRED STEP TO ACHIEVE PHASED

CONSTRUCTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DEVELOP A CONSTRUCTION

PLAN TO INSTALL THE DESIGN WITHIN THE PHASING CONSTRAINTS.

5. HVAC SYSTEMS (EXCEPT ACA-AHU-1,-2,-3,-4) IMPACTED BY THE PROJECT SCOPE SHALL NOT

BE OFFLINE FOR LONGER THAN A 6-HOUR SPAN. PROVIDE TEMPORARY PORTABLE

HEATERS/COOLERS FOR SPACES IMPACTED BY HVAC SYSTEM OUTAGES TO MAINTAIN

ADEQUATE OCCUPIED SPACE CONDITIONS DURING CONSTRUCTION.

6. CONSTRUCTION ACTIVITIES IN OCCUPIED SPACES SHALL BE PERFORMED DURING

UNOCCUPIED HOURS (NIGHTS, WEEKENDS, AND/OR HOLIDAYS). RESTORE SPACES TO

ORIGINAL CONDITIONS BEFORE HOSPITAL STAFF AND/OR PATIENTS ARRIVE.

7. CONSTRUCTION ACTIVITIES IN UNOCCUPIED SPACES THAT HAVE ADVERSE EFFECTS

(EXCESSIVE NOISE, EXCESSIVE VIBRATION, ETC.) SHALL BE PERFORMED DURING

UNOCCUPIED HOURS (NIGHTS, WEEKENDS, AND/OR HOLIDAYS).

8. COORDINATE SCHEDULE WITH THE VA TO DETERMINE EXACT ALLOWABLE TIMES OF

CONSTRUCTION ACTIVITIES IN EACH PROJECT AREA.

PHASING NOTES:

TROFFER - TYP.

DOWNLIGHT - TYP.

LINEAR STRIP - TYP.

LINE TYPE /SYMBOL DESCRIPTION

1-HOUR FIRE BARRIER

2-HOUR FIRE BARRIER

1-HOUR SMOKE BARRIER

1-HOUR HAZARDOUS AREA FIRE BARRIER

FIRE-RATED ASSEMBLY LEGEND:

S S S S

HZ HZ HZ HZ

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CORRECT REUSABLE

MEDICAL EQUIP STORAGE

589A4-24-101

800 HOSPITAL DR, COLUMBIA, MO

Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015

Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383

Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086

(412) 212-7515

STAMP

07/25/2025

100% FINAL BID

DOCUMENTS

A u to d e s k D o c s /1

A

-2

-1

C o rr e c t R e u s a b le

M e d ic a l E q u ip m e n t S to ra g e /2

M

E P

T

.0

C o lu m b ia

M

O V

A M

C R

M E

S to ra g e

A C

A H

V A

C U p g ra d e s .r v t

/2

/2

:1

:0

A

M

E001

JCL ABH

ELECTRICAL COVER SHEET

Sheet

Number Sheet Name

E001 ELECTRICAL COVER SHEET

E100 ELECTRICAL - BASEMENT FLOOR PLAN

E101 ELECTRICAL - FIRST FLOOR PLAN

E102 ELECTRICAL - SECOND FLOOR PLAN

E103 ELECTRICAL - THIRD FLOOR PLAN

E104 ELECTRICAL - SIXTH FLOOR PLAN

ED201 ELECTRICAL - ENLARGED BASEMENT FLOOR PLAN - AREA E & F - DEMOLITION

ED202 ELECTRICAL - ENLARGED BASEMENT FLOOR PLAN ROOMS - DEMOLITION

E201 ELECTRICAL - ENLARGED BASEMENT FLOOR PLAN - AREA E & F - REMODEL

E202 ELECTRICAL - ENLARGED FIRST FLOOR PLAN - AREA E & F - REMODEL

E203 ELECTRICAL - ENLARGED SECOND FLOOR PLAN - AREA E & F - REMODEL

E204 ELECTRICAL - ENLARGED FIRST FLOOR PLAN - PATHOLOGY - REMODEL

E205 ELECTRICAL - ENLARGED BASEMENT FLOOR PLAN ROOMS - REMODEL

E206 ELECTRICAL - ENLARGED BASEMENT FLOOR PLAN ROOMS - REMODEL

E207 ELECTRICAL - ENLARGED FIRST FLOOR PLAN ROOMS - REMODEL

E208 ELECTRICAL - ENLARGED FIRST FLOOR PLAN ROOMS - REMODEL

E209 ELECTRICAL - ENLARGED THIRD FLOOR PLAN ROOMS - REMODEL

E210 ELECTRICAL - PENTHOUSE FLOOR PLAN

E401 ELECTRICAL DETAILS

E501 ELECTRICAL SCHEDULES

E502 ELECTRICAL SCHEDULES

Mark Revisions: Date:

1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES

RE

G

IS

TE

RE

DPROFESSIONALENG

IN

EER

JA

E

M

.SC LESSARD

E

LEC T RICA

L

S

TATE OF CALIFORNIA

E 24240 Exp. 09-30-26

SIGNED: 06/23/25

07/29/207/25

J

J

J

J

J J

J

J

J

J

J

J

J

J

J

J

J J J

J

J

EQUIP

ROOM

F023

RADIONUCLIDE

GENERATOR

LAB

F022

HOT CELL

F020

MRI ROOM

F019

MRI

CONTROL

F017

IN VITRO

CELL TEST

LAB

F016

RADIO

PHARM./PHARKMAKINETIC

LAB

F014

VA-BIC

PET/SPECT/CT/MOLECULAR

IMAGING

SUITE

F012

JANITOR

F036

SHARED

OFFICE

F011

OFFICE

F009

OFFICE

F008

OFFICE

F007

WORK

ROOM

F006

OFFICE

F003

WORK

ROOM

F002

OFFICE

F033

MICRO

DARK ROOM

F032

CAMERA

DARK ROOM

F031

REFRIGERATOR

F030

FREEZER

F030A

TISSUE

CULTURE

(HOT)

F029A

TISSUE

PREP (HOT)

F029

TISSUE

PREP

(COLD)

F028

TISSUE

CULTURE

(COLD)

F028A

OFFICE

F025

VESTIBULE

F025A

WORK

ROOM

F026

OFFICE

F034

VESTIBULE

F034A

IMMUNOLOGY

LAB

F027

CYLINDER

STORAGE

F027A

GLASS

WASH

F024

CONFERENCE

ROOM

F001A

RECEPTIONIST

F001

VESTIBULE

F002A

GEN.

RADIOCHEMISTRY/REPTIDE

RADIOLABELING

F004

ELEC.

CLOSET

F001B

COLD LAB

F005

HOT LAB 1

F021

RADIOPHARMACEUTICAL

R&D F018

RADIOPHARMACEUTICAL

R&D F010

VESTIBULE

F009A

ELEC.

CLOSET

F035

F.A.

CONTROL

PANEL

F035A

CORRIDOR

CBF2

CORRIDOR

CBF4

Room

VESTIBULE

F023A CYLINDER

STORAGE

F015

STORAGE

F013

CORRIDOR

CBF5

STORAGE

E001G

JANITOR

E012

PHARMACY

E001

STAGING

ROOM

E001D

STERILE IV

PREP.

E001B

NARCOTIC

VAULT

E001A

OFFICE

E002A CONFERENCE

ROOM

E002E

ROOM

E002F

PROGRAM

SUPPORT

R&D E002C

A.O. RAD

E002D

RESEARCH

SERVICE

CORRIDOR

E002

ROOM

E001H

ROOM

E001J

ROOM

E001F

WORK

ROOM

E002B

OFFICE

E002H

R.C.O. R&D E002I

CLINICAL

RESEARCH

E002J

M.F.M.R.

EXECUTIVE

DIRECTOR

E002K

ROOM

E001E

ELEV.

MACHINE

ROOM

E004

STORAGE

E005

ELEV.

MACHINE

ROOM

E007

TELE./DATA

E006

MEN TOILET

E008

WOMAN

TOILET

E010

ELEC. ROOM

E009

CORRIDOR

CBE5

MECH

ROOM

E003

ELEC ROOM

E003A

STAIR #11

#11

CORRIDOR

CBF1

CORRIDOR

CBE2

CORRIDOR

CBE1

CORRIDOR

CBE3

Room E001K

Room E001L

Room E001C

(E) MCC-D8-480VQ

(E) MCC-B3-480VN

ACA-AHU-1ACA-AHU-2ACA-AHU-3

ACA-AHU-4

ACA-HWP-1ACA-HWP-2

MCC-B3-480VN-12

MCC-B3-480VN-6

MCC-B3-480VN-1

MCC-D8-480VQ-1

MCC-B3-480VN-10

MCC-D8-480VQ-16

VFD-SF-1

VFD-RF-1

VFD-SF-2

VFDR-RF-2

VFD-SF-3

VFD-RF-3

(E) PPB-B3-120VN

PPB-B3-120VN-33

VFD-SF-4

VFD-RF-4

ACA-USG-1 4

ACA-HX-1

PPB-B3-120VN-37

2 2 2

ACA-HX-2

PPB-B3-120VN-37 6

(E) LIGHT (TYP)

(E) LIGHT (TYP)

(E) LIGHT (TYP)

(E) LIGHT (TYP)

MCC-D8-480VQ-2

MCC-B3-480VN-2

MCC-B3-480VN-7

MCC-B3-480VN-13

2 3 1 4 5 5.6 6 6.3 7 8 9 10 10.6 11 11.5

H

G

F

B

C

D.1

D

E.1

E

A

WS-1

(E) LIGHT (TYP)

9 10

ACA-AHU-1,2,3 TCP

(E)ACA-AHU-4,5

TCP

11 12

11 12

PPB-B3-120VN-39

VFDR-RF-3

VFDR-SF-3

VFDR-RF-1

VFDR-SF-1VFDR-SF-2

VFDR-RF-4

VFDR-SF-4

(E) PANEL 'PPB-D8-120VE'

PPB-D8-120VE-21

PPB-B3-120VN-40

PPB-B3-120VN-38

PPB-B3-120VN-36

VFD-RF-2

(E) LVB-B3-277VN 15

ACA-AHU4-P-1

MCC-D8-480VQ-15

FDS-30

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CORRECT REUSABLE

MEDICAL EQUIP STORAGE

589A4-24-101

800 HOSPITAL DR, COLUMBIA, MO

Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015

Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383

Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086

(412) 212-7515

STAMP

07/25/2025

BASEMENT KEYPLAN

NORTH

E & F

SHIPPING

WAREHOUSE

OR ADDITION B A

ACA BUILDING

AREAS

AREA AREA

G

AREA

C & D

AREAS

BUILDING 1

100% FINAL BID

DOCUMENTS

A u to d e s k D o c s /1

A

-2

-1

C o rr e c t R e u s a b le

M e d ic a l E q u ip m e n t S to ra g e /2

M

E P

T

.0

C o lu m b ia

M

O V

A M

C R

M E

S to ra g e

A C

A H

V A

C U p g ra d e s .r v t

/2

/2

:0

:4

A

M

E201

JCL ABH

ELECTRICAL - ENLARGED BASEMENT FLOOR

PLAN - AREA E & F - REMODEL

N

1/8" = 1'-0"1

ELECTRICAL - ENLARGED BASEMENT FLOOR PLAN - AREA E & F - REMODEL

KEYNOTES - E201

NUMBER TEXT

PROVIDE POINT OF CONNECTION TO NEW AIR HANDLING UNIT (AHU) AT THIS

LOCATION. SEE E501 FOR CIRCUITING. PROVIDE ALL FIELD WIRING BETWEEN

VARIOUS COMPONENTS (SENSORS, FAN MOTORS, CONTROLLERS, ETC) WITHIN

AHU'S AS REQUIRED TO PROVIDE A COMPLETE AND FUNCTIONAL SYSTEM.

CLOSELY COORDINATE WITH MECHANICAL EQUIPMENT INSTALLER.

VARIABLE FREQUENCY DRIVE (VFD) FURNISHED BY MANUFACTURER, INSTALLED

BY CONTRACTOR.

PROVIDE POINT OF CONNECTION TO NEW AIR HANDLING UNIT (AHU). SEE SHEET

E501 FOR CIRCUITING.

PROVIDE POINT OF CONNECTION TO NEW HEATING WATER PUMP (HWP). SEE

SHEET E501 FOR CIRCUITING. PROVIDE VARIABLE FREQUENCY DRIVE (VFD). SEE

PROJECT SPECIFICATION SECTION 262911 FOR ADDITIONAL REQUIREMENTS.

PROVIDE POINT OF CONNECTION TO CONTROL PANEL FOR NEW STEAM

GENERATOR (ACA-USG-1).

PULL AND EXTEND CONDUIT AND CONDUCTORS PROTECTED IN-PLACE TO FEED

NEW CONTROL PANELS (ACA-HX-1,2).

PULL AND EXTEND CONDUIT AND CONDUCTORS PROTECTED IN-PLACE TO FEED

NEW WATER SOFTENER (WS-1).

PULL AND EXTEND CONDUIT AND CONDUCTORS PROTECTED IN-PLACE TO FEED

NEW CONTROL PANEL.

DEDUCT #1: IF ACCEPTED, EXISTING POWER AND VFDS SERVING ACA-AHU-4

SHALL REMAIN.

DEDUCT #2: IF ACCEPTED, EXISTING POWER AND VFDS SERVING ACA-AHU-3 AND

ACA-AHU-4 SHALL REMAIN.

DEDUCT #1: IF ACCEPTED, EXISTING ASSOCIATED CONTROL WIRING TO

ACA-AHU-4 SHALL REMAIN.

DEDUCT #2: IF ACCEPTED, EXISTING CONTROL PANEL AND WIRING TO

ACA-AHU-3 SHALL REMAIN. IN ADDITION, EXISTING ASSOCIATED CONTROL

WIRING TO ACA-AHU-4 SHALL REMAIN.

PROVIDE NEW FEEDER BREAKERS WITHIN MCC FOR ACA-AHU-1, ACA-AHU-2, AND

ACA-AHU-3 SUPPLY AND RETURN FANS, AND ACA-HWP-1. SEE SHEET E501 FOR

ADDITIONAL INFORMATION.

PROVIDE NEW FEEDER BREAKERS WITHIN MCC FOR ACA-AHU-4 SUPPLY AND

RETURN FANS, AND ACA-HWP-2. SEE SHEET E501 FOR ADDITIONAL

INFORMATION.

PROVIDE NEW FEEDER CONDUCTORS BETWEEN SWITCHBOARD LVB-B3-277VN

FEEDER BREAKER TO MCC-B3-480VN. SEE PARTIAL ONE-LINE DIAGRAM ON SHEET

E502 FOR QUANTITY AND SIZING. RE-USE EXISTING CONDUIT PATHWAY (2x2")

BETWEEN SWITCHBOARD AND MCC. TERMINATE NEW CONDUCTORS TO

EXISTING FEEDER BREAKER AND AJUST LONG-TIME TRIP SETTING TO 500A.

PROVIDE POINT OF CONNECTION AND FUSED DISCONNECT SWITCH (FUSED AT

6A) TO NEW IN-LINE PUMP (ACA-AHU4-P-1).

17 DEDUCT #1 & #2: IF ACCEPTED, NEW IN-LINE PUMP SHALL NOT BE INSTALLED.

REMOVE AND REINSTALL LIGHT FIXTURES, AS NEEDED, TO ACCOMMODATE

MECHANICAL SCOPE OF WORK.

NUMBER TEXT

GENERAL NOTES - E201

Mark Revisions: Date:

1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES 07/29/

RE

G

IS

TE

RE

DPROFESSIONALENG

IN

EER

JA

E

M

.SC LESSARD

E

LEC T RICA

L

S

TATE OF CALIFORNIA

E 24240 Exp. 09-30-26

207/25

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CORRECT REUSABLE

MEDICAL EQUIP STORAGE

589A4-24-101

800 HOSPITAL DR, COLUMBIA, MO

Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015

Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383

Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086

(412) 212-7515

STAMP

07/25/2025

100% FINAL BID

DOCUMENTS

A u to d e s k D o c s /1

A

-2

-1

C o rr e c t R e u s a b le

M e d ic a l E q u ip m e n t S to ra g e /2

M

E P

T

.0

C o lu m b ia

M

O V

A M

C R

M E

S to ra g e

A C

A H

V A

C U p g ra d e s .r v t

/2

/2

:1

:0

A

M

E501

JCL ABH

ELECTRICAL SCHEDULES

Notes:

Total Est. Demand Current: 469 A

Total Conn. Current: 469 A

Total Est. Demand: 390086 VA

Mechanical Equipment 367638 VA 100.00% 367638 VA Total Conn. Load: 390086 VA

Power 22447 VA 100.00% 22447 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 469 A

Total Conn. Load: 390086 VA

16 (E) MDP4-D2-277VN 3 400 A 250 A 0 VA 0 VA 0 VA

15 (E) SIZE 1 SPARE 3 100 A 20 A 0 VA 0 VA 0 VA

14 (E) VU-1 3 100 A 20 A 0 VA 0 VA 0 VA

13 (N) ACA-AHU-3 (RF-3) 3 100 A 70 A 14411 VA 14411 VA 14411 VA

12 (N) ACA-AHU-3 (SF-3) 3 400 A 120 A 26438 VA 26438 VA 26438 VA

11 (E) HRP-1 3 100 A 20 A 0 VA 0 VA 0 VA

10 (N) ACA-HWP-1 3 100 A 35 A 7482 VA 7482 VA 7482 VA

9 (E) EF-5 3 100 A 20 A 0 VA 0 VA 0 VA

8 (E) EF-4 3 100 A 20 A 0 VA 0 VA 0 VA

7 (N) ACA-AHU-2 (SF-2) 3 400 A 120 A 26438 VA 26438 VA 26438 VA

6 (N) ACA-AHU-2 (RF-2) 3 100 A 70 A 14411 VA 14411 VA 14411 VA

5 (E) SPACE 3 -- -- -- -- --

4 (E) EF-3 3 100 A 20 A 0 VA 0 VA 0 VA

3 (E) EF-1 3 100 A 20 A 0 VA 0 VA 0 VA

2 (N) ACA-AHU-1 (RF-1) 3 100 A 70 A 14411 VA 14411 VA 14411 VA

1 (N) ACA-AHU-1 (SF-1) 3 400 A 120 A 26438 VA 26438 VA 26438 VA

CKT Circuit Description # of Poles Frame Size Trip Rating

A B C

Remarks

NORMAL BRANCH DISTRIBUTION

Notes:

Enclosure: Type 1

Mounting: Surface Wires: 4

Supply From: Phases: 3 Mains Rating: 600 A

Location: E003A Volts: 480/277 Wye A.I.C. Rating: 65kA

(E) Motor Control Center: MCC-B3-480VN

Notes:

Total Est. Demand Current: 60 A

Total Conn. Current: 60 A

Total Est. Demand: 49966 VA

Mechanical Equipment 26604 VA 100.00% 26604 VA Total Conn. Load: 49966 VA

Power 23362 VA 100.00% 23362 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 60 A

Total Conn. Load: 49966 VA

16 (N) ACA-HWP-2 3 100 A 35 A 7482 VA 7482 VA 7482 VA

15 (N) ACA-AHU4-P-1 3 100 A 20 A 305 VA 305 VA 305 VA

14 (E) DSP-1 3 100 A 20 A 0 VA 0 VA 0 VA

13 (E) SPARE 3 100 A 20 A 0 VA 0 VA 0 VA

12 (E) D-12 3 400 A 20 A 0 VA 0 VA 0 VA

11 (E) SPARE 3 100 A 60 A 0 VA 0 VA 0 VA

10 (E) STEAM COND. PUMP 3 100 A 50 A 0 VA 0 VA 0 VA

9 (E) EF-8 3 100 A 20 A 0 VA 0 VA 0 VA

8 (E) EF-7 3 100 A 20 A 0 VA 0 VA 0 VA

7 (E) EF-6 3 100 A 20 A 0 VA 0 VA 0 VA

6 (E) SPARE 3 100 A 100 A 0 VA 0 VA 0 VA

5 (E) MDP4-D2-277VQ 3 400 A 250 A 0 VA 0 VA 0 VA

4 (E) PTS-1 3 100 A 20 A 0 VA 0 VA 0 VA

3 (E) EF-10 3 100 A 20 A 0 VA 0 VA 0 VA

2 (N) ACA-AHU-4 (RF-4) 3 100 A 15 A 2771 VA 2771 VA 2771 VA

1 (N) ACA-AHU-4 (SF-4) 3 100 A 30 A 6097 VA 6097 VA 6097 VA

CKT Circuit Description # of Poles Frame Size Trip Rating

A B C

Remarks

ESSENTIAL SYSTEM DISTRIBUTION - EQUIPMENT BRANCH

Notes:

Enclosure: Type 1

Mounting: Surface Wires: 4

Supply From: Phases: 3 Mains Rating: 600 A

Location: E003A Volts: 480/277 Wye A.I.C. Rating: 65kA

(E) Motor Control Center: MCC-D8-480VQ

KEYNOTES - E501

NUMBER TEXT

PROVIDE NEW 120A AND 70A 3P BREAKER TO FEED NEW AIR HANDLING UNIT

(AHU). MATCH EXISTING TYPE AND AIC RATING. SEE SHEET E201 FOR LOCATION.

PROVIDE NEW 30A AND 15A 3P TO FEED NEW AIR HANDLING UNIT (AHU)

SERVING THE EMERGENCY DEPARTMENT. MATCH EXISTING TYPE AND AIC

RATING. SEE SHEET E201 FOR LOCATION.

PROVIDE NEW 50A 3P BREAKER TO FEED NEW HEATING WATER PUMP (HWP).

MATCH EXISTING TYPE AND AIC RATING. SEE SHEET E201 FOR LOCATION.

4 UTILIZE SPARE BREAKER WITHIN PPB-B3-120VN TO FEED NEW LOAD.

PROVIDE BREAKER WITHIN PPB-B3-120VN TO FEED NEW LOAD. MATCH EXISTING

TYPE AND AIC RATING.

UTILIZE EXISTING BUCKET AFTER REMOVAL OF HWP-3. PROVIDE NEW BREAKER

TO FEED NEW IN-LINE PUMP (ACA-AHU4-P-1).

7 UTILIZE SPARE BREAKER WITHIN PANEL 'LPP-J7-120VN' TO FEED NEW LOAD.

8 UTILIZE SPARE BREAKER WITHIN PANEL 'LPB-DD8.3-120VN' TO FEED NEW LOAD.

PROVIDE NEW BREAKER WITHIN PANEL 'LPB-DD8.3-120VN' TO FEED NEW LOAD.

MATCH EXISTING TYPE AND AIC RATING

Notes:

Total Est. Demand Current: 7 A

Total Conn. Current: 7 A

Total Est. Demand: 2580 VA

Total Conn. Load: 2580 VA

Power 2580 VA 100.00% 2580 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 5 A 12 A 5 A

Total Load: 600 VA 1380 VA 600 VA

41 SPACE -- 1 -- 0 1 20 A (E) IRRIGATION CONTROL PANEL 42

39 (N) WATER SOFTENER (WS-1) 20 A 1 600 600 1 20 A (N) ACA-AHU-3 LTS AND PWR 40

37 (N) ACA-HX-1&2 CONTROL PNL 20 A 1 0 600 1 20 A (N) ACA-AHU-2 LTS AND PWR 38

35 (E) RECPT E002H 20 A 1 0 600 1 20 A (N) ACA-AHU-1 LTS AND PWR 36

33 (N) ACA-USG-1 CONTROL PNL 20 A 1 180 0 1 20 A (E) RECPT RM B-100 34

31 (E) RECPT RM B-101, E002B, E002C, E002I,... 20 A 1 0 0 1 20 A (E) RECPT RM B-100 32

29 (E) RECPT RM B-101, E002, E002C, E002D,... 20 A 1 0 0 1 20 A (E) RECPT RM B-100 30

27 (E) RECPT RM B-101B, E002B 20 A 1 0 -- 1 -- SPACE 28

25 (E) RECPT RM B-101B, E002, E002B 20 A 1 0 -- 1 -- SPACE 26

23 (E) RECPT RM B-101, CB-3, E002B 20 A 1 0 0 1 20 A (E) HOUSE AIR DRYERS 24

21 (E) RECPT RM B-101, E002E 20 A 1 0 0 1 20 A (E) DOOR HOLDERS CB-4, CB-3 22

19 (E) RECPT RM B-101, E002E 20 A 1 0 0 1 20 A (E) RECPT RM B-111 20

17 (E) RECPT RM B-101, CB-2 20 A 1 0 0 1 20 A (E) RECPT RM B-109, B-110, CB-5, B-112 18

15 (E) RECPT RM E002A, E002 20 A 1 0 0 1 20 A (E) RECPT RM B-108 16

13 (E) RECPT RM B-101, B-102, PIPE TUNNEL 20 A 1 0 0 1 20 A (E) RECPT EWC NORTH CB-5 14

11 (E) RECPT RM B-103, CB-4, B-104 NW, E002 20 A 1 0 0 1 20 A (E) RECPT RM B-106, CB-5 12

9 (E) RECPT RM B-102 CENTRAL 20 A 1 0 0 1 20 A (E) RECPT RM B-105 10

7 SPARE 40 A 1 0 0 1 20 A (E) RECPT EWC SOUTH CB-2 & CB-3 8

5 (E) RECPT RM B-102 SOUTH & BAS FOR AHU#4 30 A 1 0 0 1 20 A (E) LTG ELEV HOISTWAYS P-9, P-10, S11 6

3 (E) RECPT RM B-102 NW METERING RTU 30 A 1 0 0 1 20 A (E) LTG ELEV HOISTWAYS P-9, P-10, S11 4

1 (E) RECPT RM B102-A 40 A 1 0 0 1 20 A (E) LTG ELEV HOISTWAYS P-9, P-10, S11 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 125 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: LPB-B3-277VN Phases: 3 Mains Type: MCB

Location: E003A Volts: 120/208V A.I.C. Rating: 10kA

(E) Branch Panel: PPB-B3-120VN

Notes:

Total Est. Demand Current: 2 A

Total Conn. Current: 2 A

Total Est. Demand: 780 VA

Total Conn. Load: 780 VA

Power 780 VA 100.00% 780 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 0 A 2 A 5 A

Total Load: 0 VA 180 VA 600 VA

41 0 0 42

39 0 0

2 30 A (E) REC 30A ON PNL 1

MAIN BREAKER 100 A 3

0 0 38

35 (N) WATER SOFTENER (WS-1) 20 A 1 600 0

2 30 A (E) REC 30A ON PNL 2

33 (N) CONTROL PANEL USG-4 20 A 1 180 0 1 20 A (E) REC 34

31 SPACE -- 1 -- 0 1 20 A (E) RTU LTS & REC 32

29 SPARE 20 A 1 0 0 1 20 A (E) HEAT TRACE STEAM 30

27 SPARE 20 A 1 0 0 28

25 (E) AHU LTS 20 A 1 0 0

2 20 A (E) HEAT TRACE

23 (E) GFCI PH02 ROOF 20 A 1 0 0 24

21 (E) AHU CONTROLS POWER 20 A 1 0 0 22

19 (E) REC NORTH & WEST WALL PH01 20 A 1 0 0

3 100 A (E) PANEL 'LPP-J7-120VN2'

17 (E) REC PH02, AC-S5 FIL 20 A 1 0 0 1 20 A (E) HEAT TAPE PH01 ROOF 18

15 (E) LTS PH02 20 A 1 0 0 1 20 A (E) AC-S3 ACC. LTS & REC 16

13 (E) REC PH02 20 A 1 0 0 1 20 A (E) LTS PH02 14

11 (E) LTS PH02 20 A 1 0 0 1 20 A (E) DAMPER DELAY RELAY AC-S1 12

9 (E) REC WEST WALL ELEV. SHAFT, AC-S2 FIL 20 A 1 0 0 1 20 A (E) UNIT HEATER MACHINE ROOM 10

7 (E) REC EAST COLUMN & SOUTH WALL, AC-S... 20 A 1 0 0 1 20 A (E) UNIT HEATER PH01 SOUTH 8

5 (E) UNIT HEATER WEST PH01 20 A 1 0 0 1 20 A (E) REC PH01 ROOF SOUTH WALL 6

3 (E) LTS PH01 NORTH 20 A 1 0 0 1 20 A (E) GOULDS PUMP 4

1 (E) LTS PH01 SOUTH 20 A 1 0 0 1 20 A (E) TV ANTENNA AMP, REC EAST WALL 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 100 A

Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: LP6-H9-120VN Phases: 3 Mains Type: MCB

Location: Penthouse Volts: 120/208V A.I.C. Rating: 10kA

(E) Branch Panel: LPP-J7-120VN

Notes:

Total Est. Demand Current: 3 A

Total Conn. Current: 3 A

Total Est. Demand: 960 VA

Total Conn. Load: 960 VA

Power 960 VA 100.00% 960 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 5 A 2 A 2 A

Total Load: 600 VA 180 VA 180 VA

41 SPACE -- 1 -- -- 1 -- SPACE 42

39 (N) CONTROL PANEL USG-3 20 A 1 180 -- 1 -- SPACE 40

37 (N) WATER SOFTENER (WS-1) 20 A 1 600 0 38

35 (N) CONTROL PANEL USG-2 20 A 1 180 0

2 20 A SPARE

33 0 0 1 20 A (E) REC BELOW PANEL, LTS & REC, AHU 8 & 9 34

(E) CONDENSER UNIT - 3 20 A 2

0 0 1 20 A (E) LTS & REC AHU 7A & 7B 32

29 0 0 1 20 A (E) STEAM GENERATOR 30

(E) CONDENSER UNIT - 2 20 A 2

0 0 1 20 A (E) REC BO25B, O2 STRG G003, S. SALlY... 28

25 0 0 1 20 A (E) TACON CONTROL CABINET 26

(E) CONDENSER UNIT - 1 WEST ELE 20 A 2

0 0 1 20 A (E) REC G051 24

21 (E) REC & LTS FUTURE ELEV PIT 20 A 1 0 0 1 20 A (E) REC G051 22

19 0 0 1 20 A (E) REC G051 20

17 0 0 1 20 A (E) CABINET UNDER HEATER 2 18

(E) SPARE 50 A 3

0 0 1 20 A (E) CABINET UNDER HEATER 1 16

13 (E) RAH 20 A 1 0 0 1 20 A (E) UNIT HEATERS IN FUTURE SPD 14

11 (E) RAH 20 A 1 0 0 1 20 A (E) OVERHEAD DOOR 12

9 (E) RAH 20 A 1 0 0 1 20 A (E) REC & LT E ELEV PIT 10

7 (E) SPARE 20 A 1 0 0 1 20 A (E) REC E ELEV MACHINE RM 8

5 (E) DOMESTIC WATER HEATER - 1 20 A 1 0 0 1 20 A (E) REC & LT W ELEC PIT 6

3 (E) REC G013, CORR G014, G011, G010 20 A 1 0 0 1 20 A (E) REC V ELEC MACHINE ROOM 4

1 (E) REC CORR G007, G009, G006, G003 100 A 1 0 0 1 20 A (E) REC W & N WALL & COL AA-8.3 & COL W-8,9 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 100 A

Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: DPB-DD8.3-277VN Phases: 3 Mains Type: MCB

Location: G013 Volts: 120/208V A.I.C. Rating: 10kA

(E) Branch Panel: LPB-DD8.3-120VN

Mark Revisions: Date:

1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES

RE

G

IS

TE

RE

DPROFESSIONALENG

IN

EER

JA

E

M

.SC LESSARD

E

LEC T RICA

L

S

TATE OF CALIFORNIA

E 24240 Exp. 09-30-26

(X)REMOVABLE LINK

ATS-1 ATS-3

EXISTING GROUND

ATS-2

(E) LVB-B3-277VN

277/480V-3⌀-4W-2500AMP

A

F

A

T

SINGLE LINE DIAGRAM -REMODELSINGLE LINE DIAGRAM -DEMOLITION

NEUTRAL

G R

O U

N D

A F

A T

A

F

A

T

2 3 4 5 6 7

BUSSED

SPACE

(E) MCC-B3-480VN

3⌀-4W-600AMP

ATS-4 DPB-B3-277VN

SEE E501

A

F

A

T

A

F

A

T

A

F

A

T

A

F

A

T

(3) CLF

FUSES

(3) CLF

FUSES

(3) CLF

FUSES

(X)REMOVABLE LINK

ATS-1 ATS-3

EXISTING GROUND

ATS-2

(E) LVB-B3-277VN

277/480V-3⌀-4W-2500AMP

A

F

A

T

NEUTRAL

G R

O U

N D

A F

A T

A

F

A

T

2 3 4 5 6 7

BUSSED

SPACE

(E) MCC-B3-480VN

3⌀-4W-600AMP

ATS-4 DPB-B3-277VN

SEE E501

A

F

A

T

A

F

A

T

A

F

A

T

A

F

A

T

(3) CLF

FUSES

(3) CLF

FUSES

(3) CLF

FUSES

(E) LVB-E2-277V-NCB5

(E) LVB-E2-277V-NCB4

(E) LVB-E2-277V-NCB5

(E) LVB-E2-277V-NCB4

(X) 2 SETS OF (3) #3/0, (1) #3

GND IN 2"

(N) 2 SETS OF (3) 250KCM, (1) #1

GND, EACH IN 2" C.

ACA-HWP-1 3 480 20

NEMA

ACA-HWP-2 3 480 20

NEMA

VFD SCHEDULE

EQUIPMENT

SERVICING

MOTOR

DATA

ENCLOSURE

POLES VOLTAGE HP REMARKS

NOTES:

1 SEE DETAIL 2/E-401 FOR VFD MOUNTING.

INPUT LINE

REACTOR

REDUNDANT

VFD

YES

YES

NO

NO

BYPASS

NO

NO

CB

CB

DISCONNECT

TYPE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941 o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CORRECT REUSABLE

MEDICAL EQUIP STORAGE

589A4-24-101

800 HOSPITAL DR, COLUMBIA, MO

Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

Astral Engineers P.O. Box 190, Rancho Cucamonga, CA 91729 Phone: (909) 903-0015

Crux Consulting 18312 Harney St. / 663 N 132nd St. #73 Elkhorn, NE 68022 / Omaha, NE 68154 Phone: (402) 708-0383

Brighttree Studios 301 Brush Creek Rd Warrendale, PA 15086

(412) 212-7515

STAMP

07/25/2025

100% FINAL BID

DOCUMENTS

A u to d e s k D o c s /1

A

-2

-1

C o rr e c t R e u s a b le

M e d ic a l E q u ip m e n t S to ra g e /2

M

E P

T

.0

C o lu m b ia

M

O V

A M

C R

M E

S to ra g e

A C

A H

V A

C U p g ra d e s .r v t

/2

/2

:2

:1

A

M

E502

JCL ABH

ELECTRICAL SCHEDULES

Notes:

Total Est. Demand Current: 0 A

Total Conn. Current: 0 A

Total Est. Demand: 180 VA

Total Conn. Load: 180 VA

Receptacle 180 VA 100.00% 180 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 0 A 0 A 2 A

Total Load: 0 VA 0 VA 180 VA

41 (N) ACA -FL-1-EAST-VAV-CONTROLLER 20 A 1 180 0 1 20 A (E) BLUE CHECK IN E & S WALL 42

39 (E) SPARE 20 A 1 0 0 1 20 A (E) SPARE 40

37 (E) SPARE 20 A 1 0 0 1 20 A (E) SPARE 38

35 (E) SPARE 20 A 1 0 0 1 20 A (E) REC C1E11 TV, C1E13 TV 36

33 (E) RELAY 1, 2, 3, 4, 5 20 A 1 0 0 1 20 A (E) REC F127, F128 34

31 (E) SPARE 20 A 1 0 0 1 20 A (E) REC F127, F128 32

29 (E) FILM VIEWERS F132, C1F11, C1F13 20 A 1 0 0 1 20 A (E) REC F125, F126, C1F20 30

27 (E) REC F133, F134, F135 20 A 1 0 0 1 20 A (E) REC F137 28

25 (E) REC F132 20 A 1 0 0 1 20 A (E) REC F136 26

23 (E) REC F132 20 A 1 0 0 1 20 A (E) REC F136, F137, F137A 24

21 (E) REC F132 20 A 1 0 0 1 20 A (E) REC F138, F139, F140 22

19 (E) REC F132 20 A 1 0 0 1 20 A (E) REC F140, F141 20

17 (E) REC NURSE C1F16 20 A 1 0 0 1 20 A (E) REC F138, F139 18

15 (E) REC NURSE C1F16 20 A 1 0 0 1 20 A (E) REC F138A, C1F10, C1F12, C1F14, C1F15 16

13 (E) REC F130 20 A 1 0 0 1 20 A (E) REC F141, F142 14

11 (E) REC F130 20 A 1 0 0 1 20 A (E) REC F142, F143 12

9 (E) REC F130 20 A 1 0 0 1 20 A (E) REC F144, F145 10

7 (E) REC F130 20 A 1 0 0 1 20 A (E) REC F143, F144, F145 8

5 (E) REC SYS FURN F130 20 A 1 0 0 1 20 A (E) REC F148, F149 6

3 (E) REC SYS FURN F130 20 A 1 0 0 1 20 A (E) REC F146, F147, F149 4

1 (E) REC SYS FURN F130 20 A 1 0 0 1 20 A (E) REC F146, F147 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1 MCB Rating: 125 A

Mounting: SURFACE Wires: 4 Mains Rating: 150 A

Supply From: Phases: 3 Mains Type: MCB

Location: E137 Volts: 120/208V A.I.C. Rating:

(E) Branch Panel: PP1-D6.3-120VN-SEC1

KEYNOTES - E502

NUMBER TEXT

UTILIZE SPARE BREAKER WITHIN PANEL 'PP1-D6.3-120VN-SEC1' TO FEED NEW

CONTROLLER.

PROVIDE BREAKER WITHIN PANEL 'PP2-D10-120VC' TO FEED NEW VAV

CONTROLLER. MATCH EXISTING TYPE AND AIC RATING.

UTILIZE SPARE BREAKER WITHIN PANEL 'PPB-D8-120VN-SEC1' TO FEED LIGHTING

AND POWER TO ACA-AHU-4.

DISCONNECT AND REMOVE FEEDER CONDUCTORS BACK TO SWITCHGEAR

'LVB-B3-277VN'. PROTECT IN-PLACE CONDUIT FOR REUSE IN NEW WORK.

PROVIDE FEEDER CONDUCTORS BACK TO MOTOR CONTROL CENTER

'MCC-B3-480VN' THROUGH PROTECTED IN-PLACE CONDUIT.

6 ADJUST EXISTING BREAKER LONG TIME TRIP SETTING TO 500A.

Notes:

Total Est. Demand Current: 0 A

Total Conn. Current: 0 A

Total Est. Demand: 180 VA

Total Conn. Load: 180 VA

Receptacle 180 VA 100.00% 180 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 2 A 0 A 0 A

Total Load: 180 VA 0 VA 0 VA

41 SPACE -- 1 -- -- 1 -- SPACE 42

39 SPACE -- 1 -- -- 1 -- SPACE 40

37 (N) ACA -FL-2-EAST-VAV-CONTROLLER 20 A 1 180 -- 1 -- SPACE 38

35 (E) TAYCON CONTROLS 20 A 1 0 -- 1 -- SPACE 36

33 (E) REC F227 20 A 1 0 0 1 20 A (E) REC F229, 2 SPARE CKTS ABOVE F229... 34

31 (E) REC F230 20 A 1 0 0 1 20 A (E) PROC LTS E220, RECEP E213 32

29 (E) REC F245, F246 20 A 1 0 0 1 20 A (E) NURSE CALL RM E224A 30

27 (E) REC F245, F246 20 A 1 0 0 1 20 A (E) PROC LTS F227, F231 28

25 (E) REC F229 20 A 1 0 0 1 20 A (E) MED GAS ALARM RM 224A 26

23 (E) REC F231 20 A 1 0 0 1 20 A (E) DUMWAITER 24

21 (E) REC F231 20 A 1 0 0 1 20 A (E) REC E209, E210 22

19 (E) REC F235, F236 20 A 1 0 0 1 20 A (E) DOOR POWER C2E4 20

17 (E) REC F234, F235, F236 20 A 1 0 0 1 20 A (E) REC E213 18

15 (E) REC F234, F235 20 A 1 0 0 1 20 A (E) REC E213 16

13 (E) REC F239, F240, C2F17 20 A 1 0 0 1 20 A (E) REC E225, E226 14

11 (E) REC F237 20 A 1 0 0 1 20 A (E) REC E222, E223 12

9 (E) REC F237, F238, F240 20 A 1 0 0 1 20 A (E) REC E219, E221 10

7 (E) REC F241, F243, F244, F247 20 A 1 0 0 1 20 A (E) REC F217, E217, E218 8

5 (E) REC F236, F241, F243, F244, F247 20 A 1 0 0 1 20 A (E) REC E211, E212 6

3 (E) REC F247, F248, F249 20 A 1 0 0 1 20 A (E) REC E212, E216 4

1 (E) REC F248, F249 20 A 1 0 0 1 20 A (E) DAMPERS F253, E254,C2E2 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1 MCB Rating: 100 A

Mounting: SURFACE Wires: 4 Mains Rating: 100 A

Supply From: Phases: 3 Mains Type: MCB

Location: F252 Volts: 120/208V A.I.C. Rating: 10kA

(E) Branch Panel: PP2-D10-120VC

Notes:

Total Est. Demand Current: 2 A

Total Conn. Current: 2 A

Total Est. Demand: 600 VA

Total Conn. Load: 600 VA

Power 600 VA 100.00% 600 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 0 A 5 A 0 A

Total Load: 0 VA 600 VA 0 VA

29 0 0 30

27 0 0 28

(E) FREEZER CONDENSER UNIT E003 30 A 3

0 0

3 20 A (E) COOL CONDENSER UNIT E003

23 (E) -70 DEGREE FREZZER F027 20 A 1 0 0 1 20 A (E) EVAPORATOR 24

21 (N) ACA-AHU-4 LTS AND PWR 20 A 1 600 0 1 20 A (E)FREEZER EVAPORATOR F030 22

19 (E) -70 DEGREE FREZZER F027 20 A 1 0 0 1 20 A (E) COOLER EVAPORATOR F030 20

17 (E) -70 DEGREE FREZZER F027 20 A 1 0 0 1 20 A (E) -70 DEGREE FREZZER F027 18

15 (E) RECEPTACLES E001 20 A 1 0 0 1 20 A (E) -70 DEGREE FREZZER F027 16

13 (E) RECEPTACLES E001 20 A 1 0 0 1 20 A (E) -70 DEGREE FREZZER F027 14

11 (E) RECEPTACLES E001 20 A 1 0 0 12

9 (E) C003 CONTROLLER DRYER 20 A 1 0 0 10

7 (E) RECEPTACLES SSP-1 AIR TUNNEL 20 A 1 0 0

3 60 A

(E) CKT-7 LVL PNL, F001 ELEC RM, FA PULL IN

F035ASUB FEED TO PANEL 'PPB-D8-120VE'

5 (E) RECEPTACLES SSP-1 AIR TUNNEL 20 A 1 0 0 1 20 A (E) ELEVATOR LTS "S-11" 6

3 (E) ELEVATOR LTS "P-9" RM E-007 20 A 1 0 0 1 20 A (E) RECEPTACLES E006 4

1 (E) ELEVATOR LTS "P-10" RM E-007 20 A 1 0 0 1 20 A (E) RECEPTACLES E009 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 100 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: Phases: 3 Mains Type: MCB

Location: ELEC ROOM E009 Volts: 120/208V A.I.C. Rating: 10kA

(E) Branch Panel: PPB-D8-120VE

4 5

Mark Revisions: Date:

1 AMENDMENT #1 - BIDDER QUESTIONS-RESPONSES

RE

G

IS

TE

RE

DPROFESSIONALENG

IN

EER

JA

E

M

.SC LESSARD

E

LEC T RICA

L

S

TATE OF CALIFORNIA

E 24240 Exp. 09-30-26

E001 - ELECTRICAL COVER SHEET
E201 - ELECTRICAL - ENLARGED BASEMENT FLOOR PLAN - AREA E & F - REMODEL
E501 - ELECTRICAL SCHEDULES
E502 - ELECTRICAL SCHEDULES